S200 building hoist integration special-purpose drive manual

1. Product description
1.1 Product features
 Special-purpose model that integrates frequency inverter, brake unit, brake power
module, logic control unit.
 The brake unit of traditional hoist without short-circuit protection, our S200 built-in brake
unit have the function of short-circuit protection.
 Compare to the normal frequency control cabinet, our S200 compact, elegant
appearance, adopting cage and cage embedded installation, convenient for
transportation and save cost of wiring.
 Built-in starting-weight limiter(over weight protection),client no need purchase
separately, display can show the weight(T) or percentage, comply with safety
standards.(we own the certificate of approval from safety supervision)
 Built-in clock chip, and can set the privileged time for ease of management to customer.
 With the brake coil short-circuit protection function.
 Just need the right access of main power, limit switch, console and no need set the
function parameter of frequency inverter, boot and will work well.
 Intelligent statue display panel can display a variety limit, command signal have a clear
LED indication and silk-screen printing logo, easy for installation and inspection, great
reduce the cost of service.
 Flexible mode of connection, adopting heavy-duty connector and terminal
combinations.
 Comfortable in starting and stopping, no” weightless” feeling at open moment of
downlink band-brake.
 Special ‘S’ curve acceleration and deceleration, solving “overshoot impulse” at the
moment of the uplink loose brake.
 With torque holding at 0 speed function, no need any band-brake action to support the
forward-reverse to across 0 speed.
 Braking circuit and braking logic employ double logic signal to control double braking
contactor safety circuit respectively. Protecting crane in safety if when the contactor
touch pin of contactor has problem can’t be separated. It is conform to national
GB26557-2011 standard.
 With zero dead zone compensation function when JOG frequently, without vibration and
glide.
 Support GPS/GPRS communication interface, it can use satellite to positioning and
remote monitor, lock and unlock, easy for customer management.
1
S200 building hoist integration special-purpose drive manual
 Support conversion interface of power frequency and variable frequency.
 IP54,whole machine water-proof design.
 Anti-seismic test for the mechanical properties of the hoist/lift.
 Built-in charging protective circuit for the characteristic of frequent power off. Fast
response, NOWAIT.
1.2 S200B drive appearance

1.3 Model explanation


S 200 B 037 B
Brake type : B-braking energy type

F-Energy feedback type

Power KW

M odel code
-1
Load weight : Rated load weight *10 kg

Building hoist integration special-purpose


 
 
 
 
 
 
 
 

2
S200 building hoist integration special-purpose drive manual
1.4 Model no. and rated output current
3 phase 380V
Rated input Rated
Model Motor power Remark
voltage current(A)
S200C-037-B 37KW 3 phase 75A 11KW*3 - 15KW*2
S200C-045-B 45KW 380V 90A 13KW*3 - 15KW*3
3 phase
S200D-037-B 37KW 75A 11KW*3 - 15KW*2
380V
S200E-037-B 37KW 75A 11KW*3 - 15KW*2
S200E-045-B 45KW 3 phase 90A 13KW*3 - 15KW*3
S200E-055-B 55KW 380V 120A 15KW*3
S200E-075-B 75KW 150A 18.5KW*3 - 22KW*3

2. Product dimension and wiring


2.1 Dimension

W
W1
W2

HZ
H2

Kg %
Overweight warning
Overweight alarm
Drive status display
GPS action
H1

Fault phase action


H

Falling emergency stop


Cage inside emergency stop
Door limit
Up limit
Down limit
H2

Deceleration limit
Up command
Down command
Acceleraton command
Standby mode

Install aperture

W3
D

3
S200 building hoist integration special-purpose drive manual
Install
Model W W1 W2 W3 H H1 H2 D
aperture
S200C-037-B 820 790 420 750 410 370 145 230 Ф11
S200C-045-B 820 790 420 750 410 370 145 230 Ф11

Install aperture

Install
Model W W1 W2 H H1 D
aperture
S200E-037-B 630 606 560 600 245 210 Ф11
S200E-045-B 630 606 560 600 245 210 Ф11
S200E-055-B 630 606 560 800 350 220 Ф11
S200E-075-B 630 606 560 800 350 220 Ф11

4
S200 building hoist integration special-purpose drive manual

HZ

Kg %
超重预警
超重报警
系统状态显示 system status display
GPS动作 GPS action
错断相动作 Fault phase action
防坠急停 Falling emergency stop
茏内急停 Cage inside emergency stop
门限位 Door limit
上限位 Up limit
下限位 Down limit
减速限位 Deceleration limit
手柄上升 Handle up
手柄下降 Handle down
手柄加速 Handle acceleraton
备用模式 Standby mode

Install
Model W W1 W2 H H1 D D1 D2
aperture
S200D-037-B 630 606 560 850 365 220 165 110 Ф11

5
S200 building hoist integration special-purpose drive manual
2.2 Installation
Install stents Cage installation Embed 100MM installation Embed 165MM installation

2.3 Wiring
* S200C/E-37/45kW Main circuit connection diagram
R R R1

S S S1

T T T1

QF1

R S T R T R S T R S T R S T R S T
PR L1 L2 L3
L1
L2
L3

12 11
14 12
14
11 Rectifier circuit
T
S1
PR-14
KM7 KM6 KM5
P
QF2 Frequency

20R/80W
R11 T11 inverter KM1
0V 380V 415V 440V
(+)
T1
220V 220V
L1 N1 L2 N2
Inverter circuit
KM2
R S T L11 N11 L2 N2 U V W + PB
commutator AC
DC
DC+ DC- KM4
KM3
+ -

R N PE R S T N + - R2 S2 T2 U1 V1 W1 U2 V2 W2 U3 V3 W3 + PB
COM 24V 15V 8V
L2 N2

Canada Day socket Power Input Power


MCU Power Control Power Motor Oil 1# Motor 2# Motor 
3# Motor Braking resitor
Brakes

6
S200 building hoist integration special-purpose drive manual
* S200D Main circuit connection diagram
R
KM1

QF1
380V R
R S T
T1
Rectifier
220V
circuit

QF2
KM7 KM6 KM5
R S T Frequency
101
inverter

Phase order
Phase sequence relay

protection
Schneider RM4 TG20 103

Inverter
circuit
KM2
U V W (+) PB
AC
AC

DC DC

KM4

KM3
D R

R N PE R S T N 101 103
+ - COM 24V 15V 8V
N L
R1 S1 T1 U1 V1 W1 U2 V2 W2 U3 V3 W3 + PB
Phase order MCU Control
Canada Day Power Input Power Brakes Motor Oil 1# Motor 2# Motor 3# Motor Braking
protection Power Power
socket resitor
Note:QF1 Variable frequency main circuit switch,QF2 control power supply switch;T1 AC380/220V isolation transformer,R precharge resistors;KM1
Main contactor,KM2,KM3 brake contactor;KM4 power frequency/variable frequency contactor,KM5 power frequency forward running contactor ,KM6
power frequency reverse running contactor;KM7 oil adding control contactor(Optional)

* S200E-55/75kw Main circuit connection diagram

R S T
380V

T1 Rectifier circuit

220V
QF1 P
Frequency
KM1 R
inverter
(+)

KM2 KM7
AC Inverter circuit
DC
AC (+) PB U V W
DC

KM3

D R

R N PE R S T N + -
COM 24V 15V 8V N L
R1 S1 T1 + PB U1 V1 W1 U2 V2 W2 U3 V3 W3
Power Input MCU Control
Canada Day Power Brakes Motor Oil Braking 1# Motor 2# Motor 3# Motor
Power Power
socket resitor
Note:T1 AC380/220V isolation transformer,R precharge resistors;KM1 Main contactor,Off DC link power,
KM2,KM3 Brake contactor; KM7 Fuel control contactor(Optional)

Note: Standard Product is not equipped refueling function, and the refueling function is optional based on needs.

7
L2
L line of transformer
L2

L line of transformer
N2
N line of transformer
N2

N line of transformer
OUT8
Electric bell
Relay output

Flashlight
OUT3
HA

Brake output 2 OUT6


Power frequency
KM3

inversion
OUT2
KM6

Brake output 1 OUT5


Power frequency
KM2

Forward
OUT1
KM5

Main contactor OUT4


Frequency output
KM1

OUT7
KM4

Refuel output Power frequency GB


/ frequency mode
KM7

1 2

COM
COM
S1
S200 building hoist integration special-purpose drive manual

N line of transformer
conversion box, and implement the wiring according to the circuit wiring.

I line of transformer
109
Note: S200C / E / K is equipped with power frequency / frequency

Fault indication
110
Running indication
Cage inside console

COM
104
lighting switch
Fault reset
108
102
start up
Main command 107
Acceleration
Main command decline 106
Main command rise
105
SJ-GL type 5T lifting weight limiter

8
 
Cage inside 103
emergency stop
1 2

Refuel
Crawl
COM
COM
Anti-hoisting limit
COM COM
COM
BF BF-G OF
Brake feedback

KM3
KM2

KM4 KM5 KM6


COM
Down decelerating
Limit switch
limit
Up decelerating limit
COM
Drop limit
* S200CON-B1.1 Electric Wiring Diagram

Rise limit
COM
Skylight limit

Intelligent voice
Two-door Limit
COM

module
Single door limit
fence limit
Parachute
emergency stop

dashed box is the


Note: inside the

external circuit
Light board
GND
A+
+10V

Lock
B-
power frequency/frequency conversion

L2
Note 1: S200C / E / K is equipped with

L line of transformer L line of transformer


L2

box, and its wiring is implemented

N2
N line of transformer N line of transformer
N2

OUT8
Electric bell
Flashlight
according to this circuit.

OUT3
HA

Brake output 2 Power frequency OUT6


inversion
KM3

OUT2
KM6

Brake output 1Power Power frequency OUT5


KM2

Forward
OUT1
KM5

Main contactor OUT4


Frequency output
Relay output
KM1

OUT7 GB
KM4

Refuel output Power frequency


/frequency mode
1 2

KM4 KM5 KM6


KM7

OF
Output feedback
S1

COM COM
S200 building hoist integration special-purpose drive manual

I line of transformer
N line of transformer
Emergency output
118
Emergency input 117
109
Fault indication
Running indication 110
COM
COM
104
lighting switch
Cage inside console

108
Fault reset
102
start up
SJ-GL type 5T lifting weight limiter

Main command 107


Acceleration
Main
command decline 106

9
Main 105
command rise
Cage inside 103
emergency stop
1 2
Refuel
Crawl
COM
COM
Anti-hoisting limit
Brake feedback BF BF-G

KM3
KM2
COM
Down
decelerating limit
Up
decelerating limit
COM
* S200CON-C1.0 electrical wiring diagram

Drop limit

Limit switch
Rise limit
COM
Skylight limit
COM
Two-door Limit

voice module
COM

Intelligent
Single door limit
COM
fence limit
Parachute
emergency stop

Note: inside the


dashed box is the
external circuit
Light board
GND
A+
+10V

Lock
B-
Speaker
S200 building hoist integration special-purpose drive manual
* Power frequency converter box control circuit wiring diagram

N2
N
U V W Power frequency/
Inverter output N2 S1 S1-HG HG
frequency status
S1 indication
N2 S1-HR HR L2
L

COM COM
1
KM6 KM5
PR L1 L2 L3 S1
COM GB
2
L1
L2
L3

14 12 11

KM4
12 11 14
COM

KM4 3
COM KM5
COM KM6 OF
4
KM4
L2 KM5 L21 KM6 L24 OUT4

R S T 5
L2 L22
KM5
L2 PR L22 KM4 L23 KM6 L25 OUT5
6
KM6
KM5 L26 OUT6
7

L2 L2
9
Main power Motor Note:1.S1 Power frequency/ frequency switch 2.H1 External lighting
R S T U1 V1 W1 U2 V2 W2 U3 V3 W3 3.HG , HR Status Indicator 4.KM4 Inverter output contactor
5.KM5 power frequency output contactor
6.KM6 power frequency inversion contactor 7.PR Phase sequence relay

10
S200 building hoist integration special-purpose drive manual
*Console wiring diagram 

Console wiring diagram


JK 1 2 3 4 5 6 7 8 9 10 11 12 18 19

101 102 103 104 105 106 107 102 108 109 110 111 117 118

UP Down HS
SB2

S1 S2 S3
SB1 SY SB5 SB4 HL1 HL2 SY
SB3

start/bell strong current


light switch main command reset run command
electric lock/emergency stop refuel fault indicator electric lock/
controller
emergency stop

* Wiring diagram for aviation plug  

201
1
1. A1_COM input port
2. Empty
2 3. A3_ drop box upward
SB1 203 4. Empty
Emergency stop
3 5. A5_ Drop test
7 core aviation plug

SB2 204
Start 4 Test box for drop
SB3 205
Rise 5 1 . E1_switch between cage and cage's top
2. E2/E6_Common input port

6 3. E3_Emergency stop of cage's top


SB4 207 4. E4_drop box/cage's top/start in the cage
Fall 7 5. E5_cage's top upward
6. Empty
Operation box 7.E7_cage's top downward
Operation box
301
1 1.C1_+10V (Red)
2.C2_AD1-(White)
3.Empty
2
5 core aviation plug

4.C4_GND (Green)
SB1 303 5.C5_AD1+ (Yellow)
Start Rise
3
Pin sensor 1

1.D1_+10V(Red)
4 2. D2_AD1-(White)
SB2 305 3. Empty
Drop 4. D4_GND(Green)
5
Test box for drop Pin sensor 2
5. D5_AD1+(Yellow)

11
S200 building hoist integration special-purpose drive manual
Special instruction:
* Note for on-site install and debug
When motor drive plate and lift cage disjointed(pin not connected),use the handle to do the up/down
jog operation ,if drive plate do the upward movement, than it is normal and wiring direction is right. If
drive plate do the downward movement, than wiring direction is opposite and need to change the
motor wire.
When GPS remote control and lock the machine, inverter will display “LIFE” fault, can not reset but
can running at 10 Hz or only downward running is allowed.

2.4 Main circuit terminals array and definition


37~45kW main circuit terminals array:

AC 380V
Add section outlet

Test box
for drop
R S T N (+) PB (+) (-) U1 V1 W1 U2 V2 W2 U3 V3 W3
Operation
Braking
POWER box Brake power MOTOR 1# MOTOR 2# MOTOR 3#
resistance

Pin sensor 1# Pin sensor 2#

Terminal
Terminal name Terminal function
symbols
(+) Brake power output
Output voltage DC195V,use for brake power supply
(—) terminal
(+) Braking resistance Used for external braking resistance, recommend
PB terminal 15Ω/24KW.
R
S
Inverter input terminal Used to connect 3 phase AC power supply
T
N
U
V Inverter output terminal Used to connect the motor
W

Earth Earth terminal, earth resistance<10 OHM


E

12
S200 building hoist integration special-purpose drive manual

3. Keyboard and operation


3.1 Keyboard appearance and function

LED monitor indicator

First line LED monitor

LED monitor indicator

Second line LED monitor

Menu key

UP/DOWN
Confirm modification Shift
JOG/reverse
Function indicator Stop/reset

State indicator Forward

Key Name Function

Enter menu while standby or running, Press this key to return while
Menu key modify parameter. While standby or running, press for 1 sec to
enter condition monitoring interface.
Press to modify parameter while in menu interface. Press again to
Confirm/modify
confirm after modifying. While standby or running, press to change
key
LED monitoring items at stop.

Select parameter group in menu interface. Modify parameter while


Up/down key in modify interface.(If need set the given frequency or torque by
keyboard, pls set parameter F4.03 )

Used for select the function no.( changed by up/down key) when in
Shift key menu interface. Used for select the parameter no.(changed by
up/down key) when in modify parameter interface.

13
S200 building hoist integration special-purpose drive manual
While run/stop is controlled by keyboard, press this key, inverter
Forward run key forward rotate and the indicator is always on. While reverse, the
indicator sparks.

This key function can be defined by parameter F4.01.Press it,


Jog/reverse key machine reverse and indicator is off if this key is defined as REVE
RSE. Machine will Jog-indicator on if defined as JOG.

Machine stop if press it while run/stop is controlled by key board. Its


Stop/reset key efficiency range is defined via function no.F4.02.Inverter reset if
press it in fault state(no set if fault is not solved)

3.2 Indicator light meanings

Name State Meaning

Hz Spark Digital display the given frequency.


Hz On Digital display the output frequency.
A On Digital display the actual output current.
Unit V On Digital display the input voltage.
indicator
light V Spark Digital display the output voltage.
S On Time unit is second.
S Spark Time unit is ms,min,or h.
RPM On Digital display motor speed.
FWD On Inverter running in FORWARDD
State
indicator FWD Spark Inverter running in REVERSE
light
FWD Off Inverter stops.

Function REV/JOG On JOG.


indicator
light REV/JOG Off Reverse.

14
S200 building hoist integration special-purpose drive manual

4. Function Parameter Table


“●”: Means that the parameter can be revised during frequency inverter in a running state
“〇”: Means that the parameter can not be revised when in a running state
“×”:Indicates that the parameter can only be read, can not be changed;
“–”:indicates that the parameter is "factory settings" which is limited to be set by the factory;
4.1 Parameters
4.1.1 Basic Parameter Group
Commu
Pro nicatio
Range of setting and Factory
No. Function description pert n
definition default addres
y
s
0: VC without PG 0
1: VC without PG 1
F0.00 Control mode 1 〇 0x000
2: VC with PG 0
3: VC with PG 1
0: construction lifting machine
F0.01 Model selection 1: elevator special inverter 0 〇 0x001
2: construction elevator drive
0: Keyboard control
1: Terminal control
F0.02 Run command channel 2: RS485 communication 1 〇 0x002
control
3: Optional card
0: Keyboard no. given
Frequency given main
F0.03 6:RS485communication port 6 〇 0x003
channel selection
given
F0.04 Main channel gain 0.000~5.000 1.000 〇 0x004
Keyboard no. setting
F0.08 0.00~Upper limit 15.00Hz ● 0x008
frequency
F0.09 Max. frequency output 0.00~320.00Hz 50.00 Hz 〇 0x009
0: Upper limit frequency digital
Upper limitation source
F0.10 given 0 〇 0x00A
selection
6: RS485 communication given
F0.11 Upper limit frequency High gear frequency 50.00 0x00B
F0.12 Low limit frequency 0.00~upper limit 0.00 Hz 〇 0x00C
0: stop
Low limit frequency
F0.13 1: Run by the low limit 1 〇 0x00D
running mode
frequency
15
S200 building hoist integration special-purpose drive manual
F0.14 ACC time 1 0.01~650.00s 6.5s ● 0x00E
F0.15 DCC time 1 0.01~650.00s 2.0s ● 0x00F
0: Consistent
F0.16 Rotate direction 1: Reverse 0 ● 0x010
2: Reverse banned
F0.17 Carrier frequency 0.6~2.0KHz 1.0 ● 0x011
LED “0” digit:
0:Unrelated to temperature
1:Related to temperature
LED “10” digit:
0: Unrelated to output
frequency
Carrier frequency 1: Related to output frequency
F0.18 1000 ● 0x012
characteristic selection LED “100” digit:
0: Fixed carrier
1: Random carrier
LED “1000”:
0: PWM mode 1
1: PWM mode 2
2: PWM mode 3
0: No action
F0.19 Parameter initialization 1: Recovery factory setting 0 〇 0x013
2: Clear malfunction records
0: invalid
F0.20 AVR function selection 1: all valid 1 ● 0x014
2: Invalid in DEC only
4.1.2 Running Control Parameters Group
Comm
unicati
Range of setting and Factory Prop
No. Function description on
definition default erty addres
s
0: DEC to stop
F1.07 Stop mode 0 ● 0x107
1: free stop
Stop DC braking start
F1.08 0.00~50.00Hz 0.00Hz ● 0x108
frequency
Stop DC braking
F1.09 0.0~150.0% 120.0% ● 0x109
current
Stop DC braking
F1.10 0.0~60.0s 0.0s ● 0x10A
waiting time

16
S200 building hoist integration special-purpose drive manual
Stop DC braking
F1.11 0.0~60.0s 1.0s ● 0x10B
duration
Minimum output
F1.26 0.00~60.00Hz 1.90Hz ● 0x11A
frequency
F1.27 0 speed hold torque 0.0~150.0% 120.0% ● 0x11B 
When set as 0.0~5999.9s,
maintain o speed torque
0 speed hold torque
F1.28 according to setting time 50.0s ● 0x11C
time
When set as 6000.0s, no time
limit for o speed torque
4.1.3 Switch Value Terminal Parameter Group
Factor Commu
Prop
No. Function description Range of setting and definition y nication
erty address
default
Multifunction input 0: No function
F2.00 1: FWD 1 ● 0x200
terminal 1(X1)
Multifunction input 2: REV
F2.01 3: 3-line running control 2 ● 0x201
terminal 2(X2)
4: FWD JOG
Multifunction input
F2.02 5: REV JOG 15 ● 0x202
terminal 3(X3)
6: Free stop
Multifunction input 7: Emergency stop
F2.03 53 ● 0x203
terminal 4(X4) 8: Malfunction reset
Multifunction input 9: External fault input
F2.04 52 ● 0x204
terminal 5(X5) 15: Multistep terminal1
Multifunction input 16: Multistep terminal 2
F2.05 0 ● 0x205
terminal 6(X6) 17: Multistep terminal 3
Multifunction input 18: Multistep terminal 4
F2.06 48: lower limit state terminals 8 ● 0x206
terminal 7(X7)
(drive)
49: upper limit state terminals
(drive)
Multifunction input 52: Weighing alarm switch
F2.07 0 ● 0x207
terminal 8(X8) terminal
53: empty cage weighing
calibration terminal
X1-X4 input terminal
F2.09 0.000-60.000s 0.010s ● 0x209
filer time
X5-X8 input terminal
F2.11 0.000~60.000s 0.010s ● 0x20B
filer time
F2.29 Output terminal 1(Y1) 0: No output 20 ● 0x21D
F2.30 Output terminal 2(Y2) 1: Inverter running 20 ● 0x21E

17
S200 building hoist integration special-purpose drive manual
2: Inverter reverse running
3: fault trip alarm 1(alarm during
fault self-recovery)
Relay output terminal 6: External fault stop
F2.31 29 ● 0x21F
(TA-TB-TC) 9: FDT output (see F9.00 /
F9.01)
20: special brake logic control
29: fault loss phase fault output
Upward start
F2.32 0.00~10.00Hz 0.45 ● 0x220
frequency
Upward start
F2.33 0.00~10.00s 0.50 ● 0x221
frequency delay time
Upward loose-brake
F2.34 0.0~500.0% 50.0 ● 0x222
current value
Upward loose-brake
F2.35 0.00~10.00s 0.10 ● 0x223
current hold time
Downward start
F2.36 0.00~10.00Hz 0.4 ● 0x224
frequency
Downward start
F2.37 0.00~10.00s 0.5 ● 0x225
frequency delay time
Downward loose-brake
F2.38 0.0~500.0% 50.0 ● 0x226
current value
Downward loose-brake
F2.39 0.00~10.00s 0.10 ● 0x227
current hold time
Upward stop-band
F2.40 0.00~50.00Hz 2.00 ● 0x228
brake frequency
Upward stop-band
F2.41 0.00~10.00s 0.35 ●
brake delay time
Downward stop-band
F2.42 0.00~50.00Hz 2.00 ●
brake frequency
Downward stop-band
F2.43 0.00~10.00s 0.35 ●
brake delay time
Loose-brake signal
F2.44 0.000~10.000s 0.150 ●
output delay
Band-brake signal
F2.45 0.000~10.000s 0.150 ●
output delay

18
S200 building hoist integration special-purpose drive manual
4.1.4 Keyboard and Display Parameter Group
Pro Commu
Range of setting and Factory
No. Function description pert nication
definition default y address
0: Unlock
1: Function parameter lock
2: Function parameter and key
Parameter and key
F4.00 lock (except for 1 ● 0x400
lock selections
RUN/STOP/JOG)
3: All function parameter and
key lock
F4.01 User password 0-9999 **** ● 0x401
LED “0” digit: display the first
group
0: Given frequency
1: Output frequency
2: Output current
3: Input voltage
4: Output voltage
5: Mechanical speed
6: Torque setting
7: Output torque
8: Load weight
9: Load weight display the
The display content of
percentage
F4.11 the first line at the 3210 ● 0x40B
A: Output power
running state
B: DC bus voltage
C: Module temperature 1
D: Module temperature 2
E: ON/OFF state of input
terminal X
F: ON/OFF state of output
terminal Y
LED “10”digit: display the
second group
LED “100” digit: display the third
group LED “1000”: display the
fourth group
LED “0” digit: display the first
group
The display content of LED “10”digit: display the
F4.12 the first line at the second group 3210 ● 0x40C
stop-state LED “100” digit: display the third
group LED “1000”: display the
fourth group
19
S200 building hoist integration special-purpose drive manual
LED “0” digit: display the first
group
The display content of LED “10”digit: display the
F4.13 the second line at the second group 1209 ● 0x40D
running state LED “100” digit: display the third
group LED “1000”: display the
fourth group
LED “0” digit: display the first
group
The display content of LED “10”digit: display the
F4.14 the second line at the second group 1209 ● 0x40E
stop-state LED “100” digit: display the third
group LED “1000”: display the
fourth group
4.1.5 Motor Parameter Group
Pro Commun
Range of setting and Factory
No. Function description per ication
definition default ty address
F5.00 Reserved 〇 0x500
F5.01 Motor poles 2~48 4 〇 0x501
Model
F5.02 Motor rated power 0.4~1000.0kW 〇 0x502
setting
Model
F5.03 Motor rated frequency 0.01~Max. frequency 〇 0x503
setting
Model
F5.04 Motor rated torque 0~65000rpm 〇 0x504
setting
Model
F5.05 Motor rated voltage 0~1500V 〇 0x505
setting
Model
F5.06 Motor rated current 0.1~2000.0A 〇 0x506
setting
Model
F5.07 Motor no-load current 0.01~650.00A 〇 0x507
setting
Torque component
F5.14 0~1000 500 〇 0x50E
base

20
S200 building hoist integration special-purpose drive manual
4.1.6 Weighing Machine Alarm Recording Parameter Group
Commu
Range of setting and Factory Prop
No. Function description nication
definition default erty
address
Weighing alarm date
F7.00 2000~2099H -- × 0x700
year
Weighing alarm date
F7.01 0101~1939H -- × 0x701
month and day
Weighing alarm date
F7.02 0000~2969H -- × 0x702
hour and minute
F7.03 Weighing alarm weight 0~5000 -- × 0x703
Weighing alarm 1 date
F7.04 0101~1939H -- × 0x704
month and day
Weighing alarm 1 date
F7.05 0000~2969H -- × 0x705
hour and minute
Weighing alarm 1
F7.06 0~5000 -- × 0x706
weight
Weighing alarm 2 date
F7.07 0101~1939H -- × 0x707
month and day
Weighing alarm 2 date
F7.08 0000~2969H -- × 0x708
hour and minute
Weighing alarm 2
F7.09 0~5000 -- × 0x709
weight
Weighing alarm 3 date
F7.10 0101~1939H -- × 0x70A
month and day
Weighing alarm 3 date
F7.11 0000~2969H -- × 0x70B
hour and minute
Weighing alarm 3
F7.12 0~5000 -- × 0x70C
weight
Weighing alarm 4 date
F7.13 0101~1939H -- × 0x70D
month and day
Weighing alarm 4 date
F7.14 0000~2969H -- × 0x70E
hour and minute
Weighing alarm 4
F7.15 0~5000 -- × 0x70F
weight
Weighing alarm 5 date
F7.16 0101~1939H -- × 0x710
month and day
Weighing alarm 5 date
F7.17 0000~2969H -- × 0x711
hour and minute
Weighing alarm 5
F7.18 0~5000 -- × 0x712
weight

21
S200 building hoist integration special-purpose drive manual
Weighing alarm 6 date
F7.19 0101~1939H -- × 0x713
month and day
Weighing alarm 6 date
F7.20 0000~2969H -- × 0x714
hour and minute
Weighing alarm 6
F7.21 0~5000 -- × 0x715
weight
Weighing alarm 7 date
F7.22 0101~1939H -- × 0x716
month and day
Weighing alarm 7 date
F7.23 0000~2969H -- × 0x717
hour and minute
Weighing alarm 7
F7.24 0~5000 -- × 0x718
weight
4.1.7 V/F Control Parameter Group
Commu
Range of setting and Factory Prop
No. Function description nication
definition default erty address
0:linear
F8.00 V/F curve selection 0 〇 0x800
1:self-defined V/F curve
F8.01 Self set voltage V1 0.0~100.0% 3.0% 〇 0x801
F8.02 Self set frequency F1 0.00~max frequency 0.00Hz 〇 0x802
F8.03 Self set voltage V2 0.0~100.0% 6.5% 〇 0x803
F8.04 Self set frequency F2 0.00~max frequency 2.00Hz 〇 0x804
F8.05 Self set voltage V3 0.0~100.0% 12.0% 〇 0x805
F8.06 Self set frequency F3 0.00~max frequency 5.00Hz 〇 0x806
F8.07 Self set voltage V4 0.0~100.0% 22.0% 〇 0x807
F8.08 Self set frequency F4 0.00~max frequency 10.00Hz 〇 0x808
F8.09 Self set voltage V5 0.0~100.0% 100.0% 〇 0x809
F8.10 Self set frequency F5 0.00~max frequency 50.00Hz 〇 0x80A
Percentage of output
F8.11 25~100% 100% 〇 0x80B
voltage
Model
F8.12 Torque boost 0.1~30.0% 〇 0x80C
setting
Cut-off frequency of
F8.13 0.0~100.0% 20.0% 〇 0x80D
torque boost
V / F Slip
F8.14 0.0~200.0% 0.0% ● 0x80E
compensation
Uplink stop
F8.17 deceleration extended 0.00~50.00Hz 6.00Hz ● 0x811
frequency range
22
S200 building hoist integration special-purpose drive manual
Uplink stop
F8.18 deceleration time 0.50~50.00s 8.00s ● 0x812
variation range
Surge suppression
F8.19 0.0~500.0% 100.0% ● 0x813
ratio coefficient
Surge suppression
F8.20 5.00~25.00Hz 12.00Hz ● 0x814
start frequency
Random carrier
F8.21 0.000~5.000 1.000 ● 0x815
coefficient
Random carrier
F8.22 4.00~200.00Hz 6.00Hz ● 0x816
starting frequency
Random carrier when
F8.23 output frequency is 0.7~5.0KHz 1.5KHz ● 0x817
less than F8.22
Downlink self-defined
F8.27 0.0~100.0% 2.0% ● 0x81B
voltage V1
Downlink self-defined
F8.28 0.0~100.0% 5.0% ● 0x81C
voltage V2
Downlink self-defined
F8.29 0.0~100.0% 10.0% ● 0x81D
voltage V3
Downlink self-defined
F8.30 0.0~100.0% 20.0% ● 0x81E
voltage V4
Decelerate to a lower
F8.31 0.00~50.00Hz 1.00Hz ● 0x81F
gear frequency range
Time variation range
F8.32 0.50~50.00s 8.00s ● 0x820
when decelerating
F8.33 Restart delay 0.000~10.000s 0.100s ● 0x821

23
S200 building hoist integration special-purpose drive manual
‘0’digit: restart during
braking
0: Not allowed,
1: Allowed
‘00’digit: stop and forward
and reverse switching state
low frequency command
selection
0: invalid,
1: valid
”000”digit:lower gear
Comfort function
F8.34 frequency selection 0000H ● 0x822
selection 1
0: F0.08,
1: F9.13,
2:FC.00
”0000”digit:decelerate to low
gear deceleration time
handling selection
0: Invalid
1:up and down link
deceleration are both valid
2:only downlink deceleration
valid
Frequency variation
F8.35 0.00~5.00Hz 1.00Hz ● 0x823
range of low gear
4.1.8 Special Parameter Group
Commun
Range of setting and Factory Prop
No. Function description ication
definition default erty address
F9.00 FDT cut-off frequency 0.00~50.00Hz 2.50 ● 0x900
F9.01 FDT brake frequency 0.00~50.00Hz 6.00 ● 0x901
F9.03 Upward start delay 0.001~60.000s 0.000 ● 0x903
F9.04 Upward stop delay 0.001~60.000s 0.400 ● 0x904
F9.05 Downward start delay 0.001~60.000s 0.000 ● 0x905
F9.06 Downward stop delay 0.001~60.000s 0.000 ● 0x906
Weighing alarm function 0: valid
F9.07 0 ● 0x907
selection 1 1: invalid
0:No operation
Hoist cage weight
F9.08 1: Empty cage calibration 0 ● 0x908
calibration selection
2: Full load calibration
F9.09 Hoist cage calibration 0~10000 800 ● 0x909
F9.10 Body weight 0~500kg 70kg ● 0x90A

24
S200 building hoist integration special-purpose drive manual
F9.11 Full load weight 0~10000kg 2000kg ● 0x90B
F9.12 Load coefficient 0.0~200.0% 160.0% ● 0x90C
Torque boost cut-off
F8.13 0.0~100.0% 20.0% ● 0x90D
frequency
F9.14 X terminal delay 0~65.000 0 ● 0x90E
F9.15 MCU Software edition 0~9999 0 ● 0x90F
F9.16 Open brake: multiples 0~128 4 ● 0x910
f l kbrake:
Open h 0 current
F9.17 0~10000 200 ● 0x911
threshold
F9.18 Voice Select 0~1000 1000 ● 0x912
Input loss phase time
F9.19 0.50~10.00 1.50 ● 0x913
coefficient
F9.20 Password 1 0~FFFFH 0 ● 0x914
F9.21 Password 2 0~FFFFH 0 ● 0x915
F9.22 Password 3 0~FFFFH 0 ● 0x916
Cage top running
F9.23 0.0~50.00Hz 25.00 ● 0x917
frequency
4.1.9 Fault and Protection Parameter Group
Communi
Range of setting and Factory Prop
No. Function description cation
definition default erty
address
LED “0”digit: ACC
over-current protection
selection
0: Invalid
1: Valid
LED“00”digit: DEC
over-current protection
Protection function
FA.00 selection 0001 ● 0xA00
selection 1
0: Invalid
1: Valid
LED“000”digit: current limit
selection while running
0: Invalid
1: Valid
LED“0000”digit: reserved
LED “0”digit: DEC
Protection function over-voltage protection
FA.01 0001 ● 0xA01
selection 2 selection
0: Invalid

25
S200 building hoist integration special-purpose drive manual
1: Rating 1 over-voltage
protection
2: Rating 2 over-voltage
protection
LED “0”digit: Inverter
Overheat protection
selection
0: sudden stop and alarm
1: Emergency stop and
alarm
2: current limit running
LED “00”digit: Input loss
phase protection selection
0: Invalid
Protection function
FA.02 1: Valid 0210 ● 0xA02
selection 3
LED“000”digit: Output loss
phase protection selection
0: Invalid
1: Loss phase detection
valid, no associated with
open brake signal
2: Loss phase detection
valid,associated with open
brake signal
LED“0000”digit: Reserved
LED “0”digit: SC protection
selection
0: Invalid
1: Valid
Protection function LED“00”digit: OC protection
FA.03 0000 ● 0xA03
selection 4 selection
0: Invalid
1: Valid
LED“000”digit: reserved
LED“0000”digit: reserved
0: Fan runs after electrifying
1: Fan stop related to
temperature and work
FA.04 Fan control while running 1 ● 0xA04
2: Fan stop while machine
stop and run related to
temperature

26
S200 building hoist integration special-purpose drive manual
Energy braking action
FA.08 115.0%-140.0% 120.0% ● 0xA08
voltage
Bus under-voltage
FA.10 50.0%-100.0% 70.0% ● 0xA0A
protection
ACC OC protection
FA.15 100-250% 160% ● 0xA0F
point
DEC OC protection
FA.16 100-250% 160% ● 0xA10
point
Current limit level while
FA.17 100-250% 160% ● 0xA11
running
Current limit frequency
FA.18 ACC/DEC time while 0.00-650.00s 10.00s ● 0xA12
running
Pls see malfunction code
FA.25 Malfunction types -- × 0xA19
table
Malfunction running
FA.26 0.00~Max. frequency -- ×  0xA1A
frequency
Malfunction output
FA.27 0~1500V -- ×  0xA1B
voltage
Malfunction output
FA.28 0.1~2000.0A -- ×  0xA1C
current
Malfunction bus
FA.29 0~3000V -- ×  0xA1D
voltage
Malfunction module
FA.30 0~100℃ -- ×  0xA1E
temperature
LED “0”digit: Running
direction
0: Forward 1:Reverse
LED “00”digit: Running
Malfunction inverter
FA.31 state -- ×  0xA1F
state
0: Stop 1: Steady speed
2: ACC 3: DEC
LED “000”digit: Reserved
LED “0000”digit: Reserved
Malfunction input See input terminal chart
FA.32 -- ×  0xA20
terminal state
Malfunction output See output terminal chart
FA.33 -- ×  0xA21
terminal state
The last malfunction Pls see malfunction code
FA.34 -- ×  0xA22
type table
27
S200 building hoist integration special-purpose drive manual
The last malfunction
FA.35 0.00~Max. frequency -- × 0xA23
running frequency
The last malfunction
FA.36 0~1500V -- × 0xA24
output voltage
FA.37 The last malfunction 0.1~2000.0A -- × 0xA25
output current
FA.38 The last malfunction 0~3000V -- × 0xA26
bus voltage
FA.39 The last malfunction 0~100℃ -- × 0xA27
module temperature
LED “0”digit: Running
direction
0: FWD 1: REV
LED “00”digit: Running
FA.40 The last machine state state -- × 0xA28
0: Stop 1: Steady speed
2: ACC 3: DEC
LED “000”digit: Reserved
LED “0000”digit:Reserved
The last malfunction
FA.41 See input terminal chart -- × 0xA29
input terminal state
The last malfunction
FA.42 See input terminal chart -- × 0xA2A
output terminal state
FA.43 The last two Pls see malfunction code
-- × 0xA2B
malfunction types table
FA.44 The last three Pls see malfunction code
-- × 0xA2C
malfunction types table

28
S200 building hoist integration special-purpose drive manual
4.1.10 Special Application Functions
Pro Commu
Range of setting and Factory
No. Function description per nication
definition default
ty address
LED “0”digit: Running
enables abnormal alarm
0: invalid
Running 0 current alarm 1: valid
Fb.00 0011 〇 0xB00
selection LED “00”digit: Running 0
current alarm
0: invalid
1: valid
Running 0 current filter
Fb.01 0.020~1.000 0.100 ● 0xB01
time
Running 0 current judge
Fb.02 0~1000 200 〇 0xB02
threshold value
Low voltage adaptive
Fb.03 10~5000 500 ● 0XB03
filter coefficient
LED “0”digit: low voltage self
adaptive function
Low voltage adaptive 0: invalid 1: valid
Fb.04 0000 ● 0xB04
function selection LED “00”digit: Reserved
LED “000”digit: Reserved
LED “0000”digit:Reserved
Low voltage drop
Fb.05 0.0~100.0% 90.0% 〇 0xB05
frequency starting
Low voltage drop
Fb.06 frequency recovery 0.0~100.0% 92.0% ● 0xB06
voltage
Low voltage frequency
Fb.07 0.0~20.0% 5.0% ● 0xB07
offset adjustment
Fb.08 High gear frequency 0.00~200.00Hz 50.00 ● 0xB08
LED “0”digit: light load rising
frequency function
Light load rising
0: invalid
Fb.09 frequency function 0000 ● 0xB09
1: based on current
selection
2:based on weight
LED “00”digit: Reserved
Fb.10 Load measuring time 0.000~10.000s 1.000s ● 0xB0A
Exit judge current 1
Fb.11 0.0~150.0% 100.0% ● 0xB0B
when rising frequency

29
S200 building hoist integration special-purpose drive manual
Exit judge current 2
Fb.12 0.0~150.0% 50.0% ● 0xB0C
when rising frequency
Uplink overclock limit
Fb.13 0.00~100.00Hz 15.00Hz ● 0xB0D
value
Downlink overclock limit
Fb.14 0.00~100.00Hz 15.00Hz ● 0xB0E
value
Uplink rising frequency
Fb.15 0.0~100.0% 65.0% ● 0xB0F
judge value
Downlink rising
Fb.16 0.0~100.0% 45.0% ● 0xB10
frequency judge value
Weighing alarm
Fb.17 50.0~200.0% 105.0% ● 0xB11
coefficient
Frequency display
Fb.18 0.0~200.0% 100.0% ● 0xB12
proportional coefficient
Weighing sampling value
Fb.19 0.00~50.00 0.00 ● 0xB13
1
Weighing sampling value
Fb.20 0.00~50.00 0.00 ● 0xB14
2
Fb.21 Rate load weight 500~5000 2000 ● 0xB15
LED “0”digit:reserved
LED “00”digit: C-08 display
Elevator display function form selection
Fb.22 0000 ● 0xB16
selection 0: T(t)
1: Kg(kg)
LED “000”digit: Reserved
4.1.11 Multi speed, fault time record parameters
Pr Commun
Range of setting and Factory op
No. Function description ication
definition default ert
y address
FC.00 PLC multi speed 1 0.00~320.00Hz 5.0 ● 0xC00
See in fault information
FC.15 Fault code -- × 0xC0F
code list
FC.16 Fault date year 2000~2099H -- × 0xC10
FC.17 Fault date month and day 0101~1939H -- × 0xC11
FC.18 Fault date hour and minute 0000~2969H -- × 0xC12
FC.19 Fault MCU board state 0000~FFFFH -- × 0xC13
FC.20 Fault output frequency 0.00~max frequency -- × 0xC14
See in input terminal status
FC.21 Fault input state -- × 0xC15
diagram

30
S200 building hoist integration special-purpose drive manual
See in output terminal
FC.22 Fault output state -- × 0xC16
status diagram
See in fault information
FC.23 Fault 1 code -- × 0xC17
code list
FC.24 Fault 1date year 2000~2099H -- × 0xC18
FC.25 Fault 1 date month and day 0101~1939H -- × 0xC19
FC.26 Fault 1 date hour and minute 0000~2969H -- × 0xC1A
FC.27 Fault 1 MCU board state 0000~FFFFH -- × 0xC1B
FC.28 Fault 1 output frequency 0.00~max frequency -- × 0xC1C
See in input terminal status
FC.29 Fault 1 input state -- × 0xC1D
diagram
See in output terminal
FC.30 Fault 1 output state -- × 0xC1E
status diagram
See in fault information
FC.31 Fault 2 code -- × 0xC1F
code list
FC.32 Fault 2 date year 2000~2099H -- × 0xC20
FC.33 Fault 2 date month and day 0101~1939H -- × 0xC21
Fault 2 date hour and
FC.34 0000~2969H -- × 0xC22
minute
FC.35 Fault 2 MCU board state 0000~FFFFH -- × 0xC23
FC.36 Fault 2 output frequency 0.00~max frequency -- × 0xC24
See in input terminal status
FC.37 Fault 2 input state -- × 0xC25
diagram
See in output terminal
FC.38 Fault 2 output state -- × 0xC26
status diagram
See in fault information
FC.39 Fault 3 code -- × 0xC27
code list
FC.40 Fault 3 date year 2000~2099H -- × 0xC28
FC.41 Fault 3 date month and day 0101~1939H -- × 0xC29
Fault 3 date hour and 0000~2969H
FC.42 -- × 0xC2A
minute
FC.43 Fault 3 MCU board state 0000~FFFFH -- × 0xC2B
FC.44 Fault 3 output frequency 0.00~max frequency -- × 0xC2C
See in input terminal status
FC.45 Fault 3 input state -- × 0xC2D
diagram
See in output terminal
FC.46 Fault 3 output state -- × 0xC2E
status diagram
See in fault information
FC.47 Fault 4 code -- × 0xC2F
code list

31
S200 building hoist integration special-purpose drive manual
FC.48 Fault 4 date year 2000~2099H -- × 0xC30
FC.49 Fault 4 date month and day 0101~1939H -- × 0xC31
Fault 4 date hour and 0000~2969H
FC.50 -- × 0xC32
minute
FC.51 Fault 4 MCU board state 0000~FFFFH -- × 0xC33
FC.52 Fault 4 output frequency 0.00~max frequency -- × 0xC34
See in input terminal status
FC.53 Fault 4 input state -- × 0xC35
diagram
See in output terminal
FC.54 Fault 4 output state -- × 0xC36
status diagram
4.1.12 Communication Control Function Parameter Group
Pr
Commun
Range of setting and Factory op
No. Function description ication
definition default ert
address
y
Main-slave machine 0: Main machine
Fd.00 0 〇 0xD00
selection 1: Slave machine
Fd.01 Machine address 1~247 1 〇 0xD01
Communication baud rate
Fd.02 3: 9600bps 3 〇 0xD02
selection
Fd.03 Date format 0:(N 8 1)No checkout 0 〇 0xD03
Communication proportional
Fd.04 setting 0.00~5.00 1.00 ● 0xD04
Fd.05 Communication answer delay 0~500ms 0ms ● 0xD05
Communication overtime
Fd.06 fault time 0.1~100.0s 1.0s ● 0xD06
0: Alarm and stop freely
1: No alarm and running
2: Stop and no alarm
(Running command
RS485 Communication fault
Fd.07 given by communication) 4 ● 0xD07
action mode selection
3: Stop and no alarm
(Running command
given by all channel)
4: Alarm and stop
0:Write operation with
Transmission response response
Fd.08 1 ● 0xD08
handling 1:Write operation without
response
Note: Except the special definition function, more details for the rest functions, please refer
to the <AC80B series frequency inverter manual>.
32
S200 building hoist integration special-purpose drive manual
4.2 Special Function Specific Explanation
4.2.1 The calibration weighing function:
1.Only one person stand in the cage, and set the weight of the person into the parameter
F9.10,unit:kg.
2.Cage weight calibration: long press the empty cage calibration button for 3s or set F9.08 for 1 to
process the cage weight calibration. The buzzer will emit a sound after the calibrating. And F9.08
will reset for 0, and set the weight of cage value to F9.09.
3.Weight coefficient calibration: Add suitable weight to the cage(recommend full load 2000kg),set
the weight to parameter F9.11,then set the parameter F9.08 as 2 to do the weight coefficient
calibration, after finishing set back F9.08 as 0,coefficient save in F9.12.If the value after calibration
meets the requirement, then there’s no need to do the weigh coefficient calibration.
4.Rated load weight: the rated load weight of construction elevator can be set by Fb.21.
4.2.2 Weight test
If not the full load calibration, can add the weight and refer to the C-08 and see if the parameter
display is same with added weight or not, if same, then calibration success. Also can add the weight
till the value of the add weight and the display number is the same.
4.2.3 Light Load Acceleration Function
Fb.08 High gear frequency 0.00~200.00Hz 50.00
LED “0”digit: light load rising
frequency function
Light load rising frequency
Fb.09 0: invalid 0000
function selection
1: based on current
2:based on weight
Fb.10 Light load measuring time 0.000~10.000s 1.000s
Exit judge current 1 when rising
Fb.11 0.0~150.0% 100.0%
frequency
Exit judge current 2 when rising
Fb.12 0.0~150.0% 50.0%
frequency
Fb.13 Uplink overclock limit value 0.00~100.00Hz 15.00Hz
Fb.14 Downlink overclock limit value 0.00~100.00Hz 15.00Hz
Uplink rising frequency judge
Fb.15 0.0~100.0% 65.0%
value
Downlink rising frequency judge
Fb.16 0.0~100.0% 45.0%
value
When the output frequency is Fb.08, maintain Fb.09 setting time and judge the upscaling value,
upscale if upscaling conditions are met. Judge the current as an example: Uplink,upscale when the
33
S200 building hoist integration special-purpose drive manual
output current (% of motor rated current) is less than Fb.15, the elevated frequency is set by Fb.13.
Downlink, upscale when the output current (% of motor rated current) is less than Fb.16,the
elevated frequency is set by Fb.14. If the current in the process of upscaling is greater than the
judge value of exit current, then exit upscaling.50Hz corresponds to Fb.11,100Hz corresponds to
Fb.12 and implement linear calculation with the output frequency to get the judge value of exit
current.
4.2.4 Low Voltage Self Adaptive Function
Low voltage self adaptive filter
Fb.03 10~5000 500
coefficient
LED “0”digit:Low voltage self
Low voltage self adaptive function
Fb.04 adaptive function 0000
selection
0: invalid 1: valid
Low voltage frequency falling start
Fb.05 0.0~100.0% 90.0%
voltage
Low voltage frequency falling
Fb.06 0.0~100.0% 92.0%
recovery voltage
Low voltage frequency bias
Fb.07 0.0~20.0% 5.0%
adjustment
When bus voltage falls below Fb.05, appropriately reduce the output frequency to prevent the motor
turning into the high-frequency weak magnetic field, which can effectively ensure the motor output;
when the bus voltage is greater than Fb.06, exit voltage fall, and accelerate to the set frequency
according to the acceleration time.
4.3 Monitor code
Press “PRG” key more than 2 seconds, enter “C” parameter group.
Communicat
No. Function name Unit of setting and definition
ion add.
C-00 Given frequency 0.01Hz
C-01 Output frequency 0.01Hz
C-02 Output current 0.1A
C-03 Input voltage 0.1V
C-04 Output voltage 0.1V
C-05 Machinery speed 1RPM
C-06 Setting torque 0.1%
C-07 Output torque 0.1%
C-08 Load display 0.1T/1kg
C-09 Load percentage display 0.1%
C-10 Output power 0.1%
C-11 Bus voltage 0.1V
C-12 Module temperature 1 0.1℃
C-13 Module temperature 2 0.1℃
C-14 Input terminal X on- state See input terminal state chart

34
S200 building hoist integration special-purpose drive manual
C-15 Output terminal Y on- state See output terminal state chart
C-16 Analog VS1 input 0.001V
C-17 Analog VS2 input 0.001V
C-18 Analog AS input 0.001mA
C-19 Impulse single PUL input 0.001kHz
C-20 Analog output AO1 0.01V
C-21 Analog output AO2 0.01V/0.01mA/0.01kHz
C-22 Counting value of counter
C-23 Running time after electrify(of this time) Hour
C-24 Local accumulative running time 0.1h
C-25 Inverter power level kW
C-26 Inverter rated voltage V
C-27 Inverter rated current A
C-28 Software edition
C-29 PG feedback frequency 0.01Hz
Input terminal on/off show diagram

X1 state X8 state
X2 state X7 state
X3 state X6 state
X4 state X5 state

input terminal on input terminal off


Output terminal on/off show diagram

Y1 state Reserved
Y2 state Reserved

TA TB TC state Reserved
Reserved Reserved

output terminal on output terminal off

35
S200 building hoist integration special-purpose drive manual

5. Fault information and details


Keyboard Fault
Fault type Possible causes Treatment
display code
● Power supply is too
● Check input power,
Too low low
L.U.1 eliminate fault.
while stop ● Voltage detection
● Seek support from factory.
circuit is abnormal
● Power supply is too
low
● Check input input power,
● Power capacitance is
Too low eliminate fault.
too small, or there is big
E.LU2 voltage in ● Improve power-supply
impact current in the
run system.
power grid.
● Seek support from factory.
● Inner DC main
contactor is not closed.
● Detect power voltage and
● Power voltage
Acc eliminate fault.
E.oU1 fluctuation over limit.
over-voltage ● Restart motor until it totally
● Start running motor.
stop. Set F1.00 as 1or 2.
● Prolong deceleration time
● Deceleration time is
properly.
too short.
● Reduce load inertia or
Dec ● Load potential energy
E.oU2 improve inverter capacitance
over-voltage or inertia is too large.
or add braking unit.
● Power voltage
● Detect input power and
fluctuation over limit.
clear fault.
Constant ● Detect input power voltage
● Power voltage
E.oU3 speed and eliminate fault.
fluctuation over limit.
over-voltage ● Install input reactor.
● Check input power,
Over-voltage ● Power voltage
E.oU4 eliminate fault.
while stop fluctuation over limit.
● Seek support from factory.
● Acceleration time is
● Prolong acc time.
too short.
● Restart motor until it totally
● Start running motor.
stop. Set F1.00 as 1or 2.
Acc ● V/F curve setting is
E.oC1 ● Reset V/F curve or torque
over-current not suitable. Or torque
boost value.
boost too high.
● Select inverter with right
● Inverter capacitance is
capacitance.
too small.

36
S200 building hoist integration special-purpose drive manual
● Deceleration time is
● Prolong deceleration time.
too short.
● Connect external braking
Dec ● Load potential energy
E.oC2 resistance or braking unit.
over-current or inertia is too large.
● Select inverter with right
● Power voltage
capacitance.
fluctuation over limit.
● Check load change and
Constant ● Sudden load change.
eliminate it.
E.oC3 speed ● Power grid voltage is
● Check input power,
over-current too low.
eliminate fault.
● Reset V/F curve or torque
● V/F curve setting is
boost value.
not suitable. Or torque
● Check input power,
boost too high.
eliminate fault.
● Power grid voltage is
● Unreasonable F5.06
too low.
Motor setting.
E.oL1 ● wrong overload
over-load ● Adjust load or select
protection setting.
inverter with right
● Locked-rotor run or
capacitance.
too heavy load.
● If need long low-speed
● Universal motor long
operation, please choose
time low speed run.
special motor for inverter.
● Load is too heavy. ● Select inverter with right
● Acceleration time is capacitance.
too short. ● Prolong acceleration time
Inverter
E.oL2 ● Start running motor. ● Restart motor until it totally
over-load
● V/F curve setting is stop. Set F1.00 as 1or2.
not suitable. Or torque ● Reset V/F curve or torque
boost too high. boost value.
● Prolong acceleration time
● Acceleration time is
properly.
too short.
● Check periphery
● Short circuit between
equipment and restart after
System inverter output phases
E. SC fault eliminating.
abnormality or earth.
● Seek support from factory.
● Module is damaged.
● Check system wiring,
● Electromagnetic
earth, shield and deal as
disturb.
required.
● Temperature is too ●Make the environment
Inverter high. meet the requirement.
E.oH1
over-heat ● Air channel is blocked. ● Clear the air channel.
● Fan connection parts ● Check and reconnect the

37
S200 building hoist integration special-purpose drive manual
is loose. wire
● Fan is damaged. ● Change the same new
● Temperature detection fan.
circuit fault ● Seek support from factory.
● Temperature is too ● Make the environment
high. meeting the requirement.
● Air channel is blocked. ● Clear the air channel.
Rectifier ● Fan connection parts ● Check and reconnect the
E.oH2
over-heat is loose. wire.
● Fan is damaged. ● Change the same new
● Temperature detection fan.
circuit fault ● Seek support from factory.
● Detection overtime
● Start static detection ● Check motor connection
while motor is running. wire.
Motor static ● Capacitance ● Detect after motor
E.TE1 detection difference is too big stopping totally.
fault between motor and ● Change inverter model.
inverter. ● Reset parameter
● Motor parameter according to nameplate.
setting mistake.
● Detect while motor is
running. ● Detect after motor stop
● Detect with load. totally.
Moror ● Detection overtime ● Re-detect without load.
rotation ● Capacitance ● Check motor connection
E.TE2
detection difference is too big wire.
fault between motor and ● Change inverter model.
inverter. ● Reset parameter
● Motor parameter
according to nameplate.
setting mistake.
● Electromagnetic
Memory disturb in memory ● resume load and save.
E.EEP
fault period. ● Seek support from factory.
● EEPROM damage.

LIFE Reserved ● ● Seek support from factory.

● Check 3-phase power


Input side ● 3-phase input power supply and the phase.
E.ILF
open phase open phase. ● Check 3-phase power
supply wiring.

38
S200 building hoist integration special-purpose drive manual
● Check 3-phase output
Ouput side ● 3-phase output power
E.oLF voltage and current.
open phase open phase
● Check wiring.
Output ● Output earth terminal ● Check wiring and
E.Gnd
earth short circuit. insulation.
Current
● Detect circuit fault. ● Seek for technic support.
E.HAL detection
● Phase imbalance ● Check motor and wiring.
fault
Inverter
● Peripheral equipment ● Check peripheral
E. EF external
fault protection. equipment.
fault
Keyboard ● Keyboard wire fault.
● Check keyboard wire.
E.PAn connect ● Keyboard component
● Seek support from factory.
fault damage.
● Unsuitable baud rate
● Set suitable baud rate
setting.
setting.
Rs485com ● Communication wire
● Check communication
E. CE munication breaks.
wire.
fault ● Communication
● Set right communication
format does not match
format.
upper machine.
● implement empty cage
●load exceeds limit
Weighing calibration
E. PG ●pin-axis transducer
pre-alarm ● check pin-axis
fault
transducer
●motor and inverter
Running 0
connecting fault ● check motor wiring
E.Fb2 current
●current measuring ● check Hall line interface
fault
fault
● Parameter copy
● Check wire.
Parameter communication is fault.
E.CPE ● Select the specified
copy fault ● Copy keyboard is not
external keyboard model.
match the inverter.

39
S200 building hoist integration special-purpose drive manual

6. Quality Guarantee
The quality assurance of product would be implemented as follows:
Users can enjoy the following “three guarantee” services from the day of buying products if there
are products quality problems:
●Within 30 days after shipment,the company promises returning,replacement and maintenance of
the product.
●Within 90 days after shipment,the company promises replacement and maintenance of the
product.
●Within 18 months after shipment,the company promises only maintenance of the product.
●Products exported to countries except China shall not enjoy the warranties mentioned above.
Since the date of purchase, users can enjoy the service of the company when they pay for the
service..
Our company only takes on the liability according to our guarantee time and range. If you need
more liability guarantee, you should buy proper commercial insurance from insurance company in
advance. The other extended loss caused by malfunctions of our product is not within our
guarantee range.
Product failures caused by the following reasons would not enjoy the free warranty services of the
manufacturer:
●Failures caused by operations of users that is not operated in accordance with the requirements
of the product manual;
●Failures caused when users repair or renovate the product without communicating with the
manufacturer in advance;
●Failures caused by abnormal aging of the product resulted from poor using environment;
●Failures caused by earthquake, fire or other natural disasters or abnormal voltage;
For products that enjoy all returning,replacement and maintenance services, first the product should
be returned to the company and after responsibility confirmation,the product can be replaced or
repaired.

40
S200 building hoist integration special-purpose drive manual

Appendix 1: Lift common faults and maintenance


 Press the start button but can not running
A. Check the key switch if in “ON” state or not.
B. Check the emergency switch if unscrew pop- up or not.
C. Check the safety catcher is moving or not, or see the contactor is disconnect or not.
D. Check the monitor panel “Emergency stop in cage” “Emergency stop in case of drop”
indicator is “on” or not.
E. Check the “start” button, and observe MCU board “start” is “on” or not.
 Normal start, the main operating handle can not upward.
A. Push the main handle to upward, and observe MCU board “start” is “on” or not.
B. Check the monitor panel “upper limit” indicator normal or not (on).
C. Check the monitor panel “threshold” indicator normal or not (on).
D. If above all is normal, then observe monitor panel ,and see if have the upward state
indicator or not.
 Normal start, the main operating handle can not downward.
A. Push the main handle to downward, and observe MCU board “start” is “on” or not.
B. Check the monitor panel “upper limit” indicator normal or not (on).
C. Check the monitor panel, “threshold” indicator normal or not.
D. If above all is normal, then observe monitor panel , and see if have the downward
state indicator or not.
 Upward or downward only have low speed ,no have high speed
A. Push the main handle to the max. position(upward and downward),and observe monitor
panel “Lord to accelerate” indicator normal or not.
B. Attention the cage still in low speed position or not, and observe monitor panel
“decelerate limit” indicator normal or not.
C. If cage already away from the low speed position, “decelerate limit” indicator still not “on”,
then check the speed limit switch if have bad contact or machinery reason.
 Bad comfort level in running state, having drop and over pulse phenomenon when
upward.
A. “Caused by wrong connection between command “upward” and “downward”:When
connect the main handle upward, make sure the lift is on “upward” state and the key
is always on “ON ”state. When connect the main handle upward, make sure the lift is on
“downward” state and the key is always on “twinkle ” state.

41
S200 building hoist integration special-purpose drive manual
 Power-on trip the cage or residual-current circuit breaker.
A. Motor have the “outside short circuit”, “case”, “water” phenomenon, check the motor
insulation.
B. External connection of brake resistor have the short circuit to earth, case.
 rip the residual-current circuit breaker while in running occasionally.
A. As for the output signal of inverter is high frequency PWM, so will generate a certain
mount of high frequency leakage current, please choose residual-current circuit breaker
which current sensitivity above 200mA,action time more than 0.1S.
B. Choose B type leakage protection switch, and pulse current sensitivity RCD which have
high frequency filter and delay function.
C. Adjust parameter “F0.17=0.7-1.0, F0.18=1000” can reduce the trip time of leakage
breaker, but motor noise will increase.
D. Please check if the branch line have connect other equipment or not, if connect, pls
disconnect.
 Power on but inverter no display
A. First confirm input R,S,T, supply voltage if normal or not.
B. If R,S,T input normal, then show the soft starter resistance(20Ω/80W) broken.
C. The soft starter resistance broken have some reason: check the resistance if short circuit
or form a circuit, on power-on moment and before contactor close, big current flow the
soft starter resistance.
 Running and display fault
A. Check the 3 phase power if have phase loss or voltage unbalance phenomenon.

 Running and display fault


A. Check the motor connection line.
B. Measure inverter 3 phase output voltage if balance.

 Upward normal, but downward 60cm inverter display short circuit fault.
A. External brake resistance short circuit.
 Main handle run the upward or downward, inverter display short circuit
fault.
A. Dismantle motor line, if get normal, then one of the motor winding have the short circuit
fault.
B. Dismantle motor line, if get normal, then motor parameter have wrong setting.
C. Dismantle motor line, still in fault, then the inner part of inverter have the short circuit.
D.

42
S200 building hoist integration special-purpose drive manual
 “under-voltage” fault while in running state
A. Transformer capacity is too small, cable too long, wire diameter too thin, these caused
big pressure drop while in running.
B. Main contactor not closed.
 “Over current” fault and while in running state
A. Check the brake is open or not.
B. Check the machinery part have the phenomenon of stuck-locked or not.
C. Check the cable and see if have broken or short circuit.
D. Check the power voltage if too low or too high.
 “Over load” fault and while in running state
A. Too heavy load, check if overload running or other machinery fault.
B. Brake is no action or not open, please check.
C. Grid voltage too low.
 “Over heat” fault and while in running state
A. Check fan is running or not, if not run,change the cooling fan.
B. If the air duct block or not.
C. If the environment temperature is too high or not.
 Downward while in running or main handle drop to zero
“over voltage” fault.
A. Resistance broken or electric line disjointed.
B. Sheet resistance of the resistance is too high, power too low, easy to get error.

43