YK SC-EQ BAS Points List

Rev 2.3
January 2, 2019

BACnet
Long Name Short Name IP SI Object & N2 Metasys MODBUS MODBUS MODBUS
(BACnet Object Description) (BACnet Object Name) Notes Units Units Enum Set Instance Address Address Scale Data Type LON Profile Name LON SNVT Type

Remote Leaving Chilled Liquid Setpoint REM LEAVING CHL TEMP SP °F °C AV1 ADF 1 0001 X10 Signed nviCoolSetPt SNVT_temp_p
Remote Current Limit Setpoint REMOTE CURRENT SP % % AV2 ADF 2 0002 X10 Signed nviCapacityLimit SNVT_lev_percent
Remote Heating Setpoint REM HEATING SP °F °C AV3 ADF 3 0003 X10 Signed nviHeatSetPt SNVT_temp_p
AV4 ADF 4 0004 X10 Signed
Remote Run/Stop [0=Stop, 1=Run] REM RUN STOP CMD 0=Stop, 1=Run BV1 BD 1 0061 N/A Signed nviChillerEnable SNVT_switch
BV2 BD 2 0062 N/A Signed
BV3 BD 3 0063 N/A Signed
BV4 BD 4 0064 N/A Signed

Leaving Chilled Liquid Temperature LEAVING CH LIQ TEMP °F °C AV5 ADF 5 0005 X10 Signed nvoLvgCHWTemp SNVT_temp_p
Entering Chilled Liquid Temperature ENTERING CH LIQ TEMP °F °C AV6 ADF 6 0006 X10 Signed nvoEntCHWTemp SNVT_temp_p
Evaporator Pressure EVAPORATOR PRESSURE PSIG kPaG AV7 ADF 7 0007 X10 Signed nvoEvapPress SNVT_press
Condenser Pressure CONDENSER PRESSURE PSIG kPaG AV8 ADF 8 0008 X10 Signed nvoCondPress SNVT_press
Oil Pressure Differential OIL PRESSURE DIFERENTIAL PSID kPaD AV9 ADF 9 0009 X10 Signed nvoOilDiffPress SNVT_press
Entering Condenser Liquid Temperature ENTERING COND WATER TEMP °F °C AV10 ADF 10 0010 X10 Signed nvoEntCNDTemp SNVT_temp_p
Leaving Condenser Liquid Temperature LEAVING COND WATER TEMP °F °C AV11 ADF 11 0011 X10 Signed nvoLvgCNDTemp SNVT_temp_p
Motor % Full Load Amps MOTOR CURRENT PCT FLA % % AV12 ADF 12 0012 X10 Signed nvoPctMotorCurr SNVT_lev_percent
VSD Phase A Output Current (RMS) VSD PHASE A OUTPUT CURRENT VSD only Amps Amps AV13 ADF 13 0013 X10 Signed nvoCurrent_A SNVT_amp
Motor Phase A Current MOTOR PHASE A CURRENT SSS only Amps Amps AV13 ADF 13 0013 X10 Signed nvoCurrent_A SNVT_amp
VSD Phase B Output Current (RMS) VSD PHASE B OUTPUT CURRENT VSD only Amps Amps AV14 ADF 14 0014 X10 Signed nvoCurrent_B SNVT_amp
Motor Phase B Current MOTOR PHASE B CURRENT SSS only Amps Amps AV14 ADF 14 0014 X10 Signed nvoCurrent_B SNVT_amp
VSD Phase C Output Current (RMS) VSD PHASE C OUTPUT CURRENT VSD only Amps Amps AV15 ADF 15 0015 X10 Signed nvoCurrent_C SNVT_amp
Motor Phase C Current MOTOR PHASE C CURRENT SSS only Amps Amps AV15 ADF 15 0015 X10 Signed nvoCurrent_C SNVT_amp
VSD L1 Input Current (RMS) VSD RMS INPUT CURRENT L1 Raptyr VSD only Amps Amps AV16 ADF 16 0016 X1 Signed nvoInputCur_L1 SNVT_amp
Motor Phase A Voltage MOTOR PHASE A VOLTAGE SSS only Volts Volts AV16 ADF 16 0016 X1 Signed nvoVoltage_A SNVT_volt
VSD L2 Input Current (RMS) VSD RMS INPUT CURRENT L2 Raptyr VSD only Amps Amps AV17 ADF 17 0017 X1 Signed nvoInputCur_L2 SNVT_amp
Motor Phase B Voltage MOTOR PHASE B VOLTAGE SSS only Volts Volts AV17 ADF 17 0017 X1 Signed nvoVoltage_B SNVT_volt
VSD L3 Input Current (RMS) VSD RMS INPUT CURRENT L3 Raptyr VSD only Amps Amps AV18 ADF 18 0018 X10 Signed nvoInputCur_L3 SNVT_amp
Motor Phase C Voltage MOTOR PHASE C VOLTAGE SSS only Volts Volts AV18 ADF 18 0018 X10 Signed nvoVoltage_C SNVT_volt
Leaving Chilled Liquid Setpoint - Selected LEAVING CH LIQ TEMP ACT SP °F °C AV19 ADF 19 0019 X10 Signed nvoActiveSetpt SNVT_temp_p
Active Current Limit CURRENT LIMIT ACTIVE SP % % AV20 ADF 20 0020 X1 Signed nvoCapacityLimit SNVT_lev_percent
Evaporator Saturation Temperature EVAP SATURATION TEMP °F °C AV21 ADF 21 0021 X10 Signed nvoEvapSatTemp SNVT_temp_p
Condenser Saturation Temperature COND SATURATION TEMP °F °C AV22 ADF 22 0022 X10 Signed nvoCondSatTemp SNVT_temp_p
Discharge Temperature DISCHARGE TEMP °F °C AV23 ADF 23 0023 X10 Signed nvoDischTemp SNVT_temp_p
Oil Sump Temperature OIL SUMP TEMPERATURE °F °C AV24 ADF 24 0024 X10 Signed nvoOilSumpTemp SNVT_temp_p
Condenser Refrigerant Level COND REFRIGERANT LEVEL % % AV25 ADF 25 0025 X1 Signed nvoCondRefLvl SNVT_lev_percent
Operating Hours OPERATING HOURS Hr Hr AV26 ADF 26 0026 X1 Unsigned nvoRunHours SNVT_time_hour
Number Of Starts NUMBER OF STARTS None None AV27 ADF 27 0027 X1 Unsigned nvoSystemStarts SNVT_count
Oil Sump Pressure OIL SUMP PRESSURE PSIG kPaG AV28 ADF 28 0028 X10 Signed nvoOilSumpPress SNVT_press
Oil Pump Pressure OIL PUMP PRESSURE PSIG kPaG AV29 ADF 29 0029 X10 Signed nvoOilPumpPress SNVT_press
Motor Run [0=Off, 1=On] COMPR MOTOR STATUS 0=Off, 1=On BV5 BD 5 0065 N/A Signed nvoOnOff SNVT_switch
Liquid Line Solenoid [0=Off, 1=On] LIQUID LINE SOLENOID 0=Off, 1=On BV6 BD 6 0066 N/A Signed nvoLiqLineSolnd SNVT_switch
Chilled Liquid Pump [0=Off, 1=On] CH LIQ PUMP STAT 0=Off, 1=On BV7 BD 7 0067 N/A Signed nvoCHLPump SNVT_switch
Panel Stop Switch [0=Off, 1=On] START STOP SWITCH STATUS 0=Off, 1=On BV8 BD 8 0068 N/A Signed nvoPanelStopSw SNVT_switch
Chilled Liquid Flow Switch [0=Open, 1=Closed] CH LIQ FLOW SWITCH STAT 0=Open, 1=Closed BV9 BD 9 0069 N/A Signed nvoCHFlowSwitch SNVT_switch
Condenser Liquid Flow Switch [0=Open, 1=Closed] CND FLOW SWITCH STAT 0=Open, 1=Closed BV10 BD 10 0070 N/A Signed nvoCNDFlowSwitch SNVT_switch
Condenser Liquid Pump [0=Off, 1=On] CND LIQ PUMP STAT 0=Off, 1=On BV11 BD 11 0071 N/A Signed nvoCNDLPump SNVT_switch
BV12 BD 12 0072 N/A Signed
BV13 BD 13 0073 N/A Signed
BV14 BD 14 0074 N/A Signed
BV15 BD 15 0075 N/A Signed
BV16 BD 16 0076 N/A Signed
BV17 BD 17 0077 N/A Signed
BV18 BD 18 0078 N/A Signed
VSD Cooling System [0=Off, 1=On] VSD COOLING SYS STAT VSD only 0=Off, 1=On BV19 BD 19 0079 N/A Signed nvoVSDCoolSys SNVT_switch
Harmonic Filter Installed [0=False, 1=True] VSD HARMONIC FILTER INST VSD only 0=False,1=True BV20 BD 20 0080 N/A Signed nvoHarmonicFltr SNVT_switch
BV21 BD 21 0081 N/A Signed
BV22 BD 22 0082 N/A Signed
BV23 BD 23 0083 N/A Signed
BV24 BD 24 0084 N/A Signed
Unit Operation Code UNIT OPERATION CODE See SC.1 on Status Codes MV1 N/A N/A N/A Unsigned N/A N/A
Unit Operation Code AV UNIT OPERATION CODE AV None None See SC.1 on Status Codes AV401 ADI 1 0030 X1 Unsigned nvoOperCode SNVT_count
Unit Safety Fault Code UNIT SAFETY FAULT CODE See SC.2 on Status Codes MV2 N/A N/A N/A Unsigned N/A N/A
Unit Safety Fault Code AV UNIT SAFETY FAULT CODE AV None None See SC.2 on Status Codes AV402 ADI 2 0031 X1 Unsigned nvoSafetyCode SNVT_count
Unit Cycling Fault Code UNIT CYCLING FAULT CODE See SC.3 on Status Codes MV3 N/A N/A N/A Unsigned N/A N/A
YK SC-EQ BAS Points List
Rev 2.3
January 2, 2019

Unit Cycling Fault Code AV UNIT CYCLING FAULT CODE AV None None See SC.3 on Status Codes AV403 ADI 3 0032 X1 Unsigned nvoCyclingFault SNVT_count
Unit Warning Code UNIT WARNING CODE See SC.4 on Status Codes MV4 N/A N/A N/A Unsigned N/A N/A
Unit Warning Code AV UNIT WARNING CODE AV None None See SC.4 on Status Codes AV404 ADI 4 0033 X1 Unsigned nvoWarning SNVT_count
0=Local
1=ISN (BAS)
2=Analog
3=Digital
4=Modem
Unit Control Source [0=Local, 1=ISN (BAS), 2=Analog, 3=Digital, 4=Modem] UNIT CONTROL SOURCE 5=Remote MV5 N/A N/A N/A Unsigned N/A N/A
0=Local
1=ISN (BAS)
2=Analog
3=Digital
4=Modem
Unit Control Source AV [0=Local, 1=ISN (BAS), 2=Analog, 3=Digital, 4=Modem]
UNIT CONTROL SOURCE AV None None 5=Remote AV405 ADI 5 0034 X1 Unsigned nvoUnitCtrlSrce SNVT_count
Unit Modified Run Code UNIT MODIFIED RUN CODE See SC.12 on Status Codes MV6 N/A N/A N/A Unsigned N/A N/A
Unit Modified Run Code AV UNIT MODIFIED RUN CODE AV None None See SC.12 on Status Codes AV406 ADI 6 0035 X1 Unsigned nvoModRunFault SNVT_count
Unit Start Inhibit Code UNIT START INHIBIT CODE See SC.13 on Status Codes MV7 N/A N/A N/A Unsigned N/A N/A
Unit Start Inhibit Code AV UNIT START INHIBIT CODE AV None None See SC.13 on Status Codes AV407 ADI 7 0036 X1 Unsigned nvoInhibitFault SNVT_count
Unit Internal Fault Code UNIT INTERNAL FAULT CODE See SC.14 on Status Codes MV8 N/A N/A N/A Unsigned N/A N/A
Unit Internal Fault Code AV UNIT INTERNAL FAULT CODE AV None None See SC.14 on Status Codes AV408 ADI 8 0037 X1 Unsigned nvoInternalFault SNVT_count
MV9 ADI 9 0038 X1 Unsigned
MV10 ADI 10 0039 X1 Unsigned
High Speed Thrust Bearing Proximity Position PROX SENSOR ACT POS J, K and U Compressors Only Mils Mils AV30 ADF 30 0040 X1 Signed nvoBearingPos SNVT_length_mil
High Speed Thrust Bearing Proximity Reference PROX SENSOR REF POS J, K and U Compressors Only Mils Mils AV31 ADF 31 0041 X1 Signed nvoBearingRef SNVT_length_mil
Anti-Recycle Time Remaining ANTI RECYCLE TIME REMAIN Min Min AV32 ADF 32 0042 X1 Unsigned nvoAntiRecycle SNVT_time_min
Input % Full Load Amps INPUT CURRENT PCT FLA Raptyr VSD only % % AV33 ADF 33 0043 X1 Signed nvoPctInputCurr SNVT_lev_percent
VSD Output Voltage VSD OUTPUT VOLTAGE VSD only Volts Volts AV34 ADF 34 0044 X10 Signed nvoVSDOutputVolt SNVT_volt
VSD Input Power VSD INPUT POWER VSD only kW kW AV35 ADF 35 0045 X1 Signed nvoInputPower SNVT_power_kilo
VSD Input Kilowatt Hours VSD INPUT KWH VSD only kWh kWh AV36 ADF 36 0046 X1 Unsigned nvoInputKWH SNVT_elec_kwh_l
VSD DC Bus Voltage VSD DC BUS VOLTAGE VSD only Volts Volts AV37 ADF 37 0047 X1 Signed nvoVSDDCBusVolt SNVT_volt
VSD DC Bus Current VSD DC BUS CURRENT Non-Raptyr LVVSD VSD only Amps Amps AV38 ADF 38 0048 X1 Signed nvoVSDDCBusCurr SNVT_amp
ACC Surge Count ACC SURGE COUNT VSD only None None AV39 ADF 39 0049 X1 Unsigned nvoACCSurgeCnt SNVT_count
VSD Output Frequency VSD OUTPUT FREQUENCY VSD only Hz Hz AV40 ADF 40 0050 X1 Signed nvoVSDOutFreq SNVT_freq_hz
Harmonic Filter Max Voltage Total Harmonic Distortion FILTER MAX VOLTAGE THD LVVSD with Harminc Filter or Raptyr VSD % % AV41 ADF 41 0051 X1 Signed nvoHFltrMaxVTHD SNVT_lev_percent
Harmonic Filter Max Current Total Demand Distortion FILTER MAX CURRENT TDD LVVSD with Harminc Filter or Raptyr VSD % % AV42 ADF 42 0052 X1 Signed nvoHFltrMaxATDD SNVT_lev_percent
Harmonic Filter Total Supply KVA FILTER SUPPLY KVA LVVSD with Harminc Filter or Raptyr VSD kVA kVA AV43 ADF 43 0053 X1 Signed nvoHFltrTotSKVA SNVT_count
BV25 BD 25 0085 N/A Signed
BV26 BD 26 0086 N/A Signed
BV27 BD 27 0087 N/A Signed
BV28 BD 28 0088 N/A Signed
BV29 BD 29 0089 N/A Signed
AV44 ADF 44 0101 Div 10 Signed
AV45 ADF 45 0102 Div 10 Signed
AV46 ADF 46 0103 Div 10 Signed
AV47 ADF 47 0104 Div 10 Signed
BV30 BD 30 0161 N/A Signed
BV31 BD 31 0162 N/A Signed
BV32 BD 32 0163 N/A Signed
BV33 BD 33 0164 N/A Signed
Motor Monitoring and Motor Vibration
Motor Bearing Shaft End Vibration MTR SHAFT END VIBR Protection None None AV105 ADF 48 0105 X10 Unsigned nvoMBrgShftVibr SNVT_count
Motor Monitoring and Motor Vibration
Motor Bearing Opposite Shaft End Vibration MTR OP SHAFT END VIBR Protection None None AV106 ADF 49 0106 X10 Unsigned nvoMBrgOpShfVib SNVT_count

Motor Bearing Shaft End Temperature MTR SHAFT END TEMP Motor Monitoring and Bearing Temp Protection °F °C AV107 ADF 50 0107 X10 Signed nvoMBrgShftTemp SNVT_temp_p

Motor Bearing Opposite Shaft End Temperature MTR OP SHAFT END TEMP Motor Monitoring and Bearing Temp Protection °F °C AV108 ADF 51 0108 X10 Signed nvoMBrgOpShfTemp SNVT_temp_p

Average Winding Temperature MTR WINDING AVG TEMP Motor Monitoring and Winding Temp Protection °F °C AV109 ADF 52 0109 X10 Signed nvoAvgMWindTemp SNVT_temp_p
VSD Internal Ambient Temp VSD INTERNAL AMBIENT TEMP LVVSD only °F °C AV110 ADF 53 0110 X10 Signed nvoVSDInternalT SNVT_temp_p
VSD Converter Heatsink Temp VSD CONVERTER HSINK TEMP LVVSD only °F °C AV111 ADF 54 0111 X10 Signed nvoVSDHeatSinkT SNVT_temp_p
Pre Rotation Vanes (PRV) Position PRE ROTATION VANES POS VSD, VGD or HGBP only % % AV112 ADF 55 0112 X10 Signed nvoPRVPosition SNVT_lev_percent
ACC Map Output Frequency ACC MAP OUTPUT FREQ VSD only Hz Hz AV113 ADF 56 0113 X10 Signed nvoACCMapOutFreq SNVT_freq_hz
Condenser Refrigerant Level Setpoint COND REFRIGERANT LEVEL SP % % AV114 ADF 57 0114 X10 Signed nvoRefLvlSP SNVT_lev_percent
Drop Leg Refrigerant Temperature DROP LEG REFRIG TEMP Drop Leg Temp Enabled only °F °C AV115 ADF 58 0115 X10 Signed nvoDropLegTemp SNVT_temp_p
Leaving Heating Condenser Liquid Temperature LEAVING HEAT COND LIQ TEMP Heat Recovery only °F °C AV116 ADF 59 0116 X1 Signed nvoLvgCndHWLTmp SNVT_temp_p
Heat Pump or (Heat Recovery and Hot Water
Active Heating Setpoint HEATING ACTIVE SP Control) °F °C AV117 ADF 60 0117 X1 Signed nvoHeatActSP SNVT_temp_p
Head Pressure Control or (Heat Recovery and
Heat Recovery/Head Pressure Control Valve Cmd HEAT REC HEAD PRESS VLV CMD Hot Water Control) % % AV118 ADF 61 0118 X10 Signed nvoHR_HP_CtlVlv SNVT_lev_percent
Input Power INPUT POWER SSS only kW kW AV119 ADF 62 0119 X1 Signed nvoInputPower SNVT_power_kilo
Input Kilowatt Hours INPUT KWH SSS only kWh kWh AV120 ADF 63 0120 X1 Unsigned nvoInputKWH SNVT_elec_kwh_l
YK SC-EQ BAS Points List
Rev 2.3
January 2, 2019

SSS only
Input Kilowatt Hours = (Input Kilowatt Hours
Offset x 10,000) + Input Kilowatt Hours Low
Input Kilowatt Hours Low (SSS) INPUT KWH LO SSS kWh Lo = kWh % 10000 (integer modulus) None None AV121 ADF 64 0121 X1 Unsigned nvoKWHLo SNVT_elec_kwh
VSD Only
Input Kilowatt Hours = (Input Kilowatt Hours
Offset x 10,000) + Input Kilowatt Hours Low
Input Kilowatt Hours Low INPUT KWH LO kWh Lo = kWh % 10000 (integer modulus) None None AV121 ADF 64 0121 X1 Unsigned nvoKWHLo SNVT_elec_kwh
SSS only
Input Kilowatt Hours = (Input Kilowatt Hours
Offset x 10,000) + Input Kilowatt Hours Low
Input Kilowatt Hours Offset (SSS) INPUT KWH OFFSET SSS kWh Offset = kWh / 10000 (integer divide) None None AV122 ADF 65 0122 X1 Unsigned nvoKWHOffset SNVT_elec_kwh
VSD only
Input Kilowatt Hours = (Input Kilowatt Hours
Offset x 10,000) + Input Kilowatt Hours Low
Input Kilowatt Hours Offset INPUT KWH OFFSET kWh Offset = kWh / 10000 (integer divide) None None AV122 ADF 65 0122 X1 Unsigned nvoKWHOffset SNVT_elec_kwh
Operating Hours = (Operating Hours Offset x
10,000) + Operating Hours Low
Operating Hours Low OPERATING HOURS LO Hours Lo = Hours % 10000 (integer modulus) None None AV123 ADF 66 0123 X1 Unsigned nvoOpHrLo SNVT_time_hour
Operating Hours = (Operating Hours Offset x
10,000) + Operating Hours Low
Operating Hours Offset OPERATING HOURS OFFSET Hours Offset = Hours / 10000 (integer divide) None None AV124 ADF 67 0124 X1 Unsigned nvoOpHrOffset SNVT_time_hour
AV125 ADF 68 0125 X1 Signed
Heat Pump or (Heat Recovery and Hot Water
Local Leaving Condenser Liquid Setpoint HP LEAVING COND LIQ SP LOCAL Control) °F °C AV126 ADF 69 0126 X10 Signed nvoLocalHWSetPt SNVT_temp_p

Hot Gas Bypass Command HOT GAS BYPASS COMMAND Enable point when Hot Gas Bypass is Enabled % % AV127 ADF 70 0127 X1 Signed nvoHtGasBypasCmd SNVT_lev_percent
Enable point when Evaporator Refrigerant
Evaporator Refrigerant Temperature EVAP REFRIGERANT TEMP Temperature Sensor is Enabled °F °C AV128 ADF 71 0128 X10 Signed nvoEvapRefTemp SNVT_temp_p
AV129 ADF 72 0129 X10 Signed
Condenser Level Control Valve Mode [0=Auto,1=Manual] COND REF LEVEL CNTRL MODE 0=Auto, 1=Manual BV105 BD 34 0165 N/A Signed nvoRefLvlCtlMode SNVT_switch
BV106 BD 35 0166 N/A Signed
BV107 BD 36 0167 N/A Signed
BV108 BD 37 0168 N/A Signed
BV109 BD 38 0169 N/A Signed
BV110 BD 39 0170 N/A Signed
BV111 BD 40 0171 N/A Signed
BV112 BD 41 0172 N/A Signed
BV113 BD 42 0173 N/A Signed
BV114 BD 43 0174 N/A Signed
BV115 BD 44 0175 N/A Signed
BV116 BD 45 0176 N/A Signed
BV117 BD 46 0177 N/A Signed
BV118 BD 47 0178 N/A Signed
BV119 BD 48 0179 N/A Signed
BV120 BD 49 0180 N/A Signed
BV121 BD 50 0181 N/A Signed
BV122 BD 51 0182 N/A Signed
BV123 BD 52 0183 N/A Signed
BV124 BD 53 0184 N/A Signed
MV101 /AV411 ADI 11 0130 X1 Signed
MV102 /AV412 ADI 12 0131 X1 Signed
MV103 /AV413 ADI 13 0132 X1 Signed
MV104 /AV414 ADI 14 0133 X1 Signed
MV105 /AV415 ADI 15 0134 X1 Signed
MV106 /AV416 ADI 16 0135 X1 Signed
MV107 /AV417 ADI 17 0136 X1 Signed
MV108 /AV418 ADI 18 0137 X1 Signed
MV109 /AV419 ADI 19 0138 X1 Signed
MV110 /AV420 ADI 20 0139 X1 Signed

Motor Winding Phase A Temperature MTR WINDING PH A TEMP Motor Monitoring and Winding Temp Protection °F °C AV130 ADF 73 0140 X10 Signed nvoPhAMWindTemp SNVT_temp_p

Motor Winding Phase B Temperature MTR WINDING PH B TEMP Motor Monitoring and Winding Temp Protection °F °C AV131 ADF 74 0141 X10 Signed nvoPhBMWindTemp SNVT_temp_p

Motor Winding Phase C Temperature MTR WINDING PH C TEMP Motor Monitoring and Winding Temp Protection °F °C AV132 ADF 75 0142 X10 Signed nvoPhCMWindTemp SNVT_temp_p
Motor Monitoring and Winding Temp Protection
Motor Winding Phase A2 Temperature MTR WINDING PH A2 TEMP RTD °F °C AV133 ADF 76 0143 X10 Signed nvoPhA2MWindTemp SNVT_temp_p
Motor Monitoring and Winding Temp Protection
Motor Winding Phase B2 Temperature MTR WINDING PH B2 TEMP RTD °F °C AV134 ADF 77 0144 X10 Signed nvoPhB2MWindTemp SNVT_temp_p
Motor Monitoring and Winding Temp Protection
Motor Winding Phase C2 Temperature MTR WINDING PH C2 TEMP RTD °F °C AV135 ADF 78 0145 X10 Signed nvoPhC2MWindTemp SNVT_temp_p
VSD Oil Pump Command Frequency VSD OIL PUMP CMD FREQUENCY Hz Hz AV136 ADF 79 0146 X1 Signed nvoVSOPcmd Freq SNVT_freq_hz
Entering Heating Condenser Liquid Temperature ENTERING HEAT COND LIQ TEMP Heat Recovery only °F °C AV137 ADF 80 0147 X1 Signed nvoEntCndHwlTmp SNVT_temp_p
VSD Phase A Rectifier Baseplate Temperature VSD PH A REC BASEPLATE TEMP Raptyr VSD only °F °C AV138 ADF 81 0148 X10 Signed nvoVSDBaseplatAT SNVT_temp_p
YK SC-EQ BAS Points List
Rev 2.3
January 2, 2019

VSD Phase B Rectifier Baseplate Temperature VSD PH B REC BASEPLATE TEMP Raptyr VSD only °F °C AV139 ADF 82 0149 X10 Signed nvoVSDBaseplatBT SNVT_temp_p
VSD Phase C Rectifier Baseplate Temperature VSD PH C REC BASEPLATE TEMP Raptyr VSD only °F °C AV140 ADF 83 0150 X10 Signed nvoVSDBaseplatCT SNVT_temp_p
VSD Phase A Heatsink Temperature / Baseplate Temperature VSD PH A HEATSINK TEMP Non-Raptyr LVVSD VSD only °F °C AV141 ADF 84 0151 X10 Signed nvoVSDHeatsinkAT SNVT_temp_p
VSD Phase B Heatsink Temperature VSD PH B HEATSINK TEMP Non-Raptyr LVVSD VSD only °F °C AV142 ADF 85 0152 X10 Signed nvoVSDHeatsinkBT SNVT_temp_p
VSD Phase C Heatsink Temperature VSD PH C HEATSINK TEMP Non-Raptyr LVVSD VSD only °F °C AV143 ADF 86 0153 X10 Signed nvoVSDHeatsinkCT SNVT_temp_p
BV125 BD 54 0185 N/A Signed
BV126 BD 55 0186 N/A Signed
BV127 BD 56 0187 N/A Signed
BV128 BD 57 0188 N/A Signed
BV129 BD 58 0189 N/A Signed
Evaporator Small Temp Difference EVAP SMALL TEMP DIFF °F (diff) °C (diff) AV144 ADF 87 0190 X10 Signed nvoEvapSmTmpDiff SNVT_temp_p
Condenser Small Temp Difference COND SMALL TEMP DIFF °F (diff) °C (diff) AV145 ADF 88 0191 X10 Signed nvoCondSmTmpDiff SNVT_temp_p
Discharge Superheat DISCHARGE SUPERHEAT °F (diff) °C (diff) AV146 ADF 89 0192 X10 Signed nvoDschSuperheat SNVT_temp_p
Subcooler Effectiveness SUBCOOLER EFFECTIVENESS Drop Leg Temp Enabled only None None AV147 ADF 90 0193 X10 Signed nvoSubcoolerEff SNVT_count_f
Subcooling Temperature SUBCOOLING TEMP Drop Leg Temp Enabled only °F (diff) °C (diff) AV148 ADF 91 0194 X10 Signed nvoSubcoolingTmp SNVT_temp_p
Delta P / P DELTA P DIV P None None AV149 ADF 92 0195 X10 Signed nvoDeltaPdivP SNVT_count_f
Head Pressure HEAD PRESSURE PSID kPaD AV150 ADF 93 0196 X10 Signed nvoHeadPress SNVT_press
Stall Voltage STALL VOLTAGE Volts Volts AV151 ADF 94 0197 X10 Signed nvoStallVoltage SNVT_volt
Run/Stop Control Source [0=Local, 1=BAS, 2=Hardwire] RUN STOP CTRL SOURCE 0=Local, 1=BAS, 2=Hardwire MV10 N/A N/A N/A Unsigned N/A N/A
Run/Stop Control Source AV [0=Local, 1=BAS, 2=Hardwire] RUN STOP CTRL SOURCE AV None None 0=Local, 1=BAS, 2=Hardwire AV421 ADI 21 0198 X1 Unsigned nvoRunStopSrce SNVT_count
0=Local
1=BAS
2=0-10 Volts
3=4-20 mA
Cooling Setp Control Source [0=Local, 1=BAS, 2=0-10 Volts, 3=4-20
COOLmA,
SETP
4=PWM]
CTRL SOURCE 4=PWM MV11 N/A N/A N/A Unsigned N/A N/A
0=Local
1=BAS
2=0-10 Volts
3=4-20 mA
Cooling Setp Control Source AV [0=Local, 1=BAS, 2=0-10 Volts, 3=4-20
COOL SETP
mA, CTRL
4=PWM]
SOURCE AV None None 4=PWM AV422 ADI 22 0199 X1 Unsigned nvoCoolSetpSrce SNVT_count
0=Local
1=BAS
2=0-10 Volts
3=4-20 mA
Heating Setp Control Source [0=Local, 1=BAS, 2=0-10 Volts, 3=4-20
HEATmA,
SETP
4=PWM]
CTRL SOURCE 4=PWM MV12 N/A N/A N/A Unsigned N/A N/A
0=Local
1=BAS
2=0-10 Volts
3=4-20 mA
Heating Setp Control Source AV [0=Local, 1=BAS, 2=0-10 Volts, HEAT
3=4-20
SETP
mA,CTRL
4=PWM]
SOURCE AV None None 4=PWM AV423 ADI 23 0200 X1 Unsigned nvoHeatSetpSrce SNVT_count
0=Local
1=BAS
2=0-10 Volts
3=4-20 mA
Current Limit Control Source [0=Local, 1=BAS, 2=0-10 Volts, 3=4-20
CURRmA,
LIM4=PWM]
CTRL SOURCE 4=PWM MV13 N/A N/A N/A Unsigned N/A N/A
0=Local
1=BAS
2=0-10 Volts
3=4-20 mA
Current Limit Control Source AV [0=Local, 1=BAS, 2=0-10 Volts,CURR
3=4-20
LIM
mA,
CTRL
4=PWM]
SOURCE AV None None 4=PWM AV424 ADI 24 0201 X1 Unsigned nvoCurrLimSrce SNVT_count
YK SC-EQ BAS Points List
Rev 2.3
January 2, 2019

YK Operation Code SC.1 YK Safety Fault Code SC.2 YK Safety Fault Code SC.2 YK Safety Fault Code SC.2
*NOTE: for BACnet MSV values add 1 to number *NOTE: for BACnet MSV values add 1 to number *NOTE: for BACnet MSV values add 1 to number *NOTE: for BACnet MSV values add 1 to number
Code SC.1 Code SC.2 Code SC.2 Code SC.2
0 Unit Stopped - Ready to Start 0 No Safety Faults Present 65 VSD - High Phase C Inverter Baseplate Temperature 130 VSD - High Phase A Motor Baseplate Temperature
1 Unit Stopped - Local Shutdown 1 Evaporator - Low Pressure 66 VSD - Motor Current Imbalance 131 VSD - High Phase B Motor Baseplate Temperature
2 Unit Stopped - Remote Shutdown 2 Evaporator - Transducer Or Leaving Liquid Probe 67 Condenser - High Pressure - Stopped 132 VSD - High Phase C Motor Baseplate Temperature
3 Unit Stopped - Warning Active 3 Evaporator - Transducer Or Temperature Sensor 68 OIL – HIGH SUPPLY TEMPERATURE 133 VSD - Phase A Motor DCCT
4 Unit Stopped - Cycling Shutdown 4 Condenser - High Pressure Contacts Open 69 Motor - High Bearing Vibration 134 VSD - Phase B Motor DCCT
5 Unit Stopped - Safety Shutdown 5 Condenser - High Pressure 70 SALES ORDER – INVALID MODEL NUMBER 135 VSD - Phase C Motor DCCT
6 Unit Start Inhibit 6 Condenser - Pressure Transducer Out Of Range 71 LCSSS - Phase A Open Scr 136 Oil – High Sump Pressure
7 Unit Starting 7 Auxiliary Safety - Contacts Closed 72 LCSSS - Phase B Open Scr 137 MBC – OVERSPEED FAULT
8 Unit Running - No Abnormal Condition 8 Discharge - Low Temperature 73 LCSSS - Phase C Open Scr 138 MBC – WATCHDOG
9 Unit Running - Warning Active 9 Discharge - High Temperature 74 Motor - Lack Of Bearing Lubrication 139 MBC – POWER SUPPLY FAULT
10 Unit Running - Chiller Unload Before Shutdown 10 Oil - High Sump Temperature 75 VSD - Low Frequency Detected 140 MBC – HIGH HEATSINK TEMPERATURE
11 Unit Coastdown 11 Oil - Low Differential Pressure 76 VSD - Feedback Sensor 141 MBC – HIGH DC BUS VOLTAGE
12 Unit Running - Modified Run 12 Oil - High Differential Pressure 77 VSD - Control Fault 142 MBC – AMPLIFIER FUSE
13 Unit Stopped - Internal Shutdown 13 Oil - Pump Pressure Transducer Out Of Range 78 VSD - Drive Boot Failure 143 MBC – HIGH BEARING J TEMPERATURE
14 N/A 14 Oil - Sump Pressure Transducer Out Of Range 79 MVSSS - Phase Rotation 144 MBC – HIGH BEARING H1 TEMPERATURE
15 N/A 15 Motor - Lack of Motor Oil Change 80 MVSSS - Motor Or Starter - Current Imbalance 145 MBC – HIGH BEARING H2 TEMPERATURE
16 N/A 16 Sales Order - Invalid Compressor Model 81 MVSSS - 105% Motor Current Overload 146 MBC – HIGH BEARING K TEMPERATURE
17 N/A 17 Sales Order – Invalid Gear Code 82 MVSSS - High Instantaneous Current 147 MBC – GROUND FAULT
18 N/A 18 Oil - Differential Pressure Calibration 83 MVSSS - Failed SCR 148 MBC – LOW GATE VOLTAGE
19 N/A 19 Safety Stop 84 MVSSS - High Heatsink Temperature - Running 149 MBC – HIGH GATE VOLTAGE
20 N/A 20 Oil - Variable Speed Pump - Setpoint Not Achieved 85 MVSSS - Ground Fault 150 MBC – HIGH AMPLIFIER TEMPERATURE
21 Unit Running - Cooling - No Abnormal Condition 21 Control Panel - Power Failure 86 MVSSS - Contactor Fault 151 MBC – HIGH AMPLIFIER VOLTAGE
22 Unit Running - Cooling - Warning Active 22 Control Panel – Loss of Control Voltage 87 MVSSS - Motor Drive Fault 152 MBC – FAULT CONTACTS OPEN
23 Unit Running - Cooling - Modified Run 23 Motor Or Starter - Current Imbalance 88 MVSSS - Disconnect 153 MBC – INITIALIZATION FAILURE
24 Unit Running - Heating - No Abnormal Condition 24 Thrust Bearing - Proximity Probe Clearance 89 VSD - Power Transformer High Temperature 154 MBC – NOT LEVITATED
25 Unit Running - Heating - Warning Active 25 Thrust Bearing - Proximity Probe Uncalibrated 90 VSD - High Output Frequency 155 SYSTEM – STARTUP FAILURE
26 Unit Running - Heating - Modified Run 26 Thrust Bearing - Proximity Probe Out Of Range 91 MVVSD - Ground Fault 156 UPS – Battery Not Connected
27 Unit Running - Cooling & Heating - No Abnormal Condition 27 Thrust Bearing - High Oil Temperature 92 VSD - Main Control Board Fault 157 UPS – Inverter Low Battery Voltage
28 Unit Running - Cooling & Heating - Warning Active 28 Thrust Bearing - Oil Temperature Sensor 93 MVVSD - Contactor Fault 158 MBC – SPEED SENSOR FAULT
29 Unit Running - Cooling & Heating - Modified Run 29 VSD - High Heatsink Temperature 94 MVVSD - Interlock Fault 159 MBC – POWER FAIL LANDING
30 VSD - 105% Motor Current Overload 95 VSD - Logic Board Plug Fault 160 COMPRESSOR – LOW DISCHARGE SUPERHEAT
31 VSD - High Phase A Inverter Heatsink Temperature 96 VSD - Input Current Overload
32 VSD - High Phase B Inverter Heatsink Temperature 97 VSD - High Phase A Input Baseplate Temperature
33 VSD - High Phase C Inverter Heatsink Temperature 98 VSD - High Phase B Input Baseplate Temperature
34 VSD - High Converter Heatsink Temperature 99 VSD - High Phase C Input Baseplate Temperature
35 VSD - Precharge Lockout 100 MOTOR – LOW WINDING TEMPERATURE
36 Harmonic Filter - High Heatsink Temperature 101 VSD – INVALID PWM SOFTWARE
37 Harmonic Filter - High Total Demand Distortion 102 VSD – BASEPLATE TEMPERATURE IMBALANCE
38 LCSSS - Phase Rotation 103 VSD - DC Bus Pre-Regulation Lockout
39 LCSSS - Motor Or Starter - Current Imbalance 104 VSD - Ground Fault
40 LCSSS - 105% Motor Current Overload 105 N/A
41 LCSSS - High Instantaneous Current 106 N/A
42 LCSSS - Open Scr 107 N/A
43 LCSSS - Phase A Shorted Scr 108 VSD - Phase A Input DCCT
44 LCSSS - Phase B Shorted Scr 109 VSD - Phase B Input DCCT
45 LCSSS - Phase C Shorted Scr 110 VSD - Phase C Input DCCT
46 LCSSS - High Phase A Heatsink Temperature - Running 111 VSD - High Total Demand Distortion
47 LCSSS - High Phase B Heatsink Temperature - Running 112 Motor – Cooling Coil Leak
48 LCSSS - High Phase C Heatsink Temperature - Running 113 MVVSD - Excessive Shutdowns
49 Starter - Invalid Motor Selection 114 Isolation Valves - Not Opened
50 Oil Or Condenser Transducer Error 115 VSD - Output Phase Rotation
51 N/A (Legacy: Evaporator - Low Pressure) 116 N/A (V01-V03 was VSD - Phase Locked Loop)
52 Evaporator - Low Pressure - Smart Freeze 117 VSD - HIGH PHASE A INSTANTANEOUS CURRENT
53 Surge Protection - Excess Surge 118 VSD - HIGH PHASE B INSTANTANEOUS CURRENT
54 VSD - High Inverter Baseplate Temperature 119 VSD - HIGH PHASE C INSTANTANEOUS CURRENT
55 Harmonic Filter - High Baseplate Temperature 120 N/A (V01-V03 was VSD - Line Voltage Phase Rotation)
56 Thrust Bearing - Proximity Probe Clearance 121 VSD - Input DCCT Offset Lockout
57 Thrust Bearing - Limit Switch Open 122 VSD - Logic Board Hardware
58 VGD Actuator – Positioning Fault 123 VSD - Rectifier Program Fault
59 Oil – Sump Or Pump Transducer Error 124 VSD - Inverter Program Fault
60 Motor - High Housing Temperature 125 VSD - DC Bus Lockout - Do Not Cycle Power
61 Motor - High Winding Temperature 126 VSD - Motor Current THD Fault
62 Motor - High Bearing Temperature 127 VSD - High Phase A Motor Current
63 VSD - High Phase A Inverter Baseplate Temperature 128 VSD - High Phase B Motor Current
64 VSD - High Phase B Inverter Baseplate Temperature 129 VSD - High Phase C Motor Current
YK SC-EQ BAS Points List
Rev 2.3
January 2, 2019

YK Cycling Fault Code SC.3 YK Cycling Fault Code SC.3 YK Cycling Fault Code SC.3
*NOTE: for BACnet MSV values add 1 to number *NOTE: for BACnet MSV values add 1 to number *NOTE: for BACnet MSV values add 1 to number
Code SC.3 Code SC.3 Code SC.3
0 No Cycling Faults Present 65 LCSSS - Invalid Current Scale Selection 130 VSD - Gate Driver - CMU
1 Multiunit Cycling - Contacts Open 66 LCSSS - Run Signal 131 VSD - Gate Driver - CML
2 System Cycling - Contacts Open 67 LCSSS - Serial Communications 132 VSD - Input Power Supply
3 Oil - Low Temperature Differential 68 LCSSS - Stop Contacts Open 133 VSD - High Phase A Input Current
4 Oil - Low Sump Temperature 69 Motor Auto Lubrication In Progress 134 VSD - High Phase B Input Current
5 Control Panel - Power Failure 70 Control Panel – Loss of Control Voltage 135 VSD - High Phase C Input Current
6 Leaving Chilled Liquid - Low Temperature 71 LCSSS - Logic Board Processor 136 VSD - High Phase A Motor Current
7 Leaving Chilled Liquid - Flow Switch Open 72 LCSSS - Logic Board Power Supply 137 VSD - High Phase B Motor Current
8 Condenser - Flow Switch Open 73 VSD - Serial Communications 138 VSD - High Phase C Motor Current
9 Motor Controller - Contacts Open 74 LCSSS - Serial Communications 139 VSD - Phase A Input Gate Driver
10 Motor Controller - Loss Of Current 75 LCSSS - Phase Loss 140 VSD - Phase B Input Gate Driver
11 Power Fault 76 VSD - Low Inverter Baseplate Temperature 141 VSD - Phase C Input Gate Driver
12 Control Panel - Schedule 77 Expansion I/O – Serial Communications 142 VGD Actuator – Serial Communications
13 Starter - Low Supply Line Voltage 78 VSD - Low Phase A Inverter Baseplate Temperature 143 VSD – INVALID VSD MODEL
14 Starter - High Supply Line Voltage 79 VSD - Low Phase B Inverter Baseplate Temperature 144 VSD – BASEPLATE TEMPERATURE IMBALANCE
15 Proximity Probe - Low Supply Voltage 80 VSD - Low Phase C Inverter Baseplate Temperature 145 VSD - Low Phase A Input Baseplate Temperature
16 Oil - Variable Speed Pump - Drive Contacts Open 81 Motor Controller - Contacts Open 146 VSD - Low Phase B Input Baseplate Temperature
17 VSD - Initialization Failed 82 MVVSD - Serial Communications 147 VSD - Low Phase C Input Baseplate Temperature
18 VSD Shutdown - Requesting Fault Data... 83 VSD - Input Power Transformer 148 VSD – PHASE LOCKED LOOP
19 VSD - High Phase A Instantaneous Current 84 VSD - Input Over-Voltage 149 VSD – LINE VOLTAGE PHASE ROTATION
20 VSD - High Phase B Instantaneous Current 85 VSD - Loss Of Cooling Fan 150 N/A
21 VSD - High Phase C Instantaneous Current 86 VSD - High Instantaneous Current 151 VSD - Input Voltage Imbalance
22 VSD - Phase A Gate Driver 87 MVSSS - Initialization Failed 152 VSD - DC Bus Voltage Pre-Regulation Fault
23 VSD - Phase B Gate Driver 88 MVSSS Shutdown - Requesting Fault Data... 153 VSD - Logic Board Processor
24 VSD - Phase C Gate Driver 89 MVSSS - Power Fault 154 N/A
25 VSD - Single Phase Input Power 90 MVSSS - High Supply Line Voltage 155 VSD - Identifying Drive…
26 VSD - High DC Bus Voltage 91 MVSSS - Low Supply Line Voltage 156 Leaving Condenser Liquid - High Temperature
27 VSD - Logic Board Power Supply 92 MVSSS - Run Signal 157 Condenser - Freeze Threat - Flow Switch Open
28 VSD - Low DC Bus Voltage 93 MVSSS - Serial Communications 158 Isolation Valves - Not Closed
29 VSD - DC Bus Voltage Imbalance 94 MVSSS - Stop Contacts Open 159 VSD - Phase A Input DCCT Offset
30 VSD - High Internal Ambient Temperature 95 MVSSS - Logic Board Power Supply 160 VSD - Phase B Input DCCT Offset
31 VSD - Invalid Current Scale Selection 96 MVSSS - Phase Loss 161 VSD - Phase C Input DCCT Offset
32 VSD - Low Phase A Inverter Heatsink Temperature 97 REFRIGERANT TYPE NOT SET 162 VSD - Invalid Setpoints
33 VSD - Low Phase B Inverter Heatsink Temperature 98 VSD - Serial Communications Vyper 163 VSD - Precharge - Low DC Bus Voltage 2
34 VSD - Low Phase C Inverter Heatsink Temperature 99 LCSSS - Serial Comms 164 VSD - Serial Receive
35 VSD - Low Converter Heatsink Temperature 100 VSD - Serial Communications Raptyr 165 VSD - Phase A Motor Gate Driver
36 VSD - Precharge - DC Bus Voltage Imbalance 101 AutoDetect - Serial Communications 166 VSD - Phase B Motor Gate Driver
37 VSD - Precharge - Low DC Bus Voltage 102 VSD - DC Bus Voltage Imbalance _ AU 167 VSD - Phase C Motor Gate Driver
38 VSD - Logic Board Processor 103 VSD - DC Bus Voltage Imbalance _ AL 168 VSD - Low Phase A Motor Baseplate Temperature
39 VSD - Run Signal 104 VSD - DC Bus Voltage Imbalance _ BU 169 VSD - Low Phase B Motor Baseplate Temperature
40 VSD - Serial Receive 105 VSD - DC Bus Voltage Imbalance _ BL 170 VSD - Low Phase C Motor Baseplate Temperature
41 VSD - Stop Contacts Open 106 VSD - DC Bus Voltage Imbalance _ CU 171 VSD - Not Running
42 Harmonic Filter - Logic Board Or Communications 107 VSD - DC Bus Voltage Imbalance _ CL 172 Motor - Lack Of Bearing Lubrication
43 Harmonic Filter - High DC Bus Voltage 108 VSD - Precharge - DC Bus Voltage Imbalance - AU 173 Evaporator - Low Pressure
44 Harmonic Filter - High Phase A Current 109 VSD - Precharge - DC Bus Voltage Imbalance - AL 174 Expansion I/O – Serial Communications
45 Harmonic Filter - High Phase B Current 110 VSD - Precharge - DC Bus Voltage Imbalance - BU 175 Evaporator - Low Pressure - Smart Freeze
46 Harmonic Filter - High Phase C Current 111 VSD - Precharge - DC Bus Voltage Imbalance - BL 176 MBC – LOW DC BUS VOLTAGE
47 Harmonic Filter - Phase Locked Loop 112 VSD - Precharge - DC Bus Voltage Imbalance - CU 177 MBC – J RADIAL POSITION
48 Harmonic Filter - Precharge - Low DC Bus Voltage 113 VSD - Precharge - DC Bus Voltage Imbalance - CL 178 MBC – K RADIAL POSITION
49 Harmonic Filter - Low DC Bus Voltage 114 VSD - High DC Bus Voltage - AU 179 MBC – H AXIAL POSITION
50 Harmonic Filter - DC Bus Voltage Imbalance 115 VSD - High DC Bus Voltage - AL 180 MBC – FAULT CONTACTS OPEN
51 Harmonic Filter - Input Current Overload 116 VSD - High DC Bus Voltage - BU 181 MBC – SERIAL COMMUNICATIONS
52 Harmonic Filter - Logic Board Power Supply 117 VSD - High DC Bus Voltage - BL 182 SYSTEM – STARTUP FAILURE
53 Harmonic Filter - Run Signal 118 VSD - High DC Bus Voltage - CU 183 UPS – Line Low Battery Voltage
54 Harmonic Filter - DC Current Transformer 1 119 VSD - High DC Bus Voltage - CL 184 MBC – CALIBRATION FAULT
55 Harmonic Filter - DC Current Transformer 2 120 VSD - Gate Driver - ANU 185 MBC – BEARING CALIBRATION REQUIRED
56 LCSSS Initialization Failed 121 VSD - Gate Driver - ANL
57 LCSSS Shutdown - Requesting Fault Data... 122 VSD - Gate Driver - AMU
58 LCSSS - Low Phase A Temperature Sensor 123 VSD - Gate Driver - AML
59 LCSSS - Low Phase B Temperature Sensor 124 VSD - Gate Driver - BNU
60 LCSSS - Low Phase C Temperature Sensor 125 VSD - Gate Driver - BNL
61 LCSSS - Phase Locked Loop 126 VSD - Gate Driver - BMU
62 LCSSS - Power Fault 127 VSD - Gate Driver - BML
63 LCSSS - High Supply Line Voltage 128 VSD - Gate Driver - CNU
64 LCSSS - Low Supply Line Voltage 129 VSD - Gate Driver - CNL
YK SC-EQ BAS Points List
Rev 2.3
January 2, 2019

YK Warning Code SC.4 YK Warning Code SC.4 YK Warning Code SC.4 YK Start Inhibit Code SC.13
*NOTE: for BACnet MSV values add 1 to number *NOTE: for BACnet MSV values add 1 to number *NOTE: for BACnet MSV values add 1 to number *NOTE: for BACnet MSV values add 1 to number
Code SC.4 Code SC.4 Code SC.4 Code SC.13
0 No Warnings Present 65 ECON LCSSS - High Phase A Heatsink Temp - Stopped 130 MBC – POSITION SENSOR ERROR 0 No Inhibit Faults Present
1 Real-Time Clock Failure 66 ECON LCSSS - High Phase B Heatsink Temp – Stopped 131 UPS – Not Charging 1 Anti-Recycle
2 Setpoint Override 67 ECON LCSSS - High Phase C Heatsink Temp - Stopped 132 UPS – Line Low Battery Voltage 2 Vane Motor Switch Open
3 Condenser Or Evaporator Transducer Error 68 ECON LCSSS - High Phase A Heatsink Temperature 133 UPS – Battery Not Connected 3 Motor Current > 15% FLA
4 Evaporator - Low Pressure Limit 69 ECON LCSSS - High Phase B Heatsink Temperature 134 UPS – Check Battery Connection 4 LCSSS - High Phase A Heatsink Temperature - Stopped
5 Condenser - High Pressure Limit 70 ECON LCSSS - High Phase C Heatsink Temperature 135 PURGE – HIGH COIL TEMP 5 LCSSS - High Phase B Heatsink Temperature - Stopped
6 OIL – HIGH SUPPLY TEMPERATURE 71 ECON LCSSS - Low Phase A Temperature Sensor 136 PURGE – HIGH COIL TEMP INHIBIT 6 LCSSS - High Phase C Heatsink Temperature - Stopped
7 COMPRESSOR – LOW DISCHARGE SUPERHEAT LIMIT 72 ECON LCSSS - Low Phase B Temperature Sensor 137 PURGE – HIGH REGEN TANK TEMP 7 N/A
8 N/A 73 ECON LCSSS - Low Phase C Temperature Sensor 138 PURGE – HIGH LEVEL 8 VSD - Frequency > 0 Hz
9 Standby Lube - Low Oil Pressure 74 ECON LCSSS - Serial Receive 139 PURGE – EXCESS PURGE 9 MVSSS - High Heatsink Temperature - Stopped
10 N/A 75 ECON LCSSS - Logic Board Power Supply 140 PURGE – EQUALIZATION LOW SUCTION TEMP 10 Line Voltage Not Set
11 N/A 76 ECON LCSSS - Phase Rotation 141 PURGE – POSSIBLE AIR IN SYSTEM 11 Line Frequency Not Set
12 N/A 77 ECON LCSSS – Undefined Fault 142 PURGE – OPERATION INHIBITED 12 Oil – High Sump Pressure - Stopped
13 VGD Not Calibrated 78 COND OR ECON XDCR ERROR 13 VGD Actuator – Feedback Not Calibrated
14 VGD Actuator Switch Open 79 EVAP OR ECON XDCR ERROR 14 VGD Actuator – Limit Switch Open
15 PRV Not Calibrated 80 COND OR ECON VGD XDCR FAUILURE 15 PRV Not Calibrated
16 Vanes Uncalibrated - Fixed Speed 81 ECON HIGH STALL – VGD OVERRIDE 16 VGD Actuator – Stroke Not Calibrated
17 Harmonic Filter - Operation Inhibited 82 ECON STANDBY LUBE – LOW OIL PRESSURE 17 MBC – INITIALIZATION IN PROGRESS
18 Harmonic Filter - Data Loss 83 ECON SEAL LUBRICATION INHIBITED 18 MBC – BEARING CALIBRATION IN PROGRESS
19 Auto Lube Req'd On Next Shutdown 84 ECON MOTOR – BEARING LUBE SUGGESTED 19 MBC – BEARING CLEARANCE CHECK IN PROGRESS
20 Auto Lube Grease Level Low 85 ECON MOTOR – BEARING LUBE REQUIRED
21 Auto Lube Failed 86 ECON MOTOR – BEARING LUBE NOT DONE
22 Motor Oil Change Suggested 87 ECON LIQUID LEVEL SETPOINT NOT ACHIEVED
23 Motor Oil Change Required 88 ECONOMIZER – LEVEL HIGH
24 Lack of Motor Oil Change 89 ECON ANTI-RECYCLE
25 Seal Lubrication In Process 90 ECON COMPRESSOR – PRV MOTOR SWITCH OPEN
26 External I/O - Serial Communications 91 ECONOMIZER – PRESSURE XDCR FAILURE
27 N/A 92 ECON COMPRESSOR – HPCO SWITCH OPEN YK Modified Run Code SC.12
28 N/A 93 ECON COMPRESSOR – GEAR RATIO INVALID *NOTE: for BACnet MSV values add 1 to number
29 Surge Protection - Excess Surge Limit 94 ECON MOTOR – LINE FREQUENCY NOT SET Code SC.12
30 Excess Surge Detected 95 ECON DISCHARGE – LOW TEMPERATURE 0 No Modified Run Conditions Present
31 HARMONIC FILTER – INVALID MODEL 96 ECON DISCHARGE – HIGH TEMPERATURE 1 Reserved 1
32 Motor - High Housing Temperature 97 ECON THRUST BEARING – LIMIT SWITCH OPEN 2 Reserved 2
33 KW Meter Not Calibrated 98 ECON OIL – VSD PUMP – FAULT CONTACTS OPEN 3 Reserved 3
34 Condenser Or VGD Sensor Failure 99 ECON OIL – PUMP PRESSURE XDCR FAILURE 4 Motor - Pulldown Limit
35 Conditions Override VGD 100 ECON OIL – DIFF PRESSURE CALIBRATION 5 Motor - High Current Limit
36 Motor Bearing Lube Suggested 101 ECON OIL – LOW DIFFERENTIAL PRESSURE 6 Motor Controller – Input Pulldown Limit
37 Motor Bearing Lube Required 102 ECON OIL – HIGH DIFFERENTIAL PRESSURE 7 Motor Controller – High Input Power Limit
38 Motor Bearing Lube Not Done 103 ECON OIL – VSD PUMP – SETPOINT NOT ACHIEVED 8 Load Control Mode
39 Harmonic Filter - Data Loss 104 ECON MOTOR CONTROLLER – LOSS OF CURRENT 9 COMPRESSOR – CARRYOVER CURRENT LIMIT
40 Motor – High Winding Temperature 105 ECON MOTOR CONTROLLER – SERIAL COMMUNICATIONS 10 N/A
41 Motor – High Bearing Temperature 106 ECON MOTOR CONTROLLER – INITIALIZATION FAILED 11 VSD - Input Pulldown Limit
42 Motor – High Bearing Vibration 107 ECON MOTOR CONTROLLER – FAULT CONTACTS OPEN 12 VSD - High Input Current Limit
43 Motor – Bearing Vibration Baseline Not Set 108 ECON MOTOR – LACK OF BEARING LUBRICATION 13 Discharge – Low Superheat Limit
44 VSD - Input Voltage Imbalance 109 ECON MOTOR – CURRENT > 15 %FLA 14 ECON MOTOR – HIGH CURRENT LIMIT
45 Harmonic Filter - Not Running 110 ECON COMPRESSOR – PRV NOT CALIBRATED 15 ECON SEAL LUBRICATION IN PROGRESS
46 Condenser- Freeze Threat From Low Pressure 111 ECONOMIZER – HIGH LEVEL (STOPPED) 16 ECON ECONOMIZER – RUN DISABLED
47 Liquid Level Setpoint Not Achieved 112 SALES ORDER –INVALID MOTOR VOLTS OR FLA 17 ECON ECONOMIZER – NO DEMAND
48 VSD - DC Bus Active 113 ECON MOTOR – HIGH WINDING TEMP 18 ECON COMPRESSOR – NO DEMAND (ECON STOPPED)
49 Loss Of Subcooler Liquid Seal 114 ECON MOTOR – HIGH BEARING TEMP
50 Oil - High Sump Pressure 115 ECON MOTOR – HIGH BEARING VIBRATION
51 ECON LCSSS - Invalid Current Scale Selection 116 ECON MOTOR – VIBRATION BASELINE NOT SET
52 ECON LCSSS - Phase Loss 117 ECON MOTOR – HIGH WINDING TEMP SHUTDOWN
53 ECON LCSSS - Phase Locked Loop 118 ECON MOTOR – HIGH BEARING TEMP SHUTDOWN
54 ECON LCSSS - Power Fault 119 ECON MOTOR – HIGH BEARING VIBRATION SHUTDOWN
55 ECON LCSSS - Run Signal 120 ECON MOTOR – AUTO LUBRICATION IN PROGRESS
56 ECON LCSSS - Motor Current Imbalance 121 ECON AUTO LUBE REG’D ON NEXT SHUTDOWN YK Internal Fault Code SC.14
57 ECON LCSSS - 105 % Motor Current Overload 122 ECON AUTO LUBE GREASE LEVEL LOW *NOTE: for BACnet MSV values add 1 to number
58 ECON LCSSS - High Motor Current 123 ECON AUTO LUBE FAILED Code SC.14
59 ECON LCSSS - High Supply Line Voltage 124 ECON MMB I/O SERIAL COMMUNICATIONS 0 No Internal Faults Present
60 ECON LCSSS - Low Supply Line Voltage 125 N/A 1 Internal Error - No Timer Handles Available
61 ECON LCSSS - Open SCR 126 MBC – LOW AMPLIFIER RESISTANCE 2 Watchdog - Software Reboot
62 ECON LCSSS - Phase A Shorted SCR 127 MBC – HIGH AMPLIFIER RESISTANCE 3 Internal Error - Cannot Create Task
63 ECON LCSSS - Phase B Shorted SCR 128 MBC – LOW AMPLIFIER CURRENT 4 N/A
64 ECON LCSSS - Phase C Shorted SCR 129 MBC – HIGH AMPLIFIER CURRENT 5 INTERNAL ERROR - INVALID BRAM