SPEC NO.

: FRC-LV-CHF-A00-MC

SPECIFICATION
FIRE RESISTANT LOW VOLTAGE POWER CABLE
0.6/1 (1.2) KV CU/MICA/XLPE/LSHF
MULTI-CORE
Copper Conductor, Cross-Linked Polyethylene Insulation
and Low Smoke Halogen Free Sheathed Cables
with Fire Resistant, Flame Retardant and UV Sunlight Resistant.

REVISION ISSUED DATE


02 4 August 2022

PHELPS DODGE INTERNATIONAL (THAILAND) LIMITED


Phelps Dodge International (Thailand) Limited

CONTENTS

1. SCOPE .............................................................................................................................3
2. REFERENCE STANDARDS ..................................................................................................3
3. DEFINITIONS ...................................................................................................................4
4. APPLICATION / SERVICE CONDITIONS ..............................................................................4
5. CABLE CONSTRUCTION ....................................................................................................4
5.1 CONDUCTOR ....................................................................................................................4
5.2 INSULATION .....................................................................................................................5
5.3 CORE IDENTIFICATION .....................................................................................................5
5.4 CORE LAY UP ....................................................................................................................5
5.5 OVERSHEATH ...................................................................................................................6
6. CABLE MARKING AND IDENTIFICATION............................................................................6
7. TESTS AND INSPECTIONS .................................................................................................7
7.1 ROUTINE TESTS ................................................................................................................7
7.2 SAMPLE TESTS..................................................................................................................7
8. PACKING AND LABELING .................................................................................................7
ANNEX A - CABLE DRAWING AND TECHNICAL DATA ...............................................................8

Figure 1 – Cable drawing of 0.6/1 kV CU/MICA/XLPE/LSHF 2-Core ................................................8


Figure 2 – Cable drawing of 0.6/1 kV CU/MICA/XLPE/LSHF 3-Core ..............................................10
Figure 3 – Cable drawing of 0.6/1 kV CU/MICA/XLPE/LSHF 4-Core ..............................................12
Figure 4 – Cable drawing of 0.6/1 kV CU/MICA/XLPE/LSHF 2-Core with Ground.........................14
Figure 5 – Cable drawing of 0.6/1 kV CU/MICA/XLPE/LSHF 3-Core with Ground.........................16
Figure 6 – Cable drawing of 0.6/1 kV CU/MICA/XLPE/LSHF 4-Core with Ground.........................18

Table 1 – Technical data of 0.6/1 kV CU/MICA/XLPE/LSHF 2-Core .................................................9


Table 2 – Technical data of 0.6/1 kV CU/MICA/XLPE/LSHF 3-Core ...............................................11
Table 3 – Technical data of 0.6/1 kV CU/MICA/XLPE/LSHF 4-Core ...............................................13
Table 4 – Technical data of 0.6/1 kV CU/MICA/XLPE/LSHF 2-Core with Ground..........................15
Table 5 – Technical data of 0.6/1 kV CU/MICA/XLPE/LSHF 3-Core with Ground..........................17
Table 6 – Technical data of 0.6/1 kV CU/MICA/XLPE/LSHF 4-Core with Ground..........................19

Page 2 of 19
Spec No.: FRC-LV-CHF-A00-MC Rev.: 02 Date: 4 Aug 2022
Phelps Dodge International (Thailand) Limited

1. SCOPE
This specification specifies the construction, dimensions and test requirements of electric
cables which the manufacturer shall comply in order to supply copper conductor with fire
barrier, XLPE insulation and LSHF outer sheathed cables for 0.6/1(1.2) kV rated voltage
conforming to IEC 60502-1.

Behavior of the cables under fire conditions shall comply with requirements of
1.1 Circuit integrity test under fire conditions according to IEC 60331-21
1.2 Circuit integrity under fire alone, fire with water and fire with mechanical shock test
according to BS 6387 (Category CWZ)
1.3 Vertical flame spread test of single cable according to IEC 60332-1-2
1.4 Vertical flame spread test according to IEC 60332-3-22 (Category A)
1.5 Vertical flame spread test according to IEC 60332-3-23 (Category B)
1.6 Vertical flame spread test according to IEC 60332-3-24 (Category C)
1.7 Test on gases evolved during combustion according to IEC 60754-1 and IEC 60754-2
1.8 Smoke density test according to IEC 61034-2

2. REFERENCE STANDARDS
Except otherwise specified elsewhere in this specification, the cable shall be manufactured
and tested in conformity with the latest edition of the standards listed below:-

BS 6387, Specification for Performance requirements for cables required to maintain circuit
integrity under fire conditions
IEC 60228, Conductors of Insulated Cables
IEC 60331-21, Tests for electric cables under fire conditions - Circuit integrity - Part 21:
Procedures and requirements – Cables of rated voltage up to and including 0,6/1,0 kV
IEC 60502-1, Power cables with extruded insulation and their accessories for rated voltages
form 1 kV (Um = 1.2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV
(Um = 1.2 kV) and 3 kV (Um = 3.6 kV)
IEC 60332-1-2, Tests on electric and optical fibre cables under fire conditions - Part 1-2: Test
for vertical flame propagation for a single insulated wire or cable - Procedure for 1 kW pre-
mixed flame
IEC 60332-3-22, Tests on electric cables under fire conditions –Part 3-22: Test for vertical
flame spread of vertically-mounted bunched wires or cables – Category A
IEC 60332-3-23, Tests on electric cables under fire conditions –Part 3-23: Test for vertical
flame spread of vertically-mounted bunched wires or cables – Category B
IEC 60332-3-24, Tests on electric cables under fire conditions –Part 3-24: Test for vertical
flame spread of vertically-mounted bunched wires or cables – Category C
IEC 60754-1, Test on gases evolved during combustion of materials from cables - Part 1:
Determination of the halogen acid gas content
IEC 60754-2, Test on gases evolved during combustion of materials from cables - Part 2:
Determination of acidity (by pH measurement) and conductivity

Page 3 of 19
Spec No.: FRC-LV-CHF-A00-MC Rev.: 02 Date: 4 Aug 2022
Phelps Dodge International (Thailand) Limited

IEC 61034-2, Measurement of smoke density of cables burning under defined conditions -
Part 2: Test procedure and requirements
DEF STAN 02-713 Issue 3, Determination of the Toxicity Index of the Products of
Combustion from Small Specimens of Materials.

3. DEFINITIONS
3.1 circuit integrity
ability to continue to operate in the designated manner whilst subjected to a specified
flame source for a specified period of time
3.2 nominal cross-sectional area
value that identifies a particular size of conductor but is not subject to direct
measurement
3.3 nominal value
value by which a quantity is designated; it is checked by measurements taking into
account specified tolerances
3.4 approximate value
value which is only indicative; it is neither guaranteed nor checked
3.5 routine tests
tests made by the manufacturer on all production lengths of cable to demonstrate their
integrity
3.6 sample tests
tests made on samples of completed cable or components taken from a completed
cable, adequate to verify that the product meets the designed specifications

4. APPLICATION / SERVICE CONDITIONS


These cables are designed to be suitable for fixed installations in duct, conduit, ladder, tray
and direct burial in ground.

The insulation and other components are capable of operation continuously at a maximum
conductor temperature of 90oC for normal operation and 250oC for short circuit conditions.

5. CABLE CONSTRUCTION
The general construction of the cables is shown as cable drawing in Figure 1 to Figure 6 and
consists of the followings

5.1 CONDUCTOR
The conductor shall be plain annealed copper. Conductor size up to 6 sq.mm. shall be
concentric stranded circular construction and conductor size above 6 sq.mm. shall be
compact stranded circular construction. All various conductor constructions shall be
conformable to IEC 60228 Class 2. Minimum number of wires and diameter of
conductor shall be complying with IEC 60228.

The conductor shall be wrapped helically by mica tape with the mica in contact with
the conductor as to form a fire barrier layer for the conductor.

Page 4 of 19
Spec No.: FRC-LV-CHF-A00-MC Rev.: 02 Date: 4 Aug 2022
Phelps Dodge International (Thailand) Limited

5.2 INSULATION
The insulation shall be cross-linked polyethylene (XLPE) whose properties meet
electrical requirements, mechanical requirements and particular requirements
specify in IEC 60502-1.

The average thickness of insulation shall be not less than the nominal value specified
in Table 1 to Table 6. The minimum thickness shall not fall below 90% of the nominal
value by more than 0.1 mm.

tm > 0.9tn – 0.1


where
tm is the minimum thickness (mm)
tn is the nominal thickness (mm)

5.3 CORE IDENTIFICATION


If there is not any other requirement specified in tender documents, each insulated
core shall be identified by color as below

2-core: Brown and Blue


3-core: Brown, Black and Grey
4-core: Brown, Black, Grey and Blue
Ground core (PE): Green with Yellow strip

5.4 CORE LAY UP


The insulated cores of multi-core cables shall be laid up together with left-hand lay.
Fillers may be used to fill center interstice of the multi-core cables where necessary
to give the completed cable a substantially circular cross section.

Fillers shall be polypropylene filament or yarn or other materials that is suitable for
the operating temperature of the cable and compatible with the insulating material.

Page 5 of 19
Spec No.: FRC-LV-CHF-A00-MC Rev.: 02 Date: 4 Aug 2022
Phelps Dodge International (Thailand) Limited

5.5 OVERSHEATH
The oversheath shall be an extruded layer of low smoke halogen free compound
(LSHF) whose properties meet mechanical requirements and particular requirements
of halogen free sheathing material type ST8 specified in IEC 60502-1.

The oversheath shall be extruded over laid up cores and filled interstices between the
cores to give the completed cable a substantially circular cross section.

The nominal thicknesses of oversheath are specified in Table 1 to Table 6. The


minimum thickness of oversheath shall not fall below 80% of the nominal value by
more than 0.2 mm.
tm > 0.80tn – 0.2
where
tm is the minimum thickness (mm)
tn is the nominal thickness (mm)

The color of the oversheath shall be Orange and it shall be UV sunlight resistant.

Note: The cable with UV resistance is subjected to maintain mechanical properties


and flexibility of the oversheath in outdoor application. However, color fading may
occur in non-black colored oversheath under long exposure to sunlight.

6. CABLE MARKING AND IDENTIFICATION


The oversheath of the cables shall be legibly marked with the following information
throughout the length of the cables by printing method.

" PHELPS DODGE FRC 0.6/1 kV CU/MICA/XLPE/LSHF-UV A X B + C SQ.MM., TÜV SÜD


CERTIFIED NO. B 091380 0024, IEC 60502-1, BS 6387 CWZ, IEC 60332-3 CAT A/B/C, IEC
60754-1&-2, IEC 61034-2, DEF STAN 02-713 "

Note A : specify the number of conductor


B : specify the nominal cross-sectional area of phase conductor
C : specify the nominal cross-sectional area of ground conductor (If require)

Sequential length number shall be marked on the oversheath of cable at 1 meter intervals.

Page 6 of 19
Spec No.: FRC-LV-CHF-A00-MC Rev.: 02 Date: 4 Aug 2022
Phelps Dodge International (Thailand) Limited

7. TESTS AND INSPECTIONS


7.1 ROUTINE TESTS
The following routine tests shall be carried out in accordance with IEC 60502-1 on each
manufactured length of cable.
a) Measurement of the electrical resistance of conductors
b) High voltage test

7.2 SAMPLE TESTS


The following sample tests shall be carried out in accordance with IEC 60502-1. The
number of test sample shall be in accordance with IEC 60502-1.
a) Conductor examination
b) Check of dimensions
i) measurement of thickness of insulation and non-metallic sheath
ii) measurement of external diameter
c) Hot set test for XLPE insulation

8. PACKING AND LABELING


The cable shall be packed on non-returnable wooden reel or returnable steel reel which
covered with suitable covering to provide the cable with physical protection during storage
and transportation.

Following description shall be marked on a flange of the reel.


a) Direction of rotation of the reel
b) Type of cable, Voltage grade
c) Number of conductors and size
d) Length
e) Net weight
f) Gross weight
g) Manufacturer’s name
h) Year of manufacturing
i) Reel No.

Each end of cable shall be hermetically sealed with cap.

Page 7 of 19
Spec No.: FRC-LV-CHF-A00-MC Rev.: 02 Date: 4 Aug 2022
Phelps Dodge International (Thailand) Limited

ANNEX A - CABLE DRAWING AND TECHNICAL DATA

DRAWING & CONSTRUCTION OF


0.6/1 kV CU/MICA/XLPE/LSHF 2-core
Standard.: IEC 60502-1, IEC 60332-3 CAT A/B/C, BS 6387 (CWZ), IEC 60754-1&-2, IEC 61034-2, DEF STAN 02-713

No. Description Type

1 1 Conductor Round Stranded Copper with Mica Tape

XLPE
2 Insulation Core Identification :

Brown and Blue


2
LSHF

Orange
3 Oversheath +UV Sunlight Resistance
3

Figure 1 – Cable drawing of 0.6/1 kV CU/MICA/XLPE/LSHF 2-Core

Page 8 of 19
Spec No.: FRC-LV-CHF-A00-MC Rev.: 02 Date: 4 Aug 2022
Phelps Dodge International (Thailand) Limited

Table 1 – Technical data of 0.6/1 kV CU/MICA/XLPE/LSHF 2-Core


Description unit 2 x 1.5 2 x 2.5 2x4 2x6 2 x 10 2 x 16 2 x 25 2 x 35 2 x 50 2 x 70 2 x 95 2 x 120 2 x 150 2 x 185 2 x 240 2 x 300 2 x 400

Conductor material Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper
Class / Standard 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228

Diameter of Conductor (Approx.) mm 1.6 2.0 2.5 3.1 3.7 4.6 5.9 7.0 8.1 9.6 11.4 12.7 14.1 15.8 18.1 20.4 23.5

Fire Barrier material Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica
Insulation material XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE

Insulation thickness (Nominal) mm 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0
Diameter over Insulation (Approx.) mm 4.1 4.6 4.8 5.4 6.0 6.9 8.5 9.7 11.0 12.7 14.5 16.0 17.9 19.9 22.4 24.9 28.5
Oversheath material LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF
Oversheath thickness (Nominal) mm 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.2 2.3 2.5 2.6 2.9
Overall diameter (Min.) mm 11 12 13 14 15 17 20 22 25 28 32 35 39 44 49 54 62
(Max.) mm 14 15 16 17 18 19 23 25 28 31 35 38 42 47 52 57 65
Total cable weight (Approx.) kg/km 190 225 245 310 415 570 840 1090 1425 1945 2600 3215 3965 4935 6365 7890 10280

Minimum bending radius mm 56 58 62 68 72 76 92 100 140 155 175 190 210 235 312 342 390
Maximum conductor DC resistance at 20°C Ohm/km 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.047
Conductor AC resistance at 90°C and frequency 50 Hz Ohm/km 15.43 9.45 5.88 3.93 2.33 1.47 0.927 0.669 0.494 0.342 0.247 0.196 0.160 0.128 0.099 0.080 0.064
Inductive reactance at frequency 50 Hz Ohm/km 0.103 0.097 0.091 0.087 0.079 0.076 0.076 0.074 0.073 0.072 0.070 0.070 0.071 0.071 0.070 0.069 0.069
Minimum Insulation Resistance at 20°C Mohm-km 678 600 562 491 432 367 382 333 323 307 264 261 274 282 265 250 243

Page 9 of 19
Spec No.: FRC-LV-CHF-A00-MC Rev.: 02 Date: 4 Aug 2022
Phelps Dodge International (Thailand) Limited

DRAWING & CONSTRUCTION OF


0.6/1 kV CU/MICA/XLPE/LSHF 3-core
Standard.: IEC 60502-1, IEC 60332-3 CAT A/B/C, BS 6387 (CWZ), IEC 60754-1&-2, IEC 61034-2, DEF STAN 02-713

No. Description Type

1 1 Conductor Round Stranded Copper with Mica Tape


XLPE

2 Insulation Core Identification :

2 Brown, Black and Grey

3 Polypropylene filler (if necessary)


LSHF
3
Orange

3 Oversheath +UV Sunlight Resistance

Figure 2 – Cable drawing of 0.6/1 kV CU/MICA/XLPE/LSHF 3-Core

Page 10 of 19
Spec No.: FRC-LV-CHF-A00-MC Rev.: 02 Date: 4 Aug 2022
Phelps Dodge International (Thailand) Limited

Table 2 – Technical data of 0.6/1 kV CU/MICA/XLPE/LSHF 3-Core


Description unit 3 x 1.5 3 x 2.5 3x4 3x6 3 x 10 3 x 16 3 x 25 3 x 35 3 x 50 3 x 70 3 x 95 3 x 120 3 x 150 3 x 185 3 x 240 3 x 300 3 x 400

Conductor material Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper
Class / Standard 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228

Diameter of Conductor (Approx.) mm 1.6 2.0 2.5 3.1 3.7 4.6 5.9 7.0 8.1 9.6 11.4 12.7 14.1 15.8 18.1 20.4 23.5

Fire Barrier material Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica
Insulation material XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE

Insulation thickness (Nominal) mm 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0
Diameter over Insulation (Approx.) mm 4.1 4.6 4.8 5.4 6.0 6.9 8.5 9.7 11.0 12.7 14.5 16.0 17.9 19.9 22.4 24.9 28.5
Oversheath material LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF

Oversheath thickness (Nominal) mm 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.1 2.3 2.4 2.6 2.7 3.0
Overall diameter (Min.) mm 12 13 13 14 16 18 21 24 27 30 35 38 42 47 53 58 66
(Max.) mm 15 16 17 18 19 21 24 27 29 33 37 41 45 50 56 61 70

Total cable weight (Approx.) kg/km 215 260 290 370 510 720 1065 1395 1845 2550 3430 4255 5240 6525 8450 10480 13660

Minimum bending radius mm 60 64 68 72 76 84 96 135 145 165 185 205 225 250 336 366 420
Maximum conductor DC resistance at 20°C Ohm/km 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.047
Conductor AC resistance at 90°C and frequency 50 Hz Ohm/km 15.43 9.45 5.88 3.93 2.33 1.47 0.927 0.669 0.494 0.343 0.248 0.197 0.160 0.129 0.100 0.081 0.065
Inductive reactance at frequency 50 Hz Ohm/km 0.103 0.097 0.091 0.087 0.079 0.076 0.076 0.074 0.073 0.072 0.070 0.070 0.071 0.071 0.070 0.069 0.069
Minimum Insulation Resistance at 20°C Mohm-km 678 600 562 491 432 367 382 333 323 307 264 261 274 282 265 250 243

Page 11 of 19
Spec No.: FRC-LV-CHF-A00-MC Rev.: 02 Date: 4 Aug 2022
Phelps Dodge International (Thailand) Limited

DRAWING & CONSTRUCTION OF


0.6/1 kV CU/MICA/XLPE/LSHF 4-core
Standard.: IEC 60502-1, IEC 60332-3 CAT A/B/C, BS 6387 (CWZ), IEC 60754-1&-2, IEC 61034-2, DEF STAN 02-713

No. Description Type

1 1 Conductor Round Stranded Copper with Mica Tape


XLPE

2 Insulation Core Identification :


2 Brown, Black, Grey and Blue

3 Polypropylene filler (if necessary)


LSHF
3
Orange

4 Oversheath +UV Sunlight Resistance

Figure 3 – Cable drawing of 0.6/1 kV CU/MICA/XLPE/LSHF 4-Core

Page 12 of 19
Spec No.: FRC-LV-CHF-A00-MC Rev.: 02 Date: 4 Aug 2022
Phelps Dodge International (Thailand) Limited

Table 3 – Technical data of 0.6/1 kV CU/MICA/XLPE/LSHF 4-Core


Description unit 4 x 1.5 4 x 2.5 4x4 4x6 4 x 10 4 x 16 4 x 25 4 x 35 4 x 50 4 x 70 4 x 95 4 x 120 4 x 150 4 x 185 4 x 240 4 x 300 4 x 400

Conductor material Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper
Class / Standard 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228

Diameter of Conductor (Approx.) mm 1.6 2.0 2.5 3.1 3.7 4.6 5.9 7.0 8.1 9.6 11.4 12.7 14.1 15.8 18.1 20.4 23.5

Fire Barrier material Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica
Insulation material XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE

Insulation thickness (Nominal) mm 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0
Diameter over Insulation (Approx.) mm 4.1 4.6 4.8 5.4 6.0 6.9 8.5 9.7 11.0 12.7 14.5 16.0 17.9 19.9 22.4 24.9 28.5
Oversheath material LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF
Oversheath thickness (Nominal) mm 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.0 2.1 2.3 2.4 2.6 2.8 3.0 3.3
Overall diameter (Min.) mm 13 14 15 16 17 20 23 26 29 34 39 42 47 52 59 65 74
(Max.) mm 16 17 18 19 20 22 26 29 32 37 41 45 50 56 62 69 78
Total cable weight (Approx.) kg/km 250 305 345 445 630 895 1335 1760 2330 3255 4385 5465 6705 8380 10855 13505 17590

Minimum bending radius mm 64 68 72 76 80 88 130 145 160 185 205 225 250 336 372 414 468
Maximum conductor DC resistance at 20°C Ohm/km 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.047
Conductor AC resistance at 90°C and frequency 50 Hz Ohm/km 15.43 9.45 5.88 3.93 2.33 1.47 0.927 0.669 0.494 0.343 0.247 0.197 0.160 0.129 0.099 0.080 0.065
Inductive reactance at frequency 50 Hz Ohm/km 0.110 0.104 0.099 0.094 0.087 0.083 0.083 0.081 0.080 0.079 0.078 0.077 0.078 0.078 0.077 0.077 0.076
Minimum Insulation Resistance at 20°C Mohm-km 678 600 562 491 432 367 382 333 323 307 264 261 274 282 265 250 243

Page 13 of 19
Spec No.: FRC-LV-CHF-A00-MC Rev.: 02 Date: 4 Aug 2022
Phelps Dodge International (Thailand) Limited

DRAWING & CONSTRUCTION OF


0.6/1kV Cu/MICA/XLPE/LSHF 2-core with ground
Standard.: IEC 60502-1, IEC 60332-3 CAT A/B/C, BS 6387 (CWZ), IEC 60754-1&-2, IEC 61034-2, DEF STAN 02-713

No. Description Type


1 Conductor Round Stranded Copper with Mica Tape
1
XLPE
2 Insulation Brown and Blue
Ground core: Green/Yellow
2
3 Polypropylene filler (if necessary)
LSHF
Orange
3
+UV Sunlight Resistance
4 Oversheath

4 #REF!

Figure 4 – Cable drawing of 0.6/1 kV CU/MICA/XLPE/LSHF 2-Core with Ground

Page 14 of 19
Spec No.: FRC-LV-CHF-A00-MC Rev.: 02 Date: 4 Aug 2022
Phelps Dodge International (Thailand) Limited

Table 4 – Technical data of 0.6/1 kV CU/MICA/XLPE/LSHF 2-Core with Ground


Description unit 2x1.5+1.5 2x2.5+2.5 2x4+4 2x6+6 2x10+10 2x16+16 2x25+16 2x35+16 2x50+25 2x70+35 2x95+50 2x120+70 2x150+95 2x185+95 2x240+120 2x300+150 2x400+240
Conductor material Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper
Class / Standard 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228

Diameter of Conductor (Phase) (Approx.) mm 1.6 2.0 2.5 3.1 3.7 4.6 5.9 7.0 8.1 9.6 11.4 12.7 14.1 15.8 18.1 20.4 23.5
Diameter of Conductor (Ground) (Approx.) mm 1.6 2.0 2.5 3.1 3.7 4.6 4.6 4.6 5.9 7.0 8.1 9.6 11.4 11.4 12.7 14.1 18.1

Fire Barrier material Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica
Insulation material XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE
Insulation thickness (Phase) (Nominal) mm 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0
Diameter over Insulation (Phase) (Approx.) mm 4.1 4.6 4.5 5.1 5.7 6.6 8.3 9.4 10.8 12.4 14.3 15.8 17.6 19.6 22.1 24.7 28.2

Insulation thickness (Ground) (Nominal) mm 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.1 1.2 1.4 1.7
Diameter over Insulation (Ground) (Approx.) mm 4.1 4.6 4.5 5.1 5.7 6.6 6.6 6.6 8.3 9.4 10.8 12.4 14.3 14.3 15.8 17.6 22.1

Oversheath material LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF
Oversheath thickness (Nominal) mm 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.2 2.3 2.4 2.6 2.9

Overall diameter (Min.) mm 12 13 13 14 15 17 20 22 25 28 32 35 39 43 48 54 62


(Max.) mm 15 16 16 17 18 20 23 25 28 31 35 39 43 47 52 57 66

Total cable weight (Approx.) kg/km 205 250 285 365 505 715 950 1175 1585 2160 2900 3675 4630 5515 7065 8780 11925

Maximum conductor DC resistance at 20°C (Phase) Ohm/km 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Maximum conductor DC resistance at 20°C (Ground) Ohm/km 12.1 7.41 4.61 3.08 1.83 1.15 1.15 1.15 0.727 0.524 0.387 0.268 0.193 0.193 0.153 0.124 0.0754
Minimum Insulation Resistance at 20°C (Phase) Mohm-km 678 600 602 521 455 383 396 343 332 314 269 266 279 286 268 253 246

Minimum Insulation Resistance at 20°C (Ground) Mohm-km 678 600 602 521 455 383 383 383 396 343 332 314 269 269 266 279 268

Page 15 of 19
Spec No.: FRC-LV-CHF-A00-MC Rev.: 02 Date: 4 Aug 2022
Phelps Dodge International (Thailand) Limited

DRAWING & CONSTRUCTION OF


0.6/1kV Cu/MICA/XLPE/LSHF 3-core with ground
Standard.: IEC 60502-1, IEC 60332-3 CAT A/B/C, BS 6387 (CWZ), IEC 60754-1&-2, IEC 61034-2, DEF STAN 02-713

No. Description Type


1 Conductor Round Stranded Copper with Mica Tape
1 XLPE
2 Insulation Brown, Black, Grey

2 Ground core: Green/Yellow


3 Polypropylene filler (if necessary)
LSHF
3
Orange
+UV Sunlight Resistance
4 4 Oversheath

+Oil Resistance

Figure 5 – Cable drawing of 0.6/1 kV CU/MICA/XLPE/LSHF 3-Core with Ground

Page 16 of 19
Spec No.: FRC-LV-CHF-A00-MC Rev.: 02 Date: 4 Aug 2022
Phelps Dodge International (Thailand) Limited

Table 5 – Technical data of 0.6/1 kV CU/MICA/XLPE/LSHF 3-Core with Ground


Description unit 3x1.5+1.5 3x2.5+2.5 3x4+4 3x6+6 3x10+10 3x16+16 3x25+16 3x35+16 3x50+25 3x70+35 3x95+50 3x120+70 3x150+95 3x185+95 3x240+120 3x300+150 3x400+240
Conductor material Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper
Class / Standard 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228

Diameter of Conductor (Phase) (Approx.) mm 1.6 2.0 2.5 3.1 3.7 4.6 5.9 7.0 8.1 9.6 11.4 12.7 14.1 15.8 18.1 20.4 23.5
Diameter of Conductor (Ground) (Approx.) mm 1.6 2.0 2.5 3.1 3.7 4.6 4.6 4.6 5.9 7.0 8.1 9.6 11.4 11.4 12.7 14.1 18.1

Fire Barrier material Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica
Insulation material XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE
Insulation thickness (Phase) (Nominal) mm 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0
Diameter over Insulation (Phase) (Approx.) mm 4.1 4.6 4.5 5.1 5.7 6.6 8.3 9.4 10.8 12.4 14.3 15.8 17.6 19.6 22.1 24.7 28.2
Insulation thickness (Ground) (Nominal) mm 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.1 1.2 1.4 1.7
Diameter over Insulation (Ground) (Approx.) mm 4.1 4.6 4.5 5.1 5.7 6.6 6.6 6.6 8.3 9.4 10.8 12.4 14.3 14.3 15.8 17.6 22.1

Oversheath material LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF
Oversheath thickness (Nominal) mm 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.1 2.2 2.3 2.5 2.6 2.8 3.1
Overall diameter (Min.) mm 13 14 14 15 17 19 22 24 27 31 36 40 44 49 54 60 70
(Max.) mm 16 17 17 18 20 22 25 27 31 35 39 43 48 52 58 64 74
Total cable weight (Approx.) kg/km 250 310 340 445 625 890 1220 1535 2075 2860 3870 4890 6095 7360 9450 11745 15825

Maximum conductor DC resistance at 20°C (Phase) Ohm/km 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Maximum conductor DC resistance at 20°C (Ground) Ohm/km 12.1 7.41 4.61 3.08 1.83 1.15 1.15 1.15 0.727 0.524 0.387 0.268 0.193 0.193 0.153 0.124 0.0754
Minimum Insulation Resistance at 20°C (Phase) Mohm-km 678 600 602 521 455 383 396 343 332 314 269 266 279 286 268 253 246

Minimum Insulation Resistance at 20°C (Ground) Mohm-km 678 600 602 521 455 383 383 383 396 343 332 314 269 269 266 279 268

Page 17 of 19
Spec No.: FRC-LV-CHF-A00-MC Rev.: 02 Date: 4 Aug 2022
Phelps Dodge International (Thailand) Limited

DRAWING & CONSTRUCTION OF


0.6/1kV Cu/MICA/XLPE/LSHF 4-core with ground
Standard.: IEC 60502-1, IEC 60332-3 CAT A/B/C, BS 6387 (CWZ), IEC 60754-1&-2, IEC 61034-2, DEF STAN 02-713

No. Description Type

1 1 Conductor Round Stranded Copper with Mica Tape


XLPE
2 Insulation Brown, Black, Grey, Blue
2 Ground core: Green/Yellow
3 Polypropylene filler (if necessary)
LSHF
3
Orange
+UV Sunlight Resistance
4 Oversheath

4 +Not apply

Figure 6 – Cable drawing of 0.6/1 kV CU/MICA/XLPE/LSHF 4-Core with Ground

Page 18 of 19
Spec No.: FRC-LV-CHF-A00-MC Rev.: 02 Date: 4 Aug 2022
Phelps Dodge International (Thailand) Limited

Table 6 – Technical data of 0.6/1 kV CU/MICA/XLPE/LSHF 4-Core with Ground


Description unit 4x1.5+1.5 4x2.5+2.5 4x4+4 4x6+6 4x10+10 4x16+16 4x25+16 4x35+16 4x50+25 4x70+35 4x95+50 4x120+70 4x150+95 4x185+95 4x240+120 4x300+150 4x400+240
Conductor material Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper
Class / Standard 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228 2/IEC60228

Diameter of Conductor (Phase) (Approx.) mm 1.6 2.0 2.5 3.1 3.7 4.6 5.9 7.0 8.1 9.6 11.4 12.7 14.1 15.8 18.1 20.4 23.5
Diameter of Conductor (Ground) (Approx.) mm 1.6 2.0 2.5 3.1 3.7 4.6 4.6 4.6 5.9 7.0 8.1 9.6 11.4 11.4 12.7 14.1 18.1

Fire Barrier material Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica Mica
Insulation material XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE
Insulation thickness (Phase) (Nominal) mm 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0
Diameter over Insulation (Phase) (Approx.) mm 4.1 4.6 4.5 5.1 5.7 6.6 8.3 9.4 10.8 12.4 14.3 15.8 17.6 19.6 22.1 24.7 28.2
Insulation thickness (Ground) (Nominal) mm 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.1 1.2 1.4 1.7
Diameter over Insulation (Ground) (Approx.) mm 4.1 4.6 4.5 5.1 5.7 6.6 6.6 6.6 8.3 9.4 10.8 12.4 14.3 14.3 15.8 17.6 22.1

Oversheath material LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF LSHF
Oversheath thickness (Nominal) mm 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.2 2.3 2.5 2.6 2.9 3.1 3.4
Overall diameter (Min.) mm 14 15 15 17 18 21 25 28 32 37 42 46 52 57 65 72 82
(Max.) mm 17 18 18 20 22 24 28 31 35 40 46 50 55 61 68 76 86

Total cable weight (Approx.) kg/km 280 350 410 530 755 1080 1540 1975 2665 3685 4985 6260 7790 9500 12295 15275 20315

Maximum conductor DC resistance at 20°C (Phase) Ohm/km 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470
Maximum conductor DC resistance at 20°C (Ground) Ohm/km 12.1 7.41 4.61 3.08 1.83 1.15 1.15 1.15 0.727 0.524 0.387 0.268 0.193 0.193 0.153 0.124 0.0754
Minimum Insulation Resistance at 20°C (Phase) Mohm-km 678 600 602 521 455 383 396 343 332 314 269 266 279 286 268 253 246

Minimum Insulation Resistance at 20°C (Ground) Mohm-km 678 600 602 521 455 383 383 383 396 343 332 314 269 269 266 279 268

Page 19 of 19
Spec No.: FRC-LV-CHF-A00-MC Rev.: 02 Date: 4 Aug 2022