Report Apar Didi
Report Apar Didi
Report Apar Didi
at …………….
Jitendra Silwal
KMC No:
Contents
1. Project Detail..........................................................................................4
1.1 Building Design Parameters.........................................................................................5
1.2 Materials.......................................................................................................................5
1.2.1 Concrete................................................................................................................5
1.2.2 Reinforcement.......................................................................................................5
1.3 Load Calculations.........................................................................................................5
1.3.1 Dead Load.............................................................................................................5
1.3.2 Superimposed Dead Loads....................................................................................5
1.3.3 Live Loads.............................................................................................................6
1.3.4 Seismic Loads.......................................................................................................6
1.4 Load Combination........................................................................................................8
1.5 Mass Source..................................................................................................................8
1.6 Torsional Irregularity Check........................................................................................8
2. Structural Analysis.................................................................................9
2.1 3D modelling of the building.....................................................................................10
3. Design of Elements:..............................................................................20
3.1.1 Sample Design of Column..................................................................................27
3.1.2 Sample Design of Beam......................................................................................29
3.1.3 Sample Design of Footing...................................................................................31
3.1.4 Design of Stair.....................................................................................................39
3.1.5 Sample Design of Slab........................................................................................41
Location …………..
Type of Building: The Building covers a total plinth area of ground floor 747.3 sq
ft. The building has been designed for three storeys and stair
cover.
This report has been prepared as a part of the structural engineering analysis and design of
buildings.
1.2 Materials
Following loads have been considered for the analysis and design of the building based on the
relevant Indian Standards.
1.2.1 Concrete
Concrete is to conform to IS 456:2000 Structural use of concrete. Unless noted otherwise
concrete is to be normal-weight, with a typical dry density of 2400 kg/m3. Concrete is to
achieve the 28-day cube strength as 20 N/mm2and 25 N/mm2.
Grade of Concrete : M20
1.2.2 Reinforcement
Reinforcement bars are to be in accordance with IS 456:2000 specification for carbon
steel bars for the reinforcement of concrete is to be in accordance with IS 1786:2008
specification for high deformed steel bars for the reinforcement of concrete.
The following design strengths are to be used for the design of concrete and
reinforcement.
Grade of steel : High Yield Fe 500 N/mm2
ETABS utilizes the following procedure to generate the lateral seismic loads.
User provides seismic zone co-efficient and desired seismic load command.
The structural period (T) is calculated manually and input in the software.
W is obtained from the weight data provided by the user.
The total lateral seismic load (base shear) is then distributed by the program among
different levels of the structure
The concrete has been designed using limit state method based on IS 456 –2000. The detailing
of reinforcement has been based on IS 13920 –2016 and where required Uniform Building
Code of USA has been also referred to for detailing of reinforcement. The design has been
based on the most critical load combination mentioned above.
The analysis and design have been carried out using software called ETABS v20.3, which is a
special purpose computer program developed specifically for building structures. It provides
the Structural Engineer with all the tools necessary to create, modify, analyze, design, and
optimize the structural elements in a building model. The building geometry based on
architectural drawings been generated using above named software. The dead load, live load
and lateral loads were supplied to the digital models as per standard code of practices. Several
analysis runs were performed to achieve the best result to meet the design and service
requirements.
The design of all structural elements is done using ‘Limit State Method’. All relevant Limit
State is considered in design to ensure adequate safety and serviceability.
The design includes design for durability, construction and use in service should be
considered as a whole. The realization of design objectives requires compliance with clearly
defined standards for materials, production, workmanship, and also maintenance and use of
structure in service.
This section includes all the design process of sample calculation for a single element as
column, beam, slab and foundation.
Section Properties
b (mm) h (mm) dc (mm) Cover (Torsion) (mm)
355.6 355.6 56 30
Material Properties
Ec (MPa) fck (MPa) Lt.Wt Factor (Unitless) fy (MPa) fys (MPa)
22360.68 20 1 500 500
Notes:
N/A: Not Applicable
N/C: Not Calculated
N/N: Not Needed
Section Properties
b (mm) h (mm) bf (mm) ds (mm) dct (mm) dcb (mm)
228.6 355.6 228.6 0 35 35
Material Properties
Ec (MPa) fck (MPa) Lt.Wt Factor (Unitless) fy (MPa) fys (MPa)
22360.68 20 1 500 500
Adopted b= 355 mm
Required d= 259 mm
Adopted d = 315 mm
Adopted D = 355 mm
COMBINED FOOTING BC
1. DESIGN DATA
3. LONGITUDIONAL BM AND SF
Bending Moment
= 0.87*σy*At (d-(σyAt/(σck*b))
At= 2579 mm² 1093 mm²/m
Use 12 mm bar @ 100 mm c/c 1131 mm²/m
Development Length of 12φ bar = 58φ = 696 mm
Column A
Shear at Distance d from the face of Support =
Vu = 388.96 -(0.35/2 +0.25)* 297.36 = 263 kN
Nominal Shear Stress Ʈv = Vu/(bd) = 0.45 N/mm²
Percent Tensile Steel (Pt) = 0.45
Shear strength of M20 Concrete and 0.45% steel tc = 0.46 N/mm²
OK
Column B
Shear at Distance d from the face of Support =
Vu = 357 -(0.35/2 +0.25)* 297.36 = 208 kN
Nominal Shear Stress Ʈv = Vu/(bd) = 0.4 N/mm²
Percent Tensile Steel (Pt) = 0.45
#REF
! 0.5 N/mm²
OK
Column A
Shear Force Vu = 441 - (0.35 * 0.35* 126) = 426 kN
Nominal Shear Stress Ʈv = Vu/(bd) = 0.30 N/mm²
OK
Column B
Shear Force Vu = 691.5 - (0.35 * 0.35* 126) = 676 kN
Nominal Shear Stress Ʈv = Vu/(bd) = 0.36 N/mm²
OK
8. TRANSVERSE REINFORCEMENT
GRID -C-1-3
N/
Grade of Concrete used (σck) = 20.0 mm2
N/
Grade of steel used (σy) = 500.0 mm2
Allowable bearing capacity of Site = 95 KN/m2
Size of Column 0.4 m
Span Between Column B1-B2 = 2.52 m
Span Between Column B2-B3 = 3.74 m
Column Loads in KN
Load on Left Edge Column = 233 kN
Load on Center Column = 291 kN
Load on Right Edge Column = 238 kN
c= 9.90
L1+L3= 3.3 m
Provide L3 = 1.4 m
Design of Beam
121.7
Upward Reaction = 3 KN/m
Adopted b= 406 mm
Required d= 281 mm
A B
0.00 1.68 1.07
Reaction
Reaction at Support A (RA) 19.91 kN
Reaction at Support B (RB) 17.95 kN
For Max moment, Point of zero shear from A ia at Distance x
Then, -5.19
x= 1.33 m