Professional Documents
Culture Documents
Data Sheets Dos Cabos
Data Sheets Dos Cabos
Table of content
About Nexans 3
Symbols 4
Underground MV cables 6
Nexans brings energy to life through an extensive range of cables and cabling solutions that deliver increased performance
for our customers worldwide. Nexans’ teams are committed to a partnership approach that supports customers in four main
business areas: Power transmission and distribution (submarine and land), Energy resources (Oil & Gas, Mining and
Renewables), Transportation (Road, Rail, Air, Sea) and Building (Commercial, Residential and Data Centers). Nexans’
strategy is founded on continuous innovation in products, solutions and services, employee development, customer training
and the introduction of safe, low-environmental-impact industrial processes.
In 2013, Nexans became the rst cable player to create a Foundation to introduce sustained initiatives for access to energy
for disadvantaged communities worldwide.
We have an industrial presence in 40 countries and commercial activities worldwide, employing close to 26,000 people and
generating sales in 2015 of 6.2 billion euros.
Nexans is listed on Euronext Paris, compartment A.
Halogen free
Flame retardant
Fire retardant
Lead free
Smoke density
Conductor exibility
Underground MV cables
Single core armoured, XLPE insulated, halogen free, reduced smoke emission, reduced ame propagation (NHLSFR).
Rated voltage 12.7/22 KV (Um=24 kV)
Description
Electric cable with copper conductor, semiconductive conductor screen, XLPE
insulation, semiconductive insulation screen, copper metallic screen on each
core, LSZH bedding, aluminium wires armour (AWA), LSZH outer sheath, black
with white stripe
Application
for energy networks where mechanical stesses are expected. Suitable for
underground installation or in ducts
Note: the cable is suitable for rated voltage 12/20 KV (Um=24 kV) according to
IEC 60502-2
Design
Standards
1. copper conductor
International IEC 60332-1;
2. semiconductive conductor screen IEC 60332-3-24; IEC 60754-2;
3. XLPE insulation IEC 61034
National SANS 1339
4. semiconductive insulation screen
5. semiconductive tape
6. copper tape metallic screen
6. LSZH bedding
7. aluminium wires armour
8. LSZH outer sheath
The 3-cores are with galvanized steel wires armour (SWA) with
designation: CU/XLPE/CTS/LSF/SWA/LSF 12.7/22 KV
Conductor Lead free Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Fire retardant Smoke
exibility Yes Yes (Um) service retardant IEC density
Stranded class 12.7 / 22 (24) kV 90 °C Yes 60332-3-24 Low
2
Technical characteristics
Cross Nom. outer Approx. Max. DC Resist. Cond. Perm. current rating Current rating,
section diam. weight 20°C open air buried
[mm²] [mm] [kg/km] [Ohm/km] [A] [A]
50 32.0 1480 0.387 245 220
70 35.0 1830 0.268 300 270
95 36.0 2130 0.193 360 320
120 37.0 2460 0.153 425 360
150 39.0 2750 0.124 485 410
185 41.0 3160 0.099 550 460
240 43.0 3810 0.075 650 530
300 47.0 4650 0.06 740 600
400 50.0 5630 0.047 850 690
500 53.0 6770 0.036 980 760
630 58.0 8400 0.028 1130 850
Selling information
the cable is available with ame retardant PVC sheath, black with red stripe (FR) or ame retardant, low halogen emission
PVC sheath, black with blue stripe (LHFR)
Conductor Lead free Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Fire retardant Smoke
exibility Yes Yes (Um) service retardant IEC density
Contact
Utilities
Phone: +30 211 120 7710
sales.hellas@nexans.com
Single core armoured, XLPE insulated, halogen free, reduced smoke emission and reduced ame propagation (NHLSFR).
Rated voltage 19/33 KV (Um=36 kV)
Description
Electric cable with copper conductor, semiconductive conductor screen, XLPE
insulation, semiconductive insulation screen, copper metallic screen on each
core, LSZH bedding, aluminium wires armour (AWA), LSZH outer sheath, black
with white stripe
Application
for energy networks where mechanical stesses are expected. Suitable for
underground installation or in ducts
Note: the cable is suitable for rated voltage 18/30 KV (Um=36 kV) according to
IEC 60502-2
Design
Standards
1. copper conductor
International IEC 60332-1;
2. semiconductive conductor screen IEC 60332-3-24; IEC 60754-2;
3. XLPE insulation IEC 61034
National SANS 1339
4. semiconductive insulation screen
5. semiconductive tape
6. copper tape metallic screen
6. LSZH bedding
7. aluminium wires armour
8. LSZH outer sheath
The 3-cores are with galvanized steel wires armour (SWA) with designation: CU/
XLPE/CTS/LSF/SWA/LSF 19/33 KV
Conductor Lead free Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
exibility Yes Yes (Um) service IEC 60332-1 IEC 60332-3-24
Stranded class 2 19 / 33 (36) kV 90 °C
Technical characteristics
Cross Nom. outer Approx. Max. DC Resist. Cond. Perm. current rating Current rating,
section diam. weight 20°C open air buried
[mm²] [mm] [kg/km] [Ohm/km] [A] [A]
50 38.0 1940 0.387 245 220
70 40.0 2220 0.268 300 270
95 41.0 2530 0.193 360 320
120 43.0 2860 0.153 425 360
150 45.0 3330 0.124 485 410
185 47.0 3780 0.099 550 460
240 50.0 4450 0.075 650 530
300 52.0 5170 0.06 740 600
400 56.0 6150 0.047 850 690
500 59.0 7370 0.036 980 760
630 63.0 8990 0.028 1130 850
Selling information
Note: the cable is available with ame retardant PVC sheath, black with red stripe (FR) or ame retardant, reduced halogen
emission sheath, black with blue stripe (LHFR)
Conductor Lead free Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
exibility Yes Yes (Um) service IEC 60332-1 IEC 60332-3-24
Contact
Utilities
Phone: +30 211 120 7710
sales.hellas@nexans.com
Single core armoured, XLPE insulated, halogen free, reduced smoke emission, reduced ame propagation (NHLSFR).
Rated voltage 6.35/11 KV (Um=12kV)
Description
Electric cable with copper conductor, semiconductive conductor screen, XLPE
insulation, semiconductive insulation screen, copper metallic screen on each
core, LSZH bedding, aluminium wires armour (AWA), LSZH outer sheath, black
with white stripe
Application
for energy networks where mechanical stesses are expected. Suitable for
underground installation or in ducts
Note: the cable is suitable for rated voltage 6/10 KV (Um=12 kV) according to IEC
60502-2
Design
Standards
1. copper conductor
International IEC 60332-1;
2. semiconductive conductor screen IEC 60332-3-24; IEC 60754-2;
3. XLPE insulation IEC 61034
National SANS 1339
4. semiconductive insulation screen
5. semiconductive tape
6. copper tape metallic screen
6. LSZH bedding
7. aluminium wires armour
8. LSZH outer sheath
The 3-cores are with galvanized steel wires armour (SWA) with designation:
CU/XLPE/CTS/LSF/SWA/LSF 6.35/11 KV
Conductor Lead free Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Fire retardant Smoke
exibility Yes Yes (Um) service retardant IEC density
Stranded class 6.35 / 11 kV 90 °C Yes 60332-3-24 Low
2
Technical characteristics
Cross Nom. outer Approx. Max. DC Resist. Cond. Perm. current rating Current rating,
section diam. weight 20°C open air buried
[mm²] [mm] [kg/km] [Ohm/km] [A] [A]
50 27.0 1240 0.387 235 220
70 29.0 1450 0.268 285 270
95 30.0 1810 0.193 360 320
120 32.0 2110 0.153 415 360
150 34.0 2440 0.124 470 410
185 36.0 2840 0.099 540 460
240 39.0 3480 0.075 640 530
300 41.0 4110 0.06 740 600
400 45.0 5050 0.047 840 680
500 49.0 6340 0.036 990 750
630 53.0 7920 0.028 1110 830
Selling information
Note: the cable is available with ame retardant PVC sheath, black with red stripe (FR) or ame retardant, reduced halogen
emission PVC sheath, black with blue stripe (LHFR)
Conductor Lead free Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Fire retardant Smoke
exibility Yes Yes (Um) service retardant IEC density
CU/XLPE/CTS/LSF/SWA/LSF 12.7/22 KV WHITE STRIPE
Armoured 3-core XLPE insulated MV, halogen free, reduced smoke emission and reduced ame propagation (NHLSFR)
cable. Rated voltage 12.7/22 KV (Um=24KV)
Description
Electric cable with copper conductors, semiconductive conductor screen, XLPE
insulation, semiconductive insulation screen, copper tape metallic screen of each
core, LSZH bedding, galvanized steel wires armour (SWA) and LSZH ame
retardant outer sheath, black with white stripe.
Application
for energy networks where mechanical stresses are expected. Suitable for
underground installation or in ducts
The cable is suitable for rated voltage 12/20 KV (Um=24 KV) according to IEC
60502-2
Standards
Design
International IEC 60332-1;
1. copper conductor IEC 60332-3-24; IEC 60754-2;
2. semiconductive conductor screen IEC 61034
National SANS 1339
3. XLPE insulation
4. semiconductive insulation screen
5. semiconductive tape
6. copper tape metallic screen
6. LSZH bedding
7. galvanized steel wires armour
8. LSZH outer sheath
Single core xables are with Aluminium wires armour (AWA) with designation: CU/
XLPE/CTS/LSF/AWA/LSF 12.7/22 KV
Conductor Halogen free Lead free Rated Voltage Uo/U Max.conductor temp.in Flame Fire retardant Smoke
exibility Yes Yes (Um) service retardant IEC density
Stranded class 12.7 / 22 (24) kV 90 °C IEC 60332-1 60332-3-24 Low
2
Technical characteristics
Cross Nom. outer Approx. Max. DC Resist. Cond. Perm. current rating Current rating,
section diam. weight 20°C open air buried
[mm²] [mm] [kg/km] [Ohm/km] [A] [A]
25 56.0 4980 0.727 145 140
35 59.0 5520 0.524 180 170
50 61.0 6160 0.387 225 210
70 68.0 7980 0.268 275 255
95 71.0 9100 0.193 330 295
120 74.0 10210 0.153 380 335
150 77.0 11380 0.124 430 375
185 81.0 12920 0.099 490 420
240 87.0 15240 0.075 570 480
300 92.0 17560 0.06 650 530
Selling information
Note: the cable is available with ame retardant sheath, black with red stripe (FR) or with ame retardant, low halogen
sheath, black with blue stripe (LHFR)
Conductor Halogen free Lead free Rated Voltage Uo/U Max.conductor temp.in Flame Fire retardant Smoke
exibility Yes Yes (Um) service retardant IEC density
CU/XLPE/CTS/LSF/SWA/LSF 19/33 KV WHITE STRIPE
Armoured 3-core XLPE insulated MV, halogen free, reduced smoke emission and reduced ame propagation (NHLSFR)
cable. Rated voltage 19/33 KV (Um=36KV)
Description
Electric cable with copper conductors, semiconductive conductor screen, XLPE
insulation, semiconductive insulation screen, copper tape metallic screen of each
core, LSZH bedding, galvanized steel wires armour (SWA) and LSZH outer
sheath, black with white stripe.
Application
for energy networks where mechanical stresses are expected. Suitable for
underground installation or in ducts
The cable is suitable for rated voltage 18/30 KV (Um=36KV) according to IEC
60502-2
Standards
Design
International IEC 60332-1;
1. copper conductor IEC 60332-3-24; IEC 60754-2;
2. semiconductive conductor screen IEC 61034
National SANS 1339
3. XLPE insulation
4. semiconductive insulation screen
5. semiconductive tape
6. copper tape metallic screen
6. LSZH bedding
7. galvanized steel wires armour
8. LSZH outer sheath
Single core xables are with Aluminium wires armour (AWA) with
designation: CU/XLPE/CTS/LSF/AWA/LSF 19/33 KV
Conductor Halogen free Lead free Rated Voltage Uo/U Max.conductor temp.in Flame Fire retardant Smoke
exibility Yes Yes (Um) service retardant IEC density
Stranded class 19 / 33 (36) kV 90 °C IEC 60332-1 60332-3-24 Low
2
Technical characteristics
Cross Nom. outer Approx. Max. DC Resist. Cond. Perm. current rating Current rating,
section diam. weight 20°C open air buried
[mm²] [mm] [kg/km] [Ohm/km] [A] [A]
50 75.0 8640 0.387 225 210
70 79.0 9700 0.268 275 255
95 85.0 11710 0.193 330 295
120 88.0 12980 0.153 380 335
150 90.0 14020 0.124 430 375
185 95.0 15770 0.099 490 420
240 100.0 18190 0.075 570 480
300 107.0 21060 0.06 650 530
Selling information
the cable is available with ame retardant sheath, black with red stripe (FR) or with ame retardant, low halogen sheath,
black with blue stripe (LHFR)
Conductor Halogen free Lead free Rated Voltage Uo/U Max.conductor temp.in Flame Fire retardant Smoke
exibility Yes Yes (Um) service retardant IEC density
CU/XLPE/CTS/LSF/SWA/LSF 6.35/11 KV WHITE STRIPE
Armoured 3-core XLPE insulated MV, halogen free, reduced smoke emission and reduced ame propagation (NHLSFR)
cable. Rated voltage 6.35/11 KV (Um=12KV)
Description
Electric cable with copper conductors, semiconductive conductor screen, XLPE
insulation, semiconductive insulation screen, copper tape metallic screen of each
core, LSZH bedding, galvanized steel wires armour (SWA) and LSZH outer
sheath, black with white stripe.
Application
for energy networks where mechanical stresses are expected. Suitable for
underground installation or in ducts
The cable is suitable for rated voltage 6/10KV according to IEC 60502-2
Design
Standards
1. copper conductor International IEC 60332-1;
2. semiconductive conductor screen IEC 60332-3-24; IEC 60754-2;
IEC 61034
3. XLPE insulation
National SANS 1339
4. semiconductive insulation screen
5. semiconductive tape
6. copper tape metallic screen
6. LSZH bedding
7. galvanized steel wires armour
8. LSZH outer sheath
Single core xables are with Aluminium wires armour (AWA) with designation: CU/
XLPE/CTS/LSF/AWA/LSF 6.35/11KV
Conductor Halogen free Lead free Rated Voltage Uo/U Max.conductor temp.in Flame Fire retardant Smoke
exibility Yes Yes (Um) service retardant IEC density
Stranded class 6.35 / 11 kV 90 °C IEC 60332-1 60332-3-24 Low
2
Technical characteristics
Cross Nom. outer Approx. Max. DC Resist. Cond. Perm. current rating Current rating,
section diam. weight 20°C open air buried
[mm²] [mm] [kg/km] [Ohm/km] [A] [A]
25 46.0 3850 0.727 145 140
35 49.0 4320 0.524 175 170
50 53.0 506 0.387 220 210
70 55.0 5850 0.268 270 255
95 59.0 6990 0.193 330 300
120 63.0 8050 0.153 375 340
150 67.0 9800 0.124 430 380
185 71.0 11230 0.099 490 430
240 77.0 13520 0.075 570 490
300 82.0 15860 0.06 650 540
400 89.0 19310 0.047 740 600
Selling information
Note: the cable is available with ame retardant sheath, black with red stripe (FR) or with ame retardant, low halogen
sheath, black with blue stripe (LHFR)
Conductor Halogen free Lead free Rated Voltage Uo/U Max.conductor temp.in Flame Fire retardant Smoke
exibility Yes Yes (Um) service retardant IEC density
Contact
Utilities
Phone: +30 211 120 7710
sales.hellas@nexans.com
Single core armoured, XLPE insulated, reduced halogen emission and reduced ame propagation (LHFR). Rated voltage
12.7/22 KV (Um=24 kV)
Description
Electric cable with copper conductor, semiconductive conductor screen, XLPE
insulation, semiconductive insulation screen, copper metallic screen on each
core, PVC bedding, aluminium wires armour (AWA), PVC outer sheath, black
with blue stripe
Application
for energy networks where mechanical stesses are expected. Suitable for
underground installation or in ducts
Note: the cable is suitable for rated voltage 12/20 KV (Um=24 kV) according to
IEC 60502-2
Design
Standards
1. copper conductor
International IEC 60332-1;
2. semiconductive conductor screen IEC 60332-3-24
3. XLPE insulation National SANS 1339
4. semiconductive insulation screen
5. semiconductive tape
6. copper tape metallic screen
6. PVC bedding
7. aluminium wires armour
8. PVC outer sheath
The 3-cores are with galvanized steel wires armour (SWA) with designation: CU/
XLPE/CTS/PVC/SWA/PVC 12.7/22 KV
Conductor Lead free Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
exibility Yes No (Um) service IEC 60332-1 IEC 60332-3-24
Stranded class 2 12.7 / 22 (24) kV 90 °C
Technical characteristics
Cross Nom. outer Approx. Max. DC Resist. Cond. Perm. current rating Current rating,
section diam. weight 20°C open air buried
[mm²] [mm] [kg/km] [Ohm/km] [A] [A]
50 32.0 1440 0.387 245 220
70 35.0 1790 0.268 300 270
95 36.0 2090 0.193 360 320
120 37.0 2410 0.153 425 360
150 39.0 2700 0.124 485 410
185 41.0 3110 0.099 550 460
240 43.0 3760 0.075 650 530
300 47.0 4580 0.06 740 600
400 50.0 5550 0.047 850 690
500 53.0 6690 0.036 980 760
630 58.0 8300 0.028 1130 850
Selling information
the cable is available with ame retardant PVC sheath, black with red stripe (FR) or ame retardant, zero halogen, low
smoke emission sheath, black with white stripe (NHLSFR)
Conductor Lead free Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
exibility Yes No (Um) service IEC 60332-1 IEC 60332-3-24
Contact
Utilities
Phone: +30 211 120 7710
sales.hellas@nexans.com
Single core armoured, XLPE insulated, reduced ame propagation (FR). Rated voltage 12.7/22 KV (Um=24 kV)
Description
Electric cable with copper conductor, semiconductive conductor screen, XLPE
insulation, semiconductive insulation screen, copper metallic screen on each
core, PVC bedding, aluminium wires armour (AWA), PVC outer sheath, black
with red stripe
Application
for energy networks where mechanical stesses are expected. Suitable for
underground installation or in ducts
Note: the cable is suitable for rated voltage 12/20 KV (Um=24 kV) according to
IEC 60502-2
Design
Standards
1. copper conductor
International IEC 60332-1;
2. semiconductive conductor screen IEC 60332-3-24
3. XLPE insulation National SANS 1339
4. semiconductive insulation screen
5. semiconductive tape
6. copper tape metallic screen
6. PVC bedding
7. aluminium wires armour
8. PVC outer sheath
The 3-cores are with galvanized steel wires armour (SWA) with designation: CU/
XLPE/CTS/PVC/SWA/PVC 12.7/22 KV
Conductor Lead free Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
exibility Yes No (Um) service IEC 60332-1 IEC 60332-3-24
Stranded class 2 12.7 / 22 (24) kV 90 °C
Technical characteristics
Cross Nom. outer Approx. Max. DC Resist. Cond. Perm. current rating Current rating,
section diam. weight 20°C open air buried
[mm²] [mm] [kg/km] [Ohm/km] [A] [A]
50 32.0 1440 0.387 245 220
70 35.0 1790 0.268 300 270
95 36.0 2090 0.193 360 320
120 37.0 2410 0.153 425 360
150 39.0 2700 0.124 485 410
185 41.0 3110 0.099 550 460
240 43.0 3760 0.075 650 530
300 47.0 4580 0.06 740 600
400 50.0 5550 0.047 850 690
500 53.0 6690 0.036 980 760
630 58.0 8300 0.028 1130 850
Selling information
the cable is available with reduced halogen emission and ame retardant PVC sheath, black with blue stripe (LHFR) or
ame retardant, zero halogen, low smoke emission sheath, black with white stripe (NHLSFR)
Conductor Lead free Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
exibility Yes No (Um) service IEC 60332-1 IEC 60332-3-24
Contact
Utilities
Phone: +30 211 120 7710
sales.hellas@nexans.com
Single core armoured, XLPE insulated, reduced halogen emission and reduced ame propagation (LHFR). Rated voltage
19/33 KV (Um=36 kV)
Description
Electric cable with copper conductor, semiconductive conductor screen, XLPE
insulation, semiconductive insulation screen, copper metallic screen on each
core, PVC bedding, aluminium wires armour (AWA), PVC outer sheath, black
with blue stripe
Application
for energy networks where mechanical stesses are expected. Suitable for
underground installation or in ducts
Note: the cable is suitable for rated voltage 18/30 KV (Um=36 kV) according to
IEC 60502-2
Design
Standards
1. copper conductor
International IEC 60332-1;
2. semiconductive conductor screen IEC 60332-3-24
3. XLPE insulation National SANS 1339
4. semiconductive insulation screen
5. semiconductive tape
6. copper tape metallic screen
6. PVC bedding
7. aluminium wires armour
8. PVC outer sheath
The 3-cores are with galvanized steel wires armour (SWA) with designation: CU/
XLPE/CTS/PVC/SWA/PVC 19/33 KV
Conductor Lead free Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
exibility Yes No (Um) service IEC 60332-1 IEC 60332-3-24
Stranded class 2 19 / 33 (36) kV 90 °C
Technical characteristics
Cross Nom. outer Approx. Max. DC Resist. Cond. Perm. current rating Current rating,
section diam. weight 20°C open air buried
[mm²] [mm] [kg/km] [Ohm/km] [A] [A]
50 38.0 1890 0.387 245 220
70 40.0 2170 0.268 300 270
95 41.0 2470 0.193 360 320
120 43.0 2800 0.153 425 360
150 45.0 3270 0.124 485 410
185 47.0 3710 0.099 550 460
240 50.0 4380 0.075 650 530
300 52.0 5090 0.06 740 600
400 56.0 6060 0.047 850 690
500 59.0 7270 0.036 980 760
630 63.0 8890 0.028 1130 850
Selling information
the cable is available with ame retardant PVC sheath, black with red stripe (FR) or ame retardant, zero halogen, low
smoke emission sheath, black with white stripe (NHLSFR)
Conductor Lead free Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
exibility Yes No (Um) service IEC 60332-1 IEC 60332-3-24
Contact
Utilities
Phone: +30 211 120 7710
sales.hellas@nexans.com
Single core armoured, XLPE insulated, reduced ame propagation (FR). Rated voltage 19/33 KV (Um=36 kV)
Description
Electric cable with copper conductor, semiconductive conductor screen, XLPE
insulation, semiconductive insulation screen, copper metallic screen on each
core, PVC bedding, aluminium wires armour (AWA), PVC outer sheath, black
with red stripe
Application
for energy networks where mechanical stesses are expected. Suitable for
underground installation or in ducts
Note: the cable is suitable for rated voltage 18/30 KV (Um=36 kV) according to
IEC 60502-2
Design
Standards
1. copper conductor
International IEC 60332-1;
2. semiconductive conductor screen IEC 60332-3-24
3. XLPE insulation National SANS 1339
4. semiconductive insulation screen
5. semiconductive tape
6. copper tape metallic screen
6. PVC bedding
7. aluminium wires armour
8. PVC outer sheath
The 3-cores are with galvanized steel wires armour (SWA) with designation: CU/
XLPE/CTS/PVC/SWA/PVC 19/33 KV
Conductor Lead free Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
exibility Yes No (Um) service IEC 60332-1 IEC 60332-3-24
Stranded class 2 19 / 33 (36) kV 90 °C
Technical characteristics
Cross Nom. outer Approx. Max. DC Resist. Cond. Perm. current rating Current rating,
section diam. weight 20°C open air buried
[mm²] [mm] [kg/km] [Ohm/km] [A] [A]
50 38.0 1890 0.387 245 220
70 40.0 2170 0.268 300 270
95 41.0 2470 0.193 360 320
120 43.0 2800 0.153 425 360
150 45.0 3270 0.124 485 410
185 47.0 3710 0.099 550 460
240 50.0 4380 0.075 650 530
300 52.0 5090 0.06 740 600
400 56.0 6060 0.047 850 690
500 59.0 7270 0.036 980 760
630 63.0 8890 0.028 1130 850
Selling information
the cable is available with reduced halogen emission and ame retardant PVC sheath, black with blue stripe (LHFR) or
ame retardant, zero halogen, low smoke emission sheath, black with white stripe (NHLSFR)
Conductor Lead free Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
exibility Yes No (Um) service IEC 60332-1 IEC 60332-3-24
Contact
Utilities
Phone: +30 211 120 7710
sales.hellas@nexans.com
Single core armoured, XLPE insulated, reduced halogen emission, reduced ame propagation (LHFR). Rated voltage
6.35/11 KV (Um=12kV)
Description
Electric cable with copper conductor, semiconductive conductor screen, XLPE
insulation, semiconductive insulation screen, copper metallic screen on each
core, PVC bedding, aluminium wires armour (AWA), PVC outer sheath, black with
blue stripe
Application
for energy networks where mechanical stesses are expected. Suitable for
underground installation or in ducts
Note: the cable is suitable for rated voltage 6/10 KV (Um=12 kV) according to IEC
60502-2
Design
Standards
1. copper conductor
International IEC 60332-1;
2. semiconductive conductor screen IEC 60332-3-24
3. XLPE insulation National SANS 1339
4. semiconductive insulation screen
5. semiconductive tape
6. copper tape metallic screen
6. PVC bedding
7. aluminium wires armour
8. PVC outer sheath
The 3-cores are with galvanized steel wires armour (SWA) with designation: CU/
XLPE/CTS/PVC/AWA/PVC 6.35/11 KV
Conductor Lead free Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
exibility Yes No (Um) service IEC 60332-1 IEC 60332-3-24
Stranded class 2 6.35 / 11 kV 90 °C
Technical characteristics
Cross Nom. outer Approx. Max. DC Resist. Cond. Perm. current rating Current rating,
section diam. weight 20°C open air buried
[mm²] [mm] [kg/km] [Ohm/km] [A] [A]
50 27.0 1210 0.387 235 220
70 29.0 1420 0.268 285 270
95 30.0 1770 0.193 360 320
120 32.0 2070 0.153 415 360
150 34.0 2400 0.124 470 410
185 36.0 2790 0.099 540 460
240 39.0 3430 0.075 640 530
300 41.0 4060 0.06 740 600
400 45.0 4980 0.047 840 680
500 49.0 6270 0.036 990 750
630 53.0 7840 0.028 1110 830
Selling information
the cable is available with ame retardant PVC sheath, black with red stripe (FR) or ame retardant, low smoke, zero
halogen sheath, black with white stripe (NHLSFR)
Conductor Lead free Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
exibility Yes No (Um) service IEC 60332-1 IEC 60332-3-24
Contact
Utilities
Phone: +30 211 120 7710
sales.hellas@nexans.com
Single core armoured, XLPE insulated, reduced ame propagation (FR). Rated voltage 6.35/11 KV (Um=12kV)
Description
Electric cable with copper conductor, semiconductive conductor screen, XLPE
insulation, semiconductive insulation screen, copper metallic screen on each
core, PVC bedding, aluminium wires armour (AWA), PVC outer sheath, black
with red stripe
Application
for energy networks where mechanical stesses are expected. Suitable for
underground installation or in ducts
Note: the cable is suitable for rated voltage 6/10 KV (Um=12 kV) according to IEC
60502-2
Design
Standards
1. copper conductor
International IEC 60332-1;
2. semiconductive conductor screen IEC 60332-3-24
3. XLPE insulation National SANS 1339
4. semiconductive insulation screen
5. semiconductive tape
6. copper tape metallic screen
6. PVC bedding
7. aluminium wires armour
8. PVC outer sheath
The 3-cores are with galvanized steel wires armour (SWA) with designation: CU/
XLPE/CTS/PVC/AWA/PVC 6.35/11 KV
Conductor Lead free Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
exibility Yes No (Um) service IEC 60332-1 IEC 60332-3-24
Stranded class 2 6.35 / 11 kV 90 °C
Technical characteristics
Cross Nom. outer Approx. Max. DC Resist. Cond. Perm. current rating Current rating,
section diam. weight 20°C open air buried
[mm²] [mm] [kg/km] [Ohm/km] [A] [A]
50 27.0 1210 0.387 235 220
70 29.0 1420 0.268 285 270
95 30.0 1770 0.193 360 320
120 32.0 2070 0.153 415 360
150 34.0 2400 0.124 470 410
185 36.0 2790 0.099 540 460
240 39.0 3430 0.075 640 530
300 41.0 4060 0.06 740 600
400 45.0 4980 0.047 840 680
500 49.0 6270 0.036 990 750
630 53.0 7840 0.028 1110 830
Selling information
the cable is available with ame retardant reduced halogen emission PVC sheath, black with blue stripe (LHFR) or ame
retardant, low smoke, zero halogen sheath, black with white stripe (NHLSFR)
Conductor Lead free Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
exibility Yes No (Um) service IEC 60332-1 IEC 60332-3-24
CU/XLPE/CTS/PVC/SWA/PVC 12.7/22KV BLUE STRIPE
Armoured 3-core XLPE insulated MV, reduced halogen emission and reduced ame propagation (LHFR) cable. Rated
voltage 12.7/22 KV (Um=24KV)
Description
Electric cable with copper conductors, semiconductive conductor screen, XLPE
insulation, semiconductive insulation screen, copper tape metallic screen of each
core, PVC bedding, galvanized steel wires armour (SWA) and PVC outer sheath,
black with blue stripe.
Application
for energy networks where mechanical stresses are expected. Suitable for
underground installation or in ducts
The cable is suitable for rated voltage 12/20KV (Um=24 KV) according to IEC
60502-2
Standards
Design
International IEC 60332-1;
1. copper conductor IEC 60332-3-24
2. semiconductive conductor screen National SANS 1339
3. XLPE insulation
4. semiconductive insulation screen
5. semiconductive tape
6. copper tape metallic screen
6. PVC bedding
7. galvanized steel wires armour
8. PVC outer sheath
Single core xables are with Aluminium wires armour (AWA) with designation: CU/
XLPE/CTS/PVC/AWA/PVC 12.7/22 KV
Conductor exibility Lead free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
Stranded class 2 Yes (Um) service IEC 60332-1 IEC 60332-3-24
12.7 / 22 (24) kV 90 °C
Technical characteristics
Cross Nom. outer Approx. Max. DC Resist. Cond. Perm. current rating Current rating,
section diam. weight 20°C open air buried
[mm²] [mm] [kg/km] [Ohm/km] [A] [A]
25 56.0 4890 0.727 145 140
35 59.0 5420 0.524 180 170
50 61.0 6060 0.387 225 210
70 68.0 7860 0.268 275 255
95 71.0 8960 0.193 330 295
120 74.0 10060 0.153 380 335
150 77.0 11220 0.124 430 375
185 81.0 12740 0.099 490 420
240 87.0 15050 0.075 570 480
300 92.0 17340 0.06 650 530
Selling information
the cable is available with ame retardant PVC sheath, black with red stripe (FR) or with ame retardant, low smoke, zero
halogen sheath, black with white stripe (NHLSFR)
Conductor exibility Lead free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
Stranded class 2 Yes (Um) service IEC 60332-1 IEC 60332-3-24
CU/XLPE/CTS/PVC/SWA/PVC 12.7/22KV RED STRIPE
Armoured 3-core XLPE insulated MV, reduced ame propagation (FR) cable. Rated voltage 12.7/22 KV (Um=24KV)
Description
Electric cable with copper conductors, semiconductive conductor screen, XLPE
insulation, semiconductive insulation screen, copper tape metallic screen of each
core, PVC bedding, galvanized steel wires armour (SWA) and PVC outer sheath,
black with red stripe.
Application
for energy networks where mechanical stresses are expected. Suitable for
underground installation or in ducts
The cable is suitable for rated voltage 12/20KV (Um=24 KV) according to IEC
60502-2
Standards
Design
International IEC 60332-1;
1. copper conductor IEC 60332-3-24
2. semiconductive conductor screen National SANS 1339
3. XLPE insulation
4. semiconductive insulation screen
5. semiconductive tape
6. copper tape metallic screen
6. PVC bedding
7. galvanized steel wires armour
8. PVC outer sheath
Single core xables are with Aluminium wires armour (AWA) with designation: CU/
XLPE/CTS/PVC/AWA/PVC 12.7/22 KV
Conductor exibility Lead free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
Stranded class 2 Yes (Um) service IEC 60332-1 IEC 60332-3-24
12.7 / 22 (24) kV 90 °C
Technical characteristics
Cross Nom. outer Approx. Max. DC Resist. Cond. Perm. current rating Current rating,
section diam. weight 20°C open air buried
[mm²] [mm] [kg/km] [Ohm/km] [A] [A]
25 56.0 4890 0.727 145 140
35 59.0 5420 0.524 180 170
50 61.0 6060 0.387 225 210
70 68.0 7860 0.268 275 255
95 71.0 8960 0.193 330 295
120 74.0 10060 0.153 380 335
150 77.0 11220 0.124 430 375
185 81.0 12740 0.099 490 420
240 87.0 15050 0.075 570 480
300 92.0 17340 0.06 650 530
Selling information
the cable is available with ame retardant, reduced halogen emission PVC sheath, black with blue stripe (LHFR) or with
ame retardant, low smoke, zero halogen sheath, black with white stripe (NHLSFR)
Conductor exibility Lead free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
Stranded class 2 Yes (Um) service IEC 60332-1 IEC 60332-3-24
CU/XLPE/CTS/PVC/SWA/PVC 19/33KV BLUE STRIPE
Armoured 3-core XLPE insulated MV, reduced halogen emission and reduced ame propagation (LHFR) cable. Rated
voltage 19/33 KV (Um=36KV)
Description
Electric cable with copper conductors, semiconductive conductor screen, XLPE
insulation, semiconductive insulation screen, copper tape metallic screen of each
core, PVC bedding, galvanized steel wires armour (SWA) and PVC outer sheath,
black with blue stripe.
Application
for energy networks where mechanical stresses are expected. Suitable for
underground installation or in ducts
The cable is suitable for rated voltage 18/30 KV (Um=36 KV) according to IEC
60502-2
Standards
Design
International IEC 60332-1;
1. copper conductor IEC 60332-3-24
2. semiconductive conductor screen National SANS 1339
3. XLPE insulation
4. semiconductive insulation screen
5. semiconductive tape
6. copper tape metallic screen
6. PVC bedding
7. galvanized steel wires armour
8. PVC outer sheath
Single core xables are with Aluminium wires armour (AWA) with designation: CU/
XLPE/CTS/PVC/AWA/PVC 19/33 KV
Conductor exibility Lead free Rated Voltage Uo/U (Um) Max.conductor temp.in Flame retardant
Stranded class 2 Yes 19 / 33 (36) kV service IEC 60322-1 & IEC 60332-3
90 °C Cat.C
Technical characteristics
Cross Nom. outer Approx. Max. DC Resist. Cond. Perm. current rating Current rating,
section diam. weight 20°C open air buried
[mm²] [mm] [kg/km] [Ohm/km] [A] [A]
50 75.0 8490 0.387 225 210
70 79.0 9530 0.268 275 255
95 85.0 11530 0.193 330 295
120 88.0 12780 0.153 380 335
150 90.0 13810 0.124 430 375
185 95.0 15540 0.099 490 420
240 100.0 17940 0.075 570 480
300 107.0 20780 0.06 650 530
Selling information
the cable is available with ame retardant PVC sheath, black with red stripe (FR) or with ame retardant, low smoke, zero
halogen sheath, black with white stripe (NHLSFR)
Conductor exibility Lead free Rated Voltage Uo/U (Um) Max.conductor temp.in Flame retardant
Stranded class 2 Yes 19 / 33 (36) kV service IEC 60322-1 & IEC 60332-3
CU/XLPE/CTS/PVC/SWA/PVC 19/33KV RED STRIPE
Armoured 3-core XLPE insulated MV, reduced ame propagation (FR) cable. Rated voltage 19/33 KV (Um=36KV)
Description
Electric cable with copper conductors, semiconductive conductor screen, XLPE
insulation, semiconductive insulation screen, copper tape metallic screen of each
core, PVC bedding, galvanized steel wires armour (SWA) and PVC outer sheath,
black with red stripe.
Application
for energy networks where mechanical stresses are expected. Suitable for
underground installation or in ducts
The cable is suitable for rated voltage 18/30 KV (Um=36 KV) according to IEC
60502-2
Standards
Design
International IEC 60332-1;
1. copper conductor IEC 60332-3-24
2. semiconductive conductor screen National SANS 1339
3. XLPE insulation
4. semiconductive insulation screen
5. semiconductive tape
6. copper tape metallic screen
6. PVC bedding
7. galvanized steel wires armour
8. PVC outer sheath
Single core xables are with Aluminium wires armour (AWA) with designation: CU/
XLPE/CTS/PVC/AWA/PVC 19/33 KV
Conductor exibility Lead free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
Stranded class 2 Yes (Um) service IEC 60332-1 IEC 60332-3-24
19 / 33 (36) kV 90 °C
Technical characteristics
Cross Nom. outer Approx. Max. DC Resist. Cond. Perm. current rating Current rating,
section diam. weight 20°C open air buried
[mm²] [mm] [kg/km] [Ohm/km] [A] [A]
50 75.0 8490 0.387 225 210
70 79.0 9530 0.268 275 255
95 85.0 11530 0.193 330 295
120 88.0 12780 0.153 380 335
150 90.0 13810 0.124 430 375
185 95.0 15540 0.099 490 420
240 100.0 17940 0.075 570 480
300 107.0 20780 0.06 650 530
Selling information
the cable is available with ame retardant reduced halogen emission PVC sheath, black with blue stripe (LHFR) or with
ame retardant, low smoke, zero halogen sheath, black with white stripe (NHLSFR)
Conductor exibility Lead free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
Stranded class 2 Yes (Um) service IEC 60332-1 IEC 60332-3-24
CU/XLPE/CTS/PVC/SWA/PVC 6.35/11KV BLUE STRIPE
Armoured 3-core XLPE insulated MV, reduced halogen emission and reduced ame propagation (LHFR) cable. Rated
voltage 6.35/11 KV (Um=12KV)
Description
Electric cable with copper conductors, semiconductive conductor screen, XLPE
insulation, semiconductive insulation screen, copper tape metallic screen of each
core, PVC bedding, galvanized steel wires armour (SWA) and PVC outer sheath,
black with blue stripe.
Application
for energy networks where mechanical stresses are expected. Suitable for
underground installation or in ducts
The cable is suitable for rated voltage 6/10KV according to IEC 60502-2
Design
Standards
1. copper conductor International IEC 60332-1;
2. semiconductive conductor screen IEC 60332-3-24
National SANS 1339
3. XLPE insulation
4. semiconductive insulation screen
5. semiconductive tape
6. copper tape metallic screen
6. PVC bedding
7. galvanized steel wires armour
8. PVC outer sheath
Single core xables are with Aluminium wires armour (AWA) with designation: CU/
XLPE/CTS/PVC/AWA/PVC 6.35/11KV
Conductor exibility Lead free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
Stranded class 2 Yes (Um) service IEC 60332-1 IEC 60332-3-24
6.35 / 11 kV 90 °C
Technical characteristics
Cross Nom. outer Approx. Max. DC Resist. Cond. Perm. current rating Current rating,
section diam. weight 20°C open air buried
[mm²] [mm] [kg/km] [Ohm/km] [A] [A]
25 46.0 3780 0.727 145 140
35 49.0 4240 0.524 175 170
50 53.0 4970 0.387 220 210
70 55.0 5770 0.268 270 255
95 59.0 6890 0.193 330 300
120 63.0 7930 0.153 375 340
150 67.0 9670 0.124 430 380
185 71.0 11100 0.099 490 430
240 77.0 13360 0.075 570 490
300 82.0 15680 0.06 650 540
400 89.0 19100 0.047 740 600
Selling information
the cable is available with ame retardant sheath, black with red stripe (FR) or with ame retardant, low smoke, zero
halogen sheath, black with white stripe (NHLSFR)
Conductor exibility Lead free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
Stranded class 2 Yes (Um) service IEC 60332-1 IEC 60332-3-24
CU/XLPE/CTS/PVC/SWA/PVC 6.35/11KV RED STRIPE
Armoured 3-core XLPE insulated MV, reduced ame propagation (FR) cable. Rated voltage 6.35/11 KV (Um=12KV)
Description
Electric cable with copper conductors, semiconductive conductor screen, XLPE
insulation, semiconductive insulation screen, copper tape metallic screen of each
core, PVC bedding, galvanized steel wires armour (SWA) and PVC outer sheath,
black with red stripe.
Application
for energy networks where mechanical stresses are expected. Suitable for
underground installation or in ducts
The cable is suitable for rated voltage 6/10KV according to IEC 60502-2
Design
Standards
1. copper conductor International IEC 60332-1;
2. semiconductive conductor screen IEC 60332-3-24
National SANS 1339
3. XLPE insulation
4. semiconductive insulation screen
5. semiconductive tape
6. copper tape metallic screen
6. PVC bedding
7. galvanized steel wires armour
8. PVC outer sheath
Single core xables are with Aluminium wires armour (AWA) with designation: CU/
XLPE/CTS/PVC/AWA/PVC 6.35/11KV
Conductor exibility Lead free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
Stranded class 2 Yes (Um) service IEC 60332-1 IEC 60332-3-24
6.35 / 11 kV 90 °C
Technical characteristics
Cross Nom. outer Approx. Max. DC Resist. Cond. Perm. current rating Current rating,
section diam. weight 20°C open air buried
[mm²] [mm] [kg/km] [Ohm/km] [A] [A]
25 46.0 3780 0.727 145 140
35 49.0 4240 0.524 175 170
50 53.0 4970 0.387 220 210
70 55.0 5770 0.268 270 255
95 59.0 6890 0.193 330 300
120 63.0 7930 0.153 375 340
150 67.0 9670 0.124 430 380
185 71.0 11100 0.099 490 430
240 77.0 13360 0.075 570 490
300 82.0 15680 0.06 650 540
400 89.0 19100 0.047 740 600
Selling information
the cable is available with ame retardant reduced halogen emission PVC sheath, black with blue stripe (LHFR) or with
ame retardant, low smoke, zero halogen sheath, black with white stripe (NHLSFR)
Conductor exibility Lead free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Fire retardant
Stranded class 2 Yes (Um) service IEC 60332-1 IEC 60332-3-24
BRINGS ENERGY TO LIFE
Distributed by :