Maintenance Resetting fault indications

Caution! The fault indication is maintained until it is reset on the control panel.
Press the reset button.
If the circuit breaker remains closed and
the Ap LED remains ON after the reset,

E60306B
open the circuit breaker and contact the Micrologic 7.0 P

after-sales support department.

Fault
22/11/1999
02:04:04
Umin 100V

Reset
by test/reset
button

66 Micrologic P Schneider Electric


Viewing the event histories

Select the command Trip history


Event

E71706A

E71707A
history Trip Trip
Trip history 22/11/1999
history 02:04:04
U min Umin 160V
27/01/1999
Ir
27/06/1998
Ir
18/02/1998

then
Select a fault. View.

Select the command Alarm history


Event
history
E71708A

E71709A
Alarm Alarm
Alarm history 27/01/1999
history
13:06:09
I2 max I2 max 3400A
27/01/1999
In max
23/03/1998
U max
12/02/1998

then
Select an alarm. View.

67 Micrologic P Schneider Electric


Maintenance Operation counter and
contact-wear indicator

Select the command View and/or reset the operation counter


Event

E71736A

E71737A
E71735A
history Number of Number of Number of
operations operations operations
Operation
counter Total Total Total
17824 17824 17824
Operations Operations Operations
since last since last since last
reset reset reset
6923 0 6923

Reset ( - / + ) Reset ( - / + ) Reset ( - / + )

then
Reset… … or cancel the reset,
then confirm.

Select the command Check the wear of the contacts


Event
E71710C

history Contact
Contact wear
wear

Contact wear is indicated from 0 to 900.


The contacts should be inspected every
time the counter reaches a multiple of 100. 59

68 Micrologic P Schneider Electric


Checking/replacing the battery

Check the control-unit battery

E60307A
Micrologic 7.0 P

1 2 3

Press and hold down the test button on the control unit to check the LEDs and the
battery. The battery information is displayed if the control unit is equipped with an
external power supply or if the circuit breaker is ON.
E71751A

Battery fully charged


Battery half charged
No battery or must be replaced

If the battery needs to be changed, order a Replacing the control-unit battery


new battery with the Schneider Electric
1. remove 2. remove the battery
catalogue number 33593. the battery cover
b lithium battery
b 1.2 AA, 3.6 V, 800 mA/h
E60308A

E51443A

b ambient temperature: 130°C.

3. insert a new battery. 4. put the cover back


Check the polarity. in place. Press the
battery-test button to
check the new battery.
E60473A

E60481A

69 Micrologic P Schneider Electric


Maintenance Tests

Test the ground-fault (Micrologic 6.0 P) and earth-leakage


(Micrologic 7.0 P) protection functions
The circuit breaker must be supplied with power and closed for the test.

Press the TEST button. The circuit breaker should trip.

E60309A
5.0 P
logic
Micro

If the circuit breaker does not trip, contact the after-sales support department.

Mini test kit and portable test kit


Refer to the manual that comes with the
The test connector is used to connect the mini or the portable test kit to check that
test kits. the control unit is operating correctly.
E60310A

E60311A

5.0 P 5.0 P
logic logic
Micro Micro

70 Micrologic P Schneider Electric