Total Measure Project

quantity Unit Code Description Art. n. Revision

ELECTRICAL WORKS

ELECTRICAL SYSTEM E.01

UPS E.01.01

1.00 n. UPS DEVICE E.01.01.01


Supply and installation of UPS:
- input: 230/415 V
- output: 230/415 V
- frequency: 50/60Hz
- Power: 10 kVA - potential-free contact for remote
alarm - pre-set for inhibition by remote control - 9
integrated protected circuit breaker - in compliance
with local regulations.
-Battery backup: 15-20 Minutes at full load
Note- GC must referred to the connected load under
UPS DB panel and UPS with enough capacity must
be provided.
Brand: Schneider UPS

EARTHING SYSTEM E.01.02

1.00 l.s. Earthing E.01.02.01


Supply and installation of the earthing system in
accordance with the rules and the local regulations.

1.00 l.s. Equipotential system E.01.02.02


Supply and installation of the equipotential system
connection point (tubes, ducts for air conditioning or
cable trays) in insulated copper wire, cable terminal
and fixing terminals
1.00 l.s. PE cable E.01.02.03
Connection of the PE cable between the metallic
devices and equipments and the grounding system
inside the main panel.

CONTAINMENTS AND CABLES E.01.03


Note- GC must conduct the site survey and the length of
the conduits and cables to be evaluated accordingly.

1.00 l.s. Rigid PVC pipes - Diameter 25mm E.01.03.01


Supply and installation of rigid PVC pipes, self-
extinguishing, including junction boxes, accessories,
special components and hangers:
Diameter 25mm
1.00 l.s. Rigid PVC pipes - Diameter 32mm E.01.03.02
Supply and installation of rigid PVC pipes, self-
extinguishing, including junction boxes, accessories,
special components and hangers:
Diameter 20mm
1.00 l.s. PVC Flexible pipes - Diameter 25mm E.01.03.03
Supply and installation of PVC flexible cable ducts,
self-extinguishing, including junction boxes, suitable
for installation in:
Diameter 25mm
1.00 l.s. PVC Flexible pipes - Diameter 20mm E.01.03.04
Supply and installation of PVC flexible cable ducts,
self-extinguishing, including junction boxes, suitable
for installation in:
Diameter 20mm
1.00 l.s. PVC Flexible pipes - Diameter 32mm E.01.03.05
Supply and installation of PVC flexible cable ducts,
self-extinguishing, including junction boxes, suitable
for installation in:
Diameter 32mm
1.00 l.s. Wire mesh cable tray - dim.100*50 mm E.01.03.06
Supply and installation of wire mesh cable tray ,
accessories, special chills, baffle sensors and fixing
accessories
dim.100*50 mm
1.00 l.s. Wire mesh cable tray - dim.150*50 mm E.01.03.07
Supply and installation of wire mesh cable tray ,
accessories, special chills, baffle sensors and fixing
accessories
dim.150*50 mm
1.00 l.s. Wire mesh cable tray - dim.300*50 mm E.01.03.08
Supply and installation of wire mesh cable tray ,
accessories, special chills, baffle sensors and fixing
accessories
dim.300*50 mm
1.00 l.s. LSHF - Section 4G95 sq.mm E.01.03.09
Supply and installation of cable U0/U 0450/750V,
90° LS0H (low smoke zero halogen) isolation (H07Z-
K)
Note- It is the bidders responsibility to check and
verify the length of the cables as per the design
drawings. The size and length of the cables to be
decided as per the site survey and location of mall
isolator.

1.00 l.s. LSHF - Section 1G50 sq.mm E.01.03.10


Supply and installation of cable U0/U 0450/750V,
90° LS0H (low smoke zero halogen) isolation (H07Z-
K)
Note- It is the bidders responsibility to check and
verify the length of the cables as per site survey.

1.00 l.s. LSHF - Section 4G25 sq.mm E.01.03.11


Supply and installation of cable U0/U 0450/750V,
90° LS0H (low smoke zero halogen) isolation (H07Z-
K)
Note- It is the bidders responsibility to check and
verify the length of the cables as per site survey.

1.00 l.s. LSHF - Section 4G10 sq.mm E.01.03.12


Supply and installation of cable U0/U 0450/750V,
90° LS0H (low smoke zero halogen) isolation (H07Z-
K)
Note- It is the bidders responsibility to check and
verify the length of the cables as per site survey.

1.00 l.s. LSHF - Section 4G6 sq.mm E.01.03.13


Supply and installation of cable U0/U 0450/750V,
90° LS0H (low smoke zero halogen) isolation (H07Z-
K)
Note- It is the bidders responsibility to check and
verify the length of the cables as per site survey.

1.00 l.s. LSHF - Section 1G16 sq.mm E.01.03.14


Supply and installation of cable U0/U 0450/750V,
90° LS0H (low smoke zero halogen) isolation (H07Z-
K)
Note- It is the bidders responsibility to check and
verify the length of the cables as per the design
drawings. The size and length of the cables to be
decided as per the site survey and location of mall
isolator.

1.00 l.s. LSHF - Section 1G10 sq.mm E.01.03.15


Supply and installation of cable U0/U 0450/750V,
90° LS0H (low smoke zero halogen) isolation (H07Z-
K)
Note- It is the bidders responsibility to check and
verify the length of the cables as per site survey.

1.00 l.s. LSHF - Section 1G6 sq.mm E.01.03.16


Supply and installation of cable U0/U 0450/750V,
90° LS0H (low smoke zero halogen) isolation (H07Z-
K)
Note- It is the bidders responsibility to check and
verify the length of the cables as per site survey.
1.00 l.s. LSHF - Section 1G4 sq.mm E.01.03.17
Supply and installation of cable U0/U 0450/750V,
90° LS0H (low smoke zero halogen) isolation (H07Z-
K)
Note- It is the bidders responsibility to check and
verify the length of the cables as per site survey.

1.00 l.s. LSHF - Section 1G2.5 sq.mm E.01.03.18


Supply and installation of cable U0/U 0450/750V,
90° LS0H (low smoke zero halogen) isolation (H07Z-
K)
Note- It is the bidders responsibility to check and
verify the length of the cables as per site survey.

1.00 l.s. Closing of cable containments on areas crossing fire E.01.03.19


rated walls
Supply and installation of foam and closing of cable
ducts while crossing the fire rated wall and barriers to
comply local requirements

ELECTRICAL PANELS E.01.04

1.00 n. Sub Main Panel E.01.04.01


Supply and installation of electrical panels with the
characteristics indicated on the wiring diagrams of
the panels and the technical references
Sub Main Panel
All the panels must be cosntructed and installed as
per local electricity standards.

1.00 n. DB-L1 Panel E.01.04.02


Supply and installation of electrical panels with the
characteristics indicated on the wiring diagrams of
the panels and the technical references
DB-L1 panel
Note- Any devices that come inside the DB panels
like the timers for the lights, etc must be included in
the price.

1.00 n. DB-P1 Panel E.01.04.03


Supply and installation of electrical panels with the
characteristics indicated on the wiring diagrams of
the panels and the technical references
DB-P1 Panel
1.00 n. DB-AC1 Panel E.01.04.04
Supply and installation of electrical panels with the
characteristics indicated on the wiring diagrams of
the panels and the technical references
DB-AC1 Panel
Note- Any devices that come inside the DB panels
like the timers for the AC units, etc must be included
in the price.

1.00 n. DB-UPS1 Panel E.01.04.05


Supply and installation of electrical panels with the
characteristics indicated on the wiring diagrams of
the panels and the technical references
DB-UPS1 Panel

3.00 n. Electrical energy meters for the client E.01.04.06


Supply & Installation of electrical energy meters for
the client including the connection, termination,
calibration and interfacing it with the client server.
Meter brand/model- Schneider PM3200 and
Schneider COMX510 series data logger to be
supplied and installed as per client specifications.

1.00 n. data logger for the client E.01.04.07


Supply & Installation of data logger that to be
connected together with the electrical energy meters
for the client including the connection, termination,
calibration and interfacing it with the client server.
Meter brand/model- Schneider PM3200 and
Schneider COMX510 series data logger to be
supplied and installed as per client specifications.

1.00 n. Electrical energy meters by the authorities E.01.04.08


Cordination with Authority for the installation of
electrical energy meter of the store, and any
necessory works related to it. If the meter need to be
supplied by the tenant, GC must include the price for
it too.

LIGHTING AND POWER SYSTEM E.01.05

1.00 l.s. Lighting supply point E.01.05.01


Supply and installation of the lighting supply point for
the entire store included as part of the junction box,
power supplies, PVC and GI conduits and / or cable
trays, cables and a connection / fixing with a double
insulated cable. This must include the containment
fixing and related works for all the area.

1.00 l.s. Lighting devices E.01.05.02


Installation of lighting devices, including tracks,
coves, strip led, show window lights, internal and
external logos, table lamps, shelves and furnitures
for the sales area (supplied by the lighting supplier
and millworker) and connection to prepared light
wirings equipped, if necessary, with a power
transformer; any transformer must be placed in a
specific insulating enclosure and, if not supplied by
the purchaser, must be provided by the installer with
appropriate protective devices on the DC side.
(Precise amount to be verified on lighting designer
layout and millwork plan)
This must include the installation of remote LED
driver and any other works related to the furnuiture
lighting.

1.00 l.s Furniture connections E.01.05.03


Supply and installation of the conduiting and wiring to
the furnture lighting fixtures on the sales area
complete with termination of the cables from the DB
panels to the power drivers kept in a remote location
and then to the furniture fixture as per the furniture
fixture layout provided..
Note- The price must include the supply and
installation of the remote LED driver cabinet
including all the works related to it.

1.00 l.s Furniture lock E.01.05.04


Supply and installation for the conduiting for the
furniture locks as per the layout provided by the
millworker complete from the main lock panel until
the locks and reader installed on the furniture.

23.00 n. Luminaire 60x60 LED Panel light for the BOH area E.01.05.05
Supply and installation of Luminaire ceiling mounted
for BoH area
including point of junction box, steel conduits and / or
cable trays, cables and fixing / connection with
double insulated cable (anti UV)
1.00 n. LED Tube light E.01.05.06
Supply and installation of Luminaire ceiling mounted
LED tube light mounted for BoH area
including point of junction box, steel conduits and / or
cable trays, cables and fixing / connection with
double insulated cable (anti UV)
4.00 n. LED decorative light E.01.05.07
Supply and installation of Luminaire ceiling mounted
LED decorative light mounted for vestibule area
including point of junction box, steel conduits and / or
cable trays, cables and fixing / connection with
double insulated cable (anti UV)
15.00 n. Lighting occupancy sensors for the BOH area E.01.05.08
Supply and installation of occupancy sensors for
BoH area
including point of junction box, steel conduits and / or
cable trays, cables and fixing / connection with
double insulated cable (anti UV)
1.00 n. Lighting control switch (master switch) installed in BOH E.01.05.09

Supply and installation of switch to control the daily


lights in the sales area installed in the BOH area as
indicated on the plan with a transparent cover to be
installed for the master switch to avoid accidental
operation, including point of junction box, steel
conduits and / or cable trays, cables and fixing /
connection with double insulated cable (anti UV)

4.00 n. LED strip light beneath the wall shelf E.01.05.10


Supply and Installation of LED strip lights that to be
installed underneath the wall shelf on the safe room.

17.00 n. LED Emergency light for the sales area E.01.05.11


Supply and installation and connection to the lighting
supply point of Emergency LED luminaire in
accordance with local standard, degree of protection
IP.40, non-maintained, supplied with self-contained
batteries. 3h Autonomy
Brand: Daisalux or similiar

15.00 n. BoH Emergency LED Light E.01.05.12


Supply and installation and connection to the lighting
supply point of Emergency LED luminaire in
accordance with local standard, degree of protection
IP.40, maintained type, supplied with self-contained
batteries. 3h Autonomy for the BOH area
Brand: Daisalux or similiar

2.00 n. Exit sign E.01.05.13


Supply and installation and connection to the lighting
supply point of Output signal (evacuation safety
lighting), complies with local standard, complete with
lamp, type serviced, supplied self-contained
batteries.
Brand: Daisalux or similar

5.00 n. Exit sign (Directional) E.01.05.14


Supply and installation and connection to the lighting
supply point of Output signal (evacuation safety
lighting), complies with local standard, complete with
lamp, type serviced, supplied self-contained
batteries.
Brand: Daisalux or similar
26.00 n. 13A SSO E.01.05.15
Supply and installation of 13A single socket outlets
with conduiting, wiring and connection.
5.00 n. 13A SSO (W/P) E.01.05.16
Supply and installation of 13A single socket outlets,
weather proof type with conduiting, wiring and
connection.
12.00 n. 13A DSO E.01.05.17
Supply and installation of 13A double socket outlets
with conduiting, wiring and connection.
1.00 n. Supply & installation of power isolators for IT rack E.01.05.18
Supply and installation of 32A SP isoalator for the IT
rack including the conduiting and wiring.
6.00 n. Supply & installation of power isolators for the signage E.01.05.19

Supply and installation of 20A SP isoalator for the


signage including the conduiting, wiring and
connection to the sigange (2 no.s) lighting point.
1.00 l.s Supply & installation of power isolators for the rolling E.01.05.20
blind
Supply and installation of 20A SP isoalator for the
rolling blind including the conduiting and wiring.
2.00 n. Direct connection to Access control & antintrusion E.01.05.21
panels
Supply & installation for the conduits and wiring for
the access control and antintrusion panels, including
the installation wiring and connection with the supply
of an unswitched socket.
1.00 n. Direct connection to FACP E.01.05.22
Supply & installation for the conduits and wiring for
the fire alarm panels, including the installation wiring
and connection with the supply of an unswitched
socket.
2.00 n. Direct connection to aspiration system panel E.01.05.23
Supply & installation for the conduits and wiring for
the aspiration panel, including the installation wiring
and connection with the supply of an unswitched
socket.
5.00 n. Direct connection to access control door locks E.01.05.24
Supply & installation for the conduits and wiring for
the access control lock points, including the
installation wiring and connection.
5.00 l.s Direct connection to furniture locks cabinets E.01.05.25
Supply & installation for the conduits for the furniture
locks points, , including the installation wiring and
connection. GC must provide the conduiting for the
access controlled shelfs supplied by the millwork.

1.00 n. Direct connection to main door lock panel E.01.05.26


Supply & installation for the conduits and wiring for
the main control panel of the lock mechanism on the
main entrance.
1.00 l.s Lighting control panel E.01.05.27
Installation of complete lighting control system with
all the accessories like the controller and any other
devices, outside or subtrack, with transparent
lockable door as per the schematic provided.

1.00 l.s Bus cables E.01.05.28


Installation of DMX lighting control cables (supplied
by the lighting supplier) from the lighting control
panel, drivers and fixtures, complete with conduiting
and wiring
1.00 l.s Connection of devices E.01.05.29
Electrical connection of all cash desk and work desk
devices (supplied by the Purchaser)

SUPPLY OF MECHANICAL SYSTEM E.01.06

2.00 n. Internal HVAC unit (ducted type) E.01.06.01


Supply and installation of a user connection point
made with a double insulation multipolar cable,
including junction boxes, PVC piping and assembly
accessories:
1.00 n. VAV E.01.06.02
Supply and installation of a user connection point
made with a double insulation multipolar cable,
including junction boxes, PVC piping and assembly
accessories
6.00 n. Direct connection to fire dampers E.01.06.03
Supply & installation for the conduits and wiring for
the fire damper points, including the installation of
Flex outlets wiring and connection.
2.00 n. Direct connection to Fragrance generators E.01.06.04
Supply & installation for the conduits and wiring for
the fragrance generator points, including the
installation of Flex outlets wiring and connection.
1.00 n. Electrical power provision required for the energy meter E.01.06.05
display panel
Supply & installation for the conduits and wiring for
the energy meter display panel that will be kept on
the BOH area, as per the drawings

SPECIAL SYSTEM E.02

SOUND SYSTEM E.02.01

1.00 l.s. Sound Devices E.02.01.01


Supply and installation of audio system with
complete accessories including the AM/FM radio
tuning, CD/MP3 player, amplifier, audio controller
and all the necessory accessories installed inside the
IT rack. GC must include the cost for the cordination
and installation of all the music and related devices
inside the rack.
Note- It must be provided with individual volume
control for the VIP1, VIP2 and for the sales area as
indicated on the plan.

8.00 n. Speakers E.02.01.02


Supply and installation of speaker, complete with
mounting accessories.
Invisible speakers Brand: AMINA
3.00 n. Volume controllers E.02.01.03
Supply and installation of speaker volume controllers
(wall installation), complete with mounting
accessories to be installed near the managers desk.

1.00 l.s Cables E.02.01.04


Supply and installation of twisted cable for the audio
connection from the main audio unit to the speakers,
including the conduiting,
1.00 l.s. Testing and commissioning E.02.01.05
Testing, commission, set-up and sound check of
system (GC to supply an accurate project prepared
by a qualified sound system professionist to evaluate
the correct system and placement in accordance to
the shop area and its architecture)

DATA TRANSMISSION SYSTEM E.02.02

1.00 n. 42U data cabinet E.02.02.01


Supply and installation of an 800x1000x2000 data
cabinet for racks, cables and rack mounting
equipment, complete with glass front door with key
lock, shutter panels, fans, fixed base, wheels,
shutters, n.3x 8 power unit strips and all necessary
accessories.
Note- IT rack will be equipped with a dedicated UPS
(supplied by the bulgari IT department)

1.00 n. horizontal cable tray E.02.02.02


Supply and installation of a horizontal cable tray.
2.00 n. Patch Panel E.02.02.03
Supply and installation of Cat6 24 Port UTP Patch
Panel
41.00 n. Patch Cord E.02.02.04
Supply and installation of connecting cable RJ45-
RJ45 cat.6 1,5mt. long
41.00 n. connecting cable E.02.02.05
Connecting FTP / UTP cat.6 cable to the rack (patch
panel) and to the jacks. Certification: ISO / IEC
11801 E.
1.00 l.s data cable E.02.02.06
Supply and install UTP 4 * 2 * 24 AWG cat. 6 - Câble
CPR LS0H
13.00 n. Dual Data Socket E.02.02.07
Supply and installation of the socket group (dual
RJ45 outlet), including part of the junction box, steel
conduit and attachment / connection.
7.00 n. Data Socket for Wifi E.02.02.08
Supply and installation of the socket group, including
part of the junction box, steel conduit and attachment
/ connection as in the drawings (dual sockets)

1.00 n. Data Socket for electrical energy meters E.02.02.09


Supply and installation of the socket group, including
part of the junction box, steel conduit and attachment
/ connection for the interface of energy meters
supplied by the client with the client server, relevant
number of data points to be considered.

2.00 n. Data Socket for fragrance genarator E.02.02.10


Supply and installation of the socket group, including
part of the junction box, steel conduit and attachment
/ connection.
1.00 l.s Data Socket for interface E.02.02.11
Supply and installation of the socket group, including
part of the junction box, steel conduit and attachment
/ connection for the interface of the systems like
slaes are lighting, A/V systems etc.

4.00 n. Data Socket as per CCTV requirement E.02.02.12


Supply and installation of the socket group, including
part of the junction box, steel conduit and attachment
/ connection as per the requirement from the CCTV
contactor.

SECURITY SYSTEM E.03

FIRE ALARM SYSTEM E.03.01

1.00 n. Fire alarm control panel E.03.01.01


Supply and installation and connection to an analog
addressable fire control panel derived network
(including battery - 72 hrs duration):
2-loop fire control panel, 99 detectors for each loop,
with programmable output contacts (power relay) for
controlling the release triggers and the power
contactors
Note- Fire alarm system must be compatable with
the basebuilt fire alarm system and must be from a
brand that is approvable by the local civil defence
authority.

3.00 n. Sounder with strobe E.03.01.02


Supply, installation and connection of addressable
electronic depth sounder with flashing light
14.00 n. Optical smoke detector E.03.01.03
Supply, installation and connection of the
addressable optical smoke detector (Tyndall effect)
with insulation module, including mounting
accessories
6.00 n. Smoke detector with LED indicator E.03.01.04
Supply, installation and connection of the
addressable optical smoke detector (Tyndall effect)
with remote LED indicator with insulation module,
including mounting accessories
3.00 n. Glass break button E.03.01.05
Supply and installation of a glass break button
(manual call points) with fire alarm activation
17.00 n. Control module E.03.01.06
Supply and installation of the control module of the
fire detection system, complete with conduiting and
connection
1.00 l.s 2x1.5 mm² cable E.03.01.07
Supply and installation of FP200 2x1.5 mm² cable
red (LS0H, fire resistant 90min) - in accordance with
local requirements.
43.00 n. Connections E.03.01.08
Supply and installation of a power or loop
connection, including a part of the junction box,
conduits and / or cable trays, cables and fastening /
connection
1.00 l.s. Commisioning E.03.01.09
Commisioning system, including technical
operations, system programming and all that is
needed for the system to work.
2.00 l.s Aspirating smoke detector E.03.01.10
Supply and installation of detection units with air-
sampling device made through appropriate
perforated pipe. With two detection modules (single
channel). Behavior of uniform response and high
sensitivity to all the fires set by standard EN54.
Equipped with three indicator lights for operation,
alarm1, and alarm2. Certifications: VdS, LPCB, FM,
EN 54-20 Classes A, B, C. Protection class: IP 20
Brand: VESDA

12.00 n. Sampling points E.03.01.11


Supply and installation sampling point installed on
the ceiling with the connection with the aspiratoryu
detection pipes.
Brand: Vesda - Flush type
1.00 l.s Pipes E.03.01.12
Supply and installation of heavy rigid ABS pipe, DN
25 red, ABS sleeves and
curves, maximum 90° Bends, Caps, etc.
1.00 l.s Testing & commissioning of the system E.03.01.13
Testing and commisiioning of the system including
the programming and start-up of fire detection and
communication with the FACP.

ANTINTRUSION SYSTEM E.03.02

1.00 n. Main panel E.03.02.01


Supply and installation of the main control panel and
devices, power supply, wiring and trunking for all the
devices, foreseen on the spcecilist security project.
Devices will be supplied and installed by the
specialist contractor as per local standards.

22.00 n. Dual technology detectors E.03.02.02


Supply and installation of dual technology detectors
(wall installation).
13.00 n. Panic button E.03.02.03
Supply and installation of panic button (hidden
installation for silent operation).
2.00 n. Seismic sensor on wall E.03.02.04
Supply and installation of seismic sensors with
thermal sensor on the safe room.
15.00 n. Shock guard sensors E.03.02.05
Supply and installation of shock guard sensors.
2.00 n. Seismic floor sensor E.03.02.06
Supply and installation of seismic floor sensors with
thermal sensor.
2.00 n. Seismic sensor on the safe E.03.02.07
Supply and installation of seismic sensor with
thermal sensor on the safe.
2.00 n. Seismic sensor with keyhole protection E.03.02.08
Supply and installation of seismic sensor with
keyhole protection with thermal sensor.
2.00 n. Interlock b/w safe door and safe room door E.03.02.09
Supply and installation of interlock device and
necessary accessories between the safe door and
the safe room door.
2.00 n. Keypad for the safe E.03.02.10
Supply and installation of time delay keypad for the
safe.
4.00 n. Glass break sensor E.03.02.11
Supply and installation of glass break sensor
5.00 n. Sounder E.03.02.12
Supply and installation of sounder with batter pack.
1.00 n. LED 'ON' lights E.03.02.13
Supply and installation of LED light that shows
'ARMED' when the store is armed.
2.00 n. Keypad E.03.02.14
Supply and installation of time delay keypad.
10.00 n. Magnetic door contacts E.03.02.15
Supply and installation of Magnetic contacts.
1.00 n. Antenna E.03.02.16
Supply and installation of antenna that is needed to
sent an alert to the local police incase of a theft
attempt.
1.00 l.s Conduiting for the system E.03.02.17
Supply and installation for the conduiting for the
antintrusion system complete for the devices and the
main panel mentioned above.
1.00 l.s Cabling for the system E.03.02.18
Supply and installation for the cabling for the
antintrusion system complete for the devices and the
main panel mentioned above.
1.00 l.s Necessary interfacing E.03.02.19
Interfacing of the antintrusion system with the sales
area lighting system, with the input module and dry
contact that need to be provided and interfaced with
the lighting control device, for the sales area lighting
to turn on incase of a theft attempt.

ACCESS CONTROL SYSTEM E.03.03

8.00 l.s. Main panel E.03.03.01


Supply and installation of main control panel (wall
installation) power supply, wiring and trunking for all
the devices foreseen in the specialist project.
Devices will be supplied and installed by the
specialist contractor

8.00 n. Electrolock with buzzer E.03.03.02


Supply and installation of electrolock with buzzer.
8.00 n. Push to release E.03.03.03
Supply and installation of Push to release.
8.00 n. badge reader (supplied by the millworker) E.03.03.04
Installation of badge reader.
8.00 n. green button E.03.03.05
Supply and installation of green button.
1.00 l.s AXIS panels E.03.03.06
Installationof AXIS panels (supplied by the
millworker) in an accessible location with the IT
cabling from the IT rack including the conduiting and
termination on both the ends, cordination with the
client for the proper configuration and testing.

1.00 l.s Conduiting for the system E.03.03.07


Supply and installation for the conduiting for the
access control system complete for the devices and
the main panel mentioned above.
1.00 l.s Cabling for the system E.03.03.08
Supply and installation for the cabling for the access
contro system complete for the devices and the main
panel mentioned above.
1.00 l.s Attandance reader E.03.03.09
Supply and installation for the conduiting and cabling
(cat6 cable from the IT rack) for the attendance
reader (supplied by the client) that will be inatalled
near the BOH exit area.

CCTV SYSTEM E.03.04

1.00 l.s. CCTV Rack E.03.04.01


Supply and installation of all the cctv system
accessories like vedio recorder and other
miscellanious devices, power supply, wiring and
trunking for all the devices foreseen in the specialist
project.
Devices will be supplied and installed by the
specialist contractor, as per local cctv standards, the
complete cctv system and devices to be included in
the GC scope as per the drawings provided.
Note- Supply and installation of UPS dedicated for
the CCTV rack must be included, price must includes
that too.

16.00 n. CCTV camera (Recessed mounted) E.03.04.02


Supply and installation of reecssed mounted camera
complete with conduiting.
3.00 n. CCTV camera (vari focal type) E.03.04.03
Supply and installation of pin hole type camera
complete with conduiting.
2.00 n. CCTV camera (exterior bullet type) E.03.04.04
Supply and installation of exterior bullet type camera
complete with conduiting.
2.00 n. CCTV monitors E.03.04.05
Supply and installation of CCTV monitors with all the
accessories.
1.00 l.s Conduiting for the system E.03.04.06
Supply and installation for the conduiting for the
CCTV system complete for the devices and the
CCTV rack mentioned above.
1.00 l.s Cabling for the system E.03.04.07
Supply and installation for the cabling for the cctv
system complete for the devices and the CCTV rack
mentioned above.
1.00 l.s Testing & commissioning of the system E.03.04.08
Testing and commisioning of the system including
complete with the adjustment of the camera points
as required by the client and as per local standards.

SERVICES AND ASSISTANCES E.04

DOCUMENTATION E.04.01

1.00 l.s. As-Built E.04.01.01


PROJECT AS BUILT processing, including assembly
drawings as will be actually executed, specifying the
size, characteristics, model, brand name of the
individual elements of these facilities and all
equipment, and wiring diagrams and operating. This
documentation must definitely include:
. Technical report signed by a qualified technician;
. Documentation attesting to the performance of
instrumental examinations and tests;
. Tables and diagrams for the coordination of
protection;
. Schemes cabinets (including auxiliary diagrams)
signed by the manufacturer;
. Certificates of electrical panels prepared by the
manufacturer;
. Elaborate plans;
All documents constituting the project "As-Built" will
be complete with stamp and signature of a qualified
engineer.

ASSISTANCE WORKS - E.04.02


ELECTRICAL/SPECIAL/SECURITY SYSTEMS

1.00 l.s. Assistance works E.04.02.01


Assistance works and attendancies required for the
electrical and special systems and specialist works.
This item shall include the following activities:
- works, penetrations, reinforcements or other
activities on every kind of surface and material, on
walls, ceilings, slabs or walls, needed for the
installation of all electrical and special devices. To be
done refering to drawings, according to all products
manufacture instructions and indications and as per
Client, LL, LA and local authorities requirements;
- supply of electricity and water to the nearest point
of use and related consumption;
- including provisional and protection works,
scaffolding to reach any height, ladders, chainblock,
transportation and stacking of material/equipment
needed to carry out this work;
- unloading, handling, lifting, moving of incoming
materials and equipment, including the use of
appropriate equipment;
- removal of debris from the collection points set up
on site and transport to the point, including the
related disposal charge;
- cleaning of premises during works and on
completion;
- including any expense and whatever else is needed
to deliver a workmanlike work.
Supply and installation of yard electrical system with
characteristic suitable for the services of the firms
working into the yard. This yard electrical system
shall be realized according to laws and inclusive of
all administrative fulfilments and composed by:
lighting system realized with watertight and self
supplied fluorescent ceiling light, min. 1h autonomy;
type ASC switchboards, IP55, with differential
magnetothermic protection switches and min. 4 CEE
17 mono-phase sockets, 2 CEE 17 three-phase
sockets with interlock and all necessary to correct

Total price includes also:


-as built drawings
-shop drawings
-all necessary certification required according to the
local rules
-all testing and commissioning report (for each of the
systems)
-extra cost for possible adjustement to be carried out
to ducts, pipes, conduits and wathever installed in
presence of obstacle and restriction not foreseen in
the project
-hanging system of all equipment according to LL
requirements based on structural and acoustic
designs
-all necessary/required labels should be both in
English and local languages
-all coring of the slabs required or the cost of
notification to the LL, whenever required.
Notes:
The entries and the quantities can be subjected
to modifications, even relevant, subsequently to
possible revisions
Refer to all notes, diagrams and drawings for all
specification and construction/purchasing
instruction
Please note that the present bill of quantities
should be considered as a reference only. The
offer should include anything showed as per
drawings and with the corresponding quantities
whenever it's indicated in the bill of quantities or
not. I's a precise responsability of the bidder to
check all measurement even with reference to
the site condition and to point out all possible
works he considers not included in the bill of
quantities and price them. The offer provided will
be considered as a complete one to cover all
works as resulting from the provided drawings.
No change order will be accepted for differences
in measure from what expressed in the bill of
quantities neither for works not included in the
bill of quantities but showed in the drawings
and/or in the notes of the bid set.
Art. Unit
Remarks Total price Rate

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00
SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00
SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00
SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00
SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00
SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00
SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00
SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00
SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00
SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00
SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00
SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00
SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00
SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00
SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00
SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00

SAR 0.00
SAR 0.00

SAR 0.00

You might also like