Professional Documents
Culture Documents
CT - Semangka 1
CT - Semangka 1
1. Visual Check :
- Name Plate Available and Complete / None / Incomplete
:
- Bushing Not disabled / Disabled / Gross
:
- Grounding Connected and Not Disabled / Not Connected /
:
ddddddddddddddddddddDisabled
- Terminal Marking : Available and Complete / None / Incomplete
- Oil Level Incicator : Appropriate / Not Appropriate
2. Testing
2.1. Polarity : Appropriate / Not Appropriate
2.2. Ratio Test
Phase R
Primary Current Ratio Error Ratio % Primary Current Ratio Error Ratio %
Tap 1 Tap 6
(201.1 A) 599.3 -0.114 (199.9 A) 1005 0.521
(600:1) (1000:1)
Tap 2 Tap 7
(200.5 A) 1204 0.338 (201.1 A) 2013 0.69
(1200:1) (2000:1)
Tap 3 Tap 8
(199.9 A) 599.3 -0.113 (200.5 A) 1004 0.468
(600:1) (1000:1)
Tap 4 Tap 9
(200.5 A) 1204 0.338 (200.5 A) 2012 0.627
(1200:1) (2000:1)
Tap 5
(200.5 A) 348.2 -0.502
(350:1)
PT. TANGGAMUS ELECTRIC POWER
CURRENT
POSCO E&C KOTA AGUNG 150 KV SS TRANSFORMER
PT. INFORMATION DATASYSTEM
Phase S
Primary Current Ratio Error Ratio % Primary Current Ratio Error Ratio %
Tap 1 Tap 6
(200.5 A) 598.6 -0.223 (200.5 A) 1004 0.45
(600:1) (1000:1)
Tap 2 Tap 7
(200.5 A) 1204 0.338 (201.1 A) 2013 0.65
(1200:1) (2000:1)
Tap 3 Tap 8
(201.1 A) 599.1 -0.142 (200.5 A) 1004 0.41
(600:1) (1000:1)
Tap 4 Tap 9
(200.5 A) 1205 0.42 (200.5 A) 2012 0.60
(1200:1) (2000:1)
Tap 5
(200.5 A) 347.8 -0.608
(350:1)
Phase T
Primary Current Ratio Error Ratio % Primary Current Ratio Error Ratio %
Tap 1 Tap 6
(200.5 A) 598.6 -0.223 (200.5 A) 1003 0.395
(600:1) (1000:1)
Tap 2 Tap 7
(200.5 A) 1203 0.262 (200.5 A) 2010 0.51
(1200:1) (2000:1)
Tap 3 Tap 8
(200.5 A) 599 -0.167 (201.1 A) 1003 0.37
(600:1) (1000:1)
Tap 4 Tap 9
(201.1 A) 1202 0.224 (200.5A) 2009 0.47
(1200:1) (1000:1)
Tap 5
(200.5 A) 347.7 -0.629
(350:1)
PT. TANGGAMUS ELECTRIC POWER
CURRENT
POSCO E&C KOTA AGUNG 150 KV SS TRANSFORMER
PT. INFORMATION DATASYSTEM
TAP R S T
Phase
Bagian yang di ukur
R S T
Secondary 1 – Ground > 2000 MΩ > 2000 MΩ > 2000 MΩ
Secondary 2 – Ground > 2000 MΩ > 2000 MΩ > 2000 MΩ
Secondary 3 - Ground > 2000 MΩ > 2000 MΩ > 2000 MΩ 500 V
Secondary 4 – Ground > 2000 MΩ > 2000 MΩ > 2000 MΩ
Secondary 5 – Ground > 2000 MΩ > 2000 MΩ > 2000 MΩ
Sekunder 1 – Sekunder 2 > 2000 MΩ > 2000 MΩ > 2000 MΩ
Sekunder 1 – Sekunder 3 > 2000 MΩ > 2000 MΩ > 2000 MΩ
Sekunder 1 – Sekunder 4 > 2000 MΩ > 2000 MΩ > 2000 MΩ
Sekunder 1 – Sekunder 5 > 2000 MΩ > 2000 MΩ > 2000 MΩ 500 V
Sekunder 2 – Sekunder 3 > 2000 MΩ > 2000 MΩ > 2000 MΩ
Sekunder 2 – Sekunder 4 > 2000 MΩ > 2000 MΩ > 2000 MΩ
Sekunder 2 – Sekunder 5 > 2000 MΩ > 2000 MΩ > 2000 MΩ
PT. TANGGAMUS ELECTRIC POWER
CURRENT
POSCO E&C KOTA AGUNG 150 KV SS TRANSFORMER
PT. INFORMATION DATASYSTEM
Secondary 1
1.2 Ω 1.3 Ω 1.2 Ω
(1S1-1S2)
Secondary 2
2.3 Ω 2.3 Ω 2.2 Ω
(1S1-1S3)
Secondary 3
1.2 Ω 1.4 Ω 1.5 Ω
(2S1-2S2)
Secondary 4
2.3 Ω 2.1 Ω 2.2 Ω
(2S1-2S3)
Secondary 5
0.8 Ω 0.8 Ω 0.8 Ω
(3S1-3S2)
Secondary 6
3.8 Ω 3.9 Ω 3.7 Ω
(4S1-4S2)
Secondary 7
7.7 Ω 7.7 Ω 7.8 Ω
(4S1-4S3)
Secondary 8
3.8 Ω 3.7 Ω 3.7 Ω
(5S1-5S2)
Secondary 9
7.8 Ω 7.8 Ω 7.8 Ω
(5S1-5S3)
PT. TANGGAMUS ELECTRIC POWER
CURRENT
POSCO E&C KOTA AGUNG 150 KV SS TRANSFORMER
PT. INFORMATION DATASYSTEM
3. Note:
PT. INFORMATION
PT. TANGGAMUS POSCO E&C PUSERTIF
DATASYSTEM
ELECTRIC POWER