5.2.

2 Design of Sub-Main

Minimum flow rate is based on Saudi Aramco Engineering Standard SAES-S-020


Section 4.4.2.

Required Discharged Capacity ( Qr ) as per SAES-S-020 Section 4.4.2.


Qr = 63.08 L/sec ( 1000 GPM )

Diagram:

Full flow condition


Area of flow ( A )
A = p D² / 4
Hydraulic radius ( Rh )
Rh = D / 4

Design of Oily Water Line:


Try 12 in diameter RTR pipe
ID = 0.314 m
Area of flow ( A )
A = p D² / 4
= 0.077 m²
Hydraulic radius ( Rh )
Rh = D / 4
= 0.079 m
Using Mannings Formula:
Oily water sewer line flow velocities shall be determined by Mannings formula.

Flow Velocity ( V ):
2/3 1/2
V = Rh S / n
Rh = Hydraulic radius = 0.079 m
S = Hydraulic slope = 0.005 m/m (assumed)
n = Roughness coefficient of pipe, from Table 2 of SAES-S-030 ( RTR pipe )
= 0.013
V= 0.997 m/sec > 0.90 m/sec (SAFE)
Discharge Capacity ( Q ):
Q= VA
V= 0.997 m/sec
A= 0.077 m²
Q= 0.077 m³/sec
Q= 77.23 L/sec > 63.08 L/sec (SAFE)

Page 8 of 8