Professional Documents
Culture Documents
Inverters and Applications - Requirements of The Final Report
Inverters and Applications - Requirements of The Final Report
I. INTRODUCTION TO INVERTERS
1.3 Methods used to set up command and setpoint for the inverter.
P0700 “Selection of command source” (table 3-2)
P1000 “Selection of setpoint source” (table 3-3)
P0719 “Selection of command/frequency setpoint” (table 3-4)
II. APPLICATIONS
II.1Introduction to a specific inverter (Siemens MicroMaster 420)
2.1.1 Describe the power input and output circuits
Figure 1
L1, L2, L3 are 3 phases source input.
U, V, W are 3 phase output which is connected to induction motor.
The input source can be single phase or 3 phases.
Figure 2
The control terminal includes:
o 3 digital inputs + 1 (via select analog input as digital input)
o 1 digital output
o 1 analog input
o 1 analog output
Figure 3
2.1.2 Functions of BOP
Figure 4
Figure 5
2.1.3 Functions of digital and analogue inputs and outputs
Digital input
Digital output
Analog input
o Defines type of analog input and also enables analog input monitoring.
o Value scaling in V or %
o Defines filter time to smooth ADC time.
o Defines width of deadband on analog input.
o Defines time delay between loss of analog setpoint and appearance of fault
code F0080.
Analog output
o Defines function of the 0 - 20 mA analog output.
o Defines smoothing time [ms] for analog output signal.
o Permit absolute value.
o Defines type of analog output.
o Value scaling in V or %.
II.2Set up command and reference to operate the inverter from BOP
2.2.1 Power and control circuit connection
Connect
BOP to
inverrter
Figure 6
Figure 7
Motor selection:
Figure 8
2.2.2 Set up parameters to control the inverter
Reset parameter to default:
Set parameter P0010=30 to factory reset
Set parameter P0970=1 to reset default parameter.
Motor selection:
Figure 10
2.3.2 Set up parameters to control the inverter
Reset parameter to default:
Set parameter P0010=30 to factory reset
Set parameter P0970=1 to reset default parameter.
Figure 12
Pump selection: 10Kw, 2900rpm, 2 poles
Pressure sensor selection : Siemens QBE9200-P10
Figue 13
Figure 14
2.5.4 Set up parameters to use the PID controller for the application
Set parameter to reset vfd (the same as part 2.3)
Set motor parameter
Set parameter P0307=10kw to set rated power of motor
Figure 16
2.6.2 Program for PLCs control and monitor the inverter
Set parameter for vfd
Set parameter to reset vfd (the same as part 2.3)
Set motor parameter (the same as part 2.3)
Set parameter for vfd to operate from terminal
Set parameter P0700=2 to select command source from
terminal:
Set parameter P1000=2 to selecr frequency setpoint from
analog input
Start
button Set
frequency
Start
Status of
button
motot