Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

710/713RA Solenoid Valves

Expansion Valves
Thermal

The 710/713RA are 2-way, diaphragm valves. The 710RA is


a normally closed valve. The 713RA is a normally open valve.
These valves are used for liquid pressure differential control
for gas defrost.
Solenoid
Valves

Model Solenoid Operation


De-Energized Differential Mode
710
Energized Full Open
De-Energized Full Open
713
Energized Differential Mode
Coils

Features
• Differential adjustable from 8-40 psi Specifications
Solenoid Valves

• Angle style construction eliminates the need


Industrial

for an elbow fitting at the liquid header • Maximum fluid temperature: 250°F
• Long-life molded coils • Maximum working pressure: 500 psig
• These valves eliminate the need for an external • MOPD (710): 300 psig
check valve and the associated piping needed on MOPD (713): 250 psig
supermarket racks with gas defrost • UL/CUL file number: MP604
• Can be brazed into the line without disassembly
Shut Off
Valves

NOTE: Mounting enclosing tube more than 90o off vertical up


position is not recommended.
NOTE: All valves require AM coil except 710RA24 valves which
require either an AMCN/AMGN or ASC2 coil.
Nomenclature example: 710RA 16T11 VLC
Protectors
System

710R A 16 T 11 VLC
Valve Design Port Size Connection Type Connection Size Coil*
Series Series (in 1/16”) T = copper entended ends (in 1/8”)

* NOTE: Valves are shipped without the solenoid coils (VLC = Valve Less Coil). For available coil assemblies, see page 114.
Devices
Storage

Ordering Information and Nominal* Liquid Capacity Table - Tons (kW)


Controls
Oil

PCN Description Connection Size R-12 R-134a R-22 R-407C R-404A/R-507 R-502
053215 710RA 12 T 9 VLC 1 1/8 ODF 25.3 (89.6) 3.4 (107.6) 32.9 (116) 31.3 (111.0) 21.9 (77.5) 21.4 (75.8)
052825 710RA 16 T 9 VLC 1 1/8 ODF
052915 710RA 16 T 11 VLC 1 3/8 ODF 34.9 (123.5) 42.0 (148.7) 45.4 (161.0) 43.2 (153.0) 30.3 (107.0) 29.5 (104.0)
048411 710RA 16 T 11-13 VLC 1 3/8 x 1 5/8 ODF
049901 710RA 20 T 13 VLC 1 5/8 ODF 53.1 (188.0) 64.0 (226.6) 69.6 (246.0) 66.3 (235.0) 46.5 (165.0) 45.2 (160.0)
Regulators
Pressure

054153 710RA 24 T 17 VLC 2 1/8 ODF 76.4 (270.5) 92.0 (325.7) 100.0 (354.0) 95.2 (230.0) 66.7 (236.0) 65.0 (230.0)
053099 713RA 16 T 11 VLC 1 3/8 ODF 34.9 (123.5) 42.0 (148.7) 45.4 (161.0) 43.2 (153.0) 30.3 (107.0) 29.5 (104.0)
053220 713RA 20 T 13 1 5/8 x 1 5/8ODF 53.1 (188.0) 64.0 (226.6) 69.6 (246.0) 66.3 (235.0) 46.5 (165.0) 45.2 (160.0)
Capacities based on 100°F liquid and 40°F saturated evaporator per ARI standard 760-87.
*See Extended Capacity Tables for ratings at a wide range of conditions.
Pressure Controls
Temperature
Competitive Cross
Reference

102 Emerson Climate Technologies


710/713RA Dimensional Data (in)
Valve Conn. Size A B C D E

Expansion Valves
710/713RA12T9 1-1/8 ODF (1.13) 4.01 3.56
3.92 3.48 2.28

Thermal
710/713RA12T11 1-3/8 ODF (1.38) 5.29 4.84
710/713RA16T9 1-1/8 ODF (1.13) 4.23 3.39
710/713RA16T11 1-3/8 ODF (1.38) 4.56 4.39 3.73 3.38
5.23
710/713RA16T11-13 1-3/8 x 1-5/8 ODF (1.38 x 1.63) 4.38
710/713RA20T11 1-3/8 (1.38) 5.09 4.26
4.62 4.14
710RA20T13 1-5/8 (1.63) 5.59 4.76 4.06
710RA24T17 2-1/8 (2.13) 4.59 6.56 5.73 5.46

Solenoid
Valves
710RA Exploded View & Parts Kit Data

Coils
Solenoid Valves
Industrial
Shut Off
Valves
710RA Valve Kits
Valve Kit # PCN
710RA12 KS30154 053564
710RA16 KS30155 053565
710RA20 KS30156 053566

Protectors
710RA24 KS30279 054994

System
Gasket Kit for all 710RA valves is KG10028 (PCN 054356)

Typical Application
Liquid Pressure Differential Control for Hot Gas Defrost

Devices
Storage
Controls
Oil
NOTE: The 710RA and
the 713RA valves can not
be used as pump-down Valve Repair Kit
Regulators
Pressure

solenoid valves. “K” indicates part is supplied in valve repair kit.

NOTE: The 710RA24 Gasket Kit


requires a pilot “G” indicates part is supplied in gasket kit
connection between KG10028 [PCN-054356].
Note: Spanner wrench (X11981-1 [PCN-027451]
Pressure Controls

the valve and suction line.


Temperature

service tool) included in complete valve kit.


Coil Assembly
For available coil assemblies, see page 114.
Competitive Cross
Reference

Emerson Climate Technologies 103

You might also like