Impedance Measurement of Traction Network and Electric Train For Stability Analysis in High Speed Railways

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 15

Aalborg Universitet

Impedance Measurement of Traction Network and Electric Train for Stability Analysis
in High-Speed Railways

Pan, Pengyu; Hu, Haitao; Yang, Xiaowei; Blaabjerg, Frede; Wang, Xiongfei; He, Zhengyou

Published in:
IEEE Transactions on Power Electronics

DOI (link to publication from Publisher):


10.1109/TPEL.2018.2836660

Publication date:
2018

Document Version
Accepted author manuscript, peer reviewed version

Link to publication from Aalborg University

Citation for published version (APA):


Pan, P., Hu, H., Yang, X., Blaabjerg, F., Wang, X., & He, Z. (2018). Impedance Measurement of Traction
Network and Electric Train for Stability Analysis in High-Speed Railways. IEEE Transactions on Power
Electronics, 33(12), 10086-10100. [8359306]. https://doi.org/10.1109/TPEL.2018.2836660

General rights
Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners
and it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights.

- Users may download and print one copy of any publication from the public portal for the purpose of private study or research.
- You may not further distribute the material or use it for any profit-making activity or commercial gain
- You may freely distribute the URL identifying the publication in the public portal -
Take down policy
If you believe that this document breaches copyright please contact us at vbn@aub.aau.dk providing details, and we will remove access to
the work immediately and investigate your claim.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2836660, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 1

Impedance Measurement of Traction Network and


Electric Train for Stability Analysis in High-Speed
Railways
Pengyu Pan, Student Member, IEEE, Haitao Hu, Member, IEEE, Xiaowei Yang, Student Member, IEEE,
Frede Blaabjerg, Fellow, IEEE, Xiongfei Wang, Senior Member, IEEE and Zhengyou He, Senior
Member, IEEE


Abstract—Instability and oscillation issues have frequently tween the electric train and traction network [6], [7]. Traction
occurred in high-speed railways due to the mismatch of imped- network impedance determines the strength of the network that
ances versus frequency between the 4-quadrant converter an enough strong network can endure the negative impedance
(4QC)-based high-speed train and the traction network (herein- caused by the constant power loads, and a weak network may
after train-network). However, solely utilizing the mathematical easily arise small-signal stability issues [8], [9].
deduction to quantify the impedances appears to be difficult ow- Previous publications have shown that these instability is-
ing to unknown detailed parameters of both traction network and
electric train. This paper proposes a method to measure the
sues can be avoided in some industrial power systems by im-
equivalent impedances of traction network and the 4QC of elec- proving the power electronic control for obtaining the appro-
tric train in the stationary frame for stability analysis. A dis- priate impedance characteristics [10], [11]. These methods can
turbance circuit consisted of anti-parallel insulated gate bipolar provide a reference for designing the control of power elec-
transistor (IGBT) modules and an excitation load is adopted by tronic devices to guarantee a stable system [12], [13]. As a
means of the pulse width modulation (PWM) signal to drive the result, it is especially important for measuring the corre-
IGBTs. Consequently, a desired broad spectral excitation is then sponding impedances in industrial applications.
generated to measure the output impedance of the traction net- In terms of the impedance measurement, the existing meth-
work. When injecting the harmonics twice which are linearly ods can be classified in two categories: passive method and
independent at the same frequency, the input impedance of 4QC
of the electric train can be calculated at the corresponding fre-
active method. The former one can estimate the impedance
quency considering the frequency-coupled effect. The proposed based on the mathematical analysis and numerical processing
method shows a good measurement accuracy. Additionally, the without any disturbance injection [14]-[17]. An effective
stability and oscillation issues of the train-network system can be method based on recursive least-squares algorithm has been
then identified using measured impedances. Both simulation and proposed in [14] to estimate the grid impedance. In order to
experimental results confirm the effectiveness of the proposed improve the response speed of the measurement method, [15]
measurement methods. introduced a forgetting factor into the original recursive
least-squares estimation algorithm. Apart from that, the esti-
Index Terms—Impedance measurement, low-frequency oscil- mation model of grid impedance has been established to
lation, high-speed railway, 4-quadrant converter, electric train. gradually estimate the real impedance values by adjusting the
estimated values [16]. Furthermore, some inherent harmonics
have occurred in the power system for the switching feature of
I. INTRODUCTION grid-connected power converters, and they are used to access

P OWER electronic converters with a constant power feature


may bring a negative incremental impedance to the elec-
trical power system [1]-[7]. With increasing adoption of these
the power grid impedance [17]. As a result, the passive method
has free impact on the original system. However, the accuracy
of extracted impedance is usually unsatisfactory, and the speed
constant power loads, oscillations and stability issues have been of the impedance measurement process is slow due to its com-
frequently aroused in industrial power systems that may po- plex mathematical process.
tentially lead to a system collapse in serious operations [4], [5]. The active method relies on the harmonic injection by means
As a special power system, traction power system may en- of additional power electronic devices to detect the impedance
counter the same stability issues caused by the interaction be- [18]-[22]. In this context, a sine waveform sweep-based tech-
nique proposed in [18] produces the most promising sig-
The work is supported by National Natural Science Foundation of China nal-to-noise ratio (SNR) to measure the most accurate imped-
(NSFC 51677154), the Fundamental Research Funds for the Central Universi- ance. Nevertheless, sine waveform sweeps spend much time on
ties (2682017CX041) and Young Elite Scientists Sponsorship Program by measuring the impedance owing to its repeated injections. In
CAST (YESS 2017QNRC001). order to measure the impedance over a broad frequency range
P. Pan, H. Hu, X. Yang, Z. He are with School of Electrical Engineering,
Southwest Jiaotong University, Chengdu, China. (Email: ppyswjtu@163.com,
with only once injection, broad spectral excitations such as
hht@swjtu.edu.cn, yxwswjtu@163.com, hezy@swjtu.edu.cn). random pulse width modulation (RPWM) signals have been
F. Blaabjerg, and X. Wang are with the Department of Energy Technology adopted in [19]. However, it is not easy to guarantee the accu-
Aalborg University, Aalborg 9220, Denmark (Email: fbl@et.aau.dk, racy of the measured impedance as the excitation energy dis-
xwa@et.aau.dk). tribution in the frequency domain is irregular and uncontrolla-

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2836660, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 2

ble. Moreover, a large injected energy is required to ensure the earth-connected central tap feeds two terminals: catenary and
accuracy of the impedance measurement process, yet the pro- positive feeder line. In addition, the up-track and down-track
cedure may face a risk of disturbing the normal operation of the catenary network are connected in parallel at ATS and SP [23],
original system. Hence, a maximum-length binary sequence [24]. Usually the traction network only contains some special
(MLBS) signal, was applied to increase the SNR and reduce the harmonic frequencies which are closed to the switching
injection level, has a good performance in detecting the im- frequency of the power electronics converter as the electric
pedance of the strong grid, and shows a good applicability for railway system operates without injecting disturbance. Thus,
sensitive systems [20], [21]. In addition, the discrete-interval the impedances can be measured only at these corresponding
binary sequence (DIBS) has been used to specify the range of frequencies. In order to measure the impedances at the designed
the energy spectrum in [22], and improve the energy of the frequencies, an imposing disturbance is added to the system
specified frequencies as much as possible without increasing (see Fig. 1) to produce more desired harmonic components.
the injection current amplitude. According to the response voltage and current after imposing a
The dynamic characteristic of the traction network in the disturbance, the traction network impedance in a broad
high-speed railways varies timely, meanwhile the frequency spectrum can be detected. Correspondingly, Fig. 2
large-power/capacity 4QC-based electric train shows a non- shows the equivalent measurement model of Fig. 1, where the
linear feature. As a result, the passive method using mathe- traction network is equivalent to an ideal voltage source U g in
matical analysis and numerical processing to estimate the re- series with the impedance Z s , which is composing of resistors,
al-time accurate impedance seems to be complicate and diffi-
cult. On the other hand, the more precise train-network im- inductors and capacitors.
Zs
pedances can be obtained by using the active method, which is 27.5 kV
more applicable for the small signal stability analysis of 110kV/220kV utility power grid
Catenary
Disturbance circuit
A
train-network system. B
C Rails Electric train
Therefore, this paper proposes the active method-based im- Feeder

pedance measurement for traction network and electric train


Provide more desired harmonics
and associated stability investigation method in the high-speed
Traction substation
railway. The main contributions are: ATS SP

1) The traction network impedance at desired frequencies


can be synchronously detected by imposing disturbance for
only once through the proposed broad spectral excitation Fig. 1. Disturbance injection of AT power supply.
method, which greatly reduces the required time. Traction network Zs
2) The impedance of the 4QC of electric train can be ob- R1 L1 R2 L2 Rn Ln
tained considering the frequency coupling effect, which makes I s ,I s0
the measured 4QC impedance more accurate. U s ,U s0
Ug C1 C2 Cn
3) Before the electric train is put into operation, the measured
train-network impedances can be used to forecast the stability
of this system for ensuring a safe and stable operation condi- Disturbance
tion. Fig. 2. Equivalent measurement model of Fig. 1.
The rest of the paper is organized as follows: an impedance
However, the measurement accuracy is always effected by
measurement strategy for the traction network is introduced in
the background harmonics. In order to improve the accuracy,
Section II. Section III presents a measurement method of the
the voltage Us0 and current I s0 of the traction network are
4QC of electric train considering the frequency coupling effect.
Thus, the stability analysis based on the measured measured firstly without imposing disturbances, which also
train-network impedances is then discussed in detail in Section comprises of background harmonic frequencies besides the
IV. Section V shows the experimental validation, including the fundamental frequency. Then, a disturbance circuit is added to
measured impedances of the train-network system as well as produce the desired harmonics, and the responses of the voltage
stability condition identification. Finally, conclusions are given U s and current I s can be measured. It should be noted that the
in Section VI. theoretical maintenance time of injected harmonics is de-
pendent on the desired frequency resolution of measured im-
II. IMPEDANCE MEASUREMENT OF TRACTION NETWORK pedances, which is discussed carefully in Appendix A. The
Fourier transform is finally utilized to obtain frequency-domain
A. Basic Measurement Method
components of measured voltages and currents, and the traction
The autotransformer (AT)-fed traction network is widely network impedance can be then calculated through (1) to avoid
applied in the high-speed railways around the world, as illus- the effects of background harmonics [19].
trated in Fig. 1. The transformer in traction substation trans-
forms the three-phase 110 kV/220 kV power source to two Us ( j ) Us0( j )
single-phase 2×27.5-kV supply phases. Electric trains obtain Zs ( j ) (1)
Is ( j ) Is0( j )
the energy from the catenary network. The AT substation (ATS)
is located at approximately every 10 km-15 km along the rail-
where Us ( j ) and Is ( j ) represent the voltage and current of
road and the sectioning post (SP) is located between two trac-
tion substations. In the ATS and SP, an autotransformer with an the traction network in frequency domain after imposing dis-

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2836660, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 3

turbance; Us0 ( j ) and Is0 ( j ) are the voltage and current in C. Spectral Excitation with PWM Driving signal
the frequency domain before imposing the disturbance. PWM signals are utilized to control the anti-parallel IGBT
modules for generating a broad spectral excitation, as shown in
B. Disturbance Circuit
Fig. 3. Moreover, all IGBTs are driven by the same control
A disturbance circuit shown in Fig. 3 is applied to produce a signal that can greatly simplify the control process. The time
current with spectral components in the desired frequency between the “ON” and “OFF” states of the IGBTs changes
range. In detail, the primary-side of the step-down transformer periodically. Meanwhile the IGBT module 1 will disturb the
is connected between the catenary and the rail, while the dis- positive period of the current, and the negative period is
turbance circuit is connected to the secondary-side. Then, the perturbed by the IGBT module 2 regularly. The PWM driving
disturbance circuit, consisted of anti-parallel IGBT modules signals, resulting current and voltage waveforms are presented
and the excitation load, produces different frequency compo- in Fig. 4. One can find that an OFF-state of the IGBTs makes the
nents with different driving signals of IGBTs. Moreover, the snubber resistor and excitation load connect to the system
IGBT modules are composed of series-parallel IGBT simultaneously, which makes the response current relatively
sub-components to share the voltage and current for enduring small. Then an ON-state of the IGBTs will lead to a sudden
the large power. Furthermore, a smoothing capacitor is con- current raise as the snubber resistor is shorted and only the
nected in parallel with the disturbance circuit for filtering out excitation load works. All the PWM states make periodic gaps
undesirable higher frequencies and operates as a snubber at the occur in the response current, and thus a broad spectral
same time. excitation is generated.
Catenary
1 ON

IGBT state
PWM

Switch 0.5

0
OFF
150
IGBT module 2 IGBT module 1 Current (A) Current raise
Current drop
Cs
0
Smoothing
Snubber m 2 1
capacitor
resistor
1 -150
50
Voltage (kV)

Transformer 2
0
Excitation load Re
n
-50
Share the voltage and current
0.5 0.505 0.51 0.515 0.52 0.525 0.53 0.535 0.54
Rail Time (s)
Fig. 3. Disturbance circuit to produce the desired spectral components.
Fig. 4. PWM driving signals and the resulting current and voltage for
The excitation load determines the power level of the har- disturbance circuit.
monics excited by the disturbing circuit. Under ideal conditions, The PWM signal frequency is a significant parameter that
a smaller excitation load symbolizes a larger power level of the determines frequency components of the excited spectrum. The
excited harmonics. In the field measurement, the value of the injected frequencies are directly related to the frequency of the
excitation load needs to be adjusted according to the actual PWM driving signal.
system capacity for obtaining the most appropriate disturbance
power. As a feasible adjustment method, at first, an excitation finj n fpwm 50 n 1,2, 3... (2)
load with a large value is selected to bring a small harmonic where finj is the injected frequency component; f pwm is the
level, and then reducing the excitation load to strengthen the
injected power level until an accurate impedance can be frequency of the PWM driving signal. Obviously, a lower
measured. Moreover, in order to guarantee the safety and ra- PWM frequency will bring more abundant frequency compo-
tional of impedance measurement, the total harmonic distortion nents, which thereby gives a higher frequency resolution.
(THD) brought by the disturbance should not exceed 5% ac- For a given case, the PWM frequency is set as 1000 Hz. It
cording to “IEEE Recommended Practice and Requirements comes out that the frequencies of the excited harmonics spread
for Harmonic Control in Electric Power Systems (IEEE Std at n 1000  50 Hz, n=1,2,3... , as presented in Fig. 5. Hence, at
519-2014)”. Furthermore, this disturbance method can also these frequencies, the impedances can be measured precisely.
provide spectral excitation for other AC industrial systems (e.g., In practice, the frequency of the PWM driving signal can be set
renewable energy grid-connected system and AC microgrids) according to the actual measurement requirement of the fre-
for measuring the corresponding network impedance. In par- quency resolution.
ticular, for three-phase AC systems, the impedance can be
measured through imposing the disturbance in each phase,
respectively.

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2836660, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 4

D. Measurement Results
6
f inj  n  1000  50 Hz, n  1, 2,3...
Mag (% of Fundamental) Based on the proposed PWM excitation principle, the desired
5
n 1 n  2 n  3 spectrum distribution can be excited by adjusting the frequency
n4 n5
4 n6 and duty cycle of the PWM. In order to measure the traction
n7 n8
3
n9 network impedance with a 10 Hz frequency resolution, the
PWM frequency just needs to be set at 10 Hz according to (2).
2 Meanwhile, if the traction network impedance needs to be
1 measured in the range of 10 Hz – 2000 Hz, the duty cycle of the
PWM can be set to 0.5% or 99.5% to produce a large energy
0
0 2000 4000 6000 8000 10000 range just below 2000 Hz calculated by (3) to meet the re-
Frequency (Hz) quirement. The excited frequency distribution is presented in
Fig. 5. Injected harmonics when the PWM frequency is set to 1000 Hz. Fig. 7. It can be seen that the frequency resolution of the excited
Furthermore, the duty cycle of the PWM signal is also sig- harmonics appear to be 10 Hz, and the spectrum is distributed
nificant for excited harmonics, and it affects the distribution of in the broad bands with a large energy range below 2000 Hz
the energy spectrum. The excited energy spectrum has an en- that satisfies the requirements of the corresponding bands and
velope that is periodically attenuated, and the cycle is deduced frequency resolution.

Mag (% of Fundamental)
as
0.08 2000 Hz
fpwm / D, D 50% 10 Hz

Mag (% of Fundamental)
CYC f (3) 0.02
fpwm / (1 D), D 50%
0.06 0.01
where D is the duty cycle of the PWM driving signal; CYCf is
0
the cycle of the envelope of excited energy spectrum. 0.04 2500 2550 2600
For instance, if the duty cycle is set to 8 %, and the PWM Zoom in
Frequency (Hz)
frequency is set to 200 Hz, as a result, the excited spectrum 0.02
cycle is then calculated by (3) as 200 Hz / 8% =2500 Hz, as
shown in Fig. 6. In the first cycle of the spectrum distribution, 0
0 2000 4000 6000 8000 10000
the energy of the injected currents appear to be relatively Frequency (Hz)
maximum, and thus the impedance can be measured precisely
Fig. 7. Injected harmonics when the PWM frequency is set to 10 Hz and the
in this frequency range. Therefore, in the field measurement, PWM duty cycle is set to 0.5 %.
this value can be defined according to the measurement re-
quirement of the frequency range. By means of the MATLAB/SIMULINK platform, the im-
Alternatively, the pseudo-random binary sequence (PRBS) pedance measurement model of the traction network is built to
can generate the similar spectrum energy distribution [20]-[22]. verify the correctness of the proposed method, and the simula-
However, the difference is that the PRBS is generally used to tion time step is set as Ts 1 10 5 s . Table I lists the simulation
disturb the closed-loop control system of the existing converter, parameters of the traction network in Fig. 2. Meanwhile, Table
and makes the converter output a wide spectrum excitation II gives the simulation parameters of the disturbance circuit
[20]-[22], [25]. For the electric railway system, the converters based on the PWM driving signal. Measured results, shown in
are only installed in the electric train. To ensure a smooth mo- Fig. 8, illustrate that the measured impedance and theoretical
tion of the train, it is not allowed to add disturbances to the value match each other well. As a result, the accuracy of the
control system of the running train. Thus, it is not practical for impedance measurement method is verified.
the PRBS to measure the traction network impedance, and the The PWM frequency of this simulation case is set as 10 Hz
PWM excitation combining the proposed disturbance circuit is for obtaining the spectral excitation whose frequency resolution
selected here to inject the desired harmonics, not depending on is 10 Hz. Fig. 9 shows the AC voltage and AC current wave-
the converters and associate parameters of the electric train. forms after injecting the disturbance. As the fundamental fre-
quency of traction power system is 50 Hz, the voltage and
4
CYC f  200 Hz / 8% = 2500 Hz current waveforms will present only one disturbance spike in
Mag (% of Fundamental)

2500 Hz 2500 Hz 2500 Hz 2500 Hz every 5 cycles after injecting the disturbance. Meanwhile, the
3
voltage and current distortions caused by the disturbance are
2
small that can be almost ignored. Thus, the method can be
applied to measure the traction network impedance on line.
TABLE I
1
SIMULATION PARAMETERS OF THE TRACTION NETWORK

0 Symbol Parameter Value


0 2000 4000 6000 8000 10000
Frequency (Hz)
Ug Voltage source Ug = 27.5 kV, fg = 50 Hz
Fig. 6. Injected harmonics when the PWM frequency is set to 200 Hz and the R1, R2, R3 Network-side resistors R1 = 0.01 Ω, R2 = 0.01 Ω, R3 =
PWM duty cycle is set to 8 %. 0.01 Ω
L1, L2, L3 Network-side inductors L1 = 1 mH, L2 = 2 mH, L3 = 3 mH,
C1, C2, C3 Network-side capacitors C1 = 0.03 mF, C2 = 0.02 mF, C3 =
0.01 mF

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2836660, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 5

TABLE II should be considered during the measurement process. Other-


DISTURBANCE CIRCUIT PARAMETERS BASED ON PWM SIGNALS
wise, there will be a certain error in the impedance measure-
Symbol Parameter Value ment results, which is discussed in Appendix B. The station-
ary-frame impedance matrix considering the frequency cou-
Re Excitation load Re = 5 Ω
fpwm PWM driving signal frequency fpwm = 10 Hz
pling effect has been proposed in [26], which is given by
D PWM driving signal duty cycle D = 0.5 % Ut(j ) Zt,+( j ) Zt,- ( j ) I t(j )
(4)
100 e j 2 Ut*(j ) Z*t,- ( j ) Z*t,+( j ) e j 2 It*(j )
Magnitude (dB)

Theoretical value Measured value


Zm
t,
(j )

50 where Ut ( j ) and I t ( j ) are the response voltage and current


in frequency domain, respectively; Ut* ( j ) and I t* ( j ) are
0
corresponding conjugates of Ut ( j ) and I t ( j ) ; Zmt, ( j ) is
100 the impedance matrix of the 4QC in the stationary frame. It can
be observed from (4) that a frequency-coupled vector at 2ω0-ω
Phase (deg)

0
will appear in the system for a given vector at the angular fre-
quency ω, where ω0 represents the fundamental frequency.
In order to obtain the frequency coupling impedance of the
-100 4QC through measurement, the four components Zt, ( j ) ,
200 400 600 800 1000 1200 1400 1600 1800 2000
Frequency (Hz) Zt,- ( j ) , Z*t,+ ( j ) and Z*t,- ( j ) of Zmt, ( j ) need to be detected.
Fig. 8. The measured network impedance based on PWM driving signal. For a given voltage Ut1 ( j ) , a corresponding response current
10
4
x 10
4
I t1 ( j ) will occur in the train-network system as well as the
disturbance disturbance disturbance
44
100
100
frequency-coupled components e j 2 Ut1* ( j ) and e j 2 It1* ( j ) .
(V)

AC Current (A)

22 Thus, the frequency coupling relation is then expressed by


AC Current (A)
Voltage (V)
ACACVoltage

00 00 Ut1(j ) Zt,+( j ) Zt,-( j ) I t1(j )


5 cycles (5)
*
-2-2 j2
e U (j ) t1
Z ( j ) Z ( j ) e It1*(j )
*
t,-
*
t,+
j2

-4-4 -100
-100

Zm
t,
(j )
1 1.05 1.1 1.15 1.2
1 1.05 1.1
Time (s)
1.15 1.2 Meanwhile, for another given voltage Ut2 ( j ) , it is worth
Time (s)
Fig. 9. The AC voltage and AC current at the disturbance point. noting that Ut2 ( j ) and Ut1 ( j ) are linearly independent and
also at the same frequency. The frequency coupling relation can
III. IMPEDANCE MEASUREMENT OF THE 4QC OF ELECTRIC also be then expressed as
TRAIN
Ut2 (j ) Zt,+( j ) Zt,-( j ) I t2(j )
A. Stationary-Frame Impedance Model * (6)
j2
e Ut2 (j ) *
t,-
*
Z ( j ) Z ( j ) e It2*(j )
t,+
j2

The 4QC model detailed in Fig. 10 is controlled by a du-


Zm
t,
(j )
al-loop method with inductor current feedback acting as the
inner loop and DC voltage feedback acting as the outer loop. Equs. (5) and (6) can be then grouped as
The PLL can provide an angle reference for the control. Ut1(j ) Ut2 (j ) Zt,+( j ) Zt, -( j ) I t1(j ) I t2(j )
* *
Lt 4QC
j2
e U (j ) e Ut2 (j )
t1
j2 *
t, -
*
Z ( j ) Z ( j ) e I (j ) e I t2*(j )
t,+
j2
t1
* j2

It
Zm
t,
(j )

Ut Cdc Rdc udc (7)


As a result, the impedance matrix Zmt, ( j ) at the frequency
ω can be then solved by
id -1
 PLL 0 L uq  PLL Zt,+ ( j ) Zt, - ( j ) Ut1(j ) Ut2 (j ) It1(j ) I t2(j )
iq
 k pi 
kii
dq u Z*t, - ( j ) Z*t,+( j ) e j 2 Ut1*(j ) e j 2 Ut2*(j ) e j 2 I t1*(j ) e j 2 I t2*(j )
i SOGI i s
PWM
k
dq id k pi  ii  Zm
t,
(j )
s
L
ud
udc
(8)
Current loop iq
k
k pv  iv u * In order to measure the impedance of the 4QC at desired
 PLL frequencies, the injected frequency ω is swept in the desired
s dc

 ud Voltage loop
u
SOGI
u
kipll 1  PLL frequency range, and then the impedance matrix Zmt, ( j ) in the
k ppll 
dq uq s
0 s corresponding frequency range can be detected.
PLL
Fig. 10. The 4QC model of electric train including control. B. Measurement Method
In order to detect a more accurate input impedance of the In order to measure the input impedance matrix of the 4QC
4QC of electric train, the frequency coupling effect of the 4QC presented in (8) at desired frequencies, a voltage disturbance or

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2836660, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 6

current disturbance need to be injected into the electric train, as Start


shown in Fig. 11. In the field measurement, it is unnecessary to
inject the two types of disturbances simultaneously, and only Determine the desired frequency range of
impedance measurement
one of them is needed. Moreover, the voltage disturbance is
injected into the system in series, while the current disturbance Inject a voltage vector at the frequency ω

is paralleled into the system.


First Capture the voltage U t1 and current I t1 in time domain
Zt Zt injection
Use FFT to extract the voltages and currents at corresponding
It It frequencies including the frequency-coupling components
U t1 ( j ) I t1 ( j ) e j 2 I t1* ( j )

Source U t Train Source U t Train Inject another linearly independent voltage


vector at the same frequency ω

Determine the next


Second Capture the voltage U t2 and current I t2 in time domain desired frequency ω
injection
Use FFT to extract the voltages and currents at corresponding
(a) (b) frequencies including the frequency-coupling components
Fig. 11. Disturbance injection for impedance measurement of the 4QC. (a) U t2 ( j ) I t2 ( j ) e j 2 I t2* ( j )

Voltage disturbance. (b) Current disturbance.


Solve for the two components of the 4QC
impedance matrix by (9)
Seen from (8), the two components Zt, ( j ) and Zt,- ( j ) of Z t,+ ( j ) Z t,- ( j )

Zmt, ( j ) need to be detected since the other two components Impedance Use the conjugation calculation to get the
other two components
* * m
calculation Z*t,+ ( j ) Z*t,- ( j )
Z ( j ) and Z ( j ) of Z ( j ) can be calculated by using
t,+ t,- t,
Get the complete 4QC impedance matrix
conjugation operation. Zt, ( j ) and Zt,- ( j ) can be then ex- Zmt, ( j )

pressed as
-1
Zt,+ ( j ) It1(j ) e j 2 It1* (j ) Ut1(j ) inject all the desired All the desired
frequencies are
No
* (9) frequencies separately measured?
Zt, - ( j ) j2
It2 (j ) e It2 (j ) Ut2 (j )

Taking voltage disturbance injection as an example, Fig. 12 Yes


Stop
gives a detailed flowchart for measuring the 4QC impedance at
desired frequencies. It involves determining the desired fre-
quency range of impedance measurement firstly, and then two Fig. 12. The detailed flowchart for measuring the 4QC impedance.
voltage vectors, which are linearly independent as well as at the The voltage vector is defined in the stationary frame based
same frequency ω, are injected to the system respectively for on values of the specific length, initial phase angle and the
capturing the two groups of data of voltages and currents that angular frequency. For example, u Acos( t ) can be
are linearly independent. Afterwards, fast Fourier transformer
expressed with vector by
(FFT) is used to analyze the captured data for extracting the
voltages and currents at corresponding frequencies including u Acos( t ) U A (10)
the frequency-coupled components. Finally, the two compo- where A is the length of the vector; is the initial phase
nents Zt, ( j ) and Zt,- ( j ) of the impedance matrix Zmt, ( j ) angle. In order to make the description more clear, the voltage
vector is shown in Fig. 13.
can be solved by (9), and the other two components Z*t,+ ( j )
and Z*t,- ( j ) of Zmt, ( j ) can be calculated by conjugation op- +j

eration for obtaining a complete impedance matrix. The


measurement process is repeated by sweeping the injected
frequency ω until the 4QC impedances at all the desired fre-
u A cos( t ) U A
quencies are measured.
+1

Fig. 13. The voltage vector in the stationary frame.

The two linearly independent vectors at the same frequency


can be obtained by changing the initial phase of the injected
vectors. For example, the two linearly independent voltage
vectors at the same frequency ω can be presented by
u1 A1 cos( t 1 )
1 2 n 180 n 0,1,... (11)
u2 A 2 cos( t 2)

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2836660, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 7

For clearly describing the two linearly independent vectors at


60
the same frequency ω, the two vectors are shown in Fig. 14. u1 λ1(jω) λ2(jω)

Magnitude (dB)
40
and u2 are linearly independent when these two voltage vectors
20
are not on a line.
0
+j -20
-40
u2 A 2 cos( t ) 200
2

Phase (deg)
u1 A1 cos( t ) 100
1
2
1
+1 0

1 2 n 180 n 0,1,...
-100
0 50 100 150
Frequency (Hz)

Fig. 14. Linearly independent voltage vectors at the same frequency. Fig. 15. The eigenvalue curves of the measured 4QC impedance matrix

C. Simulation Results IV. STABILITY ANALYSIS BASED ON MEASURED IMPEDANCES


The above proposed impedance measurement method is
A. The Criterion for Stability
adopted to detect the impedance of the 4QC of electric train at
the desired frequencies. This measurement will focus on the There are available methods for stability analysis in the dif-
low frequency band as the reported instability of the real rail- ferent applications [26]-[30] wherein the impedance-based
way system almost happens at the low frequencies. For instance, stability that can be determined by using the generalized
the injected frequency is swept from 1 Hz to 150 Hz, then, the Nyquist stability criterion is widely used [26]-[29]. The im-
4QC impedance can be detected at each sweeping frequency. pedance ratio matrix can be defined as
Moreover, the train-network interaction can be analyzed by Lm ( j ) Zm
s
( j )Ytm, ( j ) (12)
plotting the frequency responses for the eigenvalues of the 4QC
m
impedance matrix against the traction network impedance [26] where Z ( j ) is the traction network impedance matrix;
s

since the eigenvalues characterize some intrinsic properties of Yt,m±( j ) is the admittance matrix of the 4QC, i.e.,
the 4QC. For this reason, the eigenvalue curves is used to de-
Yt,m±( j ) Zm
t, ±( j )
1
. Then, the stability of the train-network
scribe the impedance measurement results. Simulation param-
eters of the train are listed in Table III. system can be predicted by studying the eigenvalues of the
Fig. 15 shows the eigenvalue curves of the 4QC impedance impedance ratio matrix, which can be expressed as
matrix determined from the simulation. As can be seen, the det[ E Zm
s
( j )Ytm, ( j )] 0 (13)
curves appears to be smooth, and each frequency in the range of
1 Hz – 150 Hz can be measured. Moreover, the stability of the where E is the identity matrix. The traction network imped-
train-network system in time domain will be discussed in next ance matrix Zms ( j ) appears as a diagonal matrix since the
section to verify the accuracy of the impedance measurement traction network is balanced, which can be derived by (14) in
method. the stationary frame.
TABLE III
SIMULATION PARAMETERS OF THE TRAIN IN FIG. 10 Zs ( j ) 0
Zm
s
(j ) * (14)
Symbol Parameter Value 0 Z (j )
s

Ut The input voltage of 4QC Ut = 1770 V Furthermore, the expression (13) can be approximated as (15)
Lt The 4QC inductor Lt = 5 mH for the diagonal traction network impedance matrix [26].
Cdc Regulated capacitor Cdc = 9 mF
Rdc DC load Rdc = 50 Ω det[ E Zm
s
(j )Ytm, (j )] Zs (j ) det[ E Ytm, (j )]
udc* DC voltage reference udc* = 3000 V
fs Switching frequency fs= 1250 Hz
(15)
Kpi, Kii PI parameters of current loop Kpi = 2, Kii = 2 Observed from (15), the stability can be then identified by
Kpv, Kiv PI parameters of voltage loop Kpv = 0.5, Kiv = 2 studying the eigenvalue curves of the measured impedance
matrix of the 4QC against the traction network impedance.
Furthermore, as shown in (16), the phase difference at their
magnitude intersection determines the phase margin [31]-[33].
PM 180 Zs ( jw) t
( jw) (16)
where PM is the phase margin; Zs ( j ) and t ( j ) repre-

sent the phases of the traction network impedance and the ei-
genvalues of the 4QC impedance matrix, respectively. A phase
difference that is far less than 180°indicates a stable system
with a sufficient phase margin. Besides, a phase difference that

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2836660, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 8

is close to 180°illustrates that the system is marginally stable Zs Z t


with some resonant or unexpected harmonic components oc- R1 L1 Lt
curring. However, a phase difference that is out of 180°illus-
trates that the system is unstable with a negative phase margin. Ug C1 Cdc Rdc
B. Oscillatory Frequency Identification
The above analysis illustrates that a phase difference close to PWM
180°may make some resonant or unexpected harmonic com-
ponents occur in the system. However, an unexpected in- Fig. 16. Train-network simulation system.
ter-harmonic around 50 Hz will oscillate the system. In order to TABLE IV
identify this oscillatory frequency, the generated in- SIMULATION PARAMETERS OF THE TRAIN-NETWORK SYSTEM
ter-harmonic that overlays to the original fundamental can be Symbol Parameter Value
expressed as
Ug Voltage source Ug = 1770 V, fg = 50 Hz
SW A cos 0
t Bcos t
h (17) R1 Network-side resistor R1 = 0.129 Ω
L1 Network-side inductor L1 = 8 mH
where SW is the superimposed waveform in time domain; A C1 Network-side capacitor C1 = 20 µF
and B are the amplitudes of the fundamental and the generated Lt The 4QC inductor Lt = 5 mH
inter-harmonic, respectively; 0 (i.e., 0 2 f0 ) and h (i.e., Cdc Regulated capacitor Cdc = 9 mF
Rdc DC load Rdc = 50 Ω
h 2 f h ) are the corresponding angular frequencies, respec- udc DC-link voltage udc = 3000 V
tively. Therefore, (17) can be rewritten as fs Switching frequency fs= 1250 Hz
Kpi, Kii PI parameters of current loop Kpi = 2, Kii = 2
2 2
SW sin y t
0 (18) Kpv, Kiv PI parameters of voltage loop Kpv = 0.5, Kiv = 2
The equivalent inductance of the traction network that is
where: mainly composed of three parts: the equivalent inductances of
the utility power grid, traction transformer and catenary net-
A B cos h 0
t work is presented in Appendix C. However, the train running at
B sin h 0
t different positions of the catenary symbolizes the different
(19) equivalent length of the supplied catenary network. Obviously,
2 2
y arcsin / a longer supplied catenary will bring a larger equivalent in-
ductance. For instance, when the network equivalent induct-
Thus, the amplitude of the superimposed waveform can be ance L1 is increased from the original 8 mH to 10 mH owing to
then calculated as the increase of the equivalent catenary length, the traction
2 2 network will be weakened. Fig. 17(a) depicts the measured
SWA
(20) traction network impedance and the eigenvalues of the meas-
A2 B2 2AB cos h 0
t ured impedance matrix of the 4QC. One can observe that the
phase difference at the magnitude intersection frequency 55 Hz
As can be seen from (20), the angular frequency of SW A can is 168°. Thus, the phase margin that is only 12°illustrates that
be obtained as the resonant or unexpected inter-harmonic component nearby
SWA h 0 (21) 55 Hz may be excited in the train-network system. Moreover, it
will bring a frequency-coupled component at 45 Hz to the
Furthermore, the amplitude oscillatory frequency of the su- system according to (4), as shown in Fig. 18(a), which illus-
perimposed waveform caused by the generated inter-harmonic trates that an oscillation with a frequency of 5 Hz calculated by
around 50 Hz can be calculated as (22) will occur in the train-network system. Fig. 19(a) shows
fosc fh f0 fh 50 Hz (22) the AC voltage, AC current and DC voltage waveforms, and it
can be found that the oscillatory frequency actually appears to
where fosc is the oscillatory frequency. be 5 Hz in time domain, keeping consistent with the imped-
C. Verification for the Method ance-based stability analysis results.
In order to verify the accuracy of the measured train-network For another case, the network equivalent inductor L1 that is
increased to 12.5 mH makes the magnitude intersection fre-
impedances and the validity of the stability analysis, a
train-network simulation system is given in Fig. 16. The trac- quency vary accordingly. As a measured result, Fig. 17(b)
tion network parameters are converted to the input side of the shows the traction network impedance and associated eigen-
4QC. Initially, the train-network system remains stable as it values of the measured 4QC impedance matrix. The magnitude
operates with the parameters given in Table IV. intersection frequency is 54 Hz and the phase difference is 174°
that brings a weak phase margin of only 6° accordingly. It
illustrates that the resonant or unexpected inter-harmonic
component nearby 54 Hz occurs in this system that will bring a
frequency-coupled component at 46 Hz according to (4), shown
in Fig. 18(b). Thus, this system will oscillate with a 4 Hz fre-
quency calculated by (22), which keeps consistent with the
oscillation in time domain as shown in Fig. 19(b). Therefore,

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2836660, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 9

the accuracy of the measured train-network impedances is oscillation will occur, and determine whether the parameters of
further validated by the stability analysis results. the electric train are reasonable in order to ensure a safe and
Before the train is put into operation, the train-network im- stable operation of the high-speed railway.
pedances can be measured to forecast whether the instability or
40 40
Magnitude (dB)

20

Magnitude (dB)
20
0
λ 1 ( j ) 0
-20 λ 2 ( j ) λ 1 ( j )
55 Hz Zs ( j ) -20 λ 2 ( j )
-40 54 Hz Zs ( j )

200 -40
200
Phase (deg)

Phase (deg)
100
100
0 0
168°
174°
-100 -100
0 50 100 150 0 50 100 150
Frequency (Hz) Frequency (Hz)

(a) (b)

Fig. 17. Frequency responses for the eigenvalues of the 4QC impedance matrix and the traction network impedance after increasing the network-side inductor. (a)
Increasing L1 to 10 mH. (b) Increasing L1 to 12.5 mH.

4 10
Mag (% of Fundamental)
Mag (% of Fundamental)

55 Hz 54 Hz
3

2 5

1
45 Hz 46 Hz
0 0
0 50 100 150 0 50 100 150
Frequency (Hz) Frequency (Hz)

(a) (b)

Fig. 18. AC voltage spectrum after increasing the network-side inductor. (a) Increasing L1 to 10 mH. (b) Increasing L1 to 12.5 mH.
3200 3200
DC Voltage (V)

3100
DC Voltage (V)

3100

3000 3000

2900 2900
f osi = 5 Hz
f osi = 4 Hz
2800 2800
1 1.5 2 oscillation
2.5 3 3.5 4 oscillation
3000 1 1.5 2 2.5 3 3.5 4400
300
2000 200 2000
AC Current (A)

200
AC Current (A)
AC Voltage (V)

AC Voltage (V)

1000 100
0 0 0 0
-1000 -100
-2000 -200 -2000 -200
-300
-3000
-400
1 1.5 2 2.5 3 3.5 4 1 1.5 2 2.5 3 3.5 4
Time (s) Time (s)

(a) (b)

Fig. 19. AC voltage, AC current and DC voltage waveforms. (a) Increasing L1 to 10 mH. (b) Increasing L1 to 12.5 mH.

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2836660, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 10

Voltage regulator Traction Electrical signals


network acquisition device
V. EXPERIMENTAL VALIDATION
A. Experimental System
A train-network experimental system including the disturb-
ance circuit, shown in Fig. 20 and Fig. 21, is conducted to Train
validate the effectiveness of the impedance measurement Disturbance circuit
method for the stability analysis, and the electric parameters of
the experimental system are listed in Table V. The IGBTs of the
disturbance circuit and the experimental 4QC of electric train
are controlled by a DSP 28335 control system. Besides, the
electrical signals acquisition device is used to measure the data
of voltage and current, and then do data processing by
MATLAB to calculate the impedances of the electric train and
traction network.
In the measurement process, the traction network impedance Fig. 21. Experimental device of impedance measurement.
is first measured via the proposed method in Section II, and B. Experimental Results
then measure the frequency coupling impedance of the 4QC.
After that, the impedance-based stability analysis can be im- Fig. 22(a) shows the measured traction network impedance
plemented to prejudge the stability state before the train ac- and the associated eigenvalues of the measured 4QC imped-
cesses to the traction network. Finally, the actual stability per- ance matrix based on the experimental system. It can be seen
formance of the train-network experimental system can be that the phase difference at the magnitude intersection fre-
observed to verify the accuracy of the proposed impedance quency 52.9 Hz is 170°that symbolizes a phase margin of only
measurement and stability analysis. 10°, and may cause the inter-harmonic 52.9 Hz component in
Voltage
Traction network Measurement Train the system. Thus, an amplitude oscillation of 2.9 Hz, calculated
point
regulator R1 L1 R2 L2
iac
Lt by (22), occurs in the experimental system. The actual oscil-
Utility grid
uac latory frequency in time domain is 3 Hz as shown in Fig. 22(b),
us C1 C2 Cdc Rdc udc
and the error can be acceptable.
Then, the network equivalent inductor L1 is increased to 20.4
Disturbance injection
mH, and L2 is increased to 17.4 mH that makes the magnitude
intersection frequency vary accordingly. As a measured result,
the traction network impedance and the eigenvalues of the
Data processing Electrical signals
acquisition device measured 4QC impedance matrix being presented in Fig. 23(a)
Impedance calculation
shows that the magnitude intersection frequency is 52 Hz, and
Fig. 20. Diagram of impedance measurement. the phase difference is 172°(i.e., phase margin is 8°). Therefore,
TABLE V the resonant or unexpected inter-harmonic component nearby
TRAIN-NETWORK EXPERIMENTAL SYSTEM PARAMETERS 52 Hz may occur in the system, which oscillate this system with
a frequency of 2 Hz calculated by (22). The actual oscillatory
Symbol Parameter Value
frequency in time domain is 2.1 Hz as shown in Fig. 23(b).
us Utility power grid voltage us = 220 V Finally, reducing the network-side inductors L1 and L2 to 1
R1, R2 Network-side resistors R1 = 0.7 Ω, R2 = 0.54 Ω mH and 2 mH respectively, the traction network impedance
L1, L2 Network-side inductors L1 = 16.1 mH, L2 = 12.4 mH
C1, C2 Network-side capacitors C1 = 0.94 µF, C2 = 0.44 µF magnitude curve will drop as shown in Fig. 24(a). One can find
Rdc DC-side load Rdc = 200 Ω that the phase differences of all the magnitude curves intersec-
Lt The input inductor of 4QC Lt = 14.1 mH tions are far smaller than 180° that indicates the system is
Cdc DC capacitor Cdc = 0.44 µF definitely stable and will not produce the unexpected harmonic
udc DC-link voltage udc = 42 V
fs Switching frequency fs= 1250 Hz as shown in Fig. 24(b).
Kpi, Kii PI parameters of current loop Kpi = 4, Kii = 0.15 The measured impedances curves of the traction network and
Kpv, Kiv PI parameters of voltage loop Kpv = 0.1, Kiv = 0.002 the eigenvalues of the 4QC impedance matrix appear to be
smooth, and have the same behaviors as simulation values.
Besides, in the acceptable range of deviation, the oscillatory
frequency calculated by the magnitude intersection frequency
can match the actual oscillatory frequency in time domain,
which verifies the correctness of the measured train-network
impedances and the effectiveness of the measurement method.

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2836660, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 11

40
DC Voltage
Magnitude (dB)

f osi = 3 Hz Time (500 ms/div)


50 V/div
20
udc
λ 1 ( j )
0
λ 2 ( j )
52.9 Hz Zs ( j )
-20
iac
100 uac
Phase (deg)

0 170°
AC Voltage AC Current
20 V/div 20 A/div

-100
0 50 100 150
Frequency (Hz)

(a) (b)

Fig. 22. Train-network impedance measurement results and stability analysis. (a) The matching curves of train-network impedances. (b) Measured AC voltage, AC
current and DC voltage.
40 DC Voltage f osi = 2.1 Hz Time (1 s/div)
Magnitude (dB)

50 V/div
20
udc
λ 1 ( j )
0
λ 2 ( j )
52 Hz Zs ( j )
-20 iac
100 uac
Phase (deg)

0 172°

AC Voltage AC Current
20 V/div 10 A/div
-100
0 50 100 150
Frequency (Hz)

(a) (b)

Fig. 23. Train-network impedance measurement results and stability analysis after increasing the network-side inductor. (a) The matching curves of train-network
impedances. (b) Measured AC voltage, AC current and DC voltage.

40
DC Voltage Time (1 s/div)
Magnitude (dB)

50 V/div
20

λ 1 ( j ) udc
0
λ 2 ( j )
Zs ( j )
-20 iac
100 uac
Phase (deg)

AC Voltage AC Current
20 V/div 10 A/div
-100
0 50 100 150
Frequency (Hz)

(a) (b)

Fig. 24. Train-network impedance measurement results and stability analysis after reducing the network-side inductor. (a) The matching curves of train-network
impedances. (b) Measured AC voltage, AC current and DC voltage.

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2836660, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 12

0.025
VI. CONCLUSION t 0.02 s

Mag (% of Fundamental)
0.02
This paper presents a train-network impedance measurement
method, and uses the matching relation of the measured 0.015

train-network impedances to identify the stability issues. A 0.01


desired broad spectral excitation method by means of the PWM
0.005
signal has been proposed to detect the accurate traction network
impedance. Then, considering the frequency coupling effect, an 0
0 1000 2000 3000 4000 5000
effective impedance measurement method of the 4QC of Zoom in Frequency (Hz)
electric train has further been introduced. Moreover, based on 0.025

Mag (% of Fundamental)
the magnitude intersection frequency of the measured traction 0.02 f 50 Hz
network impedance and the eigenvalues of the measured 4QC
0.015
impedance matrix, the resonant or unexpected harmonic
component can be identified as well as the oscillatory 0.01
frequency. The proposed method has been verified by
0.005
simulations and experiments. Before the train is put into
operation, the impedance measurement and stability analysis 0
2000 2100 2200 2300 2400 2500
can be used to forecast the stability of the high-speed railways Frequency (Hz)
to ensure a safe and stable operation of this system.
(a)

APPENDIX A
0.025 t 0.1 s

Mag (% of Fundamental)
This Appendix presents the theoretical maintenance time of
injected harmonics. FFT transforms the captured signals in time 0.02
domain into the frequency domain, and the frequency resolu- 0.015
tion of the transformation results is given by
fs 0.01
f (A1)
N 0.005
where f is the frequency resolution of the FFT results; f s is
0
sampling frequency; N is the number of sampling points, and 0 1000 2000 3000 4000 5000
Zoom in Frequency (Hz)
can be calculated by
t 0.025
Mag (% of Fundamental)

N t fs (A2)
Ts f 10 Hz
0.02
where t is sampling time; Ts is sampling period. Combining 0.015
with (A1) can be converted as
0.01
1
f (A3)
t 0.005
Thus, the sampling time can be presented as
0
1 2000 2020 2040 2060 2080 2100
t (A4) Frequency (Hz)
f
For example, when the desired frequency resolution is 50 Hz, (b)
the sampling time is calculated as t 1/ 50 0.02 s according Fig. A1. The frequency resolution of the FFT results. (a) When the sampling
to (A4). Thus, the theoretical maintenance time of injected time is 0.02 s. (b) When the sampling time is 0.1 s.
harmonics is 0.02 s as shown in Fig. A1(a). When the desired In summary, the theoretical maintenance time of injected
frequency resolution is 10 Hz, the sampling time is calculated harmonics is related to the desired frequency resolution of
as t 1/ 10 0.1 s . Thus, the theoretical maintenance time is measured impedances. When the desired frequency resolution
is higher, the sampling time should be longer that symbolized a
0.1 s as shown in Fig. A1(b).
longer maintenance time of the injected harmonics.

APPENDIX B
This Appendix presents the impedance measurement result
without considering the frequency coupling. The
stationary-frame impedance matrix without considering the
frequency coupling effect is given by
Ut(j ) Zt,+( j ) 0 I t(j )
* (A5)
j2
e Ut (j ) 0 Z ( j ) e It*(j )
*
t,+
j2

Zm
t,
(j )

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2836660, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 13

where Ut ( j ) and I t ( j ) are the response voltage and current APPENDIX C


j2 * j2 *
in frequency domain; e Ut ( j ) and e It ( j ) are the The detailed impedance calculation of the whole traction
frequency coupling components; Zmt, ( j ) is the 4QC network can be found in [34], which is mainly composed of
three parts. 1) Utility power grid; 2) Traction transformer; 3)
impedance matrix without considering the frequency coupling Catenary network. These impedances are further used to
effect in the stationary frame. determine the equivalent parameters of the simulation and
The traction network and 4QC parameters are set as shown in experimental system.
Table IV. When increasing the equivalent length of the cate- The equivalent inductance of utility power grid and traction
nary, the equivalent inductance of the traction network L1 will transformer keeps almost constant owing to its constant
be increased from the original 8 mH to 10 mH, and the traction parameters. However, when the train runs to different locations
network will be weakened. Fig. A2 depicts the measured trac- of the catenary, the equivalent length of the catenary will be
tion network impedance and the eigenvalues of the measured different. A longer catenary will bring a bigger equivalent
4QC impedance matrix. The magnitude intersection frequency inductance. According to the practical system parameters, the
is seen at 52.8 Hz, and at this frequency, the phase difference is equivalent inductance and resistance of traction network can be
169°that indicates that the phase margin is only 11°. This weak then calculated.
phase margin illustrates that the resonant or unexpected in-
ter-harmonic component nearby 52.8 Hz may occur in the
REFERENCES
system. Thus, this system will oscillate with a 2.8 Hz frequency
[1] N. Sokal, “System oscillations from negative input resistance at power
based on the measured impedances. However, the actual os-
input port of switching-mode regulator, dc/dc converter, or dc/ac inverter,”
cillation frequency in time domain is 4 Hz as shown in Fig. A3. in Proc. IEEE Power Electron. Spec. Conf., Sep. 1973, pp. 138-140.
Thus, there is a certain error without considering the frequency [2] X. Wang, F. Blaabjerg, M. Liserre, Z. Chen, Y. W. Li, and J. He, “An
coupling. Therefore, the frequency coupling effect should be active damper for stabilizing power-electronics-based as systems,” IEEE
taken into account. Trans. Power Electron., vol. 29, no. 7, pp. 3318-3329, Jul. 2014.
[3] X. Wang, F. Blaabjerg, and W. Wu, “Modeling and analysis of harmonic
stability in ac power-electronics-based power system,” IEEE Trans.
20
Magnitude (dB)

Power Electron., vol. 29, no. 12, pp. 6421-6432, Dec. 2014.
[4] J. H. R. Enslin and P. J. M. Heskes, “Harmonic interaction between a
0 large number of distributed power inverters and the distribution network,”
λ 1 ( j ) IEEE Trans. Power Electron., vol. 19, no. 6, pp. 1586-1593, Nov. 2004.
-20 λ 2 ( j ) [5] M. Cespedes and J. Sun, “Renewable energy systems instability involving
52.8 Hz Zs ( j ) grid-parallel inverters,” in Proc. 24th Annu. Appl. Power Electron. Conf.,
Expo., Mar. 2009, pp. 1971-1977.
[6] H. Hu, H. Tao, F. Blaabjerg, X. Wang, Z. He, and S. Gao,
100
“Train-Network Interactions and Stability Evaluation in High-Speed
Phase (deg)

169° Railways--Part I: Phenomena and Modeling,” IEEE Trans. Power


0 Electron., vol. 33, no. 6, pp. 4627-4642, Jun. 2018.
[7] H. Hu, H. Tao, X. Wang, F. Blaabjerg, Z. He, and S. Gao,
-100 “Train-Network Interactions and Stability Evaluation in High-Speed
Railways--Part II: Influential Factors and Verifications,” IEEE Trans.
0 50 100 150 Power Electron., vol. 33, no. 6, pp. 4643-4659, Jun. 2018.
Frequency (Hz) [8] B. Wen, D. Boroyevich, R. Burgos, P.Mattavelli, and Z. Shen, “Analysis
of D-Q small-signal impedance of grid-tied inverters,” IEEE Trans.
Fig. A2. The measured traction network impedance and the eigenvalues of the Power Electron., vol. 31, no. 1, pp. 675-687, Jan. 2016.
measured 4QC impedance matrix [9] S.Vesti, T. Suntio, J. A. Oliver, R. Prieto, and J. A. Cobos,
3200 “Impedance-based stability and transient-performance assessment
applying maximum peak criteria,” IEEE Trans. Power Electron., vol. 28,
DC Voltage (V)

3100 no. 5, pp. 2099-2104, May. 2013.


[10] B. Wen, D. Boroyevich, P.Mattavelli, Z. Shen, and R. Burgos, “Influence
3000 of phase-locked loop on input admittance of three-phase voltage-source
converters,” in Proc. 28th Annu. Appl. Power Electron. Conf., Expo., Mar.
2900
2013, pp. 897-904.
f osi = 4 Hz
2800 [11] Yong Li, Qianyi Liu, Sijia Hu, Fang Liu, Yijia Cao, Longfu Luo, and
1 1.5 2 oscillation
2.5 3 3.5 4400 Christian Rehtanz, “A Virtual Impedance Comprehensive Control
Strategy for the Controllably Inductive Power Filtering System,” IEEE
2000 200 Trans. Power Electron., vol. 32, no. 2, pp. 920-926, February 2017.
AC Current (A)
AC Voltage (V)

[12] Y. Panov and M. M. Jovanovic, “Stability and dynamic performance of


0 0 current-sharing control for paralleled voltage regulator modules,” IEEE
Trans. Power Electron., vol. 17, no. 2, pp. 172-179, Mar. 2002.
-200 [13] Y. Tang, P. C. Loh, P. Wang, F. H. Choo, and F. Gao, “Exploring inherent
-2000
damping characteristic of LCL-filters for three-phase grid-connected
-400 voltage source inverters,” IEEE Trans. Power Electron., vol. 27, no. 3, pp.
1 1.5 2 2.5 3 3.5 4 1433-1443, Mar. 2012.
Time (s) [14] S. Cobreces, E. J. Bueno, D. Pizarro, F. J. Rodriguez, and F. Huerta, “Grid
impedance monitoring system for distributed power generation electronic
Fig. A3. The AC voltage, AC current and DC voltage waves. interfaces,” IEEE Trans. Instrum. Meas., vol. 58, no. 9, pp. 3112-3121,
Sep. 2009.

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2836660, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 14

[15] J. Yang, W. Li, T. Chen, W. Xu, and M. Wu, “Online estimation and multiple modern trains,” Electric Power Systems Research, no. 146, pp.
application of power grid impedance matrices based on synchronized 246-257, 2017.
phasor measurements,” IET Gener., Transm. Distrib., vol. 4, no. 9, pp.
1052-1059, Sep. 2010.
[16] M. Ciobotaru, V. Agelidis, R. Teodorescu, “Line impedance estimation
using model based identification technique,” in Proc. IEEE Power
Electron. Appl. Conf., Aug. 2011, pp. 1-9.
[17] H. Gu, X. Guo, D. Wang, and W. Wu, “Real-time grid impedance
estimation technique for grid-connected power converters,” in Proc.
IEEE Ind Electron. Conf., May. 2012, pp. 1621-1626.
[18] H. Jing, K. A. Corzine, and M. Belkhayat, “Small-signal impedance
measurement of power-electronics-based ac power systems using
line-to-line current injection,” IEEE Trans. Power Electron., vol. 24, no.
2, pp. 445-455, Feb. 2009.
[19] M. Jordan, H. Langkowski, T. D. Thanh, and D. Schulz, “Frequency
dependent grid-impedance determination with pulse-width-modulation-
signals,” in Proc. 7th Int. Conf. –Workshop Compat. Power Electron., Jun.
2011, pp. 131-136.
[20] T. Roinila, M. Vilkko, and J. Sun, “Broadband methods for online grid
impedance measurement,” in Proc. IEEE Energy Convers. Congr. Expo.,
ECCE Sep. 2013, pp. 3003-3010.
[21] T. Roinila, T. Messo and E. Santi, "MIMO-Identification Techniques for
Rapid Impedance-Based Stability Assessment of Three-Phase Systems in
DQ Domain," IEEE Trans. Power Electron, vol. 33, no. 5, pp. 4015-4022,
May 2018.
[22] T. Roinila, M. Vilkko, and J. Sun, “Online grid impedance measurement
using discrete-interval binary sequence injection,” IEEE Trans. Ind.
Electron., vol. 2, no. 4 pp. 985-993, Dec. 2014.
[23] Z. He, H. Hu, Y. Zhang and S. Gao, “Harmonic Resonance Assessment to
Traction Power-Supply System Considering Train Model in China
High-Speed Railway,” IEEE Tran. Power Del., vol. 29, no. 4, pp.
1735-1743, Aug. 2014.
[24] H. Hu, Y. Shao, L. Tang, J. Ma, Z. He and S. Gao. “Overview of
Harmonic and Resonance in Railway Electrification Systems,” IEEE
Trans. Ind. Appl., 2018.
[25] D. Martin, I. Nam, J. Siegers, and E. Santi, "Wide bandwidth three-phase
impedance identification using existing power electronics inverter," in
Applied Power Electronics Conference and Exposition (APEC), 2013
Twenty-eighth Annual IEEE, March 2013, pp. 334-341.
[26] X. Wang, L. Harnefors, F. Blaabjerg, “Unified impedance model of
grid-connected voltage-source converters,” IEEE Trans. Power Electron.,
vol. 33, no. 2, pp. 1775-1787, Feb. 2018.
[27] B. Wen, D. Boroyevich, R. Burgos, P. Mattavelli, and Z. Shen,
“Small-signal stability analysis of three-phase as systems in the presence
of constant power loads based on measured d-q frame impedances,” IEEE
Trans. Power Electron., vol. 30, no. 10, pp. 5952-5963, Dec. 2015.
[28] H. Tao, H. Hu, X. Wang, F. Blaabjerg, Z. He, “Impedance-Based
Harmonic Instability Assessment in Multiple Electric Trains and Traction
Network Interaction System,” IEEE Trans. Ind. Appl., 2018. To be
published, DOI: 10.1109/TIA.2018.2793843.
[29] H. Hu, Y. Zhou, J. Yang, Z. He and S. Gao, “A Practical Approach to
Mitigate Low-Frequency Oscillation in Railway Electrification Systems,”
IEEE Trans. Power Electron., 2018. To be published, DOI
10.1109/TPEL.2018.2803176
[30] W. Li, L. Liang, W. Liu, X. Wu, “State of Charge Estimation of Lithium
Ion Batteries Using a Discrete Time Nonlinear Observer,” IEEE Trans.
Ind. Electron., vol. 64, no.11, pp.8557-8565, 2017.
[31] Y. Wang, X. Wang, F. Blaabjerg, “Frequency scanning-based stability
analysis method for grid-connected inverter system,” in Proc. 3rd IEEE
Int. Conf. Future Energy Electronics., ECCE-Asia Jun. 2017, pp.
1575-1580.
[32] Y. Wang, X. Wang, F. Blaabjerg, and Z. Chen, “Harmonic resonance
assessment of multiple paralleled grid-connected inverters system,” in
Proc. 3rd IEEE Int. Conf. Future Energy Electronics., ECCE-Asia Jun.
2017, pp. 2070-2075.
[33] Y. Song, X. Wang, F. Blaabjerg, “Impedance-based high-frequency
resonance analysis of DFIG system in weak grids,” IEEE Trans. Power
Electron., vol. 32, no. 5, pp. 3536-3548, May. 2017.
[34] X. Jiang, H. Hu, Z. He, H. Tao and Q. Qian “Study on low-frequency
voltage fluctuation of traction power supply system introduced by

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

You might also like