FORTE E FORTEXCEL

FIRE PUMP TEST RESULTS


www.fortefortexcel.com.br forte@fortefortexcel.com.br - Tel.: (11) 5612-5837
Sprinklers
Suction
Client: Pump ID: Fire Pump 1 Rated Flow (l/min): 7733 (2043 gpm) Rated Pressure(bar): 7,0 (100 psi) Rated Speed (rpm): 1775 250 (10 in.)
Size(mm):
(Diesel)
Discharge
Location: Date: Model: Worthington - 6LRG-18 Serial No.: 34977 200 (8 in.)
Size(mm.):
Rated psi at 150% <Leave blank if
Loc ID: Notes: 740 m³ tank (dike) with 100% reserved for fire fighting 4,55 (66 psi)
flow (bar): unknown
Flowing Flow Combined Pressure Vel. Net Pump Corr. to Rated Speed Data Point Final
Inspector Outlet I.D. C*d Meter Flow Suct. Disch. Head Pressure Speed Flow Pressure Rating Pump
(mm) Pitot Readings - (bar) (l/min) (lpm) (bar) (bar) Corr. (bar) (rpm) (l/min) (bar) Rating

25,4 0 0,97 0 0 0,2 10,0 0,0 9,8 1787 0 9,7 NA


Hilário
25,4 25,4 0,97 6,6 6,6 6,6 6,6 6,6 6,6 6,6 6,6 0,0 0,0 0 8.682 0,0 7,0 0,1 7,1 1712 9.001 7,6 4-Excellent 4-Excellent
Leonardo Jr.
25,4 38,1 0,97 3,5 3,5 2,9 2,9 2,9 2,9 2,9 2,9 0,0 0,0 0 11.292 -0,4 4,1 0,1 4,6 1711 11.714 5,0 4-Excellent

in psi gpm gpm psi psi psi rpm gpm psi


Alternate Unit 1 0,97 0 0 0 0 0 0 0 0 0 0 0 2,84 142,0 0,0 139,4 1787 0 137,5
Data 1 0,97 96 96 96 96 96 96 96 96 0 0 2293 0,00 100,0 0,1 100,5 1712 2378 108,0
1 0,97 51 51 42 42 42 42 42 42 0 0 2983 -5,69 58,0 0,1 65,5 1711 3095 70,5

Flow - (L/min)
12,0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000
100 7
11,0

10,0
90 6

9,0

80 8,0 5
Net Pressure - (bar)

7,0

Net Pressure - (bar)


Net Pressure - (psi)

70 4
6,0

5,0
60 3

4,0

50 3,0 2

2,0

40 1
1,0

0,0
30 0 1.000 2.000 3.000 4.000 5.000 6.000 7.000 8.000 9.000 10.000 11.000 12.000 13.000 14.000
0
0 500 1000 1500 2000 2500
FlowFlow - (l/min)
- (gpm)
Corr. to Rated Speed Pump Ratings "Excellent" Curve "Poor" Curve "Good" Curve "Fair" Curve

Corr. to Rated Speed Pump Ratings "Excellent" Curve "Poor" Curve "Good" Curve "Fair" Curve