Comparison of Water Cooled and Air Cooled
Comparison of Water Cooled and Air Cooled
No. Items Air Cooled VRV System Water Cooled Chiller System
1. Equipment
3. Equipment a. 3 set x compressor group for each floor (Range from b. 3 set x 500 RT at Chiller Plant
Configuration 60RT to 72RT) c. 3 set x 700 HRT at Cooling Tower Plant
d. 150 m3 AC make up tank
3. Proposed a. AC ledge area at each floor 26m2 each floor a. Chiller Plant at LG 1 & 2 double volume height , area of 400 m2
plant room b. Total AC ledge area approximately 560 m2 b. Option A: Cooling Tower at Office Roof Top, area of 300 m2
area & Size OR
c. Option B: Cooling Tower at Office L7 & L8 double volume height ,
area of 300 m2
4. System N/A if outdoor unit to be placed at each floor a. Mobilisation of chiller at LG2: Requires Completely Knocked down
Limitation (CKD) during mobilisation. Height of 500RT chiller is 2.4m.
8. 15 years Life RM 10.14 mil + (RM 1.59 mil x 15 yrs) + (RM 202,800 x 15 Option A: RM 10.92 mil + (RM 1.15 mil x 15 yrs) + (RM 436,800 x 15
Cycle Cost yrs) = RM 37,129,650.00 (Highest) yrs) = RM 34,767,525.00 (Lowest)