(Eastron) DC Energy Meter

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

DC POWER AND ENERGY METERS

Measurement & Monitoring


DCM230 SERIES

Eastron DCM230 series DC meters are designed for measuring and monitoring in DC systems. The meters can measure all
important DC parameters: voltage, current, power and energy, etc. It also supports bi-directional measurement with pulse output.
All data in the meter are accessible via RS485 using Modbus RTU protocol. The meter has two versions working with AC or DC
power supply. Measuring voltage range up to 1000V DC, and current inputs are exible with DC shunt and current sensors. With
RTC equipped inside, the meter provides multi-rate information and monthly records. The meter is compact designed and
suitable for din rail installation.

Features

2 Modules Mini Size Pulse Output


LCD Display with Backlit RS485 Modbus RTU
Voltage Input 5...1000V DC Multi-tariff (RTC)
Current Input 75mV/60mV/45mV Resettable Partial Energy
Record 12 Months kWh Information Current Overload Alarm
Bi-directional Measurement Class 1.0 Accuracy

Wiring Diagram

L N 5 6 7 8 9

13

Power Supply
14 A+ B- GND + -
DCM230—1—1—1—1
RS485 Pulse
Power Supply
1: 85~300V AC
2: 9~60V DC
2

4
9
14

Max. Voltage
13

1: 1000V DC
1

3
6

2: 600V DC
5

3: 300V DC
Shunt
1: 75mV
1 2 3 4 1 2 3 4 2: 60mV
DC+ DC- I+ I- DC+ DC- I+ I- 3: 45mV
Tatiff
+ + 1: single tariff
Shunt
Load Load
Shunt 4: multi-tariff
- -
Shunt Connection: Positive Type Shunt Connection: Negative Type
Sepcications
5-1000V DC Active energy 1%
Range 5-600V DC Voltage 0.5%
Accuracy
Input Voltage 0.5%
5-300V DC Current
Power consumption ≤0.5VA Power 1%
75mV in default, Bus type RS485
Shunt 45/60mV optional
Input Current Protocol Modbus RTU
Power consumption ≤0.1VA Address range 1-247
Shunt primary 1- 2000A 1200/2400/4800/9600/
Programmable Ratio Baud rate
Over load 20Imax for 0.5s 19200bps
Communication
85-300V AC or Parity Even/Odd/None
Aux. Power Supply
9-60V DC Stop bits 1 or 2
AC power supply ≤2W/5VA Max. Bus loading 64pcs
Power Consumption
DC power supply ≤ 2W Communication distance 1000M
Installation category CAT II Response time ≤100mS
Mechanical environment M1 AC voltage withstand 4400V/1min
Insulation Capabilities
Electromagnetic environment E2 Impulse voltage withstand 4KV
Degree of pollution 2 Operating temperature -25℃~ + 55℃
Protection against penetration IP51 (in door) Environment Storage temperature -40℃~ + 70℃
Performance Criteria of dust and water
Operating humidity ≤ 90%
8KV contact/15kV
Electrostatic discharges Storage humidity ≤ 95%
air gap
Electromagnetic HF elds IEC61000-4-3 Altitude 2000m
Electrical fast transients 4kV Connections Screw terminals
Radiated & conducted Mounting Snap-on 35mm rail
IEC61326-1
emissions Housing material Self-extinguishing UL94 V-0
Housing
Tariffs 4 Weight 220g
Multi-Tariff
Time segments 8 Dimension(HxWxD) 99x36x63mm
Clock error <0.5s per day 2 Module DIN 43880
Display LCD with backlit RS485/Pulse/Aux. supply 0.5-1.5mm²
Terminals Capacity
Max. Reading 999999.9kWh Load 4-25mm²
Pulse Output 1, 10, 100, 1000imp/kWh RS485/Pulse/Aux. supply 0.4Nm
Screw Torque
Pulse Duration 60, 100, 200ms Load 3Nm

Shunt

Rated Voltage Drop 75/ 60/ 45mV 75/ 60/ 45mV 75/ 60/ 45mV 75/ 60/ 45mV 75/ 60/ 45mV
Primary Input 50A 200A 500A 1000A 2000A
Operation Temperature -40℃~+60℃ -40℃~+60℃ -40℃~+60℃ -40℃~+60℃ -40℃~+60℃
Exterior Dimension(in) 0.98x4.72x0.87 0.87x4.65x0.87 1.81x5x0.87 3.82x5x0.87 5.35x7.87x3.82
Exterior Dimension(mm) 25x120x22 22x118x22 46x127x22 97x127x22 136x200x97
Accuracy 0.5% 0.5% 0.5% 0.5% 0.5%

Web: www.eastrongroup.com E-mail: sales@eastrongroup.com


Tel: +86-573-83698881 Fax: +86-573-83698883 Add: No.1369,Chengnan Rd. Jiaxing, Zhejiang, 314001, China