REF 615 MANTRAC INCOMER

Present Protection Settings Modified Protection Settings

Current (3I, CT) Current (3I, CT)


Pry Current: 300A Pry Current: 500A
Sec Current: 1A Sec Current: 1A

PHIPTOC 1 PHIPTOC 1
Operation: On Operation: On
No of start phases: 1 out of 3 No of start phases: 1 out of 3
Start value: 1 x In Start value: 0.6 x In
Start value mult: 1.0 Start value mult: 1.0
Operate delay time: 20ms Operate delay time: 20ms
Reset delay time: 20ms Reset delay time: 20ms

DPHHPDOC 1 DPHHPDOC 1
Operation: On Operation: On
Start value: 2.75 x In Start value: 1.65 x In
Start value mult: 1.0 Start value mult: 1.0
Directional mode: Non-directional Directional mode: Non-directional
Operation curve type: IEC Def time Operation curve type: IEC Def time
Operate delay time: 400ms Operate delay time: 400ms
Reset delay time: 20ms Reset delay time: 20ms
Measurement mode: DFT Measurement mode: DFT
No of start phases: 1 out of 3 No of start phases: 1 out of 3

DPHLPDOC 1 DPHLPDOC 1
Operation: On Operation: On
No of start phases: 1 out of 3 No of start phases: 1 out of 3
Start value: 0.85 x In Start value: 0.51 x In
Start value mult: 1.0 Start value mult: 1.0
Time mult: 1.00 Time mult: 1.00
Min operate time: 500ms Min operate time: 500ms
Reset delay time: 20ms Reset delay time: 20ms
Operating Curve type: IEC Ext Inv Operating Curve type: IEC Ext Inv
Type of reset curve: Immediate Type of reset curve: Immediate
Measurement mode: DFT Measurement mode: DFT
Directional mode: Non-directional Directional mode: Non-directional