TATA CONSULTING ENGINEERS LIMITED SECTION TITLE

TCE.6134A
COVER SHEET SHEET 1 OF 7

SREE RAYALASEEMA ALKALIES & ALLIED CHEMICALS LTD.

STORM WATER DRAINS

SCHEDULE OF STORM WATER DRAINS

TCE.6134A-100-SI-6004

R0 R1 R2 R3 ISSUE
REV NO
INITIALS SIGN INITIALS SIGN INITIALS SIGN INITIALS SIGN

PPD BY KMN

CHK BY SGM R0

APP BY ARK

DATE 30-01-2012
TCE Consulting Engineers Limited SECTION TITLE
TCE.6134A
INDEX SHEET SHEET 2 OF 7

SR NO. DRAWING SHEET NO. REV DATE BY REMARKS


TATA CONSULTING ENGINEERS LIMITED SECTION TITLE
TCE.6134A
REVISION CONTROL SHEET SHEET 3 OF 7

SR NO. DRAWING REVISED REV DATE BY REMARKS


PPD BY: KMN CHD BY: SGM JOB: SREE RAYALASEEMA ALKALIES AND ALLIED APPD BY:SND
DATE: 31-01-2012 DATE: 31-01-2012 JOB NO. 6134A

DRAWING NO. TCE.6134A-100-SI-6004 REV: R0


SUB :SCHEDULE OF STORM WATER DRAINS

DRAIN DRAIN APPROX


STARTING ENDING LENGTH INVERT LEVELS DRAIN Bed
DRAIN NO. POINT POINT (M) TYPE BASE WIDTH (M) REMARKS slope
FROM TO
D1 1 2 113 99.700 99.540 R 0.35 706
D2 3 2 60 99.550 99.300 C 0.35 240
D3 3 4 65 99.550 99.275 R 0.35 236
D4 5 4 80 99.700 99.625 R 0.35 1067
D7 7 6 65 99.600 99.425 R 0.35 371
D8 7 8 60 99.600 99.425 R 0.35 343
D16 7 8 60 99.700 99.500 R 0.35 300
D17 7 8 60 99.700 99.500 R 0.35 300
D11 10 9 65 99.700 99.500 R 0.35 325
D12 10 11 55 99.700 99.500 R 0.35 275
D5 2 8 32 99.300 99.250 R 0.50 640
D9 8 11 14 99.250 99.200 R 0.50 280
D13 11 12 75 99.200 99.000 R 0.50 375
D6 4 6 58 99.275 99.225 R 0.50 1160
D10 6 9 35.3 99.225 99.150 R 0.50 471
D14 9 13 64 99.150 99.050 R 0.60 640
D15 13 12 96 99.050 98.750 R 0.60 320
H1 2 2' 8 99.300 99.290 R ---
H2 4 4' 8 99.275 99.265 R ---
H3 7 7' 8 99.425 99.415 R ---
H4 8 8' 8 99.250 99.240 R ---
H5 6 6' 8 99.225 99.215 R ---
H6 11 11' 8 99.200 99.190 R ---
H7 9 9' 8 99.150 99.140 R ---
PPD BY: KMN CHD BY: SGM JOB: SREE RAYALASEEMA ALKALIES AND ALLIED APPD BY:SND
DATE: 31-01-2012 DATE: 31-01-2012 JOB NO. 6134A

DRAWING NO. TCE.6134A-100-SI-6004 REV: R0


SUB :SCHEDULE OF STORM WATER DRAINS

DRAIN DRAIN APPROX


STARTING ENDING LENGTH INVERT LEVELS DRAIN Bed
DRAIN NO. POINT POINT (M) TYPE BASE WIDTH (M) REMARKS slope
FROM TO
PPD BY: KMN CHD BY: SGM JOB: SREE RAYALASEEMA ALKALIES AND ALLIED APPD BY:SND
DATE: 31-01-2012 DATE: 31-01-2012 JOB NO. 6134A

DRAWING NO. TCE.6134A-100-SI-6004 REV: R0


SUB :SCHEDULE OF STORM WATER DRAINS

DRAIN DRAIN APPROX


STARTING ENDING LENGTH INVERT LEVELS DRAIN Bed
DRAIN NO. POINT POINT (M) TYPE BASE WIDTH (M) REMARKS slope
FROM TO
PPD BY: KMN CHD BY: SGM JOB: SREE RAYALASEEMA ALKALIES AND ALLIED APPD BY:SND
DATE: 31-01-2012 DATE: 31-01-2012 JOB NO. 6134A

DRAWING NO. TCE.6134A-100-SI-6004 REV: R0


SUB :SCHEDULE OF STORM WATER DRAINS

DRAIN DRAIN APPROX


STARTING ENDING LENGTH INVERT LEVELS DRAIN Bed
DRAIN NO. POINT POINT (M) TYPE BASE WIDTH (M) REMARKS slope
FROM TO

C= RC PIPE CULVERT
LEGEND: R= RECTANGULAR DRAIN
RC = RC DRAIN
All revisions have been marked with shaded color
*For layout details of refer drawing no. TCE.6059A-100-SI-6003
MS COVER shall be of ms grating cover as per standard details.
This cover shalll be povided over the open drains at the road crossing .
Storm water Drainage-Asian paints limited
Notes:
1) Mannings Formula is used to calculate the velocity & discharge in the drains with mannings co-efficeint as GRADE LEVEL 1= 100
Ref Table 3.4 Pg 47 CPHEEO Manual on Sewerage (2nd Ed., 1993) n= 0.015 GRADE LEVEL 2= 100
2) Drain Numbers & nodes numbers are marked on the drain layout. 662.5
3) Rainfall design intensity for respective region (mm/hr) = 100
... Rainfall design intensity (m/s) = 2.778E-05

Discharge Calculations

DRAIN PARTICULARS Road/Paved area DRAIN DESIGN PARTICULARS SIZE CHECK


(Runoff Discharge from
Coefficient,K2=0.9) Immediate Total Discharge in
Immediate Predecessor the drain
Predecessor Drain drains (Dq m3/s)
Drain Start End Length A2 Q2 No (Dq=Q1+Q2+Q3+Q Drain Dia. Of No. of Total Depth Water Depth Side Perimeter Area Hydraulic Bed Level Bed Level Bed Fall Bed Slope Manning's Adequate(Q>Dq)/
(Q7= Dqx+Dqy+ 5+Q5+Q6+Q7) Drain
Velocity
….) m3/s) Capacity
No. Node Node L (m) (Q2=A2*K2) Width humpe pipes available at start Slopes of Drain mean depth @ Start @End F S=F/L Coefficient V=1/n*(A/P)^(2/3)*S Q=A*V Inadequate(Q<Dq) Drain No
^(1/2) m/s
(m3/s)
m2 m3/s B (m) pipe D (m) d (m) m:1 P(m) A (m2) A/P (m) (m) (m) (m) n
D1 1 2 113 1771 0.0443 - 0.0000 0.0443 0.35 0.300 0.25 0 0.85 0.088 0.10 99.700 99.540 0.160 706 0.015 0.55 0.048 Adequate D1
Humepipe D2 3 2 60 5800 0.1450 - 0.0000 0.1450 0.35 0.450 0.40 0 1.15 0.140 0.12 99.550 99.300 0.250 240 0.015 1.06 0.148 Adequate D2
D3 3 4 65 5800 0.1450 - 0.0000 0.1450 0.35 0.450 0.40 0 1.15 0.140 0.12 99.550 99.275 0.275 236 0.015 1.06 0.149 Adequate D3
D4 5 4 80 1500 0.0375 - 0.0000 0.0375 0.35 0.300 0.25 0 0.85 0.088 0.10 99.700 99.625 0.075 1067 0.015 0.45 0.039 Adequate D4
D7 7 6 65 3780 0.0945 - 0.0000 0.0945 0.35 0.400 0.35 0 1.05 0.123 0.12 99.600 99.425 0.175 371 0.015 0.83 0.101 Adequate D7
D8 7 8 60 3690 0.0923 - 0.0000 0.0923 0.35 0.400 0.35 0 1.05 0.123 0.12 99.600 99.425 0.175 343 0.015 0.86 0.105 Adequate D8
D16 7 8 60 2330 0.0583 - 0.0000 0.0583 0.35 0.300 0.25 0 0.85 0.088 0.10 99.700 99.500 0.200 300 0.015 0.84 0.074 Adequate D16
D17 7 8 60 1995 0.0499 - 0.0000 0.0499 0.35 0.300 0.25 0 0.85 0.088 0.10 99.700 99.500 0.200 300 0.015 0.84 0.074 Adequate D17
D11 10 9 65 2225 0.0556 - 0.0000 0.0556 0.35 0.300 0.25 0 0.85 0.088 0.10 99.700 99.500 0.200 325 0.015 0.81 0.071 Adequate D11
D12 10 11 55 1500 0.0375 - 0.0000 0.0375 0.35 0.300 0.30 0 0.95 0.105 0.11 99.700 99.500 0.200 275 0.015 0.93 0.097 Adequate D12
D5 2 8 32 1000 0.0250 D1, D2 0.1893 0.2143 0.50 0.700 0.65 0 1.8 0.325 0.18 99.300 99.250 0.050 640 0.015 0.84 0.273 Adequate D5
D9 8 11 14 300 0.0075 D5, D8,D17 0.3564 0.3639 0.50 0.750 0.70 0 1.9 0.350 0.18 99.250 99.200 0.050 280 0.015 1.29 0.451 Adequate D9
D13 11 12 75 480 0.0120 D12,D9 0.4014 0.4134 0.50 0.800 0.75 0 2 0.375 0.19 99.200 99.000 0.200 375 0.015 1.13 0.423 Adequate D13
D6 4 6 58 460 0.0115 D3, D4 0.1825 0.1940 0.50 0.725 0.67 0 1.85 0.337 0.18 99.275 99.225 0.050 1160 0.015 0.63 0.212 Adequate D6
D10 6 9 35.3 290 0.0073 D6, D7, D16 0.3468 0.3540 0.50 0.775 0.73 0 1.95 0.363 0.19 99.225 99.150 0.075 471 0.015 1.00 0.363 Adequate D10
D14 9 13 64 520 0.0130 D10,D11 0.4096 0.4226 0.60 0.850 0.80 0 2.2 0.480 0.22 99.150 99.050 0.100 640 0.015 0.95 0.458 Adequate D14
D15 13 12 96 610 0.0153 D14 0.4226 0.4379 0.60 0.950 0.90 0 2.4 0.540 0.23 99.050 98.750 0.300 320 0.015 1.38 0.744 Adequate D15
Humepipe H1 2 2' 8 0 0.0000 D2, D1 0.1893 0.1893 --- 0.40 2.00 0.700 ------ 0 0.837758 0.168 0.20 99.300 99.290 0.010 800 0.015 0.81 0.270 Adequate H1
H2 4 4' 8 0 0.0000 D3, D4 0.1825 0.1825 --- 0.40 2.00 0.725 ------ 0 0.837758 0.168 0.20 99.275 99.265 0.010 800 0.015 0.81 0.270 Adequate H2
H3 7 7' 8 0 0.0000 - 0.0500 0.0500 --- 0.15 2.00 0.575 ------ 0 0.314159 0.024 0.08 99.425 99.415 0.010 800 0.015 0.42 0.020 Inadequate H3
H4 8 8' 8 0 0.0000 D5, D8 0.3065 0.3065 --- 0.40 3.00 0.750 ------ 0 0.837758 0.168 0.20 99.250 99.240 0.010 800 0.015 0.81 0.405 Adequate H4
H5 6 6' 8 0 0.0000 D7, D6 0.2885 0.2885 --- 0.40 3.00 0.775 ------ 0 0.837758 0.168 0.20 99.225 99.215 0.010 800 0.015 0.81 0.405 Adequate H5
H6 11 11' 8 0 0.0000 D9 0.3639 0.3639 --- 0.40 3.00 0.800 ------ 0 0.837758 0.168 0.20 99.200 99.190 0.010 800 0.015 0.81 0.405 Adequate H6
H7 9 9' 8 0 0.0000 D10 0.3540 0.3540 --- 0.40 3.00 0.850 ------ 0 0.837758 0.168 0.20 99.150 99.140 0.010 800 0.015 0.81 0.405 Adequate H7

Humepipe

Humepipe

Page 8 of 14
Storm water Drainage-Asian paints limited
Notes:
1) Mannings Formula is used to calculate the velocity & discharge in the drains with mannings co-efficeint as GRADE LEVEL 1= 100
Ref Table 3.4 Pg 47 CPHEEO Manual on Sewerage (2nd Ed., 1993) n= 0.015 GRADE LEVEL 2= 100
2) Drain Numbers & nodes numbers are marked on the drain layout. 662.5
3) Rainfall design intensity for respective region (mm/hr) = 100
... Rainfall design intensity (m/s) = 2.778E-05

Discharge Calculations

DRAIN PARTICULARS Road/Paved area DRAIN DESIGN PARTICULARS SIZE CHECK


(Runoff Discharge from
Coefficient,K2=0.9) Immediate Total Discharge in
Immediate Predecessor the drain
Predecessor Drain drains (Dq m3/s)
Drain Start End Length A2 Q2 No (Dq=Q1+Q2+Q3+Q Drain Dia. Of No. of Total Depth Water Depth Side Perimeter Area Hydraulic Bed Level Bed Level Bed Fall Bed Slope Manning's Adequate(Q>Dq)/
(Q7= Dqx+Dqy+ 5+Q5+Q6+Q7) Drain
Velocity
….) m3/s) Capacity
No. Node Node L (m) (Q2=A2*K2) Width humpe pipes available at start Slopes of Drain mean depth @ Start @End F S=F/L Coefficient V=1/n*(A/P)^(2/3)*S Q=A*V Inadequate(Q<Dq) Drain No
^(1/2) m/s
(m3/s)
m2 m3/s B (m) pipe D (m) d (m) m:1 P(m) A (m2) A/P (m) (m) (m) (m) n

Humepipe

Humepipe

Humepipe

Humepipe

Humepipe

Humepipe

Humepipe

Humepipe

Page 9 of 14
Storm water Drainage-Asian paints limited
Notes:
1) Mannings Formula is used to calculate the velocity & discharge in the drains with mannings co-efficeint as GRADE LEVEL 1= 100
Ref Table 3.4 Pg 47 CPHEEO Manual on Sewerage (2nd Ed., 1993) n= 0.015 GRADE LEVEL 2= 100
2) Drain Numbers & nodes numbers are marked on the drain layout. 662.5
3) Rainfall design intensity for respective region (mm/hr) = 100
... Rainfall design intensity (m/s) = 2.778E-05

Discharge Calculations

DRAIN PARTICULARS Road/Paved area DRAIN DESIGN PARTICULARS SIZE CHECK


(Runoff Discharge from
Coefficient,K2=0.9) Immediate Total Discharge in
Immediate Predecessor the drain
Predecessor Drain drains (Dq m3/s)
Drain Start End Length A2 Q2 No (Dq=Q1+Q2+Q3+Q Drain Dia. Of No. of Total Depth Water Depth Side Perimeter Area Hydraulic Bed Level Bed Level Bed Fall Bed Slope Manning's Adequate(Q>Dq)/
(Q7= Dqx+Dqy+ 5+Q5+Q6+Q7) Drain
Velocity
….) m3/s) Capacity
No. Node Node L (m) (Q2=A2*K2) Width humpe pipes available at start Slopes of Drain mean depth @ Start @End F S=F/L Coefficient V=1/n*(A/P)^(2/3)*S Q=A*V Inadequate(Q<Dq) Drain No
^(1/2) m/s
(m3/s)
m2 m3/s B (m) pipe D (m) d (m) m:1 P(m) A (m2) A/P (m) (m) (m) (m) n

Humepipe

Humepipe

Humepipe

Humepipe

Humepipe

Humepipe

Humepipe

Humepipe

Humepipe

Humepipe

Humepipe

Humepipe

Page 10 of 14
Storm water Drainage-Asian paints limited
Notes:
1) Mannings Formula is used to calculate the velocity & discharge in the drains with mannings co-efficeint as GRADE LEVEL 1= 100
Ref Table 3.4 Pg 47 CPHEEO Manual on Sewerage (2nd Ed., 1993) n= 0.015 GRADE LEVEL 2= 100
2) Drain Numbers & nodes numbers are marked on the drain layout. 662.5
3) Rainfall design intensity for respective region (mm/hr) = 100
... Rainfall design intensity (m/s) = 2.778E-05

Discharge Calculations

DRAIN PARTICULARS Road/Paved area DRAIN DESIGN PARTICULARS SIZE CHECK


(Runoff Discharge from
Coefficient,K2=0.9) Immediate Total Discharge in
Immediate Predecessor the drain
Predecessor Drain drains (Dq m3/s)
Drain Start End Length A2 Q2 No (Dq=Q1+Q2+Q3+Q Drain Dia. Of No. of Total Depth Water Depth Side Perimeter Area Hydraulic Bed Level Bed Level Bed Fall Bed Slope Manning's Adequate(Q>Dq)/
(Q7= Dqx+Dqy+ 5+Q5+Q6+Q7) Drain
Velocity
….) m3/s) Capacity
No. Node Node L (m) (Q2=A2*K2) Width humpe pipes available at start Slopes of Drain mean depth @ Start @End F S=F/L Coefficient V=1/n*(A/P)^(2/3)*S Q=A*V Inadequate(Q<Dq) Drain No
^(1/2) m/s
(m3/s)
m2 m3/s B (m) pipe D (m) d (m) m:1 P(m) A (m2) A/P (m) (m) (m) (m) n
Humepipe

Humepipe

Humepipe

Humepipe

Humepipe

Humepipe

Page 11 of 14
Table 3.4 Pg 47 CPHEEO Manual on Sewerage (2nd Ed., 1993)