On 31st May at 1150hrs: Carried out Exhaust back pressure on line test @ Base Load (Forced
L63ETH >0); Alarm back press. high activated lower than set pressure 375mmH2O (406.56
mmH2O-Set press.) @ 34.8MW; 1740hrs-Test completed (Unforced L63ETH)
On 01st June 2021 at 0740hrs: Carried out Exhaust back pressure on line test at Base Load
condition (Forced L63ETH >0) Note: Alarm Back Press High activated lower than Set
pressure 381mmH2O (406.56 mmH2O-Set press.) at load 33.0MW; 1030hrs: Carried out
Max Exhaust back pressure online test with one TPM injecting (Forced L63ETH >0 ) Note:
Max Exh pressure 403.23mmH2O at 35.54MW; 1550hrs: Test completed (Unforced
L63ETH) . Satisfactory
On 02nd June 2021 at 1000hrs: Carried out Exhaust back pressure on line test at Base Load
condition (Forced L63ETH >0) Note: Alarm Back Press High activated lower than Set
pressure 381mmH2O (406.56 mmH2O-Set press.) at load 33.0MW; 1650hrs: Carried out
Max Exhaust back pressure online test with both TPM 4MW injecting GT11 ( Forced
L63ETH >0 ) Note: Max Exh pressure 462.23mmH2O at 41.6MW; Note:L63ES1 high
shutdown alarm still not activate (Set press 457.34mmH2O); 1830hrs: Test completed
(Unforced L63ETH)
Trip Setting : 508 mmH20
3.1.3.2 GT 1.2
GT21
10th June 2021 @ 0750hrs: Unit on base load & TPM #1 & #2 injecting @ 5.0MW demand,
exh press 392mmH2O @ 42.3MW unit load, ambient temp ±25°C. Note: TPM derated due
Exh Spreed high alarm.
Trip setting : 508 mmH20
GT22
10th June 2021 @ 0748hrs: Unit on base load & TPM #1 & #2 injecting @ 7.0MW demand,
exh press 425mmH2O @ 42.8MW unit load , ambient temp ±25°C. Note: Exh press High
alarm not activated.
Trip Setting : 508 mmH20
ST1.3
On 01st June 2021 at 0740hrs: Carried out highest vacuum press test without ACC spray
water (Forced L63EVT >0 ); Note: Highest Press 0.137 bara at 25.7 Deg C ambient temp.
Continue testing with one TPM injecting to GT11/GT12 without ACC spray water (Forced
L63EVT >0 ); Note: Highest Press 0.234 bara at 34.2 Deg C ambient temp; 1550hrs: Test
completed (Unforced 63EVT)
On 02nd June 2021 at 1115hrs: Carried out highest vacuum press test without ACC spray
water (Forced L63EVT >0 ) and one TPM injecting to GT11/GT12; Note: Highest Press
0.238 bara at 33.5 Deg C ambient temp. 1830hrs: Test completed (Unforced 63EVT)