Professional Documents
Culture Documents
Installation and Operating Manual For Transformer
Installation and Operating Manual For Transformer
for Transformer
Unrestricted
Table of Contents
Table of Contents
Overview of Revisions
Publisher Information
Chapter 6 Commissioning
Chapter 7 Operation
Chapter 12 Drawings
Chapter 13 Photographs
Overview of Revisions
Rev. Chapter/Page(s) Description of changes Date
0 First edition 2022-11
Publisher Information
Publisher and Service Information
Siemens Transformer (Wuhan) Co., Ltd
Energy Sector
Power Transmission Division
Transformers
No.1 Jingyang Avenue
Yangluo Economic Development Zone
Wuhan, 430415
P.R.China
Customer Support Center:
Phone: +86 27 89669866
Fax: +86 27 89669927
email: cs.stwh.cn@siemens.com
The goods have been stored, handled, or installed according to these instructions.
Operating and maintenance was done by the Customer under the supervision of the
Customer’s senior staff following Siemens´ operating instructions and complete
operating manuals are kept by the Customer and are available to Siemens during the
applicable warranty period.
Warranty claims may only be asserted if the Customer can prove that there is regular
inspection and service.
No responsibility of Siemens under warranty shall arise from consequences of
alterations and repairs by the Customer or third parties. This does, however, not apply
for repairs carried out by the Customer or third parties upon the request or with the
consent of Siemens and following the instruction and/or under the supervision of
Siemens.
No responsibility of Siemens under warranty shall arise from consequences of use of
components and parts which are not provided by Siemens.
A defect or deficiency has occurred for which Siemens is responsible due to not proper
performance or not proper fulfillment of its obligations under the contract.
The warranty obligations of Siemens do not apply to normal wear and tear. Therefore
in cases of warranty claims, ageing shall be given due consideration.
Subsequently the Customer shall do all of the inspection and service work in the intervals
stated and shall replace all the components and parts before they have reached their expected
lifetime.
Defects and deficiencies which result from service errors, exceeding the inspection and service
periods, operating errors, failure to replace the components and parts which have reached
their expected lifetime, or not observing the operating regulations shall not justify any
warranty claims.
In case of warranty claims, documentary evidence for the inspection or service work shall be
sent without delay to Siemens including the date and duly signed. Siemens shall also be
notified without delay of any defects or deficiencies, which could lead to a not proper
performance.
The inspection or service work has to be done by technical personnel, who is trained and
authorized for it. You may find detailed information on doing the inspection or service work
in the various documents in the operating and installation instruction for transformer. With
larger and more complicated sealing, assembly or service work and load interrupter switch
inspection, we recommend that you request mechanics from Siemens, who are especially
trained for this.
1 Order Data
Customer:
Peru ENEL Dolly
Station/Plant: Peru ENEL Dolly
2 Technical Data
TV - 10 1333.0
2.19 Temperatures
Ambient temperature = max.40.0 °C, min. 0 °C
ONAF:
Top oil temperature rise = 48.8 K
winding temperature rise = HV / LV / TV = 49.5 / 49.3 / 47.0 K
Winding temperature rise in copper determined from the rise in resistance
= HV / LV = 15.1 / 14.9 / 16.0 K
ONAN:
Top oil temperature rise = 49.3 K
winding temperature rise = HV / LV / TV = 51.4 / 50.9 / 47.9 K
Winding temperature rise in copper determined from the rise in resistance
= HV / LV = 13.0 / 12.5 / 13.5 K
3.1 Safety
3.1.1 General
Statutory health, safety and environmental provisions and internally applicable healthy, safety
and environment protection provisions of the transformer/reactor operator must be complied
with and are merely amended by these provisions.
This chapter contains basic notes to be observed for transport, set-up, assembly, oil filling,
commissioning, operation and maintenance. These provisions raise no claim to considering
all details or offering a solution for all events.
For safety notes for the individual components and their handling, see the respective chapters.
Non-observance of these operating instructions and improper work during transport, set-up,
assembly, oil filling, commissioning, operation and maintenance may endanger interference-
free operation of the transformer/reactor or other equipment and lead to serious personal,
property and/or environmental damage and the loss of any damages claims.
Qualified personnel are persons trained for transport, set-up, assembly, oil filling,
commissioning, operation and maintenance of the transformer/reactor and the connected
tasks and familiar with the resulting risks.
Personal injury:
DANGER
DANGER! designates directly pending danger. If it is not avoided, death or serious injury
will be the consequence.
WARNING
WARNING! designates possibly pending danger. If it is not avoided, death or serious injury
may be the consequence.
CAUTION
CAUTION! designates possibly pending danger. If it is not avoided, light or minor injury
may be the consequence.
Product/Machine/Plant Damage:
ATTENTION
ATTENTION! designates a potentially harmful situation. If it is not avoided, the system or
something in its environment may be damaged.
General notes:
NOTE
General notes (no personal injury or product/machine/plant damage)
3.1.3 Transport
Only the designated transport facilities must be used for transport (lifting, pulling, turning) or
to set down the transformer/reactor.
Designated transport facilities can be found in the binding dimension drawing or the
operating instructions of the transformer/reactor.
The center of gravity of the transformer/reactor or attachment part must be verified before
lifting or moving it.
The oil filling procedure must be performed according to the indications and notes in these
operating provisions.
The transformer/reactor with the assigned and delivered equipment must only be inspected,
operated and serviced as follows:
According to the information and notes in these operating provisions (maintenance
according to the detailed information on recommended intervals).
Work processes must only be performed by qualified, trained and experienced personnel.
Note that power transformers are deemed passive equipment without irradiation danger
pursuant to the relevant EMC provisions.
CAUTION
Observe that some media may be hot (let them cool off).
1. Power down
2. Secure against reactivation
3. Verify that the equipment is powered down
4. Ground and short-circuit
5. Cover or cordon off any adjacent live parts
DANGER
The transformer was filled with gas for transport. Therefore, observe that the tank is
subject to an overpressure of approx. 0.3 bar when opening flanges or hand holes
If the tank interior is to be accessed, remove the gas by evacuation and replace it with
dried breathing air if the tank is filled with gas (e.g. nitrogen).
Internal inspection must only be performed in the presence of Siemens service staff or a
person authorized by Siemens.
In case of internal inspection, ensure that the air in the tank has an oxygen share of
> 20 %.
Harmlessness of the breathing air must be verified by appropriate measurements before
entering the tank.
Always observe the safety directives for work in containers.
Welding and soldering work with open fire and generation of electrical sparks by testing and
switching procedures in oil-filled or partially oil-filled or oily transformer tanks, conservator,
cable terminal boxes, therefore require special safety measures like filling with nitrogen or
application of vacuum, etc. Specialists of Siemens are to be requested for such work or precise
instructions are to be requested.
3.2.1 General
All possible and imaginable provisions must be taken to prevent environmental damage
pursuant to the nationally applicable laws.
3.2.2 Disposal
Disposal of the entire transformer/reactor or its parts by the operator commits the operator to
disposing of the parts/materials according to the national environmental laws.
The following sections list the most frequent components of the transformer/reactor that
require special provisions for disposal.
See operating instructions for bushings in chapter 9 "Technical Documentation of the Heavy
Part and Accessories".
For disposal notes, see the safety data-sheet of the desiccant beads (see chapter 3.2.3).
4.1 General
The profile and weight limitations or the customer's request determine the mode of transport
for the transformer.
The different structural parts, like bushings, pipe lines, cooling devices, conservator, etc. are
marked and disassembled according to the transport conditions (see dimension drawing,
shipping parts list/packing list). The openings exposed by this are tightly closed with transport
lids.
NOTE
Transport lids are part of the scope of delivery. Unless other provisions apply expressly,
they are to be stored carefully.
For transport dimensions and detail weights and information on lifting bolts, pulling eyes and
lifting points, see the dimension drawing or loading plan.
We recommend using at least one shock recorder, depending on transport duration, for all
transport types described in the following.
ATTENTION
Ensure that all insulation parts are completely covered in oil to prevent moisturizing or
destruction of the insulation parts. The tank space freed by this must be filled with dry
gas.
ATTENTION
For specific parameters for vacuum, time and moisture, contact the manufacturer's plant.
Fill the transformer/reactor with dried gas for both transport types.
The dry air/nitrogen fill provides dry atmosphere in the transformer tank during transport and
assembly and thus maintains the electrical characteristics of insulation.
The dry air/nitrogen fill and overpressure prevent moist air from entering the active part. This
overpressure must be verified in the different transport interfaces and indicated to the
manufacturer plant in a timely manner.
Moisture indicator
The moisture indicator function is based on a chemical color change that occurs when a
certain moisture is exceeded.
If the color of moisture indicator "A" is lighter than comparison field "B", the moisture content
is > 8 %. In this case, contact the manufacturer plant for further measures.
Desiccant beads
Desiccant beads (e.g. silica gel) have the function of absorbing and binding any occurring
moisture in the tank.
If moisture is absorbed, the color of the desiccant beads changes according to the colors
indicated in the material safety data sheet (see chapter 3.2.3).
The silica gel pack has the scripture “Attention Desiccant Box inside” in the marked position.
The equipment has at least one high-pressure dry air/nitrogen bottle connected to the tank.
NOTE
The number of bottles depends on the volume to be filled and the duration of transport.
The dry air/nitrogen bottles are attached to the tank with screw terminals (to be removed
before commissioning).
Every bottle is equipped with a high-pressure controller.
If there are two bottles, a 3-directional adapter is used for connecting the bottles and the tank.
NOTE
Dry air / nitrogen are automatically supplied to the tank if the overpressure in the tank
drops below 0.1 bar. An overpressure valve opens when the overpressure in the tank
exceeds 0.55 bar.
ATTENTION
No parts of the dry air/nitrogen equipment must be removed, and the settings at the
high-pressure controllers must not be changed.
Ensure that no insulation oil enters the high-pressure controller.
Procedure:
1. Close valves at all bottles
2. Close dry air/nitrogen inlet valve at the transformer tank
3. Disconnect hose from the bottle to be replaced
4. Replace bottle
5. Connect hose to new bottle
6. Open valves at the bottles (the high-pressure gauge should now display approx. 150 bar,
the low-pressure gauge 0.35 bar)
7. Open the dry air / nitrogen inlet valve at the transformer tank
1 Low-pressure gauge
2 High-pressure gauge
3 3-directional adapter
4 Inlet valve
5 Tank
6 High-pressure controller
7 Dry air / nitrogen bottles
Fig. 4-2 Dry air / nitrogen equipment for one or two bottles
Observe that the transformer/reactor must be lifted and put down evenly horizontally.
If the transformer is put down on rails or supports, proceed according to the dimension
drawing or contact the manufacturer's plant.
2. Height tolerance
Permissible height deviations (TH) between the different points apply in the loaded state. The
distances indicated refer to the center-to-center spacing between the wheels.
3. Wheel arrangement 1
Rail 1 Rail 2
• = reference points
Fig. 4-3 Wheel arrangement 1
4. Wheel arrangement 2
Rail 1 Rail 2 Rail 3 Rail 4
• = reference points
Fig. 4-4 Wheel arrangement 2
1 Block foundation
2 Tank bottom outside contour of transformer
3 Foundation rail (total tolerance of rails to each other ± 2 mm)
4 Outside contour of separate positioned cooling system (total tolerance rail to foundation of cooling
system ± 4 mm)
5 Un-stiffed tank bottom
6 Stiffed tank bottom
Fig. 4-6 Arrangements on flat foundation with rails
The rail facility displayed (Fig. 4-6 and Fig. 4-7) is suitable for transformers with flat tank base
plates or cross-braced base plates. Two foundation rails are sufficient for base plates which
are ≤ 1500 mm wide. The total tolerance between rails is ± 2 mm. The tolerance between rails
and the cooling system foundation is ± 4 mm.
facility) with ±4 mm to the transformer standing area must be complied with. This may be
achieved, e.g., with grouting concrete.
1 Transformer
2 Cooling system
3 Adequate balance material for transformer arrangement: e.g. grouting concrete
4 Block foundation
Fig. 4-8 Arrangements on flat foundation without rails
3. Variant foundations
The requirements for the foundation as described in chapter 4.4.3, items 1 and 2, are valid
NOTE
The balance materials required to achieve the tolerances, e.g. shims, are not included in
the transformer manufacturer's delivery.
The maximum permissible inclination must be coordinated with the manufacturer's plant in
advance.
We recommend using shock recorders to monitor the maximum permissible accelerations.
Road transport
At larger inclinations and less available space, we recommend using an SPMT (Self Propelled
Module Transporter).
When the center of gravity is located high, a special low-loader must be used to ensure secure
stance during the drive.
Train transport
When transporting the transformer/reactor with a train, ensure that the respective carriage is
attached close to the tractor unit if possible to keep the impact frequency as low as possible
during the ride.
Ship transport
The transformer must be placed in the middle area of the ship to prevent large accelerations
at strong waves.
ATTENTION
The barrels must not be put down hard on the folding edges or tossed off of higher
transport platforms even if foot mats are used.
The barrels must be loaded with the intended devices, e.g. forklift with barrel gripper.
moisture. Inform the manufacturer's plant immediately for it to recommend or initiate further
measures.
The maximum shock recorder values depend on the specific design of the transformer.
vertical horizontal (transversal axis) horizontal (longitudinal axis)
max. 3 g max. 3 g max. 3 g
Tab. 4-1 Max. shock recorder values
After inspection at the destination site, the values recorded by the shock recorder must be
assessed and indicated to the manufacturer's plant, and the shock recorder/s are to be
returned to the manufacturer's plant.
Depending on the weather conditions and solar irradiation, special assessment of the
measuring results may be required. The following chart (Fig. 4-9) shows the acceptable range
of the moisture ratio.
This diagram is applicable for pressures between 0 bar and 0.35 bar.
ATTENTION
If the active part was heated before dew point measurement, the measurement will show
less beneficial values than the actual dew point, because the active part temperature is
higher than the ambient temperature.
If the values indicated are too high, contact the manufacturer.
target value of 300 MΩ, as well as (in coordination with the customer), before long-term
storage of the transformer/reactor.
DANGER
The transformer was filled with gas for transport. Therefore, observe that the tank is
subject to an overpressure of approx. 0.3 bar when opening flanges or hand holes
If the tank interior is to be accessed, remove the gas by evacuation and replace it with
dried breathing air if the tank is filled with gas (e.g. nitrogen).
Internal inspection must only be performed in the presence of Siemens service staff or a
person authorized by Siemens.
In case of internal inspection, ensure that the air in the tank has an oxygen share of
> 20 %.
Harmlessness of the breathing air must be verified by appropriate measurements before
entering the tank.
Always observe the safety directives for work in containers.
If the transformer is opened empty for inspection, the opening times must be limited to a
minimum. During this time, the tank always has to have an overpressure (blowing in dry air).
For the maximum opening duration for the respective transformer, contact the
manufacturer's plant.
2. The area to be opened (max. 1 hand- or manhole) must be secured against entrance of
contamination, moisture or foreign objects.
3. If the moisture ratio in the active part is too high, keep the transformer/reactor filled with
dry air (dew point <-50 °C) for 24 h. Then perform dew point measurement (see chapter
4.6.2.3).
5. Any tools used inside the tank must be attached to a secured rope before commencing
work.
10. After internal inspection of the transformer, verify the sealing condition.
ATTENTION
Until it is filled with oil, the transformer always has to be subject to overpressure, which
must be regularly verified and recorded.
CAUTION
The transformer core always has to be earthed during assembly and operation.
4.8 Storage
Siemens Energy is a trademark Iicensed Date, Ref. 4–16
by Siemens AG.
Document No.:170801
Serial No.:170801
4 Transport, Arrival Inspection and Storage
Siemens Energy Transformers
Transformers/reactors that are not taken into operation immediately must be stored according
to one of the following conditions.
NOTE
Start of storage is the time after completion of the arrival inspection.
WARNING
The transformer, bushings and steel frames for the cooling system must be earthed at
the intended earthing connections permanently and professionally.
A pressure vacuum indicator must be installed in a place that can be easily viewed from the
ground.
The gas pressure in the transformer/reactor and bottle should be inspected and recorded every
day for the first five days. This should preferably be done at the same time of the day.
After this period, the frequency of recordings can be reduced to once per week if no obvious
leakages occur.
Measures Inspection
period
Sight inspection of the transformer and attachment parts for damage weekly
Corrosion protection inspection monthly
Oil analysis (recommendation, operator's own responsibility) as required
Checking for oil leakage weekly
Cleaning the transformer and its components (e.g. ventilator, cooler) (operator's own as required
responsibility)
Inspection of the dehydrating breather (oil sump and desiccant) weekly
Tab. 4-2 Measures for temporary storage < 3 months
pressure vacuum indicator must be installed in a place that can be easily viewed from the
ground.
This procedure requires filling with new filters and new oil with a breakdown voltage > 60 kV
(IEC 60422) and a humidity < 10 ppm (IEC 60422).
Repeated evacuation is not required if the dew point is in the acceptance range of the humidity
ratio diagram (Fig. 4-9) and the oil is drained and treated again before actual commissioning.
For oil filling, see the instructions in chapter 5.3.
The desiccant used for the transport must be removed before evacuation/oil filling.
Measures Inspection
period
Sight inspection of the transformer and attachment parts for damage weekly
Control cabinet function Ventilator function (if attached) monthly
Corrosion protection inspection annually
Oil analysis (recommendation, operator's own responsibility) annually
Checking for oil leakage monthly
Cleaning the transformer and its components (e.g. ventilator, cooler) (operator's own as required
responsibility)
Inspection of the dehydrating breather (oil sump and desiccant) monthly
Inspection of the automatic pressure controller 1 with recording of pressure in the storage every two
bottles and transformer weeks
Tab. 4-3 Measures for temporary storage 3-18 months
1 When attaching the automatic pressure controller for long-term storage, install a pressure gauge with
an electrical contact device that emits a warning when the fill gas pressure in the tank drops below 30
mbar or when the bottle pressure reaches < 15 bar.
Siemens Energy is a trademark Iicensed Date, Ref. 4–19
by Siemens AG.
Document No.:170801
Serial No.:170801
4 Transport, Arrival Inspection and Storage
Siemens Energy Transformers
Measures Inspection
period
Regular oil level inspection at the conservator monthly
Regular replacement of the silica gel fillings at the dehydrating breather as required
Control cabinet function Ventilator function (if attached) monthly
Regular pump run monthly
Switching through the tap changer / de-energized tap changer according to the tap changer according to
manufacturer's indications with insulation oil only manufacturer
Corrosion protection must be verified regularly and repaired if required annually
Regular oil samples for verification of the operational condition of stored transformers must annually
be taken
Checking for oil leakage monthly
The transformer and its components (e.g. ventilator, cooler) should be cleaned according to as required
degree of contamination at the operator's own responsibility.
Tab. 4-4 Measures for long-term storage > 18 months
installed to one of the two cooling blocks. For more instructions, see operating instructions of
the manufacturer (set-up of cooling system for long-term storage).
Measures Inspection
period
Oil level inspection at the conservator monthly
Replacement of desiccant in the dehydrating breather as required
Function of the control cabinet2 monthly
Ventilator function (if attached)2 monthly
Pump run2 monthly
Switching through the tap changer2 / de-energized tap changer according to the tap according to
changer manufacturer's indications with insulation oil only manufacturer
Corrosion protection inspection annually
Oil analysis (recommendation, operator's own responsibility) annually
Checking for oil leakage monthly
Cleaning the transformer and its components (e.g. ventilator, cooler) (operator's own as required
responsibility)
Tab. 4-5 Storage of oil-filled transformers/reactors
installed to one of the two cooling blocks. For more instructions, see operating instructions of
the manufacturer (set-up of cooling system for long-term storage).
Pursuant to Tab. 4-7 the heavy part and accessories are categorized in storage categories, and
the recommended inspection during storage (see Tab. 4-8) should be observed.
Categories Description
A Common interior storage: Protection from moisture and dust
B Storage outside: Protection from rain
C Storage outside: no protection required
Tab. 4-6 Storage categories
Parts Category
Heavy part C
Valves B
Bushing A
Bushing pots A
Conservator A
Pipelines and brackets A
Fans A
Oil pumps A
Seals A
Small accessories (protection devices, etc.) A
Tab. 4-7 Recommended storage categories
Bushings
Bushings must be transported in boxes. The lower part is welded into plastic and desiccant is
included.
Before storage, the lower part must be inspected for signs of moisture. If the plastic packaging
is damaged, it must be replaced with the desiccant. It is recommended that the condenser
bushings be stored in a dry and clean inner room, if possible in the original transport boxes.
The front end of oil-filled bushings must be stored lifted at least at an angle of 20°.
ATTENTION
If bushings are horizontally stored, they must be placed vertically at least for 12/ 24 hours
before rated voltage/test voltage may be applied. At horizontal storage of one year or
more, vertical setup for one week is prescribed.
Small accessories
Boxes with seals, bushing connections, tape, paint material, sealing paste, protective devices,
etc. must be stored in a dry and clean inner room.
Cooling facility
Water cooling facilities must be protected from frost or completely emptied on the water side,
see cooling system description.
Fans
Fans must be stored in a dry, clean, dust- and vibration-protected place.
Pumps
Proper assembly of the connection plug and proper fit of the blind plugs must be verified for
pumps. The pump motors must be lifted from the floor and stored protected from weather.
Storage outside is possible for a duration of up to 3 months, then interior storage is required.
If the pumps are filled with oil for long-term storage, no periodic pump operation is required.
The local and national safety provisions must be strictly observed (see chapter 3).
The unit was dried under high vacuum and heat in the plant and oil-impregnated under high
vacuum in a dedicated tank. The high quality of dielectric and mechanic hardness must be
retained during assembly on the plant.
The same standards and specifications as in the manufacturer's plant apply for evacuation and
oil filling of the transformer/reactor. When the transformer/reactor is taken into operation, it
must be in the same condition as during the acceptance test in the manufacturer's plant.
Before evacuation and oil filling, ensure that all inspections at arrival/storage were performed
properly.
NOTE
If an active part must be inspected, this inspection should take place right before
evacuation and oil filling if possible.
DANGER
The transformer was filled with gas for transport. Therefore, observe that the tank is
subject to an overpressure of approx. 0.3 bar when opening flanges or hand holes
If the tank interior is to be accessed, remove the gas by evacuation and replace it with
dried breathing air if the tank is filled with gas (e.g. nitrogen).
Internal inspection must only be performed in the presence of Siemens service staff or a
person authorized by Siemens.
In case of internal inspection, ensure that the air in the tank has an oxygen share of
> 20 %.
Harmlessness of the breathing air must be verified by appropriate measurements before
entering the tank.
Always observe the safety directives for work in containers.
ATTENTION
To optimize the installation and commissioning times, choose the assembly order of the
components so that the opening time of the transformer/reactor is as low as possible.
DANGER
The tank, steel frame for the separate conservator (if present) and separate cooling
system (if present) must be grounded permanently and professionally at the intended
ground connections (see chapter 4.7 Earthing Diagrams for Transformers/Reactor Coils).
This sealing system is based on the use of rubber seals in furrows. It consists of an oil- and
heat-resistant synthetic rubber NBR (or equal).
1 Seal in groove
Fig. 5-3 Turrets Fig. 5-4 Assembly and inspection openings
These sealing systems are based on the use of rubber seals in grooves. They consist of an oil-
and heat-resistant synthetic rubber NBR (or equal).
The seals can have a rectangular or round profile.
1 Flange
2 Blind flange
3 Flat seal (asbestos-free)
Fig. 5-5 Pipeline connections
1 Indices
Fig. 5-6 Identification of associated flanges
The flanges must be clean and oil-free (remove oil with solvent).
Sealing paste must be brushed on the flange side of each seal. The contacting sealing surfaces
are not treated.
Flange connections must be tightened evenly and crosswise. Any tension from this must be
removed by installing or removing seals.
If only one seal is used, only one side must be treated with sealing paste.
If any additional seals are inserted, sealing paste may be used to fasten the seals; however,
the compression force of the two outer seals will usually be sufficient to hold the additional
seal in place.
The following information on tightening torques are aligned with the materials used and thus
may deviate from the above information.
NOTE
Generally, the tolerances for torques may be -0 % / +10 %.
The torque indications for the threads only apply when lubricants like oil and grease for
screw material of stainless steel (A2-70 or higher quality) or steel (8.8 or higher quality)
are used.
1 Nut
2 Half-nut
Fig. 5-10 Radiators and shut-off flaps
Electrical connections
The values below apply for electrical connections at penetrations.
Thread Tightening torque in Nm
M10 (3/8") 20
M12 (1/2") 40
M16 (5/8") 80
Tab. 5-4 Tightening torques for electrical connections
NOTE
The tolerances for tightening torques here are –0 % / +20 %.
Siemens Energy is a trademark Iicensed 5–9
by Siemens AG.
Document No.:170801
Serial No.:170801
5 Assembly, evacuation and oil filling
Siemens Energy Transformers
5.2 Assembly
5.2.4 Radiators
Radiator frame
The transformer is equipped with two separate radiator banks. Height differences between
individual foundations can be balanced out with boards. Install all supports, brackets and
braces. Install the top and lower distributor lines. All parts must be dry and free of
condensation.
ATTENTION
Loosen gland seal before opening or closing of the shut-off flap, then attach it again. In
the closed condition, the triangle at the flap points towards the flange marker; in the
open condition, the triangle tip is on the radiator side.
Overview
Detailed view
1 Vent
2 Oil drain
3 Brackets for fans
4 Gland seal
Fig. 5-13 Radiators (Overview and detailed view)
5.2.5 Fans
Assemble fans according to dimension drawing and assembly instructions of the fan
manufacturer (see chapter 9).
NOTE
Also see assembly instructions of the cooler manufacturer in chapter 9.
A Buchholz relay or several shut-off devices are installed in the connection line between the
cover and conservator.
ATTENTION
The shut-off devices must be open under all circumstances during operation.
When installing the Buchholz relay, observe that the arrow at the relay casing points
towards the conservator.
The conservator is usually equipped with a breathing pocket to prevent the oil from taking up
oxygen and to thus protect it from oxidation and moisture intake.
To protect the insulation oil from contamination by oil sludge from the conservator, the oil
line protrudes approx. 50 mm into it. The connection line for the air dehumidifier (breather)
ends right below the highest point of the conservator space.
1 Screw
2 Washer
3 Seal
4 Basic flange
Fig. 5-14 Pressure relief valve
1 Angle gear
2 Bracket
3 Shaft
4 Switch connection
5 Screw connection
6 Joint
7 Motor drive
Fig. 5-15 Motor drive assembly
Suggested dimensions of the vacuum pumps and vacuum lines according to tank volume:
Tank volume Pump performance Vacuum line
< 50 m3 (6600 gal) 250 m3/h (1100 gal/min) 40mm (1 1/2”)
> 50 m3 (13200 gal) 500 m3/h (2200 gal/min) 50mm (2”)
> 100 m3 (26400 gal) 1000 m3/h (4400 gal/min) > 80mm (3”)
Tab. 5-5 Evacuation equipment
NOTE
The air infiltration protection prevents infiltration of moist air into the transformer tank
or insulation parts in case of failure or standstill of the vacuum pump. The evacuation
process can be assessed as not interrupted when the remaining pressure in the
transformer tank has not risen above 1 mbar. If the prescribed residual pressure is
reached again, at least 12 hours of evacuation time must follow.
Suggested dimensions of the oil treatment pumps and oil lines according to tank volume:
Tank volume Performance of the oil treatment facility Oil line
< 50 m3 (6600 gal) 3000 l/h 25mm (1")
> 50 m3 (13200 gal) 5000 l/h 40mm (1 1/2 ")
> 100 m3 (26400 gal) 10000 l/h 50mm (2 ")
Tab. 5-6 Oil filling equipment
Recommendation:
The oil treatment facility should reach the following threshold values in a single run:
Breakdown voltage ≥ 60 kV
Oil gas content ≤ 3 Vol.-%
Oil temperature ≥ 40 °C
The oil quality must meet the Siemens standards and customer specification.
Siemens Energy is a trademark Iicensed 5–18
by Siemens AG.
Document No.:170801
Serial No.:170801
5 Assembly, evacuation and oil filling
Siemens Energy Transformers
New transformers must be filled with the oil delivered by the plant. If oil must be refilled, oil
of equal quality must be used (see oil product datasheet - mixing possibilities).
Refilling new oil on operating oil is possible if the operating oil has not aged too much. Aged
oils have a higher dissolving capacity than new oil. Therefore, it is recommended to coordinate
refilling with the manufacturer's plant.
ATTENTION
Synthetic insulation liquids (silicon and ester liquids) must not be mixed with mineral-
oil-based insulation oils.
1 liter of the insulation medium each is needed for dielectrical-chemical oil examination and
for gas-chromatography oil examination.
NOTE
The sample containers should be clean 1-liter aluminum bottles with gas-tight plastic
screw closure and seal so that no air is taken in as the sample cools. Suitable sample
bottles are available from the manufacturer's plant.
ATTENTION
Only take the oil sample with glass bottles when the sample temperature at sampling is
guaranteed to be greater or the same as the storage or transport temperature.
Otherwise, coordinate with the examination lab.
Samples for gas analyses must be taken without interruption in the overflow procedure
only to prevent contact between the insulation medium and the atmosphere as much as
possible. In every case, notice the temperature inside the oil jet in the test protocol.
Sampling points
for gas analysis examinations: usually tank "top"
for other examinations: usually tank "bottom"
2. Open the oil sampling valve and let about two to three liters of oil (from the outlet pipeline)
flow into the oil collection vessel.
3. Push the hose into the oil sample bottle to the ground. First fill the bottle slowly from the
bottom, then let oil flow strongly until oil at a volume of 2 to 3 times the bottle content has
flowed over into an oil collection container.
4. Last, reduce the oil flow again and draw the bottle from the hose downwards with the oil
sampling valve still open. Close the bottle at once when it was drawn from the hose.
Procedure when taking oil samples from the conservator of the diverter switch
1. Open the drain slide valve at the conservator diverter switch.
2. Work steps 1-6 from “Taking oil from the oil sampling valve”.
NOTE
Oil samples must only be taken with a suitable sampling valve in case of direct oil filling
to the transformer tank from oil barrels.
1 Transformer tank
2 Oil sampling valve
3 Hose
4 Oil sample bottle
5 Oil collection vessel
Fig. 5-17 Oil sampling with oil sample bottle and oil collection vessel
Regular inspections are required to ensure continuous readiness for operation of a transformer
over an extended period.
We recommend taking oil samples every 5 operating years or before any larger revisions and
to examine them for the following characteristics:
Highest voltage for Minimum evacuation Waiting Waiting time (cable terminal box)
operating equipment time time
> 60 h under oil and < 60 h under oil or
(Um)
<= 48 h outside of oil > 48 h outside of oil
x ≤ 72,5 kV 12 h 16 h 12 h 16
72,5 kV < x ≤ 123 kV 12 h 24 h 16 h 36
123 kV < x ≤ 245 kV 24 h 48 h 24 h 48
245 kV < x ≤ 550 kV 48 h 60 h 24 h 48
x > 550 kV 60 h 72 h 24 h 48
Tab. 5-8 Reference times for evacuation and waiting times
NOTE
The filling speed must be set so that the vacuum in the transformer tank is retained. If
the vacuum deteriorates by more than 1 mbar, the time is counted again from the
beginning.
yes no
Min. evacuation time: see table „guidance values“, at residual pressure ≤ 1 mbar
(after the necessary vacuum has been reached in the transformer tank)
Oil preparation via external tank before oil filling or via transformer tank
until following oil quality is reached:
Min. breakdown voltage > 60 kV (IEC 60422)
Manufacturer’s recommendation for the specific transformer :
Notes
Dehydrating breather
After oil filling is completed, the breathers have to be installed and the slide valves set to their
operating position.
yes no
Fill pressure inside the transformer tank at arrival at destination: between 30 and 300 mbar ;
Bottle pressure: ≥ 15 bar
yes no
no
Min. evacuation time: see table „guidance values“, at residual pressure ≤ 1 mbar
(after the necessary vacuum has been reached in the transformer tank)
Oil preparation via external tank before oil filling or via transformer tank
until following oil quality is reached:
Min. breakdown voltage > 60 kV (IEC 60422)
Manufacturer’s recommendation for the specific transformer :
Fig. 5-19 Flow chart for oil filling of partly filled transformers under full vacuum
yes no
yes
All winding parts up to the upper edge of the coil clamping plate
,
also all paper insulated leads are always immersed in oil.
yes no
Gas contentof oil inside the transformer Flow chart: Evacuation and oil filling of partly filled
no
≤ 10 Vol.-% transformers under full vacuum
yes
no no
Cable box seperated from transformer tank in Cable box seperated from transformer tank in
vacuum.tight arrangement. drip-proof arrangement.
yes
no
Min. evacuation time: see table „guidance values“, at residual pressure ≤ 1 mbar
(after the necessary vacuum has been reached in the transformer tank)
Oil preparation via external tank before oil filling or via transformer tank
until following oil quality is reached:
Min. breakdown voltage > 60 kV (IEC 60422)
Manufacturer’s recommendation for the specific transformer :
Maintain vacuum for 2 hours. Break vacuum with N 2 or dry air. Vent transformer and cable box.
The insulation parts of the cable box have been> 60 Std. under oil and ≤ 48 Std. out of oil
Fig. 5-21 Flow chart for oil filling of cable terminal boxes
Notes
Oil-filled cable terminal boxes are chambers attached to the transformer, in which the
electrical connection between the winding end lead and the cable to the switchboard or
overhead line is made. The oil in the cable terminal box is separated from the oil in the
transformer tank. This separation may either use drip-proof or vacuum-tight seals.
If it is drip-proof, all cable terminal boxes have to be connected to the transformer tank
before the vacuum is applied.
If it is vacuum-tight, the cable terminal boxes have to be treated like the transformer.
6 Commissioning
The relevant technical rules and accident prevention regulations (chapter 3) must be complied
with for commissioning, operation and maintenance.
6.1 General
It is recommended that transformers be commissioned by specialists in the manufacturer's
plant.
If commissioning is performed by external staff, proceed pursuant to the test reports for
electrical tests, mechanical tests and visual inspections (chapter 4.6). The individual measures
must be recorded on the commissioning protocol and submitted to the manufacturer's plant
in writing directly after completion of commissioning.
NOTE
No warranty can be assumed by Siemens for any damage resulting from improper
commissioning (pursuant to test reports).
DANGER
To avoid personal injury, observe the indicated warning notes before any operation of
the load control switch.
NOTE
For the specific tests for the individual transformer/reactor, see the commissioning
protocol (see chapter 15).
Inspection of bushings
Undamaged and clean, spark path set
Loss factor measurement
Output factor measurement
Monitoring system
Other Inspections
Earthings (shielding, star points, delta coil, etc.)
Earthing system (tank, cooling system, pipeline, bushings, conservator)
Venting (transformer, bushing, tap changer)
Checking for leakage (transformer, cooling system)
Putting locking elements into operation (transformer with bushing, cooling system)
Inspection of breather filling (transformer, tap changer, terminal boxes, cooling system)
Paint (corrosion protection)
Heating (control cabinet, motor drive)
Other Inspections
Wiring (secondary wiring terminals)
Signage
Minimum clearance to adjacent parts
Star point (type of operation)
Search for loose parts at the transformer/cooler
ATTENTION
If the minimum/maximum values for the insulation medium are not complied with, the
insulation medium must be treated again (in the cycle).
To receive reference values for later comparison purposes, we recommend performing a gas
chromatography oil analysis before switching on the transformer.
6.3 Commissioning
When all inspections have been performed satisfactorily, the transformer can be taken into
operation after a certain downtime after the last oil manipulation.
ATTENTION
Temperatures and the Buchholz relay must be monitored and inspected for vibration or
leakage during the one-hour idle operation. If the results are satisfactory, the transformer
can be loaded.
ATTENTION
If the completely assembled transformer is not connected to the mains right after
completion of the inspections for commissioning, the control cabinet and motor drive
cabinet (if applicable) must be powered to warrant function of the thermostat-controlled
heating. This measure is required to prevent too low temperatures or condensation in
the cabinet, which may lead to damage to the devices.
7 Operation
The type designation is carried out using letters (A) and figures (N) in blocks according to the
following schema. Within blocks A and N places which are not required can be omitted starting
from the right-hand side. For the purposes of data processing the data has to be entered with
after-point alignment i.e. places which have been omitted remain empty.
3 Also applies to a starting transformer with air gaps in the iron core
4 See DIN VDE 0530 part 1,annex A
Siemens Energy is a trademark Iicensed 7–3
by Siemens AG.
Document No.:170801
Serial No.:170801
7 Operation
Siemens Energy Transformers
Key to the 5th and 6th character position (code number): Size (kVA rating for transformers,
kVAr rating for reactors)
5th & 6th Type rating ST 5th & 6th Type rating ST
character position (kVA, kVAr) character position (kVA, kVAr)
35 3 71 12500
37 5 72 16000
40 10 73 20000
42 16 74 25000
43 20 75 31500
45 30 76 40000
47 50 77 50000
49 75 78 63000
50 100 79 80000
51 125 80 100000
52 160 81 125000
53 200 82 160000
54 250 83 200000
55 315 84 250000
56 400 85 315000
57 500 86 400000
58 630 87 500000
59 800 88 630000
60 1000 89 800000
61 1250 90 1000000
62 1600 91 1250000
63 2000 92 1600000
64 2500 93 2000000
65 3150 94 2500000
66 4000 95 3150000
67 5000 96 4000000
68 6300 97 5000000
69 8000 98 6300000
70 10000 99 8000000
Tab. 7-9 Examples for type rating ST
The unit rating ST which is decisive for the reference numbers of the size is the rated power
of a corresponding two-winding transformer (LT) or a reactor; this rated power is in relation
to 50Hz and continuous operation(DB).The influences of core induction and winding
temperature rise on the size are only taken into account when 0.87<KS<1.18; otherwise KS 1
is used.
The basis for the determination of the unit rating ST given in section 2 forms the apparent
power of all the windings SW which are used for transmitting power in the case of the cooling
method laid down at the last place of the type designation. Stabilizing windings and auxiliary
windings in the sense of DIN EN 60076-1 are not taken into account here.
When using an existing model the reference numbers of the size which are laid down in
tabular form in the model are to be taken over into the type designation.
If no reference is given to an existing model then the predefinitions in ST formula of
transformers and reactors apply along with the following identification symbols which
are given.
Reactors
The unit rating ST of a single-phase reactor (50Hz, DB, BN, WZUL) which has the equivalent
weight of the core-and-winding assembly (GFE + GCU) is to be used.
Key to the 7th and 8th character position (code number): Highest voltage for Equipment
Um (kV)
7th & 8th Highest voltage for 7th & 8th Highest voltage for
character position equipment UM character position equipment UM
30 ≤ 1.10 47 52
36 3.6 49 72.5
39 7.2 51 123
41 12 52 145
42 17.5 54 245
44 24 56 420
46 36 57 525
Tab. 7-1 Key to the 7th and 8th character position (code number): Highest voltage for Equipment Um (kV)
9 A tenth of the value of the number formed from both of the reference numbers is roughly the common
logarithm of the unit rating in VA (in case of transformers) or VAr (in case of reactors)
10 Standard number series R10 to DIN 323
Transformers to be connected in parallel must have the same phase displacement clock-hour
number irrespective of the connection. (A Yd5 transformer can for instance be paralleled with
Dy5.) Interconnect the terminals bearing identical markings.
Exception:
Transformers of clock-hour number 11 can be operated in parallel with transformers having
clock-hour number 5 provided that they are connected as shown in Tab. 7-2. The percent
impedance Uz of transformers to be connected in parallel should not deviate by more than 10
% from the mean value of the rated percent impedances of all units to be paralleled. No
additional measures such as the insertion of reactors to serve as additional inductances are
required in cases where the total load is such that the transformers having the lower
impedance voltage are never loaded with more than their rated currents. The smaller
transformer should preferably have the higher impedance voltage.
Transformers to be operated in parallel should preferably be equal in their rated voltage ratio
to within ± 0.5 %, or else be provided with voltage variability (on-load or off-circuit tap
changers). When power transformers with on-load tap changers are operated in parallel, the
requirement for uniform impedance voltage and voltage ratio cannot be met in all tap changer
positions. This problem can be solved by making the relative settings of the tap changers
dependent upon the load distribution. In spite of unequal impedance voltages and equal
voltage ratios of the transformers, the unit having the higher impedance voltage can, by
appropriate reduction of its voltage ratio, be caused to carry a load corresponding to its rated
power.
Dangerously high circulating currents may occur when auto-transformers with on-load tap
changers are operated in parallel, particularly when using the tappings of low impedance
voltage. These currents must be suppressed by series-connected current-limiting reactors or
by parallel-connection by current dividers. Parallel operation of transformers whose rated
outputs are in a ratio of over 2:1 is not advisable owing to the possibly higher deviations of
the UX / UR ratios of the individual transformers. Larger deviations from the voltage ratio,
impedance voltage and rated power ratio are permissible in cases where the transformers will
not be operated directly parallel on one busbar, but where parallel operation in a system is
involved.
The oil temperature during an overload period is not a measure for the temperature reached
by the winding.
U Voltage applied
f Frequency
Un Rated voltage of input side
fn Rated frequency
E Excitation
Fig. 7-3 Permissible short-time over-excitation of transformers
rising thermal stress. Induction B is directly proportional to the applied voltage U and inversely
proportional to the frequency f:
U
B
f
In accordance with DIN VDE 0532 Part 1, the transformer is able to continuously carry its rated
currents under the following conditions:
At 105 % rated voltage and rated frequency or at applied rated voltage and a frequency
deviating by 2.5% from the rated frequency.
Fig. 7-3 shows the permissible duration of over-excitation of large transformers as a function
of the ratio
U fn
E
Un f
For frequency fluctuations not exceeding + 2.5 % it can safely be assumed that f ≈ fn.
In case of permanent over-excitation between 105 % and 110 %, the load current must be
reduced as shown in Fig. 7-4. Permanent over-excitation of 110 % is only permissible in the
no-load state of the transformer.
As far as unit transformers are concerned, this means that the generating sets must not be
started and stopped with the voltage regulator switched on and enabled. In manually
11Temperature rises exceeding 150 K may be agreed for certain insulants between the manufacturer
and the user.
Siemens Energy is a trademark Iicensed 7–14
by Siemens AG.
Document No.:170801
Serial No.:170801
7 Operation
Siemens Energy Transformers
controlled plants the shunt-field rheostat setting should be reduced during shutdown. The
field-discharge switch can remain closed.
If transformers are coupled direct with generators and the load is suddenly thrown off, these
transformers can with-stand 1.4 times the rated voltage at their generator-side connections
for five seconds.
Under conditions of sudden load shedding, generator transformers with ratings up to 40 MVA
and station service transformers connected to generators must be able to withstand 1.3 times
rated voltage for five minute.
Fig. 7-4 Permissible long-time over-excitation between 100 % and 110 % (according to DIN VDE 0532, Part 1)
7.5 Troubleshooting
The following interferences are a general overview of possible interferences that may occur
at the transformer/reactor.
For detailed information, see the respective operating and assembly instructions for these
devices and components (see chapter 9).
Very strong oil flow due Take gas sample at Buchholz relay and
to inner light arcs. analyze gas
Very strong gas formation Take gas sample at Buchholz relay and
due to internal defect analyze gas
(short-circuit in the core
& coil assembly)
Protective relay for Triggered Internal defect in the load Inspection of the load transfer switch
diverter switch transfer switch
Triggered incorrectly Inspect protective relay
Pressure relief valve Triggered Max. overpressure Inspection of the load transfer switch
for diverter switch exceeded or serious
internal defect Inspection of the shut-off elements
Closed shut-off element
towards the conservator
Pressure relief valve Triggered Closed shut-off element Inspection of the pipelines and shut-off
for tank in the conservator elements
Breather with Desiccant beads Glass cylinder Replacement of glass cylinder and seals
desiccant beads discolor leaking/cracked
If monitoring and maintenance work is performed by external staff, proceed pursuant to the
check list "maintenance work and electrical tests" (see chapter 15). The individual measures
must be recorded on the checklist and submitted to the manufacturer's plant in writing directly
after completion of the monitoring and maintenance work.
NOTE
No warranty can be assumed by Siemens for any damage resulting from improper
monitoring and maintenance.
For the specific monitoring and maintenance work for the individual transformers, see the
check list "maintenance work and electrical tests" (see chapter 15).
NOTE
For the specific monitoring and maintenance work for the individual transformers, see
the check list "maintenance work and electrical tests" (see chapter 15).
When glass tubes are used as oil level indicator, clean them as follows:
Turn valve handle into shut-off position at the lower part. After turning out
of the oil drain screw, empty isolation liquid from the oil level tube into a
clean vessel. Remove upper part of the conservator, remove oil-level tube
and clean with new transformer oil. Do not use any aggressive cleaning
agents. Reassemble in reverse order.
Current transformer box Integrated current transformers either must be connected to measuring
instruments or short-circuited, e.g. in the transport condition. Every
converter secondary coil must be earthed at a clamp pursuant to the circuit
diagram. The preferred clamp for earthing is the clamp "k".
Monitoring devices The inspection glasses and contact rooms must be inspected for tightness
and freedom from corrosion. Vents and water drains must be cleaned.
Function tests
Dehydrating breather To prevent moisture from entering the conservator, the desiccant must be
replaced already if the layer of discolored active material at the top only
has the following thickness:
- approx. 3 cm for dehumidifier A DIN 42 567;
- approx. 7 cm for dehumidifier A DIN 42 562;
For this, see maintenance item "Conservator with pipelines (outside)".
Buchholz relay Mechanical operation of the warning and trigger float is to be performed
according to the Buchholz relay device description. The warning function
(gas alarm) is inspected effectively with the circuit breakers inserted.
When the warning triggers, the warning signal has to be received by the
control center, the circuit breakers must not trip. When testing the trigger
function, the circuit breakers must trigger or the generator separation must
become effective.
The respective messages in the control center must be verified.
The directional arrow points from the transformer/reactor to the
conservator.
Connection space
The test and connection space must be inspected for condensate
formation. The venting openings of the connection space must be
permeable.
Test facility
The Buchholz relay is equipped with a test device that permits separate
functional control of the two contact systems from the outside even if the
relay casing is completely filled with oil.
Switch-off
Slowly turn test button to the stop in the direction of the arrow, then
slowly press it.
The switch-off test is performed effectively with the circuit breakers
inserted. When turning back the test button into the initial position
(against the direction of the arrow), the mechanism is unlocked again. The
respective messages in the control center must be verified.
Contacts
The protective gas tubes must be checked for correct position, correct
triggering and good contact transfer. We recommend replacing the contact
tubes after 10 years of operation.
See document "Two-float Buchholz relay“.
Diverter switch protection The load control switch protection in newer transformers are load control
switch protection relays, while older transformers have a blast protection.
The functional test of the protective devices must be performed according
to the device description. Performance switch tripping, generator de-
excitation and signaling in the control center when the load control switch
protection devices trigger must be inspected.
When the load control switch protection devices trigger, the transformer
must be switched off. Switching to warning is not permissible.
Coil temperature
The converter circuits of the thermal images must be closed and must not
be opened when the transformer is under voltage. The jumpers at the
converter must be open.
Function test
Adjustment of the dial thermometer is performed by heating the
disassembled temperature sensor in the oil or water bath. Temperature is
controlled by a rod thermometer.
Resistance thermometer The resistance thermometer must be checked for function. The impedance
at 0 °C = 100 Ω.
Resistance increase = 0.38 Ω/K. Resistance of the measuring line must be
observed.
Temperature monitor setting Record set temperature in °C. Triggering of the contact is audible by a
"Click".
Oil circulation pumps Before commencing any work at the oil circulation pumps, ensure that they
were switched off and secured against reactivation.
Siemens Energy is a trademark Iicensed 8–4
by Siemens AG.
Document No.:170801
Serial No.:170801
8 Maintenance and Inspection
Siemens Energy Transformers
Cleaning
Clean the fan at intervals. Do not use a pressurized water jet!
If the temperature difference rises noticeably, cooler and protective grille
are contaminated and must be cleaned. In winter operation, observe ice
formation on the protective grille and open and arrest the frost flaps if
required.
Oil flow monitors The correct installation position of the oil flow monitors is visible by the
cast-in arrows. The contacts being established here is to be inspected at
each oil flow monitor by closing a corner valve with the pump running.
The function of other flow monitors can be inspected by closing a slide in
the main pipeline.
Air flow monitors Check contact of the air flow monitors. Contact can be achieved effectively
by covering the suction-side protective grille. Contaminated air flow
monitors must be cleaned.
Water flow monitors Check contact of the water flow monitors.
Leak monitors The leakage indicator function, in particular that of the floats as signaling
devices, must be verified by filling in spirit according to the device
description. Then ensure complete emptying and vaporizing of the test
liquid and attach the connection hoses between the cooler and leakage
indicator again.
Do not use water for testing due to danger of corrosion!
Fan and pump control Check that the control works according to the circuit diagram. Fans and
pumps must run perfectly.
Pressure relief device Check the pressure relief device for the transformer tank and, if present,
for the tap changer as well.
Test contacting the trigger elements remain in the trigger position. They
must be put in the operating position again after inspection at the device.
Cooling system The time of operation after which the coolers must be cleaned cannot be
indicated as a general value; the cleaning intervals to be determined
mainly depend on the local air and cooling water conditions. Cleaning of
the cooler is required at the latest when the oil temperature has a rising
trend with the transformer load and air or water entry temperature
remaining the same.
Interlocks
If electrical locking mechanisms are present, check their function, i.e. even
trying to operate the tap changer must switch off the transformer.
The end positions are mechanically secured. When the end position of the
tap changer is reached, further adjustment is only possible in the reverse
direction.
Drive
Operating the tap changer must be easily possible mechanically with the
hand-crank or by motor operation.
Checking the control cubicles Heating, lighting
Heating and illumination (door contact) must be checked for proper
function. The heating temperature must securely prevent condensate
formation! The thermostat of the cabinet heating must be set to approx.
20 °C.
Tightness
Switching cabinets must be water- and dust-tight according to their
protection type. Door seals and lock must not be damaged. Check and
clean casing vents if required.
Contact functions
Proper contacting pursuant to the circuit diagram must be warranted.
Wiring, ducts
Cover ducts and lines must be free of damage, wiring must not have any
aging damage.
Tap changer
Tap changer revision depends on Tap changer revision depends on switching numbers or duration of use.
switching numbers or duration of For this information, see the operating instructions of the tap changer
use (chapter 9).
Motor drive Switching through all positions
If the tap changer is operated less than 3,000 times per year or not moved
across the whole setting range, the complete setting range must be gone
through about 10 times with the transformer powered down for cleaning
the contacts.
Contactor control
Must be verified for proper function according to the circuit diagram.
Tap-to-tap interlock
To test the step control, operate the toggle or push-button S1 or S2 during
the complete run-time of an adjustment process. After switching the load
control switch, the motor drive must switch off independently. Further
adjustment must only take place after another impulse is given.
If the overrun lock in the motor drive or control center is a time relay to
switch off the drive's motor protection switch after approx. 8 sec after run-
time of 1 stage is exceeded, its function must be tested as well.
Anti-corrosion coating
See chapter 8.3.
Miscellaneous
Inspect the door seal and locking mechanism for tightness or damage.
Clean vents if required.
Check heating function, thermostat setting (approx. 20 °C) if applicable or
hygrostat if present.
Check the lighting.
Check the contact tracks and position indicators, as well as firm seat of all
terminal clamps on terminal rails.
Clean the motor drive if required..
In case of stronger mechanical vibrations transferred to the drive casing
from outside, check the seat of all screws and tighten them if required.
Oil examination
Gas-analysis examination For measuring the breakdown voltage, verification of chemical and
Gas-chromatography examination physical characteristics of the insulating liquid, taking of oil samples from
the transformer is required. Sampling is performed before commissioning
of the transformer, after extended operating duration or in case of
interference.
Oil examinations are performed for the following oil spaces:
- Transformer tank
- Conservator
- Tap selector compartment
- Bushing compartment
- Cable box
- Condenser bushing (only in special cases on instructions of the bushing
manufacturer)
Cable box
Entry of moisture into the cable Check moisture content of the cable boxes filling compound (UD).
box filling compound of
compound-filled or the oil of oil-
filled cable terminal boxes
Moisture collecting in air-filled Any collected condensation must be able to run off.
cable cover hoods
Miscellaneous
Corrosion protection Timely repair of the top coat of paint generally makes it possible to avoid
replacing the complete paint coat.
For performance, see "Repair of coatings and zinc covers“.
Spark gaps, setting according to The protective spark gaps must be set according to the indications of the
dimension drawing dimension drawing or the respective binding stipulations. Increased
distances must be considered according to the stipulations when setting up
the transformer in altitudes exceeding 1,000 m. When over-voltage
deflectors are attached, the distance of the arcing horns is generally
increased or they are completely removed.
Sound absorption Inspect the sealing strips for completeness. Entering moisture will lead to
corrosion at the transformer/reactor and the sound absorption walls.
Earth connections (protective To avoid current loops, the transformer tank and any cooling system must
earth) be earthed with a sufficient line cross-section. The earthing screw must be
inspected for firm seal and re-tightened if required.
Gas test device The bottles with the test liquids "silver nitrate solution" and "palladium
chloride solution" are marked with the best before date. Using the test
liquid after the best before date may lead to falsification of the analysis of
gas samples.
Instructions pursuant to gas test device description (chapter 9).
Electrical Tests
Electrical tests at transformers/reactors must be performed under consideration of relevant
safety provisions and assembly instructions applicable for them.
NOTE
Electrical tests are to be performed on demand but at least in a 5-year cycle.
The decision must be made by construction management and should be confirmed in writing
due to the great risk.
8.2.2 Grouting
For small leaks in tank walls with a thickness of ≥ 8 mm, grouting may be sufficient. For this,
a die, mandrel or chisel is used to drive the material around the leak towards the hole as evenly
as possible.
ATTENTION
This way, the leak is only closed temporarily and must be welded as soon as possible.
insulating oil at the tank bottom leads to a vacuum in the tank. The vacuum is the largest
above the oil level and drops to zero towards the exit height. When the tank is closed
completely, approx. 0.3 % of the overall oil volume may flow out. If more insulating oil flows
out, there is a leak somewhere that must be removed. Since the pressure outside of the tank
is higher than on the inside, no insulation oil flows out at the leak. However, air may be sucked
in through the leak. For larger transformers (> 40 MVA) or larger leaks, application of a
vacuum pump is appropriate. However, ensure that the tank is vacuum resistant, or too high
a vacuum may lead to permanent tank deformation. Corrugated sheet tanks are not vacuum
resistant!
8.2.5 Welding
Prepare repair work well so that the time the insulting oil is subject to higher heat
development remains short. Comply with fire protection measures as described. Provide two
or more fire extinguishers with suitable extinguishing agent against oil fire (fire class B)
according to transformer size.
If the weld point is above the oil level, flush the clearance with nitrogen and open it against
overpressure.
In particular, no air but only nitrogen must be pressed in through the dehumidifier when
lowering the oil level after an electrical defect.
Before opening the transformer, remove nitrogen by evacuation and replace by dry
compressed air.
repaired area is not obvious. Every layer must dry for 5 to 8 hours before the next layer is
applied.
Two layers must be applied the minimum layer thickness must be 80 µm. After application of
the zinc dust coating, interim and top coating must be applied pursuant to instructions.
9.2 Coils
The coils are made of concentrically aligned coil groups and supported against the yokes. The
insulation of the twisted or massive conductors consists of oil-soaked paper with electrical
stability.
Paper insulation thickness is dimensioned according to the voltage load. Coils with parallel
conductors are twisted. Coils with a rated voltage of 110 kV or more are partially or completely
interleaved. The insulation between the coils and against the core or yoke consists of cylinders
and shaped parts made of transformer board.
The coils are equipped with capacity rings. In axial direction, the coils are clamped between
the press plates with supports made of insulating material; pressing is performed by internal
pull rods.
All control lines in the transformer are short-circuit proof and supported voltage-safely.
Tank-cover-connection welded
This sealing system is based on the use of rubber seals in furrows. It consists of an oil- and
heat-resistant synthetic rubber NBR (or equal).
CAUTION
If the cover screw is insulated, it must not be bridged by any additional conversions.
All tank or cover attachment parts are placed in the dimension drawing.
Transport options:
Work steps Reference points Position in the dimension drawing
Lifting with hydraulic lifters 4 Lifting points 100
Lifting with crane 4 Lifting eyes 100
Pulling longitudinally 4 Pull eyes 104
Pulling transversely 4 Pull eyes 104
Tab. 9-1 Transport options
9.4 Conservator
ATTENTION
The conservator is vacuum-proof
The conservator compartment volumes are designed based on maximum oil expansion.
9.5 Earthings
WARNING
On-load tap changers (OLTC) must only be operated by instructed and authorized
specialists.
A live transformer must never be switched directly from the motor operation cabinet of
the OLTC. The OLTC must only be operated via remote control from a secure control
center.
While persons are standing close to a live transformer, e.g. during commissioning and
maintenance, no controlling operations must be performed at the load control switch.
The transformer operator is asked to indicate any damage, injury or accidents in
connection with OLTC to Siemens manufacturer’s plant without delay.
The control cabinet is installed vibration-protected at the tank and contains the following
equipment:
1. Voltage supply
2. Cooling control
3. Terminal blocks and cable screws
4. Warning and trigger contacts
Heating elements, lighting and sockets for 230V, 1-phase are installed.
The cabinet is of protection class IP 55.
DANGER
The following five safety rules must be observed:
1. Power down
2. Secure against reactivation
3. Verify that the equipment is powered down
4. Ground and short-circuit
5. Cover or cordon off any adjacent live parts
ATTENTION
If the control cabinet is out of operation or stored for any extended period, the provisions
pursuant to chapter 4.8.3, long-term storage for accessories, must be observed.
9.8 Bushings
Page / Version Date
Sheet No.
Bushing type Oil impregnated paper condenser bushing
Designation (U,.V, W): HV-U
Position in the GD001
dimension drawing:
Manufacturer: SHENYANG CHUANQI
Type: BRDLW-252/630-4
Operating instructions: /
ATTENTION
If measuring or protective devices are not connected, the secondary clamps of the
transformer must be short-circuited and earthed.
使用说明书
Explanation for Use
南京正方电气有限公司
Nanjing Fine Electric Co.,Ltd.
1. 用途
套管型电流互感器用于交流电力设备上,用于电气测量和继电保护。
Application
Bushing current transformers are applied on AC electrical equipments for measuring
and relay.
2.分类
套管型电流互感器按其用途,可分为测量级互感器和保护级互感器两种。
Class
Bushing current transformers may be divided into measuring transformers and relay
transformers according to their purpose.
3.型号说明
Type explanation
L R B—□
4.安装
安装前,对每只电流互感器外观及铭牌数据逐一检查,确保各参数符合使用要求;将检验合
格的电流互感器按照不同型号分类摆放(摆放时将铭牌正立) ,在120℃烘房内干燥24小时。
Installation
The appearance and nameplate of every current transformer should be checked to assure
the parameters to be able to meet the requirement for use. Please put the current
transformers checked according to their type(nameplate up) in 120℃ drying room for
24 hours.
4.1电流互感器的安装
拆除电流互感器的外保护层,采用三点起吊的方法,用绳子起吊电流互感器非垫块部位,
依据电流互感器装配顺序,按减极性方向(产品铭牌正立时上端面为P1)逐一装配到套筒内,
装配时注意电流互感器二次引线与套筒二次出线盒在同一方向,并用适当的方法将电流互感器
固定。
Current transformer installation
Please backout the outer surface of current transformer, suspend the current
transformer with rope on 3 spots without stow-wood, put the current transformers into
the sleeve in the light of negative polarity(the letter P1 on the upside of CT as its
nameplate stands upright),set the current transformer with its secondary lead on the
same direction as the secondary lead box, and finally fix the current transformers.
4.2接线及检查
将电流互感器的二次接线端子正确、牢固地接在二次出线板的接线柱上,并标明出线标志,
接线完毕后应做极性和变比检查。对于小变比(100/5A以下)电流互感器变比检验用电流法
测量可能误差较大,推荐采用校验仪检验。
Lead junction and examination
Secondary leads should be connected firmly with secondary terminals marked. Current
ratio and polarity examination tests are carried out after secondary lead connection.
For the current transformer with small current ratio(less than 100/5A), checkout
instrument should be suggested to test current ratio as error of current measurement
method.
5.注意事项
电流互感器的铁芯材料为硅钢片及合金等磁性材料,猛烈的敲打及撞击会对磁性能产生很大
的影响,因此,严禁搬运时将互感器在地上滚动,装配固定时严禁猛烈敲打电流互感器。
Notice
Knocking and impacting violently the core of current transformer may possibly
influence greatly magnetic performance because the core is made of silicon steel or
alloy. So, rolling or impacting the current transformer is forbidden.
6.包装和储存
电流互感器用薄膜塑料袋密封包装后装入木箱中,木箱具有足够的机械强度,可保证电流互
感器在运输中不受损伤;产品应放置在干燥通风处储存。
Packaging and storing
Please pack current transformer with plastic film bag and put them into wooden box
which should be strong enough to be able to protect current transformer from being
damaged. In addition, they should be stored at dry and ventilative place.
7.订货须知
订货时请提出产品型号、电流比、额定负荷、准确级、外形尺寸等要求,有特殊要求时在
订货时提供技术协议。
Notice for subscribing product
The requirments for type,current ratio,rated load,accuracy class and outline
dimension of current transformer should be given when subscribing products. A technical
agreement for subscribing will be supplied for special request.
9 Technical Documentation of the Heavy Part and Accessories
Siemens Energy Transformers
WARNING
Before connection or manipulation at the contacts (terminals), verify voltage freeness on
all sides and all pins
Doc-Nr.: Operating manual 42560 A | Created: 07.09.2017 | Revised: 07.09.2017 | Language: ENG 1/4
1. Welding & Painting
All butterfly valve types are delivered in tested and closed condition.
RIGHT: Closed and
To gain maximum tightness we produce our valves with very small protected valve
tolerances between flapper and valve housing.
To remain its function please always handle the butterfly
valve as further described.
In case the butterfly valve will be welded onto the transformer tank
it is absolutely necessary to keep the sealing surface between flap
and housing clean. No welding debris should get in contact with the
sealing surface.
In order not to damage the O-rings used, the setting device has to
be removed before welding. The 1“ thread has to be protected with a
screw plug.
Doc-Nr.: Operating manual 42560 A | Created: 07.09.2017 | Revised: 07.09.2017 | Language: ENG 2/4
3. The Setting Device
The Setting Device consists basically in all different versions of a thrust member Thrust Screw Thrust Member
O-ring 23
(inner brass part) and a thrust screw (hexagon brass screw). The thrust screw O-Ring 24
Flat Gasket
presses the inner thrust member to assure tightness at the area of the spindle.
This means that the valve can‘t be operated without loosening the thrust screw.
In case the valve should be welded the device has to be dismounted for welding
process to protect sealing materials. The thread has to be protected.
Remount the setting device. Place the flat gasket around the spindle then mount the thrust member in correct
direction, then assemble small O-ring, brass screw and large outer O-ring as shown in drawing.
Loose the outer thrust screw with the 36 mm spanner about 90° counterclockwise in order to ease pressure on
the inner thrust member. (tightening torque SW36: 15 Nm)
Open the valve counterclockwise using the 17 mm spanner at the thrust member until its final position.
(tightening torque when closing SW17: 70 Nm) Retighten the outer thrust screw clockwise using the 36 mm span-
ner while holding the flap with the 17 mm spanner in position Tighten the thrust screw with a maximum of 50
Nm to remain the flap in its position. (tightening torque SW36: 50 Nm)
Doc-Nr.: Operating manual 42560 A | Created: 07.09.2017 | Revised: 07.09.2017 | Language: ENG 3/4
Albert MAIER GmbH
Armaturen für Transformatoren
Industriestr. 19
71263 Weil der Stadt
Doc-Nr.: Operating manual 42560 A | Created: 07.09.2017 | Revised: 07.09.2017 | Language: ENG 4/4
9 Technical Documentation of the Heavy Part and Accessories
Siemens Energy Transformers
Gas Sampler
Position in the dimension /
drawing:
Manufacturer: EMB
Type: ZG 1.2.
Operating instructions: Operating instructions for Gas
Sampler
ATTENTION
For the contact types of the protective and monitoring devices, please see the circuit
diagram.
WARNING
For inspection of the Buchholz relay, you may require access to areas of the transformer
that pose a danger of falling (use of ladders or other aids).
Such work must only be performed by accordingly trained persons.
Before connection or manipulation at the contacts, verify voltage freeness on all sides
and all pins.
Table of contents
page
Company history 4
1 Preface 5
2 Design features 6
3 Function 8
3.1 Gas accumulation 8
3.2 Insulating liquid loss 9
3.3 Insulating liquid flow 9
4 Tests 10
2
page
9 Technical data 26
10 Options/Special designs 27
10.1 Explanations to code 17 A 29
10.2 Explanations to codes 23 and 24 29
10.3 Explanations to code 32 30
3
Elektromotoren und Gerätebau Barleben GmbH
Company history
Since its foundation the company has passed through an eventful history with regard to ownership,
affiliation and change of name associated with such development.
4
1 Preface
The Buchholz relay was developed in 1921 by Max Buchholz, Oberrat (senior councillor) at Preu-
ßische Elektrizitäts-A.G. (Prussian electricity company) in Kassel. Since that time it has been an
important protection and monitoring device for insulating liquid filled transformers with conservator
and choke coils. It also allows separate monitoring of oil-filled bushings or cable terminal boxes. It is
mounted in the cooling cycle of the device to be protected and responds to faults such as gas gene-
ration, loss of as well as high flow rates of the insulating liquid.
For transformers with hermetical closure by means of a hydro-type compensator (rubber sack) in the
conservator, the Buchholz relay can be used also a monitoring device (air cell failure relay) of the
hydro-type compensator.
The type diversity of the Buchholz relay is tailored to norms and standards as well as to special
customer demands. The type of relay to be used depends on the nominal rating and construction
features of the device to be protected. Our range of products permits optimum adaptation to actual
requirements.
Elektromotoren und Gerätebau GmbH (EMB GmbH) provides more than 60 years experience in pro-
ducing Buchholz relays and other protective devices for liquid-cooled and liquid-insulated devices. It
ranks today among the most distinguished manufacturers of this type of equipment.
EMB Buchholz relays are in compliance with DIN EN 50216-2 and are known for their easy operati-
on, high reliability and extremely long life.
Our staff of highly qualified engineers and experienced skilled workers do their best to guarantee
top-quality high-precision products. The casings are machined on modern CNC-controlled machi-
nes. All products are subjected to final inspection when all functions are checked using special test
equipment.
Profound experience and expertise in this special area are a sound basis for high product quality.
Extensive references from reputed transformer manufacturers as well as other users are proof of the
high qualitative level of the products.
EMB has been certified according to: DIN EN ISO 9001/2008, AEO F, Known Consignor (Airfreight
Security) and EAC. Further certifications have been awarded by well-known independent test labo-
ratories such as TÜVRheinland and TZO.
Figure 2 - Certificates
5
Elektromotoren und Gerätebau Barleben GmbH
2 Design features
Casing
The casing is made of weather-resistant cast aluminium alloy provided with a paint coat. It is sup-
plied either with flanged (Fig. 3/ Number 1) or screwed connection (Fig. 4/1). The different casing
designs available are shown in Section 5 for single-float Buchholz relays and Section 7 for double-
float Buchholz relays, others are available on request.
To check the switching system for proper function, the casing is provided with sightglasses (Fig. 4/2).
The sightglasses provided with scales permit reading of collected gas volume.
The relays can be provided with hinged lids (Fig. 3/2) to protect the sightglasses.
6
Cover
The cover is made of weather-resistant cast aluminium alloy provided with a paint coat.
The upper section of the cover accommodates the terminal box (Fig. 5 and 6/1). In front of the termi-
nal box are arranged the bleeding valve (Fig. 5 and 6/2) and the test key covered by a cap nut (Fig.
5 and 6/3) as well as a plate (Fig. 5 and 6/4) with instructions for actuating the test key. The terminal
box accommodates the earth terminal (Fig. 5 and 6/5) and bushings (Fig. 5 and 6/6) for the termi-
nals provided in the base of the cover. The number of these bushings determines the design of the
switching systems in terms of type and quantity of the magnet contact tubes.
The terminal box is sealed by an cap (Fig. 5 and 6/7) so that it is safe to touch and protected against
pollution. If the cap is opened the graphic symbol and the connection diagram (Fig. 5 and 6/8) are
shown. The cable can be inserted through the cable gland (Fig. 5 and 6/9).
5
9
6
1
3
2
Figure 5 - Cover with cap removed, Buchholz relay Figure 6 - Cover with cap removed, Buchholz relay
with five magnet contact tubes with up to four magnet contact tubes
7
Elektromotoren und Gerätebau Barleben GmbH
3 Function
The Buchholz relay is installed in the pipe between the tank of the device to be protected (trans-
former, reactor) and the conservator. During normal operation it is filled completely with insulating
liquid.
Due to buoyancy the float of the single-float relay and both floats of the double-float relay are at their
top position.
The upper and lower switching systems form a functional unit in the single-float Buchholz relay so
that in the event of a fault the transformer is immediately disconnected from the power system.
In the following the function of a Buchholz relay is explained using the example of a double-float
Buchholz relay. If a fault occurs inside the transformer, the Buchholz relay responds as follows:
Response: The gas in the liquid moves upwards, accumulates in the Buchholz relay and displaces
the insulating liquid level. As the liquid level falls, the upper float moves downwards.
The moving float actuates a switch contact (magnet contact tube). An alarm signal is tripped.
The lower float is not affected as from a certain gas volume the gas flows through a piping to the
conservator.
Gas
Gas
Oil
Öl
8
3.2 Insulating liquid loss (Figure 8)
Response: As the liquid level falls the top float moves downwards. An alarm is tripped. If the liquid
loss continues, conservator and piping as well as the Buchholz relay will be emptied.
As the liquid level falls, the lower float moves downwards. The moving float actuates a switch contact
so that the transformer is disconnected.
Air
Luft
Oil
Öl
Fault: A spontaneous incident generates a pressure wave moving in the direction of the conservator.
Response: The liquid flow reaches the damper arranged in the liquid flow. If the flow rate exceeds
the operating value of the damper, the latter moves in flow direction.
Due to this movement a switch contact is actuated so that the transformer is disconnected.
After release of the pressure wave the lower switching system returns to its starting position.
Buchholz relays manufactured by EMB are equipped with a damper held by a permanent magnet.
Oil
Öl
9
Elektromotoren und Gerätebau Barleben GmbH
4 Tests
Each Buchholz relay is provided with a works-number that is specified on
the test certificate and the name plate. The tests carried out on the Buch-
holz relay are recorded in the test certificate.
date of manufacture
Type (week/year)
type code
10
5 Type list of single-float Buchholz relays
5.1 Single-float Buchholz relays with threaded connection
Pipe Weight
Type Flange dimensions Device dimensions Suited for
diameter without
Internal description Type of connection (mm) (mm) transformer
DN (mm) packing
DIN description ratings of
d1 d2 d3 d4 d5 f l h1 h2 (kg)
01 Threaded
(AG 25) connection 25 - - - - 16 185 170 62 3,1 ≤1600 KVA
(CG 25) G 1½ “
02
Flange
(AF 25/6) 4-hole 25 100 75 60 12 12 185 195 62 3,6 ≤1600 KVA
(-)
03
Flange
(AF 25/10) 4-hole 25 115 85 68 14 16 200 205 62 4,0 ≤1600 KVA
(-)
25
Flange
(AF 25) 4-hole 25 100 75 - 12 15 160 195 62 3,3 ≤1600 KVA
(-)
11
Elektromotoren und Gerätebau Barleben GmbH
Pipe
Flange dimensions Device dimensions Weight
Type diameter Suited for
(mm) (mm) without
Internal description Type of connection DN (mm) transformer
packing
DIN description ratings of
d1 d2 d3 d4 d5 f l h1 h2 (kg)
30
Flange
(AF 25/10 G) 4-hole 25 115 85 - 14 16 200 205 62 4 ≤1600 KVA
(-)
170
80
h1
h2
R8
0
d5
f d1
l
d3
d2
12
6 Switching system design options for single-float Buchholz relays
Magnet contact tubes are used as switching elements. These are normally-open (NO), normally-
closed (NC) and change-over (CO) contacts. The magnet contact tube design can be derived from
the last digit of the type code. For coding, see Ordering data/Type code under Section 12.1.
13 11 13 23 11 21 13 11 1
14 12 14 24 12 22 14 12 2 4
22 24 12 14 24 12 14 22 12 14
The inner side of the cap accommodates a plate with the graphic symbol and the connection
diagram. The schemes show the switching systems in their neutral position. The neutral po-
sition is the operating condition when the Buchholz relay is filled with insulating liquid up the
required level and the device to be protected operates without any fault.
13
Elektromotoren und Gerätebau Barleben GmbH
Pipe
Flange dimensions Device dimensions Weight
Type diameter Suited for
(mm) (mm) without
Internal description Type of connection DN (mm) transformer
packing
DIN description ratings of
d1 d2 d3 d4 d5 f l h1 h2 (kg)
04 Threaded
(BG 25) connection 25 - - - - 16 185 235 90 4,2 ≤5000 KVA
(DG 25) G 1½ “
21 Threaded
(BG 25 S) connection 25 - - - - 16 185 235 90 3,6 ≤5000 KVA
(-) G 1½ “
14
7.2 Double-float Buchholz relays with flanged connection (round)
Pipe
Flange dimensions Device dimensions Weight
Type diameter Suited for
(mm) (mm) without
Internal description Type of connection DN (mm) transformer
packing
DIN description ratings of
d1 d2 d3 d4 d5 f l h1 h2 (kg)
05
Flange
(BF 25/6) 4-hole 25 100 75 60 12 12 185 235 90 4,4 ≤5000 KVA
(-)
06
Flange
(BF 25/10) 4-hole 25 115 85 68 14 18 200 235 90 4,8 ≤5000 KVA
(DR 25)
07
Flange ≥5000 KVA
(BF 50/6) 4-hole 50 140 110 90 14 12 185 235 80 4,6
≤10000 KVA
(-)
08
Flange ≥5000 KVA
(BF 50/10) 4-hole 50 165 125 102 18 16 195 250 80 5,9
≤10000 KVA
(DR 50)
09
Flange
(BF 80/10) 4-hole 80 200 160 138 18 15 195 265 80 6,2 ≥10000 KVA
(-)
24
Flange
(BF 80/6) 4-hole 80 190 150 130 18 15 195 260 80 6,0 ≥10000 KVA
(-)
15
Elektromotoren und Gerätebau Barleben GmbH
Pipe Weight
Type Flange dimensions Device dimensions Suited for
diameter without
Internal description Type of connection (mm) (mm) transformer
DN (mm) packing
DIN description ratings of
d1 d2 d3 d4 d5 f l h1 h2 (kg)
23
Flange
(BF 25/10 S) 4-hole 25 115 85 68 14 18 200 235 90 4,4 ≤5000 KVA
(-)
Pipe Weight
Type Flange dimensions Device dimensions Suited for
diameter without
Internal description Type of connection (mm) (mm) transformer
DN (mm) packing
DIN description ratings of
d1 d2 d3 d4 d5 f l h1 h2 (kg)
26
Flange 18
(BF80/10/8) 8-hole 80 200 160 138
M16
15 195 265 80 6,2 ≥10000 KVA
(DR 80)
16
7.3 Double-float Buchholz relays with flat flanged connection (round)
Pipe
Flange dimensions Device dimensions Weight
Type diameter Suited for
(mm) (mm) without
Internal description Type of connection DN (mm) transformer
packing
DIN description ratings of
d1 d2 d3 d4 d5 f l h1 h2 (kg)
28
Flange
(BF 80/10 G) 4-hole 80 200 160 - 18 18 195 265 80 6,2 ≤10000 KVA
(-)
31
Flange
(BF 25/10 G) 4-hole 25 115 85 - 14 20 200 235 90 4,8 ≤5000 KVA
(DR 25)
170
80
h1
d5
h2
R1
43
f d1
l d3
d2
Pipe
Flange dimensions Device dimensions Weight
Type diameter Suited for
(mm) (mm) without
Internal description Type of connection DN (mm) transformer
packing
DIN description ratings of
d1 d2 d3 d4 d5 f l h1 h2 (kg)
27
Flange
(BF 80/10/8 G) 8-hole 80 200 160 - 18 18 195 265 80 6,2 ≤10000 KVA
(DR 80
170
80
M16
d5
h1
R
h2
14
3
f d1
l d3
d2
17
Elektromotoren und Gerätebau Barleben GmbH
10 Flange
(BF 80/Q) square 80 125 132 - 18 20 200 235 80 5,0 ≥10000 KVA
(DQ 80) 4-hole
170
80
250
300
h1
350
h2
3
cm
d3 R1
43
b
d5
d1
f
l
b
62 Flange
≥5000 KVA
(BC 50) square 50 125 125 - 14 15 185 230 80 5,0
≤10000 KVA
(QJ 50) 4-hole
63 Flange
(BC 80) square 80 160 160 - 18 15 185 245 80 5,0 ≥10000 KVA
(QJ 80) 4-hole
170
80
250
300
350
h1
h2
R1
cm
3 43
d3
b
d5
f
d1
l
b
Pipe Weight
Flange dimensions Device dimensions Suited for
Type diameter without
Type of connection (mm) (mm) transformer
Internal description DN (mm) packing
ratings of
d1 d2 d3 d4 d5 f l h1 h2 (kg)
41 Flange
(NF 25) 4-hole 25 115 85 - 14 8 240 235 90 4,2 ≤5000 KVA
43 Flange
(NF 80) 4-hole 80 200 160 - 18 15 240 265 80 5,5 ≥10000 KVA
19
Elektromotoren und Gerätebau Barleben GmbH
Pipe Weight
Flange dimensions Device dimensions Suited for
Type diameter without
Type of connection (mm, in) (mm) transformer
Internal description DN (mm) packing
ratings of
d1 b/d2 d3 d4 d5 f l h1 h2 (kg)
Flange
51 76 72 - M10 - 127 235 90
(BS 25)
square 25 2,99 2,83 - M10 - 5 9,25 3,54
3,7 ≤ 5000 KVA
4-hole
Flange
52 140 110 - 12 12 185 235 80 ≥5000 KVA
(BS 50)
round 50 5,51 4,33 - 0,47 0,47 7,28 9,25 3,15
4,8
≤10000 KVA
6-hole
Flange
53 160 130 - 12 13 185 240 80
(BS 80)
round 80 6,30 5,12 - 0,47 0,51 7,28 9,45 3,15
5,0 ≥10000 KVA
6-hole
150
80
250
300
h1
350
h2
90
3
°
cm
d5
b
d1
l d3
b
170
80
250
300
350
h1
h2
R1
cm
3
43
d5
f d1
l d3
d2
20
8 Switching system design options for double-float Buchholz relays
Magnet contact tubes are used as switching elements. These are normally-open (NO), normally-
closed (NC) and change-over (CO) contacts. The magnet contact tube design can be derived from
the last two digits of the type code. For coding, see Ordering data/Type code under Section 12.2.
13 13 13 13 13
14 14 14 14 14
23 23 11 23 33 11 21
24 24 12 24 34 12 22
13 23 13 13 11
14 24 14 14 12
23 11 11 13
21 31 23 33 43
22 24 32 34 24 34 44
24 12 12 14 14
21
Elektromotoren und Gerätebau Barleben GmbH
11 11 11 11 21
12 12 12 12 22
21 13 23 21 31 13 21 11
22 14 24 22 32 14 22 12 14
11 21 21 21 21
12 22 24 22 24 22 24 22 24
13 11 33 43 31 41
21 31
22 24 32 34
14 12 34 44 32 42
22
...35 ...36 ... 37 ...41 ...42
Alarm Alarm Alarm Alarm Alarm
1 CO 1 CO 1 CO 2 NO 2 NO
21 21 21 13 23 13 23
22 24 22 24 22 24 14 24 14 24
13 11 11 33 11
14 12 12 14 34 12
14 13 34 33
14 24 14 24 14 24 24 34 14 24
33 43 11 21 33 11 11
12 22 34 12 12 14
34 44
23
Elektromotoren und Gerätebau Barleben GmbH
12 14 12 14 12 14 12 14 12 14
23 21 23 33 21 31 21 23
24 22 24 34 22 32 22 24
...56 ...77
Alarm Alarm
1 NC and
2 CO
1 NO
21 23
22 24
Disconnection Disconnection
1 CO 2 CO
11
12 14
24
Explanation of symbols: Example: coding „ ...1 2 “
Magnet contact tube(s) design
Upper switching system - Alarm
Lower switching system - Disconnection
13
Alarm
1 NO
14
Graphic symbol with terminal marking
11
Disconnection
1 NC
12
The inner side of the cap accommodates a plate with the graphic symbol and the connection
diagram. The schemes show the switching systems in their neutral position. The neutral po-
sition is the operating condition when the Buchholz relay is filled with insulating liquid up the
required level and the device to be protected operates without any fault.
25
Elektromotoren und Gerätebau Barleben GmbH
9 Technical data
The technical data listed in table named below are applicable to all Buchholz relays in standard ver-
sion manufactured by EMB. EMB Buchholz relays are in compliance with DIN EN 50216-2.
Parameter Data Notes
Voltage AC 5 V - max. 250 V
DC 5 V - max. 250 V
Current AC 0.01 A - max. 6 A Cos φ > 0,5
DC 0.01 A - max. 6 A L/R < 40 ms
Switching capacity AC max. 1500 VA
DC max. 1250 W
Dielectric strength AC 2500 V Between electric circuit and earth
AC 2000 V (normally-open contact, Between open contacts
normally-closed contact)
AC 1000 V (change-over contact)
Temperature range:
- Ambient temperature - 40 °C to + 55 °C Climatic testing acc. to
- 40 °F to + 131 °F DIN EN 60068-2-78: 2002-09
- Operating range
* Temperature of the insulating liquid - 40 °C to + 115 °C Others on request
- 40 °F to + 239 °F
26
10 Options/Special designs
Cable gland *
Explanation Code
M20x1,5: 1 cable gland and 1 dummy plug 1
M25x1,5: 1 cable gland and 1 dummy plug 2
M20x1,5: 2 cable glands 3
M20x1,5: 2 cable glands plus 1 additional dummy plug 3B
M25x1,5: 2 cable glands 4
M25x1,5: 2 cable glands plus 1 additional dummy plug 4B
M20x1,5: 1 Harting connector and 1 dummy plug 5
1/2“ NPT: 1 cable gland and 1 dummy plug 6
1/2“ NPT: 2 cable glands 7
Cable gland: Special request 9
Buchholz relay NM series
Buchholz relay with analogue measurement of the gas volume
(only double-float Buchholz relays, Note: Explanations to code 60) 60
Casing colour *
Casing colour RAL 9006 (white-aluminium) 40
Casing colour RAL 7001 (silver-grey) 41
Casing colour RAL 7012 (basalt-grey) 42
Casing colour RAL 7022 (umber-grey) 43
Casing colour RAL 7033 (cement-grey) 44
Casing colour RAL 7038 (agate-grey) 45
Casing colour RAL 7035 (light-grey) 46
Casing colour RAL 7016 (anthracite-grey) 47
Casing colour RAL 9002 (grey-white) 48
Casing colour RAL 7032 (siliceous-grey) 49
Climate-proof version/IP code
Climate-proof version for extreme frigid open-air conditions below - 40 °C 34
Climate-proof version for Offshore 36
Climate-proof version for aggressive industrial atmosphere 36B
IP code 66 39
Insulating liquid
Insulating liquid silicone oil 20
Insulating liquid based on ester 21
Casing
Metal plate 15
With oil drain plug (only double-float Buchholz relays) 28
With premounted Harting connector
(The option is indicated by a letter after the code.
For further information, please ask for special reference material.) 59
* Mandatory order data, for other mandatory data see Section 12.
27
Elektromotoren und Gerätebau Barleben GmbH
Switching system
Upper switching system equipped with two magnet contact tubes 35
Lower switching system equipped with two magnet contact tubes 25
Upper and lower switching system each equipped with two magnet contact tubes 33
Lower switching system equipped with three magnet contact tubes 99
Upper switching system equipped with two magnet contact tubes,
Lower switching system equipped with three magnet contact tubes 55
Two-level gas alarm system (Note: Explanations to code 17A) 17A
Testing of the switching systems by means of compressed-air and test key
(only double-float Buchholz relays, Note: Explanations to code 32) 32
Damper held in response position (only double-float Buchholz relays,
Note: Explanations to codes 23 and 24) 23
Special design approved by RWE, Germany (only double-float Buchholz relays,
Note: Explanations to codes 23 and 24) 24
Special design approved by E.ON, Germany (only double-float Buchholz relays,
Note: Explanations to codes 23 and 24) 24B
Solid floats (Insulating liquid flow max. 1,50 m/s ± 15%) 16
Alarm for gas accumulation between 250 and 300 cm³ 18
Special request
Special request (on special agreement with customer) 29
For engineering reasons the following special designs cannot be combined in the same device:
28
10.1 Explanations to code 17 A
Gases formed in the transformer rise to the conservator. In this way gases are collected in the Buch-
holz relay. When a certain volume is reached, the gases generate an alarm signal.
With the two-level alarm system the initial alarm signal is generated at a gas volume of 100-200 cm³,
and the second alarm signal at a gas volume of 250-300 cm³. This special design allows a gas sam-
ple to be taken for fault analysis already when the initial warning signal is received.
Buchholz relays with the feature „damper held in response position“ are designed such that the dam-
per after it was operated due to an unacceptable high flow rate of the insulating liquid is locked in its
position and, hence is kept in this position even after the flow rate has been reduced. This means
that the signal generated is maintained.
The damper has to be unlocked manually by turning the test key anticlockwise. When unlocking
the damper, also check the insulating liquid level in the Buchholz relay. Bleed the Buchholz relay, if
required.
29
Elektromotoren und Gerätebau Barleben GmbH
For Buchholz relays provided additionally with an air nipple (code 32), the mechanical function of
the two switching systems can be tested by means of test key (Fig. 28/1), and the upper switching
system (alarm) can be tested by pumping in air via the bleeding valve (Fig. 28/2) using a suitable test
pump. Additionally, the switching systems can be tested pneumatically. To this end, air is supplied
via an air supply nipple (Fig. 28/3) provided with a check valve. Perform the test while the Buchholz
relay is filled with insulating liquid up to the required level.
Pneumatic test of the upper switching system (alarm) using compressed air:
Air is introduced slowly into the Buchholz relay through the air supply nipple and the pipe air until
the alarm contact is made when the upper float is lowered.
Pneumatic test of the lower switching system (disconnection) using compressed air:
Through the air supply nipple and the pipe air is applied suddenly to the damper. When the damper
responds the disconnection contact is made.
After any test using air, bleed the Buchholz relay through the bleeding valve.
This special design of EMB GmbH combines the requirement of functional testing using compressed
air according to the former British standard B.E.B.S. T2 of 1966 and of functional testing using the
test key according to the former German norm DIN 42566.
2 3 1
30
11 Explanations to code 60 - Buchholz relay NM series
11.1 Design features of Buchholz relay NM series
The principal construction of the Buchholz relay with floats and damper as well as their electro-
mechanical functions have been maintained.
The Buchholz relay of series NM is equipped additionally with a capacitive sensor. The sensor is
installed in the cover of the Buchholz relay. The cap of the terminal box accommodates the electronic
amplifier of the measuring unit. Sensor and amplifier are connected by a shielded cable in three-wire
technology with a cable connector. This cable is used for the supply voltage and the output signal.
Figure 29 shows the arrangement of the measuring unit using the example of a Buchholz relay
BF 80/10/8. Apart from the dust hood and the cap of the terminal box which are higher by approx.
40mm, the installation dimensions of the relay have not been changed. Hence, relays with analogue
measuring units can be installed in existing systems.
170
109
M16
80
291
R1
34
18
138
200
15 80
195
160
The standard Buchholz relay detects undissolved gases in the insulating liquid and indicates their
presence when a specified threshold is exceeded, meaning that up to a certain gas volume, no sig-
nal is generated. Neither is it possible to gather information about the length of time it takes for gas
to accumulate.
The process of the generation of unsolved gases in the insulating liquid over time is a very important
criterion for the evaluation of the fault as the quantity and composition of the fault gases depend on
the kind and quantity of the energy of the underlying fault. Spontaneous and energy-rich faults cause
large gas quantities within a short period of time, whilst small volumes of gas are generated in the
case of minor and insidious faults.
The Buchholz relay of NM series allows continuous and analogue gas volume measurement so that
gases which have accumulated in the relay are detected at an early stage, information about the
generation of the gases obtained and the conditions provided for the analysis of the fault at an early
stage.
31
Elektromotoren und Gerätebau Barleben GmbH
The extra function of the NM series relays is ensured by a capacitive sensor and the appropriate
electronic components. Supply voltage of this assembly is DC 24 V. This voltage must be made
available by the user. The output signal of the measuring unit is a standard current signal of
DC 4 to 20 mA. It depends on the user how and in what form this signal is processed.
Extra function
Standard function
of the Buchholz
of the Buchholz relay
relay NM series
DC 5 V - max. 250 V
DC 24 V DC 0,01 A - max. 6 A
DC 4 - 20 mA
The measured value is based on capacitance variation of the sensor caused by variation of the in-
sulating liquid level in the Buchholz relay.
Analogue measurement of the gas volume is possible between 50 cm3 and 300 cm3. Lower gas vo-
lumes cannot be measured reliably because of high inaccuracies. Measurements beyond this range
are not necessary as in this case the upper switching system will respond. Besides, the construction
of the Buchholz relay (larger gas volumes escape towards the conservator) does not allow such
measurements. The operating point of the upper switching system (upper float) is a gas volume
between 200 and 300 cm3.
Response: The gas in the liquid moves upwards, accumulates in the Buchholz relay and displaces
the insulating liquid. This decreases the level of insulating liquid. Liquid level changes lead to varia-
tion of the capacity of the sensor. This change is converted into an analogue current signal.
It should be noted that for design reasons the current value of the sensor remains relatively constant
up to a gas volume of approx. 50 cm3. The function equation will provide the actual volume only when
the current signal becomes smaller and, hence the calculated volume noticeably larger.
32
12 Ordering data/Type code
For placing orders, please, use the following key:
XX X. XX. XX. XX 0 X
Type
(see Section 5)
Options/Special designs
(see Section 10) ascending sequence
01 = 0,65 ± 15%
02 = 1,00 ± 15%
03 = 1,50 ± 15%
0 = not occupied
Contact setting of
switching system
Legend:
1 = one NO contact NO = normally-open contact
2 = one NC contact NC = normally-closed contact
3 = two NO contacts CO = change-over contact
4 = two NC contacts
5 = one NO and one NC contact
6 = one CO contact
7 = two CO contacts For switching system design options for
8 = one NO and one CO contact single-float Buchholz relays see Section 6.
9 = one NC and one CO contact
33
Elektromotoren und Gerätebau Barleben GmbH
XX X. XX. XX. XX X X
Type
(see Section 7)
Options/Special designs
(see Section 10) ascending sequence
Contact setting of
upper switching system
(Alarm)
1 = one NO contact
2 = one NC contact
3 = one CO contact
4 = two NO contacts
5 = one NC and one NO contact
7 = two CO contacts
Contact setting of
lower switching system
Legend:
(Disconnection)
NO = normally-open contact
1 = one NO contact NC = normally-closed contact
2 = one NC contact CO = change-over contact
3 = two NO contacts
4 = two NC contacts
5 = one NO and one NC contact
6 = one CO contact
7 = two CO contacts For switching system design options for
9 = three NO contacts double-float Buchholz relays see Section 8.
34
12.3 Ordering example
You need a double-float Buchholz relay of type 10 (BF 80/Q) with one cable gland of M20 x 1.5 and
one dummy plug. The damper should respond at a insulating liquid flow of 1.50 m/s. The upper swit-
ching system should be equipped with one switching element (magnet contact tube) and the lower
with two switching elements (magnet contact tubes). The upper switching element should be desig-
ned as one normally open contact, and the lower as two normally open contacts. The device should
be delivered in colour RAL 7033 and should have one oil drain plug. Based on the data on page 28
the relay ordered has the following
35
Elektromotoren und Gerätebau Barleben GmbH
The gas sampling device is mounted on the transformer and connected to the Buchholz relay by
means of a pipe. It allows sampling of the relay gas at normal operating level and will be delivered
with sightglass cover.
The length of the pipe can be selected by the customer (see technical data of gas sampling device
ZG 1.2).
Figure 31 - Gas sampling device ZG 1.2. Figure 32 - Gas sampling device ZG 1.2.
in lockable box
Figure 33 - Pipe of gas sampling device ZG 1.2. Figure 34 - Sightglass cover for
gas sampling device ZG 1.2.
36
Technical data of gas sampling device ZG 1.2.:
37
Elektromotoren und Gerätebau Barleben GmbH
Casing colour
Explanation Code
Casing colour RAL 9006 (white-aluminium) 40
Casing colour RAL 7001 (silver-grey) 41
Casing colour RAL 7012 (basalt-grey) 42
Casing colour RAL 7022 (umber-grey) 43
Casing colour RAL 7033 (cement-grey) 44
Casing colour RAL 7038 (agate-grey) 45
Casing colour RAL 7035 (light-grey) 46
Casing colour RAL 7016 (anthracite-grey) 47
Casing colour RAL 9002 (grey-white) 48
Casing colour RAL 7032 (siliceous-grey) 49
Climate-proof version
Climate-proof version for extreme frigid open-air conditions below - 40 °C 34
Climate-proof version for Offshore 36
Climate-proof version for aggressive industrial atmosphere 36
Insulating liquid
Insulating liquid silicone oil 20
Insulating liquid based on ester 21
Special request
Special request (on special agreement with customer) 29
Box
Without box 0
With box 1
0 = Without box
1 = With box
38
13.2 Other additional devices for Buchholz relays
The Buchholz gas sampler provides a safe method of taking and trans-
porting gas samples from the Buchholz relay or the gas sampling de-
vice. Its capacity is 100 ml.
The gas testing device is used to test the gas accumulated in the Buch-
holz relay. It can be installed either directly on the bleeding valve of the
Buchholz relay or on the gas outlet tap of the gas sampling device. The
Buchholz gas flows through two different chemical solutions and its
colour reactions indicate the nature of the fault.
EMB’s ZG 3.2. gas tester serves to test the gases in the gas sampling
device ZG 1.2. or the Buchholz relay for the presence of carbon mono-
xide and hydrogen. The gases are analysed qualitatively.
The ZG 3.2. gas tester can be combined with EMB‘s Buchholz gas
sampler BGS. When using the BGS and introducing the defined gas
volume (100 ml), the residual gas volume in the Buchholz relay or in
the gas sampling device can be used for further analytical purposes.
For further information on the additional devices, please ask for special reference material.
39
Elektromotoren und Gerätebau Barleben GmbH
The device prevents insulating liquid from flowing into the gas testing
device. The device is installed between the Buchholz relay or gas sam-
pling device and the gas testing device.
The test pump checks the functioning of the upper switching system
(alarm) of the Buchholz relay by pumping in air. The test can be perfor-
med directly on the Buchholz relay. For that purpose, the test pump is
connected to the bleeding valve of the Buchholz relay. When the test is
performed via the gas sampling device, the test pump is connected to
the gas outlet tap of the gas sampling device.
The oil sampling device is connected to the Buchholz relay via a pipe
and is used to take oil samples from the Buchholz relay (suitable for
use with Buchholz relays with an oil drain plug). The pipe is supplied to
the customer’s specifications.
For further information on the additional devices, please ask for special reference material.
40
14 Other protection devices
The monitoring relay for tap changers, also known as the protection
relay for tap changers or oil flow relay, is a monitoring device for in-
sulating liquid-filled tap changers with conservator. It protects the tap
changer and the transformer from damage. The monitoring relay re-
sponds to excessive oil flow in the direction of the conservator and
generates a signal disconnecting the tap changer and the transformer
immediately from voltage supply.
For further information on the additional devices, please ask for special reference material.
41
Elektromotoren und Gerätebau Barleben GmbH
The oil flow indicator operates at a very low service pressure and
can therefore be installed even in oil return pipes where the oil flow is
caused by the oil pipe gradient.
For further information on the additional devices, please ask for special reference material.
42
15 Breathing Buffer Box
For further information on the additional devices, please ask for special reference material.
43
Elektromotoren und
Gerätebau Barleben GmbH
Hamburg
EMB GmbH
Otto-von-Guericke-Allee 12
D-39179 Barleben | Germany Hannover
Barleben Berlin
Magdeburg
Email: info@emb-online.de
Frankfurt
Website: www.emb-online.de
www.buchholzrelay.com
München
Due to technical improvement of our products, the information contained in this catalogue is subject to change without notice. We would
like to apologize for printing errors which have not been found despite intensive proof-ready. We assume no liability for such errors. Thank
you for your understanding.
Winding thermometer
Position in the dimension CT036
drawing:
Manufacturer: MESSKO
Type: MT-STW160F2/4/8m `
Operating instructions: Operating instructions for
WINDING THERMOSTAT
ATTENTION
For the contact types of the protective and monitoring devices, please see the circuit
diagram.
WARNING
Before connection or manipulation at the contacts (terminals), verify voltage freeness on
all sides and all pins.
Switching signal
Direct display
Transformer at the
transformer Self-sufficient and non-energy dependent pointer thermometer 3 Winding Temperature sensor ZT-F2.1 for pointer thermometer 7 Signal converter TT30: maximum flexibility in adaptation and a 10 Electronic Indicator EI 100/160
featuring the following requirement profile: maximum variety of signals
1 2 The ZT-F2.1 contains all heating elements required for representation The “electronic indicator EI 100/160” shows the temperature or a percentage
- robust and long-lived technology (Bourdon tube) of the winding temperature within the transformer. The temperature The TT30 signal converter’s task is the conversion of sensor signals output of any sensor. The information is indicated with an analog indicator in-
- functionally reliable and accurate gradient between winding and coolant depends on the current pre- into analog and digital process signals. The TT30’s user-friendly design strument and a digital LCD display. The input signal is 4 … 20 mA. The voltage
Pointer thermometer - vibration-proof and outdoor-proof sent in the winding at any given time. This winding current is propor- allows quick and easy adaptation – both mechanical and electronic supply is 24 V DC.
for oil and winding
temperature
- easy to install and commission tional to the secondary current of a current transformer mounted to a – to even the most diverse types of sensors. It’s so easy to The EI 100 can be mounted with a holder (figure 1) or with a support (figure 2) in Figure 1 EI with holder
- low-maintenance transformer. handle it can even be integrated into existing systems at a later date, the switchgear cubicle. The EI 160 (figure 3) can be mounted in the switchgear
Figure 2 EI with support
The secondary transformer current feeds a heating resistor contained without any need for modification work. That way, even older systems cubicle or directly on the transformer.
Pointer thermometer for oil temperature
Winding temperature Oil temperature 1 MT-ST160F / MT-STW160F2 (Ø 160 mm) in the dipper tube of ZT-F2.1, thereby causing a progression of the can be upgraded and made fit for remote measuring display tasks in The EI 100/160 is the ideal supplement for the thermometer with temperature
MT-ST160F; Ø 160 mm
Detection display instrument - in relation to the respective transformer load - to the supervisory room. transmitter (TT = 4 … 20 mA) and can also be used in combination with “signal
The main application of pointer thermometer types MT-ST160F and the oil temperature actually measured. That’s why we call our TT30 concept ‘Retrofit.’ converter TT30.”
Sensor Detection and MT-STW160F2 is temperature monitoring (winding/oil) in power Indication of the mean maximum winding temperature (= thermal The TT30 understands even the most diverse types of sensor signals The measured value can be presented in % or °C depending on the application.
signal output transformers or large-size distribution transformers. They are image) is yielded by this indirect method. which makes TT30 an epitome of versatility for just about any moni-
equipped with micro-switches for external switching processes (ven- Furthermore, the ZT-F2.1 permits the implementation of an additional toring task: be it temperature, position, pressure or flow monitoring
tilation control, alarm, trip) and are quick and easy to install. These sensor for direct mechanical displaying. Setting of the temperature – the TT30 can do it all. Figure 3 EI 160
robust pointer thermometers have been designed specifically for use gradient is a one-time event: it is adjusted only once at the time of Input signals:
under even the most diverse and exacting environmental conditions commissioning, via dip-switches. PT100 (RTD) (3-conductor connection)
3 4 5
(heat, cold, ambient humidity). The measuring system (Bourdon tube, In addition, the ZT-F2.1 supplies a temperature-proportional resis- 4 … 20 mA (2-conductor connection)
capillary tube, sensor) guarantees high-precision temperature displays tance signal, Pt 100 as per DIN IEC 751, for remote measuring value 0 … 20 mA (3-conductor connection) MT-ST160F / MT-STW160F2 Technical data
without any need for re-calibration or readjustments, not even after monitoring. 0 … 5 Volt (3-conductor connection)
Temperature sensor Combi well Mounting well Pointer thermometer for winding temperature Housing (standard) Steel plate, galvanized
decades of use! MT-STW160F2; Ø 160 mm Optional output signals: Cu10 as per ANSI ASME PTC 19.3 or Angle of rotation (angle-of-rotation encoder)
Mounting ring and housing Powder coated, Bayonet fixing ring with Silicone seal
4 … 20 mA. Analog output signals:
Switchgear cubicle Viewing glass Laminated safety glass with UV filter
2 MTA-F100 / MTA-F100W (Ø 100 mm) 0 … 1 mA
Analog input Signal Temperature sensor Brass, bright
4 Combi well for pointer thermometer (oil temperature) 0 … 20 mA (Error signal > 22 mA)
conversion Mounting plate Stainless steel
The functions of pointer thermometer types MTA-F100 and 4 … 20 mA (Error signal < 3.6 mA)
MTA-F100W are generally equivalent to the functions of the pointer As specified under 5), albeit with an integrated measuring shunt 4 … 20 mA (Error signal > 22 mA) Copper capillary with insulating PVC tube;
Signal output, Capillary tube
thermometers specified above. Their smaller size, however, makes Pt100 as per DIN IEC 751 for remote measuring value monitoring. Digital output signals: or additional flexible stainless-steel tube
analog Cable gland M25 brass, nickel-plated
Signal converter them ideally suited for application in switchgear cubicles and small Optional output signals: Cu10 as per ANSI ASME PTC 19.3 or RS485
Signal converter 6 7 or medium-sized distribution transformers. 4 … 20 mA. Relay output
Signal output, Characteristic data
Digital output,
digital
Microswitch setting (switching distance) 5 Mounting well for pointer thermometer (oil temperature) 8 Digital display 1272AT Measuring range -20 ... 140° C or 0 ... 160° C
Analog output RS 485 standard
Pointer thermometer for oil temperature Tolerance Category 1 as per DIN EN 13190
1+2 Narrow circuitry, standard MTA-F100, Ø 100 mm Standard mounting well for installation of the oil thermometer in The digital display types D1272AT PQ144 are used in the digital re- Place of installation Indoors and outdoors, tropic-proof
1 2 3 4 the thermometer pocket as per DIN 42 554. Kick protection against mote display of the oil and/or winding temperatures, and are Ambient temperature -50 … 80°C
mechanical damages. connected with the analog output (PT100 or 4 … 20 mA) of the combi Degree of protection IP55 as per DIN VDE 0470-1
Remote
< 1K min. 6 % min. 6 % well or the ZT-F2.1. Thanks to the ventilation system included, the viewing glass will remain mist-free
indication in the Ventilation
8 9 10 6 Measured value transducer Pt-MU The optional selection of two freely adjustable limit value contacts up to a level of 80 % of relative humidity
Control room control room
and of various different output signals (4 … 20 mA, 0 … 5 V, 0 … 10 V)
Maximum pointer All thermometers are equipped with a resettable maximum pointer in red
1+2 / 3+4 Narrow circuitry The Pt-MU measured value transducer converts the signals of a PT100 for further signal processing is available as well.
Redundant Weight approx. 2.5 kgs (6 metres of capillary line)
1 2 3 4 to a uniform signal proportional to the temperature.
system
The measured value transducer is connected, for example, to the 9 Moving-coil instrument PQ96 / PQ144 Micro-switches
< 1K min. 12 % < 1K PT100 connections on the ZT-F2.1 transformer temperature encoder or
to the combi-mounting well. It conditions the output signals of these The moving-coil instrument types PQ96 and PQ144 are used in the Quantity 1 ... 6 adjustable micro-switches (1 … 4 change-over switches)
Analog output Temperature displays El 100 digital display
devices for further processing by the computer or electrical/electronic analog remote display of the oil and/or winding temperatures, and are Contact load AC: 250 V / 5 A / cos G = 1
Pointer thermometer für winding temperature
010010000101 DC: 250 V / 0.4 A (non-inductive)
MTA-F100W, Ø 100 mm
1001000101100 indication (D1272AT PQ144). The Pt-MU is used where measured connected with the analog output (PT100 or 4 … 20 mA) of the combi
Supervisory room 0111010010010 values must be transmitted over long distances or the transmission well or the ZT-F2.1. 110 V / 0.6 A; 60 V / 1 A; 24 V / 4 A (non-inductive)
path contains interference. Switching interval 6 % of the measuring range
The two output signals (4 … 20 mA and 2 … 10 V) are no-load and Contact material Silver Cadmium Oxide (AgCdO10)
short-circuit proof. The two outputs may not be connected together. Rated insulation voltage AC: 2,500 V / 1 min
SCADA System
An auxiliary voltage (supply voltage: 230 V AC, 45-65 Hz) is required. Switch hysteresis Approx. 5° C
010010000101
1001000101100 Terminals min. 0.25 mm2 / max. 2.5 mm2
0111010010010
TRASY2 – the functional modular system for temperature measuring Pointer thermometer for oil and winding temperature MESSKO® TRASY2 – as flexible as the tasks it manages
Switching signal
Direct display
Transformer at the
transformer Self-sufficient and non-energy dependent pointer thermometer 3 Winding Temperature sensor ZT-F2.1 for pointer thermometer 7 Signal converter TT30: maximum flexibility in adaptation and a 10 Electronic Indicator EI 100/160
featuring the following requirement profile: maximum variety of signals
1 2 The ZT-F2.1 contains all heating elements required for representation The “electronic indicator EI 100/160” shows the temperature or a percentage
- robust and long-lived technology (Bourdon tube) of the winding temperature within the transformer. The temperature The TT30 signal converter’s task is the conversion of sensor signals output of any sensor. The information is indicated with an analog indicator in-
- functionally reliable and accurate gradient between winding and coolant depends on the current pre- into analog and digital process signals. The TT30’s user-friendly design strument and a digital LCD display. The input signal is 4 … 20 mA. The voltage
Pointer thermometer - vibration-proof and outdoor-proof sent in the winding at any given time. This winding current is propor- allows quick and easy adaptation – both mechanical and electronic supply is 24 V DC.
for oil and winding
temperature
- easy to install and commission tional to the secondary current of a current transformer mounted to a – to even the most diverse types of sensors. It’s so easy to The EI 100 can be mounted with a holder (figure 1) or with a support (figure 2) in Figure 1 EI with holder
- low-maintenance transformer. handle it can even be integrated into existing systems at a later date, the switchgear cubicle. The EI 160 (figure 3) can be mounted in the switchgear
Figure 2 EI with support
The secondary transformer current feeds a heating resistor contained without any need for modification work. That way, even older systems cubicle or directly on the transformer.
Pointer thermometer for oil temperature
Winding temperature Oil temperature 1 MT-ST160F / MT-STW160F2 (Ø 160 mm) in the dipper tube of ZT-F2.1, thereby causing a progression of the can be upgraded and made fit for remote measuring display tasks in The EI 100/160 is the ideal supplement for the thermometer with temperature
MT-ST160F; Ø 160 mm
Detection display instrument - in relation to the respective transformer load - to the supervisory room. transmitter (TT = 4 … 20 mA) and can also be used in combination with “signal
The main application of pointer thermometer types MT-ST160F and the oil temperature actually measured. That’s why we call our TT30 concept ‘Retrofit.’ converter TT30.”
Sensor Detection and MT-STW160F2 is temperature monitoring (winding/oil) in power Indication of the mean maximum winding temperature (= thermal The TT30 understands even the most diverse types of sensor signals The measured value can be presented in % or °C depending on the application.
signal output transformers or large-size distribution transformers. They are image) is yielded by this indirect method. which makes TT30 an epitome of versatility for just about any moni-
equipped with micro-switches for external switching processes (ven- Furthermore, the ZT-F2.1 permits the implementation of an additional toring task: be it temperature, position, pressure or flow monitoring
tilation control, alarm, trip) and are quick and easy to install. These sensor for direct mechanical displaying. Setting of the temperature – the TT30 can do it all. Figure 3 EI 160
robust pointer thermometers have been designed specifically for use gradient is a one-time event: it is adjusted only once at the time of Input signals:
under even the most diverse and exacting environmental conditions commissioning, via dip-switches. PT100 (RTD) (3-conductor connection)
3 4 5
(heat, cold, ambient humidity). The measuring system (Bourdon tube, In addition, the ZT-F2.1 supplies a temperature-proportional resis- 4 … 20 mA (2-conductor connection)
capillary tube, sensor) guarantees high-precision temperature displays tance signal, Pt 100 as per DIN IEC 751, for remote measuring value 0 … 20 mA (3-conductor connection) MT-ST160F / MT-STW160F2 Technical data
without any need for re-calibration or readjustments, not even after monitoring. 0 … 5 Volt (3-conductor connection)
Temperature sensor Combi well Mounting well Pointer thermometer for winding temperature Housing (standard) Steel plate, galvanized
decades of use! MT-STW160F2; Ø 160 mm Optional output signals: Cu10 as per ANSI ASME PTC 19.3 or Angle of rotation (angle-of-rotation encoder)
Mounting ring and housing Powder coated, Bayonet fixing ring with Silicone seal
4 … 20 mA. Analog output signals:
Switchgear cubicle Viewing glass Laminated safety glass with UV filter
2 MTA-F100 / MTA-F100W (Ø 100 mm) 0 … 1 mA
Analog input Signal Temperature sensor Brass, bright
4 Combi well for pointer thermometer (oil temperature) 0 … 20 mA (Error signal > 22 mA)
conversion Mounting plate Stainless steel
The functions of pointer thermometer types MTA-F100 and 4 … 20 mA (Error signal < 3.6 mA)
MTA-F100W are generally equivalent to the functions of the pointer As specified under 5), albeit with an integrated measuring shunt 4 … 20 mA (Error signal > 22 mA) Copper capillary with insulating PVC tube;
Signal output, Capillary tube
thermometers specified above. Their smaller size, however, makes Pt100 as per DIN IEC 751 for remote measuring value monitoring. Digital output signals: or additional flexible stainless-steel tube
analog Cable gland M25 brass, nickel-plated
Signal converter them ideally suited for application in switchgear cubicles and small Optional output signals: Cu10 as per ANSI ASME PTC 19.3 or RS485
Signal converter 6 7 or medium-sized distribution transformers. 4 … 20 mA. Relay output
Signal output, Characteristic data
Digital output,
digital
Microswitch setting (switching distance) 5 Mounting well for pointer thermometer (oil temperature) 8 Digital display 1272AT Measuring range -20 ... 140° C or 0 ... 160° C
Analog output RS 485 standard
Pointer thermometer for oil temperature Tolerance Category 1 as per DIN EN 13190
1+2 Narrow circuitry, standard MTA-F100, Ø 100 mm Standard mounting well for installation of the oil thermometer in The digital display types D1272AT PQ144 are used in the digital re- Place of installation Indoors and outdoors, tropic-proof
1 2 3 4 the thermometer pocket as per DIN 42 554. Kick protection against mote display of the oil and/or winding temperatures, and are Ambient temperature -50 … 80°C
mechanical damages. connected with the analog output (PT100 or 4 … 20 mA) of the combi Degree of protection IP55 as per DIN VDE 0470-1
Remote
< 1K min. 6 % min. 6 % well or the ZT-F2.1. Thanks to the ventilation system included, the viewing glass will remain mist-free
indication in the Ventilation
8 9 10 6 Measured value transducer Pt-MU The optional selection of two freely adjustable limit value contacts up to a level of 80 % of relative humidity
Control room control room
and of various different output signals (4 … 20 mA, 0 … 5 V, 0 … 10 V)
Maximum pointer All thermometers are equipped with a resettable maximum pointer in red
1+2 / 3+4 Narrow circuitry The Pt-MU measured value transducer converts the signals of a PT100 for further signal processing is available as well.
Redundant Weight approx. 2.5 kgs (6 metres of capillary line)
1 2 3 4 to a uniform signal proportional to the temperature.
system
The measured value transducer is connected, for example, to the 9 Moving-coil instrument PQ96 / PQ144 Micro-switches
< 1K min. 12 % < 1K PT100 connections on the ZT-F2.1 transformer temperature encoder or
to the combi-mounting well. It conditions the output signals of these The moving-coil instrument types PQ96 and PQ144 are used in the Quantity 1 ... 6 adjustable micro-switches (1 … 4 change-over switches)
Analog output Temperature displays El 100 digital display
devices for further processing by the computer or electrical/electronic analog remote display of the oil and/or winding temperatures, and are Contact load AC: 250 V / 5 A / cos G = 1
Pointer thermometer für winding temperature
010010000101 DC: 250 V / 0.4 A (non-inductive)
MTA-F100W, Ø 100 mm
1001000101100 indication (D1272AT PQ144). The Pt-MU is used where measured connected with the analog output (PT100 or 4 … 20 mA) of the combi
Supervisory room 0111010010010 values must be transmitted over long distances or the transmission well or the ZT-F2.1. 110 V / 0.6 A; 60 V / 1 A; 24 V / 4 A (non-inductive)
path contains interference. Switching interval 6 % of the measuring range
The two output signals (4 … 20 mA and 2 … 10 V) are no-load and Contact material Silver Cadmium Oxide (AgCdO10)
short-circuit proof. The two outputs may not be connected together. Rated insulation voltage AC: 2,500 V / 1 min
SCADA System
An auxiliary voltage (supply voltage: 230 V AC, 45-65 Hz) is required. Switch hysteresis Approx. 5° C
010010000101
1001000101100 Terminals min. 0.25 mm2 / max. 2.5 mm2
0111010010010
TRASY2 – the functional modular system for temperature measuring Pointer thermometer for oil and winding temperature MESSKO® TRASY2 – as flexible as the tasks it manages
Switching signal
Direct display
Transformer at the
transformer Self-sufficient and non-energy dependent pointer thermometer 3 Winding Temperature sensor ZT-F2.1 for pointer thermometer 7 Signal converter TT30: maximum flexibility in adaptation and a 10 Electronic Indicator EI 100/160
featuring the following requirement profile: maximum variety of signals
1 2 The ZT-F2.1 contains all heating elements required for representation The “electronic indicator EI 100/160” shows the temperature or a percentage
- robust and long-lived technology (Bourdon tube) of the winding temperature within the transformer. The temperature The TT30 signal converter’s task is the conversion of sensor signals output of any sensor. The information is indicated with an analog indicator in-
- functionally reliable and accurate gradient between winding and coolant depends on the current pre- into analog and digital process signals. The TT30’s user-friendly design strument and a digital LCD display. The input signal is 4 … 20 mA. The voltage
Pointer thermometer - vibration-proof and outdoor-proof sent in the winding at any given time. This winding current is propor- allows quick and easy adaptation – both mechanical and electronic supply is 24 V DC.
for oil and winding
temperature
- easy to install and commission tional to the secondary current of a current transformer mounted to a – to even the most diverse types of sensors. It’s so easy to The EI 100 can be mounted with a holder (figure 1) or with a support (figure 2) in Figure 1 EI with holder
- low-maintenance transformer. handle it can even be integrated into existing systems at a later date, the switchgear cubicle. The EI 160 (figure 3) can be mounted in the switchgear
Figure 2 EI with support
The secondary transformer current feeds a heating resistor contained without any need for modification work. That way, even older systems cubicle or directly on the transformer.
Pointer thermometer for oil temperature
Winding temperature Oil temperature 1 MT-ST160F / MT-STW160F2 (Ø 160 mm) in the dipper tube of ZT-F2.1, thereby causing a progression of the can be upgraded and made fit for remote measuring display tasks in The EI 100/160 is the ideal supplement for the thermometer with temperature
MT-ST160F; Ø 160 mm
Detection display instrument - in relation to the respective transformer load - to the supervisory room. transmitter (TT = 4 … 20 mA) and can also be used in combination with “signal
The main application of pointer thermometer types MT-ST160F and the oil temperature actually measured. That’s why we call our TT30 concept ‘Retrofit.’ converter TT30.”
Sensor Detection and MT-STW160F2 is temperature monitoring (winding/oil) in power Indication of the mean maximum winding temperature (= thermal The TT30 understands even the most diverse types of sensor signals The measured value can be presented in % or °C depending on the application.
signal output transformers or large-size distribution transformers. They are image) is yielded by this indirect method. which makes TT30 an epitome of versatility for just about any moni-
equipped with micro-switches for external switching processes (ven- Furthermore, the ZT-F2.1 permits the implementation of an additional toring task: be it temperature, position, pressure or flow monitoring
tilation control, alarm, trip) and are quick and easy to install. These sensor for direct mechanical displaying. Setting of the temperature – the TT30 can do it all. Figure 3 EI 160
robust pointer thermometers have been designed specifically for use gradient is a one-time event: it is adjusted only once at the time of Input signals:
under even the most diverse and exacting environmental conditions commissioning, via dip-switches. PT100 (RTD) (3-conductor connection)
3 4 5
(heat, cold, ambient humidity). The measuring system (Bourdon tube, In addition, the ZT-F2.1 supplies a temperature-proportional resis- 4 … 20 mA (2-conductor connection)
capillary tube, sensor) guarantees high-precision temperature displays tance signal, Pt 100 as per DIN IEC 751, for remote measuring value 0 … 20 mA (3-conductor connection) MT-ST160F / MT-STW160F2 Technical data
without any need for re-calibration or readjustments, not even after monitoring. 0 … 5 Volt (3-conductor connection)
Temperature sensor Combi well Mounting well Pointer thermometer for winding temperature Housing (standard) Steel plate, galvanized
decades of use! MT-STW160F2; Ø 160 mm Optional output signals: Cu10 as per ANSI ASME PTC 19.3 or Angle of rotation (angle-of-rotation encoder)
Mounting ring and housing Powder coated, Bayonet fixing ring with Silicone seal
4 … 20 mA. Analog output signals:
Switchgear cubicle Viewing glass Laminated safety glass with UV filter
2 MTA-F100 / MTA-F100W (Ø 100 mm) 0 … 1 mA
Analog input Signal Temperature sensor Brass, bright
4 Combi well for pointer thermometer (oil temperature) 0 … 20 mA (Error signal > 22 mA)
conversion Mounting plate Stainless steel
The functions of pointer thermometer types MTA-F100 and 4 … 20 mA (Error signal < 3.6 mA)
MTA-F100W are generally equivalent to the functions of the pointer As specified under 5), albeit with an integrated measuring shunt 4 … 20 mA (Error signal > 22 mA) Copper capillary with insulating PVC tube;
Signal output, Capillary tube
thermometers specified above. Their smaller size, however, makes Pt100 as per DIN IEC 751 for remote measuring value monitoring. Digital output signals: or additional flexible stainless-steel tube
analog Cable gland M25 brass, nickel-plated
Signal converter them ideally suited for application in switchgear cubicles and small Optional output signals: Cu10 as per ANSI ASME PTC 19.3 or RS485
Signal converter 6 7 or medium-sized distribution transformers. 4 … 20 mA. Relay output
Signal output, Characteristic data
Digital output,
digital
Microswitch setting (switching distance) 5 Mounting well for pointer thermometer (oil temperature) 8 Digital display 1272AT Measuring range -20 ... 140° C or 0 ... 160° C
Analog output RS 485 standard
Pointer thermometer for oil temperature Tolerance Category 1 as per DIN EN 13190
1+2 Narrow circuitry, standard MTA-F100, Ø 100 mm Standard mounting well for installation of the oil thermometer in The digital display types D1272AT are used in the digital remote Place of installation Indoors and outdoors, tropic-proof
1 2 3 4 the thermometer pocket as per DIN 42 554. Kick protection against display of the oil and/or winding temperatures, and are connected Ambient temperature -50 … 80°C
mechanical damages. with the analog output (PT100 or 4 … 20 mA) of the combi well or Degree of protection IP55 as per DIN VDE 0470-1
Remote
< 1K min. 6 % min. 6 % the ZT-F2.1. Thanks to the ventilation system included, the viewing glass will remain mist-free
indication in the Ventilation
8 9 10 6 Measured value transducer Pt-MU The optional selection of two freely adjustable limit value contacts up to a level of 80 % of relative humidity
Control room control room
and of various different output signals (4 … 20 mA, 0 … 5 V, 0 … 10 V)
Maximum pointer All thermometers are equipped with a resettable maximum pointer in red
1+2 / 3+4 Narrow circuitry The Pt-MU measured value transducer converts the signals of a PT100 for further signal processing is available as well.
Redundant Weight approx. 2.5 kgs (6 metres of capillary line)
1 2 3 4 to a uniform signal proportional to the temperature.
system
The measured value transducer is connected, for example, to the 9 Moving-coil instrument PQ96 / PQ144 Micro-switches
< 1K min. 12 % < 1K PT100 connections on the ZT-F2.1 transformer temperature encoder or
to the combi-mounting well. It conditions the output signals of these The moving-coil instrument types PQ96 and PQ144 are used in the Quantity 1 ... 6 adjustable micro-switches (1 … 4 change-over switches)
Analog output Temperature displays El 100 digital display
devices for further processing by the computer or electrical/electronic analog remote display of the oil and/or winding temperatures, and are Contact load AC: 250 V / 5 A / cos G = 1
Pointer thermometer für winding temperature
010010000101 DC: 250 V / 0.4 A (non-inductive)
MTA-F100W, Ø 100 mm
1001000101100 indication (D1272AT PQ144). The Pt-MU is used where measured connected with the analog output (PT100 or 4 … 20 mA) of the combi
Supervisory room 0111010010010 values must be transmitted over long distances or the transmission well or the ZT-F2.1. 110 V / 0.6 A; 60 V / 1 A; 24 V / 4 A (non-inductive)
path contains interference. Switching interval 6 % of the measuring range
The two output signals (4 … 20 mA and 2 … 10 V) are no-load and Contact material Silver Cadmium Oxide (AgCdO10)
short-circuit proof. The two outputs may not be connected together. Rated insulation voltage AC: 2,500 V / 1 min
SCADA System
An auxiliary voltage (supply voltage: 230 V AC, 45-65 Hz) is required. Switch hysteresis Approx. 5° C
010010000101
1001000101100 Terminals min. 0.25 mm2 / max. 2.5 mm2
0111010010010
TRASY2 – the functional modular system for temperature measuring Pointer thermometer for oil and winding temperature MESSKO® TRASY2 – as flexible as the tasks it manages
Switching signal
Direct display
Transformer at the
transformer Self-sufficient and non-energy dependent pointer thermometer 3 Winding Temperature sensor ZT-F2.1 for pointer thermometer 7 Signal converter TT30: maximum flexibility in adaptation and a 10 Electronic Indicator EI 100/160
featuring the following requirement profile: maximum variety of signals
1 2 The ZT-F2.1 contains all heating elements required for representation The “electronic indicator EI 100/160” shows the temperature or a percentage
- robust and long-lived technology (Bourdon tube) of the winding temperature within the transformer. The temperature The TT30 signal converter’s task is the conversion of sensor signals output of any sensor. The information is indicated with an analog indicator in-
- functionally reliable and accurate gradient between winding and coolant depends on the current pre- into analog and digital process signals. The TT30’s user-friendly design strument and a digital LCD display. The input signal is 4 … 20 mA. The voltage
Pointer thermometer - vibration-proof and outdoor-proof sent in the winding at any given time. This winding current is propor- allows quick and easy adaptation – both mechanical and electronic supply is 24 V DC.
for oil and winding
temperature
- easy to install and commission tional to the secondary current of a current transformer mounted to a – to even the most diverse types of sensors. It’s so easy to The EI 100 can be mounted with a holder (figure 1) or with a support (figure 2) in Figure 1 EI with holder
- low-maintenance transformer. handle it can even be integrated into existing systems at a later date, the switchgear cubicle. The EI 160 (figure 3) can be mounted in the switchgear
Figure 2 EI with support
The secondary transformer current feeds a heating resistor contained without any need for modification work. That way, even older systems cubicle or directly on the transformer.
Pointer thermometer for oil temperature
Winding temperature Oil temperature 1 MT-ST160F / MT-STW160F2 (Ø 160 mm) in the dipper tube of ZT-F2.1, thereby causing a progression of the can be upgraded and made fit for remote measuring display tasks in The EI 100/160 is the ideal supplement for the thermometer with temperature
MT-ST160F; Ø 160 mm
Detection display instrument - in relation to the respective transformer load - to the supervisory room. transmitter (TT = 4 … 20 mA) and can also be used in combination with “signal
The main application of pointer thermometer types MT-ST160F and the oil temperature actually measured. That’s why we call our TT30 concept ‘Retrofit.’ converter TT30.”
Sensor Detection and MT-STW160F2 is temperature monitoring (winding/oil) in power Indication of the mean maximum winding temperature (= thermal The TT30 understands even the most diverse types of sensor signals The measured value can be presented in % or °C depending on the application.
signal output transformers or large-size distribution transformers. They are image) is yielded by this indirect method. which makes TT30 an epitome of versatility for just about any moni-
equipped with micro-switches for external switching processes (ven- Furthermore, the ZT-F2.1 permits the implementation of an additional toring task: be it temperature, position, pressure or flow monitoring
tilation control, alarm, trip) and are quick and easy to install. These sensor for direct mechanical displaying. Setting of the temperature – the TT30 can do it all. Figure 3 EI 160
robust pointer thermometers have been designed specifically for use gradient is a one-time event: it is adjusted only once at the time of Input signals:
under even the most diverse and exacting environmental conditions commissioning, via dip-switches. PT100 (RTD) (3-conductor connection)
3 4 5
(heat, cold, ambient humidity). The measuring system (Bourdon tube, In addition, the ZT-F2.1 supplies a temperature-proportional resis- 4 … 20 mA (2-conductor connection)
capillary tube, sensor) guarantees high-precision temperature displays tance signal, Pt 100 as per DIN IEC 751, for remote measuring value 0 … 20 mA (3-conductor connection) MT-ST160F / MT-STW160F2 Technical data
without any need for re-calibration or readjustments, not even after monitoring. 0 … 5 Volt (3-conductor connection)
Temperature sensor Combi well Mounting well Pointer thermometer for winding temperature Housing (standard) Steel plate, galvanized
decades of use! MT-STW160F2; Ø 160 mm Optional output signals: Cu10 as per ANSI ASME PTC 19.3 or Angle of rotation (angle-of-rotation encoder)
Mounting ring and housing Powder coated, Bayonet fixing ring with Silicone seal
4 … 20 mA. Analog output signals:
Switchgear cubicle Viewing glass Laminated safety glass with UV filter
2 MTA-F100 / MTA-F100W (Ø 100 mm) 0 … 1 mA
Analog input Signal Temperature sensor Brass, bright
4 Combi well for pointer thermometer (oil temperature) 0 … 20 mA (Error signal > 22 mA)
conversion Mounting plate Stainless steel
The functions of pointer thermometer types MTA-F100 and 4 … 20 mA (Error signal < 3.6 mA)
MTA-F100W are generally equivalent to the functions of the pointer As specified under 5), albeit with an integrated measuring shunt 4 … 20 mA (Error signal > 22 mA) Copper capillary with insulating PVC tube;
Signal output, Capillary tube
thermometers specified above. Their smaller size, however, makes Pt100 as per DIN IEC 751 for remote measuring value monitoring. Digital output signals: or additional flexible stainless-steel tube
analog Cable gland M25 brass, nickel-plated
Signal converter them ideally suited for application in switchgear cubicles and small Optional output signals: Cu10 as per ANSI ASME PTC 19.3 or RS485
Signal converter 6 7 or medium-sized distribution transformers. 4 … 20 mA. Relay output
Signal output, Characteristic data
Digital output,
digital
Microswitch setting (switching distance) 5 Mounting well for pointer thermometer (oil temperature) 8 Digital display 1272AT Measuring range -20 ... 140° C or 0 ... 160° C
Analog output RS 485 standard
Pointer thermometer for oil temperature Tolerance Category 1 as per DIN EN 13190
1+2 Narrow circuitry, standard MTA-F100, Ø 100 mm Standard mounting well for installation of the oil thermometer in The digital display types D1272AT PQ144 are used in the digital re- Place of installation Indoors and outdoors, tropic-proof
1 2 3 4 the thermometer pocket as per DIN 42 554. Kick protection against mote display of the oil and/or winding temperatures, and are Ambient temperature -50 … 80°C
mechanical damages. connected with the analog output (PT100 or 4 … 20 mA) of the combi Degree of protection IP55 as per DIN VDE 0470-1
Remote
< 1K min. 6 % min. 6 % well or the ZT-F2.1. Thanks to the ventilation system included, the viewing glass will remain mist-free
indication in the Ventilation
8 9 10 6 Measured value transducer Pt-MU The optional selection of two freely adjustable limit value contacts up to a level of 80 % of relative humidity
Control room control room
and of various different output signals (4 … 20 mA, 0 … 5 V, 0 … 10 V)
Maximum pointer All thermometers are equipped with a resettable maximum pointer in red
1+2 / 3+4 Narrow circuitry The Pt-MU measured value transducer converts the signals of a PT100 for further signal processing is available as well.
Redundant Weight approx. 2.5 kgs (6 metres of capillary line)
1 2 3 4 to a uniform signal proportional to the temperature.
system
The measured value transducer is connected, for example, to the 9 Moving-coil instrument PQ96 / PQ144 Micro-switches
< 1K min. 12 % < 1K PT100 connections on the ZT-F2.1 transformer temperature encoder or
to the combi-mounting well. It conditions the output signals of these The moving-coil instrument types PQ96 and PQ144 are used in the Quantity 1 ... 6 adjustable micro-switches (1 … 4 change-over switches)
Analog output Temperature displays El 100 digital display
devices for further processing by the computer or electrical/electronic analog remote display of the oil and/or winding temperatures, and are Contact load AC: 250 V / 5 A / cos G = 1
Pointer thermometer für winding temperature
010010000101 DC: 250 V / 0.4 A (non-inductive)
MTA-F100W, Ø 100 mm
1001000101100 indication (D1272AT PQ144). The Pt-MU is used where measured connected with the analog output (PT100 or 4 … 20 mA) of the combi
Supervisory room 0111010010010 values must be transmitted over long distances or the transmission well or the ZT-F2.1. 110 V / 0.6 A; 60 V / 1 A; 24 V / 4 A (non-inductive)
path contains interference. Switching interval 6 % of the measuring range
The two output signals (4 … 20 mA and 2 … 10 V) are no-load and Contact material Silver Cadmium Oxide (AgCdO10)
short-circuit proof. The two outputs may not be connected together. Rated insulation voltage AC: 2,500 V / 1 min
SCADA System
An auxiliary voltage (supply voltage: 230 V AC, 45-65 Hz) is required. Switch hysteresis Approx. 5° C
010010000101
1001000101100 Terminals min. 0.25 mm2 / max. 2.5 mm2
0111010010010
www.messko.com
Messko GmbH
Gewerbegebiet An den Drei Hasen
Phone:
Fax:
+49 (0)6171 / 6398 - 0
+49 (0)6171 / 6398 - 98
www.messko.com
MESSKO® TRASY2 Type Series
Messko-Platz 1 E-mail: info@messko.com
D-61440 Oberursel, Germany Internet: www.messko.com Temperature Measuring Systems for Transformers
Bild 1/Fig.1
2
Français Español
1. Descriptif du produit 1. Descripción del producto
La Sonde Double est utilisée avec un thermomètre à aiguille La Vaina Doble se usa en combinación con un termómetro
et sert à la transmission à distance des valeurs mesurées. La indicador y sirve para la transmisión del valor de medición
sonde thermique (3) d'un thermomètre à aiguille est engagée de la temperatura. La sonda térmica (3) de un termómetro
dans la Sonde Double ; ainsi, la température est affichée sur indicador se introduce en la Vaina Doble, de esta manera se
place sur le thermomètre à aiguille. Un indicateur de indica in situ la temperatura en el termómetro indicador.
température électrique est raccordé sur la résistance de Para la transmisión remota se conecta un indicador de
précision PT100 intégrée (4) pour la transmission à distance. temperatura eléctrico a la resistencia de medición Pt100 (4)
La Sonde Double peut avoir une sortie analogique 4..20mA à integrada. En lugar de la salida Pt100 la Vaina Doble puede
la place de la sortie PT100. contener una salida análoga 4..20mA
3. Montage 3. Montaje
La Sonde Double convient à un montage dans une La Vaina Doble está diseñada para montarla en la bolsa para
poche de thermomètre prévue par la norme DIN 42 554. termómetros según DIN 42 554. Llenar 2/3 de la bolsa para
Remplir au 2/3 d'huile la poche de thermomètre. Dévisser la termómetros con aceite. Desenroscar la unión G1”(2) de la
fermeture G1” (2) du manchon combiné et la visser dans la Vaina Doble y enroscarla en la bolsa para termómetros.
poche de thermomètre. Enfoncer la Sonde Double dans la Introducir la Vaina Doble en la bolsa para termómetros,
poche de thermomètre, ajuster et fixer à l'aide d'un alinearla correctamente y fijarla con la contratuerca.
contre-écrou. Desenroscar la tapa. Pasar el cable para la conexión Pt100 a
IMPORTANT ! ¡ IMPORTANTE !
N'ajuster ou ne faire pivoter la sonde double que Alinear correctamente o girar la Vaina Doble
si le contre-écrou est desserré. únicamente cuando la contratuerca esté
Dévisser le couvercle. Faire passer le câble de connexion du través de una boquilla de paso PG16 y onectarlo teniendo
PT100 à travers une traversée PG16 et le raccorder en en cuenta las prescripciones VDE véase Fig.2 y 3. Insertar la
respectant les règles VDE (voir Fig.2 et 3). Introduire la sonda del termómetro indicador a través de la otra boquilla
sonde du thermomètre à travers l'autre traversée PG16 et la de paso PG16 e introducirla ~ 50 cm. Introducir la sonda
faire passer jusqu'à environ 50 cm. Pousser la sonde à fond hasta el tope en la Vaina Doble ~ 210 mm de profundidad.
dans la Sonde Double à environ 210 mm de profondeur. Retirar la conducción capilar. Fijar la boquilla de paso PG16.
Retirer le tube capillaire. Serrer la traversée PG16. Remonter Montar de nuevo la tapa.
le couvercle. 4. Mediciones comparativas, controles
4. Mesures comparatives, contrôles Después de un período de calentamiento de 30 minutos
Après avoir réchauffé le dispositif pendant 30 minutes, comparar el valor del termómetro indicador yel del
comparer l'indication du thermomètre à aiguille et l'affichage indicador electrónico. Las indicaciones deberían entrar
électronique. Les indications doivent se situer dans le cadre en el margen de tolerancia de ambos aparatos.
des tolérances des deux appareils.
5. Servicio posventa
5. Maintenance En el caso de que con las medidas mencionadas no se
Si les mesures préconisées demeurent infructueuses, veuillez consiguieran los objetivos deseados, les rogamos se dirijan
vous adresser à notre usine. a nuestra fábrica.
6. Entretien 6. Mantenimiento
La Sonde Double est sans entretien. La Vaina Doble no precisa mantenimiento.
7.1 Raccordement / Conexión 7.2 Raccordement / Conexión
2 Système bifilaire / sistema a 2 cond.
Trou dínstallation pour thermomètre / Blindage / Blindaje Trou dínstallation pour thermomètre /
Abertura de instalación para Abertura de instalación para termómetro
termómetro
1 Ligne de mesure/conductor de
medición
Système à 3 fils / sistema a 3 cond.
Blindage / Blindaje Blindage
Bornes/
Bornes/
1 Ligne de mesure/conductor de medición bornes 1 + Ligne de mesure 4..20mA
bornes 2 - Ligne de mesure 4..20mA
2 Ligne de mesure/conductor de medición
3 Ligne de comp. / conductor de comp.
Système à 4 fils / sistema a 4 cond. Blindaje
Blindage + 1. Ligne de compensation/ 1 + conductor de medición
Blindaje+ 1. conductor de compens. 2 - conductor de medición
1 Ligne de mesure/conductor de medición
2 Ligne de mesure/conductor de medición
3 2.Ligne de comp./2.conductor de comp.
Fig.2 Fig.3
3
Deutsch/English Français/Español
Technische Daten Caractéristiques techniques
Werkstoffe Matériaux
Gehäuse Aluminium, Druckguß Boîtier Aluminium, coulé sous pression
Hülse / Verschraubung Messing, blank Gaine / Fermeture Laiton, mat
filetée
Kabelverschraubung Messing, vernickelt
Passe-câble à vis Laiton, nickelé
Pt100 Ausgang Meßwiderstand nach IEC 751
Sortie PT100 Résistance de précision IEC 751
4
www.messko.com
Messko GmbH
Gewerbegebiet An den Drei Hasen
Phone:
Fax:
+49 (0)6171 / 6398 - 0
+49 (0)6171 / 6398 - 98
www.messko.com
MESSKO® COMPACT Type Series
Messko-Platz 1 E-mail: info@messko.com
D-61440 Oberursel, Germany Internet: www.messko.com Temperature Measuring Systems for Transformers
Capillary tube Copper capillary with insulating PVC tube; or additional flexible
stainless-steel tube
Characteristic data
Ventilation Thanks to the ventilation system included, the viewing glass will
remain mist-free up to a level of 80 % of relative humidity
Maximum pointer All thermometers are equipped with a resettable maximum pointer in red
Weight approx. 2.5 kgs (6 metres of capillary line)
Micro-switches
Switching signal
Direct display
Highlights at the 1 MT-ST160SK (TT) / MT-ST160W(R) (TT) (Ø 160 mm) TT30 understands even the most diverse types of sensor signals
Transformer transformer which makes TT30 an epitome of versatility for just about any mon-
• extremely long-lived and functionally reliable The main application of pointer thermometer types MT-ST160SK (TT) itoring task: be it temperature, position, pressure or flow monitoring
• Bourdon tube: precise and robust, without additional mechanical elements 1 1 and MT-ST160W(R) (TT) is temperature monitoring (winding/oil) in – the TT30 can do it all.
• Oil & winding temperature remote indication without additional devices power transformers or large-size distribution transformers. They are
• quick and easy gradient setting with fixed resistors (thermal image) equipped with micro-switches for external switching processes (ven- Input signals Analog output signals
• ambient temperature compensation: no modification required – tilation control, alarm, trip) and are quick and easy to install. These PT100 (RTD) (3-conductor 0 ... 1 mA
not even for extreme environments robust pointer thermometers have been designed specifically for use connection) 0 ... 20 mA (Error signal > 22 mA)
• output signal: 4 … 20 mA under even the most diverse and exacting environmental conditions 4 ... 20 mA (2-conductor 4 ... 20 mA (Error signal < 3.6 mA)
• in combination with the signal converter: (heat, cold, ambient humidity). The measuring system (Bourdon tube, connection) 4 ... 20 mA (Error signal > 22 mA)
analog signals: 0 … 1 mA, 0 … 20 mA, 4 … 20 mA; capillary tube, sensor) guarantees high-precision temperature displays 0 ... 20 mA (3-conductor Digital output signals
relay output; digital signals: RS 485 Oil temperature Winding temperature without any need for re-calibration or readjustments, not even after connection) RS485
• no need of re-adjustments and/or re-calibration decades of use! 0 ... 5 V (3-conductor Relay output
connection)
The detecting element
The detecting element is normally angled at 60°, with an installa- 5 Signal converter IgT-MU
tionlengh of 150 mm and doubled threaded union. The detecting
element and the thread are made out of brass (G1B). The IgT-MU signal converter is used to shape and isolate a direct
current to form an injected direct current and/or a DC voltage
Other dimensions and materials are available on request. signal.
Galvanic isolation is performed by an optocoupler. Both outputs are
Microswitch setting (switching distance) stable at no load and short-circuiting.
Input signals Output signals
1+2 Narrow setting, standard 1+2 / 3+4 Narrow setting 4 ... 20 mA (2-wire connection) 1 ... 5 VDC; 4 ... 20 mA
Signal 0 ... 10 mA; 0...10 VDC
Switchgear cubicle
conversion 1 2 3 4 1 2 3 4 0 ... 5 VDC; 0 ... 20 mA
Switching signal
Direct display
Highlights at the 1 MT-ST160SK (TT) / MT-ST160W(R) (TT) (Ø 160 mm) TT30 understands even the most diverse types of sensor signals
Transformer transformer which makes TT30 an epitome of versatility for just about any mon-
• extremely long-lived and functionally reliable The main application of pointer thermometer types MT-ST160SK (TT) itoring task: be it temperature, position, pressure or flow monitoring
• Bourdon tube: precise and robust, without additional mechanical elements 1 1 and MT-ST160W(R) (TT) is temperature monitoring (winding/oil) in – the TT30 can do it all.
• Oil & winding temperature remote indication without additional devices power transformers or large-size distribution transformers. They are
• quick and easy gradient setting with fixed resistors (thermal image) equipped with micro-switches for external switching processes (ven- Input signals Analog output signals
• ambient temperature compensation: no modification required – tilation control, alarm, trip) and are quick and easy to install. These PT100 (RTD) (3-conductor 0 ... 1 mA
not even for extreme environments robust pointer thermometers have been designed specifically for use connection) 0 ... 20 mA (Error signal > 22 mA)
• output signal: 4 … 20 mA under even the most diverse and exacting environmental conditions 4 ... 20 mA (2-conductor 4 ... 20 mA (Error signal < 3.6 mA)
• in combination with the signal converter: (heat, cold, ambient humidity). The measuring system (Bourdon tube, connection) 4 ... 20 mA (Error signal > 22 mA)
analog signals: 0 … 1 mA, 0 … 20 mA, 4 … 20 mA; capillary tube, sensor) guarantees high-precision temperature displays 0 ... 20 mA (3-conductor Digital output signals
relay output; digital signals: RS 485 Oil temperature Winding temperature without any need for re-calibration or readjustments, not even after connection) RS485
• no need of re-adjustments and/or re-calibration decades of use! 0 ... 5 V (3-conductor Relay output
connection)
The detecting element
The detecting element is normally angled at 60°, with an installa- 5 Signal converter IgT-MU
tionlengh of 150 mm and doubled threaded union. The detecting
element and the thread are made out of brass (G1B). The IgT-MU signal converter is used to shape and isolate a direct
current to form an injected direct current and/or a DC voltage
Other dimensions and materials are available on request. signal.
Galvanic isolation is performed by an optocoupler. Both outputs are
Microswitch setting (switching distance) stable at no load and short-circuiting.
Input signals Output signals
1+2 Narrow setting, standard 1+2 / 3+4 Narrow setting 4 ... 20 mA (2-wire connection) 1 ... 5 VDC; 4 ... 20 mA
Signal 0 ... 10 mA; 0...10 VDC
Switchgear cubicle
conversion 1 2 3 4 1 2 3 4 0 ... 5 VDC; 0 ... 20 mA
Switching signal
Direct display
Highlights at the 1 MT-ST160SK (TT) / MT-ST160W(R) (TT) (Ø 160 mm) TT30 understands even the most diverse types of sensor signals
Transformer transformer which makes TT30 an epitome of versatility for just about any mon-
• extremely long-lived and functionally reliable The main application of pointer thermometer types MT-ST160SK (TT) itoring task: be it temperature, position, pressure or flow monitoring
• Bourdon tube: precise and robust, without additional mechanical elements 1 1 and MT-ST160W(R) (TT) is temperature monitoring (winding/oil) in – the TT30 can do it all.
• Oil & winding temperature remote indication without additional devices power transformers or large-size distribution transformers. They are
• quick and easy gradient setting with fixed resistors (thermal image) equipped with micro-switches for external switching processes (ven- Input signals Analog output signals
• ambient temperature compensation: no modification required – tilation control, alarm, trip) and are quick and easy to install. These PT100 (RTD) (3-conductor 0 ... 1 mA
not even for extreme environments robust pointer thermometers have been designed specifically for use connection) 0 ... 20 mA (Error signal > 22 mA)
• output signal: 4 … 20 mA under even the most diverse and exacting environmental conditions 4 ... 20 mA (2-conductor 4 ... 20 mA (Error signal < 3.6 mA)
• in combination with the signal converter: (heat, cold, ambient humidity). The measuring system (Bourdon tube, connection) 4 ... 20 mA (Error signal > 22 mA)
analog signals: 0 … 1 mA, 0 … 20 mA, 4 … 20 mA; capillary tube, sensor) guarantees high-precision temperature displays 0 ... 20 mA (3-conductor Digital output signals
relay output; digital signals: RS 485 Oil temperature Winding temperature without any need for re-calibration or readjustments, not even after connection) RS485
• no need of re-adjustments and/or re-calibration decades of use! 0 ... 5 V (3-conductor Relay output
connection)
The detecting element
The detecting element is normally angled at 60°, with an installa- 5 Signal converter IgT-MU
tionlengh of 150 mm and doubled threaded union. The detecting
element and the thread are made out of brass (G1B). The IgT-MU signal converter is used to shape and isolate a direct
current to form an injected direct current and/or a DC voltage
Other dimensions and materials are available on request. signal.
Galvanic isolation is performed by an optocoupler. Both outputs are
Microswitch setting (switching distance) stable at no load and short-circuiting.
Input signals Output signals
1+2 Narrow setting, standard 1+2 / 3+4 Narrow setting 4 ... 20 mA (2-wire connection) 1 ... 5 VDC; 4 ... 20 mA
Signal 0 ... 10 mA; 0...10 VDC
Switchgear cubicle
conversion 1 2 3 4 1 2 3 4 0 ... 5 VDC; 0 ... 20 mA
Capillary tube Copper capillary with insulating PVC tube; or additional flexible
stainless-steel tube
Characteristic data
Ventilation Thanks to the ventilation system included, the viewing glass will
remain mist-free up to a level of 80 % of relative humidity
Maximum pointer All thermometers are equipped with a resettable maximum pointer in red
Weight approx. 2.5 kgs (6 metres of capillary line)
Micro-switches
Capillary tube Copper capillary with insulating PVC tube; or additional flexible
stainless-steel tube
Characteristic data
Ventilation Thanks to the ventilation system included, the viewing glass will
remain mist-free up to a level of 80 % of relative humidity
Maximum pointer All thermometers are equipped with a resettable maximum pointer in red
Weight approx. 2.5 kgs (6 metres of capillary line)
Micro-switches
!
32 16 8 4 2 1
1 2 3 4 1 2 3 4
O O
N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
O O O O
N N N N
1 2 3 4 1 2 3 4
O O
N N
9 Technical Documentation of the Heavy Part and Accessories
Siemens Energy Transformers
ATTENTION
For the contact types of the protective and monitoring devices, please see the circuit
diagram.
WARNING
Before connection or manipulation at the contacts (terminals), verify voltage freeness on
all sides and all pins.
ATTENTION
For the contact types of the protective and monitoring devices, please see the circuit
diagram.
WARNING
Before connection or manipulation at the contacts (terminals), verify voltage freeness on
all sides and all pins.
DANGER
If a pressure relief valve triggers (pressure in the tank too high), there is a high risk of
injury by hot insulation oil spraying out under pressure.
Background
The Qualitrol Series 208/213/216/LPRD00 Large Pressure Relief Devices (PRD)
are designed to be able to relieve large volumes of gas or insulating fluid rapidly
when the pressure inside a transformer reaches a pre-determined limit. The
purpose of this specification sheet is to supply customers with a means of
replicating the factory test procedure, and to offer recommendations for application.
Operating Specifications (unless otherwise noted)
*At rate of rise of 2 psi/sec or greater:
The unit will exhaust rapidly with a loud, percussive “bang” and reseal at
approximately one half its normal operating pressure. When testing, allow at least
one hour between operations; the PRD may operate at a lower pressure if re-tested
earlier.
*At rates of rise less than 2 psi/sec the tolerance on the operating pressure doubles
and the unit may release pressure slowly (“hiss”) without actuating the indicator or
optional alarm switch.
Verification Testing
The required testing apparatus is detailed on the attached sheet.
Application Recommendations
Qualitrol pressure relief devices are usually mounted in the horizontal position,
topside up. Although the horizontal position is recommended, the device may be
mounted on its side (vertical plane). Any pressure head due to side mounting or to
conservator tanks (approximately 0.5 psi/foot for petroleum based insulating oils)
should be taken into consideration when determining operating pressure, and
allowance should be made for the tolerances of the slower rate of pressure rise. A
tank opening of 5.25 inches or larger is recommended to maximize operational
response. Airflow through a 208/213/216/LPRD00 PRD with an operating pressure
of 10 PSI is approximately 8400 SCFM at 15 PSIG.
There is an optional shield available which allows the discharge flow to be
vented in a single direction.
Mounting the PRD
Tighten the bolts in an alternating pattern and repeat the pattern several times until
the flange is seated to the tank, mounting flange or plate.
IST-053-1
ECN 21879
1/25/01
IST-053-1
IST-053-1
ECN 21879
1/25/01
9 Technical Documentation of the Heavy Part and Accessories
Siemens Energy Transformers
ATTENTION
For the contact types of the protective and monitoring devices, please see the circuit
diagram.
WARNING
We expressly alert you to the danger of fire from the insulating oil. For flashpoint, see
safety data-sheet.
Restricted
Chromatograph Analyse Test Report
色谱分析试验报告
Entrusting party test field Analyse date Implementing standard
委托单位: 试验站 分析日期: 10/24/2022 试验方法标准: IEC60567
Product Number Product type Accepting standard
产品序号: 170801 产品型号: EDUN7554D 接收标准: IEC61181
Oil Name Hydrogen Carbon monoxideCarbon dioxide Methane Ethylene Acetylene Ethane Sum of hydrocarbon Remarks
氢 一氧化碳 二氧化碳 甲烷 乙烯 乙炔 乙烷 烃总和
油 号 H2 uL/L CO uL/L CO2 uL/L CH4 uL/L C2H4 uL/L C2H2 uL/L C2H6 uL/L C1+C2 uL/L 备注
Nynas Libra 0.00 1.01 50.71 0.18 0.00 0.00 0.00 0.18
Restricted
Test Report of Transformers Oil
变压器油试验报告
Entrusting party test field Oil number Sampling position bottom
委托单位: 试验站 油号: Nynas Libra 取样部位: 油罐底部
Product number Product type
产品编号: 457 产品型号: Nynas Libra
Restricted
Chromatograph Analyse Test Report
色谱分析试验报告
Entrusting party test field Analyse date Implementing standard
委托单位: 试验站 分析日期: 11/6/2022 试验方法标准: IEC60567
Product Number Product type Accepting standard
产品序号: 457 产品型号: Nynas Libra 接收标准: IEC61181
Oil Name Hydrogen Carbon monoxideCarbon dioxide Methane Ethylene Acetylene Ethane Sum of hydrocarbon Remarks
氢 一氧化碳 二氧化碳 甲烷 乙烯 乙炔 乙烷 烃总和
油 号 H2 uL/L CO uL/L CO2 uL/L CH4 uL/L C2H4 uL/L C2H2 uL/L C2H6 uL/L C1+C2 uL/L 备注
Nynas Libra 0.00 2.70 101.02 0.19 0.00 0.00 0.00 0.19
Restricted
12 Drawings
Siemens Energy Transformers
12 Drawings
No. Name Drawing No. Sheet Rev.
Dimension drawing of transformer
1. Dimension partlist drawing V04 32 845-01
2. Dimension drawing V04 32 845
3. Nameplate drawing V04 32 849
5. Transportation drawing V04 32 846
6. Temperature control circuit drawing V04 30 911
7. Operating instruction for transformer
18.69
0.050
87.93 12.04
90.88 11.38 14.6
95.11 10.86
v170801
1 2 3 4 5 6 7 8 9 10
A
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
C
Drawing / document description: Schematic diagram
Diagrama esquemático
A Table of contents
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
C 11 Device list
12 Device list-electronic temp. monitor
13 Device list-SEL-2523
14 AC supply and cooling groups
15 Cubicle heating,lighting,outlet
16 220VAC Supply
17 125VDC Supply
18 Cooling control
D
19 Transformer temperature measurement
20 Transformer temperature measurement
21 Transformer protection and signalization
22 Transformer protection and signalization
23 Transformer signalization
24 Transformer signalization
25 Transformer signalization
E
26 Control cabinet
27 Control cabinet
28 Control cabinet
29 Terminal diagram +GH009-X0
30 Terminal diagram +GH009-X1
31 Terminal diagram +GH009-X2
32 Terminal diagram +GH009-X2
F
Parts list
A
Technical
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
Device tag Quantity Description Technical Function Type number Manufacturer Pos
Characteristic
Placement QU
-X0
7 TERMINAL BLOCKS AUXILLIARY AC SUPPLY UK5N PHOENIX 1
-X1
B 3 TERMINAL BLOCKS AC SUPPLY UK35 PHOENIX 1
-X1
1 TERMINAL BLOCKS AC SUPPLY USLKG35N PHOENIX 1
-X1
6 TERMINAL BLOCKS AC SUPPLY UK5N PHOENIX 1
-X2
100 TERMINAL BLOCKS PROTECTION AND SIGNALISATION UT4 PHOENIX 1
-X3
15 TERMINAL BLOCKS FOR MOTOR PHASES AND EARTH UK5N PHOENIX 1
C -X4
8 TERMINAL BLOCKS CUPPENT TRANSFORMERS URTK/S PHOENIX 1
-X5
10 TERMINAL BLOCKS DC SUPPLY UK5N PHOENIX 1
-X6
60 TERMINAL BLOCKS PROTECTION AND SIGNALISATION UT4 PHOENIX 1
-X7
30 TERMINAL BLOCKS PROTECTION AND SIGNALISATION UT4 PHOENIX 1
-X8
20 TERMINAL BLOCKS EARTHING TERMINALS USLKG6N PHOENIX 1
D -X9
20 TERMINAL BLOCKS AC SUPPLY UK5N PHOENIX 1
-X10
15 TERMINAL BLOCKS PROTECTION AND SIGNALISATION UK5N PHOENIX 1
Parts list
A QTY. DEVICE DESCRIPTION LOCATION
DEVICE / DEVICE REFERENCE
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
TC2 TC1
CURRENT TRANSFORMER, 60HZ U U
2X1 1X1
TC2/2X1-2X2: 400/5A; 20VA; CLASS 3
TC1/1X1-1X2: 400/2A; 20VA; CLASS 3
2X2 1X2
C
Manufacturer: NAN JING ZHENGFANG +TR /21.3B
TC3
CURRENT TRANSFORMER, 60HZ u
3X1
TC3/3X1-3X2: 1220/5A; 20VA; CLASS 3
D 3X2
DEVICE LIST
A QTY. DEVICE DESCRIPTION LOCATION DEVICE DEVICE REFERENCE FUNCTION DESCRIPTION
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
Type: DBF2-5Q8
U V W PE
Manufacturer: CHINA XIAN
FAN 0.25KW 1.5A M
3
13 23 33
PE
Manufacturer: EMB
BUCHHOLZ RELAY 14 24 34
WH
BU
RD
BK
Manufacturer: TREETECH
RM
BAG RUPTURE RELAY 13 15 16 6 7 8 14
MBR
1 2 3 10 11 12
10
Manufacturer: QUALITROL
PE
OIL LEVEL INDICATOR
13 11
DEVICE LIST
A QTY. DEVICE DESCRIPTION LOCATION DEVICE DEVICE REFERENCE FUNCTION DESCRIPTION
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
Manufacturer: QUALITROL 12 14 22 24
PE
PRESSURE RELIEF DEVICE 0,55bar P P
2CO CONTACT, MILITARY TYPE CONNECTOR WITH 11 21
CABLE
1
Manufacturer: MESSKO
PE
TEMPERATURE SENSOR
2 3
3
Manufacturer: QUALITROL
PE
TEMPERATURE SENSOR
1 2
E Manufacturer: MESSKO 12 14 22 24 32 34 42 44
PE
OIL TEMPERATURE INDICATOR
11 21 31 41
A Type: MT-STW160F2
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
Manufacturer: MESSKO 12 14 22 24 32 34 42 44
PE
WINDING TEMPERATURE INDICATOR
11 21 31 41
C Manufacturer: STEGO 1
THERMOSTAT Θ
2
Manufacturer: STEGO 1
D HYGROSTAT
2
Manufacturer: STEGO 1
PE
HEATER
E 2
DEVICE LIST
A QTY. DEVICE DESCRIPTION LOCATION DEVICE DEVICE REFERENCE FUNCTION DESCRIPTION
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
Type: 04640.0-00
Manufacturer: RITTAL 1
PE
220 V AC, 50/60Hz, 250W
2
Manufacturer: GUANGZHOU,CHINA 1
Manufacturer: SIEMENS 1 3 5 13 21
THREE POLE CIRCUIT BREAKER
AUXILIARY CONTACT NO/NC 2 4 6 14 22
Manufacturer: SIEMENS 1 3 5 13 21
THREE POLE CIRCUIT BREAKER
AUXILIARY CONTACT NO/NC 2 4 6 14 22
Manufacturer: SIEMENS
2 4 6 14 22
THREE POLE CIRCUIT BREAKER
AUXILIARY CONTACT NO/NC
Type: SIE.5SY4202-7+5ST3010
Manufacturer: SIEMENS 1 3 13 21
DEVICE LIST
A QTY. DEVICE DESCRIPTION LOCATION DEVICE DEVICE REFERENCE FUNCTION DESCRIPTION
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
Type: SIE.5SY4202-7+5ST3010
1 3 13 21
Manufacturer: SIEMENS 2 4 14 22
TWO POLE CIRCUIT BREAKER
AUXILIARY CONTACT NO/NC
Manufacturer: SIEMENS 1 3 21
C Type: SIE.5SY4202-7+5ST3010
Manufacturer: SIEMENS 1 3 21
D
Manufacturer: SIEMENS 1 3 21
E Type: SIE.5SY5202-7+5ST3010
1 3 21
Manufacturer: SIEMENS
TWO POLE CIRCUIT BREAKER 2 4 22
AUXILIARY CONTACT NO/NC
DEVICE LIST
A QTY. DEVICE DESCRIPTION LOCATION DEVICE DEVICE REFERENCE FUNCTION DESCRIPTION
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
Type: SIE.AF9-30-10-13
Manufacturer: ABB A1 1 3 5 13 21 31 43
THREE POLE CONTACTOR 125V DC
AUXILIARY CONTACTS 1NO A2 2 4 6 14 22 32 44
Manufacturer: ABB A1 13 23 33 43
AUXILIARY RELAY
AUXILIARY CONTACTS 4NO A2 14 24 34 44
A Type: SIE.3UG4513-1BR20
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
Manufacturer: SIEMENS L1 L2 L3 12 14 22 24
UNDERVOLTAGE RELAY
AUXILIARY CONTACT 2CO 11 21
1 3 5
Manufacturer: ABB 33 43 57 67
MOTOR PROTECTION SWITCH
I> I> I> 34 44 58 68
2 4 6
DEVICE LIST
A QTY. DEVICE DESCRIPTION LOCATION DEVICE DEVICE REFERENCE FUNCTION DESCRIPTION
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
Type: LW39-16B-4OB-33J/3
Manufacturer: TEBIANDIANGONG 1
PE
NON-RETUREN VALVE
2
TxD+
TxD-
RxD+
GROUND
RxD-
1
4
2
5
H2 GUARE
J6
+TR DGA
Manufacturer:SIEMENS RS485 Modbus TCP
ALARM
FAULT
ALERT
J1
J2
1
9
F
1
3
PE
CO
NO
CO
NO
CO
NO
NC
NC
NC
N
L
DEVICE LIST
A QTY. DEVICE DESCRIPTION LOCATION DEVICE DEVICE REFERENCE FUNCTION DESCRIPTION
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
Type: YBLX-K1/411
Manufacturer: CHNT 21
22
Manufacturer: QUALITROL 1
CLAMP ON CT
2
CLAMP ON CT
Manufacturer: CHNT L PE N
SOCKET 2P+E, 15A
Manufacturer: Qualitrol
/19.3D
/19.3D
/19.3D
TB1:16
TB1:14
TB1:15
-A1 WINDING MAIN TANK OIL LEVEL Pt100 AMBIENT AIR WINDING Pt100 OIL ELECTRONIC TEMPERATURE
B LV SIDE POTENCIOMETER TEMPERATURE HV SIDE TEMPERATURE MONITOR
+ - QUALITROL 509 ITM
DEVANADO NIVEL DE ACEITE Pt100 TEMPERATURA DEVANADO Pt100 TEMPERATURA
ALTA TENSI N POTENCIOMETRICA DEL AIRE AMBIENTE ALTA TENSI N DEL ACEITE =
C - -
TB7:1
TB7:2
TB6:3
TB6:2
TB6:1
TB5:3
TB5:2
TB5:1
TB4:1
TB4:2
TB3:3
TB3:2
TB3:1
/21.1B
/21.1B
/22.5E
/22.5E
/22.5E
/19.2E
/19.2E
/19.2E
/20.1C
/20.1C
/19.4E
/19.4E
/19.5E
-A1
ELECTRONIC TEMPERATURE MONITOR QUALITROL 509 ITM
D
SIG. GND
SIG. GND
TXD+(B)
TXD-(A)
RXD+(B)
RXD-(A)
TXD+(B)
TXD-(A)
E
TB1:10
TB1:11
TB1:12
TB1:13
TB1:18
TB1:19
TB1:20
TB1:21
TB1:22
TB1:23
TB1:24
TB1:25
TB1:26
TB1:27
TB1:28
TB1:29
TB1:30
TB1:31
TB1:32
TB2:10
TB2:11
TB2:12
TB2:13
TB2:14
TB2:15
TB2:16
TB1:2
TB1:3
TB1:4
TB1:5
TB1:6
TB1:7
TB1:8
TB1:9
TB2:1
TB2:2
TB2:3
TB2:4
TB2:5
TB2:6
TB2:7
TB2:8
TB2:9
/23.10B
/23.10B
/23.10B
/23.10B
/23.10B
/23.6E
/23.6E
/23.6E
/23.7E
/23.7E
/23.7E
/23.3B
/23.3B
/23.3B
/23.3B
/23.4B
/23.4B
/23.4B
/23.4B
/23.4B
/23.5B
/23.5B
/23.5B
/23.5B
/23.6B
/23.6B
/23.6B
/23.6B
/23.6B
/23.7B
/23.7B
/23.7B
/23.7B
/23.7B
/23.8B
/23.8B
/23.8B
/23.8B
/23.9B
/23.9B
/23.9B
/23.9B
/23.9B
F
L2 L2 DE CONTROL EN EL TRANSFORMADOR
L3 L3
PE PE
-X1 1 2 3 4
1 3 5 13 21
-F10 -X8 1 -X8 20
50A 14 22
2 4 6
/24.3C
FAN GROUP
/24.9C
D
1 3 5 33 43 1 3 5 33 43 1 3 5 33 43
-Q1 -Q2 -Q3
1.4-2.0A 57 67 34 44 1.4-2.0A 57 67 34 44 1.4-2.0A 57 67 34 44
/18.8F
/18.8F
/18.8F
I> I> I> I> I> I> I> I> I>
2 4 6 58 68 2 4 6 58 68 2 4 6 58 68
/18.8F
/18.8F
/18.8F
1 3 5 1 3 5 1 3 5
-K1 -K2 -K3
2 4 6 2 4 6 2 4 6
-X3 1 2 3 4 5 6 7 8 9 10 11 12
U1 V1 W1 PE U1 V1 W1 PE U1 V1 W1 PE
M M M
F 3 3 3
-AN701 -AN702 -AN703
B 1 3 5 13 21 -X0 6
-F12
2A 14 22 1 3 13 21 1 3 13 21 1 3N
2 4 6
/24.4C
-F14 -F13 -Q51
10A 2 4 14 22 2A 2 4 14 22 16A
IΔ
/24.4C
/24.4C
2 4N
1 21
-B11 Θ * THERMOSTAT -S19
0-60°C 2 22
C *SET 45°C USED FOR
OVERHEATING
-X0 1 PROTECTION 21
L1 L2 L3 -S20
22
-K9 1 *TERMOSTATO
160-690V, AJUSTAR 198V -B12 %F USADO PARA -X11
0,1-20s, AJUSTAR 10s 35-95 %F 2 SOBRECALENTAMIENTO L
SET 70%
PROTECCI N
PE
1
-X0 2
-E3 N
2
-X0 3
1
D -E1
150W 1
PE -E4
2 1 2
-X0 7 -E2
250W, WITH FAN
PE
2
-X0 5
-X0 4
A
AC DISTRIBUTION BOARD 220V AC
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
-X9 1 2 3 4
1 3 13 21 1 3 13 21
-F16 -F17
6A 2 4 14 22 2A 2 4 14 22
/24.5C
/24.5C
C
-X9 -X10
6 8 1 3
D
/25.2C
/25.3C
/23.3F
/23.3F
A
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
-X5 1 2 3 4
1 3 13 21 1 3 13 21 1 3 13 21 1 3 13 21
-F19 -F20 -F21 -F22
6A 2 4 14 22 6A 2 4 14 22 2A 2 4 14 22 6A 2 4 14 22
C
/24.6C
/24.7C
/24.6C
/24.7C
-X5
6 8 A2
-X8 16 -K10
17-275V, AJUSTAR 112.5V A1
0,1-20s, AJUSTAR 10s
TB12:3
TB12:5
TB12:1
A1
/14.8B
D - +
=
1-2
3-4
16.2D / 15L+
5-6
7-8
B
13
2,4 6 8
-K4
-S3 14
3 1 5 7
AUTOMATIC
MANUAL
/24.8C
/24.8C
C
-A1
-X2 2 -X2 3
RELAY 1
/14.1E
-CT031 -CT033
35°C 11 65°C 11
12 14 12 14
TB1:2
TB1:3
TB1:4
33 33 33
-Q1 -Q2 -Q3
34 34 34
D -X6 1 2 3
-X2 1 -X2 10
-X2 5
43
-K4
44
-X2 7 -X2 8
A1
-K4 A1 A1 A1
E A2 -K1 -K2 -K3
A2 A2 A2
16.2E / 15L-
A
OIL OIL
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
B -CT023 -CT021
-CT024 -CT031
WH1 WH2
3
1
32 34 42 44
BL1 BL2
1 2 31 41
PE PE 2 PE PE °C 100°C 120°C
3
-X2 25 26 27 -X2 28 29 30
+ +
Pt 100 Pt 100
- -
TB5:3
TB5:2
TB5:1
TB3:3
TB3:2
TB3:1
ALARM TRIP
Pt100 TEMPERATURA TEMPERATURA DEL TEMPERATURA DEL
DE DEVANADO 0..160°C DEVANADO ALARMA DEVANADO DISPARO
-A1
/15.6C /4.5B /4.5B
CT INPUT 1
MODULE 2 4
32 34 42 44
2
°C 31 41
2X2 1X2 3 PE PE 105°C 145°C
A 3a
TB4:1
TB4:2
-X2 21 22
* *
/25.C5
-T1 -X4 1 2 3 -X4 -X4 4 5 6 -X4 -X8 4 -X2 46 65 66 47 67 68
1 2 X10 ATO
An1(4-20mA) +24V
S1 -X2
PW
86 87 88
8 S2
OUT
S 9
Sensformer
Connectivity box
-T1: PROVIDE BY ITM509
D -X8 3
-A1
/15.6C /4.5B
CT INPUT
MODULE 5
-CF050 -CP081
3X2
A
13 23 33
12 14 22 24
TB7:1
TB7:2
C P P
14 24 34 PE PE 11 21
-X2 39 40
*
7 8 9 -X4
-T2 -X4
1 2
-X8 5
-X8 7
Potenciómetro
-X6 49 50 51 52
D 10
-X8
-X8 8 -X6 45 46 47
RM -X2 57 85
13 15 16 6 7 8 14
E
-X8 9
-X5 10 12 -X2 55 83
Signaling
Contact
FAN GROUP ALARM OIL TRIP OIL ALARM WINDING TRIP WINDING MAIN TANK ALARM MAX MAIN TANK ALARM MIN SPARE INTERNAL FAULT
CONTROL TEMPERATURE TEMPERATURE TEMP. HV AND LV TEMP. HV AND LV OIL LEVEL OIL LEVEL TEMP. MONITOR
Grupo de fans ALARMA TEMP. DISPARO TEMP. ALARMA TEMP. DISPARO TEMP. ALARMA máxima ALARMA m nima Reserva FALA INTERNA
Control DE ACEITE DE ACEITE DEV. A.T./B.T. DEV. A.T NIVEL DE ECEITE NIVEL DE ECEITE MONITOR DE TEMP.
B RELAY 1 RELAY 2 RELAY 3 RELAY 4 RELAY 5 RELAY 6 RELAY 7 RELAY 8 SYSTEM RELAY RS 485 (MAIN) RS 485 (AUX)
4..20mA 4..20mA 4..20mA 4..20mA
SIG. GND
SIG. GND
TXD+(B)
TXD-(A)
RXD+(B)
RXD-(A)
TXD+(B)
TXD-(A)
CUREENT CUREENT CUREENT CUREENT
LOOP 1 LOOP 2 LOOP 3 LOOP 4
+ - + - + -+ -
TB1:10
TB1:11
TB1:12
TB1:13
TB1:18
TB1:19
TB1:20
TB1:21
TB1:22
TB1:23
TB1:27
TB1:28
TB1:29
TB1:24
TB1:25
TB1:26
TB1:30
TB1:31
TB1:32
TB2:10
TB2:11
TB2:12
TB2:13
TB2:14
TB2:15
TB2:16
TB1:2
TB1:3
TB1:4
TB1:5
TB1:6
TB1:7
TB1:8
TB1:9
TB2:1
TB2:2
TB2:3
TB2:4
TB2:5
TB2:6
TB2:7
TB2:8
TB2:9
-X6 1 2 3 4 5 6 14 7 21 15 8 22 16 9 23 17 10 24 18 11 25 19 12 26 20 13 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
C
X9
19 20 21 22 23
D
TxD+
TxD-
GROUND
RxD+
RxD-
DGA
1
4
2
5
J6
H2 Guard
RS485 Modbus TCP
ALARM
FAULT
ALERT
E
J1
J2
1
9
1
3
PE
CO
NO
CO
NO
CO
NO
NC
NC
NC
N
L
BK
BK
BK
BK
BK
BK
X9 X9 X8 X9 X9 X9 X9 X9 X9
6 8 13 10 11 13 14 16 17
AC220V
/16.4E
A
4/2/2022
ZHANG.YX
LIAO.W
LIU.QH
1
-X7
UNDERVOLTAGE RELE MINIMA
22 24
1
RELAY 220V AC TENSION 220V AC
21
16
-K9
V170801~03
Manufacturer's Drawing No:
SIEMENS TRANSFORMER(WUHAN) CO. LTD.
Manufacturer's Name:
2
UNDERVOLTAGE RELE MINIMA
12 14
2
RELAY 125V DC TENSION 125V DC
-K10
11
17
-Q1
-X7
57
30
-F10
33
-Q2
22
21
MAIN SUPPLY ALIMENTACI N
18
3
FAULT FAN 2 FALA DE FAN 2
58
57
-Q3
-F12
FAULT FAN 3 FALA DE FAN 3
58
57
22
21
19
4
RELAY TENSION
-F13
-K1
4
ILUMINACI N Y
CABINET HEATING CALEFACCI N
22
21
20
5
FAN 1 OPERATING VENTILADORES 1 OPERANDO
14
13
31
22
21
Drawing / document description:
Substation name:
13
-K3
-F16
13
DGA SUPPLY
22
21
21
5
-F17
-F21
Diagrama esquemático
Schematic diagram
21
22
7
37
35
21
ALIMENTACI N
FAN CONTROL SUPPLY CONTROL VENTILADORES
6
22
21
23
8
-F20
21
24
7
UNDERVOLTAGE RELE MINIMA
22
21
25
10
Revision:
-S3
Rev.4
5
26
11
AUTO. AUTOMATIC
-S3
Transformer signalization
8
27
12
MANUAL MANUAL
V04 30 911-01
-K4
Revision date:
33
(ONAF)
28
13
(ONAF)
-F1
4/2/2022
22
21
VENTILADORES ALIMENTACI N
29
14
Sheet No.
Location:
Function:
10
+GH009
43
24
1 2 3 4 5 6 7 8 9 10
A
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
+CT022
1
2 3
BLACK
BLACK
BLACK
CONTROL CUBICLE
GH009
ATO
/16.6E
/16.6E
C
X8 X10 X10
15 4 6 10 11 12
X10
8 9
X10 7
3 1 5 2
S19 S20
E3
A1 A1
C PUSH PUSH
S3
S3
25 (Acero Inoxidable)
40
25
RUBBER DAMPER
GOMA AMORTIGUADOR
SCREW M12 - TERMINALS X8 SHOULD BE INSTALLED ON INSULATORS!!
F (STAINLESS STEEL)
Tornillo M12
(acero inoxidable) DETAILS ARE NOT IN SCALE!! Detalle X - CT031, CT033, CT35 SHOULD BE INSTALLED ON INSULATORS!!
Detalle Y
(Tornillo de Puesta a Tierra)Los detalles no están a escala!!! (Punto de fijación) Terminales X8 deben ser instaladas en los aisladores!!
- CT031, CT033, CT35 deben ser instalados en los aisladores!!
Designed LIU.QH Manufacturer's Name: Substation name: Project drawing number:
V04 30 911-01 Function:
SIEMENS TRANSFORMER(WUHAN) CO. LTD. Peru ENEL PROJECT
Desig.assoc. SUN.SQ Revision: Revision date:
Manufacturer's Drawing No: Drawing / document description: Rev.4 4/2/2022 Location: +GH009
Checked LIAO.W Page description:
Approved ZHANG.YX Schematic diagram Sheet No. 26
V170801~03 Control cabinet
Date 4/2/2022 Diagrama esquemático No. of sheets 43
1 2 3 4 5 6 7 8 9 10
Puerta Abierta
D D
S19
E3
SIEMENS 3RH
K10
80
T1 X2
C T2 100 X7 X6 60
40
X4 12
X4 1
X3
15 1
X7
1 X9
X3 25
X0 X6 1
7
1 X5
X0 1 10
X1 X9
10 X5 1
D X8 20
X10
15 M12
80 1 60 60 X2 1 60 60 1 60 60 1
X1 X8 X10
E1 80 E2
30
200
30
E
A
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
BOTTOM VIEW
CABLE CONECTION PLATES
20 50
40
D
75
5.2
C Z
125
Placa de Placa de
Conexión del Conexión del
250
450
Transformador Gabinete (Removible)
340
380
125
340
TRANSFORMER CTR. ROOM
CONNECTION CONNECTION
125
PLATE PLATE
D
D
EARTHING BAR
0°
12
M L K J I H G F E D C B A
A
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
Jumper
Jumper
Wire
Wire
Target Type Terminal Target
Jumper
Cable type
Cable type
Destination Destination
E
Cable designation
Cable designation
Terminal strip designation
+GH009-X0
AUXILLIARY AC SUPPLY
F Terminal diagram
TERMINAL DIAGRAM LEGEND: Current jumper =
F,G,H = Jumper = A,B,C,D,E,I,J,K,L,M = Wire Jumper = * * * SHORT CONNECTIONS SHALL BE REMOVED AFTER MEASURING DEVICES ARE CONNECTED
M L K J I H G F E D C B A
A
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
PHO.UK5N 10
PHO.UK5N 9
PHO.UK5N 8
PHO.UK5N 7
PHO.UK5N 6
D PHO.UK5N 5
/16.3B +CR-PE PHO.USLKG35N 4 -X8:1
/16.2B +CR-L3 PHO.UK35 3 -F10:5
/16.2B +CR-L2 PHO.UK35 2 -F10:3
/16.2B +CR-L1 PHO.UK35 1 -F10:1
Sheet/ M L K J I H G F E D C B A
location
Jumper
Jumper
Wire
Wire
Target Type Terminal Target
Jumper
Cable type
Cable type
Destination Destination
E
Cable designation
Cable designation
Terminal strip designation
+GH009-X1
F Terminal diagram
TERMINAL DIAGRAM LEGEND: Current jumper =
F,G,H = Jumper = A,B,C,D,E,I,J,K,L,M = Wire Jumper = * * * SHORT CONNECTIONS SHALL BE REMOVED AFTER MEASURING DEVICES ARE CONNECTED
M L K J I H G F E D C B A
/21.7E PHO.UT4 36
/21.6E PHO.UT4 35
/23.6D PHO.UT4 34
/22.6D PHO.UT4 33
/21.6D PHO.UT4 32
/21.6D PHO.UT4 31
/21.4C +TR-CT023:2 PHO.UT4 30 -A1:TB3:1
/21.4C +TR-CT023:1 PHO.UT4 29 -A1:TB3:2
/21.3C +TR-CT023:3 PHO.UT4 28 -A1:TB3:3
B /21.1C +TR-CT024:BL2 PHO.UT4 27 -A1:TB5:1
/21.1C +TR-CT024:BL1 PHO.UT4 26 -A1:TB5:2
/21.1C +TR-CT024:WH1 PHO.UT4 25 -A1:TB5:3
PHO.UT4 24
PHO.UT4 23
/20.6E -A1:TB4:2 PHO.UT4 22 -T1:2
/20.6E -A1:TB4:1 PHO.UT4 21 -T1:1
/20.6F PHO.UT4 20
/20.6F PHO.UT4 19
/20.6F PHO.UT4 18
/20.6E PHO.UT4 17
C /20.6D PHO.UT4 16
/20.6D PHO.UT4 15
/20.6D +TR-CT021:3 PHO.UT4 14
/20.5E +TR-CT021:2 PHO.UT4 13
+TR-CT021:1 PHO.UT4 12
/20.4E PHO.UT4 11
/20.3E +TR-CT033:12 PHO.UT4 10
/20.4F PHO.UT4 9
/20.3F +TR-CT033:14 PHO.UT4 8 -X6:2
/20.3F -K4:44 PHO.UT4 7 -K4:A1
PHO.UT4 6
D /20.3E +TR-CT031:14 PHO.UT4 5 -K4:43
/20.4D PHO.UT4 4
/20.3D +TR-CT033:11 PHO.UT4 3 -X6:1
/20.3D +TR-CT031:11 PHO.UT4 2 -S3:1
/20.3E +TR-CT031:12 PHO.UT4 1
Sheet/ M L K J I H G F E D C B A
location
Jumper
Jumper
Wire
Wire
Target Type Terminal Target
Jumper
Cable type
Cable type
Destination Destination
E
Cable designation
Cable designation
Terminal strip designation
+GH009-X2
F Terminal diagram
TERMINAL DIAGRAM LEGEND: Current jumper =
F,G,H = Jumper = A,B,C,D,E,I,J,K,L,M = Wire Jumper = * * * SHORT CONNECTIONS SHALL BE REMOVED AFTER MEASURING DEVICES ARE CONNECTED
M L K J I H G F E D C B A
Jumper
Jumper
Wire
Wire
Target Type Terminal Target
Jumper
Cable type
Cable type
Destination Destination
E
Cable designation
Cable designation
Terminal strip designation
+GH009-X2
F Terminal diagram
TERMINAL DIAGRAM LEGEND: Current jumper =
F,G,H = Jumper = A,B,C,D,E,I,J,K,L,M = Wire Jumper = * * * SHORT CONNECTIONS SHALL BE REMOVED AFTER MEASURING DEVICES ARE CONNECTED
M L K J I H G F E D C B A
A
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
PHO.UT4 100
PHO.UT4 99
PHO.UT4 98
PHO.UT4 97
C PHO.UT4 96
PHO.UT4 95
PHO.UT4 94
PHO.UT4 93
PHO.UT4 92
PHO.UT4 91
PHO.UT4 90
PHO.UT4 89
+TR-CT050:3a PHO.UT4 88
+TR-CT050:3 PHO.UT4 87
+TR-CT050:4 PHO.UT4 86
D +TR-CF090:1 PHO.UT4 85
PHO.UT4 84
-RM:12 PHO.UT4 83
PHO.UT4 82
+TR-CP081:22 PHO.UT4 81
Sheet/ M L K J I H G F E D C B A
location
Jumper
Jumper
Wire
Wire
Target Type Terminal Target
Jumper
Cable type
Cable type
Destination Destination
E
Cable designation
Cable designation
Terminal strip designation
+GH009-X2
F Terminal diagram
TERMINAL DIAGRAM LEGEND: Current jumper =
F,G,H = Jumper = A,B,C,D,E,I,J,K,L,M = Wire Jumper = * * * SHORT CONNECTIONS SHALL BE REMOVED AFTER MEASURING DEVICES ARE CONNECTED
M L K J I H G F E D C B A
A
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
C
PHO.UK5N 15
PHO.UK5N 14
/16.5E PHO.UK5N 13
/16.5E -X8:9 PHO.UK5N 12 +TR-AN703:PE
/16.5E -K3:6 PHO.UK5N 11 +TR-AN703:W1
/16.4E -K3:4 PHO.UK5N 10 +TR-AN703:V1
/16.4E -K3:2 PHO.UK5N 9 +TR-AN703:U1
/16.7E -X8:8 PHO.UK5N 8 +TR-AN702:PE
/16.7E -K2:6 PHO.UK5N 7 +TR-AN702:W1
/16.7E -K2:4 PHO.UK5N 6 +TR-AN702:V1
D /16.7E -K2:2 PHO.UK5N 5 +TR-AN702:U1
/16.4E -X8:1 PHO.UK5N 4 +TR-AN701:PE
/16.4E -K1:6 PHO.UK5N 3 +TR-AN701:W1
/16.4E -K1:4 PHO.UK5N 2 +TR-AN701:V1
/16.3E -K1:2 PHO.UK5N 1 +TR-AN701:U1
Sheet/ M L K J I H G F E D C B A
location
Jumper
Jumper
Wire
Wire
Target Type Terminal Target
Jumper
Cable type
Cable type
Destination Destination
E
Cable designation
Cable designation
Terminal strip designation
+GH009-X3
FOR MOTOR PHASES AND EARTH
F Terminal diagram
TERMINAL DIAGRAM LEGEND: Current jumper =
F,G,H = Jumper = A,B,C,D,E,I,J,K,L,M = Wire Jumper = * * * SHORT CONNECTIONS SHALL BE REMOVED AFTER MEASURING DEVICES ARE CONNECTED
M L K J I H G F E D C B A
A
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
/23.4C PHO.URTK/S 12
/23.4C PHO.URTK/S 11
/23.4C PHO.URTK/S 10
/23.3C PHO.URTK/S 9 -X8:5
+TR-TC3:3X1
*
/23.3C PHO.URTK/S 8
/23.3C +TR-TC3:3X2 PHO.URTK/S 7
/22.4C PHO.URTK/S 6 -X8:3
*
D /22.4C +TR-TC1:1X1 PHO.URTK/S 5 +TR-CT050:1
/22.4C +TR-TC1:1X2 PHO.URTK/S 4 +TR-CT050:2
/22.3C PHO.URTK/S 3 -X8:3
PHO.URTK/S
*
/22.3C +TR-TC2:2X1 2
/22.3C +TR-TC2:2X2 PHO.URTK/S 1
Sheet/ M L K J I H G F E D C B A
location
Jumper
Jumper
Wire
Wire
Target Type Terminal Target
Jumper
Cable type
Cable type
Destination Destination
E
Cable designation
Cable designation
Terminal strip designation
+GH009-X4
CURRENT TRANSFORMERS
F Terminal diagram
TERMINAL DIAGRAM LEGEND: Current jumper =
F,G,H = Jumper = A,B,C,D,E,I,J,K,L,M = Wire Jumper = * * * SHORT CONNECTIONS SHALL BE REMOVED AFTER MEASURING DEVICES ARE CONNECTED
M L K J I H G F E D C B A
A
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
Jumper
Jumper
Wire
Wire
Target Type Terminal Target
Jumper
Cable type
Cable type
Destination Destination
E
Cable designation
Cable designation
Terminal strip designation
+GH009-X5
DC SUPPLY
F Terminal diagram
TERMINAL DIAGRAM LEGEND: Current jumper =
F,G,H = Jumper = A,B,C,D,E,I,J,K,L,M = Wire Jumper = * * * SHORT CONNECTIONS SHALL BE REMOVED AFTER MEASURING DEVICES ARE CONNECTED
M L K J I H G F E D C B A
Jumper
Jumper
Wire
Wire
Target Type Terminal Target
Jumper
Cable type
Cable type
Destination Destination
E
Cable designation
Cable designation
Terminal strip designation
+GH009-X6
F Terminal diagram
TERMINAL DIAGRAM LEGEND: Current jumper =
F,G,H = Jumper = A,B,C,D,E,I,J,K,L,M = Wire Jumper = * * * SHORT CONNECTIONS SHALL BE REMOVED AFTER MEASURING DEVICES ARE CONNECTED
M L K J I H G F E D C B A
A
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
PHO.UT4 60
PHO.UT4 59
PHO.UT4 58
PHO.UT4 57
C PHO.UT4 56
PHO.UT4 55
PHO.UT4 54
PHO.UT4 53
-RM:14 PHO.UT4 52 SM:CN2-4
-RM:8 PHO.UT4 51 SM:CN2-3
-RM:7 PHO.UT4 50 SM:CN2-2
-RM:6 PHO.UT4 49 SM:CN2-1
PHO.UT4 48
-A1:TB6:3 PHO.UT4 47 +TR-CL060:11
-A1:TB6:2 PHO.UT4 46 +TR-CL060:13
D -A1:TB6:1 PHO.UT4 45 +TR-CL060:10
PHO.UT4 44
-A1:TB2:16 PHO.UT4 43
-A1:TB2:15 PHO.UT4 42
-A1:TB2:14 PHO.UT4 41
Sheet/ M L K J I H G F E D C B A
location
Jumper
Jumper
Wire
Wire
Target Type Terminal Target
Jumper
Cable type
Cable type
Destination Destination
E
Cable designation
Cable designation
Terminal strip designation
+GH009-X6
F Terminal diagram
TERMINAL DIAGRAM LEGEND: Current jumper =
F,G,H = Jumper = A,B,C,D,E,I,J,K,L,M = Wire Jumper = * * * SHORT CONNECTIONS SHALL BE REMOVED AFTER MEASURING DEVICES ARE CONNECTED
M L K J I H G F E D C B A
PHO.UT4 40
PHO.UT4 39
A PHO.UT4 38
-F21:22 PHO.UT4 37
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
PHO.UT4 36
-F21:21 PHO.UT4 35
-K1:13 PHO.UT4 34
-Q1:57 PHO.UT4 33
PHO.UT4 32
-K1:14 PHO.UT4 31
-Q1:58 PHO.UT4 30
-F1:22 PHO.UT4 29
-K4:34 PHO.UT4 28
B -S3:8 PHO.UT4 27
-S3:6 PHO.UT4 26
-F22:22 PHO.UT4 25
-F20:22 PHO.UT4 24
-F19:22 PHO.UT4 23
-F17:22 PHO.UT4 22
-F16:22 PHO.UT4 21
-F13:22 PHO.UT4 20
-F12:22 PHO.UT4 19
-F10:22 PHO.UT4 18
-K10:11 PHO.UT4 17
C -K9:21 PHO.UT4 16
PHO.UT4 15
-F1:21 PHO.UT4 14
-K4:33 PHO.UT4 13
-S3:7 PHO.UT4 12
-S3:5 PHO.UT4 11
-F22:21 PHO.UT4 10
-F20:21 PHO.UT4 9
-F19:21 PHO.UT4 8
-F17:21 PHO.UT4 7
-F16:21 PHO.UT4 6
D -F13:21 PHO.UT4 5
-F12:21 PHO.UT4 4
-F10:21 PHO.UT4 3
-K10:12 PHO.UT4 2
-K9:22 PHO.UT4 1
Sheet/ M L K J I H G F E D C B A
location
Jumper
Jumper
Wire
Wire
Target Type Terminal Target
Jumper
Cable type
Cable type
Destination Destination
E
Cable designation
Cable designation
Terminal strip designation
+GH009-X7
F Terminal diagram
TERMINAL DIAGRAM LEGEND: Current jumper =
F,G,H = Jumper = A,B,C,D,E,I,J,K,L,M = Wire Jumper = * * * SHORT CONNECTIONS SHALL BE REMOVED AFTER MEASURING DEVICES ARE CONNECTED
M L K J I H G F E D C B A
A
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
PHO.USLKG6N 20
PHO.USLKG6N 19
PHO.USLKG6N 18
+TR-CT023:PE PHO.USLKG6N 17
C -A1:TB12:1 PHO.USLKG6N 16 +TR-CT024:PE
-X0:7 PHO.USLKG6N 15 -X10:5
PHO.USLKG6N 14
+TR-DGA:PE PHO.USLKG6N 13
PHO.USLKG6N 12
PHO.USLKG6N 11
+TR-CF090:PE PHO.USLKG6N 10
-RM:1 PHO.USLKG6N 9
+TR-CL060:PE PHO.USLKG6N 8 -X3:8
+TR-CF050:PE PHO.USLKG6N 7 +TR-CP081:PE
+TR-CT051:PE PHO.USLKG6N 6
D PHO.USLKG6N 5 -X4:9
+TR-CT050:PE PHO.USLKG6N 4 +TR-CT033:PE
-X4:3 PHO.USLKG6N 3 -X4:6
+TR-CT021:PE PHO.USLKG6N 2 +TR-CT031:PE
-X1:4 PHO.USLKG6N 1 -X3:4
Sheet/ M L K J I H G F E D C B A
location
Jumper
Jumper
Wire
Wire
Target Type Terminal Target
Jumper
Cable type
Cable type
Destination Destination
E
Cable designation
Cable designation
Terminal strip designation
+GH009-X8
EARTHING TERMINALS
F Terminal diagram
TERMINAL DIAGRAM LEGEND: Current jumper =
F,G,H = Jumper = A,B,C,D,E,I,J,K,L,M = Wire Jumper = * * * SHORT CONNECTIONS SHALL BE REMOVED AFTER MEASURING DEVICES ARE CONNECTED
M L K J I H G F E D C B A
A
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
PHO.UK5N 25
PHO.UK5N 24
PHO.UK5N 23 +TR-DGA J6:5
PHO.UK5N 22 +TR-DGA J6:4
PHO.UK5N 21 +TR-DGA J6:3
PHO.UK5N 20 +TR-DGA J6:2
PHO.UK5N 19 +TR-DGA J6:1
PHO.UK5N 18
PHO.UK5N 17 +TR-DGA J2:9
C PHO.UK5N 16 +TR-DGA J2:8
PHO.UK5N 15
PHO.UK5N 14 +TR-DGA J2:6
PHO.UK5N 13 +TR-DGA J2:5
PHO.UK5N 12
PHO.UK5N 11 +TR-DGA J2:3
PHO.UK5N 10 +TR-DGA J2:2
PHO.UK5N 9
-F16:4 PHO.UK5N 8 +TR-DGA J1:N
PHO.UK5N 7
-F16:2 PHO.UK5N 6 +TR-DGA J1:L
D PHO.UK5N 5
PHO.UK5N 4
-F16:3 PHO.UK5N 3
PHO.UK5N 2
-F16:1 PHO.UK5N 1
Sheet/ M L K J I H G F E D C B A
location
Jumper
Jumper
Wire
Wire
Target Type Terminal Target
Jumper
Cable type
Cable type
Destination Destination
E
Cable designation
Cable designation
Terminal strip designation
+GH009-X9
F Terminal diagram
TERMINAL DIAGRAM LEGEND: Current jumper =
F,G,H = Jumper = A,B,C,D,E,I,J,K,L,M = Wire Jumper = * * * SHORT CONNECTIONS SHALL BE REMOVED AFTER MEASURING DEVICES ARE CONNECTED
M L K J I H G F E D C B A
A
This document remains the exclusive property of the Koncar Power Transformers Ltd. Reproduction or any use not in conformity with the intended application is not permissible.
C
PHO.UK5N 15
PHO.UK5N 14
PHO.UK5N 13
+TR-CT022:3 PHO.UK5N 12 -SCB:PT100 PW
+TR-CT022:2 PHO.UK5N 11 -SCB:PT100 S+
+TR-CT022:1 PHO.UK5N 10 -SCB:PT100 S-
-ATO:OUT PHO.UK5N 9 -SCB:An1 S
-AT0:+24V PHO.UK5N 8 -SCB:An1 PW
PHO.UK5N 7 -SCB:D1B
PHO.UK5N 6
D -X8:15 PHO.UK5N 5 -SCB:PE
PHO.UK5N 4
-F17:4 PHO.UK5N 3 -SCB:N
PHO.UK5N 2 -SCB:D1A
-F17:2 PHO.UK5N 1 -SCB:L
Sheet/ M L K J I H G F E D C B A
location
Jumper
Jumper
Wire
Wire
Target Type Terminal Target
Jumper
Cable type
Cable type
Destination Destination
E
Cable designation
Cable designation
Terminal strip designation
+GH009-X10
F Terminal diagram
TERMINAL DIAGRAM LEGEND: Current jumper =
F,G,H = Jumper = A,B,C,D,E,I,J,K,L,M = Wire Jumper = * * * SHORT CONNECTIONS SHALL BE REMOVED AFTER MEASURING DEVICES ARE CONNECTED
13 Photographs
15 Check Lists
No. Designation Document No. Page Rev. Date
1 Check list „Arrival Inspection“ V170801
2 Check list „Oil Sampling“ V170801
3 Check list „Commissioning“ V170801
4 Check list "Maintenance Work and Electrical Tests" V170801
-
Heavy part
Pressure/Vacuum Bottle: bar Tank: bar Temperature: °C
Transport with oil Tank tight Tank leaking
Filling gas mbar present not present
overpressure in
the tank
Moisture image present Moisture below 8 % Moisture exceeds 8 %
not present Measured value:
Contact manufacturer
complete damaged Inspected Inspected Comments
yes no yes no on by
Transformer welding seams
Wheels/chassis/attachment
elements
Wiring
General comments:
Date Date
Name Name
Signature Signature
Customer Siemens Supervisor
Sampling
Sample Position Oil sampling tap
Oil drain device A 22/31/40 DIN 42 551
Tank: Top Middle Bottom
Diverter switch: LU tank ______________ ______________
Conservator: Transformer Diverter Switch Bushing pocket _____________
Bushing: ______________ ______________ ______________ _____________
Cable box: ______________ ______________ ______________ _____________
Sampling cause
New filling on: Filled volume: (t)
Remaining filling on: Filled volume: (t)
Interference on:
Oil treatment on:
Routine inspection:
Examinations
Recommendation:
Maintenance multiple
commissioning
contact switch
After defect or
Maintenance
transformer
damage
Requested analysis
Color number ISO 2049 / ASTM D1500
Appearance IEC 60422 / ASTM D1524
Neutralization value IEC 62021 / ASTM D974
Breakdown voltage IEC 60156 / ASTM D1816
Water content IEC 60814 / ASTM D1533
Diel. Dissipation factor at 50 Hz IEC 60247 / ASTM D924
Interfacial tension EN 14210 / ASTM D971
Dissolved Gas Analysis (DGA) IEC 60567 / ASTM 3612
Furan analysis IEC 61198 / ASTM D5837
Inhibitor content IEC 60666 / ASTM D2668
Corrosive sulfur IEC 62535 / ASTM D1275B
Corrosive sulfur DIN 51353
Passivator content IEC 60666
Additional examinations
Protocol language
German English French ____________
Sample taken by
Sampling vessels
Sampling vessels must be clean 1 liter bottles with gas-right closing mechanisms.
Usually, special aluminum bottles with plastic screw cap and seal are used. The closing
mechanism must be so tight that no air is drawn in when the sample cools off.
NOTE
Suitable sample bottles are available from the manufacturer's plant.
NOTE
Only take the oil sample with glass bottles when the sample temperature at sampling is
guaranteed to be greater or the same as the storage and transport temperature.
Otherwise, coordinate with the examination lab.
Samples for gas analysis must only be taken by the overflow procedure. The work steps
for sampling must be performed quickly and without any interruption to prevent contact
between the oil sample and the atmosphere as far as possible. In every case, notice the
temperature inside the oil jet in the test protocol.
Sampling points
for gas analysis examinations: usually tank "top"
for other examinations: usually tank "bottom"
2. Open the oil sampling valve and let about two to three liters of oil (from the outlet
pipeline) flow into the oil collection vessel.
3. Push the hose into the oil sample bottle to the ground. First fill the bottle slowly from the
bottom, then let oil flow strongly until oil at a volume of 2 to 3 times the bottle content has
flowed over into an oil collection container.
4. Last, reduce the oil flow again and draw the bottle from the hose downwards with the oil
sampling valve still open. Close the bottle at once when it was drawn from the hose.
Procedure when taking oil samples from the conservator of the diverter switch
1. Open the drain slide valve at the conservator diverter switch.
2. Work steps 1-6 from “Taking oil from the oil sampling valve”.
NOTE
Oil samples must only be taken with a suitable sampling valve in case of direct oil filling
to the transformer tank from oil barrels.
1 Transformer tank
2 Oil sampling valve
3 Hose
4 Oil sample bottle
5 Oil collection vessel
Fig. 1 Oil sampling with oil sample bottle and oil collection vessel
In Anwesenheit von:
In the prescence of
In Anwesenheit von:
In the prescence of
1. Nenndaten
Rating
Vorschriften:
Standards
Schaltgruppe:
Vector group
tap %
Frequenz: Hz
Frequency
Kühlungsart::
Type of cooling
Baujahr:
Year of Manufacture
2. Elektrische Prüfungen
Electrical tests
2.1 Isolationswiderstand
Insulations resistance
Prüfspannung: kV Gleichspannung
Test Voltage: kV DC
Zeit / Time
Min. / min.
Umgebungstemperatur: °C Öltemperartur: °C
Ambient temperature Oil temperatrue
2.1.1Kernisolation
Core insulation
Prüfspannung: 0,5 kV Gleichspannung / 2,5 kV AC
Test Voltage: 0.5 kV DC / 2.5 kV AC
Zeit / Time
Min. / min.
2.2 Schaltgruppenkontrolle
Check of vector group
Schalterstellung Anspeisung mA
Tap position Supply voltage Phase Phase Phase
2.5 Wicklungswiderstände
Winding resistances
2.6 Stromwandler
Current transformer
2.7 Öl - Durchschlagsfestigkeit
Dielectric strength of oil
Lieferfirma: Type:
Supplier of oil Type
Kessel oben
Top of main tank
Kessel unten
Bottom of main tank
Prüfspannung : V Gleichspannung
Test voltage : V DC
Isolationswiderstand:
Insulation resistance:
3.1 Regelschaltereinrichtungen
Tap changing equipment geprüfet / Bemer.
tested / remarks
Durchschalten händisch - stationär und mit Fernbedienung
Manual operation - loccal and remote operation
Sperrschalter - Kurbel oder Motorantrieb
Action of manual operation safety inerlock
Endschalter / Limit Switches
Stellungsanzeiger mechanisch u. elektrisch in allen Positionen
Mechanical and electrical check of indicator for all positions
Zählwerk für Schaltungen / Tap change counter
Motor Nennleistung / Rated power of motor W
Motor Nennstrom / Rated current of motor A
Strom gemessen / Measured current A
Überstromrelais eingestellt / Setting of overload relay
3.2 Kühlungseinrichtung
Cooling equipment
geprüfet/Bemerkungen
testet / remarks
Lüfter / Fans Pumpen /Pum.
Motor Nennleistung / Rated power of motor W W
Motor Nennstrom / Rated current of motor A A
Strom gemessen / Measured current A A
Motorschtzschalter / Motor contactors
Drehrichtung / Direction on rotation
Überstromreais eingestellt / Setting of overload relay
Kühlersteuerung händisch / Manual control of coolers
Kühlersteuerung automatisch von der HV /HV
Wicklungstemperatur NV/LV
Control cooling automatic from Tertiär
Winding - temp indicator Tertiary
Wiring
Inspection
Maintenance work Date Signature Remarks
intervalls
Checking for leaks and cleanliness
Transformer tanks, covers, domes and pipes
1 year
Bushings
1 year
Cable box
1 year
Conservator (internal)
variabel
Monitoring devices
1 year
Functional tests
Dehydrating breather
1 month
Alarm
1 year
Tripping function
1 year
Inspection
Maintenance work Date Signature Remarks
intervalls
Oil level monitor main transformer
compartment 1 year
Dial thermometers
1 year
Resistance thermometer
1 year
Fans
1 year
Leak monitors
6 Monate
Cooling system
Oil entry/exit temperature
6 months
Current transformers
Inspection
Maintenance work Date Signature Remarks
intervalls
Current transformer earthing
1 year
Interlocks
1 year
Drive
1 year
Tightness
1 year
Contact functions
1 year
Wiring, ducts
1 year
Motor drive
1 year
Contactor control
1 year
Tap-to-tap interlock
1 year
Anti-corrosion coating
1 year
Oil examination
Transformer tank (1, 2, 3, 4, 5, 6)*
1 year
Conservator (1)*
1 year
Inspection
Maintenance work Date Signature Remarks
intervalls
Tap selector compartment (1, 6)*
1 year
Condenser bushing
* recommended examinations: 1 = Disruptive discharge; 2 = Purity; 3 = Neutralization value; 4 = Saponification value; 5 = dieletrical dissipation factor; 6 = Gas analysis)
Cable box
Check moisture content of the cable boxes
filling compound variabel
Miscellaneous
Corrosion protection
1 year
Sound absorption
1 year
Electrical Tests
Winding insulation resistance
max. 5 years
Transformation measurement
max. 5 years
No-load currents
max. 5 years
Winding resistance
max. 5 years
Inspection
Maintenance work Date Signature Remarks
intervalls
Dielectric dissipation factor at condenser 2 years,
bushing max. 5 years
Insulation resistance of the wiring
2 years
In the prescence of