Download as pdf or txt
Download as pdf or txt
You are on page 1of 350

Smart Substation Control and Protection

SSC600

IEC 61850 Parameter List


1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Table of Contents

About this manual .................................................................................................................................................................................... 6

Explanations of tables ............................................................................................................................................................................. 7


Protection LLN0: G7................................................................................................................................................................................. 7

Security application: H3 ........................................................................................................................................................................ 19

Programmable LEDs: F2 ....................................................................................................................................................................... 19


GSELPRT1: D2 ........................................................................................................................................................................................ 61

61850-8-1 MMS: E1 ................................................................................................................................................................................. 63

GNRLLTMS1: C2..................................................................................................................................................................................... 64
MVGAPC1: C1 ......................................................................................................................................................................................... 71

SRGAPC1: B1 ......................................................................................................................................................................................... 72

TONGAPC1: B1 ....................................................................................................................................................................................... 74
TOFGAPC1: B1 ....................................................................................................................................................................................... 75

PTGAPC1: C1 .......................................................................................................................................................................................... 76

SCA4GAPC1: B1..................................................................................................................................................................................... 77

MVI4GAPC1: B1 ...................................................................................................................................................................................... 78

Global conditioning: G2......................................................................................................................................................................... 79

TPGAPC1: C1 .......................................................................................................................................................................................... 79

TPSGAPC1: C1 ....................................................................................................................................................................................... 80

TPMGAPC1: C1 ....................................................................................................................................................................................... 80

FLTRFRC1: Fault record: H3 ................................................................................................................................................................. 81


SPCGAPC1: D1 ....................................................................................................................................................................................... 87

VMMXU1: Three-phase voltage measurement: D1 ............................................................................................................................. 95

VSMSQI1: Sequence voltage measurement: C1 ................................................................................................................................. 98


RESVMMXU1: Residual voltage measurement: E1 .......................................................................................................................... 101

IEC60870-5-101/104: IEC60870-5-101/104: F1 .................................................................................................................................... 102

IEC60870-5-101/104: IEC60870-5-101/104: F1 .................................................................................................................................... 106


IEC60870-5-101/104: IEC60870-5-101/104: F1 .................................................................................................................................... 110

IEC60870-5-101/104: IEC60870-5-101/104: F1 .................................................................................................................................... 114

IEC60870-5-101/104: IEC60870-5-101/104: F1 .................................................................................................................................... 118


PHLPTOC1: Three phase non-directional OC, low stage: F ............................................................................................................ 121

PHHPTOC1: Three phase non-directional OC, high stage: F1 ........................................................................................................ 123

PHIPTOC1: Three phase non-directional OC, inst. stage: E1 .......................................................................................................... 125


EFLPTOC1: Non-directional earth-fault protection, low stage: G1 ................................................................................................. 126

EFHPTOC1: Non-directional earth-fault protection, high stage: F1 ............................................................................................... 128

EFIPTOC1: Non-directional earth-fault protection, inst. stage: F1 ................................................................................................. 130

II
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

NSPTOC1: Negative Phase sequence current protection: E1 ......................................................................................................... 131

ROVPTOV1: Residual overvoltage protection: D1 ............................................................................................................................ 133

PHPTUV1: Three phase undervoltage protection: D1 ...................................................................................................................... 134


PHPTOV1: Three phase overvoltage protection: D1 ........................................................................................................................ 136

PSPTUV1: Positive sequence undervoltage: D1 ............................................................................................................................... 138

NSPTOV1: Negative sequence overvoltage: D1 ............................................................................................................................... 139


FRPFRQ1: Frequency protection: D1................................................................................................................................................. 140

CCBRBRF1: Circuit breaker failure protection: E1 ........................................................................................................................... 142

INRPHAR1: Three-phase inrush detector: C1 ................................................................................................................................... 144


CBPSOF1: Switch on to fault: B1 ....................................................................................................................................................... 144

TRPPTRC1: Trip logic: F1 ................................................................................................................................................................... 145

MAPGAPC1: Multipurpose analogue protection function: C1 ........................................................................................................ 146


SSCBR1: Circuit breaker condition monitoring: F1 ......................................................................................................................... 147

MDSOPT1: Generic operation time supervision for machines and devices: D1 ........................................................................... 155

CMMXU1: Three-phase current measurement: E1 ........................................................................................................................... 156

CSMSQI1: Sequence current measurement: C1 ............................................................................................................................... 159

RESCMMXU1: Residual current measurement: E1 .......................................................................................................................... 162

PEMMXU1: Three-phase power and energy measurement: D1 ...................................................................................................... 164

FMMXU1: Frequency measurement: B1 ............................................................................................................................................ 168

SEQSPVC1: Fuse failure supervision: F ............................................................................................................................................ 168

DPHLPDOC1: Three-phase directional overcurrent, low stage: E1 ................................................................................................ 170

DPHHPDOC1: Three-phase directional overcurrent, high stage: E1 .............................................................................................. 174

DEFLPDEF1: Directional earth-fault, low stage: F1 .......................................................................................................................... 178

DEFHPDEF1: Directional earth-fault, high stage: F1 ........................................................................................................................ 182

DOPPDPR1: Reverse power / Directional over power protection: A1 ............................................................................................ 185

PDNSPTOC1: Phase discontinuity protection: D1 ........................................................................................................................... 187

T1PTTR1: Thermal overload protection, one time constant: F1 ..................................................................................................... 188

DARREC1: Autorecloser: F1 ............................................................................................................................................................... 190

SECRSYN1: Synchrocheck: C1 .......................................................................................................................................................... 199


EFPADM1: Neutral admittance protection: E1 .................................................................................................................................. 203

MFADPSDE1: Multi-frequency neutral admittance earth-fault protection: C................................................................................. 205

WPWDE1: Wattmetric directional earth-fault: C1 ............................................................................................................................. 208


INTRPTEF1: Intermittent earth fault protection: E1 .......................................................................................................................... 210

SCEFRFLO1: Fault locator: B1 ........................................................................................................................................................... 211

DQPTUV1: Directional reactive power and under voltage protection: A1 ..................................................................................... 217
LVRTPTUV1: Low voltage ride through protection function: A1 .................................................................................................... 219

VMHAI1: Voltage total harmonic distortion: C1 ................................................................................................................................ 222

PHQVVR1: Short duration voltage variations: D1 ............................................................................................................................ 223


III
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

VSQVUB1: Voltage unbalance measurement: C1............................................................................................................................. 232

CMHAI1: Current total demand distortion: D1 .................................................................................................................................. 235

OLATCC1: On-load tap changer controller: D2 ................................................................................................................................ 237


TPOSYLTC1: Tap changer position indication: D1 .......................................................................................................................... 244

ARCSARC1: Arc protection: B1.......................................................................................................................................................... 245

LSHDPFRQ1: Load shedding: C1 ....................................................................................................................................................... 246


SMVRECEIVE1: B2 ............................................................................................................................................................................... 249

MNSPTOC1: Negative-phase-sequence time overcurrent protection for machines: C1 .............................................................. 250

LOFLPTUC1: Loss of load protection: C1 ......................................................................................................................................... 252


JAMPTOC1: Stalled motor: C1 ............................................................................................................................................................ 253

STTPMSU1: Motor startup supervision: C2 ...................................................................................................................................... 254

PREVPTOC1: Phase reversal protection: B1 .................................................................................................................................... 257


MPTTR1: Motor thermal overload protection: F1 ............................................................................................................................. 258

ESMGAPC1: Allow emergency start: C1............................................................................................................................................ 261

T2PTTR1: Thermal overload protection, two time constants: D1 ................................................................................................... 262

TR2PTDF1: Transformer differential protection of two winding transformers: C1 ....................................................................... 264

LREFPNDF1: Low impedance restricted earth fault protection: D1 ............................................................................................... 272

UZPDIS1: Under impedance protection: A1 ...................................................................................................................................... 274

DSTPDIS1: Distance protection: B1 ................................................................................................................................................... 275

BBPBDF1: Busbar differential protection: B ..................................................................................................................................... 308

ZNRSRC1: Busbar differential zone selection function: A1 ............................................................................................................ 314

ANOGAPC1: Anomaly detection: A.................................................................................................................................................... 316

LBRDOB1: Load blinder: A ................................................................................................................................................................. 318

COLPTOC1: Capacitor bank overload protection: D ........................................................................................................................ 319

CUBPTOC1: Capacitor bank unbalance current, double Y bridge: D ............................................................................................. 322

HCUBPTOC1: Capacitor bank unbalance current, H bridge: D ....................................................................................................... 326

SRCPTOC1: Capacitor resonance protection: D .............................................................................................................................. 330

Ethernet channel(s): A1 ....................................................................................................................................................................... 332

Redundant Ethernet: A1 ...................................................................................................................................................................... 333


CMSUM1: C1 ......................................................................................................................................................................................... 333

CMSWI1: B1 .......................................................................................................................................................................................... 334

VMSWI1: C1 .......................................................................................................................................................................................... 335


Control LLN0: Control general: D1 ..................................................................................................................................................... 336

CBXCBR1: D1 ....................................................................................................................................................................................... 338

DCXSWI1: C1 ........................................................................................................................................................................................ 341


ESXSWI1: C1 ......................................................................................................................................................................................... 343

DCSXSWI1: C1 ...................................................................................................................................................................................... 345

ESSXSWI1: C1 ...................................................................................................................................................................................... 346


IV
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

DR LLN0: Disturbance recorder: H2................................................................................................................................................... 347

Binary channel: Disturbance recorder binary channel: A1 ............................................................................................................. 348

V
ABB Distribution Solutions – Digital Substation Products
About this manual

Before attempting any operation with SSC600, read carefully the device documentation first.
This document is addressed to anyone who needs to interact with SSC600 and its IEC 61850 features in more detail.

Revision History
Revision Date Note
A 11 Jan 2019 SSC600 v1.0
B 30 March 2020 FP1 added

C 15 Sept. 2020 FP2 added

D 23 Nov 2021 FP3 added

E 29 Nov 2022 FP4 added

Applicability
This manual is applicable to all SSC600 Smart Substation Control and Protection device versions mentioned in document Revision History above or newer versions if document update is not required.
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Explanations of tables
IEC 61850 Function IEC 61850 name
IEC 60617 Function IEC 60617 name
ANSI of function ANSI name
Category INP=input; OUT=Output; CFG=Configuration; SET=Settings; MON=Monitoring; CTR=Control; TES=Test; INF=Information; VER=Version
IECName Complete 61850 name of the data attribute (excluding the IED name)
CDC Common data class of the data object according the IEC 61850-7-3
Type Data attribute type (maximum length for strings)
FC Functional constraint acording the IEC 61850: ST=Status, MX=Measurement, CO=Control, SP=Setting; SG=Setting group, CF=Configuration, EX=Extension
ED2=Edition 2 only, ED1 edition 1 only, B=Basic, A=Advanced, P=Protocol only, H=LHMI only, O=Operator R/W, E=Engineer R/W, A=Administrator R/W, C=Coldboot, I=Application parameter re-init, #=Dependent on the
Access
product variant
Default Default value of settings, inputs and version data, settings are in pu level
Dataset Event handling default dataset
Event Event handling: P=Protocol, H=LHMI, T=transient (no deactivation events)
CMT MB=Modbus, DN=DNP, I1=IEC 60870-5-101/104, I3=IEC 60870-5-103
Parameter name Parameter name in menus
Parameter desc Parameter help in menus/ tooltip in PCM
Parameter
Enumeration values; minimum and maximum in pu level
range
Menu path Complete menu path
Channel
Relation to analog channel (if defined)
relation

Protection LLN0: G7
IEC 61850-7-4:2007
IEC IEC Parameter Parameter Channel
ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
61850 60617 name desc relation
Setting
Protection LD0.LLN0.Act2SetGr.stVa
INP SPC BOOLEAN ST B 0 I1 SG_2_ACT group 2 is Monitoring\Setting group\Outputs
LLN0 l
active
Setting
Protection LD0.LLN0.Act3SetGr.stVa
INP SPC BOOLEAN ST B 0 I1 SG_3_ACT group 3 is Monitoring\Setting group\Outputs
LLN0 l
active
Setting
Protection LD0.LLN0.Act4SetGr.stVa
INP SPC BOOLEAN ST B 0 I1 SG_4_ACT group 4 is Monitoring\Setting group\Outputs
LLN0 l
active
Setting
Protection LD0.LLN0.Act5SetGr.stVa
INP SPC BOOLEAN ST B 0 I1 SG_5_ACT group 5 is Monitoring\Setting group\Outputs
LLN0 l
active
Setting
Protection LD0.LLN0.Act6SetGr.stVa
INP SPC BOOLEAN ST B 0 I1 SG_6_ACT group 6 is Monitoring\Setting group\Outputs
LLN0 l
active
7
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

(ACT
Protection
OUT Channel StatIed P,H GRPOFF output
LLN0
channel)
Setting
Protection LD0.LLN0.Act1SetGr.stVa
OUT SPC BOOLEAN ST B I1 SG_1_ACT group 1 is Monitoring\Setting group\Outputs
LLN0 l
active
Setting
Protection LD0.LLN0.Act2SetGr.stVa
OUT SPC BOOLEAN ST B 0 I1 SG_2_ACT group 2 is Monitoring\Setting group\Outputs
LLN0 l
active
Setting
Protection LD0.LLN0.Act3SetGr.stVa
OUT SPC BOOLEAN ST B 0 I1 SG_3_ACT group 3 is Monitoring\Setting group\Outputs
LLN0 l
active
Setting
Protection LD0.LLN0.Act4SetGr.stVa
OUT SPC BOOLEAN ST B 0 I1 SG_4_ACT group 4 is Monitoring\Setting group\Outputs
LLN0 l
active
Setting
Protection LD0.LLN0.Act5SetGr.stVa
OUT SPC BOOLEAN ST B 0 I1 SG_5_ACT group 5 is Monitoring\Setting group\Outputs
LLN0 l
active
Setting
Protection LD0.LLN0.Act6SetGr.stVa
OUT SPC BOOLEAN ST B 0 I1 SG_6_ACT group 6 is Monitoring\Setting group\Outputs
LLN0 l
active
Logic
Protection LD0.LLN0.LgcSelSetGr.st SG_LOGIC_ selection
OUT SPC BOOLEAN ST ED2,B I1 Monitoring\Setting group\Outputs
LLN0 Val SEL for setting
group
Logic
Protection SG_LOGIC_ selection
OUT LD0.LLN0.LgcSelGr.stVal SPC BOOLEAN ST ED1 I1 Monitoring\Setting group\Outputs
LLN0 SEL for setting
group
Clear
Protection LD0.LLN0.IndLEDRs.Ope Indications indication
CTR SPC BOOLEAN CO B 0 I1 0=Cancel; 1=Clear Clear\Clear
LLN0 r.ctlVal and LEDs LEDs and
texts
Clear
Protection LD0.LLN0.ProgLEDRs.Op Programmabl
CTR SPC BOOLEAN CO B 0 I1 programma 0=Cancel; 1=Clear Clear\Clear
LLN0 er.ctlVal e LEDs
ble LEDs
Reset
meterering
minimum
Protection LD0.LLN0.MeasStatRs.Op Metering
CTR SPC BOOLEAN CO B 0 I1 and 0=Cancel; 1=Clear Clear\Clear
LLN0 er.ctlVal records
maximum
recorded
data
Reset all
Protection LD0.LLN0.PQRs.Oper.ctl Power
CTR SPC BOOLEAN CO B 0 I1 power 0=Cancel; 1=Clear Clear\Clear
LLN0 Val quality data
quality data
(Active
Protection LD0.LLN0.ActSetGr.Oper.
CTR INC INT32 CO I1 setting
LLN0 ctlVal
group)

8
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

(Compositi
LD0.LDEV1.ChgFlg.Oper.
Device CTR INC INT32 CO on has
ctlVal
changed)
LD0.LDEV1.WrmStrCmd. Software Reset of
Device CTR SPC BOOLEAN CO B 0 I1 0=Cancel; 1=Activate Configuration\General
Oper.ctlVal reset IED
Clear
LD0.LDEV1.EvtLstClr.Op
Device CTR SPC BOOLEAN CO B 0 I1 Events events in 0=Cancel; 1=Clear Clear\Clear
er.ctlVal
HMI
Protection 1=on2=blocked3=test4=test/blo
MON LD0.LLN0.Beh.stVal ENS Enum ST StatIed P,H (Behaviour)
LLN0 cked5=off
-2=Waiting-
Protection
MON LD0.LLN0.Health.stVal ENS Enum ST StatIed P,H I1 (Health) 1=Test1=Ok2=Warning3=Alar
LLN0
m
Protection LD0.LLN0.NamPlt.param (Name
MON LPL INT32 ST StatIed P,H
LLN0 Rev plate)
Protection (Name
MON LD0.LLN0.NamPlt.valRev LPL INT32 ST StatIed P,H
LLN0 plate)
Number of
Protection LD0.LLN0.ParChgCnt.stV Setting
MON INS INT32 ST B I1 setting 0...20000 Monitoring\IED status\Setting changes
LLN0 al changes
changes
Protection Latest
MON LD0.LLN0.ParChgCnt.t INS Timestamp ST B Setting time Monitoring\IED status\Setting changes
LLN0 setting time
-2=Waiting-
Physical LD0.LPHD1.PhyHealth.st (General
MON ENS Enum ST StatIed P,H I1 1=Test1=Ok2=Warning3=Alar
device Val state)
m
Physical (Power up
MON LD0.LPHD1.PwrUp.stVal SPS BOOLEAN ST StatIed P,H I1
device detected)
LD0.LDEV1.WrmStrDet.st (Warm start
Device MON SPS BOOLEAN ST StatIed P,H I1
Val detected)
(Watchdog
LD0.LDEV1.WacTrgDet.st
Device MON SPS BOOLEAN ST StatIed P,H I1 reset
Val
detected)
1=All ok; 2=System; 5=Time
synch error; 6=Over
temperature; 10=Watchdog
reset; 11=Power down det.;
20=IEC 61850 error;
21=Modbus error; 22=DNP3
error; 23=PNIO error;
24=Dataset error; 25=Report
LD0.LDEV1.DevWrn.stVa IED cont. error; 26=GOOSE contr.
Device MON ENS Enum ST B StatIed P,H I1 Warning Monitoring\IED status\Self-supervision
l warning error; 27=SCL config error;
28=Logic error; 29=SMT logic
error; 30=GOOSE input error;
31=ACT error; 32=GOOSE rec.
error; 33=AFL error; 34=SMV
error; 35=Comm. channel down;
40=Unack card comp.;
85=ARC1 cont. light; 86=ARC2
cont. light; 87=ARC3 cont.
9
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

light; 50=Protection comm.;


96=RTD card error,X130;
106=RTD meas. error,X130;
112=UPD voltage low,X115;
113=UPS comm. error,X115;
114=UPS cmd fail,X115;
115=Breaker oper. fail; 90=RTD
card error,X105; 91=RTD card
error,X115; 92=RTD card
error,X000; 93=RTD card
error,X100; 94=RTD card
error,X110; 95=RTD card
error,X120; 100=RTD meas.
error,X105; 101=RTD meas.
error,X115; 102=RTD meas.
error,X000; 103=RTD meas.
error,X100; 104=RTD meas.
error,X110; 105=RTD meas.
error,X120; 116=License check
fail; 117=Real-time task's
latency exceeded;
118=Redundant PSU fail;
36=Settings mismatch;
119=Internal error; 120=Internal
server connectivity failure
1=All ok; 2=System error;
3=Runtime app. error;
4=Runtime exec error; 7=File
system error; 8=Test; 10=SW
watchdog error; 11=Uaux error;
32=Settings error; 43=SO-
relay(s),X100; 44=SO-
relay(s),X110; 46=SO-
relay(s),X130; 53=PO-
relay(s),X100; 54=PO-
relay(s),X110; 56=PO-
relay(s),X130; 57=Light sensor
error; 62=Conf.error,X000;
IED
63=Conf.error,X100;
Device MON LD0.LDEV1.DevFail.stVal ENS Enum ST B StatIed P,H I1 Internal Fault internal Monitoring\IED status\Self-supervision
64=Conf.error,X110;
fault
65=Conf.error,X120;
66=Conf.error,X130; 72=Card
error,X000; 73=Card
error,X100; 74=Card
error,X110; 75=Card
error,X120; 76=Card
error,X130; 79=LHMI module;
80=RAM error; 81=ROM error;
82=EEPROM error; 83=FPGA
error; 84=RTC error; 96=RTD
card error,X130; 110=UPD card
error,X115; 111=UPD self
check,X115; 40=SO-

10
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

relay(s),X105; 41=SO-
relay(s),X115; 45=SO-
relay(s),X120; 50=PO-
relay(s),X105; 51=PO-
relay(s),X115; 55=PO-
relay(s),X120;
60=Conf.error,X105;
61=Conf.error,X115; 70=Card
error,X105; 71=Card
error,X115; 90=RTD card
error,X105; 91=RTD card
error,X115; 92=RTD card
error,X000; 93=RTD card
error,X100; 94=RTD card
error,X110; 95=RTD card
error,X120; 116=COM card
error; 117=License check fail;
118=Real-time task's latency
exceeded; 119=Redundant PSU
fail; 34=SMV error; 36=Settings
mismatch; 120=Internal error;
121=Internal server connectivity
failure
Number of
LD0.LDEV1.ChgAckCnt.st No of comp. Monitoring\IED status\Composition
Device MON INS INT32 ST A I1 compositio 0...100000
Val changes changes
n changes
IED boot
Device MON LD0.LDEV1.WrmStrCmd.t SPC Timestamp ST B Boot up time Monitoring\IED status\Self-supervision
up time
Operation
mode for
Protection LD0.LLN0.OpModSetGr.s SG operation 0=Operator; 1=Logic mode 1;
CFG ENG Enum SP B 0 setting Configuration\Setting group
LLN0 etVal mode 2=Logic mode 2
group
change
SV delay
based on
Protection LD0.LLN0.SetSvDlPct.set
CFG ING INT32 SP B,C 100 SV delay nominal 10...5000 % Configuration\System
LLN0 Val
network
frequency
Customer
LD0.LINF1.UnitNam.setV VisString255 SSC60 Unit name
informatio CFG VSG SP ED2,B Unit name Configuration\System
al (20) 0 in system
n
Customer
LD0.LINF1.NamPlt.eBayN VisString255 SSC60 Unit name
informatio CFG LPL EX ED1 Unit name Configuration\System
ame (20) 0 in system
n
IP address
LD0.LDEV1.IPAddr.setVa VisString255 ED2,B, 192.16 Configuration\Communication\Ethernet
Device CFG VSG SP IP address for rear
l (20) C 8.2.10 \Rear port(s)
port(s)
IP address
VisString255 192.16 Configuration\Communication\Ethernet
Device CFG LD0.LDEV1.NamPlt.eIp LPL EX ED1,C IP address for rear
(20) 8.2.10 \Rear port(s)
port(s)

11
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Subnet
LD0.LDEV1.IPAddrSubNt VisString255 ED2,B, 255.25 Configuration\Communication\Ethernet
Device CFG VSG SP Subnet mask mask for
w.setVal (20) C 5.255.0 \Rear port(s)
rear port(s)
Subnet
LD0.LDEV1.NamPlt.eIpSu VisString255 255.25 Configuration\Communication\Ethernet
Device CFG LPL EX ED1,C Subnet mask mask for
bNet (20) 5.255.0 \Rear port(s)
rear port(s)
Default
LD0.LDEV1.IPAddrGtw.s VisString255 ED2,B, 192.16 Default Configuration\Communication\Ethernet
Device CFG VSG SP gateway for
etVal (20) C 8.2.1 gateway \Rear port(s)
rear port(s)
Default
LD0.LDEV1.NamPlt.eIpG VisString255 192.16 Default Configuration\Communication\Ethernet
Device CFG LPL EX ED1,C gateway for
ateWay (20) 8.2.1 gateway \Rear port(s)
rear port(s)
IP address
LD0.LDEV1.IPAddrFrt.set VisString255 192.16 Configuration\Communication\Ethernet
Device CFG VSG SP ED2,B IP address for local
Val (20) 8.0.254 \Local port
port (fixed)
IP address
LD0.LDEV1.NamPlt.eIpFr VisString255 192.16 Configuration\Communication\Ethernet
Device CFG LPL EX ED1 IP address for local
ont (20) 8.0.254 \Local port
port (fixed)
IP address
LD0.LDEV1.IPAddrRem.s VisString255 192.16 Configuration\Communication\Ethernet
Device CFG VSG SP ED2,B IP address for remote
etVal (20) 8.1.254 \Remote port
port (fixed)
IP address
LD0.LDEV1.NamPlt.eIpRe VisString255 192.16 Configuration\Communication\Ethernet
Device CFG LPL EX ED1 IP address for remote
m (20) 8.1.254 \Remote port
port (fixed)
XX-
XX-
Mac
VisString255 XX- Configuration\Communication\Ethernet
Device CFG LD0.LDEV1.Mac1.setVal VSG SP ED2,B Mac address address for
(20) XX- \Rear port(s)
rear port(s)
XX-
XX
XX-
XX-
Mac
LD0.LDEV1.NamPlt.eMac VisString255 XX- Configuration\Communication\Ethernet
Device CFG LPL EX ED1 Mac address address for
Addr (20) XX- \Rear port(s)
rear port(s)
XX-
XX
XX-
XX-
Mac
VisString255 XX- Configuration\Communication\Ethernet
Device CFG LD0.LDEV1.Mac2.setVal VSG SP ED2,B Mac address address for
(20) XX- \Local port
local port
XX-
XX
XX-
XX-
Mac
LD0.LDEV1.NamPlt.eMac VisString255 XX- Configuration\Communication\Ethernet
Device CFG LPL EX ED1 Mac address address for
Addr1 (20) XX- \Local port
local port
XX-
XX
LD0.LDEV1.WrmStrCmd. Software Reset of
Device CFG SPC BOOLEAN CO B 0 I1 0=Cancel; 1=Activate Configuration\General
Oper.ctlVal reset IED
12
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Behaviour
LD0.LDEV1.BlkMod.setV Blocking for function 1=Freeze timer; 2=Block all;
Device CFG ENG Enum SP B 1 Configuration\System
al mode BLOCK 3=Block OPERATE output
inputs
Rated
LD0.LDEV1.HzSetSel.set Rated frequency
Device CFG ENG Enum SP B,C,I 1 1=50Hz; 2=60Hz Configuration\System
Val frequency of the
network
Phase
LD0.LDEV1.PhRotSet.set Phase
Device CFG ENG Enum SP B,C,I 1 rotation 1=ABC; 2=ACB Configuration\System
Val rotation
order
Overcurrent
LD0.LDEV1.ACrvSatPnt.s IDMT Sat IDMT
Device CFG ASG FLOAT32 SP A,I 50 10...50 I/I> Configuration\System
etMag.f point saturation
point
Current
LD0.LDEV1.ADmdAvMo A demand demand Configuration\Measurements\Demand
Device CFG ENG Enum SP B,I 1 1=Linear; 2=Logarithmic
d.setVal Av mode calculation metering
method
0=1 minute; 1=5 minutes; 2=10
Interval for
LD0.LDEV1.MtrDmdItrv.s Demand minutes; 3=15 minutes; 4=30 Configuration\Measurements\Demand
Device CFG ENG Enum SP B,I 0 demand
etVal interval minutes; 5=60 minutes; 6=180 metering
calculation
minutes
LD0.LDEV1.TmFrm.setVa Time 1=24H:MM:SS:MS;
Device CFG ENG Enum SP B 1 Time format Configuration\Time\System time
l format 2=12H:MM:SS:MS
1=DD.MM.YYYY;
2=DD/MM/YYYY; 3=DD-
MM-YYYY;
LD0.LDEV1.DateFrm.setV
Device CFG ENG Enum SP B 6 Date format Date format 4=MM.DD.YYYY; Configuration\Time\System time
al
5=MM/DD/YYYY; 6=YYYY-
MM-DD; 7=YYYY-DD-MM;
8=YYYY/DD/MM
FB naming
LD0.LDEV1.NamConvn.se FB naming 1=IEC61850; 2=IEC60617;
Device CFG ENG Enum SP B 1 convention Configuration\HMI
tVal convention 3=IEC-ANSI
used in IED
Web HMI
LD0.LDEV1.ConnExpTm. Web HMI
Device CFG ING INT32 SP B 3 login 1...60 min Configuration\HMI
setVal timeout
timeout
Single Line
LD0.LDEV1.SLDSymFrm. SLD symbol Diagram
Device CFG ENG Enum SP B 1 1=IEC; 2=ANSI Configuration\HMI
setVal format symbol
format
VisString255 192.16 Service port Configuration\Communication\Ethernet
Device CFG LD0.LDEV1.IPSvc.setVal VSG SP ED2,B IP address
(20) 8.3.10 IP address \Service port
LD0.LDEV1.NamPlt.eIpSv VisString255 192.16 Service port Configuration\Communication\Ethernet
Device CFG LPL EX ED1 IP address
c (20) 8.3.10 IP address \Service port
Service port
LD0.LDEV1.IPSubNtwSvc VisString255 255.25 Configuration\Communication\Ethernet
Device CFG VSG SP ED2,B Subnet mask subnet
.setVal (20) 5.255.0 \Service port
mask

13
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Service port
LD0.LDEV1.NamPlt.eIpSu VisString255 255.25 Configuration\Communication\Ethernet
Device CFG LPL EX ED1 Subnet mask subnet
bNetSvc (20) 5.255.0 \Service port
mask
XX-
XX-
Mac
VisString255 XX- Configuration\Communication\Ethernet
Device CFG LD0.LDEV1.Mac3.setVal VSG SP ED2,B Mac address address for
(20) XX- \Remote port
remote port
XX-
XX
XX-
XX-
Mac
LD0.LDEV1.NamPlt.eMac VisString255 XX- Configuration\Communication\Ethernet
Device CFG LPL EX ED1 Mac address address for
Addr2 (20) XX- \Remote port
remote port
XX-
XX
XX-
XX-
Service port
VisString255 XX- Configuration\Communication\Ethernet
Device CFG LD0.LDEV1.Mac4.setVal VSG SP ED2,B Mac address MAC
(20) XX- \Service port
address
XX-
XX
XX-
XX-
Service port
LD0.LDEV1.NamPlt.eMac VisString255 XX- Configuration\Communication\Ethernet
Device CFG LPL EX ED1 Mac address MAC
Addr3 (20) XX- \Service port
address
XX-
XX
LD0.LDEV1.EnaSvcPort.s Enable Configuration\Communication\Ethernet
Device CFG SPG BOOLEAN SP B 0 Enable
etVal service port \Service port
LD0.LDEV1.EnaRemPort. Enable Configuration\Communication\Ethernet
Device CFG SPG BOOLEAN SP B 0 Enable
setVal remote port \Remote port
LD0.LDEV1.UALogEna.se Enabling Configuration\User activity log\Server
Device CFG ENG Enum SP B 1 Enable 1=Disable; 2=Enable
tVal server 1 1 Settings
LD0.LDEV1.UALogEna2. server 2 Configuration\User activity log\Server
Device CFG ENG Enum SP B 1 Enable 1=Disable; 2=Enable
setVal Enabling 2 Settings
LD0.LDEV1.SrvrIPAdr.set VisString255 192.16 Server IP IP address Configuration\User activity log\Server
Device CFG VSG SP ED2,B
Val (20) 8.2.5 address of server 1 1 Settings
LD0.LDEV1.NamPlt.eIpSr VisString255 192.16 Server IP IP address Configuration\User activity log\Server
Device CFG LPL EX ED1
vUAL1 (20) 8.2.5 address of server 1 1 Settings
LD0.LDEV1.SrvrIPAdr2.s VisString255 192.16 Server IP IP address Configuration\User activity log\Server
Device CFG VSG SP ED2,B
etVal (20) 8.2.6 address of server 2 2 Settings
LD0.LDEV1.NamPlt.eIpSr VisString255 192.16 Server IP IP address Configuration\User activity log\Server
Device CFG LPL EX ED1
vUAL2 (20) 8.2.6 address of server 2 2 Settings
connection
LD0.LDEV1.CommType.s Connection Configuration\User activity log\Server
Device CFG ENG Enum SP B 0 type of 0=UDP; 1=TCP; 2=TCP-TLS
etVal Type 1 Settings
server 1
Connection
LD0.LDEV1.CommType2. Connection Configuration\User activity log\Server
Device CFG ENG Enum SP B 0 type of 0=UDP; 1=TCP; 2=TCP-TLS
setVal Type 2 Settings
server 2
14
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Port
LD0.LDEV1.CommPort.se Configuration\User activity log\Server
Device CFG ING INT32 SP B 514 Port Number Number of 1...7800
tVal 1 Settings
server 1
Port
LD0.LDEV1.CommPort2.s Configuration\User activity log\Server
Device CFG ING INT32 SP B 514 Port Number number of 1...7800
etVal 2 Settings
server 2
Unauth
orized
access
to this
service
is
prohibit
ed.
Unauth
orized
attempt
s and
actions
to
access Web HMI
or use message
Web HMI
LD0.LDEV1.LglMsg.setVa this shown on
Device CFG VSG VisString255 SP ED2,B logon legal Configuration\HMI
l system bottom of
message
may the logon
result screen
in civil
and/or
crimina
l
penaltie
s. All
activiti
es
perfor
med on
this
device
are
logged.
Unauth
orized
access
to this
Web HMI
service
message
is Web HMI
LD0.LDEV1.NamPlt.eLgl shown on
Device CFG LPL VisString255 EX ED1 prohibit logon legal Configuration\HMI
Msg bottom of
ed. message
the logon
Unauth
screen
orized
attempt
s and
actions
15
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

to
access
or use
this
system
may
result
in civil
and/or
crimina
l
penaltie
s. All
activiti
es
perfor
med on
this
device
are
logged.
Specifies
what is
Web HMI shown on
LD0.LDEV1.LogonPgMod 0=Off; 1=Annunciator;
Device CFG ENG Enum SP B 0 logon page logon page Configuration\HMI
.setVal 2=Dashboard; 3=Both
mode before user
has logged
in
Selected
Protection SGC
SET LD0.LLN0.SGCB.ActSG INT8U SP B 1 Active group active - -
LLN0 B
group
Protection SGC Selected
SET LD0.LLN0.SGCB.EditSG INT8U SP B,A 1 Edit group - -
LLN0 B edit group
Commit or
Protection SGC Commit
SET LD0.LLN0.SGCB.CnfEdit BOOLEAN SP B,A 0 reject the - -
LLN0 B settings
edit copy
Copy
setting 1=Cancel; 2=Copy 1 into 2;
Protection group 1 3=Copy 1 into 3; 4=Copy 1 into
SET Enum B,H 1 Copy group 1 Settings\Setting group
LLN0 values into 4; 5=Copy 1 into 5; 6=Copy 1
selected into 6; 99=Copy 1 into all
group
1=Normal mode; 2=IED
Protection LD0.LLN0.Mod.Oper.ctlV
TES ENC Enum CO B,I 1 Test mode Test mode blocked; 3=IED test; 4=IED test Tests\IED test
LLN0 al
and blocked
Allow
receiving
Physical LD0.LPHD1.Sim.Oper.ctl Allow simulated
TES SPC BOOLEAN CO ED2,B 0 I1 Tests\IED test
device Val simulation GOOSE
and SMV
messages

16
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Internal
LD0.LDEV1.FailTest.Oper Internal fault
Device TES SPC BOOLEAN CO B,H 0 I1 fault test 0=Test off; 1=Test on Tests\IED test
.ctlVal test
mode
Authority
for remote
LD0.LDEV1.ModRemCtl.s Remote test 1=Off; 2=Maintenance; 3=All
Device TES ENG Enum SP A,H 1 activation Tests\IED test
etVal mode levels
of test
mode
Physical LD0.LPHD1.PhyNam.hwR VisString255 IED HW
INF DPL DC B X HW revision Information\Product identifiers
device ev (20) revision
Physical LD0.LPHD1.PhyNam.swR VisString255 IED SW
INF DPL DC B X.X SW version Information\Product identifiers
device ev (20) version
1XXX
Physical LD0.LPHD1.PhyNam.serN VisString255 Serial IED serial
INF DPL DC B XXXX Information\Product identifiers
device um (20) number number
XXXX
Physical LD0.LPHD1.PhyNam.mod VisString255 SSC60
INF DPL DC B Type IED type Information\Product identifiers
device el (20) 0
Technical
Physical LD0.LPHD1.PhyNam.nam Technical
INF DPL VisString64 DC B TIGER key set by Information\System identifiers
device e key
tool
Customer IED
LD0.LINF1.CfgNam.setVa VisString255 Configuratio
informatio INF VSG SP ED2,B SS01 configuratio Information\Product identifiers
l (20) n name
n n name
Customer IED
LD0.LINF1.NamPlt.eConf VisString255 Configuratio
informatio INF LPL EX ED1 SS01 configuratio Information\Product identifiers
Name (20) n name
n n name
Customer Product
VisString255 Product
informatio INF LD0.LINF1.DevRev.setVal VSG SP ED2,B 1.0 FP4 version Information\Product identifiers
(64) version
n number
Customer Product
LD0.LINF1.NamPlt.eDevR VisString255 Product
informatio INF LPL EX ED1 1.0 FP4 version Information\Product identifiers
ev (64) version
n number
Customer Name of
VisString255 Customer
informatio INF LD0.LINF1.CstNam.setVal VSG SP ED2,B 0 the Information\Site identifiers
(64) name
n customer
Customer Name of
LD0.LINF1.NamPlt.eCusto VisString255 Customer
informatio INF LPL EX ED1 0 the Information\Site identifiers
mer (64) name
n customer
Customer
LD0.LINF1.CstStNam.set VisString255 Name of
informatio INF VSG SP ED2,B 0 State Information\Site identifiers
Val (64) state
n
Customer
VisString255 Name of
informatio INF LD0.LINF1.NamPlt.eState LPL EX ED1 0 State Information\Site identifiers
(64) state
n
Customer
LD0.LINF1.CstStreNam.se VisString255 Name of
informatio INF VSG SP ED2,B 0 Street Information\Site identifiers
tVal (64) the street
n

17
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Customer
VisString255 Name of
informatio INF LD0.LINF1.NamPlt.eStreet LPL EX ED1 0 Street Information\Site identifiers
(64) the street
n
Customer
LD0.LINF1.CstHouNum.se VisString255 House Number of
informatio INF VSG SP ED2,B 0 Information\Site identifiers
tVal (64) number the house
n
Customer
LD0.LINF1.NamPlt.eHous VisString255 House Number of
informatio INF LPL EX ED1 0 Information\Site identifiers
eNum (64) number the house
n
Customer
VisString255 ZIP/Postal ZIP/Postal
informatio INF LD0.LINF1.CstZip.setVal VSG SP ED2,B 0 Information\Site identifiers
(20) code code
n
Customer
VisString255 ZIP/Postal ZIP/Postal
informatio INF LD0.LINF1.NamPlt.eZip LPL EX ED1 0 Information\Site identifiers
(20) code code
n
Customer
LD0.LINF1.CstCityNam.se VisString255 City/Provin
informatio INF VSG SP ED2,B 0 City/Province Information\Site identifiers
tVal (64) ce
n
Customer
VisString255 City/Provin
informatio INF LD0.LINF1.NamPlt.eCity LPL EX ED1 0 City/Province Information\Site identifiers
(64) ce
n
Customer
LD0.LINF1.CstCntyNam.s VisString255 Name of
informatio INF VSG SP ED2,B 0 Country Information\Site identifiers
etVal (64) the country
n
Customer
LD0.LINF1.NamPlt.eCoun VisString255 Name of
informatio INF LPL EX ED1 0 Country Information\Site identifiers
try (64) the country
n
LD0.LDEV1.SwrNum.stVa VisString255 IED SW
Device INF VSS ST ED2,B SW number Information\Product identifiers
l (20) number
LD0.LDEV1.NamPlt.eSw VisString255 IED SW
Device INF LPL EX ED1 SW number Information\Product identifiers
Num (20) number
IED SW
Device INF LD0.LDEV1.SwrNum.t VSS Timestamp ST ED2,B SW date Information\Product identifiers
date
LD0.LDEV1.NamPlt.eSw VisString255 IED SW
Device INF LPL EX ED1 SW date Information\Product identifiers
Date (20) date
LD0.LDEV1.OrdrNum.stV VisString255 IED order
Device INF VSS ST ED2,B Order code Information\Product identifiers
al (20) code
LD0.LDEV1.NamPlt.eOrd VisString255 IED order
Device INF LPL EX ED1 Order code Information\Product identifiers
Num (64) code
IED
Production
Device INF LD0.LDEV1.OrdrNum.t VSS Timestamp ST ED2,B production Information\Product identifiers
date
date
IED
LD0.LDEV1.NamPlt.eProd VisString255 Production
Device INF LPL EX ED1 production Information\Product identifiers
Date (20) date
date
Protection VisString255 (Name
VER LD0.LLN0.NamPlt.swRev LPL DC G
LLN0 (20) plate)

18
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

IEC
Protection VisString255 61850- (Name
VER LD0.LLN0.NamPlt.ldNs LPL EX
LLN0 (20) 7- plate)
4:2003
Physical LD0.LPHD1.PhyNam.swR VisString255 IED SW
VER DPL DC B X.X SW version Information\Product identifiers
device ev (20) version

Security application: H3
IEC 61850 IEC 60617 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter name Parameter desc Parameter range Menu path Channel relation
Security application VER LD0.GSAL1.NamPlt.swRev LPL VisString255 (20) DC ED1 H3 (Name plate)

Programmable LEDs: F2
IEC Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Parameter range Menu path
60617 name relation
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm1.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 1 LEDs\Inputs\LED 1
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm2.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 2 LEDs\Inputs\LED 2
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm3.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 3 LEDs\Inputs\LED 3
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm4.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 4 LEDs\Inputs\LED 4
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm5.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 5 LEDs\Inputs\LED 5
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm6.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 6 LEDs\Inputs\LED 6
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm7.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 7 LEDs\Inputs\LED 7
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm8.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 8 LEDs\Inputs\LED 8
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm9.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 9 LEDs\Inputs\LED 9
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm10.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 10 LEDs\Inputs\LED 10
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm11.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 11 LEDs\Inputs\LED 11
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm12.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 12 LEDs\Inputs\LED 12
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm13.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 13 LEDs\Inputs\LED 13
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm14.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 14 LEDs\Inputs\LED 14

19
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable Alarm input for Monitoring\Programmable


INP LD0.LEDGGIO1.Alm15.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 15 LEDs\Inputs\LED 15
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm16.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 16 LEDs\Inputs\LED 16
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm17.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 17 LEDs\Inputs\LED 17
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm18.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 18 LEDs\Inputs\LED 18
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm19.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 19 LEDs\Inputs\LED 19
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm20.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 20 LEDs\Inputs\LED 20
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm21.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 21 LEDs\Inputs\LED 21
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm22.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 22 LEDs\Inputs\LED 22
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm23.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 23 LEDs\Inputs\LED 23
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm24.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 24 LEDs\Inputs\LED 24
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm25.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 25 LEDs\Inputs\LED 25
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm26.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 26 LEDs\Inputs\LED 26
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm27.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 27 LEDs\Inputs\LED 27
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm28.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 28 LEDs\Inputs\LED 28
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm29.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 29 LEDs\Inputs\LED 29
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm30.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 30 LEDs\Inputs\LED 30
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm31.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 31 LEDs\Inputs\LED 31
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm32.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 32 LEDs\Inputs\LED 32
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm33.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 33 LEDs\Inputs\LED 33
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm34.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 34 LEDs\Inputs\LED 34
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm35.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 35 LEDs\Inputs\LED 35
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm36.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 36 LEDs\Inputs\LED 36
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm37.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 37 LEDs\Inputs\LED 37

20
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable Alarm input for Monitoring\Programmable


INP LD0.LEDGGIO1.Alm38.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 38 LEDs\Inputs\LED 38
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm39.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 39 LEDs\Inputs\LED 39
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm40.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 40 LEDs\Inputs\LED 40
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm41.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 41 LEDs\Inputs\LED 41
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm42.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 42 LEDs\Inputs\LED 42
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm43.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 43 LEDs\Inputs\LED 43
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm44.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 44 LEDs\Inputs\LED 44
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm45.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 45 LEDs\Inputs\LED 45
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm46.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 46 LEDs\Inputs\LED 46
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm47.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 47 LEDs\Inputs\LED 47
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm48.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 48 LEDs\Inputs\LED 48
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm49.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 49 LEDs\Inputs\LED 49
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm50.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 50 LEDs\Inputs\LED 50
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm51.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 51 LEDs\Inputs\LED 51
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm52.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 52 LEDs\Inputs\LED 52
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm53.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 53 LEDs\Inputs\LED 53
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm54.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 54 LEDs\Inputs\LED 54
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm55.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 55 LEDs\Inputs\LED 55
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm56.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 56 LEDs\Inputs\LED 56
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm57.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 57 LEDs\Inputs\LED 57
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm58.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 58 LEDs\Inputs\LED 58
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm59.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 59 LEDs\Inputs\LED 59
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm60.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 60 LEDs\Inputs\LED 60

21
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable Alarm input for Monitoring\Programmable


INP LD0.LEDGGIO1.Alm61.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 61 LEDs\Inputs\LED 61
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm62.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 62 LEDs\Inputs\LED 62
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm63.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 63 LEDs\Inputs\LED 63
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm64.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 64 LEDs\Inputs\LED 64
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm65.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 65 LEDs\Inputs\LED 65
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm66.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 66 LEDs\Inputs\LED 66
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm67.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 67 LEDs\Inputs\LED 67
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm68.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 68 LEDs\Inputs\LED 68
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm69.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 69 LEDs\Inputs\LED 69
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm70.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 70 LEDs\Inputs\LED 70
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm71.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 71 LEDs\Inputs\LED 71
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm72.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 72 LEDs\Inputs\LED 72
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm73.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 73 LEDs\Inputs\LED 73
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm74.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 74 LEDs\Inputs\LED 74
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm75.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 75 LEDs\Inputs\LED 75
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm76.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 76 LEDs\Inputs\LED 76
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm77.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 77 LEDs\Inputs\LED 77
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm78.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 78 LEDs\Inputs\LED 78
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm79.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 79 LEDs\Inputs\LED 79
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm80.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 80 LEDs\Inputs\LED 80
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm81.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 81 LEDs\Inputs\LED 81
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm82.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 82 LEDs\Inputs\LED 82
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm83.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 83 LEDs\Inputs\LED 83

22
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable Alarm input for Monitoring\Programmable


INP LD0.LEDGGIO1.Alm84.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 84 LEDs\Inputs\LED 84
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm85.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 85 LEDs\Inputs\LED 85
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm86.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 86 LEDs\Inputs\LED 86
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm87.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 87 LEDs\Inputs\LED 87
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm88.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 88 LEDs\Inputs\LED 88
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm89.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 89 LEDs\Inputs\LED 89
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm90.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 90 LEDs\Inputs\LED 90
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm91.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 91 LEDs\Inputs\LED 91
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm92.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 92 LEDs\Inputs\LED 92
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm93.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 93 LEDs\Inputs\LED 93
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm94.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 94 LEDs\Inputs\LED 94
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm95.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 95 LEDs\Inputs\LED 95
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm96.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 96 LEDs\Inputs\LED 96
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm97.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 97 LEDs\Inputs\LED 97
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm98.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 98 LEDs\Inputs\LED 98
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm99.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 99 LEDs\Inputs\LED 99
Programmable Alarm input for Monitoring\Programmable
INP LD0.LEDGGIO1.Alm100.stVal SPS BOOLEAN ST B 0 I1 ALARM
LEDs LED 100 LEDs\Inputs\LED 100
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind1.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 1 LEDs\Inputs\LED 1
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind2.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 2 LEDs\Inputs\LED 2
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind3.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 3 LEDs\Inputs\LED 3
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind4.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 4 LEDs\Inputs\LED 4
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind5.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 5 LEDs\Inputs\LED 5
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind6.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 6 LEDs\Inputs\LED 6

23
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable Ok input for Monitoring\Programmable


INP LD0.LEDGGIO1.Ind7.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 7 LEDs\Inputs\LED 7
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind8.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 8 LEDs\Inputs\LED 8
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind9.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 9 LEDs\Inputs\LED 9
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind10.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 10 LEDs\Inputs\LED 10
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind11.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 11 LEDs\Inputs\LED 11
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind12.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 12 LEDs\Inputs\LED 12
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind13.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 13 LEDs\Inputs\LED 13
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind14.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 14 LEDs\Inputs\LED 14
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind15.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 15 LEDs\Inputs\LED 15
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind16.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 16 LEDs\Inputs\LED 16
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind17.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 17 LEDs\Inputs\LED 17
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind18.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 18 LEDs\Inputs\LED 18
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind19.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 19 LEDs\Inputs\LED 19
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind20.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 20 LEDs\Inputs\LED 20
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind21.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 21 LEDs\Inputs\LED 21
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind22.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 22 LEDs\Inputs\LED 22
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind23.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 23 LEDs\Inputs\LED 23
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind24.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 24 LEDs\Inputs\LED 24
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind25.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 25 LEDs\Inputs\LED 25
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind26.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 26 LEDs\Inputs\LED 26
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind27.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 27 LEDs\Inputs\LED 27
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind28.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 28 LEDs\Inputs\LED 28
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind29.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 29 LEDs\Inputs\LED 29

24
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable Ok input for Monitoring\Programmable


INP LD0.LEDGGIO1.Ind30.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 30 LEDs\Inputs\LED 30
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind31.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 31 LEDs\Inputs\LED 31
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind32.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 32 LEDs\Inputs\LED 32
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind33.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 33 LEDs\Inputs\LED 33
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind34.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 34 LEDs\Inputs\LED 34
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind35.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 35 LEDs\Inputs\LED 35
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind36.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 36 LEDs\Inputs\LED 36
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind37.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 37 LEDs\Inputs\LED 37
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind38.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 38 LEDs\Inputs\LED 38
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind39.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 39 LEDs\Inputs\LED 39
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind40.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 40 LEDs\Inputs\LED 40
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind41.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 41 LEDs\Inputs\LED 41
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind42.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 42 LEDs\Inputs\LED 42
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind43.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 43 LEDs\Inputs\LED 43
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind44.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 44 LEDs\Inputs\LED 44
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind45.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 45 LEDs\Inputs\LED 45
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind46.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 46 LEDs\Inputs\LED 46
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind47.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 47 LEDs\Inputs\LED 47
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind48.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 48 LEDs\Inputs\LED 48
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind49.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 49 LEDs\Inputs\LED 49
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind50.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 50 LEDs\Inputs\LED 50
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind51.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 51 LEDs\Inputs\LED 51
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind52.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 52 LEDs\Inputs\LED 52

25
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable Ok input for Monitoring\Programmable


INP LD0.LEDGGIO1.Ind53.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 53 LEDs\Inputs\LED 53
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind54.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 54 LEDs\Inputs\LED 54
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind55.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 55 LEDs\Inputs\LED 55
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind56.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 56 LEDs\Inputs\LED 56
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind57.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 57 LEDs\Inputs\LED 57
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind58.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 58 LEDs\Inputs\LED 58
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind59.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 59 LEDs\Inputs\LED 59
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind60.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 60 LEDs\Inputs\LED 60
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind61.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 61 LEDs\Inputs\LED 61
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind62.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 62 LEDs\Inputs\LED 62
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind63.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 63 LEDs\Inputs\LED 63
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind64.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 64 LEDs\Inputs\LED 64
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind65.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 65 LEDs\Inputs\LED 65
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind66.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 66 LEDs\Inputs\LED 66
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind67.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 67 LEDs\Inputs\LED 67
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind68.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 68 LEDs\Inputs\LED 68
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind69.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 69 LEDs\Inputs\LED 69
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind70.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 70 LEDs\Inputs\LED 70
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind71.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 71 LEDs\Inputs\LED 71
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind72.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 72 LEDs\Inputs\LED 72
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind73.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 73 LEDs\Inputs\LED 73
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind74.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 74 LEDs\Inputs\LED 74
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind75.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 75 LEDs\Inputs\LED 75

26
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable Ok input for Monitoring\Programmable


INP LD0.LEDGGIO1.Ind76.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 76 LEDs\Inputs\LED 76
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind77.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 77 LEDs\Inputs\LED 77
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind78.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 78 LEDs\Inputs\LED 78
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind79.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 79 LEDs\Inputs\LED 79
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind80.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 80 LEDs\Inputs\LED 80
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind81.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 81 LEDs\Inputs\LED 81
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind82.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 82 LEDs\Inputs\LED 82
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind83.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 83 LEDs\Inputs\LED 83
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind84.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 84 LEDs\Inputs\LED 84
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind85.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 85 LEDs\Inputs\LED 85
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind86.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 86 LEDs\Inputs\LED 86
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind87.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 87 LEDs\Inputs\LED 87
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind88.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 88 LEDs\Inputs\LED 88
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind89.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 89 LEDs\Inputs\LED 89
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind90.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 90 LEDs\Inputs\LED 90
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind91.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 91 LEDs\Inputs\LED 91
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind92.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 92 LEDs\Inputs\LED 92
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind93.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 93 LEDs\Inputs\LED 93
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind94.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 94 LEDs\Inputs\LED 94
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind95.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 95 LEDs\Inputs\LED 95
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind96.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 96 LEDs\Inputs\LED 96
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind97.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 97 LEDs\Inputs\LED 97
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind98.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 98 LEDs\Inputs\LED 98

27
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable Ok input for Monitoring\Programmable


INP LD0.LEDGGIO1.Ind99.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 99 LEDs\Inputs\LED 99
Programmable Ok input for Monitoring\Programmable
INP LD0.LEDGGIO1.Ind100.stVal SPS BOOLEAN ST B 0 I1 OK
LEDs LED 100 LEDs\Inputs\LED 100
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED1.stVal SPS BOOLEAN ST B 0 RESET
LEDs LED 1 LEDs\Inputs\LED 1
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED2.stVal SPS BOOLEAN ST B 0 RESET
LEDs LED 2 LEDs\Inputs\LED 2
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED3.stVal SPS BOOLEAN ST B 0 RESET
LEDs LED 3 LEDs\Inputs\LED 3
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED4.stVal SPS BOOLEAN ST B 0 RESET
LEDs LED 4 LEDs\Inputs\LED 4
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED5.stVal SPS BOOLEAN ST B 0 RESET
LEDs LED 5 LEDs\Inputs\LED 5
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED6.stVal SPS BOOLEAN ST B 0 RESET
LEDs LED 6 LEDs\Inputs\LED 6
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED7.stVal SPS BOOLEAN ST B 0 RESET
LEDs LED 7 LEDs\Inputs\LED 7
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED8.stVal SPS BOOLEAN ST B 0 RESET
LEDs LED 8 LEDs\Inputs\LED 8
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED9.stVal SPS BOOLEAN ST B 0 RESET
LEDs LED 9 LEDs\Inputs\LED 9
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED10.stVal SPS BOOLEAN ST B 0 RESET
LEDs LED 10 LEDs\Inputs\LED 10
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED11.stVal SPS BOOLEAN ST B 0 RESET
LEDs LED 11 LEDs\Inputs\LED 11
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED12.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 12 LEDs\Inputs\LED 12
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED13.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 13 LEDs\Inputs\LED 13
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED14.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 14 LEDs\Inputs\LED 14
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED15.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 15 LEDs\Inputs\LED 15
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED16.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 16 LEDs\Inputs\LED 16
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED17.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 17 LEDs\Inputs\LED 17
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED18.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 18 LEDs\Inputs\LED 18
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED19.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 19 LEDs\Inputs\LED 19
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED20.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 20 LEDs\Inputs\LED 20
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED21.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 21 LEDs\Inputs\LED 21

28
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable Reset input for Monitoring\Programmable


INP LD0.LEDGGIO1.InRsLED22.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 22 LEDs\Inputs\LED 22
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED23.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 23 LEDs\Inputs\LED 23
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED24.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 24 LEDs\Inputs\LED 24
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED25.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 25 LEDs\Inputs\LED 25
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED26.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 26 LEDs\Inputs\LED 26
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED27.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 27 LEDs\Inputs\LED 27
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED28.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 28 LEDs\Inputs\LED 28
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED29.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 29 LEDs\Inputs\LED 29
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED30.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 30 LEDs\Inputs\LED 30
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED31.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 31 LEDs\Inputs\LED 31
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED32.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 32 LEDs\Inputs\LED 32
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED33.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 33 LEDs\Inputs\LED 33
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED34.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 34 LEDs\Inputs\LED 34
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED35.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 35 LEDs\Inputs\LED 35
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED36.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 36 LEDs\Inputs\LED 36
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED37.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 37 LEDs\Inputs\LED 37
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED38.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 38 LEDs\Inputs\LED 38
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED39.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 39 LEDs\Inputs\LED 39
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED40.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 40 LEDs\Inputs\LED 40
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED41.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 41 LEDs\Inputs\LED 41
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED42.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 42 LEDs\Inputs\LED 42
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED43.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 43 LEDs\Inputs\LED 43
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED44.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 44 LEDs\Inputs\LED 44

29
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable Reset input for Monitoring\Programmable


INP LD0.LEDGGIO1.InRsLED45.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 45 LEDs\Inputs\LED 45
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED46.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 46 LEDs\Inputs\LED 46
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED47.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 47 LEDs\Inputs\LED 47
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED48.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 48 LEDs\Inputs\LED 48
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED49.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 49 LEDs\Inputs\LED 49
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED50.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 50 LEDs\Inputs\LED 50
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED51.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 51 LEDs\Inputs\LED 51
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED52.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 52 LEDs\Inputs\LED 52
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED53.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 53 LEDs\Inputs\LED 53
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED54.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 54 LEDs\Inputs\LED 54
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED55.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 55 LEDs\Inputs\LED 55
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED56.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 56 LEDs\Inputs\LED 56
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED57.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 57 LEDs\Inputs\LED 57
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED58.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 58 LEDs\Inputs\LED 58
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED59.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 59 LEDs\Inputs\LED 59
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED60.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 60 LEDs\Inputs\LED 60
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED61.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 61 LEDs\Inputs\LED 61
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED62.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 62 LEDs\Inputs\LED 62
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED63.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 63 LEDs\Inputs\LED 63
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED64.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 64 LEDs\Inputs\LED 64
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED65.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 65 LEDs\Inputs\LED 65
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED66.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 66 LEDs\Inputs\LED 66
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED67.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 67 LEDs\Inputs\LED 67

30
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable Reset input for Monitoring\Programmable


INP LD0.LEDGGIO1.InRsLED68.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 68 LEDs\Inputs\LED 68
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED69.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 69 LEDs\Inputs\LED 69
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED70.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 70 LEDs\Inputs\LED 70
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED71.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 71 LEDs\Inputs\LED 71
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED72.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 72 LEDs\Inputs\LED 72
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED73.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 73 LEDs\Inputs\LED 73
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED74.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 74 LEDs\Inputs\LED 74
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED75.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 75 LEDs\Inputs\LED 75
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED76.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 76 LEDs\Inputs\LED 76
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED77.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 77 LEDs\Inputs\LED 77
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED78.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 78 LEDs\Inputs\LED 78
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED79.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 79 LEDs\Inputs\LED 79
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED80.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 80 LEDs\Inputs\LED 80
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED81.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 81 LEDs\Inputs\LED 81
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED82.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 82 LEDs\Inputs\LED 82
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED83.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 83 LEDs\Inputs\LED 83
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED84.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 84 LEDs\Inputs\LED 84
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED85.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 85 LEDs\Inputs\LED 85
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED86.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 86 LEDs\Inputs\LED 86
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED87.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 87 LEDs\Inputs\LED 87
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED88.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 88 LEDs\Inputs\LED 88
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED89.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 89 LEDs\Inputs\LED 89
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED90.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 90 LEDs\Inputs\LED 90

31
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable Reset input for Monitoring\Programmable


INP LD0.LEDGGIO1.InRsLED91.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 91 LEDs\Inputs\LED 91
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED92.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 92 LEDs\Inputs\LED 92
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED93.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 93 LEDs\Inputs\LED 93
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED94.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 94 LEDs\Inputs\LED 94
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED95.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 95 LEDs\Inputs\LED 95
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED96.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 96 LEDs\Inputs\LED 96
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED97.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 97 LEDs\Inputs\LED 97
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED98.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 98 LEDs\Inputs\LED 98
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED99.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 99 LEDs\Inputs\LED 99
Programmable Reset input for Monitoring\Programmable
INP LD0.LEDGGIO1.InRsLED100.stVal SPS BOOLEAN ST B 0 I1 RESET
LEDs LED 100 LEDs\Inputs\LED 100
Programmable
CTR LD0.LEDGGIO1.LEDSt1.Oper.ctlVal ENC INT32 CO (LED 1)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt2.Oper.ctlVal ENC INT32 CO (LED 2)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt3.Oper.ctlVal ENC INT32 CO (LED 3)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt4.Oper.ctlVal ENC INT32 CO (LED 4)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt5.Oper.ctlVal ENC INT32 CO (LED 5)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt6.Oper.ctlVal ENC INT32 CO (LED 6)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt7.Oper.ctlVal ENC INT32 CO (LED 7)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt8.Oper.ctlVal ENC INT32 CO (LED 8)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt9.Oper.ctlVal ENC INT32 CO (LED 9)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt10.Oper.ctlVal ENC INT32 CO (LED 10)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt11.Oper.ctlVal ENC INT32 CO (LED 11)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt12.Oper.ctlVal ENC INT32 CO (LED 12)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt13.Oper.ctlVal ENC INT32 CO (LED 13)
LEDs

32
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable
CTR LD0.LEDGGIO1.LEDSt14.Oper.ctlVal ENC INT32 CO (LED 14)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt15.Oper.ctlVal ENC INT32 CO (LED 15)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt16.Oper.ctlVal ENC INT32 CO (LED 16)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt17.Oper.ctlVal ENC INT32 CO (LED 17)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt18.Oper.ctlVal ENC INT32 CO (LED 18)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt19.Oper.ctlVal ENC INT32 CO (LED 19)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt20.Oper.ctlVal ENC INT32 CO (LED 20)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt21.Oper.ctlVal ENC INT32 CO (LED 21)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt22.Oper.ctlVal ENC INT32 CO (LED 22)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt23.Oper.ctlVal ENC INT32 CO (LED 23)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt24.Oper.ctlVal ENC INT32 CO (LED 24)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt25.Oper.ctlVal ENC INT32 CO (LED 25)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt26.Oper.ctlVal ENC INT32 CO (LED 26)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt27.Oper.ctlVal ENC INT32 CO (LED 27)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt28.Oper.ctlVal ENC INT32 CO (LED 28)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt29.Oper.ctlVal ENC INT32 CO (LED 29)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt30.Oper.ctlVal ENC INT32 CO (LED 30)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt31.Oper.ctlVal ENC INT32 CO (LED 31)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt32.Oper.ctlVal ENC INT32 CO (LED 32)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt33.Oper.ctlVal ENC INT32 CO (LED 33)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt34.Oper.ctlVal ENC INT32 CO (LED 34)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt35.Oper.ctlVal ENC INT32 CO (LED 35)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt36.Oper.ctlVal ENC INT32 CO (LED 36)
LEDs

33
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable
CTR LD0.LEDGGIO1.LEDSt37.Oper.ctlVal ENC INT32 CO (LED 37)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt38.Oper.ctlVal ENC INT32 CO (LED 38)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt39.Oper.ctlVal ENC INT32 CO (LED 39)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt40.Oper.ctlVal ENC INT32 CO (LED 40)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt41.Oper.ctlVal ENC INT32 CO (LED 41)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt42.Oper.ctlVal ENC INT32 CO (LED 42)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt43.Oper.ctlVal ENC INT32 CO (LED 43)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt44.Oper.ctlVal ENC INT32 CO (LED 44)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt45.Oper.ctlVal ENC INT32 CO (LED 45)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt46.Oper.ctlVal ENC INT32 CO (LED 46)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt47.Oper.ctlVal ENC INT32 CO (LED 47)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt48.Oper.ctlVal ENC INT32 CO (LED 48)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt49.Oper.ctlVal ENC INT32 CO (LED 49)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt50.Oper.ctlVal ENC INT32 CO (LED 50)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt51.Oper.ctlVal ENC INT32 CO (LED 51)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt52.Oper.ctlVal ENC INT32 CO (LED 52)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt53.Oper.ctlVal ENC INT32 CO (LED 53)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt54.Oper.ctlVal ENC INT32 CO (LED 54)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt55.Oper.ctlVal ENC INT32 CO (LED 55)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt56.Oper.ctlVal ENC INT32 CO (LED 56)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt57.Oper.ctlVal ENC INT32 CO (LED 57)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt58.Oper.ctlVal ENC INT32 CO (LED 58)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt59.Oper.ctlVal ENC INT32 CO (LED 59)
LEDs

34
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable
CTR LD0.LEDGGIO1.LEDSt60.Oper.ctlVal ENC INT32 CO (LED 60)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt61.Oper.ctlVal ENC INT32 CO (LED 61)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt62.Oper.ctlVal ENC INT32 CO (LED 62)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt63.Oper.ctlVal ENC INT32 CO (LED 63)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt64.Oper.ctlVal ENC INT32 CO (LED 64)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt65.Oper.ctlVal ENC INT32 CO (LED 65)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt66.Oper.ctlVal ENC INT32 CO (LED 66)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt67.Oper.ctlVal ENC INT32 CO (LED 67)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt68.Oper.ctlVal ENC INT32 CO (LED 68)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt69.Oper.ctlVal ENC INT32 CO (LED 69)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt70.Oper.ctlVal ENC INT32 CO (LED 70)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt71.Oper.ctlVal ENC INT32 CO (LED 71)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt72.Oper.ctlVal ENC INT32 CO (LED 72)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt73.Oper.ctlVal ENC INT32 CO (LED 73)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt74.Oper.ctlVal ENC INT32 CO (LED 74)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt75.Oper.ctlVal ENC INT32 CO (LED 75)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt76.Oper.ctlVal ENC INT32 CO (LED 76)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt77.Oper.ctlVal ENC INT32 CO (LED 77)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt78.Oper.ctlVal ENC INT32 CO (LED 78)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt79.Oper.ctlVal ENC INT32 CO (LED 79)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt80.Oper.ctlVal ENC INT32 CO (LED 80)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt81.Oper.ctlVal ENC INT32 CO (LED 81)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt82.Oper.ctlVal ENC INT32 CO (LED 82)
LEDs

35
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable
CTR LD0.LEDGGIO1.LEDSt83.Oper.ctlVal ENC INT32 CO (LED 83)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt84.Oper.ctlVal ENC INT32 CO (LED 84)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt85.Oper.ctlVal ENC INT32 CO (LED 85)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt86.Oper.ctlVal ENC INT32 CO (LED 86)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt87.Oper.ctlVal ENC INT32 CO (LED 87)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt88.Oper.ctlVal ENC INT32 CO (LED 88)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt89.Oper.ctlVal ENC INT32 CO (LED 89)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt90.Oper.ctlVal ENC INT32 CO (LED 90)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt91.Oper.ctlVal ENC INT32 CO (LED 91)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt92.Oper.ctlVal ENC INT32 CO (LED 92)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt93.Oper.ctlVal ENC INT32 CO (LED 93)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt94.Oper.ctlVal ENC INT32 CO (LED 94)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt95.Oper.ctlVal ENC INT32 CO (LED 95)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt96.Oper.ctlVal ENC INT32 CO (LED 96)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt97.Oper.ctlVal ENC INT32 CO (LED 97)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt98.Oper.ctlVal ENC INT32 CO (LED 98)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt99.Oper.ctlVal ENC INT32 CO (LED 99)
LEDs
Programmable
CTR LD0.LEDGGIO1.LEDSt100.Oper.ctlVal ENC INT32 CO (LED 100)
LEDs
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt1.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 1 3=Alarm LEDs\Monitored data
LED 1
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt2.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 2 3=Alarm LEDs\Monitored data
LED 2
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt3.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 3 3=Alarm LEDs\Monitored data
LED 3

36
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt4.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 4 3=Alarm LEDs\Monitored data
LED 4
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt5.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 5 3=Alarm LEDs\Monitored data
LED 5
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt6.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 6 3=Alarm LEDs\Monitored data
LED 6
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt7.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 7 3=Alarm LEDs\Monitored data
LED 7
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt8.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 8 3=Alarm LEDs\Monitored data
LED 8
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt9.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 9 3=Alarm LEDs\Monitored data
LED 9
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt10.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 10 3=Alarm LEDs\Monitored data
LED 10
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt11.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 11 3=Alarm LEDs\Monitored data
LED 11
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt12.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 12 3=Alarm LEDs\Monitored data
LED 12
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt13.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 13 3=Alarm LEDs\Monitored data
LED 13
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt14.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 14 3=Alarm LEDs\Monitored data
LED 14
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt15.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 15 3=Alarm LEDs\Monitored data
LED 15
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt16.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 16 3=Alarm LEDs\Monitored data
LED 16
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt17.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 17 3=Alarm LEDs\Monitored data
LED 17
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt18.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 18 3=Alarm LEDs\Monitored data
LED 18
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt19.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 19 3=Alarm LEDs\Monitored data
LED 19

37
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt20.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 20 3=Alarm LEDs\Monitored data
LED 20
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt21.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 21 3=Alarm LEDs\Monitored data
LED 21
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt22.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 22 3=Alarm LEDs\Monitored data
LED 22
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt23.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 23 3=Alarm LEDs\Monitored data
LED 23
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt24.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 24 3=Alarm LEDs\Monitored data
LED 24
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt25.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 25 3=Alarm LEDs\Monitored data
LED 25
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt26.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 26 3=Alarm LEDs\Monitored data
LED 26
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt27.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 27 3=Alarm LEDs\Monitored data
LED 27
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt28.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 28 3=Alarm LEDs\Monitored data
LED 28
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt29.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 29 3=Alarm LEDs\Monitored data
LED 29
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt30.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 30 3=Alarm LEDs\Monitored data
LED 30
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt31.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 31 3=Alarm LEDs\Monitored data
LED 31
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt32.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 32 3=Alarm LEDs\Monitored data
LED 32
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt33.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 33 3=Alarm LEDs\Monitored data
LED 33
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt34.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 34 3=Alarm LEDs\Monitored data
LED 34
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt35.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 35 3=Alarm LEDs\Monitored data
LED 35

38
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt36.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 36 3=Alarm LEDs\Monitored data
LED 36
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt37.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 37 3=Alarm LEDs\Monitored data
LED 37
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt38.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 38 3=Alarm LEDs\Monitored data
LED 38
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt39.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 39 3=Alarm LEDs\Monitored data
LED 39
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt40.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 40 3=Alarm LEDs\Monitored data
LED 40
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt41.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 41 3=Alarm LEDs\Monitored data
LED 41
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt42.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 42 3=Alarm LEDs\Monitored data
LED 42
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt43.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 43 3=Alarm LEDs\Monitored data
LED 43
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt44.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 44 3=Alarm LEDs\Monitored data
LED 44
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt45.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 45 3=Alarm LEDs\Monitored data
LED 45
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt46.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 46 3=Alarm LEDs\Monitored data
LED 46
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt47.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 47 3=Alarm LEDs\Monitored data
LED 47
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt48.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 48 3=Alarm LEDs\Monitored data
LED 48
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt49.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 49 3=Alarm LEDs\Monitored data
LED 49
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt50.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 50 3=Alarm LEDs\Monitored data
LED 50
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt51.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 51 3=Alarm LEDs\Monitored data
LED 51

39
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt52.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 52 3=Alarm LEDs\Monitored data
LED 52
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt53.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 53 3=Alarm LEDs\Monitored data
LED 53
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt54.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 54 3=Alarm LEDs\Monitored data
LED 54
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt55.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 55 3=Alarm LEDs\Monitored data
LED 55
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt56.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 56 3=Alarm LEDs\Monitored data
LED 56
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt57.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 57 3=Alarm LEDs\Monitored data
LED 57
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt58.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 58 3=Alarm LEDs\Monitored data
LED 58
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt59.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 59 3=Alarm LEDs\Monitored data
LED 59
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt60.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 60 3=Alarm LEDs\Monitored data
LED 60
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt61.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 61 3=Alarm LEDs\Monitored data
LED 61
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt62.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 62 3=Alarm LEDs\Monitored data
LED 62
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt63.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 63 3=Alarm LEDs\Monitored data
LED 63
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt64.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 64 3=Alarm LEDs\Monitored data
LED 64
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt65.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 65 3=Alarm LEDs\Monitored data
LED 65
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt66.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 66 3=Alarm LEDs\Monitored data
LED 66
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt67.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 67 3=Alarm LEDs\Monitored data
LED 67

40
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt68.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 68 3=Alarm LEDs\Monitored data
LED 68
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt69.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 69 3=Alarm LEDs\Monitored data
LED 69
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt70.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 70 3=Alarm LEDs\Monitored data
LED 70
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt71.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 71 3=Alarm LEDs\Monitored data
LED 71
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt72.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 72 3=Alarm LEDs\Monitored data
LED 72
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt73.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 73 3=Alarm LEDs\Monitored data
LED 73
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt74.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 74 3=Alarm LEDs\Monitored data
LED 74
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt75.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 75 3=Alarm LEDs\Monitored data
LED 75
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt76.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 76 3=Alarm LEDs\Monitored data
LED 76
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt77.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 77 3=Alarm LEDs\Monitored data
LED 77
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt78.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 78 3=Alarm LEDs\Monitored data
LED 78
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt79.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 79 3=Alarm LEDs\Monitored data
LED 79
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt80.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 80 3=Alarm LEDs\Monitored data
LED 80
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt81.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 81 3=Alarm LEDs\Monitored data
LED 81
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt82.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 82 3=Alarm LEDs\Monitored data
LED 82
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt83.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 83 3=Alarm LEDs\Monitored data
LED 83

41
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt84.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 84 3=Alarm LEDs\Monitored data
LED 84
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt85.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 85 3=Alarm LEDs\Monitored data
LED 85
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt86.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 86 3=Alarm LEDs\Monitored data
LED 86
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt87.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 87 3=Alarm LEDs\Monitored data
LED 87
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt88.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 88 3=Alarm LEDs\Monitored data
LED 88
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt89.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 89 3=Alarm LEDs\Monitored data
LED 89
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt90.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 90 3=Alarm LEDs\Monitored data
LED 90
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt91.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 91 3=Alarm LEDs\Monitored data
LED 91
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt92.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 92 3=Alarm LEDs\Monitored data
LED 92
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt93.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 93 3=Alarm LEDs\Monitored data
LED 93
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt94.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 94 3=Alarm LEDs\Monitored data
LED 94
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt95.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 95 3=Alarm LEDs\Monitored data
LED 95
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt96.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 96 3=Alarm LEDs\Monitored data
LED 96
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt97.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 97 3=Alarm LEDs\Monitored data
LED 97
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt98.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 98 3=Alarm LEDs\Monitored data
LED 98
Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt99.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 99 3=Alarm LEDs\Monitored data
LED 99

42
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Status of
Programmable Programmable 0=None; 1=Ok; Monitoring\Programmable
MON LD0.LEDGGIO1.LEDSt100.stVal ENC Enum ST B StatIO P I1 programmable
LEDs LED 100 3=Alarm LEDs\Monitored data
LED 100
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt1.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 1 LED description LEDs\LED 1
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt1.d ENC DC Description
LEDs (64) LEDs LED 1 LED description LEDs\LED 1
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt2.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 2 LED description LEDs\LED 2
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt2.d ENC DC Description
LEDs (64) LEDs LED 2 LED description LEDs\LED 2
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt3.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 3 LED description LEDs\LED 3
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt3.d ENC DC Description
LEDs (64) LEDs LED 3 LED description LEDs\LED 3
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt4.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 4 LED description LEDs\LED 4
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt4.d ENC DC Description
LEDs (64) LEDs LED 4 LED description LEDs\LED 4
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt5.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 5 LED description LEDs\LED 5
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt5.d ENC DC Description
LEDs (64) LEDs LED 5 LED description LEDs\LED 5
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt6.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 6 LED description LEDs\LED 6
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt6.d ENC DC Description
LEDs (64) LEDs LED 6 LED description LEDs\LED 6
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt7.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 7 LED description LEDs\LED 7
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt7.d ENC DC Description
LEDs (64) LEDs LED 7 LED description LEDs\LED 7
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt8.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 8 LED description LEDs\LED 8
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt8.d ENC DC Description
LEDs (64) LEDs LED 8 LED description LEDs\LED 8
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt9.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 9 LED description LEDs\LED 9
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt9.d ENC DC Description
LEDs (64) LEDs LED 9 LED description LEDs\LED 9
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt10.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 10 LED description LEDs\LED 10
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt10.d ENC DC Description
LEDs (64) LEDs LED 10 LED description LEDs\LED 10
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt11.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 11 LED description LEDs\LED 11
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt11.d ENC DC Description
LEDs (64) LEDs LED 11 LED description LEDs\LED 11
43
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable Programmable Programmable Configuration\Programmable


CFG LD0.LEDGGIO1.LEDSt12.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 12 LED description LEDs\LED 12
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt12.d ENC DC Description
LEDs (64) LEDs LED 12 LED description LEDs\LED 12
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt13.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 13 LED description LEDs\LED 13
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt13.d ENC DC Description
LEDs (64) LEDs LED 13 LED description LEDs\LED 13
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt14.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 14 LED description LEDs\LED 14
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt14.d ENC DC Description
LEDs (64) LEDs LED 14 LED description LEDs\LED 14
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt15.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 15 LED description LEDs\LED 15
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt15.d ENC DC Description
LEDs (64) LEDs LED 15 LED description LEDs\LED 15
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt16.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 16 LED description LEDs\LED 16
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt16.d ENC DC Description
LEDs (64) LEDs LED 16 LED description LEDs\LED 16
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt17.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 17 LED description LEDs\LED 17
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt17.d ENC DC Description
LEDs (64) LEDs LED 17 LED description LEDs\LED 17
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt18.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 18 LED description LEDs\LED 18
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt18.d ENC DC Description
LEDs (64) LEDs LED 18 LED description LEDs\LED 18
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt19.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 19 LED description LEDs\LED 19
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt19.d ENC DC Description
LEDs (64) LEDs LED 19 LED description LEDs\LED 19
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt20.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 20 LED description LEDs\LED 20
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt20.d ENC DC Description
LEDs (64) LEDs LED 20 LED description LEDs\LED 20
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt21.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 21 LED description LEDs\LED 21
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt21.d ENC DC Description
LEDs (64) LEDs LED 21 LED description LEDs\LED 21
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt22.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 22 LED description LEDs\LED 22
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt22.d ENC DC Description
LEDs (64) LEDs LED 22 LED description LEDs\LED 22
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt23.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 23 LED description LEDs\LED 23

44
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable VisString255 Programmable Programmable Configuration\Programmable


CFG LD0.LEDGGIO1.LEDSt23.d ENC DC Description
LEDs (64) LEDs LED 23 LED description LEDs\LED 23
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt24.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 24 LED description LEDs\LED 24
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt24.d ENC DC Description
LEDs (64) LEDs LED 24 LED description LEDs\LED 24
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt25.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 25 LED description LEDs\LED 25
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt25.d ENC DC Description
LEDs (64) LEDs LED 25 LED description LEDs\LED 25
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt26.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 26 LED description LEDs\LED 26
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt26.d ENC DC Description
LEDs (64) LEDs LED 26 LED description LEDs\LED 26
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt27.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 27 LED description LEDs\LED 27
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt27.d ENC DC Description
LEDs (64) LEDs LED 27 LED description LEDs\LED 27
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt28.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 28 LED description LEDs\LED 28
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt28.d ENC DC Description
LEDs (64) LEDs LED 28 LED description LEDs\LED 28
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt29.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 29 LED description LEDs\LED 29
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt29.d ENC DC Description
LEDs (64) LEDs LED 29 LED description LEDs\LED 29
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt30.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 30 LED description LEDs\LED 30
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt30.d ENC DC Description
LEDs (64) LEDs LED 30 LED description LEDs\LED 30
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt31.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 31 LED description LEDs\LED 31
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt31.d ENC DC Description
LEDs (64) LEDs LED 31 LED description LEDs\LED 31
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt32.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 32 LED description LEDs\LED 32
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt32.d ENC DC Description
LEDs (64) LEDs LED 32 LED description LEDs\LED 32
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt33.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 33 LED description LEDs\LED 33
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt33.d ENC DC Description
LEDs (64) LEDs LED 33 LED description LEDs\LED 33
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt34.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 34 LED description LEDs\LED 34
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt34.d ENC DC Description
LEDs (64) LEDs LED 34 LED description LEDs\LED 34

45
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable Programmable Programmable Configuration\Programmable


CFG LD0.LEDGGIO1.LEDSt35.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 35 LED description LEDs\LED 35
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt35.d ENC DC Description
LEDs (64) LEDs LED 35 LED description LEDs\LED 35
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt36.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 36 LED description LEDs\LED 36
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt36.d ENC DC Description
LEDs (64) LEDs LED 36 LED description LEDs\LED 36
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt37.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 37 LED description LEDs\LED 37
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt37.d ENC DC Description
LEDs (64) LEDs LED 37 LED description LEDs\LED 37
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt38.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 38 LED description LEDs\LED 38
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt38.d ENC DC Description
LEDs (64) LEDs LED 38 LED description LEDs\LED 38
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt39.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 39 LED description LEDs\LED 39
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt39.d ENC DC Description
LEDs (64) LEDs LED 39 LED description LEDs\LED 39
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt40.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 40 LED description LEDs\LED 40
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt40.d ENC DC Description
LEDs (64) LEDs LED 40 LED description LEDs\LED 40
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt41.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 41 LED description LEDs\LED 41
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt41.d ENC DC Description
LEDs (64) LEDs LED 41 LED description LEDs\LED 41
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt42.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 42 LED description LEDs\LED 42
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt42.d ENC DC Description
LEDs (64) LEDs LED 42 LED description LEDs\LED 42
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt43.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 43 LED description LEDs\LED 43
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt43.d ENC DC Description
LEDs (64) LEDs LED 43 LED description LEDs\LED 43
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt44.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 44 LED description LEDs\LED 44
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt44.d ENC DC Description
LEDs (64) LEDs LED 44 LED description LEDs\LED 44
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt45.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 45 LED description LEDs\LED 45
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt45.d ENC DC Description
LEDs (64) LEDs LED 45 LED description LEDs\LED 45
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt46.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 46 LED description LEDs\LED 46

46
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable VisString255 Programmable Programmable Configuration\Programmable


CFG LD0.LEDGGIO1.LEDSt46.d ENC DC Description
LEDs (64) LEDs LED 46 LED description LEDs\LED 46
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt47.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 47 LED description LEDs\LED 47
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt47.d ENC DC Description
LEDs (64) LEDs LED 47 LED description LEDs\LED 47
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt48.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 48 LED description LEDs\LED 48
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt48.d ENC DC Description
LEDs (64) LEDs LED 48 LED description LEDs\LED 48
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt49.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 49 LED description LEDs\LED 49
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt49.d ENC DC Description
LEDs (64) LEDs LED 49 LED description LEDs\LED 49
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt50.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 50 LED description LEDs\LED 50
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt50.d ENC DC Description
LEDs (64) LEDs LED 50 LED description LEDs\LED 50
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt51.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 51 LED description LEDs\LED 51
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt51.d ENC DC Description
LEDs (64) LEDs LED 51 LED description LEDs\LED 51
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt52.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 52 LED description LEDs\LED 52
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt52.d ENC DC Description
LEDs (64) LEDs LED 52 LED description LEDs\LED 52
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt53.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 53 LED description LEDs\LED 53
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt53.d ENC DC Description
LEDs (64) LEDs LED 53 LED description LEDs\LED 53
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt54.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 54 LED description LEDs\LED 54
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt54.d ENC DC Description
LEDs (64) LEDs LED 54 LED description LEDs\LED 54
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt55.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 55 LED description LEDs\LED 55
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt55.d ENC DC Description
LEDs (64) LEDs LED 55 LED description LEDs\LED 55
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt56.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 56 LED description LEDs\LED 56
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt56.d ENC DC Description
LEDs (64) LEDs LED 56 LED description LEDs\LED 56
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt57.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 57 LED description LEDs\LED 57
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt57.d ENC DC Description
LEDs (64) LEDs LED 57 LED description LEDs\LED 57

47
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable Programmable Programmable Configuration\Programmable


CFG LD0.LEDGGIO1.LEDSt58.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 58 LED description LEDs\LED 58
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt58.d ENC DC Description
LEDs (64) LEDs LED 58 LED description LEDs\LED 58
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt59.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 59 LED description LEDs\LED 59
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt59.d ENC DC Description
LEDs (64) LEDs LED 59 LED description LEDs\LED 59
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt60.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 60 LED description LEDs\LED 60
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt60.d ENC DC Description
LEDs (64) LEDs LED 60 LED description LEDs\LED 60
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt61.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 61 LED description LEDs\LED 61
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt61.d ENC DC Description
LEDs (64) LEDs LED 61 LED description LEDs\LED 61
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt62.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 62 LED description LEDs\LED 62
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt62.d ENC DC Description
LEDs (64) LEDs LED 62 LED description LEDs\LED 62
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt63.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 63 LED description LEDs\LED 63
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt63.d ENC DC Description
LEDs (64) LEDs LED 63 LED description LEDs\LED 63
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt64.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 64 LED description LEDs\LED 64
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt64.d ENC DC Description
LEDs (64) LEDs LED 64 LED description LEDs\LED 64
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt65.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 65 LED description LEDs\LED 65
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt65.d ENC DC Description
LEDs (64) LEDs LED 65 LED description LEDs\LED 65
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt66.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 66 LED description LEDs\LED 66
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt66.d ENC DC Description
LEDs (64) LEDs LED 66 LED description LEDs\LED 66
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt67.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 67 LED description LEDs\LED 67
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt67.d ENC DC Description
LEDs (64) LEDs LED 67 LED description LEDs\LED 67
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt68.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 68 LED description LEDs\LED 68
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt68.d ENC DC Description
LEDs (64) LEDs LED 68 LED description LEDs\LED 68
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt69.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 69 LED description LEDs\LED 69

48
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable VisString255 Programmable Programmable Configuration\Programmable


CFG LD0.LEDGGIO1.LEDSt69.d ENC DC Description
LEDs (64) LEDs LED 69 LED description LEDs\LED 69
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt70.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 70 LED description LEDs\LED 70
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt70.d ENC DC Description
LEDs (64) LEDs LED 70 LED description LEDs\LED 70
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt71.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 71 LED description LEDs\LED 71
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt71.d ENC DC Description
LEDs (64) LEDs LED 71 LED description LEDs\LED 71
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt72.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 72 LED description LEDs\LED 72
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt72.d ENC DC Description
LEDs (64) LEDs LED 72 LED description LEDs\LED 72
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt73.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 73 LED description LEDs\LED 73
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt73.d ENC DC Description
LEDs (64) LEDs LED 73 LED description LEDs\LED 73
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt74.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 74 LED description LEDs\LED 74
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt74.d ENC DC Description
LEDs (64) LEDs LED 74 LED description LEDs\LED 74
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt75.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 75 LED description LEDs\LED 75
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt75.d ENC DC Description
LEDs (64) LEDs LED 75 LED description LEDs\LED 75
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt76.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 76 LED description LEDs\LED 76
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt76.d ENC DC Description
LEDs (64) LEDs LED 76 LED description LEDs\LED 76
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt77.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 77 LED description LEDs\LED 77
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt77.d ENC DC Description
LEDs (64) LEDs LED 77 LED description LEDs\LED 77
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt78.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 78 LED description LEDs\LED 78
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt78.d ENC DC Description
LEDs (64) LEDs LED 78 LED description LEDs\LED 78
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt79.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 79 LED description LEDs\LED 79
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt79.d ENC DC Description
LEDs (64) LEDs LED 79 LED description LEDs\LED 79
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt80.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 80 LED description LEDs\LED 80
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt80.d ENC DC Description
LEDs (64) LEDs LED 80 LED description LEDs\LED 80

49
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable Programmable Programmable Configuration\Programmable


CFG LD0.LEDGGIO1.LEDSt81.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 81 LED description LEDs\LED 81
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt81.d ENC DC Description
LEDs (64) LEDs LED 81 LED description LEDs\LED 81
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt82.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 82 LED description LEDs\LED 82
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt82.d ENC DC Description
LEDs (64) LEDs LED 82 LED description LEDs\LED 82
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt83.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 83 LED description LEDs\LED 83
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt83.d ENC DC Description
LEDs (64) LEDs LED 83 LED description LEDs\LED 83
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt84.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 84 LED description LEDs\LED 84
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt84.d ENC DC Description
LEDs (64) LEDs LED 84 LED description LEDs\LED 84
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt85.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 85 LED description LEDs\LED 85
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt85.d ENC DC Description
LEDs (64) LEDs LED 85 LED description LEDs\LED 85
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt86.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 86 LED description LEDs\LED 86
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt86.d ENC DC Description
LEDs (64) LEDs LED 86 LED description LEDs\LED 86
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt87.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 87 LED description LEDs\LED 87
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt87.d ENC DC Description
LEDs (64) LEDs LED 87 LED description LEDs\LED 87
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt88.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 88 LED description LEDs\LED 88
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt88.d ENC DC Description
LEDs (64) LEDs LED 88 LED description LEDs\LED 88
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt89.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 89 LED description LEDs\LED 89
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt89.d ENC DC Description
LEDs (64) LEDs LED 89 LED description LEDs\LED 89
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt90.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 90 LED description LEDs\LED 90
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt90.d ENC DC Description
LEDs (64) LEDs LED 90 LED description LEDs\LED 90
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt91.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 91 LED description LEDs\LED 91
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt91.d ENC DC Description
LEDs (64) LEDs LED 91 LED description LEDs\LED 91
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt92.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 92 LED description LEDs\LED 92

50
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Programmable VisString255 Programmable Programmable Configuration\Programmable


CFG LD0.LEDGGIO1.LEDSt92.d ENC DC Description
LEDs (64) LEDs LED 92 LED description LEDs\LED 92
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt93.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 93 LED description LEDs\LED 93
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt93.d ENC DC Description
LEDs (64) LEDs LED 93 LED description LEDs\LED 93
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt94.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 94 LED description LEDs\LED 94
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt94.d ENC DC Description
LEDs (64) LEDs LED 94 LED description LEDs\LED 94
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt95.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 95 LED description LEDs\LED 95
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt95.d ENC DC Description
LEDs (64) LEDs LED 95 LED description LEDs\LED 95
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt96.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 96 LED description LEDs\LED 96
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt96.d ENC DC Description
LEDs (64) LEDs LED 96 LED description LEDs\LED 96
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt97.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 97 LED description LEDs\LED 97
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt97.d ENC DC Description
LEDs (64) LEDs LED 97 LED description LEDs\LED 97
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt98.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 98 LED description LEDs\LED 98
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt98.d ENC DC Description
LEDs (64) LEDs LED 98 LED description LEDs\LED 98
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt99.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 99 LED description LEDs\LED 99
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt99.d ENC DC Description
LEDs (64) LEDs LED 99 LED description LEDs\LED 99
Programmable Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt100.dU ENC Unicode255 DC ED2,B Description
LEDs LEDs LED 100 LED description LEDs\LED 100
Programmable VisString255 Programmable Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSt100.d ENC DC Description
LEDs (64) LEDs LED 100 LED description LEDs\LED 100
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq1.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 1
LED 1 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq2.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 2
LED 2 3=LatchedAck-F-
S
Alarm mode for 0=Follow-S;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq3.setVal ENG Enum SP B,I 0 Alarm mode programmable 1=Follow-F;
LEDs LEDs\LED 3
LED 3 2=Latched-S;

51
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq4.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 4
LED 4 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq5.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 5
LED 5 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq6.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 6
LED 6 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq7.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 7
LED 7 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq8.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 8
LED 8 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq9.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 9
LED 9 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq10.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 10
LED 10 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq11.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 11
LED 11 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq12.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 12
LED 12 3=LatchedAck-F-
S
Alarm mode for 0=Follow-S;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq13.setVal ENG Enum SP B,I 0 Alarm mode programmable 1=Follow-F;
LEDs LEDs\LED 13
LED 13 2=Latched-S;

52
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq14.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 14
LED 14 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq15.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 15
LED 15 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq16.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 16
LED 16 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq17.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 17
LED 17 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq18.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 18
LED 18 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq19.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 19
LED 19 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq20.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 20
LED 20 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq21.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 21
LED 21 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq22.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 22
LED 22 3=LatchedAck-F-
S
Alarm mode for 0=Follow-S;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq23.setVal ENG Enum SP B,I 0 Alarm mode programmable 1=Follow-F;
LEDs LEDs\LED 23
LED 23 2=Latched-S;

53
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq24.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 24
LED 24 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq25.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 25
LED 25 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq26.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 26
LED 26 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq27.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 27
LED 27 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq28.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 28
LED 28 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq29.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 29
LED 29 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq30.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 30
LED 30 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq31.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 31
LED 31 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq32.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 32
LED 32 3=LatchedAck-F-
S
Alarm mode for 0=Follow-S;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq33.setVal ENG Enum SP B,I 0 Alarm mode programmable 1=Follow-F;
LEDs LEDs\LED 33
LED 33 2=Latched-S;

54
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq34.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 34
LED 34 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq35.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 35
LED 35 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq36.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 36
LED 36 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq37.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 37
LED 37 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq38.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 38
LED 38 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq39.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 39
LED 39 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq40.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 40
LED 40 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq41.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 41
LED 41 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq42.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 42
LED 42 3=LatchedAck-F-
S
Alarm mode for 0=Follow-S;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq43.setVal ENG Enum SP B,I 0 Alarm mode programmable 1=Follow-F;
LEDs LEDs\LED 43
LED 43 2=Latched-S;

55
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq44.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 44
LED 44 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq45.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 45
LED 45 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq46.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 46
LED 46 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq47.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 47
LED 47 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq48.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 48
LED 48 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq49.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 49
LED 49 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq50.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 50
LED 50 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq51.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 51
LED 51 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq52.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 52
LED 52 3=LatchedAck-F-
S
Alarm mode for 0=Follow-S;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq53.setVal ENG Enum SP B,I 0 Alarm mode programmable 1=Follow-F;
LEDs LEDs\LED 53
LED 53 2=Latched-S;

56
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq54.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 54
LED 54 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq55.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 55
LED 55 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq56.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 56
LED 56 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq57.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 57
LED 57 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq58.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 58
LED 58 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq59.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 59
LED 59 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq60.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 60
LED 60 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq61.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 61
LED 61 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq62.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 62
LED 62 3=LatchedAck-F-
S
Alarm mode for 0=Follow-S;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq63.setVal ENG Enum SP B,I 0 Alarm mode programmable 1=Follow-F;
LEDs LEDs\LED 63
LED 63 2=Latched-S;

57
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq64.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 64
LED 64 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq65.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 65
LED 65 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq66.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 66
LED 66 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq67.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 67
LED 67 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq68.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 68
LED 68 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq69.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 69
LED 69 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq70.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 70
LED 70 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq71.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 71
LED 71 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq72.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 72
LED 72 3=LatchedAck-F-
S
Alarm mode for 0=Follow-S;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq73.setVal ENG Enum SP B,I 0 Alarm mode programmable 1=Follow-F;
LEDs LEDs\LED 73
LED 73 2=Latched-S;

58
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq74.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 74
LED 74 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq75.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 75
LED 75 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq76.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 76
LED 76 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq77.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 77
LED 77 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq78.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 78
LED 78 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq79.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 79
LED 79 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq80.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 80
LED 80 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq81.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 81
LED 81 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq82.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 82
LED 82 3=LatchedAck-F-
S
Alarm mode for 0=Follow-S;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq83.setVal ENG Enum SP B,I 0 Alarm mode programmable 1=Follow-F;
LEDs LEDs\LED 83
LED 83 2=Latched-S;

59
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq84.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 84
LED 84 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq85.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 85
LED 85 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq86.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 86
LED 86 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq87.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 87
LED 87 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq88.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 88
LED 88 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq89.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 89
LED 89 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq90.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 90
LED 90 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq91.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 91
LED 91 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq92.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 92
LED 92 3=LatchedAck-F-
S
Alarm mode for 0=Follow-S;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq93.setVal ENG Enum SP B,I 0 Alarm mode programmable 1=Follow-F;
LEDs LEDs\LED 93
LED 93 2=Latched-S;

60
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq94.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 94
LED 94 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq95.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 95
LED 95 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq96.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 96
LED 96 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq97.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 97
LED 97 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq98.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 98
LED 98 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq99.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 99
LED 99 3=LatchedAck-F-
S
0=Follow-S;
Alarm mode for 1=Follow-F;
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.LEDSeq100.setVal ENG Enum SP B,I 0 Alarm mode programmable 2=Latched-S;
LEDs LEDs\LED 100
LED 100 3=LatchedAck-F-
S
Colour for the
Programmable Configuration\Programmable
CFG LD0.LEDGGIO1.AlmColr.setVal ENG Enum SP B,I 2 Alarm colour alarm state of 1=Green; 2=Red
LEDs LEDs\General
the LED
Programmable VisString255
VER LD0.LEDGGIO1.NamPlt.swRev LPL DC ED1 F2 (Name plate)
LEDs (20)

GSELPRT1: D2
IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Menu path
60617 name range relation
Receiver Alarm Monitoring\I/O
GSELPRT1 GSE GSE OUT LD0.GSELPRT1.Alm.stVal SPS BOOLEAN ST B StatUrg P,H I1 ALARM
general status\Communication\GSELPRT1\Outputs
61
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Active if receiving Monitoring\I/O


GSELPRT1 GSE GSE OUT LD0.GSELPRT1.RxSim.stVal SPS BOOLEAN ST B I1 SIMULATED
simulation status\Communication\GSELPRT1\Outputs
Resets GOOSE
Monitoring\I/O
GSELPRT1 GSE GSE CTR LD0.GSELPRT1.CntRs.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Reset counters diagnostics
status\Communication\GSELPRT1\Monitoring
counters
Received GOOSE Monitoring\I/O
GSELPRT1 GSE GSE MON LD0.GSELPRT1.FrRxCnt.stVal INS INT32 ST B I1 Received msgs 0...10000000
messages. status\Communication\GSELPRT1\Monitoring
Transmitted Transmitted Monitoring\I/O
GSELPRT1 GSE GSE MON LD0.GSELPRT1.FrTxCnt.stVal INS INT32 ST B I1 0...10000000
msgs GOOSE messages. status\Communication\GSELPRT1\Monitoring
Received GOOSE Monitoring\I/O
GSELPRT1 GSE GSE MON LD0.GSELPRT1.RxStCnt.stVal INS INT32 ST B I1 State changes 0...10000000
state changes. status\Communication\GSELPRT1\Monitoring
Received GOOSE
SeqNum Monitoring\I/O
GSELPRT1 GSE GSE MON LD0.GSELPRT1.RxSeqCnt.stVal INS INT32 ST B I1 sequence number 0...10000000
changes status\Communication\GSELPRT1\Monitoring
changes.
Received GOOSE
Monitoring\I/O
GSELPRT1 GSE GSE MON LD0.GSELPRT1.RxTestCnt.stVal INS INT32 ST B I1 Test msgs messages with test 0...10000000
status\Communication\GSELPRT1\Monitoring
bit set to TRUE.
State number miss
or disorder in Monitoring\I/O
GSELPRT1 GSE GSE MON LD0.GSELPRT1.StWrnCnt.stVal INS INT32 ST B I1 State warnings 0...10000000
GOOSE message status\Communication\GSELPRT1\Monitoring
reception.
Sequence number
miss or disorder in Monitoring\I/O
GSELPRT1 GSE GSE MON LD0.GSELPRT1.SeqWrnCnt.stVal INS INT32 ST B I1 Seq. warnings 0...10000000
GOOSE message status\Communication\GSELPRT1\Monitoring
reception.
Receiver timeouts.
Goose messages Monitoring\I/O
GSELPRT1 GSE GSE MON LD0.GSELPRT1.RxTmOutCnt.stVal INS INT32 ST B I1 Recv. timeouts 0...10000000
were not received status\Communication\GSELPRT1\Monitoring
in defined time.
Received
configuration
ConfRev Monitoring\I/O
GSELPRT1 GSE GSE MON LD0.GSELPRT1.ConfErrCnt.stVal INS INT32 ST B I1 revision 0...10000000
errors status\Communication\GSELPRT1\Monitoring
mismatched
GOOSE messages.
Received GOOSE
messages with
NdsComm Monitoring\I/O
GSELPRT1 GSE GSE MON LD0.GSELPRT1.NdsComCnt.stVal INS INT32 ST B I1 Needs 0...10000000
errors status\Communication\GSELPRT1\Monitoring
Commissioning bit
set to TRUE.
Received dataset
Monitoring\I/O
GSELPRT1 GSE GSE MON LD0.GSELPRT1.DSErrCnt.stVal INS INT32 ST B I1 Dataset errors mismatched 0...10000000
status\Communication\GSELPRT1\Monitoring
GOOSE messages.
Resets GOOSE
Monitoring\I/O
GSELPRT1 GSE GSE MON LD0.GSELPRT1.CntRs.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Reset counters diagnostics
status\Communication\GSELPRT1\Monitoring
counters
Received GOOSE
Simulation messages with Monitoring\I/O
GSELPRT1 GSE GSE MON LD0.GSELPRT1.RxSimCnt.stVal INS INT32 ST B I1 0...10000000
msgs simulation bit set to status\Communication\GSELPRT1\Monitoring
TRUE.
62
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Transmitted Sent GOOSE state Monitoring\I/O


GSELPRT1 GSE GSE MON LD0.GSELPRT1.TxStCnt.stVal INS INT32 ST B I1 0...10000000
state changes changes. status\Communication\GSELPRT1\Monitoring
VisString255
GSELPRT1 GSE GSE VER LD0.GSELPRT1.NamPlt.swRev LPL DC D2 (Name plate)
(20)

61850-8-1 MMS: E1
IEC IEC Parameter Parameter Channel
ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Menu path
61850 60617 name range relation
MMS Communication
61850-
status (True = OK,
8-1 OUT LD0.MMSLPRT1.ChLiv.stVal SPS BOOLEAN ST B I1 CHLIV Monitoring\Communication\MMSLPRT1
False = No
MMS
connections)
61850-
(Setting group editing
8-1 CTR LD0.MMSLPRT1.SetCnfMod.Oper.ctlVal SPC BOOLEAN CO I I1
mode)
MMS
61850-
Reset
8-1 CTR LD0.MMSLPRT1.CntRs.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Reset MMS counters Monitoring\Communication\MMSLPRT1
counters
MMS
61850-
Successful MMS successful
8-1 MON LD0.MMSLPRT1.SucConn.stVal INS INT32 ST B I1 0...10000000 Monitoring\Communication\MMSLPRT1
conn. connections
MMS
61850-
Failed MMS failed
8-1 MON LD0.MMSLPRT1.FailConn.stVal INS INT32 ST B I1 0...10000000 Monitoring\Communication\MMSLPRT1
conn. connections
MMS
61850-
8-1 MON LD0.MMSLPRT1.ConcCnt.stVal INS INT32 ST B I1 Concludes MMS concludes 0...10000000 Monitoring\Communication\MMSLPRT1
MMS
61850-
8-1 MON LD0.MMSLPRT1.TxAbtCnt.stVal INS INT32 ST B I1 Sent aborts MMS sent aborts 0...10000000 Monitoring\Communication\MMSLPRT1
MMS
61850-
Recv.
8-1 MON LD0.MMSLPRT1.RxAbtCnt.stVal INS INT32 ST B I1 MMS received aborts 0...10000000 Monitoring\Communication\MMSLPRT1
aborts
MMS
61850-
8-1 MON LD0.MMSLPRT1.TxRejCnt.stVal INS INT32 ST B I1 Sent rejects MMS sent rejects 0...10000000 Monitoring\Communication\MMSLPRT1
MMS
61850-
Recv. MMS received
8-1 MON LD0.MMSLPRT1.RxRqCnt.stVal INS INT32 ST B I1 0...10000000 Monitoring\Communication\MMSLPRT1
requests requests
MMS
61850-
Failed
8-1 MON LD0.MMSLPRT1.FailRqCnt.stVal INS INT32 ST B I1 MMS failed requests 0...10000000 Monitoring\Communication\MMSLPRT1
requests
MMS
61850-
8-1 MON LD0.MMSLPRT1.SucReaCnt.stVal INS INT32 ST B I1 Reads MMS successful reads 0...10000000 Monitoring\Communication\MMSLPRT1
MMS

63
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

61850-
Failed
8-1 MON LD0.MMSLPRT1.FailReaCnt.stVal INS INT32 ST B I1 MMS failed reads 0...10000000 Monitoring\Communication\MMSLPRT1
reads
MMS
61850-
MMS successful
8-1 MON LD0.MMSLPRT1.SucWrCnt.stVal INS INT32 ST B I1 Writes 0...10000000 Monitoring\Communication\MMSLPRT1
writes
MMS
61850-
Failed
8-1 MON LD0.MMSLPRT1.FailWrCnt.stVal INS INT32 ST B I1 MMS failed writes 0...10000000 Monitoring\Communication\MMSLPRT1
writes
MMS
61850-
MMS Information
8-1 MON LD0.MMSLPRT1.InfRpCnt.stVal INS INT32 ST B I1 Reports 0...10000000 Monitoring\Communication\MMSLPRT1
reports
MMS
61850-
Active MMS active
8-1 MON LD0.MMSLPRT1.ActConnCnt.stVal INS INT32 ST B I1 0...10000000 Monitoring\Communication\MMSLPRT1
conn. connections
MMS
61850-
Reset
8-1 MON LD0.MMSLPRT1.CntRs.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Reset MMS counters Monitoring\Communication\MMSLPRT1
counters
MMS
61850-
IEC 61850-8-1 unit 1=Primary;
8-1 CFG LD0.MMSLPRT1.UnitMod.setVal ENG Enum SP B,C 0 Unit mode Configuration\Communication\MMSLPRT1
mode 0=Nominal
MMS
61850-
VisString255 Edition IEC 61850 IEC 61850 version
8-1 INF LD0.MMSLPRT1.NamPlt.d LPL DC B Information\System identifiers
(64) 2 version selection
MMS
61850-
VisString255
8-1 VER LD0.MMSLPRT1.NamPlt.swRev LPL DC E1 (Name plate)
(20)
MMS

GNRLLTMS1: C2
Channe
IEC Categor CD Datase Even CM Parameter Parameter
IEC 61850 ANSI IECName Type FC Access Default Parameter desc Menu path l
60617 y C t t T name range
relation
GNRLLTMS TSYNC(1 TSYNC(1
OUT LD0.GNRLLTMS1.Alm.stVal SPS BOOLEAN ST ED2 I1 (Alarm)
1 ) )
GNRLLTMS TSYNC(1 TSYNC(1
OUT LD0.GNRLLTMM1.Alm.stVal SPS BOOLEAN ST ED1 I1 (Alarm)
1 ) )
GNRLLTMS TSYNC(1 TSYNC(1
OUT LD0.GNRLLTMS1.Wrn.stVal SPS BOOLEAN ST ED2 I1 (Warning)
1 ) )
GNRLLTMS TSYNC(1 TSYNC(1
OUT LD0.GNRLLTMM1.Wrn.stVal SPS BOOLEAN ST ED1 I1 (Warning)
1 ) )
Number of
significant bits
GNRLLTMS TSYNC(1 TSYNC(1 Synch in the Fraction Monitoring\IED status\Time
MON LD0.GNRLLTMS1.TmAcc.stVal INS INT32 ST ED2,B I1 0...128
1 ) ) accuracy Of Second in synchronization
the time
accuracy part

64
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

of the time
stamp.
Number of
significant bits
in the Fraction
GNRLLTMS TSYNC(1 TSYNC(1 Synch Of Second in Monitoring\IED status\Time
MON LD0.GNRLLTMM1.TmAcc.stVal INS INT32 ST ED1 I1 0...128
1 ) ) accuracy the time synchronization
accuracy part
of the time
stamp.
0=No sync;
Time
SMV 1=Local
GNRLLTMS TSYNC(1 TSYNC(1 StatIe synchronized Monitoring\IED status\SMV
MON LD0.GNRLLTMS1.TmSyn.stVal ENS Enum ST ED2,B P,H I1 Synch clock;
1 ) ) d according to accuracy
accuracy 2=Global
IEC 61850-9-2
clock
0=No sync;
Time
SMV 1=Local
GNRLLTMS TSYNC(1 TSYNC(1 StatIe synchronized Monitoring\IED status\SMV
MON LD0.GNRLLTMM1.TmSyn.stVal ENS Enum ST ED1 P,H I1 Synch clock;
1 ) ) d according to accuracy
accuracy 2=Global
IEC 61850-9-2
clock
Time channel
GNRLLTMS TSYNC(1 TSYNC(1 StatIe Synch 0=Down; Monitoring\IED status\Time
MON LD0.GNRLLTMS1.TmChSt1.stVal SPS BOOLEAN ST ED2,B P,H I1 status
1 ) ) d status 1=Up synchronization
(up/down)
Time channel
GNRLLTMS TSYNC(1 TSYNC(1 StatIe Synch 0=Down; Monitoring\IED status\Time
MON LD0.GNRLLTMM1.TmChSt1.stVal SPS BOOLEAN ST ED1 P,H I1 status
1 ) ) d status 1=Up synchronization
(up/down)
0=Not
defined;
1=SNTP
primary;
2=SNTP
secondary;
3=SNTP
tertiary or
further;
4=IEEE 1588
master;
5=IEEE 1588
GNRLLTMS TSYNC(1 TSYNC(1 StatIe Synch Current time slave; Monitoring\IED status\Time
MON LD0.GNRLLTMS1.TmSrcSt.stVal ENS Enum ST ED2,B P,H I1
1 ) ) d source source 6=IEEE 1588 synchronization
further;
7=IRIG-B;
8=DNP 3.0;
9=Modbus;
10=SPA;
11=LON
VATS;
12=LON
other;
13=PPS;
14=Minute
pulse;
65
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

15=local
GPS;
16=IEC60870
-5-101;
17=IEC60870
-5-103;
18=IEC60870
-5-104;
19=EXT;
20=LHMI;
21=Line
differential;
99=Free
running,
locally
generated
0=Not
defined;
1=SNTP
primary;
2=SNTP
secondary;
3=SNTP
tertiary or
further;
4=IEEE 1588
master;
5=IEEE 1588
slave;
6=IEEE 1588
further;
7=IRIG-B;
8=DNP 3.0;
9=Modbus;
GNRLLTMS TSYNC(1 TSYNC(1 StatIe Synch Current time Monitoring\IED status\Time
MON LD0.GNRLLTMM1.TmSrcSt.stVal ENS Enum ST ED1 P,H I1 10=SPA;
1 ) ) d source source synchronization
11=LON
VATS;
12=LON
other;
13=PPS;
14=Minute
pulse;
15=local
GPS;
16=IEC60870
-5-101;
17=IEC60870
-5-103;
18=IEC60870
-5-104;
19=EXT;
20=LHMI;
21=Line

66
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

differential;
99=Free
running,
locally
generated
Grandmaster
Identity octet
GNRLLTMS TSYNC(1 TSYNC(1 VS VisString25 ---------------- Grandmaste Monitoring\IED status\Time
MON LD0.GNRLLTMS1.MstrId.setVal SP ED2,B string
1 ) ) G 5 (20) --- r identity synchronization\IEEE 1588
according to
PTPv2
Grandmaster
Identity octet
GNRLLTMS TSYNC(1 TSYNC(1 VisString25 E ---------------- Grandmaste Monitoring\IED status\Time
MON LD0.GNRLLTMS1.NamPlt.mstrId LPL ED1 string
1 ) ) 5 (20) X --- r identity synchronization\IEEE 1588
according to
PTPv2
Time 0=None;
GNRLLTMS TSYNC(1 TSYNC(1 EN Synch Configuration\Time\Synchronizati
CFG LD0.GNRLLTMS1.TmSrcSel1.setVal Enum SP ED2,B,I 3 synchronizatio 1=SNTP;
1 ) ) G source on
n source 3=IEEE 1588
Time 0=None;
GNRLLTMS TSYNC(1 TSYNC(1 EN Synch Configuration\Time\Synchronizati
CFG LD0.GNRLLTMM1.TmSrcSel1.setVal Enum SP ED1 3 synchronizatio 1=SNTP;
1 ) ) G source on
n source 3=IEEE 1588
The domain is
identified by
GNRLLTMS TSYNC(1 TSYNC(1 PTP an integer, the Configuration\Time\Synchronizati
CFG LD0.GNRLLTMS1.DomId.setVal ING INT32 SP ED2,B 0 0...127
1 ) ) domain ID domainNumbe on
r, in the range
of 0 to 255.
The domain is
identified by
GNRLLTMS TSYNC(1 TSYNC(1 PTP an integer, the Configuration\Time\Synchronizati
CFG LD0.GNRLLTMM1.DomId.setVal ING INT32 SP ED1 0 0...127
1 ) ) domain ID domainNumbe on
r, in the range
of 0 to 255.
IP address for
GNRLLTMS TSYNC(1 TSYNC(1 VS VisString25 10.58.125.16 IP SNTP
CFG LD0.GNRLLTMS1.IPAddrSNTP1.setVal SP ED2,B,C SNTP primary Configuration\Time\SNTP
1 ) ) G 5 (20) 5 primary
server
IP address for
GNRLLTMS TSYNC(1 TSYNC(1 VisString25 E 10.58.125.16 IP SNTP
CFG LD0.GNRLLTMS1.NamPlt.eIpSNTPpri LPL ED1,C SNTP primary Configuration\Time\SNTP
1 ) ) 5 (20) X 5 primary
server
IP address for
GNRLLTMS TSYNC(1 TSYNC(1 VS VisString25 192.168.2.16 IP SNTP SNTP
CFG LD0.GNRLLTMS1.IPAddrSNTP2.setVal SP ED2,B,C Configuration\Time\SNTP
1 ) ) G 5 (20) 5 secondary secondary
server
IP address for
GNRLLTMS TSYNC(1 TSYNC(1 VisString25 E 192.168.2.16 IP SNTP SNTP
CFG LD0.GNRLLTMS1.NamPlt.eIpSNTPsec LPL ED1,C Configuration\Time\SNTP
1 ) ) 5 (20) X 5 secondary secondary
server
1=P2P
GNRLLTMS TSYNC(1 TSYNC(1 EN PTP profile Configuration\Time\Synchronizati
CFG LD0.GNRLLTMS1.PTPProfMod.setVal Enum SP ED2,B 2 PTP profile Default 1588-
1 ) ) G mode on
2008;
67
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

2=Power
profile
C37.238-
2011
1=P2P
Default 1588-
2008;
GNRLLTMS TSYNC(1 TSYNC(1 EN PTP profile Configuration\Time\Synchronizati
CFG LD0.GNRLLTMM1.PTPProfMod.setVal Enum SP ED1 2 PTP profile 2=Power
1 ) ) G mode on
profile
C37.238-
2011
Local time
GNRLLTIM Local time -840...840
CFG LD0.GNRLLTIM1.TmOfsTmm.setVal ING INT32 SP B 0 offset in Configuration\Time\System time
1 offset min
minutes
GNRLLTIM DST in use Configuration\Time\Daylight
CFG LD0.GNRLLTIM1.TmUseDT.setVal SPG BOOLEAN SP B 1 DST in use
1 setting saving time
0=reserved;
1=Monday;
2=Tuesday;
Daylight
3=Wednesda
GNRLLTIM LD0.GNRLLTIM1.TmChgDT.setCal.week DST on day saving time Configuration\Time\Daylight
CFG TSG Enum SP ED2,B 0 y;
1 Day (weekday) on, day of saving time
4=Thursday;
week
5=Friday;
6=Saturday;
7=Sunday
0=reserved;
1=Monday;
2=Tuesday;
Daylight
3=Wednesda
GNRLLTIM E DST on day saving time Configuration\Time\Daylight
CFG LD0.GNRLLTIM1.NamPlt.weekDayDT LPL Enum ED1 0 y;
1 X (weekday) on, day of saving time
4=Thursday;
week
5=Friday;
6=Saturday;
7=Sunday
1=January;
2=February;
3=March;
4=April;
5=May;
Daylight
DST on 6=June;
GNRLLTIM saving time Configuration\Time\Daylight
CFG LD0.GNRLLTIM1.TmChgDT.setCal.month TSG Enum SP ED2,B 5 date 7=July;
1 on, date saving time
(month) 8=August;
(dd:mm)
9=September;
10=October;
11=Novembe
r;
12=December
Daylight 1=January;
DST on
GNRLLTIM E saving time 2=February; Configuration\Time\Daylight
CFG LD0.GNRLLTIM1.NamPlt.monthDT LPL Enum ED1 5 date
1 X on, date 3=March; saving time
(month)
(dd:mm) 4=April;

68
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

5=May;
6=June;
7=July;
8=August;
9=September;
10=October;
11=Novembe
r;
12=December
Daylight
GNRLLTIM DST on saving time Configuration\Time\Daylight
CFG LD0.GNRLLTIM1.TmChgDT.setCal.day TSG INT8U SP ED2,B 1 1...31
1 date (day) on, date saving time
(dd:mm)
Daylight
GNRLLTIM E DST on saving time Configuration\Time\Daylight
CFG LD0.GNRLLTIM1.NamPlt.dayDT LPL INT8U ED1 1 1...31
1 X date (day) on, date saving time
(dd:mm)
DST on Daylight
GNRLLTIM Configuration\Time\Daylight
CFG LD0.GNRLLTIM1.TmChgDT.setCal.hr TSG INT8U SP ED2,B 2 time saving time 0...23 h
1 saving time
(hours) on, time (hh)
DST on Daylight
GNRLLTIM E Configuration\Time\Daylight
CFG LD0.GNRLLTIM1.NamPlt.hrDT LPL INT8U ED1 2 time saving time 0...23 h
1 X saving time
(hours) on, time (hh)
DST on Daylight
GNRLLTIM Configuration\Time\Daylight
CFG LD0.GNRLLTIM1.TmChgDT.setCal.mn TSG INT8U SP ED2,B 0 time saving time 0...59 min
1 saving time
(minutes) on, time (mm)
DST on Daylight
GNRLLTIM E Configuration\Time\Daylight
CFG LD0.GNRLLTIM1.NamPlt.mnDT LPL INT8U ED1 0 time saving time 0...59 min
1 X saving time
(minutes) on, time (mm)
0=reserved;
1=Monday;
2=Tuesday;
Daylight
DST off 3=Wednesda
GNRLLTIM LD0.GNRLLTIM1.TmChgST.setCal.week saving time Configuration\Time\Daylight
CFG TSG Enum SP ED2,B 0 day y;
1 Day off, day of saving time
(weekday) 4=Thursday;
week
5=Friday;
6=Saturday;
7=Sunday
0=reserved;
1=Monday;
2=Tuesday;
Daylight
DST off 3=Wednesda
GNRLLTIM E saving time Configuration\Time\Daylight
CFG LD0.GNRLLTIM1.NamPlt.weekDayST LPL Enum ED1 0 day y;
1 X off, day of saving time
(weekday) 4=Thursday;
week
5=Friday;
6=Saturday;
7=Sunday
Daylight 1=January;
DST off
GNRLLTIM saving time 2=February; Configuration\Time\Daylight
CFG LD0.GNRLLTIM1.TmChgST.setCal.month TSG Enum SP ED2,B 9 date
1 off, date 3=March; saving time
(month)
(dd:mm) 4=April;
69
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

5=May;
6=June;
7=July;
8=August;
9=September;
10=October;
11=Novembe
r;
12=December
1=January;
2=February;
3=March;
4=April;
5=May;
Daylight
DST off 6=June;
GNRLLTIM E saving time Configuration\Time\Daylight
CFG LD0.GNRLLTIM1.NamPlt.monthST LPL Enum ED1 9 date 7=July;
1 X off, date saving time
(month) 8=August;
(dd:mm)
9=September;
10=October;
11=Novembe
r;
12=December
Daylight
GNRLLTIM DST off saving time Configuration\Time\Daylight
CFG LD0.GNRLLTIM1.TmChgST.setCal.day TSG INT8U SP ED2,B 25 1...31
1 date (day) off, date saving time
(dd:mm)
Daylight
GNRLLTIM E DST off saving time Configuration\Time\Daylight
CFG LD0.GNRLLTIM1.NamPlt.dayST LPL INT8U ED1 25 1...31
1 X date (day) off, date saving time
(dd:mm)
DST off Daylight
GNRLLTIM Configuration\Time\Daylight
CFG LD0.GNRLLTIM1.TmChgST.setCal.hr TSG INT8U SP ED2,B 2 time saving time 0...23 h
1 saving time
(hours) off, time (hh)
DST off Daylight
GNRLLTIM E Configuration\Time\Daylight
CFG LD0.GNRLLTIM1.NamPlt.hrST LPL INT8U ED1 2 time saving time 0...23 h
1 X saving time
(hours) off, time (hh)
DST off Daylight
GNRLLTIM Configuration\Time\Daylight
CFG LD0.GNRLLTIM1.TmChgST.setCal.mn TSG INT8U SP ED2,B 0 time saving time 0...59 min
1 saving time
(minutes) off, time (mm)
DST off Daylight
GNRLLTIM E Configuration\Time\Daylight
CFG LD0.GNRLLTIM1.NamPlt.mnST LPL INT8U ED1 0 time saving time 0...59 min
1 X saving time
(minutes) off, time (mm)
GNRLLTIM VS VisString25
CFG LD0.GNRLLTIM1.TmSys.setVal SP ED2,B 0 Time Time Configuration\Time\System time
1 G 5 (20)
GNRLLTIM VisString25 E
CFG LD0.GNRLLTIM1.NamPlt.tmSys LPL ED1 0 Time Time Configuration\Time\System time
1 5 (20) X
GNRLLTIM VS VisString25
CFG LD0.GNRLLTIM1.DateSys.setVal SP ED2,B 0 Date Date Configuration\Time\System time
1 G 5 (20)
GNRLLTIM VisString25 E
CFG LD0.GNRLLTIM1.NamPlt.dateSys LPL ED1 0 Date Date Configuration\Time\System time
1 5 (20) X
70
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Daylight
GNRLLTIM -720...720 Configuration\Time\Daylight
CFG LD0.GNRLLTIM1.TmOfsDT.setVal ING INT32 SP B 60 DST offset saving time
1 min saving time
offset
GNRLLTMS TSYNC(1 TSYNC(1 VisString25 D ED2,ED
VER LD0.GNRLLTMS1.NamPlt.swRev LPL C2 (Name plate)
1 ) ) 5 (20) C 1
GNRLLTMS TSYNC(1 TSYNC(1 VisString25 D
VER LD0.GNRLLTMM1.NamPlt.swRev LPL ED1 C2 (Name plate)
1 ) ) 5 (20) C

MVGAPC1: C1
IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Menu path
60617 name range relation
Monitoring\I/O status\Generic
MVGAPC1 MV(1) MV(1) INP LD0.MVGAPC1.Ind1.stVal SPS BOOLEAN ST B 0 IN1 IN1 status
logic\MVGAPC1\Inputs
Monitoring\I/O status\Generic
MVGAPC1 MV(1) MV(1) INP LD0.MVGAPC1.Ind2.stVal SPS BOOLEAN ST B 0 IN2 IN2 status
logic\MVGAPC1\Inputs
Monitoring\I/O status\Generic
MVGAPC1 MV(1) MV(1) INP LD0.MVGAPC1.Ind3.stVal SPS BOOLEAN ST B 0 IN3 IN3 status
logic\MVGAPC1\Inputs
Monitoring\I/O status\Generic
MVGAPC1 MV(1) MV(1) INP LD0.MVGAPC1.Ind4.stVal SPS BOOLEAN ST B 0 IN4 IN4 status
logic\MVGAPC1\Inputs
Monitoring\I/O status\Generic
MVGAPC1 MV(1) MV(1) INP LD0.MVGAPC1.Ind5.stVal SPS BOOLEAN ST B 0 IN5 IN5 status
logic\MVGAPC1\Inputs
Monitoring\I/O status\Generic
MVGAPC1 MV(1) MV(1) INP LD0.MVGAPC1.Ind6.stVal SPS BOOLEAN ST B 0 IN6 IN6 status
logic\MVGAPC1\Inputs
Monitoring\I/O status\Generic
MVGAPC1 MV(1) MV(1) INP LD0.MVGAPC1.Ind7.stVal SPS BOOLEAN ST B 0 IN7 IN7 status
logic\MVGAPC1\Inputs
Monitoring\I/O status\Generic
MVGAPC1 MV(1) MV(1) INP LD0.MVGAPC1.Ind8.stVal SPS BOOLEAN ST B 0 IN8 IN8 status
logic\MVGAPC1\Inputs
Monitoring\I/O status\Generic
MVGAPC1 MV(1) MV(1) OUT LD0.MVGAPC1.SPCSO1.stVal SPC BOOLEAN ST B StatIed P,H I1 Q1 Q1 status
logic\MVGAPC1\Outputs
Monitoring\I/O status\Generic
MVGAPC1 MV(1) MV(1) OUT LD0.MVGAPC1.SPCSO2.stVal SPC BOOLEAN ST B StatIed P,H I1 Q2 Q2 status
logic\MVGAPC1\Outputs
Monitoring\I/O status\Generic
MVGAPC1 MV(1) MV(1) OUT LD0.MVGAPC1.SPCSO3.stVal SPC BOOLEAN ST B StatIed P,H I1 Q3 Q3 status
logic\MVGAPC1\Outputs
Monitoring\I/O status\Generic
MVGAPC1 MV(1) MV(1) OUT LD0.MVGAPC1.SPCSO4.stVal SPC BOOLEAN ST B StatIed P,H I1 Q4 Q4 status
logic\MVGAPC1\Outputs
Monitoring\I/O status\Generic
MVGAPC1 MV(1) MV(1) OUT LD0.MVGAPC1.SPCSO5.stVal SPC BOOLEAN ST B StatIed P,H I1 Q5 Q5 status
logic\MVGAPC1\Outputs
Monitoring\I/O status\Generic
MVGAPC1 MV(1) MV(1) OUT LD0.MVGAPC1.SPCSO6.stVal SPC BOOLEAN ST B StatIed P,H I1 Q6 Q6 status
logic\MVGAPC1\Outputs
Monitoring\I/O status\Generic
MVGAPC1 MV(1) MV(1) OUT LD0.MVGAPC1.SPCSO7.stVal SPC BOOLEAN ST B StatIed P,H I1 Q7 Q7 status
logic\MVGAPC1\Outputs
Monitoring\I/O status\Generic
MVGAPC1 MV(1) MV(1) OUT LD0.MVGAPC1.SPCSO8.stVal SPC BOOLEAN ST B StatIed P,H I1 Q8 Q8 status
logic\MVGAPC1\Outputs
VisString255 MVGAPC1 Output Configuration\Generic
MVGAPC1 MV(1) MV(1) CFG LD0.MVGAPC1.SPCSO1.d SPC DC B Description
(64) Q1 description logic\MVGAPC1\Output 1
71
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

VisString255 MVGAPC1 Output Configuration\Generic


MVGAPC1 MV(1) MV(1) CFG LD0.MVGAPC1.SPCSO2.d SPC DC B Description
(64) Q2 description logic\MVGAPC1\Output 2
VisString255 MVGAPC1 Output Configuration\Generic
MVGAPC1 MV(1) MV(1) CFG LD0.MVGAPC1.SPCSO3.d SPC DC B Description
(64) Q3 description logic\MVGAPC1\Output 3
VisString255 MVGAPC1 Output Configuration\Generic
MVGAPC1 MV(1) MV(1) CFG LD0.MVGAPC1.SPCSO4.d SPC DC B Description
(64) Q4 description logic\MVGAPC1\Output 4
VisString255 MVGAPC1 Output Configuration\Generic
MVGAPC1 MV(1) MV(1) CFG LD0.MVGAPC1.SPCSO5.d SPC DC B Description
(64) Q5 description logic\MVGAPC1\Output 5
VisString255 MVGAPC1 Output Configuration\Generic
MVGAPC1 MV(1) MV(1) CFG LD0.MVGAPC1.SPCSO6.d SPC DC B Description
(64) Q6 description logic\MVGAPC1\Output 6
VisString255 MVGAPC1 Output Configuration\Generic
MVGAPC1 MV(1) MV(1) CFG LD0.MVGAPC1.SPCSO7.d SPC DC B Description
(64) Q7 description logic\MVGAPC1\Output 7
VisString255 MVGAPC1 Output Configuration\Generic
MVGAPC1 MV(1) MV(1) CFG LD0.MVGAPC1.SPCSO8.d SPC DC B Description
(64) Q8 description logic\MVGAPC1\Output 8
VisString255
MVGAPC1 MV(1) MV(1) VER LD0.MVGAPC1.NamPlt.swRev LPL DC ED1 C1 (Name plate)
(20)

SRGAPC1: B1
IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Menu path
60617 name range relation
Set Q1 output when Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) INP LD0.SRGAPC1.Ind1.stVal SPS BOOLEAN ST B 0 I1 S1
set logic\SRGAPC1\Inputs
Set Q2 output when Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) INP LD0.SRGAPC1.Ind2.stVal SPS BOOLEAN ST B 0 I1 S2
set logic\SRGAPC1\Inputs
Set Q3 output when Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) INP LD0.SRGAPC1.Ind3.stVal SPS BOOLEAN ST B 0 I1 S3
set logic\SRGAPC1\Inputs
Set Q4 output when Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) INP LD0.SRGAPC1.Ind4.stVal SPS BOOLEAN ST B 0 I1 S4
set logic\SRGAPC1\Inputs
Set Q5 output when Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) INP LD0.SRGAPC1.Ind5.stVal SPS BOOLEAN ST B 0 I1 S5
set logic\SRGAPC1\Inputs
Set Q6 output when Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) INP LD0.SRGAPC1.Ind6.stVal SPS BOOLEAN ST B 0 I1 S6
set logic\SRGAPC1\Inputs
Set Q7 output when Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) INP LD0.SRGAPC1.Ind7.stVal SPS BOOLEAN ST B 0 I1 S7
set logic\SRGAPC1\Inputs
Set Q8 output when Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) INP LD0.SRGAPC1.Ind8.stVal SPS BOOLEAN ST B 0 I1 S8
set logic\SRGAPC1\Inputs
Resets Q1 output Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) INP LD0.SRGAPC1.Rs1.stVal SPC BOOLEAN ST B 0 I1 R1
when set logic\SRGAPC1\Inputs
Resets Q2 output Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) INP LD0.SRGAPC1.Rs2.stVal SPC BOOLEAN ST B 0 I1 R2
when set logic\SRGAPC1\Inputs
Resets Q3 output Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) INP LD0.SRGAPC1.Rs3.stVal SPC BOOLEAN ST B 0 I1 R3
when set logic\SRGAPC1\Inputs
Resets Q4 output Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) INP LD0.SRGAPC1.Rs4.stVal SPC BOOLEAN ST B 0 I1 R4
when set logic\SRGAPC1\Inputs

72
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Resets Q5 output Monitoring\I/O status\Generic


SRGAPC1 SR(1) SR(1) INP LD0.SRGAPC1.Rs5.stVal SPC BOOLEAN ST B 0 I1 R5
when set logic\SRGAPC1\Inputs
Resets Q6 output Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) INP LD0.SRGAPC1.Rs6.stVal SPC BOOLEAN ST B 0 I1 R6
when set logic\SRGAPC1\Inputs
Resets Q7 output Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) INP LD0.SRGAPC1.Rs7.stVal SPC BOOLEAN ST B 0 I1 R7
when set logic\SRGAPC1\Inputs
Resets Q8 output Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) INP LD0.SRGAPC1.Rs8.stVal SPC BOOLEAN ST B 0 I1 R8
when set logic\SRGAPC1\Inputs
Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) OUT LD0.SRGAPC1.SPCSO1.stVal SPC BOOLEAN ST B I1 Q1 Q1 status
logic\SRGAPC1\Outputs
Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) OUT LD0.SRGAPC1.SPCSO2.stVal SPC BOOLEAN ST B I1 Q2 Q2 status
logic\SRGAPC1\Outputs
Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) OUT LD0.SRGAPC1.SPCSO3.stVal SPC BOOLEAN ST B I1 Q3 Q3 status
logic\SRGAPC1\Outputs
Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) OUT LD0.SRGAPC1.SPCSO4.stVal SPC BOOLEAN ST B I1 Q4 Q4 status
logic\SRGAPC1\Outputs
Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) OUT LD0.SRGAPC1.SPCSO5.stVal SPC BOOLEAN ST B I1 Q5 Q5 status
logic\SRGAPC1\Outputs
Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) OUT LD0.SRGAPC1.SPCSO6.stVal SPC BOOLEAN ST B I1 Q6 Q6 status
logic\SRGAPC1\Outputs
Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) OUT LD0.SRGAPC1.SPCSO7.stVal SPC BOOLEAN ST B I1 Q7 Q7 status
logic\SRGAPC1\Outputs
Monitoring\I/O status\Generic
SRGAPC1 SR(1) SR(1) OUT LD0.SRGAPC1.SPCSO8.stVal SPC BOOLEAN ST B I1 Q8 Q8 status
logic\SRGAPC1\Outputs
Resets Q1 output 0=Cancel;
SRGAPC1 SR(1) SR(1) CTR LD0.SRGAPC1.Rs1.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Reset Q1 Configuration\Generic logic\SRGAPC1
when set 1=Reset
Resets Q2 output 0=Cancel;
SRGAPC1 SR(1) SR(1) CTR LD0.SRGAPC1.Rs2.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Reset Q2 Configuration\Generic logic\SRGAPC1
when set 1=Reset
Resets Q3 output 0=Cancel;
SRGAPC1 SR(1) SR(1) CTR LD0.SRGAPC1.Rs3.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Reset Q3 Configuration\Generic logic\SRGAPC1
when set 1=Reset
Resets Q4 output 0=Cancel;
SRGAPC1 SR(1) SR(1) CTR LD0.SRGAPC1.Rs4.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Reset Q4 Configuration\Generic logic\SRGAPC1
when set 1=Reset
Resets Q5 output 0=Cancel;
SRGAPC1 SR(1) SR(1) CTR LD0.SRGAPC1.Rs5.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Reset Q5 Configuration\Generic logic\SRGAPC1
when set 1=Reset
Resets Q6 output 0=Cancel;
SRGAPC1 SR(1) SR(1) CTR LD0.SRGAPC1.Rs6.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Reset Q6 Configuration\Generic logic\SRGAPC1
when set 1=Reset
Resets Q7 output 0=Cancel;
SRGAPC1 SR(1) SR(1) CTR LD0.SRGAPC1.Rs7.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Reset Q7 Configuration\Generic logic\SRGAPC1
when set 1=Reset
Resets Q8 output 0=Cancel;
SRGAPC1 SR(1) SR(1) CTR LD0.SRGAPC1.Rs8.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Reset Q8 Configuration\Generic logic\SRGAPC1
when set 1=Reset
Resets Q1 output 0=Cancel;
SRGAPC1 SR(1) SR(1) CFG LD0.SRGAPC1.Rs1.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Reset Q1 Configuration\Generic logic\SRGAPC1
when set 1=Reset
Resets Q2 output 0=Cancel;
SRGAPC1 SR(1) SR(1) CFG LD0.SRGAPC1.Rs2.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Reset Q2 Configuration\Generic logic\SRGAPC1
when set 1=Reset
Resets Q3 output 0=Cancel;
SRGAPC1 SR(1) SR(1) CFG LD0.SRGAPC1.Rs3.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Reset Q3 Configuration\Generic logic\SRGAPC1
when set 1=Reset

73
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Resets Q4 output 0=Cancel;


SRGAPC1 SR(1) SR(1) CFG LD0.SRGAPC1.Rs4.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Reset Q4 Configuration\Generic logic\SRGAPC1
when set 1=Reset
Resets Q5 output 0=Cancel;
SRGAPC1 SR(1) SR(1) CFG LD0.SRGAPC1.Rs5.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Reset Q5 Configuration\Generic logic\SRGAPC1
when set 1=Reset
Resets Q6 output 0=Cancel;
SRGAPC1 SR(1) SR(1) CFG LD0.SRGAPC1.Rs6.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Reset Q6 Configuration\Generic logic\SRGAPC1
when set 1=Reset
Resets Q7 output 0=Cancel;
SRGAPC1 SR(1) SR(1) CFG LD0.SRGAPC1.Rs7.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Reset Q7 Configuration\Generic logic\SRGAPC1
when set 1=Reset
Resets Q8 output 0=Cancel;
SRGAPC1 SR(1) SR(1) CFG LD0.SRGAPC1.Rs8.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Reset Q8 Configuration\Generic logic\SRGAPC1
when set 1=Reset
VisString255
SRGAPC1 SR(1) SR(1) VER LD0.SRGAPC1.NamPlt.swRev LPL DC ED1 B1 (Name plate)
(20)

TONGAPC1: B1
IEC Parameter Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Menu path
60617 name desc range relation
Monitoring\I/O status\Generic
TONGAPC1 TON(1) TON(1) INP LD0.TONGAPC1.Ind1.stVal SPS BOOLEAN ST B 0 I1 IN1 Input 1
timers\TONGAPC1\Inputs
Monitoring\I/O status\Generic
TONGAPC1 TON(1) TON(1) INP LD0.TONGAPC1.Ind2.stVal SPS BOOLEAN ST B 0 I1 IN2 Input 2
timers\TONGAPC1\Inputs
Monitoring\I/O status\Generic
TONGAPC1 TON(1) TON(1) INP LD0.TONGAPC1.Ind3.stVal SPS BOOLEAN ST B 0 I1 IN3 Input 3
timers\TONGAPC1\Inputs
Monitoring\I/O status\Generic
TONGAPC1 TON(1) TON(1) INP LD0.TONGAPC1.Ind4.stVal SPS BOOLEAN ST B 0 I1 IN4 Input 4
timers\TONGAPC1\Inputs
Monitoring\I/O status\Generic
TONGAPC1 TON(1) TON(1) INP LD0.TONGAPC1.Ind5.stVal SPS BOOLEAN ST B 0 I1 IN5 Input 5
timers\TONGAPC1\Inputs
Monitoring\I/O status\Generic
TONGAPC1 TON(1) TON(1) INP LD0.TONGAPC1.Ind6.stVal SPS BOOLEAN ST B 0 I1 IN6 Input 6
timers\TONGAPC1\Inputs
Monitoring\I/O status\Generic
TONGAPC1 TON(1) TON(1) INP LD0.TONGAPC1.Ind7.stVal SPS BOOLEAN ST B 0 I1 IN7 Input 7
timers\TONGAPC1\Inputs
Monitoring\I/O status\Generic
TONGAPC1 TON(1) TON(1) INP LD0.TONGAPC1.Ind8.stVal SPS BOOLEAN ST B 0 I1 IN8 Input 8
timers\TONGAPC1\Inputs
Monitoring\I/O status\Generic
TONGAPC1 TON(1) TON(1) OUT LD0.TONGAPC1.SPCSO1.stVal SPC BOOLEAN ST B I1 Q1 Output 1
timers\TONGAPC1\Outputs
Monitoring\I/O status\Generic
TONGAPC1 TON(1) TON(1) OUT LD0.TONGAPC1.SPCSO2.stVal SPC BOOLEAN ST B I1 Q2 Output 2
timers\TONGAPC1\Outputs
Monitoring\I/O status\Generic
TONGAPC1 TON(1) TON(1) OUT LD0.TONGAPC1.SPCSO3.stVal SPC BOOLEAN ST B I1 Q3 Output 3
timers\TONGAPC1\Outputs
Monitoring\I/O status\Generic
TONGAPC1 TON(1) TON(1) OUT LD0.TONGAPC1.SPCSO4.stVal SPC BOOLEAN ST B I1 Q4 Output 4
timers\TONGAPC1\Outputs
Monitoring\I/O status\Generic
TONGAPC1 TON(1) TON(1) OUT LD0.TONGAPC1.SPCSO5.stVal SPC BOOLEAN ST B I1 Q5 Output 5
timers\TONGAPC1\Outputs
Monitoring\I/O status\Generic
TONGAPC1 TON(1) TON(1) OUT LD0.TONGAPC1.SPCSO6.stVal SPC BOOLEAN ST B I1 Q6 Output 6
timers\TONGAPC1\Outputs

74
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Monitoring\I/O status\Generic
TONGAPC1 TON(1) TON(1) OUT LD0.TONGAPC1.SPCSO7.stVal SPC BOOLEAN ST B I1 Q7 Output 7
timers\TONGAPC1\Outputs
Monitoring\I/O status\Generic
TONGAPC1 TON(1) TON(1) OUT LD0.TONGAPC1.SPCSO8.stVal SPC BOOLEAN ST B I1 Q8 Output 8
timers\TONGAPC1\Outputs
On delay On delay 0...3600000
TONGAPC1 TON(1) TON(1) CFG LD0.TONGAPC1.OnDlTmms1.setVal ING INT32 SP B 0 Configuration\Generic timers\TONGAPC1
time 1 time ms
On delay On delay 0...3600000
TONGAPC1 TON(1) TON(1) CFG LD0.TONGAPC1.OnDlTmms2.setVal ING INT32 SP B 0 Configuration\Generic timers\TONGAPC1
time 2 time ms
On delay On delay 0...3600000
TONGAPC1 TON(1) TON(1) CFG LD0.TONGAPC1.OnDlTmms3.setVal ING INT32 SP B 0 Configuration\Generic timers\TONGAPC1
time 3 time ms
On delay On delay 0...3600000
TONGAPC1 TON(1) TON(1) CFG LD0.TONGAPC1.OnDlTmms4.setVal ING INT32 SP B 0 Configuration\Generic timers\TONGAPC1
time 4 time ms
On delay On delay 0...3600000
TONGAPC1 TON(1) TON(1) CFG LD0.TONGAPC1.OnDlTmms5.setVal ING INT32 SP B 0 Configuration\Generic timers\TONGAPC1
time 5 time ms
On delay On delay 0...3600000
TONGAPC1 TON(1) TON(1) CFG LD0.TONGAPC1.OnDlTmms6.setVal ING INT32 SP B 0 Configuration\Generic timers\TONGAPC1
time 6 time ms
On delay On delay 0...3600000
TONGAPC1 TON(1) TON(1) CFG LD0.TONGAPC1.OnDlTmms7.setVal ING INT32 SP B 0 Configuration\Generic timers\TONGAPC1
time 7 time ms
On delay On delay 0...3600000
TONGAPC1 TON(1) TON(1) CFG LD0.TONGAPC1.OnDlTmms8.setVal ING INT32 SP B 0 Configuration\Generic timers\TONGAPC1
time 8 time ms
VisString255 (Name
TONGAPC1 TON(1) TON(1) VER LD0.TONGAPC1.NamPlt.swRev LPL DC ED1 B1
(20) plate)

TOFGAPC1: B1
IEC Parameter Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Menu path
60617 name desc range relation
Input 1 Monitoring\I/O status\Generic
TOFGAPC1 TOF(1) TOF(1) INP LD0.TOFGAPC1.Ind1.stVal SPS BOOLEAN ST B 0 I1 IN1
status timers\TOFGAPC1\Inputs
Input 2 Monitoring\I/O status\Generic
TOFGAPC1 TOF(1) TOF(1) INP LD0.TOFGAPC1.Ind2.stVal SPS BOOLEAN ST B 0 I1 IN2
status timers\TOFGAPC1\Inputs
Input 3 Monitoring\I/O status\Generic
TOFGAPC1 TOF(1) TOF(1) INP LD0.TOFGAPC1.Ind3.stVal SPS BOOLEAN ST B 0 I1 IN3
status timers\TOFGAPC1\Inputs
Input 4 Monitoring\I/O status\Generic
TOFGAPC1 TOF(1) TOF(1) INP LD0.TOFGAPC1.Ind4.stVal SPS BOOLEAN ST B 0 I1 IN4
status timers\TOFGAPC1\Inputs
Input 5 Monitoring\I/O status\Generic
TOFGAPC1 TOF(1) TOF(1) INP LD0.TOFGAPC1.Ind5.stVal SPS BOOLEAN ST B 0 I1 IN5
status timers\TOFGAPC1\Inputs
Input 6 Monitoring\I/O status\Generic
TOFGAPC1 TOF(1) TOF(1) INP LD0.TOFGAPC1.Ind6.stVal SPS BOOLEAN ST B 0 I1 IN6
status timers\TOFGAPC1\Inputs
Input 7 Monitoring\I/O status\Generic
TOFGAPC1 TOF(1) TOF(1) INP LD0.TOFGAPC1.Ind7.stVal SPS BOOLEAN ST B 0 I1 IN7
status timers\TOFGAPC1\Inputs
Input 8 Monitoring\I/O status\Generic
TOFGAPC1 TOF(1) TOF(1) INP LD0.TOFGAPC1.Ind8.stVal SPS BOOLEAN ST B 0 I1 IN8
status timers\TOFGAPC1\Inputs
Output 1 Monitoring\I/O status\Generic
TOFGAPC1 TOF(1) TOF(1) OUT LD0.TOFGAPC1.SPCSO1.stVal SPC BOOLEAN ST B I1 Q1
status timers\TOFGAPC1\Outputs

75
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Output 2 Monitoring\I/O status\Generic


TOFGAPC1 TOF(1) TOF(1) OUT LD0.TOFGAPC1.SPCSO2.stVal SPC BOOLEAN ST B I1 Q2
status timers\TOFGAPC1\Outputs
Output 3 Monitoring\I/O status\Generic
TOFGAPC1 TOF(1) TOF(1) OUT LD0.TOFGAPC1.SPCSO3.stVal SPC BOOLEAN ST B I1 Q3
status timers\TOFGAPC1\Outputs
Output 4 Monitoring\I/O status\Generic
TOFGAPC1 TOF(1) TOF(1) OUT LD0.TOFGAPC1.SPCSO4.stVal SPC BOOLEAN ST B I1 Q4
status timers\TOFGAPC1\Outputs
Output 5 Monitoring\I/O status\Generic
TOFGAPC1 TOF(1) TOF(1) OUT LD0.TOFGAPC1.SPCSO5.stVal SPC BOOLEAN ST B I1 Q5
status timers\TOFGAPC1\Outputs
Output 6 Monitoring\I/O status\Generic
TOFGAPC1 TOF(1) TOF(1) OUT LD0.TOFGAPC1.SPCSO6.stVal SPC BOOLEAN ST B I1 Q6
status timers\TOFGAPC1\Outputs
Output 7 Monitoring\I/O status\Generic
TOFGAPC1 TOF(1) TOF(1) OUT LD0.TOFGAPC1.SPCSO7.stVal SPC BOOLEAN ST B I1 Q7
status timers\TOFGAPC1\Outputs
Output 8 Monitoring\I/O status\Generic
TOFGAPC1 TOF(1) TOF(1) OUT LD0.TOFGAPC1.SPCSO8.stVal SPC BOOLEAN ST B I1 Q8
status timers\TOFGAPC1\Outputs
Off delay Off delay 0...3600000
TOFGAPC1 TOF(1) TOF(1) CFG LD0.TOFGAPC1.OffDlTmms1.setVal ING INT32 SP B 0 Configuration\Generic timers\TOFGAPC1
time 1 time ms
Off delay Off delay 0...3600000
TOFGAPC1 TOF(1) TOF(1) CFG LD0.TOFGAPC1.OffDlTmms2.setVal ING INT32 SP B 0 Configuration\Generic timers\TOFGAPC1
time 2 time ms
Off delay Off delay 0...3600000
TOFGAPC1 TOF(1) TOF(1) CFG LD0.TOFGAPC1.OffDlTmms3.setVal ING INT32 SP B 0 Configuration\Generic timers\TOFGAPC1
time 3 time ms
Off delay Off delay 0...3600000
TOFGAPC1 TOF(1) TOF(1) CFG LD0.TOFGAPC1.OffDlTmms4.setVal ING INT32 SP B 0 Configuration\Generic timers\TOFGAPC1
time 4 time ms
Off delay Off delay 0...3600000
TOFGAPC1 TOF(1) TOF(1) CFG LD0.TOFGAPC1.OffDlTmms5.setVal ING INT32 SP B 0 Configuration\Generic timers\TOFGAPC1
time 5 time ms
Off delay Off delay 0...3600000
TOFGAPC1 TOF(1) TOF(1) CFG LD0.TOFGAPC1.OffDlTmms6.setVal ING INT32 SP B 0 Configuration\Generic timers\TOFGAPC1
time 6 time ms
Off delay Off delay 0...3600000
TOFGAPC1 TOF(1) TOF(1) CFG LD0.TOFGAPC1.OffDlTmms7.setVal ING INT32 SP B 0 Configuration\Generic timers\TOFGAPC1
time 7 time ms
Off delay Off delay 0...3600000
TOFGAPC1 TOF(1) TOF(1) CFG LD0.TOFGAPC1.OffDlTmms8.setVal ING INT32 SP B 0 Configuration\Generic timers\TOFGAPC1
time 8 time ms
VisString255 (Name
TOFGAPC1 TOF(1) TOF(1) VER LD0.TOFGAPC1.NamPlt.swRev LPL DC ED1 B1
(20) plate)

PTGAPC1: C1
IEC IEC Parameter Parameter Parameter Channel
ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Menu path
61850 60617 name desc range relation
Monitoring\I/O status\Generic
PTGAPC1 PT(1) PT(1) INP LD0.PTGAPC1.Ind1.stVal SPS BOOLEAN ST B 0 I1 IN1 Input 1 status
timers\PTGAPC1\Inputs
Monitoring\I/O status\Generic
PTGAPC1 PT(1) PT(1) INP LD0.PTGAPC1.Ind2.stVal SPS BOOLEAN ST B 0 I1 IN2 Input 2 status
timers\PTGAPC1\Inputs
Monitoring\I/O status\Generic
PTGAPC1 PT(1) PT(1) INP LD0.PTGAPC1.Ind3.stVal SPS BOOLEAN ST B 0 I1 IN3 Input 3 status
timers\PTGAPC1\Inputs
Monitoring\I/O status\Generic
PTGAPC1 PT(1) PT(1) INP LD0.PTGAPC1.Ind4.stVal SPS BOOLEAN ST B 0 I1 IN4 Input 4 status
timers\PTGAPC1\Inputs

76
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Monitoring\I/O status\Generic
PTGAPC1 PT(1) PT(1) INP LD0.PTGAPC1.Ind5.stVal SPS BOOLEAN ST B 0 I1 IN5 Input 5 status
timers\PTGAPC1\Inputs
Monitoring\I/O status\Generic
PTGAPC1 PT(1) PT(1) INP LD0.PTGAPC1.Ind6.stVal SPS BOOLEAN ST B 0 I1 IN6 Input 6 status
timers\PTGAPC1\Inputs
Monitoring\I/O status\Generic
PTGAPC1 PT(1) PT(1) INP LD0.PTGAPC1.Ind7.stVal SPS BOOLEAN ST B 0 I1 IN7 Input 7 status
timers\PTGAPC1\Inputs
Monitoring\I/O status\Generic
PTGAPC1 PT(1) PT(1) INP LD0.PTGAPC1.Ind8.stVal SPS BOOLEAN ST B 0 I1 IN8 Input 8 status
timers\PTGAPC1\Inputs
Output 1 Monitoring\I/O status\Generic
PTGAPC1 PT(1) PT(1) OUT LD0.PTGAPC1.SPCSO1.stVal SPC BOOLEAN ST B I1 Q1
status timers\PTGAPC1\Outputs
Output 2 Monitoring\I/O status\Generic
PTGAPC1 PT(1) PT(1) OUT LD0.PTGAPC1.SPCSO2.stVal SPC BOOLEAN ST B I1 Q2
status timers\PTGAPC1\Outputs
Output 3 Monitoring\I/O status\Generic
PTGAPC1 PT(1) PT(1) OUT LD0.PTGAPC1.SPCSO3.stVal SPC BOOLEAN ST B I1 Q3
status timers\PTGAPC1\Outputs
Output 4 Monitoring\I/O status\Generic
PTGAPC1 PT(1) PT(1) OUT LD0.PTGAPC1.SPCSO4.stVal SPC BOOLEAN ST B I1 Q4
status timers\PTGAPC1\Outputs
Output 5 Monitoring\I/O status\Generic
PTGAPC1 PT(1) PT(1) OUT LD0.PTGAPC1.SPCSO5.stVal SPC BOOLEAN ST B I1 Q5
status timers\PTGAPC1\Outputs
Output 6 Monitoring\I/O status\Generic
PTGAPC1 PT(1) PT(1) OUT LD0.PTGAPC1.SPCSO6.stVal SPC BOOLEAN ST B I1 Q6
status timers\PTGAPC1\Outputs
Output 7 Monitoring\I/O status\Generic
PTGAPC1 PT(1) PT(1) OUT LD0.PTGAPC1.SPCSO7.stVal SPC BOOLEAN ST B I1 Q7
status timers\PTGAPC1\Outputs
Output 8 Monitoring\I/O status\Generic
PTGAPC1 PT(1) PT(1) OUT LD0.PTGAPC1.SPCSO8.stVal SPC BOOLEAN ST B I1 Q8
status timers\PTGAPC1\Outputs
0...3600000
PTGAPC1 PT(1) PT(1) CFG LD0.PTGAPC1.PlsTmms1.setVal ING INT32 SP B 0 Pulse time 1 Pulse time Configuration\Generic timers\PTGAPC1
ms
0...3600000
PTGAPC1 PT(1) PT(1) CFG LD0.PTGAPC1.PlsTmms2.setVal ING INT32 SP B 0 Pulse time 2 Pulse time Configuration\Generic timers\PTGAPC1
ms
0...3600000
PTGAPC1 PT(1) PT(1) CFG LD0.PTGAPC1.PlsTmms3.setVal ING INT32 SP B 0 Pulse time 3 Pulse time Configuration\Generic timers\PTGAPC1
ms
0...3600000
PTGAPC1 PT(1) PT(1) CFG LD0.PTGAPC1.PlsTmms4.setVal ING INT32 SP B 0 Pulse time 4 Pulse time Configuration\Generic timers\PTGAPC1
ms
0...3600000
PTGAPC1 PT(1) PT(1) CFG LD0.PTGAPC1.PlsTmms5.setVal ING INT32 SP B 0 Pulse time 5 Pulse time Configuration\Generic timers\PTGAPC1
ms
0...3600000
PTGAPC1 PT(1) PT(1) CFG LD0.PTGAPC1.PlsTmms6.setVal ING INT32 SP B 0 Pulse time 6 Pulse time Configuration\Generic timers\PTGAPC1
ms
0...3600000
PTGAPC1 PT(1) PT(1) CFG LD0.PTGAPC1.PlsTmms7.setVal ING INT32 SP B 0 Pulse time 7 Pulse time Configuration\Generic timers\PTGAPC1
ms
0...3600000
PTGAPC1 PT(1) PT(1) CFG LD0.PTGAPC1.PlsTmms8.setVal ING INT32 SP B 0 Pulse time 8 Pulse time Configuration\Generic timers\PTGAPC1
ms
VisString255
PTGAPC1 PT(1) PT(1) VER LD0.PTGAPC1.NamPlt.swRev LPL DC ED1 C1 (Name plate)
(20)

SCA4GAPC1: B1

77
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

IEC Parameter Parameter Channel


IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
Analog input
Monitoring\I/O status\Generic
SCA4GAPC1 SCA4(1) SCA4(1) INP LD0.SCA4GAPC1.AnIn1.mag.f MV FLOAT32 MX B 0.0 I1 AI1_VALUE value of -10000.0...10000.0
logic\SCA4GAPC1\Inputs
channel 1
Analog input
Monitoring\I/O status\Generic
SCA4GAPC1 SCA4(1) SCA4(1) INP LD0.SCA4GAPC1.AnIn2.mag.f MV FLOAT32 MX B 0.0 I1 AI2_VALUE value of -10000.0...10000.0
logic\SCA4GAPC1\Inputs
channel 2
Analog input
Monitoring\I/O status\Generic
SCA4GAPC1 SCA4(1) SCA4(1) INP LD0.SCA4GAPC1.AnIn3.mag.f MV FLOAT32 MX B 0.0 I1 AI3_VALUE value of -10000.0...10000.0
logic\SCA4GAPC1\Inputs
channel 3
Analog input
Monitoring\I/O status\Generic
SCA4GAPC1 SCA4(1) SCA4(1) INP LD0.SCA4GAPC1.AnIn4.mag.f MV FLOAT32 MX B 0.0 I1 AI4_VALUE value of -10000.0...10000.0
logic\SCA4GAPC1\Inputs
channel 4
Analog
- Monitoring\I/O status\Generic
SCA4GAPC1 SCA4(1) SCA4(1) OUT LD0.SCA4GAPC1.AnValOut1.mag.f MV FLOAT32 MX B MeasFlt P I1 AO1_VALUE value 1 after
2000000.0...2000000.0 logic\SCA4GAPC1\Outputs
scaling
Analog
- Monitoring\I/O status\Generic
SCA4GAPC1 SCA4(1) SCA4(1) OUT LD0.SCA4GAPC1.AnValOut2.mag.f MV FLOAT32 MX B MeasFlt P I1 AO2_VALUE value 2 after
2000000.0...2000000.0 logic\SCA4GAPC1\Outputs
scaling
Analog
- Monitoring\I/O status\Generic
SCA4GAPC1 SCA4(1) SCA4(1) OUT LD0.SCA4GAPC1.AnValOut3.mag.f MV FLOAT32 MX B MeasFlt P I1 AO3_VALUE value 3 after
2000000.0...2000000.0 logic\SCA4GAPC1\Outputs
scaling
Analog
- Monitoring\I/O status\Generic
SCA4GAPC1 SCA4(1) SCA4(1) OUT LD0.SCA4GAPC1.AnValOut4.mag.f MV FLOAT32 MX B MeasFlt P I1 AO4_VALUE value 4 after
2000000.0...2000000.0 logic\SCA4GAPC1\Outputs
scaling
Scale ratio
Configuration\Generic
SCA4GAPC1 SCA4(1) SCA4(1) CFG LD0.SCA4GAPC1.ScaleAnIn1.setMag.f ASG FLOAT32 SP B 1.000 Scale ratio 1 for analog 0.001...1000.000
logic\SCA4GAPC1
value 1
Scale ratio
Configuration\Generic
SCA4GAPC1 SCA4(1) SCA4(1) CFG LD0.SCA4GAPC1.ScaleAnIn2.setMag.f ASG FLOAT32 SP B 1.000 Scale ratio 2 for analog 0.001...1000.000
logic\SCA4GAPC1
value 2
Scale ratio
Configuration\Generic
SCA4GAPC1 SCA4(1) SCA4(1) CFG LD0.SCA4GAPC1.ScaleAnIn3.setMag.f ASG FLOAT32 SP B 1.000 Scale ratio 3 for analog 0.001...1000.000
logic\SCA4GAPC1
value 3
Scale ratio
Configuration\Generic
SCA4GAPC1 SCA4(1) SCA4(1) CFG LD0.SCA4GAPC1.ScaleAnIn4.setMag.f ASG FLOAT32 SP B 1.000 Scale ratio 4 for analog 0.001...1000.000
logic\SCA4GAPC1
value 4
VisString255
SCA4GAPC1 SCA4(1) SCA4(1) VER LD0.SCA4GAPC1.NamPlt.swRev LPL DC ED1 B1 (Name plate)
(20)

MVI4GAPC1: B1
IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
Integer input - Monitoring\I/O status\Generic
MVI4GAPC1 MVI4(1) MVI4(1) INP LD0.MVI4GAPC1.IntIn1.stVal INS INT32 ST B 0 I1 IN1
value 1 2147483648...2147483647 logic\MVI4GAPC1\Inputs

78
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Integer input - Monitoring\I/O status\Generic


MVI4GAPC1 MVI4(1) MVI4(1) INP LD0.MVI4GAPC1.IntIn2.stVal INS INT32 ST B 0 I1 IN2
value 2 2147483648...2147483647 logic\MVI4GAPC1\Inputs
Integer input - Monitoring\I/O status\Generic
MVI4GAPC1 MVI4(1) MVI4(1) INP LD0.MVI4GAPC1.IntIn3.stVal INS INT32 ST B 0 I1 IN3
value 3 2147483648...2147483647 logic\MVI4GAPC1\Inputs
Integer input - Monitoring\I/O status\Generic
MVI4GAPC1 MVI4(1) MVI4(1) INP LD0.MVI4GAPC1.IntIn4.stVal INS INT32 ST B 0 I1 IN4
value 4 2147483648...2147483647 logic\MVI4GAPC1\Inputs
Integer
- Monitoring\I/O status\Generic
MVI4GAPC1 MVI4(1) MVI4(1) OUT LD0.MVI4GAPC1.ISCSO1.stVal INC INT32 ST B MeasFlt P I1 OUT1 output value
2147483648...2147483647 logic\MVI4GAPC1\Outputs
1
Integer
- Monitoring\I/O status\Generic
MVI4GAPC1 MVI4(1) MVI4(1) OUT LD0.MVI4GAPC1.ISCSO2.stVal INC INT32 ST B MeasFlt P I1 OUT2 output value
2147483648...2147483647 logic\MVI4GAPC1\Outputs
2
Integer
- Monitoring\I/O status\Generic
MVI4GAPC1 MVI4(1) MVI4(1) OUT LD0.MVI4GAPC1.ISCSO3.stVal INC INT32 ST B MeasFlt P I1 OUT3 output value
2147483648...2147483647 logic\MVI4GAPC1\Outputs
3
Integer
- Monitoring\I/O status\Generic
MVI4GAPC1 MVI4(1) MVI4(1) OUT LD0.MVI4GAPC1.ISCSO4.stVal INC INT32 ST B MeasFlt P I1 OUT4 output value
2147483648...2147483647 logic\MVI4GAPC1\Outputs
4
VisString255
MVI4GAPC1 MVI4(1) MVI4(1) VER LD0.MVI4GAPC1.NamPlt.swRev LPL DC ED1 B1 (Name plate)
(20)

Global conditioning: G2
IEC Parameter Parameter Menu Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range
60617 name desc path relation
Global
INP LD0.LEDPTRC1.InRs.stVal SPS BOOLEAN ST 0 I1 (Reset)
conditioning
Global (Input
INP LD0.LEDPTRC1.InOp.stVal SPS BOOLEAN ST 0 I1
conditioning operate)
Global
INP LD0.LEDPTRC1.InStr.stVal SPS BOOLEAN ST 0 I1 (Input start)
conditioning
Global
OUT LD0.LEDPTRC1.Op.general ACT BOOLEAN ST StatIed P,H I1 (Operate)
conditioning
Global
OUT LD0.LEDPTRC1.Str.general ACD BOOLEAN ST StatIed P,H I1 (Start)
conditioning
Global
MON LD0.LEDPTRC1.Str.dirGeneral ACD Enum ST StatIed P,H (Start) 0=unknown1=forward2=backward3=both
conditioning
Global VisString255
VER LD0.LEDPTRC1.NamPlt.swRev LPL DC ED1 G2 (Name plate)
conditioning (20)

TPGAPC1: C1
IEC IEC Parameter Parameter Channel
ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Menu path
61850 60617 name range relation
Monitoring\I/O status\Generic
TPGAPC1 TP(1) TP(1) INP LD0.TPGAPC1.Ind1.stVal SPS BOOLEAN ST B 0 I1 IN1 Input 1
timers\TPGAPC1\Inputs
79
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Monitoring\I/O status\Generic
TPGAPC1 TP(1) TP(1) INP LD0.TPGAPC1.Ind2.stVal SPS BOOLEAN ST B 0 I1 IN2 Input 2
timers\TPGAPC1\Inputs
Monitoring\I/O status\Generic
TPGAPC1 TP(1) TP(1) OUT LD0.TPGAPC1.SPCSO1.stVal SPC BOOLEAN ST B I1 OUT1 Output 1 status
timers\TPGAPC1\Outputs
Monitoring\I/O status\Generic
TPGAPC1 TP(1) TP(1) OUT LD0.TPGAPC1.SPCSO2.stVal SPC BOOLEAN ST B I1 OUT2 Output 2 status
timers\TPGAPC1\Outputs
Minimum pulse
TPGAPC1 TP(1) TP(1) CFG LD0.TPGAPC1.PlsTmms.setVal ING INT32 SP B 150 Pulse time 0...60000 ms Configuration\Generic timers\TPGAPC1
time
VisString255
TPGAPC1 TP(1) TP(1) VER LD0.TPGAPC1.NamPlt.swRev LPL DC ED1 C1 (Name plate)
(20)

TPSGAPC1: C1
IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Menu path
60617 name range relation
Monitoring\I/O status\Generic
TPSGAPC1 TPS(1) TPS(1) INP LD0.TPSGAPC1.Ind1.stVal SPS BOOLEAN ST B 0 I1 IN1 Input 1
timers\TPSGAPC1\Inputs
Monitoring\I/O status\Generic
TPSGAPC1 TPS(1) TPS(1) INP LD0.TPSGAPC1.Ind2.stVal SPS BOOLEAN ST B 0 I1 IN2 Input 2
timers\TPSGAPC1\Inputs
Monitoring\I/O status\Generic
TPSGAPC1 TPS(1) TPS(1) OUT LD0.TPSGAPC1.SPCSO1.stVal SPC BOOLEAN ST B I1 OUT1 Output 1 status
timers\TPSGAPC1\Outputs
Monitoring\I/O status\Generic
TPSGAPC1 TPS(1) TPS(1) OUT LD0.TPSGAPC1.SPCSO2.stVal SPC BOOLEAN ST B I1 OUT2 Output 2 status
timers\TPSGAPC1\Outputs
Minimum pulse
TPSGAPC1 TPS(1) TPS(1) CFG LD0.TPSGAPC1.PlsTms.setVal ING INT32 SP B 0 Pulse time 0...300 s Configuration\Generic timers\TPSGAPC1
time
VisString255
TPSGAPC1 TPS(1) TPS(1) VER LD0.TPSGAPC1.NamPlt.swRev LPL DC ED1 C1 (Name plate)
(20)

TPMGAPC1: C1
IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Menu path
60617 name range relation
Monitoring\I/O status\Generic
TPMGAPC1 TPM(1) TPM(1) INP LD0.TPMGAPC1.Ind1.stVal SPS BOOLEAN ST B 0 I1 IN1 Input 1
timers\TPMGAPC1\Inputs
Monitoring\I/O status\Generic
TPMGAPC1 TPM(1) TPM(1) INP LD0.TPMGAPC1.Ind2.stVal SPS BOOLEAN ST B 0 I1 IN2 Input 2
timers\TPMGAPC1\Inputs
Monitoring\I/O status\Generic
TPMGAPC1 TPM(1) TPM(1) OUT LD0.TPMGAPC1.SPCSO1.stVal SPC BOOLEAN ST B I1 OUT1 Output 1 status
timers\TPMGAPC1\Outputs
Monitoring\I/O status\Generic
TPMGAPC1 TPM(1) TPM(1) OUT LD0.TPMGAPC1.SPCSO2.stVal SPC BOOLEAN ST B I1 OUT2 Output 2 status
timers\TPMGAPC1\Outputs
Minimum pulse
TPMGAPC1 TPM(1) TPM(1) CFG LD0.TPMGAPC1.PlsTmm.setVal ING INT32 SP B 0 Pulse time 0...300 min Configuration\Generic timers\TPMGAPC1
time
VisString255
TPMGAPC1 TPM(1) TPM(1) VER LD0.TPMGAPC1.NamPlt.swRev LPL DC ED1 C1 (Name plate)
(20)

80
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

FLTRFRC1: Fault record: H3


IEC Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Parameter range Menu path
60617 name relation
(Block signal
FLTRFRC1 FaultRec1 FaultRec1 INP LD0.FLTRFRC1.Blk.stVal SPS BOOLEAN ST 0 I1 for all binary
outputs)
(Operate input
FLTRFRC1 FaultRec1 FaultRec1 INP LD0.FLTRFRC1.InOp.stVal SPS BOOLEAN ST 0 I1
for triggering)
(Start input for
FLTRFRC1 FaultRec1 FaultRec1 INP LD0.FLTRFRC1.InStr.stVal SPS BOOLEAN ST 0 I1
triggering)
(Breaker open
FLTRFRC1 FaultRec1 FaultRec1 INP LD0.FLTRFRC1.InCBClr.stVal SPS BOOLEAN ST 0 I1
status)
Reset fault
FLTRFRC1 FaultRec1 FaultRec1 CTR LD0.FLTRFRC1.RcdRs.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Fault records 0=Cancel; 1=Clear Clear\Clear
records
(Select
FLTRFRC1 FaultRec1 FaultRec1 CTR LD0.FLTRFRC1.SelRow.Oper.ctlVal INC INT32 CO
recording)
Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.Hz.mag.f MV FLOAT32 MX B MeasReg P I1 Frequency Frequency 30.00...80.00 Hz
data\Fault record
Distance to
Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.FltDiskm.mag.f MV FLOAT32 MX B MeasReg P I1 Fault distance fault measured 0.00...3000.00 pu
data\Fault record
in pu
Fault record Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.OpCnt.stVal INS INT32 ST B MeasReg P I1 Fault number 0...999999
number data\Fault record
Time and Fault record Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.OpCnt.t INS Timestamp ST B MeasReg P
date time stamp data\Fault record
0=Unknown;
1=PHLPTOC;
6=PHHPTOC;
12=PHIPTOC;
17=EFLPTOC;
22=EFHPTOC;
30=EFIPTOC;
35=NSPTOC; -
7=INTRPTEF; -
5=STTPMSU; -
3=JAMPTOC;
Protection Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.ProFcn.stVal ENS Enum ST B MeasReg P I1 Protection 41=PDNSPTOC;
function data\Fault record
44=T1PTTR;
46=T2PTTR; 48=MPTTR;
50=DEFLPDEF;
53=DEFHPDEF;
56=EFPADM;
59=FRPFRQ;
65=LSHDPFRQ;
71=DPHLPDOC;
74=DPHHPDOC;
77=MAPGAPC;
85=MNSPTOC;
81
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

88=LOFLPTUC;
90=TR2PTDF;
91=LNPLDF;
92=LREFPNDF;
94=MPDIF;
96=HREFPDIF;
100=ROVPTOV;
104=PHPTOV;
108=PHPTUV;
112=NSPTOV;
116=PSPTUV;
118=ARCSARC; -
96=SPHIPTOC; -
93=SPHLPTOC; -
92=SPHLPTOC; -
89=SPHHPTOC; -
88=SPHHPTOC; -
87=SPHPTUV; -
86=SPHPTUV; -
85=SPHPTUV; -
84=SPHPTUV; -
83=SPHPTOV; -
82=SPHPTOV; -
81=SPHPTOV; -
80=SPHPTOV; -
25=OEPVPH; -
24=OEPVPH; -
23=OEPVPH; -
22=OEPVPH; -
19=PSPTOV; -
18=PSPTOV; -
15=PREVPTOC; -
12=PHPTUC; -
11=PHPTUC; -9=PHIZ;
5=PHLTPTOC; -
13=PHPTUC; -
30=PHDSTPDIS; -
29=TR3PTDF; -
28=HICPDIF; -
27=HIBPDIF; -
26=HIAPDIF; -
98=RESCPSCH; -
57=FDEFLPDEF; -
56=FDEFLPDEF; -
54=FEFLPTOC; -
53=FDPHLPDOC; -
52=FDPHLPDOC; -
50=FPHLPTOC; -
47=MAP12GAPC; -
46=MAP12GAPC; -
45=MAP12GAPC; -
44=MAP12GAPC; -
43=MAP12GAPC; -
42=MAP12GAPC; -
82
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

41=MAP12GAPC; -
40=MAP12GAPC; -
37=HAEFPTOC; -
33=WPWDE;
97=HREFPDIF; -
117=XDEFLPDEF; -
116=XDEFLPDEF; -
115=SDPHLPDOC; -
114=SDPHLPDOC; -
113=XNSPTOC; -
112=XNSPTOC; -
111=XEFIPTOC; -
110=XEFHPTOC; -
109=XEFHPTOC; -
108=XEFLPTOC; -
107=XEFLPTOC; -
66=DQPTUV; -
65=VVSPPAM; -
64=PHPVOC; -
63=H3EFPSEF; -
60=HCUBPTOC; -
59=CUBPTOC; -
72=DOPPDPR; -
69=DUPPDPR; -
61=COLPTOC; -
62=SRCPTOC; -
70=DUPPDPR; -
58=UZPDIS; -
36=UEXPDIS;
14=MFADPSDE; -
10=LVRTPTUV; -
122=DPH3LPDOC; -
121=DPH3HPDOC; -
120=DPH3HPDOC; -
119=PH3LPTOC; -
118=PH3LPTOC; -
79=PH3HPTOC; -
78=PH3HPTOC; -
77=PH3IPTOC; -
127=PHAPTUV; -
124=PHAPTOV; -
123=DPH3LPDOC; -
68=PHPVOC; -
39=UEXPDIS;
98=MHZPDIF; -
4=MREFPTOC; -
38=DSTPDIS;
121=ANOGAPC;
122=BBPBDF
Protection
Protection Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.ProFcnInst.stVal INS INT32 ST B MeasReg P I1 function 1...999999
instance data\Fault record
instance

83
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Maximum start
duration of all Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.StrDur.mag.f MV FLOAT32 MX B MeasReg P I1 Start duration 0.00...100.00 %
stages during data\Fault record
the fault
Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.StrOpTm.mag.f MV FLOAT32 MX B MeasReg P I1 Operate time Operate time 0.000...999999.999 s
data\Fault record
Active setting Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.ActSetGr.stVal INC INT32 ST B MeasReg P I1 Active group 1...6
group data\Fault record
Maximum
Max diff phase A Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.Max50DifAA.mag.f MV FLOAT32 MX B MeasReg P I1 0.000...80.000 pu
current IL1 differential data\Fault record
current
Maximum
Max diff phase B Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.Max50DifAB.mag.f MV FLOAT32 MX B MeasReg P I1 0.000...80.000 pu
current IL2 differential data\Fault record
current
Maximum
Max diff phase C Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.Max50DifAC.mag.f MV FLOAT32 MX B MeasReg P I1 0.000...80.000 pu
current IL3 differential data\Fault record
current
Maximum
Max bias Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.Max50RstAA.mag.f MV FLOAT32 MX B MeasReg P I1 phase A bias 0.000...50.000 pu
current IL1 data\Fault record
current
Maximum
Max bias Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.Max50RstAB.mag.f MV FLOAT32 MX B MeasReg P I1 phase B bias 0.000...50.000 pu
current IL2 data\Fault record
current
Maximum
Max bias Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.Max50RstAC.mag.f MV FLOAT32 MX B MeasReg P I1 phase C bias 0.000...50.000 pu
current IL3 data\Fault record
current
Differential
Diff current Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.DifAPhsA.mag.f MV FLOAT32 MX B MeasReg P I1 current phase 0.000...80.000 pu
IL1 data\Fault record
A
Differential
Diff current Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.DifAPhsB.mag.f MV FLOAT32 MX B MeasReg P I1 current phase 0.000...80.000 pu
IL2 data\Fault record
B
Differential
Diff current Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.DifAPhsC.mag.f MV FLOAT32 MX B MeasReg P I1 current phase 0.000...80.000 pu
IL3 data\Fault record
C
Bias current Bias current Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.RstAPhsA.mag.f MV FLOAT32 MX B MeasReg P I1 0.000...50.000 pu
IL1 phase A data\Fault record
Bias current Bias current Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.RstAPhsB.mag.f MV FLOAT32 MX B MeasReg P I1 0.000...50.000 pu
IL2 phase B data\Fault record
Bias current Bias current Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.RstAPhsC.mag.f MV FLOAT32 MX B MeasReg P I1 0.000...50.000 pu
IL3 phase C data\Fault record
Differential
Diff current Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.DifARes.mag.f MV FLOAT32 MX B MeasReg P I1 current 0.000...80.000 pu
Io data\Fault record
residual
Bias current Bias current Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.RstARes.mag.f MV FLOAT32 MX B MeasReg P I1 0.000...50.000 pu
Io residual data\Fault record
84
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Maximum
Max current Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.Max50APhsA1.mag.f MV FLOAT32 MX ED2,B MeasReg P I1 phase A 0.000...50.000 xIn IL1TCTR1
IL1 data\Fault record
current
Maximum
Max current Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.Max50APhA1.mag.f MV FLOAT32 MX ED1 MeasReg P I1 phase A 0.000...50.000 xIn IL1TCTR1
IL1 data\Fault record
current
Maximum
Max current Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.Max50APhsB1.mag.f MV FLOAT32 MX ED2,B MeasReg P I1 phase B 0.000...50.000 xIn IL1TCTR1
IL2 data\Fault record
current
Maximum
Max current Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.Max50APhB1.mag.f MV FLOAT32 MX ED1 MeasReg P I1 phase B 0.000...50.000 xIn IL1TCTR1
IL2 data\Fault record
current
Maximum
Max current Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.Max50APhsC1.mag.f MV FLOAT32 MX ED2,B MeasReg P I1 phase C 0.000...50.000 xIn IL1TCTR1
IL3 data\Fault record
current
Maximum
Max current Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.Max50APhC1.mag.f MV FLOAT32 MX ED1 MeasReg P I1 phase C 0.000...50.000 xIn IL1TCTR1
IL3 data\Fault record
current
Maximum
Max current Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.Max50ARes1.mag.f MV FLOAT32 MX B MeasReg P I1 residual 0.000...50.000 xIn RESTCTR1
Io data\Fault record
current
Phase A Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.APhsA1.mag.f MV FLOAT32 MX B MeasReg P I1 Current IL1 0.000...50.000 xIn IL1TCTR1
current data\Fault record
Phase B Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.APhsB1.mag.f MV FLOAT32 MX B MeasReg P I1 Current IL2 0.000...50.000 xIn IL1TCTR1
current data\Fault record
Phase C Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.APhsC1.mag.f MV FLOAT32 MX B MeasReg P I1 Current IL3 0.000...50.000 xIn IL1TCTR1
current data\Fault record
Residual Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.ARes1.mag.f MV FLOAT32 MX B MeasReg P I1 Current Io 0.000...50.000 xIn RESTCTR1
current data\Fault record
Calculated
Current Io- Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.AResClc1.mag.f MV FLOAT32 MX B MeasReg P I1 residual 0.000...50.000 xIn IL1TCTR1
Calc data\Fault record
current
Positive
Current Ps- Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.APsSeq1.mag.f MV FLOAT32 MX B MeasReg P I1 sequence 0.000...50.000 xIn IL1TCTR1
Seq data\Fault record
current
Negative
Current Ng- Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.ANgSeq1.mag.f MV FLOAT32 MX B MeasReg P I1 sequence 0.000...50.000 xIn IL1TCTR1
Seq data\Fault record
current
Phase A to
Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.PPVPhsAB1.mag.f MV FLOAT32 MX B MeasReg P I1 Voltage U12 phase B 0.000...4.000 xUn UL1TVTR1
data\Fault record
voltage
Phase B to
Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.PPVPhsBC1.mag.f MV FLOAT32 MX B MeasReg P I1 Voltage U23 phase C 0.000...4.000 xUn UL1TVTR1
data\Fault record
voltage
Phase C to
Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.PPVPhsCA1.mag.f MV FLOAT32 MX B MeasReg P I1 Voltage U31 phase A 0.000...4.000 xUn UL1TVTR1
data\Fault record
voltage

85
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Residual Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.VRes1.mag.f MV FLOAT32 MX B MeasReg P I1 Voltage Uo 0.000...4.000 xUn RESTVTR1
voltage data\Fault record
Voltage Zro- Zero sequence Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.VZro1.mag.f MV FLOAT32 MX B MeasReg P I1 0.000...4.000 xUn UL1TVTR1
Seq voltage data\Fault record
Positive
Voltage Ps- Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.VPsSeq1.mag.f MV FLOAT32 MX B MeasReg P I1 sequence 0.000...4.000 xUn UL1TVTR1
Seq data\Fault record
voltage
Negative
Voltage Ng- Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.VNgSeq1.mag.f MV FLOAT32 MX B MeasReg P I1 sequence 0.000...4.000 xUn UL1TVTR1
Seq data\Fault record
voltage
PTTR
calculated
temperature of
PTTR Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.MaxTmpRl.mag.f MV FLOAT32 MX B MeasReg P I1 the protected 0.00...99.99
thermal level data\Fault record
object relative
to the operate
level
PDNSPTOC1 PDNSPTOC1 Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.AMaxNgPs.mag.f MV FLOAT32 MX B MeasReg P I1 0.00...999.99 %
rat. I2/I1 ratio I2/I1 data\Fault record
Angle residual
voltage - Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.DifANAngVN1.mag.f MV FLOAT32 MX ED2,B MeasReg P I1 Angle Uo - Io -180.00...180.00 deg
residual data\Fault record
current
Angle residual
voltage - Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.DifNAngVN1.mag.f MV FLOAT32 MX ED1 MeasReg P I1 Angle Uo - Io -180.00...180.00 deg
residual data\Fault record
current
Angle phase B
Angle U23 - to phase C Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.DifAAAngVBC1.mag.f MV FLOAT32 MX ED2,B MeasReg P I1 -180.00...180.00 deg
IL1 voltage - phase data\Fault record
A current
Angle phase B
Angle U23 - to phase C Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.DifAAngBC1.mag.f MV FLOAT32 MX ED1 MeasReg P I1 -180.00...180.00 deg
IL1 voltage - phase data\Fault record
A current
Angle phase C
Angle U31 - to phase A Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.DifABAngVCA1.mag.f MV FLOAT32 MX ED2,B MeasReg P I1 -180.00...180.00 deg
IL2 voltage - phase data\Fault record
B current
Angle phase C
Angle U31 - to phase A Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.DifBAngCA1.mag.f MV FLOAT32 MX ED1 MeasReg P I1 -180.00...180.00 deg
IL2 voltage - phase data\Fault record
B current
Angle phase A
Angle U12 - to phase B Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.DifACAngVAB1.mag.f MV FLOAT32 MX ED2,B MeasReg P I1 -180.00...180.00 deg
IL3 voltage - phase data\Fault record
C current
Angle U12 - Angle phase A Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.DifCAngAB1.mag.f MV FLOAT32 MX ED1 MeasReg P I1 -180.00...180.00 deg
IL3 to phase B data\Fault record

86
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

voltage - phase
C current
Frequency Frequency Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.HzRteChg.mag.f MV FLOAT32 MX B MeasReg P I1 -10.00...10.00 Hz/s
gradient gradient data\Fault record
Breaker clear Breaker clear Monitoring\Recorded
FLTRFRC1 FaultRec1 FaultRec1 MON LD0.FLTRFRC1.CBClrTm.mag.f MV FLOAT32 MX B MeasReg P I1 0.000...3.000 s
time time data\Fault record
Operation Off / Configuration\Fault
FLTRFRC1 FaultRec1 FaultRec1 CFG LD0.FLTRFRC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
On record
Triggering 0=From all faults; 1=From Configuration\Fault
FLTRFRC1 FaultRec1 FaultRec1 CFG LD0.FLTRFRC1.TrgSet.setVal ENG Enum SP B 0 Trig mode
mode operate; 2=From only start record
Selects used
measurement
A
mode phase 1=RMS; 2=DFT; 3=Peak- Configuration\Fault
FLTRFRC1 FaultRec1 FaultRec1 CFG LD0.FLTRFRC1.AMeasMod.setVal ENG Enum SP A 2 measurement
currents and to-Peak record
mode
residual
current
VisString255
FLTRFRC1 FaultRec1 FaultRec1 VER LD0.FLTRFRC1.NamPlt.swRev LPL DC H3 (Name plate)
(20)

SPCGAPC1: D1
IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
Block signal
for Monitoring\I/O
SPCGAPC1 SPC(1) SPC(1) INP LD0.SPCGAPC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK activating status\Generic
the blocking logic\SPCGAPC1\Inputs
mode
Input of Monitoring\I/O
SPCGAPC1 SPC(1) SPC(1) INP LD0.SPCGAPC1.Ind1.stVal SPS BOOLEAN ST B 0 IN1 control point status\Generic
1 logic\SPCGAPC1\Inputs
Input of Monitoring\I/O
SPCGAPC1 SPC(1) SPC(1) INP LD0.SPCGAPC1.Ind2.stVal SPS BOOLEAN ST B 0 IN2 control point status\Generic
2 logic\SPCGAPC1\Inputs
Input of Monitoring\I/O
SPCGAPC1 SPC(1) SPC(1) INP LD0.SPCGAPC1.Ind3.stVal SPS BOOLEAN ST B 0 IN3 control point status\Generic
3 logic\SPCGAPC1\Inputs
Input of Monitoring\I/O
SPCGAPC1 SPC(1) SPC(1) INP LD0.SPCGAPC1.Ind4.stVal SPS BOOLEAN ST B 0 IN4 control point status\Generic
4 logic\SPCGAPC1\Inputs
Input of Monitoring\I/O
SPCGAPC1 SPC(1) SPC(1) INP LD0.SPCGAPC1.Ind5.stVal SPS BOOLEAN ST B 0 IN5 control point status\Generic
5 logic\SPCGAPC1\Inputs
Input of Monitoring\I/O
SPCGAPC1 SPC(1) SPC(1) INP LD0.SPCGAPC1.Ind6.stVal SPS BOOLEAN ST B 0 IN6 control point status\Generic
6 logic\SPCGAPC1\Inputs

87
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Input of Monitoring\I/O
SPCGAPC1 SPC(1) SPC(1) INP LD0.SPCGAPC1.Ind7.stVal SPS BOOLEAN ST B 0 IN7 control point status\Generic
7 logic\SPCGAPC1\Inputs
Input of Monitoring\I/O
SPCGAPC1 SPC(1) SPC(1) INP LD0.SPCGAPC1.Ind8.stVal SPS BOOLEAN ST B 0 IN8 control point status\Generic
8 logic\SPCGAPC1\Inputs
Input of Monitoring\I/O
SPCGAPC1 SPC(1) SPC(1) INP LD0.SPCGAPC1.Ind9.stVal SPS BOOLEAN ST B 0 IN9 control point status\Generic
9 logic\SPCGAPC1\Inputs
Input of Monitoring\I/O
SPCGAPC1 SPC(1) SPC(1) INP LD0.SPCGAPC1.Ind10.stVal SPS BOOLEAN ST B 0 IN10 control point status\Generic
10 logic\SPCGAPC1\Inputs
Input of Monitoring\I/O
SPCGAPC1 SPC(1) SPC(1) INP LD0.SPCGAPC1.Ind11.stVal SPS BOOLEAN ST B 0 IN11 control point status\Generic
11 logic\SPCGAPC1\Inputs
Input of Monitoring\I/O
SPCGAPC1 SPC(1) SPC(1) INP LD0.SPCGAPC1.Ind12.stVal SPS BOOLEAN ST B 0 IN12 control point status\Generic
12 logic\SPCGAPC1\Inputs
Input of Monitoring\I/O
SPCGAPC1 SPC(1) SPC(1) INP LD0.SPCGAPC1.Ind13.stVal SPS BOOLEAN ST B 0 IN13 control point status\Generic
13 logic\SPCGAPC1\Inputs
Input of Monitoring\I/O
SPCGAPC1 SPC(1) SPC(1) INP LD0.SPCGAPC1.Ind14.stVal SPS BOOLEAN ST B 0 IN14 control point status\Generic
14 logic\SPCGAPC1\Inputs
Input of Monitoring\I/O
SPCGAPC1 SPC(1) SPC(1) INP LD0.SPCGAPC1.Ind15.stVal SPS BOOLEAN ST B 0 IN15 control point status\Generic
15 logic\SPCGAPC1\Inputs
Input of Monitoring\I/O
SPCGAPC1 SPC(1) SPC(1) INP LD0.SPCGAPC1.Ind16.stVal SPS BOOLEAN ST B 0 IN16 control point status\Generic
16 logic\SPCGAPC1\Inputs
Monitoring\I/O
Output 1
SPCGAPC1 SPC(1) SPC(1) OUT LD0.SPCGAPC1.SPCSO1.stVal SPC BOOLEAN ST B StatUrg P,H I1 O1 status\Generic
status
logic\SPCGAPC1\Outputs
Monitoring\I/O
Output 2
SPCGAPC1 SPC(1) SPC(1) OUT LD0.SPCGAPC1.SPCSO2.stVal SPC BOOLEAN ST B StatUrg P,H I1 O2 status\Generic
status
logic\SPCGAPC1\Outputs
Monitoring\I/O
Output 3
SPCGAPC1 SPC(1) SPC(1) OUT LD0.SPCGAPC1.SPCSO3.stVal SPC BOOLEAN ST B StatUrg P,H I1 O3 status\Generic
status
logic\SPCGAPC1\Outputs
Monitoring\I/O
Output 4
SPCGAPC1 SPC(1) SPC(1) OUT LD0.SPCGAPC1.SPCSO4.stVal SPC BOOLEAN ST B StatUrg P,H I1 O4 status\Generic
status
logic\SPCGAPC1\Outputs
Monitoring\I/O
Output 5
SPCGAPC1 SPC(1) SPC(1) OUT LD0.SPCGAPC1.SPCSO5.stVal SPC BOOLEAN ST B StatUrg P,H I1 O5 status\Generic
status
logic\SPCGAPC1\Outputs
Monitoring\I/O
Output 6
SPCGAPC1 SPC(1) SPC(1) OUT LD0.SPCGAPC1.SPCSO6.stVal SPC BOOLEAN ST B StatUrg P,H I1 O6 status\Generic
status
logic\SPCGAPC1\Outputs

88
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Monitoring\I/O
Output 7
SPCGAPC1 SPC(1) SPC(1) OUT LD0.SPCGAPC1.SPCSO7.stVal SPC BOOLEAN ST B StatUrg P,H I1 O7 status\Generic
status
logic\SPCGAPC1\Outputs
Monitoring\I/O
Output 8
SPCGAPC1 SPC(1) SPC(1) OUT LD0.SPCGAPC1.SPCSO8.stVal SPC BOOLEAN ST B StatUrg P,H I1 O8 status\Generic
status
logic\SPCGAPC1\Outputs
Monitoring\I/O
Output 9
SPCGAPC1 SPC(1) SPC(1) OUT LD0.SPCGAPC1.SPCSO9.stVal SPC BOOLEAN ST B StatUrg P,H I1 O9 status\Generic
status
logic\SPCGAPC1\Outputs
Monitoring\I/O
Output 10
SPCGAPC1 SPC(1) SPC(1) OUT LD0.SPCGAPC1.SPCSO10.stVal SPC BOOLEAN ST B StatUrg P,H I1 O10 status\Generic
status
logic\SPCGAPC1\Outputs
Monitoring\I/O
Output 11
SPCGAPC1 SPC(1) SPC(1) OUT LD0.SPCGAPC1.SPCSO11.stVal SPC BOOLEAN ST B StatUrg P,H I1 O11 status\Generic
status
logic\SPCGAPC1\Outputs
Monitoring\I/O
Output 12
SPCGAPC1 SPC(1) SPC(1) OUT LD0.SPCGAPC1.SPCSO12.stVal SPC BOOLEAN ST B StatUrg P,H I1 O12 status\Generic
status
logic\SPCGAPC1\Outputs
Monitoring\I/O
Output 13
SPCGAPC1 SPC(1) SPC(1) OUT LD0.SPCGAPC1.SPCSO13.stVal SPC BOOLEAN ST B StatUrg P,H I1 O13 status\Generic
status
logic\SPCGAPC1\Outputs
Monitoring\I/O
Output 14
SPCGAPC1 SPC(1) SPC(1) OUT LD0.SPCGAPC1.SPCSO14.stVal SPC BOOLEAN ST B StatUrg P,H I1 O14 status\Generic
status
logic\SPCGAPC1\Outputs
Monitoring\I/O
Output 15
SPCGAPC1 SPC(1) SPC(1) OUT LD0.SPCGAPC1.SPCSO15.stVal SPC BOOLEAN ST B StatUrg P,H I1 O15 status\Generic
status
logic\SPCGAPC1\Outputs
Monitoring\I/O
Output 16
SPCGAPC1 SPC(1) SPC(1) OUT LD0.SPCGAPC1.SPCSO16.stVal SPC BOOLEAN ST B StatUrg P,H I1 O16 status\Generic
status
logic\SPCGAPC1\Outputs
Trig output
SPCGAPC1 SPC(1) SPC(1) CTR LD0.SPCGAPC1.SPCSO1.Oper.ctlVal SPC BOOLEAN CO B 0 I1 TRIG 1 Control\SPCGAPC1
1
Trig output
SPCGAPC1 SPC(1) SPC(1) CTR LD0.SPCGAPC1.SPCSO2.Oper.ctlVal SPC BOOLEAN CO B 0 I1 TRIG 2 Control\SPCGAPC1
2
Trig output
SPCGAPC1 SPC(1) SPC(1) CTR LD0.SPCGAPC1.SPCSO3.Oper.ctlVal SPC BOOLEAN CO B 0 I1 TRIG 3 Control\SPCGAPC1
3
Trig output
SPCGAPC1 SPC(1) SPC(1) CTR LD0.SPCGAPC1.SPCSO4.Oper.ctlVal SPC BOOLEAN CO B 0 I1 TRIG 4 Control\SPCGAPC1
4
Trig output
SPCGAPC1 SPC(1) SPC(1) CTR LD0.SPCGAPC1.SPCSO5.Oper.ctlVal SPC BOOLEAN CO B 0 I1 TRIG 5 Control\SPCGAPC1
5
Trig output
SPCGAPC1 SPC(1) SPC(1) CTR LD0.SPCGAPC1.SPCSO6.Oper.ctlVal SPC BOOLEAN CO B 0 I1 TRIG 6 Control\SPCGAPC1
6
Trig output
SPCGAPC1 SPC(1) SPC(1) CTR LD0.SPCGAPC1.SPCSO7.Oper.ctlVal SPC BOOLEAN CO B 0 I1 TRIG 7 Control\SPCGAPC1
7
Trig output
SPCGAPC1 SPC(1) SPC(1) CTR LD0.SPCGAPC1.SPCSO8.Oper.ctlVal SPC BOOLEAN CO B 0 I1 TRIG 8 Control\SPCGAPC1
8
Trig output
SPCGAPC1 SPC(1) SPC(1) CTR LD0.SPCGAPC1.SPCSO9.Oper.ctlVal SPC BOOLEAN CO B 0 I1 TRIG 9 Control\SPCGAPC1
9
89
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Trig output
SPCGAPC1 SPC(1) SPC(1) CTR LD0.SPCGAPC1.SPCSO10.Oper.ctlVal SPC BOOLEAN CO B 0 I1 TRIG 10 Control\SPCGAPC1
10
Trig output
SPCGAPC1 SPC(1) SPC(1) CTR LD0.SPCGAPC1.SPCSO11.Oper.ctlVal SPC BOOLEAN CO B 0 I1 TRIG 11 Control\SPCGAPC1
11
Trig output
SPCGAPC1 SPC(1) SPC(1) CTR LD0.SPCGAPC1.SPCSO12.Oper.ctlVal SPC BOOLEAN CO B 0 I1 TRIG 12 Control\SPCGAPC1
12
Trig output
SPCGAPC1 SPC(1) SPC(1) CTR LD0.SPCGAPC1.SPCSO13.Oper.ctlVal SPC BOOLEAN CO B 0 I1 TRIG 13 Control\SPCGAPC1
13
Trig output
SPCGAPC1 SPC(1) SPC(1) CTR LD0.SPCGAPC1.SPCSO14.Oper.ctlVal SPC BOOLEAN CO B 0 I1 TRIG 14 Control\SPCGAPC1
14
Trig output
SPCGAPC1 SPC(1) SPC(1) CTR LD0.SPCGAPC1.SPCSO15.Oper.ctlVal SPC BOOLEAN CO B 0 I1 TRIG 15 Control\SPCGAPC1
15
Trig output
SPCGAPC1 SPC(1) SPC(1) CTR LD0.SPCGAPC1.SPCSO16.Oper.ctlVal SPC BOOLEAN CO B 0 I1 TRIG 16 Control\SPCGAPC1
16
Operation
0=Pulsed;
Operation mode for Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO1.pulseConfig.cmdQual SPC Enum CF B,I -1 1=Toggle/Persistent;
mode generic logic\SPCGAPC1\Output 1
-1=Off
control point
Pulse length
Pulse for pulsed Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO1.pulseConfig.onDur SPC INT32U CF B,I 1000 10...3600000 ms
length operation logic\SPCGAPC1\Output 1
mode
Generic
SPCGAPC1 Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO1.dU SPC Unicode255 DC ED2,B Description control point
Output 1 logic\SPCGAPC1\Output 1
description
Generic
VisString255 SPCGAPC1 Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO1.d SPC DC Description control point
(64) Output 1 logic\SPCGAPC1\Output 1
description
Operation
0=Pulsed;
Operation mode for Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO2.pulseConfig.cmdQual SPC Enum CF B,I -1 1=Toggle/Persistent;
mode generic logic\SPCGAPC1\Output 2
-1=Off
control point
Pulse length
Pulse for pulsed Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO2.pulseConfig.onDur SPC INT32U CF B,I 1000 10...3600000 ms
length operation logic\SPCGAPC1\Output 2
mode
Generic
SPCGAPC1 Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO2.dU SPC Unicode255 DC ED2,B Description control point
Output 2 logic\SPCGAPC1\Output 2
description
Generic
VisString255 SPCGAPC1 Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO2.d SPC DC Description control point
(64) Output 2 logic\SPCGAPC1\Output 2
description
Operation
0=Pulsed;
Operation mode for Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO3.pulseConfig.cmdQual SPC Enum CF B,I -1 1=Toggle/Persistent;
mode generic logic\SPCGAPC1\Output 3
-1=Off
control point
Pulse Pulse length Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO3.pulseConfig.onDur SPC INT32U CF B,I 1000 10...3600000 ms
length for pulsed logic\SPCGAPC1\Output 3

90
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

operation
mode
Generic
SPCGAPC1 Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO3.dU SPC Unicode255 DC ED2,B Description control point
Output 3 logic\SPCGAPC1\Output 3
description
Generic
VisString255 SPCGAPC1 Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO3.d SPC DC Description control point
(64) Output 3 logic\SPCGAPC1\Output 3
description
Operation
0=Pulsed;
Operation mode for Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO4.pulseConfig.cmdQual SPC Enum CF B,I -1 1=Toggle/Persistent;
mode generic logic\SPCGAPC1\Output 4
-1=Off
control point
Pulse length
Pulse for pulsed Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO4.pulseConfig.onDur SPC INT32U CF B,I 1000 10...3600000 ms
length operation logic\SPCGAPC1\Output 4
mode
Generic
SPCGAPC1 Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO4.dU SPC Unicode255 DC ED2,B Description control point
Output 4 logic\SPCGAPC1\Output 4
description
Generic
VisString255 SPCGAPC1 Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO4.d SPC DC Description control point
(64) Output 4 logic\SPCGAPC1\Output 4
description
Operation
0=Pulsed;
Operation mode for Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO5.pulseConfig.cmdQual SPC Enum CF B,I -1 1=Toggle/Persistent;
mode generic logic\SPCGAPC1\Output 5
-1=Off
control point
Pulse length
Pulse for pulsed Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO5.pulseConfig.onDur SPC INT32U CF B,I 1000 10...3600000 ms
length operation logic\SPCGAPC1\Output 5
mode
Generic
SPCGAPC1 Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO5.dU SPC Unicode255 DC ED2,B Description control point
Output 5 logic\SPCGAPC1\Output 5
description
Generic
VisString255 SPCGAPC1 Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO5.d SPC DC Description control point
(64) Output 5 logic\SPCGAPC1\Output 5
description
Operation
0=Pulsed;
Operation mode for Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO6.pulseConfig.cmdQual SPC Enum CF B,I -1 1=Toggle/Persistent;
mode generic logic\SPCGAPC1\Output 6
-1=Off
control point
Pulse length
Pulse for pulsed Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO6.pulseConfig.onDur SPC INT32U CF B,I 1000 10...3600000 ms
length operation logic\SPCGAPC1\Output 6
mode
Generic
SPCGAPC1 Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO6.dU SPC Unicode255 DC ED2,B Description control point
Output 6 logic\SPCGAPC1\Output 6
description

91
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Generic
VisString255 SPCGAPC1 Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO6.d SPC DC Description control point
(64) Output 6 logic\SPCGAPC1\Output 6
description
Operation
0=Pulsed;
Operation mode for Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO7.pulseConfig.cmdQual SPC Enum CF B,I -1 1=Toggle/Persistent;
mode generic logic\SPCGAPC1\Output 7
-1=Off
control point
Pulse length
Pulse for pulsed Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO7.pulseConfig.onDur SPC INT32U CF B,I 1000 10...3600000 ms
length operation logic\SPCGAPC1\Output 7
mode
Generic
SPCGAPC1 Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO7.dU SPC Unicode255 DC ED2,B Description control point
Output 7 logic\SPCGAPC1\Output 7
description
Generic
VisString255 SPCGAPC1 Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO7.d SPC DC Description control point
(64) Output 7 logic\SPCGAPC1\Output 7
description
Operation
0=Pulsed;
Operation mode for Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO8.pulseConfig.cmdQual SPC Enum CF B,I -1 1=Toggle/Persistent;
mode generic logic\SPCGAPC1\Output 8
-1=Off
control point
Pulse length
Pulse for pulsed Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO8.pulseConfig.onDur SPC INT32U CF B,I 1000 10...3600000 ms
length operation logic\SPCGAPC1\Output 8
mode
Generic
SPCGAPC1 Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO8.dU SPC Unicode255 DC ED2,B Description control point
Output 8 logic\SPCGAPC1\Output 8
description
Generic
VisString255 SPCGAPC1 Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO8.d SPC DC Description control point
(64) Output 8 logic\SPCGAPC1\Output 8
description
Operation
0=Pulsed;
Operation mode for Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO9.pulseConfig.cmdQual SPC Enum CF B,I -1 1=Toggle/Persistent;
mode generic logic\SPCGAPC1\Output 9
-1=Off
control point
Pulse length
Pulse for pulsed Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO9.pulseConfig.onDur SPC INT32U CF B,I 1000 10...3600000 ms
length operation logic\SPCGAPC1\Output 9
mode
Generic
SPCGAPC1 Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO9.dU SPC Unicode255 DC ED2,B Description control point
Output 9 logic\SPCGAPC1\Output 9
description
Generic
VisString255 SPCGAPC1 Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO9.d SPC DC Description control point
(64) Output 9 logic\SPCGAPC1\Output 9
description
Operation
0=Pulsed; Configuration\Generic
Operation mode for
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO10.pulseConfig.cmdQual SPC Enum CF B,I -1 1=Toggle/Persistent; logic\SPCGAPC1\Output
mode generic
-1=Off 10
control point

92
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Pulse length
Configuration\Generic
Pulse for pulsed
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO10.pulseConfig.onDur SPC INT32U CF B,I 1000 10...3600000 ms logic\SPCGAPC1\Output
length operation
10
mode
Generic Configuration\Generic
SPCGAPC1
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO10.dU SPC Unicode255 DC ED2,B Description control point logic\SPCGAPC1\Output
Output 10
description 10
Generic Configuration\Generic
VisString255 SPCGAPC1
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO10.d SPC DC Description control point logic\SPCGAPC1\Output
(64) Output 10
description 10
Operation
0=Pulsed; Configuration\Generic
Operation mode for
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO11.pulseConfig.cmdQual SPC Enum CF B,I -1 1=Toggle/Persistent; logic\SPCGAPC1\Output
mode generic
-1=Off 11
control point
Pulse length
Configuration\Generic
Pulse for pulsed
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO11.pulseConfig.onDur SPC INT32U CF B,I 1000 10...3600000 ms logic\SPCGAPC1\Output
length operation
11
mode
Generic Configuration\Generic
SPCGAPC1
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO11.dU SPC Unicode255 DC ED2,B Description control point logic\SPCGAPC1\Output
Output 11
description 11
Generic Configuration\Generic
VisString255 SPCGAPC1
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO11.d SPC DC Description control point logic\SPCGAPC1\Output
(64) Output 11
description 11
Operation
0=Pulsed; Configuration\Generic
Operation mode for
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO12.pulseConfig.cmdQual SPC Enum CF B,I -1 1=Toggle/Persistent; logic\SPCGAPC1\Output
mode generic
-1=Off 12
control point
Pulse length
Configuration\Generic
Pulse for pulsed
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO12.pulseConfig.onDur SPC INT32U CF B,I 1000 10...3600000 ms logic\SPCGAPC1\Output
length operation
12
mode
Generic Configuration\Generic
SPCGAPC1
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO12.dU SPC Unicode255 DC ED2,B Description control point logic\SPCGAPC1\Output
Output 12
description 12
Generic Configuration\Generic
VisString255 SPCGAPC1
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO12.d SPC DC Description control point logic\SPCGAPC1\Output
(64) Output 12
description 12
Operation
0=Pulsed; Configuration\Generic
Operation mode for
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO13.pulseConfig.cmdQual SPC Enum CF B,I -1 1=Toggle/Persistent; logic\SPCGAPC1\Output
mode generic
-1=Off 13
control point
Pulse length
Configuration\Generic
Pulse for pulsed
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO13.pulseConfig.onDur SPC INT32U CF B,I 1000 10...3600000 ms logic\SPCGAPC1\Output
length operation
13
mode
Generic Configuration\Generic
SPCGAPC1
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO13.dU SPC Unicode255 DC ED2,B Description control point logic\SPCGAPC1\Output
Output 13
description 13

93
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Generic Configuration\Generic
VisString255 SPCGAPC1
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO13.d SPC DC Description control point logic\SPCGAPC1\Output
(64) Output 13
description 13
Operation
0=Pulsed; Configuration\Generic
Operation mode for
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO14.pulseConfig.cmdQual SPC Enum CF B,I -1 1=Toggle/Persistent; logic\SPCGAPC1\Output
mode generic
-1=Off 14
control point
Pulse length
Configuration\Generic
Pulse for pulsed
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO14.pulseConfig.onDur SPC INT32U CF B,I 1000 10...3600000 ms logic\SPCGAPC1\Output
length operation
14
mode
Generic Configuration\Generic
SPCGAPC1
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO14.dU SPC Unicode255 DC ED2,B Description control point logic\SPCGAPC1\Output
Output 14
description 14
Generic Configuration\Generic
VisString255 SPCGAPC1
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO14.d SPC DC Description control point logic\SPCGAPC1\Output
(64) Output 14
description 14
Operation
0=Pulsed; Configuration\Generic
Operation mode for
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO15.pulseConfig.cmdQual SPC Enum CF B,I -1 1=Toggle/Persistent; logic\SPCGAPC1\Output
mode generic
-1=Off 15
control point
Pulse length
Configuration\Generic
Pulse for pulsed
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO15.pulseConfig.onDur SPC INT32U CF B,I 1000 10...3600000 ms logic\SPCGAPC1\Output
length operation
15
mode
Generic Configuration\Generic
SPCGAPC1
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO15.dU SPC Unicode255 DC ED2,B Description control point logic\SPCGAPC1\Output
Output 15
description 15
Generic Configuration\Generic
VisString255 SPCGAPC1
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO15.d SPC DC Description control point logic\SPCGAPC1\Output
(64) Output 15
description 15
Operation
0=Pulsed; Configuration\Generic
Operation mode for
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO16.pulseConfig.cmdQual SPC Enum CF B,I -1 1=Toggle/Persistent; logic\SPCGAPC1\Output
mode generic
-1=Off 16
control point
Pulse length
Configuration\Generic
Pulse for pulsed
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO16.pulseConfig.onDur SPC INT32U CF B,I 1000 10...3600000 ms logic\SPCGAPC1\Output
length operation
16
mode
Generic Configuration\Generic
SPCGAPC1
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO16.dU SPC Unicode255 DC ED2,B Description control point logic\SPCGAPC1\Output
Output 16
description 16
Generic Configuration\Generic
VisString255 SPCGAPC1
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.SPCSO16.d SPC DC Description control point logic\SPCGAPC1\Output
(64) Output 16
description 16
Local
Loc Rem remote Configuration\Generic
SPCGAPC1 SPC(1) SPC(1) CFG LD0.SPCGAPC1.LocRemRst.setVal SPG BOOLEAN SP B 1
restriction switch logic\SPCGAPC1\General
restriction

94
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

VisString255
SPCGAPC1 SPC(1) SPC(1) VER LD0.SPCGAPC1.NamPlt.swRev LPL DC ED1 D1 (Name plate)
(20)

VMMXU1: Three-phase voltage measurement: D1


IEC
Categor Acces Defaul Even CM Parameter Parameter Channel
IEC 61850 6061 ANSI IECName CDC Type FC Dataset Parameter name Menu path
y s t t T desc range relation
7
VMMXU 3V(1 (ACT input
3U(1) INP Channel U3P
1 ) channel)
Block signal
VMMXU 3V(1 Monitoring\I/O
3U(1) INP LD0.VMMXU1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK for all binary
1 ) status\Measurements\VMMXU1\Inputs
outputs
VMMXU 3V(1 HIGH_ALAR Monitoring\I/O
3U(1) OUT LD0.VMMXU1.HiAlm.stVal SPS BOOLEAN ST B StatUrg P,H I1 High alarm
1 ) M status\Measurements\VMMXU1\Outputs
VMMXU 3V(1 High Monitoring\I/O
3U(1) OUT LD0.VMMXU1.HiWrn.stVal SPS BOOLEAN ST B StatUrg P,H I1 HIGH_WARN
1 ) warning status\Measurements\VMMXU1\Outputs
VMMXU 3V(1 Low Monitoring\I/O
3U(1) OUT LD0.VMMXU1.LoWrn.stVal SPS BOOLEAN ST B StatUrg P,H I1 LOW_WARN
1 ) warning status\Measurements\VMMXU1\Outputs
VMMXU 3V(1 Monitoring\I/O
3U(1) OUT LD0.VMMXU1.LoAlm.stVal SPS BOOLEAN ST B StatUrg P,H I1 LOW_ALARM Low alarm
1 ) status\Measurements\VMMXU1\Outputs
Measured
phase to
VMMXU 3V(1 LD0.VMMXU1.PPV.phsAB.instCVal.mag. M MeasFl phase 0.00...4.00 UL1TVTR
3U(1) MON DEL FLOAT32 B P U12-kV Measurements\VMMXU1
1 ) f X t voltage xUn 1
amplitude
phase AB
- Monitoring\I/O
VMMXU 3V(1 M MeasFl UL1TVTR
3U(1) MON LD0.VMMXU1.PPV.phsAB.instCVal.ang.f DEL FLOAT32 B P U_ANGL_AB U12 angle 180.00...180.0 status\Measurements\VMMXU1\Monitore
1 ) X t 1
0 deg d data
U12
Amplitude, Monitoring\I/O
VMMXU 3V(1 M MeasFl 0.00...4.00 UL1TVTR
3U(1) MON LD0.VMMXU1.PPV.phsAB.cVal.mag.f DEL FLOAT32 B P I1 U_DB_AB magnitude of status\Measurements\VMMXU1\Monitore
1 ) X t xUn 1
reported d data
value
0=normal;
U12 1=high; Monitoring\I/O
VMMXU 3V(1 M MeasFl U_RANGE_A UL1TVTR
3U(1) MON LD0.VMMXU1.PPV.phsAB.range DEL Enum B P Amplitude 2=low; status\Measurements\VMMXU1\Monitore
1 ) X t B 1
range 3=high-high; d data
4=low-low
Measured
phase to
VMMXU 3V(1 M MeasFl phase 0.00...4.00 UL1TVTR
3U(1) MON LD0.VMMXU1.PPV.phsBC.instCVal.mag.f DEL FLOAT32 B P U23-kV Measurements\VMMXU1
1 ) X t voltage xUn 1
amplitude
phase BC

95
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

- Monitoring\I/O
VMMXU 3V(1 M MeasFl UL1TVTR
3U(1) MON LD0.VMMXU1.PPV.phsBC.instCVal.ang.f DEL FLOAT32 B P U_ANGL_BC U23 angle 180.00...180.0 status\Measurements\VMMXU1\Monitore
1 ) X t 1
0 deg d data
U23
Amplitude, Monitoring\I/O
VMMXU 3V(1 M MeasFl 0.00...4.00 UL1TVTR
3U(1) MON LD0.VMMXU1.PPV.phsBC.cVal.mag.f DEL FLOAT32 B P I1 U_DB_BC magnitude of status\Measurements\VMMXU1\Monitore
1 ) X t xUn 1
reported d data
value
0=normal;
U23 1=high; Monitoring\I/O
VMMXU 3V(1 M MeasFl U_RANGE_B UL1TVTR
3U(1) MON LD0.VMMXU1.PPV.phsBC.range DEL Enum B P Amplitude 2=low; status\Measurements\VMMXU1\Monitore
1 ) X t C 1
range 3=high-high; d data
4=low-low
Measured
phase to
VMMXU 3V(1 LD0.VMMXU1.PPV.phsCA.instCVal.mag. M MeasFl phase 0.00...4.00 UL1TVTR
3U(1) MON DEL FLOAT32 B P U31-kV Measurements\VMMXU1
1 ) f X t voltage xUn 1
amplitude
phase CA
- Monitoring\I/O
VMMXU 3V(1 M MeasFl UL1TVTR
3U(1) MON LD0.VMMXU1.PPV.phsCA.instCVal.ang.f DEL FLOAT32 B P U_ANGL_CA U31 angle 180.00...180.0 status\Measurements\VMMXU1\Monitore
1 ) X t 1
0 deg d data
U31
Amplitude, Monitoring\I/O
VMMXU 3V(1 M MeasFl 0.00...4.00 UL1TVTR
3U(1) MON LD0.VMMXU1.PPV.phsCA.cVal.mag.f DEL FLOAT32 B P I1 U_DB_CA magnitude of status\Measurements\VMMXU1\Monitore
1 ) X t xUn 1
reported d data
value
0=normal;
U31 1=high; Monitoring\I/O
VMMXU 3V(1 M MeasFl U_RANGE_C UL1TVTR
3U(1) MON LD0.VMMXU1.PPV.phsCA.range DEL Enum B P Amplitude 2=low; status\Measurements\VMMXU1\Monitore
1 ) X t A 1
range 3=high-high; d data
4=low-low
UL1
Amplitude, Monitoring\I/O
VMMXU 3V(1 WY M MeasFl 0.00...5.00 UL1TVTR
3U(1) MON LD0.VMMXU1.PhV.phsA.cVal.mag.f FLOAT32 B P I1 U_INST_A magnitude of status\Measurements\VMMXU1\Monitore
1 ) E X t xUn 1
instantaneou d data
s value
- Monitoring\I/O
VMMXU 3V(1 WY M MeasFl UL1TVTR
3U(1) MON LD0.VMMXU1.PhV.phsA.cVal.ang.f FLOAT32 B P U_ANGL_A UL1 angle 180.00...180.0 status\Measurements\VMMXU1\Monitore
1 ) E X t 1
0 deg d data
UL2
Amplitude, Monitoring\I/O
VMMXU 3V(1 WY M MeasFl 0.00...5.00 UL1TVTR
3U(1) MON LD0.VMMXU1.PhV.phsB.cVal.mag.f FLOAT32 B P I1 U_INST_B magnitude of status\Measurements\VMMXU1\Monitore
1 ) E X t xUn 1
instantaneou d data
s value
- Monitoring\I/O
VMMXU 3V(1 WY M MeasFl UL1TVTR
3U(1) MON LD0.VMMXU1.PhV.phsB.cVal.ang.f FLOAT32 B P U_ANGL_B UL2 angle 180.00...180.0 status\Measurements\VMMXU1\Monitore
1 ) E X t 1
0 deg d data

96
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

UL3
Amplitude, Monitoring\I/O
VMMXU 3V(1 WY M MeasFl 0.00...5.00 UL1TVTR
3U(1) MON LD0.VMMXU1.PhV.phsC.cVal.mag.f FLOAT32 B P I1 U_INST_C magnitude of status\Measurements\VMMXU1\Monitore
1 ) E X t xUn 1
instantaneou d data
s value
- Monitoring\I/O
VMMXU 3V(1 WY M MeasFl UL1TVTR
3U(1) MON LD0.VMMXU1.PhV.phsC.cVal.ang.f FLOAT32 B P U_ANGL_C UL3 angle 180.00...180.0 status\Measurements\VMMXU1\Monitore
1 ) E X t 1
0 deg d data
Demand Monitoring\I/O
VMMXU 3V(1 M 0.00...4.00 UL1TVTR
3U(1) MON LD0.VAVMMXU1.PPV.phsAB.cVal.mag.f DEL FLOAT32 B I1 U_DMD_AB value of U12 status\Measurements\VMMXU1\Monitore
1 ) X xUn 1
voltage d data
Demand Monitoring\I/O
VMMXU 3V(1 M 0.00...4.00 UL1TVTR
3U(1) MON LD0.VAVMMXU1.PPV.phsBC.cVal.mag.f DEL FLOAT32 B I1 U_DMD_BC value of U23 status\Measurements\VMMXU1\Monitore
1 ) X xUn 1
voltage d data
Demand Monitoring\I/O
VMMXU 3V(1 M 0.00...4.00 UL1TVTR
3U(1) MON LD0.VAVMMXU1.PPV.phsCA.cVal.mag.f DEL FLOAT32 B I1 U_DMD_CA value of U31 status\Measurements\VMMXU1\Monitore
1 ) X xUn 1
voltage d data
Demand Monitoring\I/O
VMMXU 3V(1 WY M 0.00...5.00 UL1TVTR
3U(1) MON LD0.VAVMMXU1.PhV.phsA.cVal.mag.f FLOAT32 B I1 U_DMD_A value of UL1 status\Measurements\VMMXU1\Monitore
1 ) E X xUn 1
voltage d data
Demand Monitoring\I/O
VMMXU 3V(1 WY M 0.00...5.00 UL1TVTR
3U(1) MON LD0.VAVMMXU1.PhV.phsB.cVal.mag.f FLOAT32 B I1 U_DMD_B value of UL2 status\Measurements\VMMXU1\Monitore
1 ) E X xUn 1
voltage d data
Demand Monitoring\I/O
VMMXU 3V(1 WY M 0.00...5.00 UL1TVTR
3U(1) MON LD0.VAVMMXU1.PhV.phsC.cVal.mag.f FLOAT32 B I1 U_DMD_C value of UL3 status\Measurements\VMMXU1\Monitore
1 ) E X xUn 1
voltage d data
VMMXU 3V(1 Operation
3U(1) CFG LD0.VMMXU1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off Configuration\Measurements\VMMXU1
1 ) Off / On
Deadband
configuratio
n value for
integral
VMMXU 3V(1 calculation. UL1TVTR
3U(1) CFG LD0.VMMXU1.PPV.phsAB.db DEL INT32U CF B,I 10000 V deadband 100...100000 Configuration\Measurements\VMMXU1
1 ) (percentage 1
of difference
between min
and max as
0,001 % s)
VMMXU 3V(1 LD0.VMMXU1.PPV.phsAB.rangeC.hhLim. V high high High alarm 0.00...4.00 UL1TVTR
3U(1) CFG DEL FLOAT32 CF B,I 1.40 Configuration\Measurements\VMMXU1
1 ) f limit voltage limit xUn 1
High
VMMXU 3V(1 0.00...4.00 UL1TVTR
3U(1) CFG LD0.VMMXU1.PPV.phsAB.rangeC.hLim.f DEL FLOAT32 CF B,I 1.20 V high limit warning Configuration\Measurements\VMMXU1
1 ) xUn 1
voltage limit
Low
VMMXU 3V(1 0.00...4.00 UL1TVTR
3U(1) CFG LD0.VMMXU1.PPV.phsAB.rangeC.lLim.f DEL FLOAT32 CF B,I 0.00 V low limit warning Configuration\Measurements\VMMXU1
1 ) xUn 1
voltage limit
VMMXU 3V(1 Low alarm 0.00...4.00 UL1TVTR
3U(1) CFG LD0.VMMXU1.PPV.phsAB.rangeC.llLim.f DEL FLOAT32 CF B,I 0.00 V low low limit Configuration\Measurements\VMMXU1
1 ) voltage limit xUn 1

97
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Selects used
VMMXU 3V(1 Measurement 1=RMS;
3U(1) CFG LD0.VMMXU1.VMeasMod.setVal ENG Enum SP A 2 measurement Configuration\Measurements\VMMXU1
1 ) mode 2=DFT
mode
Number of
phases 1=1 out of 3;
VMMXU 3V(1
3U(1) CFG LD0.VMMXU1.NumPh.setVal ENG Enum SP B 1 Num of phases required by 2=2 out of 3; Configuration\Measurements\VMMXU1
1 )
limit 3=3 out of 3
supervision
VMMXU 3V(1 VisString25
3U(1) VER LD0.VMMXU1.NamPlt.swRev LPL DC ED1 D1 (Name plate)
1 ) 5 (20)

VSMSQI1: Sequence voltage measurement: C1


IEC Categor CD Acces Defaul Even CM Parameter Parameter Parameter Channel
IEC 60617 ANSI IECName Type FC Dataset Menu path
61850 y C s t t T name desc range relation
VSMSQI U1,U2,U0(1 V1,V2,V0(1 (ACT input
INP Channel U3P
1 ) ) channel)
Measured
VSMSQI U1,U2,U0(1 V1,V2,V0(1 LD0.VSMSQI1.SeqV.c1.instCVal.mag M MeasFl positive 0.00...4.00 UL1TVTR
MON SEQ FLOAT32 B P PsSeq-kV Measurements\VSMSQI1
1 ) ) .f X t sequence xUn 1
voltage
Positive
- Monitoring\I/O
VSMSQI U1,U2,U0(1 V1,V2,V0(1 LD0.VSMSQI1.SeqV.c1.instCVal.ang. M MeasFl sequence UL1TVTR
MON SEQ FLOAT32 B P U1_ANGL 180.00...180.0 status\Measurements\VSMSQI1\Monitor
1 ) ) f X t voltage 1
0 deg ed data
angle
Positive
sequence
Monitoring\I/O
VSMSQI U1,U2,U0(1 V1,V2,V0(1 M MeasFl voltage 0.00...4.00 UL1TVTR
MON LD0.VSMSQI1.SeqV.c1.cVal.mag.f SEQ FLOAT32 B P I1 U1_DB status\Measurements\VSMSQI1\Monitor
1 ) ) X t amplitude, xUn 1
ed data
reported
value
Positive 0=normal;
sequence 1=high; Monitoring\I/O
VSMSQI U1,U2,U0(1 V1,V2,V0(1 M MeasFl U1_RANG UL1TVTR
MON LD0.VSMSQI1.SeqV.c1.range SEQ Enum B P voltage 2=low; status\Measurements\VSMSQI1\Monitor
1 ) ) X t E 1
amplitude 3=high-high; ed data
range 4=low-low
Measured
VSMSQI U1,U2,U0(1 V1,V2,V0(1 LD0.VSMSQI1.SeqV.c2.instCVal.mag M MeasFl negative 0.00...4.00 UL1TVTR
MON SEQ FLOAT32 B P NgSeq-kV Measurements\VSMSQI1
1 ) ) .f X t sequence xUn 1
voltage
Negative
- Monitoring\I/O
VSMSQI U1,U2,U0(1 V1,V2,V0(1 LD0.VSMSQI1.SeqV.c2.instCVal.ang. M MeasFl sequence UL1TVTR
MON SEQ FLOAT32 B P U2_ANGL 180.00...180.0 status\Measurements\VSMSQI1\Monitor
1 ) ) f X t voltage 1
0 deg ed data
angle
Negative
Monitoring\I/O
VSMSQI U1,U2,U0(1 V1,V2,V0(1 M MeasFl sequence 0.00...4.00 UL1TVTR
MON LD0.VSMSQI1.SeqV.c2.cVal.mag.f SEQ FLOAT32 B P I1 U2_DB status\Measurements\VSMSQI1\Monitor
1 ) ) X t voltage xUn 1
ed data
amplitude,

98
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

reported
value
Negative 0=normal;
sequence 1=high; Monitoring\I/O
VSMSQI U1,U2,U0(1 V1,V2,V0(1 M MeasFl U2_RANG UL1TVTR
MON LD0.VSMSQI1.SeqV.c2.range SEQ Enum B P voltage 2=low; status\Measurements\VSMSQI1\Monitor
1 ) ) X t E 1
amplitude 3=high-high; ed data
range 4=low-low
Measured
VSMSQI U1,U2,U0(1 V1,V2,V0(1 LD0.VSMSQI1.SeqV.c3.instCVal.mag M MeasFl zero 0.00...4.00 UL1TVTR
MON SEQ FLOAT32 B P ZroSeq-kV Measurements\VSMSQI1
1 ) ) .f X t sequence xUn 1
voltage
Zero
- Monitoring\I/O
VSMSQI U1,U2,U0(1 V1,V2,V0(1 LD0.VSMSQI1.SeqV.c3.instCVal.ang. M MeasFl sequence UL1TVTR
MON SEQ FLOAT32 B P U0_ANGL 180.00...180.0 status\Measurements\VSMSQI1\Monitor
1 ) ) f X t voltage 1
0 deg ed data
angle
Zero
sequence
Monitoring\I/O
VSMSQI U1,U2,U0(1 V1,V2,V0(1 M MeasFl voltage 0.00...4.00 UL1TVTR
MON LD0.VSMSQI1.SeqV.c3.cVal.mag.f SEQ FLOAT32 B P I1 U0_DB status\Measurements\VSMSQI1\Monitor
1 ) ) X t amplitude, xUn 1
ed data
reported
value
Zero 0=normal;
sequence 1=high; Monitoring\I/O
VSMSQI U1,U2,U0(1 V1,V2,V0(1 M MeasFl U0_RANG UL1TVTR
MON LD0.VSMSQI1.SeqV.c3.range SEQ Enum B P voltage 2=low; status\Measurements\VSMSQI1\Monitor
1 ) ) X t E 1
amplitude 3=high-high; ed data
range 4=low-low
VSMSQI U1,U2,U0(1 V1,V2,V0(1 EN Operation
CFG LD0.VSMSQI1.Mod.Oper.ctlVal Enum CO B,I 1 Operation 1=on; 5=off Configuration\Measurements\VSMSQI1
1 ) ) C Off / On
Deadband
configuratio
n value for
positive
sequence
voltage for
VSMSQI U1,U2,U0(1 V1,V2,V0(1 Ps Seq V UL1TVTR
CFG LD0.VSMSQI1.SeqV.c1.db SEQ INT32U CF B,I 10000 integral 100...100000 Configuration\Measurements\VSMSQI1
1 ) ) deadband 1
calculation.
(percentage
of difference
between min
and max as
0,001 % s)
High alarm
voltage limit
VSMSQI U1,U2,U0(1 V1,V2,V0(1 LD0.VSMSQI1.SeqV.c1.rangeC.hhLi Ps Seq V Hi 0.00...4.00 UL1TVTR
CFG SEQ FLOAT32 CF B,I 1.40 for positive Configuration\Measurements\VSMSQI1
1 ) ) m.f high Lim xUn 1
sequence
voltage
High
VSMSQI U1,U2,U0(1 V1,V2,V0(1 LD0.VSMSQI1.SeqV.c1.rangeC.hLim. Ps Seq V warning 0.00...4.00 UL1TVTR
CFG SEQ FLOAT32 CF B,I 1.20 Configuration\Measurements\VSMSQI1
1 ) ) f high limit voltage limit xUn 1
for positive

99
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

sequence
voltage
Low
warning
VSMSQI U1,U2,U0(1 V1,V2,V0(1 Ps Seq V voltage limit 0.00...4.00 UL1TVTR
CFG LD0.VSMSQI1.SeqV.c1.rangeC.lLim.f SEQ FLOAT32 CF B,I 0.00 Configuration\Measurements\VSMSQI1
1 ) ) low limit for positive xUn 1
sequence
voltage
Low alarm
Ps Seq V voltage limit
VSMSQI U1,U2,U0(1 V1,V2,V0(1 LD0.VSMSQI1.SeqV.c1.rangeC.llLim. 0.00...4.00 UL1TVTR
CFG SEQ FLOAT32 CF B,I 0.00 low low for positive Configuration\Measurements\VSMSQI1
1 ) ) f xUn 1
Lim sequence
voltage
Deadband
configuratio
n value for
negative
sequence
voltage for
VSMSQI U1,U2,U0(1 V1,V2,V0(1 Ng Seq V UL1TVTR
CFG LD0.VSMSQI1.SeqV.c2.db SEQ INT32U CF B,I 10000 integral 100...100000 Configuration\Measurements\VSMSQI1
1 ) ) deadband 1
calculation.
(percentage
of difference
between min
and max as
0,001 % s)
High alarm
voltage limit
VSMSQI U1,U2,U0(1 V1,V2,V0(1 LD0.VSMSQI1.SeqV.c2.rangeC.hhLi Ng Seq V 0.00...4.00 UL1TVTR
CFG SEQ FLOAT32 CF B,I 0.20 for negative Configuration\Measurements\VSMSQI1
1 ) ) m.f Hi high Lim xUn 1
sequence
voltage
High
warning
VSMSQI U1,U2,U0(1 V1,V2,V0(1 LD0.VSMSQI1.SeqV.c2.rangeC.hLim. Ng Seq V voltage limit 0.00...4.00 UL1TVTR
CFG SEQ FLOAT32 CF B,I 0.05 Configuration\Measurements\VSMSQI1
1 ) ) f High limit for negative xUn 1
sequence
voltage
Low
warning
VSMSQI U1,U2,U0(1 V1,V2,V0(1 Ng Seq V voltage limit 0.00...4.00 UL1TVTR
CFG LD0.VSMSQI1.SeqV.c2.rangeC.lLim.f SEQ FLOAT32 CF B,I 0.00 Configuration\Measurements\VSMSQI1
1 ) ) low limit for negative xUn 1
sequence
voltage
Low alarm
Ng Seq V voltage limit
VSMSQI U1,U2,U0(1 V1,V2,V0(1 LD0.VSMSQI1.SeqV.c2.rangeC.llLim. 0.00...4.00 UL1TVTR
CFG SEQ FLOAT32 CF B,I 0.00 low low for negative Configuration\Measurements\VSMSQI1
1 ) ) f xUn 1
Lim sequence
voltage
Deadband
VSMSQI U1,U2,U0(1 V1,V2,V0(1 Zro V UL1TVTR
CFG LD0.VSMSQI1.SeqV.c3.db SEQ INT32U CF B,I 10000 configuratio 100...100000 Configuration\Measurements\VSMSQI1
1 ) ) deadband 1
n value for
100
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

zero
sequence
voltage for
integral
calculation.
(percentage
of difference
between min
and max as
0,001 % s)
High alarm
voltage limit
VSMSQI U1,U2,U0(1 V1,V2,V0(1 LD0.VSMSQI1.SeqV.c3.rangeC.hhLi Zro V Hi 0.00...4.00 UL1TVTR
CFG SEQ FLOAT32 CF B,I 0.20 for zero Configuration\Measurements\VSMSQI1
1 ) ) m.f high Lim xUn 1
sequence
voltage
High
warning
VSMSQI U1,U2,U0(1 V1,V2,V0(1 LD0.VSMSQI1.SeqV.c3.rangeC.hLim. Zro V High voltage limit 0.00...4.00 UL1TVTR
CFG SEQ FLOAT32 CF B,I 0.05 Configuration\Measurements\VSMSQI1
1 ) ) f limit for zero xUn 1
sequence
voltage
Low
warning
VSMSQI U1,U2,U0(1 V1,V2,V0(1 Zro V low voltage limit 0.00...4.00 UL1TVTR
CFG LD0.VSMSQI1.SeqV.c3.rangeC.lLim.f SEQ FLOAT32 CF B,I 0.00 Configuration\Measurements\VSMSQI1
1 ) ) limit for zero xUn 1
sequence
voltage
Low alarm
voltage limit
VSMSQI U1,U2,U0(1 V1,V2,V0(1 LD0.VSMSQI1.SeqV.c3.rangeC.llLim. Zro V low 0.00...4.00 UL1TVTR
CFG SEQ FLOAT32 CF B,I 0.00 for zero Configuration\Measurements\VSMSQI1
1 ) ) f low Lim xUn 1
sequence
voltage
VSMSQI U1,U2,U0(1 V1,V2,V0(1 VisString25 (Name
VER LD0.VSMSQI1.NamPlt.swRev LPL DC ED1 C1
1 ) ) 5 (20) plate)

RESVMMXU1: Residual voltage measurement: E1


IEC
ANS Categor Acces Defaul Even CM Parameter Channel
IEC 61850 6061 IECName CDC Type FC Dataset Parameter name Parameter desc Menu path
I y s t t T range relation
7
RESVMMXU Uo(1 Vn(1 (ACT input
INP Channel URES
1 ) ) channel)
Block signal
RESVMMXU Uo(1 Vn(1 Monitoring\I/O
INP LD0.RESVMMXU1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK for all binary
1 ) ) status\Measurements\RESVMMXU1\Inputs
outputs
Monitoring\I/O
RESVMMXU Uo(1 Vn(1 StatUr HIGH_ALAR
OUT LD0.RESVMMXU1.HiAlm.stVal SPS BOOLEAN ST B P,H I1 High alarm status\Measurements\RESVMMXU1\Output
1 ) ) g M
s

101
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Monitoring\I/O
RESVMMXU Uo(1 Vn(1 StatUr
OUT LD0.RESVMMXU1.HiWrn.stVal SPS BOOLEAN ST B P,H I1 HIGH_WARN High warning status\Measurements\RESVMMXU1\Output
1 ) ) g
s
RESVMMXU Uo(1 Vn(1 (RESVMMXU
CTR LD0.RESVMMXU1.RcdRs.Oper.ctlVal SPC BOOLEAN CO I1
1 ) ) 1 demands)
Measured
RESVMMXU Uo(1 Vn(1 LD0.RESVMMXU1.PhV.res.instCVal.ma WY M MeasFl 0.00...4.00 RESTVTR
MON FLOAT32 B P Uo-kV residual Measurements\RESVMMXU1
1 ) ) g.f E X t xUn 1
voltage
- Monitoring\I/O
RESVMMXU Uo(1 Vn(1 LD0.RESVMMXU1.PhV.res.instCVal.an WY M MeasFl Residual RESTVTR
MON FLOAT32 B P U_ANGL_RES 180.00...180.0 status\Measurements\RESVMMXU1\Monit
1 ) ) g.f E X t voltage angle 1
0 deg ored data
Residual
voltage Monitoring\I/O
RESVMMXU Uo(1 Vn(1 WY M MeasFl 0.00...4.00 RESTVTR
MON LD0.RESVMMXU1.PhV.res.cVal.mag.f FLOAT32 B P I1 U_DB_RES Amplitude, status\Measurements\RESVMMXU1\Monit
1 ) ) E X t xUn 1
magnitude of ored data
reported value
0=normal;
Residual
1=high; Monitoring\I/O
RESVMMXU Uo(1 Vn(1 WY M MeasFl U_RANGE_RE voltage RESTVTR
MON LD0.RESVMMXU1.PhV.res.range Enum B P 2=low; status\Measurements\RESVMMXU1\Monit
1 ) ) E X t S Amplitude 1
3=high-high; ored data
range
4=low-low
Demand value Monitoring\I/O
RESVMMXU Uo(1 Vn(1 WY M 0.00...4.00 RESTVTR
MON LD0.RVAVMMXU1.PhV.res.cVal.mag.f FLOAT32 B I1 U_DMD_RES of residual status\Measurements\RESVMMXU1\Monit
1 ) ) E X xUn 1
voltage ored data
RESVMMXU Uo(1 Vn(1 Operation Off Configuration\Measurements\RESVMMXU
CFG LD0.RESVMMXU1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
1 ) ) / On 1
Deadband
configuration
value for
integral
RESVMMXU Uo(1 Vn(1 WY calculation. Configuration\Measurements\RESVMMXU RESTVTR
CFG LD0.RESVMMXU1.PhV.res.db INT32U CF B,I 10000 V deadband res 100...100000
1 ) ) E (percentage of 1 1
difference
between min
and max as
0,001 % s)
RESVMMXU Uo(1 Vn(1 LD0.RESVMMXU1.PhV.res.rangeC.hhLi WY V Hi high limit High alarm 0.00...4.00 Configuration\Measurements\RESVMMXU RESTVTR
CFG FLOAT32 CF B,I 0.20
1 ) ) m.f E res voltage limit xUn 1 1
RESVMMXU Uo(1 Vn(1 LD0.RESVMMXU1.PhV.res.rangeC.hLi WY High warning 0.00...4.00 Configuration\Measurements\RESVMMXU RESTVTR
CFG FLOAT32 CF B,I 0.05 V high limit res
1 ) ) m.f E voltage limit xUn 1 1
Selects used
RESVMMXU Uo(1 Vn(1 Measurement 1=RMS; Configuration\Measurements\RESVMMXU
CFG LD0.RESVMMXU1.VMeasMod.setVal ENG Enum SP A 2 measurement
1 ) ) mode 2=DFT 1
mode
RESVMMXU Uo(1 Vn(1 VisString25
VER LD0.RESVMMXU1.NamPlt.swRev LPL DC ED1 E1 (Name plate)
1 ) ) 5 (20)

IEC60870-5-101/104: IEC60870-5-101/104: F1
102
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

IEC Channe
IEC ANS Categor CD Acces Defaul Datase Even CM Parameter
6061 IECName Type FC Parameter desc Parameter range Menu path l
61850 I y C s t t t T name
7 relation
IEC60870 Control point
C Configuration\Communication\Protocols\IEC6087
-5- INP LD0.I5CLPRT1.ITotFrz.Oper.ctlVal SPC BOOLEAN A 0 I1 IT_FRZ for freezing
O 0-5-101/104(1)
101/104 integrated totals
IEC60870
I5CLPRT1 Monitoring\Communication\Protocols\IEC60870-
-5- OUT LD0.I5CLPRT1.ChLiv.stVal SPS BOOLEAN ST B I1 STATUS
Status 5-101/104(1)
101/104
IEC60870 Control point
C Configuration\Communication\Protocols\IEC6087
-5- CTR LD0.I5CLPRT1.ITotFrz.Oper.ctlVal SPC BOOLEAN A 0 I1 IT_FRZ for freezing
O 0-5-101/104(1)
101/104 integrated totals
IEC60870
C Reset Monitoring\Communication\Protocols\IEC60870-
-5- CTR LD0.I5CLPRT1.CntRs.Oper.ctlVal SPC BOOLEAN B 0 I1 Reset counters
O counters 5-101/104(1)
101/104
IEC60870
Received Received Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT1.FrRxCnt.stVal INS INT32 ST B I1 -1...2147483646
frames frames 5-101/104(1)
101/104
IEC60870
Link layer Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT1.LnkErrCnt.stVal INS INT32 ST B I1 Link errors -1...2147483646
errors 5-101/104(1)
101/104
IEC60870
Physical Physical layer Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT1.PhyErrCnt.stVal INS INT32 ST B I1 -1...2147483646
errors errors 5-101/104(1)
101/104
IEC60870
Transport Transport layer Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT1.TranErrCnt.stVal INS INT32 ST B I1 -1...2147483646
errors errors 5-101/104(1)
101/104
IEC60870
Transmitte Transmitted Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT1.FrTxCnt.stVal INS INT32 ST B I1 -1...2147483646
d frames frames 5-101/104(1)
101/104
Number of
IEC60870 rejected
CnReject Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT1.ConnRejSck.stVal INS INT32 ST B I1 connections due -1...2147483646
no sockets 5-101/104(1)
101/104 to no sockets
available
Connection
IEC60870 CnReject
rejected due to Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT1.ConnRejRg.stVal INS INT32 ST B I1 unregistere -1...2147483646
unregistered 5-101/104(1)
101/104 d
client
IEC60870
C Reset Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT1.CntRs.Oper.ctlVal SPC BOOLEAN B 0 I1 Reset counters
O counters 5-101/104(1)
101/104
Selects if this
IEC60870 protocol
C Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.Mod.Oper.ctlVal ENC Enum B,C,I 5 Operation instance is 1=on; 5=off
O 0-5-101/104(1)
101/104 enabled or
disabled

103
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

IEC60870
EN 3=IEC104 - Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.CommPort.setVal Enum SP B,C 3 Port Port selection
G Ethernet 0-5-101/104(1)
101/104
IEC60870 Frame start
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.StrFrDl.setVal ING INT32 SP A 4 Start Delay delay for serial 0...20 char
0-5-101/104(1)
101/104 communication
IEC60870 Frame end
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.EndFrDl.setVal ING INT32 SP A 4 End Delay delay for serial 0...20 char
0-5-101/104(1)
101/104 communication
IEC60870 Control point
C Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.ITotFrz.Oper.ctlVal SPC BOOLEAN A 0 I1 IT_FRZ for freezing
O 0-5-101/104(1)
101/104 integrated totals
IEC60870
Device Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.DevAddr.setVal ING INT32 SP B 1 Device address 1...65535
Address 0-5-101/104(1)
101/104
IEC60870 Common
ASDU Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.ASDUAddr.setVal ING INT32 SP B 1 address of 1...65535
Address 0-5-101/104(1)
101/104 ASDU
IEC60870
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.TCPPort.setVal ING INT32 SP A,C 2404 TCP Port Server TCP port 0...65535
0-5-101/104(1)
101/104
IEC60870
EN Link mode 0=Balanced; Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.LnkMod.setVal Enum SP B 0 Link Mode
G setting 1=Unbalanced 0-5-101/104(1)
101/104
IEC60870 Cause of
COT Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.COTLen.setVal ING INT32 SP B 2 transmission 1...2
Length 0-5-101/104(1)
101/104 length
IEC60870 Information
IOA Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.IOALen.setVal ING INT32 SP B 3 Object Address 1...3
Length 0-5-101/104(1)
101/104 length
IEC60870 Link
Link Address Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.LnkAddrLen.setVal ING INT32 SP B 2 Address 1...2
Length 0-5-101/104(1)
101/104 Length
IEC60870 ASDU
LD0.I5CLPRT1.ASDUAddrLen.setV ASDU Address Configuration\Communication\Protocols\IEC6087
-5- CFG ING INT32 SP ED2,B 2 I1 Address 1...2
al Length 0-5-101/104(1)
101/104 Length
IEC60870 ASDU
ASDU Address Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.ASDUAdrLen.setVal ING INT32 SP ED1 2 I1 Address 1...2
Length 0-5-101/104(1)
101/104 Length
Single character
IEC60870
Single Char response Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.SglCharRsp.setVal SPG BOOLEAN SP A 0
Resp enabled/disable 0-5-101/104(1)
101/104
d
Enable/disable
IEC60870
Show Bad bad time quality Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.IndBadTmQ.setVal SPG BOOLEAN SP A 1
Time indication in 0-5-101/104(1)
101/104
events

104
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

IEC60870 Time stamp


EN Time 0=Short 24bit; Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.TmFrmSel.setVal Enum SP A 1 format 3 or 7
G Format 1=Full 56bit 0-5-101/104(1)
101/104 octet
IEC60870 Selects between
EN Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.EvtTmMod.setVal Enum SP A 1 Time Zone UTC/Local 0=Local; 1=UTC
G 0-5-101/104(1)
101/104 time
Event buffer
IEC60870
EN Overflow overflow 0=Oldest+indication Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.EvtBufMod.setVal Enum SP A 0
G Mode handling ; 1=Keep newest 0-5-101/104(1)
101/104
mechanism
IEC60870 Counter
EN Counter 0=Read by master; Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.CntRpMod.setVal Enum SP A 0 reporting after
G Reporting 1=Spontaneous 0-5-101/104(1)
101/104 freeze
Freezing mode
IEC60870 0=Not in use;
EN Freeze for externally Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.CntFrzMod.setVal Enum SP A 0 1=Freeze only;
G mode triggered 0-5-101/104(1)
101/104 2=Freeze and Reset
integrated totals
IEC60870 IEC60870-5-
TX window Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.TxWinWid.setVal ING INT32 SP A 12 104 transmit 1...20
(k) 0-5-101/104(1)
101/104 window (k)
IEC60870 RX IEC60870-5-
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.RxWinWid.setVal ING INT32 SP A 8 window 104 receive 1...20
0-5-101/104(1)
101/104 (w) window (w)
IEC60870 IEC60870-5-
TX timeout Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.Tm1Tmms.setVal ING INT32 SP A 30000 104 transmit 1...60000 ms
(t1) 0-5-101/104(1)
101/104 timeout (t1)
IEC60870 IEC60870-5-
RX timeout Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.Tm2Tmms.setVal ING INT32 SP A 10000 104 receive 1...60000 ms
(t2) 0-5-101/104(1)
101/104 timeout (t1)
IEC60870 IEC60870-5-
Test Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.Tm3Tmms.setVal ING INT32 SP A 20000 104 link test 1...60000 ms
interval (t3) 0-5-101/104(1)
101/104 interval (t3)
Overflow
IEC60870 indication
ED2, Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.OvIndAddrGI.setVal ING INT32 SP 60000 I1 OvInd IOA address for 0...16777215
A 0-5-101/104(1)
101/104 interrogated
data
Overflow
IEC60870 indication
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.OvIndAdrGI.setVal ING INT32 SP ED1 60000 I1 OvInd IOA address for 0...16777215
0-5-101/104(1)
101/104 interrogated
data
Overflow
IEC60870 indication
OvInd Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.OvIndAddr.setVal ING INT32 SP A 60000 address for non- 0...16777215
NoGI IOA 0-5-101/104(1)
101/104 interrogated
data
IEC60870
Selection Selection Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.SelTms.setVal ING INT32 SP A 30 1...65 s
Timeout timeout for 0-5-101/104(1)
101/104
105
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

control SBO
operations
IEC60870
Cyclical Cyclical period Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.CycPer.setVal ING INT32 SP A 10 1...604800 s
Period in seconds 0-5-101/104(1)
101/104
Special mode
for masters that
require inverted
DIR bit on
Balanced
IEC60870 IEC101 line. If
Inverted Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.InvDIR.setVal SPG BOOLEAN SP A 0 enabled, this
DIR bit 0-5-101/104(1)
101/104 protocol
instance will be
non-compliant
with the IEC
60870-5-101
standard.
IEC60870
VisString25 IP address of Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.CliIP.setVal VSG SP ED2,B 0.0.0.0 I1 ClientIP
5 (20) the client 0-5-101/104(1)
101/104
IEC60870
EN VisString25 IP address of Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.CommPort.eIp EX ED1 0.0.0.0 I1 ClientIP
G 5 (20) the client 0-5-101/104(1)
101/104
Maximum
IEC60870 delay for
Command Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.CmdDl.setVal ING INT32 SP B 5000 timestamped 0...65535 ms
delay 0-5-101/104(1)
101/104 commands in
milliseconds.
IEC60870
Mapping Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT1.MapSel.setVal ING INT32 SP A,C 1 Mapping select 1...2
select 0-5-101/104(1)
101/104
IEC60870
VisString25 D
-5- VER LD0.I5CLPRT1.NamPlt.swRev LPL F1 (Name plate)
5 (20) C
101/104

IEC60870-5-101/104: IEC60870-5-101/104: F1
IEC Channe
IEC ANS Categor CD Acces Defaul Datase Even CM Parameter
6061 IECName Type FC Parameter desc Parameter range Menu path l
61850 I y C s t t t T name
7 relation
IEC60870 Control point
C Configuration\Communication\Protocols\IEC6087
-5- INP LD0.I5CLPRT2.ITotFrz.Oper.ctlVal SPC BOOLEAN A 0 I1 IT_FRZ for freezing
O 0-5-101/104(2)
101/104 integrated totals
IEC60870
Monitoring\Communication\Protocols\IEC60870-
-5- OUT LD0.I5CLPRT2.ChLiv.stVal SPS BOOLEAN ST B I1 STATUS Status
5-101/104(2)
101/104

106
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

IEC60870 Control point


C Configuration\Communication\Protocols\IEC6087
-5- CTR LD0.I5CLPRT2.ITotFrz.Oper.ctlVal SPC BOOLEAN A 0 I1 IT_FRZ for freezing
O 0-5-101/104(2)
101/104 integrated totals
IEC60870
C Reset Monitoring\Communication\Protocols\IEC60870-
-5- CTR LD0.I5CLPRT2.CntRs.Oper.ctlVal SPC BOOLEAN B 0 I1 Reset counters
O counters 5-101/104(2)
101/104
IEC60870
Received Received Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT2.FrRxCnt.stVal INS INT32 ST B I1 -1...2147483646
frames frames 5-101/104(2)
101/104
IEC60870
Link layer Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT2.LnkErrCnt.stVal INS INT32 ST B I1 Link errors -1...2147483646
errors 5-101/104(2)
101/104
IEC60870
Physical Physical layer Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT2.PhyErrCnt.stVal INS INT32 ST B I1 -1...2147483646
errors errors 5-101/104(2)
101/104
IEC60870
Transport Transport layer Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT2.TranErrCnt.stVal INS INT32 ST B I1 -1...2147483646
errors errors 5-101/104(2)
101/104
IEC60870
Transmitte Transmitted Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT2.FrTxCnt.stVal INS INT32 ST B I1 -1...2147483646
d frames frames 5-101/104(2)
101/104
Number of
IEC60870 rejected
CnReject Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT2.ConnRejSck.stVal INS INT32 ST B I1 connections due -1...2147483646
no sockets 5-101/104(2)
101/104 to no sockets
available
Connection
IEC60870 CnReject
rejected due to Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT2.ConnRejRg.stVal INS INT32 ST B I1 unregistere -1...2147483646
unregistered 5-101/104(2)
101/104 d
client
IEC60870
C Reset Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT2.CntRs.Oper.ctlVal SPC BOOLEAN B 0 I1 Reset counters
O counters 5-101/104(2)
101/104
Selects if this
IEC60870 protocol
C Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.Mod.Oper.ctlVal ENC Enum B,C,I 5 Operation instance is 1=on; 5=off
O 0-5-101/104(2)
101/104 enabled or
disabled
IEC60870
EN 3=IEC104 - Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.CommPort.setVal Enum SP B,C 3 Port Port selection
G Ethernet 0-5-101/104(2)
101/104
IEC60870 Frame start
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.StrFrDl.setVal ING INT32 SP A 4 Start Delay delay for serial 0...20 char
0-5-101/104(2)
101/104 communication
IEC60870 Frame end
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.EndFrDl.setVal ING INT32 SP A 4 End Delay delay for serial 0...20 char
0-5-101/104(2)
101/104 communication

107
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

IEC60870 Control point


C Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.ITotFrz.Oper.ctlVal SPC BOOLEAN A 0 I1 IT_FRZ for freezing
O 0-5-101/104(2)
101/104 integrated totals
IEC60870
Device Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.DevAddr.setVal ING INT32 SP B 1 Device address 1...65535
Address 0-5-101/104(2)
101/104
IEC60870 Common
ASDU Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.ASDUAddr.setVal ING INT32 SP B 1 address of 1...65535
Address 0-5-101/104(2)
101/104 ASDU
IEC60870
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.TCPPort.setVal ING INT32 SP A,C 2404 TCP Port Server TCP port 0...65535
0-5-101/104(2)
101/104
IEC60870
EN Link mode 0=Balanced; Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.LnkMod.setVal Enum SP B 0 Link Mode
G setting 1=Unbalanced 0-5-101/104(2)
101/104
IEC60870 Cause of
COT Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.COTLen.setVal ING INT32 SP B 2 transmission 1...2
Length 0-5-101/104(2)
101/104 length
IEC60870 Information
IOA Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.IOALen.setVal ING INT32 SP B 3 Object Address 1...3
Length 0-5-101/104(2)
101/104 length
IEC60870 Link
Link Address Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.LnkAddrLen.setVal ING INT32 SP B 2 Address 1...2
Length 0-5-101/104(2)
101/104 Length
IEC60870 ASDU
LD0.I5CLPRT2.ASDUAddrLen.setV ASDU Address Configuration\Communication\Protocols\IEC6087
-5- CFG ING INT32 SP ED2,B 2 I1 Address 1...2
al Length 0-5-101/104(2)
101/104 Length
IEC60870 ASDU
ASDU Address Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.ASDUAdrLen.setVal ING INT32 SP ED1 2 I1 Address 1...2
Length 0-5-101/104(2)
101/104 Length
Single character
IEC60870
Single Char response Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.SglCharRsp.setVal SPG BOOLEAN SP A 0
Resp enabled/disable 0-5-101/104(2)
101/104
d
Enable/disable
IEC60870
Show Bad bad time quality Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.IndBadTmQ.setVal SPG BOOLEAN SP A 1
Time indication in 0-5-101/104(2)
101/104
events
IEC60870 Time stamp
EN Time 0=Short 24bit; Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.TmFrmSel.setVal Enum SP A 1 format 3 or 7
G Format 1=Full 56bit 0-5-101/104(2)
101/104 octet
IEC60870 Selects between
EN Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.EvtTmMod.setVal Enum SP A 1 Time Zone UTC/Local 0=Local; 1=UTC
G 0-5-101/104(2)
101/104 time
Event buffer
IEC60870
EN Overflow overflow 0=Oldest+indication Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.EvtBufMod.setVal Enum SP A 0
G Mode handling ; 1=Keep newest 0-5-101/104(2)
101/104
mechanism

108
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

IEC60870 Counter
EN Counter 0=Read by master; Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.CntRpMod.setVal Enum SP A 0 reporting after
G Reporting 1=Spontaneous 0-5-101/104(2)
101/104 freeze
Freezing mode
IEC60870 0=Not in use;
EN Freeze for externally Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.CntFrzMod.setVal Enum SP A 0 1=Freeze only;
G mode triggered 0-5-101/104(2)
101/104 2=Freeze and Reset
integrated totals
IEC60870 IEC60870-5-
TX window Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.TxWinWid.setVal ING INT32 SP A 12 104 transmit 1...20
(k) 0-5-101/104(2)
101/104 window (k)
IEC60870 RX IEC60870-5-
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.RxWinWid.setVal ING INT32 SP A 8 window 104 receive 1...20
0-5-101/104(2)
101/104 (w) window (w)
IEC60870 IEC60870-5-
TX timeout Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.Tm1Tmms.setVal ING INT32 SP A 30000 104 transmit 1...60000 ms
(t1) 0-5-101/104(2)
101/104 timeout (t1)
IEC60870 IEC60870-5-
RX timeout Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.Tm2Tmms.setVal ING INT32 SP A 10000 104 receive 1...60000 ms
(t2) 0-5-101/104(2)
101/104 timeout (t1)
IEC60870 IEC60870-5-
Test Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.Tm3Tmms.setVal ING INT32 SP A 20000 104 link test 1...60000 ms
interval (t3) 0-5-101/104(2)
101/104 interval (t3)
Overflow
IEC60870 indication
ED2, Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.OvIndAddrGI.setVal ING INT32 SP 60000 I1 OvInd IOA address for 0...16777215
A 0-5-101/104(2)
101/104 interrogated
data
Overflow
IEC60870 indication
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.OvIndAdrGI.setVal ING INT32 SP ED1 60000 I1 OvInd IOA address for 0...16777215
0-5-101/104(2)
101/104 interrogated
data
Overflow
IEC60870 indication
OvInd Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.OvIndAddr.setVal ING INT32 SP A 60000 address for non- 0...16777215
NoGI IOA 0-5-101/104(2)
101/104 interrogated
data
Selection
IEC60870
Selection timeout for Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.SelTms.setVal ING INT32 SP A 30 1...65 s
Timeout control SBO 0-5-101/104(2)
101/104
operations
IEC60870
Cyclical Cyclical period Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.CycPer.setVal ING INT32 SP A 10 1...604800 s
Period in seconds 0-5-101/104(2)
101/104
Special mode
for masters that
IEC60870
Inverted require inverted Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.InvDIR.setVal SPG BOOLEAN SP A 0
DIR bit DIR bit on 0-5-101/104(2)
101/104
Balanced
IEC101 line. If
109
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

enabled, this
protocol
instance will be
non-compliant
with the IEC
60870-5-101
standard.
IEC60870
VisString25 IP address of Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.CliIP.setVal VSG SP ED2,B 0.0.0.0 I1 ClientIP
5 (20) the client 0-5-101/104(2)
101/104
IEC60870
EN VisString25 IP address of Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.CommPort.eIp EX ED1 0.0.0.0 I1 ClientIP
G 5 (20) the client 0-5-101/104(2)
101/104
Maximum
IEC60870 delay for
Command Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.CmdDl.setVal ING INT32 SP B 5000 timestamped 0...65535 ms
delay 0-5-101/104(2)
101/104 commands in
milliseconds.
IEC60870
Mapping Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT2.MapSel.setVal ING INT32 SP A,C 1 Mapping select 1...2
select 0-5-101/104(2)
101/104
IEC60870
VisString25 D
-5- VER LD0.I5CLPRT2.NamPlt.swRev LPL F1 (Name plate)
5 (20) C
101/104

IEC60870-5-101/104: IEC60870-5-101/104: F1
IEC Channe
IEC ANS Categor CD Acces Defaul Datase Even CM Parameter
6061 IECName Type FC Parameter desc Parameter range Menu path l
61850 I y C s t t t T name
7 relation
IEC60870 Control point
C Configuration\Communication\Protocols\IEC6087
-5- INP LD0.I5CLPRT3.ITotFrz.Oper.ctlVal SPC BOOLEAN A 0 I1 IT_FRZ for freezing
O 0-5-101/104(3)
101/104 integrated totals
IEC60870
Monitoring\Communication\Protocols\IEC60870-
-5- OUT LD0.I5CLPRT3.ChLiv.stVal SPS BOOLEAN ST B I1 STATUS Status
5-101/104(3)
101/104
IEC60870 Control point
C Configuration\Communication\Protocols\IEC6087
-5- CTR LD0.I5CLPRT3.ITotFrz.Oper.ctlVal SPC BOOLEAN A 0 I1 IT_FRZ for freezing
O 0-5-101/104(3)
101/104 integrated totals
IEC60870
C Reset Monitoring\Communication\Protocols\IEC60870-
-5- CTR LD0.I5CLPRT3.CntRs.Oper.ctlVal SPC BOOLEAN B 0 I1 Reset counters
O counters 5-101/104(3)
101/104
IEC60870
Received Received Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT3.FrRxCnt.stVal INS INT32 ST B I1 -1...2147483646
frames frames 5-101/104(3)
101/104
IEC60870
Link layer Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT3.LnkErrCnt.stVal INS INT32 ST B I1 Link errors -1...2147483646
errors 5-101/104(3)
101/104

110
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

IEC60870
Physical Physical layer Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT3.PhyErrCnt.stVal INS INT32 ST B I1 -1...2147483646
errors errors 5-101/104(3)
101/104
IEC60870
Transport Transport layer Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT3.TranErrCnt.stVal INS INT32 ST B I1 -1...2147483646
errors errors 5-101/104(3)
101/104
IEC60870
Transmitte Transmitted Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT3.FrTxCnt.stVal INS INT32 ST B I1 -1...2147483646
d frames frames 5-101/104(3)
101/104
Number of
IEC60870 rejected
CnReject Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT3.ConnRejSck.stVal INS INT32 ST B I1 connections due -1...2147483646
no sockets 5-101/104(3)
101/104 to no sockets
available
Connection
IEC60870 CnReject
rejected due to Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT3.ConnRejRg.stVal INS INT32 ST B I1 unregistere -1...2147483646
unregistered 5-101/104(3)
101/104 d
client
IEC60870
C Reset Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT3.CntRs.Oper.ctlVal SPC BOOLEAN B 0 I1 Reset counters
O counters 5-101/104(3)
101/104
Selects if this
IEC60870 protocol
C Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.Mod.Oper.ctlVal ENC Enum B,C,I 5 Operation instance is 1=on; 5=off
O 0-5-101/104(3)
101/104 enabled or
disabled
IEC60870
EN 3=IEC104 - Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.CommPort.setVal Enum SP B,C 3 Port Port selection
G Ethernet 0-5-101/104(3)
101/104
IEC60870 Frame start
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.StrFrDl.setVal ING INT32 SP A 4 Start Delay delay for serial 0...20 char
0-5-101/104(3)
101/104 communication
IEC60870 Frame end
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.EndFrDl.setVal ING INT32 SP A 4 End Delay delay for serial 0...20 char
0-5-101/104(3)
101/104 communication
IEC60870 Control point
C Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.ITotFrz.Oper.ctlVal SPC BOOLEAN A 0 I1 IT_FRZ for freezing
O 0-5-101/104(3)
101/104 integrated totals
IEC60870
Device Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.DevAddr.setVal ING INT32 SP B 1 Device address 1...65535
Address 0-5-101/104(3)
101/104
IEC60870 Common
ASDU Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.ASDUAddr.setVal ING INT32 SP B 1 address of 1...65535
Address 0-5-101/104(3)
101/104 ASDU
IEC60870
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.TCPPort.setVal ING INT32 SP A,C 2404 TCP Port Server TCP port 0...65535
0-5-101/104(3)
101/104

111
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

IEC60870
EN Link mode 0=Balanced; Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.LnkMod.setVal Enum SP B 0 Link Mode
G setting 1=Unbalanced 0-5-101/104(3)
101/104
IEC60870 Cause of
COT Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.COTLen.setVal ING INT32 SP B 2 transmission 1...2
Length 0-5-101/104(3)
101/104 length
IEC60870 Information
IOA Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.IOALen.setVal ING INT32 SP B 3 Object Address 1...3
Length 0-5-101/104(3)
101/104 length
IEC60870 Link
Link Address Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.LnkAddrLen.setVal ING INT32 SP B 2 Address 1...2
Length 0-5-101/104(3)
101/104 Length
IEC60870 ASDU
LD0.I5CLPRT3.ASDUAddrLen.setV ASDU Address Configuration\Communication\Protocols\IEC6087
-5- CFG ING INT32 SP ED2,B 2 I1 Address 1...2
al Length 0-5-101/104(3)
101/104 Length
IEC60870 ASDU
ASDU Address Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.ASDUAdrLen.setVal ING INT32 SP ED1 2 I1 Address 1...2
Length 0-5-101/104(3)
101/104 Length
Single character
IEC60870
Single Char response Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.SglCharRsp.setVal SPG BOOLEAN SP A 0
Resp enabled/disable 0-5-101/104(3)
101/104
d
Enable/disable
IEC60870
Show Bad bad time quality Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.IndBadTmQ.setVal SPG BOOLEAN SP A 1
Time indication in 0-5-101/104(3)
101/104
events
IEC60870 Time stamp
EN Time 0=Short 24bit; Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.TmFrmSel.setVal Enum SP A 1 format 3 or 7
G Format 1=Full 56bit 0-5-101/104(3)
101/104 octet
IEC60870 Selects between
EN Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.EvtTmMod.setVal Enum SP A 1 Time Zone UTC/Local 0=Local; 1=UTC
G 0-5-101/104(3)
101/104 time
Event buffer
IEC60870
EN Overflow overflow 0=Oldest+indication Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.EvtBufMod.setVal Enum SP A 0
G Mode handling ; 1=Keep newest 0-5-101/104(3)
101/104
mechanism
IEC60870 Counter
EN Counter 0=Read by master; Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.CntRpMod.setVal Enum SP A 0 reporting after
G Reporting 1=Spontaneous 0-5-101/104(3)
101/104 freeze
Freezing mode
IEC60870 0=Not in use;
EN Freeze for externally Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.CntFrzMod.setVal Enum SP A 0 1=Freeze only;
G mode triggered 0-5-101/104(3)
101/104 2=Freeze and Reset
integrated totals
IEC60870 IEC60870-5-
TX window Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.TxWinWid.setVal ING INT32 SP A 12 104 transmit 1...20
(k) 0-5-101/104(3)
101/104 window (k)
IEC60870 RX IEC60870-5-
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.RxWinWid.setVal ING INT32 SP A 8 window 104 receive 1...20
0-5-101/104(3)
101/104 (w) window (w)
112
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

IEC60870 IEC60870-5-
TX timeout Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.Tm1Tmms.setVal ING INT32 SP A 30000 104 transmit 1...60000 ms
(t1) 0-5-101/104(3)
101/104 timeout (t1)
IEC60870 IEC60870-5-
RX timeout Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.Tm2Tmms.setVal ING INT32 SP A 10000 104 receive 1...60000 ms
(t2) 0-5-101/104(3)
101/104 timeout (t1)
IEC60870 IEC60870-5-
Test Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.Tm3Tmms.setVal ING INT32 SP A 20000 104 link test 1...60000 ms
interval (t3) 0-5-101/104(3)
101/104 interval (t3)
Overflow
IEC60870 indication
ED2, Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.OvIndAddrGI.setVal ING INT32 SP 60000 I1 OvInd IOA address for 0...16777215
A 0-5-101/104(3)
101/104 interrogated
data
Overflow
IEC60870 indication
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.OvIndAdrGI.setVal ING INT32 SP ED1 60000 I1 OvInd IOA address for 0...16777215
0-5-101/104(3)
101/104 interrogated
data
Overflow
IEC60870 indication
OvInd Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.OvIndAddr.setVal ING INT32 SP A 60000 address for non- 0...16777215
NoGI IOA 0-5-101/104(3)
101/104 interrogated
data
Selection
IEC60870
Selection timeout for Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.SelTms.setVal ING INT32 SP A 30 1...65 s
Timeout control SBO 0-5-101/104(3)
101/104
operations
IEC60870
Cyclical Cyclical period Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.CycPer.setVal ING INT32 SP A 10 1...604800 s
Period in seconds 0-5-101/104(3)
101/104
Special mode
for masters that
require inverted
DIR bit on
Balanced
IEC60870 IEC101 line. If
Inverted Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.InvDIR.setVal SPG BOOLEAN SP A 0 enabled, this
DIR bit 0-5-101/104(3)
101/104 protocol
instance will be
non-compliant
with the IEC
60870-5-101
standard.
IEC60870
VisString25 IP address of Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.CliIP.setVal VSG SP ED2,B 0.0.0.0 I1 ClientIP
5 (20) the client 0-5-101/104(3)
101/104
IEC60870
EN VisString25 IP address of Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.CommPort.eIp EX ED1 0.0.0.0 I1 ClientIP
G 5 (20) the client 0-5-101/104(3)
101/104

113
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Maximum
IEC60870 delay for
Command Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.CmdDl.setVal ING INT32 SP B 5000 timestamped 0...65535 ms
delay 0-5-101/104(3)
101/104 commands in
milliseconds.
IEC60870
Mapping Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT3.MapSel.setVal ING INT32 SP A,C 1 Mapping select 1...2
select 0-5-101/104(3)
101/104
IEC60870
VisString25 D
-5- VER LD0.I5CLPRT3.NamPlt.swRev LPL F1 (Name plate)
5 (20) C
101/104

IEC60870-5-101/104: IEC60870-5-101/104: F1
IEC Channe
IEC ANS Categor CD Acces Defaul Datase Even CM Parameter
6061 IECName Type FC Parameter desc Parameter range Menu path l
61850 I y C s t t t T name
7 relation
IEC60870 Control point
C Configuration\Communication\Protocols\IEC6087
-5- INP LD0.I5CLPRT4.ITotFrz.Oper.ctlVal SPC BOOLEAN A 0 I1 IT_FRZ for freezing
O 0-5-101/104(4)
101/104 integrated totals
IEC60870
Monitoring\Communication\Protocols\IEC60870-
-5- OUT LD0.I5CLPRT4.ChLiv.stVal SPS BOOLEAN ST B I1 STATUS Status
5-101/104(4)
101/104
IEC60870 Control point
C Configuration\Communication\Protocols\IEC6087
-5- CTR LD0.I5CLPRT4.ITotFrz.Oper.ctlVal SPC BOOLEAN A 0 I1 IT_FRZ for freezing
O 0-5-101/104(4)
101/104 integrated totals
IEC60870
C Reset Monitoring\Communication\Protocols\IEC60870-
-5- CTR LD0.I5CLPRT4.CntRs.Oper.ctlVal SPC BOOLEAN B 0 I1 Reset counters
O counters 5-101/104(4)
101/104
IEC60870
Received Received Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT4.FrRxCnt.stVal INS INT32 ST B I1 -1...2147483646
frames frames 5-101/104(4)
101/104
IEC60870
Link layer Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT4.LnkErrCnt.stVal INS INT32 ST B I1 Link errors -1...2147483646
errors 5-101/104(4)
101/104
IEC60870
Physical Physical layer Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT4.PhyErrCnt.stVal INS INT32 ST B I1 -1...2147483646
errors errors 5-101/104(4)
101/104
IEC60870
Transport Transport layer Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT4.TranErrCnt.stVal INS INT32 ST B I1 -1...2147483646
errors errors 5-101/104(4)
101/104
IEC60870
Transmitte Transmitted Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT4.FrTxCnt.stVal INS INT32 ST B I1 -1...2147483646
d frames frames 5-101/104(4)
101/104
IEC60870 Number of
CnReject Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT4.ConnRejSck.stVal INS INT32 ST B I1 rejected -1...2147483646
no sockets 5-101/104(4)
101/104 connections due

114
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

to no sockets
available
Connection
IEC60870 CnReject
rejected due to Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT4.ConnRejRg.stVal INS INT32 ST B I1 unregistere -1...2147483646
unregistered 5-101/104(4)
101/104 d
client
IEC60870
C Reset Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT4.CntRs.Oper.ctlVal SPC BOOLEAN B 0 I1 Reset counters
O counters 5-101/104(4)
101/104
Selects if this
IEC60870 protocol
C Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.Mod.Oper.ctlVal ENC Enum B,C,I 5 Operation instance is 1=on; 5=off
O 0-5-101/104(4)
101/104 enabled or
disabled
IEC60870
EN 3=IEC104 - Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.CommPort.setVal Enum SP B,C 3 Port Port selection
G Ethernet 0-5-101/104(4)
101/104
IEC60870 Frame start
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.StrFrDl.setVal ING INT32 SP A 4 Start Delay delay for serial 0...20 char
0-5-101/104(4)
101/104 communication
IEC60870 Frame end
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.EndFrDl.setVal ING INT32 SP A 4 End Delay delay for serial 0...20 char
0-5-101/104(4)
101/104 communication
IEC60870 Control point
C Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.ITotFrz.Oper.ctlVal SPC BOOLEAN A 0 I1 IT_FRZ for freezing
O 0-5-101/104(4)
101/104 integrated totals
IEC60870
Device Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.DevAddr.setVal ING INT32 SP B 1 Device address 1...65535
Address 0-5-101/104(4)
101/104
IEC60870 Common
ASDU Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.ASDUAddr.setVal ING INT32 SP B 1 address of 1...65535
Address 0-5-101/104(4)
101/104 ASDU
IEC60870
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.TCPPort.setVal ING INT32 SP A,C 2404 TCP Port Server TCP port 0...65535
0-5-101/104(4)
101/104
IEC60870
EN Link mode 0=Balanced; Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.LnkMod.setVal Enum SP B 0 Link Mode
G setting 1=Unbalanced 0-5-101/104(4)
101/104
IEC60870 Cause of
COT Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.COTLen.setVal ING INT32 SP B 2 transmission 1...2
Length 0-5-101/104(4)
101/104 length
IEC60870 Information
IOA Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.IOALen.setVal ING INT32 SP B 3 Object Address 1...3
Length 0-5-101/104(4)
101/104 length
IEC60870 Link
Link Address Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.LnkAddrLen.setVal ING INT32 SP B 2 Address 1...2
Length 0-5-101/104(4)
101/104 Length

115
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

IEC60870 ASDU
LD0.I5CLPRT4.ASDUAddrLen.setV ASDU Address Configuration\Communication\Protocols\IEC6087
-5- CFG ING INT32 SP ED2,B 2 I1 Address 1...2
al Length 0-5-101/104(4)
101/104 Length
IEC60870 ASDU
ASDU Address Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.ASDUAdrLen.setVal ING INT32 SP ED1 2 I1 Address 1...2
Length 0-5-101/104(4)
101/104 Length
Single character
IEC60870
Single Char response Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.SglCharRsp.setVal SPG BOOLEAN SP A 0
Resp enabled/disable 0-5-101/104(4)
101/104
d
Enable/disable
IEC60870
Show Bad bad time quality Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.IndBadTmQ.setVal SPG BOOLEAN SP A 1
Time indication in 0-5-101/104(4)
101/104
events
IEC60870 Time stamp
EN Time 0=Short 24bit; Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.TmFrmSel.setVal Enum SP A 1 format 3 or 7
G Format 1=Full 56bit 0-5-101/104(4)
101/104 octet
IEC60870 Selects between
EN Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.EvtTmMod.setVal Enum SP A 1 Time Zone UTC/Local 0=Local; 1=UTC
G 0-5-101/104(4)
101/104 time
Event buffer
IEC60870
EN Overflow overflow 0=Oldest+indication Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.EvtBufMod.setVal Enum SP A 0
G Mode handling ; 1=Keep newest 0-5-101/104(4)
101/104
mechanism
IEC60870 Counter
EN Counter 0=Read by master; Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.CntRpMod.setVal Enum SP A 0 reporting after
G Reporting 1=Spontaneous 0-5-101/104(4)
101/104 freeze
Freezing mode
IEC60870 0=Not in use;
EN Freeze for externally Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.CntFrzMod.setVal Enum SP A 0 1=Freeze only;
G mode triggered 0-5-101/104(4)
101/104 2=Freeze and Reset
integrated totals
IEC60870 IEC60870-5-
TX window Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.TxWinWid.setVal ING INT32 SP A 12 104 transmit 1...20
(k) 0-5-101/104(4)
101/104 window (k)
IEC60870 RX IEC60870-5-
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.RxWinWid.setVal ING INT32 SP A 8 window 104 receive 1...20
0-5-101/104(4)
101/104 (w) window (w)
IEC60870 IEC60870-5-
TX timeout Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.Tm1Tmms.setVal ING INT32 SP A 30000 104 transmit 1...60000 ms
(t1) 0-5-101/104(4)
101/104 timeout (t1)
IEC60870 IEC60870-5-
RX timeout Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.Tm2Tmms.setVal ING INT32 SP A 10000 104 receive 1...60000 ms
(t2) 0-5-101/104(4)
101/104 timeout (t1)
IEC60870 IEC60870-5-
Test Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.Tm3Tmms.setVal ING INT32 SP A 20000 104 link test 1...60000 ms
interval (t3) 0-5-101/104(4)
101/104 interval (t3)
IEC60870 Overflow
ED2, Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.OvIndAddrGI.setVal ING INT32 SP 60000 I1 OvInd IOA indication 0...16777215
A 0-5-101/104(4)
101/104 address for
116
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

interrogated
data
Overflow
IEC60870 indication
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.OvIndAdrGI.setVal ING INT32 SP ED1 60000 I1 OvInd IOA address for 0...16777215
0-5-101/104(4)
101/104 interrogated
data
Overflow
IEC60870 indication
OvInd Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.OvIndAddr.setVal ING INT32 SP A 60000 address for non- 0...16777215
NoGI IOA 0-5-101/104(4)
101/104 interrogated
data
Selection
IEC60870
Selection timeout for Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.SelTms.setVal ING INT32 SP A 30 1...65 s
Timeout control SBO 0-5-101/104(4)
101/104
operations
IEC60870
Cyclical Cyclical period Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.CycPer.setVal ING INT32 SP A 10 1...604800 s
Period in seconds 0-5-101/104(4)
101/104
Special mode
for masters that
require inverted
DIR bit on
Balanced
IEC60870 IEC101 line. If
Inverted Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.InvDIR.setVal SPG BOOLEAN SP A 0 enabled, this
DIR bit 0-5-101/104(4)
101/104 protocol
instance will be
non-compliant
with the IEC
60870-5-101
standard.
IEC60870
VisString25 IP address of Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.CliIP.setVal VSG SP ED2,B 0.0.0.0 I1 ClientIP
5 (20) the client 0-5-101/104(4)
101/104
IEC60870
EN VisString25 IP address of Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.CommPort.eIp EX ED1 0.0.0.0 I1 ClientIP
G 5 (20) the client 0-5-101/104(4)
101/104
Maximum
IEC60870 delay for
Command Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.CmdDl.setVal ING INT32 SP B 5000 timestamped 0...65535 ms
delay 0-5-101/104(4)
101/104 commands in
milliseconds.
IEC60870
Mapping Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT4.MapSel.setVal ING INT32 SP A,C 1 Mapping select 1...2
select 0-5-101/104(4)
101/104
IEC60870
VisString25 D
-5- VER LD0.I5CLPRT4.NamPlt.swRev LPL F1 (Name plate)
5 (20) C
101/104

117
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

IEC60870-5-101/104: IEC60870-5-101/104: F1
IEC Channe
IEC ANS Categor CD Acces Defaul Datase Even CM Parameter
6061 IECName Type FC Parameter desc Parameter range Menu path l
61850 I y C s t t t T name
7 relation
IEC60870 Control point
C Configuration\Communication\Protocols\IEC6087
-5- INP LD0.I5CLPRT5.ITotFrz.Oper.ctlVal SPC BOOLEAN A 0 I1 IT_FRZ for freezing
O 0-5-101/104(5)
101/104 integrated totals
IEC60870
Monitoring\Communication\Protocols\IEC60870-
-5- OUT LD0.I5CLPRT5.ChLiv.stVal SPS BOOLEAN ST B I1 STATUS Status
5-101/104(5)
101/104
IEC60870 Control point
C Configuration\Communication\Protocols\IEC6087
-5- CTR LD0.I5CLPRT5.ITotFrz.Oper.ctlVal SPC BOOLEAN A 0 I1 IT_FRZ for freezing
O 0-5-101/104(5)
101/104 integrated totals
IEC60870
C Reset Monitoring\Communication\Protocols\IEC60870-
-5- CTR LD0.I5CLPRT5.CntRs.Oper.ctlVal SPC BOOLEAN B 0 I1 Reset counters
O counters 5-101/104(5)
101/104
IEC60870
Received Received Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT5.FrRxCnt.stVal INS INT32 ST B I1 -1...2147483646
frames frames 5-101/104(5)
101/104
IEC60870
Link layer Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT5.LnkErrCnt.stVal INS INT32 ST B I1 Link errors -1...2147483646
errors 5-101/104(5)
101/104
IEC60870
Physical Physical layer Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT5.PhyErrCnt.stVal INS INT32 ST B I1 -1...2147483646
errors errors 5-101/104(5)
101/104
IEC60870
Transport Transport layer Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT5.TranErrCnt.stVal INS INT32 ST B I1 -1...2147483646
errors errors 5-101/104(5)
101/104
IEC60870
Transmitte Transmitted Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT5.FrTxCnt.stVal INS INT32 ST B I1 -1...2147483646
d frames frames 5-101/104(5)
101/104
Number of
IEC60870 rejected
CnReject Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT5.ConnRejSck.stVal INS INT32 ST B I1 connections due -1...2147483646
no sockets 5-101/104(5)
101/104 to no sockets
available
Connection
IEC60870 CnReject
rejected due to Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT5.ConnRejRg.stVal INS INT32 ST B I1 unregistere -1...2147483646
unregistered 5-101/104(5)
101/104 d
client
IEC60870
C Reset Monitoring\Communication\Protocols\IEC60870-
-5- MON LD0.I5CLPRT5.CntRs.Oper.ctlVal SPC BOOLEAN B 0 I1 Reset counters
O counters 5-101/104(5)
101/104
IEC60870 Selects if this
C Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.Mod.Oper.ctlVal ENC Enum B,C,I 5 Operation protocol 1=on; 5=off
O 0-5-101/104(5)
101/104 instance is

118
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

enabled or
disabled
IEC60870
EN 3=IEC104 - Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.CommPort.setVal Enum SP B,C 3 Port Port selection
G Ethernet 0-5-101/104(5)
101/104
IEC60870 Frame start
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.StrFrDl.setVal ING INT32 SP A 4 Start Delay delay for serial 0...20 char
0-5-101/104(5)
101/104 communication
IEC60870 Frame end
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.EndFrDl.setVal ING INT32 SP A 4 End Delay delay for serial 0...20 char
0-5-101/104(5)
101/104 communication
IEC60870 Control point
C Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.ITotFrz.Oper.ctlVal SPC BOOLEAN A 0 I1 IT_FRZ for freezing
O 0-5-101/104(5)
101/104 integrated totals
IEC60870
Device Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.DevAddr.setVal ING INT32 SP B 1 Device address 1...65535
Address 0-5-101/104(5)
101/104
IEC60870 Common
ASDU Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.ASDUAddr.setVal ING INT32 SP B 1 address of 1...65535
Address 0-5-101/104(5)
101/104 ASDU
IEC60870
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.TCPPort.setVal ING INT32 SP A,C 2404 TCP Port Server TCP port 0...65535
0-5-101/104(5)
101/104
IEC60870
EN Link mode 0=Balanced; Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.LnkMod.setVal Enum SP B 0 Link Mode
G setting 1=Unbalanced 0-5-101/104(5)
101/104
IEC60870 Cause of
COT Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.COTLen.setVal ING INT32 SP B 2 transmission 1...2
Length 0-5-101/104(5)
101/104 length
IEC60870 Information
IOA Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.IOALen.setVal ING INT32 SP B 3 Object Address 1...3
Length 0-5-101/104(5)
101/104 length
IEC60870 Link
Link Address Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.LnkAddrLen.setVal ING INT32 SP B 2 Address 1...2
Length 0-5-101/104(5)
101/104 Length
IEC60870 ASDU
LD0.I5CLPRT5.ASDUAddrLen.setV ASDU Address Configuration\Communication\Protocols\IEC6087
-5- CFG ING INT32 SP ED2,B 2 I1 Address 1...2
al Length 0-5-101/104(5)
101/104 Length
IEC60870 ASDU
ASDU Address Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.ASDUAdrLen.setVal ING INT32 SP ED1 2 I1 Address 1...2
Length 0-5-101/104(5)
101/104 Length
Single character
IEC60870
Single Char response Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.SglCharRsp.setVal SPG BOOLEAN SP A 0
Resp enabled/disable 0-5-101/104(5)
101/104
d
Enable/disable
IEC60870
Show Bad bad time quality Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.IndBadTmQ.setVal SPG BOOLEAN SP A 1
Time indication in 0-5-101/104(5)
101/104
events
119
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

IEC60870 Time stamp


EN Time 0=Short 24bit; Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.TmFrmSel.setVal Enum SP A 1 format 3 or 7
G Format 1=Full 56bit 0-5-101/104(5)
101/104 octet
IEC60870 Selects between
EN Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.EvtTmMod.setVal Enum SP A 1 Time Zone UTC/Local 0=Local; 1=UTC
G 0-5-101/104(5)
101/104 time
Event buffer
IEC60870
EN Overflow overflow 0=Oldest+indication Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.EvtBufMod.setVal Enum SP A 0
G Mode handling ; 1=Keep newest 0-5-101/104(5)
101/104
mechanism
IEC60870 Counter
EN Counter 0=Read by master; Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.CntRpMod.setVal Enum SP A 0 reporting after
G Reporting 1=Spontaneous 0-5-101/104(5)
101/104 freeze
Freezing mode
IEC60870 0=Not in use;
EN Freeze for externally Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.CntFrzMod.setVal Enum SP A 0 1=Freeze only;
G mode triggered 0-5-101/104(5)
101/104 2=Freeze and Reset
integrated totals
IEC60870 IEC60870-5-
TX window Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.TxWinWid.setVal ING INT32 SP A 12 104 transmit 1...20
(k) 0-5-101/104(5)
101/104 window (k)
IEC60870 RX IEC60870-5-
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.RxWinWid.setVal ING INT32 SP A 8 window 104 receive 1...20
0-5-101/104(5)
101/104 (w) window (w)
IEC60870 IEC60870-5-
TX timeout Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.Tm1Tmms.setVal ING INT32 SP A 30000 104 transmit 1...60000 ms
(t1) 0-5-101/104(5)
101/104 timeout (t1)
IEC60870 IEC60870-5-
RX timeout Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.Tm2Tmms.setVal ING INT32 SP A 10000 104 receive 1...60000 ms
(t2) 0-5-101/104(5)
101/104 timeout (t1)
IEC60870 IEC60870-5-
Test Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.Tm3Tmms.setVal ING INT32 SP A 20000 104 link test 1...60000 ms
interval (t3) 0-5-101/104(5)
101/104 interval (t3)
Overflow
IEC60870 indication
ED2, Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.OvIndAddrGI.setVal ING INT32 SP 60000 I1 OvInd IOA address for 0...16777215
A 0-5-101/104(5)
101/104 interrogated
data
Overflow
IEC60870 indication
Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.OvIndAdrGI.setVal ING INT32 SP ED1 60000 I1 OvInd IOA address for 0...16777215
0-5-101/104(5)
101/104 interrogated
data
Overflow
IEC60870 indication
OvInd Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.OvIndAddr.setVal ING INT32 SP A 60000 address for non- 0...16777215
NoGI IOA 0-5-101/104(5)
101/104 interrogated
data
IEC60870
Selection Selection Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.SelTms.setVal ING INT32 SP A 30 1...65 s
Timeout timeout for 0-5-101/104(5)
101/104
120
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

control SBO
operations
IEC60870
Cyclical Cyclical period Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.CycPer.setVal ING INT32 SP A 10 1...604800 s
Period in seconds 0-5-101/104(5)
101/104
Special mode
for masters that
require inverted
DIR bit on
Balanced
IEC60870 IEC101 line. If
Inverted Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.InvDIR.setVal SPG BOOLEAN SP A 0 enabled, this
DIR bit 0-5-101/104(5)
101/104 protocol
instance will be
non-compliant
with the IEC
60870-5-101
standard.
IEC60870
VisString25 IP address of Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.CliIP.setVal VSG SP ED2,B 0.0.0.0 I1 ClientIP
5 (20) the client 0-5-101/104(5)
101/104
IEC60870
EN VisString25 IP address of Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.CommPort.eIp EX ED1 0.0.0.0 I1 ClientIP
G 5 (20) the client 0-5-101/104(5)
101/104
Maximum
IEC60870 delay for
Command Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.CmdDl.setVal ING INT32 SP B 5000 timestamped 0...65535 ms
delay 0-5-101/104(5)
101/104 commands in
milliseconds.
IEC60870
Mapping Configuration\Communication\Protocols\IEC6087
-5- CFG LD0.I5CLPRT5.MapSel.setVal ING INT32 SP A,C 1 Mapping select 1...2
select 0-5-101/104(5)
101/104
IEC60870
VisString25 D
-5- VER LD0.I5CLPRT5.NamPlt.swRev LPL F1 (Name plate)
5 (20) C
101/104

PHLPTOC1: Three phase non-directional OC, low stage: F


IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
51P- (ACT input
PHLPTOC1 3I>(1) INP Channel I3P
1(1) channel)
Block signal
51P- for activating Monitoring\I/O status\Current
PHLPTOC1 3I>(1) INP LD0.PHLPTOC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
1(1) the blocking protection\PHLPTOC1\Inputs
mode
Enable signal
51P- Monitoring\I/O status\Current
PHLPTOC1 3I>(1) INP LD0.PHLPTOC1.InEnaMult.stVal SPS BOOLEAN ST B 0 I1 ENA_MULT for current
1(1) protection\PHLPTOC1\Inputs
multiplier
121
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

51P- Monitoring\I/O status\Current


PHLPTOC1 3I>(1) OUT LD0.PHLPTOC1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start (A,B,C)
1(1) protection\PHLPTOC1\Outputs
51P- Monitoring\I/O status\Current
PHLPTOC1 3I>(1) OUT LD0.PHLPTOC1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate (A,B,C)
1(1) protection\PHLPTOC1\Outputs
1=on; 2=blocked;
51P- 3=test; Monitoring\FB status\Current
PHLPTOC1 3I>(1) MON LD0.PHLPTOC1.Beh.stVal ENS Enum ST B PHLPTOC1 Status
1(1) 4=test/blocked; protection
5=off
Ratio of start Monitoring\I/O status\Current
51P-
PHLPTOC1 3I>(1) MON LD0.PHLPTOC1.StrDur.mag.f MV FLOAT32 MX B START_DUR time / operate 0.00...100.00 % protection\PHLPTOC1\Monitored
1(1)
time data
51P- Operation Off Settings\Settings\Current
PHLPTOC1 3I>(1) SET LD0.PHLPTOC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
1(1) / On protection\PHLPTOC1
1=ANSI Ext. inv.;
2=ANSI Very inv.;
3=ANSI Norm. inv.;
4=ANSI Mod. inv.;
5=ANSI Def. Time;
6=L.T.E. inv.;
7=L.T.V. inv.;
8=L.T. inv.; 9=IEC
Selection of Norm. inv.; 10=IEC
51P- Operating Settings\Settings\Current
PHLPTOC1 3I>(1) SET LD0.PHLPTOC1.TmACrv.setCharact CURVE Enum SG B,I 15 time delay Very inv.; 11=IEC
1(1) curve type protection\PHLPTOC1
curve type inv.; 12=IEC Ext.
inv.; 13=IEC S.T.
inv.; 14=IEC L.T.
inv.; 15=IEC Def.
Time;
17=Programmable;
18=RI type; 19=RD
type; 20=UK
rectifier
Parameter A
51P- Curve for customer Settings\Settings\Current
PHLPTOC1 3I>(1) SET LD0.PHLPTOC1.TmACrv.setParA CURVE FLOAT32 SP B,I 28.2000 0.0086...50000.0000
1(1) parameter A programmable protection\PHLPTOC1
curve
Parameter B
51P- Curve for customer Settings\Settings\Current
PHLPTOC1 3I>(1) SET LD0.PHLPTOC1.TmACrv.setParB CURVE FLOAT32 SP B,I 0.1217 0.0000...0.7120
1(1) parameter B programmable protection\PHLPTOC1
curve
Parameter C
51P- Curve for customer Settings\Settings\Current
PHLPTOC1 3I>(1) SET LD0.PHLPTOC1.TmACrv.setParC CURVE FLOAT32 SP B,I 2.00 0.02...6.00
1(1) parameter C programmable protection\PHLPTOC1
curve
Parameter D
51P- Curve for customer Settings\Settings\Current
PHLPTOC1 3I>(1) SET LD0.PHLPTOC1.TmACrv.setParD CURVE FLOAT32 SP B,I 29.10 0.46...30.00
1(1) parameter D programmable protection\PHLPTOC1
curve
51P- Curve Parameter E Settings\Settings\Current
PHLPTOC1 3I>(1) SET LD0.PHLPTOC1.TmACrv.setParE CURVE FLOAT32 SP B,I 1.0 0.0...1.0
1(1) parameter E for customer protection\PHLPTOC1

122
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

programmable
curve
51P- Settings\Settings\Current
PHLPTOC1 3I>(1) SET LD0.PHLPTOC1.StrVal.setMag.f ASG FLOAT32 SG B 0.05 Start value Start value 0.05...5.00 xIn IL1TCTR1
1(1) protection\PHLPTOC1
Time
51P- Time multiplier in Settings\Settings\Current
PHLPTOC1 3I>(1) SET LD0.PHLPTOC1.TmMult.setMag.f ASG FLOAT32 SG B 1.000 0.025...15.000
1(1) multiplier IEC/ANSI protection\PHLPTOC1
IDMT curves
Minimum
51P- Minimum operate time Settings\Settings\Current
PHLPTOC1 3I>(1) SET LD0.PHLPTOC1.MinOpTmms.setVal ING INT32 SP A 20 20...60000 ms
1(1) operate time for IDMT protection\PHLPTOC1
curves
51P- Operate delay Operate delay Settings\Settings\Current
PHLPTOC1 3I>(1) SET LD0.PHLPTOC1.OpDlTmms.setVal ING INT32 SG B 40 40...300000 ms
1(1) time time protection\PHLPTOC1
Selection of 1=Immediate;
51P- Type of reset Settings\Settings\Current
PHLPTOC1 3I>(1) SET LD0.PHLPTOC1.TypRsCrv.setVal ENG Enum SG A 1 reset curve 2=Def time reset;
1(1) curve protection\PHLPTOC1
type 3=Inverse reset
51P- Reset delay Reset delay Settings\Settings\Current
PHLPTOC1 3I>(1) SET LD0.PHLPTOC1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
1(1) time time protection\PHLPTOC1
Number of
phases 1=1 out of 3; 2=2
51P- Num of start Settings\Settings\Current
PHLPTOC1 3I>(1) SET LD0.PHLPTOC1.NumPh.setVal ENG Enum SP B 1 required for out of 3; 3=3 out of
1(1) phases protection\PHLPTOC1
operate 3
activation
Multiplier for
51P- Start value Settings\Settings\Current
PHLPTOC1 3I>(1) SET LD0.PHLPTOC1.StrValMult.setMag.f ASG FLOAT32 SG B 1.0 scaling the 0.8...10.0
1(1) Mult protection\PHLPTOC1
start value
Selects used
51P- Measurement 1=RMS; 2=DFT; Settings\Settings\Current
PHLPTOC1 3I>(1) SET LD0.PHLPTOC1.AMeasMod.setVal ENG Enum SP A 2 measurement
1(1) mode 3=Peak-to-Peak protection\PHLPTOC1
mode
0=Reset; 1=Activate
START; 2=Deactive
51P- Test control START; 9=Activate Tests\Function tests\Current
PHLPTOC1 3I>(1) TES LD0.PHLPTOC1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 PHLPTOC1
1(1) for outputs OPERATE; protection
10=Deactive
OPERATE
51P- VisString255
PHLPTOC1 3I>(1) VER LD0.PHLPTOC1.NamPlt.swRev LPL DC ED1 F (Name plate)
1(1) (20)

PHHPTOC1: Three phase non-directional OC, high stage: F1


IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
51P- (ACT input
PHHPTOC1 3I>>(1) INP Channel I3P
2(1) channel)
51P- Block signal Monitoring\I/O status\Current
PHHPTOC1 3I>>(1) INP LD0.PHHPTOC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
2(1) for activating protection\PHHPTOC1\Inputs

123
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

the blocking
mode
Enable signal
51P- Monitoring\I/O status\Current
PHHPTOC1 3I>>(1) INP LD0.PHHPTOC1.InEnaMult.stVal SPS BOOLEAN ST B 0 I1 ENA_MULT for current
2(1) protection\PHHPTOC1\Inputs
multiplier
51P- Monitoring\I/O status\Current
PHHPTOC1 3I>>(1) OUT LD0.PHHPTOC1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start (A,B,C)
2(1) protection\PHHPTOC1\Outputs
51P- Monitoring\I/O status\Current
PHHPTOC1 3I>>(1) OUT LD0.PHHPTOC1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate (A,B,C)
2(1) protection\PHHPTOC1\Outputs
1=on; 2=blocked;
51P- 3=test;
PHHPTOC1 3I>>(1) MON LD0.PHHPTOC1.Beh.stVal ENS Enum ST B PHHPTOC1 Status Monitoring\FB status
2(1) 4=test/blocked;
5=off
Ratio of start Monitoring\I/O status\Current
51P-
PHHPTOC1 3I>>(1) MON LD0.PHHPTOC1.StrDur.mag.f MV FLOAT32 MX B START_DUR time / operate 0.00...100.00 % protection\PHHPTOC1\Monitored
2(1)
time data
51P- Operation Off Settings\Settings\Current
PHHPTOC1 3I>>(1) SET LD0.PHHPTOC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
2(1) / On protection\PHHPTOC1
1=ANSI Ext. inv.;
3=ANSI Norm.
inv.; 5=ANSI Def.
Time; 9=IEC
Selection of
51P- Operating Norm. inv.; Settings\Settings\Current
PHHPTOC1 3I>>(1) SET LD0.PHHPTOC1.TmACrv.setCharact CURVE Enum SG B,I 15 time delay
2(1) curve type 10=IEC Very protection\PHHPTOC1
curve type
inv.; 12=IEC Ext.
inv.; 15=IEC Def.
Time;
17=Programmable
Parameter A
51P- Curve for customer Settings\Settings\Current
PHHPTOC1 3I>>(1) SET LD0.PHHPTOC1.TmACrv.setParA CURVE FLOAT32 SP B,I 28.2000 0.0086...120.0000
2(1) parameter A programmable protection\PHHPTOC1
curve
Parameter B
51P- Curve for customer Settings\Settings\Current
PHHPTOC1 3I>>(1) SET LD0.PHHPTOC1.TmACrv.setParB CURVE FLOAT32 SP B,I 0.1217 0.0000...0.7120
2(1) parameter B programmable protection\PHHPTOC1
curve
Parameter C
51P- Curve for customer Settings\Settings\Current
PHHPTOC1 3I>>(1) SET LD0.PHHPTOC1.TmACrv.setParC CURVE FLOAT32 SP B,I 2.00 0.02...2.00
2(1) parameter C programmable protection\PHHPTOC1
curve
Parameter D
51P- Curve for customer Settings\Settings\Current
PHHPTOC1 3I>>(1) SET LD0.PHHPTOC1.TmACrv.setParD CURVE FLOAT32 SP B,I 29.10 0.46...30.00
2(1) parameter D programmable protection\PHHPTOC1
curve
Parameter E
51P- Curve for customer Settings\Settings\Current
PHHPTOC1 3I>>(1) SET LD0.PHHPTOC1.TmACrv.setParE CURVE FLOAT32 SP B,I 1.0 0.0...1.0
2(1) parameter E programmable protection\PHHPTOC1
curve
51P- Settings\Settings\Current
PHHPTOC1 3I>>(1) SET LD0.PHHPTOC1.StrVal.setMag.f ASG FLOAT32 SG B 0.10 Start value Start value 0.10...40.00 xIn IL1TCTR1
2(1) protection\PHHPTOC1
124
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Time
51P- Time multiplier in Settings\Settings\Current
PHHPTOC1 3I>>(1) SET LD0.PHHPTOC1.TmMult.setMag.f ASG FLOAT32 SG B 1.000 0.025...15.0
2(1) multiplier IEC/ANSI protection\PHHPTOC1
IDMT curves
Minimum
51P- Minimum operate time Settings\Settings\Current
PHHPTOC1 3I>>(1) SET LD0.PHHPTOC1.MinOpTmms.setVal ING INT32 SP A 20 20...60000 ms
2(1) operate time for IDMT protection\PHHPTOC1
curves
51P- Operate delay Operate delay Settings\Settings\Current
PHHPTOC1 3I>>(1) SET LD0.PHHPTOC1.OpDlTmms.setVal ING INT32 SG B 40 40...200000 ms
2(1) time time protection\PHHPTOC1
Selection of 1=Immediate;
51P- Type of reset Settings\Settings\Current
PHHPTOC1 3I>>(1) SET LD0.PHHPTOC1.TypRsCrv.setVal ENG Enum SG A 1 reset curve 2=Def time reset;
2(1) curve protection\PHHPTOC1
type 3=Inverse reset
51P- Reset delay Reset delay Settings\Settings\Current
PHHPTOC1 3I>>(1) SET LD0.PHHPTOC1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
2(1) time time protection\PHHPTOC1
Number of
phases 1=1 out of 3; 2=2
51P- Num of start Settings\Settings\Current
PHHPTOC1 3I>>(1) SET LD0.PHHPTOC1.NumPh.setVal ENG Enum SP B 1 required for out of 3; 3=3 out
2(1) phases protection\PHHPTOC1
operate of 3
activation
Multiplier for
51P- Start value Settings\Settings\Current
PHHPTOC1 3I>>(1) SET LD0.PHHPTOC1.StrValMult.setMag.f ASG FLOAT32 SG B 1.0 scaling the 0.8...10.0
2(1) Mult protection\PHHPTOC1
start value
Selects used
51P- Measurement 1=RMS; 2=DFT; Settings\Settings\Current
PHHPTOC1 3I>>(1) SET LD0.PHHPTOC1.AMeasMod.setVal ENG Enum SP A 2 measurement
2(1) mode 3=Peak-to-Peak protection\PHHPTOC1
mode
0=Reset;
1=Activate
START;
2=Deactive
51P- Test control Tests\Function tests\Current
PHHPTOC1 3I>>(1) TES LD0.PHHPTOC1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 PHHPTOC1 START;
2(1) for outputs protection
9=Activate
OPERATE;
10=Deactive
OPERATE
51P- VisString255
PHHPTOC1 3I>>(1) VER LD0.PHHPTOC1.NamPlt.swRev LPL DC ED1 F1 (Name plate)
2(1) (20)

PHIPTOC1: Three phase non-directional OC, inst. stage: E1


IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
(ACT input
PHIPTOC1 3I>>>(1) 50P/51P(1) INP Channel I3P
channel)
Block
signal for Monitoring\I/O status\Current
PHIPTOC1 3I>>>(1) 50P/51P(1) INP LD0.PHIPTOC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
activating protection\PHIPTOC1\Inputs
the

125
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

blocking
mode
Enable
signal for Monitoring\I/O status\Current
PHIPTOC1 3I>>>(1) 50P/51P(1) INP LD0.PHIPTOC1.InEnaMult.stVal SPS BOOLEAN ST B 0 I1 ENA_MULT
current protection\PHIPTOC1\Inputs
multiplier
Monitoring\I/O status\Current
PHIPTOC1 3I>>>(1) 50P/51P(1) OUT LD0.PHIPTOC1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start (A,B,C)
protection\PHIPTOC1\Outputs
Monitoring\I/O status\Current
PHIPTOC1 3I>>>(1) 50P/51P(1) OUT LD0.PHIPTOC1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate (A,B,C)
protection\PHIPTOC1\Outputs
1=on; 2=blocked;
3=test;
PHIPTOC1 3I>>>(1) 50P/51P(1) MON LD0.PHIPTOC1.Beh.stVal ENS Enum ST B PHIPTOC1 Status Monitoring\FB status
4=test/blocked;
5=off
Ratio of
Monitoring\I/O status\Current
start time /
PHIPTOC1 3I>>>(1) 50P/51P(1) MON LD0.PHIPTOC1.StrDur.mag.f MV FLOAT32 MX B START_DUR 0.00...100.00 % protection\PHIPTOC1\Monitored
operate
data
time
Operation Settings\Settings\Current
PHIPTOC1 3I>>>(1) 50P/51P(1) SET LD0.PHIPTOC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
Off / On protection\PHIPTOC1
Settings\Settings\Current
PHIPTOC1 3I>>>(1) 50P/51P(1) SET LD0.PHIPTOC1.StrVal.setMag.f ASG FLOAT32 SG B 1.00 Start value Start value 1.00...40.00 xIn IL1TCTR1
protection\PHIPTOC1
Operate delay Operate Settings\Settings\Current
PHIPTOC1 3I>>>(1) 50P/51P(1) SET LD0.PHIPTOC1.OpDlTmms.setVal ING INT32 SG B 20 20...200000 ms
time delay time protection\PHIPTOC1
Reset delay Reset delay Settings\Settings\Current
PHIPTOC1 3I>>>(1) 50P/51P(1) SET LD0.PHIPTOC1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
time time protection\PHIPTOC1
Number of
phases 1=1 out of 3; 2=2
Num of start Settings\Settings\Current
PHIPTOC1 3I>>>(1) 50P/51P(1) SET LD0.PHIPTOC1.NumPh.setVal ENG Enum SP B 1 required out of 3; 3=3 out
phases protection\PHIPTOC1
for operate of 3
activation
Multiplier
Start value for scaling Settings\Settings\Current
PHIPTOC1 3I>>>(1) 50P/51P(1) SET LD0.PHIPTOC1.StrValMult.setMag.f ASG FLOAT32 SG B 1.0 0.8...10.0
Mult the start protection\PHIPTOC1
value
0=Reset;
1=Activate
START;
Test 2=Deactive
Tests\Function tests\Current
PHIPTOC1 3I>>>(1) 50P/51P(1) TES LD0.PHIPTOC1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 PHIPTOC1 control for START;
protection
outputs 9=Activate
OPERATE;
10=Deactive
OPERATE
VisString255 (Name
PHIPTOC1 3I>>>(1) 50P/51P(1) VER LD0.PHIPTOC1.NamPlt.swRev LPL DC ED1 E1
(20) plate)

EFLPTOC1: Non-directional earth-fault protection, low stage: G1


126
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

IEC Parameter Parameter Channel


IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
51N- (ACT input
EFLPTOC1 Io>(1) INP Channel IRES
1(1) channel)
Block signal
51N- for activating Monitoring\I/O status\Current
EFLPTOC1 Io>(1) INP LD0.EFLPTOC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
1(1) the blocking protection\EFLPTOC1\Inputs
mode
Enable signal
51N- Monitoring\I/O status\Current
EFLPTOC1 Io>(1) INP LD0.EFLPTOC1.InEnaMult.stVal SPS BOOLEAN ST B 0 I1 ENA_MULT for current
1(1) protection\EFLPTOC1\Inputs
multiplier
51N- Monitoring\I/O status\Current
EFLPTOC1 Io>(1) OUT LD0.EFLPTOC1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start
1(1) protection\EFLPTOC1\Outputs
51N- Monitoring\I/O status\Current
EFLPTOC1 Io>(1) OUT LD0.EFLPTOC1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate
1(1) protection\EFLPTOC1\Outputs
1=on; 2=blocked;
51N- 3=test;
EFLPTOC1 Io>(1) MON LD0.EFLPTOC1.Beh.stVal ENS Enum ST B EFLPTOC1 Status Monitoring\FB status
1(1) 4=test/blocked;
5=off
Ratio of start Monitoring\I/O status\Current
51N-
EFLPTOC1 Io>(1) MON LD0.EFLPTOC1.StrDur.mag.f MV FLOAT32 MX B START_DUR time / operate 0.00...100.00 % protection\EFLPTOC1\Monitored
1(1)
time data
51N- Operation Off Settings\Settings\Current
EFLPTOC1 Io>(1) SET LD0.EFLPTOC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
1(1) / On protection\EFLPTOC1
1=ANSI Ext. inv.;
2=ANSI Very inv.;
3=ANSI Norm.
inv.; 4=ANSI Mod.
inv.; 5=ANSI Def.
Time; 6=L.T.E.
inv.; 7=L.T.V. inv.;
8=L.T. inv.; 9=IEC
Selection of
51N- Operating Norm. inv.; 10=IEC Settings\Settings\Current
EFLPTOC1 Io>(1) SET LD0.EFLPTOC1.TmACrv.setCharact CURVE Enum SG B,I 15 time delay
1(1) curve type Very inv.; 11=IEC protection\EFLPTOC1
curve type
inv.; 12=IEC Ext.
inv.; 13=IEC S.T.
inv.; 14=IEC L.T.
inv.; 15=IEC Def.
Time;
17=Programmable;
18=RI type; 19=RD
type
Parameter A
51N- Curve for customer Settings\Settings\Current
EFLPTOC1 Io>(1) SET LD0.EFLPTOC1.TmACrv.setParA CURVE FLOAT32 SP B,I 28.2000 0.0086...120.0000
1(1) parameter A programmable protection\EFLPTOC1
curve
Parameter B
51N- Curve for customer Settings\Settings\Current
EFLPTOC1 Io>(1) SET LD0.EFLPTOC1.TmACrv.setParB CURVE FLOAT32 SP B,I 0.1217 0.0000...0.7120
1(1) parameter B programmable protection\EFLPTOC1
curve
127
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Parameter C
51N- Curve for customer Settings\Settings\Current
EFLPTOC1 Io>(1) SET LD0.EFLPTOC1.TmACrv.setParC CURVE FLOAT32 SP B,I 2.00 0.02...2.00
1(1) parameter C programmable protection\EFLPTOC1
curve
Parameter D
51N- Curve for customer Settings\Settings\Current
EFLPTOC1 Io>(1) SET LD0.EFLPTOC1.TmACrv.setParD CURVE FLOAT32 SP B,I 29.10 0.46...30.00
1(1) parameter D programmable protection\EFLPTOC1
curve
Parameter E
51N- Curve for customer Settings\Settings\Current
EFLPTOC1 Io>(1) SET LD0.EFLPTOC1.TmACrv.setParE CURVE FLOAT32 SP B,I 1.0 0.0...1.0
1(1) parameter E programmable protection\EFLPTOC1
curve
51N- Settings\Settings\Current
EFLPTOC1 Io>(1) SET LD0.EFLPTOC1.StrVal.setMag.f ASG FLOAT32 SG B 0.010 Start value Start value 0.010...5.000 xIn RESTCTR1
1(1) protection\EFLPTOC1
Time
51N- Time multiplier in Settings\Settings\Current
EFLPTOC1 Io>(1) SET LD0.EFLPTOC1.TmMult.setMag.f ASG FLOAT32 SG B 1.000 0.025...15.00
1(1) multiplier IEC/ANSI protection\EFLPTOC1
IDMT curves
Minimum
51N- Minimum operate time Settings\Settings\Current
EFLPTOC1 Io>(1) SET LD0.EFLPTOC1.MinOpTmms.setVal ING INT32 SP A 20 20...60000 ms
1(1) operate time for IDMT protection\EFLPTOC1
curves
51N- Operate delay Operate delay Settings\Settings\Current
EFLPTOC1 Io>(1) SET LD0.EFLPTOC1.OpDlTmms.setVal ING INT32 SG B 40 40...200000 ms
1(1) time time protection\EFLPTOC1
Selection of 1=Immediate;
51N- Type of reset Settings\Settings\Current
EFLPTOC1 Io>(1) SET LD0.EFLPTOC1.TypRsCrv.setVal ENG Enum SG A 1 reset curve 2=Def time reset;
1(1) curve protection\EFLPTOC1
type 3=Inverse reset
51N- Reset delay Reset delay Settings\Settings\Current
EFLPTOC1 Io>(1) SET LD0.EFLPTOC1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
1(1) time time protection\EFLPTOC1
Selects used
51N- Measurement 1=RMS; 2=DFT; Settings\Settings\Current
EFLPTOC1 Io>(1) SET LD0.EFLPTOC1.AMeasMod.setVal ENG Enum SP A 2 measurement
1(1) mode 3=Peak-to-Peak protection\EFLPTOC1
mode
Multiplier for
51N- Start value Settings\Settings\Current
EFLPTOC1 Io>(1) SET LD0.EFLPTOC1.StrValMult.setMag.f ASG FLOAT32 SG B 1.0 scaling the 0.8...10.0
1(1) Mult protection\EFLPTOC1
start value
0=Reset;
1=Activate START;
2=Deactive
51N- Test control Tests\Function tests\Current
EFLPTOC1 Io>(1) TES LD0.EFLPTOC1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 EFLPTOC1 START; 9=Activate
1(1) for outputs protection
OPERATE;
10=Deactive
OPERATE
51N- VisString255
EFLPTOC1 Io>(1) VER LD0.EFLPTOC1.NamPlt.swRev LPL DC ED1 G1 (Name plate)
1(1) (20)

EFHPTOC1: Non-directional earth-fault protection, high stage: F1

128
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

IEC Parameter Parameter Channel


IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
EFHPTOC 51N- (ACT input
Io>>(1) INP Channel IRES
1 2(1) channel)
Block signal
EFHPTOC 51N- for activating Monitoring\I/O status\Current
Io>>(1) INP LD0.EFHPTOC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
1 2(1) the blocking protection\EFHPTOC1\Inputs
mode
Enable signal
EFHPTOC 51N- Monitoring\I/O status\Current
Io>>(1) INP LD0.EFHPTOC1.InEnaMult.stVal SPS BOOLEAN ST B 0 I1 ENA_MULT for current
1 2(1) protection\EFHPTOC1\Inputs
multiplier
EFHPTOC 51N- Monitoring\I/O status\Current
Io>>(1) OUT LD0.EFHPTOC1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start
1 2(1) protection\EFHPTOC1\Outputs
EFHPTOC 51N- Monitoring\I/O status\Current
Io>>(1) OUT LD0.EFHPTOC1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate
1 2(1) protection\EFHPTOC1\Outputs
1=on; 2=blocked;
EFHPTOC 51N- 3=test;
Io>>(1) MON LD0.EFHPTOC1.Beh.stVal ENS Enum ST B EFHPTOC1 Status Monitoring\FB status
1 2(1) 4=test/blocked;
5=off
Ratio of start Monitoring\I/O status\Current
EFHPTOC 51N- START_DU
Io>>(1) MON LD0.EFHPTOC1.StrDur.mag.f MV FLOAT32 MX B time / operate 0.00...100.00 % protection\EFHPTOC1\Monitore
1 2(1) R
time d data
EFHPTOC 51N- Operation Off Settings\Settings\Current
Io>>(1) SET LD0.EFHPTOC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
1 2(1) / On protection\EFHPTOC1
1=ANSI Ext. inv.;
3=ANSI Norm.
inv.; 5=ANSI
Def. Time; 9=IEC
Selection of Norm. inv.;
EFHPTOC 51N- Operating Settings\Settings\Current
Io>>(1) SET LD0.EFHPTOC1.TmACrv.setCharact CURVE Enum SG B,I 15 time delay 10=IEC Very
1 2(1) curve type protection\EFHPTOC1
curve type inv.; 12=IEC Ext.
inv.; 15=IEC Def.
Time;
17=Programmabl
e
Parameter A
EFHPTOC 51N- Curve for customer Settings\Settings\Current
Io>>(1) SET LD0.EFHPTOC1.TmACrv.setParA CURVE FLOAT32 SP B,I 28.2000 0.0086...120.0000
1 2(1) parameter A programmabl protection\EFHPTOC1
e curve
Parameter B
EFHPTOC 51N- Curve for customer Settings\Settings\Current
Io>>(1) SET LD0.EFHPTOC1.TmACrv.setParB CURVE FLOAT32 SP B,I 0.1217 0.0000...0.7120
1 2(1) parameter B programmabl protection\EFHPTOC1
e curve
Parameter C
EFHPTOC 51N- Curve for customer Settings\Settings\Current
Io>>(1) SET LD0.EFHPTOC1.TmACrv.setParC CURVE FLOAT32 SP B,I 2.00 0.02...2.00
1 2(1) parameter C programmabl protection\EFHPTOC1
e curve
EFHPTOC 51N- Curve Parameter D Settings\Settings\Current
Io>>(1) SET LD0.EFHPTOC1.TmACrv.setParD CURVE FLOAT32 SP B,I 29.10 0.46...30.00
1 2(1) parameter D for customer protection\EFHPTOC1

129
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

programmabl
e curve
Parameter E
EFHPTOC 51N- Curve for customer Settings\Settings\Current
Io>>(1) SET LD0.EFHPTOC1.TmACrv.setParE CURVE FLOAT32 SP B,I 1.0 0.0...1.0
1 2(1) parameter E programmabl protection\EFHPTOC1
e curve
EFHPTOC 51N- Settings\Settings\Current RESTCTR
Io>>(1) SET LD0.EFHPTOC1.StrVal.setMag.f ASG FLOAT32 SG B 0.10 Start value Start value 0.10...40.00 xIn
1 2(1) protection\EFHPTOC1 1
Time
EFHPTOC 51N- Time multiplier in Settings\Settings\Current
Io>>(1) SET LD0.EFHPTOC1.TmMult.setMag.f ASG FLOAT32 SG B 1.000 0.025...15.00
1 2(1) multiplier IEC/ANSI protection\EFHPTOC1
IDMT curves
Minimum
EFHPTOC 51N- Minimum operate time Settings\Settings\Current
Io>>(1) SET LD0.EFHPTOC1.MinOpTmms.setVal ING INT32 SP A 20 20...60000 ms
1 2(1) operate time for IDMT protection\EFHPTOC1
curves
EFHPTOC 51N- Operate delay Operate delay Settings\Settings\Current
Io>>(1) SET LD0.EFHPTOC1.OpDlTmms.setVal ING INT32 SG B 40 40...200000 ms
1 2(1) time time protection\EFHPTOC1
Selection of 1=Immediate;
EFHPTOC 51N- Type of reset Settings\Settings\Current
Io>>(1) SET LD0.EFHPTOC1.TypRsCrv.setVal ENG Enum SG A 1 reset curve 2=Def time reset;
1 2(1) curve protection\EFHPTOC1
type 3=Inverse reset
EFHPTOC 51N- Reset delay Reset delay Settings\Settings\Current
Io>>(1) SET LD0.EFHPTOC1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
1 2(1) time time protection\EFHPTOC1
Selects used
EFHPTOC 51N- Measurement 1=RMS; 2=DFT; Settings\Settings\Current
Io>>(1) SET LD0.EFHPTOC1.AMeasMod.setVal ENG Enum SP A 2 measurement
1 2(1) mode 3=Peak-to-Peak protection\EFHPTOC1
mode
Multiplier for
EFHPTOC 51N- Start value Settings\Settings\Current
Io>>(1) SET LD0.EFHPTOC1.StrValMult.setMag.f ASG FLOAT32 SG B 1.0 scaling the 0.8...10.0
1 2(1) Mult protection\EFHPTOC1
start value
0=Reset;
1=Activate
START;
2=Deactive
EFHPTOC 51N- LD0.EFHPTOC1.TstOutCmd.Oper.ctlVa Test control Tests\Function tests\Current
Io>>(1) TES ENC Enum CO B 0 EFHPTOC1 START;
1 2(1) l for outputs protection
9=Activate
OPERATE;
10=Deactive
OPERATE
EFHPTOC 51N- VisString25
Io>>(1) VER LD0.EFHPTOC1.NamPlt.swRev LPL DC ED1 F1 (Name plate)
1 2(1) 5 (20)

EFIPTOC1: Non-directional earth-fault protection, inst. stage: F1


IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
(ACT
EFIPTOC1 Io>>>(1) 50N/51N(1) INP Channel IRES input
channel)
130
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Block
signal for
activating Monitoring\I/O status\Current
EFIPTOC1 Io>>>(1) 50N/51N(1) INP LD0.EFIPTOC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
the protection\EFIPTOC1\Inputs
blocking
mode
Enable
signal for Monitoring\I/O status\Current
EFIPTOC1 Io>>>(1) 50N/51N(1) INP LD0.EFIPTOC1.InEnaMult.stVal SPS BOOLEAN ST B 0 I1 ENA_MULT
current protection\EFIPTOC1\Inputs
multiplier
Monitoring\I/O status\Current
EFIPTOC1 Io>>>(1) 50N/51N(1) OUT LD0.EFIPTOC1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start
protection\EFIPTOC1\Outputs
Monitoring\I/O status\Current
EFIPTOC1 Io>>>(1) 50N/51N(1) OUT LD0.EFIPTOC1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate
protection\EFIPTOC1\Outputs
1=on; 2=blocked;
3=test;
EFIPTOC1 Io>>>(1) 50N/51N(1) MON LD0.EFIPTOC1.Beh.stVal ENS Enum ST B EFIPTOC1 Status Monitoring\FB status
4=test/blocked;
5=off
Ratio of
Monitoring\I/O status\Current
start time /
EFIPTOC1 Io>>>(1) 50N/51N(1) MON LD0.EFIPTOC1.StrDur.mag.f MV FLOAT32 MX B START_DUR 0.00...100.00 % protection\EFIPTOC1\Monitored
operate
data
time
Operation Settings\Settings\Current
EFIPTOC1 Io>>>(1) 50N/51N(1) SET LD0.EFIPTOC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
Off / On protection\EFIPTOC1
Settings\Settings\Current
EFIPTOC1 Io>>>(1) 50N/51N(1) SET LD0.EFIPTOC1.StrVal.setMag.f ASG FLOAT32 SG B 1.00 Start value Start value 1.00...40.00 xIn RESTCTR1
protection\EFIPTOC1
Operate delay Operate Settings\Settings\Current
EFIPTOC1 Io>>>(1) 50N/51N(1) SET LD0.EFIPTOC1.OpDlTmms.setVal ING INT32 SG B 20 20...200000 ms
time delay time protection\EFIPTOC1
Reset delay Reset Settings\Settings\Current
EFIPTOC1 Io>>>(1) 50N/51N(1) SET LD0.EFIPTOC1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
time delay time protection\EFIPTOC1
Multiplier
Start value for scaling Settings\Settings\Current
EFIPTOC1 Io>>>(1) 50N/51N(1) SET LD0.EFIPTOC1.StrValMult.setMag.f ASG FLOAT32 SG B 1.0 0.8...10.0
Mult the start protection\EFIPTOC1
value
0=Reset;
1=Activate
START;
Test 2=Deactive
Tests\Function tests\Current
EFIPTOC1 Io>>>(1) 50N/51N(1) TES LD0.EFIPTOC1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 EFIPTOC1 control for START;
protection
outputs 9=Activate
OPERATE;
10=Deactive
OPERATE
VisString255 (Name
EFIPTOC1 Io>>>(1) 50N/51N(1) VER LD0.EFIPTOC1.NamPlt.swRev LPL DC ED1 F1
(20) plate)

NSPTOC1: Negative Phase sequence current protection: E1


131
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

IEC IEC Parameter Parameter Channel


ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
61850 60617 name desc relation
(ACT input
NSPTOC1 I2>(1) 46(1) INP Channel I3P
channel)
Block signal
for activating Monitoring\I/O status\Current
NSPTOC1 I2>(1) 46(1) INP LD0.NSPTOC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
the blocking protection\NSPTOC1\Inputs
mode
Enable signal
Monitoring\I/O status\Current
NSPTOC1 I2>(1) 46(1) INP LD0.NSPTOC1.InEnaMult.stVal SPS BOOLEAN ST B 0 I1 ENA_MULT for current
protection\NSPTOC1\Inputs
multiplier
Monitoring\I/O status\Current
NSPTOC1 I2>(1) 46(1) OUT LD0.NSPTOC1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start
protection\NSPTOC1\Outputs
Monitoring\I/O status\Current
NSPTOC1 I2>(1) 46(1) OUT LD0.NSPTOC1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate
protection\NSPTOC1\Outputs
1=on; 2=blocked;
NSPTOC1 I2>(1) 46(1) MON LD0.NSPTOC1.Beh.stVal ENS Enum ST B NSPTOC1 Status 3=test; 4=test/blocked; Monitoring\FB status
5=off
Ratio of start Monitoring\I/O status\Current
NSPTOC1 I2>(1) 46(1) MON LD0.NSPTOC1.StrDur.mag.f MV FLOAT32 MX B START_DUR time / operate 0.00...100.00 % protection\NSPTOC1\Monitored
time data
Operation Off Settings\Settings\Current
NSPTOC1 I2>(1) 46(1) SET LD0.NSPTOC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
/ On protection\NSPTOC1
1=ANSI Ext. inv.;
2=ANSI Very inv.;
3=ANSI Norm. inv.;
4=ANSI Mod. inv.;
5=ANSI Def. Time;
6=L.T.E. inv.;
7=L.T.V. inv.; 8=L.T.
Selection of
Operating inv.; 9=IEC Norm. Settings\Settings\Current
NSPTOC1 I2>(1) 46(1) SET LD0.NSPTOC1.TmACrv.setCharact CURVE Enum SG B,I 15 time delay
curve type inv.; 10=IEC Very inv.; protection\NSPTOC1
curve type
11=IEC inv.; 12=IEC
Ext. inv.; 13=IEC S.T.
inv.; 14=IEC L.T. inv.;
15=IEC Def. Time;
17=Programmable;
18=RI type; 19=RD
type
Parameter A
Curve for customer Settings\Settings\Current
NSPTOC1 I2>(1) 46(1) SET LD0.NSPTOC1.TmACrv.setParA CURVE FLOAT32 SP B,I 28.2000 0.0086...120.0000
parameter A programmable protection\NSPTOC1
curve
Parameter B
Curve for customer Settings\Settings\Current
NSPTOC1 I2>(1) 46(1) SET LD0.NSPTOC1.TmACrv.setParB CURVE FLOAT32 SP B,I 0.1217 0.0000...0.7120
parameter B programmable protection\NSPTOC1
curve
Curve Parameter C Settings\Settings\Current
NSPTOC1 I2>(1) 46(1) SET LD0.NSPTOC1.TmACrv.setParC CURVE FLOAT32 SP B,I 2.00 0.02...2.00
parameter C for customer protection\NSPTOC1

132
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

programmable
curve
Parameter D
Curve for customer Settings\Settings\Current
NSPTOC1 I2>(1) 46(1) SET LD0.NSPTOC1.TmACrv.setParD CURVE FLOAT32 SP B,I 29.10 0.46...30.00
parameter D programmable protection\NSPTOC1
curve
Parameter E
Curve for customer Settings\Settings\Current
NSPTOC1 I2>(1) 46(1) SET LD0.NSPTOC1.TmACrv.setParE CURVE FLOAT32 SP B,I 1.0 0.0...1.0
parameter E programmable protection\NSPTOC1
curve
Settings\Settings\Current
NSPTOC1 I2>(1) 46(1) SET LD0.NSPTOC1.StrVal.setMag.f ASG FLOAT32 SG B 0.30 Start value Start value 0.01...5.00 xIn IL1TCTR1
protection\NSPTOC1
Time
Time multiplier in Settings\Settings\Current
NSPTOC1 I2>(1) 46(1) SET LD0.NSPTOC1.TmMult.setMag.f ASG FLOAT32 SG B 1.000 0.025...15.0
multiplier IEC/ANSI protection\NSPTOC1
IDMT curves
Minimum
Minimum operate time Settings\Settings\Current
NSPTOC1 I2>(1) 46(1) SET LD0.NSPTOC1.MinOpTmms.setVal ING INT32 SP A 20 20...60000 ms
operate time for IDMT protection\NSPTOC1
curves
Operate delay Operate delay Settings\Settings\Current
NSPTOC1 I2>(1) 46(1) SET LD0.NSPTOC1.OpDlTmms.setVal ING INT32 SG B 40 40...200000 ms
time time protection\NSPTOC1
Selection of 1=Immediate; 2=Def
Type of reset Settings\Settings\Current
NSPTOC1 I2>(1) 46(1) SET LD0.NSPTOC1.TypRsCrv.setVal ENG Enum SG A 1 reset curve time reset; 3=Inverse
curve protection\NSPTOC1
type reset
Reset delay Reset delay Settings\Settings\Current
NSPTOC1 I2>(1) 46(1) SET LD0.NSPTOC1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
time time protection\NSPTOC1
Multiplier for
Start value Settings\Settings\Current
NSPTOC1 I2>(1) 46(1) SET LD0.NSPTOC1.StrValMult.setMag.f ASG FLOAT32 SG B 1.0 scaling the 0.8...10.0
Mult protection\NSPTOC1
start value
0=Reset; 1=Activate
START; 2=Deactive
Test control START; 9=Activate Tests\Function tests\Current
NSPTOC1 I2>(1) 46(1) TES LD0.NSPTOC1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 NSPTOC1
for outputs OPERATE; protection
10=Deactive
OPERATE
VisString255
NSPTOC1 I2>(1) 46(1) VER LD0.NSPTOC1.NamPlt.swRev LPL DC ED1 E1 (Name plate)
(20)

ROVPTOV1: Residual overvoltage protection: D1


IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
(ACT input
ROVPTOV1 Uo>(1) 59G(1) INP Channel URES
channel)
Block signal
Monitoring\I/O status\Voltage
ROVPTOV1 Uo>(1) 59G(1) INP LD0.ROVPTOV1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK for
protection\ROVPTOV1\Inputs
activating
133
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

the blocking
mode
Monitoring\I/O status\Voltage
ROVPTOV1 Uo>(1) 59G(1) OUT LD0.ROVPTOV1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start
protection\ROVPTOV1\Outputs
Monitoring\I/O status\Voltage
ROVPTOV1 Uo>(1) 59G(1) OUT LD0.ROVPTOV1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate
protection\ROVPTOV1\Outputs
1=on; 2=blocked;
3=test;
ROVPTOV1 Uo>(1) 59G(1) MON LD0.ROVPTOV1.Beh.stVal ENS Enum ST B ROVPTOV1 Status Monitoring\FB status
4=test/blocked;
5=off
Ratio of start Monitoring\I/O status\Voltage
ROVPTOV1 Uo>(1) 59G(1) MON LD0.ROVPTOV1.StrDur.mag.f MV FLOAT32 MX B START_DUR time / 0.00...100.00 % protection\ROVPTOV1\Monitored
operate time data
Operation Settings\Settings\Voltage
ROVPTOV1 Uo>(1) 59G(1) SET LD0.ROVPTOV1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
Off / On protection\ROVPTOV1
Residual
Settings\Settings\Voltage
ROVPTOV1 Uo>(1) 59G(1) SET LD0.ROVPTOV1.StrVal.setMag.f ASG FLOAT32 SG B 0.030 Start value overvoltage 0.010...1.000 xUn RESTVTR1
protection\ROVPTOV1
start value
Operate delay Operate Settings\Settings\Voltage
ROVPTOV1 Uo>(1) 59G(1) SET LD0.ROVPTOV1.OpDlTmms.setVal ING INT32 SG B 40 40...300000 ms
time delay time protection\ROVPTOV1
Reset delay Reset delay Settings\Settings\Voltage
ROVPTOV1 Uo>(1) 59G(1) SET LD0.ROVPTOV1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
time time protection\ROVPTOV1
0=Reset;
1=Activate
START;
2=Deactive
Test control Tests\Function tests\Voltage
ROVPTOV1 Uo>(1) 59G(1) TES LD0.ROVPTOV1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 ROVPTOV1 START;
for outputs protection
9=Activate
OPERATE;
10=Deactive
OPERATE
VisString255 (Name
ROVPTOV1 Uo>(1) 59G(1) VER LD0.ROVPTOV1.NamPlt.swRev LPL DC ED1 D1
(20) plate)

PHPTUV1: Three phase undervoltage protection: D1


IEC Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Parameter range Menu path
60617 name relation
(ACT input
PHPTUV1 3U<(1) 27(1) INP Channel U3P
channel)
Block signal for
Monitoring\I/O status\Voltage
PHPTUV1 3U<(1) 27(1) INP LD0.PHPTUV1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK activating the
protection\PHPTUV1\Inputs
blocking mode
Monitoring\I/O status\Voltage
PHPTUV1 3U<(1) 27(1) OUT LD0.PHPTUV1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start (A,B,C)
protection\PHPTUV1\Outputs
Monitoring\I/O status\Voltage
PHPTUV1 3U<(1) 27(1) OUT LD0.PHPTUV1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate (A,B,C)
protection\PHPTUV1\Outputs

134
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

1=on; 2=blocked;
PHPTUV1 3U<(1) 27(1) MON LD0.PHPTUV1.Beh.stVal ENS Enum ST B PHPTUV1 Status 3=test; Monitoring\FB status
4=test/blocked; 5=off
Ratio of start Monitoring\I/O status\Voltage
PHPTUV1 3U<(1) 27(1) MON LD0.PHPTUV1.StrDur.mag.f MV FLOAT32 MX B START_DUR time / operate 0.00...100.00 % protection\PHPTUV1\Monitored
time data
Operation Off / Settings\Settings\Voltage
PHPTUV1 3U<(1) 27(1) SET LD0.PHPTUV1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
On protection\PHPTUV1
5=ANSI Def. Time;
Selection of 15=IEC Def. Time;
Operating Settings\Settings\Voltage
PHPTUV1 3U<(1) 27(1) SET LD0.PHPTUV1.TmVCrv.setCharact CURVE Enum SG B,I 15 time delay 21=Inv. Curve A;
curve type protection\PHPTUV1
curve type 22=Inv. Curve B;
23=Programmable
Parameter A for
Curve customer Settings\Settings\Voltage
PHPTUV1 3U<(1) 27(1) SET LD0.PHPTUV1.TmVCrv.setParA CURVE FLOAT32 SP B,I 1.000 0.005...200.000
parameter A programmable protection\PHPTUV1
curve
Parameter B for
Curve customer Settings\Settings\Voltage
PHPTUV1 3U<(1) 27(1) SET LD0.PHPTUV1.TmVCrv.setParB CURVE FLOAT32 SP B,I 1.00 0.50...100.00
parameter B programmable protection\PHPTUV1
curve
Parameter C for
Curve customer Settings\Settings\Voltage
PHPTUV1 3U<(1) 27(1) SET LD0.PHPTUV1.TmVCrv.setParC CURVE FLOAT32 SP B,I 0.0 0.0...1.0
parameter C programmable protection\PHPTUV1
curve
Parameter D for
Curve customer Settings\Settings\Voltage
PHPTUV1 3U<(1) 27(1) SET LD0.PHPTUV1.TmVCrv.setParD CURVE FLOAT32 SP B,I 0.000 0.000...60.000
parameter D programmable protection\PHPTUV1
curve
Parameter E for
Curve customer Settings\Settings\Voltage
PHPTUV1 3U<(1) 27(1) SET LD0.PHPTUV1.TmVCrv.setParE CURVE FLOAT32 SP B,I 1.000 0.000...3.000
parameter E programmable protection\PHPTUV1
curve
Settings\Settings\Voltage
PHPTUV1 3U<(1) 27(1) SET LD0.PHPTUV1.StrVal.setMag.f ASG FLOAT32 SG B 0.90 Start value Start value 0.05...1.20 xUn UL1TVTR1
protection\PHPTUV1
Time multiplier
Time Settings\Settings\Voltage
PHPTUV1 3U<(1) 27(1) SET LD0.PHPTUV1.TmMult.setMag.f ASG FLOAT32 SG B 1.000 in IEC/ANSI 0.025...15.0
multiplier protection\PHPTUV1
IDMT curves
Minimum
Minimum Settings\Settings\Voltage
PHPTUV1 3U<(1) 27(1) SET LD0.PHPTUV1.MinOpTmms.setVal ING INT32 SP A 60 operate time for 60...60000 ms
operate time protection\PHPTUV1
IDMT curves
Operate delay Operate delay Settings\Settings\Voltage
PHPTUV1 3U<(1) 27(1) SET LD0.PHPTUV1.OpDlTmms.setVal ING INT32 SG B 60 60...300000 ms
time time protection\PHPTUV1
Reset delay Reset delay Settings\Settings\Voltage
PHPTUV1 3U<(1) 27(1) SET LD0.PHPTUV1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
time time protection\PHPTUV1
Type of reset Selection of 1=Immediate; 2=Def Settings\Settings\Voltage
PHPTUV1 3U<(1) 27(1) SET LD0.PHPTUV1.TypRsCrv.setVal ENG Enum SG A 1
curve reset curve type time reset protection\PHPTUV1
Voltage block Low level Settings\Settings\Voltage
PHPTUV1 3U<(1) 27(1) SET LD0.PHPTUV1.BlkVal.setMag.f ASG FLOAT32 SP A 0.20 0.05...1.00 xUn UL1TVTR1
value blocking for protection\PHPTUV1
135
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

undervoltage
mode
Number of
Num of start phases required 1=1 out of 3; 2=2 out Settings\Settings\Voltage
PHPTUV1 3U<(1) 27(1) SET LD0.PHPTUV1.NumPh.setVal ENG Enum SP B 1
phases for operate of 3; 3=3 out of 3 protection\PHPTUV1
activation
Tuning
Curve Sat parameter to Settings\Settings\Voltage
PHPTUV1 3U<(1) 27(1) SET LD0.PHPTUV1.CrvSatRl.setMag.f ASG FLOAT32 SP A,I 0.0 0.0...10.0
Relative avoid curve protection\PHPTUV1
discontinuities
Parameter to
Voltage select phase or 1=phase-to-earth; Settings\Settings\Voltage
PHPTUV1 3U<(1) 27(1) SET LD0.PHPTUV1.VSel.setVal ENG Enum SP B 2
selection phase-to-phase 2=phase-to-phase protection\PHPTUV1
voltages
Enable block Enable internal Settings\Settings\Voltage
PHPTUV1 3U<(1) 27(1) SET LD0.PHPTUV1.EnaBlkVal.setVal SPG BOOLEAN SP A 1
value blocking protection\PHPTUV1
Relative
Relative Settings\Settings\Voltage
PHPTUV1 3U<(1) 27(1) SET LD0.PHPTUV1.HysRl.setMag.f ASG FLOAT32 SP A,I 4.0 hysteresis for 1.0...5.0 %
hysteresis protection\PHPTUV1
operation
Type of time Selection of 1=Freeze Op timer; Settings\Settings\Voltage
PHPTUV1 3U<(1) 27(1) SET LD0.PHPTUV1.TypTmRs.setVal ENG Enum SG A 1
reset time reset 2=Decrease Op timer protection\PHPTUV1
0=Reset; 1=Activate
START; 2=Deactive
Test control for START; 9=Activate Tests\Function tests\Voltage
PHPTUV1 3U<(1) 27(1) TES LD0.PHPTUV1.TestPro.Oper.ctlVal ENC Enum CO B 0 PHPTUV1
outputs OPERATE; protection
10=Deactive
OPERATE
VisString255
PHPTUV1 3U<(1) 27(1) VER LD0.PHPTUV1.NamPlt.swRev LPL DC ED1 D1 (Name plate)
(20)

PHPTOV1: Three phase overvoltage protection: D1


IEC Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Parameter range Menu path
60617 name relation
(ACT input
PHPTOV1 3U>(1) 59(1) INP Channel U3P
channel)
Block signal for
Monitoring\I/O status\Voltage
PHPTOV1 3U>(1) 59(1) INP LD0.PHPTOV1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK activating the
protection\PHPTOV1\Inputs
blocking mode
Monitoring\I/O status\Voltage
PHPTOV1 3U>(1) 59(1) OUT LD0.PHPTOV1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start (A,B,C)
protection\PHPTOV1\Outputs
Monitoring\I/O status\Voltage
PHPTOV1 3U>(1) 59(1) OUT LD0.PHPTOV1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate (A,B,C)
protection\PHPTOV1\Outputs
1=on; 2=blocked;
PHPTOV1 3U>(1) 59(1) MON LD0.PHPTOV1.Beh.stVal ENS Enum ST B PHPTOV1 Status 3=test; 4=test/blocked; Monitoring\FB status
5=off

136
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Ratio of start Monitoring\I/O status\Voltage


PHPTOV1 3U>(1) 59(1) MON LD0.PHPTOV1.StrDur.mag.f MV FLOAT32 MX B START_DUR time / operate 0.00...100.00 % protection\PHPTOV1\Monitored
time data
Operation Off / Settings\Settings\Voltage
PHPTOV1 3U>(1) 59(1) SET LD0.PHPTOV1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
On protection\PHPTOV1
5=ANSI Def. Time;
15=IEC Def. Time;
Selection of
Operating 17=Inv. Curve A; Settings\Settings\Voltage
PHPTOV1 3U>(1) 59(1) SET LD0.PHPTOV1.TmVCrv.setCharact CURVE Enum SG B,I 15 time delay
curve type 18=Inv. Curve B; protection\PHPTOV1
curve type
19=Inv. Curve C;
20=Programmable
Parameter A for
Curve customer Settings\Settings\Voltage
PHPTOV1 3U>(1) 59(1) SET LD0.PHPTOV1.TmVCrv.setParA CURVE FLOAT32 SP B,I 1.000 0.005...200.000
parameter A programmable protection\PHPTOV1
curve
Parameter B for
Curve customer Settings\Settings\Voltage
PHPTOV1 3U>(1) 59(1) SET LD0.PHPTOV1.TmVCrv.setParB CURVE FLOAT32 SP B,I 1.00 0.50...100.00
parameter B programmable protection\PHPTOV1
curve
Parameter C for
Curve customer Settings\Settings\Voltage
PHPTOV1 3U>(1) 59(1) SET LD0.PHPTOV1.TmVCrv.setParC CURVE FLOAT32 SP B,I 0.0 0.0...1.0
parameter C programmable protection\PHPTOV1
curve
Parameter D for
Curve customer Settings\Settings\Voltage
PHPTOV1 3U>(1) 59(1) SET LD0.PHPTOV1.TmVCrv.setParD CURVE FLOAT32 SP B,I 0.000 0.000...60.000
parameter D programmable protection\PHPTOV1
curve
Parameter E for
Curve customer Settings\Settings\Voltage
PHPTOV1 3U>(1) 59(1) SET LD0.PHPTOV1.TmVCrv.setParE CURVE FLOAT32 SP B,I 1.000 0.000...3.000
parameter E programmable protection\PHPTOV1
curve
Settings\Settings\Voltage
PHPTOV1 3U>(1) 59(1) SET LD0.PHPTOV1.StrVal.setMag.f ASG FLOAT32 SG B 1.10 Start value Start value 0.05...1.60 xUn UL1TVTR1
protection\PHPTOV1
Time multiplier
Time Settings\Settings\Voltage
PHPTOV1 3U>(1) 59(1) SET LD0.PHPTOV1.TmMult.setMag.f ASG FLOAT32 SG B 1.000 in IEC/ANSI 0.025...15.0
multiplier protection\PHPTOV1
IDMT curves
Minimum
Minimum Settings\Settings\Voltage
PHPTOV1 3U>(1) 59(1) SET LD0.PHPTOV1.MinOpTmms.setVal ING INT32 SP A 40 operate time for 40...60000 ms
operate time protection\PHPTOV1
IDMT curves
Operate delay Operate delay Settings\Settings\Voltage
PHPTOV1 3U>(1) 59(1) SET LD0.PHPTOV1.OpDlTmms.setVal ING INT32 SG B 40 40...300000 ms
time time protection\PHPTOV1
Reset delay Reset delay Settings\Settings\Voltage
PHPTOV1 3U>(1) 59(1) SET LD0.PHPTOV1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
time time protection\PHPTOV1
Type of reset Selection of 1=Immediate; 2=Def Settings\Settings\Voltage
PHPTOV1 3U>(1) 59(1) SET LD0.PHPTOV1.TypRsCrv.setVal ENG Enum SG A 1
curve reset curve type time reset protection\PHPTOV1
Number of
Num of start phases required 1=1 out of 3; 2=2 out Settings\Settings\Voltage
PHPTOV1 3U>(1) 59(1) SET LD0.PHPTOV1.NumPh.setVal ENG Enum SP B 1
phases for operate of 3; 3=3 out of 3 protection\PHPTOV1
activation
137
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Tuning
Curve Sat parameter to Settings\Settings\Voltage
PHPTOV1 3U>(1) 59(1) SET LD0.PHPTOV1.CrvSatRl.setMag.f ASG FLOAT32 SP A,I 0.0 0.0...10.0
Relative avoid curve protection\PHPTOV1
discontinuities
Parameter to
Voltage select phase or 1=phase-to-earth; Settings\Settings\Voltage
PHPTOV1 3U>(1) 59(1) SET LD0.PHPTOV1.VSel.setVal ENG Enum SP B 2
selection phase-to-phase 2=phase-to-phase protection\PHPTOV1
voltages
Relative
Relative Settings\Settings\Voltage
PHPTOV1 3U>(1) 59(1) SET LD0.PHPTOV1.HysRl.setMag.f ASG FLOAT32 SP A,I 4.0 hysteresis for 1.0...5.0 %
hysteresis protection\PHPTOV1
operation
Type of time Selection of 1=Freeze Op timer; Settings\Settings\Voltage
PHPTOV1 3U>(1) 59(1) SET LD0.PHPTOV1.TypTmRs.setVal ENG Enum SG A 1
reset time reset 2=Decrease Op timer protection\PHPTOV1
0=Reset; 1=Activate
START; 2=Deactive
Test control for START; 9=Activate Tests\Function tests\Voltage
PHPTOV1 3U>(1) 59(1) TES LD0.PHPTOV1.TestPro.Oper.ctlVal ENC Enum CO B 0 PHPTOV1
outputs OPERATE; protection
10=Deactive
OPERATE
VisString255
PHPTOV1 3U>(1) 59(1) VER LD0.PHPTOV1.NamPlt.swRev LPL DC ED1 D1 (Name plate)
(20)

PSPTUV1: Positive sequence undervoltage: D1


IEC IEC Parameter Parameter Channel
ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
61850 60617 name desc relation
(ACT input
PSPTUV1 U1<(1) 47U+(1) INP Channel U3P
channel)
Block signal
for
Monitoring\I/O status\Voltage
PSPTUV1 U1<(1) 47U+(1) INP LD0.PSPTUV1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK activating
protection\PSPTUV1\Inputs
the blocking
mode
Monitoring\I/O status\Voltage
PSPTUV1 U1<(1) 47U+(1) OUT LD0.PSPTUV1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start
protection\PSPTUV1\Outputs
Monitoring\I/O status\Voltage
PSPTUV1 U1<(1) 47U+(1) OUT LD0.PSPTUV1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate
protection\PSPTUV1\Outputs
1=on; 2=blocked;
PSPTUV1 U1<(1) 47U+(1) MON LD0.PSPTUV1.Beh.stVal ENS Enum ST B PSPTUV1 Status 3=test; Monitoring\FB status
4=test/blocked; 5=off
Ratio of Monitoring\I/O status\Voltage
PSPTUV1 U1<(1) 47U+(1) MON LD0.PSPTUV1.StrDur.mag.f MV FLOAT32 MX B START_DUR start time / 0.00...100.00 % protection\PSPTUV1\Monitored
operate time data
Operation Settings\Settings\Voltage
PSPTUV1 U1<(1) 47U+(1) SET LD0.PSPTUV1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off IL1TCTR1
Off / On protection\PSPTUV1
Settings\Settings\Voltage
PSPTUV1 U1<(1) 47U+(1) SET LD0.PSPTUV1.StrVal.setMag.f ASG FLOAT32 SG B 0.500 Start value Start value 0.010...1.200 xUn UL1TVTR1
protection\PSPTUV1

138
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Operate delay Operate Settings\Settings\Voltage


PSPTUV1 U1<(1) 47U+(1) SET LD0.PSPTUV1.OpDlTmms.setVal ING INT32 SG B 40 40...120000 ms
time delay time protection\PSPTUV1
Reset delay Reset delay Settings\Settings\Voltage
PSPTUV1 U1<(1) 47U+(1) SET LD0.PSPTUV1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
time time protection\PSPTUV1
Internal
Voltage block Settings\Settings\Voltage
PSPTUV1 U1<(1) 47U+(1) SET LD0.PSPTUV1.BlkVal.setMag.f ASG FLOAT32 SG A 0.20 blocking 0.01...1.00 xUn UL1TVTR1
value protection\PSPTUV1
level
Enable
Enable block Settings\Settings\Voltage
PSPTUV1 U1<(1) 47U+(1) SET LD0.PSPTUV1.EnaBlkVal.setVal SPG BOOLEAN SG A 1 Internal
value protection\PSPTUV1
Blocking
Relative
Relative Settings\Settings\Voltage
PSPTUV1 U1<(1) 47U+(1) SET LD0.PSPTUV1.HysRl.setMag.f ASG FLOAT32 SP A,I 4.0 hysteresis 1.0...5.0 %
hysteresis protection\PSPTUV1
for operation
0=Reset; 1=Activate
START; 2=Deactive
Test control START; 9=Activate Tests\Function tests\Voltage
PSPTUV1 U1<(1) 47U+(1) TES LD0.PSPTUV1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 PSPTUV1
for outputs OPERATE; protection
10=Deactive
OPERATE
VisString255 (Name
PSPTUV1 U1<(1) 47U+(1) VER LD0.PSPTUV1.NamPlt.swRev LPL DC ED1 D1
(20) plate)

NSPTOV1: Negative sequence overvoltage: D1


IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
47O- (ACT input
NSPTOV1 U2>(1) INP Channel U3P
(1) channel)
Block signal
for
47O- Monitoring\I/O status\Voltage
NSPTOV1 U2>(1) INP LD0.NSPTOV1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK activating
(1) protection\NSPTOV1\Inputs
the blocking
mode
47O- Monitoring\I/O status\Voltage
NSPTOV1 U2>(1) OUT LD0.NSPTOV1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start
(1) protection\NSPTOV1\Outputs
47O- Monitoring\I/O status\Voltage
NSPTOV1 U2>(1) OUT LD0.NSPTOV1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate
(1) protection\NSPTOV1\Outputs
1=on; 2=blocked;
47O-
NSPTOV1 U2>(1) MON LD0.NSPTOV1.Beh.stVal ENS Enum ST B NSPTOV1 Status 3=test; 4=test/blocked; Monitoring\FB status
(1)
5=off
Ratio of start Monitoring\I/O status\Voltage
47O-
NSPTOV1 U2>(1) MON LD0.NSPTOV1.StrDur.mag.f MV FLOAT32 MX B START_DUR time / 0.00...100.00 % protection\NSPTOV1\Monitored
(1)
operate time data
47O- Operation Settings\Settings\Voltage
NSPTOV1 U2>(1) SET LD0.NSPTOV1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
(1) Off / On protection\NSPTOV1
47O- Settings\Settings\Voltage
NSPTOV1 U2>(1) SET LD0.NSPTOV1.StrVal.setMag.f ASG FLOAT32 SG B 0.030 Start value Start value 0.010...1.000 xUn UL1TVTR1
(1) protection\NSPTOV1

139
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

47O- Operate delay Operate Settings\Settings\Voltage


NSPTOV1 U2>(1) SET LD0.NSPTOV1.OpDlTmms.setVal ING INT32 SG B 40 40...120000 ms
(1) time delay time protection\NSPTOV1
47O- Reset delay Reset delay Settings\Settings\Voltage
NSPTOV1 U2>(1) SET LD0.NSPTOV1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
(1) time time protection\NSPTOV1
0=Reset; 1=Activate
START; 2=Deactive
47O- Test control START; 9=Activate Tests\Function tests\Voltage
NSPTOV1 U2>(1) TES LD0.NSPTOV1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 NSPTOV1
(1) for outputs OPERATE; protection
10=Deactive
OPERATE
47O- VisString255
NSPTOV1 U2>(1) VER LD0.NSPTOV1.NamPlt.swRev LPL DC ED1 D1 (Name plate)
(1) (20)

FRPFRQ1: Frequency protection: D1


IEC Channel
IEC 60617 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter name Parameter desc Parameter range Menu path
61850 relation
(ACT input
FRPFRQ1 f>/f<,df/dt(1) 81(1) INP Channel U3P
channel)
Block signal for
Monitoring\I/O status\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) INP LD0.FRPTRC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK activating the
protection\FRPFRQ1\Inputs
blocking mode
Monitoring\I/O status\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) OUT LD0.FRPTRC1.Op.general ACT BOOLEAN ST B I1 OPERATE Operate
protection\FRPFRQ1\Outputs
Monitoring\I/O status\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) OUT LD0.FRPTRC1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start
protection\FRPFRQ1\Outputs
Start signal for Monitoring\I/O status\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) OUT LD0.FRPTOF1.Str.general ACD BOOLEAN ST B I1 ST_OFRQ
overfrequency protection\FRPFRQ1\Outputs
Operate signal
Monitoring\I/O status\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) OUT LD0.FRPTOF1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPR_OFRQ for
protection\FRPFRQ1\Outputs
overfrequency
Start signal for Monitoring\I/O status\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) OUT LD0.FRPTUF1.Str.general ACD BOOLEAN ST B I1 ST_UFRQ
underfrequency protection\FRPFRQ1\Outputs
Operate signal
Monitoring\I/O status\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) OUT LD0.FRPTUF1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPR_UFRQ for
protection\FRPFRQ1\Outputs
underfrequency
Start signal for
Monitoring\I/O status\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) OUT LD0.FRPFRC1.Str.general ACD BOOLEAN ST B I1 ST_FRG frequency
protection\FRPFRQ1\Outputs
gradient
Operate signal
Monitoring\I/O status\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) OUT LD0.FRPFRC1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPR_FRG for frequency
protection\FRPFRQ1\Outputs
gradient
1=on; 2=blocked;
FRPFRQ1 f>/f<,df/dt(1) 81(1) MON LD0.FRPTRC1.Beh.stVal ENS Enum ST B FRPFRQ1 Status 3=test; 4=test/blocked; Monitoring\FB status
5=off

140
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Monitoring\I/O status\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) MON LD0.FRPTRC1.StrDur.mag.f MV FLOAT32 MX B START_DUR Start duration 0.00...100.00 % protection\FRPFRQ1\Monitored
data
Monitoring\I/O status\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) MON LD0.FRPTOF1.StrDur.mag.f MV FLOAT32 MX B ST_DUR_OFRQ Start duration 0.00...100.00 % protection\FRPFRQ1\Monitored
data
Monitoring\I/O status\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) MON LD0.FRPTUF1.StrDur.mag.f MV FLOAT32 MX B ST_DUR_UFRQ Start duration 0.00...100.00 % protection\FRPFRQ1\Monitored
data
Monitoring\I/O status\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) MON LD0.FRPFRC1.StrDur.mag.f MV FLOAT32 MX B ST_DUR_FRG Start duration 0.00...100.00 % protection\FRPFRQ1\Monitored
data
Operation Off / Settings\Settings\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) SET LD0.FRPTRC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
On protection\FRPFRQ1
1=Freq<; 2=Freq>;
Frequency
3=df/dt; 4=Freq< +
protection Settings\Settings\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) SET LD0.FRPTRC1.OpModProHz.setVal ENG Enum SG B 1 Operation mode df/dt; 5=Freq> + df/dt;
operation mode protection\FRPFRQ1
6=Freq< OR df/dt;
selection
7=Freq> OR df/dt
Frequency start
Settings\Settings\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) SET LD0.FRPTOF1.StrVal.setMag.f ASG FLOAT32 SG B 1.050 Start value Freq> value 0.900...1.200 xFn
protection\FRPFRQ1
overfrequency
Operate delay
Settings\Settings\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) SET LD0.FRPTOF1.OpDlTmms.setVal ING INT32 SG B 200 Operate Tm Freq time for 80...200000 ms
protection\FRPFRQ1
frequency
Reset delay
Reset delay Tm Settings\Settings\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) SET LD0.FRPTOF1.RsDlTmms.setVal ING INT32 SP A 0 time for 0...60000 ms
Freq protection\FRPFRQ1
frequency
Frequency start
Settings\Settings\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) SET LD0.FRPTUF1.StrVal.setMag.f ASG FLOAT32 SG B 0.950 Start value Freq< value 0.800...1.100 xFn
protection\FRPFRQ1
underfrequency
Frequency start
-0.2000...0.2000 xFn Settings\Settings\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) SET LD0.FRPFRC1.StrVal.setMag.f ASG FLOAT32 SG B 0.0100 Start value df/dt value rate of
/s protection\FRPFRQ1
change
Operate delay
time for Settings\Settings\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) SET LD0.FRPFRC1.OpDlTmms.setVal ING INT32 SG B 400 Operate Tm df/dt 120...200000 ms
frequency rate protection\FRPFRQ1
of change
Reset delay
Reset delay Tm Settings\Settings\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) SET LD0.FRPFRC1.RsDlTmms.setVal ING INT32 SP A 0 time for rate of 0...60000 ms
df/dt protection\FRPFRQ1
change
0=Reset; 1=Activate
START; 2=Deactive
START; 9=Activate
OPERATE;
Test control for Tests\Function tests\Frequency
FRPFRQ1 f>/f<,df/dt(1) 81(1) TES LD0.FRPTRC1.TestPro.Oper.ctlVal ENC Enum CO B 0 FRPFRQ1 10=Deactive
outputs protection
OPERATE;
69=Activate
OPR_UFRQ;
70=Deactive
141
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

OPR_UFRQ;
71=Activate
OPR_OFRQ;
72=Deactive
OPR_OFRQ;
73=Activate
OPR_FRG;
74=Deactive
OPR_FRG;
75=Activate
ST_UFRQ;
76=Deactive
ST_UFRQ;
77=Activate
ST_OFRQ;
78=Deactive
ST_OFRQ;
79=Activate ST_FRG;
80=Deactive ST_FRG
VisString255
FRPFRQ1 f>/f<,df/dt(1) 81(1) VER LD0.FRPTRC1.NamPlt.swRev LPL DC ED1 D1 (Name plate)
(20)

CCBRBRF1: Circuit breaker failure protection: E1


Categor CD Acces Defaul Datase Even CM Parameter Channel
IEC 61850 IEC 60617 ANSI IECName Type FC Parameter name Parameter range Menu path
y C s t t t T desc relation
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 (ACT input
INP Channel I3P
1 ) ) channel)
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 (ACT input
INP Channel IRES
1 ) ) channel)
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 Block CBFP Monitoring\I/O status\Other
INP LD0.CCBRBRF1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
1 ) ) operation protection\CCBRBRF1\Inputs
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 CBFP start Monitoring\I/O status\Other
INP LD0.CCBRBRF1.InStr.stVal SPS BOOLEAN ST B 0 I1 START
1 ) ) command protection\CCBRBRF1\Inputs
CB in
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 Monitoring\I/O status\Other
INP LD0.CCBRBRF1.InPosCls.stVal SPS BOOLEAN ST B 0 I1 POSCLOSE closed
1 ) ) protection\CCBRBRF1\Inputs
position
CB faulty
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 Monitoring\I/O status\Other
INP LD0.CCBRBRF1.InCBFlt.stVal SPS BOOLEAN ST B 0 I1 CB_FAULT and unable
1 ) ) protection\CCBRBRF1\Inputs
to trip
Delayed CB Monitoring\I/O status\Other
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 AC CB_FAULT_A
OUT LD0.CCBRBRF1.Str.general BOOLEAN ST B StatIed P,H I1 failure protection\CCBRBRF1\Outpu
1 ) ) D L
alarm ts
Monitoring\I/O status\Other
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 P,H,
OUT LD0.CCBRBRF1.OpEx.general ACT BOOLEAN ST B StatIed TRBU Backup trip protection\CCBRBRF1\Outpu
1 ) ) T
ts
Monitoring\I/O status\Other
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 P,H,
OUT LD0.CCBRBRF1.OpIn.general ACT BOOLEAN ST B StatIed TRRET Retrip protection\CCBRBRF1\Outpu
1 ) ) T
ts
142
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

1=on;
2=blocked;
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1
MON LD0.CCBRBRF1.Beh.stVal ENS Enum ST B CCBRBRF1 Status 3=test; Monitoring\FB status
1 ) )
4=test/blocked;
5=off
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 C Operation Settings\Settings\Other
SET LD0.CCBRBRF1.Mod.Oper.ctlVal ENC Enum B,I 1 Operation 1=on; 5=off
1 ) ) O Off / On protection\CCBRBRF1
Operating 1=Current;
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 EN CB failure Settings\Settings\Other
SET LD0.CCBRBRF1.FailMod.setVal Enum SP B 1 mode of 2=Breaker
1 ) ) G mode protection\CCBRBRF1
function status; 3=Both
Delay timer
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 Settings\Settings\Other
SET LD0.CCBRBRF1.FailTmms.setVal ING INT32 SP B 240 CB failure delay for backup 0...60000 ms
1 ) ) protection\CCBRBRF1
trip
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 Delay timer Settings\Settings\Other
SET LD0.CCBRBRF1.TPTrTmms.setVal ING INT32 SP B 120 Retrip time 0...60000 ms
1 ) ) for retrip protection\CCBRBRF1
Operating
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 Settings\Settings\Other
SET LD0.CCBRBRF1.DetValA.setMag.f ASG FLOAT32 SP B 0.30 Current value phase 0.05...2.00 xIn IL1TCTR1
1 ) ) protection\CCBRBRF1
current
1=Off;
Operating
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 EN CB fail retrip 2=Without Settings\Settings\Other
SET LD0.CCBRBRF1.ReTrMod.setVal Enum SP B 1 mode of
1 ) ) G mode Check; protection\CCBRBRF1
retrip logic
3=Current check
Pulse length
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 of retrip and Settings\Settings\Other
SET LD0.CCBRBRF1.TrPlsTmms.setVal ING INT32 SP A 200 Trip pulse time 0...60000 ms
1 ) ) backup trip protection\CCBRBRF1
outputs
Operating
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 Current value Settings\Settings\Other RESTCTR
SET LD0.CCBRBRF1.DetValARes.setMag.f ASG FLOAT32 SP B 0.30 residual 0.05...2.00 xIn
1 ) ) Res protection\CCBRBRF1 1
current
Phase
current
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 EN Measurement 2=DFT; 3=Peak- Settings\Settings\Other
SET LD0.CCBRBRF1.AMeasMod.setVal Enum SP A 3 measuremen
1 ) ) G mode to-Peak protection\CCBRBRF1
t mode of
function
Circuit
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 Settings\Settings\Other
SET LD0.CCBRBRF1.CBAlmTmms.setVal ING INT32 SP A 5000 CB fault delay breaker 0...60000 ms
1 ) ) protection\CCBRBRF1
faulty delay
Backup trip 1=2 out of 4;
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 EN CB failure trip Settings\Settings\Other
SET LD0.CCBRBRF1.OpExMod.setVal Enum SP B 2 current 2=1 out of 3;
1 ) ) G mode protection\CCBRBRF1
check mode 3=1 out of 4
Start reset 1=Rising edge;
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 EN Start latching Settings\Settings\Other
SET LD0.CCBRBRF1.StrLtcMod.setVal Enum SP A 1 delayed or 2=Level
1 ) ) G mode protection\CCBRBRF1
immediately sensitive
0=Reset;
25=Activate
CB_FAULT_A
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 LD0.CCBRBRF1.TstOutCmd.Oper.ctlV C Test control Tests\Function tests\Other
TES ENC Enum B 0 CCBRBRF1 L; 26=Deactive
1 ) ) al O for outputs protection
CB_FAULT_A
L; 27=Activate
TRBU;
143
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

28=Deactive
TRBU;
29=Activate
TRRET;
30=Deactive
TRRET
CCBRBRF 3I>/Io>BF(1 51BF/51NBF(1 VisString25 D (Name
VER LD0.CCBRBRF1.NamPlt.swRev LPL ED1 E1
1 ) ) 5 (20) C plate)

INRPHAR1: Three-phase inrush detector: C1


IEC Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Parameter range Menu path
60617 name relation
(ACT input
INRPHAR1 3I2f>(1) 68(1) INP Channel I3P
channel)
Block input Monitoring\I/O status\Current
INRPHAR1 3I2f>(1) 68(1) INP LD0.INRPHAR1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
status protection\INRPHAR1\Inputs
Second
Monitoring\I/O status\Current
INRPHAR1 3I2f>(1) 68(1) OUT LD0.INRPHAR1.Str.general ACD BOOLEAN ST B StatIO P I1 BLK2H harmonic based (A,B,C)
protection\INRPHAR1\Outputs
block
1=on; 2=blocked;
3=test;
INRPHAR1 3I2f>(1) 68(1) MON LD0.INRPHAR1.Beh.stVal ENS Enum ST B INRPHAR1 Status Monitoring\FB status
4=test/blocked;
5=off
Operation Off / Settings\Settings\Current
INRPHAR1 3I2f>(1) 68(1) SET LD0.INRPHAR1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off IL1TCTR1
On protection\INRPHAR1
Ratio of the 2.
to the 1.
Settings\Settings\Current
INRPHAR1 3I2f>(1) 68(1) SET LD0.INRPHAR1.PhStr.setMag.f ASG FLOAT32 SG B 20 Start value harmonic 5...100 %
protection\INRPHAR1
leading to
restraint
Operate Operate delay Settings\Settings\Current
INRPHAR1 3I2f>(1) 68(1) SET LD0.INRPHAR1.OpDlTmms.setVal ING INT32 SG B 20 20...60000 ms
delay time time protection\INRPHAR1
Reset delay Reset delay Settings\Settings\Current
INRPHAR1 3I2f>(1) 68(1) SET LD0.INRPHAR1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
time time protection\INRPHAR1
0=Reset;
35=Activate
Test control for Tests\Function tests\Current
INRPHAR1 3I2f>(1) 68(1) TES LD0.INRPHAR1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 INRPHAR1 BLK2H;
outputs protection
36=Deactive
BLK2H
VisString255
INRPHAR1 3I2f>(1) 68(1) VER LD0.INRPHAR1.NamPlt.swRev LPL DC ED1 C1 (Name plate)
(20)

CBPSOF1: Switch on to fault: B1


IEC IEC Channel
ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter name Parameter desc Parameter range Menu path
61850 60617 relation
144
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Monitoring\I/O status\Other
CBPSOF1 SOTF(1) SOTF(1) INP LD0.CBPSOF1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK Block of function
protection\CBPSOF1\Inputs
Start from
function to be Monitoring\I/O status\Other
CBPSOF1 SOTF(1) SOTF(1) INP LD0.CBPSOF1.InStr.stVal SPS BOOLEAN ST B 0 I1 START
accelerated by protection\CBPSOF1\Inputs
SOTF
Start from
function to be Monitoring\I/O status\Other
CBPSOF1 SOTF(1) SOTF(1) INP LD0.CBPSOF1.InDlStr.stVal SPS BOOLEAN ST B 0 I1 START_DLYD
accelerated with protection\CBPSOF1\Inputs
delay by SOTF
External enabling
Monitoring\I/O status\Other
CBPSOF1 SOTF(1) SOTF(1) INP LD0.CBPSOF1.InCBCls.stVal SPS BOOLEAN ST B 0 I1 CB_CL_CMD of SOTF by CB
protection\CBPSOF1\Inputs
close command
Monitoring\I/O status\Other
CBPSOF1 SOTF(1) SOTF(1) OUT LD0.CBPSOF1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate
protection\CBPSOF1\Outputs
1=on; 2=blocked;
3=test;
CBPSOF1 SOTF(1) SOTF(1) MON LD0.CBPSOF1.Beh.stVal ENS Enum ST B CBPSOF1 Status Monitoring\FB status
4=test/blocked;
5=off
Operation Off / Settings\Settings\Other
CBPSOF1 SOTF(1) SOTF(1) SET LD0.CBPSOF1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
On protection\CBPSOF1
SOTF detection
SOTF reset Settings\Settings\Other
CBPSOF1 SOTF(1) SOTF(1) SET LD0.CBPSOF1.RsDlTmms.setVal ING INT32 SG A 1000 period after 0...60000 ms
time protection\CBPSOF1
initialization
Operate delay Time delay for Settings\Settings\Other
CBPSOF1 SOTF(1) SOTF(1) SET LD0.CBPSOF1.OpDlTmms.setVal ING INT32 SG B 0 0...60000 ms
time start input protection\CBPSOF1
0=Reset;
9=Activate
Test control for Tests\Function tests\Other
CBPSOF1 SOTF(1) SOTF(1) TES LD0.CBPSOF1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 CBPSOF1 OPERATE;
outputs protection
10=Deactive
OPERATE
VisString255
CBPSOF1 SOTF(1) SOTF(1) VER LD0.CBPSOF1.NamPlt.swRev LPL DC B1 (Name plate)
(20)

TRPPTRC1: Trip logic: F1


IEC Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Parameter range Menu path
60617 name relation
Master Monitoring\I/O status\Trip
TRPPTRC1 94/86(1) INP LD0.TRPPTRC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK Block of function
Trip(1) logic\TRPPTRC1\Inputs
Master Monitoring\I/O status\Trip
TRPPTRC1 94/86(1) INP LD0.TRPPTRC1.Op.general ACT BOOLEAN ST B 0 StatIO P I1 OPERATE Operate
Trip(1) logic\TRPPTRC1\Inputs
Input for resetting
Master Monitoring\I/O status\Trip
TRPPTRC1 94/86(1) INP LD0.TRPPTRC1.LORs.stVal SPC BOOLEAN ST B 0 I1 RST_LKOUT the circuit breaker
Trip(1) logic\TRPPTRC1\Inputs
lockout function
Master General trip output Monitoring\I/O status\Trip
TRPPTRC1 94/86(1) OUT LD0.TRPPTRC1.Tr.general ACT BOOLEAN ST B StatNrml P,H TRIP
Trip(1) signal logic\TRPPTRC1\Outputs

145
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Circuit breaker
Master Monitoring\I/O status\Trip
TRPPTRC1 94/86(1) OUT LD0.TRPPTRC1.ClsLO.stVal SPS BOOLEAN ST B I1 CL_LKOUT lockout output (set
Trip(1) logic\TRPPTRC1\Outputs
until reset)
Master Reset TRPPTRC1
TRPPTRC1 94/86(1) CTR LD0.TRPPTRC1.LORs.Oper.ctlVal SPC BOOLEAN CO B,H 0 I1 TRPPTRC1 0=Cancel; 1=Clear Clear\Clear
Trip(1) lockout and latch
Master
TRPPTRC1 94/86(1) CTR LD0.TRPPTRC1.TrRs.Oper.ctlVal SPC BOOLEAN CO I1 (Reset latched trip)
Trip(1)
1=on; 2=blocked;
Master
TRPPTRC1 94/86(1) MON LD0.TRPPTRC1.Beh.stVal ENS Enum ST B TRPPTRC1 Status 3=test; Monitoring\FB status
Trip(1)
4=test/blocked; 5=off
Master Configuration\Trip
TRPPTRC1 94/86(1) CFG LD0.TRPPTRC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation Operation Off / On 1=on; 5=off
Trip(1) logic\TRPPTRC1
Master Trip pulse Minimum duration Configuration\Trip
TRPPTRC1 94/86(1) CFG LD0.TRPPTRC1.TrPlsTmms.setVal ING INT32 SP B 250 20...60000 ms
Trip(1) time of trip output signal logic\TRPPTRC1
1=Non-latched;
Master Trip output Select the operation Configuration\Trip
TRPPTRC1 94/86(1) CFG LD0.TRPPTRC1.TrOutMod.setVal ENG Enum SP B 1 2=Latched;
Trip(1) mode mode for trip output logic\TRPPTRC1
3=Lockout
Master VisString255
TRPPTRC1 94/86(1) VER LD0.TRPPTRC1.NamPlt.swRev LPL DC ED1 F1 (Name plate)
Trip(1) (20)

MAPGAPC1: Multipurpose analogue protection function: C1


IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
Block
signal for
activating Monitoring\I/O status\Other
MAPGAPC1 MAP(1) MAP(1) INP LD0.MAPGAPC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
the protection\MAPGAPC1\Inputs
blocking
mode
Analogue Monitoring\I/O status\Other
MAPGAPC1 MAP(1) MAP(1) INP LD0.MAPGAPC1.AnIn.mag.f MV FLOAT32 MX B 0.0 I1 AI_VALUE -10000.0...10000.0
input value protection\MAPGAPC1\Inputs
Enable Monitoring\I/O status\Other
MAPGAPC1 MAP(1) MAP(1) INP LD0.MAPGAPC1.InEnaAdd.stVal SPS BOOLEAN ST B 0 I1 ENA_ADD
start added protection\MAPGAPC1\Inputs
Monitoring\I/O status\Other
MAPGAPC1 MAP(1) MAP(1) OUT LD0.MAPGAPC1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start
protection\MAPGAPC1\Outputs
Monitoring\I/O status\Other
MAPGAPC1 MAP(1) MAP(1) OUT LD0.MAPGAPC1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate
protection\MAPGAPC1\Outputs
1=on; 2=blocked;
3=test;
MAPGAPC1 MAP(1) MAP(1) MON LD0.MAPGAPC1.Beh.stVal ENS Enum ST B MAPGAPC1 Status Monitoring\FB status
4=test/blocked;
5=off
Ratio of
Monitoring\I/O status\Other
start time /
MAPGAPC1 MAP(1) MAP(1) MON LD0.MAPGAPC1.StrDur.mag.f MV FLOAT32 MX B START_DUR 0.00...100.00 % protection\MAPGAPC1\Monitored
operate
data
time

146
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Operation Settings\Settings\Other
MAPGAPC1 MAP(1) MAP(1) SET LD0.MAPGAPC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
Off / On protection\MAPGAPC1
Settings\Settings\Other
MAPGAPC1 MAP(1) MAP(1) SET LD0.MAPGAPC1.StrVal.setMag.f ASG FLOAT32 SG B 0.0 Start value Start value -10000.0...10000.0
protection\MAPGAPC1
Operate delay Operate Settings\Settings\Other
MAPGAPC1 MAP(1) MAP(1) SET LD0.MAPGAPC1.OpDlTmms.setVal ING INT32 SG B 0 0...200000 ms
time delay time protection\MAPGAPC1
Reset delay Reset Settings\Settings\Other
MAPGAPC1 MAP(1) MAP(1) SET LD0.MAPGAPC1.RsDlTmms.setVal ING INT32 SP A 0 0...60000 ms
time delay time protection\MAPGAPC1
Operation Operation Settings\Settings\Other
MAPGAPC1 MAP(1) MAP(1) SET LD0.MAPGAPC1.OpModCom.setVal ENG Enum SP B,I 1 1=Over; 2=Under
mode mode protection\MAPGAPC1
Absolute
Absolute hysteresis Settings\Settings\Other
MAPGAPC1 MAP(1) MAP(1) SET LD0.MAPGAPC1.HysAbs.setMag.f ASG FLOAT32 SP A,I 0.10 0.01...100.00
hysteresis for protection\MAPGAPC1
operation
Start value Start value Settings\Settings\Other
MAPGAPC1 MAP(1) MAP(1) SET LD0.MAPGAPC1.StrValAdd.setMag.f ASG FLOAT32 SG B 0.0 -100.0...100.0
Add Add protection\MAPGAPC1
0=Reset; 1=Activate
START; 2=Deactive
Test
START; 9=Activate Tests\Function tests\Other
MAPGAPC1 MAP(1) MAP(1) TES LD0.MAPGAPC1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 MAPGAPC1 control for
OPERATE; protection
outputs
10=Deactive
OPERATE
VisString255 (Name
MAPGAPC1 MAP(1) MAP(1) VER LD0.MAPGAPC1.NamPlt.swRev LPL DC ED1 C1
(20) plate)

SSCBR1: Circuit breaker condition monitoring: F1


Channe
IEC Categor CD Datase Even CM Parameter
IEC 61850 ANSI IECName Type FC Access Default Parameter name Parameter range Menu path l
60617 y C t t T desc
relation
CBCM(1 CBCM(1 (ACT input
SSCBR1 INP Channel I3P
) ) channel)
Monitoring\I/O
CBCM(1 CBCM(1 Block input
SSCBR1 INP LD0.SSCBR1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK status\Condition
) ) status
monitoring\SSCBR1\Inputs
Signal for
Monitoring\I/O
CBCM(1 CBCM(1 open
SSCBR1 INP LD0.SSCBR1.ColOpn.stVal SPS BOOLEAN ST B 0 I1 OPEN_CB_EXE status\Condition
) ) command to
monitoring\SSCBR1\Inputs
coil
Signal for
Monitoring\I/O
CBCM(1 CBCM(1 open position
SSCBR1 INP LD0.SSCBR1.InPosOpn.stVal SPS BOOLEAN ST B 0 I1 POSOPEN status\Condition
) ) of apparatus
monitoring\SSCBR1\Inputs
from I/O
Signal for
Monitoring\I/O
CBCM(1 CBCM(1 closeposition
SSCBR1 INP LD0.SSCBR1.InPosCls.stVal SPS BOOLEAN ST B 0 I1 POSCLOSE status\Condition
) ) of apparatus
monitoring\SSCBR1\Inputs
from I/O

147
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Signal for
Monitoring\I/O
CBCM(1 CBCM(1 close
SSCBR1 INP LD0.SSCBR1.ColCls.stVal SPS BOOLEAN ST B 0 I1 CLOSE_CB_EXE status\Condition
) ) command to
monitoring\SSCBR1\Inputs
coil
Reset Monitoring\I/O
CBCM(1 CBCM(1
SSCBR1 INP LD0.SSCBR1.RsAccmAPwr.stVal SPC BOOLEAN ST B 0 I1 RST_IPOW accumulation status\Condition
) )
energy monitoring\SSCBR1\Inputs
Reset input
for CB Monitoring\I/O
CBCM(1 CBCM(1
SSCBR1 INP LD0.SSCBR1.RsCBWear.stVal SPC BOOLEAN ST B 0 I1 RST_CB_WEAR remaining life status\Condition
) )
and operation monitoring\SSCBR1\Inputs
counter
Reset input
for CB Monitoring\I/O
CBCM(1 CBCM(1
SSCBR1 INP LD0.SSCBR1.RsTrvTm.stVal SPC BOOLEAN ST B 0 I1 RST_TRV_T closing and status\Condition
) )
opening monitoring\SSCBR1\Inputs
travel times
Binary Monitoring\I/O
SSIMG1 INP LD0.SSIMG1.PresAlm.stVal SPS BOOLEAN ST B 0 I1 PRES_ALM_IN pressure status\Condition
alarm input monitoring\SSCBR1\Inputs
Binary
Monitoring\I/O
pressure input
SSIMG1 INP LD0.SSIMG1.PresBlk.stVal SPS BOOLEAN ST B 0 I1 PRES_LO_IN status\Condition
for lockout
monitoring\SSCBR1\Inputs
indication
CB spring Monitoring\I/O
SSOPM1 INP LD0.SSOPM1.SprChaStr.stVal SPS BOOLEAN ST B 0 I1 SPR_CHR_ST charging status\Condition
started input monitoring\SSCBR1\Inputs
Monitoring\I/O
CB spring
SSOPM1 INP LD0.SSOPM1.SprChaStop.stVal SPS BOOLEAN ST B 0 I1 SPR_CHR status\Condition
charged input
monitoring\SSCBR1\Inputs
Reset input
for the Monitoring\I/O
SSOPM1 INP LD0.SSOPM1.RsSprChaTm.stVal SPC BOOLEAN ST B 0 I1 RST_SPR_T charging time status\Condition
of the CB monitoring\SSCBR1\Inputs
spring
Number of
CB Monitoring\I/O
CBCM(1 CBCM(1
SSCBR1 OUT LD0.SSCBR1.OpCntAlm.stVal SPS BOOLEAN ST B StatIed P,H I1 OPR_ALM operations status\Condition
) )
exceeds monitoring\SSCBR1\Outputs
alarm limit
Monitoring\I/O
CBCM(1 CBCM(1 CB is in open
SSCBR1 OUT LD0.SSCBR1.PosOpn.stVal SPS BOOLEAN ST B I1 OPENPOS status\Condition
) ) position
monitoring\SSCBR1\Outputs
CB is in
invalid
Monitoring\I/O
CBCM(1 CBCM(1 position (not
SSCBR1 OUT LD0.SSCBR1.PosIvd.stVal SPS BOOLEAN ST B I1 INVALIDPOS status\Condition
) ) positively
monitoring\SSCBR1\Outputs
open or
closed)

148
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

CB is in Monitoring\I/O
CBCM(1 CBCM(1
SSCBR1 OUT LD0.SSCBR1.PosCls.stVal SPS BOOLEAN ST B I1 CLOSEPOS closed status\Condition
) )
position monitoring\SSCBR1\Outputs
CB open
Monitoring\I/O
CBCM(1 CBCM(1 TRV_T_OP_AL travel time
SSCBR1 OUT LD0.SSCBR1.OpnAlm.stVal SPS BOOLEAN ST B StatIed P,H I1 status\Condition
) ) M exceeded set
monitoring\SSCBR1\Outputs
value
CB close
Monitoring\I/O
CBCM(1 CBCM(1 TRV_T_CL_AL travel time
SSCBR1 OUT LD0.SSCBR1.ClsAlm.stVal SPS BOOLEAN ST B StatIed P,H I1 status\Condition
) ) M exceeded set
monitoring\SSCBR1\Outputs
value
Number of
CB Monitoring\I/O
CBCM(1 CBCM(1
SSCBR1 OUT LD0.SSCBR1.OpCntLO.stVal SPS BOOLEAN ST B StatIed P,H I1 OPR_LO operations status\Condition
) )
exceeds monitoring\SSCBR1\Outputs
lockout limit
CB 'not
Monitoring\I/O
CBCM(1 CBCM(1 operated for
SSCBR1 OUT LD0.SSCBR1.LonTmAlm.stVal SPS BOOLEAN ST B StatIed P,H I1 MON_ALM status\Condition
) ) long time'
monitoring\SSCBR1\Outputs
alarm
Accumulated
currents Monitoring\I/O
CBCM(1 CBCM(1
SSCBR1 OUT LD0.SSCBR1.APwrAlm.stVal SPS BOOLEAN ST B StatIed P,H I1 IPOW_ALM power status\Condition
) )
(Iyt),exceede monitoring\SSCBR1\Outputs
d alarm limit
Accumulated
currents
Monitoring\I/O
CBCM(1 CBCM(1 power
SSCBR1 OUT LD0.SSCBR1.APwrLO.stVal SPS BOOLEAN ST B StatIed P,H I1 IPOW_LO status\Condition
) ) (Iyt),exceede
monitoring\SSCBR1\Outputs
d lockout
limit
Remaining
Monitoring\I/O
CBCM(1 CBCM(1 life of CB
SSCBR1 OUT LD0.SSCBR1.RmnNumOpAlm.stVal SPS BOOLEAN ST ED2,B StatIed P,H I1 CB_LIFE_ALM status\Condition
) ) exceeded
monitoring\SSCBR1\Outputs
alarm limit
Remaining
Monitoring\I/O
CBCM(1 CBCM(1 life of CB
SSCBR1 OUT LD0.SSCBR1.RmnNumAlm.stVal SPS BOOLEAN ST ED1 StatIed P,H I1 CB_LIFE_ALM status\Condition
) ) exceeded
monitoring\SSCBR1\Outputs
alarm limit
Pressure Monitoring\I/O
SSIMG1 OUT LD0.SSIMG1.InsAlm.stVal SPS BOOLEAN ST B StatIed P,H I1 PRES_ALM below alarm status\Condition
level monitoring\SSCBR1\Outputs
Pressure Monitoring\I/O
SSIMG1 OUT LD0.SSIMG1.InsBlk.stVal SPS BOOLEAN ST B StatIed P,H I1 PRES_LO below status\Condition
lockout level monitoring\SSCBR1\Outputs
Spring
Monitoring\I/O
charging time
SSOPM1 OUT LD0.SSOPM1.SprChaAlm.stVal SPS BOOLEAN ST B StatIed P,H I1 SPR_CHR_ALM status\Condition
has crossed
monitoring\SSCBR1\Outputs
the set value

149
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Resets
CBCM(1 CBCM(1 LD0.SSCBR1.RsAccmAPwr.Oper.ctlVa SSCBR1 SSCBR1
SSCBR1 CTR SPC BOOLEAN CO B 0 I1 0=Cancel; 1=Clear Clear\Clear
) ) l acc.energy accumulation
energy
Reset
SSCBR1 CB
CBCM(1 CBCM(1
SSCBR1 CTR LD0.SSCBR1.RsCBWear.Oper.ctlVal SPC BOOLEAN CO B 0 I1 SSCBR1 rem.life remaining life 0=Cancel; 1=Clear Clear\Clear
) )
and operation
counter
Reset CB
CBCM(1 CBCM(1 SSCBR1 travel closing and
SSCBR1 CTR LD0.SSCBR1.RsTrvTm.Oper.ctlVal SPC BOOLEAN CO B 0 I1 0=Cancel; 1=Clear Clear\Clear
) ) times opening
travel times
Reset the
LD0.SSOPM1.RsSprChaTm.Oper.ctlVa SSCBR1 charging time
SSOPM1 CTR SPC BOOLEAN CO B 0 I1 0=Cancel; 1=Clear Clear\Clear
l spr.charge t of the CB
spring
1=on; 2=blocked;
CBCM(1 CBCM(1 3=test;
SSCBR1 MON LD0.SSCBR1.Beh.stVal ENS Enum ST B SSCBR1 Status Monitoring\FB status
) ) 4=test/blocked;
5=off
Travel time
Monitoring\I/O
of the CB
CBCM(1 CBCM(1 M status\Condition
SSCBR1 MON LD0.SSCBR1.OpTmOpn.mag.f MV FLOAT32 B I1 T_TRV_OP during 0...60000 ms
) ) X monitoring\SSCBR1\Monitore
opening
d data
operation
Travel time
Monitoring\I/O
of the CB
CBCM(1 CBCM(1 M status\Condition
SSCBR1 MON LD0.SSCBR1.OpTmCls.mag.f MV FLOAT32 B I1 T_TRV_CL during 0...60000 ms
) ) X monitoring\SSCBR1\Monitore
closing
d data
operation
Monitoring\I/O
Number of
CBCM(1 CBCM(1 status\Condition
SSCBR1 MON LD0.SSCBR1.OpCntRs.stVal INC INT32 ST B StatIed P,H I1 NO_OPR CB operation 0...99999
) ) monitoring\SSCBR1\Monitore
cycle
d data
The number Monitoring\I/O
CBCM(1 CBCM(1 of days CB status\Condition
SSCBR1 MON LD0.SSCBR1.InaTmdCnt.stVal INS INT32 ST B I1 INA_DAYS 0...9999
) ) has been monitoring\SSCBR1\Monitore
inactive d data
Monitoring\I/O
CB
SPH1SCBR status\Condition
MON LD0.SPH1SCBR1.RmnNumOp.stVal INS INT32 ST B I1 CB_LIFE_A Remaining -99999...99999
1 monitoring\SSCBR1\Monitore
life phase A
d data
Accumulated Monitoring\I/O
SPH1SCBR M currents status\Condition
MON LD0.SPH1SCBR1.AccmAPwr.mag.f MV FLOAT32 B I1 IPOW_A 0.000...30000.000
1 X power (Iyt), monitoring\SSCBR1\Monitore
phase A d data
CB
SPH2SCBR Monitoring\I/O
MON LD0.SPH2SCBR1.RmnNumOp.stVal INS INT32 ST B I1 CB_LIFE_B Remaining -99999...99999
1 status\Condition
life phase B
150
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

monitoring\SSCBR1\Monitore
d data
Accumulated Monitoring\I/O
SPH2SCBR M currents status\Condition
MON LD0.SPH2SCBR1.AccmAPwr.mag.f MV FLOAT32 B I1 IPOW_B 0.000...30000.000
1 X power (Iyt), monitoring\SSCBR1\Monitore
phase B d data
Monitoring\I/O
CB
SPH3SCBR status\Condition
MON LD0.SPH3SCBR1.RmnNumOp.stVal INS INT32 ST B I1 CB_LIFE_C Remaining -99999...99999
1 monitoring\SSCBR1\Monitore
life phase C
d data
Accumulated Monitoring\I/O
SPH3SCBR M currents status\Condition
MON LD0.SPH3SCBR1.AccmAPwr.mag.f MV FLOAT32 B I1 IPOW_C 0.000...30000.000
1 X power (Iyt), monitoring\SSCBR1\Monitore
phase C d data
Monitoring\I/O
The charging
M status\Condition
SSOPM1 MON LD0.SSOPM1.TmsSprCha.mag.f MV FLOAT32 B I1 T_SPR_CHR time of the 0.00...99.99 s
X monitoring\SSCBR1\Monitore
CB spring
d data
CBCM(1 CBCM(1 Operation Off Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
) ) / On monitoring\SSCBR1
Alarm limit
CBCM(1 CBCM(1 Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.OpAlmNum.setVal ING INT32 SP B 200 Alarm Op number for number of 0...99999
) ) monitoring\SSCBR1
operations
Alarm level
CBCM(1 CBCM(1 setting for Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.OpnAlmTmms.setVal ING INT32 SP B 40 Open alarm time 0...200 ms
) ) open travel monitoring\SSCBR1
time in ms
Correction
CBCM(1 CBCM(1 factor for Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.CorOpnTmms.setVal ING INT32 SP A 10 Opening time Cor -100...100 ms
) ) open travel monitoring\SSCBR1
time in ms
Alarm level
CBCM(1 CBCM(1 Setting for Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.ClsAlmTmms.setVal ING INT32 SP B 40 Close alarm time 0...200 ms
) ) close travel monitoring\SSCBR1
time in ms
Correction
CBCM(1 CBCM(1 factor for CB Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.CorClsTmms.setVal ING INT32 SP A 10 Closing time Cor -100...100 ms
) ) close travel monitoring\SSCBR1
time in ms
Corr. factor
for time dif in
CBCM(1 CBCM(1 Difference Cor Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.CorDifTmms.setVal ING INT32 SP B 5 aux. and main -10...10 ms
) ) time monitoring\SSCBR1
contacts open
time
Lock out
CBCM(1 CBCM(1 Lockout Op limit for Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.OpLONum.setVal ING INT32 SP B 300 0...99999
) ) number number of monitoring\SSCBR1
operations
CBCM(1 CBCM(1 Number of Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.OpNumRtg.setVal ING INT32 SP B 10000 Op number rated 1...99999
) ) operations monitoring\SSCBR1
151
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

possible at
rated current
Alarm level
CBCM(1 CBCM(1 Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.NumOpAlmLev.setVal ING INT32 SP ED2,A 500 Life alarm level for CB 0...99999
) ) monitoring\SSCBR1
remaining life
Alarm level
CBCM(1 CBCM(1 Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.NumAlmLev.setVal ING INT32 SP ED1 500 Life alarm level for CB 0...99999
) ) monitoring\SSCBR1
remaining life
Number of
operations
CBCM(1 CBCM(1 Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.OpNumFlt.setVal ING INT32 SP B 1000 Op number fault possible at 1...10000
) ) monitoring\SSCBR1
rated fault
current
The operation
numbers
CBCM(1 CBCM(1 Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.CntIniVal.setVal ING INT32 SP A,I 0 Counter initial Val counter 0...99999
) ) monitoring\SSCBR1
initialization
value
Alarm limit
CBCM(1 CBCM(1 value of the Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.InaAlmTmd.setVal ING INT32 SP B,I 2000 Inactive Alm days 0...9999
) ) inactive days monitoring\SSCBR1
counter
Initial value
CBCM(1 CBCM(1 of the Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.IniInaTmd.setVal ING INT32 SP A,I 0 Ini inactive days 0...9999
) ) inactive days monitoring\SSCBR1
counter
Alarm time of
CBCM(1 CBCM(1 Inactive Alm the inactive Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.InaAlmTmh.setVal ING INT32 SP A,I 0 0...23 h
) ) hours days counter monitoring\SSCBR1
in hours
Travel time
1=From Cmd to
CBCM(1 CBCM(1 EN Travel time Clc calculation Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.TrvClcMod.setVal Enum SP B 2 Pos; 2=From Pos
) ) G mode mode monitoring\SSCBR1
to Pos
selection
Directional
CBCM(1 CBCM(1 coefficient Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.DirCff.setMag.f ASG FLOAT32 SP B,I -1.50 Directional Coef -3.00...-0.50
) ) for CB life monitoring\SSCBR1
calculation
Initial value
CBCM(1 CBCM(1 ED2,B, Initial CB Rmn Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.IniRmnNumOp.setMag.f ASG FLOAT32 SP 5000 for the CB 0...99999
) ) I life monitoring\SSCBR1
remaining life
Initial value
CBCM(1 CBCM(1 Initial CB Rmn Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.IniRmnNum.setMag.f ASG FLOAT32 SP ED1 5000 for the CB 0...99999
) ) life monitoring\SSCBR1
remaining life
Setting of
alarm level
CBCM(1 CBCM(1 2500.0 Alm Acc currents for Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.AlmAccmAPwr.setMag.f ASG FLOAT32 SP ED2,B 0.00...20000.00
) ) 0 Pwr accumulated monitoring\SSCBR1
currents
power
152
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Setting of
alarm level
CBCM(1 CBCM(1 2500.0 Alm Acc currents for Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.AlmAccAPwr.setMag.f ASG FLOAT32 SP ED1 0.00...20000.00
) ) 0 Pwr accumulated monitoring\SSCBR1
currents
power
RMS current
CBCM(1 CBCM(1 setting below Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.AccmStopA.setMag.f ASG FLOAT32 SP B 10.00 Acc stop current 5.00...500.00 A
) ) which engy monitoring\SSCBR1
acm stops
Lockout limit
setting for
CBCM(1 CBCM(1 2500.0 LO Acc currents Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.LOAccmAPwr.setMag.f ASG FLOAT32 SP B accumulated 0.00...20000.00
) ) 0 Pwr monitoring\SSCBR1
currents
power
Current
exponent
CBCM(1 CBCM(1 Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.AExpn.setMag.f ASG FLOAT32 SP B,I 2.00 Current exponent setting for 0.00...2.00
) ) monitoring\SSCBR1
energy
calculation
Rated
CBCM(1 CBCM(1 1000.0 operating Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.AOpRtg.setMag.f ASG FLOAT32 SP B Rated Op current 100.00...5000.00 A
) ) 0 current of the monitoring\SSCBR1
breaker
Rated fault
CBCM(1 CBCM(1 5000.0 500.00...75000.00 Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.AFltRtg.setMag.f ASG FLOAT32 SP B Rated fault current current of the
) ) 0 A monitoring\SSCBR1
breaker
Initial value
CBCM(1 CBCM(1 Ini Acc currents for Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.IniAccmAPwr.setMag.f ASG FLOAT32 SP ED2,A 0.00 0.00...20000.00
) ) Pwr accumulation monitoring\SSCBR1
energy (Iyt)
Initial value
CBCM(1 CBCM(1 Ini Acc currents for Configuration\Condition
SSCBR1 CFG LD0.SSCBR1.IniAccAPwr.setMag.f ASG FLOAT32 SP ED1 0.00 0.00...20000.00
) ) Pwr accumulation monitoring\SSCBR1
energy (Iyt)
Time delay
Pressure alarm for gas Configuration\Condition
SSIMG1 CFG LD0.SSIMG1.InsAlmTmms.setVal ING INT32 SP A 10 0...60000 ms
time pressure monitoring\SSCBR1
alarm in ms
Time delay
for gas Configuration\Condition
SSIMG1 CFG LD0.SSIMG1.InsBlkTmms.setVal ING INT32 SP A 10 Pres lockout time 0...60000 ms
pressure monitoring\SSCBR1
lockout in ms
Setting of
alarm for
Spring charge Configuration\Condition
SSOPM1 CFG LD0.SSOPM1.SprChaTmms.setVal ING INT32 SP B 15000 spring 0...60000 ms
time monitoring\SSCBR1
charging time
of CB in ms
CBCM(1 CBCM(1 Test control 0=Reset; 9=Act. Tests\Function tests\Condition
SSCBR1 TES LD0.SSCBR1.TestSpvn.Oper.ctlVal ENC Enum CO B 0 SSCBR1
) ) for outputs TRV_T_OP_ALM monitoring
153
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

; 10=Deact.
TRV_T_OP_ALM
; 11=Act.
TRV_T_CL_ALM
; 12=Deact.
TRV_T_CL_ALM
; 17=Activate
SPR_CHR_ALM;
18=Deactive
SPR_CHR_ALM;
19=Activate
OPR_ALM;
20=Deactive
OPR_ALM;
21=Activate
OPR_LO;
22=Deactive
OPR_LO;
23=Activate
IPOW_ALM;
24=Deactive
IPOW_ALM;
25=Activate
IPOW_LO;
26=Deactive
IPOW_LO;
27=Activate
CB_LIFE_ALM;
28=Deactive
CB_LIFE_ALM;
29=Activate
MON_ALM;
30=Deactive
MON_ALM;
31=Activate
PRES_ALM;
32=Deactive
PRES_ALM;
33=Activate
PRES_LO;
34=Deactive
PRES_LO;
35=Activate
OPENPOS;
36=Deactive
OPENPOS;
37=Activate
INVALIDPOS;
38=Deactive
INVALIDPOS;
39=Activate
CLOSEPOS;
40=Deactive
CLOSEPOS
154
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

CBCM(1 CBCM(1 VisString25


SSCBR1 VER LD0.SSCBR1.NamPlt.swRev LPL DC ED1 F1 (Name plate)
) ) 5 (20)

MDSOPT1: Generic operation time supervision for machines and devices: D1


IEC Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Parameter range Menu path
60617 name relation
Block input Monitoring\I/O status\Condition
MDSOPT1 OPTS(1) OPTM(1) INP LD0.MDSOPT1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
status monitoring\MDSOPT1\Inputs
Resets the
accumulated Monitoring\I/O status\Condition
MDSOPT1 OPTS(1) OPTM(1) INP LD0.MDSOPT1.OpTmRs.stVal SPC BOOLEAN ST B 0 I1 RESET
operation time monitoring\MDSOPT1\Inputs
to initial value
When active
indicates the Monitoring\I/O status\Condition
MDSOPT1 OPTS(1) OPTM(1) INP LD0.MDSOPT1.TmOp.stVal SPS BOOLEAN ST B 0 I1 POS_ACTIVE
equipment is monitoring\MDSOPT1\Inputs
running
Warning
accumulated
Monitoring\I/O status\Condition
MDSOPT1 OPTS(1) OPTM(1) OUT LD0.MDSOPT1.OpTmWrn.stVal SPS BOOLEAN ST B StatIed P,H I1 WARNING operation time
monitoring\MDSOPT1\Outputs
exceeds
Warning value
Alarm
accumulated
Monitoring\I/O status\Condition
MDSOPT1 OPTS(1) OPTM(1) OUT LD0.MDSOPT1.OpTmAlm.stVal SPS BOOLEAN ST B StatIed P,H I1 ALARM operation time
monitoring\MDSOPT1\Outputs
exceeds Alarm
value
Resets the
MDSOPT1 accumulated
MDSOPT1 OPTS(1) OPTM(1) CTR LD0.MDSOPT1.OpTmRs.Oper.ctlVal SPC BOOLEAN CO B 0 I1 0=Cancel; 1=Clear Clear\Clear
operation t operation time
to initial value
1=on; 2=blocked;
3=test;
MDSOPT1 OPTS(1) OPTM(1) MON LD0.MDSOPT1.Beh.stVal ENS Enum ST B MDSOPT1 Status Monitoring\FB status
4=test/blocked;
5=off
Monitoring\I/O status\Condition
Total operation
MDSOPT1 OPTS(1) OPTM(1) MON LD0.MDSOPT1.OpTmh.stVal INS INT32 ST B I1 OPR_TIME 0...299999 h monitoring\MDSOPT1\Monitored
time in hours
data
Operation Off Configuration\Condition
MDSOPT1 OPTS(1) OPTM(1) CFG LD0.MDSOPT1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
/ On monitoring\MDSOPT1
Warning value
for operation Configuration\Condition
MDSOPT1 OPTS(1) OPTM(1) CFG LD0.MDSOPT1.OpWrnTmh.setVal ING INT32 SP B 8000 Warning value 0...299999 h
time monitoring\MDSOPT1
supervision
Alarm value
for operation Configuration\Condition
MDSOPT1 OPTS(1) OPTM(1) CFG LD0.MDSOPT1.OpAlmTmh.setVal ING INT32 SP B 10000 Alarm value 0...299999 h
time monitoring\MDSOPT1
supervision

155
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Initial value
for operation Configuration\Condition
MDSOPT1 OPTS(1) OPTM(1) CFG LD0.MDSOPT1.IniOpTmh.setVal ING INT32 SP A 0 Initial value 0...299999 h
time monitoring\MDSOPT1
supervision
Time of day
Operating time when alarm Configuration\Condition
MDSOPT1 OPTS(1) OPTM(1) CFG LD0.MDSOPT1.OpActTmh.setVal ING INT32 SP A 0 0...23 h
hour and warning monitoring\MDSOPT1
will occur
Operating time
1=Immediate;
Operating time mode for Configuration\Condition
MDSOPT1 OPTS(1) OPTM(1) CFG LD0.MDSOPT1.OpActMod.setVal ENG Enum SP A 1 2=Timed Warn;
mode warning and monitoring\MDSOPT1
3=Timed Warn Alm
alarm
0=Reset;
17=Activate
ALARM;
18=Deactive
Operation Off Tests\Function tests\Condition
MDSOPT1 OPTS(1) OPTM(1) TES LD0.MDSOPT1.TstOutCmd.Oper.ctlVal ENC Enum CO B 1 MDSOPT1 ALARM;
/ On monitoring
19=Activate
WARNING;
20=Deactive
WARNING
VisString255
MDSOPT1 OPTS(1) OPTM(1) VER LD0.MDSOPT1.NamPlt.swRev LPL DC D1 (Name plate)
(20)

CMMXU1: Three-phase current measurement: E1


IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter name Menu path
60617 desc range relation
(ACT input
CMMXU1 3I(1) 3I(1) INP Channel I3P
channel)
Block signal
Monitoring\I/O
CMMXU1 3I(1) 3I(1) INP LD0.CMMXU1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK for all binary
status\Measurements\CMMXU1\Inputs
outputs
Monitoring\I/O
CMMXU1 3I(1) 3I(1) OUT LD0.CMMXU1.HiAlm.stVal SPS BOOLEAN ST B StatUrg P,H I1 HIGH_ALARM High alarm
status\Measurements\CMMXU1\Outputs
Monitoring\I/O
CMMXU1 3I(1) 3I(1) OUT LD0.CMMXU1.HiWrn.stVal SPS BOOLEAN ST B StatUrg P,H I1 HIGH_WARN High warning
status\Measurements\CMMXU1\Outputs
Monitoring\I/O
CMMXU1 3I(1) 3I(1) OUT LD0.CMMXU1.LoWrn.stVal SPS BOOLEAN ST B StatUrg P,H I1 LOW_WARN Low warning
status\Measurements\CMMXU1\Outputs
Monitoring\I/O
CMMXU1 3I(1) 3I(1) OUT LD0.CMMXU1.LoAlm.stVal SPS BOOLEAN ST B StatUrg P,H I1 LOW_ALARM Low alarm
status\Measurements\CMMXU1\Outputs
(CMMXU1
CMMXU1 3I(1) 3I(1) CTR LD0.CMMXU1.RcdRs.Oper.ctlVal SPC BOOLEAN CO I1
demands)
Measured
current
CMMXU1 3I(1) 3I(1) MON LD0.CMMXU1.A.phsA.instCVal.mag.f WYE FLOAT32 MX B MeasFlt P IL1-A 0.00...40.00 xIn Measurements\CMMXU1 IL1TCTR1
amplitude
phase A

156
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

- Monitoring\I/O
IL1 current
CMMXU1 3I(1) 3I(1) MON LD0.CMMXU1.A.phsA.instCVal.ang.f WYE FLOAT32 MX B MeasFlt P I_ANGL_A 180.00...180.00 status\Measurements\CMMXU1\Monitored IL1TCTR1
angle
deg data
IL1
Monitoring\I/O
Amplitude,
CMMXU1 3I(1) 3I(1) MON LD0.CMMXU1.A.phsA.cVal.mag.f WYE FLOAT32 MX B MeasFlt P I1 I_DB_A 0.00...40.00 xIn status\Measurements\CMMXU1\Monitored IL1TCTR1
magnitude of
data
reported value
0=normal;
IL1 Monitoring\I/O
1=high; 2=low;
CMMXU1 3I(1) 3I(1) MON LD0.CMMXU1.A.phsA.range WYE Enum MX B MeasFlt P I_RANGE_A Amplitude status\Measurements\CMMXU1\Monitored IL1TCTR1
3=high-high;
range data
4=low-low
Measured
current
CMMXU1 3I(1) 3I(1) MON LD0.CMMXU1.A.phsB.instCVal.mag.f WYE FLOAT32 MX B MeasFlt P IL2-A 0.00...40.00 xIn Measurements\CMMXU1 IL1TCTR1
amplitude
phase B
- Monitoring\I/O
IL2 current
CMMXU1 3I(1) 3I(1) MON LD0.CMMXU1.A.phsB.instCVal.ang.f WYE FLOAT32 MX B MeasFlt P I_ANGL_B 180.00...180.00 status\Measurements\CMMXU1\Monitored IL1TCTR1
angle
deg data
IL2
Monitoring\I/O
Amplitude,
CMMXU1 3I(1) 3I(1) MON LD0.CMMXU1.A.phsB.cVal.mag.f WYE FLOAT32 MX B MeasFlt P I1 I_DB_B 0.00...40.00 xIn status\Measurements\CMMXU1\Monitored IL1TCTR1
magnitude of
data
reported value
0=normal;
IL2 Monitoring\I/O
1=high; 2=low;
CMMXU1 3I(1) 3I(1) MON LD0.CMMXU1.A.phsB.range WYE Enum MX B MeasFlt P I_RANGE_B Amplitude status\Measurements\CMMXU1\Monitored IL1TCTR1
3=high-high;
range data
4=low-low
Measured
current
CMMXU1 3I(1) 3I(1) MON LD0.CMMXU1.A.phsC.instCVal.mag.f WYE FLOAT32 MX B MeasFlt P IL3-A 0.00...40.00 xIn Measurements\CMMXU1 IL1TCTR1
amplitude
phase C
- Monitoring\I/O
IL3 current
CMMXU1 3I(1) 3I(1) MON LD0.CMMXU1.A.phsC.instCVal.ang.f WYE FLOAT32 MX B MeasFlt P I_ANGL_C 180.00...180.00 status\Measurements\CMMXU1\Monitored IL1TCTR1
angle
deg data
IL3
Monitoring\I/O
Amplitude,
CMMXU1 3I(1) 3I(1) MON LD0.CMMXU1.A.phsC.cVal.mag.f WYE FLOAT32 MX B MeasFlt P I1 I_DB_C 0.00...40.00 xIn status\Measurements\CMMXU1\Monitored IL1TCTR1
magnitude of
data
reported value
0=normal;
IL3 Monitoring\I/O
1=high; 2=low;
CMMXU1 3I(1) 3I(1) MON LD0.CMMXU1.A.phsC.range WYE Enum MX B MeasFlt P I_RANGE_C Amplitude status\Measurements\CMMXU1\Monitored IL1TCTR1
3=high-high;
range data
4=low-low
Monitoring\I/O
Demand value
CMMXU1 3I(1) 3I(1) MON LD0.CAVMMXU1.A.phsA.cVal.mag.f WYE FLOAT32 MX B I1 I_DMD_A 0.00...40.00 xIn status\Measurements\CMMXU1\Monitored IL1TCTR1
of IL1 current
data
Monitoring\I/O
Demand value
CMMXU1 3I(1) 3I(1) MON LD0.CAVMMXU1.A.phsB.cVal.mag.f WYE FLOAT32 MX B I1 I_DMD_B 0.00...40.00 xIn status\Measurements\CMMXU1\Monitored IL1TCTR1
of IL2 current
data
Monitoring\I/O
Demand value
CMMXU1 3I(1) 3I(1) MON LD0.CAVMMXU1.A.phsC.cVal.mag.f WYE FLOAT32 MX B I1 I_DMD_C 0.00...40.00 xIn status\Measurements\CMMXU1\Monitored IL1TCTR1
of IL3 current
data
157
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Maximum
Max demand Monitoring\Recorded
CMMXU1 3I(1) 3I(1) MON LD0.CMAMMXU1.A.phsA.cVal.mag.f WYE FLOAT32 MX B I1 demand for 0.00...40.00 xIn IL1TCTR1
IL1 data\Measurements\CMMXU1
Phase A
Time of
Time max maximum Monitoring\Recorded
CMMXU1 3I(1) 3I(1) MON LD0.CMAMMXU1.A.phsA.t WYE Timestamp MX B IL1TCTR1
demand IL1 demand phase data\Measurements\CMMXU1
A
Maximum
Max demand Monitoring\Recorded
CMMXU1 3I(1) 3I(1) MON LD0.CMAMMXU1.A.phsB.cVal.mag.f WYE FLOAT32 MX B I1 demand for 0.00...40.00 xIn IL1TCTR1
IL2 data\Measurements\CMMXU1
Phase B
Time of
Time max maximum Monitoring\Recorded
CMMXU1 3I(1) 3I(1) MON LD0.CMAMMXU1.A.phsB.t WYE Timestamp MX B IL1TCTR1
demand IL2 demand phase data\Measurements\CMMXU1
B
Maximum
Max demand Monitoring\Recorded
CMMXU1 3I(1) 3I(1) MON LD0.CMAMMXU1.A.phsC.cVal.mag.f WYE FLOAT32 MX B I1 demand for 0.00...40.00 xIn IL1TCTR1
IL3 data\Measurements\CMMXU1
Phase C
Time of
Time max maximum Monitoring\Recorded
CMMXU1 3I(1) 3I(1) MON LD0.CMAMMXU1.A.phsC.t WYE Timestamp MX B IL1TCTR1
demand IL3 demand phase data\Measurements\CMMXU1
C
Minimum
Min demand Monitoring\Recorded
CMMXU1 3I(1) 3I(1) MON LD0.CMIMMXU1.A.phsA.cVal.mag.f WYE FLOAT32 MX B I1 demand for 0.00...40.00 xIn IL1TCTR1
IL1 data\Measurements\CMMXU1
Phase A
Time of
Time min minimum Monitoring\Recorded
CMMXU1 3I(1) 3I(1) MON LD0.CMIMMXU1.A.phsA.t WYE Timestamp MX B IL1TCTR1
demand IL1 demand phase data\Measurements\CMMXU1
A
Minimum
Min demand Monitoring\Recorded
CMMXU1 3I(1) 3I(1) MON LD0.CMIMMXU1.A.phsB.cVal.mag.f WYE FLOAT32 MX B I1 demand for 0.00...40.00 xIn IL1TCTR1
IL2 data\Measurements\CMMXU1
Phase B
Time of
Time min minimum Monitoring\Recorded
CMMXU1 3I(1) 3I(1) MON LD0.CMIMMXU1.A.phsB.t WYE Timestamp MX B IL1TCTR1
demand IL2 demand phase data\Measurements\CMMXU1
B
Minimum
Min demand Monitoring\Recorded
CMMXU1 3I(1) 3I(1) MON LD0.CMIMMXU1.A.phsC.cVal.mag.f WYE FLOAT32 MX B I1 demand for 0.00...40.00 xIn IL1TCTR1
IL3 data\Measurements\CMMXU1
Phase C
Time of
Time min minimum Monitoring\Recorded
CMMXU1 3I(1) 3I(1) MON LD0.CMIMMXU1.A.phsC.t WYE Timestamp MX B IL1TCTR1
demand IL3 demand phase data\Measurements\CMMXU1
C
Operation Off
CMMXU1 3I(1) 3I(1) CFG LD0.CMMXU1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off Configuration\Measurements\CMMXU1
/ On
Deadband
configuration
value for
CMMXU1 3I(1) 3I(1) CFG LD0.CMMXU1.A.phsA.db WYE INT32U CF B,I 2500 A deadband 100...100000 Configuration\Measurements\CMMXU1 IL1TCTR1
integral
calculation.
(percentage of
158
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

difference
between min
and max as
0,001 % s)
A high high High alarm
CMMXU1 3I(1) 3I(1) CFG LD0.CMMXU1.A.phsA.rangeC.hhLim.f WYE FLOAT32 CF B,I 1.40 0.00...40.00 xIn Configuration\Measurements\CMMXU1 IL1TCTR1
limit current limit
High warning
CMMXU1 3I(1) 3I(1) CFG LD0.CMMXU1.A.phsA.rangeC.hLim.f WYE FLOAT32 CF B,I 1.20 A high limit 0.00...40.00 xIn Configuration\Measurements\CMMXU1 IL1TCTR1
current limit
Low warning
CMMXU1 3I(1) 3I(1) CFG LD0.CMMXU1.A.phsA.rangeC.lLim.f WYE FLOAT32 CF B,I 0.00 A low limit 0.00...40.00 xIn Configuration\Measurements\CMMXU1 IL1TCTR1
current limit
Low alarm
CMMXU1 3I(1) 3I(1) CFG LD0.CMMXU1.A.phsA.rangeC.llLim.f WYE FLOAT32 CF B,I 0.00 A low low limit 0.00...40.00 xIn Configuration\Measurements\CMMXU1 IL1TCTR1
current limit
Selects used
Measurement 1=RMS;
CMMXU1 3I(1) 3I(1) CFG LD0.CMMXU1.AMeasMod.setVal ENG Enum SP A 2 measurement Configuration\Measurements\CMMXU1
mode 2=DFT
mode
Number of
phases 1=1 out of 3;
CMMXU1 3I(1) 3I(1) CFG LD0.CMMXU1.NumPh.setVal ENG Enum SP B 1 Num of phases required by 2=2 out of 3; Configuration\Measurements\CMMXU1
limit 3=3 out of 3
supervision
VisString255
CMMXU1 3I(1) 3I(1) VER LD0.CMMXU1.NamPlt.swRev LPL DC ED1 E1 (Name plate)
(20)

CSMSQI1: Sequence current measurement: C1


IEC IEC Categor CD Acces Defaul Even CM Parameter Parameter Parameter Channel
ANSI IECName Type FC Dataset Menu path
61850 60617 y C s t t T name desc range relation
CSMSQI I1,I2,I0(1 I1,I2,I0(1 (ACT input
INP Channel I3P
1 ) ) channel)
Measured
CSMSQI I1,I2,I0(1 I1,I2,I0(1 M MeasFl positive 0.00...40.00 IL1TCTR
MON LD0.CSMSQI1.SeqA.c1.instCVal.mag.f SEQ FLOAT32 B P PsSeq-A Measurements\CSMSQI1
1 ) ) X t sequence xIn 1
current
Positive - Monitoring\I/O
CSMSQI I1,I2,I0(1 I1,I2,I0(1 M MeasFl IL1TCTR
MON LD0.CSMSQI1.SeqA.c1.instCVal.ang.f SEQ FLOAT32 B P I1_ANGL sequence 180.00...180.0 status\Measurements\CSMSQI1\Monitore
1 ) ) X t 1
current angle 0 deg d data
Positive
sequence
Monitoring\I/O
CSMSQI I1,I2,I0(1 I1,I2,I0(1 M MeasFl current 0.00...40.00 IL1TCTR
MON LD0.CSMSQI1.SeqA.c1.cVal.mag.f SEQ FLOAT32 B P I1 I1_DB status\Measurements\CSMSQI1\Monitore
1 ) ) X t amplitude, xIn 1
d data
reported
value
Positive
0=normal;
sequence Monitoring\I/O
CSMSQI I1,I2,I0(1 I1,I2,I0(1 M MeasFl I1_RANG 1=high; 2=low; IL1TCTR
MON LD0.CSMSQI1.SeqA.c1.range SEQ Enum B P current status\Measurements\CSMSQI1\Monitore
1 ) ) X t E 3=high-high; 1
amplitude d data
4=low-low
range

159
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Measured
CSMSQI I1,I2,I0(1 I1,I2,I0(1 M MeasFl negative 0.00...40.00 IL1TCTR
MON LD0.CSMSQI1.SeqA.c2.instCVal.mag.f SEQ FLOAT32 B P NgSeq-A Measurements\CSMSQI1
1 ) ) X t sequence xIn 1
current
Negative - Monitoring\I/O
CSMSQI I1,I2,I0(1 I1,I2,I0(1 M MeasFl IL1TCTR
MON LD0.CSMSQI1.SeqA.c2.instCVal.ang.f SEQ FLOAT32 B P I2_ANGL sequence 180.00...180.0 status\Measurements\CSMSQI1\Monitore
1 ) ) X t 1
current angle 0 deg d data
Negative
sequence
Monitoring\I/O
CSMSQI I1,I2,I0(1 I1,I2,I0(1 M MeasFl current 0.00...40.00 IL1TCTR
MON LD0.CSMSQI1.SeqA.c2.cVal.mag.f SEQ FLOAT32 B P I1 I2_DB status\Measurements\CSMSQI1\Monitore
1 ) ) X t amplitude, xIn 1
d data
reported
value
Negative
0=normal;
sequence Monitoring\I/O
CSMSQI I1,I2,I0(1 I1,I2,I0(1 M MeasFl I2_RANG 1=high; 2=low; IL1TCTR
MON LD0.CSMSQI1.SeqA.c2.range SEQ Enum B P current status\Measurements\CSMSQI1\Monitore
1 ) ) X t E 3=high-high; 1
amplitude d data
4=low-low
range
Measured
CSMSQI I1,I2,I0(1 I1,I2,I0(1 M MeasFl zero 0.00...40.00 IL1TCTR
MON LD0.CSMSQI1.SeqA.c3.instCVal.mag.f SEQ FLOAT32 B P ZroSeq-A Measurements\CSMSQI1
1 ) ) X t sequence xIn 1
current
Zero - Monitoring\I/O
CSMSQI I1,I2,I0(1 I1,I2,I0(1 M MeasFl IL1TCTR
MON LD0.CSMSQI1.SeqA.c3.instCVal.ang.f SEQ FLOAT32 B P I0_ANGL sequence 180.00...180.0 status\Measurements\CSMSQI1\Monitore
1 ) ) X t 1
current angle 0 deg d data
Zero
sequence
Monitoring\I/O
CSMSQI I1,I2,I0(1 I1,I2,I0(1 M MeasFl current 0.00...40.00 IL1TCTR
MON LD0.CSMSQI1.SeqA.c3.cVal.mag.f SEQ FLOAT32 B P I1 I0_DB status\Measurements\CSMSQI1\Monitore
1 ) ) X t amplitude, xIn 1
d data
reported
value
Zero
0=normal;
sequence Monitoring\I/O
CSMSQI I1,I2,I0(1 I1,I2,I0(1 M MeasFl I0_RANG 1=high; 2=low; IL1TCTR
MON LD0.CSMSQI1.SeqA.c3.range SEQ Enum B P current status\Measurements\CSMSQI1\Monitore
1 ) ) X t E 3=high-high; 1
amplitude d data
4=low-low
range
CSMSQI I1,I2,I0(1 I1,I2,I0(1 Operation
CFG LD0.CSMSQI1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off Configuration\Measurements\CSMSQI1
1 ) ) Off / On
Deadband
configuratio
n value for
positive
sequence
current for
CSMSQI I1,I2,I0(1 I1,I2,I0(1 Ps Seq A IL1TCTR
CFG LD0.CSMSQI1.SeqA.c1.db SEQ INT32U CF B,I 2500 integral 100...100000 Configuration\Measurements\CSMSQI1
1 ) ) deadband 1
calculation.
(percentage
of difference
between min
and max as
0,001 % s)
160
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

High alarm
Ps Seq A current limit
CSMSQI I1,I2,I0(1 I1,I2,I0(1 LD0.CSMSQI1.SeqA.c1.rangeC.hhLim. 0.00...40.00 IL1TCTR
CFG SEQ FLOAT32 CF B,I 1.40 Hi high for positive Configuration\Measurements\CSMSQI1
1 ) ) f xIn 1
Lim sequence
current
High
warning
CSMSQI I1,I2,I0(1 I1,I2,I0(1 Ps Seq A current limit 0.00...40.00 IL1TCTR
CFG LD0.CSMSQI1.SeqA.c1.rangeC.hLim.f SEQ FLOAT32 CF B,I 1.20 Configuration\Measurements\CSMSQI1
1 ) ) high limit for positive xIn 1
sequence
current
Low warning
current limit
CSMSQI I1,I2,I0(1 I1,I2,I0(1 Ps Seq A 0.00...40.00 IL1TCTR
CFG LD0.CSMSQI1.SeqA.c1.rangeC.lLim.f SEQ FLOAT32 CF B,I 0.00 for positive Configuration\Measurements\CSMSQI1
1 ) ) low limit xIn 1
sequence
current
Low alarm
Ps Seq A current limit
CSMSQI I1,I2,I0(1 I1,I2,I0(1 0.00...40.00 IL1TCTR
CFG LD0.CSMSQI1.SeqA.c1.rangeC.llLim.f SEQ FLOAT32 CF B,I 0.00 low low for positive Configuration\Measurements\CSMSQI1
1 ) ) xIn 1
Lim sequence
current
Deadband
configuratio
n value for
negative
sequence
current for
CSMSQI I1,I2,I0(1 I1,I2,I0(1 Ng Seq A IL1TCTR
CFG LD0.CSMSQI1.SeqA.c2.db SEQ INT32U CF B,I 2500 integral 100...100000 Configuration\Measurements\CSMSQI1
1 ) ) deadband 1
calculation.
(percentage
of difference
between min
and max as
0,001 % s)
High alarm
Ng Seq A current limit
CSMSQI I1,I2,I0(1 I1,I2,I0(1 LD0.CSMSQI1.SeqA.c2.rangeC.hhLim. 0.00...40.00 IL1TCTR
CFG SEQ FLOAT32 CF B,I 0.20 Hi high for negative Configuration\Measurements\CSMSQI1
1 ) ) f xIn 1
Lim sequence
current
High
warning
CSMSQI I1,I2,I0(1 I1,I2,I0(1 Ng Seq A current limit 0.00...40.00 IL1TCTR
CFG LD0.CSMSQI1.SeqA.c2.rangeC.hLim.f SEQ FLOAT32 CF B,I 0.05 Configuration\Measurements\CSMSQI1
1 ) ) High limit for negative xIn 1
sequence
current
Low warning
current limit
CSMSQI I1,I2,I0(1 I1,I2,I0(1 Ng Seq A 0.00...40.00 IL1TCTR
CFG LD0.CSMSQI1.SeqA.c2.rangeC.lLim.f SEQ FLOAT32 CF B,I 0.00 for negative Configuration\Measurements\CSMSQI1
1 ) ) low limit xIn 1
sequence
current

161
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Low alarm
Ng Seq A current limit
CSMSQI I1,I2,I0(1 I1,I2,I0(1 0.00...40.00 IL1TCTR
CFG LD0.CSMSQI1.SeqA.c2.rangeC.llLim.f SEQ FLOAT32 CF B,I 0.00 low low for negative Configuration\Measurements\CSMSQI1
1 ) ) xIn 1
Lim sequence
current
Deadband
configuratio
n value for
zero
sequence
current for
CSMSQI I1,I2,I0(1 I1,I2,I0(1 Zro A IL1TCTR
CFG LD0.CSMSQI1.SeqA.c3.db SEQ INT32U CF B,I 2500 integral 100...100000 Configuration\Measurements\CSMSQI1
1 ) ) deadband 1
calculation.
(percentage
of difference
between min
and max as
0,001 % s)
High alarm
current limit
CSMSQI I1,I2,I0(1 I1,I2,I0(1 LD0.CSMSQI1.SeqA.c3.rangeC.hhLim. Zro A Hi 0.00...40.00 IL1TCTR
CFG SEQ FLOAT32 CF B,I 0.20 for zero Configuration\Measurements\CSMSQI1
1 ) ) f high Lim xIn 1
sequence
current
High
warning
CSMSQI I1,I2,I0(1 I1,I2,I0(1 Zro A High current limit 0.00...40.00 IL1TCTR
CFG LD0.CSMSQI1.SeqA.c3.rangeC.hLim.f SEQ FLOAT32 CF B,I 0.05 Configuration\Measurements\CSMSQI1
1 ) ) limit for zero xIn 1
sequence
current
Low warning
current limit
CSMSQI I1,I2,I0(1 I1,I2,I0(1 Zro A low 0.00...40.00 IL1TCTR
CFG LD0.CSMSQI1.SeqA.c3.rangeC.lLim.f SEQ FLOAT32 CF B,I 0.00 for zero Configuration\Measurements\CSMSQI1
1 ) ) limit xIn 1
sequence
current
Low alarm
current limit
CSMSQI I1,I2,I0(1 I1,I2,I0(1 Zro A low 0.00...40.00 IL1TCTR
CFG LD0.CSMSQI1.SeqA.c3.rangeC.llLim.f SEQ FLOAT32 CF B,I 0.00 for zero Configuration\Measurements\CSMSQI1
1 ) ) low Lim xIn 1
sequence
current
CSMSQI I1,I2,I0(1 I1,I2,I0(1 VisString25
VER LD0.CSMSQI1.NamPlt.swRev LPL DC ED1 C1 (Name plate)
1 ) ) 5 (20)

RESCMMXU1: Residual current measurement: E1


IEC
ANS Categor Acces Defaul Even CM Parameter Parameter Channel
IEC 61850 6061 IECName CDC Type FC Dataset Parameter desc Menu path
I y s t t T name range relation
7
RESCMMXU (ACT input
Io(1) In(1) INP Channel IRES
1 channel)

162
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Block signal
RESCMMXU Monitoring\I/O
Io(1) In(1) INP LD0.RESCMMXU1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK for all binary
1 status\Measurements\RESCMMXU1\Inputs
outputs
RESCMMXU StatUr HIGH_ALAR Monitoring\I/O
Io(1) In(1) OUT LD0.RESCMMXU1.HiAlm.stVal SPS BOOLEAN ST B P,H I1 High alarm
1 g M status\Measurements\RESCMMXU1\Outputs
RESCMMXU StatUr Monitoring\I/O
Io(1) In(1) OUT LD0.RESCMMXU1.HiWrn.stVal SPS BOOLEAN ST B P,H I1 HIGH_WARN High warning
1 g status\Measurements\RESCMMXU1\Outputs
RESCMMXU (RESCMMXU
Io(1) In(1) CTR LD0.RESCMMXU1.RcdRs.Oper.ctlVal SPC BOOLEAN CO I1
1 1 demands)
Measured
RESCMMXU LD0.RESCMMXU1.A.res.instCVal.ma WY M MeasFl 0.00...40.00 RESTCTR
Io(1) In(1) MON FLOAT32 B P Io-A residual Measurements\RESCMMXU1
1 g.f E X t xIn 1
current
- Monitoring\I/O
RESCMMXU LD0.RESCMMXU1.A.res.instCVal.ang WY M MeasFl Residual RESTCTR
Io(1) In(1) MON FLOAT32 B P I_ANGL_RES 180.00...180.0 status\Measurements\RESCMMXU1\Monito
1 .f E X t current angle 1
0 deg red data
Residual
current Monitoring\I/O
RESCMMXU WY M MeasFl 0.00...40.00 RESTCTR
Io(1) In(1) MON LD0.RESCMMXU1.A.res.cVal.mag.f FLOAT32 B P I1 I_DB_RES Amplitude, status\Measurements\RESCMMXU1\Monito
1 E X t xIn 1
magnitude of red data
reported value
0=normal;
Residual
1=high; Monitoring\I/O
RESCMMXU WY M MeasFl I_RANGE_RE current RESTCTR
Io(1) In(1) MON LD0.RESCMMXU1.A.res.range Enum B P 2=low; status\Measurements\RESCMMXU1\Monito
1 E X t S Amplitude 1
3=high-high; red data
range
4=low-low
Demand value Monitoring\I/O
RESCMMXU WY M 0.00...40.00 RESTCTR
Io(1) In(1) MON LD0.RCAVMMXU1.A.res.cVal.mag.f FLOAT32 B I1 I_DMD_RES of residual status\Measurements\RESCMMXU1\Monito
1 E X xIn 1
current red data
Maximum
RESCMMXU WY M Max demand demand for 0.00...40.00 Monitoring\Recorded RESTCTR
Io(1) In(1) MON LD0.RCMAMMXU1.A.res.cVal.mag.f FLOAT32 B I1
1 E X Io residual xIn data\Measurements\RESCMMXU1 1
current
Time of
maximum
RESCMMXU WY M Time max Monitoring\Recorded RESTCTR
Io(1) In(1) MON LD0.RCMAMMXU1.A.res.t Timestamp B demand
1 E X demand Io data\Measurements\RESCMMXU1 1
residual
current
Minimum
RESCMMXU WY M demand for 0.00...40.00 Monitoring\Recorded RESTCTR
Io(1) In(1) MON LD0.RCMIMMXU1.A.res.cVal.mag.f FLOAT32 B I1 Min demand Io
1 E X residual xIn data\Measurements\RESCMMXU1 1
current
Time of
minimum
RESCMMXU WY M Time min Monitoring\Recorded RESTCTR
Io(1) In(1) MON LD0.RCMIMMXU1.A.res.t Timestamp B demand
1 E X demand Io data\Measurements\RESCMMXU1 1
residual
current
RESCMMXU Operation Off /
Io(1) In(1) CFG LD0.RESCMMXU1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off Configuration\Measurements\RESCMMXU1
1 On

163
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Deadband
configuration
value for
integral
RESCMMXU WY calculation. RESTCTR
Io(1) In(1) CFG LD0.RESCMMXU1.A.res.db INT32U CF B,I 2500 A deadband res 100...100000 Configuration\Measurements\RESCMMXU1
1 E (percentage of 1
difference
between min
and max as
0,001 % s)
RESCMMXU LD0.RESCMMXU1.A.res.rangeC.hhLi WY A Hi high limit High alarm 0.00...40.00 RESTCTR
Io(1) In(1) CFG FLOAT32 CF B,I 0.20 Configuration\Measurements\RESCMMXU1
1 m.f E res current limit xIn 1
RESCMMXU LD0.RESCMMXU1.A.res.rangeC.hLim WY A high limit High warning 0.00...40.00 RESTCTR
Io(1) In(1) CFG FLOAT32 CF B,I 0.05 Configuration\Measurements\RESCMMXU1
1 .f E res current limit xIn 1
Selects used
RESCMMXU Measurement 1=RMS;
Io(1) In(1) CFG LD0.RESCMMXU1.AMeasMod.setVal ENG Enum SP A 2 measurement Configuration\Measurements\RESCMMXU1
1 mode 2=DFT
mode
RESCMMXU VisString25
Io(1) In(1) VER LD0.RESCMMXU1.NamPlt.swRev LPL DC ED1 E1 (Name plate)
1 5 (20)

PEMMXU1: Three-phase power and energy measurement: D1


Channe
IEC Categor CD Acces Defaul Even CM Parameter
IEC 61850 ANSI IECName Type FC Dataset Parameter name Parameter range Menu path l
60617 y C s t t T desc
relation
PEMMXU P,E(1 P,E(1 (ACT input
INP Channel U3P
1 ) ) channel)
PEMMXU P,E(1 P,E(1 (ACT input
INP Channel I3P
1 ) ) channel)
Reset of
PEMMXU P,E(1 P,E(1 accumulated Monitoring\I/O
INP LD0.PEMMTR1.SupDmdRs.stVal SPC BOOLEAN ST B 0 I1 RSTACM
1 ) ) energy status\Measurements\PEMMXU1\Inputs
reading
PEMMXU P,E(1 P,E(1 (PEMMXU1
CTR LD0.PEMMXU1.RcdRs.Oper.ctlVal SPC BOOLEAN CO I1
1 ) ) demands)
Reset of
PEMMXU P,E(1 P,E(1 LD0.PEMMTR1.SupDmdRs.Oper.ctlVa PEMMXU1 accumulated
CTR SPC BOOLEAN CO B 0 I1 0=Cancel; 1=Clear Clear\Clear
1 ) ) l acc.energy energy
reading
-
PEMMXU P,E(1 P,E(1 M MeasFl Total Active
MON LD0.PEMMXU1.TotW.instMag.f MV FLOAT32 B P I1 P-kW 999999.9...999999. Measurements\PEMMXU1
1 ) ) X t Power
9 kW
Active
power, - Monitoring\I/O
PEMMXU P,E(1 P,E(1 M MeasFl
MON LD0.PEMMXU1.TotW.mag.f MV FLOAT32 B P P_DB magnitude 999999.9...999999. status\Measurements\PEMMXU1\Monitore
1 ) ) X t
of reported 9 kW d data
value

164
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Total -
PEMMXU P,E(1 P,E(1 M MeasFl
MON LD0.PEMMXU1.TotVAr.instMag.f MV FLOAT32 B P I1 Q-kVAr Reactive 999999.9...999999. Measurements\PEMMXU1
1 ) ) X t
Power 9 kVAr
Reactive
power, - Monitoring\I/O
PEMMXU P,E(1 P,E(1 M MeasFl
MON LD0.PEMMXU1.TotVAr.mag.f MV FLOAT32 B P Q_DB magnitude 999999.9...999999. status\Measurements\PEMMXU1\Monitore
1 ) ) X t
of reported 9 kVAr d data
value
Total -
PEMMXU P,E(1 P,E(1 M MeasFl
MON LD0.PEMMXU1.TotVA.instMag.f MV FLOAT32 B P I1 S-kVA Apparent 999999.9...999999. Measurements\PEMMXU1
1 ) ) X t
Power 9 kVA
Apparent
power, - Monitoring\I/O
PEMMXU P,E(1 P,E(1 M MeasFl
MON LD0.PEMMXU1.TotVA.mag.f MV FLOAT32 B P S_DB magnitude 999999.9...999999. status\Measurements\PEMMXU1\Monitore
1 ) ) X t
of reported 9 kVA d data
value
PEMMXU P,E(1 P,E(1 M MeasFl Average
MON LD0.PEMMXU1.TotPF.instMag.f MV FLOAT32 B P I1 PF -1.00...1.00 Measurements\PEMMXU1
1 ) ) X t Power factor
Power
factor, Monitoring\I/O
PEMMXU P,E(1 P,E(1 M MeasFl
MON LD0.PEMMXU1.TotPF.mag.f MV FLOAT32 B P PF_DB magnitude -1.00...1.00 status\Measurements\PEMMXU1\Monitore
1 ) ) X t
of reported d data
value
Accumulate
Monitoring\I/O
PEMMXU P,E(1 P,E(1 d reverse
MON LD0.PEMMTR1.SupWh.actVal BCR INT64 ST B I1 EA_RV_ACM 0...999999999 kWh status\Measurements\PEMMXU1\Monitore
1 ) ) active
d data
energy value
Accumulate
Monitoring\I/O
PEMMXU P,E(1 P,E(1 d reverse 0...999999999
MON LD0.PEMMTR1.SupVArh.actVal BCR INT64 ST B I1 ER_RV_ACM status\Measurements\PEMMXU1\Monitore
1 ) ) reactive kVArh
d data
energy value
Accumulate
Monitoring\I/O
PEMMXU P,E(1 P,E(1 EA_FWD_AC d forward
MON LD0.PEMMTR1.DmdWh.actVal BCR INT64 ST B I1 0...999999999 kWh status\Measurements\PEMMXU1\Monitore
1 ) ) M active
d data
energy value
Accumulate
Monitoring\I/O
PEMMXU P,E(1 P,E(1 ER_FWD_AC d forward 0...999999999
MON LD0.PEMMTR1.DmdVArh.actVal BCR INT64 ST B I1 status\Measurements\PEMMXU1\Monitore
1 ) ) M reactive kVArh
d data
energy value
Demand - Monitoring\I/O
PEMMXU P,E(1 P,E(1 M
MON LD0.PEAVMMXU1.TotW.mag.f MV FLOAT32 B I1 P_DMD value of 999999.9...999999. status\Measurements\PEMMXU1\Monitore
1 ) ) X
active power 9 kW d data
Demand
- Monitoring\I/O
PEMMXU P,E(1 P,E(1 M value of
MON LD0.PEAVMMXU1.TotVAr.mag.f MV FLOAT32 B I1 Q_DMD 999999.9...999999. status\Measurements\PEMMXU1\Monitore
1 ) ) X reactive
9 kVAr d data
power
Demand
- Monitoring\I/O
PEMMXU P,E(1 P,E(1 M value of
MON LD0.PEAVMMXU1.TotVA.mag.f MV FLOAT32 B I1 S_DMD 999999.9...999999. status\Measurements\PEMMXU1\Monitore
1 ) ) X apparent
9 kVA d data
power
165
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Demand Monitoring\I/O
PEMMXU P,E(1 P,E(1 M
MON LD0.PEAVMMXU1.TotPF.mag.f MV FLOAT32 B I1 PF_DMD value of -1.00...1.00 status\Measurements\PEMMXU1\Monitore
1 ) ) X
power factor d data
Maximum
-
PEMMXU P,E(1 P,E(1 M demand Monitoring\Recorded
MON LD0.PEMAMMXU1.TotW.mag.f MV FLOAT32 B I1 Max demand P 999999.9...999999.
1 ) ) X value of data\Measurements\PEMMXU1
9 kW
active power
Time of
PEMMXU P,E(1 P,E(1 M Time max dmd Monitoring\Recorded
MON LD0.PEMAMMXU1.TotW.t MV Timestamp B maximum
1 ) ) X P data\Measurements\PEMMXU1
demand
Maximum
demand -
PEMMXU P,E(1 P,E(1 M Monitoring\Recorded
MON LD0.PEMAMMXU1.TotVAr.mag.f MV FLOAT32 B I1 Max demand Q value of 999999.9...999999.
1 ) ) X data\Measurements\PEMMXU1
reactive 9 kVAr
power
Time of
PEMMXU P,E(1 P,E(1 M Time max dmd Monitoring\Recorded
MON LD0.PEMAMMXU1.TotVAr.t MV Timestamp B maximum
1 ) ) X Q data\Measurements\PEMMXU1
demand
Maximum
demand -
PEMMXU P,E(1 P,E(1 M Monitoring\Recorded
MON LD0.PEMAMMXU1.TotVA.mag.f MV FLOAT32 B I1 Max demand S value of 999999.9...999999.
1 ) ) X data\Measurements\PEMMXU1
apparent 9 kVA
power
Time of
PEMMXU P,E(1 P,E(1 M Time max dmd Monitoring\Recorded
MON LD0.PEMAMMXU1.TotVA.t MV Timestamp B maximum
1 ) ) X S data\Measurements\PEMMXU1
demand
Minimum
-
PEMMXU P,E(1 P,E(1 M demand Monitoring\Recorded
MON LD0.PEMIMMXU1.TotW.mag.f MV FLOAT32 B I1 Min demand P 999999.9...999999.
1 ) ) X value of data\Measurements\PEMMXU1
9 kW
active power
Time of
PEMMXU P,E(1 P,E(1 M Time min dmd Monitoring\Recorded
MON LD0.PEMIMMXU1.TotW.t MV Timestamp B minimum
1 ) ) X P data\Measurements\PEMMXU1
demand
Minimum
demand -
PEMMXU P,E(1 P,E(1 M Monitoring\Recorded
MON LD0.PEMIMMXU1.TotVAr.mag.f MV FLOAT32 B I1 Min demand Q value of 999999.9...999999.
1 ) ) X data\Measurements\PEMMXU1
reactive 9 kVAr
power
Time of
PEMMXU P,E(1 P,E(1 M Time min dmd Monitoring\Recorded
MON LD0.PEMIMMXU1.TotVAr.t MV Timestamp B minimum
1 ) ) X Q data\Measurements\PEMMXU1
demand
Minimum
demand -
PEMMXU P,E(1 P,E(1 M Monitoring\Recorded
MON LD0.PEMIMMXU1.TotVA.mag.f MV FLOAT32 B I1 Min demand S value of 999999.9...999999.
1 ) ) X data\Measurements\PEMMXU1
apparent 9 kVA
power
Time of
PEMMXU P,E(1 P,E(1 M Time min dmd Monitoring\Recorded
MON LD0.PEMIMMXU1.TotVA.t MV Timestamp B minimum
1 ) ) X S data\Measurements\PEMMXU1
demand

166
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

PEMMXU P,E(1 P,E(1 Operation


CFG LD0.PEMMXU1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off Configuration\Measurements\PEMMXU1
1 ) ) Off / On
Unit
multiplier
for
PEMMXU P,E(1 P,E(1
CFG LD0.PEMMXU1.TotW.units.multiplier MV Enum CF B,I 3 Power unit Mult presentation 3=Kilo; 6=Mega Configuration\Measurements\PEMMXU1
1 ) )
of the power
related
values
Direction of
active power
PEMMXU P,E(1 P,E(1 EN Active power 1=Forward;
CFG LD0.PEMMXU1.WhDir.setVal Enum SP B 1 flow: Configuration\Measurements\PEMMXU1
1 ) ) G Dir 2=Reverse
Forward,
Reverse
Direction of
reactive
PEMMXU P,E(1 P,E(1 EN Reactive power 1=Forward;
CFG LD0.PEMMXU1.VArhDir.setVal Enum SP B 1 power flow: Configuration\Measurements\PEMMXU1
1 ) ) G Dir 2=Reverse
Forward,
Reverse
Unit
multiplier
for
PEMMXU P,E(1 P,E(1 LD0.PEMMTR1.SupWh.units.multiplie Energy unit presentation
CFG BCR Enum CF B,I 3 3=Kilo; 6=Mega Configuration\Measurements\PEMMXU1
1 ) ) r Mult of the
energy
related
values
Preset Initial
value for
PEMMXU P,E(1 P,E(1 Forward Wh
CFG LD0.PEMMTR1.IniDmdWh.setVal ING INT32 SP A 0 forward 0...999999999 Configuration\Measurements\PEMMXU1
1 ) ) Initial
active
energy
Preset Initial
value for
PEMMXU P,E(1 P,E(1 Reverse Wh
CFG LD0.PEMMTR1.IniSupWh.setVal ING INT32 SP A 0 reverse 0...999999999 Configuration\Measurements\PEMMXU1
1 ) ) Initial
active
energy
Preset Initial
value for
PEMMXU P,E(1 P,E(1 Forward VArh
CFG LD0.PEMMTR1.IniDmdVArh.setVal ING INT32 SP A 0 forward 0...999999999 Configuration\Measurements\PEMMXU1
1 ) ) Initial
reactive
energy
Preset Initial
value for
PEMMXU P,E(1 P,E(1 Reverse VArh
CFG LD0.PEMMTR1.IniSupVArh.setVal ING INT32 SP A 0 reverse 0...999999999 Configuration\Measurements\PEMMXU1
1 ) ) Initial
reactive
energy
PEMMXU P,E(1 P,E(1 VisString25
VER LD0.PEMMXU1.NamPlt.swRev LPL DC ED1 D1 (Name plate)
1 ) ) 5 (20)

167
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

FMMXU1: Frequency measurement: B1


IEC IEC Parameter Channel
ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Parameter range Menu path
61850 60617 name relation
FMMXU1 f(1) f(1) INP Channel U3P (ACT input channel)
FMMXU1 f(1) f(1) MON LD0.FMMXU1.Hz.instMag.f MV FLOAT32 MX B MeasFlt P f-Hz Measured frequency 35.00...75.00 Hz Measurements\FMMXU1
Monitoring\I/O
Frequency, reported
FMMXU1 f(1) f(1) MON LD0.FMMXU1.Hz.mag.f MV FLOAT32 MX B MeasFlt P I1 F_DB 35.00...75.00 Hz status\Measurements\FMMXU1\Monitored
value
data
0=normal;
Monitoring\I/O
Measured frequency 1=high; 2=low;
FMMXU1 f(1) f(1) MON LD0.FMMXU1.Hz.range MV Enum MX B MeasFlt P F_RANGE status\Measurements\FMMXU1\Monitored
range 3=high-high;
data
4=low-low
FMMXU1 f(1) f(1) CFG LD0.FMMXU1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation Operation Off / On 1=on; 5=off Configuration\Measurements\FMMXU1
Deadband
configuration value for
integral calculation
FMMXU1 f(1) f(1) CFG LD0.FMMXU1.Hz.db MV INT32U CF B,I 1000 F deadband 100...100000 Configuration\Measurements\FMMXU1
(percentage of
difference between min
and max as 0,001 % s)
F high high High alarm frequency
FMMXU1 f(1) f(1) CFG LD0.FMMXU1.Hz.rangeC.hhLim.f MV FLOAT32 CF B,I 60.00 35.00...75.00 Hz Configuration\Measurements\FMMXU1
limit limit
High warning
FMMXU1 f(1) f(1) CFG LD0.FMMXU1.Hz.rangeC.hLim.f MV FLOAT32 CF B,I 55.00 F high limit 35.00...75.00 Hz Configuration\Measurements\FMMXU1
frequency limit
Low warning
FMMXU1 f(1) f(1) CFG LD0.FMMXU1.Hz.rangeC.lLim.f MV FLOAT32 CF B,I 45.00 F low limit 35.00...75.00 Hz Configuration\Measurements\FMMXU1
frequency limit
F low low Low alarm frequency
FMMXU1 f(1) f(1) CFG LD0.FMMXU1.Hz.rangeC.llLim.f MV FLOAT32 CF B,I 40.00 35.00...75.00 Hz Configuration\Measurements\FMMXU1
limit limit
Def
Default frequency 1=Nominal;
FMMXU1 f(1) f(1) CFG LD0.FMMXU1.DefHzSel.setVal ENG Enum SP A,I 1 frequency Configuration\Measurements\FMMXU1
selection 2=Zero
Sel
VisString255
FMMXU1 f(1) f(1) VER LD0.FMMXU1.NamPlt.swRev LPL DC ED1 B1 (Name plate)
(20)

SEQSPVC1: Fuse failure supervision: F


IEC Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter name Parameter range Menu path
60617 desc relation
(ACT input
SEQSPVC1 FUSEF(1) 60(1) INP Channel U3P
channel)
(ACT input
SEQSPVC1 FUSEF(1) 60(1) INP Channel I3P
channel)
Block of Monitoring\I/O
SEQSPVC1 FUSEF(1) 60(1) INP LD0.SEQSPVC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
function status\Supervision\SEQSPVC1\Inputs
Active when Monitoring\I/O
SEQSPVC1 FUSEF(1) 60(1) INP LD0.SEQSPVC1.InPosCls.stVal SPS BOOLEAN ST B 0 I1 CB_CLOSED
circuit status\Supervision\SEQSPVC1\Inputs
168
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

breaker is
closed
Active when
line Monitoring\I/O
SEQSPVC1 FUSEF(1) 60(1) INP LD0.SEQSPVC1.InDsconOpn.stVal SPS BOOLEAN ST B 0 I1 DISCON_OPEN
disconnector status\Supervision\SEQSPVC1\Inputs
is open
Active when
external
MCB opens Monitoring\I/O
SEQSPVC1 FUSEF(1) 60(1) INP LD0.SEQSPVC1.InMCBOpn.stVal SPS BOOLEAN ST B 0 I1 MINCB_OPEN
protected status\Supervision\SEQSPVC1\Inputs
voltage
circuit
General start Monitoring\I/O
SEQSPVC1 FUSEF(1) 60(1) OUT LD0.SEQSPVC1.Str.general ACD BOOLEAN ST B StatIed P,H I1 FUSEF_U
of function status\Supervision\SEQSPVC1\Outputs
Three-phase
Monitoring\I/O
SEQSPVC1 FUSEF(1) 60(1) OUT LD0.SEQSPVC1.Str3Ph.general ACD BOOLEAN ST B StatIed P,H FUSEF_3PH start of
status\Supervision\SEQSPVC1\Outputs
function
1=on;
2=blocked;
SEQSPVC1 FUSEF(1) 60(1) MON LD0.SEQSPVC1.Beh.stVal ENS Enum ST B SEQSPVC1 Status 3=test; Monitoring\FB status\Supervision
4=test/blocked;
5=off
Operation
SEQSPVC1 FUSEF(1) 60(1) CFG LD0.SEQSPVC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off Configuration\Supervision\SEQSPVC1
Off / On
Minimum
operate level
Min Op current of phase
SEQSPVC1 FUSEF(1) 60(1) CFG LD0.SEQSPVC1.BlkValA.setMag.f ASG FLOAT32 SP A 0.10 0.01...1.00 xIn Configuration\Supervision\SEQSPVC1 IL1TCTR1
delta current for
delta
calculation
Operate level
Neg Seq current of neg seq
SEQSPVC1 FUSEF(1) 60(1) CFG LD0.SEQSPVC1.NgSeqLevA.setMag.f ASG FLOAT32 SP A 0.03 0.03...0.20 xIn Configuration\Supervision\SEQSPVC1 IL1TCTR1
Lev undercurrent
element
Operate level
Current change
SEQSPVC1 FUSEF(1) 60(1) CFG LD0.SEQSPVC1.ChgRteA.setMag.f ASG FLOAT32 SP A 0.15 of change in 0.01...0.50 xIn Configuration\Supervision\SEQSPVC1 IL1TCTR1
rate
phase current
Enabling
Change rate operation of
SEQSPVC1 FUSEF(1) 60(1) CFG LD0.SEQSPVC1.ChgRteEna.setVal SPG BOOLEAN SP A 0 Configuration\Supervision\SEQSPVC1
enable change based
function
Operate level
Voltage change of change in
SEQSPVC1 FUSEF(1) 60(1) CFG LD0.SEQSPVC1.ChgRteV.setMag.f ASG FLOAT32 SP A 0.40 0.25...0.90 xUn Configuration\Supervision\SEQSPVC1 UL1TVTR1
rate phase
voltage
Enabling
SEQSPVC1 FUSEF(1) 60(1) CFG LD0.SEQSPVC1.EnaSealIn.setVal SPG BOOLEAN SP A 0 Enable seal in seal in Configuration\Supervision\SEQSPVC1
functionality
Min Op voltage Minimum
SEQSPVC1 FUSEF(1) 60(1) CFG LD0.SEQSPVC1.BlkValV.setMag.f ASG FLOAT32 SP A 0.50 0.01...1.00 xUn Configuration\Supervision\SEQSPVC1 UL1TVTR1
delta operate level
169
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

of phase
voltage for
delta
calculation
Operate level
of seal-in
SEQSPVC1 FUSEF(1) 60(1) CFG LD0.SEQSPVC1.SealInV.setMag.f ASG FLOAT32 SP A 0.50 Seal in voltage 0.01...1.00 xUn Configuration\Supervision\SEQSPVC1 UL1TVTR1
phase
voltage
Operate level
Neg Seq voltage of neg seq
SEQSPVC1 FUSEF(1) 60(1) CFG LD0.SEQSPVC1.NgSeqLevV.setMag.f ASG FLOAT32 SP A 0.10 0.03...0.20 xUn Configuration\Supervision\SEQSPVC1 UL1TVTR1
Lev overvoltage
element
Operate level
Current dead Lin for open
SEQSPVC1 FUSEF(1) 60(1) CFG LD0.SEQSPVC1.DeaLinValA.setMag.f ASG FLOAT32 SP A 0.05 0.05...1.00 xIn Configuration\Supervision\SEQSPVC1 IL1TCTR1
Val phase current
detection
0=Reset;
43=Activate
FUSEF_3PH;
44=Deactive
Test control
SEQSPVC1 FUSEF(1) 60(1) TES LD0.SEQSPVC1.TestSpvn.Oper.ctlVal ENC Enum CO B 0 SEQSPVC1 FUSEF_3PH; Tests\Function tests\Supervision
for outputs
45=Activate
FUSEF_U;
46=Deactive
FUSEF_U
VisString255
SEQSPVC1 FUSEF(1) 60(1) VER LD0.SEQSPVC1.NamPlt.swRev LPL DC F (Name plate)
(20)

DPHLPDOC1: Three-phase directional overcurrent, low stage: E1


IEC
ANS Categor Acces CM Parameter Parameter Channel
IEC 61850 6061 IECName CDC Type FC Default Dataset Event Parameter range Menu path
I y s T name desc relation
7
DPHLPDOC 3I>- 67- (ACT input
INP Channel U3P
1 >(1) 1(1) channel)
DPHLPDOC 3I>- 67- (ACT input
INP Channel I3P
1 >(1) 1(1) channel)
Block signal
DPHLPDOC 3I>- 67- for activating Monitoring\I/O status\Current
INP LD0.DPHLPTOC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
1 >(1) 1(1) the blocking protection\DPHLPDOC1\Inputs
mode
Enable signal
DPHLPDOC 3I>- 67- Monitoring\I/O status\Current
INP LD0.DPHLPTOC1.InEnaMult.stVal SPS BOOLEAN ST B 0 I1 ENA_MULT for current
1 >(1) 1(1) protection\DPHLPDOC1\Inputs
multiplier
Forces
DPHLPDOC 3I>- 67- protection to Monitoring\I/O status\Current
INP LD0.DPHLPTOC1.NonDir.stVal SPS BOOLEAN ST B 0 I1 NON_DIR
1 >(1) 1(1) non- protection\DPHLPDOC1\Inputs
directional

170
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

DPHLPDOC 3I>- 67- StatNrm Monitoring\I/O status\Current


OUT LD0.DPHLPTOC1.Str.general ACD BOOLEAN ST B P,H I1 START Start (A,B,C)
1 >(1) 1(1) l protection\DPHLPDOC1\Outputs
DPHLPDOC 3I>- 67- StatNrm P,H, Monitoring\I/O status\Current
OUT LD0.DPHLPTOC1.Op.general ACT BOOLEAN ST B I1 OPERATE Operate (A,B,C)
1 >(1) 1(1) l T protection\DPHLPDOC1\Outputs
1=on; 2=blocked;
DPHLPDOC 3I>- 67- 3=test;
MON LD0.DPHLPTOC1.Beh.stVal ENS Enum ST B DPHLPDOC1 Status Monitoring\FB status
1 >(1) 1(1) 4=test/blocked;
5=off
0=unknown;
Monitoring\I/O status\Current
DPHLPDOC 3I>- 67- StatNrm Detected fault 1=forward;
MON LD0.DPHLPTOC1.Str.dirGeneral ACD Enum ST B P,H FAULT_DIR protection\DPHLPDOC1\Monitore
1 >(1) 1(1) l direction 2=backward;
d data
3=both
Ratio of start Monitoring\I/O status\Current
DPHLPDOC 3I>- 67- M
MON LD0.DPHLPTOC1.StrDur.mag.f MV FLOAT32 B START_DUR time / operate 0.00...100.00 % protection\DPHLPDOC1\Monitore
1 >(1) 1(1) X
time d data
0=unknown;
Monitoring\I/O status\Current
DPHLPDOC 3I>- 67- Direction 1=forward;
MON LD0.DPHLRDIR1.Dir.dirGeneral ACD Enum ST B DIRECTION protection\DPHLPDOC1\Monitore
1 >(1) 1(1) information 2=backward;
d data
3=both
0=unknown;
Monitoring\I/O status\Current
DPHLPDOC 3I>- 67- Direction 1=forward;
MON LD0.DPHLRDIR1.Dir.dirPhsA ACD Enum ST B I1 DIR_A protection\DPHLPDOC1\Monitore
1 >(1) 1(1) phase A 2=backward; -
d data
1=both
0=unknown;
Monitoring\I/O status\Current
DPHLPDOC 3I>- 67- Direction 1=forward;
MON LD0.DPHLRDIR1.Dir.dirPhsB ACD Enum ST B I1 DIR_B protection\DPHLPDOC1\Monitore
1 >(1) 1(1) phase B 2=backward; -
d data
1=both
0=unknown;
Monitoring\I/O status\Current
DPHLPDOC 3I>- 67- Direction 1=forward;
MON LD0.DPHLRDIR1.Dir.dirPhsC ACD Enum ST B I1 DIR_C protection\DPHLPDOC1\Monitore
1 >(1) 1(1) phase C 2=backward; -
d data
1=both
Calculated
Monitoring\I/O status\Current
DPHLPDOC 3I>- 67- LD0.DPHLRDIR1.OpChrAngPhsA.mag M angle -180.00...180.00
MON MV FLOAT32 ED2,B I1 ANGLE_A protection\DPHLPDOC1\Monitore
1 >(1) 1(1) .f X difference, deg
d data
Phase A
Calculated
Monitoring\I/O status\Current
DPHLPDOC 3I>- 67- M angle -180.00...180.00
MON LD0.DPHLRDIR1.OpChrAngA.mag.f MV FLOAT32 ED1 I1 ANGLE_A protection\DPHLPDOC1\Monitore
1 >(1) 1(1) X difference, deg
d data
Phase A
Calculated
Monitoring\I/O status\Current
DPHLPDOC 3I>- 67- LD0.DPHLRDIR1.OpChrAngPhsB.mag. M angle -180.00...180.00
MON MV FLOAT32 ED2,B I1 ANGLE_B protection\DPHLPDOC1\Monitore
1 >(1) 1(1) f X difference, deg
d data
Phase B
Calculated
Monitoring\I/O status\Current
DPHLPDOC 3I>- 67- M angle -180.00...180.00
MON LD0.DPHLRDIR1.OpChrAngB.mag.f MV FLOAT32 ED1 I1 ANGLE_B protection\DPHLPDOC1\Monitore
1 >(1) 1(1) X difference, deg
d data
Phase B
Monitoring\I/O status\Current
DPHLPDOC 3I>- 67- LD0.DPHLRDIR1.OpChrAngPhsC.mag. M Calculated -180.00...180.00
MON MV FLOAT32 ED2,B I1 ANGLE_C protection\DPHLPDOC1\Monitore
1 >(1) 1(1) f X angle deg
d data
171
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

difference,
Phase C
Calculated
Monitoring\I/O status\Current
DPHLPDOC 3I>- 67- M angle -180.00...180.00
MON LD0.DPHLRDIR1.OpChrAngC.mag.f MV FLOAT32 ED1 I1 ANGLE_C protection\DPHLPDOC1\Monitore
1 >(1) 1(1) X difference, deg
d data
Phase C
Voltage Monitoring\I/O status\Current
DPHLPDOC 3I>- 67- VMEM_USE
MON LD0.DPHLRDIR1.VMemUsedSt.stVal SPS BOOLEAN ST B I1 memory in protection\DPHLPDOC1\Monitore
1 >(1) 1(1) D
use status d data
DPHLPDOC 3I>- 67- Operation Off Settings\Settings\Current
SET LD0.DPHLPTOC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off IL1TCTR1
1 >(1) 1(1) / On protection\DPHLPDOC1
1=ANSI Ext. inv.;
2=ANSI Very
inv.; 3=ANSI
Norm. inv.;
4=ANSI Mod.
inv.; 5=ANSI Def.
Time; 6=L.T.E.
inv.; 7=L.T.V.
inv.; 8=L.T. inv.;
Selection of
DPHLPDOC 3I>- 67- CURV Operating 9=IEC Norm. inv.; Settings\Settings\Current
SET LD0.DPHLPTOC1.TmACrv.setCharact Enum SG B,I 15 time delay
1 >(1) 1(1) E curve type 10=IEC Very inv.; protection\DPHLPDOC1
curve type
11=IEC inv.;
12=IEC Ext. inv.;
13=IEC S.T. inv.;
14=IEC L.T. inv.;
15=IEC Def.
Time;
17=Programmable
; 18=RI type;
19=RD type
Parameter A
DPHLPDOC 3I>- 67- CURV 28.200 Curve for customer Settings\Settings\Current
SET LD0.DPHLPTOC1.TmACrv.setParA FLOAT32 SP B,I 0.0086...120.0000
1 >(1) 1(1) E 0 parameter A programmabl protection\DPHLPDOC1
e curve
Parameter B
DPHLPDOC 3I>- 67- CURV Curve for customer Settings\Settings\Current
SET LD0.DPHLPTOC1.TmACrv.setParB FLOAT32 SP B,I 0.1217 0.0000...0.7120
1 >(1) 1(1) E parameter B programmabl protection\DPHLPDOC1
e curve
Parameter C
DPHLPDOC 3I>- 67- CURV Curve for customer Settings\Settings\Current
SET LD0.DPHLPTOC1.TmACrv.setParC FLOAT32 SP B,I 2.00 0.02...2.00
1 >(1) 1(1) E parameter C programmabl protection\DPHLPDOC1
e curve
Parameter D
DPHLPDOC 3I>- 67- CURV Curve for customer Settings\Settings\Current
SET LD0.DPHLPTOC1.TmACrv.setParD FLOAT32 SP B,I 29.10 0.46...30.00
1 >(1) 1(1) E parameter D programmabl protection\DPHLPDOC1
e curve
Parameter E
DPHLPDOC 3I>- 67- CURV Curve for customer Settings\Settings\Current
SET LD0.DPHLPTOC1.TmACrv.setParE FLOAT32 SP B,I 1.0 0.0...1.0
1 >(1) 1(1) E parameter E programmabl protection\DPHLPDOC1
e curve
172
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

DPHLPDOC 3I>- 67- Settings\Settings\Current


SET LD0.DPHLPTOC1.StrVal.setMag.f ASG FLOAT32 SG B 0.05 Start value Start value 0.05...5.00 xIn IL1TCTR1
1 >(1) 1(1) protection\DPHLPDOC1
Time
DPHLPDOC 3I>- 67- Time multiplier in Settings\Settings\Current
SET LD0.DPHLPTOC1.TmMult.setMag.f ASG FLOAT32 SG B 1.000 0.025...15.0
1 >(1) 1(1) multiplier IEC/ANSI protection\DPHLPDOC1
IDMT curves
Minimum
DPHLPDOC 3I>- 67- Minimum operate time Settings\Settings\Current
SET LD0.DPHLPTOC1.MinOpTmms.setVal ING INT32 SP A 20 20...60000 ms
1 >(1) 1(1) operate time for IDMT protection\DPHLPDOC1
curves
DPHLPDOC 3I>- 67- Operate delay Operate delay Settings\Settings\Current
SET LD0.DPHLPTOC1.OpDlTmms.setVal ING INT32 SG B 40 40...200000 ms
1 >(1) 1(1) time time protection\DPHLPDOC1
Selection of 1=Immediate;
DPHLPDOC 3I>- 67- Type of reset Settings\Settings\Current
SET LD0.DPHLPTOC1.TypRsCrv.setVal ENG Enum SG A 1 reset curve 2=Def time reset;
1 >(1) 1(1) curve protection\DPHLPDOC1
type 3=Inverse reset
DPHLPDOC 3I>- 67- Reset delay Reset delay Settings\Settings\Current
SET LD0.DPHLPTOC1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
1 >(1) 1(1) time time protection\DPHLPDOC1
1=Non-
DPHLPDOC 3I>- 67- Directional Directional directional; Settings\Settings\Current
SET LD0.DPHLPTOC1.DirMod.setVal ENG Enum SG B 2
1 >(1) 1(1) mode mode 2=Forward; protection\DPHLPDOC1
3=Reverse
Number of
phases 1=1 out of 3; 2=2
DPHLPDOC 3I>- 67- Num of start Settings\Settings\Current
SET LD0.DPHLPTOC1.NumPh.setVal ENG Enum SP B 1 required for out of 3; 3=3 out
1 >(1) 1(1) phases protection\DPHLPDOC1
operate of 3
activation
Multiplier for
DPHLPDOC 3I>- 67- Start value Settings\Settings\Current
SET LD0.DPHLPTOC1.StrValMult.setMag.f ASG FLOAT32 SG B 1.0 scaling the 0.8...10.0
1 >(1) 1(1) Mult protection\DPHLPDOC1
start value
Selects used
DPHLPDOC 3I>- 67- Measurement 1=RMS; 2=DFT; Settings\Settings\Current
SET LD0.DPHLPTOC1.AMeasMod.setVal ENG Enum SP A 2 measurement
1 >(1) 1(1) mode 3=Peak-to-Peak protection\DPHLPDOC1
mode
Allows prot
activation as
DPHLPDOC 3I>- 67- Settings\Settings\Current
SET LD0.DPHLPTOC1.AllwNonDir.setVal SPG BOOLEAN SP A 0 Allow Non Dir non-dir when
1 >(1) 1(1) protection\DPHLPDOC1
dir info is
invalid
DPHLPDOC 3I>- 67- Characteristic Characteristic Settings\Settings\Current
SET LD0.DPHLRDIR1.ChrAng.setMag.f ASG FLOAT32 SG B +60 -179...180 deg
1 >(1) 1(1) angle angle protection\DPHLPDOC1
Minimum
DPHLPDOC 3I>- 67- LD0.DPHLRDIR1.MinFwdAng.setMag. Min forward phase angle Settings\Settings\Current
SET ASG FLOAT32 SG B 80 0...90 deg
1 >(1) 1(1) f angle in forward protection\DPHLPDOC1
direction
Minimum
DPHLPDOC 3I>- 67- Min reverse phase angle Settings\Settings\Current
SET LD0.DPHLRDIR1.MinRvAng.setMag.f ASG FLOAT32 SG B 80 0...90 deg
1 >(1) 1(1) angle in reverse protection\DPHLPDOC1
direction
DPHLPDOC 3I>- 67- LD0.DPHLRDIR1.MaxFwdAng.setMag. Max forward Maximum Settings\Settings\Current
SET ASG FLOAT32 SG B 80 0...90 deg
1 >(1) 1(1) f angle phase angle protection\DPHLPDOC1
173
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

in forward
direction
Maximum
DPHLPDOC 3I>- 67- Max reverse phase angle Settings\Settings\Current
SET LD0.DPHLRDIR1.MaxRvAng.setMag.f ASG FLOAT32 SG B 80 0...90 deg
1 >(1) 1(1) angle in reverse protection\DPHLPDOC1
direction
Minimum
DPHLPDOC 3I>- 67- Min operate Settings\Settings\Current
SET LD0.DPHLRDIR1.BlkValA.setMag.f ASG FLOAT32 SP A 0.01 operating 0.01...1.00 xIn IL1TCTR1
1 >(1) 1(1) current protection\DPHLPDOC1
current
Minimum
DPHLPDOC 3I>- 67- Min operate Settings\Settings\Current UL1TVTR
SET LD0.DPHLRDIR1.BlkValV.setMag.f ASG FLOAT32 SP A 0.01 operating 0.01...1.00 xUn
1 >(1) 1(1) voltage protection\DPHLPDOC1 1
voltage
Reference 1=Self pol;
DPHLPDOC 3I>- 67- quantity used 4=Neg. seq. volt.; Settings\Settings\Current
SET LD0.DPHLRDIR1.PolQty.setVal ENG Enum SG A 5 Pol quantity
1 >(1) 1(1) to determine 5=Cross pol; protection\DPHLPDOC1
fault direction 7=Pos. seq. volt.
DPHLPDOC 3I>- 67- Voltage Mem Voltage Settings\Settings\Current
SET LD0.DPHLRDIR1.VMemTmms.setVal ING INT32 SG A 40 0...3000 ms
1 >(1) 1(1) time memory time protection\DPHLPDOC1
0=Reset;
1=Activate
START;
2=Deactive
DPHLPDOC 3I>- 67- Test control Tests\Function tests\Current
TES LD0.DPHLPTOC1.TestPro.Oper.ctlVal ENC Enum CO B 0 DPHLPDOC1 START;
1 >(1) 1(1) for outputs protection
9=Activate
OPERATE;
10=Deactive
OPERATE
DPHLPDOC 3I>- 67- VisString25
VER LD0.DPHLPTOC1.NamPlt.swRev LPL DC ED1 E1 (Name plate)
1 >(1) 1(1) 5 (20)

DPHHPDOC1: Three-phase directional overcurrent, high stage: E1


IEC
ANS Categor Acces CM Parameter Parameter Channel
IEC 61850 6061 IECName CDC Type FC Default Dataset Event Parameter range Menu path
I y s T name desc relation
7
DPHHPDOC 3I>>- 67- (ACT input
INP Channel U3P
1 >(1) 2(1) channel)
DPHHPDOC 3I>>- 67- (ACT input
INP Channel I3P
1 >(1) 2(1) channel)
Block signal
DPHHPDOC 3I>>- 67- for activating Monitoring\I/O status\Current
INP LD0.DPHHPTOC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
1 >(1) 2(1) the blocking protection\DPHHPDOC1\Inputs
mode
Enable signal
DPHHPDOC 3I>>- 67- Monitoring\I/O status\Current
INP LD0.DPHHPTOC1.InEnaMult.stVal SPS BOOLEAN ST B 0 I1 ENA_MULT for current
1 >(1) 2(1) protection\DPHHPDOC1\Inputs
multiplier
DPHHPDOC 3I>>- 67- Forces Monitoring\I/O status\Current
INP LD0.DPHHPTOC1.NonDir.stVal SPS BOOLEAN ST B 0 I1 NON_DIR
1 >(1) 2(1) protection to protection\DPHHPDOC1\Inputs
174
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

non-
directional
DPHHPDOC 3I>>- 67- StatNrm Monitoring\I/O status\Current
OUT LD0.DPHHPTOC1.Str.general ACD BOOLEAN ST B P,H I1 START Start (A,B,C)
1 >(1) 2(1) l protection\DPHHPDOC1\Outputs
DPHHPDOC 3I>>- 67- StatNrm P,H, Monitoring\I/O status\Current
OUT LD0.DPHHPTOC1.Op.general ACT BOOLEAN ST B I1 OPERATE Operate (A,B,C)
1 >(1) 2(1) l T protection\DPHHPDOC1\Outputs
1=on; 2=blocked;
DPHHPDOC 3I>>- 67- 3=test;
MON LD0.DPHHPTOC1.Beh.stVal ENS Enum ST B DPHHPDOC1 Status Monitoring\FB status
1 >(1) 2(1) 4=test/blocked;
5=off
0=unknown;
Monitoring\I/O status\Current
DPHHPDOC 3I>>- 67- StatNrm Detected fault 1=forward;
MON LD0.DPHHPTOC1.Str.dirGeneral ACD Enum ST B P,H FAULT_DIR protection\DPHHPDOC1\Monitore
1 >(1) 2(1) l direction 2=backward;
d data
3=both
Ratio of start Monitoring\I/O status\Current
DPHHPDOC 3I>>- 67- M
MON LD0.DPHHPTOC1.StrDur.mag.f MV FLOAT32 B START_DUR time / operate 0.00...100.00 % protection\DPHHPDOC1\Monitore
1 >(1) 2(1) X
time d data
0=unknown;
Monitoring\I/O status\Current
DPHHPDOC 3I>>- 67- Direction 1=forward;
MON LD0.DPHHRDIR1.Dir.dirGeneral ACD Enum ST B DIRECTION protection\DPHHPDOC1\Monitore
1 >(1) 2(1) information 2=backward;
d data
3=both
0=unknown;
Monitoring\I/O status\Current
DPHHPDOC 3I>>- 67- Direction 1=forward;
MON LD0.DPHHRDIR1.Dir.dirPhsA ACD Enum ST B I1 DIR_A protection\DPHHPDOC1\Monitore
1 >(1) 2(1) phase A 2=backward; -
d data
1=both
0=unknown;
Monitoring\I/O status\Current
DPHHPDOC 3I>>- 67- Direction 1=forward;
MON LD0.DPHHRDIR1.Dir.dirPhsB ACD Enum ST B I1 DIR_B protection\DPHHPDOC1\Monitore
1 >(1) 2(1) phase B 2=backward; -
d data
1=both
0=unknown;
Monitoring\I/O status\Current
DPHHPDOC 3I>>- 67- Direction 1=forward;
MON LD0.DPHHRDIR1.Dir.dirPhsC ACD Enum ST B I1 DIR_C protection\DPHHPDOC1\Monitore
1 >(1) 2(1) phase C 2=backward; -
d data
1=both
Calculated
Monitoring\I/O status\Current
DPHHPDOC 3I>>- 67- LD0.DPHHRDIR1.OpChrAngPhsA.mag M angle -180.00...180.00
MON MV FLOAT32 ED2,B I1 ANGLE_A protection\DPHHPDOC1\Monitore
1 >(1) 2(1) .f X difference, deg
d data
Phase A
Calculated
Monitoring\I/O status\Current
DPHHPDOC 3I>>- 67- M angle -180.00...180.00
MON LD0.DPHHRDIR1.OpChrAngA.mag.f MV FLOAT32 ED1 I1 ANGLE_A protection\DPHHPDOC1\Monitore
1 >(1) 2(1) X difference, deg
d data
Phase A
Calculated
Monitoring\I/O status\Current
DPHHPDOC 3I>>- 67- LD0.DPHHRDIR1.OpChrAngPhsB.mag. M angle -180.00...180.00
MON MV FLOAT32 ED2,B I1 ANGLE_B protection\DPHHPDOC1\Monitore
1 >(1) 2(1) f X difference, deg
d data
Phase B
Calculated
Monitoring\I/O status\Current
DPHHPDOC 3I>>- 67- M angle -180.00...180.00
MON LD0.DPHHRDIR1.OpChrAngB.mag.f MV FLOAT32 ED1 I1 ANGLE_B protection\DPHHPDOC1\Monitore
1 >(1) 2(1) X difference, deg
d data
Phase B

175
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Calculated
Monitoring\I/O status\Current
DPHHPDOC 3I>>- 67- LD0.DPHHRDIR1.OpChrAngPhsC.mag. M angle -180.00...180.00
MON MV FLOAT32 ED2,B I1 ANGLE_C protection\DPHHPDOC1\Monitore
1 >(1) 2(1) f X difference, deg
d data
Phase C
Calculated
Monitoring\I/O status\Current
DPHHPDOC 3I>>- 67- M angle -180.00...180.00
MON LD0.DPHHRDIR1.OpChrAngC.mag.f MV FLOAT32 ED1 I1 ANGLE_C protection\DPHHPDOC1\Monitore
1 >(1) 2(1) X difference, deg
d data
Phase C
Voltage Monitoring\I/O status\Current
DPHHPDOC 3I>>- 67- VMEM_USE
MON LD0.DPHHRDIR1.VMemUsedSt.stVal SPS BOOLEAN ST B I1 memory in protection\DPHHPDOC1\Monitore
1 >(1) 2(1) D
use status d data
DPHHPDOC 3I>>- 67- Operation Off Settings\Settings\Current
SET LD0.DPHHPTOC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
1 >(1) 2(1) / On protection\DPHHPDOC1
1=ANSI Ext.
inv.; 3=ANSI
Norm. inv.;
5=ANSI Def.
Time; 9=IEC
Selection of
DPHHPDOC 3I>>- 67- CURV Operating Norm. inv.; Settings\Settings\Current
SET LD0.DPHHPTOC1.TmACrv.setCharact Enum SG B,I 15 time delay
1 >(1) 2(1) E curve type 10=IEC Very protection\DPHHPDOC1
curve type
inv.; 12=IEC Ext.
inv.; 15=IEC Def.
Time;
17=Programmabl
e
Parameter A
DPHHPDOC 3I>>- 67- CURV 28.200 Curve for customer Settings\Settings\Current
SET LD0.DPHHPTOC1.TmACrv.setParA FLOAT32 SP B,I 0.0086...120.0000
1 >(1) 2(1) E 0 parameter A programmabl protection\DPHHPDOC1
e curve
Parameter B
DPHHPDOC 3I>>- 67- CURV Curve for customer Settings\Settings\Current
SET LD0.DPHHPTOC1.TmACrv.setParB FLOAT32 SP B,I 0.1217 0.0000...0.7120
1 >(1) 2(1) E parameter B programmabl protection\DPHHPDOC1
e curve
Parameter C
DPHHPDOC 3I>>- 67- CURV Curve for customer Settings\Settings\Current
SET LD0.DPHHPTOC1.TmACrv.setParC FLOAT32 SP B,I 2.00 0.02...2.00
1 >(1) 2(1) E parameter C programmabl protection\DPHHPDOC1
e curve
Parameter D
DPHHPDOC 3I>>- 67- CURV Curve for customer Settings\Settings\Current
SET LD0.DPHHPTOC1.TmACrv.setParD FLOAT32 SP B,I 29.10 0.46...30.00
1 >(1) 2(1) E parameter D programmabl protection\DPHHPDOC1
e curve
Parameter E
DPHHPDOC 3I>>- 67- CURV Curve for customer Settings\Settings\Current
SET LD0.DPHHPTOC1.TmACrv.setParE FLOAT32 SP B,I 1.0 0.0...1.0
1 >(1) 2(1) E parameter E programmabl protection\DPHHPDOC1
e curve
DPHHPDOC 3I>>- 67- Settings\Settings\Current
SET LD0.DPHHPTOC1.StrVal.setMag.f ASG FLOAT32 SG B 0.10 Start value Start value 0.10...40.00 xIn IL1TCTR1
1 >(1) 2(1) protection\DPHHPDOC1
DPHHPDOC 3I>>- 67- Time Time Settings\Settings\Current
SET LD0.DPHHPTOC1.TmMult.setMag.f ASG FLOAT32 SG B 1.000 0.025...15.00
1 >(1) 2(1) multiplier multiplier in protection\DPHHPDOC1

176
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

IEC/ANSI
IDMT curves
Minimum
DPHHPDOC 3I>>- 67- Minimum operate time Settings\Settings\Current
SET LD0.DPHHPTOC1.MinOpTmms.setVal ING INT32 SP A 20 20...60000 ms
1 >(1) 2(1) operate time for IDMT protection\DPHHPDOC1
curves
DPHHPDOC 3I>>- 67- Operate delay Operate delay Settings\Settings\Current
SET LD0.DPHHPTOC1.OpDlTmms.setVal ING INT32 SG B 40 40...200000 ms
1 >(1) 2(1) time time protection\DPHHPDOC1
Selection of 1=Immediate;
DPHHPDOC 3I>>- 67- Type of reset Settings\Settings\Current
SET LD0.DPHHPTOC1.TypRsCrv.setVal ENG Enum SG A 1 reset curve 2=Def time reset;
1 >(1) 2(1) curve protection\DPHHPDOC1
type 3=Inverse reset
DPHHPDOC 3I>>- 67- Reset delay Reset delay Settings\Settings\Current
SET LD0.DPHHPTOC1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
1 >(1) 2(1) time time protection\DPHHPDOC1
1=Non-
DPHHPDOC 3I>>- 67- Directional Directional directional; Settings\Settings\Current
SET LD0.DPHHPTOC1.DirMod.setVal ENG Enum SG B 2
1 >(1) 2(1) mode mode 2=Forward; protection\DPHHPDOC1
3=Reverse
Number of
phases 1=1 out of 3; 2=2
DPHHPDOC 3I>>- 67- Num of start Settings\Settings\Current
SET LD0.DPHHPTOC1.NumPh.setVal ENG Enum SP B 1 required for out of 3; 3=3 out
1 >(1) 2(1) phases protection\DPHHPDOC1
operate of 3
activation
Multiplier for
DPHHPDOC 3I>>- 67- Start value Settings\Settings\Current
SET LD0.DPHHPTOC1.StrValMult.setMag.f ASG FLOAT32 SG B 1.0 scaling the 0.8...10.0
1 >(1) 2(1) Mult protection\DPHHPDOC1
start value
Selects used
DPHHPDOC 3I>>- 67- Measurement 1=RMS; 2=DFT; Settings\Settings\Current
SET LD0.DPHHPTOC1.AMeasMod.setVal ENG Enum SP A 2 measurement
1 >(1) 2(1) mode 3=Peak-to-Peak protection\DPHHPDOC1
mode
Allows prot
activation as
DPHHPDOC 3I>>- 67- Settings\Settings\Current
SET LD0.DPHHPTOC1.AllwNonDir.setVal SPG BOOLEAN SP A 0 Allow Non Dir non-dir when
1 >(1) 2(1) protection\DPHHPDOC1
dir info is
invalid
DPHHPDOC 3I>>- 67- Characteristic Characteristic Settings\Settings\Current
SET LD0.DPHHRDIR1.ChrAng.setMag.f ASG FLOAT32 SG B +60 -179...180 deg
1 >(1) 2(1) angle angle protection\DPHHPDOC1
Minimum
DPHHPDOC 3I>>- 67- LD0.DPHHRDIR1.MinFwdAng.setMag. Min forward phase angle Settings\Settings\Current
SET ASG FLOAT32 SG B 80 0...90 deg
1 >(1) 2(1) f angle in forward protection\DPHHPDOC1
direction
Minimum
DPHHPDOC 3I>>- 67- Min reverse phase angle Settings\Settings\Current
SET LD0.DPHHRDIR1.MinRvAng.setMag.f ASG FLOAT32 SG B 80 0...90 deg
1 >(1) 2(1) angle in reverse protection\DPHHPDOC1
direction
Maximum
DPHHPDOC 3I>>- 67- LD0.DPHHRDIR1.MaxFwdAng.setMag. Max forward phase angle Settings\Settings\Current
SET ASG FLOAT32 SG B 80 0...90 deg
1 >(1) 2(1) f angle in forward protection\DPHHPDOC1
direction
DPHHPDOC 3I>>- 67- Max reverse Maximum Settings\Settings\Current
SET LD0.DPHHRDIR1.MaxRvAng.setMag.f ASG FLOAT32 SG B 80 0...90 deg
1 >(1) 2(1) angle phase angle protection\DPHHPDOC1
177
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

in reverse
direction
Minimum
DPHHPDOC 3I>>- 67- Min operate Settings\Settings\Current
SET LD0.DPHHRDIR1.BlkValA.setMag.f ASG FLOAT32 SP A 0.01 operating 0.01...1.00 xIn IL1TCTR1
1 >(1) 2(1) current protection\DPHHPDOC1
current
Minimum
DPHHPDOC 3I>>- 67- Min operate Settings\Settings\Current UL1TVTR
SET LD0.DPHHRDIR1.BlkValV.setMag.f ASG FLOAT32 SP A 0.01 operating 0.01...1.00 xUn
1 >(1) 2(1) voltage protection\DPHHPDOC1 1
voltage
Reference 1=Self pol;
DPHHPDOC 3I>>- 67- quantity used 4=Neg. seq. volt.; Settings\Settings\Current
SET LD0.DPHHRDIR1.PolQty.setVal ENG Enum SG A 5 Pol quantity
1 >(1) 2(1) to determine 5=Cross pol; protection\DPHHPDOC1
fault direction 7=Pos. seq. volt.
DPHHPDOC 3I>>- 67- Voltage Mem Voltage Settings\Settings\Current
SET LD0.DPHHRDIR1.VMemTmms.setVal ING INT32 SG A 40 0...3000 ms
1 >(1) 2(1) time memory time protection\DPHHPDOC1
0=Reset;
1=Activate
START;
2=Deactive
DPHHPDOC 3I>>- 67- Test control Tests\Function tests\Current
TES LD0.DPHHPTOC1.TestPro.Oper.ctlVal ENC Enum CO B 0 DPHHPDOC1 START;
1 >(1) 2(1) for outputs protection
9=Activate
OPERATE;
10=Deactive
OPERATE
DPHHPDOC 3I>>- 67- VisString25
VER LD0.DPHHPTOC1.NamPlt.swRev LPL DC ED1 E1 (Name plate)
1 >(1) 2(1) 5 (20)

DEFLPDEF1: Directional earth-fault, low stage: F1


IEC
ANS Categor Acces CM Parameter Parameter Channel
IEC 61850 6061 IECName CDC Type FC Default Dataset Event Parameter range Menu path
I y s T name desc relation
7
DEFLPDEF Io>- 67N- (ACT input
INP Channel U3P
1 >(1) 1(1) channel)
DEFLPDEF Io>- 67N- (ACT input
INP Channel I3P
1 >(1) 1(1) channel)
DEFLPDEF Io>- 67N- (ACT input
INP Channel URES
1 >(1) 1(1) channel)
DEFLPDEF Io>- 67N- (ACT input
INP Channel IRES
1 >(1) 1(1) channel)
Block signal
DEFLPDEF Io>- 67N- for activating Monitoring\I/O status\Current
INP LD0.DEFLPTOC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
1 >(1) 1(1) the blocking protection\DEFLPDEF1\Inputs
mode
Enable signal
DEFLPDEF Io>- 67N- Monitoring\I/O status\Current
INP LD0.DEFLPTOC1.InEnaMult.stVal SPS BOOLEAN ST B 0 I1 ENA_MULT for current
1 >(1) 1(1) protection\DEFLPDEF1\Inputs
multiplier

178
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Relay
DEFLPDEF Io>- 67N- Monitoring\I/O status\Current
INP LD0.DEFLRDIR1.InRcaCtl.stVal SPS BOOLEAN ST B 0 I1 RCA_CTL characteristic
1 >(1) 1(1) protection\DEFLPDEF1\Inputs
angle control
DEFLPDEF Io>- 67N- StatNrm Monitoring\I/O status\Current
OUT LD0.DEFLPTOC1.Str.general ACD BOOLEAN ST B P,H I1 START Start
1 >(1) 1(1) l protection\DEFLPDEF1\Outputs
DEFLPDEF Io>- 67N- StatNrm P,H, Monitoring\I/O status\Current
OUT LD0.DEFLPTOC1.Op.general ACT BOOLEAN ST B I1 OPERATE Operate
1 >(1) 1(1) l T protection\DEFLPDEF1\Outputs
1=on; 2=blocked;
DEFLPDEF Io>- 67N- 3=test;
MON LD0.DEFLPTOC1.Beh.stVal ENS Enum ST B DEFLPDEF1 Status Monitoring\FB status
1 >(1) 1(1) 4=test/blocked;
5=off
0=unknown;
Monitoring\I/O status\Current
DEFLPDEF Io>- 67N- StatNrm Detected fault 1=forward;
MON LD0.DEFLPTOC1.Str.dirGeneral ACD Enum ST B P,H FAULT_DIR protection\DEFLPDEF1\Monitore
1 >(1) 1(1) l direction 2=backward;
d data
3=both
Ratio of start Monitoring\I/O status\Current
DEFLPDEF Io>- 67N- M
MON LD0.DEFLPTOC1.StrDur.mag.f MV FLOAT32 B START_DUR time / operate 0.00...100.00 % protection\DEFLPDEF1\Monitore
1 >(1) 1(1) X
time d data
0=unknown;
Monitoring\I/O status\Current
DEFLPDEF Io>- 67N- Direction 1=forward;
MON LD0.DEFLRDIR1.Dir.dirGeneral ACD Enum ST B DIRECTION protection\DEFLPDEF1\Monitore
1 >(1) 1(1) information 2=backward;
d data
3=both
Calculated Monitoring\I/O status\Current
DEFLPDEF Io>- 67N- M
MON LD0.DEFLRDIR1.OpAEF.mag.f MV FLOAT32 B I1 I_OPER operating 0.00...40.00 xIn protection\DEFLPDEF1\Monitore RESTCTR1
1 >(1) 1(1) X
current d data
Angle
between Monitoring\I/O status\Current
DEFLPDEF Io>- 67N- M -180.00...180.00
MON LD0.DEFLRDIR1.OpPolAng.mag.f MV FLOAT32 B I1 ANGLE polarizing and protection\DEFLPDEF1\Monitore
1 >(1) 1(1) X deg
operating d data
quantity
Angle
between
Monitoring\I/O status\Current
DEFLPDEF Io>- 67N- M ANGLE_RC operating -180.00...180.00
MON LD0.DEFLRDIR1.OpChrAng.mag.f MV FLOAT32 B I1 protection\DEFLPDEF1\Monitore
1 >(1) 1(1) X A angle and deg
d data
characteristic
angle
DEFLPDEF Io>- 67N- Operation Off Settings\Settings\Current
SET LD0.DEFLPTOC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
1 >(1) 1(1) / On protection\DEFLPDEF1
1=ANSI Ext. inv.;
2=ANSI Very
inv.; 3=ANSI
Norm. inv.;
4=ANSI Mod.
Selection of
DEFLPDEF Io>- 67N- CURV Operating inv.; 5=ANSI Def. Settings\Settings\Current
SET LD0.DEFLPTOC1.TmACrv.setCharact Enum SG B,I 15 time delay
1 >(1) 1(1) E curve type Time; 6=L.T.E. protection\DEFLPDEF1
curve type
inv.; 7=L.T.V.
inv.; 8=L.T. inv.;
9=IEC Norm. inv.;
10=IEC Very inv.;
11=IEC inv.;
179
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

12=IEC Ext. inv.;


13=IEC S.T. inv.;
14=IEC L.T. inv.;
15=IEC Def.
Time;
17=Programmable
; 18=RI type;
19=RD type
Parameter A
DEFLPDEF Io>- 67N- CURV 28.200 Curve for customer Settings\Settings\Current
SET LD0.DEFLPTOC1.TmACrv.setParA FLOAT32 SP B,I 0.0086...120.0000
1 >(1) 1(1) E 0 parameter A programmabl protection\DEFLPDEF1
e curve
Parameter B
DEFLPDEF Io>- 67N- CURV Curve for customer Settings\Settings\Current
SET LD0.DEFLPTOC1.TmACrv.setParB FLOAT32 SP B,I 0.1217 0.0000...0.7120
1 >(1) 1(1) E parameter B programmabl protection\DEFLPDEF1
e curve
Parameter C
DEFLPDEF Io>- 67N- CURV Curve for customer Settings\Settings\Current
SET LD0.DEFLPTOC1.TmACrv.setParC FLOAT32 SP B,I 2.00 0.02...2.00
1 >(1) 1(1) E parameter C programmabl protection\DEFLPDEF1
e curve
Parameter D
DEFLPDEF Io>- 67N- CURV Curve for customer Settings\Settings\Current
SET LD0.DEFLPTOC1.TmACrv.setParD FLOAT32 SP B,I 29.10 0.46...30.00
1 >(1) 1(1) E parameter D programmabl protection\DEFLPDEF1
e curve
Parameter E
DEFLPDEF Io>- 67N- CURV Curve for customer Settings\Settings\Current
SET LD0.DEFLPTOC1.TmACrv.setParE FLOAT32 SP B,I 1.0 0.0...1.0
1 >(1) 1(1) E parameter E programmabl protection\DEFLPDEF1
e curve
DEFLPDEF Io>- 67N- Settings\Settings\Current
SET LD0.DEFLPTOC1.StrVal.setMag.f ASG FLOAT32 SG B 0.010 Start value Start value 0.010...5.000 xIn RESTCTR1
1 >(1) 1(1) protection\DEFLPDEF1
Time
DEFLPDEF Io>- 67N- Time multiplier in Settings\Settings\Current
SET LD0.DEFLPTOC1.TmMult.setMag.f ASG FLOAT32 SG B 1.000 0.025...15.00
1 >(1) 1(1) multiplier IEC/ANSI protection\DEFLPDEF1
IDMT curves
Minimum
DEFLPDEF Io>- 67N- Minimum operate time Settings\Settings\Current
SET LD0.DEFLPTOC1.MinOpTmms.setVal ING INT32 SP A 50 50...60000 ms
1 >(1) 1(1) operate time for IDMT protection\DEFLPDEF1
curves
DEFLPDEF Io>- 67N- Operate delay Operate delay Settings\Settings\Current
SET LD0.DEFLPTOC1.OpDlTmms.setVal ING INT32 SG B 50 50...200000 ms
1 >(1) 1(1) time time protection\DEFLPDEF1
Selection of 1=Immediate;
DEFLPDEF Io>- 67N- Type of reset Settings\Settings\Current
SET LD0.DEFLPTOC1.TypRsCrv.setVal ENG Enum SG A 1 reset curve 2=Def time reset;
1 >(1) 1(1) curve protection\DEFLPDEF1
type 3=Inverse reset
DEFLPDEF Io>- 67N- Reset delay Reset delay Settings\Settings\Current
SET LD0.DEFLPTOC1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
1 >(1) 1(1) time time protection\DEFLPDEF1
1=Non-
DEFLPDEF Io>- 67N- Directional Directional directional; Settings\Settings\Current
SET LD0.DEFLPTOC1.DirMod.setVal ENG Enum SG B 2
1 >(1) 1(1) mode mode 2=Forward; protection\DEFLPDEF1
3=Reverse

180
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

DEFLPDEF Io>- 67N- Voltage start Voltage start Settings\Settings\Current RESTVTR


SET LD0.DEFLPTOC1.VStr.setMag.f ASG FLOAT32 SG B 0.010 0.010...1.000 xUn
1 >(1) 1(1) value value protection\DEFLPDEF1 1
Multiplier for
DEFLPDEF Io>- 67N- Start value Settings\Settings\Current
SET LD0.DEFLPTOC1.StrValMult.setMag.f ASG FLOAT32 SG B 1.0 scaling the 0.8...10.0
1 >(1) 1(1) Mult protection\DEFLPDEF1
start value
Allows prot
activation as
DEFLPDEF Io>- 67N- Allow Non Settings\Settings\Current
SET LD0.DEFLPTOC1.AllwNonDir.setVal SPG BOOLEAN SP A 0 non-dir when
1 >(1) 1(1) Dir protection\DEFLPDEF1
dir info is
invalid
Selects used
DEFLPDEF Io>- 67N- Measurement 1=RMS; 2=DFT; Settings\Settings\Current
SET LD0.DEFLPTOC1.AMeasMod.setVal ENG Enum SP A 2 measurement
1 >(1) 1(1) mode 3=Peak-to-Peak protection\DEFLPDEF1
mode
DEFLPDEF Io>- 67N- Enable Enable Settings\Settings\Current
SET LD0.DEFLPTOC1.EnaVLim.setVal SPG BOOLEAN SG A 1
1 >(1) 1(1) voltage limit voltage limit protection\DEFLPDEF1
DEFLPDEF Io>- 67N- Characteristic Characteristic Settings\Settings\Current
SET LD0.DEFLRDIR1.ChrAng.setMag.f ASG FLOAT32 SG B -90 -179...180 deg
1 >(1) 1(1) angle angle protection\DEFLPDEF1
Minimum
DEFLPDEF Io>- 67N- Min forward phase angle in Settings\Settings\Current
SET LD0.DEFLRDIR1.MinFwdAng.setMag.f ASG FLOAT32 SG B 80 0...180 deg
1 >(1) 1(1) angle forward protection\DEFLPDEF1
direction
Minimum
DEFLPDEF Io>- 67N- Min reverse phase angle in Settings\Settings\Current
SET LD0.DEFLRDIR1.MinRvAng.setMag.f ASG FLOAT32 SG B 80 0...180 deg
1 >(1) 1(1) angle reverse protection\DEFLPDEF1
direction
Maximum
DEFLPDEF Io>- 67N- LD0.DEFLRDIR1.MaxFwdAng.setMag. Max forward phase angle in Settings\Settings\Current
SET ASG FLOAT32 SG B 80 0...180 deg
1 >(1) 1(1) f angle forward protection\DEFLPDEF1
direction
Maximum
DEFLPDEF Io>- 67N- Max reverse phase angle in Settings\Settings\Current
SET LD0.DEFLRDIR1.MaxRvAng.setMag.f ASG FLOAT32 SG B 80 0...180 deg
1 >(1) 1(1) angle reverse protection\DEFLPDEF1
direction
Minimum
DEFLPDEF Io>- 67N- Min operate Settings\Settings\Current
SET LD0.DEFLRDIR1.BlkValA.setMag.f ASG FLOAT32 SP A 0.005 operating 0.005...1.000 xIn RESTCTR1
1 >(1) 1(1) current protection\DEFLPDEF1
current
Minimum
DEFLPDEF Io>- 67N- Min operate Settings\Settings\Current RESTVTR
SET LD0.DEFLRDIR1.BlkValV.setMag.f ASG FLOAT32 SP A 0.01 operating 0.01...1.00 xUn
1 >(1) 1(1) voltage protection\DEFLPDEF1 1
voltage
Reference
DEFLPDEF Io>- 67N- quantity used 3=Zero seq. volt.; Settings\Settings\Current
SET LD0.DEFLRDIR1.PolQty.setVal ENG Enum SP A,I 3 Pol quantity
1 >(1) 1(1) to determine 4=Neg. seq. volt. protection\DEFLPDEF1
fault direction
1=Phase angle;
DEFLPDEF Io>- 67N- Operation Operation 2=IoSin; 3=IoCos; Settings\Settings\Current
SET LD0.DEFLRDIR1.OpModEF.setVal ENG Enum SG A 1
1 >(1) 1(1) mode criteria 4=Phase angle 80; protection\DEFLPDEF1
5=Phase angle 88
DEFLPDEF Io>- 67N- Correction Angle Settings\Settings\Current
SET LD0.DEFLRDIR1.CorAng.setMag.f ASG FLOAT32 SP A 0.0 0.0...10.0 deg
1 >(1) 1(1) angle correction protection\DEFLPDEF1
181
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Rotate
DEFLPDEF Io>- 67N- Settings\Settings\Current
SET LD0.DEFLRDIR1.RevPol.setVal SPG BOOLEAN SP A 0 Pol reversal polarizing
1 >(1) 1(1) protection\DEFLPDEF1
quantity
0=Reset;
1=Activate
START;
2=Deactive
DEFLPDEF Io>- 67N- Test control Tests\Function tests\Current
TES LD0.DEFLPTOC1.TestPro.Oper.ctlVal ENC Enum CO B 0 DEFLPDEF1 START;
1 >(1) 1(1) for outputs protection
9=Activate
OPERATE;
10=Deactive
OPERATE
DEFLPDEF Io>- 67N- VisString25
VER LD0.DEFLPTOC1.NamPlt.swRev LPL DC ED1 F1 (Name plate)
1 >(1) 1(1) 5 (20)

DEFHPDEF1: Directional earth-fault, high stage: F1


IEC
ANS Categor Acces CM Parameter Parameter Channel
IEC 61850 6061 IECName CDC Type FC Default Dataset Event Parameter range Menu path
I y s T name desc relation
7
DEFHPDEF Io>>- 67N- (ACT input
INP Channel U3P
1 >(1) 2(1) channel)
DEFHPDEF Io>>- 67N- (ACT input
INP Channel I3P
1 >(1) 2(1) channel)
DEFHPDEF Io>>- 67N- (ACT input
INP Channel URES
1 >(1) 2(1) channel)
DEFHPDEF Io>>- 67N- (ACT input
INP Channel IRES
1 >(1) 2(1) channel)
Block signal
DEFHPDEF Io>>- 67N- for activating Monitoring\I/O status\Current
INP LD0.DEFHPTOC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
1 >(1) 2(1) the blocking protection\DEFHPDEF1\Inputs
mode
Enable signal
DEFHPDEF Io>>- 67N- Monitoring\I/O status\Current
INP LD0.DEFHPTOC1.InEnaMult.stVal SPS BOOLEAN ST B 0 I1 ENA_MULT for current
1 >(1) 2(1) protection\DEFHPDEF1\Inputs
multiplier
Relay
DEFHPDEF Io>>- 67N- Monitoring\I/O status\Current
INP LD0.DEFHRDIR1.InRcaCtl.stVal SPS BOOLEAN ST B 0 I1 RCA_CTL characteristic
1 >(1) 2(1) protection\DEFHPDEF1\Inputs
angle control
DEFHPDEF Io>>- 67N- StatNrm Monitoring\I/O status\Current
OUT LD0.DEFHPTOC1.Str.general ACD BOOLEAN ST B P,H I1 START Start
1 >(1) 2(1) l protection\DEFHPDEF1\Outputs
DEFHPDEF Io>>- 67N- StatNrm P,H, Monitoring\I/O status\Current
OUT LD0.DEFHPTOC1.Op.general ACT BOOLEAN ST B I1 OPERATE Operate
1 >(1) 2(1) l T protection\DEFHPDEF1\Outputs
1=on; 2=blocked;
DEFHPDEF Io>>- 67N- 3=test;
MON LD0.DEFHPTOC1.Beh.stVal ENS Enum ST B DEFHPDEF1 Status Monitoring\FB status
1 >(1) 2(1) 4=test/blocked;
5=off

182
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

0=unknown;
Monitoring\I/O status\Current
DEFHPDEF Io>>- 67N- StatNrm Detected fault 1=forward;
MON LD0.DEFHPTOC1.Str.dirGeneral ACD Enum ST B P,H FAULT_DIR protection\DEFHPDEF1\Monitore
1 >(1) 2(1) l direction 2=backward;
d data
3=both
Ratio of start Monitoring\I/O status\Current
DEFHPDEF Io>>- 67N- M
MON LD0.DEFHPTOC1.StrDur.mag.f MV FLOAT32 B START_DUR time / operate 0.00...100.00 % protection\DEFHPDEF1\Monitore
1 >(1) 2(1) X
time d data
0=unknown;
Monitoring\I/O status\Current
DEFHPDEF Io>>- 67N- Direction 1=forward;
MON LD0.DEFHRDIR1.Dir.dirGeneral ACD Enum ST B DIRECTION protection\DEFHPDEF1\Monitore
1 >(1) 2(1) information 2=backward;
d data
3=both
Calculated Monitoring\I/O status\Current
DEFHPDEF Io>>- 67N- M
MON LD0.DEFHRDIR1.OpAEF.mag.f MV FLOAT32 B I1 I_OPER operating 0.00...40.00 xIn protection\DEFHPDEF1\Monitore RESTCTR1
1 >(1) 2(1) X
current d data
Angle
between Monitoring\I/O status\Current
DEFHPDEF Io>>- 67N- M -180.00...180.00
MON LD0.DEFHRDIR1.OpPolAng.mag.f MV FLOAT32 B I1 ANGLE polarizing and protection\DEFHPDEF1\Monitore
1 >(1) 2(1) X deg
operating d data
quantity
Angle
between
Monitoring\I/O status\Current
DEFHPDEF Io>>- 67N- M ANGLE_RC operating -180.00...180.00
MON LD0.DEFHRDIR1.OpChrAng.mag.f MV FLOAT32 B I1 protection\DEFHPDEF1\Monitore
1 >(1) 2(1) X A angle and deg
d data
characteristic
angle
DEFHPDEF Io>>- 67N- Operation Off Settings\Settings\Current
SET LD0.DEFHPTOC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
1 >(1) 2(1) / On protection\DEFHPDEF1
1=ANSI Ext. inv.;
3=ANSI Norm.
inv.; 5=ANSI
Selection of
DEFHPDEF Io>>- 67N- CURV Operating Def. Time; Settings\Settings\Current
SET LD0.DEFHPTOC1.TmACrv.setCharact Enum SG B,I 15 time delay
1 >(1) 2(1) E curve type 15=IEC Def. protection\DEFHPDEF1
curve type
Time;
17=Programmabl
e
Parameter A
DEFHPDEF Io>>- 67N- CURV 28.200 Curve for customer Settings\Settings\Current
SET LD0.DEFHPTOC1.TmACrv.setParA FLOAT32 SP B,I 0.0086...120.0000
1 >(1) 2(1) E 0 parameter A programmabl protection\DEFHPDEF1
e curve
Parameter B
DEFHPDEF Io>>- 67N- CURV Curve for customer Settings\Settings\Current
SET LD0.DEFHPTOC1.TmACrv.setParB FLOAT32 SP B,I 0.1217 0.0000...0.7120
1 >(1) 2(1) E parameter B programmabl protection\DEFHPDEF1
e curve
Parameter C
DEFHPDEF Io>>- 67N- CURV Curve for customer Settings\Settings\Current
SET LD0.DEFHPTOC1.TmACrv.setParC FLOAT32 SP B,I 2.00 0.02...2.00
1 >(1) 2(1) E parameter C programmabl protection\DEFHPDEF1
e curve
DEFHPDEF Io>>- 67N- CURV Curve Parameter D Settings\Settings\Current
SET LD0.DEFHPTOC1.TmACrv.setParD FLOAT32 SP B,I 29.10 0.46...30.00
1 >(1) 2(1) E parameter D for customer protection\DEFHPDEF1

183
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

programmabl
e curve
Parameter E
DEFHPDEF Io>>- 67N- CURV Curve for customer Settings\Settings\Current
SET LD0.DEFHPTOC1.TmACrv.setParE FLOAT32 SP B,I 1.0 0.0...1.0
1 >(1) 2(1) E parameter E programmabl protection\DEFHPDEF1
e curve
DEFHPDEF Io>>- 67N- Settings\Settings\Current
SET LD0.DEFHPTOC1.StrVal.setMag.f ASG FLOAT32 SG B 0.10 Start value Start value 0.10...40.00 xIn RESTCTR1
1 >(1) 2(1) protection\DEFHPDEF1
Time
DEFHPDEF Io>>- 67N- Time multiplier in Settings\Settings\Current
SET LD0.DEFHPTOC1.TmMult.setMag.f ASG FLOAT32 SG B 1.000 0.025...15.00
1 >(1) 2(1) multiplier IEC/ANSI protection\DEFHPDEF1
IDMT curves
Minimum
DEFHPDEF Io>>- 67N- Minimum operate time Settings\Settings\Current
SET LD0.DEFHPTOC1.MinOpTmms.setVal ING INT32 SP A 40 40...60000 ms
1 >(1) 2(1) operate time for IDMT protection\DEFHPDEF1
curves
DEFHPDEF Io>>- 67N- Operate delay Operate delay Settings\Settings\Current
SET LD0.DEFHPTOC1.OpDlTmms.setVal ING INT32 SG B 40 40...200000 ms
1 >(1) 2(1) time time protection\DEFHPDEF1
Selection of 1=Immediate;
DEFHPDEF Io>>- 67N- Type of reset Settings\Settings\Current
SET LD0.DEFHPTOC1.TypRsCrv.setVal ENG Enum SG A 1 reset curve 2=Def time reset;
1 >(1) 2(1) curve protection\DEFHPDEF1
type 3=Inverse reset
DEFHPDEF Io>>- 67N- Reset delay Reset delay Settings\Settings\Current
SET LD0.DEFHPTOC1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
1 >(1) 2(1) time time protection\DEFHPDEF1
1=Non-
DEFHPDEF Io>>- 67N- Directional Directional directional; Settings\Settings\Current
SET LD0.DEFHPTOC1.DirMod.setVal ENG Enum SG B 2
1 >(1) 2(1) mode mode 2=Forward; protection\DEFHPDEF1
3=Reverse
DEFHPDEF Io>>- 67N- Voltage start Voltage start Settings\Settings\Current RESTVTR
SET LD0.DEFHPTOC1.VStr.setMag.f ASG FLOAT32 SG B 0.010 0.010...1.000 xUn
1 >(1) 2(1) value value protection\DEFHPDEF1 1
Multiplier for
DEFHPDEF Io>>- 67N- Start value Settings\Settings\Current
SET LD0.DEFHPTOC1.StrValMult.setMag.f ASG FLOAT32 SG B 1.0 scaling the 0.8...10.0
1 >(1) 2(1) Mult protection\DEFHPDEF1
start value
Allows prot
activation as
DEFHPDEF Io>>- 67N- Allow Non Settings\Settings\Current
SET LD0.DEFHPTOC1.AllwNonDir.setVal SPG BOOLEAN SP A 0 non-dir when
1 >(1) 2(1) Dir protection\DEFHPDEF1
dir info is
invalid
Selects used
DEFHPDEF Io>>- 67N- Measurement 1=RMS; 2=DFT; Settings\Settings\Current
SET LD0.DEFHPTOC1.AMeasMod.setVal ENG Enum SP A 2 measurement
1 >(1) 2(1) mode 3=Peak-to-Peak protection\DEFHPDEF1
mode
DEFHPDEF Io>>- 67N- Enable Enable Settings\Settings\Current
SET LD0.DEFHPTOC1.EnaVLim.setVal SPG BOOLEAN SG A 1
1 >(1) 2(1) voltage limit voltage limit protection\DEFHPDEF1
DEFHPDEF Io>>- 67N- Characteristic Characteristic Settings\Settings\Current
SET LD0.DEFHRDIR1.ChrAng.setMag.f ASG FLOAT32 SG B -90 -179...180 deg
1 >(1) 2(1) angle angle protection\DEFHPDEF1
Minimum
DEFHPDEF Io>>- 67N- Min forward phase angle in Settings\Settings\Current
SET LD0.DEFHRDIR1.MinFwdAng.setMag.f ASG FLOAT32 SG B 80 0...180 deg
1 >(1) 2(1) angle forward protection\DEFHPDEF1
direction

184
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Minimum
DEFHPDEF Io>>- 67N- Min reverse phase angle in Settings\Settings\Current
SET LD0.DEFHRDIR1.MinRvAng.setMag.f ASG FLOAT32 SG B 80 0...180 deg
1 >(1) 2(1) angle reverse protection\DEFHPDEF1
direction
Maximum
DEFHPDEF Io>>- 67N- LD0.DEFHRDIR1.MaxFwdAng.setMag. Max forward phase angle in Settings\Settings\Current
SET ASG FLOAT32 SG B 80 0...180 deg
1 >(1) 2(1) f angle forward protection\DEFHPDEF1
direction
Maximum
DEFHPDEF Io>>- 67N- Max reverse phase angle in Settings\Settings\Current
SET LD0.DEFHRDIR1.MaxRvAng.setMag.f ASG FLOAT32 SG B 80 0...180 deg
1 >(1) 2(1) angle reverse protection\DEFHPDEF1
direction
Minimum
DEFHPDEF Io>>- 67N- Min operate Settings\Settings\Current
SET LD0.DEFHRDIR1.BlkValA.setMag.f ASG FLOAT32 SP A 0.005 operating 0.005...1.000 xIn RESTCTR1
1 >(1) 2(1) current protection\DEFHPDEF1
current
Minimum
DEFHPDEF Io>>- 67N- Min operate Settings\Settings\Current RESTVTR
SET LD0.DEFHRDIR1.BlkValV.setMag.f ASG FLOAT32 SP A 0.01 operating 0.01...1.00 xUn
1 >(1) 2(1) voltage protection\DEFHPDEF1 1
voltage
Reference
DEFHPDEF Io>>- 67N- quantity used 3=Zero seq. volt.; Settings\Settings\Current
SET LD0.DEFHRDIR1.PolQty.setVal ENG Enum SP A,I 3 Pol quantity
1 >(1) 2(1) to determine 4=Neg. seq. volt. protection\DEFHPDEF1
fault direction
1=Phase angle;
2=IoSin;
DEFHPDEF Io>>- 67N- Operation Operation Settings\Settings\Current
SET LD0.DEFHRDIR1.OpModEF.setVal ENG Enum SG A 1 3=IoCos; 4=Phase
1 >(1) 2(1) mode criteria protection\DEFHPDEF1
angle 80; 5=Phase
angle 88
DEFHPDEF Io>>- 67N- Correction Angle Settings\Settings\Current
SET LD0.DEFHRDIR1.CorAng.setMag.f ASG FLOAT32 SP A 0.0 0.0...10.0 deg
1 >(1) 2(1) angle correction protection\DEFHPDEF1
Rotate
DEFHPDEF Io>>- 67N- Settings\Settings\Current
SET LD0.DEFHRDIR1.RevPol.setVal SPG BOOLEAN SP A 0 Pol reversal polarizing
1 >(1) 2(1) protection\DEFHPDEF1
quantity
0=Reset;
1=Activate
START;
2=Deactive
DEFHPDEF Io>>- 67N- Test control Tests\Function tests\Current
TES LD0.DEFHPTOC1.TestPro.Oper.ctlVal ENC Enum CO B 0 DEFHPDEF1 START;
1 >(1) 2(1) for outputs protection
9=Activate
OPERATE;
10=Deactive
OPERATE
DEFHPDEF Io>>- 67N- VisString25
VER LD0.DEFHPTOC1.NamPlt.swRev LPL DC ED1 F1 (Name plate)
1 >(1) 2(1) 5 (20)

DOPPDPR1: Reverse power / Directional over power protection: A1


IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation

185
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

(ACT input
DOPPDPR1 P>/Q>(1) 32R/32O(1) INP Channel U3P
channel)
(ACT input
DOPPDPR1 P>/Q>(1) 32R/32O(1) INP Channel I3P
channel)
Block
signal for
activating Monitoring\I/O status\Power
DOPPDPR1 P>/Q>(1) 32R/32O(1) INP LD0.DPPDOP1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
the protection\DOPPDPR1\Inputs
blocking
mode
Monitoring\I/O status\Power
DOPPDPR1 P>/Q>(1) 32R/32O(1) OUT LD0.DPPDOP1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start
protection\DOPPDPR1\Outputs
Monitoring\I/O status\Power
DOPPDPR1 P>/Q>(1) 32R/32O(1) OUT LD0.DPPDOP1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate
protection\DOPPDPR1\Outputs
1=on; 2=blocked;
3=test;
DOPPDPR1 P>/Q>(1) 32R/32O(1) MON LD0.DPPDOP1.Beh.stVal ENS Enum ST B DOPPDPR1 Status Monitoring\FB status
4=test/blocked;
5=off
Ratio of
Monitoring\I/O status\Power
start time /
DOPPDPR1 P>/Q>(1) 32R/32O(1) MON LD0.DPPDOP1.StrDur.mag.f MV FLOAT32 MX B START_DUR 0.00...100.00 % protection\DOPPDPR1\Monitored
operate
data
time
Monitoring\I/O status\Power
Active -160.000...160.000
DOPPDPR1 P>/Q>(1) 32R/32O(1) MON LD0.DOPMMXU1.TotW.mag.f MV FLOAT32 MX B I1 P protection\DOPPDPR1\Monitored
power xSn
data
Monitoring\I/O status\Power
Reactive -160.000...160.000
DOPPDPR1 P>/Q>(1) 32R/32O(1) MON LD0.DOPMMXU1.TotVAr.mag.f MV FLOAT32 MX B I1 Q protection\DOPPDPR1\Monitored
power xSn
data
Monitoring\I/O status\Power
Apparent
DOPPDPR1 P>/Q>(1) 32R/32O(1) MON LD0.DOPMMXU1.TotVA.mag.f MV FLOAT32 MX B I1 S 0.000...160.000 xSn protection\DOPPDPR1\Monitored
power
data
Monitoring\I/O status\Power
Power -180.00...180.00
DOPPDPR1 P>/Q>(1) 32R/32O(1) MON LD0.DOPMMXU1.TotPFAng.mag.f MV FLOAT32 MX B I1 PF_ANGLE protection\DOPPDPR1\Monitored
factor angle deg
data
Operation Settings\Settings\Power
DOPPDPR1 P>/Q>(1) 32R/32O(1) SET LD0.DPPDOP1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
On/Off protection\DOPPDPR1
Directional Directional 2=Forward; Settings\Settings\Power
DOPPDPR1 P>/Q>(1) 32R/32O(1) SET LD0.DPPDOP1.DirMod.setVal ENG Enum SG B 2
mode mode 3=Reverse protection\DOPPDPR1
Settings\Settings\Power
DOPPDPR1 P>/Q>(1) 32R/32O(1) SET LD0.DPPDOP1.StrVal.setMag.f ASG FLOAT32 SG B 1.0 Start value Start value 0.01...2.00 xSn
protection\DOPPDPR1
Operate delay Operate Settings\Settings\Power
DOPPDPR1 P>/Q>(1) 32R/32O(1) SET LD0.DPPDOP1.OpDlTmms.setVal ING INT32 SG B 40 40...300000 ms
time delay time protection\DOPPDPR1
Reset delay Reset delay Settings\Settings\Power
DOPPDPR1 P>/Q>(1) 32R/32O(1) SET LD0.DPPDOP1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
time time protection\DOPPDPR1
1=PhsA, PhsB,
Selection of
PhsC; 2=Arone;
Measurement power Settings\Settings\Power
DOPPDPR1 P>/Q>(1) 32R/32O(1) SET LD0.DPPDOP1.PwrMeasMod.setVal ENG Enum SP B 3 3=Pos Seq;
mode calculation protection\DOPPDPR1
4=PhsAB;
method
5=PhsBC;
186
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

6=PhsCA; 7=PhsA;
8=PhsB; 9=PhsC
Reverse the
definition
Settings\Settings\Power
DOPPDPR1 P>/Q>(1) 32R/32O(1) SET LD0.DPPDOP1.RevPol.setVal SPG BOOLEAN SP A 0 Pol reversal of the
protection\DOPPDPR1
power
direction
Adjustable
Settings\Settings\Power
DOPPDPR1 P>/Q>(1) 32R/32O(1) SET LD0.DPPDOP1.PwrAng.setMag.f ASG FLOAT32 SG B 0 Power angle angle for -90...90 deg
protection\DOPPDPR1
power
0=Reset;
1=Activate START;
2=Deactive
Test control Tests\Function tests\Power
DOPPDPR1 P>/Q>(1) 32R/32O(1) TES LD0.DPPDOP1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 DOPPDPR1 START; 9=Activate
for outputs protection
OPERATE;
10=Deactive
OPERATE
VisString255 (Name
DOPPDPR1 P>/Q>(1) 32R/32O(1) VER LD0.DPPDOP1.NamPlt.swRev LPL DC ED1 A1
(20) plate)

PDNSPTOC1: Phase discontinuity protection: D1


IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
(ACT
PDNSPTOC1 I2/I1>(1) 46PD(1) INP Channel I3P input
channel)
Block
signal for
activating Monitoring\I/O status\Current
PDNSPTOC1 I2/I1>(1) 46PD(1) INP LD0.PDNSPTOC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
the protection\PDNSPTOC1\Inputs
blocking
mode
Monitoring\I/O status\Current
PDNSPTOC1 I2/I1>(1) 46PD(1) OUT LD0.PDNSPTOC1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start
protection\PDNSPTOC1\Outputs
Monitoring\I/O status\Current
PDNSPTOC1 I2/I1>(1) 46PD(1) OUT LD0.PDNSPTOC1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate
protection\PDNSPTOC1\Outputs
1=on;
2=blocked;
PDNSPTOC1 I2/I1>(1) 46PD(1) MON LD0.PDNSPTOC1.Beh.stVal ENS Enum ST B PDNSPTOC1 Status 3=test; Monitoring\FB status
4=test/blocked;
5=off
Measured
Monitoring\I/O status\Current
current
PDNSPTOC1 I2/I1>(1) 46PD(1) MON LD0.PDNSPTOC1.ImbNgA.mag.f MV FLOAT32 MX B I1 RATIO_I2_I1 0.00...999.99 % protection\PDNSPTOC1\Monitored
ratio I2 /
data
I1
Monitoring\I/O status\Current
Ratio of
PDNSPTOC1 I2/I1>(1) 46PD(1) MON LD0.PDNSPTOC1.StrDur.mag.f MV FLOAT32 MX B START_DUR 0.00...100.00 % protection\PDNSPTOC1\Monitored
start time /
data
187
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

operate
time
Operation Settings\Settings\Current
PDNSPTOC1 I2/I1>(1) 46PD(1) SET LD0.PDNSPTOC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
Off / On protection\PDNSPTOC1
Settings\Settings\Current
PDNSPTOC1 I2/I1>(1) 46PD(1) SET LD0.PDNSPTOC1.StrVal.setMag.f ASG FLOAT32 SG B 10 Start value Start value 10...100 %
protection\PDNSPTOC1
Operate delay Operate Settings\Settings\Current
PDNSPTOC1 I2/I1>(1) 46PD(1) SET LD0.PDNSPTOC1.OpDlTmms.setVal ING INT32 SG B 100 100...30000 ms
time delay time protection\PDNSPTOC1
Reset delay Reset Settings\Settings\Current
PDNSPTOC1 I2/I1>(1) 46PD(1) SET LD0.PDNSPTOC1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
time delay time protection\PDNSPTOC1
Minimum
Min phase Settings\Settings\Current
PDNSPTOC1 I2/I1>(1) 46PD(1) SET LD0.PDNSPTOC1.MinPhA.setMag.f ASG FLOAT32 SP A 0.10 phase 0.05...0.30 xIn IL1TCTR1
current protection\PDNSPTOC1
current
0=Reset;
1=Activate
START;
Test 2=Deactive
Tests\Function tests\Current
PDNSPTOC1 I2/I1>(1) 46PD(1) TES LD0.PDNSPTOC1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 PDNSPTOC1 control for START;
protection
outputs 9=Activate
OPERATE;
10=Deactive
OPERATE
VisString255 (Name
PDNSPTOC1 I2/I1>(1) 46PD(1) VER LD0.PDNSPTOC1.NamPlt.swRev LPL DC ED1 D1
(20) plate)

T1PTTR1: Thermal overload protection, one time constant: F1


IEC IEC Channel
ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter name Parameter desc Parameter range Menu path
61850 60617 relation
(ACT input
T1PTTR1 3Ith>F(1) 49F(1) INP Channel I3P
channel)
Block signal for Monitoring\I/O status\Current
T1PTTR1 3Ith>F(1) 49F(1) INP LD0.T1PTTR1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLK_OPR
operate outputs protection\T1PTTR1\Inputs
Enable Current Monitoring\I/O status\Current
T1PTTR1 3Ith>F(1) 49F(1) INP LD0.T1PTTR1.InEnaMult.stVal SPS BOOLEAN ST B 0 I1 ENA_MULT
multiplier protection\T1PTTR1\Inputs
The ambient
temperature Monitoring\I/O status\Current
T1PTTR1 3Ith>F(1) 49F(1) INP LD0.T1PTTR1.TmpAmb.mag.f MV FLOAT32 MX B 0 I1 AMB_TEMP -99...999 °C
used in the protection\T1PTTR1\Inputs
calculation
Monitoring\I/O status\Current
T1PTTR1 3Ith>F(1) 49F(1) OUT LD0.T1PTTR1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start
protection\T1PTTR1\Outputs
Monitoring\I/O status\Current
T1PTTR1 3Ith>F(1) 49F(1) OUT LD0.T1PTTR1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate
protection\T1PTTR1\Outputs
Monitoring\I/O status\Current
T1PTTR1 3Ith>F(1) 49F(1) OUT LD0.T1PTTR1.AlmThm.stVal SPS BOOLEAN ST B StatUrg P,H I1 ALARM Thermal Alarm
protection\T1PTTR1\Outputs
Thermal Monitoring\I/O status\Current
T1PTTR1 3Ith>F(1) 49F(1) OUT LD0.T1PTTR1.BlkThm.stVal SPS BOOLEAN ST B I1 BLK_CLOSE
overload protection\T1PTTR1\Outputs
188
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

indicator. To
inhibite reclose.
Reset
T1PTTR1
T1PTTR1 3Ith>F(1) 49F(1) CTR LD0.T1PTTR1.RsTmp.Oper.ctlVal SPC BOOLEAN CO B 0 I1 T1PTTR1 0=Cancel; 1=Clear Clear\Clear
temperature
tempetature
1=on; 2=blocked;
3=test;
T1PTTR1 3Ith>F(1) 49F(1) MON LD0.T1PTTR1.Beh.stVal ENS Enum ST B T1PTTR1 Status Monitoring\FB status
4=test/blocked;
5=off
The calculated
Monitoring\I/O status\Current
temperature of
T1PTTR1 3Ith>F(1) 49F(1) MON LD0.T1PTTR1.Tmp.mag.f MV FLOAT32 MX B MeasFlt P I1 TEMP -100.0...9999.9 °C protection\T1PTTR1\Monitored
the protected
data
object
The calculated
temperature of
Monitoring\I/O status\Current
the protected
T1PTTR1 3Ith>F(1) 49F(1) MON LD0.T1PTTR1.TmpRl.mag.f MV FLOAT32 MX B MeasFlt P I1 TEMP_RL 0.00...99.99 protection\T1PTTR1\Monitored
object relative
data
to the operate
level
The ambient
Monitoring\I/O status\Current
temperature
T1PTTR1 3Ith>F(1) 49F(1) MON LD0.T1PTTR1.TmpUsed.mag.f MV FLOAT32 MX B I1 TEMP_AMB -99...999 °C protection\T1PTTR1\Monitored
used in the
data
calculation
Monitoring\I/O status\Current
Estimated time
T1PTTR1 3Ith>F(1) 49F(1) MON LD0.T1PTTR1.OpTm.stVal INS INT32 ST B I1 T_OPERATE 0...60000 s protection\T1PTTR1\Monitored
to operate
data
Estimated time Monitoring\I/O status\Current
T1PTTR1 3Ith>F(1) 49F(1) MON LD0.T1PTTR1.BlkThmRsTm.stVal INS INT32 ST B I1 T_ENA_CLOSE to deactivate 0...60000 s protection\T1PTTR1\Monitored
BLK_CLOSE data
Operation Off / Settings\Settings\Current
T1PTTR1 3Ith>F(1) 49F(1) SET LD0.T1PTTR1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
On protection\T1PTTR1
Temperature
Maximum Settings\Settings\Current
T1PTTR1 3Ith>F(1) 49F(1) SET LD0.T1PTTR1.TmpMax.setMag.f ASG FLOAT32 SG B 90.0 level for 20.0...200.0 °C
temperature protection\T1PTTR1
operate
Time constant
Settings\Settings\Current
T1PTTR1 3Ith>F(1) 49F(1) SET LD0.T1PTTR1.ConsTms1.setVal ING INT32 SG B 2700 Time constant of the line in 60...60000 s
protection\T1PTTR1
seconds.
Temperature
Settings\Settings\Current
T1PTTR1 3Ith>F(1) 49F(1) SET LD0.T1PTTR1.AlmVal.setMag.f ASG FLOAT32 SG B 80.0 Alarm value level for start 20.0...150.0 °C
protection\T1PTTR1
(alarm)
Current
multiplier when
Current Settings\Settings\Current
T1PTTR1 3Ith>F(1) 49F(1) SET LD0.T1PTTR1.AMult.setVal ING INT32 SG A 1 function is used 1...5
multiplier protection\T1PTTR1
for parallel
lines
The load
current leading
Current Settings\Settings\Current
T1PTTR1 3Ith>F(1) 49F(1) SET LD0.T1PTTR1.ARef.setMag.f ASG FLOAT32 SG B 1.00 to Temperature 0.05...4.00 xIn IL1TCTR1
reference protection\T1PTTR1
raise
temperature
189
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Ambient
temperature
used when no
Env temperature Settings\Settings\Current
T1PTTR1 3Ith>F(1) 49F(1) SET LD0.T1PTTR1.EnvTmpSet.setMag.f ASG FLOAT32 SG B 40 external -50...100 °C
Set protection\T1PTTR1
temperature
measurement
available
Temperature
raise above
Initial Settings\Settings\Current
T1PTTR1 3Ith>F(1) 49F(1) SET LD0.T1PTTR1.IniTmp.setMag.f ASG FLOAT32 SP A 0.0 ambient -50.0...100.0 °C
temperature protection\T1PTTR1
temperature at
startup
Temperature
Reclose for reset of Settings\Settings\Current
T1PTTR1 3Ith>F(1) 49F(1) SET LD0.T1PTTR1.RecTmpSet.setMag.f ASG FLOAT32 SG B 70.0 20.0...150.0 °C
temperature block reclose protection\T1PTTR1
after operate
End
Settings\Settings\Current
T1PTTR1 3Ith>F(1) 49F(1) SET LD0.T1PTTR1.TmpR.setMag.f ASG FLOAT32 SG B 75.0 Temperature rise temperature rise 0.0...200.0 °C
protection\T1PTTR1
above ambient
0=Reset; 1=Activate
START; 2=Deactive
START; 9=Activate
OPERATE;
10=Deactive
OPERATE;
Test control for 17=Activate Tests\Function tests\Current
T1PTTR1 3Ith>F(1) 49F(1) TES LD0.T1PTTR1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 T1PTTR1
outputs ALARM; protection
18=Deactive
ALARM;
21=Activate
BLK_CLOSE;
22=Deactive
BLK_CLOSE
VisString255
T1PTTR1 3Ith>F(1) 49F(1) VER LD0.T1PTTR1.NamPlt.swRev LPL DC ED1 F1 (Name plate)
(20)

DARREC1: Autorecloser: F1
IEC Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter name Parameter desc Parameter range Menu path
60617 relation
Interrupts and
O- inhibits Monitoring\I/O
DARREC1 79(1) INP LD0.DARREC1.InInhRec.stVal SPS BOOLEAN ST B 0 I1 INHIBIT_RECL
>I(1) reclosing status\Control\DARREC1\Inputs
sequence
Blocks and
holds the
O- reclose shot Monitoring\I/O
DARREC1 79(1) INP LD0.DARREC1.InBlkThm.stVal SPS BOOLEAN ST B 0 I1 BLK_THERM
>I(1) from the status\Control\DARREC1\Inputs
thermal
overload
190
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Level sensitive
signal for
O- Monitoring\I/O
DARREC1 79(1) INP LD0.DARREC1.InRecOn.stVal SPS BOOLEAN ST B 0 I1 RECL_ON allowing (high)
>I(1) status\Control\DARREC1\Inputs
/ not allowing
(low) reclosing
Blocks and
O- Monitoring\I/O
DARREC1 79(1) INP LD0.DARREC1.InBlkRclTm.stVal SPS BOOLEAN ST B 0 I1 BLK_RCLM_T resets reclaim
>I(1) status\Control\DARREC1\Inputs
time
O- Circuit breaker Monitoring\I/O
DARREC1 79(1) INP LD0.DARREC1.InCBPos.stVal SPS BOOLEAN ST B 0 I1 CB_POS
>I(1) position input status\Control\DARREC1\Inputs
O- Circuit breaker Monitoring\I/O
DARREC1 79(1) INP LD0.DARREC1.InCBRdy.stVal SPS BOOLEAN ST B 1 I1 CB_READY
>I(1) status signal status\Control\DARREC1\Inputs
O- Synchronizing Monitoring\I/O
DARREC1 79(1) INP LD0.DARREC1.InSynChk.stVal SPS BOOLEAN ST B 0 I1 SYNC
>I(1) check fulfilled status\Control\DARREC1\Inputs
A zone
O- sequence Monitoring\I/O
DARREC1 79(1) INP LD0.DARREC1.InIncrPntr.stVal SPS BOOLEAN ST B 0 I1 INC_SHOTP
>I(1) coordination status\Control\DARREC1\Inputs
signal
AR
O- initialization / Monitoring\I/O
DARREC1 79(1) INP LD0.DARREC1.InIni1.stVal SPS BOOLEAN ST B 0 I1 INIT_1
>I(1) blocking signal status\Control\DARREC1\Inputs
1
AR
O- initialization / Monitoring\I/O
DARREC1 79(1) INP LD0.DARREC1.InIni2.stVal SPS BOOLEAN ST B 0 I1 INIT_2
>I(1) blocking signal status\Control\DARREC1\Inputs
2
AR
O- initialization / Monitoring\I/O
DARREC1 79(1) INP LD0.DARREC1.InIni3.stVal SPS BOOLEAN ST B 0 I1 INIT_3
>I(1) blocking signal status\Control\DARREC1\Inputs
3
AR
O- initialization / Monitoring\I/O
DARREC1 79(1) INP LD0.DARREC1.InIni4.stVal SPS BOOLEAN ST B 0 I1 INIT_4
>I(1) blocking signal status\Control\DARREC1\Inputs
4
AR
O- initialization / Monitoring\I/O
DARREC1 79(1) INP LD0.DARREC1.InIni5.stVal SPS BOOLEAN ST B 0 I1 INIT_5
>I(1) blocking signal status\Control\DARREC1\Inputs
5
AR
O- initialization / Monitoring\I/O
DARREC1 79(1) INP LD0.DARREC1.InIni6.stVal SPS BOOLEAN ST B 0 I1 INIT_6
>I(1) blocking signal status\Control\DARREC1\Inputs
6
Delayed AR
O- initialization / Monitoring\I/O
DARREC1 79(1) INP LD0.DARREC1.InDlIni2.stVal SPS BOOLEAN ST B 0 I1 DEL_INIT_2
>I(1) blocking signal status\Control\DARREC1\Inputs
2
Delayed AR
O- initialization / Monitoring\I/O
DARREC1 79(1) INP LD0.DARREC1.InDlIni3.stVal SPS BOOLEAN ST B 0 I1 DEL_INIT_3
>I(1) blocking signal status\Control\DARREC1\Inputs
3
191
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Delayed AR
O- initialization / Monitoring\I/O
DARREC1 79(1) INP LD0.DARREC1.InDlIni4.stVal SPS BOOLEAN ST B 0 I1 DEL_INIT_4
>I(1) blocking signal status\Control\DARREC1\Inputs
4
Blocks and
O- Monitoring\I/O
DARREC1 79(1) INP LD0.DARREC1.InBlkRecTm.stVal SPS BOOLEAN ST B 0 I1 BLK_RECL_T resets reclose
>I(1) status\Control\DARREC1\Inputs
time
Close (reclose)
O- Monitoring\I/O
DARREC1 79(1) OUT LD0.DARREC1.OpCls.general ACT BOOLEAN ST B StatNrml P,H,T CLOSE_CB command for (A,B,C)
>I(1) status\Control\DARREC1\Outputs
circuit breaker
Open
O- Monitoring\I/O
DARREC1 79(1) OUT LD0.DARREC1.OpOpn.general ACT BOOLEAN ST B StatNrml P,H OPEN_CB command for (A,B,C)
>I(1) status\Control\DARREC1\Outputs
circuit breaker
Signal
O- indicating that Monitoring\I/O
DARREC1 79(1) OUT LD0.DARREC1.LO.stVal SPS BOOLEAN ST B StatNrml P,H I1 LOCKED
>I(1) AR is locked status\Control\DARREC1\Outputs
out
Indicates that
the AR is ready
for a new
O- sequence, i.e. Monitoring\I/O
DARREC1 79(1) OUT LD0.DARREC1.RdyRec.stVal SPS BOOLEAN ST B StatIed P,H I1 READY
>I(1) the status\Control\DARREC1\Outputs
CB_READY
input equals
TRUE
Reclosing
O- Monitoring\I/O
DARREC1 79(1) OUT LD0.DARREC1.ActRec.stVal SPS BOOLEAN ST B StatIed P,H I1 ACTIVE sequence is in
>I(1) status\Control\DARREC1\Outputs
progress
Indicates an
O- unsuccessful Monitoring\I/O
DARREC1 79(1) OUT LD0.DARREC1.UnsRec.stVal SPS BOOLEAN ST B StatNrml P,H I1 UNSUC_RECL
>I(1) reclosing status\Control\DARREC1\Outputs
sequence
Reclosing shot
in progress,
O- Monitoring\I/O
DARREC1 79(1) OUT LD0.DARREC1.PrgRec.stVal SPS BOOLEAN ST B StatNrml P,H I1 INPRO activated
>I(1) status\Control\DARREC1\Outputs
during dead
time
Wait for
O- Monitoring\I/O
DARREC1 79(1) OUT LD0.DARREC1.WtMstr.stVal SPS BOOLEAN ST B StatIed P,H I1 CMD_WAIT master
>I(1) status\Control\DARREC1\Outputs
command
A signal for
coordination
O- Monitoring\I/O
DARREC1 79(1) OUT LD0.DARREC1.ProCrd.stVal SPS BOOLEAN ST B I1 PROT_CRD between the
>I(1) status\Control\DARREC1\Outputs
AR and the
protection
O- Autoreclosing Monitoring\I/O
DARREC1 79(1) OUT LD0.DARREC1.AutoRecOn.stVal SPS BOOLEAN ST B StatIed P,H I1 AR_ON
>I(1) allowed status\Control\DARREC1\Outputs
O-
DARREC1 79(1) CTR LD0.DARREC1.BlkRec.Oper.ctlVal SPC BOOLEAN CO I1 (Block reclose)
>I(1)

192
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

DARREC1
O-
DARREC1 79(1) CTR LD0.DARREC1.RecRs.Oper.ctlVal SPC BOOLEAN CO B 0 I1 DARREC1 reset reset to initial 0=Cancel; 1=Clear Clear\Clear
>I(1)
condition
O- DARREC1 DARREC1 all
DARREC1 79(1) CTR LD0.DARREC1.CntRs.Oper.ctlVal SPC BOOLEAN CO B 0 I1 0=Cancel; 1=Clear Clear\Clear
>I(1) counters counters reset
(Signal for
O-
DARREC1 79(1) CTR LD0.DARREC1.DsaCnt.Oper.ctlVal SPC BOOLEAN CO I1 counter
>I(1)
disabling)
1=on; 2=blocked;
O-
DARREC1 79(1) MON LD0.DARREC1.Beh.stVal ENS Enum ST B DARREC1 Status 3=test; 4=test/blocked; Monitoring\FB status
>I(1)
5=off
Resetable
Monitoring\I/O
O- operation
DARREC1 79(1) MON LD0.DARREC1.OpCntRs.stVal INC INT32 ST B I1 COUNTER 0...2147483647 status\Control\DARREC1\Monitored
>I(1) counter, all
data
shots
-1=Not defined;
1=Ready;
2=InProgress;
3=Successful;
4=WaitingForTrip;
AR status Monitoring\I/O
O- 5=TripFromProtection;
DARREC1 79(1) MON LD0.DARREC1.AutoRecSt.stVal ENS Enum ST B StatIed P,H I1 STATUS signal for status\Control\DARREC1\Monitored
>I(1) 6=FaultDisappeared;
IEC61850 data
7=WaitToComplete;
8=CBclosed;
9=CycleUnsuccessful;
10=Unsuccessful;
11=Aborted
Resetable Monitoring\I/O
O-
DARREC1 79(1) MON LD0.DARREC1.RecCnt1.stVal INS INT32 ST B I1 CNT_SHOT1 operation 0...2147483647 status\Control\DARREC1\Monitored
>I(1)
counter, shot 1 data
Resetable Monitoring\I/O
O-
DARREC1 79(1) MON LD0.DARREC1.RecCnt2.stVal INS INT32 ST B I1 CNT_SHOT2 operation 0...2147483647 status\Control\DARREC1\Monitored
>I(1)
counter, shot 2 data
Resetable Monitoring\I/O
O-
DARREC1 79(1) MON LD0.DARREC1.RecCnt3.stVal INS INT32 ST B I1 CNT_SHOT3 operation 0...2147483647 status\Control\DARREC1\Monitored
>I(1)
counter, shot 3 data
Resetable Monitoring\I/O
O-
DARREC1 79(1) MON LD0.DARREC1.RecCnt4.stVal INS INT32 ST B I1 CNT_SHOT4 operation 0...2147483647 status\Control\DARREC1\Monitored
>I(1)
counter, shot 4 data
Resetable Monitoring\I/O
O-
DARREC1 79(1) MON LD0.DARREC1.RecCnt5.stVal INS INT32 ST B I1 CNT_SHOT5 operation 0...2147483647 status\Control\DARREC1\Monitored
>I(1)
counter, shot 5 data
Indicates a
Monitoring\I/O
O- successful
DARREC1 79(1) MON LD0.DARREC1.SucRec.stVal SPS BOOLEAN ST B StatNrml P,H I1 SUC_RECL status\Control\DARREC1\Monitored
>I(1) reclosing
data
sequence
Indicates an Monitoring\I/O
O-
DARREC1 79(1) MON LD0.DARREC1.UnsCBCls.stVal SPS BOOLEAN ST B StatIed P,H I1 UNSUC_CB unsuccessful status\Control\DARREC1\Monitored
>I(1)
CB closing data

193
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Reclosing shot Monitoring\I/O


O-
DARREC1 79(1) MON LD0.DARREC1.PrgRec1.stVal SPS BOOLEAN ST B StatIed P,H I1 INPRO_1 in progress, status\Control\DARREC1\Monitored
>I(1)
shot 1 data
Reclosing shot Monitoring\I/O
O-
DARREC1 79(1) MON LD0.DARREC1.PrgRec2.stVal SPS BOOLEAN ST B StatIed P,H I1 INPRO_2 in progress, status\Control\DARREC1\Monitored
>I(1)
shot 2 data
Reclosing shot Monitoring\I/O
O-
DARREC1 79(1) MON LD0.DARREC1.PrgRec3.stVal SPS BOOLEAN ST B StatIed P,H I1 INPRO_3 in progress, status\Control\DARREC1\Monitored
>I(1)
shot 3 data
Reclosing shot Monitoring\I/O
O-
DARREC1 79(1) MON LD0.DARREC1.PrgRec4.stVal SPS BOOLEAN ST B StatIed P,H I1 INPRO_4 in progress, status\Control\DARREC1\Monitored
>I(1)
shot 4 data
Reclosing shot Monitoring\I/O
O-
DARREC1 79(1) MON LD0.DARREC1.PrgRec5.stVal SPS BOOLEAN ST B StatIed P,H I1 INPRO_5 in progress, status\Control\DARREC1\Monitored
>I(1)
shot 5 data
Signal
indicating that Monitoring\I/O
O-
DARREC1 79(1) MON LD0.DARREC1.PrgDsr.stVal SPS BOOLEAN ST B StatIed P,H I1 DISCR_INPRO discrimination status\Control\DARREC1\Monitored
>I(1)
time is in data
progress
Signal
Monitoring\I/O
O- indicating that
DARREC1 79(1) MON LD0.DARREC1.PrgCutOut.stVal SPS BOOLEAN ST B StatIed P,H I1 CUTOUT_INPRO status\Control\DARREC1\Monitored
>I(1) cut-out time is
data
in progress
Frequent Monitoring\I/O
O-
DARREC1 79(1) MON LD0.DARREC1.FrqOpCnt.stVal INS INT32 ST B I1 FRQ_OPR_CNT operation 0...2147483647 status\Control\DARREC1\Monitored
>I(1)
counter data
Frequent Monitoring\I/O
O-
DARREC1 79(1) MON LD0.DARREC1.FrqOpAlm.stVal SPS BOOLEAN ST B StatIed P,H I1 FRQ_OPR_AL operation status\Control\DARREC1\Monitored
>I(1)
counter alarm data
Signal for Monitoring\I/O
O-
DARREC1 79(1) MON LD0.DARREC1.DsaCnt.stVal SPC BOOLEAN ST B I1 DISA_COUNT counter status\Control\DARREC1\Monitored
>I(1)
disabling data
O- (Reclaim time
DARREC1 79(1) MON LD0.DARREC1.RclTmStr.stVal SPS BOOLEAN ST StatIed P,H I1
>I(1) started)
Indicates CB
manual closing Monitoring\I/O
O-
DARREC1 79(1) MON LD0.DARREC1.CBManCls.stVal SPS BOOLEAN ST B StatIed P,H I1 MAN_CB_CL during status\Control\DARREC1\Monitored
>I(1)
reclosing data
sequence
Monitoring\I/O
O- Shot pointer
DARREC1 79(1) MON LD0.DARREC1.ShotPntr.stVal INS INT32 ST B StatIed P,H I1 SHOT_PTR 1...7 status\Control\DARREC1\Monitored
>I(1) value
data
Monitoring\I/O
O- Switch-onto-
DARREC1 79(1) MON LD0.DARREC1.SOF.stVal SPS BOOLEAN ST B I1 SOTF status\Control\DARREC1\Monitored
>I(1) fault
data
O- Operation
DARREC1 79(1) SET LD0.DARREC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off Settings\Settings\Control\DARREC1
>I(1) Off/On

194
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

O- Dead time for


DARREC1 79(1) SET LD0.DARREC1.Rec1Tmms1.setVal ING INT32 SP B 5000 First reclose time 0...300000 ms Settings\Settings\Control\DARREC1
>I(1) CBB1
O- Second reclose Dead time for
DARREC1 79(1) SET LD0.DARREC1.Rec1Tmms2.setVal ING INT32 SP B 5000 0...300000 ms Settings\Settings\Control\DARREC1
>I(1) time CBB2
O- Dead time for
DARREC1 79(1) SET LD0.DARREC1.Rec1Tmms3.setVal ING INT32 SP B 5000 Third reclose time 0...300000 ms Settings\Settings\Control\DARREC1
>I(1) CBB3
O- Fourth reclose Dead time for
DARREC1 79(1) SET LD0.DARREC1.Rec1Tmms4.setVal ING INT32 SP B 5000 0...300000 ms Settings\Settings\Control\DARREC1
>I(1) time CBB4
O- Dead time for
DARREC1 79(1) SET LD0.DARREC1.Rec1Tmms5.setVal ING INT32 SP B 5000 Fifth reclose time 0...300000 ms Settings\Settings\Control\DARREC1
>I(1) CBB5
O- Dead time for
DARREC1 79(1) SET LD0.DARREC1.Rec1Tmms6.setVal ING INT32 SP B 5000 Sixth reclose time 0...300000 ms Settings\Settings\Control\DARREC1
>I(1) CBB6
O- Seventh reclose Dead time for
DARREC1 79(1) SET LD0.DARREC1.Rec1Tmms7.setVal ING INT32 SP B 5000 0...300000 ms Settings\Settings\Control\DARREC1
>I(1) time CBB7
O-
DARREC1 79(1) SET LD0.DARREC1.RclTmms.setVal ING INT32 SP B 10000 Reclaim time Reclaim time 100...1800000 ms Settings\Settings\Control\DARREC1
>I(1)
Defines INIT
O- lines that are
DARREC1 79(1) SET LD0.DARREC1.AutoIni.setVal ING INT32 SP B,I 0 Auto init 0...63 Settings\Settings\Control\DARREC1
>I(1) activated at
auto initiation
Reclosing
O- Reclosing operation (Off, 1=Off; 2=External Ctl;
DARREC1 79(1) SET LD0.DARREC1.RecOp.setVal ENG Enum SP B 1 Settings\Settings\Control\DARREC1
>I(1) operation External Ctl / 3=On
On)
O- Manual close Manual close
DARREC1 79(1) SET LD0.DARREC1.ManClsMod.setVal SPG BOOLEAN SP A 0 Settings\Settings\Control\DARREC1
>I(1) mode mode
Allowed CB
O- closing time
DARREC1 79(1) SET LD0.DARREC1.WtClsTmms.setVal ING INT32 SP A 250 Wait close time 50...10000 ms Settings\Settings\Control\DARREC1
>I(1) after reclose
command
Maximum wait
O- time for
DARREC1 79(1) SET LD0.DARREC1.MaxWtTmms.setVal ING INT32 SP A 10000 Max wait time 100...1800000 ms Settings\Settings\Control\DARREC1
>I(1) BLK_RECL_T
release
Maximum wait
time for
O- Max Thm block
DARREC1 79(1) SET LD0.DARREC1.MaxBlkTmms.setVal ING INT32 SP A 10000 thermal 100...1800000 ms Settings\Settings\Control\DARREC1
>I(1) time
blocking signal
deactivation
Cutout time for
O-
DARREC1 79(1) SET LD0.DARREC1.CutOutTmms.setVal ING INT32 SP A 10000 Cut-out time protection 0...1800000 ms Settings\Settings\Control\DARREC1
>I(1)
coordination
Discrimination
O-
DARREC1 79(1) SET LD0.DARREC1.DsrTmms1.setVal ING INT32 SP A 0 Dsr time shot 1 time for first 0...10000 ms Settings\Settings\Control\DARREC1
>I(1)
reclosing
Discrimination
O-
DARREC1 79(1) SET LD0.DARREC1.DsrTmms2.setVal ING INT32 SP A 0 Dsr time shot 2 time for second 0...10000 ms Settings\Settings\Control\DARREC1
>I(1)
reclosing

195
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Discrimination
O-
DARREC1 79(1) SET LD0.DARREC1.DsrTmms3.setVal ING INT32 SP A 0 Dsr time shot 3 time for third 0...10000 ms Settings\Settings\Control\DARREC1
>I(1)
reclosing
Discrimination
O-
DARREC1 79(1) SET LD0.DARREC1.DsrTmms4.setVal ING INT32 SP A 0 Dsr time shot 4 time for fourth 0...10000 ms Settings\Settings\Control\DARREC1
>I(1)
reclosing
1=None; 2=Low
O- Terminal
DARREC1 79(1) SET LD0.DARREC1.TermPrio.setVal ENG Enum SP B 1 Terminal priority (follower); 3=High Settings\Settings\Control\DARREC1
>I(1) priority
(master)
Selection for
O- Synchronisation synchronizing
DARREC1 79(1) SET LD0.DARREC1.SynSet.setVal ING INT32 SP B 0 0...127 Settings\Settings\Control\DARREC1
>I(1) set requirement for
reclosing
Wait time for
O- reclosing
DARREC1 79(1) SET LD0.DARREC1.AutoWtTmms.setVal ING INT32 SP A 2000 Auto wait time 0...60000 ms Settings\Settings\Control\DARREC1
>I(1) condition
fullfilling
O- Automatic
DARREC1 79(1) SET LD0.DARREC1.AutoLORs.setVal SPG BOOLEAN SP A 1 Auto lockout reset Settings\Settings\Control\DARREC1
>I(1) lockout reset
Protection
O- Protection crd
DARREC1 79(1) SET LD0.DARREC1.ProCrdLim.setVal ING INT32 SP A 1 coordination 1...5 Settings\Settings\Control\DARREC1
>I(1) limit
shot limit
1=No condition; 2=AR
Protection
O- Protection crd inoperative; 3=CB close
DARREC1 79(1) SET LD0.DARREC1.ProCrdMod.setVal ENG Enum SP A 4 coordination Settings\Settings\Control\DARREC1
>I(1) mode manual; 4=AR inop,
mode
CB man; 5=Always
1=Not allowed;
O- Auto initiation 2=When sync fails;
DARREC1 79(1) SET LD0.DARREC1.AutoIniCnd.setVal ENG Enum SP B 2 Auto initiation cnd Settings\Settings\Control\DARREC1
>I(1) condition 3=CB doesn't close;
4=Both
Tripping line,
defines INIT
O- inputs which
DARREC1 79(1) SET LD0.DARREC1.TrLin.setVal ING INT32 SP B 0 Tripping line 0...63 Settings\Settings\Control\DARREC1
>I(1) cause
OPEN_CB
activation
Control line,
defines INIT
O-
DARREC1 79(1) SET LD0.DARREC1.CtlLin.setVal ING INT32 SP A 63 Control line inputs which 0...63 Settings\Settings\Control\DARREC1
>I(1)
are protection
signals
O- Enable shot
DARREC1 79(1) SET LD0.DARREC1.EnaShotJmp.setVal SPG BOOLEAN SP A 1 Enable shot jump Settings\Settings\Control\DARREC1
>I(1) jumping
Circuit breaker
O- CB closed Pos
DARREC1 79(1) SET LD0.DARREC1.CBClsPosSt.setVal SPG BOOLEAN SP A 0 closed position Settings\Settings\Control\DARREC1
>I(1) status
status
Sets 4th delay
O- Fourth delay in
DARREC1 79(1) SET LD0.DARREC1.Ena4DlSOF.setVal SPG BOOLEAN SP B,I 0 into use for all Settings\Settings\Control\DARREC1
>I(1) SOTF
DEL_INIT

196
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

signals during
SOTF
O- Initiation lines
DARREC1 79(1) SET LD0.DARREC1.IniSigCBB1.setVal ING INT32 SP B 0 Init signals CBB1 0...63 Settings\Settings\Control\DARREC1
>I(1) for CBB1
O- Initiation lines
DARREC1 79(1) SET LD0.DARREC1.IniSigCBB2.setVal ING INT32 SP B 0 Init signals CBB2 0...63 Settings\Settings\Control\DARREC1
>I(1) for CBB2
O- Initiation lines
DARREC1 79(1) SET LD0.DARREC1.IniSigCBB3.setVal ING INT32 SP B 0 Init signals CBB3 0...63 Settings\Settings\Control\DARREC1
>I(1) for CBB3
O- Initiation lines
DARREC1 79(1) SET LD0.DARREC1.IniSigCBB4.setVal ING INT32 SP B 0 Init signals CBB4 0...63 Settings\Settings\Control\DARREC1
>I(1) for CBB4
O- Initiation lines
DARREC1 79(1) SET LD0.DARREC1.IniSigCBB5.setVal ING INT32 SP B 0 Init signals CBB5 0...63 Settings\Settings\Control\DARREC1
>I(1) for CBB5
O- Initiation lines
DARREC1 79(1) SET LD0.DARREC1.IniSigCBB6.setVal ING INT32 SP B 0 Init signals CBB6 0...63 Settings\Settings\Control\DARREC1
>I(1) for CBB6
O- Initiation lines
DARREC1 79(1) SET LD0.DARREC1.IniSigCBB7.setVal ING INT32 SP B 0 Init signals CBB7 0...63 Settings\Settings\Control\DARREC1
>I(1) for CBB7
O- Blocking lines
DARREC1 79(1) SET LD0.DARREC1.BlkSigCBB1.setVal ING INT32 SP A 0 Blk signals CBB1 0...63 Settings\Settings\Control\DARREC1
>I(1) for CBB1
O- Blocking lines
DARREC1 79(1) SET LD0.DARREC1.BlkSigCBB2.setVal ING INT32 SP A 0 Blk signals CBB2 0...63 Settings\Settings\Control\DARREC1
>I(1) for CBB2
O- Blocking lines
DARREC1 79(1) SET LD0.DARREC1.BlkSigCBB3.setVal ING INT32 SP A 0 Blk signals CBB3 0...63 Settings\Settings\Control\DARREC1
>I(1) for CBB3
O- Blocking lines
DARREC1 79(1) SET LD0.DARREC1.BlkSigCBB4.setVal ING INT32 SP A 0 Blk signals CBB4 0...63 Settings\Settings\Control\DARREC1
>I(1) for CBB4
O- Blocking lines
DARREC1 79(1) SET LD0.DARREC1.BlkSigCBB5.setVal ING INT32 SP A 0 Blk signals CBB5 0...63 Settings\Settings\Control\DARREC1
>I(1) for CBB5
O- Blocking lines
DARREC1 79(1) SET LD0.DARREC1.BlkSigCBB6.setVal ING INT32 SP A 0 Blk signals CBB6 0...63 Settings\Settings\Control\DARREC1
>I(1) for CBB6
O- Blocking lines
DARREC1 79(1) SET LD0.DARREC1.BlkSigCBB7.setVal ING INT32 SP A 0 Blk signals CBB7 0...63 Settings\Settings\Control\DARREC1
>I(1) for CBB7
O- Shot number Shot number
DARREC1 79(1) SET LD0.DARREC1.ShotNum1.setVal ING INT32 SP B 0 0...5 Settings\Settings\Control\DARREC1
>I(1) CBB1 for CBB1
O- Shot number Shot number
DARREC1 79(1) SET LD0.DARREC1.ShotNum2.setVal ING INT32 SP B 0 0...5 Settings\Settings\Control\DARREC1
>I(1) CBB2 for CBB2
O- Shot number Shot number
DARREC1 79(1) SET LD0.DARREC1.ShotNum3.setVal ING INT32 SP B 0 0...5 Settings\Settings\Control\DARREC1
>I(1) CBB3 for CBB3
O- Shot number Shot number
DARREC1 79(1) SET LD0.DARREC1.ShotNum4.setVal ING INT32 SP B 0 0...5 Settings\Settings\Control\DARREC1
>I(1) CBB4 for CBB4
O- Shot number Shot number
DARREC1 79(1) SET LD0.DARREC1.ShotNum5.setVal ING INT32 SP B 0 0...5 Settings\Settings\Control\DARREC1
>I(1) CBB5 for CBB5
O- Shot number Shot number
DARREC1 79(1) SET LD0.DARREC1.ShotNum6.setVal ING INT32 SP B 0 0...5 Settings\Settings\Control\DARREC1
>I(1) CBB6 for CBB6
O- Shot number Shot number
DARREC1 79(1) SET LD0.DARREC1.ShotNum7.setVal ING INT32 SP B 0 0...5 Settings\Settings\Control\DARREC1
>I(1) CBB7 for CBB7
Delay time for
O-
DARREC1 79(1) SET LD0.DARREC1.Str2Tmms1.setVal ING INT32 SP A 0 Str 2 delay shot 1 start2, 1st 0...300000 ms Settings\Settings\Control\DARREC1
>I(1)
reclose
197
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Delay time for


O-
DARREC1 79(1) SET LD0.DARREC1.Str2Tmms2.setVal ING INT32 SP A 0 Str 2 delay shot 2 start2 2nd 0...300000 ms Settings\Settings\Control\DARREC1
>I(1)
reclose
Delay time for
O-
DARREC1 79(1) SET LD0.DARREC1.Str2Tmms3.setVal ING INT32 SP A 0 Str 2 delay shot 3 start2 3rd 0...300000 ms Settings\Settings\Control\DARREC1
>I(1)
reclose
Delay time for
O-
DARREC1 79(1) SET LD0.DARREC1.Str2Tmms4.setVal ING INT32 SP A 0 Str 2 delay shot 4 start2, 4th 0...300000 ms Settings\Settings\Control\DARREC1
>I(1)
reclose
Delay time for
O-
DARREC1 79(1) SET LD0.DARREC1.Str3Tmms1.setVal ING INT32 SP A 0 Str 3 delay shot 1 start3, 1st 0...300000 ms Settings\Settings\Control\DARREC1
>I(1)
reclose
Delay time for
O-
DARREC1 79(1) SET LD0.DARREC1.Str3Tmms2.setVal ING INT32 SP A 0 Str 3 delay shot 2 start3 2nd 0...300000 ms Settings\Settings\Control\DARREC1
>I(1)
reclose
Delay time for
O-
DARREC1 79(1) SET LD0.DARREC1.Str3Tmms3.setVal ING INT32 SP A 0 Str 3 delay shot 3 start3 3rd 0...300000 ms Settings\Settings\Control\DARREC1
>I(1)
reclose
Delay time for
O-
DARREC1 79(1) SET LD0.DARREC1.Str3Tmms4.setVal ING INT32 SP A 0 Str 3 delay shot 4 start3, 4th 0...300000 ms Settings\Settings\Control\DARREC1
>I(1)
reclose
Delay time for
O-
DARREC1 79(1) SET LD0.DARREC1.Str4Tmms1.setVal ING INT32 SP A 0 Str 4 delay shot 1 start4, 1st 0...300000 ms Settings\Settings\Control\DARREC1
>I(1)
reclose
Delay time for
O-
DARREC1 79(1) SET LD0.DARREC1.Str4Tmms2.setVal ING INT32 SP A 0 Str 4 delay shot 2 start4 2nd 0...300000 ms Settings\Settings\Control\DARREC1
>I(1)
reclose
Delay time for
O-
DARREC1 79(1) SET LD0.DARREC1.Str4Tmms3.setVal ING INT32 SP A 0 Str 4 delay shot 3 start4 3rd 0...300000 ms Settings\Settings\Control\DARREC1
>I(1)
reclose
Delay time for
O-
DARREC1 79(1) SET LD0.DARREC1.Str4Tmms4.setVal ING INT32 SP A 0 Str 4 delay shot 4 start4, 4th 0...300000 ms Settings\Settings\Control\DARREC1
>I(1)
reclose
Frequent
O- Frq Op counter operation
DARREC1 79(1) SET LD0.DARREC1.FrqCntLim.setVal ING INT32 SP B 0 0...250 Settings\Settings\Control\DARREC1
>I(1) limit counter lockout
limit
Frequent
O- Frq Op counter
DARREC1 79(1) SET LD0.DARREC1.FrqCntTmm.setVal ING INT32 SP B 1 operation 1...250 min Settings\Settings\Control\DARREC1
>I(1) time
counter time
Frequent
O- Frq Op recovery operation
DARREC1 79(1) SET LD0.DARREC1.FrqRcvTmm.setVal ING INT32 SP B 1 1...250 min Settings\Settings\Control\DARREC1
>I(1) time counter
recovery time
O- CB close pulse
DARREC1 79(1) SET LD0.DARREC1.PlsTmms.setVal ING INT32 SP B 200 Close pulse time 10...10000 ms Settings\Settings\Control\DARREC1
>I(1) time
Maximum wait
O-
DARREC1 79(1) SET LD0.DARREC1.MaxTrTmms.setVal ING INT32 SP A 10000 Max trip time time for 100...10000 ms Settings\Settings\Control\DARREC1
>I(1)
deactivation of
198
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

protection
signals
0=Reset; 5=Activate
OPEN_CB; 6=Deactive
OPEN_CB; 7=Activate
CLOSE_CB;
8=Deactive
CLOSE_CB;
9=Activate
CMD_WAIT;
10=Deactive
CMD_WAIT;
11=Activate
PROT_CRD;
12=Deactive
O- Test control for PROT_CRD;
DARREC1 79(1) TES LD0.DARREC1.TestCtl.Oper.ctlVal ENC Enum CO B 0 DARREC1 Tests\Function tests\Control
>I(1) outputs 13=Activate INPRO;
14=Deactive INPRO;
15=Activate LOCKED;
16=Deactive LOCKED;
17=Activate
UNSUC_RECL;
18=Deactive
UNSUC_RECL;
19=Activate AR_ON;
20=Deactive AR_ON;
21=Activate READY;
22=Deactive READY;
45=Activate ACTIVE;
46=Deactive ACTIVE
O- VisString255
DARREC1 79(1) VER LD0.DARREC1.NamPlt.swRev LPL DC ED1 F1 (Name plate)
>I(1) (20)

SECRSYN1: Synchrocheck: C1
IEC ANS Categor CD Acces Defaul Even CM Parameter Channel
IEC 61850 IECName Type FC Dataset Parameter name Parameter range Menu path
60617 I y C s t t T desc relation
SECRSYN SYNC(1 (ACT input
25(1) INP Channel U3P1
1 ) channel)
SECRSYN SYNC(1 (ACT input
25(1) INP Channel U3P2
1 ) channel)
Blocking
signal of the
SECRSYN SYNC(1 synchro check Monitoring\I/O
25(1) INP LD0.SECRSYN1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
1 ) and voltage status\Control\SECRSYN1\Inputs
check
function
External
SECRSYN SYNC(1 Monitoring\I/O
25(1) INP LD0.SECRSYN1.ClsRq.stVal SPS BOOLEAN ST B 0 I1 CL_COMMAND closing
1 ) status\Control\SECRSYN1\Inputs
request
199
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Request to
bypass
SECRSYN SYNC(1 Monitoring\I/O
25(1) INP LD0.SECRSYN1.Byps.stVal SPS BOOLEAN ST B 0 I1 BYPASS synchronism
1 ) status\Control\SECRSYN1\Inputs
check and
voltage check
SECRSYN SYNC(1 Systems in Monitoring\I/O
25(1) OUT LD0.SECRSYN1.Rel.stVal SPS BOOLEAN ST B I1 SYNC_OK
1 ) synchronism status\Control\SECRSYN1\Outputs
SECRSYN SYNC(1 StatNrm Synchronizin Monitoring\I/O
25(1) OUT LD0.SECRSYN1.SynPrg.stVal SPC BOOLEAN ST B P,H I1 SYNC_INPRO
1 ) l g in progress status\Control\SECRSYN1\Outputs
SECRSYN SYNC(1 CB closing Monitoring\I/O
25(1) OUT LD0.SECRSYN1.FailCmd.stVal SPS BOOLEAN ST B StatUrg P,H I1 CMD_FAIL_AL
1 ) request failed status\Control\SECRSYN1\Outputs
SECRSYN SYNC(1 CB closing Monitoring\I/O
25(1) OUT LD0.SECRSYN1.FailSyn.stVal SPS BOOLEAN ST B StatUrg P,H I1 CL_FAIL_AL
1 ) failed status\Control\SECRSYN1\Outputs
SECRSYN SYNC(1 Live Line, Monitoring\I/O
25(1) OUT LD0.SECRSYN1.LLDBInd.stVal SPS BOOLEAN ST B I1 LLDB
1 ) Dead Bus status\Control\SECRSYN1\Outputs
SECRSYN SYNC(1 Live Line, Monitoring\I/O
25(1) OUT LD0.SECRSYN1.LLLBInd.stVal SPS BOOLEAN ST B I1 LLLB
1 ) Live Bus status\Control\SECRSYN1\Outputs
SECRSYN SYNC(1 Dead Line, Monitoring\I/O
25(1) OUT LD0.SECRSYN1.DLLBInd.stVal SPS BOOLEAN ST B I1 DLLB
1 ) Live Bus status\Control\SECRSYN1\Outputs
SECRSYN SYNC(1 Dead Line, Monitoring\I/O
25(1) OUT LD0.SECRSYN1.DLDBInd.stVal SPS BOOLEAN ST B I1 DLDB
1 ) Dead Bus status\Control\SECRSYN1\Outputs
1=on;
2=blocked;
SECRSYN SYNC(1
25(1) MON LD0.SECRSYN1.Beh.stVal ENS Enum ST B SECRSYN1 Status 3=test; Monitoring\FB status
1 )
4=test/blocked;
5=off
Voltage
Monitoring\I/O
SECRSYN SYNC(1 difference out
25(1) MON LD0.SECRSYN1.VInd.stVal SPS BOOLEAN ST B I1 U_DIFF_SYNC status\Control\SECRSYN1\Monitore
1 ) of limit for
d data
synchronizing
Phase angle
Monitoring\I/O
SECRSYN SYNC(1 difference out
25(1) MON LD0.SECRSYN1.AngInd.stVal SPS BOOLEAN ST B I1 PH_DIF_SYNC status\Control\SECRSYN1\Monitore
1 ) of limit for
d data
synchronizing
Frequency
Monitoring\I/O
SECRSYN SYNC(1 difference out
25(1) MON LD0.SECRSYN1.HzInd.stVal SPS BOOLEAN ST B I1 FR_DIFF_SYNC status\Control\SECRSYN1\Monitore
1 ) of limit for
d data
synchronizing
Calculated
Monitoring\I/O
SECRSYN SYNC(1 M voltage
25(1) MON LD0.SECRSYN1.DifVClc.mag.f MV FLOAT32 B I1 U_DIFF_MEAS 0.00...1.00 xUn status\Control\SECRSYN1\Monitore
1 ) X amplitude
d data
difference
Calculated
Monitoring\I/O
SECRSYN SYNC(1 M FR_DIFF_MEA voltage 0.000...0.100
25(1) MON LD0.SECRSYN1.DifHzClc.mag.f MV FLOAT32 B I1 status\Control\SECRSYN1\Monitore
1 ) X S frequency xFn
d data
difference
Monitoring\I/O
SECRSYN SYNC(1 M PH_DIFF_MEA Calculated
25(1) MON LD0.SECRSYN1.DifAngClc.mag.f MV FLOAT32 B I1 0.00...180.00 deg status\Control\SECRSYN1\Monitore
1 ) X S voltage phase
d data
200
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

angle
difference
0=Unknown;
1=Both Live;
Energization Monitoring\I/O
SECRSYN SYNC(1 2=Live L, Dead
25(1) MON LD0.SECRSYN1.EnSt.stVal ENS Enum ST B StatUrg P,H I1 ENERG_STATE state of Line status\Control\SECRSYN1\Monitore
1 ) B; 3=Dead L,
and Bus d data
Live B; 4=Both
Dead
SECRSYN SYNC(1 Operation Off Settings\Settings\Control\SECRSYN
25(1) SET LD0.SECRSYN1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off IL1TCTR1
1 ) / On 1
Maximum
SECRSYN SYNC(1 Difference voltage Settings\Settings\Control\SECRSYN
25(1) SET LD0.SECRSYN1.DifV.setMag.f ASG FLOAT32 SG B 0.05 0.01...0.50 xUn
1 ) voltage difference 1
limit
Maximum
SECRSYN SYNC(1 Difference frequency 0.001...0.100 Settings\Settings\Control\SECRSYN
25(1) SET LD0.SECRSYN1.DifHz.setMag.f ASG FLOAT32 SG B 0.001
1 ) frequency difference xFn 1
limit
Maximum
SECRSYN SYNC(1 angle Settings\Settings\Control\SECRSYN
25(1) SET LD0.SECRSYN1.DifAng.setMag.f ASG FLOAT32 SG B 5 Difference angle 5...90 deg
1 ) difference 1
limit
-1=Off; 1=Both
Dead; 2=Live L,
Dead B; 3=Dead
L, Live B;
SECRSYN SYNC(1 EN Energizing Settings\Settings\Control\SECRSYN
25(1) SET LD0.SECRSYN1.LivDeaMod.setVal Enum SG B 1 Live dead mode 4=Dead Bus, L
1 ) G check mode 1
Any; 5=Dead L,
Bus Any; 6=One
Live, Dead;
7=Not Both Live
Voltage low
SECRSYN SYNC(1 limit line for Settings\Settings\Control\SECRSYN UL1TVTR
25(1) SET LD0.SECRSYN1.DeaLinVal.setMag.f ASG FLOAT32 SP B 0.2 Dead line value 0.1...0.8 xUn
1 ) energizing 1 2
check
Voltage high
SECRSYN SYNC(1 limit line for Settings\Settings\Control\SECRSYN UL1TVTR
25(1) SET LD0.SECRSYN1.LivLinVal.setMag.f ASG FLOAT32 SP B 0.8 Live line value 0.2...1.0 xUn
1 ) energizing 1 2
check
Voltage low
SECRSYN SYNC(1 limit bus for Settings\Settings\Control\SECRSYN UL1TVTR
25(1) SET LD0.SECRSYN1.DeaBusVal.setMag.f ASG FLOAT32 SP B 0.2 Dead bus value 0.1...0.8 xUn
1 ) energizing 1 1
check
Voltage high
SECRSYN SYNC(1 limit bus for Settings\Settings\Control\SECRSYN UL1TVTR
25(1) SET LD0.SECRSYN1.LivBusVal.setMag.f ASG FLOAT32 SP B 0.5 Live bus value 0.2...1.0 xUn
1 ) energizing 1 1
check
Breaker
SECRSYN SYNC(1 Settings\Settings\Control\SECRSYN
25(1) SET LD0.SECRSYN1.PlsTmms.setVal ING INT32 SP A 200 Close pulse closing pulse 200...60000 ms
1 ) 1
duration
201
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

SECRSYN SYNC(1 Closing time of Closing time Settings\Settings\Control\SECRSYN


25(1) SET LD0.SECRSYN1.CBTmms.setVal ING INT32 SP A 60 40...250 ms
1 ) CB of the breaker 1
Synchro
1=Off;
SECRSYN SYNC(1 EN Synchro check check Settings\Settings\Control\SECRSYN
25(1) SET LD0.SECRSYN1.OpModSC.setVal Enum SP B 3 2=Synchronous;
1 ) G mode operation 1
3=Asynchronous
mode
Selection of
synchro check
SECRSYN SYNC(1 EN 1=Continuous; Settings\Settings\Control\SECRSYN
25(1) SET LD0.SECRSYN1.OpModCtl.setVal Enum SP A 1 Control mode command or
1 ) G 2=Command 1
Continuous
control mode
Maximum
SECRSYN SYNC(1 Max energizing Settings\Settings\Control\SECRSYN
25(1) SET LD0.SECRSYN1.MaxVEn.setMag.f ASG FLOAT32 SP B 1.05 voltage for 0.50...1.15 xUn
1 ) V 1
energizing
Correction of
phase
difference
SECRSYN SYNC(1 Settings\Settings\Control\SECRSYN
25(1) SET LD0.SECRSYN1.PhSht.setMag.f ASG FLOAT32 SP A 0 Phase shift between -180...180 deg
1 ) 1
measured
U_BUS and
U_LINE
Time delay
SECRSYN SYNC(1 Settings\Settings\Control\SECRSYN
25(1) SET LD0.SECRSYN1.EnTmms.setVal ING INT32 SP A 100 Energizing time for energizing 100...60000 ms
1 ) 1
check
Maximum
SECRSYN SYNC(1 LD0.SECRSYN1.MaxSynTmms.setVa Maximum Syn 100...6000000 Settings\Settings\Control\SECRSYN
25(1) SET ING INT32 SP A 2000 time to accept
1 ) l time ms 1
synchronizing
Minimum
SECRSYN SYNC(1 LD0.SECRSYN1.MinSynTmms.setVa Minimum Syn Settings\Settings\Control\SECRSYN
25(1) SET ING INT32 SP A 0 time to accept 0...60000 ms
1 ) l time 1
synchronizing
SECRSYN SYNC(1 Voltage source Voltage Settings\Settings\Control\SECRSYN
25(1) SET LD0.SECRSYN1.VSrcSw.setVal SPG BOOLEAN SP A 0
1 ) switch source switch 1
0=Reset;
29=Activate
SYNC_INPRO;
30=Deactive
SYNC_INPRO;
31=Activate
SYNC_OK;
32=Deactive
SYNC_OK;
SECRSYN SYNC(1 Test control
25(1) TES LD0.SECRSYN1.TestCtl.Oper.ctlVal ENC Enum CO B 0 SECRSYN1 33=Activate Tests\Function tests\Control
1 ) for outputs
CL_FAIL_AL;
34=Deactive
CL_FAIL_AL;
35=Activate
CMD_FAIL_AL
; 36=Deactive
CMD_FAIL_AL
; 37=Activate
LLDB;
202
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

38=Deactive
LLDB;
39=Activate
LLLB;
40=Deactive
LLLB;
41=Activate
DLLB;
42=Deactive
DLLB;
43=Activate
DLDB;
44=Deactive
DLDB
SECRSYN SYNC(1 VisString25
25(1) VER LD0.SECRSYN1.NamPlt.swRev LPL DC ED1 C1 (Name plate)
1 ) 5 (20)

EFPADM1: Neutral admittance protection: E1


IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
Yo>- (ACT input
EFPADM1 21YN(1) INP Channel URES
>(1) channel)
Yo>- (ACT input
EFPADM1 21YN(1) INP Channel IRES
>(1) channel)
Block signal
Yo>- for activating Monitoring\I/O status\Current
EFPADM1 21YN(1) INP LD0.EFPADM1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
>(1) the blocking protection\EFPADM1\Inputs
mode
External
trigger to
Yo>- Monitoring\I/O status\Current
EFPADM1 21YN(1) INP LD0.EFPADM1.TrgSt.stVal SPS BOOLEAN ST B 0 I1 RELEASE release neutral
>(1) protection\EFPADM1\Inputs
admittance
protection
Yo>- Monitoring\I/O status\Current
EFPADM1 21YN(1) OUT LD0.EFPADM1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start
>(1) protection\EFPADM1\Outputs
Yo>- Monitoring\I/O status\Current
EFPADM1 21YN(1) OUT LD0.EFPADM1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate
>(1) protection\EFPADM1\Outputs
1=on; 2=blocked;
Yo>- 3=test;
EFPADM1 21YN(1) MON LD0.EFPADM1.Beh.stVal ENS Enum ST B EFPADM1 Status Monitoring\FB status
>(1) 4=test/blocked;
5=off
0=unknown; Monitoring\I/O status\Current
Yo>- Detected fault
EFPADM1 21YN(1) MON LD0.EFPADM1.Str.dirGeneral ACD Enum ST B StatNrml P,H FAULT_DIR 1=forward; protection\EFPADM1\Monitored
>(1) direction
2=backward; 3=both data
Ratio of start Monitoring\I/O status\Current
Yo>-
EFPADM1 21YN(1) MON LD0.EFPADM1.StrDur.mag.f MV FLOAT32 MX B START_DUR time / operate 0.00...100.00 % protection\EFPADM1\Monitored
>(1)
time data

203
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Real part of
Monitoring\I/O status\Current
Yo>- calculated -1000.00...1000.00
EFPADM1 21YN(1) MON LD0.EFPADM1.Cond.mag.f MV FLOAT32 MX B I1 COND_RES protection\EFPADM1\Monitored
>(1) neutral mS
data
admittance
Imaginary
part of Monitoring\I/O status\Current
Yo>- -1000.00...1000.00
EFPADM1 21YN(1) MON LD0.EFPADM1.Sus.mag.f MV FLOAT32 MX B I1 SUS_RES calculated protection\EFPADM1\Monitored
>(1) mS
neutral data
admittance
Yo>- Operation Off Settings\Settings\Current
EFPADM1 21YN(1) SET LD0.EFPADM1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
>(1) / On protection\EFPADM1
Yo>- Voltage start Voltage start Settings\Settings\Current
EFPADM1 21YN(1) SET LD0.EFPADM1.VStr.setMag.f ASG FLOAT32 SG B 0.15 0.01...2.00 xUn RESTVTR1
>(1) value value protection\EFPADM1
Yo>- Operate delay Operate delay Settings\Settings\Current
EFPADM1 21YN(1) SET LD0.EFPADM1.OpDlTmms.setVal ING INT32 SG B 60 60...200000 ms
>(1) time time protection\EFPADM1
1=Non-directional;
Yo>- Directional Directional Settings\Settings\Current
EFPADM1 21YN(1) SET LD0.EFPADM1.DirMod.setVal ENG Enum SG B 2 2=Forward;
>(1) mode mode protection\EFPADM1
3=Reverse
Yo>- Reset delay Reset delay Settings\Settings\Current
EFPADM1 21YN(1) SET LD0.EFPADM1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
>(1) time time protection\EFPADM1
1=Yo; 2=Go; 3=Bo;
Yo>- Operation Operation 4=Yo, Go; 5=Yo, Settings\Settings\Current
EFPADM1 21YN(1) SET LD0.EFPADM1.OpModAdm.setVal ENG Enum SG B 1
>(1) mode criteria Bo; 6=Go, Bo; protection\EFPADM1
7=Yo, Go, Bo
Minimum
Yo>- Min operate Settings\Settings\Current
EFPADM1 21YN(1) SET LD0.EFPADM1.BlkValA.setMag.f ASG FLOAT32 SP A 0.01 operating 0.01...1.00 xIn RESTCTR1
>(1) current protection\EFPADM1
current
Minimum
Yo>- Min operate Settings\Settings\Current
EFPADM1 21YN(1) SET LD0.EFPADM1.BlkValV.setMag.f ASG FLOAT32 SP A 0.01 operating 0.01...1.00 xUn RESTVTR1
>(1) voltage protection\EFPADM1
voltage
Tilt angle of
Yo>- Conductance Settings\Settings\Current
EFPADM1 21YN(1) SET LD0.EFPADM1.CondTiltAng.setMag.f ASG FLOAT32 SG ED2,A 0 conductance -30...30 deg
>(1) tilt Ang protection\EFPADM1
boundary line
Tilt angle of
Yo>- Conductance Settings\Settings\Current
EFPADM1 21YN(1) SET LD0.EFPADM1.CondTltAng.setMag.f ASG FLOAT32 SG ED1 0 conductance -30...30 deg
>(1) tilt Ang protection\EFPADM1
boundary line
Conductance
Yo>- Conductance threshold in Settings\Settings\Current
EFPADM1 21YN(1) SET LD0.EFPADM1.CondFwd.setMag.f ASG FLOAT32 SG B 1.00 -500.00...500.00 mS
>(1) forward forward protection\EFPADM1
direction
Conductance
Yo>- Conductance threshold in Settings\Settings\Current
EFPADM1 21YN(1) SET LD0.EFPADM1.CondRv.setMag.f ASG FLOAT32 SG B -1.0 -500.00...500.00 mS
>(1) reverse reverse protection\EFPADM1
direction
Tilt angle of
Yo>- Susceptance Settings\Settings\Current
EFPADM1 21YN(1) SET LD0.EFPADM1.SusTiltAng.setMag.f ASG FLOAT32 SG A 0 susceptance -30...30 deg
>(1) tilt Ang protection\EFPADM1
boundary line
Yo>- Susceptance Susceptance Settings\Settings\Current
EFPADM1 21YN(1) SET LD0.EFPADM1.SusFwd.setMag.f ASG FLOAT32 SG B 1.00 -500.00...500.00 mS
>(1) forward threshold in protection\EFPADM1
204
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

forward
direction
Susceptance
Yo>- Susceptance threshold in Settings\Settings\Current
EFPADM1 21YN(1) SET LD0.EFPADM1.SusRv.setMag.f ASG FLOAT32 SG B -1.00 -500.00...500.00 mS
>(1) reverse reverse protection\EFPADM1
direction
Yo>- Admittance Settings\Settings\Current
EFPADM1 21YN(1) SET LD0.EFPADM1.CirclRd.setMag.f ASG FLOAT32 SG B 1.00 Circle radius 0.05...500.00 mS
>(1) circle radius protection\EFPADM1
Admittance
Yo>- Circle circle Settings\Settings\Current
EFPADM1 21YN(1) SET LD0.EFPADM1.CirclCond.setMag.f ASG FLOAT32 SG B 0.00 -500.00...500.00 mS
>(1) conductance midpoint, protection\EFPADM1
conductance
Admittance
Yo>- Circle circle Settings\Settings\Current
EFPADM1 21YN(1) SET LD0.EFPADM1.CirclSus.setMag.f ASG FLOAT32 SG B 0.00 -500.00...500.00 mS
>(1) susceptance midpoint, protection\EFPADM1
susceptance
Rotate
Yo>- Settings\Settings\Current
EFPADM1 21YN(1) SET LD0.EFPADM1.RevPol.setVal SPG BOOLEAN SP A 0 Pol reversal polarizing
>(1) protection\EFPADM1
quantity
Admittance
Yo>- Admittance Settings\Settings\Current
EFPADM1 21YN(1) SET LD0.EFPADM1.AdmClcMod.setVal ENG Enum SP A 1 calculation 1=Normal; 2=Delta
>(1) Clc mode protection\EFPADM1
mode
0=Reset; 1=Activate
START; 2=Deactive
Yo>- Test control START; 9=Activate Tests\Function tests\Current
EFPADM1 21YN(1) TES LD0.EFPADM1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 EFPADM1
>(1) for outputs OPERATE; protection
10=Deactive
OPERATE
Yo>- VisString255
EFPADM1 21YN(1) VER LD0.EFPADM1.NamPlt.swRev LPL DC E1 (Name plate)
>(1) (20)

MFADPSDE1: Multi-frequency neutral admittance earth-fault protection: C


IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
Io>- (ACT input
MFADPSDE1 67YN(1) INP Channel URES
>Y(1) channel)
Io>- (ACT input
MFADPSDE1 67YN(1) INP Channel IRES
>Y(1) channel)
Block signal
Io>- for activating Monitoring\I/O status\Current
MFADPSDE1 67YN(1) INP LD0.MFADPSDE1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
>Y(1) the blocking protection\MFADPSDE1\Inputs
mode
External
Io>- trigger to Monitoring\I/O status\Current
MFADPSDE1 67YN(1) INP LD0.MFADPSDE1.TrgSt.stVal SPS BOOLEAN ST B 0 I1 RELEASE
>Y(1) release protection\MFADPSDE1\Inputs
neutral

205
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

admittance
protection
External
trigger to Monitoring\I/O status\Current
MFADRDIR1 INP LD0.MFADRDIR1.DirRs.stVal SPC BOOLEAN ST B 0 I1 RESET
reset direction protection\MFADPSDE1\Inputs
calculatio
Io>- Monitoring\I/O status\Current
MFADPSDE1 67YN(1) OUT LD0.MFADPSDE1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start
>Y(1) protection\MFADPSDE1\Outputs
Io>- Monitoring\I/O status\Current
MFADPSDE1 67YN(1) OUT LD0.MFADPSDE1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate
>Y(1) protection\MFADPSDE1\Outputs
Intermittent
Io>- Monitoring\I/O status\Current
MFADPSDE1 67YN(1) OUT LD0.MFADPSDE1.ItmEFInd.stVal SPS BOOLEAN ST B I1 INTR_EF earth-fault
>Y(1) protection\MFADPSDE1\Outputs
indication
Block signal
for EF to
Io>- indicate Monitoring\I/O status\Current
MFADPSDE1 67YN(1) OUT LD0.MFADPSDE1.InhEF.stVal SPS BOOLEAN ST B I1 BLK_EF
>Y(1) opposite protection\MFADPSDE1\Outputs
direction
peaks
Current
Io>- transient Monitoring\I/O status\Current
MFADPSDE1 67YN(1) OUT LD0.MFADPSDE1.PkInd.stVal SPS BOOLEAN ST B I1 PEAK_IND
>Y(1) detection protection\MFADPSDE1\Outputs
indication
1=on;
2=blocked;
Io>-
MFADPSDE1 67YN(1) MON LD0.MFADPSDE1.Beh.stVal ENS Enum ST B MFADPSDE1 Status 3=test; Monitoring\FB status
>Y(1)
4=test/blocked;
5=off
0=unknown;
Monitoring\I/O status\Current
Io>- Detected fault 1=forward;
MFADPSDE1 67YN(1) MON LD0.MFADPSDE1.Str.dirGeneral ACD Enum ST B StatNrml P,H FAULT_DIR protection\MFADPSDE1\Monitored
>Y(1) direction 2=backward;
data
3=both
Ratio of start Monitoring\I/O status\Current
Io>-
MFADPSDE1 67YN(1) MON LD0.MFADPSDE1.StrDur.mag.f MV FLOAT32 MX B START_DUR time / operate 0.00...100.00 % protection\MFADPSDE1\Monitored
>Y(1)
time data
0=unknown;
Monitoring\I/O status\Current
Direction 1=forward;
MFADRDIR1 MON LD0.MFADRDIR1.Dir.dirGeneral ACD Enum ST B DIRECTION protection\MFADPSDE1\Monitored
information 2=backward;
data
3=both
Angle
between Monitoring\I/O status\Current
-180.00...180.00
MFADRDIR1 MON LD0.MFADRDIR1.OpPolAng.mag.f MV FLOAT32 MX B I1 ANGLE polarizing protection\MFADPSDE1\Monitored
deg
and operating data
quantity
Io>- Operation Off Settings\Settings\Current
MFADPSDE1 67YN(1) SET LD0.MFADPSDE1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
>Y(1) / On protection\MFADPSDE1
Io>- Voltage start Voltage start Settings\Settings\Current
MFADPSDE1 67YN(1) SET LD0.MFADPSDE1.GndStr.setMag.f ASG FLOAT32 SG B 0.10 0.01...1.00 xUn RESTVTR1
>Y(1) value value protection\MFADPSDE1

206
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Io>- Start delay Start delay Settings\Settings\Current


MFADPSDE1 67YN(1) SET LD0.MFADPSDE1.StrDlTmms.setVal ING INT32 SP A 30 30...60000 ms
>Y(1) time time protection\MFADPSDE1
Io>- Operate delay Operate delay Settings\Settings\Current
MFADPSDE1 67YN(1) SET LD0.MFADPSDE1.OpDlTmms.setVal ING INT32 SG B 500 60...1200000 ms
>Y(1) time time protection\MFADPSDE1
Io>- Directional Directional 2=Forward; Settings\Settings\Current
MFADPSDE1 67YN(1) SET LD0.MFADPSDE1.DirMod.setVal ENG Enum SG B 2
>Y(1) mode mode 3=Reverse protection\MFADPSDE1
Io>- Reset delay Reset delay Settings\Settings\Current
MFADPSDE1 67YN(1) SET LD0.MFADPSDE1.RsDlTmms.setVal ING INT32 SP A 500 0...60000 ms
>Y(1) time time protection\MFADPSDE1
Peak counter
Io>- Peak counter Settings\Settings\Current
MFADPSDE1 67YN(1) SET LD0.MFADPSDE1.PkCntLim.setVal ING INT32 SP A 2 limit for 2...20
>Y(1) limit protection\MFADPSDE1
restriking EF
1=Intermittent
EF; 2=Transient
Io>- Operation Operation Settings\Settings\Current
MFADPSDE1 67YN(1) SET LD0.MFADPSDE1.OpModTEF.setVal ENG Enum SP B,I 3 EF; 3=General
>Y(1) mode criteria protection\MFADPSDE1
EF; 4=Alarming
EF
Minimum
Min operate Settings\Settings\Current
MFADRDIR1 SET LD0.MFADRDIR1.BlkValA.setMag.f ASG FLOAT32 SG A 0.01 operate 0.005...5.000 xIn RESTCTR1
current protection\MFADPSDE1
current
Rotate
Settings\Settings\Current
MFADRDIR1 SET LD0.MFADRDIR1.RevPol.setVal SPG BOOLEAN SP A 0 Pol reversal polarizing
protection\MFADPSDE1
quantity
Characteristic Settings\Settings\Current
MFADRDIR1 SET LD0.MFADRDIR1.TiltAng.setMag.f ASG FLOAT32 SG A 5 Tilt angle 2.0...20.0 deg
tilt angle protection\MFADPSDE1
Operating 1=Adaptive;
Operating Settings\Settings\Current
MFADRDIR1 SET LD0.MFADRDIR1.OpQtySel.setVal ENG Enum SG A 1 quantity 2=Amplitude;
quantity protection\MFADPSDE1
selection 3=Resistive
0=Reset;
1=Activate
START;
2=Deactive
START;
9=Activate
OPERATE;
10=Deactive
OPERATE;
121=Activate
Io>- Test control Tests\Function tests\Current
MFADPSDE1 67YN(1) TES LD0.MFADPSDE1.TestPro.Oper.ctlVal ENC Enum CO B 0 MFADPSDE1 INTR_EF;
>Y(1) for outputs protection
122=Deactive
INTR_EF;
123=Activate
PEAK_IND;
124=Deactive
PEAK_IND;
23=Activate
BLK_EF;
24=Deactive
BLK_EF
Io>- VisString255
MFADPSDE1 67YN(1) VER LD0.MFADPSDE1.NamPlt.swRev LPL DC ED1 C (Name plate)
>Y(1) (20)
207
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

WPWDE1: Wattmetric directional earth-fault: C1


IEC IEC Parameter Channel
ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Parameter range Menu path
61850 60617 name relation
Po>- (ACT input
WPWDE1 32N(1) INP Channel URES
>(1) channel)
Po>- (ACT input
WPWDE1 32N(1) INP Channel IRES
>(1) channel)
Block signal for
Po>- Monitoring\I/O status\Current
WPWDE1 32N(1) INP LD0.WPSDE1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK activating the
>(1) protection\WPWDE1\Inputs
blocking mode
Relay
Po>- Monitoring\I/O status\Current
WPWDE1 32N(1) INP LD0.WRDIR1.InRcaCtl.stVal SPS BOOLEAN ST B 0 I1 RCA_CTL characteristic
>(1) protection\WPWDE1\Inputs
angle control
Po>- Monitoring\I/O status\Current
WPWDE1 32N(1) OUT LD0.WPSDE1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start
>(1) protection\WPWDE1\Outputs
Po>- Monitoring\I/O status\Current
WPWDE1 32N(1) OUT LD0.WPSDE1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate
>(1) protection\WPWDE1\Outputs
1=on; 2=blocked;
Po>-
WPWDE1 32N(1) MON LD0.WPSDE1.Beh.stVal ENS Enum ST B WPWDE1 Status 3=test; 4=test/blocked; Monitoring\FB status
>(1)
5=off
0=unknown; Monitoring\I/O status\Current
Po>- Detected fault
WPWDE1 32N(1) MON LD0.WPSDE1.Str.dirGeneral ACD Enum ST B StatNrml P,H FAULT_DIR 1=forward; protection\WPWDE1\Monitored
>(1) direction
2=backward; 3=both data
Ratio of start Monitoring\I/O status\Current
Po>-
WPWDE1 32N(1) MON LD0.WPSDE1.StrDur.mag.f MV FLOAT32 MX B START_DUR time / operate 0.00...100.00 % protection\WPWDE1\Monitored
>(1)
time data
0=unknown; Monitoring\I/O status\Current
Po>- Direction
WPWDE1 32N(1) MON LD0.WRDIR1.Dir.dirGeneral ACD Enum ST B DIRECTION 1=forward; protection\WPWDE1\Monitored
>(1) information
2=backward; 3=both data
Angle between
Monitoring\I/O status\Current
Po>- polarizing and
WPWDE1 32N(1) MON LD0.WRDIR1.OpPolAng.mag.f MV FLOAT32 MX B I1 ANGLE -180.00...180.00 deg protection\WPWDE1\Monitored
>(1) operating
data
quantity
Angle between
operating angle Monitoring\I/O status\Current
Po>-
WPWDE1 32N(1) MON LD0.WRDIR1.OpChrAng.mag.f MV FLOAT32 MX B I1 ANGLE_RCA and -180.00...180.00 deg protection\WPWDE1\Monitored
>(1)
characteristic data
angle
Calculated Monitoring\I/O status\Current
Po>- -160.000...160.000
WPWDE1 32N(1) MON LD0.WMMXU1.W.res.cVal.mag.f WYE FLOAT32 MX B I1 RES_POWER residual active protection\WPWDE1\Monitored
>(1) xPn
power data
Po>- Operation Off / Settings\Settings\Current
WPWDE1 32N(1) SET LD0.WPSDE1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off IL1TCTR1
>(1) On protection\WPWDE1
Po>- Voltage start Start value for Settings\Settings\Current
WPWDE1 32N(1) SET LD0.WPSDE1.GndStr.setMag.f ASG FLOAT32 SG B 0.010 0.010...1.000 xUn RESTCTR1
>(1) value residual voltage protection\WPWDE1

208
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Minimum
operate residual
Po>- Current start Settings\Settings\Current
WPWDE1 32N(1) SET LD0.WPSDE1.GndOp.setMag.f ASG FLOAT32 SG B 0.010 current for 0.010...5.000 xIn RESTCTR1
>(1) value protection\WPWDE1
deciding fault
direction
Operate delay
Po>- Operate delay Settings\Settings\Current
WPWDE1 32N(1) SET LD0.WPSDE1.OpDlTmms.setVal ING INT32 SG B 60 time for definite 60...200000 ms
>(1) time protection\WPWDE1
time
Po>- Directional Directional 2=Forward; Settings\Settings\Current
WPWDE1 32N(1) SET LD0.WPSDE1.DirMod.setVal ENG Enum SG B 2
>(1) mode mode 3=Reverse protection\WPWDE1
Start value for
Po>- Power start Settings\Settings\Current
WPWDE1 32N(1) SET LD0.WPSDE1.StrVal.setMag.f ASG FLOAT32 SG B 0.003 residual active 0.003...1.000 xPn
>(1) value protection\WPWDE1
power
Selection of 5=ANSI Def. Time;
Po>- Operating Settings\Settings\Current
WPWDE1 32N(1) SET LD0.WPSDE1.TmACrv.setCharact CURVE Enum SG B 15 time delay curve 15=IEC Def. Time;
>(1) curve type protection\WPWDE1
type 20=Wattmetric IDMT
Time multiplier
Po>- Time Settings\Settings\Current
WPWDE1 32N(1) SET LD0.WPSDE1.TmMult.setMag.f ASG FLOAT32 SG B 1 for Wattmetric 0.025...2.00
>(1) multiplier protection\WPWDE1
IDMT curves
Po>- Reset delay Settings\Settings\Current
WPWDE1 32N(1) SET LD0.WPSDE1.RsDlTmms.setVal ING INT32 SP A 20 Reset delay time 0...60000 ms
>(1) time protection\WPWDE1
Reference value
of residual
Po>- Reference Settings\Settings\Current
WPWDE1 32N(1) SET LD0.WPSDE1.RefW.setMag.f ASG FLOAT32 SG B 0.150 power for 0.050...1.000 xPn
>(1) power protection\WPWDE1
Wattmetric
IDMT curves
Selects used
Po>- Measurement current 1=RMS; 2=DFT; Settings\Settings\Current
WPWDE1 32N(1) SET LD0.WPSDE1.AMeasMod.setVal ENG Enum SP A 2
>(1) mode measurement 3=Peak-to-Peak protection\WPWDE1
mode
Po>- Characteristic Characteristic Settings\Settings\Current
WPWDE1 32N(1) SET LD0.WRDIR1.ChrAng.setMag.f ASG FLOAT32 SG B -90 -179...180 deg
>(1) angle angle protection\WPWDE1
Minimum
Po>- Min operate Settings\Settings\Current
WPWDE1 32N(1) SET LD0.WRDIR1.BlkValA.setMag.f ASG FLOAT32 SP A 0.010 operating 0.010...1.000 xIn RESTCTR1
>(1) current protection\WPWDE1
current
Minimum
Po>- Min operate Settings\Settings\Current
WPWDE1 32N(1) SET LD0.WRDIR1.BlkValV.setMag.f ASG FLOAT32 SP A 0.01 operating 0.01...1.00 xUn RESTCTR1
>(1) voltage protection\WPWDE1
voltage
Po>- Correction Settings\Settings\Current
WPWDE1 32N(1) SET LD0.WRDIR1.CorAng.setMag.f ASG FLOAT32 SP A 2.0 Angle correction 0.0...10.0 deg
>(1) angle protection\WPWDE1
Rotate
Po>- Settings\Settings\Current
WPWDE1 32N(1) SET LD0.WRDIR1.RevPol.setVal SPG BOOLEAN SP A 0 Pol reversal polarizing
>(1) protection\WPWDE1
quantity
0=Reset; 1=Activate
START; 2=Deactive
Po>- Test control for START; 9=Activate Tests\Function tests\Current
WPWDE1 32N(1) TES LD0.WPSDE1.TestPro.Oper.ctlVal ENC Enum CO B 0 WPWDE1
>(1) outputs OPERATE; protection
10=Deactive
OPERATE
209
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Po>- VisString255
WPWDE1 32N(1) VER LD0.WPSDE1.NamPlt.swRev LPL DC ED1 C1 (Name plate)
>(1) (20)

INTRPTEF1: Intermittent earth fault protection: E1


IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
Io>- (ACT input
INTRPTEF1 67NIEF(1) INP Channel URES
>IEF(1) channel)
Io>- (ACT input
INTRPTEF1 67NIEF(1) INP Channel IRES
>IEF(1) channel)
Block
signal for
Io>- Monitoring\I/O status\Current
INTRPTEF1 67NIEF(1) INP LD0.INTRPTEF1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK activating
>IEF(1) protection\INTRPTEF1\Inputs
the blocking
mode
Io>- Monitoring\I/O status\Current
INTRPTEF1 67NIEF(1) OUT LD0.INTRPTEF1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start
>IEF(1) protection\INTRPTEF1\Outputs
Io>- Monitoring\I/O status\Current
INTRPTEF1 67NIEF(1) OUT LD0.INTRPTEF1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate
>IEF(1) protection\INTRPTEF1\Outputs
Block
signal for
EF to
Io>- Monitoring\I/O status\Current
INTRPTEF1 67NIEF(1) OUT LD0.INTRPTEF1.InhEF.stVal SPS BOOLEAN ST B I1 BLK_EF indicate
>IEF(1) protection\INTRPTEF1\Outputs
opposite
direction
peaks
1=on;
2=blocked;
Io>-
INTRPTEF1 67NIEF(1) MON LD0.INTRPTEF1.Beh.stVal ENS Enum ST B INTRPTEF1 Status 3=test; Monitoring\FB status
>IEF(1)
4=test/blocked;
5=off
0=unknown;
Detected Monitoring\I/O status\Current
Io>- 1=forward;
INTRPTEF1 67NIEF(1) MON LD0.INTRPTEF1.Str.dirGeneral ACD Enum ST B StatNrml P,H FAULT_DIR fault protection\INTRPTEF1\Monitored
>IEF(1) 2=backward;
direction data
3=both
Ratio of Monitoring\I/O status\Current
Io>-
INTRPTEF1 67NIEF(1) MON LD0.INTRPTEF1.StrDur.mag.f MV FLOAT32 MX B START_DUR start time / 0.00...100.00 % protection\INTRPTEF1\Monitored
>IEF(1)
operate time data
Io>- Operation Settings\Settings\Current
INTRPTEF1 67NIEF(1) SET LD0.INTRPTEF1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
>IEF(1) Off / On protection\INTRPTEF1
Io>- Voltage start Voltage Settings\Settings\Current
INTRPTEF1 67NIEF(1) SET LD0.INTRPTEF1.GndStr.setMag.f ASG FLOAT32 SG B 0.20 0.05...0.50 xUn RESTVTR1
>IEF(1) value start value protection\INTRPTEF1
1=Non-
Io>- Directional Directional directional; Settings\Settings\Current
INTRPTEF1 67NIEF(1) SET LD0.INTRPTEF1.DirMod.setVal ENG Enum SG B 2
>IEF(1) mode mode 2=Forward; protection\INTRPTEF1
3=Reverse

210
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Io>- Operate delay Operate Settings\Settings\Current


INTRPTEF1 67NIEF(1) SET LD0.INTRPTEF1.OpDlTmms.setVal ING INT32 SG B 500 40...1200000 ms
>IEF(1) time delay time protection\INTRPTEF1
Io>- Reset delay Reset delay Settings\Settings\Current
INTRPTEF1 67NIEF(1) SET LD0.INTRPTEF1.RsDlTmms.setVal ING INT32 SP A 500 40...60000 ms
>IEF(1) time time protection\INTRPTEF1
Minimum
operating
Io>- Min operate Settings\Settings\Current
INTRPTEF1 67NIEF(1) SET LD0.INTRPTEF1.BlkValA.setMag.f ASG FLOAT32 SP A 0.01 current for 0.01...1.00 xIn RESTCTR1
>IEF(1) current protection\INTRPTEF1
transient
detector
Min
requirement
Io>- Peak counter for peak Settings\Settings\Current
INTRPTEF1 67NIEF(1) SET LD0.INTRPTEF1.PkCntLim.setVal ING INT32 SP A 2 2...20
>IEF(1) limit counter protection\INTRPTEF1
before start
in IEF mode
1=Intermittent
Io>- Operation Operation Settings\Settings\Current
INTRPTEF1 67NIEF(1) SET LD0.INTRPTEF1.OpModTEF.setVal ENG Enum SP B 1 EF; 2=Transient
>IEF(1) mode criteria protection\INTRPTEF1
EF
0=Reset;
1=Activate
START;
2=Deactive
START;
9=Activate
Io>- Test control Tests\Function tests\Current
INTRPTEF1 67NIEF(1) TES LD0.INTRPTEF1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 INTRPTEF1 OPERATE;
>IEF(1) for outputs protection
10=Deactive
OPERATE;
31=Activate
BLK_EF;
32=Deactive
BLK_EF
Io>- VisString255 (Name
INTRPTEF1 67NIEF(1) VER LD0.INTRPTEF1.NamPlt.swRev LPL DC ED1 E1
>IEF(1) (20) plate)

SCEFRFLO1: Fault locator: B1


Channe
IEC Categor Acces Defaul Even CM
IEC 61850 ANSI IECName CDC Type FC Dataset Parameter name Parameter desc Parameter range Menu path l
60617 y s t t T
relation
SCEFRFLO FLOC(1 21FL(1 (ACT input
INP Channel U3P
1 ) ) channel)
SCEFRFLO FLOC(1 21FL(1 (ACT input
INP Channel I3P
1 ) ) channel)
SCEFRFLO FLOC(1 21FL(1 (ACT input
INP Channel URES
1 ) ) channel)
Signal for
SCEFRFLO FLOC(1 21FL(1 Monitoring\I/O status\Other
INP LD0.SCEFRFLO1.RcdBlk.stVal SPS BOOLEAN ST B 0 I1 BLOCK blocking the
1 ) ) protection\SCEFRFLO1\Inputs
triggering

211
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Distance
SCEFRFLO FLOC(1 21FL(1 calculation Monitoring\I/O status\Other
INP LD0.SCEFRFLO1.Trg.stVal SPC BOOLEAN ST B 0 I1 TRIGG
1 ) ) triggering protection\SCEFRFLO1\Inputs
signal
XC0F
SCEFRFLO FLOC(1 21FL(1 calculation Monitoring\I/O status\Other
INP LD0.SCEFRFLO1.TrgXC0F.stVal SPC BOOLEAN ST B 0 I1 TRIGG_XC0F
1 ) ) triggering protection\SCEFRFLO1\Inputs
signal
SCEFRFLO FLOC(1 21FL(1 StatNrm Fault location Monitoring\I/O status\Other
OUT LD0.SCEFRFLO1.Alm.stVal SPS BOOLEAN ST B P,H I1 ALARM
1 ) ) l alarm signal protection\SCEFRFLO1\Outputs
(Triggering
SCEFRFLO FLOC(1 21FL(1 signal for
CTR LD0.SCEFRFLO1.Trg.Oper.ctlVal SPC BOOLEAN CO I1
1 ) ) distance
calculation)
(Triggering
SCEFRFLO FLOC(1 21FL(1 signal for
CTR LD0.SCEFRFLO1.TrgXC0F.Oper.ctlVal SPC BOOLEAN CO I1
1 ) ) XC0F
calculation)
SCEFRFLO1
SCEFRFLO FLOC(1 21FL(1 SCEFRFLO1 0=Cancel;
CTR LD0.SCEFRFLO1.RcdRs.Oper.ctlVal SPC BOOLEAN CO B 0 I1 recorded data Clear\Clear
1 ) ) reset 1=Clear
reset
1=on;
2=blocked;
SCEFRFLO FLOC(1 21FL(1
MON LD0.SCEFRFLO1.Beh.stVal ENS Enum ST B SCEFRFLO1 Status 3=test; Monitoring\FB status
1 ) )
4=test/blocked;
5=off
Fault distance
Monitoring\I/O status\Other
SCEFRFLO FLOC(1 21FL(1 M FLT_DISTANC in units 0.00...3000.00
MON LD0.SCEFRFLO1.FltDiskm.mag.f MV FLOAT32 B I1 protection\SCEFRFLO1\Monitore
1 ) ) X E selected by the pu
d data
user
1=AG Fault;
2=BG Fault;
3=CG Fault;
Monitoring\I/O status\Other
SCEFRFLO FLOC(1 21FL(1 Fault 4=AB Fault;
MON LD0.SCEFRFLO1.FltLoop.stVal ENS Enum ST B I1 FAULT_LOOP protection\SCEFRFLO1\Monitore
1 ) ) impedance loop 5=BC Fault;
d data
6=CA Fault;
7=ABC Fault; -
5=No fault
Fault point Monitoring\I/O status\Other
SCEFRFLO FLOC(1 21FL(1 M 0.0...1000000.0
MON LD0.SCEFRFLO1.FltPtR.mag.f MV FLOAT32 B I1 RF resistance in protection\SCEFRFLO1\Monitore
1 ) ) X ohm
primary ohms d data
Fault loop Monitoring\I/O status\Other
SCEFRFLO FLOC(1 21FL(1 M 0.0...1000000.0
MON LD0.SCEFRFLO1.FltR.mag.f MV FLOAT32 B I1 RFLOOP resistance in protection\SCEFRFLO1\Monitore
1 ) ) X ohm
primary ohms d data
Fault loop Monitoring\I/O status\Other
SCEFRFLO FLOC(1 21FL(1 M 0.0...1000000.0
MON LD0.SCEFRFLO1.FltX.mag.f MV FLOAT32 B I1 XFLOOP reactance in protection\SCEFRFLO1\Monitore
1 ) ) X ohm
primary ohms d data
Monitoring\I/O status\Other
SCEFRFLO FLOC(1 21FL(1 M Positive 0.0...1000000.0
MON LD0.SCEFRFLO1.PhReact.mag.f MV FLOAT32 B I1 XFPHASE protection\SCEFRFLO1\Monitore
1 ) ) X sequence fault ohm
d data
212
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

reactance in
primary ohms
Monitoring\I/O status\Other
SCEFRFLO FLOC(1 21FL(1 M Fault to load
MON LD0.SCEFRFLO1.RatFltALod.mag.f MV FLOAT32 B I1 IFLT_PER_ILD 0.00...60000.00 protection\SCEFRFLO1\Monitore
1 ) ) X current ratio
d data
Estimated Monitoring\I/O status\Other
SCEFRFLO FLOC(1 21FL(1 M
MON LD0.SCEFRFLO1.EqDisLod.mag.f MV FLOAT32 B I1 S_CALC equivalent load 0.00...1.00 protection\SCEFRFLO1\Monitore
1 ) ) X
distance d data
Estimated PhE
Monitoring\I/O status\Other
SCEFRFLO FLOC(1 21FL(1 M capacitive 0.0...1000000.0
MON LD0.SCEFRFLO1.PhGndCapac.mag.f MV FLOAT32 B I1 XC0F_CALC protection\SCEFRFLO1\Monitore
1 ) ) X reactance of ohm
d data
line
Monitoring\I/O status\Other
SCEFRFLO FLOC(1 21FL(1 Fault distance
MON LD0.SCEFRFLO1.FltDisQ.stVal INS INT32 ST B I1 FLT_DIST_Q 0...511 protection\SCEFRFLO1\Monitore
1 ) ) quality
d data
1=AG Fault;
2=BG Fault;
3=CG Fault;
SCEFRFLO FLOC(1 21FL(1 4=AB Fault; Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.FltLoop.stVal ENS Enum ST B I1 Flt loop Fault loop
1 ) ) 5=BC Fault; protection\SCEFRFLO1
6=CA Fault;
7=ABC Fault; -
5=No fault
SCEFRFLO FLOC(1 21FL(1 M 0.00...3000.00 Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.FltDiskm.mag.f MV FLOAT32 B I1 Flt distance Fault distance
1 ) ) X pu protection\SCEFRFLO1
SCEFRFLO FLOC(1 21FL(1 M Estimate Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.FltDiskm.t MV Timestamp B Triggering time
1 ) ) X triggering time protection\SCEFRFLO1
SCEFRFLO FLOC(1 21FL(1 M Flt point 0.0...1000000.0 Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.FltPtR.mag.f MV FLOAT32 B I1 Fault resistance
1 ) ) X resistance ohm protection\SCEFRFLO1
SCEFRFLO FLOC(1 21FL(1 Fault distance Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.FltDisQ.stVal INS INT32 ST B I1 Flt Dist quality 0...511
1 ) ) quality protection\SCEFRFLO1
SCEFRFLO FLOC(1 21FL(1 M Flt loop Fault loop 0.0...1000000.0 Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.FltR.mag.f MV FLOAT32 B I1
1 ) ) X resistance resistance ohm protection\SCEFRFLO1
SCEFRFLO FLOC(1 21FL(1 M Flt loop Fault loop 0.0...1000000.0 Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.FltX.mag.f MV FLOAT32 B I1
1 ) ) X reactance reactance ohm protection\SCEFRFLO1
SCEFRFLO FLOC(1 21FL(1 M Flt phase Fault phase 0.0...1000000.0 Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.PhReact.mag.f MV FLOAT32 B I1
1 ) ) X reactance reactance ohm protection\SCEFRFLO1
SCEFRFLO FLOC(1 21FL(1 M Flt to Lod Cur Fault to load Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.RatFltALod.mag.f MV FLOAT32 B I1 0.00...60000.00
1 ) ) X ratio current ratio protection\SCEFRFLO1
Estimated
SCEFRFLO FLOC(1 21FL(1 M Equivalent load Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.EqDisLod.mag.f MV FLOAT32 B I1 equivalent load 0.00...1.00
1 ) ) X Dis protection\SCEFRFLO1
distance
Estimated PhE
SCEFRFLO FLOC(1 21FL(1 M capacitive 0.0...1000000.0 Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.PhGndCapac.mag.f MV FLOAT32 B I1 XC0F Calc
1 ) ) X reactance of the ohm protection\SCEFRFLO1
line
Pre-fault
SCEFRFLO FLOC(1 21FL(1 LD0.FLO1RFRC1.APreFltPhA.cVal.mag. CM M A Pre Flt Phs A Monitoring\Recorded data\Other
MON FLOAT32 B I1 current phase 0.00...40.00 xIn
1 ) ) f V X Magn protection\SCEFRFLO1
A, magnitude
213
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Pre-fault
SCEFRFLO FLOC(1 21FL(1 LD0.FLO1RFRC1.APreFltPhA.cVal.ang. CM M A Pre Flt Phs A -180.00...180.00 Monitoring\Recorded data\Other
MON FLOAT32 B current phase
1 ) ) f V X Angl deg protection\SCEFRFLO1
A, angle
SCEFRFLO FLOC(1 21FL(1 CM M Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.APreFltPhA.t Timestamp B Pre fault time Pre-fault time
1 ) ) V X protection\SCEFRFLO1
Pre-fault
SCEFRFLO FLOC(1 21FL(1 LD0.FLO1RFRC1.APreFltPhB.cVal.mag. CM M A Pre Flt Phs B Monitoring\Recorded data\Other
MON FLOAT32 B I1 current phase 0.00...40.00 xIn
1 ) ) f V X Magn protection\SCEFRFLO1
B, magnitude
Pre-fault
SCEFRFLO FLOC(1 21FL(1 CM M A Pre Flt Phs B -180.00...180.00 Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.APreFltPhB.cVal.ang.f FLOAT32 B current phase
1 ) ) V X Angl deg protection\SCEFRFLO1
B, angle
Pre-fault
SCEFRFLO FLOC(1 21FL(1 LD0.FLO1RFRC1.APreFltPhC.cVal.mag. CM M A Pre Flt Phs C Monitoring\Recorded data\Other
MON FLOAT32 B I1 current phase 0.00...40.00 xIn
1 ) ) f V X Magn protection\SCEFRFLO1
C, magnitude
Pre-fault
SCEFRFLO FLOC(1 21FL(1 CM M A Pre Flt Phs C -180.00...180.00 Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.APreFltPhC.cVal.ang.f FLOAT32 B current phase
1 ) ) V X Angl deg protection\SCEFRFLO1
C, angle
Pre-fault
SCEFRFLO FLOC(1 21FL(1 LD0.FLO1RFRC1.VPreFltPhA.cVal.mag. CM M V Pre Flt Phs A Monitoring\Recorded data\Other
MON FLOAT32 B I1 voltage phase 0.00...40.00 xIn
1 ) ) f V X Magn protection\SCEFRFLO1
A, magnitude
Pre-fault
SCEFRFLO FLOC(1 21FL(1 LD0.FLO1RFRC1.VPreFltPhA.cVal.ang. CM M V Pre Flt Phs A -180.00...180.00 Monitoring\Recorded data\Other
MON FLOAT32 B voltage phase
1 ) ) f V X Angl deg protection\SCEFRFLO1
A, angle
Pre-fault
SCEFRFLO FLOC(1 21FL(1 LD0.FLO1RFRC1.VPreFltPhB.cVal.mag. CM M V Pre Flt Phs B Monitoring\Recorded data\Other
MON FLOAT32 B I1 voltage phase 0.00...40.00 xIn
1 ) ) f V X Magn protection\SCEFRFLO1
B, magnitude
Pre-fault
SCEFRFLO FLOC(1 21FL(1 CM M V Pre Flt Phs B -180.00...180.00 Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.VPreFltPhB.cVal.ang.f FLOAT32 B voltage phase
1 ) ) V X Angl deg protection\SCEFRFLO1
B, angle
Pre-fault
SCEFRFLO FLOC(1 21FL(1 LD0.FLO1RFRC1.VPreFltPhC.cVal.mag. CM M V Pre Flt Phs C Monitoring\Recorded data\Other
MON FLOAT32 B I1 voltage phase 0.00...40.00 xIn
1 ) ) f V X Magn protection\SCEFRFLO1
C, magnitude
Pre-fault
SCEFRFLO FLOC(1 21FL(1 CM M V Pre Flt Phs C -180.00...180.00 Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.VPreFltPhC.cVal.ang.f FLOAT32 B voltage phase
1 ) ) V X Angl deg protection\SCEFRFLO1
C, angle
Fault current
SCEFRFLO FLOC(1 21FL(1 CM M A Flt Phs A Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.AFltPhA.cVal.mag.f FLOAT32 B I1 phase A, 0.00...40.00 xIn
1 ) ) V X Magn protection\SCEFRFLO1
magnitude
SCEFRFLO FLOC(1 21FL(1 CM M A Flt Phs A Fault current -180.00...180.00 Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.AFltPhA.cVal.ang.f FLOAT32 B
1 ) ) V X angle phase A, angle deg protection\SCEFRFLO1
Fault current
SCEFRFLO FLOC(1 21FL(1 CM M A Flt Phs B Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.AFltPhB.cVal.mag.f FLOAT32 B I1 phase B, 0.00...40.00 xIn
1 ) ) V X Magn protection\SCEFRFLO1
magnitude
SCEFRFLO FLOC(1 21FL(1 CM M A Flt Phs B Fault current -180.00...180.00 Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.AFltPhB.cVal.ang.f FLOAT32 B
1 ) ) V X angle phase B, angle deg protection\SCEFRFLO1
Fault current
SCEFRFLO FLOC(1 21FL(1 CM M A Flt Phs C Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.AFltPhC.cVal.mag.f FLOAT32 B I1 phase C, 0.00...40.00 xIn
1 ) ) V X Magn protection\SCEFRFLO1
magnitude

214
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

SCEFRFLO FLOC(1 21FL(1 CM M A Flt Phs C Fault current -180.00...180.00 Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.AFltPhC.cVal.ang.f FLOAT32 B
1 ) ) V X angle phase C, angle deg protection\SCEFRFLO1
Fault voltage
SCEFRFLO FLOC(1 21FL(1 CM M V Flt Phs A Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.VFltPhA.cVal.mag.f FLOAT32 B I1 phase A, 0.00...40.00 xIn
1 ) ) V X Magn protection\SCEFRFLO1
magnitude
SCEFRFLO FLOC(1 21FL(1 CM M V Flt Phs A Fault voltage -180.00...180.00 Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.VFltPhA.cVal.ang.f FLOAT32 B
1 ) ) V X angle phase A, angle deg protection\SCEFRFLO1
Fault voltage
SCEFRFLO FLOC(1 21FL(1 CM M V Flt Phs B Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.VFltPhB.cVal.mag.f FLOAT32 B I1 phase B, 0.00...40.00 xIn
1 ) ) V X Magn protection\SCEFRFLO1
magnitude
SCEFRFLO FLOC(1 21FL(1 CM M V Flt Phs B Fault voltage -180.00...180.00 Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.VFltPhB.cVal.ang.f FLOAT32 B
1 ) ) V X angle phase B, angle deg protection\SCEFRFLO1
Fault voltage
SCEFRFLO FLOC(1 21FL(1 CM M V Flt Phs C Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.VFltPhC.cVal.mag.f FLOAT32 B I1 phase C, 0.00...40.00 xIn
1 ) ) V X Magn protection\SCEFRFLO1
magnitude
SCEFRFLO FLOC(1 21FL(1 CM M V Flt Phs C Fault voltage -180.00...180.00 Monitoring\Recorded data\Other
MON LD0.FLO1RFRC1.VFltPhC.cVal.ang.f FLOAT32 B
1 ) ) V X angle phase C, angle deg protection\SCEFRFLO1
SCEFRFLO FLOC(1 21FL(1 Operation Off / Settings\Settings\Other
SET LD0.SCEFRFLO1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
1 ) ) On protection\SCEFRFLO1
Impedance per
phase of max.
SCEFRFLO FLOC(1 21FL(1 Z Max phase 1.0...10000.0 Settings\Settings\Other
SET LD0.SCEFRFLO1.ZMaxLod.setMag.f ASG FLOAT32 SG B 80.0 load,
1 ) ) load ohm protection\SCEFRFLO1
overcurr./under
-imp., PSL
Line PhE
SCEFRFLO FLOC(1 21FL(1 21000 leakage 20...1000000 Settings\Settings\Other
SET LD0.SCEFRFLO1.PhLeakRis.setMag.f ASG FLOAT32 SG B Ph leakage Ris
1 ) ) 0 resistance in ohm protection\SCEFRFLO1
primary ohms
Line PhE
SCEFRFLO FLOC(1 21FL(1 Ph capacitive capacitive 10...1000000 Settings\Settings\Other
SET LD0.SCEFRFLO1.PhLinCapac.setMag.f ASG FLOAT32 SG B 7000
1 ) ) React reactance in ohm protection\SCEFRFLO1
primary ohms
Equivalent load
distance when
SCEFRFLO FLOC(1 21FL(1 Equivalent load Settings\Settings\Other
SET LD0.SCEFRFLO1.EqLodDis.setMag.f ASG FLOAT32 SG A 0.50 EF algorithm 0.00...1.00
1 ) ) Dis protection\SCEFRFLO1
equals to load
modelling
Trigger mode
SCEFRFLO FLOC(1 21FL(1 Calculation Trg 1=Internal; Settings\Settings\Other
SET LD0.SCEFRFLO1.TrgMod.setVal ENG Enum SP B 2 for distance
1 ) ) mode 2=External protection\SCEFRFLO1
calculation
High alarm
SCEFRFLO FLOC(1 21FL(1 High alarm Dis limit for Settings\Settings\Other
SET LD0.SCEFRFLO1.HiLimSpt.setMag.f ASG FLOAT32 SG A 0.000 0.000...1.000 pu
1 ) ) limit calculated protection\SCEFRFLO1
distance
Low alarm
SCEFRFLO FLOC(1 21FL(1 Low alarm Dis limit for Settings\Settings\Other
SET LD0.SCEFRFLO1.LoLimSpt.setMag.f ASG FLOAT32 SG A 0.000 0.000...1.000 pu
1 ) ) limit calculated protection\SCEFRFLO1
distance

215
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Selection for 1=Load


SCEFRFLO FLOC(1 21FL(1 PhE-loop compensation; Settings\Settings\Other
SET LD0.SCEFRFLO1.EFAlgSel.setVal ENG Enum SP A 1 EF algorithm Sel
1 ) ) calculation 2=Load protection\SCEFRFLO1
algorithm modelling
Selection for
SCEFRFLO FLOC(1 21FL(1 EF algorithm Cur 1=Io based; Settings\Settings\Other
SET LD0.SCEFRFLO1.EFAlgASel.setVal ENG Enum SP A 1 earth-fault
1 ) ) Sel 2=I2 based protection\SCEFRFLO1
current model
Enable load
SCEFRFLO FLOC(1 21FL(1 Load Com PP 0=Disabled; Settings\Settings\Other
SET LD0.SCEFRFLO1.EnaLodComp.setVal SPG BOOLEAN SP A 1 compensation
1 ) ) loops 1=Enabled protection\SCEFRFLO1
for PP/3P-loops
Enable calc.
without
SCEFRFLO FLOC(1 21FL(1 Enable simple 0=Disabled; Settings\Settings\Other
SET LD0.SCEFRFLO1.SimpMod.setVal SPG BOOLEAN SP A 0 impedance
1 ) ) model 1=Enabled protection\SCEFRFLO1
settings for
PP/3P-loops
Allowed
variation of
SCEFRFLO FLOC(1 21FL(1 Distance estimate Settings\Settings\Other
SET LD0.SCEFRFLO1.DisEstVa.setMag.f ASG FLOAT32 SP A 0.015 short circuit 0.001...0.300
1 ) ) Va protection\SCEFRFLO1
distance
estimate
Phase voltage 1=Accurate;
SCEFRFLO FLOC(1 21FL(1 Phase voltage Settings\Settings\Other
SET LD0.SCEFRFLO1.PhVMeas.setVal ENG Enum SP B 1 measurement 2=Ph-to-ph
1 ) ) Meas protection\SCEFRFLO1
principle without Uo
SCEFRFLO FLOC(1 21FL(1 Line Len section Line length, 0.000...1000.00 Settings\Settings\Other
SET LD0.SCEF1ZLIN1.LinLenkm.setMag.f ASG FLOAT32 SG B 0.000
1 ) ) A section A 0 pu protection\SCEFRFLO1
Positive
SCEFRFLO FLOC(1 21FL(1 sequence line 0.000...1000.00 Settings\Settings\Other
SET LD0.SCEF1ZLIN1.RPs.setMag.f ASG FLOAT32 SG B 1.000 R1 line section A
1 ) ) resistance, line 0 ohm / pu protection\SCEFRFLO1
section A
Positive
SCEFRFLO FLOC(1 21FL(1 sequence line 0.000...1000.00 Settings\Settings\Other
SET LD0.SCEF1ZLIN1.XPs.setMag.f ASG FLOAT32 SG B 1.000 X1 line section A
1 ) ) reactance, line 0 ohm / pu protection\SCEFRFLO1
section A
Zero sequence
SCEFRFLO FLOC(1 21FL(1 0.000...1000.00 Settings\Settings\Other
SET LD0.SCEF1ZLIN1.RZer.setMag.f ASG FLOAT32 SG B 4.000 R0 line section A line resistance,
1 ) ) 0 ohm / pu protection\SCEFRFLO1
line section A
Zero sequence
SCEFRFLO FLOC(1 21FL(1 0.000...1000.00 Settings\Settings\Other
SET LD0.SCEF1ZLIN1.XZer.setMag.f ASG FLOAT32 SG B 4.000 X0 line section A line reactance,
1 ) ) 0 ohm / pu protection\SCEFRFLO1
line section A
SCEFRFLO FLOC(1 21FL(1 Line Len section Line length, 0.000...1000.00 Settings\Settings\Other
SET LD0.SCEF2ZLIN1.LinLenkm.setMag.f ASG FLOAT32 SG A 0.000
1 ) ) B section B 0 pu protection\SCEFRFLO1
Positive
SCEFRFLO FLOC(1 21FL(1 sequence line 0.000...1000.00 Settings\Settings\Other
SET LD0.SCEF2ZLIN1.RPs.setMag.f ASG FLOAT32 SG A 1.000 R1 line section B
1 ) ) resistance, line 0 ohm / pu protection\SCEFRFLO1
section B
Positive
SCEFRFLO FLOC(1 21FL(1 sequence line 0.000...1000.00 Settings\Settings\Other
SET LD0.SCEF2ZLIN1.XPs.setMag.f ASG FLOAT32 SG A 1.000 X1 line section B
1 ) ) reactance, line 0 ohm / pu protection\SCEFRFLO1
section B

216
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Zero sequence
SCEFRFLO FLOC(1 21FL(1 0.000...1000.00 Settings\Settings\Other
SET LD0.SCEF2ZLIN1.RZer.setMag.f ASG FLOAT32 SG A 4.000 R0 line section B line resistance,
1 ) ) 0 ohm / pu protection\SCEFRFLO1
line section B
Zero sequence
SCEFRFLO FLOC(1 21FL(1 0.000...1000.00 Settings\Settings\Other
SET LD0.SCEF2ZLIN1.XZer.setMag.f ASG FLOAT32 SG A 4.000 X0 line section B line reactance,
1 ) ) 0 ohm / pu protection\SCEFRFLO1
line section B
SCEFRFLO FLOC(1 21FL(1 Line Len section Line length, 0.000...1000.00 Settings\Settings\Other
SET LD0.SCEF3ZLIN1.LinLenkm.setMag.f ASG FLOAT32 SG A 0.000
1 ) ) C section C 0 pu protection\SCEFRFLO1
Positive
SCEFRFLO FLOC(1 21FL(1 sequence line 0.000...1000.00 Settings\Settings\Other
SET LD0.SCEF3ZLIN1.RPs.setMag.f ASG FLOAT32 SG A 1.000 R1 line section C
1 ) ) resistance, line 0 ohm / pu protection\SCEFRFLO1
section C
Positive
SCEFRFLO FLOC(1 21FL(1 sequence line 0.000...1000.00 Settings\Settings\Other
SET LD0.SCEF3ZLIN1.XPs.setMag.f ASG FLOAT32 SG A 1.000 X1 line section C
1 ) ) reactance, line 0 ohm / pu protection\SCEFRFLO1
section C
Zero sequence
SCEFRFLO FLOC(1 21FL(1 0.000...1000.00 Settings\Settings\Other
SET LD0.SCEF3ZLIN1.RZer.setMag.f ASG FLOAT32 SG A 4.000 R0 line section C line resistance,
1 ) ) 0 ohm / pu protection\SCEFRFLO1
line section C
Zero sequence
SCEFRFLO FLOC(1 21FL(1 0.000...1000.00 Settings\Settings\Other
SET LD0.SCEF3ZLIN1.XZer.setMag.f ASG FLOAT32 SG A 4.000 X0 line section C line reactance,
1 ) ) 0 ohm / pu protection\SCEFRFLO1
line section C
0=Reset;
39=Activate
SCEFRFLO FLOC(1 21FL(1 Test control for Tests\Function tests\Other
TES LD0.SCEFRFLO1.TestProRl.Oper.ctlVal ENC Enum CO B 0 SCEFRFLO1 ALARM;
1 ) ) outputs protection
40=Deactive
ALARM
SCEFRFLO FLOC(1 21FL(1 VisString25
VER LD0.SCEFRFLO1.NamPlt.swRev LPL DC ED1 B1 (Name plate)
1 ) ) 5 (20)

DQPTUV1: Directional reactive power and under voltage protection: A1


IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
(ACT
Q>-
DQPTUV1 32Q,27(1) INP Channel U3P input
>,3U<(1)
channel)
(ACT
Q>-
DQPTUV1 32Q,27(1) INP Channel I3P input
>,3U<(1)
channel)
Block
signal for
Q>- activating Monitoring\I/O status\Power
DQPTUV1 32Q,27(1) INP LD0.DQPTUV1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
>,3U<(1) the protection\DQPTUV1\Inputs
blocking
mode
Q>- Monitoring\I/O status\Power
DQPTUV1 32Q,27(1) OUT LD0.DQPTUV1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start
>,3U<(1) protection\DQPTUV1\Outputs
217
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Q>- Monitoring\I/O status\Power


DQPTUV1 32Q,27(1) OUT LD0.DQPTUV1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate
>,3U<(1) protection\DQPTUV1\Outputs
1=on; 2=blocked;
Q>- 3=test;
DQPTUV1 32Q,27(1) MON LD0.DQPTUV1.Beh.stVal ENS Enum ST B DQPTUV1 Status Monitoring\FB status
>,3U<(1) 4=test/blocked;
5=off
Ratio of
Monitoring\I/O status\Power
Q>- start time /
DQPTUV1 32Q,27(1) MON LD0.DQPTUV1.StrDur.mag.f MV FLOAT32 MX B START_DUR 0.00...100.00 % protection\DQPTUV1\Monitored
>,3U<(1) operate
data
time
Monitoring\I/O status\Power
Q>- Reactive -160.000...+160.000
DQPTUV1 32Q,27(1) MON LD0.DQMMXU1.TotVAr.mag.f MV FLOAT32 MX B I1 Q protection\DQPTUV1\Monitored
>,3U<(1) power xSn
data
Q>- Operation Settings\Settings\Power
DQPTUV1 32Q,27(1) SET LD0.DQPTUV1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
>,3U<(1) On/Off protection\DQPTUV1
Start value
Q>- Voltage start for under Settings\Settings\Power
DQPTUV1 32Q,27(1) SET LD0.DQPTUV1.StrVal.setMag.f ASG FLOAT32 SG B 0.85 0.20...1.20 xUn UL1TVTR1
>,3U<(1) value voltage protection\DQPTUV1
detection
Q>- Operate delay Operate Settings\Settings\Power
DQPTUV1 32Q,27(1) SET LD0.DQPTUV1.OpDlTmms.setVal ING INT32 SG B 500 100...300000 ms
>,3U<(1) time delay time protection\DQPTUV1
Minimum
reactive
Q>- Min reactive power Settings\Settings\Power
DQPTUV1 32Q,27(1) SET LD0.DQPDOP1.StrVal.setMag.f ASG FLOAT32 SP A 0.05 0.01...0.50 xSn
>,3U<(1) power needed for protection\DQPTUV1
function to
operate
Minimum
Q>- Min Ps Seq positive Settings\Settings\Power
DQPTUV1 32Q,27(1) SET LD0.DQPDOP1.BlkValA.setMag.f ASG FLOAT32 SP A 0.05 0.02...0.20 xIn IL1TCTR1
>,3U<(1) current sequence protection\DQPTUV1
current
Reverse
the
definition
Q>- of the Settings\Settings\Power
DQPTUV1 32Q,27(1) SET LD0.DQPDOP1.RevPol.setVal SPG BOOLEAN SP A 0 Pol reversal
>,3U<(1) positive protection\DQPTUV1
reactive
power
direction
Power
Q>- Pwr sector Settings\Settings\Power
DQPTUV1 32Q,27(1) SET LD0.DQPDOP1.PwrSectRed.setMag.f ASG FLOAT32 SP A 3 sector 0...10 deg
>,3U<(1) reduction protection\DQPTUV1
reduction
0=Reset; 1=Activate
START; 2=Deactive
Test
Q>- START; 9=Activate Tests\Function tests\Power
DQPTUV1 32Q,27(1) TES LD0.DQPTUV1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 DQPTUV1 control for
>,3U<(1) OPERATE; protection
outputs
10=Deactive
OPERATE
Q>- VisString255 (Name
DQPTUV1 32Q,27(1) VER LD0.DQPTUV1.NamPlt.swRev LPL DC ED1 A1
>,3U<(1) (20) plate)
218
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

LVRTPTUV1: Low voltage ride through protection function: A1


Categor Acces Defaul Even CM Parameter Parameter Parameter Channel
IEC 61850 IEC 60617 ANSI IECName CDC Type FC Dataset Menu path
y s t t T name desc range relation
U<rt(1)<
LVRTPTUV 27RT(1 (ACT input
td=""></rt(1)< INP Channel U3P
1 ) channel)
>
Block
signal for
U<rt(1)<
LVRTPTUV 27RT(1 activating Monitoring\I/O status\Voltage
td=""></rt(1)< INP LD0.LVRTPTUV1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
1 ) the protection\LVRTPTUV1\Inputs
>
blocking
mode
U<rt(1)< Monitoring\I/O status\Voltage
LVRTPTUV 27RT(1 AC StatNrm
td=""></rt(1)< OUT LD0.LVRTPTUV1.Str.general BOOLEAN ST B P,H I1 START Start protection\LVRTPTUV1\Output
1 ) D l
> s
U<rt(1)< Monitoring\I/O status\Voltage
LVRTPTUV 27RT(1 StatNrm
td=""></rt(1)< OUT LD0.LVRTPTUV1.Op.general ACT BOOLEAN ST B P,H I1 OPERATE Operate protection\LVRTPTUV1\Output
1 ) l
> s
1=on;
U<rt(1)< 2=blocked;
LVRTPTUV 27RT(1 LVRTPTUV
td=""></rt(1)< MON LD0.LVRTPTUV1.Beh.stVal ENS Enum ST B Status 3=test; Monitoring\FB status
1 ) 1
> 4=test/blocked
; 5=off
U<rt(1)<
LVRTPTUV 27RT(1 C Operation Settings\Settings\Voltage
td=""></rt(1)< SET LD0.LVRTPTUV1.Mod.Oper.ctlVal ENC Enum B,I 1 Operation 1=on; 5=off
1 ) O Off / On protection\LVRTPTUV1
>
Voltage
value
U<rt(1)<
LVRTPTUV 27RT(1 Voltage start below 0.05...1.20 Settings\Settings\Voltage UL1TVTR
td=""></rt(1)< SET LD0.LVRTPTUV1.StrVal.setMag.f ASG FLOAT32 SG B 0.90
1 ) value which xUn protection\LVRTPTUV1 1
>
function
starts
Coordinate
U<rt(1)< s used for
LVRTPTUV 27RT(1 Active Settings\Settings\Voltage
td=""></rt(1)< SET LD0.LVRTPTUV1.NumPt.setVal ING INT32 SP B 3 defining 1...10
1 ) coordinates protection\LVRTPTUV1
> LVRT
curve
1st time
U<rt(1)< coordinate
LVRTPTUV 27RT(1 Recovery Settings\Settings\Voltage
td=""></rt(1)< SET LD0.LVRTPTUV1.CrvPt0Tmms.setVal ING INT32 SP B 500 for defining 0...300000 ms
1 ) time 1 protection\LVRTPTUV1
> LVRT
curve
2nd time
U<rt(1)< coordinate
LVRTPTUV 27RT(1 Recovery Settings\Settings\Voltage
td=""></rt(1)< SET LD0.LVRTPTUV1.CrvPt1Tmms.setVal ING INT32 SP B 1000 for defining 0...300000 ms
1 ) time 2 protection\LVRTPTUV1
> LVRT
curve

219
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

3rd time
U<rt(1)< coordinate
LVRTPTUV 27RT(1 Recovery Settings\Settings\Voltage
td=""></rt(1)< SET LD0.LVRTPTUV1.CrvPt2Tmms.setVal ING INT32 SP B 10000 for defining 0...300000 ms
1 ) time 3 protection\LVRTPTUV1
> LVRT
curve
4th time
U<rt(1)< coordinate
LVRTPTUV 27RT(1 Recovery Settings\Settings\Voltage
td=""></rt(1)< SET LD0.LVRTPTUV1.CrvPt3Tmms.setVal ING INT32 SP B 10000 for defining 0...300000 ms
1 ) time 4 protection\LVRTPTUV1
> LVRT
curve
5th time
U<rt(1)< coordinate
LVRTPTUV 27RT(1 Recovery Settings\Settings\Voltage
td=""></rt(1)< SET LD0.LVRTPTUV1.CrvPt4Tmms.setVal ING INT32 SP B 10000 for defining 0...300000 ms
1 ) time 5 protection\LVRTPTUV1
> LVRT
curve
6th time
U<rt(1)< coordinate
LVRTPTUV 27RT(1 Recovery Settings\Settings\Voltage
td=""></rt(1)< SET LD0.LVRTPTUV1.CrvPt5Tmms.setVal ING INT32 SP B 10000 for defining 0...300000 ms
1 ) time 6 protection\LVRTPTUV1
> LVRT
curve
7th time
U<rt(1)< coordinate
LVRTPTUV 27RT(1 Recovery Settings\Settings\Voltage
td=""></rt(1)< SET LD0.LVRTPTUV1.CrvPt6Tmms.setVal ING INT32 SP B 10000 for defining 0...300000 ms
1 ) time 7 protection\LVRTPTUV1
> LVRT
curve
8th time
U<rt(1)< coordinate
LVRTPTUV 27RT(1 Recovery Settings\Settings\Voltage
td=""></rt(1)< SET LD0.LVRTPTUV1.CrvPt7Tmms.setVal ING INT32 SP B 10000 for defining 0...300000 ms
1 ) time 8 protection\LVRTPTUV1
> LVRT
curve
9th time
U<rt(1)< coordinate
LVRTPTUV 27RT(1 Recovery Settings\Settings\Voltage
td=""></rt(1)< SET LD0.LVRTPTUV1.CrvPt8Tmms.setVal ING INT32 SP B 10000 for defining 0...300000 ms
1 ) time 9 protection\LVRTPTUV1
> LVRT
curve
10th time
U<rt(1)< coordinate
LVRTPTUV 27RT(1 Recovery Settings\Settings\Voltage
td=""></rt(1)< SET LD0.LVRTPTUV1.CrvPt9Tmms.setVal ING INT32 SP B 10000 for defining 0...300000 ms
1 ) time 10 protection\LVRTPTUV1
> LVRT
curve
1st voltage
U<rt(1)< coordinate
LVRTPTUV 27RT(1 LD0.LVRTPTUV1.CrvPt0Ydir.setMag. Voltage level 0.00...1.20 Settings\Settings\Voltage UL1TVTR
td=""></rt(1)< SET ASG FLOAT32 SP B 0.20 for defining
1 ) f 1 xUn protection\LVRTPTUV1 1
> LVRT
curve
2nd voltage
U<rt(1)< coordinate
LVRTPTUV 27RT(1 LD0.LVRTPTUV1.CrvPt1Ydir.setMag. Voltage level 0.00...1.20 Settings\Settings\Voltage UL1TVTR
td=""></rt(1)< SET ASG FLOAT32 SP B 0.80 for defining
1 ) f 2 xUn protection\LVRTPTUV1 1
> LVRT
curve

220
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

3rd voltage
U<rt(1)< coordinate
LVRTPTUV 27RT(1 LD0.LVRTPTUV1.CrvPt2Ydir.setMag. Voltage level 0.00...1.20 Settings\Settings\Voltage UL1TVTR
td=""></rt(1)< SET ASG FLOAT32 SP B 0.90 for defining
1 ) f 3 xUn protection\LVRTPTUV1 1
> LVRT
curve
4th voltage
U<rt(1)< coordinate
LVRTPTUV 27RT(1 LD0.LVRTPTUV1.CrvPt3Ydir.setMag. Voltage level 0.00...1.20 Settings\Settings\Voltage UL1TVTR
td=""></rt(1)< SET ASG FLOAT32 SP B 0.90 for defining
1 ) f 4 xUn protection\LVRTPTUV1 1
> LVRT
curve
5th voltage
U<rt(1)< coordinate
LVRTPTUV 27RT(1 LD0.LVRTPTUV1.CrvPt4Ydir.setMag. Voltage level 0.00...1.20 Settings\Settings\Voltage UL1TVTR
td=""></rt(1)< SET ASG FLOAT32 SP B 0.90 for defining
1 ) f 5 xUn protection\LVRTPTUV1 1
> LVRT
curve
6th voltage
U<rt(1)< coordinate
LVRTPTUV 27RT(1 LD0.LVRTPTUV1.CrvPt5Ydir.setMag. Voltage level 0.00...1.20 Settings\Settings\Voltage UL1TVTR
td=""></rt(1)< SET ASG FLOAT32 SP B 0.90 for defining
1 ) f 6 xUn protection\LVRTPTUV1 1
> LVRT
curve
7th voltage
U<rt(1)< coordinate
LVRTPTUV 27RT(1 LD0.LVRTPTUV1.CrvPt6Ydir.setMag. Voltage level 0.00...1.20 Settings\Settings\Voltage UL1TVTR
td=""></rt(1)< SET ASG FLOAT32 SP B 0.90 for defining
1 ) f 7 xUn protection\LVRTPTUV1 1
> LVRT
curve
8th voltage
U<rt(1)< coordinate
LVRTPTUV 27RT(1 LD0.LVRTPTUV1.CrvPt7Ydir.setMag. Voltage level 0.00...1.20 Settings\Settings\Voltage UL1TVTR
td=""></rt(1)< SET ASG FLOAT32 SP B 0.90 for defining
1 ) f 8 xUn protection\LVRTPTUV1 1
> LVRT
curve
9th voltage
U<rt(1)< coordinate
LVRTPTUV 27RT(1 LD0.LVRTPTUV1.CrvPt8Ydir.setMag. Voltage level 0.00...1.20 Settings\Settings\Voltage UL1TVTR
td=""></rt(1)< SET ASG FLOAT32 SP B 0.90 for defining
1 ) f 9 xUn protection\LVRTPTUV1 1
> LVRT
curve
10th
voltage
U<rt(1)<
LVRTPTUV 27RT(1 LD0.LVRTPTUV1.CrvPt9Ydir.setMag. Voltage level coordinate 0.00...1.20 Settings\Settings\Voltage UL1TVTR
td=""></rt(1)< SET ASG FLOAT32 SP B 0.90
1 ) f 10 for defining xUn protection\LVRTPTUV1 1
>
LVRT
curve
4=Exactly 1 of
U<rt(1)< Number of 3; 5=Exactly 2
LVRTPTUV 27RT(1 Num of start Settings\Settings\Voltage
td=""></rt(1)< SET LD0.LVRTPTUV1.NumPh.setVal ENG Enum SP B 4 faulty of 3;
1 ) phases protection\LVRTPTUV1
> phases 6=Exactly 3 of
3
Parameter 1=Highest Ph-
U<rt(1)< to select to-E;
LVRTPTUV 27RT(1 Voltage Settings\Settings\Voltage
td=""></rt(1)< SET LD0.LVRTPTUV1.VCrtSel.setVal ENG Enum SP B 4 voltage for 2=Lowest Ph-
1 ) selection protection\LVRTPTUV1
> curve to-E;
monitoring 3=Highest Ph-
221
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

to-Ph;
4=Lowest Ph-
to-Ph;
5=Positive Seq
0=Reset;
1=Activate
START;
U<rt(1)< 2=Deactive
LVRTPTUV 27RT(1 C LVRTPTUV Test control Tests\Function tests\Voltage
td=""></rt(1)< TES LD0.LVRTPTUV1.TestPro.Oper.ctlVal ENC Enum B 1 START;
1 ) O 1 for outputs protection
> 9=Activate
OPERATE;
10=Deactive
OPERATE
U<rt(1)<
LVRTPTUV 27RT(1 VisString25 D (Name
td=""></rt(1)< VER LD0.LVRTPTUV1.NamPlt.swRev LPL ED1 A1
1 ) 5 (20) C plate)
>

VMHAI1: Voltage total harmonic distortion: C1


IEC Parameter Parameter Channel
IEC 60617 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Menu path
61850 name range relation
(ACT input
VMHAI1 PQM3U(1) PQM3V(1) INP Channel U3P
channel)
Block signal
Monitoring\I/O status\Power
VMHAI1 PQM3U(1) PQM3V(1) INP LD0.VMHAI1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK for all binary
quality\VMHAI1\Inputs
outputs
Alarm signal Monitoring\I/O status\Power
VMHAI1 PQM3U(1) PQM3V(1) OUT LD0.VMHAI1.Alm.stVal SPS BOOLEAN ST B StatUrg P,H I1 ALARM
for THD quality\VMHAI1\Outputs
(VMHAI1
VMHAI1 PQM3U(1) PQM3V(1) CTR LD0.VMHAI1.RcdRs.Oper.ctlVal SPC BOOLEAN CO I1
max.demands)
3 second mean Monitoring\I/O status\Power
0.00...500.00
VMHAI1 PQM3U(1) PQM3V(1) MON LD0.VMHAI1.ThdPhV.phsA.cVal.mag.f WYE FLOAT32 MX B I1 3SMHTHD_A value of THD quality\VMHAI1\Monitored
%
for phase A data
3 second mean Monitoring\I/O status\Power
0.00...500.00
VMHAI1 PQM3U(1) PQM3V(1) MON LD0.VMHAI1.ThdPhV.phsB.cVal.mag.f WYE FLOAT32 MX B I1 3SMHTHD_B value of THD quality\VMHAI1\Monitored
%
for phase B data
3 second mean Monitoring\I/O status\Power
0.00...500.00
VMHAI1 PQM3U(1) PQM3V(1) MON LD0.VMHAI1.ThdPhV.phsC.cVal.mag.f WYE FLOAT32 MX B I1 3SMHTHD_C value of THD quality\VMHAI1\Monitored
%
for phase C data
Demand value Monitoring\I/O status\Power
0.00...500.00
VMHAI1 PQM3U(1) PQM3V(1) MON LD0.VMHAI1.DmdThdPhV.phsA.cVal.mag.f WYE FLOAT32 MX B I1 DMD_THD_A for THD for quality\VMHAI1\Monitored
%
phase A data
Demand value Monitoring\I/O status\Power
0.00...500.00
VMHAI1 PQM3U(1) PQM3V(1) MON LD0.VMHAI1.DmdThdPhV.phsB.cVal.mag.f WYE FLOAT32 MX B I1 DMD_THD_B for THD for quality\VMHAI1\Monitored
%
phase B data
Demand value Monitoring\I/O status\Power
0.00...500.00
VMHAI1 PQM3U(1) PQM3V(1) MON LD0.VMHAI1.DmdThdPhV.phsC.cVal.mag.f WYE FLOAT32 MX B I1 DMD_THD_C for THD for quality\VMHAI1\Monitored
%
phase C data
222
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Maximum
Max demand 0.00...500.00 Monitoring\Recorded
VMHAI1 PQM3U(1) PQM3V(1) MON LD0.VMHAI1.MaxDmdThdV.phsA.cVal.mag.f WYE FLOAT32 MX B I1 demand THD
THD UL1 % data\Power quality\VMHAI1
for phase A
Time of
Time max dmd maximum Monitoring\Recorded
VMHAI1 PQM3U(1) PQM3V(1) MON LD0.VMHAI1.MaxDmdThdV.phsA.t WYE Timestamp MX B
THD UL1 demand THD data\Power quality\VMHAI1
phase A
Maximum
Max demand 0.00...500.00 Monitoring\Recorded
VMHAI1 PQM3U(1) PQM3V(1) MON LD0.VMHAI1.MaxDmdThdV.phsB.cVal.mag.f WYE FLOAT32 MX B I1 demand THD
THD UL2 % data\Power quality\VMHAI1
for phase B
Time of
Time max dmd maximum Monitoring\Recorded
VMHAI1 PQM3U(1) PQM3V(1) MON LD0.VMHAI1.MaxDmdThdV.phsB.t WYE Timestamp MX B
THD UL2 demand THD data\Power quality\VMHAI1
phase B
Maximum
Max demand 0.00...500.00 Monitoring\Recorded
VMHAI1 PQM3U(1) PQM3V(1) MON LD0.VMHAI1.MaxDmdThdV.phsC.cVal.mag.f WYE FLOAT32 MX B I1 demand THD
THD UL3 % data\Power quality\VMHAI1
for phase C
Time of
Time max dmd maximum Monitoring\Recorded
VMHAI1 PQM3U(1) PQM3V(1) MON LD0.VMHAI1.MaxDmdThdV.phsC.t WYE Timestamp MX B
THD UL3 demand THD data\Power quality\VMHAI1
phase C
Operation Off Settings\Settings\Power
VMHAI1 PQM3U(1) PQM3V(1) SET LD0.VMHAI1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off IL1TCTR1
/ On quality\VMHAI1
THD alarm THD alarm Settings\Settings\Power
VMHAI1 PQM3U(1) PQM3V(1) SET LD0.VMHAI1.ThdVVal.setMag.f ASG FLOAT32 SP B 50.0 1.0...100.0 %
limit limit quality\VMHAI1
0=1 minute;
1=5 minutes;
2=10 minutes;
Time interval
Demand 3=15 minutes; Settings\Settings\Power
VMHAI1 PQM3U(1) PQM3V(1) SET LD0.VMHAI1.DmdItrv.setVal ENG Enum SP B 2 for demand
interval 4=30 minutes; quality\VMHAI1
calculation
5=60 minutes;
6=180
minutes
Demand
Demand 1=Sliding; Settings\Settings\Power
VMHAI1 PQM3U(1) PQM3V(1) SET LD0.VMHAI1.DmdWinMod.setVal ENG Enum SP B 1 calculation
window 2=Non-sliding quality\VMHAI1
window type
VisString255
VMHAI1 PQM3U(1) PQM3V(1) VER LD0.VMHAI1.NamPlt.swRev LPL DC ED1 C1 (Name plate)
(20)

PHQVVR1: Short duration voltage variations: D1


IEC Categor CD Acces Defaul Even CM Parameter Channel
IEC 61850 ANSI IECName Type FC Dataset Parameter name Parameter range Menu path
60617 y C s t t T desc relation
PHQVVR PQMU(1 PQMV(1 (ACT input
INP Channel U3P
1 ) ) channel)
PHQVVR PQMU(1 PQMV(1 (ACT input
INP Channel I3P
1 ) ) channel)

223
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Block signal
PHQVVR PQMU(1 PQMV(1 for activating Monitoring\I/O status\Power
INP LD0.PH1QVVR1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
1 ) ) the blocking quality\PHQVVR1\Inputs
mode
PHQVVR PQMU(1 PQMV(1 Voltage dip Monitoring\I/O status\Power
OUT LD0.PH1QVVR1.DipStr.stVal SPS BOOLEAN ST B I1 DIPST
1 ) ) active quality\PHQVVR1\Outputs
PHQVVR PQMU(1 PQMV(1 Voltage Monitoring\I/O status\Power
OUT LD0.PH1QVVR1.SwlStr.stVal SPS BOOLEAN ST B I1 SWELLST
1 ) ) swell active quality\PHQVVR1\Outputs
Voltage
PHQVVR PQMU(1 PQMV(1 Monitoring\I/O status\Power
OUT LD0.PH1QVVR1.IntrStr.stVal SPS BOOLEAN ST B I1 INTST interruption
1 ) ) quality\PHQVVR1\Outputs
active
Voltage
PHQVVR PQMU(1 PQMV(1 Monitoring\I/O status\Power
OUT LD0.PH1QVVR1.VaOp.stVal SPS BOOLEAN ST B I1 OPERATE variation
1 ) ) quality\PHQVVR1\Outputs
detected
Voltage
PHQVVR PQMU(1 PQMV(1 StatUr Monitoring\I/O status\Power
OUT LD0.PH1QVVR1.VaStrGen.stVal SPS BOOLEAN ST B P,H I1 START variation
1 ) ) g quality\PHQVVR1\Outputs
present
(Resettable
PHQVVR PQMU(1 PQMV(1
CTR LD0.PH1QVVR1.OpCntRs.Oper.ctlVal INC INT32 CO I1 operation
1 ) )
counter)
PHQVVR PQMU(1 PQMV(1 (Counters
CTR LD0.PH1QVVR1.CntRs.Oper.ctlVal SPC BOOLEAN CO I1
1 ) ) reset)
PHQVVR PQMU(1 PQMV(1 (Recorded
CTR LD0.PH1QVVR1.RcdRs.Oper.ctlVal SPC BOOLEAN CO I1
1 ) ) data reset)
1=on;
2=blocked;
PHQVVR PQMU(1 PQMV(1
MON LD0.PH1QVVR1.Beh.stVal ENS Enum ST B PHQVVR1 Status 3=test; Monitoring\FB status
1 ) )
4=test/blocked;
5=off
Start Phase
A (Voltage Monitoring\I/O status\Power
PHQVVR PQMU(1 PQMV(1
MON LD0.PH1QVVR1.VarStr.stVal SPS BOOLEAN ST B I1 ST_A Variation quality\PHQVVR1\Monitore
1 ) )
Event in d data
progress)
Instantaneou
Monitoring\I/O status\Power
PHQVVR PQMU(1 PQMV(1 s swell
MON LD0.PH1QVVR1.SwlInstCnt.stVal INS INT32 ST B I1 INSTSWELLCNT 0...2147483647 quality\PHQVVR1\Monitore
1 ) ) operation
d data
counter
Momentary
Monitoring\I/O status\Power
PHQVVR PQMU(1 PQMV(1 swell
MON LD0.PH1QVVR1.SwlMomCnt.stVal INS INT32 ST B I1 MOMSWELLCNT 0...2147483647 quality\PHQVVR1\Monitore
1 ) ) operation
d data
counter
Temporary
Monitoring\I/O status\Power
PHQVVR PQMU(1 PQMV(1 swell
MON LD0.PH1QVVR1.SwlTmpCnt.stVal INS INT32 ST B I1 TEMPSWELLCNT 0...2147483647 quality\PHQVVR1\Monitore
1 ) ) operation
d data
counter
Maximum Monitoring\I/O status\Power
PHQVVR PQMU(1 PQMV(1 MAXDURSWELLCN
MON LD0.PH1QVVR1.SwlMaxCnt.stVal INS INT32 ST B I1 duration 0...2147483647 quality\PHQVVR1\Monitore
1 ) ) T
swell d data
224
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

operation
counter
Instantaneou
Monitoring\I/O status\Power
PHQVVR PQMU(1 PQMV(1 s dip
MON LD0.PH1QVVR1.DipInstCnt.stVal INS INT32 ST B I1 INSTDIPCNT 0...2147483647 quality\PHQVVR1\Monitore
1 ) ) operation
d data
counter
Temporary Monitoring\I/O status\Power
PHQVVR PQMU(1 PQMV(1
MON LD0.PH1QVVR1.DipTmpCnt.stVal INS INT32 ST B I1 TEMPDIPCNT dip operation 0...2147483647 quality\PHQVVR1\Monitore
1 ) )
counter d data
Momentary Monitoring\I/O status\Power
PHQVVR PQMU(1 PQMV(1
MON LD0.PH1QVVR1.DipMomCnt.stVal INS INT32 ST B I1 MOMDIPCNT dip operation 0...2147483647 quality\PHQVVR1\Monitore
1 ) )
counter d data
Maximum
Monitoring\I/O status\Power
PHQVVR PQMU(1 PQMV(1 duration dip
MON LD0.PH1QVVR1.DipMaxCnt.stVal INS INT32 ST B I1 MAXDURDIPCNT 0...2147483647 quality\PHQVVR1\Monitore
1 ) ) operation
d data
counter
Momentary
Monitoring\I/O status\Power
PHQVVR PQMU(1 PQMV(1 interruption
MON LD0.PH1QVVR1.IntrMomCnt.stVal INS INT32 ST B I1 MOMINTCNT 0...2147483647 quality\PHQVVR1\Monitore
1 ) ) operation
d data
counter
Temporary
Monitoring\I/O status\Power
PHQVVR PQMU(1 PQMV(1 interruption
MON LD0.PH1QVVR1.IntrTmpCnt.stVal INS INT32 ST B I1 TEMPINTCNT 0...2147483647 quality\PHQVVR1\Monitore
1 ) ) operation
d data
counter
Sustained
Monitoring\I/O status\Power
PHQVVR PQMU(1 PQMV(1 interruption
MON LD0.PH1QVVR1.IntrSstCnt.stVal INS INT32 ST B I1 SUSTINTCNT 0...2147483647 quality\PHQVVR1\Monitore
1 ) ) operation
d data
counter
Maximum
duration Monitoring\I/O status\Power
PHQVVR PQMU(1 PQMV(1
MON LD0.PH1QVVR1.IntrMaxCnt.stVal INS INT32 ST B I1 MAXDURINTCNT interruption 0...2147483647 quality\PHQVVR1\Monitore
1 ) )
operation d data
counter
Start Phase B
(Voltage Monitoring\I/O status\Power
PHQVVR PQMU(1 PQMV(1
MON LD0.PH2QVVR1.VarStr.stVal SPS BOOLEAN ST B I1 ST_B Variation quality\PHQVVR1\Monitore
1 ) )
Event in d data
progress)
Start Phase C
(Voltage Monitoring\I/O status\Power
PHQVVR PQMU(1 PQMV(1
MON LD0.PH3QVVR1.VarStr.stVal SPS BOOLEAN ST B I1 ST_C Variation quality\PHQVVR1\Monitore
1 ) )
Event in d data
progress)
0=No variation;
1=Swell; 2=Dip; Monitoring\Recorded
PHQVVR PQMU(1 PQMV(1 Variation 3=Swell + dip; data\Power
MON LD0.QVV1RQRC1.VVaTyp.stVal ENS Enum ST B I1 Variation type
1 ) ) type 4=Interruption; quality\PHQVVR1\Variation
5=Swell + Int; 1
6=Dip + Int;

225
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

7=Swell+dip+In
t
Monitoring\Recorded
PHQVVR PQMU(1 PQMV(1 data\Power
MON LD0.QVV1RQRC1.VVaTyp.t ENS Timestamp ST B Time Time
1 ) ) quality\PHQVVR1\Variation
1
Monitoring\Recorded
Variation
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV1RQRC1.VVaPhsA.mag.f MV FLOAT32 B I1 Variation Ph A magnitude 0.00...5.00 xUn
1 ) ) X quality\PHQVVR1\Variation
Phase A
1
Variation Monitoring\Recorded
PHQVVR PQMU(1 PQMV(1 M magnitude data\Power
MON LD0.QVV1RQRC1.VVaPhsA.t MV Timestamp B Var Ph A rec time
1 ) ) X Phase A time quality\PHQVVR1\Variation
stamp 1
Monitoring\Recorded
Variation
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV1RQRC1.VVaPhsB.mag.f MV FLOAT32 B I1 Variation Ph B magnitude 0.00...5.00 xUn
1 ) ) X quality\PHQVVR1\Variation
Phase B
1
Variation Monitoring\Recorded
PHQVVR PQMU(1 PQMV(1 M magnitude data\Power
MON LD0.QVV1RQRC1.VVaPhsB.t MV Timestamp B Var Ph B rec time
1 ) ) X Phase B time quality\PHQVVR1\Variation
stamp 1
Monitoring\Recorded
Variation
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV1RQRC1.VVaPhsC.mag.f MV FLOAT32 B I1 Variation Ph C magnitude 0.00...5.00 xUn
1 ) ) X quality\PHQVVR1\Variation
Phase C
1
Variation Monitoring\Recorded
PHQVVR PQMU(1 PQMV(1 M magnitude data\Power
MON LD0.QVV1RQRC1.VVaPhsC.t MV Timestamp B Var Ph C rec time
1 ) ) X Phase C time quality\PHQVVR1\Variation
stamp 1
Monitoring\Recorded
Variation
PHQVVR PQMU(1 PQMV(1 M 0.000...3600.00 data\Power
MON LD0.QVV1RQRC1.VVaTmPhsA.mag.f MV FLOAT32 B I1 Variation Dur Ph A duration
1 ) ) X 0s quality\PHQVVR1\Variation
Phase A
1
Monitoring\Recorded
Variation Ph
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV1RQRC1.VVaTmPhsA.t MV Timestamp B Var Dur Ph A time A start time
1 ) ) X quality\PHQVVR1\Variation
stamp
1
Monitoring\Recorded
Variation
PHQVVR PQMU(1 PQMV(1 M 0.000...3600.00 data\Power
MON LD0.QVV1RQRC1.VVaTmPhsB.mag.f MV FLOAT32 B I1 Variation Dur Ph B duration
1 ) ) X 0s quality\PHQVVR1\Variation
Phase B
1
Monitoring\Recorded
Variation Ph
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV1RQRC1.VVaTmPhsB.t MV Timestamp B Var Dur Ph B time B start time
1 ) ) X quality\PHQVVR1\Variation
stamp
1
Monitoring\Recorded
Variation
PHQVVR PQMU(1 PQMV(1 M 0.000...3600.00 data\Power
MON LD0.QVV1RQRC1.VVaTmPhsC.mag.f MV FLOAT32 B I1 Variation Dur Ph C duration
1 ) ) X 0s quality\PHQVVR1\Variation
Phase C
1
226
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Monitoring\Recorded
Variation Ph
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV1RQRC1.VVaTmPhsC.t MV Timestamp B Var Dur Ph C time C start time
1 ) ) X quality\PHQVVR1\Variation
stamp
1
Current
Monitoring\Recorded
magnitude
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV1RQRC1.APreVaPhsA.mag.f MV FLOAT32 B I1 Var current Ph A Phase A 0.00...60.00 xIn
1 ) ) X quality\PHQVVR1\Variation
preceding
1
variation
Current
Monitoring\Recorded
magnitude
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV1RQRC1.APreVaPhsB.mag.f MV FLOAT32 B I1 Var current Ph B Phase B 0.00...60.00 xIn
1 ) ) X quality\PHQVVR1\Variation
preceding
1
variation
Current
Monitoring\Recorded
magnitude
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV1RQRC1.APreVaPhsC.mag.f MV FLOAT32 B I1 Var current Ph C Phase C 0.00...60.00 xIn
1 ) ) X quality\PHQVVR1\Variation
preceding
1
variation
0=No variation;
1=Swell; 2=Dip;
3=Swell + dip; Monitoring\Recorded
PHQVVR PQMU(1 PQMV(1 Variation 4=Interruption; data\Power
MON LD0.QVV2RQRC1.VVaTyp.stVal ENS Enum ST B I1 Variation type
1 ) ) type 5=Swell + Int; quality\PHQVVR1\Variation
6=Dip + Int; 2
7=Swell+dip+In
t
Monitoring\Recorded
PHQVVR PQMU(1 PQMV(1 data\Power
MON LD0.QVV2RQRC1.VVaTyp.t ENS Timestamp ST B Time Time
1 ) ) quality\PHQVVR1\Variation
2
Monitoring\Recorded
Variation
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV2RQRC1.VVaPhsA.mag.f MV FLOAT32 B I1 Variation Ph A magnitude 0.00...5.00 xUn
1 ) ) X quality\PHQVVR1\Variation
Phase A
2
Variation Monitoring\Recorded
PHQVVR PQMU(1 PQMV(1 M magnitude data\Power
MON LD0.QVV2RQRC1.VVaPhsA.t MV Timestamp B Var Ph A rec time
1 ) ) X Phase A time quality\PHQVVR1\Variation
stamp 2
Monitoring\Recorded
Variation
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV2RQRC1.VVaPhsB.mag.f MV FLOAT32 B I1 Variation Ph B magnitude 0.00...5.00 xUn
1 ) ) X quality\PHQVVR1\Variation
Phase B
2
Variation Monitoring\Recorded
PHQVVR PQMU(1 PQMV(1 M magnitude data\Power
MON LD0.QVV2RQRC1.VVaPhsB.t MV Timestamp B Var Ph B rec time
1 ) ) X Phase B time quality\PHQVVR1\Variation
stamp 2
Monitoring\Recorded
Variation
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV2RQRC1.VVaPhsC.mag.f MV FLOAT32 B I1 Variation Ph C magnitude 0.00...5.00 xUn
1 ) ) X quality\PHQVVR1\Variation
Phase C
2
227
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Variation Monitoring\Recorded
PHQVVR PQMU(1 PQMV(1 M magnitude data\Power
MON LD0.QVV2RQRC1.VVaPhsC.t MV Timestamp B Var Ph C rec time
1 ) ) X Phase C time quality\PHQVVR1\Variation
stamp 2
Monitoring\Recorded
Variation
PHQVVR PQMU(1 PQMV(1 M 0.000...3600.00 data\Power
MON LD0.QVV2RQRC1.VVaTmPhsA.mag.f MV FLOAT32 B I1 Variation Dur Ph A duration
1 ) ) X 0s quality\PHQVVR1\Variation
Phase A
2
Monitoring\Recorded
Variation Ph
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV2RQRC1.VVaTmPhsA.t MV Timestamp B Var Dur Ph A time A start time
1 ) ) X quality\PHQVVR1\Variation
stamp
2
Monitoring\Recorded
Variation
PHQVVR PQMU(1 PQMV(1 M 0.000...3600.00 data\Power
MON LD0.QVV2RQRC1.VVaTmPhsB.mag.f MV FLOAT32 B I1 Variation Dur Ph B duration
1 ) ) X 0s quality\PHQVVR1\Variation
Phase B
2
Monitoring\Recorded
Variation Ph
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV2RQRC1.VVaTmPhsB.t MV Timestamp B Var Dur Ph B time B start time
1 ) ) X quality\PHQVVR1\Variation
stamp
2
Monitoring\Recorded
Variation
PHQVVR PQMU(1 PQMV(1 M 0.000...3600.00 data\Power
MON LD0.QVV2RQRC1.VVaTmPhsC.mag.f MV FLOAT32 B I1 Variation Dur Ph C duration
1 ) ) X 0s quality\PHQVVR1\Variation
Phase C
2
Monitoring\Recorded
Variation Ph
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV2RQRC1.VVaTmPhsC.t MV Timestamp B Var Dur Ph C time C start time
1 ) ) X quality\PHQVVR1\Variation
stamp
2
Current
Monitoring\Recorded
magnitude
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV2RQRC1.APreVaPhsA.mag.f MV FLOAT32 B I1 Var current Ph A Phase A 0.00...60.00 xIn
1 ) ) X quality\PHQVVR1\Variation
preceding
2
variation
Current
Monitoring\Recorded
magnitude
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV2RQRC1.APreVaPhsB.mag.f MV FLOAT32 B I1 Var current Ph B Phase B 0.00...60.00 xIn
1 ) ) X quality\PHQVVR1\Variation
preceding
2
variation
Current
Monitoring\Recorded
magnitude
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV2RQRC1.APreVaPhsC.mag.f MV FLOAT32 B I1 Var current Ph C Phase C 0.00...60.00 xIn
1 ) ) X quality\PHQVVR1\Variation
preceding
2
variation
0=No variation;
1=Swell; 2=Dip;
3=Swell + dip; Monitoring\Recorded
PHQVVR PQMU(1 PQMV(1 Variation 4=Interruption; data\Power
MON LD0.QVV3RQRC1.VVaTyp.stVal ENS Enum ST B I1 Variation type
1 ) ) type 5=Swell + Int; quality\PHQVVR1\Variation
6=Dip + Int; 3
7=Swell+dip+In
t
228
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Monitoring\Recorded
PHQVVR PQMU(1 PQMV(1 data\Power
MON LD0.QVV3RQRC1.VVaTyp.t ENS Timestamp ST B Time Time
1 ) ) quality\PHQVVR1\Variation
3
Monitoring\Recorded
Variation
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV3RQRC1.VVaPhsA.mag.f MV FLOAT32 B I1 Variation Ph A magnitude 0.00...5.00 xUn
1 ) ) X quality\PHQVVR1\Variation
Phase A
3
Variation Monitoring\Recorded
PHQVVR PQMU(1 PQMV(1 M magnitude data\Power
MON LD0.QVV3RQRC1.VVaPhsA.t MV Timestamp B Var Ph A rec time
1 ) ) X Phase A time quality\PHQVVR1\Variation
stamp 3
Monitoring\Recorded
Variation
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV3RQRC1.VVaPhsB.mag.f MV FLOAT32 B I1 Variation Ph B magnitude 0.00...5.00 xUn
1 ) ) X quality\PHQVVR1\Variation
Phase B
3
Variation Monitoring\Recorded
PHQVVR PQMU(1 PQMV(1 M magnitude data\Power
MON LD0.QVV3RQRC1.VVaPhsB.t MV Timestamp B Var Ph B rec time
1 ) ) X Phase B time quality\PHQVVR1\Variation
stamp 3
Monitoring\Recorded
Variation
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV3RQRC1.VVaPhsC.mag.f MV FLOAT32 B I1 Variation Ph C magnitude 0.00...5.00 xUn
1 ) ) X quality\PHQVVR1\Variation
Phase C
3
Variation Monitoring\Recorded
PHQVVR PQMU(1 PQMV(1 M magnitude data\Power
MON LD0.QVV3RQRC1.VVaPhsC.t MV Timestamp B Var Ph C rec time
1 ) ) X Phase C time quality\PHQVVR1\Variation
stamp 3
Monitoring\Recorded
Variation
PHQVVR PQMU(1 PQMV(1 M 0.000...3600.00 data\Power
MON LD0.QVV3RQRC1.VVaTmPhsA.mag.f MV FLOAT32 B I1 Variation Dur Ph A duration
1 ) ) X 0s quality\PHQVVR1\Variation
Phase A
3
Monitoring\Recorded
Variation Ph
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV3RQRC1.VVaTmPhsA.t MV Timestamp B Var Dur Ph A time A start time
1 ) ) X quality\PHQVVR1\Variation
stamp
3
Monitoring\Recorded
Variation
PHQVVR PQMU(1 PQMV(1 M 0.000...3600.00 data\Power
MON LD0.QVV3RQRC1.VVaTmPhsB.mag.f MV FLOAT32 B I1 Variation Dur Ph B duration
1 ) ) X 0s quality\PHQVVR1\Variation
Phase B
3
Monitoring\Recorded
Variation Ph
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV3RQRC1.VVaTmPhsB.t MV Timestamp B Var Dur Ph B time B start time
1 ) ) X quality\PHQVVR1\Variation
stamp
3
Monitoring\Recorded
Variation
PHQVVR PQMU(1 PQMV(1 M 0.000...3600.00 data\Power
MON LD0.QVV3RQRC1.VVaTmPhsC.mag.f MV FLOAT32 B I1 Variation Dur Ph C duration
1 ) ) X 0s quality\PHQVVR1\Variation
Phase C
3

229
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Monitoring\Recorded
Variation Ph
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV3RQRC1.VVaTmPhsC.t MV Timestamp B Var Dur Ph C time C start time
1 ) ) X quality\PHQVVR1\Variation
stamp
3
Current
Monitoring\Recorded
magnitude
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV3RQRC1.APreVaPhsA.mag.f MV FLOAT32 B I1 Var current Ph A Phase A 0.00...60.00 xIn
1 ) ) X quality\PHQVVR1\Variation
preceding
3
variation
Current
Monitoring\Recorded
magnitude
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV3RQRC1.APreVaPhsB.mag.f MV FLOAT32 B I1 Var current Ph B Phase B 0.00...60.00 xIn
1 ) ) X quality\PHQVVR1\Variation
preceding
3
variation
Current
Monitoring\Recorded
magnitude
PHQVVR PQMU(1 PQMV(1 M data\Power
MON LD0.QVV3RQRC1.APreVaPhsC.mag.f MV FLOAT32 B I1 Var current Ph C Phase C 0.00...60.00 xIn
1 ) ) X quality\PHQVVR1\Variation
preceding
3
variation
PHQVVR PQMU(1 PQMV(1 Operation Settings\Settings\Power
SET LD0.PH1QVVR1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
1 ) ) Off / On quality\PHQVVR1
Dip limit 1
PHQVVR PQMU(1 PQMV(1 in % of Settings\Settings\Power
SET LD0.PH1QVVR1.DipStrVal.setMag.f ASG FLOAT32 SG B 80.0 Voltage dip set 1 10.0...100.0 %
1 ) ) reference quality\PHQVVR1
voltage
Dip limit 2
PHQVVR PQMU(1 PQMV(1 in % of Settings\Settings\Power
SET LD0.PH1QVVR1.DipStr2Val.setMag.f ASG FLOAT32 SG B 80.0 Voltage dip set 2 10.0...100.0 %
1 ) ) reference quality\PHQVVR1
voltage
Dip limit 3
PHQVVR PQMU(1 PQMV(1 in % of Settings\Settings\Power
SET LD0.PH1QVVR1.DipStr3Val.setMag.f ASG FLOAT32 SG B 80.0 Voltage dip set 3 10.0...100.0 %
1 ) ) reference quality\PHQVVR1
voltage
Swell limit 1
PHQVVR PQMU(1 PQMV(1 in % of Settings\Settings\Power
SET LD0.PH1QVVR1.SwlStrVal.setMag.f ASG FLOAT32 SG B 120.0 Voltage swell set 1 100.0...140.0 %
1 ) ) reference quality\PHQVVR1
voltage
Swell limit 2
PHQVVR PQMU(1 PQMV(1 in % of Settings\Settings\Power
SET LD0.PH1QVVR1.SwlStr2Val.setMag.f ASG FLOAT32 SG B 120.0 Voltage swell set 2 100.0...140.0 %
1 ) ) reference quality\PHQVVR1
voltage
Swell limit 3
PHQVVR PQMU(1 PQMV(1 in % of Settings\Settings\Power
SET LD0.PH1QVVR1.SwlStr3Val.setMag.f ASG FLOAT32 SG B 120.0 Voltage swell set 3 100.0...140.0 %
1 ) ) reference quality\PHQVVR1
voltage
Interruption
PHQVVR PQMU(1 PQMV(1 limit in % of Settings\Settings\Power
SET LD0.PH1QVVR1.IntrStrVal.setMag.f ASG FLOAT32 SG B 10.0 Voltage Int set 0.0...100.0 %
1 ) ) reference quality\PHQVVR1
voltage

230
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Reference
PHQVVR PQMU(1 PQMV(1 10.0...200.0 Settings\Settings\Power UL1TVTR
SET LD0.PH1QVVR1.RefV.setMag.f ASG FLOAT32 SG B 57.7 Reference voltage supply
1 ) ) %Un quality\PHQVVR1 1
voltage in %
Voltage
PHQVVR PQMU(1 PQMV(1 Settings\Settings\Power
SET LD0.PH1QVVR1.Dip1Cyc.setMag.f ASG FLOAT32 SG B 3.0 VVa dip time 1 variation dip 0.5...54.0 cycles
1 ) ) quality\PHQVVR1
duration 1
Voltage
PHQVVR PQMU(1 PQMV(1 10.0...180.0 Settings\Settings\Power
SET LD0.PH1QVVR1.Dip2Cyc.setMag.f ASG FLOAT32 SG B 30.0 VVa dip time 2 variation dip
1 ) ) cycles quality\PHQVVR1
duration 2
Voltage
PHQVVR PQMU(1 PQMV(1 Settings\Settings\Power
SET LD0.PH1QVVR1.Dip3Tmms.setVal ING INT32 SG B 3000 VVa dip time 3 variation dip 2000...60000 ms
1 ) ) quality\PHQVVR1
duration 3
Voltage
PHQVVR PQMU(1 PQMV(1 variation Settings\Settings\Power
SET LD0.PH1QVVR1.Swl1Cyc.setMag.f ASG FLOAT32 SG B 0.5 VVa swell time 1 0.5...54.0 cycles
1 ) ) swell quality\PHQVVR1
duration 1
Voltage
PHQVVR PQMU(1 PQMV(1 variation 10.0...80.0 Settings\Settings\Power
SET LD0.PH1QVVR1.Swl2Cyc.setMag.f ASG FLOAT32 SG B 10.0 VVa swell time 2
1 ) ) swell cycles quality\PHQVVR1
duration 2
Voltage
PHQVVR PQMU(1 PQMV(1 variation Settings\Settings\Power
SET LD0.PH1QVVR1.Swl3Tmms.setVal ING INT32 SG B 2000 VVa swell time 3 2000...60000 ms
1 ) ) swell quality\PHQVVR1
duration 3
Voltage
PHQVVR PQMU(1 PQMV(1 Settings\Settings\Power
SET LD0.PH1QVVR1.Intr1Cyc.setMag.f ASG FLOAT32 SG B 3.0 VVa Int time 1 variation Int 0.5...30.0 cycles
1 ) ) quality\PHQVVR1
duration 1
Voltage
PHQVVR PQMU(1 PQMV(1 10.0...180.0 Settings\Settings\Power
SET LD0.PH1QVVR1.Intr2Cyc.setMag.f ASG FLOAT32 SG B 30.0 VVa Int time 2 variation Int
1 ) ) cycles quality\PHQVVR1
duration 2
Voltage
PHQVVR PQMU(1 PQMV(1 variation Settings\Settings\Power
SET LD0.PH1QVVR1.Intr3Tmms.setVal ING INT32 SG B 3000 VVa Int time 3 2000...60000 ms
1 ) ) interruption quality\PHQVVR1
duration 3
Maximum
PHQVVR PQMU(1 PQMV(1 voltage 100...3600000 Settings\Settings\Power
SET LD0.PH1QVVR1.MaxDurTmms.setVal ING INT32 SG B 60000 VVa Dur Max
1 ) ) variation ms quality\PHQVVR1
duration
1=Ph A; 2=Ph
B; 3=Ph A + B;
Monitored
PHQVVR PQMU(1 PQMV(1 EN 4=Ph C; 5=Ph A Settings\Settings\Power
SET LD0.PH1QVVR1.PhSpvn.setVal Enum SP A 7 Phase supervision voltage
1 ) ) G + C; 6=Ph B + quality\PHQVVR1
phase
C; 7=Ph A + B
+C
PHQVVR PQMU(1 PQMV(1 EN Three/Single 1=Three Phase; Settings\Settings\Power
SET LD0.PH1QVVR1.OpModPh.setVal Enum SP A 2 Phase mode
1 ) ) G phase mode 2=Single Phase quality\PHQVVR1
1=Swell; 2=Dip;
Enable
PHQVVR PQMU(1 PQMV(1 EN 3=Swell + dip; Settings\Settings\Power
SET LD0.PH1QVVR1.VVaEna.setVal Enum SP B 7 Variation enable variation
1 ) ) G 4=Interruption; quality\PHQVVR1
type
5=Swell + Int;
231
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

6=Dip + Int;
7=Swell+dip+In
t
0=Reset;
1=Activate
START;
2=Deactive
START;
9=Activate
OPERATE;
10=Deactive
OPERATE; -
59=Activate
PHQVVR PQMU(1 PQMV(1 LD0.PH1QVVR1.TstOutCmd.Oper.ctlV Test control Tests\Function tests\Power
TES ENC Enum CO B 0 PHQVVR1 SWELLST; -
1 ) ) al for outputs quality
60=Deactive
SWELLST; -
61=Activate
DIPST; -
62=Deactive
DIPST; -
63=Activate
INTST; -
64=Deactive
INTST
PHQVVR PQMU(1 PQMV(1 VisString25
VER LD0.PH1QVVR1.NamPlt.swRev LPL DC ED1 D1 (Name plate)
1 ) ) 5 (20)

VSQVUB1: Voltage unbalance measurement: C1


Channe
Categor CD Acces Defaul Even CM
IEC 61850 IEC 60617 ANSI IECName Type FC Dataset Parameter name Parameter desc Parameter range Menu path l
y C s t t T
relation
VSQVUB PQUUB(1 PQVUB(1 (ACT input
INP Channel U3P
1 ) ) channel)
Block all outputs
VSQVUB PQUUB(1 PQVUB(1 Monitoring\I/O status\Power
INP LD0.VSQVUB1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK except measured
1 ) ) quality\VSQVUB1\Inputs
values
Alarm active
when 3 sec
VSQVUB PQUUB(1 PQVUB(1 StatNrm Monitoring\I/O status\Power
OUT LD0.VSQVUB1.VarStr.stVal SPS BOOLEAN ST B P,H I1 MN_UNB_AL voltage
1 ) ) l quality\VSQVUB1\Outputs
unbalance
exceeds the limit
Alarm active
VSQVUB PQUUB(1 PQVUB(1 StatNrm when percentile Monitoring\I/O status\Power
OUT LD0.VSQVUB1.HiPctVUnb.stVal SPS BOOLEAN ST B P,H I1 PCT_UNB_AL
1 ) ) l unbalance quality\VSQVUB1\Outputs
exceeds the limit
VSQVUB PQUUB(1 PQVUB(1 Observation Monitoring\I/O status\Power
OUT LD0.VSQVUB1.ObsPerAct.stVal SPS BOOLEAN ST B I1 OBS_PR_ACT
1 ) ) period is active quality\VSQVUB1\Outputs

232
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

(Trigger for
VSQVUB PQUUB(1 PQVUB(1
CTR LD0.VSQVUB1.TrgObsPer.Oper.ctlVal SPC BOOLEAN CO I1 observation
1 ) )
period)
VSQVUB PQUUB(1 PQVUB(1 (Recorded data
CTR LD0.VSQVUB1.RcdRs.Oper.ctlVal SPC BOOLEAN CO I1
1 ) ) reset)
1=on;
2=blocked;
VSQVUB PQUUB(1 PQVUB(1
MON LD0.VSQVUB1.Beh.stVal ENS Enum ST B VSQVUB1 Status 3=test; Monitoring\FB status
1 ) )
4=test/blocked;
5=off
Maximum
voltage
Monitoring\I/O status\Power
VSQVUB PQUUB(1 PQVUB(1 M unbalance
MON LD0.VSQVUB1.MaxVVa.mag.f MV FLOAT32 B I1 MAX_UNB_VAL 0.00...150.00 % quality\VSQVUB1\Monitore
1 ) ) X measured in the
d data
observation
period
Time stamp at
which maximum
voltage Monitoring\I/O status\Power
VSQVUB PQUUB(1 PQVUB(1 M MAX_UNB_TIM
MON LD0.VSQVUB1.MaxVVa.t MV Timestamp B unbalance quality\VSQVUB1\Monitore
1 ) ) X E
measured in the d data
observation
period
Limit below
Monitoring\I/O status\Power
VSQVUB PQUUB(1 PQVUB(1 M which percentile
MON LD0.VSQVUB1.PctUnbVal.mag.f MV FLOAT32 B I1 PCT_UNB_VAL 0.00...150.00 % quality\VSQVUB1\Monitore
1 ) ) X unbalance of the
d data
values lie
Non sliding 3
Monitoring\I/O status\Power
VSQVUB PQUUB(1 PQVUB(1 M second mean
MON LD0.VSQVUB1.VUnb3sMn.mag.f MV FLOAT32 B I1 3S_MN_UNB 0.00...150.00 % quality\VSQVUB1\Monitore
1 ) ) X value of voltage
d data
unbalance
Sliding 10
Monitoring\I/O status\Power
VSQVUB PQUUB(1 PQVUB(1 M minutes mean
MON LD0.VSQVUB1.VUnb10mMn.mag.f MV FLOAT32 B I1 10MIN_MN_UNB 0.00...150.00 % quality\VSQVUB1\Monitore
1 ) ) X value of voltage
d data
unbalance
Time stamp of
starting of the Monitoring\I/O status\Power
VSQVUB PQUUB(1 PQVUB(1
MON LD0.VSQVUB1.ObsPerStr.t SPS Timestamp ST B PR_STR_TIME previous quality\VSQVUB1\Monitore
1 ) )
observation d data
period
Time stamp of
Monitoring\I/O status\Power
VSQVUB PQUUB(1 PQVUB(1 end of previous
MON LD0.VSQVUB1.ObsPerEnd.t SPS Timestamp ST B PR_END_TIME quality\VSQVUB1\Monitore
1 ) ) observation
d data
period
Maximum 3 Monitoring\Recorded
VSQVUB PQUUB(1 PQVUB(1 M Max unbalance seconds data\Power
MON LD0.QVU1RQRC1.MaxVVa.mag.f MV FLOAT32 B I1 0.00...150.00 %
1 ) ) X Volt unbalance quality\VSQVUB1\Unbalanc
voltage e1
VSQVUB PQUUB(1 PQVUB(1 M Time Max Unb Time stamp of Monitoring\Recorded
MON LD0.QVU1RQRC1.MaxVVa.t MV Timestamp B
1 ) ) X Volt maximum data\Power
233
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

voltage quality\VSQVUB1\Unbalanc
unbalance e1
Monitoring\Recorded
Time duration
VSQVUB PQUUB(1 PQVUB(1 M Alarm high mean 0.000...3600.00 data\Power
MON LD0.QVU1RQRC1.VVaTm.mag.f MV FLOAT32 B I1 for alarm high
1 ) ) X Dur 0s quality\VSQVUB1\Unbalanc
mean unbalance
e1
Maximum 3 Monitoring\Recorded
VSQVUB PQUUB(1 PQVUB(1 M Max unbalance seconds data\Power
MON LD0.QVU2RQRC1.MaxVVa.mag.f MV FLOAT32 B I1 0.00...150.00 %
1 ) ) X Volt unbalance quality\VSQVUB1\Unbalanc
voltage e2
Time stamp of Monitoring\Recorded
VSQVUB PQUUB(1 PQVUB(1 M Time Max Unb maximum data\Power
MON LD0.QVU2RQRC1.MaxVVa.t MV Timestamp B
1 ) ) X Volt voltage quality\VSQVUB1\Unbalanc
unbalance e2
Monitoring\Recorded
Time duration
VSQVUB PQUUB(1 PQVUB(1 M Alarm high mean 0.000...3600.00 data\Power
MON LD0.QVU2RQRC1.VVaTm.mag.f MV FLOAT32 B I1 for alarm high
1 ) ) X Dur 0s quality\VSQVUB1\Unbalanc
mean unbalance
e2
Maximum 3 Monitoring\Recorded
VSQVUB PQUUB(1 PQVUB(1 M Max unbalance seconds data\Power
MON LD0.QVU3RQRC1.MaxVVa.mag.f MV FLOAT32 B I1 0.00...150.00 %
1 ) ) X Volt unbalance quality\VSQVUB1\Unbalanc
voltage e3
Time stamp of Monitoring\Recorded
VSQVUB PQUUB(1 PQVUB(1 M Time Max Unb maximum data\Power
MON LD0.QVU3RQRC1.MaxVVa.t MV Timestamp B
1 ) ) X Volt voltage quality\VSQVUB1\Unbalanc
unbalance e3
Monitoring\Recorded
Time duration
VSQVUB PQUUB(1 PQVUB(1 M Alarm high mean 0.000...3600.00 data\Power
MON LD0.QVU3RQRC1.VVaTm.mag.f MV FLOAT32 B I1 for alarm high
1 ) ) X Dur 0s quality\VSQVUB1\Unbalanc
mean unbalance
e3
VSQVUB PQUUB(1 PQVUB(1 Operation Settings\Settings\Power
SET LD0.VSQVUB1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
1 ) ) On/Off quality\VSQVUB1
1=Neg Seq;
Set the operation 2=Zero Seq;
VSQVUB PQUUB(1 PQVUB(1 EN Unb detection mode for voltage 3=Neg to Pos Settings\Settings\Power
SET LD0.VSQVUB1.UnbDetMth.setVal Enum SP B 3
1 ) ) G method unbalance Seq; 4=Zero to quality\VSQVUB1
calculation Pos Seq; 5=Ph
vectors Comp
Voltage
VSQVUB PQUUB(1 PQVUB(1 Unbalance start Settings\Settings\Power
SET LD0.VSQVUB1.StrVal.setMag.f ASG FLOAT32 SP B 1 unbalance start 1...100 %
1 ) ) Val quality\VSQVUB1
value
Specifies the
1=Single;
VSQVUB PQUUB(1 PQVUB(1 EN observation Settings\Settings\Power
SET LD0.VSQVUB1.TrgModPQ.setVal Enum SP B 3 Trigger mode 2=Periodic;
1 ) ) G period triggering quality\VSQVUB1
3=Continuous
mode
Observation 1=1 Hour; 2=12
VSQVUB PQUUB(1 PQVUB(1 EN Obs period period for Hours; 3=1 Settings\Settings\Power
SET LD0.VSQVUB1.ObsPerSel.setVal Enum SP B 5
1 ) ) G selection unbalance Day; 4=7 Days; quality\VSQVUB1
calculation 5=User defined

234
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

User define
observation
VSQVUB PQUUB(1 PQVUB(1 User Def Obs Settings\Settings\Power
SET LD0.VSQVUB1.ObsPerUsr.setVal ING INT32 SP B 168 period for 1...168 h
1 ) ) period quality\VSQVUB1
statistic
calculation
The percent to
which percentile
VSQVUB PQUUB(1 PQVUB(1 Percentile Settings\Settings\Power
SET LD0.VSQVUB1.PctUnb.setMag.f ASG FLOAT32 SP B 95 value 1...100 %
1 ) ) unbalance quality\VSQVUB1
PCT_UNB_VA
L is calculated
Calendar time
VSQVUB PQUUB(1 PQVUB(1 Obs period Str for observation Settings\Settings\Power
SET LD0.VSQVUB1.PerStrDate.setCal.occ TSG INT16U SP ED2,B 2011 2008...2076
1 ) ) year period start year quality\VSQVUB1
in YYYY
0=reserved;
1=January;
2=February;
3=March;
Calendar time 4=April;
VSQVUB PQUUB(1 PQVUB(1 LD0.VSQVUB1.PerStrDate.setCal.mont Obs period Str for observation 5=May; 6=June; Settings\Settings\Power
SET TSG Enum SP ED2,B 1
1 ) ) h month period start 7=July; quality\VSQVUB1
month 8=August;
9=September;
10=October;
11=November;
12=December
Calendar time
VSQVUB PQUUB(1 PQVUB(1 Settings\Settings\Power
SET LD0.VSQVUB1.PerStrDate.setCal.day TSG INT8U SP ED2,B 1 Obs period Str day for observation 1...31
1 ) ) quality\VSQVUB1
period start day
Calendar time
VSQVUB PQUUB(1 PQVUB(1 Obs period Str Settings\Settings\Power
SET LD0.VSQVUB1.PerStrDate.setCal.hr TSG INT8U SP ED2,B 0 for observation 0...23 h
1 ) ) hour quality\VSQVUB1
period start hour
0=Reset;
11=Activate
MN_UNB_AL;
12=Deactive
MN_UNB_AL;
13=Activate
VSQVUB PQUUB(1 PQVUB(1 Test control for Tests\Function tests\Power
TES LD0.VSQVUB1.TestOth.Oper.ctlVal ENC Enum CO B 0 VSQVUB1 PCT_UNB_AL;
1 ) ) outputs quality
14=Deactive
PCT_UNB_AL;
15=Activate
OBS_PR_ACT;
16=Deactive
OBS_PR_ACT
VSQVUB PQUUB(1 PQVUB(1 VisString25
VER LD0.VSQVUB1.NamPlt.swRev LPL DC ED1 C1 (Name plate)
1 ) ) 5 (20)

CMHAI1: Current total demand distortion: D1


235
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

IEC IEC Parameter Parameter Channel


ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Menu path
61850 60617 name range relation
(ACT input
CMHAI1 PQM3I(1) PQM3I(1) INP Channel I3P
channel)
Block signal
Monitoring\I/O status\Power
CMHAI1 PQM3I(1) PQM3I(1) INP LD0.CMHAI1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK for all binary
quality\CMHAI1\Inputs
outputs
Alarm signal Monitoring\I/O status\Power
CMHAI1 PQM3I(1) PQM3I(1) OUT LD0.CMHAI1.Alm.stVal SPS BOOLEAN ST B StatUrg P,H I1 ALARM
for TDD quality\CMHAI1\Outputs
(CMHAI1
CMHAI1 PQM3I(1) PQM3I(1) CTR LD0.CMHAI1.RcdRs.Oper.ctlVal SPC BOOLEAN CO I1
max.demands)
3 second mean Monitoring\I/O status\Power
CMHAI1 PQM3I(1) PQM3I(1) MON LD0.CMHAI1.TddA.phsA.cVal.mag.f WYE FLOAT32 MX B I1 3SMHTDD_A value of TDD 0.00...500.00 % quality\CMHAI1\Monitored
for phase A data
3 second mean Monitoring\I/O status\Power
CMHAI1 PQM3I(1) PQM3I(1) MON LD0.CMHAI1.TddA.phsB.cVal.mag.f WYE FLOAT32 MX B I1 3SMHTDD_B value of TDD 0.00...500.00 % quality\CMHAI1\Monitored
for phase B data
3 second mean Monitoring\I/O status\Power
CMHAI1 PQM3I(1) PQM3I(1) MON LD0.CMHAI1.TddA.phsC.cVal.mag.f WYE FLOAT32 MX B I1 3SMHTDD_C value of TDD 0.00...500.00 % quality\CMHAI1\Monitored
for phase C data
Demand value Monitoring\I/O status\Power
CMHAI1 PQM3I(1) PQM3I(1) MON LD0.CMHAI1.DmdTddA.phsA.cVal.mag.f WYE FLOAT32 MX B I1 DMD_TDD_A for TDD for 0.00...500.00 % quality\CMHAI1\Monitored
phase A data
Demand value Monitoring\I/O status\Power
CMHAI1 PQM3I(1) PQM3I(1) MON LD0.CMHAI1.DmdTddA.phsB.cVal.mag.f WYE FLOAT32 MX B I1 DMD_TDD_B for TDD for 0.00...500.00 % quality\CMHAI1\Monitored
phase B data
Demand value Monitoring\I/O status\Power
CMHAI1 PQM3I(1) PQM3I(1) MON LD0.CMHAI1.DmdTddA.phsC.cVal.mag.f WYE FLOAT32 MX B I1 DMD_TDD_C for TDD for 0.00...500.00 % quality\CMHAI1\Monitored
phase C data
Maximum
Max demand Monitoring\Recorded
CMHAI1 PQM3I(1) PQM3I(1) MON LD0.CMHAI1.MaxDmdTddA.phsA.cVal.mag.f WYE FLOAT32 MX B I1 demand TDD 0.00...500.00 %
TDD IL1 data\Power quality\CMHAI1
for phase A
Time of
Time max dmd maximum Monitoring\Recorded
CMHAI1 PQM3I(1) PQM3I(1) MON LD0.CMHAI1.MaxDmdTddA.phsA.t WYE Timestamp MX B
TDD IL1 demand TDD data\Power quality\CMHAI1
phase A
Maximum
Max demand Monitoring\Recorded
CMHAI1 PQM3I(1) PQM3I(1) MON LD0.CMHAI1.MaxDmdTddA.phsB.cVal.mag.f WYE FLOAT32 MX B I1 demand TDD 0.00...500.00 %
TDD IL2 data\Power quality\CMHAI1
for phase B
Time of
Time max dmd maximum Monitoring\Recorded
CMHAI1 PQM3I(1) PQM3I(1) MON LD0.CMHAI1.MaxDmdTddA.phsB.t WYE Timestamp MX B
TDD IL2 demand TDD data\Power quality\CMHAI1
phase B
Maximum
Max demand Monitoring\Recorded
CMHAI1 PQM3I(1) PQM3I(1) MON LD0.CMHAI1.MaxDmdTddA.phsC.cVal.mag.f WYE FLOAT32 MX B I1 demand TDD 0.00...500.00 %
TDD IL3 data\Power quality\CMHAI1
for phase C
Time max dmd Time of Monitoring\Recorded
CMHAI1 PQM3I(1) PQM3I(1) MON LD0.CMHAI1.MaxDmdTddA.phsC.t WYE Timestamp MX B
TDD IL3 maximum data\Power quality\CMHAI1

236
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

demand TDD
phase C
Operation Off / Settings\Settings\Power
CMHAI1 PQM3I(1) PQM3I(1) SET LD0.CMHAI1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
On quality\CMHAI1
Initial Dmd Initial demand Settings\Settings\Power
CMHAI1 PQM3I(1) PQM3I(1) SET LD0.CMHAI1.NomA.setMag.f ASG FLOAT32 SP A 1.0 0.10...1.0 xIn IL1TCTR1
current current quality\CMHAI1
TDD alarm TDD alarm Settings\Settings\Power
CMHAI1 PQM3I(1) PQM3I(1) SET LD0.CMHAI1.TddAVal.setMag.f ASG FLOAT32 SP B 50.0 1.0...100.0 %
limit limit quality\CMHAI1
0=1 minute;
1=5 minutes;
Time interval 2=10 minutes;
Demand Settings\Settings\Power
CMHAI1 PQM3I(1) PQM3I(1) SET LD0.CMHAI1.DmdItrv.setVal ENG Enum SP B 2 for demand 3=15 minutes;
interval quality\CMHAI1
calculation 4=30 minutes;
5=60 minutes;
6=180 minutes
Demand
Demand 1=Sliding; Settings\Settings\Power
CMHAI1 PQM3I(1) PQM3I(1) SET LD0.CMHAI1.DmdWinMod.setVal ENG Enum SP B 1 calculation
window 2=Non-sliding quality\CMHAI1
window type
VisString255
CMHAI1 PQM3I(1) PQM3I(1) VER LD0.CMHAI1.NamPlt.swRev LPL DC ED1 D1 (Name plate)
(20)

OLATCC1: On-load tap changer controller: D2


IEC IEC Categor Acces Defaul Even CM Channel
ANSI IECName CDC Type FC Dataset Parameter name Parameter desc Parameter range Menu path
61850 60617 y s t t T relation
OLATCC COLTC(1 90V(1 (ACT input
INP Channel U3P
1 ) ) channel)
OLATCC COLTC(1 90V(1 (ACT input
INP Channel I3P
1 ) ) channel)
OLATCC COLTC(1 90V(1 (ACT input
INP Channel TAP_POS
1 ) ) channel)
OLATCC COLTC(1 90V(1 External signal for Monitoring\I/O
INP LD0.OLATCC1.LTCBlk.stVal SPC BOOLEAN ST B 0 I1 LTC_BLOCK
1 ) ) blocking status\Control\OLATCC1\Inputs
OLATCC COLTC(1 90V(1 Reduce set voltage Monitoring\I/O
INP LD0.OLATCC1.VRed1.stVal SPC BOOLEAN ST B 0 I1 RSV
1 ) ) active status\Control\OLATCC1\Inputs
Integer value
OLATCC COLTC(1 90V(1 representing tap Monitoring\I/O
INP LD0.OLATCC1.Trf1TapPos.stVal INS INT32 ST B 0 I1 TR1_TAP_POS -36...36
1 ) ) changer position of status\Control\OLATCC1\Inputs
transformer 1
Integer value
OLATCC COLTC(1 90V(1 representing tap Monitoring\I/O
INP LD0.OLATCC1.Trf2TapPos.stVal INS INT32 ST B 0 I1 TR2_TAP_POS -36...36
1 ) ) changer position of status\Control\OLATCC1\Inputs
transformer 2
Integer value
OLATCC COLTC(1 90V(1 representing tap Monitoring\I/O
INP LD0.OLATCC1.Trf3TapPos.stVal INS INT32 ST B 0 I1 TR3_TAP_POS -36...36
1 ) ) changer position of status\Control\OLATCC1\Inputs
transformer 3

237
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

(Change follower
OLATCC COLTC(1 90V(1
INP LD0.OLATCC1.TapChgFllw.stVal INS INT32 ST 0 I1 tap position (stop,
1 ) )
lower, higher))
Network
OLATCC COLTC(1 90V(1 connection status of Monitoring\I/O
INP LD0.OLATCC1.InConSt.stVal SPS BOOLEAN ST B 0 I1 CON_STATUS
1 ) ) the (own) status\Control\OLATCC1\Inputs
transformer
OLATCC COLTC(1 90V(1 Tap changer Monitoring\I/O
INP LD0.OLATCC1.InLTCOp.stVal SPS BOOLEAN ST B 0 I1 TCO
1 ) ) operating input status\Control\OLATCC1\Inputs
Received current
OLATCC COLTC(1 90V(1 CM M Monitoring\I/O
INP LD0.OLATCC1.Trf1A.cVal.mag.f FLOAT32 B 0.00 I1 TR1_I_AMPL magnitude from 0.00...15000.00 A
1 ) ) V X status\Control\OLATCC1\Inputs
transformer 1
Received current
OLATCC COLTC(1 90V(1 CM M -180.00...180.00 Monitoring\I/O
INP LD0.OLATCC1.Trf1A.cVal.ang.f FLOAT32 B 0.0 TR1_I_ANGL angle from
1 ) ) V X deg status\Control\OLATCC1\Inputs
transformer 1
Received current
OLATCC COLTC(1 90V(1 CM M Monitoring\I/O
INP LD0.OLATCC1.Trf2A.cVal.mag.f FLOAT32 B 0.00 I1 TR2_I_AMPL magnitude from 0.00...15000.00 A
1 ) ) V X status\Control\OLATCC1\Inputs
transformer 2
Received current
OLATCC COLTC(1 90V(1 CM M -180.00...180.00 Monitoring\I/O
INP LD0.OLATCC1.Trf2A.cVal.ang.f FLOAT32 B 0.0 TR2_I_ANGL angle from
1 ) ) V X deg status\Control\OLATCC1\Inputs
transformer 2
Received current
OLATCC COLTC(1 90V(1 CM M Monitoring\I/O
INP LD0.OLATCC1.Trf3A.cVal.mag.f FLOAT32 B 0.00 I1 TR3_I_AMPL magnitude from 0.00...15000.00 A
1 ) ) V X status\Control\OLATCC1\Inputs
transformer 3
Received current
OLATCC COLTC(1 90V(1 CM M -180.00...180.00 Monitoring\I/O
INP LD0.OLATCC1.Trf3A.cVal.ang.f FLOAT32 B 0.0 TR3_I_ANGL angle from
1 ) ) V X deg status\Control\OLATCC1\Inputs
transformer 3
Raise command
OLATCC COLTC(1 90V(1 Monitoring\I/O
INP LD0.OLATCC1.TapChgR.stVal SPS BOOLEAN ST B 0 I1 RAISE_LOCAL input from
1 ) ) status\Control\OLATCC1\Inputs
configuration
Lower command
OLATCC COLTC(1 90V(1 LOWER_LOCA Monitoring\I/O
INP LD0.OLATCC1.TapChgL.stVal SPS BOOLEAN ST B 0 I1 input from
1 ) ) L status\Control\OLATCC1\Inputs
configuration
OLATCC COLTC(1 90V(1 (Input auto
INP LD0.OLATCC1.InAuto.stVal SPS BOOLEAN ST 0 I1
1 ) ) operation)
OLATCC COLTC(1 90V(1 (Input parallel
INP LD0.OLATCC1.InParOp.stVal SPS BOOLEAN ST 0 I1
1 ) ) operation )
Integer value
OLATCC COLTC(1 90V(1 LD0.OLATCC1.TapChg.valWTr.pos representing tap Monitoring\I/O
OUT BSC INT8 ST B TR0_TAP_POS -36...36
1 ) ) Val changer position of status\Control\OLATCC1\Outputs
own transformer
Monitoring\I/O
OLATCC COLTC(1 90V(1 StatNrm Parallel or single
OUT LD0.OLATCC1.ParOp.stVal SPC BOOLEAN ST B P,H I1 PARALLEL status\Control\OLATCC1\Monitor
1 ) ) l operation
ed data
Monitoring\I/O
OLATCC COLTC(1 90V(1 StatNrm Auto/Manual
OUT LD0.OLATCC1.Auto.stVal SPC BOOLEAN ST B P,H I1 AUTO status\Control\OLATCC1\Monitor
1 ) ) l indication
ed data
OLATCC COLTC(1 90V(1 Monitoring\I/O
OUT LD0.OLATCC1.TapOpErr.stVal SPS BOOLEAN ST B StatUrg P,H I1 ALARM Alarm status
1 ) ) status\Control\OLATCC1\Outputs
238
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

OLATCC COLTC(1 90V(1 Raise command for Monitoring\I/O


OUT LD0.OLATCC1.TapOpR.stVal SPS BOOLEAN ST B StatIO P,T I1 RAISE_OWN
1 ) ) own transformer status\Control\OLATCC1\Outputs
OLATCC COLTC(1 90V(1 Lower command Monitoring\I/O
OUT LD0.OLATCC1.TapOpL.stVal SPS BOOLEAN ST B StatIO P,T I1 LOWER_OWN
1 ) ) for own transformer status\Control\OLATCC1\Outputs
Monitoring\I/O
OLATCC COLTC(1 90V(1 Indication of over
OUT LD0.OLATCC1.LTCBlkAHi.stVal SPS BOOLEAN ST B StatUrg P,H I1 BLKD_I_LOD status\Control\OLATCC1\Monitor
1 ) ) current blocking
ed data
Monitoring\I/O
OLATCC COLTC(1 90V(1 Indication of under
OUT LD0.OLATCC1.LTCBlkVLo.stVal SPS BOOLEAN ST B StatUrg P,H I1 BLKD_U_UN status\Control\OLATCC1\Monitor
1 ) ) voltage blocking
ed data
Monitoring\I/O
OLATCC COLTC(1 90V(1 Indication of
OUT LD0.OLATCC1.Blk.stVal SPS BOOLEAN ST B StatUrg P,H I1 BLKD_LTCBLK status\Control\OLATCC1\Monitor
1 ) ) external blocking
ed data
OLATCC COLTC(1 90V(1 Parallel failure Monitoring\I/O
OUT LD0.OLATCC1.ErrPar.stVal SPS BOOLEAN ST B StatUrg P,H I1 PAR_FAIL
1 ) ) detected status\Control\OLATCC1\Outputs
Lower/Raise
command for
OLATCC COLTC(1 90V(1 follower Monitoring\I/O
OUT LD0.OLATCC1.TapOpFllw1.stVal INS INT32 ST B I1 FLLW1_CTL 0...2
1 ) ) transformer 1 in the status\Control\OLATCC1\Outputs
Master/Follower
operation mode
Lower/Raise
command for
OLATCC COLTC(1 90V(1 follower Monitoring\I/O
OUT LD0.OLATCC1.TapOpFllw2.stVal INS INT32 ST B I1 FLLW2_CTL 0...2
1 ) ) transformer 2 in the status\Control\OLATCC1\Outputs
Master/Follower
operation mode
Lower/Raise
command for
OLATCC COLTC(1 90V(1 follower Monitoring\I/O
OUT LD0.OLATCC1.TapOpFllw3.stVal INS INT32 ST B I1 FLLW3_CTL 0...2
1 ) ) transformer 3 in the status\Control\OLATCC1\Outputs
Master/Follower
operation mode
OLATCC COLTC(1 90V(1 CM M Transmitted current Monitoring\I/O
OUT LD0.OLATCC1.LodAVec.cVal.mag.f FLOAT32 B I1 TR0_I_AMPL 0.00...15000.00 A
1 ) ) V X magnitude status\Control\OLATCC1\Outputs
OLATCC COLTC(1 90V(1 CM M Transmitted current -180.00...180.00 Monitoring\I/O
OUT LD0.OLATCC1.LodAVec.cVal.ang.f FLOAT32 B TR0_I_ANGL
1 ) ) V X angle deg status\Control\OLATCC1\Outputs
Monitoring\I/O
OLATCC COLTC(1 90V(1 Indication of raise
OUT LD0.OLATCC1.LTCRnbk.stVal SPS BOOLEAN ST B StatUrg P,H I1 RNBK_U_OV status\Control\OLATCC1\Monitor
1 ) ) voltage runback
ed data
Indication of high Monitoring\I/O
OLATCC COLTC(1 90V(1
OUT LD0.OLATCC1.CircAHiBlk.stVal SPS BOOLEAN ST B StatUrg P,H I1 BLKD_I_CIR circulating current status\Control\OLATCC1\Monitor
1 ) )
blocking ed data
OLATCC COLTC(1 90V(1
OUT LD0.OLATCC1.CtlDlSt.stVal SPS BOOLEAN ST I1 (Timer on)
1 ) )
0=Cancel;
OLATCC COLTC(1 90V(1
CTR LD0.OLATCC1.TapChg.Oper.ctlVal BSC Tcmd CO B 0 I1 Manual control Manual control 1=Lower; Control\OLATCC1
1 ) )
2=Raise

239
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

OLATCC COLTC(1 90V(1 (Parallel/Independe


CTR LD0.OLATCC1.ParOp.Oper.ctlVal SPC BOOLEAN CO I1
1 ) ) nt operation)
OLATCC COLTC(1 90V(1 (Automatic/Manual
CTR LD0.OLATCC1.Auto.Oper.ctlVal SPC BOOLEAN CO I1
1 ) ) operation)
OLATCC COLTC(1 90V(1 OLATCC1 OLATCC1 counter 0=Cancel;
CTR LD0.OLATCC1.CntRs.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Clear\Clear
1 ) ) counter reset 1=Clear
1=on; 2=blocked;
OLATCC COLTC(1 90V(1 3=test;
MON LD0.OLATCC1.Beh.stVal ENS Enum ST B OLATCC1 Status Monitoring\FB status
1 ) ) 4=test/blocked;
5=off
Total number of
raise and lower Monitoring\I/O
OLATCC COLTC(1 90V(1
MON LD0.OLATCC1.OpCntRs.stVal INC INT32 ST B I1 OPR_CNT commands given in 0...2147483647 status\Control\OLATCC1\Monitor
1 ) )
the manual and ed data
automatic modes
Control voltage, Monitoring\I/O
OLATCC COLTC(1 90V(1 M
MON LD0.OLATCC1.CtlV.mag.f MV FLOAT32 B I1 U_CTL Up, target voltage 0.000...3.000 xUn status\Control\OLATCC1\Monitor
1 ) ) X
level ed data
Calculated
circulating current - Monitoring\I/O
OLATCC COLTC(1 90V(1 M
MON LD0.OLATCC1.CircA.mag.f MV FLOAT32 B I1 I_CIR calculated in -10.00...10.00 xIn status\Control\OLATCC1\Monitor
1 ) ) X
operation modes ed data
NRP and MCC
Phase-to-phase Monitoring\I/O
OLATCC COLTC(1 90V(1 M UL1TVTR
MON LD0.OLATCC1.VMeas.mag.f MV FLOAT32 B I1 U_MEAS voltage, average 0.00...5.00 xUn status\Control\OLATCC1\Monitor
1 ) ) X 1
filtered ed data
Measured angle
Monitoring\I/O
OLATCC COLTC(1 90V(1 M value between
MON LD0.OLATCC1.AngVAPhA.mag.f MV FLOAT32 B I1 ANGL_UA_IA -180...180 deg status\Control\OLATCC1\Monitor
1 ) ) X phase A voltage
ed data
and current
0=Timer off;
1=Lower timer1
on; 2=Raise
Timer T1, T2 or Monitoring\I/O
OLATCC COLTC(1 90V(1 timer1 on;
MON LD0.OLATCC1.CtlDlOn.stVal ENS Enum ST B StatIed P,H I1 TIMER_STS fast lower timer status\Control\OLATCC1\Monitor
1 ) ) 3=Lower timer2
active ed data
on; 4=Raise
timer2 on; 5=Fast
lower T on
0=Not in use;
1=Manual;
The acting Monitoring\I/O
OLATCC COLTC(1 90V(1 StatNrm OPR_MODE_ST 2=Auto single;
MON LD0.OLATCC1.CtlOpModSt.stVal ENS Enum ST B P,H I1 operation mode of status\Control\OLATCC1\Monitor
1 ) ) l S 3=Auto master;
the function block ed data
4=Auto follower;
5=MCC; 6=NRP
Voltage difference
Monitoring\I/O
OLATCC COLTC(1 90V(1 M between Measured -2.000...2.000
MON LD0.OLATCC1.CtlVDif.mag.f MV FLOAT32 B I1 UD_CTL status\Control\OLATCC1\Monitor
1 ) ) X voltage - Control xUn
ed data
Voltage: Um - Up

240
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Monitoring\I/O
OLATCC COLTC(1 90V(1 M Calculated line drop
MON LD0.OLATCC1.ClcLDC.mag.f MV FLOAT32 B I1 LDC -2.00...2.00 xUn status\Control\OLATCC1\Monitor
1 ) ) X compensation
ed data
Bit-coded output
Monitoring\I/O
OLATCC COLTC(1 90V(1 showing the
MON LD0.OLATCC1.BlkSt.stVal INS INT32 ST B I1 BLK_STATUS 0...127 status\Control\OLATCC1\Monitor
1 ) ) blocking status for
ed data
the next operation
0=No alarm;
1=Cmd error;
2=TCO error;
3=Cmd + TCO
Monitoring\I/O
OLATCC COLTC(1 90V(1 Status and reason err; 4=Pump
MON LD0.OLATCC1.AlmReas.stVal ENS Enum ST B I1 ALARM_REAS status\Control\OLATCC1\Monitor
1 ) ) for alarm error; 5=Pump +
ed data
cmd err; 6=Pump
+ TCO err;
7=Pmp+TCO+cm
d err
0=No failed
followers;
1=Follower 1;
2=Follower 2;
Monitoring\I/O
OLATCC COLTC(1 90V(1 3=Followers 1+2;
MON LD0.OLATCC1.FllwFlt.stVal ENS Enum ST B I1 FAIL_FLLW Failed followers status\Control\OLATCC1\Monitor
1 ) ) 4=Follower 3;
ed data
5=Followers 1+3;
6=Followers 2+3;
7=Followers
1+2+3
0=No parall units;
1=Trafo 1;
2=Trafo 2;
Parallel units Monitoring\I/O
OLATCC COLTC(1 90V(1 PAR_UNIT_MC 3=Trafos 1 and 2;
MON LD0.OLATCC1.NumParUnit.stVal ENS Enum ST B I1 included in MCC status\Control\OLATCC1\Monitor
1 ) ) C 4=Trafo 3;
calculation ed data
5=Trafos 1 and 3;
6=Trafos 2 and 3;
7=Trafos 1+2+3
Number of controls Monitoring\I/O
OLATCC COLTC(1 90V(1 OP_TM_NUM_
MON LD0.OLATCC1.OpTmhNum.stVal INS INT32 ST B I1 for own tap changer 0...2147483647 status\Control\OLATCC1\Monitor
1 ) ) H
during last hour ed data
OLATCC COLTC(1 90V(1 Settings\Settings\Control\OLATC
SET LD0.OLATCC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation Operation Off / On 1=on; 5=off
1 ) ) C1
OLATCC COLTC(1 90V(1 Band center Band center voltage Settings\Settings\Control\OLATC
SET LD0.OLATCC1.BndCtr.setMag.f ASG FLOAT32 SG B 1.000 0.000...2.000 xUn
1 ) ) voltage Us C1
Allowed deviation
OLATCC COLTC(1 90V(1 Band width Settings\Settings\Control\OLATC
SET LD0.OLATCC1.BndWid.setMag.f ASG FLOAT32 SP B 3.00 of the control 1.20...18.00 %Un
1 ) ) voltage C1
voltage
Control delay time
OLATCC COLTC(1 90V(1 Control delay Settings\Settings\Control\OLATC
SET LD0.OLATCC1.CtlDlTmms.setVal ING INT32 SG B 60000 for the first control 1000...300000 ms
1 ) ) time 1 C1
pulse
Control delay time
OLATCC COLTC(1 90V(1 Control delay Settings\Settings\Control\OLATC
SET LD0.OLATCC1.CtlDl2Tmms.setVal ING INT32 SG B 30000 for the following 1000...300000 ms
1 ) ) time 2 C1
control pulses
241
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Resistive line-drop
OLATCC COLTC(1 90V(1 Settings\Settings\Control\OLATC
SET LD0.OLATCC1.LDCR.setMag.f ASG FLOAT32 SG B 0.0 Line drop V Ris compensation 0.0...25.0 %
1 ) ) C1
factor
Reactive line-drop
OLATCC COLTC(1 90V(1 Line drop V Settings\Settings\Control\OLATC
SET LD0.OLATCC1.LDCX.setMag.f ASG FLOAT32 SG B 0.0 compensation 0.0...25.0 %
1 ) ) React C1
factor
Voltage limit,
OLATCC COLTC(1 90V(1 where fast lower Settings\Settings\Control\OLATC
SET LD0.OLATCC1.RnbkRV.setMag.f ASG FLOAT32 SP B 1.25 Runback raise V 0.80...2.40 xUn
1 ) ) commands takes C1
place
OLATCC COLTC(1 90V(1 Load current Load current Settings\Settings\Control\OLATC
SET LD0.OLATCC1.LimLodA.setMag.f ASG FLOAT32 SP B 2.00 0.10...5.00 xIn
1 ) ) limit blocking limit C1
OLATCC COLTC(1 90V(1 Delay Selection of delay 0=Inverse time; Settings\Settings\Control\OLATC
SET LD0.OLATCC1.TmDlChr.setVal SPG BOOLEAN SP B 1
1 ) ) characteristic characteristic 1=Definite time C1
OLATCC COLTC(1 90V(1 Step size for reduce Settings\Settings\Control\OLATC
SET LD0.OLATCC1.VRedVal.setMag.f ASG FLOAT32 SG B 0.00 Band reduction 0.00...9.00 %Un
1 ) ) set voltage (RSV) C1
Tap changer limit
position which
OLATCC COLTC(1 90V(1 Settings\Settings\Control\OLATC
SET LD0.OLATCC1.TapBlkR.setVal ING INT32 SP B 17 Raise block tap gives highest -36...36
1 ) ) C1
voltage on the
regulated side
Tap changer limit
position which
OLATCC COLTC(1 90V(1 Settings\Settings\Control\OLATC
SET LD0.OLATCC1.TapBlkL.setVal ING INT32 SP B 0 Lower block tap gives lowest -36...36
1 ) ) C1
voltage on the
regulated side
Voltage limit,
where further
OLATCC COLTC(1 90V(1 Block lower Settings\Settings\Control\OLATC
SET LD0.OLATCC1.BlkVLo.setMag.f ASG FLOAT32 SP B 0.70 voltage lowering 0.10...1.20 xUn
1 ) ) voltage C1
commands are
blocked
2=Auto master;
OLATCC COLTC(1 90V(1 Auto parallel Parallel mode Settings\Settings\Control\OLATC
SET LD0.OLATCC1.ParTrfMod.setVal ENG Enum SG B 2 3=Auto follower;
1 ) ) mode selection C1
5=NRP; 7=MCC
Load phase-shift,
OLATCC COLTC(1 90V(1 used only with the Settings\Settings\Control\OLATC
SET LD0.OLATCC1.LodPhAng.setMag.f ASG FLOAT32 SG B 0 Load phase angle -89...89 deg
1 ) ) negative reactance C1
principle
OLATCC COLTC(1 90V(1 Stability factor in Settings\Settings\Control\OLATC
SET LD0.OLATCC1.StabFact.setMag.f ASG FLOAT32 SG B 0.0 Stability factor 0.0...70.0 %
1 ) ) parallel operation C1
1=Manual;
2=Auto single;
OLATCC COLTC(1 90V(1 Settings\Settings\Control\OLATC
SET LD0.OLATCC1.VCtlOpMod.setVal ENG Enum SP B 5 Operation mode The operation mode 3=Auto parallel;
1 ) ) C1
4=Input control;
5=Command
Output pulse
OLATCC COLTC(1 90V(1 duration, common Settings\Settings\Control\OLATC
SET LD0.OLATCC1.LTCPlsTmms.setVal ING INT32 SP B 1500 LTC pulse time 500...10000 ms
1 ) ) for raise and lower C1
pulses

242
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

1=Custom
disabled; 2=OC;
3=UV; 4=OC,
OLATCC COLTC(1 90V(1 Custom Man Customized manual Settings\Settings\Control\OLATC
SET LD0.OLATCC1.ManBlkTyp.setVal ENG Enum SP B 2 UV; 5=EXT;
1 ) ) blocking blocking C1
6=OC, EXT;
7=UV, EXT;
8=OC, UV, EXT
Blocking limit for
OLATCC COLTC(1 90V(1 Settings\Settings\Control\OLATC
SET LD0.OLATCC1.LimCircA.setMag.f ASG FLOAT32 SP B 0.15 Cir current limit high circulating 0.10...5.00 xIn
1 ) ) C1
current
Maximum limit for
OLATCC COLTC(1 90V(1 Settings\Settings\Control\OLATC
SET LD0.OLATCC1.LimLDC.setMag.f ASG FLOAT32 SP B 0.10 LDC limit line drop 0.00...2.00 xUn
1 ) ) C1
compensation term
OLATCC COLTC(1 90V(1 Selection for line Settings\Settings\Control\OLATC
SET LD0.OLATCC1.LDCEna.setVal SPG BOOLEAN SP B 1 LDC enable
1 ) ) drop compensation C1
OLATCC COLTC(1 90V(1 Rv Pwr flow Reverse power flow Settings\Settings\Control\OLATC
SET LD0.OLATCC1.RPFAllw.setVal SPG BOOLEAN SP A 0
1 ) ) allowed allowed C1
Allowed number of
OLATCC COLTC(1 90V(1 Max operations controls per one Settings\Settings\Control\OLATC
SET LD0.OLATCC1.OpTmhMax.setVal ING INT32 SP A 100 0...10000
1 ) ) in 1h hour sliding C1
window
Time delay before
OLATCC COLTC(1 90V(1 Cmd error delay Settings\Settings\Control\OLATC
SET LD0.OLATCC1.CmdErrTms.setVal ING INT32 SP A 20 command error will 10...50 s
1 ) ) time C1
be activated
Time delay between
OLATCC COLTC(1 90V(1 Follower delay successive follower Settings\Settings\Control\OLATC
SET LD0.OLATCC1.FllwDlTms.setVal ING INT32 SP A 6 6...20 s
1 ) ) time commands by a C1
master
OLATCC COLTC(1 90V(1 Settings\Settings\Control\OLATC
SET LD0.OLATCC1.AlmEna.setVal SPG BOOLEAN SP A 1 Alarms enabled Alarm selection
1 ) ) C1
Number of parallel
OLATCC COLTC(1 90V(1 transformers in Settings\Settings\Control\OLATC
SET LD0.OLATCC1.ParTrfNum.setVal ING INT32 SP B,I 0 Parallel trafos 0...10
1 ) ) addition to own C1
transformer
0=Reset;
3=Activate
ALARM;
4=Deactive
ALARM;
23=Activate
RAISE;
24=Deactive
OLATCC COLTC(1 90V(1 Test control for
TES LD0.OLATCC1.TestCtl.Oper.ctlVal ENC Enum CO B 1 OLATCC1 RAISE; Tests\Function tests\Control
1 ) ) outputs
27=Activate
LOWER;
28=Deactive
LOWER;
27=Activate
PAR_FAIL;
28=Deactive
PAR_FAIL
243
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

OLATCC COLTC(1 90V(1 VisString25


VER LD0.OLATCC1.NamPlt.swRev LPL DC D2 (Name plate)
1 ) ) 5 (20)

TPOSYLTC1: Tap changer position indication: D1


Channe
Categor CD Acces Defaul Even CM Parameter Paramete Parameter
IEC 61850 IEC 60617 ANSI IECName Type FC Dataset Menu path l
y C s t t T name r desc range
relation
Tap Monitoring\I/O
TPOSYLTC TPOSM(1 84M(1 LD0.TPOSYLTC1.TapPos.valWTr.posVa StatUr
INP ISC INT8 ST B 0 P,H I1 TAP_POS position -63...63 status\Measurements\TPOSYLTC1\Monitore
1 ) ) l g
indication d data
End
position
raise or
TPOSYLTC TPOSM(1 84M(1 END_POS_ highest Monitoring\I/O
INP LD0.TPOSYLTC1.EndPosR.stVal SPS BOOLEAN ST B 0 I1
1 ) ) R allowed status\Measurements\TPOSYLTC1\Inputs
tap
position
reached
End
position
lower or
TPOSYLTC TPOSM(1 84M(1 lowest Monitoring\I/O
INP LD0.TPOSYLTC1.EndPosL.stVal SPS BOOLEAN ST B 0 I1 END_POS_L
1 ) ) allowed status\Measurements\TPOSYLTC1\Inputs
tap
position
reached
TPOSYLTC TPOSM(1 84M(1 Binary Monitoring\I/O
INP LD0.TPOSYLTC1.InBit1.stVal SPS BOOLEAN ST B 0 I1 BI0
1 ) ) input 1 status\Measurements\TPOSYLTC1\Inputs
TPOSYLTC TPOSM(1 84M(1 Binary Monitoring\I/O
INP LD0.TPOSYLTC1.InBit2.stVal SPS BOOLEAN ST B 0 I1 BI1
1 ) ) input 2 status\Measurements\TPOSYLTC1\Inputs
TPOSYLTC TPOSM(1 84M(1 Binary Monitoring\I/O
INP LD0.TPOSYLTC1.InBit3.stVal SPS BOOLEAN ST B 0 I1 BI2
1 ) ) input 3 status\Measurements\TPOSYLTC1\Inputs
TPOSYLTC TPOSM(1 84M(1 Binary Monitoring\I/O
INP LD0.TPOSYLTC1.InBit4.stVal SPS BOOLEAN ST B 0 I1 BI3
1 ) ) input 4 status\Measurements\TPOSYLTC1\Inputs
TPOSYLTC TPOSM(1 84M(1 Binary Monitoring\I/O
INP LD0.TPOSYLTC1.InBit5.stVal SPS BOOLEAN ST B 0 I1 BI4
1 ) ) input 5 status\Measurements\TPOSYLTC1\Inputs
TPOSYLTC TPOSM(1 84M(1 Binary Monitoring\I/O
INP LD0.TPOSYLTC1.InBit6.stVal SPS BOOLEAN ST B 0 I1 BI5
1 ) ) input 6 status\Measurements\TPOSYLTC1\Inputs
Binary
TPOSYLTC TPOSM(1 84M(1 Monitoring\I/O
INP LD0.TPOSYLTC1.InBit7.stVal SPS BOOLEAN ST B 0 I1 SIGN_BIT input sign
1 ) ) status\Measurements\TPOSYLTC1\Inputs
bit
(ACT
TPOSYLTC TPOSM(1 84M(1
OUT Channel TAP_POS output
1 ) )
channel)
TPOSYLTC TPOSM(1 84M(1 C Operation
CFG LD0.TPOSYLTC1.Mod.Oper.ctlVal ENC Enum B,I 1 Operation 1=on; 5=off Configuration\Measurements\TPOSYLTC1
1 ) ) O Off / On

244
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

1=NAT2INT;
Operation
TPOSYLTC TPOSM(1 84M(1 EN Operation 2=BCD2INT;
CFG LD0.TPOSYLTC1.BinCdMod.setVal Enum SP B 2 mode Configuration\Measurements\TPOSYLTC1
1 ) ) G mode 3=GRAY2IN
selection
T
TPOSYLTC TPOSM(1 84M(1 VisString25 D (Name
VER LD0.TPOSYLTC1.NamPlt.swRev LPL D1
1 ) ) 5 (20) C plate)

ARCSARC1: Arc protection: B1


IEC Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter name Parameter range Menu path
60617 desc relation
(ACT
ARCSARC1 ARC(1) 50L/50NL(1) INP Channel I3P input
channel)
(ACT
ARCSARC1 ARC(1) 50L/50NL(1) INP Channel IRES input
channel)
Block
signal for Monitoring\I/O status\Other
ARCSARC1 ARC(1) 50L/50NL(1) INP LD0.ARCSARC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
all binary protection\ARCSARC1\Inputs
outputs
Remote
Monitoring\I/O status\Other
ARCSARC1 ARC(1) 50L/50NL(1) INP LD0.ARCSARC1.InRemFA.stVal SPS BOOLEAN ST B 0 I1 REM_FLT_ARC Fault arc
protection\ARCSARC1\Inputs
detected
Operation
Monitoring\I/O status\Other
ARCSARC1 ARC(1) 50L/50NL(1) INP LD0.ARCPTRC1.InOpMod.stVal SPS BOOLEAN ST B 0 I1 OPR_MODE mode
protection\ARCSARC1\Inputs
input
Monitoring\I/O status\Other
ARCSARC1 ARC(1) 50L/50NL(1) OUT LD0.ARCPTRC1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate
protection\ARCSARC1\Outputs
(Fault arc
ARCSARC1 ARC(1) 50L/50NL(1) CTR INT32
counter)
1=on;
2=blocked;
ARCSARC1 ARC(1) 50L/50NL(1) MON LD0.ARCSARC1.Beh.stVal ENS Enum ST B ARCSARC1 Status 3=test; Monitoring\FB status
4=test/blocked;
5=off
(Fault arc
ARCSARC1 ARC(1) 50L/50NL(1) MON BOOLEAN StatIed P,H
detected)
Operation Settings\Settings\Other
ARCSARC1 ARC(1) 50L/50NL(1) SET LD0.ARCSARC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
Off / On protection\ARCSARC1
Operating
Settings\Settings\Other
ARCSARC1 ARC(1) 50L/50NL(1) SET LD0.ARC1PIOC1.StrVal.setMag.f ASG FLOAT32 SG B 2.50 Phase start value phase 0.50...40.00 xIn IL1TCTR1
protection\ARCSARC1
current
Operating
Ground start Settings\Settings\Other
ARCSARC1 ARC(1) 50L/50NL(1) SET LD0.ARC2PIOC1.StrVal.setMag.f ASG FLOAT32 SG B 0.20 residual 0.05...8.00 xIn RESTCTR1
value protection\ARCSARC1
current

245
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

1=Light+current;
Operation Settings\Settings\Other
ARCSARC1 ARC(1) 50L/50NL(1) SET LD0.ARCPTRC1.OpModArc.setVal ENG Enum SG B 1 Operation mode 2=Light only;
mode protection\ARCSARC1
3=BI controlled
0=Reset;
Test
9=Activate
control Tests\Function tests\Other
ARCSARC1 ARC(1) 50L/50NL(1) TES LD0.ARCSARC1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 ARCSARC1 OPERATE;
for protection
10=Deactive
outputs
OPERATE
VisString255 (Name
ARCSARC1 ARC(1) 50L/50NL(1) VER LD0.ARCSARC1.NamPlt.swRev LPL DC ED1 B1
(20) plate)

LSHDPFRQ1: Load shedding: C1


Channe
Categor Acces Defaul CM Parameter Parameter
IEC 61850 IEC 60617 ANSI IECName CDC Type FC Dataset Event Parameter name Menu path l
y s t T desc range
relation
LSHDPFRQ UFLS/R(1 81LSH(1 (ACT input
INP Channel U3P
1 ) ) channel)
Block
signal for
LSHDPFRQ UFLS/R(1 81LSH(1 Monitoring\I/O status\Frequency
INP LD0.LSHDPTRC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK activating
1 ) ) protection\LSHDPFRQ1\Inputs
the blocking
mode
Manual
LSHDPFRQ UFLS/R(1 81LSH(1 MAN_RESTOR Monitoring\I/O status\Frequency
INP LD0.LSHDPTOF1.ManRest.stVal SPC BOOLEAN ST B 0 I1 restore
1 ) ) E protection\LSHDPFRQ1\Inputs
signal
LSHDPFRQ UFLS/R(1 81LSH(1 Block Monitoring\I/O status\Frequency
INP LD0.LSHDPTOF1.BlkRest.stVal SPC BOOLEAN ST B 0 I1 BLK_REST
1 ) ) restore protection\LSHDPFRQ1\Inputs
Operation
LSHDPFRQ UFLS/R(1 81LSH(1 StatNrm P,H, Monitoring\I/O status\Frequency
OUT LD0.LSHDPTRC1.Op.general ACT BOOLEAN ST B I1 OPERATE of load
1 ) ) l T protection\LSHDPFRQ1\Outputs
shedding
LSHDPFRQ UFLS/R(1 81LSH(1 AC StatNrm Monitoring\I/O status\Frequency
OUT LD0.LSHDPTRC1.Str.general BOOLEAN ST B P,H I1 START Start
1 ) ) D l protection\LSHDPFRQ1\Outputs
Pick-Up
signal for
LSHDPFRQ UFLS/R(1 81LSH(1 AC Monitoring\I/O status\Frequency
OUT LD0.LSHDPTUF1.Str.general BOOLEAN ST B I1 ST_FRQ under
1 ) ) D protection\LSHDPFRQ1\Outputs
frequency
detection
Operate
LSHDPFRQ UFLS/R(1 81LSH(1 signal for Monitoring\I/O status\Frequency
OUT LD0.LSHDPTUF1.Op.general ACT BOOLEAN ST B I1 OPR_FRQ
1 ) ) under protection\LSHDPFRQ1\Outputs
frequency
Pick-Up
LSHDPFRQ UFLS/R(1 81LSH(1 AC signal for Monitoring\I/O status\Frequency
OUT LD0.LSHDPFRC1.Str.general BOOLEAN ST B I1 ST_FRG
1 ) ) D high df/dt protection\LSHDPFRQ1\Outputs
detection

246
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Operate
LSHDPFRQ UFLS/R(1 81LSH(1 Monitoring\I/O status\Frequency
OUT LD0.LSHDPFRC1.Op.general ACT BOOLEAN ST B I1 OPR_FRG signal for
1 ) ) protection\LSHDPFRQ1\Outputs
high df/dt
Restore
frequency
LSHDPFRQ UFLS/R(1 81LSH(1 AC StatNrm attained and Monitoring\I/O status\Frequency
OUT LD0.LSHDPTOF1.Str.general BOOLEAN ST B P,H I1 ST_REST
1 ) ) D l restore protection\LSHDPFRQ1\Outputs
timer
started
Restore
signal for
LSHDPFRQ UFLS/R(1 81LSH(1 StatNrm P,H, Monitoring\I/O status\Frequency
OUT LD0.LSHDPTOF1.Op.general ACT BOOLEAN ST B I1 RESTORE load
1 ) ) l T protection\LSHDPFRQ1\Outputs
restoring
purposes
(Manual
LSHDPFRQ UFLS/R(1 81LSH(1
CTR LD0.LSHDPTOF1.ManRest.Oper.ctlVal SPC BOOLEAN CO I1 restore
1 ) )
command)
LSHDPFRQ UFLS/R(1 81LSH(1 (Cancel
CTR LD0.LSHDPTOF1.BlkRest.Oper.ctlVal SPC BOOLEAN CO I1
1 ) ) restore)
1=on;
2=blocked;
LSHDPFRQ UFLS/R(1 81LSH(1
MON LD0.LSHDPTRC1.Beh.stVal ENS Enum ST B LSHDPFRQ1 Status 3=test; Monitoring\FB status
1 ) )
4=test/blocked
; 5=off
Monitoring\I/O status\Frequency
LSHDPFRQ UFLS/R(1 81LSH(1 M Start 0.00...100.00
MON LD0.LSHDPTRC1.StrDur.mag.f MV FLOAT32 B START_DUR protection\LSHDPFRQ1\Monitore
1 ) ) X duration %
d data
LSHDPFRQ UFLS/R(1 81LSH(1 Operation Settings\Settings\Frequency
SET LD0.LSHDPTRC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
1 ) ) Off / On protection\LSHDPFRQ1
LSHDPFRQ UFLS/R(1 81LSH(1 Restore delay Time delay 80...200000 Settings\Settings\Frequency
SET LD0.LSHDPTRC1.OpDlTmms.setVal ING INT32 SG B 300
1 ) ) time to restore ms protection\LSHDPFRQ1
Time delay
after which
LSHDPFRQ UFLS/R(1 81LSH(1 Settings\Settings\Frequency
SET LD0.LSHDPTRC1.RsDlTmms.setVal ING INT32 SP A 50 Reset delay time the definite 0...60000 ms
1 ) ) protection\LSHDPFRQ1
timers will
reset
Set the
operation 1=Freq<;
LSHDPFRQ UFLS/R(1 81LSH(1 mode for 6=Freq< OR Settings\Settings\Frequency
SET LD0.LSHDPTRC1.LodShdMod.setVal ENG Enum SG B 1 Load shed mode
1 ) ) load df/dt; 8=Freq< protection\LSHDPFRQ1
shedding AND df/dt
function
Frequency
LSHDPFRQ UFLS/R(1 81LSH(1 0.800...1.200 Settings\Settings\Frequency
SET LD0.LSHDPTUF1.StrVal.setMag.f ASG FLOAT32 SG B 0.975 Start value Freq setting/start
1 ) ) xFn protection\LSHDPFRQ1
value
Time delay
to operate
LSHDPFRQ UFLS/R(1 81LSH(1 80...200000 Settings\Settings\Frequency
SET LD0.LSHDPTUF1.OpDlTmms.setVal ING INT32 SG B 200 Operate Tm Freq for under
1 ) ) ms protection\LSHDPFRQ1
frequency
stage
247
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Setting of
frequency
LSHDPFRQ UFLS/R(1 81LSH(1 -0.200...-0.005 Settings\Settings\Frequency
SET LD0.LSHDPFRC1.StrVal.setMag.f ASG FLOAT32 SG B -0.010 Start value df/dt gradient for
1 ) ) xFn /s protection\LSHDPFRQ1
df/dt
detection
Time delay
LSHDPFRQ UFLS/R(1 81LSH(1 to operate 120...200000 Settings\Settings\Frequency
SET LD0.LSHDPFRC1.OpDlTmms.setVal ING INT32 SG B 200 Operate Tm df/dt
1 ) ) for df/dt ms protection\LSHDPFRQ1
stage
Restore
LSHDPFRQ UFLS/R(1 81LSH(1 frequency 0.800...1.200 Settings\Settings\Frequency
SET LD0.LSHDPTOF1.StrVal.setMag.f ASG FLOAT32 SG B 0.998 Restore start Val
1 ) ) setting xFn protection\LSHDPFRQ1
value
Mode of
operation of 1=Disabled;
LSHDPFRQ UFLS/R(1 81LSH(1 Settings\Settings\Frequency
SET LD0.LSHDPTOF1.RestMod.setVal ENG Enum SG B 1 Restore mode restore 2=Auto;
1 ) ) protection\LSHDPFRQ1
functionalit 3=Manual
y
0=Reset;
1=Activate
START;
2=Deactive
START;
9=Activate
OPERATE;
10=Deactive
OPERATE; -
21=Activate
OPR_UFRQ; -
22=Deactive
OPR_UFRQ; -
25=Activate
OPR_FRG; -
26=Deactive
LSHDPFRQ UFLS/R(1 81LSH(1 LD0.LSHDPTRC1.TstOutCmd.Oper.ctlV Test control Tests\Function tests\Frequency
TES ENC Enum CO B 0 LSHDPFRQ1 OPR_FRG; -
1 ) ) al for outputs protection
27=Activate
ST_UFRQ; -
28=Deactive
ST_UFRQ; -
31=Activate
ST_FRG; -
32=Deactive
ST_FRG;
115=Activate
RESTORE;
116=Deactive
RESTORE; -
55=Activate
ST_REST; -
56=Deactive
ST_REST

248
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

LSHDPFRQ UFLS/R(1 81LSH(1 VisString25 (Name


VER LD0.LSHDPTRC1.NamPlt.swRev LPL DC ED1 C1
1 ) ) 5 (20) plate)

SMVRECEIVE1: B2
Chann
Categor CD Defaul Datase Even CM Parameter Paramete Parameter el
IEC 61850 IEC 60617 ANSI IECName Type FC Access Menu path
y C t t t T name r desc range relatio
n
(ACT
SMVRECEIV SMVRECEIV SMVRECEIV
OUT Channel I3P output
E1 E1 E1
channel)
(ACT
SMVRECEIV SMVRECEIV SMVRECEIV I3P_VIRT_
OUT Channel output
E1 E1 E1 A
channel)
(ACT
SMVRECEIV SMVRECEIV SMVRECEIV I3P_VIRT_
OUT Channel output
E1 E1 E1 B
channel)
(ACT
Current
OUT Channel IRES output
(Io,SMVCT)
channel)
(ACT
Current IRES_CAL
OUT Channel output
(Io,SMVCT) C
channel)
(ACT
SMVRECEIV SMVRECEIV SMVRECEIV
OUT Channel U3P output
E1 E1 E1
channel)
(ACT
Voltage
OUT Channel URES output
(Uo,SMVVT)
channel)
(ACT
Voltage URES_CAL
OUT Channel output
(Uo,SMVVT) C
channel)
SMVRECEIV SMVRECEIV SMVRECEIV StatIe Monitoring\Communication\SMVRECEIV
OUT LD0.SVIL1TCTR1.Alm.stVal SPS BOOLEAN ST B P,H I1 ALARM Alarm
E1 E1 E1 d E1
SMVRECEIV SMVRECEIV SMVRECEIV StatIe Monitoring\Communication\SMVRECEIV
OUT LD0.SVIL1TCTR1.Wrn.stVal SPS BOOLEAN ST B P,H I1 WARNING Warning
E1 E1 E1 d E1
Active if
SMVRECEIV SMVRECEIV SMVRECEIV SIMULATE receiving Monitoring\Communication\SMVRECEIV
OUT LD0.SVIL1TCTR1.RxSim.stVal SPS BOOLEAN ST B I1
E1 E1 E1 D simulatio E1
n
Active if
block has
SMVRECEIV SMVRECEIV SMVRECEIV CONFIGER been Monitoring\Communication\SMVRECEIV
MON LD0.SVIL1TCTR1.ConfErr.stVal SPS BOOLEAN ST B I1
E1 E1 E1 R wrongly E1
configure
d

249
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Current StatIe
MON LD0.SVRESTCTR1.Alm.stVal SPS BOOLEAN ST P,H I1 (Alarm)
(Io,SMVCT) d
Current StatIe (Warning
MON LD0.SVRESTCTR1.Wrn.stVal SPS BOOLEAN ST P,H I1
(Io,SMVCT) d )
SMVRECEIV SMVRECEIV SMVRECEIV StatIe
MON LD0.SVUL1TVTR1.Alm.stVal SPS BOOLEAN ST P,H I1 (Alarm)
E1 E1 E1 d
SMVRECEIV SMVRECEIV SMVRECEIV StatIe (Warning
MON LD0.SVUL1TVTR1.Wrn.stVal SPS BOOLEAN ST P,H I1
E1 E1 E1 d )
Voltage StatIe
MON LD0.SVRESTVTR1.Alm.stVal SPS BOOLEAN ST P,H I1 (Alarm)
(Uo,SMVVT) d
Voltage StatIe (Warning
MON LD0.SVRESTVTR1.Wrn.stVal SPS BOOLEAN ST P,H I1
(Uo,SMVVT) d )
Primary Primary
SMVRECEIV SMVRECEIV SMVRECEIV AS 1.0...6000.0 Configuration\Communication\SMVRECEI
CFG LD0.SVIL1TCTR1.ARtg.setMag.f FLOAT32 SP B,I 100.0 phase phase
E1 E1 E1 G A VE1
current current
Sampled
value ID
SMVRECEIV SMVRECEIV SMVRECEIV VS VisString25 ED2,B, of the Configuration\Communication\SMVRECEI
CFG LD0.SVIL1TCTR1.SmvId.setVal SP 0 SV identifier
E1 E1 E1 G 5 I received VE1
9-2
stream
Sampled
value ID
SMVRECEIV SMVRECEIV SMVRECEIV VisString25 E of the Configuration\Communication\SMVRECEI
CFG LD0.SVIL1TCTR1.NamPlt.eSmvId LPL ED1,I 0 SV identifier
E1 E1 E1 5 X received VE1
9-2
stream
SV angle
correctio
SMVRECEIV SMVRECEIV SMVRECEIV LD0.SVIL1TCTR1.SvAngCor.setM AS SV angle Configuration\Communication\SMVRECEI
CFG FLOAT32 SP B,C,I -0.6 n for -5.0...5.0 deg
E1 E1 E1 ag.f G correction VE1
merging
unit
Primary Primary
Current AS 1.0...6000.0 Configuration\Communication\SMVRECEI
CFG LD0.SVRESTCTR1.ARtg.setMag.f FLOAT32 SP B,I 100.0 residual residual
(Io,SMVCT) G A VE1
current current
Primary Primary
SMVRECEIV SMVRECEIV SMVRECEIV AS 20.00 0.100...440.0 Configuration\Communication\SMVRECEI
CFG LD0.SVUL1TVTR1.VRtg.setMag.f FLOAT32 SP B,I phase phase
E1 E1 E1 G 0 00 kV VE1
voltage voltage
Primary Primary
Voltage AS 11.54 0.1...440.000 Configuration\Communication\SMVRECEI
CFG LD0.SVRESTVTR1.VRtg.setMag.f FLOAT32 SP B,I residual residual
(Uo,SMVVT) G 7 kV VE1
voltage voltage
SMVRECEIV SMVRECEIV SMVRECEIV VisString25 D (Name
VER LD0.SVIL1TCTR1.NamPlt.swRev LPL ED1,I B2
E1 E1 E1 5 (20) C plate)

MNSPTOC1: Negative-phase-sequence time overcurrent protection for machines: C1


IEC Categor Acces Even CM Parameter Channel
IEC 61850 ANSI IECName CDC Type FC Default Dataset Parameter name Parameter range Menu path
60617 y s t T desc relation
250
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

MNSPTOC I2>M(1 46M(1 (ACT input


INP Channel I3P
1 ) ) channel)
Block signal
for
MNSPTOC I2>M(1 46M(1 Monitoring\I/O status\Current
INP LD0.MNSPTOC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK activating
1 ) ) protection\MNSPTOC1\Inputs
the blocking
mode
MNSPTOC I2>M(1 46M(1 StatNrm Monitoring\I/O status\Current
OUT LD0.MNSPTOC1.Str.general ACD BOOLEAN ST B P,H I1 START Start
1 ) ) l protection\MNSPTOC1\Outputs
MNSPTOC I2>M(1 46M(1 StatNrm P,H, Monitoring\I/O status\Current
OUT LD0.MNSPTOC1.Op.general ACT BOOLEAN ST B I1 OPERATE Operate
1 ) ) l T protection\MNSPTOC1\Outputs
Overheated
MNSPTOC I2>M(1 46M(1 machine Monitoring\I/O status\Current
OUT LD0.MNSPTOC1.StrInh.stVal SPS BOOLEAN ST B I1 BLK_RESTART
1 ) ) reconnection protection\MNSPTOC1\Outputs
blocking
1=on;
2=blocked;
MNSPTOC I2>M(1 46M(1
MON LD0.MNSPTOC1.Beh.stVal ENS Enum ST B MNSPTOC1 Status 3=test; Monitoring\FB status
1 ) )
4=test/blocked;
5=off
Ratio of Monitoring\I/O status\Current
MNSPTOC I2>M(1 46M(1 M
MON LD0.MNSPTOC1.StrDur.mag.f MV FLOAT32 B START_DUR start time / 0.00...100.00 % protection\MNSPTOC1\Monitore
1 ) ) X
operate time d data
Estimated
Monitoring\I/O status\Current
MNSPTOC I2>M(1 46M(1 T_ENARESTAR time to reset
MON LD0.MNSPTOC1.TmsRecEna.stVal INS INT32 ST B I1 0...10000 s protection\MNSPTOC1\Monitore
1 ) ) T of block
d data
restart
MNSPTOC I2>M(1 46M(1 Operation Settings\Settings\Current
SET LD0.MNSPTOC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
1 ) ) Off / On protection\MNSPTOC1
5=ANSI Def.
Time; 15=IEC
Selection of
MNSPTOC I2>M(1 46M(1 CURV Operating curve Def. Time; Settings\Settings\Current
SET LD0.MNSPTOC1.TmACrv.setCharact Enum SG B 15 time delay
1 ) ) E type 17=Inv. Curve protection\MNSPTOC1
curve type
A; 18=Inv.
Curve B
MNSPTOC I2>M(1 46M(1 Settings\Settings\Current IL1TCTR
SET LD0.MNSPTOC1.StrVal.setMag.f ASG FLOAT32 SG B 0.20 Start value Start value 0.01...0.50 xIn
1 ) ) protection\MNSPTOC1 1
Machine
MNSPTOC I2>M(1 46M(1 Machine time Settings\Settings\Current
SET LD0.MNSPTOC1.TmMult.setMag.f ASG FLOAT32 SG B 5.0 related time 5.0...100.0
1 ) ) Mult protection\MNSPTOC1
constant
Minimum
MNSPTOC I2>M(1 46M(1 Minimum operate operate time Settings\Settings\Current
SET LD0.MNSPTOC1.MinOpTmms.setVal ING INT32 SP B 100 100...120000 ms
1 ) ) time for IDMT protection\MNSPTOC1
curves
Max operate
time
MNSPTOC I2>M(1 46M(1 100000 Maximum operate regardless of 500000...720000 Settings\Settings\Current
SET LD0.MNSPTOC1.MaxOpTmms.setVal ING INT32 SP B
1 ) ) 0 time the inverse 0 ms protection\MNSPTOC1
characteristi
c
251
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

MNSPTOC I2>M(1 46M(1 Operate delay Operate Settings\Settings\Current


SET LD0.MNSPTOC1.OpDlTmms.setVal ING INT32 SG B 1000 100...120000 ms
1 ) ) time delay time protection\MNSPTOC1
MNSPTOC I2>M(1 46M(1 Reset delay Settings\Settings\Current
SET LD0.MNSPTOC1.RsDlTmms.setVal ING INT32 SP A 20 Reset delay time 0...60000 ms
1 ) ) time protection\MNSPTOC1
Rated
current (Ir)
of the
MNSPTOC I2>M(1 46M(1 Settings\Settings\Current IL1TCTR
SET LD0.MNSPTOC1.ARef.setMag.f ASG FLOAT32 SP A 1.00 Current reference machine 0.30...2.00 xIn
1 ) ) protection\MNSPTOC1 1
(used only
in the
IDMT)
Time
MNSPTOC I2>M(1 46M(1 required to Settings\Settings\Current
SET LD0.MNSPTOC1.ClTms.setVal ING INT32 SP B 50 Cooling time 5...7200 s
1 ) ) cool the protection\MNSPTOC1
machine
0=Reset;
1=Activate
START;
2=Deactive
START;
9=Activate
MNSPTOC I2>M(1 46M(1 LD0.MNSPTOC1.TstOutCmd.Oper.ctlV Test control Tests\Function tests\Current
TES ENC Enum CO B 0 MNSPTOC1 OPERATE;
1 ) ) al for outputs protection
10=Deactive
OPERATE; -
9=Activate
BLK_RESTART
; -10=Deactive
BLK_RESTART
MNSPTOC I2>M(1 46M(1 VisString25 (Name
VER LD0.MNSPTOC1.NamPlt.swRev LPL DC ED1 C1
1 ) ) 5 (20) plate)

LOFLPTUC1: Loss of load protection: C1


IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
(ACT input
LOFLPTUC1 3I<(1) 37(1) INP Channel I3P
channel)
Block all
binary
Monitoring\I/O status\Current
LOFLPTUC1 3I<(1) 37(1) INP LD0.LOFLPTUC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK outputs by
protection\LOFLPTUC1\Inputs
resetting
timers
Monitoring\I/O status\Current
LOFLPTUC1 3I<(1) 37(1) OUT LD0.LOFLPTUC1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start
protection\LOFLPTUC1\Outputs
Monitoring\I/O status\Current
LOFLPTUC1 3I<(1) 37(1) OUT LD0.LOFLPTUC1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate
protection\LOFLPTUC1\Outputs
1=on; 2=blocked;
LOFLPTUC1 3I<(1) 37(1) MON LD0.LOFLPTUC1.Beh.stVal ENS Enum ST B LOFLPTUC1 Status Monitoring\FB status
3=test;

252
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

4=test/blocked;
5=off
Ratio of start Monitoring\I/O status\Current
LOFLPTUC1 3I<(1) 37(1) MON LD0.LOFLPTUC1.StrDur.mag.f MV FLOAT32 MX B START_DUR time / 0.00...100.00 % protection\LOFLPTUC1\Monitored
operate time data
Operation Settings\Settings\Current
LOFLPTUC1 3I<(1) 37(1) SET LD0.LOFLPTUC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
Off / On protection\LOFLPTUC1
Current
Start value Settings\Settings\Current
LOFLPTUC1 3I<(1) 37(1) SET LD0.LOFLPTUC1.StrVal.setMag.f ASG FLOAT32 SG B 0.50 setting/Start 0.01...1.00 xIn IL1TCTR1
high protection\LOFLPTUC1
value high
Operate delay Operate Settings\Settings\Current
LOFLPTUC1 3I<(1) 37(1) SET LD0.LOFLPTUC1.OpDlTmms.setVal ING INT32 SG B 2000 400...600000 ms
time delay time protection\LOFLPTUC1
Reset delay Reset delay Settings\Settings\Current
LOFLPTUC1 3I<(1) 37(1) SET LD0.LOFLPTUC1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
time time protection\LOFLPTUC1
Current
Start value Settings\Settings\Current
LOFLPTUC1 3I<(1) 37(1) SET LD0.LOFLPTUC1.BlkValA.setMag.f ASG FLOAT32 SG B 0.10 setting/Start 0.01...0.50 xIn IL1TCTR1
low protection\LOFLPTUC1
value low
0=Reset;
1=Activate
START;
2=Deactive
Test control Tests\Function tests\Current
LOFLPTUC1 3I<(1) 37(1) TES LD0.LOFLPTUC1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 LOFLPTUC1 START;
for outputs protection
9=Activate
OPERATE;
10=Deactive
OPERATE
VisString255
LOFLPTUC1 3I<(1) 37(1) VER LD0.LOFLPTUC1.NamPlt.swRev LPL DC ED1 C1 (Name plate)
(20)

JAMPTOC1: Stalled motor: C1


IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
(ACT input
JAMPTOC1 Ist>(1) 51LR(1) INP Channel I3P
channel)
Block signal
for
Monitoring\I/O status\Current
JAMPTOC1 Ist>(1) 51LR(1) INP LD0.JAMPTOC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK activating
protection\JAMPTOC1\Inputs
the blocking
mode
Monitoring\I/O status\Current
JAMPTOC1 Ist>(1) 51LR(1) OUT LD0.JAMPTOC1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate (A,B,C)
protection\JAMPTOC1\Outputs
1=on; 2=blocked;
3=test;
JAMPTOC1 Ist>(1) 51LR(1) MON LD0.JAMPTOC1.Beh.stVal ENS Enum ST B JAMPTOC1 Status Monitoring\FB status
4=test/blocked;
5=off

253
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Monitoring\I/O status\Current
JAMPTOC1 Ist>(1) 51LR(1) MON LD0.JAMPTOC1.Str.general ACD BOOLEAN ST B I1 START Start (A,B,C) protection\JAMPTOC1\Monitored
data
Ratio of Monitoring\I/O status\Current
JAMPTOC1 Ist>(1) 51LR(1) MON LD0.JAMPTOC1.StrDur.mag.f MV FLOAT32 MX B START_DUR start time / 0.00...100.00 % protection\JAMPTOC1\Monitored
operate time data
Operation Settings\Settings\Current
JAMPTOC1 Ist>(1) 51LR(1) SET LD0.JAMPTOC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
Off / On protection\JAMPTOC1
Settings\Settings\Current
JAMPTOC1 Ist>(1) 51LR(1) SET LD0.JAMPTOC1.StrVal.setMag.f ASG FLOAT32 SP B 2.50 Start value Start value 0.10...10.00 xIn IL1TCTR1
protection\JAMPTOC1
Operate delay Operate Settings\Settings\Current
JAMPTOC1 Ist>(1) 51LR(1) SET LD0.JAMPTOC1.OpDlTmms.setVal ING INT32 SP B 2000 100...120000 ms
time delay time protection\JAMPTOC1
Reset delay Reset delay Settings\Settings\Current
JAMPTOC1 Ist>(1) 51LR(1) SET LD0.JAMPTOC1.RsDlTmms.setVal ING INT32 SP A 100 0...60000 ms
time time protection\JAMPTOC1
0=Reset;
9=Activate
Test control Tests\Function tests\Current
JAMPTOC1 Ist>(1) 51LR(1) TES LD0.JAMPTOC1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 JAMPTOC1 OPERATE;
for outputs protection
10=Deactive
OPERATE
VisString255 (Name
JAMPTOC1 Ist>(1) 51LR(1) VER LD0.JAMPTOC1.NamPlt.swRev LPL DC ED1 C1
(20) plate)

STTPMSU1: Motor startup supervision: C2


IEC
Categor CD Acces Defaul Even CM Parameter Parameter Channel
IEC 61850 6061 ANSI IECName Type FC Dataset Parameter name Menu path
y C s t t T desc range relation
7
STTPMSU Is2t 49,66,48,51LR(1 (ACT input
INP Channel I3P
1 n<(1) ) channel)
STTPMSU Is2t 49,66,48,51LR(1 Block of Monitoring\I/O status\Current
INP LD0.STTPMSS1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
1 n<(1) ) function protection\STTPMSU1\Inputs
Enable
emergency
STTPMSU Is2t 49,66,48,51LR(1 ST_EMERG_EN start to Monitoring\I/O status\Current
INP LD0.STTPMSS1.EnaEmgStr.stVal SPS BOOLEAN ST B 0 I1
1 n<(1) ) A disable lock protection\STTPMSU1\Inputs
of start of
motor
Input signal
STTPMSU Is2t 49,66,48,51LR(1 for showing Monitoring\I/O status\Current
INP LD0.STTPMSS1.StlInd.stVal SPS BOOLEAN ST B 0 I1 STALL_IND
1 n<(1) ) the motor is protection\STTPMSU1\Inputs
not stalling
Blocks lock
STTPMSU Is2t 49,66,48,51LR(1 out condition Monitoring\I/O status\Current
INP LD0.STTPMSS1.BlkLOStr.stVal SPS BOOLEAN ST B 0 I1 BLK_LK_ST
1 n<(1) ) for restart of protection\STTPMSU1\Inputs
motor
Input
STTPMSU Is2t 49,66,48,51LR(1 Monitoring\I/O status\Current
INP LD0.STTPMSS1.InPosCls.stVal SPS BOOLEAN ST B 0 I1 CB_CLOSED showing the
1 n<(1) ) protection\STTPMSU1\Inputs
status of
254
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

motor circuit
breaker
Signal to
STTPMSU Is2t 49,66,48,51LR(1 AC StatNrm show that Monitoring\I/O status\Current
OUT LD0.STTPMSS1.Str.general BOOLEAN ST B P,H I1 MOT_START
1 n<(1) ) D l motor startup protection\STTPMSU1\Outputs
is in progress
Operate/trip
STTPMSU Is2t 49,66,48,51LR(1 StatNrm P,H, signal for Monitoring\I/O status\Current
OUT LD0.STTPMSS1.Op.general ACT BOOLEAN ST B I1 OPR_STALL
1 n<(1) ) l T stalling protection\STTPMSU1\Outputs
protection.
Operate/trip
STTPMSU Is2t 49,66,48,51LR(1 StatNrm P,H, signal for Monitoring\I/O status\Current
OUT LD0.STTPMRI1.Op.general ACT BOOLEAN ST B I1 OPR_IIT
1 n<(1) ) l T thermal protection\STTPMSU1\Outputs
stress.
Lock out
STTPMSU Is2t 49,66,48,51LR(1 StatNrm condition for Monitoring\I/O status\Current
OUT LD0.STTPMRI1.StrInh.stVal SPS BOOLEAN ST B P,H I1 LOCK_START
1 n<(1) ) l restart of protection\STTPMSU1\Outputs
motor.
Reset
STTPMSU Is2t 49,66,48,51LR(1 LD0.STTPMRI1.RsStrUpCnt.Oper.ctlV STTPMSU1 number of 0=Cancel;
CTR SPC BOOLEAN CO B 0 I1 Clear\Clear
1 n<(1) ) al counter motor start- 1=Clear
ups counter
1=on;
2=blocked;
STTPMSU Is2t 49,66,48,51LR(1
MON LD0.STTPMSS1.Beh.stVal ENS Enum ST B STTPMSU1 Status 3=test; Monitoring\FB status
1 n<(1) )
4=test/blocked;
5=off
Start time
relative to Monitoring\I/O status\Current
STTPMSU Is2t 49,66,48,51LR(1 M
MON LD0.STTPMSS1.StrDur.mag.f MV FLOAT32 B STALL_RL the operate 0.00...100.00 % protection\STTPMSU1\Monitore
1 n<(1) ) X
time for stall d data
condition
Time left for
restart when Monitoring\I/O status\Current
STTPMSU Is2t 49,66,48,51LR(1
MON LD0.STTPMRI1.StrInhTmm.stVal INS INT32 ST B I1 T_RST_ENA lockstart is 0...999 min protection\STTPMSU1\Monitore
1 n<(1) )
enabled in d data
minutes
Number of Monitoring\I/O status\Current
STTPMSU Is2t 49,66,48,51LR(1
MON LD0.STTPMRI1.StrUpCntRs.stVal INC INT32 ST B I1 START_CNT motor start- 0...999999 protection\STTPMSU1\Monitore
1 n<(1) )
ups occurred d data
Thermal
stress relative
Monitoring\I/O status\Current
STTPMSU Is2t 49,66,48,51LR(1 M to set
MON LD0.STTPMRI1.ThmStsPct.mag.f MV FLOAT32 B I1 IIT_RL 0.00...100.00 % protection\STTPMSU1\Monitore
1 n<(1) ) X maximum
d data
thermal
stress
Cumulated Monitoring\I/O status\Current
STTPMSU Is2t 49,66,48,51LR(1 M ED2,
MON LD0.STTPMRI1.TmsCumStrUp.mag.f MV FLOAT32 I1 T_ST_CNT start-up time 0.0...99999.9 s protection\STTPMSU1\Monitore
1 n<(1) ) X B
in sec d data

255
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Cumulated Monitoring\I/O status\Current


STTPMSU Is2t 49,66,48,51LR(1 M
MON LD0.STTPMRI1.TmCumStrUp.mag.f MV FLOAT32 ED1 I1 T_ST_CNT start-up time 0.0...99999.9 s protection\STTPMSU1\Monitore
1 n<(1) ) X
in sec d data
Measured
Monitoring\I/O status\Current
STTPMSU Is2t 49,66,48,51LR(1 M motor latest
MON LD0.STTPMRI1.TmsStrUp.mag.f MV FLOAT32 B I1 START_TIME 0.0...999.9 s protection\STTPMSU1\Monitore
1 n<(1) ) X startup time
d data
in sec
STTPMSU Is2t 49,66,48,51LR(1 Operation Settings\Settings\Current
SET LD0.STTPMSS1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
1 n<(1) ) Off / On protection\STTPMSU1
Current value
STTPMSU Is2t 49,66,48,51LR(1 for detecting Settings\Settings\Current IL1TCTR
SET LD0.STTPMSS1.MotStr.setMag.f ASG FLOAT32 SG A 1.5 Start detection A 0.1...10.0 xIn
1 n<(1) ) starting of protection\STTPMSU1 1
motor.
STTPMSU Is2t 49,66,48,51LR(1 Permitted Settings\Settings\Current
SET LD0.STTPMSS1.LokRotTms.setVal ING INT32 SG B 10 Lock rotor time 2...120 s
1 n<(1) ) stalling time protection\STTPMSU1
1=IIt; 2=IIt,
Motor start-
STTPMSU Is2t 49,66,48,51LR(1 EN CB; 3=IIt + Settings\Settings\Current
SET LD0.STTPMSS1.OpModStUp.setVal Enum SP B 1 Operation mode up operation
1 n<(1) ) G stall; 4=IIt + protection\STTPMSU1
mode
stall, CB
Time delay
to check for
STTPMSU Is2t 49,66,48,51LR(1 ED2, Str over delay completion Settings\Settings\Current
SET LD0.STTPMSS1.StrOvDlTmms.setVal ING INT32 SG 100 0...60000 ms
1 n<(1) ) B time of motor protection\STTPMSU1
startup
period
Time delay
to check for
STTPMSU Is2t 49,66,48,51LR(1 Str over delay completion Settings\Settings\Current
SET LD0.STTPMSS1.OvDlTmms.setVal ING INT32 SG ED1 100 0...60000 ms
1 n<(1) ) time of motor protection\STTPMSU1
startup
period
Current limit
to check for
STTPMSU Is2t 49,66,48,51LR(1 Settings\Settings\Current IL1TCTR
SET LD0.STTPMSS1.MotStop.setMag.f ASG FLOAT32 SP A 0.12 Motor standstill A motor 0.05...0.20 xIn
1 n<(1) ) protection\STTPMSU1 1
standstill
condition
Motor
STTPMSU Is2t 49,66,48,51LR(1 Settings\Settings\Current IL1TCTR
SET LD0.STTPMRI1.SetA.setMag.f ASG FLOAT32 SG B 2.0 Motor start-up A starting 1.0...10.0 xIn
1 n<(1) ) protection\STTPMSU1 1
current
STTPMSU Is2t 49,66,48,51LR(1 Motor start-up Motor Settings\Settings\Current
SET LD0.STTPMRI1.SetTms.setVal ING INT32 SG B 5 1...80 s
1 n<(1) ) time starting time protection\STTPMSU1
Time delay
STTPMSU Is2t 49,66,48,51LR(1 Restart inhibit between Settings\Settings\Current
SET LD0.STTPMRI1.InhTmm.setVal ING INT32 SP B 30 0...250 min
1 n<(1) ) time consecutive protection\STTPMSU1
startups
Initial value
STTPMSU Is2t 49,66,48,51LR(1 LD0.STTPMRI1.StrUpCntRs.Oper.ctlV Ini start up for the Settings\Settings\Current
SET INC INT32 CO B 0 I1 0...999999
1 n<(1) ) al counter START_CN protection\STTPMSU1
T

256
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Start time
STTPMSU Is2t 49,66,48,51LR(1 counter Settings\Settings\Current
SET LD0.STTPMRI1.CntRedRte.setMag.f ASG FLOAT32 SP B 60.0 Counter Red rate 2.0...250.0 s/h
1 n<(1) ) reduction protection\STTPMSU1
rate
Start time
reduction
STTPMSU Is2t 49,66,48,51LR(1 Emg start Red Settings\Settings\Current
SET LD0.STTPMRI1.EmgRedRte.setMag.f ASG FLOAT32 SP B 20.00 factor when 0.00...100.00 %
1 n<(1) ) rate protection\STTPMSU1
emergency
start is On
Cumulative
STTPMSU Is2t 49,66,48,51LR(1 Cumulative time time based Settings\Settings\Current
SET LD0.STTPMRI1.CumLimTms.setVal ING INT32 SP B 10 1...500 s
1 n<(1) ) Lim restart inhibit protection\STTPMSU1
limit
0=Reset;
49=Activate
OPR_IIT;
50=Deactive
OPR_IIT;
51=Activate
OPR_STALL;
52=Deactive
STTPMSU Is2t 49,66,48,51LR(1 Test control Tests\Function tests\Current
TES LD0.STTPMSS1.TestPro.Oper.ctlVal ENC Enum CO B 0 STTPMSU1 OPR_STALL;
1 n<(1) ) for outputs protection
53=Activate
MOT_START;
54=Deactive
MOT_START;
55=Activate
LOCK_START
; 56=Deactive
LOCK_START
STTPMSU Is2t 49,66,48,51LR(1 VisString25
VER LD0.STTPMSS1.NamPlt.swRev LPL DC ED1 C2 (Name plate)
1 n<(1) ) 5 (20)

PREVPTOC1: Phase reversal protection: B1


IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
(ACT
PREVPTOC1 I2>>(1) 46R(1) INP Channel I3P input
channel)
Block
signal for
activating Monitoring\I/O status\Current
PREVPTOC1 I2>>(1) 46R(1) INP LD0.PREVPTOC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
the protection\PREVPTOC1\Inputs
blocking
mode
Monitoring\I/O status\Current
PREVPTOC1 I2>>(1) 46R(1) OUT LD0.PREVPTOC1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start
protection\PREVPTOC1\Outputs
Monitoring\I/O status\Current
PREVPTOC1 I2>>(1) 46R(1) OUT LD0.PREVPTOC1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate
protection\PREVPTOC1\Outputs
257
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

1=on; 2=blocked;
3=test;
PREVPTOC1 I2>>(1) 46R(1) MON LD0.PREVPTOC1.Beh.stVal ENS Enum ST B PREVPTOC1 Status Monitoring\FB status
4=test/blocked;
5=off
Ratio of
Monitoring\I/O status\Current
start time /
PREVPTOC1 I2>>(1) 46R(1) MON LD0.PREVPTOC1.StrDur.mag.f MV FLOAT32 MX B START_DUR 0.00...100.00 % protection\PREVPTOC1\Monitored
operate
data
time
Operation Settings\Settings\Current
PREVPTOC1 I2>>(1) 46R(1) SET LD0.PREVPTOC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off IL1TCTR1
Off / On protection\PREVPTOC1
Settings\Settings\Current
PREVPTOC1 I2>>(1) 46R(1) SET LD0.PREVPTOC1.StrVal.setMag.f ASG FLOAT32 SG B 0.75 Start value Start value 0.05...1.00 xIn IL1TCTR1
protection\PREVPTOC1
Operate delay Operate Settings\Settings\Current
PREVPTOC1 I2>>(1) 46R(1) SET LD0.PREVPTOC1.OpDlTmms.setVal ING INT32 SG B 100 100...60000 ms
time delay time protection\PREVPTOC1
0=Reset;
1=Activate
START;
Test 2=Deactive
Tests\Function tests\Current
PREVPTOC1 I2>>(1) 46R(1) TES LD0.PREVPTOC1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 PREVPTOC1 control for START;
protection
outputs 9=Activate
OPERATE;
10=Deactive
OPERATE
VisString255 (Name
PREVPTOC1 I2>>(1) 46R(1) VER LD0.PREVPTOC1.NamPlt.swRev LPL DC ED1 B1
(20) plate)

MPTTR1: Motor thermal overload protection: F1


IEC IEC Parameter Channel
ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter name Parameter range Menu path
61850 60617 desc relation
(ACT input
MPTTR1 3Ith>M(1) 49M(1) INP Channel I3P
channel)
Block signal
for activating Monitoring\I/O status\Current
MPTTR1 3Ith>M(1) 49M(1) INP LD0.MPTTR1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
the blocking protection\MPTTR1\Inputs
mode
Signal for
indicating the
Monitoring\I/O status\Current
MPTTR1 3Ith>M(1) 49M(1) INP LD0.MPTTR1.EnaEmgStr.stVal SPS BOOLEAN ST B 0 I1 START_EMERG need for
protection\MPTTR1\Inputs
emergency
start
The ambient
temperature Monitoring\I/O status\Current
MPTTR1 3Ith>M(1) 49M(1) INP LD0.MPTTR1.TmpAmb.mag.f MV FLOAT32 MX B 0 I1 AMB_TEMP -99...999 °C
used in the protection\MPTTR1\Inputs
calculation
Monitoring\I/O status\Current
MPTTR1 3Ith>M(1) 49M(1) OUT LD0.MPTTR1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate
protection\MPTTR1\Outputs

258
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Thermal Monitoring\I/O status\Current


MPTTR1 3Ith>M(1) 49M(1) OUT LD0.MPTTR1.AlmThm.stVal SPS BOOLEAN ST B StatUrg P,H I1 ALARM
Alarm protection\MPTTR1\Outputs
Thermal
overload Monitoring\I/O status\Current
MPTTR1 3Ith>M(1) 49M(1) OUT LD0.MPTTR1.BlkThm.stVal SPS BOOLEAN ST B StatNrml P,H I1 BLK_RESTART
indicator, to protection\MPTTR1\Outputs
inhibit restart
Reset
MPTTR1
MPTTR1 3Ith>M(1) 49M(1) CTR LD0.MPTTR1.RsTmp.Oper.ctlVal SPC BOOLEAN CO B 0 I1 MPTTR1 0=Cancel; 1=Clear Clear\Clear
temperature
tempetature
1=on; 2=blocked;
3=test;
MPTTR1 3Ith>M(1) 49M(1) MON LD0.MPTTR1.Beh.stVal ENS Enum ST B MPTTR1 Status Monitoring\FB status
4=test/blocked;
5=off
The
calculated
temperature
Monitoring\I/O status\Current
of the
MPTTR1 3Ith>M(1) 49M(1) MON LD0.MPTTR1.TmpRl.mag.f MV FLOAT32 MX B MeasFlt P I1 TEMP_RL 0.00...9.99 protection\MPTTR1\Monitored
protected
data
object relative
to the operate
level
The ambient
Monitoring\I/O status\Current
temperature
MPTTR1 3Ith>M(1) 49M(1) MON LD0.MPTTR1.TmpUsed.mag.f MV FLOAT32 MX B I1 TEMP_AMB -99...999 °C protection\MPTTR1\Monitored
used in the
data
calculation
Thermal level
Monitoring\I/O status\Current
at beginning
MPTTR1 3Ith>M(1) 49M(1) MON LD0.MPTTR1.ThmLevStr.mag.f MV FLOAT32 MX B I1 THERMLEV_ST 0.00...9.99 protection\MPTTR1\Monitored
of motor
data
startup
Thermal level
Monitoring\I/O status\Current
at the end of
MPTTR1 3Ith>M(1) 49M(1) MON LD0.MPTTR1.ThmLevEnd.mag.f MV FLOAT32 MX B I1 THERMLEV_END 0.00...9.99 protection\MPTTR1\Monitored
motor startup
data
situation
Estimated
Monitoring\I/O status\Current
time to reset
MPTTR1 3Ith>M(1) 49M(1) MON LD0.MPTTR1.BlkThmRsTm.stVal INS INT32 ST B I1 T_ENARESTART 0...99999 s protection\MPTTR1\Monitored
of block
data
restart
Operation Off Settings\Settings\Current
MPTTR1 3Ith>M(1) 49M(1) SET LD0.MPTTR1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
/ On protection\MPTTR1
Motor time
constant
Time constant during the Settings\Settings\Current
MPTTR1 3Ith>M(1) 49M(1) SET LD0.MPTTR1.ConsTms1.setVal ING INT32 SG B 320 80...4000 s
normal normal protection\MPTTR1
operation of
motor
Motor time
constant Settings\Settings\Current
MPTTR1 3Ith>M(1) 49M(1) SET LD0.MPTTR1.ConsTms2.setVal ING INT32 SG B 320 Time constant start 80...4000 s
during the protection\MPTTR1
start of motor

259
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Motor time
constant
during the Settings\Settings\Current
MPTTR1 3Ith>M(1) 49M(1) SET LD0.MPTTR1.ConsTms3.setVal ING INT32 SG B 500 Time constant stop 80...60000 s
standstill protection\MPTTR1
condition of
motor
Thermal level
Alarm thermal above which Settings\Settings\Current
MPTTR1 3Ith>M(1) 49M(1) SET LD0.MPTTR1.AlmVal.setMag.f ASG FLOAT32 SG B 95.0 50.0...100.0 %
value function gives protection\MPTTR1
an alarm
The load
current
leading to Settings\Settings\Current
MPTTR1 3Ith>M(1) 49M(1) SET LD0.MPTTR1.ARef.setMag.f ASG FLOAT32 SP A 1.00 Current reference 0.30...2.00 xIn IL1TCTR1
Temperature protection\MPTTR1
raise
temperature
Thermal level
above which
Settings\Settings\Current
MPTTR1 3Ith>M(1) 49M(1) SET LD0.MPTTR1.DropoutVal.setMag.f ASG FLOAT32 SG B 40.0 Restart thermal Val function 20.0...80.0 %
protection\MPTTR1
inhibits motor
restarting
Weighting Settings\Settings\Current
MPTTR1 3Ith>M(1) 49M(1) SET LD0.MPTTR1.WghFact.setMag.f ASG FLOAT32 SG B 50.0 Weighting factor p 20.0...100.0 %
factor (p) protection\MPTTR1
Overload Settings\Settings\Current
MPTTR1 3Ith>M(1) 49M(1) SET LD0.MPTTR1.OvlFact.setMag.f ASG FLOAT32 SG B 1.05 Overload factor 1.00...1.20
factor (k) protection\MPTTR1
Heating effect
factor for
Settings\Settings\Current
MPTTR1 3Ith>M(1) 49M(1) SET LD0.MPTTR1.NgSeqFact.setMag.f ASG FLOAT32 SG B 0.0 Negative Seq factor negative 0.0...10.0
protection\MPTTR1
sequence
current
Ambient
temperature
used when no
Env temperature Settings\Settings\Current
MPTTR1 3Ith>M(1) 49M(1) SET LD0.MPTTR1.EnvTmpSet.setMag.f ASG FLOAT32 SG B 40.0 external -20.0...70.0 °C
Set protection\MPTTR1
temperature
measurement
available
Initial thermal
Settings\Settings\Current
MPTTR1 3Ith>M(1) 49M(1) SET LD0.MPTTR1.IniTmp.setMag.f ASG FLOAT32 SP A 74.0 Initial thermal Val level of the 0.0...100.0 %
protection\MPTTR1
motor
Mode of
1=FLC Only; 2=Use
Env temperature measuring Settings\Settings\Current
MPTTR1 3Ith>M(1) 49M(1) SET LD0.MPTTR1.EnvTmpMod.setVal ENG Enum SG B 1 input; 3=Set Amb
mode ambient protection\MPTTR1
Temp
temperature
0=Reset; 9=Activate
OPERATE;
10=Deactive
Test control Tests\Function tests\Current
MPTTR1 3Ith>M(1) 49M(1) TES LD0.MPTTR1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 MPTTR1 OPERATE;
for outputs protection
17=Activate
ALARM;
18=Deactive
260
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

ALARM; -
9=Activate
BLK_RESTART; -
10=Deactive
BLK_RESTART
VisString255
MPTTR1 3Ith>M(1) 49M(1) VER LD0.MPTTR1.NamPlt.swRev LPL DC ED1 F1 (Name plate)
(20)

ESMGAPC1: Allow emergency start: C1


Categor CD Acces Defaul Even CM Parameter Parameter Channel
IEC 61850 IEC 60617 ANSI IECName Type FC Dataset Parameter name Menu path
y C s t t T desc range relation
(ACT
ESMGAPC ESTART(1 ESTART(1
INP Channel I3P input
1 ) )
channel)
Block
signal for
ESMGAPC ESTART(1 ESTART(1 activating Monitoring\I/O
INP LD0.ESMGAPC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
1 ) ) the status\Control\ESMGAPC1\Inputs
blocking
mode
Emergenc
ESMGAPC ESTART(1 ESTART(1 Monitoring\I/O
INP LD0.ESMGAPC1.RqEmgStr.stVal SPS BOOLEAN ST B 0 I1 ST_EMERG_RQ y start
1 ) ) status\Control\ESMGAPC1\Inputs
input
ESMGAPC ESTART(1 ESTART(1 AC StatNrm ST_EMERG_EN Emergenc Monitoring\I/O
OUT LD0.ESMGAPC1.Str.general BOOLEAN ST B P,H I1
1 ) ) D l A y start status\Control\ESMGAPC1\Outputs
1=on;
2=blocked;
ESMGAPC ESTART(1 ESTART(1
MON LD0.ESMGAPC1.Beh.stVal ENS Enum ST B ESMGAPC1 Status 3=test; Monitoring\FB status
1 ) )
4=test/blocked
; 5=off
Emergenc
Monitoring\I/O
ESMGAPC ESTART(1 ESTART(1 y start
MON LD0.ESMGAPC1.Op.t ACT Timestamp ST B T_ST_EMERG status\Control\ESMGAPC1\Monitor
1 ) ) activation
ed data
timestamp
ESMGAPC ESTART(1 ESTART(1 C Operation Settings\Settings\Control\ESMGAP
SET LD0.ESMGAPC1.Mod.Oper.ctlVal ENC Enum B,I 1 Operation 1=on; 5=off
1 ) ) O Off / On C1
Current
limit to
ESMGAPC ESTART(1 ESTART(1 check for Settings\Settings\Control\ESMGAP IL1TCTR
SET LD0.ESMGAPC1.StrVal.setMag.f ASG FLOAT32 SG A 0.12 Motor standstill A 0.05...0.20 xIn
1 ) ) motor C1 1
standstill
condition
0=Reset;
Test 1=Activate
ESMGAPC ESTART(1 ESTART(1 LD0.ESMGAPC1.TstOutCmd.Oper.ctlV C
TES ENC Enum B 0 ESMGAPC1 control for START; Tests\Function tests\Control
1 ) ) al O
outputs 2=Deactive
START

261
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

ESMGAPC ESTART(1 ESTART(1 VisString25 D (Name


VER LD0.ESMGAPC1.NamPlt.swRev LPL ED1 C1
1 ) ) 5 (20) C plate)

T2PTTR1: Thermal overload protection, two time constants: D1


IEC Categor Acces Defaul CM Parameter Parameter Channel
IEC 60617 ANSI IECName CDC Type FC Dataset Event Parameter name Menu path
61850 y s t T desc range relation
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 (ACT input
INP Channel I3P
1 ) ) channel)
Block signal
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 for activating Monitoring\I/O status\Current
INP LD0.T2PTTR1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
1 ) ) the blocking protection\T2PTTR1\Inputs
mode
The ambient
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 M temperature Monitoring\I/O status\Current
INP LD0.T2PTTR1.TmpAmb.mag.f MV FLOAT32 B 0 I1 AMB_TEMP -99...999 °C
1 ) ) X used in the protection\T2PTTR1\Inputs
calculation
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 AC StatNrm Monitoring\I/O status\Current
OUT LD0.T2PTTR1.Str.general BOOLEAN ST B P,H I1 START Start
1 ) ) D l protection\T2PTTR1\Outputs
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 StatNrm P,H, Monitoring\I/O status\Current
OUT LD0.T2PTTR1.Op.general ACT BOOLEAN ST B I1 OPERATE Operate
1 ) ) l T protection\T2PTTR1\Outputs
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 Thermal Monitoring\I/O status\Current
OUT LD0.T2PTTR1.AlmThm.stVal SPS BOOLEAN ST B StatUrg P,H I1 ALARM
1 ) ) Alarm protection\T2PTTR1\Outputs
Thermal
overload
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 Monitoring\I/O status\Current
OUT LD0.T2PTTR1.BlkThm.stVal SPS BOOLEAN ST B I1 BLK_CLOSE indicator. To
1 ) ) protection\T2PTTR1\Outputs
inhibite
reclose.
Reset
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 0=Cancel;
CTR LD0.T2PTTR1.RsTmp.Oper.ctlVal SPC BOOLEAN CO B 0 I1 T2PTTR1 T2PTTR1 Clear\Clear
1 ) ) 1=Clear
temperature
1=on;
2=blocked;
T2PTTR 3Ith>T/G/C(1 49T/G/C(1
MON LD0.T2PTTR1.Beh.stVal ENS Enum ST B T2PTTR1 Status 3=test; Monitoring\FB status
1 ) )
4=test/blocked
; 5=off
The
calculated
Monitoring\I/O status\Current
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 M temperature -100.0...9999.9
MON LD0.T2PTTR1.Tmp.mag.f MV FLOAT32 B MeasFlt P I1 TEMP protection\T2PTTR1\Monitore
1 ) ) X of the °C
d data
protected
object
The
calculated
Monitoring\I/O status\Current
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 M temperature
MON LD0.T2PTTR1.TmpRl.mag.f MV FLOAT32 B MeasFlt P I1 TEMP_RL 0.00...99.99 protection\T2PTTR1\Monitore
1 ) ) X of the
d data
protected
object

262
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

relative to the
operate level
The ambient
Monitoring\I/O status\Current
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 M temperature
MON LD0.T2PTTR1.TmpUsed.mag.f MV FLOAT32 B I1 TEMP_AMB -99...999 °C protection\T2PTTR1\Monitore
1 ) ) X used in the
d data
calculation
Estimated Monitoring\I/O status\Current
T2PTTR 3Ith>T/G/C(1 49T/G/C(1
MON LD0.T2PTTR1.OpTm.stVal INS INT32 ST B I1 T_OPERATE time to 0...60000 s protection\T2PTTR1\Monitore
1 ) )
operate d data
Estimated
time to Monitoring\I/O status\Current
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 T_ENA_CLOS
MON LD0.T2PTTR1.BlkThmRsTm.stVal INS INT32 ST B I1 deactivate 0...60000 s protection\T2PTTR1\Monitore
1 ) ) E
BLK_CLOS d data
E in seconds
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 Operation Off Settings\Settings\Current
SET LD0.T2PTTR1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
1 ) ) / On protection\T2PTTR1
Maximum
temperature
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 Max Settings\Settings\Current
SET LD0.T2PTTR1.TmpMax.setMag.f ASG FLOAT32 SG B 105.0 allowed for 0.0...200.0 °C
1 ) ) temperature protection\T2PTTR1
the
transformer
Short time
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 Short time Settings\Settings\Current
SET LD0.T2PTTR1.ConsTms1.setVal ING INT32 SG B 450 constant in 6...60000 s
1 ) ) constant protection\T2PTTR1
seconds
Long time
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 Long time Settings\Settings\Current
SET LD0.T2PTTR1.ConsTms2.setVal ING INT32 SG B 7200 constant in 60...60000 s
1 ) ) constant protection\T2PTTR1
seconds
Alarm
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 Alarm Settings\Settings\Current
SET LD0.T2PTTR1.AlmVal.setMag.f ASG FLOAT32 SG B 90.0 temperature, 40.0...100.0 %
1 ) ) temperature protection\T2PTTR1
percent value
The load
current
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 Current leading to Settings\Settings\Current IL1TCTR
SET LD0.T2PTTR1.ARef.setMag.f ASG FLOAT32 SG A 1.00 0.05...4.00 xIn
1 ) ) reference Temperature protection\T2PTTR1 1
raise
temperature
Ambient
temperature
used when no
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 Env temperature Settings\Settings\Current
SET LD0.T2PTTR1.EnvTmpSet.setMag.f ASG FLOAT32 SG B 40 external -50...100 °C
1 ) ) Set protection\T2PTTR1
temperature
measurement
available
Initial
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 Initial Settings\Settings\Current
SET LD0.T2PTTR1.IniTmp.setMag.f ASG FLOAT32 SP A 80.0 temperature, 0.0...100.0 %
1 ) ) temperature protection\T2PTTR1
percent value
Temperature
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 Reclose for reset of Settings\Settings\Current
SET LD0.T2PTTR1.RecTmpSet.setMag.f ASG FLOAT32 SG B 60.0 40.0...100.0 %
1 ) ) temperature block reclose protection\T2PTTR1
after operate
263
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

End
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 temperature Settings\Settings\Current
SET LD0.T2PTTR1.TmpR.setMag.f ASG FLOAT32 SG B 78.0 Temperature rise 0.0...200.0 °C
1 ) ) rise above protection\T2PTTR1
ambient
Weighting
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 Weighting factor factor of the Settings\Settings\Current
SET LD0.T2PTTR1.WghFact.setMag.f ASG FLOAT32 SG B 0.40 0.00...1.00
1 ) ) p short time protection\T2PTTR1
constant
Operate
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 Operate Settings\Settings\Current
SET LD0.T2PTTR1.OpTmp.setMag.f ASG FLOAT32 SG B 100.0 temperature, 80.0...120.0 %
1 ) ) temperature protection\T2PTTR1
percent value
0=Reset;
1=Activate
START;
2=Deactive
START;
9=Activate
OPERATE;
10=Deactive
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 LD0.T2PTTR1.TstOutCmd.Oper.ctlVa Test control Tests\Function tests\Current
TES ENC Enum CO B 0 T2PTTR1 OPERATE;
1 ) ) l for outputs protection
17=Activate
ALARM;
18=Deactive
ALARM;
21=Activate
BLK_CLOSE;
22=Deactive
BLK_CLOSE
T2PTTR 3Ith>T/G/C(1 49T/G/C(1 VisString25
VER LD0.T2PTTR1.NamPlt.swRev LPL DC ED1 D1 (Name plate)
1 ) ) 5 (20)

TR2PTDF1: Transformer differential protection of two winding transformers: C1


IEC Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter name Parameter desc Parameter range Menu path
60617 relation
(ACT input
TR2PTDF1 3dI>T(1) 87T(1) INP Channel I3P1
channel)
(ACT input
TR2PTDF1 3dI>T(1) 87T(1) INP Channel I3P2
channel)
(ACT input
TR2PTDF1 3dI>T(1) 87T(1) INP Channel TAP_POS
channel)
Monitoring\I/O
TR2PTDF1 3dI>T(1) 87T(1) INP LD0.TR2PTRC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK Block status\Differential
prot\TR2PTDF1\Inputs
Blocks operate Monitoring\I/O
TR2PTDF1 3dI>T(1) 87T(1) INP LD0.TR2LPDIF1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLK_OPR_LS outputs from status\Differential
biased stage prot\TR2PTDF1\Inputs

264
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Blocks operate
Monitoring\I/O
outputs from
TR2PTDF1 3dI>T(1) 87T(1) INP LD0.TR2HPDIF1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLK_OPR_HS status\Differential
instantaneous
prot\TR2PTDF1\Inputs
stage
Monitoring\I/O
Operate
TR2PTDF1 3dI>T(1) 87T(1) OUT LD0.TR2PTRC1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE (A,B,C) status\Differential
combined
prot\TR2PTDF1\Outputs
Monitoring\I/O
Operate from
TR2PTDF1 3dI>T(1) 87T(1) OUT LD0.TR2LPDIF1.Op.general ACT BOOLEAN ST B I1 OPR_LS status\Differential
low set
prot\TR2PTDF1\Outputs
Monitoring\I/O
Waveform
TR2PTDF1 3dI>T(1) 87T(1) OUT LD0.TR2LPDIF1.BlkWavSt.general ACT BOOLEAN ST B StatNrml P,H BLKDWAV (A,B,C) status\Differential
blocking status
prot\TR2PTDF1\Outputs
2nd harmonic Monitoring\I/O
TR2PTDF1 3dI>T(1) 87T(1) OUT LD0.TR2LPDIF1.Blk2HSt.general ACT BOOLEAN ST B StatNrml P,H BLKD2H restraint block (A,B,C) status\Differential
status prot\TR2PTDF1\Outputs
5th harmonic Monitoring\I/O
TR2PTDF1 3dI>T(1) 87T(1) OUT LD0.TR2LPDIF1.Blk5HSt.general ACT BOOLEAN ST B StatNrml P,H BLKD5H restraint block (A,B,C) status\Differential
status prot\TR2PTDF1\Outputs
Monitoring\I/O
Operate from
TR2PTDF1 3dI>T(1) 87T(1) OUT LD0.TR2HPDIF1.Op.general ACT BOOLEAN ST B I1 OPR_HS status\Differential
high set
prot\TR2PTDF1\Outputs
1=on;
2=blocked;
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2PTRC1.Beh.stVal ENS Enum ST B TR2PTDF1 Status 3=test; Monitoring\FB status
4=test/blocked;
5=off
Monitoring\I/O
Operate phase status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2PTRC1.Op.phsA ACT BOOLEAN ST B StatNrml P,H,T I1 OPR_A
A prot\TR2PTDF1\Monitored
data
Monitoring\I/O
Operate phase status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2PTRC1.Op.phsB ACT BOOLEAN ST B StatNrml P,H,T I1 OPR_B
B prot\TR2PTDF1\Monitored
data
Monitoring\I/O
Operate phase status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2PTRC1.Op.phsC ACT BOOLEAN ST B StatNrml P,H,T I1 OPR_C
C prot\TR2PTDF1\Monitored
data
Monitoring\I/O
Differential
status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.DifAClc.phsA.cVal.mag.f WYE FLOAT32 MX B I1 ID_A Current phase 0.00...80.00 xIr
prot\TR2PTDF1\Monitored
A
data
Monitoring\I/O
Differential
status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.DifAClc.phsB.cVal.mag.f WYE FLOAT32 MX B I1 ID_B Current phase 0.00...80.00 xIr
prot\TR2PTDF1\Monitored
B
data
Differential
Monitoring\I/O
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.DifAClc.phsC.cVal.mag.f WYE FLOAT32 MX B I1 ID_C Current phase 0.00...80.00 xIr
status\Differential
C
265
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

prot\TR2PTDF1\Monitored
data
Monitoring\I/O
Biasing current status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.RstA.phsA.cVal.mag.f WYE FLOAT32 MX B I1 IB_A 0.00...80.00 xIr
phase A prot\TR2PTDF1\Monitored
data
Monitoring\I/O
Biasing current status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.RstA.phsB.cVal.mag.f WYE FLOAT32 MX B I1 IB_B 0.00...80.00 xIr
phase B prot\TR2PTDF1\Monitored
data
Monitoring\I/O
Biasing current status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.RstA.phsC.cVal.mag.f WYE FLOAT32 MX B I1 IB_C 0.00...80.00 xIr
phase C prot\TR2PTDF1\Monitored
data
Monitoring\I/O
Waveform
status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.BlkWavSt.phsA ACT BOOLEAN ST B StatNrml P,H BLKDWAV_A blocking phase
prot\TR2PTDF1\Monitored
A status
data
Monitoring\I/O
Waveform
status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.BlkWavSt.phsB ACT BOOLEAN ST B StatNrml P,H BLKDWAV_B blocking phase
prot\TR2PTDF1\Monitored
B status
data
Monitoring\I/O
Waveform
status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.BlkWavSt.phsC ACT BOOLEAN ST B StatNrml P,H BLKDWAV_C blocking phase
prot\TR2PTDF1\Monitored
C status
data
Monitoring\I/O
2nd harmonic
status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.Blk2HSt.phsA ACT BOOLEAN ST B StatNrml P,H BLKD2H_A restraint block
prot\TR2PTDF1\Monitored
phase A status
data
Monitoring\I/O
2nd harmonic
status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.Blk2HSt.phsB ACT BOOLEAN ST B StatNrml P,H BLKD2H_B restraint block
prot\TR2PTDF1\Monitored
phase B status
data
Monitoring\I/O
2nd harmonic
status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.Blk2HSt.phsC ACT BOOLEAN ST B StatNrml P,H BLKD2H_C restraint block
prot\TR2PTDF1\Monitored
phase C status
data
Monitoring\I/O
5th harmonic
status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.Blk5HSt.phsA ACT BOOLEAN ST B StatNrml P,H BLKD5H_A restraint block
prot\TR2PTDF1\Monitored
phase A status
data
Monitoring\I/O
5th harmonic
status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.Blk5HSt.phsB ACT BOOLEAN ST B StatNrml P,H BLKD5H_B restraint block
prot\TR2PTDF1\Monitored
phase B status
data
Monitoring\I/O
5th harmonic
status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.Blk5HSt.phsC ACT BOOLEAN ST B StatNrml P,H BLKD5H_C restraint block
prot\TR2PTDF1\Monitored
phase C status
data
266
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Connection
group Monitoring\I/O
compensated status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.ScyAComp.phsA.cVal.mag.f WYE FLOAT32 MX B I1 I_AMPL_A2 0.00...40.00 xIr
secondary prot\TR2PTDF1\Monitored
current phase data
A
Connection
group Monitoring\I/O
compensated status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.ScyAComp.phsB.cVal.mag.f WYE FLOAT32 MX B I1 I_AMPL_B2 0.00...40.00 xIr
secondary prot\TR2PTDF1\Monitored
current phase data
B
Connection
group Monitoring\I/O
compensated status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.ScyAComp.phsC.cVal.mag.f WYE FLOAT32 MX B I1 I_AMPL_C2 0.00...40.00 xIr
secondary prot\TR2PTDF1\Monitored
current phase data
C
Connection
group Monitoring\I/O
compensated status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.PriAComp.phsA.cVal.mag.f WYE FLOAT32 MX B I1 I_AMPL_A1 0.00...40.00 xIr
primary prot\TR2PTDF1\Monitored
current phase data
A
Connection
group Monitoring\I/O
compensated status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.PriAComp.phsB.cVal.mag.f WYE FLOAT32 MX B I1 I_AMPL_B1 0.00...40.00 xIr
primary prot\TR2PTDF1\Monitored
current phase data
B
Connection
group Monitoring\I/O
compensated status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.PriAComp.phsC.cVal.mag.f WYE FLOAT32 MX B I1 I_AMPL_C1 0.00...40.00 xIr
primary prot\TR2PTDF1\Monitored
current phase data
C
Current phase Monitoring\I/O
angle phase A -180.00...180.00 status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.AngPriAB.mag.f MV FLOAT32 MX B I1 I_ANGL_A1_B1
to B, winding deg prot\TR2PTDF1\Monitored
1 data
Current phase Monitoring\I/O
angle phase B -180.00...180.00 status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.AngPriBC.mag.f MV FLOAT32 MX B I1 I_ANGL_B1_C1
to C, winding deg prot\TR2PTDF1\Monitored
1 data
Current phase Monitoring\I/O
angle phase C -180.00...180.00 status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.AngPriCA.mag.f MV FLOAT32 MX B I1 I_ANGL_C1_A1
to A, winding deg prot\TR2PTDF1\Monitored
1 data
Current phase -180.00...180.00 Monitoring\I/O
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.AngScyAB.mag.f MV FLOAT32 MX B I1 I_ANGL_A2_B2
angle phase A deg status\Differential

267
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

to B, winding prot\TR2PTDF1\Monitored
2 data
Current phase Monitoring\I/O
angle phase B -180.00...180.00 status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.AngScyBC.mag.f MV FLOAT32 MX B I1 I_ANGL_B2_C2
to C, winding deg prot\TR2PTDF1\Monitored
2 data
Current phase Monitoring\I/O
angle phase C -180.00...180.00 status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.AngScyCA.mag.f MV FLOAT32 MX B I1 I_ANGL_C2_A2
to A, winding deg prot\TR2PTDF1\Monitored
2 data
Current phase
Monitoring\I/O
angle diff
-180.00...180.00 status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.AngPriScyA.mag.f MV FLOAT32 MX B I1 I_ANGL_A1_A2 between
deg prot\TR2PTDF1\Monitored
winding 1 and
data
2, phase A
Current phase
Monitoring\I/O
angle diff
-180.00...180.00 status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.AngPriScyB.mag.f MV FLOAT32 MX B I1 I_ANGL_B1_B2 between
deg prot\TR2PTDF1\Monitored
winding 1 and
data
2, phase B
Current phase
Monitoring\I/O
angle diff
-180.00...180.00 status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2LPDIF1.AngPriScyC.mag.f MV FLOAT32 MX B I1 I_ANGL_C1_C2 between
deg prot\TR2PTDF1\Monitored
winding 1 and
data
2, phase C
2nd harmonic
Monitoring\I/O
restraint
status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2H2PHAR1.Str.general ACD BOOLEAN ST B I1 BLKD2HPHAR blocking for (A,B,C)
prot\TR2PTDF1\Monitored
PHAR LN,
data
combined
2nd harmonic
Monitoring\I/O
restraint
status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2H2PHAR1.Str.phsA ACD BOOLEAN ST B I1 BLKD2HPHAR_A blocking for
prot\TR2PTDF1\Monitored
PHAR LN,
data
phase A
2nd harmonic
Monitoring\I/O
restraint
status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2H2PHAR1.Str.phsB ACD BOOLEAN ST B I1 BLKD2HPHAR_B blocking for
prot\TR2PTDF1\Monitored
PHAR LN,
data
phase B
2nd harmonic
Monitoring\I/O
restraint
status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2H2PHAR1.Str.phsC ACD BOOLEAN ST B I1 BLKD2HPHAR_C blocking for
prot\TR2PTDF1\Monitored
PHAR LN,
data
phase C
Differential Monitoring\I/O
current second status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2H2PHAR1.AHRat.phsA.cVal.mag.f WYE FLOAT32 MX B I1 I_2H_RAT_A 0.00...1.00
harmonic ratio, prot\TR2PTDF1\Monitored
phase A data

268
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Differential Monitoring\I/O
current second status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2H2PHAR1.AHRat.phsB.cVal.mag.f WYE FLOAT32 MX B I1 I_2H_RAT_B 0.00...1.00
harmonic ratio, prot\TR2PTDF1\Monitored
phase B data
Differential Monitoring\I/O
current second status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2H2PHAR1.AHRat.phsC.cVal.mag.f WYE FLOAT32 MX B I1 I_2H_RAT_C 0.00...1.00
harmonic ratio, prot\TR2PTDF1\Monitored
phase C data
5th harmonic
Monitoring\I/O
restraint
status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2H5PHAR1.Str.general ACD BOOLEAN ST B I1 BLKD5HPHAR blocking for (A,B,C)
prot\TR2PTDF1\Monitored
PHAR LN,
data
combined
5th harmonic
Monitoring\I/O
restraint
status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2H5PHAR1.Str.phsA ACD BOOLEAN ST B I1 BLKD5HPHAR_A blocking for
prot\TR2PTDF1\Monitored
PHAR LN,
data
phase A
5th harmonic
Monitoring\I/O
restraint
status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2H5PHAR1.Str.phsB ACD BOOLEAN ST B I1 BLKD5HPHAR_B blocking for
prot\TR2PTDF1\Monitored
PHAR LN,
data
phase B
5th harmonic
Monitoring\I/O
restraint
status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2H5PHAR1.Str.phsC ACD BOOLEAN ST B I1 BLKD5HPHAR_C blocking for
prot\TR2PTDF1\Monitored
PHAR LN,
data
phase C
Differential Monitoring\I/O
current fifth status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2H5PHAR1.AHRat.phsA.cVal.mag.f WYE FLOAT32 MX B I1 I_5H_RAT_A 0.00...1.00
harmonic ratio, prot\TR2PTDF1\Monitored
phase A data
Differential Monitoring\I/O
current fifth status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2H5PHAR1.AHRat.phsB.cVal.mag.f WYE FLOAT32 MX B I1 I_5H_RAT_B 0.00...1.00
harmonic ratio, prot\TR2PTDF1\Monitored
phase B data
Differential Monitoring\I/O
current fifth status\Differential
TR2PTDF1 3dI>T(1) 87T(1) MON LD0.TR2H5PHAR1.AHRat.phsC.cVal.mag.f WYE FLOAT32 MX B I1 I_5H_RAT_C 0.00...1.00
harmonic ratio, prot\TR2PTDF1\Monitored
phase C data
Operation Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2PTRC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
Off/On prot\TR2PTDF1
Basic setting
Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2LPDIF1.LoSet.setMag.f ASG FLOAT32 SG B 20 Low operate value for biased 5...50 %Ir
prot\TR2PTDF1
operation
5=Waveform;
6=2.h + Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2LPDIF1.RstMod.setVal ENG Enum SG B 9 Restraint mode Restraint mode
waveform; 8=5.h prot\TR2PTDF1
+ waveform;

269
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

9=2.h + 5.h +
wav
Slope of the
second line of Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2LPDIF1.SpeScn2.setMag.f ASG FLOAT32 SG B 30 Slope section 2 10...50 %
the operating prot\TR2PTDF1
characteristics
Turn-point
between the
second and the Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2LPDIF1.EndScn2.setMag.f ASG FLOAT32 SG B 150 End section 2 100...500 %Ir
third line of prot\TR2PTDF1
the operating
characteristics
Slope of the
third line of Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2LPDIF1.SpeScn3.setMag.f ASG FLOAT32 SG A 100 Slope section 3 10...100 %
the operating prot\TR2PTDF1
characteristics
CT connection
type.
Determined by
CT connection the directions 1=Type 1; Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2LPDIF1.CTConnTyp.setVal ENG Enum SP B 1
type of the 2=Type 2 prot\TR2PTDF1
connected
current
transformers
Connection of
1=Y; 2=YN; Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2LPDIF1.Wnd1Typ.setVal ENG Enum SP B 1 Winding 1 type the HV side
3=D; 4=Z; 5=ZN prot\TR2PTDF1
windings
Connection of
1=y; 2=yn; 3=d; Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2LPDIF1.Wnd2Typ.setVal ENG Enum SP B 1 Winding 2 type the LV side
4=z; 5=zn prot\TR2PTDF1
windings
Setting the 0=Clk Num 0;
phase shift 1=Clk Num 1;
between HV 2=Clk Num 2;
and LV with 4=Clk Num 4;
clock number 5=Clk Num 5; Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2LPDIF1.ClkNum.setVal ENG Enum SP B 0 Clock number
for connection 6=Clk Num 6; prot\TR2PTDF1
group 7=Clk Num 7;
compensation 8=Clk Num 8;
(e.g. Dyn11 -> 10=Clk Num 10;
11) 11=Clk Num 11
1=Not
Elimination of eliminated;
the zero- 2=Winding 1; Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2LPDIF1.ZroAElm.setVal ENG Enum SP B 1 Zro A elimination
sequence 3=Winding 2; prot\TR2PTDF1
current 4=Winding 1
and 2
The tap
position
Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2LPDIF1.MinWndTap.setVal ING INT32 SP A 36 Min winding tap number -36...36
prot\TR2PTDF1
resulting the
minimum
270
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

number of
effective
winding turns
on the side of
the transformer
where the tap
changer is.
The tap
position
number
resulting the
maximum
number of Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2LPDIF1.MaxWndTap.setVal ING INT32 SP A 0 Max winding tap -36...36
effective prot\TR2PTDF1
winding turns
on the side of
the transformer
where the tap
changer is.
The nominal
position of the
tap changer
resulting the
default Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2LPDIF1.TapNomLTC1.setVal ING INT32 SP A,I 18 Tap nominal -36...36
transformation prot\TR2PTDF1
ratio of the
transformer (as
if there was no
tap changer)
The winding
1=Not in use;
where the tap Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2LPDIF1.TapWnd.setVal ENG Enum SP A 1 Tapped winding 2=Winding 1;
changer is prot\TR2PTDF1
3=Winding 2
connected to
The percentage
change in
voltage Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2LPDIF1.StepTap1.setMag.f ASG FLOAT32 SP A 1.50 Step of tap 0.60...9.00 %
corresponding prot\TR2PTDF1
one step of the
tap changer
2. harmonic
Harmonic deblock deblocking in Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2LPDIF1.HDBlk.setVal SPG BOOLEAN SG A 1
2. case of switch prot\TR2PTDF1
on to fault
CT ratio
CT ratio Cor Wnd Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2LPDIF1.CTRatCor1.setMag.f ASG FLOAT32 SP B 1.00 correction, 0.40...4.00
1 prot\TR2PTDF1
winding 1
CT ratio
CT ratio Cor Wnd Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2LPDIF1.CTRatCor2.setMag.f ASG FLOAT32 SP B 1.00 correction, 0.40...4.00
2 prot\TR2PTDF1
winding 2
2. harmonic Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2H2PHAR1.PhStr.setMag.f ASG FLOAT32 SG B 15 Start value 2.H 7...20 %
blocking ratio prot\TR2PTDF1
271
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

5. harmonic Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2H5PHAR1.PhStr.setMag.f ASG FLOAT32 SG B 35 Start value 5.H 10...50 %
blocking ratio prot\TR2PTDF1
5. harmonic
Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2H5PHAR1.PhStop.setMag.f ASG FLOAT32 SG A 35 Stop value 5.H deblocking 10...50 %
prot\TR2PTDF1
ratio
5. harmonic
Harmonic deblock deblocking in Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2H5PHAR1.HDBlk.setVal SPG BOOLEAN SG A 0
5. case of severe prot\TR2PTDF1
overvoltage
Instantaneous Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2HPDIF1.HiSet.setMag.f ASG FLOAT32 SG B 1000 High operate value 500...3000 %Ir
stage setting prot\TR2PTDF1
Enable high set Settings\Settings\Differential
TR2PTDF1 3dI>T(1) 87T(1) SET LD0.TR2HPDIF1.EnaHiSet.setVal SPG BOOLEAN SG A 1 Enable high set
stage prot\TR2PTDF1
0=Reset;
9=Activate
OPERATE;
10=Deactive
OPERATE;
59=Activate
OPR_LS;
60=Deactive
OPR_LS;
61=Activate
OPR_HS;
62=Deactive
Test control Tests\Function
TR2PTDF1 3dI>T(1) 87T(1) TES LD0.TR2LPDIF1.TestPro.Oper.ctlVal ENC Enum CO B 0 TR2PTDF1 OPR_HS;
for outputs tests\Differential prot
63=Activate
BLKD2H;
64=Deactive
BLKD2H;
65=Activate
BLKD5H;
66=Deactive
BLKD5H;
67=Activate
BLKDWAV;
68=Deactive
BLKDWAV
VisString255
TR2PTDF1 3dI>T(1) 87T(1) VER LD0.TR2LPDIF1.NamPlt.swRev LPL DC ED1 C1 (Name plate)
(20)

LREFPNDF1: Low impedance restricted earth fault protection: D1


IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
(ACT input
LREFPNDF1 dIoLo>(1) 87NL(1) INP Channel I3P
channel)
(ACT input
LREFPNDF1 dIoLo>(1) 87NL(1) INP Channel IRES
channel)

272
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Block signal
Monitoring\I/O
for activating
LREFPNDF1 dIoLo>(1) 87NL(1) INP LD0.LREFPDIF1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK status\Differential
the blocking
prot\LREFPNDF1\Inputs
mode
Monitoring\I/O
LREFPNDF1 dIoLo>(1) 87NL(1) OUT LD0.LREFPDIF1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start status\Differential
prot\LREFPNDF1\Outputs
Monitoring\I/O
LREFPNDF1 dIoLo>(1) 87NL(1) OUT LD0.LREFPDIF1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate status\Differential
prot\LREFPNDF1\Outputs
Monitoring\I/O
2nd harmonic
LREFPNDF1 dIoLo>(1) 87NL(1) OUT LD0.LREFPDIF1.Blk2HSt.general ACT BOOLEAN ST B BLK2H status\Differential
block
prot\LREFPNDF1\Outputs
1=on; 2=blocked;
3=test;
LREFPNDF1 dIoLo>(1) 87NL(1) MON LD0.LREFPDIF1.Beh.stVal ENS Enum ST B LREFPNDF1 Status Monitoring\FB status
4=test/blocked;
5=off
Directional Monitoring\I/O
differential status\Differential
LREFPNDF1 dIoLo>(1) 87NL(1) MON LD0.LREFPDIF1.DifAClc.res.cVal.mag.f WYE FLOAT32 MX B I1 ID_COSPHI 0.00...80.00 xIn IL1TCTR1
current Id prot\LREFPNDF1\Monitored
cosphi data
Monitoring\I/O
status\Differential
LREFPNDF1 dIoLo>(1) 87NL(1) MON LD0.LREFPDIF1.RstA.res.cVal.mag.f WYE FLOAT32 MX B I1 IB Bias current 0.00...80.00 xIn IL1TCTR1
prot\LREFPNDF1\Monitored
data
Monitoring\I/O
Ratio of start
status\Differential
LREFPNDF1 dIoLo>(1) 87NL(1) MON LD0.LREFPDIF1.StrDur.mag.f MV FLOAT32 MX B START_DUR time / operate 0.00...100.00 %
prot\LREFPNDF1\Monitored
time
data
Monitoring\I/O
2nd harmonic status\Differential
LREFPNDF1 dIoLo>(1) 87NL(1) MON LD0.LREFPHAR1.Str.general ACD BOOLEAN ST B I1 RES2H
restraint prot\LREFPNDF1\Monitored
data
Operation Off Settings\Settings\Differential
LREFPNDF1 dIoLo>(1) 87NL(1) SET LD0.LREFPDIF1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
/ On prot\LREFPNDF1
Settings\Settings\Differential
LREFPNDF1 dIoLo>(1) 87NL(1) SET LD0.LREFPDIF1.LoSet.setMag.f ASG FLOAT32 SG B 5.0 Operate value Operate value 5.0...50.0 %In
prot\LREFPNDF1
Minimum Minimum Settings\Settings\Differential
LREFPNDF1 dIoLo>(1) 87NL(1) SET LD0.LREFPDIF1.MinOpTmms.setVal ING INT32 SG A 40 40...300000 ms
operate time operate time prot\LREFPNDF1
Restraint Restraint 1=None; Settings\Settings\Differential
LREFPNDF1 dIoLo>(1) 87NL(1) SET LD0.LREFPDIF1.RstMod.setVal ENG Enum SG A 1
mode mode 2=Harmonic2 prot\LREFPNDF1
Reset delay Reset delay Settings\Settings\Differential
LREFPNDF1 dIoLo>(1) 87NL(1) SET LD0.LREFPDIF1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
time time prot\LREFPNDF1
CT CT
1=Type 1; 2=Type Settings\Settings\Differential
LREFPNDF1 dIoLo>(1) 87NL(1) SET LD0.LREFPDIF1.CTConnTyp.setVal ENG Enum SP B 2 connection connection
2 prot\LREFPNDF1
type type
The ratio of
Start value Settings\Settings\Differential
LREFPNDF1 dIoLo>(1) 87NL(1) SET LD0.LREFPHAR1.PhStr.setMag.f ASG FLOAT32 SG A 50 the 2. 10...50 %
2.H prot\LREFPNDF1
harmonic to
273
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

fundamental
component
required for
blocking
0=Reset;
1=Activate
START;
2=Deactive
START;
9=Activate
Test control Tests\Function
LREFPNDF1 dIoLo>(1) 87NL(1) TES LD0.LREFPDIF1.TstOutCmd.Oper.ctlVal ENC Enum CO B 0 LREFPNDF1 OPERATE;
for outputs tests\Differential prot
10=Deactive
OPERATE;
35=Activate
BLK2H;
36=Deactive
BLK2H
VisString255
LREFPNDF1 dIoLo>(1) 87NL(1) VER LD0.LREFPDIF1.NamPlt.swRev LPL DC ED1 D1 (Name plate)
(20)

UZPDIS1: Under impedance protection: A1


Parameter Parameter Channel
IEC 61850 IEC 60617 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
name desc relation
Z<g(1)< (ACT input
UZPDIS1 21G(1) INP Channel U3P
td=""></g(1)<> channel)
Z<g(1)< (ACT input
UZPDIS1 21G(1) INP Channel I3P
td=""></g(1)<> channel)
Block signal
Monitoring\I/O
Z<g(1)< for activating
UZPDIS1 21G(1) INP LD0.UZPDIS1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK status\Impedance
td=""></g(1)<> the blocking
protection\UZPDIS1\Inputs
mode
Monitoring\I/O
Z<g(1)<
UZPDIS1 21G(1) OUT LD0.UZPDIS1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 START Start status\Impedance
td=""></g(1)<>
protection\UZPDIS1\Outputs
Monitoring\I/O
Z<g(1)<
UZPDIS1 21G(1) OUT LD0.UZPDIS1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate status\Impedance
td=""></g(1)<>
protection\UZPDIS1\Outputs
1=on;
2=blocked;
Z<g(1)<
UZPDIS1 21G(1) MON LD0.UZPDIS1.Beh.stVal ENS Enum ST B UZPDIS1 Status 3=test; Monitoring\FB status
td=""></g(1)<>
4=test/blocked;
5=off
Monitoring\I/O
Ratio of start
Z<g(1)< status\Impedance
UZPDIS1 21G(1) MON LD0.UZPDIS1.StrDur.mag.f MV FLOAT32 MX B START_DUR time / operate 0.00...100.00 %
td=""></g(1)<> protection\UZPDIS1\Monitored
time (in %)
data
Phase-to- 0.00...200.00 Monitoring\I/O
UZMMXU1 MON LD0.UZMMXU1.ZPP.phsAB.cVal.mag.f DEL FLOAT32 MX B I1 Z_AMPL_AB
phase A-B xZn status\Impedance
274
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

impedance protection\UZPDIS1\Monitored
amplitude data
Phase-to- Monitoring\I/O
phase B-C 0.00...200.00 status\Impedance
UZMMXU1 MON LD0.UZMMXU1.ZPP.phsBC.cVal.mag.f DEL FLOAT32 MX B I1 Z_AMPL_BC
impedance xZn protection\UZPDIS1\Monitored
amplitude data
Phase-to- Monitoring\I/O
phase C-A 0.00...200.00 status\Impedance
UZMMXU1 MON LD0.UZMMXU1.ZPP.phsCA.cVal.mag.f DEL FLOAT32 MX B I1 Z_AMPL_CA
impedance xZn protection\UZPDIS1\Monitored
amplitude data
Z<g(1)< Operation Off Settings\Settings\Impedance
UZPDIS1 21G(1) SET LD0.UZPDIS1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
td=""></g(1)<> / On protection\UZPDIS1
Radius of the
Z<g(1)< Percentage Settings\Settings\Impedance
UZPDIS1 21G(1) SET LD0.UZPDIS1.PoRch.setMag.f ASG FLOAT32 SG B 7 origin centric 1...6000 %Zn
td=""></g(1)<> reach protection\UZPDIS1
circle
Z<g(1)< Operate delay Operate delay Settings\Settings\Impedance
UZPDIS1 21G(1) SET LD0.UZPDIS1.OpDlTmms.setVal ING INT32 SG B 200 40...200000 ms
td=""></g(1)<> time time protection\UZPDIS1
Z<g(1)< Reset delay Reset delay Settings\Settings\Impedance
UZPDIS1 21G(1) SET LD0.UZPDIS1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
td=""></g(1)<> time time protection\UZPDIS1
Selects used
Z<g(1)< Measurement 2=DFT; 3=Peak- Settings\Settings\Impedance
UZPDIS1 21G(1) SET LD0.UZPDIS1.AMeasMod.setVal ENG Enum SP B 2 measurement
td=""></g(1)<> mode to-Peak protection\UZPDIS1
mode
Select voltage
2=1Phase-to-
and current
Z<g(1)< Impedance phase; Settings\Settings\Impedance
UZPDIS1 21G(1) SET LD0.UZPDIS1.ZMeasMod.setVal ENG Enum SP B 4 signals for
td=""></g(1)<> Meas mode 4=3Phase-to- protection\UZPDIS1
impedance
phase
calculation
Z<g(1)< Phase Sel for Voltage phase 1=AB; 2=BC; Settings\Settings\Impedance
UZPDIS1 21G(1) SET LD0.UZPDIS1.PhSelZClc.setVal ENG Enum SP B 1
td=""></g(1)<> Z Clc selection 3=CA protection\UZPDIS1
0=Reset;
1=Activate
START;
2=Deactive
Z<g(1)< Test control Tests\Function tests\Impedance
UZPDIS1 21G(1) TES LD0.UZPDIS1.TstOutCmd.Oper.ctlVal ENC Enum CO B 1 UZPDIS1 START;
td=""></g(1)<> for outputs protection
9=Activate
OPERATE;
10=Deactive
OPERATE
Z<g(1)< VisString255
UZPDIS1 21G(1) VER LD0.UZPDIS1.NamPlt.swRev LPL DC ED1 A1 (Name plate)
td=""></g(1)<> (20)

DSTPDIS1: Distance protection: B1


IEC
Categor CD Acces Defaul Even CM Channel
IEC 61850 6061 ANSI IECName Type FC Dataset Parameter name Parameter desc Parameter range Menu path
y C s t t T relation
7
DSTPDIS 21P(1 (ACT input
Z<(1) INP Channel U3P
1 ) channel)
275
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

DSTPDIS 21P(1 (ACT input


Z<(1) INP Channel I3P
1 ) channel)
DSTPDIS 21P(1 (ACT input
Z<(1) INP Channel I3P_PAR
1 ) channel)
DSTPDIS 21P(1 (ACT input
Z<(1) INP Channel I3P_REF
1 ) channel)
DSTPDIS 21P(1 (ACT input
Z<(1) INP Channel URES
1 ) channel)
Block signal for
DSTPDIS 21P(1 Monitoring\I/O status\Distance
Z<(1) INP LD0.GFCPDIS1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK activating the
1 ) protection\DSTPDIS1\Inputs
blocking mode
DSTPDIS 21P(1 Network Monitoring\I/O status\Distance
Z<(1) INP LD0.GFCPDIS1.GndMod.stVal SPS BOOLEAN ST B 0 I1 SYS_EARTHING
1 ) earthing method protection\DSTPDIS1\Inputs
External
DSTPDIS 21P(1 Monitoring\I/O status\Distance
Z<(1) INP LD0.GFCPDIS1.RcdTrg.stVal SPC BOOLEAN ST B 0 I1 TRIGG_REC triggering for all
1 ) protection\DSTPDIS1\Inputs
recorded data
DSTPDIS 21P(1 Block GFC Monitoring\I/O status\Distance
Z<(1) INP LD0.GFCPDIS1.BlkOp.stVal SPS BOOLEAN ST B 0 I1 BLOCK_GFC
1 ) operate protection\DSTPDIS1\Inputs
DSTPDIS 21P(1 Monitoring\I/O status\Distance
Z<(1) INP LD0.DST1PDIS1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK_Z1 Block zone 1
1 ) protection\DSTPDIS1\Inputs
DSTPDIS 21P(1 Monitoring\I/O status\Distance
Z<(1) INP LD0.DST2PDIS1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK_Z2 Block zone 2
1 ) protection\DSTPDIS1\Inputs
DSTPDIS 21P(1 Monitoring\I/O status\Distance
Z<(1) INP LD0.DST3PDIS1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK_Z3 Block zone 3
1 ) protection\DSTPDIS1\Inputs
DSTPDIS 21P(1 Monitoring\I/O status\Distance
Z<(1) INP LD0.DST4PDIS1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK_Z4 Block zone 4
1 ) protection\DSTPDIS1\Inputs
DSTPDIS 21P(1 Monitoring\I/O status\Distance
Z<(1) INP LD0.DST5PDIS1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK_Z5 Block zone 5
1 ) protection\DSTPDIS1\Inputs
DSTPDIS 21P(1 AC StatNrm Monitoring\I/O status\Distance
Z<(1) OUT LD0.GFCPDIS1.Str.general BOOLEAN ST B P,H I1 START_GFC Start, GFC
1 ) D l protection\DSTPDIS1\Outputs
Time delayed
DSTPDIS 21P(1 StatNrm P,H, Monitoring\I/O status\Distance
Z<(1) OUT LD0.GFCPDIS1.Op.general ACT BOOLEAN ST B I1 OPERATE_GFC operate signal,
1 ) l T protection\DSTPDIS1\Outputs
GFC
Indication of a
DSTPDIS 21P(1 cross-country- Monitoring\I/O status\Distance
Z<(1) OUT LD0.GFCPDIS1.XcnDet.stVal SPS BOOLEAN ST B I1 XC_FLT
1 ) fault (high imp. protection\DSTPDIS1\Outputs
earthed), GFC
DSTPDIS 21P(1 AC StatNrm General start Monitoring\I/O status\Distance
Z<(1) OUT LD0.DST1PDIS1.Str.general BOOLEAN ST B P,H I1 START_Z1
1 ) D l signal, zone 1 protection\DSTPDIS1\Outputs
Time delayed
DSTPDIS 21P(1 StatNrm P,H, Monitoring\I/O status\Distance
Z<(1) OUT LD0.DST1PDIS1.Op.general ACT BOOLEAN ST B I1 OPERATE_Z1 operate signal,
1 ) l T protection\DSTPDIS1\Outputs
zone 1
DSTPDIS 21P(1 AC StatNrm General start Monitoring\I/O status\Distance
Z<(1) OUT LD0.DST2PDIS1.Str.general BOOLEAN ST B P,H I1 START_Z2
1 ) D l signal, zone 2 protection\DSTPDIS1\Outputs
Time delayed
DSTPDIS 21P(1 StatNrm P,H, Monitoring\I/O status\Distance
Z<(1) OUT LD0.DST2PDIS1.Op.general ACT BOOLEAN ST B I1 OPERATE_Z2 operate signal,
1 ) l T protection\DSTPDIS1\Outputs
zone 2

276
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

DSTPDIS 21P(1 AC StatNrm General start Monitoring\I/O status\Distance


Z<(1) OUT LD0.DST3PDIS1.Str.general BOOLEAN ST B P,H I1 START_Z3
1 ) D l signal, zone 3 protection\DSTPDIS1\Outputs
Time delayed
DSTPDIS 21P(1 StatNrm P,H, Monitoring\I/O status\Distance
Z<(1) OUT LD0.DST3PDIS1.Op.general ACT BOOLEAN ST B I1 OPERATE_Z3 operate signal,
1 ) l T protection\DSTPDIS1\Outputs
zone 3
DSTPDIS 21P(1 AC StatNrm General start Monitoring\I/O status\Distance
Z<(1) OUT LD0.DST4PDIS1.Str.general BOOLEAN ST B P,H I1 START_Z4
1 ) D l signal, zone 4 protection\DSTPDIS1\Outputs
Time delayed
DSTPDIS 21P(1 StatNrm P,H, Monitoring\I/O status\Distance
Z<(1) OUT LD0.DST4PDIS1.Op.general ACT BOOLEAN ST B I1 OPERATE_Z4 operate signal,
1 ) l T protection\DSTPDIS1\Outputs
zone 4
DSTPDIS 21P(1 AC StatNrm General start Monitoring\I/O status\Distance
Z<(1) OUT LD0.DST5PDIS1.Str.general BOOLEAN ST B P,H I1 START_Z5
1 ) D l signal, zone 5 protection\DSTPDIS1\Outputs
Time delayed
DSTPDIS 21P(1 StatNrm P,H, Monitoring\I/O status\Distance
Z<(1) OUT LD0.DST5PDIS1.Op.general ACT BOOLEAN ST B I1 OPERATE_Z5 operate signal,
1 ) l T protection\DSTPDIS1\Outputs
zone 5
DSTPDIS 21P(1 (Recorded data
Z<(1) CTR LD0.GFCPDIS1.RcdTrg.Oper.ctlVal SPC BOOLEAN CO I1
1 ) trigg)
DSTPDIS 21P(1 (Recorded data
Z<(1) CTR LD0.GFCPDIS1.RcdRs.Oper.ctlVal SPC BOOLEAN CO I1
1 ) reset)
1=on;
2=blocked;
DSTPDIS 21P(1 Monitoring\FB status\Distance
Z<(1) MON LD0.GFCPDIS1.Beh.stVal ENS Enum ST B DSTPDIS1 Status 3=test;
1 ) protection
4=test/blocked;
5=off
4=AB Fault;
5=BC Fault;
6=CA Fault;
Start signals for Monitoring\I/O status\Distance
DSTPDIS 21P(1 7=ABC Fault; -
Z<(1) MON LD0.GFCPDIS1.FltLoop.stVal ENS Enum ST B I1 STARTS_GFC phases A, B and protection\DSTPDIS1\Monitore
1 ) 5=No fault;
C, GFC d data
1=AG Fault;
2=BG Fault;
3=CG Fault
5=BC Fault;
Release signals 6=CA Fault; Monitoring\I/O status\Distance
DSTPDIS 21P(1
Z<(1) MON LD0.GFCPDIS1.RelPPLoop.stVal ENS Enum ST B I1 RELEASE_PP for PP/3P loops, 7=ABC Fault; protection\DSTPDIS1\Monitore
1 )
GFC 4=AB Fault; - d data
5=No fault
-5=No fault;
1=AG Fault;
2=BG Fault;
Release signals Monitoring\I/O status\Distance
DSTPDIS 21P(1 3=CG Fault;
Z<(1) MON LD0.GFCPDIS1.RelPhLoop.stVal ENS Enum ST B I1 RELEASE_PE for PE-loops, protection\DSTPDIS1\Monitore
1 ) 4=AB Fault;
GFC d data
5=BC Fault;
6=CA Fault;
7=ABC Fault
Indication of a Monitoring\I/O status\Distance
DSTPDIS 21P(1
Z<(1) MON LD0.GFCPDIS1.EFDet.stVal SPS BOOLEAN ST B I1 EARTH_FLT single phase protection\DSTPDIS1\Monitore
1 )
earth-fault, GFC d data

277
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Earth-fault 0=unknown;
Monitoring\I/O status\Distance
DSTPDIS 21P(1 AC direction (low 1=forward;
Z<(1) MON LD0.GFCRDIR1.Dir.dirGeneral Enum ST B DIR_E_FLT protection\DSTPDIS1\Monitore
1 ) D imp. earthed), 2=backward;
d data
GFC 3=both
Monitoring\I/O status\Distance
DSTPDIS 21P(1 Voltage memory
Z<(1) MON LD0.GFCRDIR1.VMemUsedSt.stVal SPS BOOLEAN ST B I1 VMEM_USED protection\DSTPDIS1\Monitore
1 ) in use status
d data
PP/3P-loop - Monitoring\I/O status\Distance
DSTPDIS 21P(1 M
Z<(1) MON LD0.DST1PDIS1.PPLoopRis.mag.f MV FLOAT32 B I1 FLTLOOP_RPP resistance, zone 3000.00...3000.0 protection\DSTPDIS1\Monitore
1 ) X
1 0 ohm d data
- Monitoring\I/O status\Distance
DSTPDIS 21P(1 M PP/3P-loop
Z<(1) MON LD0.DST1PDIS1.PPLoopX.mag.f MV FLOAT32 B I1 FLTLOOP_XPP 3000.00...3000.0 protection\DSTPDIS1\Monitore
1 ) X reactance, zone 1
0 ohm d data
Start signals for Monitoring\I/O status\Distance
DSTPDIS 21P(1
Z<(1) MON LD0.DST1PDIS1.FltLoopZn.stVal INS INT32 ST B I1 STARTS_Z1 phases A, B and -5...31 protection\DSTPDIS1\Monitore
1 )
C, zone 1 d data
Resistance used
- Monitoring\I/O status\Distance
DSTPDIS 21P(1 M in dir.
Z<(1) MON LD0.DST1PDIS1.DirRisZn.mag.f MV FLOAT32 B I1 DIR_LOOP_R 3000.00...3000.0 protection\DSTPDIS1\Monitore
1 ) X evaluation, zone
0 ohm d data
1
Reactance used - Monitoring\I/O status\Distance
DSTPDIS 21P(1 M
Z<(1) MON LD0.DST1PDIS1.DirReactZn.mag.f MV FLOAT32 B I1 DIR_LOOP_X in dir. eval., zone 3000.00...3000.0 protection\DSTPDIS1\Monitore
1 ) X
1 0 ohm d data
First PE-loop - Monitoring\I/O status\Distance
DSTPDIS 21P(1 M
Z<(1) MON LD0.DST1PDIS1.PhLoopRis1.mag.f MV FLOAT32 B I1 FLTLOOP_RFST resistance, zone 3000.00...3000.0 protection\DSTPDIS1\Monitore
1 ) X
1 0 ohm d data
- Monitoring\I/O status\Distance
DSTPDIS 21P(1 M First PE-loop
Z<(1) MON LD0.DST1PDIS1.PhLoopX1.mag.f MV FLOAT32 B I1 FLTLOOP_XFST 3000.00...3000.0 protection\DSTPDIS1\Monitore
1 ) X reactance, zone 1
0 ohm d data
Second PE-loop - Monitoring\I/O status\Distance
DSTPDIS 21P(1 M
Z<(1) MON LD0.DST1PDIS1.PhLoopRis2.mag.f MV FLOAT32 B I1 FLTLOOP_RSND resistance, zone 3000.00...3000.0 protection\DSTPDIS1\Monitore
1 ) X
1 0 ohm d data
- Monitoring\I/O status\Distance
DSTPDIS 21P(1 M Second PE-loop
Z<(1) MON LD0.DST1PDIS1.PhLoopX2.mag.f MV FLOAT32 B I1 FLTLOOP_XSND 3000.00...3000.0 protection\DSTPDIS1\Monitore
1 ) X reactance, zone 1
0 ohm d data
Phase to earth
- Monitoring\I/O status\Distance
DSTPDIS 21P(1 M reactance in
Z<(1) MON LD0.DST1PDIS1.PhReact.mag.f MV FLOAT32 B I1 FLTPH_X 3000.00...3000.0 protection\DSTPDIS1\Monitore
1 ) X phase domain,
0 ohm d data
zone 1
Monitoring\I/O status\Distance
DSTPDIS 21P(1 TLT_ANG_CONFLIC Tilt angle
Z<(1) MON LD0.DST1PDIS1.ErrTiltAng.stVal INS INT32 ST B I1 0...1023 protection\DSTPDIS1\Monitore
1 ) T conflict
d data
Start signals for Monitoring\I/O status\Distance
DSTPDIS 21P(1
Z<(1) MON LD0.DST2PDIS1.FltLoopZn.stVal INS INT32 ST B I1 STARTS_Z2 phases A, B and -5...31 protection\DSTPDIS1\Monitore
1 )
C, zone 2 d data
Start signals for Monitoring\I/O status\Distance
DSTPDIS 21P(1
Z<(1) MON LD0.DST3PDIS1.FltLoopZn.stVal INS INT32 ST B I1 STARTS_Z3 phases A, B and -5...31 protection\DSTPDIS1\Monitore
1 )
C, zone 3 d data

278
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Start signals for Monitoring\I/O status\Distance


DSTPDIS 21P(1
Z<(1) MON LD0.DST4PDIS1.FltLoopZn.stVal INS INT32 ST B I1 STARTS_Z4 phases A, B and -5...31 protection\DSTPDIS1\Monitore
1 )
C, zone 4 d data
Start signals for Monitoring\I/O status\Distance
DSTPDIS 21P(1
Z<(1) MON LD0.DST5PDIS1.FltLoopZn.stVal INS INT32 ST B I1 STARTS_Z5 phases A, B and -5...31 protection\DSTPDIS1\Monitore
1 )
C, zone 5 d data
0=unknown;
Monitoring\I/O status\Distance
DSTPDIS 21P(1 AC Direction of fault 1=forward;
Z<(1) MON LD0.DSTRDIR1.Dir.dirGeneral Enum ST B DIRECTION protection\DSTPDIS1\Monitore
1 ) D or load 2=backward;
d data
3=both
-5=No fault; -
4=ABCG Fault; -
3=CAG Fault; -
2=BCG Fault; -
1=ABG Fault;
Release signals Monitoring\Recorded
DSTPDIS 21P(1 1=AG Fault;
Z<(1) MON LD0.GFC1RFRC1.RelPhLoop.stVal ENS Enum ST B I1 Release PE-loop for PE-loops, data\Distance
1 ) 2=BG Fault;
GFC protection\DSTPDIS1\Fault 1
3=CG Fault;
4=AB Fault;
5=BC Fault;
6=CA Fault;
7=ABC Fault
-5=No fault; -
4=ABCG Fault; -
3=CAG Fault; -
2=BCG Fault; -
1=ABG Fault;
Release signals Monitoring\Recorded
DSTPDIS 21P(1 1=AG Fault;
Z<(1) MON LD0.GFC1RFRC1.RelPPLoop.stVal ENS Enum ST B I1 Release PP-loop for PP/3P loops. data\Distance
1 ) 2=BG Fault;
GFC protection\DSTPDIS1\Fault 1
3=CG Fault;
4=AB Fault;
5=BC Fault;
6=CA Fault;
7=ABC Fault
Indication of a
Monitoring\Recorded
DSTPDIS 21P(1 cross-country-
Z<(1) MON LD0.GFC1RFRC1.XcnDet.stVal SPS BOOLEAN ST B I1 Cross country fault data\Distance
1 ) fault (high imp.
protection\DSTPDIS1\Fault 1
earthed), GFC
Indication of a Monitoring\Recorded
DSTPDIS 21P(1
Z<(1) MON LD0.GFC1RFRC1.EFDet.stVal SPS BOOLEAN ST B I1 Earth fault detected single phase data\Distance
1 )
earth-fault, GFC protection\DSTPDIS1\Fault 1
Monitoring\Recorded
DSTPDIS 21P(1
Z<(1) MON LD0.GFC1RFRC1.EFDet.t SPS Timestamp ST B Time Time data\Distance
1 )
protection\DSTPDIS1\Fault 1
Earth-fault 0=unknown;
Monitoring\Recorded
DSTPDIS 21P(1 AC direction (low 1=forward;
Z<(1) MON LD0.GFC1RFRC1.EFDir.dirGeneral Enum ST B Earth-fault direction data\Distance
1 ) D impedance 2=backward;
protection\DSTPDIS1\Fault 1
earthed), GFC 3=both
Monitoring\Recorded
DSTPDIS 21P(1 Operate signal of
Z<(1) MON LD0.GFC1RFRC1.ZnOpSt.stVal INS INT32 ST B I1 Operate of all zones 0...31 data\Distance
1 ) all zones
protection\DSTPDIS1\Fault 1
279
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

0=unknown;
Monitoring\Recorded
DSTPDIS 21P(1 AC Direction of fault 1=forward;
Z<(1) MON LD0.GFC1RFRC1.DirZn1.dirGeneral Enum ST B Fault/load Dir Zn1 data\Distance
1 ) D or load zone 1 2=backward;
protection\DSTPDIS1\Fault 1
3=both
Direction - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC1RFRC1.DirRisZn1.mag.f MV FLOAT32 B I1 Dir resistance Zn1 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
1 0 ohm protection\DSTPDIS1\Fault 1
- Monitoring\Recorded
DSTPDIS 21P(1 M Direction
Z<(1) MON LD0.GFC1RFRC1.DirXZn1.mag.f MV FLOAT32 B I1 Dir reactance Zn1 3000.00...3000.0 data\Distance
1 ) X reactance, zone 1
0 ohm protection\DSTPDIS1\Fault 1
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC1RFRC1.PhLoopRis1.mag.f MV FLOAT32 B I1 Flt loop 1st Ris Zn1 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
1 0 ohm protection\DSTPDIS1\Fault 1
- Monitoring\Recorded
DSTPDIS 21P(1 M First PE-loop
Z<(1) MON LD0.GFC1RFRC1.PhLoopX1.mag.f MV FLOAT32 B I1 Flt loop 1st Rea Zn1 3000.00...3000.0 data\Distance
1 ) X reactance, zone 1
0 ohm protection\DSTPDIS1\Fault 1
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC1RFRC1.PhLoopRis2.mag.f MV FLOAT32 B I1 Flt loop 2nd Ris Zn1 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
1 0 ohm protection\DSTPDIS1\Fault 1
- Monitoring\Recorded
DSTPDIS 21P(1 M Second PE-loop
Z<(1) MON LD0.GFC1RFRC1.PhLoopX2.mag.f MV FLOAT32 B I1 Flt loop 2nd Rea Zn1 3000.00...3000.0 data\Distance
1 ) X reactance, zone 1
0 ohm protection\DSTPDIS1\Fault 1
PP-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC1RFRC1.PPLoopRis.mag.f MV FLOAT32 B I1 Flt PP-loop Ris Zn1 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
1 0 ohm protection\DSTPDIS1\Fault 1
- Monitoring\Recorded
DSTPDIS 21P(1 M PP-loop
Z<(1) MON LD0.GFC1RFRC1.PPLoopX.mag.f MV FLOAT32 B I1 Flt PP-loop Rea Zn1 3000.00...3000.0 data\Distance
1 ) X reactance, zone 1
0 ohm protection\DSTPDIS1\Fault 1
Phase to earth
- Monitoring\Recorded
DSTPDIS 21P(1 M reactance in
Z<(1) MON LD0.GFC1RFRC1.PhX.mag.f MV FLOAT32 B I1 Phase reactance Zn1 3000.00...3000.0 data\Distance
1 ) X phase domain,
0 ohm protection\DSTPDIS1\Fault 1
zone 1
Direction - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC1RFRC1.DirRisZn2.mag.f MV FLOAT32 B I1 Dir resistance Zn2 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
2 0 ohm protection\DSTPDIS1\Fault 1
Direction - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC1RFRC1.DirRisZn3.mag.f MV FLOAT32 B I1 Dir resistance Zn3 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
3 0 ohm protection\DSTPDIS1\Fault 1
Direction - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC1RFRC1.DirRisZn4.mag.f MV FLOAT32 B I1 Dir resistance Zn4 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
4 0 ohm protection\DSTPDIS1\Fault 1
Direction - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC1RFRC1.DirRisZn5.mag.f MV FLOAT32 B I1 Dir resistance Zn5 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
5 0 ohm protection\DSTPDIS1\Fault 1
- Monitoring\Recorded
DSTPDIS 21P(1 M Direction
Z<(1) MON LD0.GFC1RFRC1.DirXZn2.mag.f MV FLOAT32 B I1 Dir reactance Zn2 3000.00...3000.0 data\Distance
1 ) X reactance, zone 2
0 ohm protection\DSTPDIS1\Fault 1

280
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

- Monitoring\Recorded
DSTPDIS 21P(1 M Direction
Z<(1) MON LD0.GFC1RFRC1.DirXZn3.mag.f MV FLOAT32 B I1 Dir reactance Zn3 3000.00...3000.0 data\Distance
1 ) X reactance, zone 3
0 ohm protection\DSTPDIS1\Fault 1
- Monitoring\Recorded
DSTPDIS 21P(1 M Direction
Z<(1) MON LD0.GFC1RFRC1.DirXZn4.mag.f MV FLOAT32 B I1 Dir reactance Zn4 3000.00...3000.0 data\Distance
1 ) X reactance, zone 4
0 ohm protection\DSTPDIS1\Fault 1
- Monitoring\Recorded
DSTPDIS 21P(1 M Direction
Z<(1) MON LD0.GFC1RFRC1.DirXZn5.mag.f MV FLOAT32 B I1 Dir reactance Zn5 3000.00...3000.0 data\Distance
1 ) X reactance, zone 5
0 ohm protection\DSTPDIS1\Fault 1
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC1RFRC1.PhRisFstZn2.mag.f MV FLOAT32 I1 Flt loop 1st Ris Zn2 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
2 0 ohm protection\DSTPDIS1\Fault 1
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC1RFRC1.PhRis1Zn2.mag.f MV FLOAT32 ED1 I1 Flt loop 1st Ris Zn2 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
2 0 ohm protection\DSTPDIS1\Fault 1
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC1RFRC1.PhRisFstZn3.mag.f MV FLOAT32 I1 Flt loop 1st Ris Zn3 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
3 0 ohm protection\DSTPDIS1\Fault 1
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC1RFRC1.PhRis1Zn3.mag.f MV FLOAT32 ED1 I1 Flt loop 1st Ris Zn3 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
3 0 ohm protection\DSTPDIS1\Fault 1
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC1RFRC1.PhRisFstZn4.mag.f MV FLOAT32 I1 Flt loop 1st Ris Zn4 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
4 0 ohm protection\DSTPDIS1\Fault 1
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC1RFRC1.PhRis1Zn4.mag.f MV FLOAT32 ED1 I1 Flt loop 1st Ris Zn4 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
4 0 ohm protection\DSTPDIS1\Fault 1
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC1RFRC1.PhRisFstZn5.mag.f MV FLOAT32 I1 Flt loop 1st Ris Zn5 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
5 0 ohm protection\DSTPDIS1\Fault 1
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC1RFRC1.PhRis1Zn5.mag.f MV FLOAT32 ED1 I1 Flt loop 1st Ris Zn5 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
5 0 ohm protection\DSTPDIS1\Fault 1
- Monitoring\Recorded
DSTPDIS 21P(1 M First PE-loop
Z<(1) MON LD0.GFC1RFRC1.PhXFstZn2.mag.f MV FLOAT32 B I1 Flt loop 1st Rea Zn2 3000.00...3000.0 data\Distance
1 ) X reactance, zone 2
0 ohm protection\DSTPDIS1\Fault 1
- Monitoring\Recorded
DSTPDIS 21P(1 M First PE-loop
Z<(1) MON LD0.GFC1RFRC1.PhXFstZn3.mag.f MV FLOAT32 B I1 Flt loop 1st Rea Zn3 3000.00...3000.0 data\Distance
1 ) X reactance, zone 3
0 ohm protection\DSTPDIS1\Fault 1
- Monitoring\Recorded
DSTPDIS 21P(1 M First PE-loop
Z<(1) MON LD0.GFC1RFRC1.PhXFstZn4.mag.f MV FLOAT32 B I1 Flt loop 1st Rea Zn4 3000.00...3000.0 data\Distance
1 ) X reactance, zone 4
0 ohm protection\DSTPDIS1\Fault 1
- Monitoring\Recorded
DSTPDIS 21P(1 M First PE-loop
Z<(1) MON LD0.GFC1RFRC1.PhXFstZn5.mag.f MV FLOAT32 B I1 Flt loop 1st Rea Zn5 3000.00...3000.0 data\Distance
1 ) X reactance, zone 5
0 ohm protection\DSTPDIS1\Fault 1
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC1RFRC1.PhRisScdZn2.mag.f MV FLOAT32 I1 Flt loop 2nd Ris Zn2 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
2 0 ohm protection\DSTPDIS1\Fault 1

281
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Second PE-loop - Monitoring\Recorded


DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC1RFRC1.PhRis2Zn2.mag.f MV FLOAT32 ED1 I1 Flt loop 2nd Ris Zn2 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
2 0 ohm protection\DSTPDIS1\Fault 1
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC1RFRC1.PhRisScdZn3.mag.f MV FLOAT32 I1 Flt loop 2nd Ris Zn3 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
3 0 ohm protection\DSTPDIS1\Fault 1
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC1RFRC1.PhRis2Zn3.mag.f MV FLOAT32 ED1 I1 Flt loop 2nd Ris Zn3 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
3 0 ohm protection\DSTPDIS1\Fault 1
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC1RFRC1.PhRisScdZn4.mag.f MV FLOAT32 I1 Flt loop 2nd Ris Zn4 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
4 0 ohm protection\DSTPDIS1\Fault 1
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC1RFRC1.PhRis2Zn4.mag.f MV FLOAT32 ED1 I1 Flt loop 2nd Ris Zn4 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
4 0 ohm protection\DSTPDIS1\Fault 1
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC1RFRC1.PhRisScdZn5.mag.f MV FLOAT32 I1 Flt loop 2nd Ris Zn5 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
5 0 ohm protection\DSTPDIS1\Fault 1
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC1RFRC1.PhRis2Zn5.mag.f MV FLOAT32 ED1 I1 Flt loop 2nd Ris Zn5 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
5 0 ohm protection\DSTPDIS1\Fault 1
- Monitoring\Recorded
DSTPDIS 21P(1 M Second PE-loop
Z<(1) MON LD0.GFC1RFRC1.PhXScdZn2.mag.f MV FLOAT32 B I1 Flt loop 2nd Rea Zn2 3000.00...3000.0 data\Distance
1 ) X reactance, zone 2
0 ohm protection\DSTPDIS1\Fault 1
- Monitoring\Recorded
DSTPDIS 21P(1 M Second PE-loop
Z<(1) MON LD0.GFC1RFRC1.PhXScdZn3.mag.f MV FLOAT32 B I1 Flt loop 2nd Rea Zn3 3000.00...3000.0 data\Distance
1 ) X reactance, zone 3
0 ohm protection\DSTPDIS1\Fault 1
- Monitoring\Recorded
DSTPDIS 21P(1 M Second PE-loop
Z<(1) MON LD0.GFC1RFRC1.PhXScdZn4.mag.f MV FLOAT32 B I1 Flt loop 2nd Rea Zn4 3000.00...3000.0 data\Distance
1 ) X reactance, zone 4
0 ohm protection\DSTPDIS1\Fault 1
- Monitoring\Recorded
DSTPDIS 21P(1 M Second PE-loop
Z<(1) MON LD0.GFC1RFRC1.PhXScdZn5.mag.f MV FLOAT32 B I1 Flt loop 2nd Rea Zn5 3000.00...3000.0 data\Distance
1 ) X reactance, zone 5
0 ohm protection\DSTPDIS1\Fault 1
PP-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC1RFRC1.PPRisZn2.mag.f MV FLOAT32 B I1 Flt PP-loop Ris Zn2 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
2 0 ohm protection\DSTPDIS1\Fault 1
PP-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC1RFRC1.PPRisZn3.mag.f MV FLOAT32 B I1 Flt PP-loop Ris Zn3 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
3 0 ohm protection\DSTPDIS1\Fault 1
PP-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC1RFRC1.PPRisZn4.mag.f MV FLOAT32 B I1 Flt PP-loop Ris Zn4 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
4 0 ohm protection\DSTPDIS1\Fault 1
PP-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC1RFRC1.PPRisZn5.mag.f MV FLOAT32 B I1 Flt PP-loop Ris Zn5 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
5 0 ohm protection\DSTPDIS1\Fault 1
- Monitoring\Recorded
DSTPDIS 21P(1 M PP-loop
Z<(1) MON LD0.GFC1RFRC1.PPXZn2.mag.f MV FLOAT32 B I1 Flt PP-loop Rea Zn2 3000.00...3000.0 data\Distance
1 ) X reactance, zone 2
0 ohm protection\DSTPDIS1\Fault 1

282
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

- Monitoring\Recorded
DSTPDIS 21P(1 M PP-loop
Z<(1) MON LD0.GFC1RFRC1.PPXZn3.mag.f MV FLOAT32 B I1 Flt PP-loop Rea Zn3 3000.00...3000.0 data\Distance
1 ) X reactance, zone 3
0 ohm protection\DSTPDIS1\Fault 1
- Monitoring\Recorded
DSTPDIS 21P(1 M PP-loop
Z<(1) MON LD0.GFC1RFRC1.PPXZn4.mag.f MV FLOAT32 B I1 Flt PP-loop Rea Zn4 3000.00...3000.0 data\Distance
1 ) X reactance, zone 4
0 ohm protection\DSTPDIS1\Fault 1
- Monitoring\Recorded
DSTPDIS 21P(1 M PP-loop
Z<(1) MON LD0.GFC1RFRC1.PPXZn5.mag.f MV FLOAT32 B I1 Flt PP-loop Rea Zn5 3000.00...3000.0 data\Distance
1 ) X reactance, zone 5
0 ohm protection\DSTPDIS1\Fault 1
Phase to earth
- Monitoring\Recorded
DSTPDIS 21P(1 M reactance in
Z<(1) MON LD0.GFC1RFRC1.PhXZn2.mag.f MV FLOAT32 B I1 Phase reactance Zn2 3000.00...3000.0 data\Distance
1 ) X phase domain,
0 ohm protection\DSTPDIS1\Fault 1
zone 2
Phase to earth
- Monitoring\Recorded
DSTPDIS 21P(1 M reactance in
Z<(1) MON LD0.GFC1RFRC1.PhXZn3.mag.f MV FLOAT32 B I1 Phase reactance Zn3 3000.00...3000.0 data\Distance
1 ) X phase domain,
0 ohm protection\DSTPDIS1\Fault 1
zone 3
Phase to earth
- Monitoring\Recorded
DSTPDIS 21P(1 M reactance in
Z<(1) MON LD0.GFC1RFRC1.PhXZn4.mag.f MV FLOAT32 B I1 Phase reactance Zn4 3000.00...3000.0 data\Distance
1 ) X phase domain,
0 ohm protection\DSTPDIS1\Fault 1
zone 4
Phase to earth
- Monitoring\Recorded
DSTPDIS 21P(1 M reactance in
Z<(1) MON LD0.GFC1RFRC1.PhXZn5.mag.f MV FLOAT32 B I1 Phase reactance Zn5 3000.00...3000.0 data\Distance
1 ) X phase domain,
0 ohm protection\DSTPDIS1\Fault 1
zone 5
0=unknown;
Monitoring\Recorded
DSTPDIS 21P(1 AC Direction of fault 1=forward;
Z<(1) MON LD0.GFC1RFRC1.DirZn2.dirGeneral Enum ST B Fault/load Dir Zn2 data\Distance
1 ) D or load zone 2 2=backward;
protection\DSTPDIS1\Fault 1
3=both
0=unknown;
Monitoring\Recorded
DSTPDIS 21P(1 AC Direction of fault 1=forward;
Z<(1) MON LD0.GFC1RFRC1.DirZn3.dirGeneral Enum ST B Fault/load Dir Zn3 data\Distance
1 ) D or load zone 3 2=backward;
protection\DSTPDIS1\Fault 1
3=both
0=unknown;
Monitoring\Recorded
DSTPDIS 21P(1 AC Direction of fault 1=forward;
Z<(1) MON LD0.GFC1RFRC1.DirZn4.dirGeneral Enum ST B Fault/load Dir Zn4 data\Distance
1 ) D or load zone 4 2=backward;
protection\DSTPDIS1\Fault 1
3=both
0=unknown;
Monitoring\Recorded
DSTPDIS 21P(1 AC Direction of fault 1=forward;
Z<(1) MON LD0.GFC1RFRC1.DirZn5.dirGeneral Enum ST B Fault/load Dir Zn5 data\Distance
1 ) D or load zone 5 2=backward;
protection\DSTPDIS1\Fault 1
3=both
-5=No fault; -
4=ABCG Fault; -
3=CAG Fault; -
Release signals 2=BCG Fault; - Monitoring\Recorded
DSTPDIS 21P(1
Z<(1) MON LD0.GFC2RFRC1.RelPhLoop.stVal ENS Enum ST B I1 Release PE-loop for PE-loops, 1=ABG Fault; data\Distance
1 )
GFC 1=AG Fault; protection\DSTPDIS1\Fault 2
2=BG Fault;
3=CG Fault;
4=AB Fault;
283
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

5=BC Fault;
6=CA Fault;
7=ABC Fault
-5=No fault; -
4=ABCG Fault; -
3=CAG Fault; -
2=BCG Fault; -
1=ABG Fault;
Release signals Monitoring\Recorded
DSTPDIS 21P(1 1=AG Fault;
Z<(1) MON LD0.GFC2RFRC1.RelPPLoop.stVal ENS Enum ST B I1 Release PP-loop for PP/3P loops. data\Distance
1 ) 2=BG Fault;
GFC protection\DSTPDIS1\Fault 2
3=CG Fault;
4=AB Fault;
5=BC Fault;
6=CA Fault;
7=ABC Fault
Indication of a
Monitoring\Recorded
DSTPDIS 21P(1 cross-country-
Z<(1) MON LD0.GFC2RFRC1.XcnDet.stVal SPS BOOLEAN ST B I1 Cross country fault data\Distance
1 ) fault (high imp.
protection\DSTPDIS1\Fault 2
earthed), GFC
Indication of a Monitoring\Recorded
DSTPDIS 21P(1
Z<(1) MON LD0.GFC2RFRC1.EFDet.stVal SPS BOOLEAN ST B I1 Earth fault detected single phase data\Distance
1 )
earth-fault, GFC protection\DSTPDIS1\Fault 2
Monitoring\Recorded
DSTPDIS 21P(1
Z<(1) MON LD0.GFC2RFRC1.EFDet.t SPS Timestamp ST B Time Time data\Distance
1 )
protection\DSTPDIS1\Fault 2
Earth-fault 0=unknown;
Monitoring\Recorded
DSTPDIS 21P(1 AC direction (low 1=forward;
Z<(1) MON LD0.GFC2RFRC1.EFDir.dirGeneral Enum ST B Earth-fault direction data\Distance
1 ) D impedance 2=backward;
protection\DSTPDIS1\Fault 2
earthed), GFC 3=both
Monitoring\Recorded
DSTPDIS 21P(1 Operate signal of
Z<(1) MON LD0.GFC2RFRC1.ZnOpSt.stVal INS INT32 ST B I1 Operate of all zones 0...31 data\Distance
1 ) all zones
protection\DSTPDIS1\Fault 2
0=unknown;
Monitoring\Recorded
DSTPDIS 21P(1 AC Direction of fault 1=forward;
Z<(1) MON LD0.GFC2RFRC1.DirZn1.dirGeneral Enum ST B Fault/load Dir Zn1 data\Distance
1 ) D or load zone 1 2=backward;
protection\DSTPDIS1\Fault 2
3=both
Direction - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC2RFRC1.DirRisZn1.mag.f MV FLOAT32 B I1 Dir resistance Zn1 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
1 0 ohm protection\DSTPDIS1\Fault 2
- Monitoring\Recorded
DSTPDIS 21P(1 M Direction
Z<(1) MON LD0.GFC2RFRC1.DirXZn1.mag.f MV FLOAT32 B I1 Dir reactance Zn1 3000.00...3000.0 data\Distance
1 ) X reactance, zone 1
0 ohm protection\DSTPDIS1\Fault 2
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC2RFRC1.PhLoopRis1.mag.f MV FLOAT32 B I1 Flt loop 1st Ris Zn1 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
1 0 ohm protection\DSTPDIS1\Fault 2
- Monitoring\Recorded
DSTPDIS 21P(1 M First PE-loop
Z<(1) MON LD0.GFC2RFRC1.PhLoopX1.mag.f MV FLOAT32 B I1 Flt loop 1st Rea Zn1 3000.00...3000.0 data\Distance
1 ) X reactance, zone 1
0 ohm protection\DSTPDIS1\Fault 2

284
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Second PE-loop - Monitoring\Recorded


DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC2RFRC1.PhLoopRis2.mag.f MV FLOAT32 B I1 Flt loop 2nd Ris Zn1 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
1 0 ohm protection\DSTPDIS1\Fault 2
- Monitoring\Recorded
DSTPDIS 21P(1 M Second PE-loop
Z<(1) MON LD0.GFC2RFRC1.PhLoopX2.mag.f MV FLOAT32 B I1 Flt loop 2nd Rea Zn1 3000.00...3000.0 data\Distance
1 ) X reactance, zone 1
0 ohm protection\DSTPDIS1\Fault 2
PP-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC2RFRC1.PPLoopRis.mag.f MV FLOAT32 B I1 Flt PP-loop Ris Zn1 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
1 0 ohm protection\DSTPDIS1\Fault 2
- Monitoring\Recorded
DSTPDIS 21P(1 M PP-loop
Z<(1) MON LD0.GFC2RFRC1.PPLoopX.mag.f MV FLOAT32 B I1 Flt PP-loop Rea Zn1 3000.00...3000.0 data\Distance
1 ) X reactance, zone 1
0 ohm protection\DSTPDIS1\Fault 2
Phase to earth
- Monitoring\Recorded
DSTPDIS 21P(1 M reactance in
Z<(1) MON LD0.GFC2RFRC1.PhX.mag.f MV FLOAT32 B I1 Phase reactance Zn1 3000.00...3000.0 data\Distance
1 ) X phase domain,
0 ohm protection\DSTPDIS1\Fault 2
zone 1
Direction - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC2RFRC1.DirRisZn2.mag.f MV FLOAT32 B I1 Dir resistance Zn2 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
2 0 ohm protection\DSTPDIS1\Fault 2
Direction - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC2RFRC1.DirRisZn3.mag.f MV FLOAT32 B I1 Dir resistance Zn3 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
3 0 ohm protection\DSTPDIS1\Fault 2
Direction - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC2RFRC1.DirRisZn4.mag.f MV FLOAT32 B I1 Dir resistance Zn4 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
4 0 ohm protection\DSTPDIS1\Fault 2
Direction - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC2RFRC1.DirRisZn5.mag.f MV FLOAT32 B I1 Dir resistance Zn5 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
5 0 ohm protection\DSTPDIS1\Fault 2
- Monitoring\Recorded
DSTPDIS 21P(1 M Direction
Z<(1) MON LD0.GFC2RFRC1.DirXZn2.mag.f MV FLOAT32 B I1 Dir reactance Zn2 3000.00...3000.0 data\Distance
1 ) X reactance, zone 2
0 ohm protection\DSTPDIS1\Fault 2
- Monitoring\Recorded
DSTPDIS 21P(1 M Direction
Z<(1) MON LD0.GFC2RFRC1.DirXZn3.mag.f MV FLOAT32 B I1 Dir reactance Zn3 3000.00...3000.0 data\Distance
1 ) X reactance, zone 3
0 ohm protection\DSTPDIS1\Fault 2
- Monitoring\Recorded
DSTPDIS 21P(1 M Direction
Z<(1) MON LD0.GFC2RFRC1.DirXZn4.mag.f MV FLOAT32 B I1 Dir reactance Zn4 3000.00...3000.0 data\Distance
1 ) X reactance, zone 4
0 ohm protection\DSTPDIS1\Fault 2
- Monitoring\Recorded
DSTPDIS 21P(1 M Direction
Z<(1) MON LD0.GFC2RFRC1.DirXZn5.mag.f MV FLOAT32 B I1 Dir reactance Zn5 3000.00...3000.0 data\Distance
1 ) X reactance, zone 5
0 ohm protection\DSTPDIS1\Fault 2
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC2RFRC1.PhRisFstZn2.mag.f MV FLOAT32 I1 Flt loop 1st Ris Zn2 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
2 0 ohm protection\DSTPDIS1\Fault 2
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC2RFRC1.PhRis1Zn2.mag.f MV FLOAT32 ED1 I1 Flt loop 1st Ris Zn2 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
2 0 ohm protection\DSTPDIS1\Fault 2
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC2RFRC1.PhRisFstZn3.mag.f MV FLOAT32 I1 Flt loop 1st Ris Zn3 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
3 0 ohm protection\DSTPDIS1\Fault 2
285
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

First PE-loop - Monitoring\Recorded


DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC2RFRC1.PhRis1Zn3.mag.f MV FLOAT32 ED1 I1 Flt loop 1st Ris Zn3 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
3 0 ohm protection\DSTPDIS1\Fault 2
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC2RFRC1.PhRisFstZn4.mag.f MV FLOAT32 I1 Flt loop 1st Ris Zn4 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
4 0 ohm protection\DSTPDIS1\Fault 2
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC2RFRC1.PhRis1Zn4.mag.f MV FLOAT32 ED1 I1 Flt loop 1st Ris Zn4 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
4 0 ohm protection\DSTPDIS1\Fault 2
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC2RFRC1.PhRisFstZn5.mag.f MV FLOAT32 I1 Flt loop 1st Ris Zn5 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
5 0 ohm protection\DSTPDIS1\Fault 2
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC2RFRC1.PhRis1Zn5.mag.f MV FLOAT32 ED1 I1 Flt loop 1st Ris Zn5 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
5 0 ohm protection\DSTPDIS1\Fault 2
- Monitoring\Recorded
DSTPDIS 21P(1 M First PE-loop
Z<(1) MON LD0.GFC2RFRC1.PhXFstZn2.mag.f MV FLOAT32 B I1 Flt loop 1st Rea Zn2 3000.00...3000.0 data\Distance
1 ) X reactance, zone 2
0 ohm protection\DSTPDIS1\Fault 2
- Monitoring\Recorded
DSTPDIS 21P(1 M First PE-loop
Z<(1) MON LD0.GFC2RFRC1.PhXFstZn3.mag.f MV FLOAT32 B I1 Flt loop 1st Rea Zn3 3000.00...3000.0 data\Distance
1 ) X reactance, zone 3
0 ohm protection\DSTPDIS1\Fault 2
- Monitoring\Recorded
DSTPDIS 21P(1 M First PE-loop
Z<(1) MON LD0.GFC2RFRC1.PhXFstZn4.mag.f MV FLOAT32 B I1 Flt loop 1st Rea Zn4 3000.00...3000.0 data\Distance
1 ) X reactance, zone 4
0 ohm protection\DSTPDIS1\Fault 2
- Monitoring\Recorded
DSTPDIS 21P(1 M First PE-loop
Z<(1) MON LD0.GFC2RFRC1.PhXFstZn5.mag.f MV FLOAT32 B I1 Flt loop 1st Rea Zn5 3000.00...3000.0 data\Distance
1 ) X reactance, zone 5
0 ohm protection\DSTPDIS1\Fault 2
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC2RFRC1.PhRisScdZn2.mag.f MV FLOAT32 I1 Flt loop 2nd Ris Zn2 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
2 0 ohm protection\DSTPDIS1\Fault 2
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC2RFRC1.PhRis2Zn2.mag.f MV FLOAT32 ED1 I1 Flt loop 2nd Ris Zn2 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
2 0 ohm protection\DSTPDIS1\Fault 2
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC2RFRC1.PhRisScdZn3.mag.f MV FLOAT32 I1 Flt loop 2nd Ris Zn3 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
3 0 ohm protection\DSTPDIS1\Fault 2
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC2RFRC1.PhRis2Zn3.mag.f MV FLOAT32 ED1 I1 Flt loop 2nd Ris Zn3 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
3 0 ohm protection\DSTPDIS1\Fault 2
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC2RFRC1.PhRisScdZn4.mag.f MV FLOAT32 I1 Flt loop 2nd Ris Zn4 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
4 0 ohm protection\DSTPDIS1\Fault 2
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC2RFRC1.PhRis2Zn4.mag.f MV FLOAT32 ED1 I1 Flt loop 2nd Ris Zn4 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
4 0 ohm protection\DSTPDIS1\Fault 2
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC2RFRC1.PhRisScdZn5.mag.f MV FLOAT32 I1 Flt loop 2nd Ris Zn5 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
5 0 ohm protection\DSTPDIS1\Fault 2

286
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Second PE-loop - Monitoring\Recorded


DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC2RFRC1.PhRis2Zn5.mag.f MV FLOAT32 ED1 I1 Flt loop 2nd Ris Zn5 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
5 0 ohm protection\DSTPDIS1\Fault 2
- Monitoring\Recorded
DSTPDIS 21P(1 M Second PE-loop
Z<(1) MON LD0.GFC2RFRC1.PhXScdZn2.mag.f MV FLOAT32 B I1 Flt loop 2nd Rea Zn2 3000.00...3000.0 data\Distance
1 ) X reactance, zone 2
0 ohm protection\DSTPDIS1\Fault 2
- Monitoring\Recorded
DSTPDIS 21P(1 M Second PE-loop
Z<(1) MON LD0.GFC2RFRC1.PhXScdZn3.mag.f MV FLOAT32 B I1 Flt loop 2nd Rea Zn3 3000.00...3000.0 data\Distance
1 ) X reactance, zone 3
0 ohm protection\DSTPDIS1\Fault 2
- Monitoring\Recorded
DSTPDIS 21P(1 M Second PE-loop
Z<(1) MON LD0.GFC2RFRC1.PhXScdZn4.mag.f MV FLOAT32 B I1 Flt loop 2nd Rea Zn4 3000.00...3000.0 data\Distance
1 ) X reactance, zone 4
0 ohm protection\DSTPDIS1\Fault 2
- Monitoring\Recorded
DSTPDIS 21P(1 M Second PE-loop
Z<(1) MON LD0.GFC2RFRC1.PhXScdZn5.mag.f MV FLOAT32 B I1 Flt loop 2nd Rea Zn5 3000.00...3000.0 data\Distance
1 ) X reactance, zone 5
0 ohm protection\DSTPDIS1\Fault 2
PP-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC2RFRC1.PPRisZn2.mag.f MV FLOAT32 B I1 Flt PP-loop Ris Zn2 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
2 0 ohm protection\DSTPDIS1\Fault 2
PP-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC2RFRC1.PPRisZn3.mag.f MV FLOAT32 B I1 Flt PP-loop Ris Zn3 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
3 0 ohm protection\DSTPDIS1\Fault 2
PP-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC2RFRC1.PPRisZn4.mag.f MV FLOAT32 B I1 Flt PP-loop Ris Zn4 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
4 0 ohm protection\DSTPDIS1\Fault 2
PP-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC2RFRC1.PPRisZn5.mag.f MV FLOAT32 B I1 Flt PP-loop Ris Zn5 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
5 0 ohm protection\DSTPDIS1\Fault 2
- Monitoring\Recorded
DSTPDIS 21P(1 M PP-loop
Z<(1) MON LD0.GFC2RFRC1.PPXZn2.mag.f MV FLOAT32 B I1 Flt PP-loop Rea Zn2 3000.00...3000.0 data\Distance
1 ) X reactance, zone 2
0 ohm protection\DSTPDIS1\Fault 2
- Monitoring\Recorded
DSTPDIS 21P(1 M PP-loop
Z<(1) MON LD0.GFC2RFRC1.PPXZn3.mag.f MV FLOAT32 B I1 Flt PP-loop Rea Zn3 3000.00...3000.0 data\Distance
1 ) X reactance, zone 3
0 ohm protection\DSTPDIS1\Fault 2
- Monitoring\Recorded
DSTPDIS 21P(1 M PP-loop
Z<(1) MON LD0.GFC2RFRC1.PPXZn4.mag.f MV FLOAT32 B I1 Flt PP-loop Rea Zn4 3000.00...3000.0 data\Distance
1 ) X reactance, zone 4
0 ohm protection\DSTPDIS1\Fault 2
- Monitoring\Recorded
DSTPDIS 21P(1 M PP-loop
Z<(1) MON LD0.GFC2RFRC1.PPXZn5.mag.f MV FLOAT32 B I1 Flt PP-loop Rea Zn5 3000.00...3000.0 data\Distance
1 ) X reactance, zone 5
0 ohm protection\DSTPDIS1\Fault 2
Phase to earth
- Monitoring\Recorded
DSTPDIS 21P(1 M reactance in
Z<(1) MON LD0.GFC2RFRC1.PhXZn2.mag.f MV FLOAT32 B I1 Phase reactance Zn2 3000.00...3000.0 data\Distance
1 ) X phase domain,
0 ohm protection\DSTPDIS1\Fault 2
zone 2
Phase to earth
- Monitoring\Recorded
DSTPDIS 21P(1 M reactance in
Z<(1) MON LD0.GFC2RFRC1.PhXZn3.mag.f MV FLOAT32 B I1 Phase reactance Zn3 3000.00...3000.0 data\Distance
1 ) X phase domain,
0 ohm protection\DSTPDIS1\Fault 2
zone 3

287
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Phase to earth
- Monitoring\Recorded
DSTPDIS 21P(1 M reactance in
Z<(1) MON LD0.GFC2RFRC1.PhXZn4.mag.f MV FLOAT32 B I1 Phase reactance Zn4 3000.00...3000.0 data\Distance
1 ) X phase domain,
0 ohm protection\DSTPDIS1\Fault 2
zone 4
Phase to earth
- Monitoring\Recorded
DSTPDIS 21P(1 M reactance in
Z<(1) MON LD0.GFC2RFRC1.PhXZn5.mag.f MV FLOAT32 B I1 Phase reactance Zn5 3000.00...3000.0 data\Distance
1 ) X phase domain,
0 ohm protection\DSTPDIS1\Fault 2
zone 5
0=unknown;
Monitoring\Recorded
DSTPDIS 21P(1 AC Direction of fault 1=forward;
Z<(1) MON LD0.GFC2RFRC1.DirZn2.dirGeneral Enum ST B Fault/load Dir Zn2 data\Distance
1 ) D or load zone 2 2=backward;
protection\DSTPDIS1\Fault 2
3=both
0=unknown;
Monitoring\Recorded
DSTPDIS 21P(1 AC Direction of fault 1=forward;
Z<(1) MON LD0.GFC2RFRC1.DirZn3.dirGeneral Enum ST B Fault/load Dir Zn3 data\Distance
1 ) D or load zone 3 2=backward;
protection\DSTPDIS1\Fault 2
3=both
0=unknown;
Monitoring\Recorded
DSTPDIS 21P(1 AC Direction of fault 1=forward;
Z<(1) MON LD0.GFC2RFRC1.DirZn4.dirGeneral Enum ST B Fault/load Dir Zn4 data\Distance
1 ) D or load zone 4 2=backward;
protection\DSTPDIS1\Fault 2
3=both
0=unknown;
Monitoring\Recorded
DSTPDIS 21P(1 AC Direction of fault 1=forward;
Z<(1) MON LD0.GFC2RFRC1.DirZn5.dirGeneral Enum ST B Fault/load Dir Zn5 data\Distance
1 ) D or load zone 5 2=backward;
protection\DSTPDIS1\Fault 2
3=both
-5=No fault; -
4=ABCG Fault; -
3=CAG Fault; -
2=BCG Fault; -
1=ABG Fault;
Release signals Monitoring\Recorded
DSTPDIS 21P(1 1=AG Fault;
Z<(1) MON LD0.GFC3RFRC1.RelPhLoop.stVal ENS Enum ST B I1 Release PE-loop for PE-loops, data\Distance
1 ) 2=BG Fault;
GFC protection\DSTPDIS1\Fault 3
3=CG Fault;
4=AB Fault;
5=BC Fault;
6=CA Fault;
7=ABC Fault
-5=No fault; -
4=ABCG Fault; -
3=CAG Fault; -
2=BCG Fault; -
1=ABG Fault;
Release signals Monitoring\Recorded
DSTPDIS 21P(1 1=AG Fault;
Z<(1) MON LD0.GFC3RFRC1.RelPPLoop.stVal ENS Enum ST B I1 Release PP-loop for PP/3P loops. data\Distance
1 ) 2=BG Fault;
GFC protection\DSTPDIS1\Fault 3
3=CG Fault;
4=AB Fault;
5=BC Fault;
6=CA Fault;
7=ABC Fault
Monitoring\Recorded
DSTPDIS 21P(1 Indication of a
Z<(1) MON LD0.GFC3RFRC1.XcnDet.stVal SPS BOOLEAN ST B I1 Cross country fault data\Distance
1 ) cross-country-
protection\DSTPDIS1\Fault 3
288
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

fault (high imp.


earthed), GFC
Indication of a Monitoring\Recorded
DSTPDIS 21P(1
Z<(1) MON LD0.GFC3RFRC1.EFDet.stVal SPS BOOLEAN ST B I1 Earth fault detected single phase data\Distance
1 )
earth-fault, GFC protection\DSTPDIS1\Fault 3
Monitoring\Recorded
DSTPDIS 21P(1
Z<(1) MON LD0.GFC3RFRC1.EFDet.t SPS Timestamp ST B Time Time data\Distance
1 )
protection\DSTPDIS1\Fault 3
Earth-fault 0=unknown;
Monitoring\Recorded
DSTPDIS 21P(1 AC direction (low 1=forward;
Z<(1) MON LD0.GFC3RFRC1.EFDir.dirGeneral Enum ST B Earth-fault direction data\Distance
1 ) D impedance 2=backward;
protection\DSTPDIS1\Fault 3
earthed), GFC 3=both
Monitoring\Recorded
DSTPDIS 21P(1 Operate signal of
Z<(1) MON LD0.GFC3RFRC1.ZnOpSt.stVal INS INT32 ST B I1 Operate of all zones 0...31 data\Distance
1 ) all zones
protection\DSTPDIS1\Fault 3
0=unknown;
Monitoring\Recorded
DSTPDIS 21P(1 AC Direction of fault 1=forward;
Z<(1) MON LD0.GFC3RFRC1.DirZn1.dirGeneral Enum ST B Fault/load Dir Zn1 data\Distance
1 ) D or load zone 1 2=backward;
protection\DSTPDIS1\Fault 3
3=both
Direction - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC3RFRC1.DirRisZn1.mag.f MV FLOAT32 B I1 Dir resistance Zn1 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
1 0 ohm protection\DSTPDIS1\Fault 3
- Monitoring\Recorded
DSTPDIS 21P(1 M Direction
Z<(1) MON LD0.GFC3RFRC1.DirXZn1.mag.f MV FLOAT32 B I1 Dir reactance Zn1 3000.00...3000.0 data\Distance
1 ) X reactance, zone 1
0 ohm protection\DSTPDIS1\Fault 3
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC3RFRC1.PhLoopRis1.mag.f MV FLOAT32 B I1 Flt loop 1st Ris Zn1 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
1 0 ohm protection\DSTPDIS1\Fault 3
- Monitoring\Recorded
DSTPDIS 21P(1 M First PE-loop
Z<(1) MON LD0.GFC3RFRC1.PhLoopX1.mag.f MV FLOAT32 B I1 Flt loop 1st Rea Zn1 3000.00...3000.0 data\Distance
1 ) X reactance, zone 1
0 ohm protection\DSTPDIS1\Fault 3
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC3RFRC1.PhLoopRis2.mag.f MV FLOAT32 B I1 Flt loop 2nd Ris Zn1 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
1 0 ohm protection\DSTPDIS1\Fault 3
- Monitoring\Recorded
DSTPDIS 21P(1 M Second PE-loop
Z<(1) MON LD0.GFC3RFRC1.PhLoopX2.mag.f MV FLOAT32 B I1 Flt loop 2nd Rea Zn1 3000.00...3000.0 data\Distance
1 ) X reactance, zone 1
0 ohm protection\DSTPDIS1\Fault 3
PP-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC3RFRC1.PPLoopRis.mag.f MV FLOAT32 B I1 Flt PP-loop Ris Zn1 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
1 0 ohm protection\DSTPDIS1\Fault 3
- Monitoring\Recorded
DSTPDIS 21P(1 M PP-loop
Z<(1) MON LD0.GFC3RFRC1.PPLoopX.mag.f MV FLOAT32 B I1 Flt PP-loop Rea Zn1 3000.00...3000.0 data\Distance
1 ) X reactance, zone 1
0 ohm protection\DSTPDIS1\Fault 3
Phase to earth
- Monitoring\Recorded
DSTPDIS 21P(1 M reactance in
Z<(1) MON LD0.GFC3RFRC1.PhX.mag.f MV FLOAT32 B I1 Phase reactance Zn1 3000.00...3000.0 data\Distance
1 ) X phase domain,
0 ohm protection\DSTPDIS1\Fault 3
zone 1

289
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Direction - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC3RFRC1.DirRisZn2.mag.f MV FLOAT32 B I1 Dir resistance Zn2 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
2 0 ohm protection\DSTPDIS1\Fault 3
Direction - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC3RFRC1.DirRisZn3.mag.f MV FLOAT32 B I1 Dir resistance Zn3 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
3 0 ohm protection\DSTPDIS1\Fault 3
Direction - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC3RFRC1.DirRisZn4.mag.f MV FLOAT32 B I1 Dir resistance Zn4 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
4 0 ohm protection\DSTPDIS1\Fault 3
Direction - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC3RFRC1.DirRisZn5.mag.f MV FLOAT32 B I1 Dir resistance Zn5 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
5 0 ohm protection\DSTPDIS1\Fault 3
- Monitoring\Recorded
DSTPDIS 21P(1 M Direction
Z<(1) MON LD0.GFC3RFRC1.DirXZn2.mag.f MV FLOAT32 B I1 Dir reactance Zn2 3000.00...3000.0 data\Distance
1 ) X reactance, zone 2
0 ohm protection\DSTPDIS1\Fault 3
- Monitoring\Recorded
DSTPDIS 21P(1 M Direction
Z<(1) MON LD0.GFC3RFRC1.DirXZn3.mag.f MV FLOAT32 B I1 Dir reactance Zn3 3000.00...3000.0 data\Distance
1 ) X reactance, zone 3
0 ohm protection\DSTPDIS1\Fault 3
- Monitoring\Recorded
DSTPDIS 21P(1 M Direction
Z<(1) MON LD0.GFC3RFRC1.DirXZn4.mag.f MV FLOAT32 B I1 Dir reactance Zn4 3000.00...3000.0 data\Distance
1 ) X reactance, zone 4
0 ohm protection\DSTPDIS1\Fault 3
- Monitoring\Recorded
DSTPDIS 21P(1 M Direction
Z<(1) MON LD0.GFC3RFRC1.DirXZn5.mag.f MV FLOAT32 B I1 Dir reactance Zn5 3000.00...3000.0 data\Distance
1 ) X reactance, zone 5
0 ohm protection\DSTPDIS1\Fault 3
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC3RFRC1.PhRisFstZn2.mag.f MV FLOAT32 I1 Flt loop 1st Ris Zn2 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
2 0 ohm protection\DSTPDIS1\Fault 3
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC3RFRC1.PhRis1Zn2.mag.f MV FLOAT32 ED1 I1 Flt loop 1st Ris Zn2 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
2 0 ohm protection\DSTPDIS1\Fault 3
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC3RFRC1.PhRisFstZn3.mag.f MV FLOAT32 I1 Flt loop 1st Ris Zn3 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
3 0 ohm protection\DSTPDIS1\Fault 3
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC3RFRC1.PhRis1Zn3.mag.f MV FLOAT32 ED1 I1 Flt loop 1st Ris Zn3 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
3 0 ohm protection\DSTPDIS1\Fault 3
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC3RFRC1.PhRisFstZn4.mag.f MV FLOAT32 I1 Flt loop 1st Ris Zn4 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
4 0 ohm protection\DSTPDIS1\Fault 3
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC3RFRC1.PhRis1Zn4.mag.f MV FLOAT32 ED1 I1 Flt loop 1st Ris Zn4 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
4 0 ohm protection\DSTPDIS1\Fault 3
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC3RFRC1.PhRisFstZn5.mag.f MV FLOAT32 I1 Flt loop 1st Ris Zn5 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
5 0 ohm protection\DSTPDIS1\Fault 3
First PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC3RFRC1.PhRis1Zn5.mag.f MV FLOAT32 ED1 I1 Flt loop 1st Ris Zn5 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
5 0 ohm protection\DSTPDIS1\Fault 3

290
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

- Monitoring\Recorded
DSTPDIS 21P(1 M First PE-loop
Z<(1) MON LD0.GFC3RFRC1.PhXFstZn2.mag.f MV FLOAT32 B I1 Flt loop 1st Rea Zn2 3000.00...3000.0 data\Distance
1 ) X reactance, zone 2
0 ohm protection\DSTPDIS1\Fault 3
- Monitoring\Recorded
DSTPDIS 21P(1 M First PE-loop
Z<(1) MON LD0.GFC3RFRC1.PhXFstZn3.mag.f MV FLOAT32 B I1 Flt loop 1st Rea Zn3 3000.00...3000.0 data\Distance
1 ) X reactance, zone 3
0 ohm protection\DSTPDIS1\Fault 3
- Monitoring\Recorded
DSTPDIS 21P(1 M First PE-loop
Z<(1) MON LD0.GFC3RFRC1.PhXFstZn4.mag.f MV FLOAT32 B I1 Flt loop 1st Rea Zn4 3000.00...3000.0 data\Distance
1 ) X reactance, zone 4
0 ohm protection\DSTPDIS1\Fault 3
- Monitoring\Recorded
DSTPDIS 21P(1 M First PE-loop
Z<(1) MON LD0.GFC3RFRC1.PhXFstZn5.mag.f MV FLOAT32 B I1 Flt loop 1st Rea Zn5 3000.00...3000.0 data\Distance
1 ) X reactance, zone 5
0 ohm protection\DSTPDIS1\Fault 3
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC3RFRC1.PhRisScdZn2.mag.f MV FLOAT32 I1 Flt loop 2nd Ris Zn2 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
2 0 ohm protection\DSTPDIS1\Fault 3
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC3RFRC1.PhRis2Zn2.mag.f MV FLOAT32 ED1 I1 Flt loop 2nd Ris Zn2 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
2 0 ohm protection\DSTPDIS1\Fault 3
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC3RFRC1.PhRisScdZn3.mag.f MV FLOAT32 I1 Flt loop 2nd Ris Zn3 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
3 0 ohm protection\DSTPDIS1\Fault 3
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC3RFRC1.PhRis2Zn3.mag.f MV FLOAT32 ED1 I1 Flt loop 2nd Ris Zn3 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
3 0 ohm protection\DSTPDIS1\Fault 3
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC3RFRC1.PhRisScdZn4.mag.f MV FLOAT32 I1 Flt loop 2nd Ris Zn4 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
4 0 ohm protection\DSTPDIS1\Fault 3
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC3RFRC1.PhRis2Zn4.mag.f MV FLOAT32 ED1 I1 Flt loop 2nd Ris Zn4 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
4 0 ohm protection\DSTPDIS1\Fault 3
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M ED2,
Z<(1) MON LD0.GFC3RFRC1.PhRisScdZn5.mag.f MV FLOAT32 I1 Flt loop 2nd Ris Zn5 resistance, zone 3000.00...3000.0 data\Distance
1 ) X B
5 0 ohm protection\DSTPDIS1\Fault 3
Second PE-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC3RFRC1.PhRis2Zn5.mag.f MV FLOAT32 ED1 I1 Flt loop 2nd Ris Zn5 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
5 0 ohm protection\DSTPDIS1\Fault 3
- Monitoring\Recorded
DSTPDIS 21P(1 M Second PE-loop
Z<(1) MON LD0.GFC3RFRC1.PhXScdZn2.mag.f MV FLOAT32 B I1 Flt loop 2nd Rea Zn2 3000.00...3000.0 data\Distance
1 ) X reactance, zone 2
0 ohm protection\DSTPDIS1\Fault 3
- Monitoring\Recorded
DSTPDIS 21P(1 M Second PE-loop
Z<(1) MON LD0.GFC3RFRC1.PhXScdZn3.mag.f MV FLOAT32 B I1 Flt loop 2nd Rea Zn3 3000.00...3000.0 data\Distance
1 ) X reactance, zone 3
0 ohm protection\DSTPDIS1\Fault 3
- Monitoring\Recorded
DSTPDIS 21P(1 M Second PE-loop
Z<(1) MON LD0.GFC3RFRC1.PhXScdZn4.mag.f MV FLOAT32 B I1 Flt loop 2nd Rea Zn4 3000.00...3000.0 data\Distance
1 ) X reactance, zone 4
0 ohm protection\DSTPDIS1\Fault 3
- Monitoring\Recorded
DSTPDIS 21P(1 M Second PE-loop
Z<(1) MON LD0.GFC3RFRC1.PhXScdZn5.mag.f MV FLOAT32 B I1 Flt loop 2nd Rea Zn5 3000.00...3000.0 data\Distance
1 ) X reactance, zone 5
0 ohm protection\DSTPDIS1\Fault 3

291
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

PP-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC3RFRC1.PPRisZn2.mag.f MV FLOAT32 B I1 Flt PP-loop Ris Zn2 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
2 0 ohm protection\DSTPDIS1\Fault 3
PP-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC3RFRC1.PPRisZn3.mag.f MV FLOAT32 B I1 Flt PP-loop Ris Zn3 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
3 0 ohm protection\DSTPDIS1\Fault 3
PP-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC3RFRC1.PPRisZn4.mag.f MV FLOAT32 B I1 Flt PP-loop Ris Zn4 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
4 0 ohm protection\DSTPDIS1\Fault 3
PP-loop - Monitoring\Recorded
DSTPDIS 21P(1 M
Z<(1) MON LD0.GFC3RFRC1.PPRisZn5.mag.f MV FLOAT32 B I1 Flt PP-loop Ris Zn5 resistance, zone 3000.00...3000.0 data\Distance
1 ) X
5 0 ohm protection\DSTPDIS1\Fault 3
- Monitoring\Recorded
DSTPDIS 21P(1 M PP-loop
Z<(1) MON LD0.GFC3RFRC1.PPXZn2.mag.f MV FLOAT32 B I1 Flt PP-loop Rea Zn2 3000.00...3000.0 data\Distance
1 ) X reactance, zone 2
0 ohm protection\DSTPDIS1\Fault 3
- Monitoring\Recorded
DSTPDIS 21P(1 M PP-loop
Z<(1) MON LD0.GFC3RFRC1.PPXZn3.mag.f MV FLOAT32 B I1 Flt PP-loop Rea Zn3 3000.00...3000.0 data\Distance
1 ) X reactance, zone 3
0 ohm protection\DSTPDIS1\Fault 3
- Monitoring\Recorded
DSTPDIS 21P(1 M PP-loop
Z<(1) MON LD0.GFC3RFRC1.PPXZn4.mag.f MV FLOAT32 B I1 Flt PP-loop Rea Zn4 3000.00...3000.0 data\Distance
1 ) X reactance, zone 4
0 ohm protection\DSTPDIS1\Fault 3
- Monitoring\Recorded
DSTPDIS 21P(1 M PP-loop
Z<(1) MON LD0.GFC3RFRC1.PPXZn5.mag.f MV FLOAT32 B I1 Flt PP-loop Rea Zn5 3000.00...3000.0 data\Distance
1 ) X reactance, zone 5
0 ohm protection\DSTPDIS1\Fault 3
Phase to earth
- Monitoring\Recorded
DSTPDIS 21P(1 M reactance in
Z<(1) MON LD0.GFC3RFRC1.PhXZn2.mag.f MV FLOAT32 B I1 Phase reactance Zn2 3000.00...3000.0 data\Distance
1 ) X phase domain,
0 ohm protection\DSTPDIS1\Fault 3
zone 2
Phase to earth
- Monitoring\Recorded
DSTPDIS 21P(1 M reactance in
Z<(1) MON LD0.GFC3RFRC1.PhXZn3.mag.f MV FLOAT32 B I1 Phase reactance Zn3 3000.00...3000.0 data\Distance
1 ) X phase domain,
0 ohm protection\DSTPDIS1\Fault 3
zone 3
Phase to earth
- Monitoring\Recorded
DSTPDIS 21P(1 M reactance in
Z<(1) MON LD0.GFC3RFRC1.PhXZn4.mag.f MV FLOAT32 B I1 Phase reactance Zn4 3000.00...3000.0 data\Distance
1 ) X phase domain,
0 ohm protection\DSTPDIS1\Fault 3
zone 4
Phase to earth
- Monitoring\Recorded
DSTPDIS 21P(1 M reactance in
Z<(1) MON LD0.GFC3RFRC1.PhXZn5.mag.f MV FLOAT32 B I1 Phase reactance Zn5 3000.00...3000.0 data\Distance
1 ) X phase domain,
0 ohm protection\DSTPDIS1\Fault 3
zone 5
0=unknown;
Monitoring\Recorded
DSTPDIS 21P(1 AC Direction of fault 1=forward;
Z<(1) MON LD0.GFC3RFRC1.DirZn2.dirGeneral Enum ST B Fault/load Dir Zn2 data\Distance
1 ) D or load zone 2 2=backward;
protection\DSTPDIS1\Fault 3
3=both
0=unknown;
Monitoring\Recorded
DSTPDIS 21P(1 AC Direction of fault 1=forward;
Z<(1) MON LD0.GFC3RFRC1.DirZn3.dirGeneral Enum ST B Fault/load Dir Zn3 data\Distance
1 ) D or load zone 3 2=backward;
protection\DSTPDIS1\Fault 3
3=both

292
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

0=unknown;
Monitoring\Recorded
DSTPDIS 21P(1 AC Direction of fault 1=forward;
Z<(1) MON LD0.GFC3RFRC1.DirZn4.dirGeneral Enum ST B Fault/load Dir Zn4 data\Distance
1 ) D or load zone 4 2=backward;
protection\DSTPDIS1\Fault 3
3=both
0=unknown;
Monitoring\Recorded
DSTPDIS 21P(1 AC Direction of fault 1=forward;
Z<(1) MON LD0.GFC3RFRC1.DirZn5.dirGeneral Enum ST B Fault/load Dir Zn5 data\Distance
1 ) D or load zone 5 2=backward;
protection\DSTPDIS1\Fault 3
3=both
DSTPDIS 21P(1 Operation Off / Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off IL1TCTR1
1 ) On protection\DSTPDIS1
DSTPDIS 21P(1 Phase current Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.PhStr.setMag.f ASG FLOAT32 SG B 2.00 Str A Ph Sel GFC 0.10...10.00 xIn IL1TCTR1
1 ) start value, PSL protection\DSTPDIS1
Residual voltage
DSTPDIS 21P(1 start value, EF- Settings\Settings\Distance RESTVTR
Z<(1) SET LD0.GFCPDIS1.GndStr.setMag.f ASG FLOAT32 SG B 0.15 Gnd Str voltage GFC 0.02...1.00 xUn
1 ) detection protection\DSTPDIS1 1
function
Directional 1=Non-
DSTPDIS 21P(1 EN mode, earth-fault directional; Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.DirMod.setVal Enum SG A 1 Dir mode EF GFC
1 ) G directional 2=Forward; protection\DSTPDIS1
function 3=Reverse
Load
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.AngLod.setMag.f ASG FLOAT32 SG B 25.0 Angle load area GFC discrimination 5.0...45.0 deg
1 ) protection\DSTPDIS1
angle, PSL
DSTPDIS 21P(1 Time delay to Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.OpDlTmms.setVal ING INT32 SG B 3000 Operate delay GFC 100...60000 ms
1 ) operate, GFC protection\DSTPDIS1
Resistive
forward reach
DSTPDIS 21P(1 for load 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.RisFwdLod.setMag.f ASG FLOAT32 SG B 80.00 Ris Fwd Rch Lod GFC
1 ) discrimination, ohm protection\DSTPDIS1
undrerimpedance
, PSL
Resistive reverse
reach for load
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.RisRvLod.setMag.f ASG FLOAT32 SG B 80.00 Ris Rv Rch Lod GFC discrimination,
1 ) ohm protection\DSTPDIS1
undrerimpedance
, PSL
Resistive
forward reach
DSTPDIS 21P(1 LD0.GFCPDIS1.RisGndFwdRch.setMag ED2, 0.00...500.00 Settings\Settings\Distance
Z<(1) SET ASG FLOAT32 SG 100.00 Ris Gnd Fwd Rch GFC for PE-loops,
1 ) .f B ohm protection\DSTPDIS1
underimpedance,
PSL
Resistive
forward reach
DSTPDIS 21P(1 0.00...500.00 Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.RGndFwdRch.setMag.f ASG FLOAT32 SG ED1 100.00 Ris Gnd Fwd Rch GFC for PE-loops,
1 ) ohm protection\DSTPDIS1
underimpedance,
PSL
Resistive reverse
DSTPDIS 21P(1 ED2, 0.00...500.00 Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.RisGndRvRch.setMag.f ASG FLOAT32 SG 100.00 Ris Gnd Rv Rch GFC reach for PE-
1 ) B ohm protection\DSTPDIS1
loops,

293
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

underimpedance,
PSL
Resistive reverse
reach for PE-
DSTPDIS 21P(1 0.00...500.00 Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.RGndRvRch.setMag.f ASG FLOAT32 SG ED1 100.00 Ris Gnd Rv Rch GFC loops,
1 ) ohm protection\DSTPDIS1
underimpedance,
PSL
Resistive
forward reach
DSTPDIS 21P(1 ED2, 0.00...100.00 Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.RisPhFwdRch.setMag.f ASG FLOAT32 SG 30.00 Ris PP Fwd Rch GFC for PP-loops,
1 ) B ohm protection\DSTPDIS1
underimpedance,
PSL
Resistive
forward reach
DSTPDIS 21P(1 0.00...100.00 Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.RPhFwdRch.setMag.f ASG FLOAT32 SG ED1 30.00 Ris PP Fwd Rch GFC for PP-loops,
1 ) ohm protection\DSTPDIS1
underimpedance,
PSL
Resistive reverse
reach for PP-
DSTPDIS 21P(1 ED2, 0.00...100.00 Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.RisPhRvRch.setMag.f ASG FLOAT32 SG 30.00 Ris PP Rv Rch GFC loops,
1 ) B ohm protection\DSTPDIS1
underimpedance,
PSL
Resistive reverse
reach for PP-
DSTPDIS 21P(1 0.00...100.00 Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.RPhRvRch.setMag.f ASG FLOAT32 SG ED1 30.00 Ris PP Rv Rch GFC loops,
1 ) ohm protection\DSTPDIS1
underimpedance,
PSL
Enable load
DSTPDIS 21P(1 discrimination, Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.LodDsrMod.setVal SPG BOOLEAN SG B 0 Load Dsr mode GFC
1 ) underimpedance, protection\DSTPDIS1
PSL
Phase voltage 1=Accurate;
DSTPDIS 21P(1 EN Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.PhVMeas.setVal Enum SP B 1 Phase voltage Meas measurement 2=Ph-to-ph
1 ) G protection\DSTPDIS1
principle without Uo
1=High
impedance;
DSTPDIS 21P(1 EN Network neutral Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.SysGnd.setVal Enum SP B 2 System grounding GFC 2=Low
1 ) G earthing method protection\DSTPDIS1
impedance;
3=From input
1=No filter;
2=No
preference;
3=Cyc A-B-C-A;
Phase preference
4=Cyc A-C-B-A;
DSTPDIS 21P(1 EN mode for high Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.PhPrfModHi.setVal Enum SP B 1 Ph Prf mode Hi Z GFC 5=Acyc A-B-C;
1 ) G impedance protection\DSTPDIS1
6=Acyc A-C-B;
earthed network
7=Acyc B-A-C;
8=Acyc B-C-A;
9=Acyc C-A-B;
10=Acyc C-B-A

294
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

1=All loops;
Loop selection 2=PE only; 3=PP
DSTPDIS 21P(1 EN mode for low only; 4=BLK Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.PhPrfModLo.setVal Enum SP B 1 Ph Prf mode Lo Z GFC
1 ) G impedance leading PE; protection\DSTPDIS1
earthed network 5=BLK lagging
PE
Impedance
DSTPDIS 21P(1 EN characteristic, 1=Rectangular; Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.ZMod.setVal Enum SP B 1 Impedance mode Zn
1 ) G underimpedance, 2=Polar protection\DSTPDIS1
PSL
1=Quadrilateral;
2=Mho
Impedance (circular);
DSTPDIS 21P(1 EN Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.ZChrModGnd.setVal Enum SP B 1 Impedance Chr Gnd Zn characteristic for 3=Mho Dir line;
1 ) G protection\DSTPDIS1
PE-loops, zones 4=Offset Dir
line; 5=Bullet
(combi)
1=Quadrilateral;
2=Mho
Impedance
(circular);
DSTPDIS 21P(1 EN characteristic for Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.ZChrModPP.setVal Enum SP B 1 Impedance Chr PP Zn 3=Mho Dir line;
1 ) G PP/3P-loops, protection\DSTPDIS1
4=Offset Dir
zones
line; 5=Bullet
(combi)
EF current
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.EnaAStab.setVal SPG BOOLEAN SP A 0 EF Cur stabilization stabilization
1 ) protection\DSTPDIS1
enabled
Residual current
DSTPDIS 21P(1 ratio for parallel Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.FactEFABal.setMag.f ASG FLOAT32 SP A,I 1.200 Fact EF current Bal 1.000...2.000
1 ) line protection\DSTPDIS1
compensation
Operate timer
DSTPDIS 21P(1 EN 1=Independent; Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.ZnTmMod.setVal Enum SP A,I 1 Zone timer mode start mode,
1 ) G 2=Common protection\DSTPDIS1
zones
1=Overcurrent;
2=Vol Dep
Overcur;
DSTPDIS 21P(1 EN Phase selection Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.PhSelMod.setVal Enum SG B 1 Phase Sel mode GFC 3=Under
1 ) G method protection\DSTPDIS1
impedance;
4=OC AND Und
impedance
1=Io; 2=Io OR
DSTPDIS 21P(1 EN Earth-fault (EF) Uo; 3=Io AND Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.EFDetMod.setVal Enum SG B 1 EF detection Mod GFC
1 ) G detection method Uo; 4=Io AND protection\DSTPDIS1
IoRef
Phase current
DSTPDIS 21P(1 start value, Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.PhLoStr.setMag.f ASG FLOAT32 SG B 0.80 Lo A Ph Sel GFC 0.10...10.00 xIn IL1TCTR1
1 ) voltage dep. over protection\DSTPDIS1
current, PSL
DSTPDIS 21P(1 PE-voltage start Settings\Settings\Distance UL1TVTR
Z<(1) SET LD0.GFCPDIS1.PhVPhSel.setMag.f ASG FLOAT32 SG B 0.46 Ph V Ph Sel GFC 0.05...1.00 xUn
1 ) value, voltage protection\DSTPDIS1 1
295
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

dep. over
current, PSL
PP-voltage start
DSTPDIS 21P(1 value, voltage Settings\Settings\Distance UL1TVTR
Z<(1) SET LD0.GFCPDIS1.PPVPhSel.setMag.f ASG FLOAT32 SG B 0.80 PP V Ph Sel GFC 0.10...1.00 xUn
1 ) dep. over protection\DSTPDIS1 1
current, PSL
Impedance
DSTPDIS 21P(1 EN characteristic, 1=Quadrilateral; Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.ZChrMod.setVal Enum SG B 1 Z Chr Mod Ph Sel GFC
1 ) G underimpedance, 2=Mho (circular) protection\DSTPDIS1
PSL
Reactive forward
reach for PE-
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.XGndFwdRch.setMag.f ASG FLOAT32 SG B 40.00 X Gnd Fwd reach GFC loops,
1 ) ohm protection\DSTPDIS1
underimpedance,
PSL
Reactive reverse
reach for PE-
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.XGndRvRch.setMag.f ASG FLOAT32 SG B 40.00 X Gnd Rv reach GFC loops,
1 ) ohm protection\DSTPDIS1
underimpedance,
PSL
Reactive forward
reach for PP-
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.XPhFwdRch.setMag.f ASG FLOAT32 SG B 40.00 X PP Fwd reach GFC loops,
1 ) ohm protection\DSTPDIS1
underimpedance,
PSL
Reactive reverse
reach for PP-
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.XPhRvRch.setMag.f ASG FLOAT32 SG B 40.00 X PP Rv reach GFC loops,
1 ) ohm protection\DSTPDIS1
underimpedance,
PSL
Basic start value
DSTPDIS 21P(1 for residual curr., Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.GndOp1.setMag.f ASG FLOAT32 SG B 0.10 Gnd Op current GFC 0.00...10.00 xIn IL1TCTR1
1 ) EF-detection protection\DSTPDIS1
function
Transformer
neutral curr. start
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.GndOpRef.setMag.f ASG FLOAT32 SG B 0.10 Gnd Op A Ref GFC val., EF- 0.01...10.00 xIn IL1TCTR1
1 ) protection\DSTPDIS1
detection
function
Res. curr. start
DSTPDIS 21P(1 value for slope 2, Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.GndOp2.setMag.f ASG FLOAT32 SG A 1.00 Gnd Op current 2 GFC 0.10...10.00 xIn IL1TCTR1
1 ) EF-detection protection\DSTPDIS1
function
Slope 1 for res.
curr.
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.StabSpe1.setMag.f ASG FLOAT32 SG A 0.10 Stab slope 1 GFC stabilization, EF- 0.00...0.30
1 ) protection\DSTPDIS1
detection
function
DSTPDIS 21P(1 Slope 2 for res. Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.StabSpe2.setMag.f ASG FLOAT32 SG A 1.00 Stab slope 2 GFC 0.00...1.00
1 ) current protection\DSTPDIS1
296
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

stabilization, EF-
detection
function
Phase current
start value for
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.APhStabVal.setMag.f ASG FLOAT32 SG A 2.00 A Ph Stab value GFC slope 2, EF- 1.00...10.00 xIn IL1TCTR1
1 ) protection\DSTPDIS1
detection
function
Residual current
DSTPDIS 21P(1 start value, XC- Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.GndOpXcn.setMag.f ASG FLOAT32 SG B 0.20 Gnd Op A XC GFC 0.10...10.00 xIn IL1TCTR1
1 ) fault detection protection\DSTPDIS1
function
PP-voltage start
DSTPDIS 21P(1 value, XC-fault Settings\Settings\Distance UL1TVTR
Z<(1) SET LD0.GFCPDIS1.PPVValXcn.setMag.f ASG FLOAT32 SG B 0.80 PP voltage XC GFC 0.10...1.00 xUn
1 ) detection protection\DSTPDIS1 1
function
Time delay for
residual current,
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.XcnDlTmms.setVal ING INT32 SG A 100 Cross-country Dl GFC XC-fault 0...10000 ms
1 ) protection\DSTPDIS1
detection
function
1=Zone 1;
2=Zones 1-2;
DSTPDIS 21P(1 EN Active zones Settings\Settings\Distance
Z<(1) SET LD0.GFCPDIS1.SelActZn.setVal Enum SP B,I 1 Select active zones 3=Zones 1-3;
1 ) G selection protection\DSTPDIS1
4=Zones 1-4;
5=All 5 zones
Characteristic
DSTPDIS 21P(1 angle, earth-fault Settings\Settings\Distance
Z<(1) SET LD0.GFCRDIR1.ChrAng.setMag.f ASG FLOAT32 SG A 75 Chr angle GFC -179...180 deg
1 ) directional protection\DSTPDIS1
function
Left hand side
DSTPDIS 21P(1 angle, earth-fault Settings\Settings\Distance
Z<(1) SET LD0.GFCRDIR1.MinFwdAng.setMag.f ASG FLOAT32 SG A 80 Min phase angle GFC 0...90 deg
1 ) directional protection\DSTPDIS1
function
Right hand side
DSTPDIS 21P(1 angle, earth-fault Settings\Settings\Distance
Z<(1) SET LD0.GFCRDIR1.MaxFwdAng.setMag.f ASG FLOAT32 SG A 80 Max phase angle GFC 0...90 deg
1 ) directional protection\DSTPDIS1
function
-1=Zro vol.OR
Polarization
cur.; 2=Zero seq.
DSTPDIS 21P(1 EN method, earth- Settings\Settings\Distance
Z<(1) SET LD0.GFCRDIR1.PolQty.setVal Enum SG A 3 Pol quantity GFC cur.; 3=Zero seq.
1 ) G fault directional protection\DSTPDIS1
volt.; 4=Neg.
function
seq. volt.
DSTPDIS 21P(1 Voltage memory Settings\Settings\Distance
Z<(1) SET LD0.GFCRDIR1.VMemTmms.setVal ING INT32 SP A,I 40 Voltage Mem time 0...300000 ms
1 ) time protection\DSTPDIS1
2=Forward;
DSTPDIS 21P(1 EN Directional 3=Reverse; Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.DirMod.setVal Enum SG B 2 Directional mode Zn1
1 ) G mode, zone 1 1=Non- protection\DSTPDIS1
directional

297
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Enable operate
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.PhDlMod.setVal SPG BOOLEAN SG B 1 PP Op delay Mod Zn1 timer for PP/3P-
1 ) protection\DSTPDIS1
loops, zone 1
Time delay to
DSTPDIS 21P(1 operate of Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.PhDlTmms.setVal ING INT32 SG B 40 PP operate delay Zn1 40...60000 ms
1 ) PP/3P-loops, protection\DSTPDIS1
zone 1
Enable operate
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.GndDlMod.setVal SPG BOOLEAN SG B 1 Gnd Op Dl mode Zn1 timer for PE-
1 ) protection\DSTPDIS1
loops, zone 1
Time delay to
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.GndDlTmms.setVal ING INT32 SG B 40 Gnd operate Dl Zn1 operate of PE- 40...60000 ms
1 ) protection\DSTPDIS1
loops, zone 1
Positive
DSTPDIS 21P(1 sequence 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.X1.setMag.f ASG FLOAT32 SG B 40.00 X1 zone 1
1 ) reactive reach, ohm protection\DSTPDIS1
zone 1
Positive
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.LinAng.setMag.f ASG FLOAT32 SG B 45.0 Z1 angle zone 1 sequence line 15.0...90.0 deg
1 ) protection\DSTPDIS1
angle, zone 1
Residual
compensation
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.K0Fact.setMag.f ASG FLOAT32 SG B 1.0 Factor K0 zone 1 factor 0.0...4.0
1 ) protection\DSTPDIS1
magnitude, zone
1
Residual
DSTPDIS 21P(1 compensation Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.K0FactAng.setMag.f ASG FLOAT32 SG B 0 Factor K0 angle Zn1 -135...135 deg
1 ) factor angle, protection\DSTPDIS1
zone 1
Positive
DSTPDIS 21P(1 0.01...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.Z1Mod.setMag.f ASG FLOAT32 SG B 56.57 Z1 zone 1 sequence reach,
1 ) ohm protection\DSTPDIS1
zone 1
Enable PE-loop
DSTPDIS 21P(1 Op Mod Gnd loops Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.OpModGnd.setVal SPG BOOLEAN SG B 0 measurement,
1 ) Zn1 protection\DSTPDIS1
zone 1
Enable PP/3P-
DSTPDIS 21P(1 loop Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.OpModPP.setVal SPG BOOLEAN SG B 0 Op Mod PP loops Zn1
1 ) measurement, protection\DSTPDIS1
zone 1
Positive
DSTPDIS 21P(1 sequence 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.R1.setMag.f ASG FLOAT32 SG B 40.00 R1 zone 1
1 ) resistive reach, ohm protection\DSTPDIS1
zone 1
Pos. seq. reactive
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.X1Rv.setMag.f ASG FLOAT32 SG B 40.00 X1 reverse zone 1 reach in rev. dir.,
1 ) ohm protection\DSTPDIS1
non-dir. zone 1
Positive
DSTPDIS 21P(1 sequence reach 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.Z1Rv.setMag.f ASG FLOAT32 SG B 56.57 Z1 reverse zone 1
1 ) in rev. dir., non- ohm protection\DSTPDIS1
dir. zone 1
298
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Minimum
DSTPDIS 21P(1 resistive reach of 0.00...100.00 Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.MinRisPP.setMag.f ASG FLOAT32 SG B 30.00 Min Ris PP Rch Zn1
1 ) PP/3P-loops, ohm protection\DSTPDIS1
zone 1
Maximum
DSTPDIS 21P(1 resistive reach of 0.00...100.00 Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.MaxRisPP.setMag.f ASG FLOAT32 SG B 30.00 Max Ris PP Rch Zn1
1 ) PP/3P-loops, ohm protection\DSTPDIS1
zone 1
Enable load
DSTPDIS 21P(1 compensation Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.EnaLodComp.setVal SPG BOOLEAN SG B 1 Load Comp zone 1
1 ) for PE-loops, protection\DSTPDIS1
zone 1
Zero sequence
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.R0.setMag.f ASG FLOAT32 SG B 160.00 R0 zone 1 resistive reach,
1 ) ohm protection\DSTPDIS1
zone 1
Zero sequence
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.X0.setMag.f ASG FLOAT32 SG B 160.00 X0 zone 1 reactive reach,
1 ) ohm protection\DSTPDIS1
zone 1
Minimum
DSTPDIS 21P(1 0.00...500.00 Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.MinRisGnd.setMag.f ASG FLOAT32 SG B 100.00 Min Ris Gnd Rch Zn1 resistive reach of
1 ) ohm protection\DSTPDIS1
PE-loops, zone 1
Maximum
DSTPDIS 21P(1 0.00...500.00 Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.MaxRisGnd.setMag.f ASG FLOAT32 SG B 100.00 Max Ris Gnd Rch Zn1 resistive reach of
1 ) ohm protection\DSTPDIS1
PE-loops, zone 1
Tilt angle
DSTPDIS 21P(1 (positive value Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.TiltAng.setMag.f ASG FLOAT32 SG A 0 Tilt angle zone 1 -45...45 deg
1 ) increases zone protection\DSTPDIS1
area), zone 1
Enable parallel
line
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.ParLinComp.setVal SPG BOOLEAN SG A 0 Par line Comp zone 1 compensation
1 ) protection\DSTPDIS1
for PE-loops,
zone 1
Parallel line zero
DSTPDIS 21P(1 sequence mutual 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.Rm0.setMag.f ASG FLOAT32 SG A 40.00 Mutual R0 zone 1
1 ) resistance, zone ohm protection\DSTPDIS1
1
Parallel line zero
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST1PDIS1.Xm0.setMag.f ASG FLOAT32 SG A 40.00 Mutual X0 zone 1 sequence mutual
1 ) ohm protection\DSTPDIS1
reactance, zone 1
1=Non-
DSTPDIS 21P(1 EN Directional directional; Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.DirMod.setVal Enum SG B 2 Directional mode Zn2
1 ) G mode, zone 2 2=Forward; protection\DSTPDIS1
3=Reverse
Enable operate
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.PhDlMod.setVal SPG BOOLEAN SG B 1 PP Op delay Mod Zn2 timer for PP/3P-
1 ) protection\DSTPDIS1
loops, zone 2
Enable operate
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.PhDlTmms.setVal ING INT32 SG B 40 PP Op delay Mod Zn2 timer for PP/3P- 40...60000 ms
1 ) protection\DSTPDIS1
loops, zone 2
299
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Enable operate
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.GndDlMod.setVal SPG BOOLEAN SG B 1 Gnd Op Dl mode Zn2 timer for PE-
1 ) protection\DSTPDIS1
loops, zone 2
Time delay to
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.GndDlTmms.setVal ING INT32 SG B 40 Gnd operate Dl Zn2 operate of PE- 40...60000 ms
1 ) protection\DSTPDIS1
loops, zone 2
Positive
DSTPDIS 21P(1 sequence 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.X1.setMag.f ASG FLOAT32 SG B 40.00 X1 zone 2
1 ) reactive reach, ohm protection\DSTPDIS1
zone 2
Positive
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.LinAng.setMag.f ASG FLOAT32 SG B 45.0 Z1 angle zone 2 sequence line 15.0...90.0 deg
1 ) protection\DSTPDIS1
angle, zone 2
Residual
compensation
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.K0Fact.setMag.f ASG FLOAT32 SG B 1.0 Factor K0 zone 2 factor 0.0...4.0
1 ) protection\DSTPDIS1
magnitude, zone
2
Residual
DSTPDIS 21P(1 compensation Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.K0FactAng.setMag.f ASG FLOAT32 SG B 0 Factor K0 angle Zn2 -135...135 deg
1 ) factor angle, protection\DSTPDIS1
zone 2
Positive
DSTPDIS 21P(1 0.01...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.Z1Mod.setMag.f ASG FLOAT32 SG B 56.57 Z1 zone 2 sequence reach,
1 ) ohm protection\DSTPDIS1
zone 2
Enable PE-loop
DSTPDIS 21P(1 Op Mod Gnd loops Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.OpModGnd.setVal SPG BOOLEAN SG B 0 measurement,
1 ) Zn2 protection\DSTPDIS1
zone 2
Enable PP/3P-
DSTPDIS 21P(1 loop Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.OpModPP.setVal SPG BOOLEAN SG B 0 Op Mod PP loops Zn2
1 ) measurement, protection\DSTPDIS1
zone 2
Positive
DSTPDIS 21P(1 sequence 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.R1.setMag.f ASG FLOAT32 SG B 40.00 R1 zone 2
1 ) resistive reach, ohm protection\DSTPDIS1
zone 2
Pos. seq. reactive
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.X1Rv.setMag.f ASG FLOAT32 SG B 40.00 X1 reverse zone 2 reach in rev. dir.,
1 ) ohm protection\DSTPDIS1
non-dir. zone 2
Positive
DSTPDIS 21P(1 sequence reach 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.Z1Rv.setMag.f ASG FLOAT32 SG B 56.57 Z1 reverse zone 2
1 ) in rev. dir., non- ohm protection\DSTPDIS1
dir. zone 2
Minimum
DSTPDIS 21P(1 resistive reach of 0.00...100.00 Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.MinRisPP.setMag.f ASG FLOAT32 SG B 30.00 Min Ris PP Rch Zn2
1 ) PP/3P-loops, ohm protection\DSTPDIS1
zone 2
DSTPDIS 21P(1 Maximum 0.00...100.00 Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.MaxRisPP.setMag.f ASG FLOAT32 SG B 30.00 Max Ris PP Rch Zn2
1 ) resistive reach of ohm protection\DSTPDIS1

300
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

PP/3P-loops,
zone 2
Enable load
DSTPDIS 21P(1 compensation Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.EnaLodComp.setVal SPG BOOLEAN SG B 1 Load Comp zone 2
1 ) for PE-loops, protection\DSTPDIS1
zone 2
Zero sequence
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.R0.setMag.f ASG FLOAT32 SG B 160.00 R0 zone 2 resistive reach,
1 ) ohm protection\DSTPDIS1
zone 2
Zero sequence
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.X0.setMag.f ASG FLOAT32 SG B 160.00 X0 zone 2 reactive reach,
1 ) ohm protection\DSTPDIS1
zone 2
Minimum
DSTPDIS 21P(1 0.00...500.00 Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.MinRisGnd.setMag.f ASG FLOAT32 SG B 100.00 Min Ris Gnd Rch Zn2 resistive reach of
1 ) ohm protection\DSTPDIS1
PE-loops, zone 2
Maximum
DSTPDIS 21P(1 0.00...500.00 Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.MaxRisGnd.setMag.f ASG FLOAT32 SG B 100.00 Max Ris Gnd Rch Zn2 resistive reach of
1 ) ohm protection\DSTPDIS1
PE-loops, zone 2
Tilt angle
DSTPDIS 21P(1 (positive value Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.TiltAng.setMag.f ASG FLOAT32 SG A 0 Tilt angle zone 2 -45...45 deg
1 ) increases zone protection\DSTPDIS1
area), zone 2
Enable parallel
line
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.ParLinComp.setVal SPG BOOLEAN SG A 0 Par line Comp zone 2 compensation
1 ) protection\DSTPDIS1
for PE-loops,
zone 2
Parallel line zero
DSTPDIS 21P(1 sequence mutual 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.Rm0.setMag.f ASG FLOAT32 SG A 40.00 Mutual R0 zone 2
1 ) resistance, zone ohm protection\DSTPDIS1
2
Parallel line zero
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST2PDIS1.Xm0.setMag.f ASG FLOAT32 SG A 40.00 Mutual X0 zone 2 sequence mutual
1 ) ohm protection\DSTPDIS1
reactance, zone 2
1=Non-
DSTPDIS 21P(1 EN Directional directional; Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.DirMod.setVal Enum SG B 2 Directional mode Zn3
1 ) G mode, zone 3 2=Forward; protection\DSTPDIS1
3=Reverse
Enable operate
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.PhDlMod.setVal SPG BOOLEAN SG B 1 PP Op delay Mod Zn3 timer for PP/3P-
1 ) protection\DSTPDIS1
loops, zone 3
Time delay to
DSTPDIS 21P(1 operate of Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.PhDlTmms.setVal ING INT32 SG B 40 PP operate delay Zn3 40...60000 ms
1 ) PP/3P-loops, protection\DSTPDIS1
zone 3
Enable operate
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.GndDlMod.setVal SPG BOOLEAN SG B 1 Gnd Op Dl mode Zn3 timer for PE-
1 ) protection\DSTPDIS1
loops, zone 3

301
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Time delay to
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.GndDlTmms.setVal ING INT32 SG B 40 Gnd operate Dl Zn3 operate of PE- 40...60000 ms
1 ) protection\DSTPDIS1
loops, zone 3
Positive
DSTPDIS 21P(1 sequence 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.X1.setMag.f ASG FLOAT32 SG B 40.00 X1 zone 3
1 ) reactive reach, ohm protection\DSTPDIS1
zone 3
Positive
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.LinAng.setMag.f ASG FLOAT32 SG B 45.0 Z1 angle zone 3 sequence line 15.0...90.0 deg
1 ) protection\DSTPDIS1
angle, zone 3
Residual
compensation
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.K0Fact.setMag.f ASG FLOAT32 SG B 1.0 Factor K0 zone 3 factor 0.0...4.0
1 ) protection\DSTPDIS1
magnitude, zone
3
Residual
DSTPDIS 21P(1 compensation Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.K0FactAng.setMag.f ASG FLOAT32 SG B 0 Factor K0 angle Zn3 -135...135 deg
1 ) factor angle, protection\DSTPDIS1
zone 3
Positive
DSTPDIS 21P(1 0.01...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.Z1Mod.setMag.f ASG FLOAT32 SG B 56.57 Z1 zone 3 sequence reach,
1 ) ohm protection\DSTPDIS1
zone 3
Enable PE-loop
DSTPDIS 21P(1 Op Mod Gnd loops Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.OpModGnd.setVal SPG BOOLEAN SG B 0 measurement,
1 ) Zn3 protection\DSTPDIS1
zone 3
Enable PP/3P-
DSTPDIS 21P(1 loop Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.OpModPP.setVal SPG BOOLEAN SG B 0 Op Mod PP loops Zn3
1 ) measurement, protection\DSTPDIS1
zone 3
Positive
DSTPDIS 21P(1 sequence 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.R1.setMag.f ASG FLOAT32 SG B 40.00 R1 zone 3
1 ) resistive reach, ohm protection\DSTPDIS1
zone 3
Pos. seq. reactive
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.X1Rv.setMag.f ASG FLOAT32 SG B 40.00 X1 reverse zone 3 reach in rev. dir.,
1 ) ohm protection\DSTPDIS1
non-dir. zone 3
Positive
DSTPDIS 21P(1 sequence reach 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.Z1Rv.setMag.f ASG FLOAT32 SG B 56.57 Z1 reverse zone 3
1 ) in rev. dir., non- ohm protection\DSTPDIS1
dir. zone 3
Minimum
DSTPDIS 21P(1 resistive reach of 0.00...100.00 Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.MinRisPP.setMag.f ASG FLOAT32 SG B 30.00 Min Ris PP Rch Zn3
1 ) PP/3P-loops, ohm protection\DSTPDIS1
zone 3
Maximum
DSTPDIS 21P(1 resistive reach of 0.00...100.00 Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.MaxRisPP.setMag.f ASG FLOAT32 SG B 30.00 Max Ris PP Rch Zn3
1 ) PP/3P-loops, ohm protection\DSTPDIS1
zone 3
DSTPDIS 21P(1 Enable load Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.EnaLodComp.setVal SPG BOOLEAN SG B 1 Load Comp zone 3
1 ) compensation protection\DSTPDIS1
302
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

for PE-loops,
zone 3
Zero sequence
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.R0.setMag.f ASG FLOAT32 SG B 160.00 R0 zone 3 resistive reach,
1 ) ohm protection\DSTPDIS1
zone 3
Zero sequence
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.X0.setMag.f ASG FLOAT32 SG B 160.00 X0 zone 3 reactive reach,
1 ) ohm protection\DSTPDIS1
zone 3
Minimum
DSTPDIS 21P(1 0.00...500.00 Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.MinRisGnd.setMag.f ASG FLOAT32 SG B 100.00 Min Ris Gnd Rch Zn3 resistive reach of
1 ) ohm protection\DSTPDIS1
PE-loops, zone 3
Maximum
DSTPDIS 21P(1 0.00...500.00 Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.MaxRisGnd.setMag.f ASG FLOAT32 SG B 100.00 Max Ris Gnd Rch Zn3 resistive reach of
1 ) ohm protection\DSTPDIS1
PE-loops, zone 3
Tilt angle
DSTPDIS 21P(1 (positive value Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.TiltAng.setMag.f ASG FLOAT32 SG A 0 Tilt angle zone 3 -45...45 deg
1 ) increases zone protection\DSTPDIS1
area), zone 3
Enable parallel
line
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.ParLinComp.setVal SPG BOOLEAN SG A 0 Par line Comp zone 3 compensation
1 ) protection\DSTPDIS1
for PE-loops,
zone 3
Parallel line zero
DSTPDIS 21P(1 sequence mutual 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.Rm0.setMag.f ASG FLOAT32 SG A 40.00 Mutual R0 zone 3
1 ) resistance, zone ohm protection\DSTPDIS1
3
Parallel line zero
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST3PDIS1.Xm0.setMag.f ASG FLOAT32 SG A 40.00 Mutual X0 zone 3 sequence mutual
1 ) ohm protection\DSTPDIS1
reactance, zone 3
1=Non-
DSTPDIS 21P(1 EN Directional directional; Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.DirMod.setVal Enum SG B 2 Directional mode Zn4
1 ) G mode, zone 4 2=Forward; protection\DSTPDIS1
3=Reverse
Enable operate
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.PhDlMod.setVal SPG BOOLEAN SG B 1 PP Op delay Mod Zn4 timer for PP/3P-
1 ) protection\DSTPDIS1
loops, zone 4
Time delay to
DSTPDIS 21P(1 operate of Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.PhDlTmms.setVal ING INT32 SG B 40 PP operate delay Zn4 40...60000 ms
1 ) PP/3P-loops, protection\DSTPDIS1
zone 4
Enable operate
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.GndDlMod.setVal SPG BOOLEAN SG B 1 Gnd Op Dl mode Zn4 timer for PE-
1 ) protection\DSTPDIS1
loops, zone 4
Time delay to
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.GndDlTmms.setVal ING INT32 SG B 40 Gnd operate Dl Zn4 operate of PE- 40...60000 ms
1 ) protection\DSTPDIS1
loops, zone 4
DSTPDIS 21P(1 Positive 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.X1.setMag.f ASG FLOAT32 SG B 40.00 X1 zone 4
1 ) sequence ohm protection\DSTPDIS1
303
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

reactive reach,
zone 4
Positive
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.LinAng.setMag.f ASG FLOAT32 SG B 45.0 Z1 angle zone 4 sequence line 15.0...90.0 deg
1 ) protection\DSTPDIS1
angle, zone 4
Residual
compensation
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.K0Fact.setMag.f ASG FLOAT32 SG B 1.0 Factor K0 zone 4 factor 0.0...4.0
1 ) protection\DSTPDIS1
magnitude, zone
4
Residual
DSTPDIS 21P(1 compensation Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.K0FactAng.setMag.f ASG FLOAT32 SG B 0 Factor K0 angle Zn4 -135...135 deg
1 ) factor angle, protection\DSTPDIS1
zone 4
Positive
DSTPDIS 21P(1 0.01...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.Z1Mod.setMag.f ASG FLOAT32 SG B 56.57 Z1 zone 4 sequence reach,
1 ) ohm protection\DSTPDIS1
zone 4
Enable PE-loop
DSTPDIS 21P(1 Op Mod Gnd loops Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.OpModGnd.setVal SPG BOOLEAN SG B 0 measurement,
1 ) Zn4 protection\DSTPDIS1
zone 4
Enable PP/3P-
DSTPDIS 21P(1 loop Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.OpModPP.setVal SPG BOOLEAN SG B 0 Op Mod PP loops Zn4
1 ) measurement, protection\DSTPDIS1
zone 4
Positive
DSTPDIS 21P(1 sequence 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.R1.setMag.f ASG FLOAT32 SG B 40.00 R1 zone 4
1 ) resistive reach, ohm protection\DSTPDIS1
zone 4
Pos. seq. reactive
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.X1Rv.setMag.f ASG FLOAT32 SG B 40.00 X1 reverse zone 4 reach in rev. dir.,
1 ) ohm protection\DSTPDIS1
non-dir. zone 4
Positive
DSTPDIS 21P(1 sequence reach 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.Z1Rv.setMag.f ASG FLOAT32 SG B 56.57 Z1 reverse zone 4
1 ) in rev. dir., non- ohm protection\DSTPDIS1
dir. zone 4
Minimum
DSTPDIS 21P(1 resistive reach of 0.00...100.00 Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.MinRisPP.setMag.f ASG FLOAT32 SG B 30.00 Min Ris PP Rch Zn4
1 ) PP/3P-loops, ohm protection\DSTPDIS1
zone 4
Maximum
DSTPDIS 21P(1 resistive reach of 0.00...100.00 Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.MaxRisPP.setMag.f ASG FLOAT32 SG B 30.00 Max Ris PP Rch Zn4
1 ) PP/3P-loops, ohm protection\DSTPDIS1
zone 4
Enable load
DSTPDIS 21P(1 compensation Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.EnaLodComp.setVal SPG BOOLEAN SG B 1 Load Comp zone 4
1 ) for PE-loops, protection\DSTPDIS1
zone 4
Zero sequence
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.R0.setMag.f ASG FLOAT32 SG B 160.00 R0 zone 4 resistive reach,
1 ) ohm protection\DSTPDIS1
zone 4
304
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Zero sequence
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.X0.setMag.f ASG FLOAT32 SG B 160.00 X0 zone 4 reactive reach,
1 ) ohm protection\DSTPDIS1
zone 4
Minimum
DSTPDIS 21P(1 0.00...500.00 Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.MinRisGnd.setMag.f ASG FLOAT32 SG B 100.00 Min Ris Gnd Rch Zn4 resistive reach of
1 ) ohm protection\DSTPDIS1
PE-loops, zone 4
Maximum
DSTPDIS 21P(1 0.00...500.00 Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.MaxRisGnd.setMag.f ASG FLOAT32 SG B 100.00 Max Ris Gnd Rch Zn4 resistive reach of
1 ) ohm protection\DSTPDIS1
PE-loops, zone 4
Tilt angle
DSTPDIS 21P(1 (positive value Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.TiltAng.setMag.f ASG FLOAT32 SG A 0 Tilt angle zone 4 -45...45 deg
1 ) increases zone protection\DSTPDIS1
area), zone 4
Enable parallel
line
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.ParLinComp.setVal SPG BOOLEAN SG A 0 Par line Comp zone 4 compensation
1 ) protection\DSTPDIS1
for PE-loops,
zone 4
Parallel line zero
DSTPDIS 21P(1 sequence mutual 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.Rm0.setMag.f ASG FLOAT32 SG A 40.00 Mutual R0 zone 4
1 ) resistance, zone ohm protection\DSTPDIS1
4
Parallel line zero
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST4PDIS1.Xm0.setMag.f ASG FLOAT32 SG A 40.00 Mutual X0 zone 4 sequence mutual
1 ) ohm protection\DSTPDIS1
reactance, zone 4
1=Non-
DSTPDIS 21P(1 EN Directional directional; Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.DirMod.setVal Enum SG B 2 Directional mode Zn5
1 ) G mode, zone 5 2=Forward; protection\DSTPDIS1
3=Reverse
Enable operate
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.PhDlMod.setVal SPG BOOLEAN SG B 1 PP Op delay Mod Zn5 timer for PP/3P-
1 ) protection\DSTPDIS1
loops, zone 5
Time delay to
DSTPDIS 21P(1 operate of Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.PhDlTmms.setVal ING INT32 SG B 40 PP operate delay Zn5 40...60000 ms
1 ) PP/3P-loops, protection\DSTPDIS1
zone 5
Enable operate
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.GndDlMod.setVal SPG BOOLEAN SG B 1 Gnd Op Dl mode Zn5 timer for PE-
1 ) protection\DSTPDIS1
loops, zone 5
Time delay to
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.GndDlTmms.setVal ING INT32 SG B 40 Gnd operate Dl Zn5 operate of PE- 40...60000 ms
1 ) protection\DSTPDIS1
loops, zone 5
Positive
DSTPDIS 21P(1 sequence 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.X1.setMag.f ASG FLOAT32 SG B 40.00 X1 zone 5
1 ) reactive reach, ohm protection\DSTPDIS1
zone 5
Positive
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.LinAng.setMag.f ASG FLOAT32 SG B 45.0 Z1 angle zone 5 sequence line 15.0...90.0 deg
1 ) protection\DSTPDIS1
angle, zone 5

305
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Residual
compensation
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.K0Fact.setMag.f ASG FLOAT32 SG B 1.0 Factor K0 zone 5 factor 0.0...4.0
1 ) protection\DSTPDIS1
magnitude, zone
5
Residual
DSTPDIS 21P(1 compensation Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.K0FactAng.setMag.f ASG FLOAT32 SG B 0 Factor K0 angle Zn5 -135...135 deg
1 ) factor angle, protection\DSTPDIS1
zone 5
Positive
DSTPDIS 21P(1 0.01...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.Z1Mod.setMag.f ASG FLOAT32 SG B 56.57 Z1 zone 5 sequence reach,
1 ) ohm protection\DSTPDIS1
zone 5
Enable PE-loop
DSTPDIS 21P(1 Op Mod Gnd loops Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.OpModGnd.setVal SPG BOOLEAN SG B 0 measurement,
1 ) Zn5 protection\DSTPDIS1
zone 5
Enable PP/3P-
DSTPDIS 21P(1 loop Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.OpModPP.setVal SPG BOOLEAN SG B 0 Op Mod PP loops Zn5
1 ) measurement, protection\DSTPDIS1
zone 5
ositive sequence
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.R1.setMag.f ASG FLOAT32 SG B 40.00 R1 zone 5 resistive reach,
1 ) ohm protection\DSTPDIS1
zone 5
Pos. seq. reactive
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.X1Rv.setMag.f ASG FLOAT32 SG B 40.00 X1 reverse zone 5 reach in rev. dir.,
1 ) ohm protection\DSTPDIS1
non-dir. zone 5
Positive
DSTPDIS 21P(1 sequence reach 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.Z1Rv.setMag.f ASG FLOAT32 SG B 56.57 Z1 reverse zone 5
1 ) in rev. dir., non- ohm protection\DSTPDIS1
dir. zone 5
Minimum
DSTPDIS 21P(1 resistive reach of 0.00...100.00 Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.MinRisPP.setMag.f ASG FLOAT32 SG B 30.00 Min Ris PP Rch Zn5
1 ) PP/3P-loops, ohm protection\DSTPDIS1
zone 5
Maximum
DSTPDIS 21P(1 resistive reach of 0.00...100.00 Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.MaxRisPP.setMag.f ASG FLOAT32 SG B 30.00 Max Ris PP Rch Zn5
1 ) PP/3P-loops, ohm protection\DSTPDIS1
zone 5
Enable load
DSTPDIS 21P(1 compensation Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.EnaLodComp.setVal SPG BOOLEAN SG B 1 Load Comp zone 5
1 ) for PE-loops, protection\DSTPDIS1
zone 5
Zero sequence
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.R0.setMag.f ASG FLOAT32 SG B 160.00 R0 zone 5 resistive reach,
1 ) ohm protection\DSTPDIS1
zone 5
Zero sequence
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.X0.setMag.f ASG FLOAT32 SG B 160.00 X0 zone 5 reactive reach,
1 ) ohm protection\DSTPDIS1
zone 5
Minimum
DSTPDIS 21P(1 0.00...500.00 Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.MinRisGnd.setMag.f ASG FLOAT32 SG B 100.00 Min Ris Gnd Rch Zn5 resistive reach of
1 ) ohm protection\DSTPDIS1
PE-loops, zone 5
306
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Maximum
DSTPDIS 21P(1 0.00...500.00 Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.MaxRisGnd.setMag.f ASG FLOAT32 SG B 100.00 Max Ris Gnd Rch Zn5 resistive reach of
1 ) ohm protection\DSTPDIS1
PE-loops, zone 5
Tilt angle
DSTPDIS 21P(1 (positive value Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.TiltAng.setMag.f ASG FLOAT32 SG A 0 Tilt angle zone 5 -45...45 deg
1 ) increases zone protection\DSTPDIS1
area), zone 5
Enable parallel
line
DSTPDIS 21P(1 Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.ParLinComp.setVal SPG BOOLEAN SG A 0 Par line Comp zone 5 compensation
1 ) protection\DSTPDIS1
for PE-loops,
zone 5
Parallel line zero
DSTPDIS 21P(1 sequence mutual 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.Rm0.setMag.f ASG FLOAT32 SG A 40.00 Mutual R0 zone 5
1 ) resistance, zone ohm protection\DSTPDIS1
5
Parallel line zero
DSTPDIS 21P(1 0.00...3000.00 Settings\Settings\Distance
Z<(1) SET LD0.DST5PDIS1.Xm0.setMag.f ASG FLOAT32 SG A 40.00 Mutual X0 zone 5 sequence mutual
1 ) ohm protection\DSTPDIS1
reactance, zone 5
Angle from R-
DSTPDIS 21P(1 axis to left hand Settings\Settings\Distance
Z<(1) SET LD0.DSTRDIR1.MinFwdAng.setMag.f ASG FLOAT32 SP B 115 Min phase angle zone 90...135 deg
1 ) side directional protection\DSTPDIS1
line
Angle from R-
DSTPDIS 21P(1 axis to right Settings\Settings\Distance
Z<(1) SET LD0.DSTRDIR1.MaxFwdAng.setMag.f ASG FLOAT32 SP B 15 Max phase angle zone 0...45 deg
1 ) hand side protection\DSTPDIS1
directional line
5=Cross pol;
DSTPDIS 21P(1 EN Mho polarization Settings\Settings\Distance
Z<(1) SET LD0.DSTRDIR1.PolQty.setVal Enum SP B 7 Pol quantity zone 7=Pos. seq. volt.;
1 ) G method for zones protection\DSTPDIS1
1=Self pol
0=Reset;
87=Activate
OPERATE_Z1;
88=Deactive
OPERATE_Z1;
89=Activate
OPERATE_Z2;
90=Deactive
OPERATE_Z2;
91=Activate
DSTPDIS 21P(1 Test control for Tests\Function tests\Distance
Z<(1) TES LD0.GFCPDIS1.TestPro.Oper.ctlVal ENC Enum CO B 0 DSTPDIS1 OPERATE_Z3;
1 ) outputs protection
92=Deactive
OPERATE_Z3;
93=Activate
OPERATE_Z4;
94=Deactive
OPERATE_Z4;
95=Activate
OPERATE_Z5;
96=Deactive
OPERATE_Z5;
307
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

97=Activate
START_Z1;
98=Deactive
START_Z1;
99=Activate
START_Z2;
100=Deactive
START_Z2;
101=Activate
START_Z3;
102=Deactive
START_Z3;
103=Activate
START_Z4;
104=Deactive
START_Z4;
105=Activate
START_Z5;
106=Deactive
START_Z5;
109=Activate
START_GFC;
110=Deactive
START_GFC; -
3=Activate
OPERATE_GFC
; -4=Deactive
OPERATE_GFC
; -5=Activate
XC_FLT; -
6=Deactive
XC_FLT
DSTPDIS 21P(1 VisString25
Z<(1) VER LD0.GFCPDIS1.NamPlt.swRev LPL DC ED1 B1 (Name plate)
1 ) 5 (20)

BBPBDF1: Busbar differential protection: B


IEC IEC Parameter Channel
ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter name Parameter range Menu path
61850 60617 desc relation
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F1
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F2
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F3
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F4
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F5
channel)

308
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F6
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F7
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F8
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F9
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F10
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F11
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F12
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F13
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F14
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F15
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F16
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F17
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F18
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F19
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F20
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F21
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F22
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F23
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F24
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F25
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F26
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F27
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F28
channel)

309
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F29
channel)
(ACT input
BBPBDF1 3Id/I 87BL INP Channel I3P_F30
channel)
Block signal
Monitoring\I/O
for activating
BBPBDF1 3Id/I 87BL INP LD0.BBPTRC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK status\Differential
the blocking
prot\BBPBDF1\Inputs
mode
Signal for
enabling or
Monitoring\I/O
triggering the
BBPBDF1 3Id/I 87BL INP LD0.SFAPDIF1.TrgEFPro.stVal SPC BOOLEAN ST B 0 I1 TRG_SEF status\Differential
sensitive
prot\BBPBDF1\Inputs
earth-fault
protection
Reset
Monitoring\I/O
BBPBDF1
BBPBDF1 3Id/I 87BL INP LD0.BBCCSPVC1.OpnCTDetRs.stVal SPC BOOLEAN ST B 0 I1 RST_OCT status\Differential
open CT
prot\BBPBDF1\Inputs
detection
Monitoring\I/O
BBPBDF1 3Id/I 87BL OUT LD0.BBPTRC1.Str.general ACD BOOLEAN ST B I1 START Start status\Differential
prot\BBPBDF1\Outputs
Monitoring\I/O
BBPBDF1 3Id/I 87BL OUT LD0.BBPTRC1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE Operate status\Differential
prot\BBPBDF1\Outputs
Monitoring\I/O
Operate signal
BBPBDF1 3Id/I 87BL OUT LD0.ZNAPDIF1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPR_ZA (A,B,C) status\Differential
from zone A
prot\BBPBDF1\Outputs
External Monitoring\I/O
BBPBDF1 3Id/I 87BL OUT LD0.ZNAPDIF1.OpEx.general ACT BOOLEAN ST B StatNrml P,H OPR_EX_ZA operate signal status\Differential
for zone A prot\BBPBDF1\Outputs
Internal block Monitoring\I/O
BBPBDF1 3Id/I 87BL OUT LD0.ZNAPDIF1.BlkIntnSt.general ACT BOOLEAN ST B INT_BLKD_ZA status for zone (A,B,C) status\Differential
A prot\BBPBDF1\Outputs
Monitoring\I/O
Operate signal
BBPBDF1 3Id/I 87BL OUT LD0.ZNBPDIF1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPR_ZB (A,B,C) status\Differential
from zone B
prot\BBPBDF1\Outputs
External Monitoring\I/O
BBPBDF1 3Id/I 87BL OUT LD0.ZNBPDIF1.OpEx.general ACT BOOLEAN ST B StatNrml P,H OPR_EX_ZB operate signal status\Differential
for zone B prot\BBPBDF1\Outputs
Internal block Monitoring\I/O
BBPBDF1 3Id/I 87BL OUT LD0.ZNBPDIF1.BlkIntnSt.general ACT BOOLEAN ST B INT_BLKD_ZB status for zone (A,B,C) status\Differential
B prot\BBPBDF1\Outputs
Operate signal Monitoring\I/O
BBPBDF1 3Id/I 87BL OUT LD0.ZNCZPDIF1.Op.general ACT BOOLEAN ST B I1 OPR_ZN from check (A,B,C) status\Differential
zone prot\BBPBDF1\Outputs
Operate signal
Monitoring\I/O
for sensitive
BBPBDF1 3Id/I 87BL OUT LD0.SFAPDIF1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPR_SEF_ZA (A,B,C) status\Differential
eafth-fault for
prot\BBPBDF1\Outputs
zone A
310
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Operate signal
Monitoring\I/O
for sensitive
BBPBDF1 3Id/I 87BL OUT LD0.SFBPDIF1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPR_SEF_ZB (A,B,C) status\Differential
eafth-fault for
prot\BBPBDF1\Outputs
zone B
Monitoring\I/O
Open CT
BBPBDF1 3Id/I 87BL OUT LD0.BBCCSPVC1.FailACirc.general ACT BOOLEAN ST B CT_OPEN (A,B,C) status\Differential
detected
prot\BBPBDF1\Outputs
Reset
BBPBDF1
BBPBDF1 3Id/I 87BL CTR LD0.BBCCSPVC1.OpnCTDetRs.Oper.ctlVal SPC BOOLEAN CO B 0 I1 BBPBDF1 0=Cancel; 1=Clear Clear\Clear
open CT
detection
1=on; 2=blocked; 3=test; Monitoring\FB
BBPBDF1 3Id/I 87BL MON LD0.BBPTRC1.Beh.stVal ENS Enum ST B BBPBDF1 Status
4=test/blocked; 5=off status\Differential prot
Monitoring\I/O
Differential
status\Differential
BBPBDF1 3Id/I 87BL MON LD0.ZNAPDIF1.DifAClc.phsA.cVal.mag.f WYE FLOAT32 MX B I1 ID_ZA_A current Zone 0.00...80.00
prot\BBPBDF1\Monitored
A phase A
data
Monitoring\I/O
Differential
status\Differential
BBPBDF1 3Id/I 87BL MON LD0.ZNAPDIF1.DifAClc.phsB.cVal.mag.f WYE FLOAT32 MX B I1 ID_ZA_B current Zone 0.00...80.00
prot\BBPBDF1\Monitored
A phase B
data
Monitoring\I/O
Differential
status\Differential
BBPBDF1 3Id/I 87BL MON LD0.ZNAPDIF1.DifAClc.phsC.cVal.mag.f WYE FLOAT32 MX B I1 ID_ZA_C current Zone 0.00...80.00
prot\BBPBDF1\Monitored
A phase C
data
Monitoring\I/O
Biasing
status\Differential
BBPBDF1 3Id/I 87BL MON LD0.ZNAPDIF1.RstA.phsA.cVal.mag.f WYE FLOAT32 MX B I1 IB_ZA_A current Zone 0.00...80.00
prot\BBPBDF1\Monitored
A phase A
data
Monitoring\I/O
Biasing
status\Differential
BBPBDF1 3Id/I 87BL MON LD0.ZNAPDIF1.RstA.phsB.cVal.mag.f WYE FLOAT32 MX B I1 IB_ZA_B current Zone 0.00...80.00
prot\BBPBDF1\Monitored
A phase B
data
Monitoring\I/O
Biasing
status\Differential
BBPBDF1 3Id/I 87BL MON LD0.ZNAPDIF1.RstA.phsC.cVal.mag.f WYE FLOAT32 MX B I1 IB_ZA_C current Zone 0.00...80.00
prot\BBPBDF1\Monitored
A phase C
data
Monitoring\I/O
Differential
status\Differential
BBPBDF1 3Id/I 87BL MON LD0.ZNBPDIF1.DifAClc.phsA.cVal.mag.f WYE FLOAT32 MX B I1 ID_ZB_A current Zone 0.00...80.00
prot\BBPBDF1\Monitored
B phase A
data
Monitoring\I/O
Differential
status\Differential
BBPBDF1 3Id/I 87BL MON LD0.ZNBPDIF1.DifAClc.phsB.cVal.mag.f WYE FLOAT32 MX B I1 ID_ZB_B current Zone 0.00...80.00
prot\BBPBDF1\Monitored
B phase B
data
Monitoring\I/O
Differential
status\Differential
BBPBDF1 3Id/I 87BL MON LD0.ZNBPDIF1.DifAClc.phsC.cVal.mag.f WYE FLOAT32 MX B I1 ID_ZB_C current Zone 0.00...80.00
prot\BBPBDF1\Monitored
B phase C
data

311
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Monitoring\I/O
Biasing
status\Differential
BBPBDF1 3Id/I 87BL MON LD0.ZNBPDIF1.RstA.phsA.cVal.mag.f WYE FLOAT32 MX B I1 IB_ZB_A current Zone 0.00...80.00
prot\BBPBDF1\Monitored
B phase A
data
Monitoring\I/O
Biasing
status\Differential
BBPBDF1 3Id/I 87BL MON LD0.ZNBPDIF1.RstA.phsB.cVal.mag.f WYE FLOAT32 MX B I1 IB_ZB_B current Zone 0.00...80.00
prot\BBPBDF1\Monitored
B phase B
data
Monitoring\I/O
Biasing
status\Differential
BBPBDF1 3Id/I 87BL MON LD0.ZNBPDIF1.RstA.phsC.cVal.mag.f WYE FLOAT32 MX B I1 IB_ZB_C current Zone 0.00...80.00
prot\BBPBDF1\Monitored
B phase C
data
Monitoring\I/O
Differential
status\Differential
BBPBDF1 3Id/I 87BL MON LD0.ZNCZPDIF1.DifAClc.phsA.cVal.mag.f WYE FLOAT32 MX B I1 ID_ZN_A current check 0.00...80.00
prot\BBPBDF1\Monitored
zone phase A
data
Monitoring\I/O
Differential
status\Differential
BBPBDF1 3Id/I 87BL MON LD0.ZNCZPDIF1.DifAClc.phsB.cVal.mag.f WYE FLOAT32 MX B I1 ID_ZN_B current check 0.00...80.00
prot\BBPBDF1\Monitored
zone phase B
data
Monitoring\I/O
Differential
status\Differential
BBPBDF1 3Id/I 87BL MON LD0.ZNCZPDIF1.DifAClc.phsC.cVal.mag.f WYE FLOAT32 MX B I1 ID_ZN_C current check 0.00...80.00
prot\BBPBDF1\Monitored
zone phase C
data
Monitoring\I/O
Biasing
status\Differential
BBPBDF1 3Id/I 87BL MON LD0.ZNCZPDIF1.RstA.phsA.cVal.mag.f WYE FLOAT32 MX B I1 IB_ZN_A current check 0.00...80.00
prot\BBPBDF1\Monitored
zone phase A
data
Monitoring\I/O
Biasing
status\Differential
BBPBDF1 3Id/I 87BL MON LD0.ZNCZPDIF1.RstA.phsB.cVal.mag.f WYE FLOAT32 MX B I1 IB_ZN_B current check 0.00...80.00
prot\BBPBDF1\Monitored
zone phase B
data
Monitoring\I/O
Biasing
status\Differential
BBPBDF1 3Id/I 87BL MON LD0.ZNCZPDIF1.RstA.phsC.cVal.mag.f WYE FLOAT32 MX B I1 IB_ZN_C current check 0.00...80.00
prot\BBPBDF1\Monitored
zone phase C
data
Operation Off Settings\Settings\Differential
BBPBDF1 3Id/I 87BL SET LD0.BBPTRC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
/ On prot\BBPBDF1
Operation
threshold for Settings\Settings\Differential
BBPBDF1 3Id/I 87BL SET LD0.ZNAPDIF1.LoSet.setMag.f ASG FLOAT32 SG B 20 Operate value 5...150 %Ir
differential prot\BBPBDF1
characteristic
Slope of the
Settings\Settings\Differential
BBPBDF1 3Id/I 87BL SET LD0.ZNAPDIF1.SpeScn2.setMag.f ASG FLOAT32 SG B 50 Slope section 2 differential 25...75 %
prot\BBPBDF1
characteristic
Operation
Operate value threshold for Settings\Settings\Differential
BBPBDF1 3Id/I 87BL SET LD0.ZNCZPDIF1.LoSet.setMag.f ASG FLOAT32 SG B 20 5...150 %Ir
CZ check zone prot\BBPBDF1
characteristic

312
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Slope of the
Slope section 2 Settings\Settings\Differential
BBPBDF1 3Id/I 87BL SET LD0.ZNCZPDIF1.SpeScn2.setMag.f ASG FLOAT32 SG B 50 check zone 25...75 %
CZ prot\BBPBDF1
characteristic
Enable check
Enable check Settings\Settings\Differential
BBPBDF1 3Id/I 87BL SET LD0.ZNCZPDIF1.EnaZnChk.setVal SPG BOOLEAN SP B 1 zone
zone prot\BBPBDF1
functionality
Operation
threshold for
Operate value Settings\Settings\Differential
BBPBDF1 3Id/I 87BL SET LD0.SFAPDIF1.LoSet.setMag.f ASG FLOAT32 SG B 20 sensitive 5...150 %Ir
SEF prot\BBPBDF1
earth-fault
protection
Operate delay Operate delay Settings\Settings\Differential
BBPBDF1 3Id/I 87BL SET LD0.SFAPDIF1.MinOpTmms.setVal ING INT32 SG B 50 20...200000 ms
time time prot\BBPBDF1
Reset delay Settings\Settings\Differential
BBPBDF1 3Id/I 87BL SET LD0.SFAPDIF1.RsDlTmms.setVal ING INT32 SP B 20 Reset delay time 0...60000 ms
time prot\BBPBDF1
Blocking limit
Block value for sensitive Settings\Settings\Differential
BBPBDF1 3Id/I 87BL SET LD0.SFAPDIF1.MaxOpA.setMag.f ASG FLOAT32 SP A 150 50...500 %Ir
SEF earth-fault prot\BBPBDF1
characteristic
Enable
sensitive Settings\Settings\Differential
BBPBDF1 3Id/I 87BL SET LD0.SFAPDIF1.EnaEFPro.setVal SPG BOOLEAN SP A 1 Enable SEF
earth-fault prot\BBPBDF1
protection
Minimum
operate
Settings\Settings\Differential
BBPBDF1 3Id/I 87BL SET LD0.BBCCSPVC1.StrVal.setMag.f ASG FLOAT32 SP A 5 Start value OCT current 5...50 %Ir
prot\BBPBDF1
differential
level
Enable open Settings\Settings\Differential
BBPBDF1 3Id/I 87BL SET LD0.BBCCSPVC1.EnaOpnCT.setVal SPG BOOLEAN SP A false Enable OCT
CT detection prot\BBPBDF1
0=Reset; 1=Activate
START; 2=Deactive
START; 9=Activate
OPERATE; 10=Deactive
OPERATE; -9=Activate
OPR_ZA; -10=Deactive
OPR_ZA; -11=Activate
OPR_ZB; -12=Deactive
OPR_ZB; -13=Activate
OPR_ZN; -14=Deactive
Test control Tests\Function
BBPBDF1 3Id/I 87BL TES LD0.BBPTRC1.TestPro.Oper.ctlVal ENC Enum CO B 0 BBPBDF1 OPR_ZN; -15=Activate
for outputs tests\Differential prot
OPR_SEF_ZA; -
16=Deactive
OPR_SEF_ZA; -
17=Activate
OPR_SEF_ZB; -
18=Deactive
OPR_SEF_ZB; -
19=Activate
OPR_EX_ZA; -
20=Deactive
313
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

OPR_EX_ZA; -
21=Activate
OPR_EX_ZB; -
22=Deactive
OPR_EX_ZB; -
23=Activate
INT_BLKD_ZA; -
24=Deactive
INT_BLKD_ZA; -
25=Activate
INT_BLKD_ZB; -
26=Deactive
INT_BLKD_ZB; -
27=Activate CT_OPEN; -
28=Deactive CT_OPEN
VisString255
BBPBDF1 3Id/I 87BL VER LD0.BBPTRC1.NamPlt.swRev LPL DC ED1 B (Name plate)
(20)

ZNRSRC1: Busbar differential zone selection function: A1


Parameter Channel
IEC 61850 IEC 60617 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Parameter range Menu path
name relation
(ACT input
ZNRSRC1 ZNRSRC1 ZNRSRC1 INP Channel I3P
channel)
Monitoring\I/O
Exclude from
ZNRSRC1 ZNRSRC1 ZNRSRC1 INP LD0.ZNRSRC1.ExclChkZn.stVal SPS BOOLEAN ST B 0 I1 EXCL_CHKZ status\Differential
check zone
prot\ZNRSRC1\Inputs
Monitoring\I/O
External operate
ZNRSRC1 ZNRSRC1 ZNRSRC1 INP LD0.ZNRSRC1.OpExInd.stVal SPS BOOLEAN ST B 0 I1 EXT_OPR status\Differential
signal
prot\ZNRSRC1\Inputs
Disable function,
current to busbar Monitoring\I/O
ZNRSRC1 ZNRSRC1 ZNRSRC1 INP LD0.ZNRSRC1.InDsaSt.stVal SPS BOOLEAN ST B 0 I1 DISABLE differential status\Differential
protection forced to prot\ZNRSRC1\Inputs
zero
Signal for open
Monitoring\I/O
position of
ZNRSRC1 ZNRSRC1 ZNRSRC1 INP BOOLEAN B 1 POSOPEN_A status\Differential
apparatus from I/O
prot\ZNRSRC1\Inputs
zone A
Signal for close
Monitoring\I/O
position of
ZNRSRC1 ZNRSRC1 ZNRSRC1 INP BOOLEAN B 0 POSCLOSE_A status\Differential
apparatus from I/O
prot\ZNRSRC1\Inputs
zone A
Signal for close
Monitoring\I/O
request of
ZNRSRC1 ZNRSRC1 ZNRSRC1 INP BOOLEAN B 0 CL_CMD_A status\Differential
apparatus from I/O
prot\ZNRSRC1\Inputs
zone A

314
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Signal for open


Monitoring\I/O
position of
ZNRSRC1 ZNRSRC1 ZNRSRC1 INP BOOLEAN B 1 POSOPEN_B status\Differential
apparatus from I/O
prot\ZNRSRC1\Inputs
zone B
Signal for close
Monitoring\I/O
position of
ZNRSRC1 ZNRSRC1 ZNRSRC1 INP BOOLEAN B 0 POSCLOSE_B status\Differential
apparatus from I/O
prot\ZNRSRC1\Inputs
zone B
Signal for close
Monitoring\I/O
request of
ZNRSRC1 ZNRSRC1 ZNRSRC1 INP BOOLEAN B 0 CL_CMD_B status\Differential
apparatus from I/O
prot\ZNRSRC1\Inputs
zone B
(ACT output
ZNRSRC1 ZNRSRC1 ZNRSRC1 OUT Channel I3P_F
channel)
Measurements Monitoring\I/O
ZNRSRC1 ZNRSRC1 ZNRSRC1 OUT LD0.ZNRSRC1.ZnConn1.stVal SPS BOOLEAN ST B I1 ZONE_A connected to zone status\Differential
A prot\ZNRSRC1\Outputs
Measurements Monitoring\I/O
ZNRSRC1 ZNRSRC1 ZNRSRC1 OUT LD0.ZNRSRC1.ZnConn2.stVal SPS BOOLEAN ST B I1 ZONE_B connected to zone status\Differential
B prot\ZNRSRC1\Outputs
Monitoring\I/O
Apparatus state
ZNRSRC1 ZNRSRC1 ZNRSRC1 OUT LD0.ZNRSRC1.Alm1.stVal SPS BOOLEAN ST B StatNrml P,H I1 ALARM_A status\Differential
alarm from zone A
prot\ZNRSRC1\Outputs
Monitoring\I/O
Apparatus state
ZNRSRC1 ZNRSRC1 ZNRSRC1 OUT LD0.ZNRSRC1.Alm2.stVal SPS BOOLEAN ST B StatNrml P,H I1 ALARM_B status\Differential
alarm from zone B
prot\ZNRSRC1\Outputs
1=on; 2=blocked;
3=test; Monitoring\FB
ZNRSRC1 ZNRSRC1 ZNRSRC1 MON LD0.ZNRSRC1.Beh.stVal ENS Enum ST B ZNRSRC1 Status
4=test/blocked; status\Differential prot
5=off
Settings\Settings\Differential
ZNRSRC1 ZNRSRC1 ZNRSRC1 SET LD0.ZNRSRC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation Operation Off / On 1=on; 5=off
prot\ZNRSRC1
CT ratio Current transformer Settings\Settings\Differential
ZNRSRC1 ZNRSRC1 ZNRSRC1 SET LD0.ZNRSRC1.CTRatCor.setMag.f ASG FLOAT32 SP B 1.000 0.200...5.000
correction ratio correction prot\ZNRSRC1
1=No reversal;
Currrent
Polarity 2=All Zones; 3=For Settings\Settings\Differential
ZNRSRC1 ZNRSRC1 ZNRSRC1 SET LD0.ZNRSRC1.ZnRevPol.setVal ENG Enum SP B 1 measurement
reversal Zone A; 4=For prot\ZNRSRC1
polarity reversal
Zone B
Setting to
1=Zone A; 2=Zone Settings\Settings\Differential
ZNRSRC1 ZNRSRC1 ZNRSRC1 SET LD0.ZNRSRC1.ActZn.setVal ENG Enum SP B 3 Active zone activate/deactivate
B; 3=Zone A&B prot\ZNRSRC1
zones
Event delay of the
Settings\Settings\Differential
ZNRSRC1 ZNRSRC1 ZNRSRC1 SET LD0.ZNRSRC1.PosDlTmms.setVal ING INT32 SP A 200 Event delay intermediate and 0...60000 ms
prot\ZNRSRC1
bad position
Close Cmd Close command Settings\Settings\Differential
ZNRSRC1 ZNRSRC1 ZNRSRC1 SET LD0.ZNRSRC1.ClsCmdTmms.setVal ING INT32 SP A 500 10...60000 ms
timeout timeout prot\ZNRSRC1
1=Make-before-
Apparatus contact Settings\Settings\Differential
ZNRSRC1 ZNRSRC1 ZNRSRC1 SET LD0.ZNRSRC1.ConTyp.setVal ENG Enum SP A 1 Contact type break; 2=Break-
type prot\ZNRSRC1
before-make
315
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

0=Reset;
101=Activate
ZONE_A;
102=Deactive
ZONE_A;
103=Activate
ZONE_B;
104=Deactive
Test control for Tests\Function
ZNRSRC1 ZNRSRC1 ZNRSRC1 TES LD0.ZNRSRC1.TestProRl.Oper.ctlVal ENC Enum CO B 0 ZNRSRC1 ZONE_B;
outputs tests\Differential prot
105=Activate
ALARM_A;
106=Deactive
ALARM_A;
107=Activate
ALARM_B;
108=Deactive
ALARM_B
VisString255
ZNRSRC1 ZNRSRC1 ZNRSRC1 VER LD0.ZNRSRC1.NamPlt.swRev LPL DC A1 (Name plate)
(20)

ANOGAPC1: Anomaly detection: A


CM Parameter Parameter Parameter Channel
IEC 61850 IEC 60617 ANSI Category IECName CDC Type FC Access Default Dataset Event Menu path
T name desc range relation
ANOGAPC (ACT input
ANOGAPC1 ANOGAPC(1) INP Channel U3P
(1) channel)
ANOGAPC (ACT input
ANOGAPC1 ANOGAPC(1) INP Channel I3P
(1) channel)
ANOGAPC (ACT input
ANOGAPC1 ANOGAPC(1) INP Channel URES
(1) channel)
ANOGAPC (ACT input
ANOGAPC1 ANOGAPC(1) INP Channel IRES
(1) channel)
Block
ANOGAPC signal for Monitoring\I/O status\Anomaly
ANOGAPC1 ANOGAPC(1) INP LD0.ANOGAPC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
(1) all binary detection\ANOGAPC1\Inputs
outputs
ANOGAPC StatNrm P,H, Monitoring\I/O status\Anomaly
ANOGAPC1 ANOGAPC(1) OUT LD0.ANOGAPC1.Op.general ACT BOOLEAN ST B I1 OPERATE Operate
(1) l T detection\ANOGAPC1\Outputs
1=on;
2=blocked;
ANOGAPC
ANOGAPC1 ANOGAPC(1) MON LD0.ANOGAPC1.Beh.stVal ENS Enum ST B ANOGAPC1 status 3=test; Monitoring\FB status
(1)
4=test/blocked
; 5=off
Anomality Monitoring\I/O status\Anomaly
ANOGAPC
ANOGAPC1 ANOGAPC(1) MON LD0.ANOGAPC1.AOp.phsA ACT BOOLEAN ST B OPR_I_A in current detection\ANOGAPC1\Monitore
(1)
phase 1 d data
Anomality Monitoring\I/O status\Anomaly
ANOGAPC
ANOGAPC1 ANOGAPC(1) MON LD0.ANOGAPC1.AOp.phsB ACT BOOLEAN ST B OPR_I_B in current detection\ANOGAPC1\Monitore
(1)
phase 2 d data
316
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Anomality Monitoring\I/O status\Anomaly


ANOGAPC
ANOGAPC1 ANOGAPC(1) MON LD0.ANOGAPC1.AOp.phsC ACT BOOLEAN ST B OPR_I_C in current detection\ANOGAPC1\Monitore
(1)
phase 3 d data
Anomality Monitoring\I/O status\Anomaly
ANOGAPC
ANOGAPC1 ANOGAPC(1) MON LD0.ANOGAPC1.AOp.neut ACT BOOLEAN ST B OPR_I_RES in current detection\ANOGAPC1\Monitore
(1)
residual d data
Anomality Monitoring\I/O status\Anomaly
ANOGAPC
ANOGAPC1 ANOGAPC(1) MON LD0.ANOGAPC1.PhVOp.phsA ACT BOOLEAN ST B OPR_U_A in voltage detection\ANOGAPC1\Monitore
(1)
phase 1 d data
Anomality Monitoring\I/O status\Anomaly
ANOGAPC
ANOGAPC1 ANOGAPC(1) MON LD0.ANOGAPC1.PhVOp.phsB ACT BOOLEAN ST B OPR_U_B in voltage detection\ANOGAPC1\Monitore
(1)
phase 2 d data
Anomality Monitoring\I/O status\Anomaly
ANOGAPC
ANOGAPC1 ANOGAPC(1) MON LD0.ANOGAPC1.PhVOp.phsC ACT BOOLEAN ST B OPR_U_C in voltage detection\ANOGAPC1\Monitore
(1)
phase 3 d data
Anomality Monitoring\I/O status\Anomaly
ANOGAPC OPR_U_RE
ANOGAPC1 ANOGAPC(1) MON LD0.ANOGAPC1.PhVOp.neut ACT BOOLEAN ST B in voltage detection\ANOGAPC1\Monitore
(1) S
residual d data
ANOGAPC LD0.ANOGAPC1.Mod.Oper.ctlV C Operation Settings\Settings\Anomaly
ANOGAPC1 ANOGAPC(1) SET ENC Enum B,I 1 Operation 1=on; 5=off
(1) al O Off / On detection\ANOGAPC1
Sliding
window
size in
ANOGAPC LD0.ANOGAPC1.AnoWinCyc.s Detection Settings\Settings\Anomaly
ANOGAPC1 ANOGAPC(1) SET ING INT32 SP B,I 50 fundamenta 1...10000
(1) etVal window size detection\ANOGAPC1
l cycles for
anomaly
detection
Operate
level of the
latest to
ANOGAPC LD0.ANOGAPC1.AnoLevPhV.s Anomaly Settings\Settings\Anomaly
ANOGAPC1 ANOGAPC(1) SET ING INT32 SP B 200 mean 101...10000
(1) etVal level PhV detection\ANOGAPC1
anomaly
ratio for
PhV
Operate
level of the
latest to
ANOGAPC LD0.ANOGAPC1.AnoLevResV. Anomaly Settings\Settings\Anomaly
ANOGAPC1 ANOGAPC(1) SET ING INT32 SP B 200 mean 101...10000
(1) setVal level Res V detection\ANOGAPC1
anomaly
ratio for
Res V
Operate
level of the
ANOGAPC LD0.ANOGAPC1.AnoLevA.setV Anomaly latest to Settings\Settings\Anomaly
ANOGAPC1 ANOGAPC(1) SET ING INT32 SP B 200 101...10000
(1) al level A mean detection\ANOGAPC1
anomaly
ratio for A
Operate
ANOGAPC LD0.ANOGAPC1.AnoLevResA. Anomaly Settings\Settings\Anomaly
ANOGAPC1 ANOGAPC(1) SET ING INT32 SP B 200 level of the 101...10000
(1) setVal level Res A detection\ANOGAPC1
latest to
317
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

mean
anomaly
ratio for
Res A
0=Reset;
9=Activate
ANOGAPC LD0.ANOGAPC1.TestPro.Oper.c C Test control Tests\Function tests\Anomaly
ANOGAPC1 ANOGAPC(1) TES ENC Enum B 0 ANOGAPC1 OPERATE;
(1) tlVal O for outputs detection
10=Deactive
OPERATE
ANOGAPC VisString255 D (Name
ANOGAPC1 ANOGAPC(1) VER LD0.ANOGAPC1.NamPlt.swRev LPL ED1 A
(1) (20) C plate)

LBRDOB1: Load blinder: A


IEC Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter name Parameter range Menu path
60617 desc relation
(ACT input
LBRDOB1 LB(1) 21LB(1) INP Channel U3P
channel)
(ACT input
LBRDOB1 LB(1) 21LB(1) INP Channel I3P
channel)
Block signal
for activating Monitoring\I/O status\Impedance
LBRDOB1 LB(1) 21LB(1) INP LD0.LBRDOB1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
the blocking protection\LBRDOB1\Inputs
mode
Load
discrimination
Monitoring\I/O status\Impedance
LBRDOB1 LB(1) 21LB(1) OUT LD0.LBRDOB1.LodDsrFwd.stVal SPS BOOLEAN ST B StatNrml P,H I1 LB_FORWARD active in
protection\LBRDOB1\Outputs
forward
direction
Load
discrimination
Monitoring\I/O status\Impedance
LBRDOB1 LB(1) 21LB(1) OUT LD0.LBRDOB1.LodDsrRv.stVal SPS BOOLEAN ST B StatNrml P,H I1 LB_REVERSE active in
protection\LBRDOB1\Outputs
reverse
direction
1=on; 2=blocked;
3=test; Monitoring\FB status\Impedance
LBRDOB1 LB(1) 21LB(1) MON LD0.LBRDOB1.Beh.stVal ENS Enum ST B LBRDOB1 Status
4=test/blocked; protection
5=off
Positive
Monitoring\I/O status\Impedance
sequence
LBRDOB1 LB(1) 21LB(1) MON LD0.LBMMXU1.ZPs.cVal.mag.f CMV FLOAT32 MX B I1 Z1_AMPL 0.00...99999.00 ohm protection\LBRDOB1\Monitored
impedance
data
amplitude
Positive
Monitoring\I/O status\Impedance
sequence
LBRDOB1 LB(1) 21LB(1) MON LD0.LBMMXU1.ZPs.cVal.ang.f CMV FLOAT32 MX B Z1_ANGLE -180...180 deg protection\LBRDOB1\Monitored
impedance
data
phase angle
Operation Off Settings\Settings\Impedance
LBRDOB1 LB(1) 21LB(1) SET LD0.LBRDOB1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
/ On protection\LBRDOB1

318
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Resistive
Resistive reach forward reach Settings\Settings\Impedance
LBRDOB1 LB(1) 21LB(1) SET LD0.LBRDOB1.RisFwdLod.setMag.f ASG FLOAT32 SG B 150.00 1.00...6000.00 ohm
Fw for load protection\LBRDOB1
discrimination
Resistive
Resistive reach reverse reach Settings\Settings\Impedance
LBRDOB1 LB(1) 21LB(1) SET LD0.LBRDOB1.RisRvLod.setMag.f ASG FLOAT32 SG B 150.00 1.00...6000.00 ohm
Rv for load protection\LBRDOB1
discrimination
Maximum
Max impedance Settings\Settings\Impedance
LBRDOB1 LB(1) 21LB(1) SET LD0.LBRDOB1.AngLodMax.setMag.f ASG FLOAT32 SG B 25 angle for load 5...85 deg
angle protection\LBRDOB1
area
Minimum
Min impedance Settings\Settings\Impedance
LBRDOB1 LB(1) 21LB(1) SET LD0.LBRDOB1.AngLodMin.setMag.f ASG FLOAT32 SG B -25 angle for load -85...-5 deg
angle protection\LBRDOB1
area
Minimum
Min Ps Seq positive Settings\Settings\Impedance
LBRDOB1 LB(1) 21LB(1) SET LD0.LBRDOB1.MinPsSeqV.setMag.f ASG FLOAT32 SP A 0.1 0.1...1.0 xUn UL1TVTR1
voltage sequence protection\LBRDOB1
voltage
Maximum
Max Ng Seq negative Settings\Settings\Impedance
LBRDOB1 LB(1) 21LB(1) SET LD0.LBRDOB1.MaxNgSeqA.setMag.f ASG FLOAT32 SP A 0.20 0.01...10.00 xIn IL1TCTR1
current sequence protection\LBRDOB1
current
1=Non-directional;
Directional Directional Settings\Settings\Impedance
LBRDOB1 LB(1) 21LB(1) SET LD0.LBRDOB1.DirMod.setVal ENG Enum SG B 2 2=Forward;
mode mode protection\LBRDOB1
3=Reverse
0=Reset; 1=Activate
OPERATE;
2=Deactive
OPERATE;
109=Activate
Test control LB_FORWARD; Tests\Function tests\Impedance
LBRDOB1 LB(1) 21LB(1) TES LD0.LBRDOB1.TestProRl.Oper.ctlVal ENC Enum CO B 0 LBRDOB1
for outputs 110=Deactive protection
LB_FORWARD;
111=Activate
LB_REVERSE;
112=Deactive
LB_REVERSE
VisString255
LBRDOB1 LB(1) 21LB(1) VER LD0.LBRDOB1.NamPlt.swRev LPL DC A (Name plate)
(20)

COLPTOC1: Capacitor bank overload protection: D


IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter name Menu path
60617 desc range relation
COLPTOC 3I>3I<(1 (ACT input
51C/37(1) INP Channel I3P
1 ) channel)
Block signal
COLPTOC 3I>3I<(1 Monitoring\I/O status\Current
51C/37(1) INP LD0.COL1PTOC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK for
1 ) protection\COLPTOC1\Inputs
activating
319
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

the blocking
mode
Input
showing the
COLPTOC 3I>3I<(1 status of Monitoring\I/O status\Current
51C/37(1) INP LD0.COLPTUC1.InPosCls.stVal SPS BOOLEAN ST B 0 I1 CB_CLOSED
1 ) capacitor protection\COLPTOC1\Inputs
circuit
breaker
COLPTOC 3I>3I<(1 Overload Monitoring\I/O status\Current
51C/37(1) OUT LD0.COL1PTOC1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 ST_OVLOD
1 ) started protection\COLPTOC1\Outputs
COLPTOC 3I>3I<(1 Overload Monitoring\I/O status\Current
51C/37(1) OUT LD0.COL1PTOC1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPR_OVLOD
1 ) operated protection\COLPTOC1\Outputs
COLPTOC 3I>3I<(1 Monitoring\I/O status\Current
51C/37(1) OUT LD0.COL2PTOC1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 ALARM Alarm
1 ) protection\COLPTOC1\Outputs
Under
COLPTOC 3I>3I<(1 Monitoring\I/O status\Current
51C/37(1) OUT LD0.COLPTUC1.Str.general ACD BOOLEAN ST B StatNrml P,H I1 ST_UN_I current
1 ) protection\COLPTOC1\Outputs
started
Operate
COLPTOC 3I>3I<(1 Monitoring\I/O status\Current
51C/37(1) OUT LD0.COLPTUC1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPR_UN_I under
1 ) protection\COLPTOC1\Outputs
current
Inhibit re-
COLPTOC 3I>3I<(1 close of Monitoring\I/O status\Current
51C/37(1) OUT LD0.COLPTUC1.InhRec.stVal SPS BOOLEAN ST B I1 BLK_CLOSE
1 ) capacitor protection\COLPTOC1\Outputs
bank
Reset
COLPTOC 3I>3I<(1 COLPTOC1 Inh COLPTOC1 0=Cancel;
51C/37(1) CTR LD0.COLPTUC1.LORs.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Clear\Clear
1 ) reclose inhibit 1=Clear
reclose
1=on;
2=blocked;
COLPTOC 3I>3I<(1 Monitoring\FB status\Current
51C/37(1) MON LD0.COL1PTOC1.Beh.stVal ENS Enum ST B COLPTOC1 Status 3=test;
1 ) protection
4=test/blocked;
5=off
Start
Monitoring\I/O status\Current
COLPTOC 3I>3I<(1 duration for 0.00...100.00
51C/37(1) MON LD0.COL1PTOC1.StrDur.mag.f MV FLOAT32 MX B ST_DUR_OVLOD protection\COLPTOC1\Monitored
1 ) overload %
data
stage
Phase A
peak value
of the Monitoring\I/O status\Current
COLPTOC 3I>3I<(1
51C/37(1) MON LD0.COL1PTOC1.PkIAPhA.mag.f MV FLOAT32 MX B I1 I_PEAK_INT_A integrated 0.00...40.00 protection\COLPTOC1\Monitored
1 )
current of data
the
capacitor
Phase B
peak value Monitoring\I/O status\Current
COLPTOC 3I>3I<(1
51C/37(1) MON LD0.COL1PTOC1.PkIAPhB.mag.f MV FLOAT32 MX B I1 I_PEAK_INT_B of the 0.00...40.00 protection\COLPTOC1\Monitored
1 )
integrated data
current of

320
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

the
capacitor
Phase C
peak value
of the Monitoring\I/O status\Current
COLPTOC 3I>3I<(1
51C/37(1) MON LD0.COL1PTOC1.PkIAPhC.mag.f MV FLOAT32 MX B I1 I_PEAK_INT_C integrated 0.00...40.00 protection\COLPTOC1\Monitored
1 )
current of data
the
capacitor
Start
duration for Monitoring\I/O status\Current
COLPTOC 3I>3I<(1 0.00...100.00
51C/37(1) MON LD0.COLPTUC1.StrDur.mag.f MV FLOAT32 MX B ST_DUR_UN_I under protection\COLPTOC1\Monitored
1 ) %
current data
operation
COLPTOC 3I>3I<(1 Operation Settings\Settings\Current
51C/37(1) SET LD0.COL1PTOC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
1 ) Off / On protection\COLPTOC1
Start value
COLPTOC 3I>3I<(1 Start value Settings\Settings\Current
51C/37(1) SET LD0.COL1PTOC1.StrVal.setMag.f ASG FLOAT32 SG B 1.00 for overload 0.30...1.50 xIn IL1TCTR1
1 ) overload protection\COLPTOC1
stage
Time
multiplier
for
COLPTOC 3I>3I<(1 Settings\Settings\Current
51C/37(1) SET LD0.COL1PTOC1.TmMult.setMag.f ASG FLOAT32 SG B 1.00 Time multiplier Capacitor 0.05...2.00
1 ) protection\COLPTOC1
Bank
protection
curves
Number of
phases 1=1 out of 3;
COLPTOC 3I>3I<(1 Num of start Settings\Settings\Current
51C/37(1) SET LD0.COL1PTOC1.NumPh.setVal ENG Enum SP B 1 required for 2=2 out of 3;
1 ) phases protection\COLPTOC1
operate 3=3 out of 3
activation
Alarm start
COLPTOC 3I>3I<(1 value (% of Settings\Settings\Current
51C/37(1) SET LD0.COL2PTOC1.StrVal.setMag.f ASG FLOAT32 SG B 105 Alarm start value 80...120 %
1 ) Start value protection\COLPTOC1
overload)
COLPTOC 3I>3I<(1 Alarm delay 500...6000000 Settings\Settings\Current
51C/37(1) SET LD0.COL2PTOC1.OpDlTmms.setVal ING INT32 SG B 300000 Alarm delay time
1 ) time ms protection\COLPTOC1
Start value
COLPTOC 3I>3I<(1 for under Settings\Settings\Current
51C/37(1) SET LD0.COLPTUC1.StrVal.setMag.f ASG FLOAT32 SG B 0.50 Start value Un Cur 0.10...0.70 xIn IL1TCTR1
1 ) current protection\COLPTOC1
operation
Delay time
COLPTOC 3I>3I<(1 for under 100...120000 Settings\Settings\Current
51C/37(1) SET LD0.COLPTUC1.OpDlTmms.setVal ING INT32 SG B 1000 Un Cur delay time
1 ) current ms protection\COLPTOC1
operation
Enable
COLPTOC 3I>3I<(1 Enable under under 0=Disable; Settings\Settings\Current
51C/37(1) SET LD0.COLPTUC1.EnaUnCur.setVal SPG BOOLEAN SP A 1
1 ) current current 1=Enable protection\COLPTOC1
functionality

321
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

1=Non-
COLPTOC 3I>3I<(1 Reclose inhibit Reclose Settings\Settings\Current
51C/37(1) SET LD0.COLPTUC1.RecInhMod.setVal ENG Enum SP B 1 latched;
1 ) mode inhibit mode protection\COLPTOC1
3=Lockout
COLPTOC 3I>3I<(1 Reclose inhibit Reclose Settings\Settings\Current
51C/37(1) SET LD0.COLPTUC1.RecInhTms.setVal ING INT32 SG A 1 1...6000 s
1 ) time inhibit time protection\COLPTOC1
0=Reset;
17=Activate
ALARM;
18=Deactive
ALARM;
21=Activate
BLK_CLOSE;
22=Deactive
BLK_CLOSE;
113=Activate
OPR_OVLOD;
114=Deactive
COLPTOC 3I>3I<(1 Test control Tests\Function tests\Current
51C/37(1) TES LD0.COL1PTOC1.TestPro.Oper.ctlVal ENC Enum CO B 1 COLPTOC1 OPR_OVLOD;
1 ) for outputs protection
115=Activate
ST_OVLOD;
116=Deactive
ST_OVLOD;
117=Activate
OPR_UN_I;
118=Deactive
OPR_UN_I;
119=Activate
ST_UN_I;
120=Deactive
ST_UN_I
COLPTOC 3I>3I<(1 VisString255 (Name
51C/37(1) VER LD0.COL1PTOC1.NamPlt.swRev LPL DC ED1 D
1 ) (20) plate)

CUBPTOC1: Capacitor bank unbalance current, double Y bridge: D


IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
CUBPTOC 51NC (ACT input
dI>C(1) INP Channel I3P
1 -1(1) channel)
CUBPTOC 51NC (ACT input
dI>C(1) INP Channel IUNB
1 -1(1) channel)
Block signal
CUBPTOC 51NC for activating Monitoring\I/O status\Current
dI>C(1) INP LD0.CUB1PTOC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
1 -1(1) the blocking protection\CUBPTOC1\Inputs
mode
CUBPTOC 51NC StatNr Monitoring\I/O status\Current
dI>C(1) OUT LD0.CUB1PTOC1.Op.general ACT BOOLEAN ST B P,H,T I1 ALARM Alarm
1 -1(1) ml protection\CUBPTOC1\Outputs
CUBPTOC 51NC StatNr Monitoring\I/O status\Current
dI>C(1) OUT LD0.CUB2PTOC1.Str.general ACD BOOLEAN ST B P,H I1 START Start
1 -1(1) ml protection\CUBPTOC1\Outputs

322
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

CUBPTOC 51NC StatNr Monitoring\I/O status\Current


dI>C(1) OUT LD0.CUB2PTOC1.Op.general ACT BOOLEAN ST B P,H,T I1 OPERATE Operate
1 -1(1) ml protection\CUBPTOC1\Outputs
(Total
number of
CUBPTOC 51NC
dI>C(1) CTR LD0.CUB1PTOC1.FailCnt.Oper.ctlVal INC INT32 CO capacitor
1 -1(1)
element
failures)
(Capacitor
element
CUBPTOC 51NC
dI>C(1) CTR LD0.CUB1PTOC1.CntBr1PhsA.Oper.ctlVal INC INT32 CO failures in
1 -1(1)
branch1 of
phase A)
(Capacitor
element
CUBPTOC 51NC
dI>C(1) CTR LD0.CUB1PTOC1.CntBr2PhsA.Oper.ctlVal INC INT32 CO failures in
1 -1(1)
branch2 of
phase A)
(Capacitor
element
CUBPTOC 51NC
dI>C(1) CTR LD0.CUB1PTOC1.CntBr1PhsB.Oper.ctlVal INC INT32 CO failures in
1 -1(1)
branch1 of
phase B)
(Capacitor
element
CUBPTOC 51NC
dI>C(1) CTR LD0.CUB1PTOC1.CntBr2PhsB.Oper.ctlVal INC INT32 CO failures in
1 -1(1)
branch2 of
phase B)
(Capacitor
element
CUBPTOC 51NC
dI>C(1) CTR LD0.CUB1PTOC1.CntBr1PhsC.Oper.ctlVal INC INT32 CO failures in
1 -1(1)
branch1 of
phase C)
(Capacitor
element
CUBPTOC 51NC
dI>C(1) CTR LD0.CUB1PTOC1.CntBr2PhsC.Oper.ctlVal INC INT32 CO failures in
1 -1(1)
branch2 of
phase C)
CUBPTOC 51NC CUBPTOC1 Reset all the
dI>C(1) CTR LD0.CUB1PTOC1.CntRs.Oper.ctlVal SPC BOOLEAN CO B 0 I1 0=Cancel; 1=Clear Clear\Clear
1 -1(1) counters counters
Record
CUBPTOC 51NC Record 0=Do not record;
dI>C(1) CTR LD0.CUB1PTOC1.RcdUnb.Oper.ctlVal SPC BOOLEAN CO B 0 I1 unbalance Control\CUBPTOC1
1 -1(1) unbalance 1=Record
current
1=on; 2=blocked;
CUBPTOC 51NC 3=test; Monitoring\FB status\Current
dI>C(1) MON LD0.CUB1PTOC1.Beh.stVal ENS Enum ST B CUBPTOC1 Status
1 -1(1) 4=test/blocked; protection
5=off
Total number Monitoring\I/O status\Current
CUBPTOC 51NC FAIL_COU
dI>C(1) MON LD0.CUB1PTOC1.FailCnt.stVal INC INT32 ST B I1 of element 0...2147483647 protection\CUBPTOC1\Monitor
1 -1(1) NT
failures ed data

323
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Number of
element Monitoring\I/O status\Current
CUBPTOC 51NC COUNT_BR
dI>C(1) MON LD0.CUB1PTOC1.CntBr1PhsA.stVal INC INT32 ST B I1 failures in 0...2147483647 protection\CUBPTOC1\Monitor
1 -1(1) 1_A
branch1 ed data
phase-A
Number of
element Monitoring\I/O status\Current
CUBPTOC 51NC COUNT_BR
dI>C(1) MON LD0.CUB1PTOC1.CntBr2PhsA.stVal INC INT32 ST B I1 failures in 0...2147483647 protection\CUBPTOC1\Monitor
1 -1(1) 2_A
branch2 ed data
phase-A
Number of
element Monitoring\I/O status\Current
CUBPTOC 51NC COUNT_BR
dI>C(1) MON LD0.CUB1PTOC1.CntBr1PhsB.stVal INC INT32 ST B I1 failures in 0...2147483647 protection\CUBPTOC1\Monitor
1 -1(1) 1_B
branch1 ed data
phase-B
Number of
element Monitoring\I/O status\Current
CUBPTOC 51NC COUNT_BR
dI>C(1) MON LD0.CUB1PTOC1.CntBr2PhsB.stVal INC INT32 ST B I1 failures in 0...2147483647 protection\CUBPTOC1\Monitor
1 -1(1) 2_B
branch2 ed data
phase-B
Number of
element Monitoring\I/O status\Current
CUBPTOC 51NC COUNT_BR
dI>C(1) MON LD0.CUB1PTOC1.CntBr1PhsC.stVal INC INT32 ST B I1 failures in 0...2147483647 protection\CUBPTOC1\Monitor
1 -1(1) 1_C
branch1 ed data
phase-C
Number of
element Monitoring\I/O status\Current
CUBPTOC 51NC COUNT_BR
dI>C(1) MON LD0.CUB1PTOC1.CntBr2PhsC.stVal INC INT32 ST B I1 failures in 0...2147483647 protection\CUBPTOC1\Monitor
1 -1(1) 2_C
branch2 ed data
phase-C
Recorded
natural Monitoring\I/O status\Current
CUBPTOC 51NC LD0.CUB1PTOC1.NatUnbCur.neut.cVal.m M I_NAT_AM
dI>C(1) MON WYE FLOAT32 B I1 unbalance 0.00...5.00 xIn protection\CUBPTOC1\Monitor
1 -1(1) ag.f X PL
current ed data
amplitude
Recorded
Monitoring\I/O status\Current
CUBPTOC 51NC LD0.CUB1PTOC1.NatUnbCur.neut.cVal.an M I_NAT_AN natural -179.00...179.00
dI>C(1) MON WYE FLOAT32 B protection\CUBPTOC1\Monitor
1 -1(1) g.f X GL unbalance deg
ed data
current angle
Compensated
Monitoring\I/O status\Current
CUBPTOC 51NC LD0.CUB1PTOC1.CompUnbCur.neut.cVal. M I_COM_AM unbalance
dI>C(1) MON WYE FLOAT32 B I1 0.00...5.00 xIn protection\CUBPTOC1\Monitor
1 -1(1) mag.f X PL current
ed data
amplitude
Compensated Monitoring\I/O status\Current
CUBPTOC 51NC LD0.CUB1PTOC1.CompUnbCur.neut.cVal. M I_COM_AN -179.00...179.00
dI>C(1) MON WYE FLOAT32 B unbalance protection\CUBPTOC1\Monitor
1 -1(1) ang.f X GL deg
current angle ed data
Ratio of start Monitoring\I/O status\Current
CUBPTOC 51NC M START_DU
dI>C(1) MON LD0.CUB2PTOC1.StrDur.mag.f MV FLOAT32 B time / operate 0.00...100.00 % protection\CUBPTOC1\Monitor
1 -1(1) X R
time ed data

324
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

CUBPTOC 51NC Operation Settings\Settings\Current


dI>C(1) SET LD0.CUB1PTOC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
1 -1(1) Off / On protection\CUBPTOC1
CUBPTOC 51NC Alarm start Alarm start Settings\Settings\Current IL1TCT
dI>C(1) SET LD0.CUB1PTOC1.StrVal.setMag.f ASG FLOAT32 SG B 0.05 0.01...1.00 xIn
1 -1(1) value value protection\CUBPTOC1 R2
CUBPTOC 51NC Alarm delay Alarm delay Settings\Settings\Current
dI>C(1) SET LD0.CUB1PTOC1.OpDlTmms.setVal ING INT32 SG B 200000 50...200000 ms
1 -1(1) time time protection\CUBPTOC1
Element
failure limit
CUBPTOC 51NC Element fail Settings\Settings\Current
dI>C(1) SET LD0.CUB1PTOC1.FailCntLim.setVal ING INT32 SG A 3 above which 1...100
1 -1(1) limit protection\CUBPTOC1
alarm is
active
Enable
natural
CUBPTOC 51NC Natural Settings\Settings\Current
dI>C(1) SET LD0.CUB1PTOC1.NatCompEna.setVal SPG BOOLEAN SG A 0 unbalance
1 -1(1) Comp enable protection\CUBPTOC1
compensatio
n
Mode of
CUBPTOC 51NC 1=Normal; Settings\Settings\Current
dI>C(1) SET LD0.CUB1PTOC1.UnbAlmMod.setVal ENG Enum SG B 1 Alarm mode operation for
1 -1(1) 2=Element counter protection\CUBPTOC1
Alarm stage
Location of
CUBPTOC 51NC 1=Internal; Settings\Settings\Current
dI>C(1) SET LD0.CUB1PTOC1.FuLoct.setVal ENG Enum SG A 1 Fuse location capacitor
1 -1(1) 2=External protection\CUBPTOC1
fuse
1=ANSI Ext. inv.;
2=ANSI Very inv.;
3=ANSI Norm.
inv.; 4=ANSI Mod.
inv.; 5=ANSI Def.
Time; 6=L.T.E.
inv.; 7=L.T.V. inv.;
8=L.T. inv.; 9=IEC
Selection of
CUBPTOC 51NC CURV Operating Norm. inv.; Settings\Settings\Current
dI>C(1) SET LD0.CUB2PTOC1.TmACrv.setCharact Enum SG B,I 15 time delay
1 -1(1) E curve type 10=IEC Very inv.; protection\CUBPTOC1
curve type
11=IEC inv.;
12=IEC Ext. inv.;
13=IEC S.T. inv.;
14=IEC L.T. inv.;
15=IEC Def. Time;
17=Programmable;
18=RI type;
19=RD type
Parameter A
CUBPTOC 51NC CURV 28.200 Curve for customer Settings\Settings\Current
dI>C(1) SET LD0.CUB2PTOC1.TmACrv.setParA FLOAT32 SP B,I 0.0086 ...120.0000
1 -1(1) E 0 parameter A programmabl protection\CUBPTOC1
e curve
Parameter B
CUBPTOC 51NC CURV Curve for customer Settings\Settings\Current
dI>C(1) SET LD0.CUB2PTOC1.TmACrv.setParB FLOAT32 SP B,I 0.1217 0.0000 ...0.7120
1 -1(1) E parameter B programmabl protection\CUBPTOC1
e curve
CUBPTOC 51NC CURV Curve Parameter C Settings\Settings\Current
dI>C(1) SET LD0.CUB2PTOC1.TmACrv.setParC FLOAT32 SP B,I 2.00 0.02...2.00
1 -1(1) E parameter C for customer protection\CUBPTOC1

325
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

programmabl
e curve
Parameter E
CUBPTOC 51NC CURV Curve for customer Settings\Settings\Current
dI>C(1) SET LD0.CUB2PTOC1.TmACrv.setParE FLOAT32 SP B,I 1.0 0.0...1.0
1 -1(1) E parameter E programmabl protection\CUBPTOC1
e curve
CUBPTOC 51NC Settings\Settings\Current IL1TCT
dI>C(1) SET LD0.CUB2PTOC1.StrVal.setMag.f ASG FLOAT32 SG B 0.10 Start value Start value 0.01...1.00 xIn
1 -1(1) protection\CUBPTOC1 R2
Time
CUBPTOC 51NC Time multiplier in Settings\Settings\Current
dI>C(1) SET LD0.CUB2PTOC1.TmMult.setMag.f ASG FLOAT32 SG B 1.00 0.05...15.00
1 -1(1) multiplier IEC/ANSI protection\CUBPTOC1
IDMT curves
Minimum
CUBPTOC 51NC Minimum operate time Settings\Settings\Current
dI>C(1) SET LD0.CUB2PTOC1.MinOpTmms.setVal ING INT32 SP A 20 20...60000 ms
1 -1(1) operate time for IDMT protection\CUBPTOC1
curves
CUBPTOC 51NC Operate Operate Settings\Settings\Current
dI>C(1) SET LD0.CUB2PTOC1.OpDlTmms.setVal ING INT32 SG B 5000 50...200000 ms
1 -1(1) delay time delay time protection\CUBPTOC1
CUBPTOC 51NC Reset delay Reset delay Settings\Settings\Current
dI>C(1) SET LD0.CUB2PTOC1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
1 -1(1) time time protection\CUBPTOC1
0=Reset;
1=Activate
START;
2=Deactive
START;
9=Activate
CUBPTOC 51NC Test control Tests\Function tests\Current
dI>C(1) TES LD0.CUB1PTOC1.TestPro.Oper.ctlVal ENC Enum CO B 1 CUBPTOC1 OPERATE;
1 -1(1) for outputs protection
10=Deactive
OPERATE;
17=Activate
ALARM;
18=Deactive
ALARM
CUBPTOC 51NC VisString25
dI>C(1) VER LD0.CUB1PTOC1.NamPlt.swRev LPL DC ED1 D (Name plate)
1 -1(1) 5 (20)

HCUBPTOC1: Capacitor bank unbalance current, H bridge: D


IEC Defau Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Dataset Event CMT Parameter range Menu path
60617 lt name desc relation
51NC (ACT input
HCUBPTOC1 3dI>C(1) INP Channel I3P1
-2(1) channel)
51NC (ACT input
HCUBPTOC1 3dI>C(1) INP Channel I3P2
-2(1) channel)
Block signal
for
51NC Monitoring\I/O status\Current
HCUBPTOC1 3dI>C(1) INP LD0.HCUB1PTOC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK activating
-2(1) protection\HCUBPTOC1\Inputs
the blocking
mode
326
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Monitoring\I/O status\Current
51NC StatNr
HCUBPTOC1 3dI>C(1) OUT LD0.HCUB1PTOC1.Op.general ACT BOOLEAN ST B P,H,T I1 ALARM Alarm protection\HCUBPTOC1\Output
-2(1) ml
s
Monitoring\I/O status\Current
51NC StatNr
HCUBPTOC1 3dI>C(1) OUT LD0.HCUB2PTOC1.Str.general ACD BOOLEAN ST B P,H I1 START Start protection\HCUBPTOC1\Output
-2(1) ml
s
Monitoring\I/O status\Current
51NC StatNr
HCUBPTOC1 3dI>C(1) OUT LD0.HCUB2PTOC1.Op.general ACT BOOLEAN ST B P,H,T I1 OPERATE Operate protection\HCUBPTOC1\Output
-2(1) ml
s
0=Do not record;
1=Record all
Record phases;
51NC LD0.HCUB1PTOC1.UnbRcdPh.Oper.ctlV Record natural 2=Record phase
HCUBPTOC1 3dI>C(1) CTR ENC Enum CO B 0 Control\HCUBPTOC1
-2(1) al unbalance unbalance A; 3=Record
current phase B;
4=Record phase
C
1=on;
2=blocked;
51NC Monitoring\FB status\Current
HCUBPTOC1 3dI>C(1) MON LD0.HCUB1PTOC1.Beh.stVal ENS Enum ST B HCUBPTOC1 Status 3=test;
-2(1) protection
4=test/blocked;
5=off
Recorded
natural
Monitoring\I/O status\Current
51NC LD0.HCUB1PTOC1.NatUnbCur.phsA.cV M I_NAT_AMP unbalance
HCUBPTOC1 3dI>C(1) MON WYE FLOAT32 B I1 0.00...5.00 xIn protection\HCUBPTOC1\Monit
-2(1) al.mag.f X L_A current
ored data
amplitude
phase A
Recorded
natural Monitoring\I/O status\Current
51NC LD0.HCUB1PTOC1.NatUnbCur.phsA.cV M I_NAT_ANG -179.00...179.00
HCUBPTOC1 3dI>C(1) MON WYE FLOAT32 B unbalance protection\HCUBPTOC1\Monit
-2(1) al.ang.f X L_A deg
current angle ored data
phase A
Recorded
natural
Monitoring\I/O status\Current
51NC LD0.HCUB1PTOC1.NatUnbCur.phsB.cV M I_NAT_AMP unbalance
HCUBPTOC1 3dI>C(1) MON WYE FLOAT32 B I1 0.00...5.00 xIn protection\HCUBPTOC1\Monit
-2(1) al.mag.f X L_B current
ored data
amplitude
phase B
Recorded
natural Monitoring\I/O status\Current
51NC LD0.HCUB1PTOC1.NatUnbCur.phsB.cV M I_NAT_ANG -179.00...179.00
HCUBPTOC1 3dI>C(1) MON WYE FLOAT32 B unbalance protection\HCUBPTOC1\Monit
-2(1) al.ang.f X L_B deg
current angle ored data
phase B
Recorded
natural
Monitoring\I/O status\Current
51NC LD0.HCUB1PTOC1.NatUnbCur.phsC.cV M I_NAT_AMP unbalance
HCUBPTOC1 3dI>C(1) MON WYE FLOAT32 B I1 0.00...5.00 xIn protection\HCUBPTOC1\Monit
-2(1) al.mag.f X L_C current
ored data
amplitude
phase C

327
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Recorded
natural Monitoring\I/O status\Current
51NC LD0.HCUB1PTOC1.NatUnbCur.phsC.cV M I_NAT_ANG -179.00...179.00
HCUBPTOC1 3dI>C(1) MON WYE FLOAT32 B unbalance protection\HCUBPTOC1\Monit
-2(1) al.ang.f X L_C deg
current angle ored data
phase C
Compensate
d unbalance Monitoring\I/O status\Current
51NC LD0.HCUB1PTOC1.CompUnbCur.phsA. M I_COM_AMP
HCUBPTOC1 3dI>C(1) MON WYE FLOAT32 B I1 current 0.00...5.00 xIn protection\HCUBPTOC1\Monit
-2(1) cVal.mag.f X L_A
amplitude ored data
phase A
Compensate
Monitoring\I/O status\Current
51NC LD0.HCUB1PTOC1.CompUnbCur.phsA. M I_COM_ANG d unbalance -179.00...179.00
HCUBPTOC1 3dI>C(1) MON WYE FLOAT32 B protection\HCUBPTOC1\Monit
-2(1) cVal.ang.f X L_A current angle deg
ored data
phase A
Compensate
d unbalance Monitoring\I/O status\Current
51NC LD0.HCUB1PTOC1.CompUnbCur.phsB.c M I_COM_AMP
HCUBPTOC1 3dI>C(1) MON WYE FLOAT32 B I1 current 0.00...5.00 xIn protection\HCUBPTOC1\Monit
-2(1) Val.mag.f X L_B
amplitude ored data
phase B
Compensate
Monitoring\I/O status\Current
51NC LD0.HCUB1PTOC1.CompUnbCur.phsB.c M I_COM_ANG d unbalance -179.00...179.00
HCUBPTOC1 3dI>C(1) MON WYE FLOAT32 B protection\HCUBPTOC1\Monit
-2(1) Val.ang.f X L_B current angle deg
ored data
phase B
Compensate
d unbalance Monitoring\I/O status\Current
51NC LD0.HCUB1PTOC1.CompUnbCur.phsC.c M I_COM_AMP
HCUBPTOC1 3dI>C(1) MON WYE FLOAT32 B I1 current 0.00...5.00 xIn protection\HCUBPTOC1\Monit
-2(1) Val.mag.f X L_C
amplitude ored data
phase C
Compensate
Monitoring\I/O status\Current
51NC LD0.HCUB1PTOC1.CompUnbCur.phsC.c M I_COM_ANG d unbalance -179.00...179.00
HCUBPTOC1 3dI>C(1) MON WYE FLOAT32 B protection\HCUBPTOC1\Monit
-2(1) Val.ang.f X L_C current angle deg
ored data
phase C
Ratio of start Monitoring\I/O status\Current
51NC M
HCUBPTOC1 3dI>C(1) MON LD0.HCUB2PTOC1.StrDur.mag.f MV FLOAT32 B START_DUR time / 0.00...100.00 % protection\HCUBPTOC1\Monit
-2(1) X
operate time ored data
51NC Operation Settings\Settings\Current
HCUBPTOC1 3dI>C(1) SET LD0.HCUB1PTOC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
-2(1) Off / On protection\HCUBPTOC1
51NC Alarm start Alarm start Settings\Settings\Current IL1TCTR
HCUBPTOC1 3dI>C(1) SET LD0.HCUB1PTOC1.StrVal.setMag.f ASG FLOAT32 SG B 0.05 0.01...1.00 xIn
-2(1) value value protection\HCUBPTOC1 2
51NC 20000 Alarm delay Alarm delay Settings\Settings\Current
HCUBPTOC1 3dI>C(1) SET LD0.HCUB1PTOC1.OpDlTmms.setVal ING INT32 SG B 40...200000 ms
-2(1) 0 time time protection\HCUBPTOC1
Enable
natural
51NC LD0.HCUB1PTOC1.CompEnaPhsA.setV Natural Comp Settings\Settings\Current
HCUBPTOC1 3dI>C(1) SET SPG BOOLEAN SG ED2,A 0 unbalance
-2(1) al Ena PhA protection\HCUBPTOC1
compensatio
n PhA
Enable
51NC Natural Comp Settings\Settings\Current
HCUBPTOC1 3dI>C(1) SET LD0.HCUB1PTOC1.CompEnaPhA.setVal SPG BOOLEAN SG ED1 0 natural
-2(1) Ena PhA protection\HCUBPTOC1
unbalance

328
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

compensatio
n PhA
Enable
natural
51NC LD0.HCUB1PTOC1.CompEnaPhsB.setVa Natural Comp Settings\Settings\Current
HCUBPTOC1 3dI>C(1) SET SPG BOOLEAN SG ED2,A 0 unbalance
-2(1) l Ena PhB protection\HCUBPTOC1
compensatio
n PhB
Enable
natural
51NC Natural Comp Settings\Settings\Current
HCUBPTOC1 3dI>C(1) SET LD0.HCUB1PTOC1.CompEnaPhB.setVal SPG BOOLEAN SG ED1 0 unbalance
-2(1) Ena PhB protection\HCUBPTOC1
compensatio
n PhB
Enable
natural
51NC LD0.HCUB1PTOC1.CompEnaPhsC.setVa Natural Comp Settings\Settings\Current
HCUBPTOC1 3dI>C(1) SET SPG BOOLEAN SG ED2,A 0 unbalance
-2(1) l Ena PhC protection\HCUBPTOC1
compensatio
n PhC
Enable
natural
51NC Natural Comp Settings\Settings\Current
HCUBPTOC1 3dI>C(1) SET LD0.HCUB1PTOC1.CompEnaPhC.setVal SPG BOOLEAN SG ED1 0 unbalance
-2(1) Ena PhC protection\HCUBPTOC1
compensatio
n PhC
1=ANSI Ext.
inv.; 2=ANSI
Very inv.;
3=ANSI Norm.
inv.; 4=ANSI
Mod. inv.;
5=ANSI Def.
Time; 6=L.T.E.
inv.; 7=L.T.V.
inv.; 8=L.T. inv.;
Selection of 9=IEC Norm.
51NC Operating Settings\Settings\Current
HCUBPTOC1 3dI>C(1) SET LD0.HCUB2PTOC1.TmACrv.setCharact CURVE Enum SG B,I 15 time delay inv.; 10=IEC
-2(1) curve type protection\HCUBPTOC1
curve type Very inv.;
11=IEC inv.;
12=IEC Ext.
inv.; 13=IEC
S.T. inv.;
14=IEC L.T.
inv.; 15=IEC
Def. Time;
17=Programmabl
e; 18=RI type;
19=RD type
Parameter A
51NC 28.20 Curve for customer 0.0086 Settings\Settings\Current
HCUBPTOC1 3dI>C(1) SET LD0.HCUB2PTOC1.TmACrv.setParA CURVE FLOAT32 SP B,I
-2(1) 00 parameter A programmab ...120.0000 protection\HCUBPTOC1
le curve
51NC 0.121 Curve Parameter B Settings\Settings\Current
HCUBPTOC1 3dI>C(1) SET LD0.HCUB2PTOC1.TmACrv.setParB CURVE FLOAT32 SP B,I 0.0000 ...0.7120
-2(1) 7 parameter B for customer protection\HCUBPTOC1

329
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

programmab
le curve
Parameter C
51NC Curve for customer Settings\Settings\Current
HCUBPTOC1 3dI>C(1) SET LD0.HCUB2PTOC1.TmACrv.setParC CURVE FLOAT32 SP B,I 2.00 0.02...2.00
-2(1) parameter C programmab protection\HCUBPTOC1
le curve
Parameter E
51NC Curve for customer Settings\Settings\Current
HCUBPTOC1 3dI>C(1) SET LD0.HCUB2PTOC1.TmACrv.setParE CURVE FLOAT32 SP B,I 1.0 0.0...1.0
-2(1) parameter E programmab protection\HCUBPTOC1
le curve
51NC Settings\Settings\Current IL1TCTR
HCUBPTOC1 3dI>C(1) SET LD0.HCUB2PTOC1.StrVal.setMag.f ASG FLOAT32 SG B 0.10 Start value Start value 0.01...1.00 xIn
-2(1) protection\HCUBPTOC1 2
Time
multiplier in
51NC Time Settings\Settings\Current
HCUBPTOC1 3dI>C(1) SET LD0.HCUB2PTOC1.TmMult.setMag.f ASG FLOAT32 SG B 1.00 IEC/ANSI 0.05...15.00
-2(1) multiplier protection\HCUBPTOC1
IDMT
curves
Minimum
51NC Minimum operate time Settings\Settings\Current
HCUBPTOC1 3dI>C(1) SET LD0.HCUB2PTOC1.MinOpTmms.setVal ING INT32 SP A 20 20...60000 ms
-2(1) operate time for IDMT protection\HCUBPTOC1
curves
51NC Operate delay Operate Settings\Settings\Current
HCUBPTOC1 3dI>C(1) SET LD0.HCUB2PTOC1.OpDlTmms.setVal ING INT32 SG B 5000 40...200000 ms
-2(1) time delay time protection\HCUBPTOC1
51NC Reset delay Reset delay Settings\Settings\Current
HCUBPTOC1 3dI>C(1) SET LD0.HCUB2PTOC1.RsDlTmms.setVal ING INT32 SP A 20 0...60000 ms
-2(1) time time protection\HCUBPTOC1
0=Reset;
1=Activate
START;
2=Deactive
START;
9=Activate
51NC Test control Tests\Function tests\Current
HCUBPTOC1 3dI>C(1) TES LD0.HCUB1PTOC1.TestPro.Oper.ctlVal ENC Enum CO B 1 HCUBPTOC1 OPERATE;
-2(1) for outputs protection
10=Deactive
OPERATE;
17=Activate
ALARM;
18=Deactive
ALARM
51NC VisString25
HCUBPTOC1 3dI>C(1) VER LD0.HCUB1PTOC1.NamPlt.swRev LPL DC ED1 D (Name plate)
-2(1) 5 (20)

SRCPTOC1: Capacitor resonance protection: D


IEC Parameter Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
60617 name desc relation
(ACT input
SRCPTOC1 TD>(1) 55TD(1) INP Channel I3P
channel)
Block signal Monitoring\I/O status\Current
SRCPTOC1 TD>(1) 55TD(1) INP LD0.SRC1PTOC1.Blk.stVal SPS BOOLEAN ST B 0 I1 BLOCK
for activating protection\SRCPTOC1\Inputs
330
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

the blocking
mode
Input signal
from higher
Monitoring\I/O status\Current
SRCPTOC1 TD>(1) 55TD(1) INP LD0.SRC2PTOC1.InReso.stVal SPS BOOLEAN ST B 0 I1 RESO_IN frequency
protection\SRCPTOC1\Inputs
resonance
branch
Monitoring\I/O status\Current
SRCPTOC1 TD>(1) 55TD(1) OUT LD0.SRC1PTOC1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 ALARM Alarm
protection\SRCPTOC1\Outputs
Operate Monitoring\I/O status\Current
SRCPTOC1 TD>(1) 55TD(1) OUT LD0.SRC2PTOC1.Op.general ACT BOOLEAN ST B StatNrml P,H,T I1 OPERATE
signal protection\SRCPTOC1\Outputs
1=on; 2=blocked;
3=test; Monitoring\FB status\Current
SRCPTOC1 TD>(1) 55TD(1) MON LD0.SRC1PTOC1.Beh.stVal ENS Enum ST B SRCPTOC1 Status
4=test/blocked; protection
5=off
Resonance Monitoring\I/O status\Current
SRCPTOC1 TD>(1) 55TD(1) MON LD0.SRC1PTOC1.ResoA.phsA.cVal.mag.f WYE FLOAT32 MX B I1 I_RESO_A current for 0.00...40.00 xIn protection\SRCPTOC1\Monitored
phase A data
Resonance Monitoring\I/O status\Current
SRCPTOC1 TD>(1) 55TD(1) MON LD0.SRC1PTOC1.ResoA.phsB.cVal.mag.f WYE FLOAT32 MX B I1 I_RESO_B current for 0.00...40.00 xIn protection\SRCPTOC1\Monitored
phase B data
Resonance Monitoring\I/O status\Current
SRCPTOC1 TD>(1) 55TD(1) MON LD0.SRC1PTOC1.ResoA.phsC.cVal.mag.f WYE FLOAT32 MX B I1 I_RESO_C current for 0.00...40.00 xIn protection\SRCPTOC1\Monitored
phase C data
Operation Settings\Settings\Current
SRCPTOC1 TD>(1) 55TD(1) SET LD0.SRC1PTOC1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
Off / On protection\SRCPTOC1
Alarm limit
Alarm start for filtered Settings\Settings\Current
SRCPTOC1 TD>(1) 55TD(1) SET LD0.SRC1PTOC1.StrVal.setMag.f ASG FLOAT32 SG B 0.03 0.03...0.50 xIn IL1TCTR1
value harmonic protection\SRCPTOC1
currents
Alarm delay
Alarm delay time for Settings\Settings\Current
SRCPTOC1 TD>(1) 55TD(1) SET LD0.SRC1PTOC1.OpDlTmms.setVal ING INT32 SG B 200 120...360000 ms
time resonance protection\SRCPTOC1
alarm
Tuning
frequency
Tuning
harmonic Settings\Settings\Current
SRCPTOC1 TD>(1) 55TD(1) SET LD0.SRC1PTOC1.TunHNum.setVal ING INT32 SG B 11 harmonic 1...11
number of protection\SRCPTOC1
Num
the filter
branch
Tripping
limit for
filtered
harmonic Settings\Settings\Current
SRCPTOC1 TD>(1) 55TD(1) SET LD0.SRC2PTOC1.StrVal.setMag.f ASG FLOAT32 SG B 0.03 Start value 0.03...0.50 xIn IL1TCTR1
currents protection\SRCPTOC1
indicating
resonance
condition

331
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Operate
Operate Settings\Settings\Current
SRCPTOC1 TD>(1) 55TD(1) SET LD0.SRC2PTOC1.OpDlTmms.setVal ING INT32 SG B 200 delay time 120...360000 ms
delay time protection\SRCPTOC1
for resonance
0=Reset;
9=Activate
OPERATE;
10=Deactive
Test control Tests\Function tests\Current
SRCPTOC1 TD>(1) 55TD(1) TES LD0.SRC1PTOC1.TestPro.Oper.ctlVal ENC Enum CO B 1 SRCPTOC1 OPERATE;
for outputs protection
17=Activate
ALARM;
18=Deactive
ALARM
VisString255
SRCPTOC1 TD>(1) 55TD(1) VER LD0.SRC1PTOC1.NamPlt.swRev LPL DC ED1 D (Name plate)
(20)

Ethernet channel(s): A1
IEC Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter name Parameter desc Menu path
60617 range relation
Process bus
Ethernet
OUT LD0.SCHLCCH1.ChLiv.stVal SPS BOOLEAN ST A StatIed P,H I1 CHLIV Ethernet channel Monitoring\Communication\Ethernet\Activity
channel(s)
live
Process bus
Ethernet Monitoring\Communication\Ethernet\Link
OUT LD0.SCHLCCH1.LnkLiv.stVal SPS BOOLEAN ST A I1 LNKLIV Ethernet port link
channel(s) statuses
status
Process bus
Ethernet
MON LD0.SCHLCCH1.ChLivP.stVal SPS BOOLEAN ST A I1 CHLIVP redundant Ethernet Monitoring\Communication\Ethernet\Activity
channel(s)
channel live
Ethernet Main Ethernet
MON LD0.SCHLCCH1.ChLivM.stVal SPS BOOLEAN ST A I1 CHLIVM Monitoring\Communication\Ethernet\Activity
channel(s) channel live
Local mode
Ethernet
MON LD0.SCHLCCH1.ChLivL.stVal SPS BOOLEAN ST A I1 CHLIVL Ethernet channel Monitoring\Communication\Ethernet\Activity
channel(s)
live
Remote mode
Ethernet
MON LD0.SCHLCCH1.ChLivR.stVal SPS BOOLEAN ST A I1 CHLIVR Ethernet channel Monitoring\Communication\Ethernet\Activity
channel(s)
live
Process bus
Ethernet Monitoring\Communication\Ethernet\Link
MON LD0.SCHLCCH1.LnkLivP.stVal SPS BOOLEAN ST A I1 LNKLIVP redundant Ethernet
channel(s) statuses
port link status
Ethernet Main Ethernet port Monitoring\Communication\Ethernet\Link
MON LD0.SCHLCCH1.LnkLivM.stVal SPS BOOLEAN ST A I1 LNKLIVM
channel(s) link status statuses
Local mode
Ethernet Monitoring\Communication\Ethernet\Link
MON LD0.SCHLCCH1.LnkLivL.stVal SPS BOOLEAN ST A I1 LNKLIVL Ethernet port link
channel(s) statuses
status
Remote mode
Ethernet Monitoring\Communication\Ethernet\Link
MON LD0.SCHLCCH1.LnkLivR.stVal SPS BOOLEAN ST A I1 LNKLIVR Ethernet port link
channel(s) statuses
status

332
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Ethernet Process bus 0=Off; Configuration\Communication\Ethernet\Rear


CFG LD0.SCHLCCH1.PortMod.setVal ENG Enum SP B 0 Ethernet port mode
channel(s) interface mode 1=On port(s)
Process bus
Ethernet 0=Off; Configuration\Communication\Ethernet\Rear
CFG LD0.SCHLCCH1.PortModP.setVal ENG Enum SP B 0 redundant Ethernet port mode
channel(s) 1=On port(s)
interface mode
Ethernet Main interface 0=Off; Configuration\Communication\Ethernet\Rear
CFG LD0.SCHLCCH1.PortModM.setVal ENG Enum SP B 1 Ethernet port mode
channel(s) mode 1=On port(s)
Ethernet VisString255
VER LD0.SCHLCCH1.NamPlt.swRev LPL DC ED1 A1 (SCHLCCH1)
channel(s) (20)

Redundant Ethernet: A1
IEC Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter name Parameter desc Menu path
60617 range relation
Redundant Ethernet
OUT LD0.RCHLCCH1.ChLiv.stVal SPS BOOLEAN ST A StatIed P,H I1 CHLIV_A Monitoring\Communication\Ethernet\Activity
Ethernet channel A live
Ethernet
Redundant
OUT LD0.RCHLCCH1.RedChLiv.stVal SPS BOOLEAN ST A StatIed P,H I1 REDCHLIV_B redundant Monitoring\Communication\Ethernet\Activity
Ethernet
channel B live
Redundant Port A link
OUT LD0.RCHLCCH1.LnkLiv.stVal SPS BOOLEAN ST A I1 LNKLIV_A Monitoring\Communication\Ethernet\Link statuses
Ethernet status
Redundant Port B link
OUT LD0.RCHLCCH1.RedLnkLiv.stVal SPS BOOLEAN ST A I1 REDLNKLIV_B Monitoring\Communication\Ethernet\Link statuses
Ethernet status
Ethernet
Redundant 1=None;
CFG LD0.RCHLCCH1.RedCfg.setVal ENG Enum SP B,C 1 Redundant mode redundant Configuration\Communication\Ethernet\Redundancy
Ethernet 2=PRP
mode
Ethernet
Redundant 2=Separated;
CFG LD0.RCHLCCH1.BusCfg.setVal ENG Enum SP B,C 2 Bus mode redundant bus Configuration\Communication\Ethernet\Redundancy
Ethernet 3=Combined
mode
Redundant VisString255
VER LD0.RCHLCCH1.NamPlt.swRev LPL DC ED1 A1 (RCHLCCH1)
Ethernet (20)

CMSUM1: C1
IEC IEC Parameter Channel
ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter name Parameter desc Menu path
61850 60617 range relation
(ACT input
CMSUM1 CSUM(1) CSUM(1) INP Channel I3P1
channel)
(ACT input
CMSUM1 CSUM(1) CSUM(1) INP Channel I3P2
channel)
(ACT output
CMSUM1 CSUM(1) CSUM(1) OUT Channel I3P
channel)
(ACT output
CMSUM1 CSUM(1) CSUM(1) OUT Channel IRES
channel)
(ACT output
CMSUM1 CSUM(1) CSUM(1) OUT Channel IRES_CALC
channel)
333
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

CMSUM1 CSUM(1) CSUM(1) OUT LD0.SIL1TCTR1.Alm.stVal SPS BOOLEAN ST B StatIed P,H I1 ALARM ALARM Monitoring\Logic\CMSUM1
CMSUM1 CSUM(1) CSUM(1) OUT LD0.SIL1TCTR1.Wrn.stVal SPS BOOLEAN ST B StatIed P,H I1 WARNING WARNING Monitoring\Logic\CMSUM1
Primary phase Primary phase
CMSUM1 CSUM(1) CSUM(1) CFG LD0.SIL1TCTR1.ARtg.setMag.f ASG FLOAT32 SP B,I 100.0 1.0...6000.0 A Configuration\Logic\CMSUM1
current current
Primary residual Primary residual
CMSUM1 CSUM(1) CSUM(1) CFG LD0.SRESTCTR1.ARtg.setMag.f ASG FLOAT32 SP B,I 100.0 1.0...6000.0 A Configuration\Logic\CMSUM1
current current
VisString255
CMSUM1 CSUM(1) CSUM(1) VER LD0.SIL1TCTR1.NamPlt.swRev LPL DC ED1 C1 (Name plate)
(20)

CMSWI1: B1
IEC IEC Channel
ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter name Parameter desc Parameter range Menu path
61850 60617 relation
(ACT input
CMSWI1 CSWI(1) CSWI(1) INP Channel I3P1
channel)
(ACT input
CMSWI1 CSWI(1) CSWI(1) INP Channel I3P2
channel)
(ACT input
CMSWI1 CSWI(1) CSWI(1) INP Channel I3P3
channel)
(ACT input
CMSWI1 CSWI(1) CSWI(1) INP Channel I3P4
channel)
(ACT input
CMSWI1 CSWI(1) CSWI(1) INP Channel IRES1
channel)
(ACT input
CMSWI1 CSWI(1) CSWI(1) INP Channel IRES2
channel)
(ACT input
CMSWI1 CSWI(1) CSWI(1) INP Channel IRES3
channel)
(ACT input
CMSWI1 CSWI(1) CSWI(1) INP Channel IRES4
channel)
Switch to source Monitoring\I/O status\Generic
CMSWI1 CSWI(1) CSWI(1) INP LD0.CMSWI1.InSrcSwSt1.stVal SPS BOOLEAN ST B 0 I1 SWITCH_TO2
2 logic\CMSWI1\Inputs
Switch to source Monitoring\I/O status\Generic
CMSWI1 CSWI(1) CSWI(1) INP LD0.CMSWI1.InSrcSwSt2.stVal SPS BOOLEAN ST B 0 I1 SWITCH_TO3
3 logic\CMSWI1\Inputs
Switch to source Monitoring\I/O status\Generic
CMSWI1 CSWI(1) CSWI(1) INP LD0.CMSWI1.InSrcSwSt3.stVal SPS BOOLEAN ST B 0 I1 SWITCH_TO4
4 logic\CMSWI1\Inputs
(ACT output
CMSWI1 CSWI(1) CSWI(1) OUT Channel I3P
channel)
(ACT output
CMSWI1 CSWI(1) CSWI(1) OUT Channel IRES
channel)
Selected current
Monitoring\I/O status\Generic
CMSWI1 CSWI(1) CSWI(1) OUT LD0.CMSWI1.SelStSrc1.stVal SPS BOOLEAN ST B I1 SOURCE1 source is source
logic\CMSWI1\Outputs
1
Selected current
Monitoring\I/O status\Generic
CMSWI1 CSWI(1) CSWI(1) OUT LD0.CMSWI1.SelStSrc2.stVal SPS BOOLEAN ST B I1 SOURCE2 source is source
logic\CMSWI1\Outputs
2

334
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Selected current
Monitoring\I/O status\Generic
CMSWI1 CSWI(1) CSWI(1) OUT LD0.CMSWI1.SelStSrc3.stVal SPS BOOLEAN ST B I1 SOURCE3 source is source
logic\CMSWI1\Outputs
3
Selected current
Monitoring\I/O status\Generic
CMSWI1 CSWI(1) CSWI(1) OUT LD0.CMSWI1.SelStSrc4.stVal SPS BOOLEAN ST B I1 SOURCE4 source is source
logic\CMSWI1\Outputs
4
Monitoring\I/O status\Generic
CMSWI1 CSWI(1) CSWI(1) OUT LD0.CMSWI1.Alm.stVal SPS BOOLEAN ST B StatIed P,H I1 ALARM Alarm
logic\CMSWI1\Outputs
Monitoring\I/O status\Generic
CMSWI1 CSWI(1) CSWI(1) OUT LD0.CMSWI1.Wrn.stVal SPS BOOLEAN ST B StatIed P,H I1 WARNING Warning
logic\CMSWI1\Outputs
Monitoring\I/O status\Generic
CMSWI1 CSWI(1) CSWI(1) OUT LD0.CMSWI1.AlmRes.stVal SPS BOOLEAN ST B StatIed P,H I1 IRES_ALARM Alarm
logic\CMSWI1\Outputs
Monitoring\I/O status\Generic
CMSWI1 CSWI(1) CSWI(1) OUT LD0.CMSWI1.WrnRes.stVal SPS BOOLEAN ST B StatIed P,H I1 IRES_WARNING Warning
logic\CMSWI1\Outputs
1=Source 1;
2=Source 2; Monitoring\I/O status\Generic
CMSWI1 CSWI(1) CSWI(1) MON LD0.CMSWI1.SrcUsed.stVal ENS Enum ST B StatUrg P,H I1 SWITCH_POS Switch position
3=Source 3; logic\CMSWI1\Monitored data
4=Source 4
VisString255
CMSWI1 CSWI(1) CSWI(1) VER LD0.CMSWI1.NamPlt.swRev LPL DC B1 (Name plate)
(20)

VMSWI1: C1
IEC IEC Channel
ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter name Parameter desc Parameter range Menu path
61850 60617 relation
(ACT input
VMSWI1 VSWI(1) VSWI(1) INP Channel U3P1
channel)
(ACT input
VMSWI1 VSWI(1) VSWI(1) INP Channel U3P2
channel)
(ACT input
VMSWI1 VSWI(1) VSWI(1) INP Channel U3P3
channel)
(ACT input
VMSWI1 VSWI(1) VSWI(1) INP Channel U3P4
channel)
(ACT input
VMSWI1 VSWI(1) VSWI(1) INP Channel URES1
channel)
(ACT input
VMSWI1 VSWI(1) VSWI(1) INP Channel URES2
channel)
(ACT input
VMSWI1 VSWI(1) VSWI(1) INP Channel URES3
channel)
(ACT input
VMSWI1 VSWI(1) VSWI(1) INP Channel URES4
channel)
Switch to source Monitoring\I/O status\Generic
VMSWI1 VSWI(1) VSWI(1) INP LD0.VMSWI1.InSrcSwSt1.stVal SPS BOOLEAN ST B 0 I1 SWITCH_TO2
2 logic\VMSWI1\Inputs
Switch to source Monitoring\I/O status\Generic
VMSWI1 VSWI(1) VSWI(1) INP LD0.VMSWI1.InSrcSwSt2.stVal SPS BOOLEAN ST B 0 I1 SWITCH_TO3
3 logic\VMSWI1\Inputs

335
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Switch to source Monitoring\I/O status\Generic


VMSWI1 VSWI(1) VSWI(1) INP LD0.VMSWI1.InSrcSwSt3.stVal SPS BOOLEAN ST B 0 I1 SWITCH_TO4
4 logic\VMSWI1\Inputs
(ACT output
VMSWI1 VSWI(1) VSWI(1) OUT Channel U3P
channel)
(ACT output
VMSWI1 VSWI(1) VSWI(1) OUT Channel URES
channel)
Selected voltage
Monitoring\I/O status\Generic
VMSWI1 VSWI(1) VSWI(1) OUT LD0.VMSWI1.SelStSrc1.stVal SPS BOOLEAN ST B I1 SOURCE1 source is source
logic\VMSWI1\Outputs
1
Selected voltage
Monitoring\I/O status\Generic
VMSWI1 VSWI(1) VSWI(1) OUT LD0.VMSWI1.SelStSrc2.stVal SPS BOOLEAN ST B I1 SOURCE2 source is source
logic\VMSWI1\Outputs
2
Selected voltage
Monitoring\I/O status\Generic
VMSWI1 VSWI(1) VSWI(1) OUT LD0.VMSWI1.SelStSrc3.stVal SPS BOOLEAN ST B I1 SOURCE3 source is source
logic\VMSWI1\Outputs
3
Selected voltage
Monitoring\I/O status\Generic
VMSWI1 VSWI(1) VSWI(1) OUT LD0.VMSWI1.SelStSrc4.stVal SPS BOOLEAN ST B I1 SOURCE4 source is source
logic\VMSWI1\Outputs
4
Monitoring\I/O status\Generic
VMSWI1 VSWI(1) VSWI(1) OUT LD0.VMSWI1.Alm.stVal SPS BOOLEAN ST B StatIed P,H I1 ALARM Alarm
logic\VMSWI1\Outputs
Monitoring\I/O status\Generic
VMSWI1 VSWI(1) VSWI(1) OUT LD0.VMSWI1.Wrn.stVal SPS BOOLEAN ST B StatIed P,H I1 WARNING Warning
logic\VMSWI1\Outputs
Monitoring\I/O status\Generic
VMSWI1 VSWI(1) VSWI(1) OUT LD0.VMSWI1.AlmRes.stVal SPS BOOLEAN ST B StatIed P,H I1 URES_ALARM Alarm
logic\VMSWI1\Outputs
Monitoring\I/O status\Generic
VMSWI1 VSWI(1) VSWI(1) OUT LD0.VMSWI1.WrnRes.stVal SPS BOOLEAN ST B StatIed P,H I1 URES_WARNING Warning
logic\VMSWI1\Outputs
1=Source 1;
2=Source 2; Monitoring\I/O status\Generic
VMSWI1 VSWI(1) VSWI(1) MON LD0.VMSWI1.SrcUsed.stVal ENS Enum ST B StatUrg P,H I1 SWITCH_POS Switch position
3=Source 3; logic\VMSWI1\Monitored data
4=Source 4
VisString255
VMSWI1 VSWI(1) VSWI(1) VER LD0.VMSWI1.NamPlt.swRev LPL DC C1 (Name plate)
(20)

Control LLN0: Control general: D1


IEC 61850-7-4:2007
IEC IEC Parameter Parameter Channel
ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter range Menu path
61850 60617 name desc relation
Control (Control
INP CTRL.LLN0.LocKeyOff.stVal SPS BOOLEAN ST 0 I1
LLN0 disable)
Control (Control
INP CTRL.LLN0.LocKeyLoc.stVal SPS BOOLEAN ST 0 I1
LLN0 local)
Control (Control
INP CTRL.LLN0.LocKeyRem.stVal SPS BOOLEAN ST 0 I1
LLN0 remote)
Control (Control
INP CTRL.LLN0.LocKeySta.stVal SPS BOOLEAN ST 0 I1
LLN0 station)

336
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Control
INP CTRL.LLN0.LocKeyAll.stVal SPS BOOLEAN ST 0 I1 (Control all)
LLN0
Control (Control
OUT CTRL.LLN0.LocKeyOff.stVal SPS BOOLEAN ST 0 I1
LLN0 disable)
Control (Control
OUT CTRL.LLN0.LocKeyLoc.stVal SPS BOOLEAN ST 0 I1
LLN0 local)
Control (Control
OUT CTRL.LLN0.LocKeyRem.stVal SPS BOOLEAN ST 0 I1
LLN0 remote)
Control (Control
OUT CTRL.LLN0.LocKeySta.stVal SPS BOOLEAN ST 0 I1
LLN0 station)
Control
OUT CTRL.LLN0.LocKeyAll.stVal SPS BOOLEAN ST 0 I1 (Control all)
LLN0
Control (Station
CTR CTRL.LLN0.LocSta.Oper.ctlVal SPC BOOLEAN CO I1
LLN0 operation)
Control (Local /
MON CTRL.LLN0.Loc.stVal SPS BOOLEAN ST OW,ER,AW StatUrg P,H I1
LLN0 Remote)
Control (Local
MON CTRL.LLN0.LocKey.stVal SPS BOOLEAN ST StatUrg P,H I1
LLN0 operation)
Control (Station
MON CTRL.LLN0.LocSta.Oper.ctlVal SPC BOOLEAN CO I1
LLN0 operation)
0=not-supported1=bay-
control2=station-control3=remote-
Control (Station control4=automatic-
MON CTRL.LLN0.LocSta.Oper.origin.orCat SPC Enum CO
LLN0 operation) bay5=automatic-
station6=automatic-
remote7=maintenance8=process
Control (Station
MON CTRL.LLN0.LocSta.Oper.origin.orIdent SPC Octet64 CO
LLN0 operation)
Control (Station
MON CTRL.LLN0.LocSta.Oper.ctlNum SPC INT8U CO
LLN0 operation)
Control (Station
MON CTRL.LLN0.LocSta.Oper.Test SPC BOOLEAN CO
LLN0 operation)
Control (Station
MON CTRL.LLN0.LocSta.Oper.Check SPC Bstring2 CO
LLN0 operation)
Control (Station
MON CTRL.LLN0.LocSta.stVal SPC BOOLEAN ST StatUrg P,H I1
LLN0 operation)
Control (Station 0=status-only1=direct-with-normal-
MON CTRL.LLN0.LocSta.ctlModel SPC Enum CF
LLN0 operation) security
Control (Multiple
MON CTRL.LLN0.MltLev.setVal SPG BOOLEAN SP
LLN0 levels)
Control (Commands
MON CTRL.LLN0.CmdBlk.stVal SPC BOOLEAN ST StatUrg P,H I1
LLN0 blocked)
Control (Commands
MON CTRL.LLN0.CmdBlk.ctlModel SPC Enum CF 0=status-only
LLN0 blocked)
Latest 0=No commands; 1=Select open;
Control Command
MON Enum B command 2=Select close; 3=Operate open; Monitoring\Control command
LLN0 response
response 4=Operate close; 5=Direct open;
337
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

6=Direct close; 7=Cancel;


8=Position reached; 9=Position
timeout; 10=Object status only;
11=Object direct; 12=Object select;
13=RL local allowed; 14=RL
remote allowed; 15=RL off;
16=Function off; 17=Function
blocked; 18=Command progress;
19=Select timeout; 20=Missing
authority; 21=Close not enabled;
22=Open not enabled; 23=Internal
fault; 24=Already close; 25=Wrong
client; 26=RL station allowed;
27=RL change; 28=Abortion by trip
0=Off; 1=Local; 2=Remote;
Control LR state
MON CTRL.LLN0.LocKeyHMI.stVal ENS Enum ST B,OW,ER,AW StatUrg P,H I1 LR state 3=Station; 4=L+R; 5=L+S; Monitoring\Control command
LLN0 monitoring
6=L+S+R; 7=S+R
Enabling
Control Control and
CFG CTRL.LLN0.Mod.Oper.ctlVal ENC Enum CO A,I 1 1=On; 2=Blocked; 5=Off Configuration\Control\General
LLN0 mode disabling
control
LR control
Control LR through LR
CFG CTRL.LLN0.LocRemMod.setVal ENG Enum SP B 2 2=Binary input Configuration\Control\General
LLN0 control key or
binary input
Control
command
Control Station 1=L,R; 2=L,S,R; 3=L,R,L+R;
CFG CTRL.LLN0.StaLevSet.setVal ENG Enum SP B 1 originator Configuration\Control\General
LLN0 authority 4=L,S,S+R,L+S,L+S+R
category
usage
Control VisString255
VER CTRL.LLN0.NamPlt.swRev LPL DC D1 (Control)
LLN0 (20)
IEC
Control VisString255 61850-
VER CTRL.LLN0.NamPlt.ldNs LPL EX (Control)
LLN0 (20) 7-
4:2003

CBXCBR1: D1
IEC Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter name Parameter desc Parameter range Menu path
60617 relation
I<->O I<->O Enables Monitoring\I/O
CBXCBR1 INP CTRL.CBCILO1.EnaOpn.stVal SPS BOOLEAN ST B 1 StatUrg P,H I1 ENA_OPEN
CB(1) CB(1) opening status\Control\CBXCBR1\Inputs
I<->O I<->O Monitoring\I/O
CBXCBR1 INP CTRL.CBCILO1.EnaCls.stVal SPS BOOLEAN ST B 1 StatUrg P,H I1 ENA_CLOSE Enables closing
CB(1) CB(1) status\Control\CBXCBR1\Inputs
I<->O I<->O Synchronism- Monitoring\I/O
CBXCBR1 INP CTRL.CBCSWI1.InSynOk.stVal SPS BOOLEAN ST B 1 I1 SYNC_OK
CB(1) CB(1) check OK status\Control\CBXCBR1\Inputs
I<->O I<->O Discards Monitoring\I/O
CBXCBR1 INP CTRL.CBCSWI1.SynItlByps.stVal SPS BOOLEAN ST B 0 StatUrg P,H I1 SYNC_ITL_BYP
CB(1) CB(1) ENA_OPEN status\Control\CBXCBR1\Inputs
338
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

and
ENA_CLOSE
interlocking
when TRUE
I<->O I<->O Monitoring\I/O
CBXCBR1 INP CTRL.CBXCBR1.BlkOpn.stVal SPC BOOLEAN ST B 0 StatUrg P,H I1 BLK_OPEN Blocks opening
CB(1) CB(1) status\Control\CBXCBR1\Inputs
I<->O I<->O Monitoring\I/O
CBXCBR1 INP CTRL.CBXCBR1.BlkCls.stVal SPC BOOLEAN ST B 0 StatUrg P,H I1 BLK_CLOSE Blocks closing
CB(1) CB(1) status\Control\CBXCBR1\Inputs
I<->O I<->O Monitoring\I/O
CBXCBR1 INP BOOLEAN B 0 TRIP Trip signal
CB(1) CB(1) status\Control\CBXCBR1\Inputs
I<->O I<->O Monitoring\I/O
CBXCBR1 INP BOOLEAN B 0 AU_OPEN Auxiliary open
CB(1) CB(1) status\Control\CBXCBR1\Inputs
I<->O I<->O Monitoring\I/O
CBXCBR1 INP BOOLEAN B 0 AU_CLOSE Auxiliary close
CB(1) CB(1) status\Control\CBXCBR1\Inputs
Signal for open
I<->O I<->O position of Monitoring\I/O
CBXCBR1 INP BOOLEAN B 0 POSOPEN
CB(1) CB(1) apparatus from status\Control\CBXCBR1\Inputs
I/O
Signal for close
I<->O I<->O position of Monitoring\I/O
CBXCBR1 INP BOOLEAN B 0 POSCLOSE
CB(1) CB(1) apparatus from status\Control\CBXCBR1\Inputs
I/O
I<->O I<->O Monitoring\I/O
CBXCBR1 OUT CTRL.CBCSWI1.Pos.stSeld DPC BOOLEAN ST B StatUrg P,H I1 SELECTED Object selected
CB(1) CB(1) status\Control\CBXCBR1\Outputs
Executes the
I<->O I<->O Monitoring\I/O
CBXCBR1 OUT CTRL.CBCSWI1.OpOpn.general ACT BOOLEAN ST B EXE_OP command for
CB(1) CB(1) status\Control\CBXCBR1\Outputs
open direction
Executes the
I<->O I<->O Monitoring\I/O
CBXCBR1 OUT CTRL.CBCSWI1.OpCls.general ACT BOOLEAN ST B EXE_CL command for
CB(1) CB(1) status\Control\CBXCBR1\Outputs
close direction
Signal for open
I<->O I<->O position of Monitoring\I/O
CBXCBR1 OUT CTRL.CBCSWI1.PosOpn.stVal SPS BOOLEAN ST B I1 OPENPOS
CB(1) CB(1) apparatus from status\Control\CBXCBR1\Outputs
I/O
Signal for close
I<->O I<->O position of Monitoring\I/O
CBXCBR1 OUT CTRL.CBCSWI1.PosCls.stVal SPS BOOLEAN ST B I1 CLOSEPOS
CB(1) CB(1) apparatus from status\Control\CBXCBR1\Outputs
I/O
I<->O I<->O Apparatus Monitoring\I/O
CBXCBR1 OUT CTRL.CBCSWI1.PosOk.stVal SPS BOOLEAN ST B I1 OKPOS
CB(1) CB(1) position is ok status\Control\CBXCBR1\Outputs
Opening is
I<->O I<->O enabled based Monitoring\I/O
CBXCBR1 OUT CTRL.CBCSWI1.OpnEna.stVal SPS BOOLEAN ST B I1 OPEN_ENAD
CB(1) CB(1) on the input status\Control\CBXCBR1\Outputs
status
Closing is
I<->O I<->O enabled based Monitoring\I/O
CBXCBR1 OUT CTRL.CBCSWI1.ClsEna.stVal SPS BOOLEAN ST B I1 CLOSE_ENAD
CB(1) CB(1) on the input status\Control\CBXCBR1\Outputs
status

339
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

I<->O I<->O Monitoring\I/O


CBXCBR1 OUT BOOLEAN B OP_REQ Open request
CB(1) CB(1) status\Control\CBXCBR1\Outputs
I<->O I<->O Monitoring\I/O
CBXCBR1 OUT BOOLEAN B CL_REQ Close request
CB(1) CB(1) status\Control\CBXCBR1\Outputs
Breaker
I<->O I<->O Operation
CBXCBR1 CTR CTRL.CBCSWI1.OpCntRs.Oper.ctlVal INC INT32 CO A 0 I1 operation 0...10000 Configuration\Control\CBXCBR1
CB(1) CB(1) counter
cycles
I<->O I<->O (Switch,
CBXCBR1 CTR CTRL.CBCSWI1.Pos.SBOw.ctlVal DPC BOOLEAN CO
CB(1) CB(1) general)
I<->O I<->O (Switch,
CBXCBR1 CTR CTRL.CBCSWI1.Pos.Oper.ctlVal DPC BOOLEAN CO I1
CB(1) CB(1) general)
I<->O I<->O (Switch,
CBXCBR1 CTR CTRL.CBCSWI1.Pos.Cancel.ctlVal DPC BOOLEAN CO
CB(1) CB(1) general)
I<->O I<->O (Local
CBXCBR1 MON CTRL.CBCSWI1.Loc.stVal SPS BOOLEAN ST StatUrg P,H I1
CB(1) CB(1) operation)
0=intermediate;
Apparatus Monitoring\I/O
I<->O I<->O 1=open;
CBXCBR1 MON CTRL.CBCSWI1.Pos.stVal DPC Dbpos ST B StatUrg P,H I1 POSITION position status\Control\CBXCBR1\Monitored
CB(1) CB(1) 2=closed;
indication data
3=faulty
I<->O I<->O Operation
CBXCBR1 CFG CTRL.CBCSWI1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off Configuration\Control\CBXCBR1
CB(1) CB(1) mode on/off
Breaker
I<->O I<->O Operation
CBXCBR1 CFG CTRL.CBCSWI1.OpCntRs.Oper.ctlVal INC INT32 CO A 0 I1 operation 0...10000 Configuration\Control\CBXCBR1
CB(1) CB(1) counter
cycles
I<->O I<->O Open and close
CBXCBR1 CFG CTRL.CBCSWI1.Pos.pulseConfig.onDur DPC INT32U CF B,I 200 Pulse length 10...60000 ms Configuration\Control\CBXCBR1
CB(1) CB(1) pulse length
0=status-only;
1=direct-with-
I<->O I<->O Select control normal-security;
CBXCBR1 CFG CTRL.CBCSWI1.Pos.ctlModel DPC Enum CF B,I 4 Control model Configuration\Control\CBXCBR1
CB(1) CB(1) model 4=sbo-with-
enhanced-
security
I<->O I<->O Select timeout 10000...300000
CBXCBR1 CFG CTRL.CBCSWI1.Pos.sboTimeout DPC INT32U CF B,I 30000 Select timeout Configuration\Control\CBXCBR1
CB(1) CB(1) in ms ms
Timeout for
I<->O I<->O Operation
CBXCBR1 CFG CTRL.CBCSWI1.Pos.operTimeout DPC INT32U CF B,I 500 negative 10...60000 ms Configuration\Control\CBXCBR1
CB(1) CB(1) timeout
termination
CBXCBR1
I<->O I<->O Control Object
CBXCBR1 CFG CTRL.CBCSWI1.Pos.dU DPC Unicode255 DC ED2,B switch Identification Configuration\Control\CBXCBR1
CB(1) CB(1) identification
position
CBXCBR1
I<->O I<->O VisString255 Control Object
CBXCBR1 CFG CTRL.CBCSWI1.Pos.d DPC DC switch Identification Configuration\Control\CBXCBR1
CB(1) CB(1) (64) identification
position
Event delay of
I<->O I<->O the
CBXCBR1 CFG CTRL.CBCSWI1.PosDlTmms.setVal ING INT32 SP A 200 Event delay 0...10000 ms Configuration\Control\CBXCBR1
CB(1) CB(1) intermediate
position

340
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

I<->O I<->O Stop in right


CBXCBR1 CFG CTRL.CBCSWI1.AdpPls.setVal SPG BOOLEAN SP A 1 Adaptive pulse Configuration\Control\CBXCBR1
CB(1) CB(1) position
External
I<->O I<->O VisString255
CBXCBR1 CFG CTRL.CBXCBR1.EEName.vendor DPL DC A 0 Vendor equipment Configuration\Control\CBXCBR1
CB(1) CB(1) (20)
vendor
External
I<->O I<->O VisString255
CBXCBR1 CFG CTRL.CBXCBR1.EEName.serNum DPL DC A 0 Serial number equipment Configuration\Control\CBXCBR1
CB(1) CB(1) (20)
serial number
External
I<->O I<->O VisString255
CBXCBR1 CFG CTRL.CBXCBR1.EEName.model DPL DC A 0 Model equipment Configuration\Control\CBXCBR1
CB(1) CB(1) (20)
model
I<->O I<->O VisString255
CBXCBR1 VER CTRL.CBCILO1.NamPlt.swRev LPL DC ED1 D1 (Name plate)
CB(1) CB(1) (20)

DCXSWI1: C1
IEC Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Parameter range Menu path
60617 name relation
I<->O I<->O Enables Monitoring\I/O
DCXSWI1 INP CTRL.DCCILO1.EnaOpn.stVal SPS BOOLEAN ST B 1 StatUrg P,H I1 ENA_OPEN
DCC(1) DCC(1) opening status\Control\DCXSWI1\Inputs
I<->O I<->O Enables Monitoring\I/O
DCXSWI1 INP CTRL.DCCILO1.EnaCls.stVal SPS BOOLEAN ST B 1 StatUrg P,H I1 ENA_CLOSE
DCC(1) DCC(1) closing status\Control\DCXSWI1\Inputs
Discards
ENA_OPEN
I<->O I<->O and Monitoring\I/O
DCXSWI1 INP CTRL.DCCILO1.ItlByps.stVal SPS BOOLEAN ST B 0 StatUrg P,H I1 ITL_BYPASS
DCC(1) DCC(1) ENA_CLOSE status\Control\DCXSWI1\Inputs
interlocking
when TRUE
I<->O I<->O Blocks Monitoring\I/O
DCXSWI1 INP CTRL.DCXSWI1.BlkOpn.stVal SPC BOOLEAN ST B 0 StatUrg P,H I1 BLK_OPEN
DCC(1) DCC(1) opening status\Control\DCXSWI1\Inputs
I<->O I<->O Monitoring\I/O
DCXSWI1 INP CTRL.DCXSWI1.BlkCls.stVal SPC BOOLEAN ST B 0 StatUrg P,H I1 BLK_CLOSE Blocks closing
DCC(1) DCC(1) status\Control\DCXSWI1\Inputs
Executes the
I<->O I<->O Monitoring\I/O
DCXSWI1 INP BOOLEAN B 0 AU_OPEN command for
DCC(1) DCC(1) status\Control\DCXSWI1\Inputs
open direction
Executes the
I<->O I<->O Monitoring\I/O
DCXSWI1 INP BOOLEAN B 0 AU_CLOSE command for
DCC(1) DCC(1) status\Control\DCXSWI1\Inputs
close direction
I<->O I<->O Apparatus Monitoring\I/O
DCXSWI1 INP BOOLEAN B 0 POSOPEN
DCC(1) DCC(1) open position status\Control\DCXSWI1\Inputs
I<->O I<->O Apparatus Monitoring\I/O
DCXSWI1 INP BOOLEAN B 0 POSCLOSE
DCC(1) DCC(1) close position status\Control\DCXSWI1\Inputs
I<->O I<->O Monitoring\I/O
DCXSWI1 OUT CTRL.DCCSWI1.Pos.stSeld DPC BOOLEAN ST B StatUrg P,H I1 SELECTED Object selected
DCC(1) DCC(1) status\Control\DCXSWI1\Outputs
Executes the
I<->O I<->O Monitoring\I/O
DCXSWI1 OUT CTRL.DCCSWI1.OpOpn.general ACT BOOLEAN ST B EXE_OP command for
DCC(1) DCC(1) status\Control\DCXSWI1\Outputs
open direction
341
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Executes the
I<->O I<->O Monitoring\I/O
DCXSWI1 OUT CTRL.DCCSWI1.OpCls.general ACT BOOLEAN ST B EXE_CL command for
DCC(1) DCC(1) status\Control\DCXSWI1\Outputs
close direction
I<->O I<->O Apparatus Monitoring\I/O
DCXSWI1 OUT CTRL.DCCSWI1.PosOpn.stVal SPS BOOLEAN ST B I1 OPENPOS
DCC(1) DCC(1) open position status\Control\DCXSWI1\Outputs
I<->O I<->O Apparatus Monitoring\I/O
DCXSWI1 OUT CTRL.DCCSWI1.PosCls.stVal SPS BOOLEAN ST B I1 CLOSEPOS
DCC(1) DCC(1) closed position status\Control\DCXSWI1\Outputs
I<->O I<->O Apparatus Monitoring\I/O
DCXSWI1 OUT CTRL.DCCSWI1.PosOk.stVal SPS BOOLEAN ST B I1 OKPOS
DCC(1) DCC(1) position is ok status\Control\DCXSWI1\Outputs
Opening is
I<->O I<->O enabled based Monitoring\I/O
DCXSWI1 OUT CTRL.DCCSWI1.OpnEna.stVal SPS BOOLEAN ST B I1 OPEN_ENAD
DCC(1) DCC(1) on the input status\Control\DCXSWI1\Outputs
status
Closing is
I<->O I<->O enabled based Monitoring\I/O
DCXSWI1 OUT CTRL.DCCSWI1.ClsEna.stVal SPS BOOLEAN ST B I1 CLOSE_ENAD
DCC(1) DCC(1) on the input status\Control\DCXSWI1\Outputs
status
Breaker
I<->O I<->O Operation
DCXSWI1 CTR CTRL.DCCSWI1.OpCntRs.Oper.ctlVal INC INT32 CO A 0 I1 operation 0...10000 Configuration\Control\DCXSWI1
DCC(1) DCC(1) counter
cycles
I<->O I<->O (Switch,
DCXSWI1 CTR CTRL.DCCSWI1.Pos.SBOw.ctlVal DPC BOOLEAN CO
DCC(1) DCC(1) general)
I<->O I<->O (Switch,
DCXSWI1 CTR CTRL.DCCSWI1.Pos.Oper.ctlVal DPC BOOLEAN CO I1
DCC(1) DCC(1) general)
I<->O I<->O (Switch,
DCXSWI1 CTR CTRL.DCCSWI1.Pos.Cancel.ctlVal DPC BOOLEAN CO
DCC(1) DCC(1) general)
I<->O I<->O (Local
DCXSWI1 MON CTRL.DCCSWI1.Loc.stVal SPS BOOLEAN ST StatUrg P,H I1
DCC(1) DCC(1) operation)
0=intermediate;
Apparatus Monitoring\I/O
I<->O I<->O 1=open;
DCXSWI1 MON CTRL.DCCSWI1.Pos.stVal DPC Dbpos ST B StatUrg P,H I1 POSITION position status\Control\DCXSWI1\Monitored
DCC(1) DCC(1) 2=closed;
indication data
3=faulty
I<->O I<->O Operation
DCXSWI1 CFG CTRL.DCCSWI1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off Configuration\Control\DCXSWI1
DCC(1) DCC(1) mode on/off
Breaker
I<->O I<->O Operation
DCXSWI1 CFG CTRL.DCCSWI1.OpCntRs.Oper.ctlVal INC INT32 CO A 0 I1 operation 0...10000 Configuration\Control\DCXSWI1
DCC(1) DCC(1) counter
cycles
I<->O I<->O Open and close
DCXSWI1 CFG CTRL.DCCSWI1.Pos.pulseConfig.onDur DPC INT32U CF B,I 100 Pulse length 10...60000 ms Configuration\Control\DCXSWI1
DCC(1) DCC(1) pulse length
0=status-only;
1=direct-with-
I<->O I<->O Select control normal-security;
DCXSWI1 CFG CTRL.DCCSWI1.Pos.ctlModel DPC Enum CF B,I 4 Control model Configuration\Control\DCXSWI1
DCC(1) DCC(1) model 4=sbo-with-
enhanced-
security
I<->O I<->O Select timeout 10000...300000
DCXSWI1 CFG CTRL.DCCSWI1.Pos.sboTimeout DPC INT32U CF B,I 30000 Select timeout Configuration\Control\DCXSWI1
DCC(1) DCC(1) in ms ms

342
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Timeout for
I<->O I<->O Operation
DCXSWI1 CFG CTRL.DCCSWI1.Pos.operTimeout DPC INT32U CF B,I 30000 negative 10...60000 ms Configuration\Control\DCXSWI1
DCC(1) DCC(1) timeout
termination
DCXSWI1
I<->O I<->O Control Object
DCXSWI1 CFG CTRL.DCCSWI1.Pos.dU DPC Unicode255 DC ED2,B switch Identification Configuration\Control\DCXSWI1
DCC(1) DCC(1) identification
position
DCXSWI1
I<->O I<->O VisString255 Control Object
DCXSWI1 CFG CTRL.DCCSWI1.Pos.d DPC DC switch Identification Configuration\Control\DCXSWI1
DCC(1) DCC(1) (64) identification
position
Event delay of
I<->O I<->O the
DCXSWI1 CFG CTRL.DCCSWI1.PosDlTmms.setVal ING INT32 SP A 10000 Event delay 0...60000 ms Configuration\Control\DCXSWI1
DCC(1) DCC(1) intermediate
position
I<->O I<->O Stop in right
DCXSWI1 CFG CTRL.DCCSWI1.AdpPls.setVal SPG BOOLEAN SP A 1 Adaptive pulse Configuration\Control\DCXSWI1
DCC(1) DCC(1) position
External
I<->O I<->O VisString255
DCXSWI1 CFG CTRL.DCXSWI1.EEName.vendor DPL DC A 0 Vendor equipment Configuration\Control\DCXSWI1
DCC(1) DCC(1) (20)
vendor
External
I<->O I<->O VisString255
DCXSWI1 CFG CTRL.DCXSWI1.EEName.serNum DPL DC A 0 Serial number equipment Configuration\Control\DCXSWI1
DCC(1) DCC(1) (20)
serial number
External
I<->O I<->O VisString255
DCXSWI1 CFG CTRL.DCXSWI1.EEName.model DPL DC A 0 Model equipment Configuration\Control\DCXSWI1
DCC(1) DCC(1) (20)
model
I<->O I<->O VisString255
DCXSWI1 VER CTRL.DCCILO1.NamPlt.swRev LPL DC ED1 C1 (Name plate)
DCC(1) DCC(1) (20)

ESXSWI1: C1
IEC IEC Channel
ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter name Parameter desc Parameter range Menu path
61850 60617 relation
I<->O I<->O Enables Monitoring\I/O
ESXSWI1 INP CTRL.ESCILO1.EnaOpn.stVal SPS BOOLEAN ST B 1 StatUrg P,H I1 ENA_OPEN
ESC(1) ESC(1) opening status\Control\ESXSWI1\Inputs
I<->O I<->O Monitoring\I/O
ESXSWI1 INP CTRL.ESCILO1.EnaCls.stVal SPS BOOLEAN ST B 1 StatUrg P,H I1 ENA_CLOSE Enables closing
ESC(1) ESC(1) status\Control\ESXSWI1\Inputs
Discards
ENA_OPEN
I<->O I<->O and Monitoring\I/O
ESXSWI1 INP CTRL.ESCILO1.ItlByps.stVal SPS BOOLEAN ST B 0 StatUrg P,H I1 ITL_BYPASS
ESC(1) ESC(1) ENA_CLOSE status\Control\ESXSWI1\Inputs
interlocking
when TRUE
I<->O I<->O Monitoring\I/O
ESXSWI1 INP CTRL.ESXSWI1.BlkOpn.stVal SPC BOOLEAN ST B 0 StatUrg P,H I1 BLK_OPEN Blocks opening
ESC(1) ESC(1) status\Control\ESXSWI1\Inputs
I<->O I<->O Monitoring\I/O
ESXSWI1 INP CTRL.ESXSWI1.BlkCls.stVal SPC BOOLEAN ST B 0 StatUrg P,H I1 BLK_CLOSE Blocks closing
ESC(1) ESC(1) status\Control\ESXSWI1\Inputs
Executes the
I<->O I<->O Monitoring\I/O
ESXSWI1 INP BOOLEAN B 0 AU_OPEN command for
ESC(1) ESC(1) status\Control\ESXSWI1\Inputs
open direction
343
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Executes the
I<->O I<->O Monitoring\I/O
ESXSWI1 INP BOOLEAN B 0 AU_CLOSE command for
ESC(1) ESC(1) status\Control\ESXSWI1\Inputs
close direction
I<->O I<->O Apparatus open Monitoring\I/O
ESXSWI1 INP BOOLEAN B 0 POSOPEN
ESC(1) ESC(1) position status\Control\ESXSWI1\Inputs
I<->O I<->O Apparatus close Monitoring\I/O
ESXSWI1 INP BOOLEAN B 0 POSCLOSE
ESC(1) ESC(1) position status\Control\ESXSWI1\Inputs
I<->O I<->O Monitoring\I/O
ESXSWI1 OUT CTRL.ESCSWI1.Pos.stSeld DPC BOOLEAN ST B StatUrg P,H I1 SELECTED Object selected
ESC(1) ESC(1) status\Control\ESXSWI1\Outputs
Executes the
I<->O I<->O Monitoring\I/O
ESXSWI1 OUT CTRL.ESCSWI1.OpOpn.general ACT BOOLEAN ST B EXE_OP command for
ESC(1) ESC(1) status\Control\ESXSWI1\Outputs
open direction
Executes the
I<->O I<->O Monitoring\I/O
ESXSWI1 OUT CTRL.ESCSWI1.OpCls.general ACT BOOLEAN ST B EXE_CL command for
ESC(1) ESC(1) status\Control\ESXSWI1\Outputs
close direction
I<->O I<->O Apparatus open Monitoring\I/O
ESXSWI1 OUT CTRL.ESCSWI1.PosOpn.stVal SPS BOOLEAN ST B I1 OPENPOS
ESC(1) ESC(1) position status\Control\ESXSWI1\Outputs
I<->O I<->O Apparatus Monitoring\I/O
ESXSWI1 OUT CTRL.ESCSWI1.PosCls.stVal SPS BOOLEAN ST B I1 CLOSEPOS
ESC(1) ESC(1) closed position status\Control\ESXSWI1\Outputs
I<->O I<->O Apparatus Monitoring\I/O
ESXSWI1 OUT CTRL.ESCSWI1.PosOk.stVal SPS BOOLEAN ST B I1 OKPOS
ESC(1) ESC(1) position is ok status\Control\ESXSWI1\Outputs
Opening is
I<->O I<->O enabled based Monitoring\I/O
ESXSWI1 OUT CTRL.ESCSWI1.OpnEna.stVal SPS BOOLEAN ST B I1 OPEN_ENAD
ESC(1) ESC(1) on the input status\Control\ESXSWI1\Outputs
status
Closing is
I<->O I<->O enabled based Monitoring\I/O
ESXSWI1 OUT CTRL.ESCSWI1.ClsEna.stVal SPS BOOLEAN ST B I1 CLOSE_ENAD
ESC(1) ESC(1) on the input status\Control\ESXSWI1\Outputs
status
I<->O I<->O Operation Breaker
ESXSWI1 CTR CTRL.ESCSWI1.OpCntRs.Oper.ctlVal INC INT32 CO A 0 I1 0...10000 Configuration\Control\ESXSWI1
ESC(1) ESC(1) counter operation cycles
I<->O I<->O (Switch,
ESXSWI1 CTR CTRL.ESCSWI1.Pos.SBOw.ctlVal DPC BOOLEAN CO
ESC(1) ESC(1) general)
I<->O I<->O (Switch,
ESXSWI1 CTR CTRL.ESCSWI1.Pos.Oper.ctlVal DPC BOOLEAN CO I1
ESC(1) ESC(1) general)
I<->O I<->O (Switch,
ESXSWI1 CTR CTRL.ESCSWI1.Pos.Cancel.ctlVal DPC BOOLEAN CO
ESC(1) ESC(1) general)
I<->O I<->O (Local
ESXSWI1 MON CTRL.ESCSWI1.Loc.stVal SPS BOOLEAN ST StatUrg P,H I1
ESC(1) ESC(1) operation)
0=intermediate;
Apparatus Monitoring\I/O
I<->O I<->O 1=open;
ESXSWI1 MON CTRL.ESCSWI1.Pos.stVal DPC Dbpos ST B StatUrg P,H I1 POSITION position status\Control\ESXSWI1\Monitored
ESC(1) ESC(1) 2=closed;
indication data
3=faulty
I<->O I<->O Operation mode
ESXSWI1 CFG CTRL.ESCSWI1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off Configuration\Control\ESXSWI1
ESC(1) ESC(1) on/off
I<->O I<->O Operation Breaker
ESXSWI1 CFG CTRL.ESCSWI1.OpCntRs.Oper.ctlVal INC INT32 CO A 0 I1 0...10000 Configuration\Control\ESXSWI1
ESC(1) ESC(1) counter operation cycles

344
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

I<->O I<->O Open and close


ESXSWI1 CFG CTRL.ESCSWI1.Pos.pulseConfig.onDur DPC INT32U CF B,I 100 Pulse length 10...60000 ms Configuration\Control\ESXSWI1
ESC(1) ESC(1) pulse length
0=status-only;
1=direct-with-
I<->O I<->O Select control
ESXSWI1 CFG CTRL.ESCSWI1.Pos.ctlModel DPC Enum CF B,I 4 Control model normal-security; Configuration\Control\ESXSWI1
ESC(1) ESC(1) model
4=sbo-with-
enhanced-security
I<->O I<->O Select timeout 10000...300000
ESXSWI1 CFG CTRL.ESCSWI1.Pos.sboTimeout DPC INT32U CF B,I 30000 Select timeout Configuration\Control\ESXSWI1
ESC(1) ESC(1) in ms ms
Timeout for
I<->O I<->O Operation
ESXSWI1 CFG CTRL.ESCSWI1.Pos.operTimeout DPC INT32U CF B,I 30000 negative 10...60000 ms Configuration\Control\ESXSWI1
ESC(1) ESC(1) timeout
termination
ESXSWI1
I<->O I<->O Control Object
ESXSWI1 CFG CTRL.ESCSWI1.Pos.dU DPC Unicode255 DC ED2,B switch Identification Configuration\Control\ESXSWI1
ESC(1) ESC(1) identification
position
ESXSWI1
I<->O I<->O VisString255 Control Object
ESXSWI1 CFG CTRL.ESCSWI1.Pos.d DPC DC switch Identification Configuration\Control\ESXSWI1
ESC(1) ESC(1) (64) identification
position
Event delay of
I<->O I<->O
ESXSWI1 CFG CTRL.ESCSWI1.PosDlTmms.setVal ING INT32 SP A 10000 Event delay the intermediate 0...60000 ms Configuration\Control\ESXSWI1
ESC(1) ESC(1)
position
I<->O I<->O Stop in right
ESXSWI1 CFG CTRL.ESCSWI1.AdpPls.setVal SPG BOOLEAN SP A 1 Adaptive pulse Configuration\Control\ESXSWI1
ESC(1) ESC(1) position
External
I<->O I<->O VisString255
ESXSWI1 CFG CTRL.ESXSWI1.EEName.vendor DPL DC A 0 Vendor equipment Configuration\Control\ESXSWI1
ESC(1) ESC(1) (20)
vendor
External
I<->O I<->O VisString255
ESXSWI1 CFG CTRL.ESXSWI1.EEName.serNum DPL DC A 0 Serial number equipment Configuration\Control\ESXSWI1
ESC(1) ESC(1) (20)
serial number
External
I<->O I<->O VisString255
ESXSWI1 CFG CTRL.ESXSWI1.EEName.model DPL DC A 0 Model equipment Configuration\Control\ESXSWI1
ESC(1) ESC(1) (20)
model
I<->O I<->O VisString255
ESXSWI1 VER CTRL.ESCILO1.NamPlt.swRev LPL DC ED1 C1 (Name plate)
ESC(1) ESC(1) (20)

DCSXSWI1: C1
IEC Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Parameter range Menu path
60617 name relation
Signal for open
I<->O I<->O position of Monitoring\I/O
DCSXSWI1 INP BOOLEAN B 0 POSOPEN
DC(1) DC(1) apparatus from status\Control\DCSXSWI1\Inputs
I/O
Signal for close
I<->O I<->O position of Monitoring\I/O
DCSXSWI1 INP BOOLEAN B 0 POSCLOSE
DC(1) DC(1) apparatus from status\Control\DCSXSWI1\Inputs
I/O

345
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

I<->O I<->O Apparatus open Monitoring\I/O


DCSXSWI1 OUT CTRL.DCSCSWI1.PosOpn.stVal SPS BOOLEAN ST B I1 OPENPOS
DC(1) DC(1) position status\Control\DCSXSWI1\Outputs
I<->O I<->O Apparatus Monitoring\I/O
DCSXSWI1 OUT CTRL.DCSCSWI1.PosCls.stVal SPS BOOLEAN ST B I1 CLOSEPOS
DC(1) DC(1) closed position status\Control\DCSXSWI1\Outputs
I<->O I<->O Apparatus Monitoring\I/O
DCSXSWI1 OUT CTRL.DCSCSWI1.PosOk.stVal SPS BOOLEAN ST B I1 OKPOS
DC(1) DC(1) position is ok status\Control\DCSXSWI1\Outputs
0=intermediate;
Apparatus Monitoring\I/O
I<->O I<->O 1=open;
DCSXSWI1 MON CTRL.DCSCSWI1.Pos.stVal DPC Dbpos ST B StatUrg P,H I1 POSITION position status\Control\DCSXSWI1\Monitored
DC(1) DC(1) 2=closed;
indication data
3=faulty
External
I<->O I<->O VisString255
DCSXSWI1 CFG CTRL.DCSXSWI1.EEName.vendor DPL DC A 0 Vendor equipment Configuration\Control\DCSXSWI1
DC(1) DC(1) (20)
vendor
External
I<->O I<->O VisString255 Serial
DCSXSWI1 CFG CTRL.DCSXSWI1.EEName.serNum DPL DC A 0 equipment Configuration\Control\DCSXSWI1
DC(1) DC(1) (20) number
serial number
External
I<->O I<->O VisString255
DCSXSWI1 CFG CTRL.DCSXSWI1.EEName.model DPL DC A 0 Model equipment Configuration\Control\DCSXSWI1
DC(1) DC(1) (20)
model
DCSXSWI1
I<->O I<->O Control Object
DCSXSWI1 CFG CTRL.DCSCSWI1.Pos.dU DPC Unicode255 DC ED2,B switch Identification Configuration\Control\DCSXSWI1
DC(1) DC(1) identification
position
DCSXSWI1
I<->O I<->O VisString255 Control Object
DCSXSWI1 CFG CTRL.DCSCSWI1.Pos.d DPC DC switch Identification Configuration\Control\DCSXSWI1
DC(1) DC(1) (64) identification
position
Event delay of
I<->O I<->O the
DCSXSWI1 CFG CTRL.DCSCSWI1.PosDlTmms.setVal ING INT32 SP A 30000 Event delay 0...60000 ms Configuration\Control\DCSXSWI1
DC(1) DC(1) intermediate
position
I<->O I<->O VisString255
DCSXSWI1 VER CTRL.DCSXSWI1.NamPlt.swRev LPL DC ED1 C1 (Name plate)
DC(1) DC(1) (20)

ESSXSWI1: C1
IEC Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Parameter range Menu path
60617 name relation
Signal for open
I<->O I<->O position of Monitoring\I/O
ESSXSWI1 INP BOOLEAN B 0 POSOPEN
ES(1) ES(1) apparatus from status\Control\ESSXSWI1\Inputs
I/O
Signal for close
I<->O I<->O position of Monitoring\I/O
ESSXSWI1 INP BOOLEAN B 0 POSCLOSE
ES(1) ES(1) apparatus from status\Control\ESSXSWI1\Inputs
I/O
I<->O I<->O Apparatus open Monitoring\I/O
ESSXSWI1 OUT CTRL.ESSCSWI1.PosOpn.stVal SPS BOOLEAN ST B I1 OPENPOS
ES(1) ES(1) position status\Control\ESSXSWI1\Outputs
I<->O I<->O Apparatus Monitoring\I/O
ESSXSWI1 OUT CTRL.ESSCSWI1.PosCls.stVal SPS BOOLEAN ST B I1 CLOSEPOS
ES(1) ES(1) closed position status\Control\ESSXSWI1\Outputs
346
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

I<->O I<->O Apparatus Monitoring\I/O


ESSXSWI1 OUT CTRL.ESSCSWI1.PosOk.stVal SPS BOOLEAN ST B I1 OKPOS
ES(1) ES(1) position is ok status\Control\ESSXSWI1\Outputs
Apparatus 0=intermediate; Monitoring\I/O
I<->O I<->O
ESSXSWI1 MON CTRL.ESSCSWI1.Pos.stVal DPC Dbpos ST B StatUrg P,H I1 POSITION position 1=open; 2=closed; status\Control\ESSXSWI1\Monitored
ES(1) ES(1)
indication 3=faulty data
External
I<->O I<->O VisString255
ESSXSWI1 CFG CTRL.ESSXSWI1.EEName.vendor DPL DC A 0 Vendor equipment Configuration\Control\ESSXSWI1
ES(1) ES(1) (20)
vendor
External
I<->O I<->O VisString255 Serial
ESSXSWI1 CFG CTRL.ESSXSWI1.EEName.serNum DPL DC A 0 equipment Configuration\Control\ESSXSWI1
ES(1) ES(1) (20) number
serial number
External
I<->O I<->O VisString255
ESSXSWI1 CFG CTRL.ESSXSWI1.EEName.model DPL DC A 0 Model equipment Configuration\Control\ESSXSWI1
ES(1) ES(1) (20)
model
ESSXSWI1
I<->O I<->O Control Object
ESSXSWI1 CFG CTRL.ESSCSWI1.Pos.dU DPC Unicode255 DC ED2,B switch Identification Configuration\Control\ESSXSWI1
ES(1) ES(1) identification
position
ESSXSWI1
I<->O I<->O VisString255 Control Object
ESSXSWI1 CFG CTRL.ESSCSWI1.Pos.d DPC DC switch Identification Configuration\Control\ESSXSWI1
ES(1) ES(1) (64) identification
position
Event delay of
I<->O I<->O
ESSXSWI1 CFG CTRL.ESSCSWI1.PosDlTmms.setVal ING INT32 SP A 30000 Event delay the intermediate 0...60000 ms Configuration\Control\ESSXSWI1
ES(1) ES(1)
position
I<->O I<->O VisString255
ESSXSWI1 VER CTRL.ESSXSWI1.NamPlt.swRev LPL DC ED1 C1 (Name plate)
ES(1) ES(1) (20)

DR LLN0: Disturbance recorder: H2


IEC 61850-7-4:2007
IEC Parameter Channel
IEC 61850 ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Parameter range Menu path
60617 name relation
Disturbance
OUT DR.RDRE1.RcdStr.stVal SPS BOOLEAN ST StatDR P I1 (Recording started)
recorder
Disturbance Manual trigger for the Disturbance
CTR DR.RDRE1.RcdTrg.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Trig recording 0=Cancel; 1=Trig
recorder disturbance recorder records\Disturbance records
Disturbance Disturbance Clear all disturbance 0=Cancel;
CTR DR.RDRE1.MemClr.Oper.ctlVal SPC BOOLEAN CO B 0 I1 Clear\Clear
recorder records recordings in the memory 1=Clear
Disturbance
MON DR.RDRE1.RcdMade.stVal SPS BOOLEAN ST StatDR P I1 (Recording made)
recorder
Disturbance
MON DR.RDRE1.RcdDltInd.stVal SPS BOOLEAN ST StatDR P I1 (Recording deleted)
recorder
Disturbance
MON DR.RDRE1.MemFullSt.stVal SPS BOOLEAN ST StatDR P I1 (Memory full)
recorder
Disturbance
MON DR.RDRE1.OvWrRcdInd.stVal SPS BOOLEAN ST StatDR P I1 (Overwrite of rec.)
recorder
Disturbance
MON DR.RDRE1.PerTrgInd.stVal SPS BOOLEAN ST StatDR P I1 (Periodic triggering)
recorder
347
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Disturbance
MON DR.RDRE1.ManTrgInd.stVal SPS BOOLEAN ST StatDR P I1 (Manual triggering)
recorder
Configuration\Disturbance
DR LLN0 CFG DR.LLN0.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation Disturbance recorder on / off 1=on; 5=off
recorder\General
Disturbance Periodic trig Time between periodic Configuration\Disturbance
CFG DR.RDRE1.PerTrgTms.setVal ING INT32 SP A 0 0...604800 s
recorder time triggerings in seconds recorder\General
Time how long triggerings
Disturbance Exclusion Configuration\Disturbance
CFG DR.RDRE1.ExclTmms.setVal ING INT32 SP A 0 for the same reason are 0...1000000 ms
recorder time recorder\General
ignored in milliseconds
Disturbance Operation 1=Overwrite; Configuration\Disturbance
CFG DR.RDRE1.RcdMod.setVal ENG Enum SP A 2 Saturation / overwrite
recorder mode 2=Saturation recorder\General
Length of recording
Disturbance Configuration\Disturbance
CFG DR.RDRE1.PreTrgLen.setVal ING INT32 SP B 50 Pre-trg length preceding the triggering in 0...100 %
recorder recorder\General
percent
Disturbance Record length in Configuration\Disturbance
CFG DR.RDRE1.RcdLen.setVal ING INT32 SP B,I 50 Record length 10...3000 cycles
recorder fundamental cycles recorder\General
Storage rate for waveform
Disturbance 80=80 samples / Configuration\Disturbance
CFG DR.RDRE1.StoRteSel.setVal ENG Enum SP A,I 80 Storage rate recordings in samples per
recorder cycle recorder\General
cycle
Storage mode selection
Disturbance Stor. mode 0=Waveform; Configuration\Disturbance
CFG DR.RDRE1.StoModPer.setVal ENG Enum SP A,I 0 (waveform / trend) for
recorder periodic 1=Trend / cycle recorder\General
periodic trigger
Storage mode selection
Disturbance Stor. mode 0=Waveform; Configuration\Disturbance
CFG DR.RDRE1.StoModMan.setVal ENG Enum SP A,I 0 (waveform / trend) for
recorder manual 1=Trend / cycle recorder\General
manual trigger
Append all configured SMV
Disturbance Append SMV Configuration\Disturbance
CFG DR.RDRE1.AddSMV.setVal SPG BOOLEAN SP A,I 1 streams at the end of each
recorder streams recorder\General
COMTRADE file
VisString255
DR LLN0 VER DR.LLN0.NamPlt.swRev LPL DC H2 (Name plate)
(20)
IEC
VisString255
DR LLN0 VER DR.LLN0.NamPlt.ldNs LPL EX 61850-7- (Name plate)
(20)
4:2003

Binary channel: Disturbance recorder binary channel: A1


IEC IEC Parameter Channel
ANSI Category IECName CDC Type FC Access Default Dataset Event CMT Parameter desc Parameter range Menu path
61850 60617 name relation
Binary
INP DR.RBDR1.BinInSt.stVal SPS BOOLEAN ST 0 (input)
channel
Binary Binary channel on / Configuration\Disturbance
CFG DR.RBDR1.Mod.Oper.ctlVal ENC Enum CO B,I 1 Operation 1=on; 5=off
channel off recorder\RBDR1
1=Positive or Rising;
Binary Level rising / falling / both Configuration\Disturbance
CFG DR.RBDR1.LevMod.setVal ENG Enum SP B,I 4 2=Negative or Falling; 3=Both;
channel trigger mode / trigger off recorder\RBDR1
4=Level trigger off

348
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E Smart Substation Control and Protection
SSC600
IEC 61850 Parameter List

Storage mode
Binary Storage Configuration\Disturbance
CFG DR.RBDR1.StoMod.setVal ENG Enum SP A,I 0 selection (waveform 0=Waveform; 1=Trend / cycle
channel mode recorder\RBDR1
/ trend)
Binary
Binary VisString255 Channel id Channel identifier Configuration\Disturbance
CFG DR.RBDR1.BinInSt.d SPS DC A channel
channel (64) text text recorder\RBDR1
input
Binary VisString255
VER DR.RBDR1.NamPlt.swRev LPL DC ED1 A1 (Name plate)
channel (20)

349
ABB Distribution Solutions – Digital Substation Products
1MRS759162 E 2022
ABB Distribution Solutions
Digital Substation Products
P.O. Box 699
FI-65101 VAASA, Finland
Phone +358 10 22 11

www.abb.com/mediumvoltage
www.abb.com/relion
www.abb.com/substationautomation

You might also like