Professional Documents
Culture Documents
Energy Based Fault Detection Scheme For Hybrid Microgrid
Energy Based Fault Detection Scheme For Hybrid Microgrid
Hybrid Microgrid
2021 IEEE 8th Uttar Pradesh Section International Conference on Electrical, Electronics and Computer Engineering (UPCON) | 978-1-6654-0962-9/21/$31.00 ©2021 IEEE | DOI: 10.1109/UPCON52273.2021.9667650
Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on April 08,2022 at 08:44:26 UTC from IEEE Xplore. Restrictions apply.
Utility LVDC DC load
AC/DC DC/DC
DC/DC
DC load
PV Array
Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on April 08,2022 at 08:44:26 UTC from IEEE Xplore. Restrictions apply.
Battery
Utility Mains
DC/AC
AC Load
Isolating
Switch
Converter Controller
DC load
M2
L1 L2
D1 Rf1
100 m cable
R2 R3 R4
R1
M1
M3
C2
C1 C4
C3 Battery
Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on April 08,2022 at 08:44:26 UTC from IEEE Xplore. Restrictions apply.
From the Fig4, the voltage VA at any time t will be Start
VA=VB+iA1RAB + LAB diA1/dt (1) Initialization
Where, iA1 =current sensed by IEDA1 K=0
N0
RAB , LAB = Equivalent resistance and inductance of
segment AB Sense of Vj and Ij
Now, Pole to Pole fault is considered at an instsnt t1
The voltage across bus A can be expressed as E kj =∑V(t) I(t)
VAf(t1)=Vf(t1) + IA1f(t1) RAf + LAf diAf1/dt (2) For each cyle of 0.2 sec
Where, VAF(t1) & IA1f(t1) = Sampled value of voltage and
current recognizes by IEDA1 during fault
Vf(t1)=Voltage at the faulted point Δ Ekj=Ekj(t)-Ekj(t-0.2)
RAf , LAf = Value of Resistance and inductance between
IEDA1 and faulted point N0
The difference between equation (1) and (2) , If Δ Ekj>Ethp
VAf (t1)- VA = Vf (t1) -VA + iA1f (t1) RAf - iA1RAB+LAf diAf1/dt
- LAB diA1/dt (3)
Where, VA=Pre fault voltage YES
VAf(t1)=Voltage during fault K=1
∆VA= Vf (t1) -VA + iA1f (t1) RAf - iA1RAB+LAf diAf1/dt
- LAB diA1/dt (4)
Where, ∆VA=Change in voltage at bus A during fault Send the Trip signal
to breaker
From (1),
∆iA = VA -VB + iA1RAB / LAB (5) Fig 5: Fault detection algorithm
∆EA = ∆VA ∆iA ∆t
Energy packets calculated for a time interval of 0.2 sec The remaining IEDs verify the status of the tripping level
E (t) = ∫ ∆VA ∆iA dt after waiting for a few predetermined intervals. IED
An index ∆Ekj is calculated as delivers the trip signal to cut off the defective portion
∆Ekj = ∆Ekj(t) - ∆Ekj(t-0.1) (6) from the healthy section if ∆E exceeds the threshold value
Ethp where Ethp and Eths are the main and secondary level
When this index exceeds the defined threshold fault in the threshold values, respectively.
system is detected.
A . Threshold Setting
IV. PROPOSED METHOD
The threshold for the proposed method is decided after
The fault detection method is based on the energy packets verifying the energy change for the different operating
calculated over a definite period. As the prime provide the conditions: loading level, operating modes, and fault. The
backup from the AC side and in the conventional grid pole-to-pole and pole-to-ground fault are simulated in
with 50 Hz system, the primary operates within 5 cycles. MATLAB/SIMULINK with different fault resistance, and
Failure of primary asks for the operation of backup, which locations and the change in energy are recorded.
comes after 0.1 seconds. For this reason, a period of 0.1 is Similarly, the irradiance of PV is also changed with
selected to provide the backup during reverse power flow, different loading conditions to compute the energy change
i.e., DC to AC side. It is observed that the fault current during different loading conditions. The per-unit change is
and its rate of change are affected by the circuit presented in the Table. 1 below. The maximum change
parameters during fault and the filter circuit parameters of observed is 1.2. hence considering the measurement
the DC circuit. Hence, in this scheme, both voltage and errors, the threshold is selected as 1.3. All backup
current data are utilized to derive the energy of a system, protection activates at a defined time delay of Ts, which is
and the energy packets are calculated for a particular decided before the relays are set. The process is similar to
period. The difference between the two consecutive the selection of the time setting multiplier in OCR.
energy packets is observed, and when it is greater than the
threshold, fault in line is detected. When a fault occurs in
the system, the SSR nearest to the faulty part activates TABLE I
Pickup Threshold Setting For Different Loading Condition
quickly, referred to as primary level Protection. There are
two layers of protection with this approach. The Loading ∆Ekj(J) €=∆Ekj / EF.L
secondary level provides the necessary protection for the level(pu.) (pu.)
rest portion. If main level protection fails to protect
against a fault during a fault, secondary level protection is 0.5 0.22 0.83
used. If the measured value ∆E of the SSR nearest to the
faulty segment exceeds the predetermined threshold value 1 0.27 1.03
Ethp, the related intelligent electronics device (IED) sends
a trip signal to the SSR, causing the faulty section to be 1.25 0.30 1.12
isolated. Secondary level protection steps in if the nearest
SSR is unable to detect a Fault. 1.50 0.32 1.2
Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on April 08,2022 at 08:44:26 UTC from IEEE Xplore. Restrictions apply.
E(t)-E(t-0.2) J
V. SIMULATION RESULTS AND DISCUSSION
10
40
A. Pole to Pole Fault 30
20
40
Rf = 0.1 Ohm
10
30 Rf= 10 Ohm
Bus voltage[V]
10
0
5 0.5 1 1.5 2
Time[sec]
0
0.8 0.85 0.9 0.95 1 1.05 1.1 1.15 1.2
. Fig 7.b: Current with input signal containing noise
Time[sec]
5
Fig 6.b : Currents for pole to pole fault
Energy Packets
6 Rf=0.1 ohm 3
2
RF=10 ohm
E (t)- E ( t- 0 .2 )
4 1
0
0 0.2 0.4 0.6 0.8 1
2 Time[sec]
Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on April 08,2022 at 08:44:26 UTC from IEEE Xplore. Restrictions apply.
4
E(t)-E(t-0.2)
E(t)-E(t-0.2)
0.4
2
0.3
1 0.2
0
0.1
0.5 0.6 0.7 0.8 0.9 1 1.1
Time[sec] 0
0 0.2 0.4 0.6 0.8 1 1.2 1.4
Fig 7.d: Difference between the consecutive energy packets.
Time[sec]
The effect of noise on the proposed method is tested for a
Fig 8.d: Energy difference waveform during the load change condition
pole-to-pole fault. The voltage and current signals
obtained are plotted in Fig.7.a and Fig.7.b, respectively. VI. CONCLUSIONS
During this condition, 3 dB noise is added to the signal.
A novel Energy-based fault detection scheme is proposed
Then the Energy is calculated using the voltage and for a hybrid Microgrid system which is reliable compared
current of the relay, and the calculated Energy is plotted in to the current based fault detection schemes. The proposed
Fig.7.c. The change in Energy plotted in Fig.7.d reveals method is capable of detecting high resistance faults.
that the fault is detected even the noise is present in the Sudden change in load is tested, and results reveal that the
signal. method operates satisfactorily. The scheme's benefit is
C. Performance With Load Change: that it can provide and obtain a higher level of selectivity
Since the voltage and current are affected by the load without using any physical communication link. The
changes, it is obvious that the load change will affect the proposed protection scheme is providing satisfactory
performance of the proposed method. Hence the technique results with overloading conditions and noise introduced
is tested for different load change conditions. During these in the system. Simulations carried for several operating
changing load conditions, the voltage and current of the conditions reveals the proposed method provides better
relay are collected and plotted in Fig. 8.a and Fig.8.b. The security.
Energy computed is plotted in Fig. 8.c, and the change in VII. Acknowledgement
Energy is presented in Fig. 8.d. It can be observed in Fig
8.a that change in current magnitude is very less in We are thankful to SERB, India for providing funding for
the project titled "Development of novel protection
comparison to the fault; hence it will not trigger the relay
schemes for Hybrid micro grid", sanction order No,
logic. Hence the proposed method is not affected by the
SRG/2020/002302 to carry out the research work.
load change in the system.
VIII. REFERENCES
Fault current
[1] S. Mirsaeidi, X. Dong, S. Shi, and D. Tzelepis, “Challenges, advances and future
Currents[A]
10 125% loading directions in protection of hybrid AC/DC microgrids,” IET Renew. Power Gener., vol.
11, no. 12, pp. 1495–1502, 2017, doi: 10.1049/iet-rpg.2017.0079.
[2] P. M. Kishore and B. Ravikumar, “Refined Hybrid Microgrid Architecture for the
5 Improvement of Voltage Profile,” Energy Procedia, vol. 90, no. December 2015, pp.
645–654, 2016, doi: 10.1016/j.egypro.2016.11.233.
[3] S. Sarangi, B. K. Sahu, and P. K. Rout, “Distributed generation hybrid AC/DC
microgrid protection: A critical review on issues, strategies, and future directions,” Int.
0
J. Energy Res., vol. 44, no. 5, pp. 3347–3364, 2020, doi: 10.1002/er.5128.
0.5 1 1.5 2
Time[sec] [4] S. Xue, J. Lian, J. Qi, and B. Fan, “Pole-to-ground fault analysis and fast protection
scheme for HVDC based on overhead transmission lines,” Energies, vol. 10, no. 7,
Fig8.a: Current waveform during the load change 2017, doi: 10.3390/en10071059.
[5] D. Salomonsson, L. Söder, and A. Sannino, “Protection of low-voltage DC microgrids,”
IEEE Trans. Power Deliv., vol. 24, no. 3, pp. 1045–1053, 2009, doi:
40 10.1109/TPWRD.2009.2016622.
Voltage[V]
location in VSC-based DC network cables,” IEEE Trans. Ind. Electron., vol. 59, no. 10,
4 pp. 3827–3837, 2012, doi: 10.1109/TIE.2011.2162712.
3 [11] M. Shamsoddini, B. Vahidi, R. Razani, and Y. A. R. I. Mohamed, “A novel protection
scheme for low voltage DC microgrid using inductance estimation,” Int. J. Electr.
2 Power Energy Syst., vol. 120, no. June 2019, p. 105992, 2020, doi:
1 10.1016/j.ijepes.2020.105992.
[12] A. Meghwani, S. Chakrabarti, and S. C. Srivastava, “A fast scheme for fault detection in
0 0.5 1 1.5 DC microgrid based on voltage prediction,” 2016 Natl. Power Syst. Conf. NPSC 2016,
Time[sec] 2017, doi: 10.1109/NPSC.2016.7858867.
[13] M. Farhadi and O. A. Mohammed, “Event-Based Protection Scheme for a Multiterminal
Hybrid DC Power System,” IEEE Trans. Smart Grid, vol. 6, no. 4, pp. 1658–1669,
Fig 8.c: Energy packets waveform during the load change condition 2015, doi: 10.1109/TSG.2015.2396995.
[14] S. Beheshtaein, R. M. Cuzner, M. Forouzesh, M. Savaghebi, and J. M. Guerrero, “DC
Microgrid Protection: A Comprehensive Review,” IEEE J. Emerg. Sel. Top. Power
Electron., vol. PP, no. c, pp. 1–1, 2019, doi: 10.1109/jestpe.2019.2904588.
[15] A. Srivastava, R. Mohanty, M. A. F. Ghazvini, L. A. Tuan, D. Steen, and O. Carlson,
“A Review on Challenges and Solutions in Microgrid Protection,” 2021.
Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on April 08,2022 at 08:44:26 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on April 08,2022 at 08:44:26 UTC from IEEE Xplore. Restrictions apply.