MLII Modbus Mapping Manual FV 4-33-05

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 118

MultiLoad II

MODBUS MAPPING
MultiLoad II, MultiLoad II SMP,
Multiload II SCS

June 2020
Firmware version 4.33.05
TOPTECH SYSTEMS

MultiLoad II
MODBUS MAPPING

© Toptech Systems
1124 Florida Central Parkway
Longwood, FL 32750
Phone 407.332.1774

Copyright Notice
Copyright © 2006 - 2020 Toptech Systems, Inc. All Rights Reserved.
The information contained in this document is proprietary and confidential. No part of this document may be copied, reproduced, or transmitted in any
medium without the express written permission of Toptech Systems, Inc.

Disclaimer
Toptech Systems assumes no responsibility for damages resulting from installation or use of its products. Toptech Systems will not be liable for any claims of
damage, lost data, or lost time as a result of using its products.

MultiLoad II – Modbus Mapping


Table of Contents

Chapter 1 Getting Started .......................................................... 6


Register Numbering ................................................................................. 6
Data Types............................................................................................... 6
1.2.1 Configuration Data Types ......................................................................................6

ASCII Table.............................................................................................. 7
Protocol Selection .................................................................................... 8
Chapter 2 Protocol Specification ............................................ 9
Modbus RTU protocol .............................................................................. 9
2.1.1 Read Holding Registers (fn=3) ...............................................................................9

2.1.2 Write Single Registers (fn=6) ............................................................................... 10

2.1.3 Loopback/Maintenance (fn=8) ............................................................................. 10

2.1.4 Preset Multiple Registers (fn=16) ......................................................................... 10

2.1.5 Error Responses (fn= +128) ................................................................................ 11

Modbus TCP-IP protocol ........................................................................ 11


2.2.1 Read Holding Registers (fn=3) ............................................................................. 12

2.2.2 Write Single Registers (fn=6) ............................................................................... 13

2.2.3 Loopback/Maintenance (fn=8) ............................................................................. 13

2.2.4 Preset Multiple Registers (fn=16) ......................................................................... 13

2.2.5 Error Responses (fn= +128) ................................................................................ 14

Extended Service Registers ................................................................... 14


Chapter 3 Information/Definition Registers ....................... 16
MultiLoad Information Registers ............................................................ 16
Communication Registers ...................................................................... 16
BOL Registers........................................................................................ 16

i
Hazard Registers ................................................................................... 18
Product Registers .................................................................................. 19
Driver Database Registers ..................................................................... 20
GPS Site Database Definitions .............................................................. 20
Bilingual Message Support .................................................................... 21
Log Message Registers ......................................................................... 21
Transaction Registers .......................................................................... 21
Custom Logic Registers....................................................................... 22
Chapter 4 Configuration Registers ....................................... 24
Configuration Data Types ...................................................................... 24
Configuration Indexing ........................................................................... 33
RCU Level Configuration Registers ....................................................... 34
Bay Level Configuration Registers ......................................................... 36
Preset Configuration Registers .............................................................. 37
Component Configuration Registers ...................................................... 41
Additive Configuration Registers ............................................................ 44
Chapter 5 Real -Time Registers ............................................. 47
Real-Time Totalizer Registers................................................................ 47
5.1.1 Real-Time Preset Gross Totalizer ........................................................................ 47

5.1.2 Real-Time Meter Gross Totalizer ......................................................................... 47

5.1.3 Real-Time Component Gross Totalizer ................................................................ 49

5.1.4 Real-Time Additive Gross Totalizer ...................................................................... 51

5.1.5 Real-Time Preset Net Totalizer ............................................................................ 56

5.1.6 Real-Time Component Net Totalizer .................................................................... 57

5.1.7 Real-Time Preset Mass Totalizer ......................................................................... 59

5.1.8 Real-Time Component Mass Totalizer ................................................................. 59

Real-Time Value Registers .................................................................... 62

2
5.2.1 Preset quantity in whole units .............................................................................. 62

5.2.2 Preset Delivered Gross Quantity in Whole Units .................................................. 62

5.2.3 Preset Delivered Net Quantity in Whole Units ...................................................... 63

5.2.4 Preset Batch Average Temp in Tenths or Hundredths .......................................... 63

5.2.5 Batch Average Pressure in Tenths or Hundredths................................................ 63

5.2.6 Preset Batch Average Density/Relative Density/Gravity ....................................... 64

5.2.7 Preset Gross Flow Rate in Whole Units ............................................................... 64

5.2.8 Meter Delivered Gross Quantity in Whole Units ................................................... 65

5.2.9 Meter Gross Flow Rate in Whole Units ................................................................ 66

5.2.10 Component Delivered Gross Quantity in Whole Units......................................... 68

5.2.11 Component Delivered Net Quantity in Whole Units ............................................ 70

5.2.12 Component Batch Average Temp in Tenths or Hundredths ................................ 73

5.2.13 Component Batch Average Pressure in Tenths or Hundredths ........................... 75

5.2.14 Component Batch Average Density/Relative Density/Gravity ............................. 78

5.2.15 Component Current Temp in Hundredths........................................................... 80

5.2.16 Component Current Pressure in Hundredths...................................................... 83

5.2.17 Component Current Density in Tenths ............................................................... 85

5.2.18 Additive Delivered Quantity in Thousands .......................................................... 87

5.2.19 Component Current Relative Density in Ten Thousands .................................... 92

5.2.20 Component Current BSW Hund ......................................................................... 95

5.2.21 Component Current API Gravity Tenths ............................................................. 97

5.2.22 Component Current Mass Delivered ................................................................ 100

Chapter 6 Alarm Registers .................................................... 101


Alarm Messages .................................................................................. 101
6.1.1 Bay Alarm Messages......................................................................................... 101

6.1.2 Preset Alarm Messages..................................................................................... 101

6.1.3 Meter Alarm Messages ...................................................................................... 102

3
6.1.4 Component Alarm Messages............................................................................. 102

6.1.5 Additive Alarm Messages .................................................................................. 102

Trip Preset Alarms ............................................................................... 102


Request Alarms ................................................................................... 103
6.3.1 Request Preset Alarms ...................................................................................... 103

6.3.2 Request Bay Alarms .......................................................................................... 103

6.3.3 Request Component Alarms .............................................................................. 103

6.3.4 Request Meter Alarms ....................................................................................... 106

6.3.5 Request Additive Alarms ................................................................................... 107

Chapter 7 Preset Status Registers ..................................... 113


Preset State ......................................................................................... 113
Preset Status ....................................................................................... 113
State/Status Registers ......................................................................... 114
Start Preset Flow ................................................................................. 114
Stop Preset Flow.................................................................................. 114

4
MULTILOAD II – MODBUS MAPPING

Overview
This document is designed to guide users through the available Modbus registers within the MultiLoad. It will help
users quickly setup Modbus communication with the MultiLoad to reference status and value register addresses
and configurable details.

The following table provides an information map to the material available in this guide.

Chapter Topics Covered


1.Getting Started Modbus Register numbering, data types and communication.

2.Protocol Specification Protocol used to reference Modbus registers and return information.

3.Information/Definition Registers Definitions of Modbus register addresses, data type, read/write permissions,
min/max value and preset/meter/component/additive assignment.

4.Real-Time Registers Addresses of real-time totalizers and value registers.

5.Alarm Registers Addresses of preset, meter, component and additive registers.

6.Preset Status Addresses of preset state, status and flow.

The following keys make it easier to find the information you need in this guide:

ICON KEY
Important information to enhance understanding and make better use of the product.

See MultiLoad Communications Manual.

Note that this guide covers MultiLoad II Modbus Mapping information only. For information about base MultiLoad
firmware please consult the MultiLoad II User Guide. For information about wiring other models please consult
the respecetive Installation Guides. For information about the MultiLoad register interface and Modbus
communication, please reference the MultiLoad II Communication Guide. Updated versions of all manuals,
including this one, are available on our website at http://www.toptech.com.

5
MULTILOAD II – MODBUS MAPPING

1
Chapter

Chapter 1 Getting Started

Before getting started, it is good to know the standard Modbus connection equipment, communication
configuration and data type information. This topic also provides some basic communications concepts, as well as
Toptech's recommendations for achieving optimum performance. Understand the format type that is being used
and their charactersistics as well as the ASCII codes.

Host communication can occur via multi-dropped RS-232/RS-485 serial on COM 1 or Ethernet 10/100 socket
communication on port 7734. Port 7735 supports SSL encryption (TLS v1.2 only for security reasons) and can be
enabled via the network setup screen.

Register Numbering
Modbus registers start at 0 and extend to 13024. Modbus registers are either 16-bit or 32-bit depending on the
data field it represents and 32-bit modbus registers are evenly addressed. When referencing a preset, meter
component or meter, the modbus registers are incremented based on the max quantity available within a
MultiLoad configuration.

Data Types
There are six different data types for Modbus registers shown in the table below. Char means a character
value based on the ASCII value seen in Table 1.3. Integer data types include signed and unsigned. The max
for a 16-bit register is 65,535 and 4,294,967,296 for a 32-bit register. However, most MultiLoad registers
maximum values are 1,000,000,000 before they roll over.
Data Type Description Min Value Max Value
char Numerical 48 57
char Alphabetical 32 122
uint unsigned integer 0 65535
int signed integer -32768 32767
u long int unsigned long int 0 4294967295
perc percent 0.00% 100.00%

1.2.1 Configuration Data Types


These data types are represent in the configuration modbus registers as implied decimals.

6
MULTILOAD II – MODBUS MAPPING

Data Type Description


signed div 10 Positive or negative value with tenths place of a decimal
signed div 100 Positive or negative value hundreths place of a decimal
unsigned div 100 Value with hundreths place of a decimal
unsigned div 1000 Value with thousandsths place of a decimal

ASCII Table
Characters in MultiLoad modbus are represented by their ASCII Decimal value. For example, A=65 a=97
Decimal Char Decimal Char Decimal Char
32 [Space] 63 ? 94 ^
33 ! 64 @ 95 _
34 " 65 A 96 `
35 # 66 B 97 a
36 $ 67 C 98 b
37 % 68 D 99 c
38 & 69 E 100 d
39 ‘ 70 F 101 e
40 ( 71 G 102 f
41 ) 72 H 103 g
42 * 73 I 104 h
43 + 74 J 105 i
44 , 75 K 106 j
45 - 76 L 107 k
46 . 77 M 108 l
47 / 78 N 109 m
48 0 79 O 110 n
49 1 80 P 111 o
50 2 81 Q 112 p
51 3 82 R 113 q
52 4 83 S 114 r
53 5 84 T 115 s
54 6 85 U 116 t
55 7 86 V 117 u
56 8 87 W 118 v
57 9 88 X 119 w
58 : 89 Y 120 x
59 ; 90 Z 121 y
60 < 91 [ 122 z
61 = 92 \
62 > 93 ]

7
MULTILOAD II – MODBUS MAPPING

Protocol Selection
See MultiLoad Communications Manual for more information on Protocol Selection.

8
MULTILOAD II – MODBUS MAPPING

2
Chapter

Chapter 2 Protocol Specification

Modbus RTU protocol


The Modbus-RTU protocol has been implemented to be as compatible as possible with the original published
Modicon Modbus-RTU standard.
Note: The Modbus protocol allows parameter register access only as defined by the explicit mapping in
this manual. To send the ASCII commands (R000, T`A, MAM, MRS, etc.) that are handled by the other three
protocols; the Modbus Extended Services registers must be used.
Using the Modbus protocol, MultiLoad accepts data in the following format:

Quiet Time ADR FN ... CRC1 CRC2 Quiet Time

Modbus-RTU protocol messages are framed by a quiet time of three and one-half characters.
ADR is binary character of the address of the MultiLoad, typically 0x01.
Fn is the Modbus function. Functions implemented are as follows.
The formal specification of Modbus lists the starting Holding Register address as 40001. The Modbus
Holding Register functions (Fn 3, 6 and 16) all have an implied 4XXXX reference. Referencing Holding
Register 40001 is addressed as register 0000 in the register address field in the message for fn 3, 6 and 16.
Since Modbus addressing has been implemented in various ways over the years, to avoid confusion in this
manual, the Modbus Holding Register addresses listed are the value in the register address field in the message.
If it is necessary to know the formal Modbus Holding Register address, simply add 40001 to the register
addresses listed in the manual.

2.1.1 Read Holding Registers (fn=3)


Note: Both Modbus registers MUST be read at the same time when reading 32-bit values.
Tx:

Number
Start Start Number of
Of
Quiet Time ADR FN=3 Register Register Registers CRC1 CRC2 Quiet Time
Registers
MSB LSB LSB
MSB

Rx:

FN=3 1st 1st Next Next


Quiet Byte Quiet
ADR (+128 if Register Register Register Register … CRC1 CRC2
Time Count Time
error) MSB LSB MSB MSB

9
MULTILOAD II – MODBUS MAPPING

2.1.2 Write Single Registers (fn=6)


Note: cannot be used for 32-bit registers.

Tx:

Start Start
Register Register
Quiet Time ADR FN=6 Register Register CRC1 CRC2 Quiet Time
MSB LSB
MSB LSB

Rx:

FN=6 Start Start


Register Register
Quiet Time ADR (+128 if Register Register CRC1 CRC2 Quiet Time
MSB LSB
error) MSB LSB

2.1.3 Loopback/Maintenance (fn=8)


Note: only loopback of command supported.
Tx:

Diagnostic Diagnostic
Quiet Time ADR FN=8 Data MSB Data LSB CRC1 CRC2 Quiet Time
Code MSB Code LSB

Rx:

Diagnostic Diagnostic
Quiet Time ADR FN=8 Data MSB Data LSB CRC1 CRC2 Quiet Time
Code MSB Code LSB

2.1.4 Preset Multiple Registers (fn=16)


Note: Both Modbus registers MUST be written at the same time when writing 32-bit values.
Tx:

Number
Number
Start Start
Quiet Of of Byte
ADR FN=16 Register Register
Time Registers Registers Count
MSB LSB
LSB
MSB

1st
Register 1st Next Next
Quiet
Register Register Register … CRC1 CRC2
MSB Time
LSB MSB MSB

Rx:

10
MULTILOAD II – MODBUS MAPPING

Number
FN=16 Number
Start Start
Of of
Quiet Time ADR (+128 if Register Register CRC1 CRC2 Quiet Time
Registers Registers
error) MSB LSB
LSB
MSB

2.1.5 Error Responses (fn= +128)


Rx:

Error
Quiet Time ADR FN+128 CRC2 CRC1
Subcode

Error Sub codes are:


1 = Invalid Function Code indicates that the use of an invalid or unimplemented function has been
attempted.
2 = Invalid Address Field indicates that a read or write was made to an invalid address. Can also
indicate that a read or write to a single register of a 32-bit value has been attempted.
3 = Invalid Data Field indicates that an attempt to write an invalid value to a register has occurred.
This error code will also be returned if an attempt is made to change a value under Weights and Measures
control without with W&M switch being in the active state.
4 = Query Processing Failure. This code is not returned.

Modbus TCP-IP protocol


The Modbus-TCP/IP protocol has been implemented to be as compatible as possible with the original
published Modbus-TCP/IP standard v1.0b.
Note: The Modbus protocol allows parameter register access only as defined by the explicit mapping in
this manual. To send the ASCII commands (R000, T`A, MAM, MRS, etc.) that are handled by the other
three protocols; the Modbus Extended Services registers must be used.
Using the Modbus TCP/IP protocol, MultiLoad accepts data in the following format:

MBAP FN DATA

Modbus-TCP/IP protocol messages are framed by a MBAP-Header.

Fields Length Description Client Server

Transaction Identifier 2 Bytes Identification of a Initialized by the client Recopied by the server
MODBUS Request/ from the received request
Response transaction.

Protocol Identifier 2 Bytes 0 = Modbus Protocol Initialized by the client Recopied by the server
from the received request

11
MULTILOAD II – MODBUS MAPPING

Fields Length Description Client Server

Length 2 Bytes Number of following Initialized by the client Initialized by the server
bytes (request) (Response)

Unit Identifier 1 Byte Identification of a remote Initialized by the client Recopied by the server
slave connected on a from the received request
serial line or on other
buses

The header is 7 bytes long:

Transaction Identifier - It is used for transaction pairing, the MODBUS server copies in the response the
transaction identifier of the request.

Protocol Identifier – It is used for intra-system multiplexing. The MODBUS protocol is identified by the value
0.

Length - The length field is a byte count of the following fields, including the Unit Identifier and data fields.

Unit Identifier – This field is used for intra-system routing purpose. It is typically used to communicate to a
MODBUS+ or a MODBUS serial line slave through a gateway between an Ethernet TCP-IP network and a
MODBUS serial line. This field is set by the MODBUS Client in the request and must be returned with the
same value in the response by the server.

All MODBUS/TCP ADU are sent via TCP to registered port 502.

Remark: the different fields are encoded in Big-endian.

Fn is the Modbus function. Functions implemented are as follows.


The formal specification of Modbus lists the starting Holding Register address as 40001. The Modbus
Holding Register functions (Fn 3, 6 and 16) all have an implied 4XXXX reference. Referencing Holding
Register 40001 is addressed as register 0000 in the register address field in the message for fn 3, 6 and 16.
Since Modbus addressing has been implemented in various ways over the years, to avoid confusion in this
manual, the Modbus Holding Register addresses listed are the value in the register address field in the
message. If it is necessary to know the formal Modbus Holding Register address, simply add 40001 to the
register addresses listed in the manual.

2.2.1 Read Holding Registers (fn=3)


Note: Both Modbus registers MUST be read at the same time when reading 32-bit values.
Tx:

Number
Number
Start Start
Of of
MBAP FN=3 Register Register
Registers Registers
MSB LSB
LSB
MSB

12
MULTILOAD II – MODBUS MAPPING

Rx:

FN=3 1st 1st Next Next


Byte Register
MBAP (+128 if Register Register Register …
Count
error) MSB LSB MSB MSB

2.2.2 Write Single Registers (fn=6)


Note: cannot be used for 32-bit registers.
Tx:

Start Start Register Register


MBAP FN=6 Register Register
MSB LSB MSB LSB

Rx:

FN=6 Start Start Register Register


MBAP (+128 if Register Register
MSB LSB MSB LSB
error)

2.2.3 Loopback/Maintenance (fn=8)


Note: only loopback of command supported.
Tx:

Diagnostic Diagnostic
MBAP FN=8 Data MSB Data LSB
Code MSB Code LSB

Rx:

Diagnostic Diagnostic
MBAP FN=8 Data MSB Data LSB
Code MSB Code LSB

2.2.4 Preset Multiple Registers (fn=16)


Note: Both Modbus registers MUST be written at the same time when writing 32-bit values.
Tx:

Number Number
Start Start
of Byte
MBAP FN=16 Register Register Of Registers
Registers Count
MSB LSB
MSB LSB

1st Register
1st Next Next
MSB Register Register Register …
LSB MSB MSB

13
MULTILOAD II – MODBUS MAPPING

Rx:

Number
FN=16 Number
Start Start
Of of
MBAP (+128 if Register Register
Registers Registers
error) MSB LSB
LSB
MSB

2.2.5 Error Responses (fn= +128)


Rx:

Error
MBAP FN+128
Subcode

Error Sub codes are:


1 = Invalid Function Code indicates that the use of an invalid or unimplemented function has been
attempted.
2 = Invalid Address Field indicates that a read or write was made to an invalid address. Can also
indicate that a read or write to a single register of a 32-bit value has been attempted.
3 = Invalid Data Field indicates that an attempt to write an invalid value to a register has occurred.
This error code will also be returned if an attempt is made to change a value under Weights and Measures
control without with W&M switch being in the active state.
4 = Query Processing Failure. This code is not returned.

Extended Service Registers


Not all commands native to the MultiLoad II have corresponding mapping to Modbus registers. The
Extended Services register was implemented as a way to support sending and receiving native Multiload II
commands across the Modbus RTU interface. Any native command listed can be sent to the MultiLoad via
the extended Services Register.
Modbus Registers:
Write Holding Register=9000, Len=1, 16-Bit Integer (Command Length)
Write Holding Register=9001, Max Len=999, Characters (Command Text)
Read Holding Register=9000, Len=2, 32-Bit Integer (Reply Length)
Read Holding Register=9001, Max Len=999, Characters (Reply Text)
Perform the following operations to use of the Extended Services Register:
1. Write the Command Length into the Holding Register 9000 (max value of 999 characters).
2. Write the Command Text into the Holding Register 9001 (max length of 999).
3. Command will execute when the final character of the Command Text is written
(9001+Command Length-1).
4. Read the Reply Length from the Holding Register 9000 (max value of 999 characters).
5. Read the Reply Text from the Holding Register 9001 (max length of 999).

14
MULTILOAD II – MODBUS MAPPING

Steps 1 & 2 can be done with a single Modbus Function 16.


Steps 4 & 5 can be done with a single Modbus Function 3.

15
MULTILOAD II – MODBUS MAPPING

3
Chapter

Chapter 3 Information/Definition Registers


This chapter outlines the information and definition register available in the MultiLoad.

MultiLoad Information Registers


Register Length Description Read/Write Data Type Min Value Max Value
0 35 Product Name and Revision Read char 32 122
35 12 Date and Time Read/Write char 32 122
178 40 Terminal SPLC Code Read/Write char 48 57
218 25 Terminal Name Read/Write char 32 122

Communication Registers
Register Length Description Read/Write Data Type Min Value Max Value
47 1 FCM Com Poll Rate Read uint 0 65535
50 2 Ethernet IP Address Read/Write uint 0 65535
52 2 Ethernet IP Mask Read/Write uint 0 65535
54 2 Ethernet IP Gateway Read/Write uint 0 65535
56 40 Ethernet IP Host Read/Write uint 0 65535
243 6 COM Port 1 Config Parameters Read/Write char 48 57
249 6 COM Port 2 Config Parameters Read/Write char 48 57
255 6 COM Port 3 Config Parameters Read/Write char 48 57

BOL Registers
Register Length Description Read/Write Data Type Min Value Max Value
48 1 Current BOL Number Read uint 0 65535
350 1 BOL Line For Position Read/Write uint 0 65535
351 1 BOL Position Read/Write uint 0 65535
352 1 BOL Line For Driver Read/Write uint 0 65535
353 1 BOL Position For Dirver Read/Write uint 0 65535
354 1 Company ID Line Read/Write uint 0 65535
355 1 Company ID Pos Read/Write uint 0 65535
356 1 Load Date Line Read/Write uint 0 65535
357 1 Load Date Position Read/Write uint 0 65535

16
MULTILOAD II – MODBUS MAPPING

Register Length Description Read/Write Data Type Min Value Max Value
358 1 Load Start Time Line Read/Write uint 0 65535
359 1 Load Start Time Position Read/Write uint 0 65535
360 1 Load End Time Line Read/Write uint 0 65535
361 1 Load End Time Position Read/Write uint 0 65535
362 1 Corrected To Line Read/Write uint 0 65535
363 1 Corrected To Position Read/Write uint 0 65535
364 1 Hazard Field Line Read/Write uint 0 65535
365 1 Hazard Field Position Read/Write uint 0 65535
366 1 Product Line Read/Write uint 0 65535
367 1 Product Code Position Read/Write uint 0 65535
368 1 Product Position Read/Write uint 0 65535
369 1 Gross Volume Position Read/Write uint 0 65535
370 1 Net Volume Position Read/Write uint 0 65535
371 1 Temperature Position Read/Write uint 0 65535
Meter/Preset Number
372 1 Position Read/Write uint 0 65535
373 1 Gravity Position Read/Write uint 0 65535
374 1 Pressure Position Read/Write uint 0 65535
375 1 Alarm Position Read/Write uint 0 65535
376 1 Total Gross BOL Position Read/Write uint 0 65535
377 1 Total Gross BOL Line Read/Write uint 0 65535
378 1 Total Net BOL Position Read/Write uint 0 65535
379 1 Total Net BOL Line Read/Write uint 0 65535
Base Product 1 Totalizer
380 1 Position Read/Write uint 0 65535
381 1 Base Product 1 Totalizer Line Read/Write uint 0 65535
382 1 Additive 1 Totalizer Position Read/Write uint 0 65535
383 1 Additive 1 Totalizer Line Read/Write uint 0 65535
Base Product 2 Totalizer
384 1 Position Read/Write uint 0 65535
385 1 Base Product 2 Totalizer Line Read/Write uint 0 65535
386 1 Additive 2 Totalizer Position Read/Write uint 0 65535
387 1 Additive 2 Totalizer Line Read/Write uint 0 65535
388 1 Company Address Position 1 Read/Write uint 0 65535
389 1 Company Address Line 1 Read/Write uint 0 65535
390 1 Company Address Position 2 Read/Write uint 0 65535
391 1 Company Addres Line 2 Read/Write uint 0 65535
392 1 Company Address Position 3 Read/Write uint 0 65535
393 1 Company Address Line 3 Read/Write uint 0 65535
417 1 Modbus BOL Literal Index Read/Write uint 0 65535
418 1 BOL Line Read/Write uint 0 65535

17
MULTILOAD II – MODBUS MAPPING

Register Length Description Read/Write Data Type Min Value Max Value
419 80 BOL Literals Read/Write uint 32 122
550 1 Prompt Length Read/Write uint 0 65535
551 1 BOL Line Read/Write uint 0 65535
552 1 BOL Position Read/Write uint 0 65535
553 20 Prompts Read/Write char 32 122
573 1 Prompt Length Read/Write uint 0 65535
574 1 BOL Line Read/Write uint 0 65535
575 1 BOL Position Read/Write uint 0 65535
576 20 Prompts Read/Write char 32 122
596 1 Prompt Length Read/Write uint 0 65535
597 1 BOL Line Read/Write uint 0 65535
598 1 BOL Position Read/Write uint 0 65535
599 20 Prompts Read/Write char 32 122
619 1 Prompt Length Read/Write uint 0 65535
620 1 BOL Line Read/Write uint 0 65535
621 1 BOL Position Read/Write uint 0 65535
622 20 Prompts Read/Write char 32 122
642 1 Prompt Length Read/Write uint 0 65535
643 1 BOL Line Read/Write uint 0 65535
644 1 BOL Position Read/Write uint 0 65535
645 20 Prompts Read/Write char 32 122
665 1 Prompt Length Read/Write uint 0 65535
666 1 BOL Line Read/Write uint 0 65535
667 1 BOL Position Read/Write uint 0 65535
668 20 Prompts Read/Write char 32 122
688 1 Prompt Length Read/Write uint 0 65535
689 1 BOL Line Read/Write uint 0 65535
690 1 BOL Position Read/Write uint 0 65535
691 20 Prompts Read/Write char 32 122
711 1 Prompt Length Read/Write uint 0 65535
712 1 BOL Line Read/Write uint 0 65535
713 1 BOL Position Read/Write uint 0 65535
714 20 Prompts Read/Write char 32 122

Hazard Registers
Register Length Description Read/Write Data Type Min Value Max Value
734 200 Hazard Definitions Read/Write char 32 122

18
MULTILOAD II – MODBUS MAPPING

Product Registers
Note: Last Product Definition register used=2283 (only 6 additives).

Register Length Description Read/Write Data Type Min Value Max Value
2200 1 Modbus Product Definition Index Read/Write uint 0 65535
2201 1 Hazard Index Read/Write uint 0 65535
2202 6 Product Code Read/Write char 48 57
2208 25 Long Product Description Read/Write char 32 122
2233 10 Product Description Read/Write char 32 122
2243 1 Product Index Component 1 Read/Write uint 0 65535
2244 1 Recipe Percentage Read/Write uint 0 65535
2245 1 Product Index Component 2 Read/Write uint 0 65535
2246 1 Recipe Percentage Read/Write uint 0 65535
2247 1 Product Index Component 3 Read/Write uint 0 65535
2248 1 Recipe Percentage Read/Write uint 0 65535
2249 1 Product Index Component 4 Read/Write uint 0 65535
2250 1 Recipe Percentage Read/Write uint 0 65535
2251 1 Product Index Component 5 Read/Write uint 0 65535
2252 1 Recipe Percentage Read/Write uint 0 65535
2253 1 Product Index Component 6 Read/Write uint 0 65535
2254 1 Recipe Percentage Read/Write uint 0 65535
2255 1 Product Index Component 7 Read/Write uint 0 65535
2256 1 Recipe Percentage Read/Write uint 0 65535
2257 1 Product Index Component 8 Read/Write uint 0 65535
2258 1 Recipe Percentage Read/Write uint 0 65535
2259 1 Additive 1 Code Read/Write uint 0 65535
2260 1 Additive Percentage Read/Write uint 0 65535
2261 1 Additive 2 Code Read/Write uint 0 65535
2262 1 Additive Percentage Read/Write uint 0 65535
2263 1 Additive 3 Code Read/Write uint 0 65535
2264 1 Additive Percentage Read/Write uint 0 65535
2265 1 Additive 4 Code Read/Write uint 0 65535
2266 1 Additive Percentage Read/Write uint 0 65535
2267 1 Additive 5 Code Read/Write uint 0 65535
2268 1 Additive Percentage Read/Write uint 0 65535
2269 1 Additive 6 Code Read/Write uint 0 65535
2270 1 Additive Percentage Read/Write uint 0 65535
2271 1 Additive Null Read/Write uint 0 65535
2272 1 Sampler 1 Code Read/Write uint 0 65535
2273 1 Sampler Pacing Rate Read/Write uint 0 65535
2274 1 Sampler 2 Code Read/Write uint 0 65535
2275 1 Sampler Pacing Rate Read/Write uint 0 65535

19
MULTILOAD II – MODBUS MAPPING

Register Length Description Read/Write Data Type Min Value Max Value
2276 1 Sampler 3 Code Read/Write uint 0 65535
2277 1 Sampler Pacing Rate Read/Write uint 0 65535
2278 1 Sampler 4 Code Read/Write uint 0 65535
2279 1 Sampler Pacing Rate Read/Write uint 0 65535
2280 1 Sampler 5 Code Read/Write uint 0 65535
2281 1 Sampler Pacing Rate Read/Write uint 0 65535
2282 1 Sampler 6 Code Read/Write uint 0 65535
2283 1 Sampler Pacing Rate Read/Write uint 0 65535
2284 1 Sampler Null Read/Write uint 0 65535

Driver Database Registers


Register Length Description Read/Write Data Type Min Value Max Value
2300 1 Modbus Card Database Index Read/Write uint 0 65535
2301 2 Card Number Read/Write char 48 57
2303 1 PIN ID For Card Read/Write char 48 57
2304 1 Company ID Read/Write char 48 57
2305 1 Language Index For Driver Read/Write uint 0 65535
2306 1 Bit Mapped Preset Lockout Read/Write uint 0 65535
2700 25 Authorized Driver Read/Write char 32 122
2725 25 Stockholder Read/Write char 32 122
2750 25 Customer Read/Write char 32 122
2775 25 Account Read/Write char 32 122
2800 25 Consignee Read/Write char 32 122
2825 25 Driver Name Read/Write char 32 122
2850 1 Input Terminating Key Read/Write char 32 122
2851 24 Input Data Read/Write char 32 122
2900 80 Card Data Read/Write char 32 122

GPS Site Database Definitions


Register Length Description Read/Write Data Type Min Value Max Value
2350 1 Modbus GPS Site Database Index Read/Write uint 0 65535
2351 15 GPS Site Name Read/Write char 32 122
2366 2 GPS Site Latitude Read/Write char 32 122
2368 2 GPS Site Longitude Read/Write char 32 122

20
MULTILOAD II – MODBUS MAPPING

Bilingual Message Support


Register Length Description Read/Write Data Type Min Value Max Value
2369 1 Language Index For Driver Read/Write uint 0 65535
2400 1 Modbus Language Prompt Index Read/Write uint 0 65535
2401 1 Language Prompt Code Read/Write char 32 122
2402 60 Language Message Read/Write char 32 122

Log Message Registers


Register Length Description Read/Write Data Type Min Value Max Value
2600 2 Host Log Message Count Read/Write uint 0 65535
2602 2 Event Log YYMMDD Read/Write uint 0 65535
2604 2 Event Log HHMMSS Read/Write uint 0 65535
2606 20 Event Log Message for RCU Read/Write uint 0 65535
2686 1 Host Log Extract Message Index Read/Write uint 0 65535

Transaction Registers
Note: Set Register 7801 to 0 for Transaction Header information or 1 for Transaction Detail information.

Min
Register Length Description Read/Write Data Type Value Max Value
Modbus Transaction Number
7800
1 Index Read/Write char 32 122
Modbus Trasaction Detail
7801
1 Index Read/Write char 32 122
Transaction Header Card
7810
2 Number Read/Write uint 32 122
7812 1 Transaction Header Company Read/Write char 32 122
Transaction Header Load
7813
1 Start Read/Write char 32 122
Transaction Header Load
7814
1 Stop Read/Write char 32 122
Transaction Head Load
7815
1 Stop(or Start) Date Read/Write char 32 122
Transaction Header Number
7816
1 of Detail Records Read/Write char 32 122
7817 25 Transaction Header Prompts Read/Write char 32 122
7842 25 Transaction Header Prompts Read/Write char 32 122
7867 25 Transaction Header Prompts Read/Write char 32 122
7892 25 Transaction Header Prompts Read/Write char 32 122
7810 1 Transaction Detail Preset Read/Write uint 32 122

21
MULTILOAD II – MODBUS MAPPING

Min
Register Length Description Read/Write Data Type Value Max Value
7811 1 Transaction Detail Type Read/Write uint 32 122
Transaction Detail Product
7812
6 Code Read/Write char 32 122
Transaction Detail Gross
7818
2 Delivered Read/Write uint 32 122
Transaction Detail Net
7820
2 Delivered Read/Write uint 32 122
Transaction Detail Average
7822
1 Temperature Read/Write uint 32 122
Transaction Detail Density
7823
1 Gravity Read/Write uint 32 122
Transaction Detail
7824
1 Compartment ID Read/Write uint 32 122
7825 1 Transaction Detail Pressure Read/Write uint 32 122
Transaction Detail API
7826
1 Expansion Coefficient Read/Write uint 32 122
Transaction Detail Corrected
7827
1 Density Gravity Read/Write uint 32 122
Transaction Detail Volume
7828
1 Correction Factor Read/Write uint 32 122
7829 1 Transaction Detail BSW Read/Write uint 32 122
Transaction Detail Alibilog
7830
1 Alarm Read/Write uint 32 122
Transaction Detail Batch
7831
2 Number Read/Write uint 32 122
Transaction Detail Mass
7833
2 Delivered Read/Write uint 32 122
Transaction Detail
7835 Termperature Correction
1 Factor Read/Write uint 32 122
Transaction Detail Pressure
7836
1 Correction Factor Read/Write uint 32 122

Custom Logic Registers


Register Length Description Read/Write Data Type Min Value Max Value
12000 2 Custom Logic Register [0000] Read/Write uint 0 65535
… … … … … … …
13023 2 Custom Logic Register [1023] Read/Write uint 0 65535

22
MULTILOAD II – MODBUS MAPPING

23
MULTILOAD II – MODBUS MAPPING

4
Chapter

Chapter 4 Configuration Registers


This section outlines the first 100 configuration registers for the RCU and equipment levels available in the
MultiLoad, additional configuration registers are accessable through the extended service registers using Smith
protocol. The minimum, maxiumum and default values are specifc to the configuration parameter and not the
register size.

Configuration Data Types


Configuration data types listed below have more than one option selectable within the configuration.

Multiple Levels:

Disable/Enable
Definition Numerical Value
Disabled 0
Enabled 1

W&M Alarm Reset Mode


Definition Numerical Value
Authorize 0
Clear 1
2 minutes 2
5 minutes 3
15 minutes 4
30 minutes 5
60 minutes 6
3 hours 7
12 hours 8
24 hours 9

24
MULTILOAD II – MODBUS MAPPING

Deliver Type
Output Pulse Type
Definition Numerical Value
Gross 0
Net 1
Mass 2

RCU Level:

Program Mode Language


Driver Language
Definition Numerical Value
English 0
Spanish 1
Portuguese 2
French 3
German 4
Simplified Chinese 5
Traditional Chinese 6
Thai 7

Card Reader Type


Definition Numerical Value
Disabled 0
Bucket Captive 1
Bucket Noncaptive 2
Slot Captive 3
Slot Noncaptive 4
iButton 5
Bucket Dual Noncaptive 6
Slot Dual Noncaptive 7

25
MULTILOAD II – MODBUS MAPPING

Processing Mode
Definition Numerical Value
Stand-alone 0
Remote 1
UAP 2
UAP Gate 3

Mass Measure Used


Definition Numerical Value
None 0
Pounds 1
Short Tons 2
Long Tons 3
Grams 4
Kilograms 5
Density of Air 6
Metric Tons 7

Measure Used
Definition Numerical Value
Gallons 0
Liters 1
Cubic Meters 2
Tonnes 3
Kilograms 4
Grams 5
Pounds 6
Barrels 7
No Measure 8
Liters 9

26
MULTILOAD II – MODBUS MAPPING

Decaliters 10

Display Load Volume


Definition Numerical Value
Disabled 0
Gross 1
Net 2
Mass 3

Decimal Mark Type


Definition Numerical Value
Decimal 0
Comma 1

SCS Prompting
Definition Numerical Value
None 0
BSW 1
Density 2
BSW and Density 3

Sampler UOM
Definition Numerical Value
None 0
cc 1
oz 2

27
MULTILOAD II – MODBUS MAPPING

Bay Level:

Temperature UOM
Definition Numerical Value
Celsius 0
Fahrenheit 1

Deadman Mode
Definition Numerical Value
No Mode 0
Continuous Hold 1
Hold & Release 2
Push 3

Preset Level:

Blending Type
Definition Numerical Value
None 0
Ratio 1
Sequential 2
Ratio and Sequential 3
Watercut 4

Blend On Lead Comp


Definition Numerical Value
None 0
First Component 1
Highest Percentage 2
Lowest Percentage 3

28
MULTILOAD II – MODBUS MAPPING

Flow Rate Mode


Definition Numerical Value
Minutes 0
Hours 1

Meter Level:
Meter Type
Definition Numerical Value
Volume Pulse 0
Mass Pulse 1
Volume Analog 2
Khrone 3
Micromotion 4

Component Level:

API 54YG Products


Definition Numerical Value
No Product 0
Propane 1
Propylene 2
Butane 3
Isobutane 4
Isobutene 5
Cis-But-2-ene 6
Trans-But-2-ene 7
But-1-ene 8
But-1,3-dien 9
Methanol 10
Ethanol 11

29
MULTILOAD II – MODBUS MAPPING

API 54YG Products


Definition Numerical Value
Isopropanol 12
Isobutanol 13
MTBE 14
TAME 15
Benzol 16
Toluol 17
o-Xylol 18
m-Xylol 19
p-Xylol 20

API BIO
Definition Numerical Value
None 0
E5 1
E10 2
E80 3
E85 4
E100 5
Benzin/Petrol 6
Diesel 7
B5 Rapeseed Oil 8
B7 Rapeseed Oil 9
B100 Rapeseed Oil 10
B5 Soy Bean Oil 11
B7 Soy Bean Oil 12
B100 Soy Bean Oil 13

30
MULTILOAD II – MODBUS MAPPING

Density UOM
Definition Numerical Value
3
kg/m 1
Api Gravity 2
Relative Density 3

Pressure UOM
Definition Numerical Value
psig 1
kPa 2
bar 3

API ASTMD1555 Product


Definition Numerical Value
None 0
Benzene 1
Cumene 2
Cyclohexane 3
Ethylbenzene 4
Styrene 5
Toluene 6
m-Xylene 7
o-Xylene 8
p-Xylene 9
300-350°F Hydrocarbon 10
350-400°F Hydrocarbon 11

Additive Level:

31
MULTILOAD II – MODBUS MAPPING

Additive Type
Definition Numerical Value
Solenoid w/ Meter 1
Piston w/ Normal Feedback 2
Piston w/ Inverted Feedback 3
Piston w/ No Feedback 4
Analog Valve w/ Meter 5

Additive Mode
Definition Numerical Value
Start On Batch 0
Start On High Flow 1
Start On Volume 2

Tank Level:

Active Tank Mode


Definition Numerical Value
Deactive 0
Loading 1
Unloading 2
Loading and Unloading 3

Security Level:

Password Complexity
Definition Numerical Value
None 0
Alpha 1
Numeric 2
Alpha and Numeric 3
Special Character 4

32
MULTILOAD II – MODBUS MAPPING

Password Complexity
Definition Numerical Value
Alpha and Special Character 5
Numeric and Special Character 6
Alpha, Numeric, and Special Character 7

FCM Addressing:

MSB FCM Address Bitwise Representation LSB


Custom Logic Enabled Invert FCM Number Port Number
1 bit 1 bit 1 bit 5 bits 6 bits

Examples
FCM Port Bitwise Representation Numerical Value
Number Number
1 4 0 1 0 00001 000100 4164
3 11 0 1 0 00011 001011 4299

Configuration Indexing
Configuration Index determines the preset, component, meter and additive you are editing when writing
commands to the modbus registers addressed in this chapter.

Register Length Description Read/Write Data Type Min Value Max Value
996 1 Modbus Preset Index Read/Write unsigned int 0 11
997 1 Modbus Component Index Read/Write unsigned int 0 7
998 1 Modbus Meter Index Read/Write unsigned int 0 4
999 1 Modbus Additive Index Read/Write unsigned int 0 15

33
MULTILOAD II – MODBUS MAPPING

RCU Level Configuration Registers


Read/Writ Min Max Default
Register Length Description e Data Type Value Value Value
Reload ROM Lang Read/Writ
1008 2 Read/Write disable/enable
File e
1016 2 Driver Language Read/Write language English
Program Mode
1018 2 Read/Write language English
Language
1020 2 Card Reader Type Read/Write card-reader 1
1022 2 Prox Card Pull Secs Read/Write unsigned int 2 30 3
remote
1024 2 Processing Mode Read/Write Enabled
processing
1026 2 Message Swap Delay Read/Write unsigned int 1 60 3
1028 2 Message Hold Delay Read/Write unsigned int 1 60 10
Max GPS Site
1030 2 Read/Write unsigned int 0 10000 200
Distance
1032 2 Auto Authorize Read/Write disable/enable Disabled
1034 2 MM/DD/YY Date Read/Write disable/enable Enabled
1036 2 Mass Measure Used Read/Write mass measure None
1038 2 Load Date From End Read/Write disable/enable Enabled
1040 2 Measure Used Read/Write measures Gallons
1042 2 Print Blend Details Read/Write unsigned int 0 2 1
1044 2 Compartment Entry Read/Write disable/enable Disabled
1046 2 Config Timeout Mins Read/Write unsigned int 0 99 20
1048 2 Print Totalizers Read/Write totalizers None
1050 2 Simulation Mode Read/Write disable/enable Disabled
1052 2 Large Prompts Read/Write disable/enable Disabled
1054 2 Confirm Flow Starts Read/Write disable/enable Disabled
1056 2 Display Adtv as CCs Read/Write disable/enable Disabled
1058 2 Display Hundredths Read/Write disable/enable Disabled
1060 2 Use Hundredths Read/Write disable/enable Disabled
1062 2 W&M Density Lock Read/Write disable/enable Disabled
1064 2 Print Ticket Read/Write disable/enable Disabled
Form Feed After
1066 2 Read/Write disable/enable Enabled
Ticket
1068 2 Print Ticket on PCM Read/Write disable/enable Disabled
1070 2 Ticket PCM Read/Write unsigned int 0 32 0
1072 2 Meter Arch Timeout Read/Write unsigned int 0 120 120
1074 2 Inactivity Timeout Read/Write unsigned int 0 60 35
Print Msg Log on
1076 2 Read/Write disable/enable Disabled
PCM
1078 2 Message Log PCM# Read/Write unsigned int 0 32 0

34
MULTILOAD II – MODBUS MAPPING

Read/Writ Min Max Default


Register Length Description e Data Type Value Value Value
1080 2 No Prox Pull If Flow Read/Write disable/enable Disabled
1082 2 Host Down Timeout Read/Write unsigned int 30 999 120
1084 2 Host Wait Timeout Read/Write unsigned int 60 999 999
1086 2 Prt Alibi Log on PCM Read/Write disable/enable Disabled
1088 2 Alibi Log PCM# Read/Write unsigned int 0 3 0
1090 2 Swing Arm Secondary Read/Write disable/enable Disabled
Screen Saver
1092 2 Read/Write unsigned int 0 65535 600
Timeout
1094 2 Screen Saver Bright Read/Write percent 0 10000 5000
Min Time Change
1096 2 Read/Write unsigned int 0 65535 60
Secs
1098 2 Display Load Volume Read/Write disable/enable Disabled
1100 2 Display Help Read/Write disable/enable Disabled
Measure On Load
1102 2 Read/Write disable/enable Disabled
Scrn
1104 2 Status Scrn Lockout Read/Write disable/enable Enabled
1106 2 Load Screen Timeout Read/Write unsigned int 0 65535 60
1108 2 Preset Slct Timeout Read/Write unsigned int 0 65535 0
1110 2 Pixel Test Read/Write disable/enable Disabled
1112 2 Meter Proving Mode Read/Write disable/enable Disabled
1114 2 Decimal Mark Type Read/Write Decimal Mark Decimal
1116 2 Display Preset Tot. Read/Write disable/enable Disabled
Default Driver 99999
1118 2 Read/Write unsigned int 1 1
Number 99
99999
1120 2 Default Facility Code Read/Write unsigned int 0 0
99
SCS Prompting (SCS
1122 2 Read/Write scs prompt None All None
Only)
Sample UOM
1124 2 Sample UOM Read/Write None oz None
units
1126 2 Unused Read/Write
SCS Prompting Befor
1128 2 Read/Write SCS Display After After
Display (SCS Only) e
1130 2 Max Lines on Ticket Read/Write unsigned int 0 106 66
Startup Keypad disable/enable
1132 2 Read/Write Disabled
Locked
10000
1134 2 Screen Brightness Read/Write Percent 500 10000
1136 2 W&M Key FCM# Read/Write fcm address Disabled
1138 2 Program Key FCM# Read/Write fcm address Disabled
1180 2 RCU Address Read/Write unsigned int 0 999 1

35
MULTILOAD II – MODBUS MAPPING

Bay Level Configuration Registers


Min Max Default
Register Length Description Read/Write Data Type Value Value Value
1200 2 Number Bay Presets Read/Write unsigned int 1 12 1
1202 2 Number of FCMs Read/Write unsigned int 0 32 1
1204 2 Number of PCMs Read/Write unsigned int 0 32 1
Temperature
1206 2 Temperature UOM Read/Write C
UOM
Disable
1208 2 Canada API Limits Read/Write disable/enable
d
1210 2 Number of Tanks Read/Write unsigned int 0 10 0
1212 2 Bay Number Read/Write unsigned int 0 9999 0
Number External
1214 2 Read/Write unsigned int 0 12 0
Presets
1216 2 Unused Read/Write
1218 2 Unused Read/Write
1356 2 Output Pulse Type Read/Write Delivery Type Gross
Disable
1358 2 Start Transaction Read/Write fcm address
d
Disable
1360 2 End Transaction Read/Write fcm address
d
Disable
1362 2 Output Pulse FCM# Read/Write fcm address
d
unsigned div
1364 2 Output Pulse Factor Read/Write 0.001 50 10
1000
1366 2 Deadman Mode Read/Write Unsigned int 0 3 0
Input Deadman Disable
1368 2 Read/Write fcm address
FCM# d
1370 2 Deadman Stop Timer Read/Write Unsigned int 0 65535 180
Output Deadman Disable
1372 2 Read/Write fcm address
FCM# d
Deadman Warning
1374 2 Read/Write Unsigned int 0 65535 30
Timer
Deadman Bypass Disable
1376 2 Read/Write fcm address
FCM# d
Disable
1378 2 Alarm Out FCM# Read/Write fcm address
d
Disable
1380 2 Authorized FCM# Read/Write fcm address
d
Disable
1382 2 Permiss 0 FCM# Read/Write fcm address
d

36
MULTILOAD II – MODBUS MAPPING

Min Max Default


Register Length Description Read/Write Data Type Value Value Value
Disable
1384 2 Permiss 1 FCM# Read/Write fcm address
d
Disable
1386 2 Permiss 2 FCM# Read/Write fcm address
d
Disable
1388 2 Permiss 3 FCM# Read/Write fcm address
d
Disable
1390 2 Permiss 4 FCM# Read/Write fcm address
d
Disable
1392 2 Permiss 5 FCM# Read/Write fcm address
d
Disable
1394 2 Permiss 6 FCM# Read/Write fcm address
d
Disable
1396 2 Permiss 7 FCM# Read/Write fcm address
d
Disable
1398 2 Permiss Out FCM# Read/Write fcm address
d

Preset Configuration Registers


Min Max Default
Register Length Description Read/Write Data Type Value Value Value
Flow Control
1600 2 Read/Write unsigned int 0 31 0
Module#
1602 2 Side-Stream on Mtr# Read/Write unsigned int 0 6 0
Side Stream on Any
1604 2 Read/Write disable/enable Disabled
Meter
1606 2 Unused Read/Write
1608 2 Meter Address Read/Write unsigned int 0 255 0
Volume
1610 2 Meter Type Read/Write meter type
Pulse
1612 2 Max Quad Errors Read/Write unsigned int 0 65535 10
1614 2 Reset Quad Errors Read/Write unsigned int 1000 65535 10000
1616 2 Low Flow Alarm Rate Read/Write unsigned int 0 65535 10
Low Flow Alarm unsigned 999.99
1618 2 Read/Write 0 10
Time div1000 9
1620 2 Excess Flw Alrm Rate Read/Write unsigned int 0 9999 800
1622 2 Minimum Flow Rate Read/Write unsigned int 0 9999 50
1624 2 Maximum Flow Rate Read/Write unsigned int 0 9999 650
1626 2 Low Flow DB Rate Read/Write unsigned int 0 9999 40
1628 2 High Flow DB Rate Read/Write unsigned int 0 9999 40
1630 2 1st Stage DB Rate Read/Write unsigned int 0 9999 40
1632 2 2nd Stage DB Rate Read/Write unsigned int 0 9999 40

37
MULTILOAD II – MODBUS MAPPING

Min Max Default


Register Length Description Read/Write Data Type Value Value Value
unsigned
1634 2 Valve Cntl Alrm Time Read/Write 0 65.535 10
div1000
1636 2 Valve Fault Alrm Vol Read/Write unsigned int 0 65535 30
1638 2 Creep Reset Time Read/Write unsigned int 0 65535 0
unsigned
1640 2 Ratio Adj P. Factor Read/Write 0 655.35 10
div100
unsigned
1642 2 Ratio Adj D. Factor Read/Write 0 655.35 0.3
div100
Meter Creep Alrm
1644 2 Read/Write unsigned int 0 65535 15
Vol
unsigned
1646 2 Flow Scan Time Read/Write 0.1 1 0.1
div1000
unsigned
1648 2 Valve Dwell Time Read/Write 0.01 65.535 1
div1000
Valve Dwell
1650 2 Read/Write unsigned int 0 9999 0
StepRate
Valve Dwell unsigned
1652 2 Read/Write 0 5 0
StepTime div1000
Adaptive Valve
1654 2 Read/Write disable/enable Disabled
Control
1656 2 Analog Valve Control Read/Write disable/enable Disabled
4-20mA Increase unsigned div
1658 2 Read/Write 0 4 0.08
Step 1000
4-20mA Decrease unsigned div
1660 2 Read/Write 0 4 0.8
Step 1000
Excess Flow Alarm unsigned div
1662 2 Read/Write 0 65535 0
Time 1000
Analog Valve No unsigned div
1664 2 Read/Write 0 20.000 0
Flow mA 1000
1666 2 Unused Read/Write
Analog Meter Flow
1668 2 Read/Write unsigned int 0 9999 0
Rate @ 4mA
Analog Meter Flow
1670 2 Read/Write unsigned int 0 9999 600
Rate @ 20mA
Analog Meter Flow -
1672 2 Read/Write signed div1000 9.999 0
Rate Offset 9.999
Analog Meter Flow
1674 2 Read/Write unsigned int 0 9999 0
Rate Cutoff
1676 2 Unused Read/Write
1678 2 Unused Read/Write
Density Sensor fcm address
1680 2 Read/Write Disabled
FCM# analog input
1682 2 Unused Read/Write

38
MULTILOAD II – MODBUS MAPPING

Min Max Default


Register Length Description Read/Write Data Type Value Value Value
1684 2 Default Density Read/Write unsigned div10 0 9999.9 0
1686 2 Alarm Low Density Read/Write unsigned div10 0 9999.9 0
1688 2 Alarm High Density Read/Write unsigned div10 0 9999.9 12000
1690 2 Density Alarm Time Read/Write unsigned int 0 60 0
Density @ Low
1692 2 Read/Write unsigned div10 0 4000 0
Value
Density @ High
1694 2 Read/Write unsigned div10 0 4000 12000
value
1696 2 Density Offset Read/Write signed div10 -300 300 0
1698 2 Unused Read/Write
1700 2 Unused Read/Write
Pressure Sensor fcm address
1702 2 Read/Write Disabled
FCM# analog input
1704 2 Unused Read/Write
unsigned 9999.9
1706 2 Default Pressure Read/Write 0 9999.99
div100 9
unsigned 9999.9
1708 2 Alarm Low Pressure Read/Write 0 100
div100 9
unsigned 9999.9
1710 2 Alarm High Pressure Read/Write 0 450
div100 9
1712 2 Pressure Alarm Time Read/Write unsigned int 0 60 0
Pressure @ Low unsigned
1714 2 Read/Write 0 4000 0
Value div100
Pressure @ High unsigned
1716 2 Read/Write 0 4000 650
Value div100
1718 2 Pressure Offset Read/Write signed div100 -30 30 0
1678 2 Unused Read/Write
Relative Density fcm address
1680 2 Read/Write Disabled
Sensor FCM# analog input
1682 2 Unused Read/Write
Default Relative unsigned
1684 2 Read/Write 0 2 0
Density div10000
Alarm Low Relative unsigned
1686 2 Read/Write 0 2 0
Density div10000
Alarm High Relative unsigned
1688 2 Read/Write 0 2 1.2
Density div10000
1690 2 Rel. Den. Alrm Time Read/Write unsigned int 0 60 0
Relative Density @ unsigned
1692 2 Read/Write 0 4 0
Low Value div10000
Relative Density @ unsigned
1694 2 Read/Write 0 4 1.2
High Value div10000

39
MULTILOAD II – MODBUS MAPPING

Min Max Default


Register Length Description Read/Write Data Type Value Value Value
Relative Density signed
1696 2 Read/Write -0.3 0.3 0
Offset div10000
unsigned
1740 2 2% MF Limit Ref Read/Write 0 6.5535 0
div10000
Adjacent MF Dev unsigned
1742 2 Read/Write 0 0.1 0
Limt div10000
unsigned
1744 2 Temp Offset Limit Read/Write 0 5 3
div100
1746 2 Output Pulse FCM# Read/Write fcm address Disabled
unsigned div
1748 2 Output Pulse Factor Read/Write 1.000 50.000 10.000
1000
1760 2 Unused Read/Write
1762 2 Alarm Out FCM# Read/Write fcm address Disabled
1764 2 Authorized FCM# Read/Write fcm address Disabled
1766 2 Permiss FCM# Read/Write fcm address Disabled
1768 2 Permiss Out FCM# Read/Write fcm address Disabled
1770 2 Meter K-Factor Read/Write unsigned int 1 65535 50
1772 2 Quad Check Enable Read/Write disable/enable Disabled
1774 2 Unused Read/Write
1776 2 Temperature Offset Read/Write signed div100 -5 5 0
Temperature Alarm
1778 2 Read/Write unsigned int 0 60 0
Time
fcm address
1780 2 Temp Sensor FCM# Read/Write Disabled
analog input
1782 2 Temperature Sensor Read/Write disable/enable Enabled
1784 2 Default Temperature Read/Write signed div10 -999.9 999.9 999.9
1786 2 Alarm Low Temp Read/Write signed div10 -999.9 999.9 -999.9
1788 2 Alarm High Temp Read/Write signed div10 -999.9 999.9 999.9
1790 2 Temp Module Type Read/Write unsigned int 0 19 0
Temperature @ Low
1792 2 Read/Write signed div10 -999.9 999.9 -50
Value
Temperature @ High
1794 2 Read/Write signed div10 -999.9 999.9 350.0
Value
1796 2 Unused Read/Write
1798 2 unused Read/Write
1800 2 Unused Read/Write
1802 2 Unused Read/Write
1804 2 Unused Read/Write
1806 2 Unused Read/Write
1808 2 Unused Read/Write
1810 2 Unused Read/Write

40
MULTILOAD II – MODBUS MAPPING

Min Max Default


Register Length Description Read/Write Data Type Value Value Value
1812 2 Unused Read/Write
1814 2 Unused Read/Write
API Gravity Sensor fcm address
1816 2 Read/Write Disabled
FCM# analog input
1818 2 Default API Gravity Read/Write unsigned div10 -1000 11000 0
Alarm Low API
1820 2 Read/Write unsigned div10 -1000 11000 0
Gravity
Alarm High API
1822 2 Read/Write unsigned div10 -1000 11000 11000
Gravity
API Gravity Alarm
1824 2 Read/Write unsigned int 0 60 0
Time
API Gravity @ Low
1826 2 Read/Write unsigned div10 -1000 11000 0
Value
API Gravity @ High
1828 2 Read/Write unsigned div10 -1000 11000 11000
Value
1830 2 API Gravity Offset Read/Write unsigned div10 -3000 3000 0

Component Configuration Registers


Min Max Default
Register Length Description Read/Write Data Type Value Value Value
1800 2 Meter# Read/Write unsigned int 1 6 1
1802 2 High Flow Rate Read/Write unsigned int 0 9999 600
1804 2 1st Stage Trip Vol Read/Write unsigned int 0 65535 70
1806 2 1st Stage Flow Rate Read/Write unsigned int 0 9999 225
1808 2 2nd Stage Trip Vol Read/Write unsigned int 0 65535 20
1810 2 2nd Stage Flow Rate Read/Write unsigned int 0 9999 150
unsigned
1812 2 Final Trip Vol Read/Write 0 655.35 1.15
div100
unsigned
1814 2 Final Trip Max Time Read/Write 0 65.535 5
div1000
1816 2 Final Trip Vol Lock Read/Write disable/enable Disabled
Unauth Flow Alrm
1818 2 Read/Write unsigned int 0 65535 10
Vol
99999
1820 2 Tank Group Read/Write unsigned int 0 0
99
W&M Recipe unsigned div
1822 2 Read/Write 0.00 100.00 0.00
Percentage 100
1824 2 Unused Read/Write
1826 2 BlkValve Open Rate Read/Write unsigned int 0 9999 0
1828 2 BlkValve Open Delay Read/Write unsigned int 0 65535 0
1830 2 B.V. Open Alrm Time Read/Write unsigned int 2 65535 10

41
MULTILOAD II – MODBUS MAPPING

Min Max Default


Register Length Description Read/Write Data Type Value Value Value
1832 2 B.V. Close Alrm Time Read/Write unsigned int 2 65535 10
1834 2 Pump Start Delay Read/Write unsigned int 0 65535 3
1836 2 Pump Stop Delay Read/Write unsigned int 0 65535 30
Pump Start Alrm
1838 2 Read/Write unsigned int 2 65535 2
Time
1840 2 Flow Start Delay Read/Write unsigned int 0 65535 5
1842 2 Unused Read/Write
1844 2 Unauth Reset Time Read/Write unsigned int 0 65535 0
1846 2 Unused Read/Write
1848 2 Fallback Rate Read/Write unsigned int 0 9999 350
1850 2 Fallback Time Read/Write unsigned int 0 65535 0
1852 2 Fallback Retry Time Read/Write unsigned int 0 65535 0
1854 2 Fallback Retry Vol Read/Write unsigned int 0 65535 0
Fallback Minimum unsigned 99999
1856 2 Read/Write 0 0
Pressure div100 9
Fallback Minimum
1858 2 Read/Write unsigned int 0 9999 0
Rate
Fallback Increase
1860 2 Read/Write unsigned int 0 9999 0
Rate
Fallback Decrease
1862 2 Read/Write unsigned int 0 9999 0
Rate
Fallback Retry Min unsigned 99999
1864 2 Read/Write 0 0
Pressure div100 9
Fallback Vapor
1866 2 Read/Write disable/enable Disabled
Pressure
1868 2 Unused Read/Write
1870 2 Unused Read/Write
1872 2 Unused Read/Write
1874 2 Unused Read/Write
1876 2 Unused Read/Write
1878 2 API Table Read/Write API table name None
1880 2 API 54YG Product Read/Write 54YG Products 0 20 None
API Extrapolated disable/enabl
1882 2 Read/Write Disabled
Range e
PTB BIO
1884 2 API BIO Read/Write 0 13 None
Products
1886 2 API Gravity Read/Write signed div10 -100 1100 0
unsigned
1888 2 Relative Density Read/Write 0 9 0
div10000
1890 2 Default Density Read/Write unsigned div10 0 9999.9 0
1892 2 Expansion Coef. Read/Write unsigned div10 0 2000 0
1894 2 Hydrometer Used Read/Write disable/enable Disabled

42
MULTILOAD II – MODBUS MAPPING

Min Max Default


Register Length Description Read/Write Data Type Value Value Value
commodity
1896 2 Commodity Type Read/Write 0 3 1
type
Expansion Coef. expansion coef
1898 2 Read/Write 1 2 1
UOM uom type
density uom
1900 2 Density UOM Read/Write 1 3 1
type
pressure uom
1902 2 Pressure UOM Read/Write 1 3 3
type
Reference
1904 2 Read/Write unsigned int 0 9999 60
Temperature
1906 2 Alcohol Percentage Read/Write Percent 0 100 0
1908 2 API Alarm Time Read/Write unsigned int 0 120 0
Compressibility
1910 2 Read/Write unsigned int 0 99999 0
Factor
API ASTMD1555 API ASTM No
1912 2 Read/Write
Product D1555 Product
1914 2 Unused Read/Write
1916 2 Unused Read/Write
1918 2 Unused Read/Write
1920 2 Unused Read/Write
1922 2 Unused Read/Write
1924 2 Unused Read/Write
1926 2 Unused Read/Write
1928 2 Unused Read/Write
1930 2 Unused Read/Write
1932 2 Unused Read/Write
1934 2 Unused Read/Write
1936 2 Unused Read/Write
1938 2 Unused Read/Write
1940 2 Unused Read/Write
1942 2 Output Pulse FCM# Read/Write fcm address Disabled
unsigned div
1944 2 Output Pulse Factor Read/Write 1 50 10
1000
1946 2 Output Pulse Type Read/Write Delivery Type Gross
1948 2 Close Blk Val FCM# Read/Write fcm address Disabled
1950 2 Blk Val Status FCM Read/Write fcm address Disabled
1952 2 Open Blk Val FCM# Read/Write fcm address Disabled
1954 2 Unused Read/Write
1956 2 Pump Run FCM# Read/Write fcm address Disabled
1958 2 Pump Kill FCM# Read/Write fcm address Disabled
1960 2 Pump Status FCM# Read/Write fcm address Disabled

43
MULTILOAD II – MODBUS MAPPING

Min Max Default


Register Length Description Read/Write Data Type Value Value Value
1962 2 Alarm Out FCM# Read/Write fcm address Disabled
1964 2 Authorized FCM# Read/Write fcm address Disabled
1966 2 Permiss FCM# Read/Write fcm address Disabled
1968 2 Permiss Out FCM# Read/Write fcm address Disabled
unsigned
1970 2 Meter Factor #1 Read/Write 0.8 1.2 1
div10000
Meter Factor #1
1972 2 Read/Write unsigned int 0 9999 150
Rate
unsigned
1974 2 Meter Factor #2 Read/Write 0.8 1.2 1
div10000
Meter Factor #2
1976 2 Read/Write unsigned int 0 9999 200
Rate
unsigned
1978 2 Meter Factor #3 Read/Write 0.8 1.2 1
div10000
Meter Factor #3
1980 2 Read/Write unsigned int 0 9999 400
Rate
unsigned
1982 2 Meter Factor #4 Read/Write 0.8 1.2 1
div10000
Meter Factor #4
1984 2 Read/Write unsigned int 0 9999 800
Rate
# Meter Factors
1986 2 Read/Write unsigned int 1 4 4
Used
1988 2 Unused Read/Write

Additive Configuration Registers


Min Max Default
Register Length Description Read/Write Data Type Value Value Value
2000 2 Additive Enable Read/Write disable/enable Enabled
2002 2 Flow Control Module# Read/Write unsigned int 0 31 0
2004 2 FCM Port# Read/Write unsigned int 0 3 0
disable/enable
2006 2 W&M Controlled Read/Write Disabled
disable/enabl
2008 2 Upstream Block Valve Read/Write Disabled
e
99999
2010 2 Tank Group Read/Write unsigned int 0 0
99
2012 2 Additive Type Read/Write disable/enable 0 4 0
unsigned 0.000
2014 2 Additive P Factor Read/Write 10 0.1
div10000 0
unsigned 0.000 0.600
2016 2 Additive I Time Read/Write 0.3
div10000 0 0
0.600
2018 2 Additive D Time Read/Write uint div10000 0.000 0
0

44
MULTILOAD II – MODBUS MAPPING

Min Max Default


Register Length Description Read/Write Data Type Value Value Value
unsigned div 20.000
2020 2 Additive No Flow mA Read/Write 0.000 0.000
1000
2022 2 Unused Read/Write
2032 2 Additive Mode Read/Write Additive Mode NONE
2034 2 Start Volume Read/Write unsigned int 0 65535 0
2036 2 Restart Volume Read/Write unsigned int 0 65535 0
2038 2 Solenoid Shut Pulses Read/Write unsigned int 0 255 0
2040 2 Shutoff Vol From End Read/Write unsigned int 0 65535 0
2042 2 LastInj Vol From End Read/Write unsigned int 0 65535 20
2044 2 Line Flush Min Vol Read/Write unsigned int 0 65535 0
2046 2 Assigned Component Read/Write unsigned int 0 8 0
W&M Recipe percent div 0.000 6.553
2048 2 Read/Write 0.0000%
Percentage 10000 0% 5%
2050 2 Add Check Start VOL Read/Write unsigned int 0 65535 0
2052 2 Unused Read/Write
unsigned
2054 2 Additive Vol/Inject Read/Write 0 6.5535 0.02
div10000
unsigned 0.000
2056 2 Vol/Inject Cal Factr Read/Write 6.5535 1
div10000 1
2058 2 Unused Read/Write
Additive Tol
2060 2 Read/Write Percent 0 100 0
Percentage
2062 2 Additive Mtr K-Factr Read/Write unsigned int 0 65535 2600
unsigned 0.000
2064 2 Additive Mtr Factor Read/Write 6.5535 1
div10000 1
2066 2 Max Pstn Missed Inj Read/Write unsigned int 0 65535 0
unsigned
2068 2 MaxSolenoid Inj Time Read/Write 0.1 10 4
div1000
2070 2 Under Add Alrm # Inj Read/Write unsigned int 0 65535 3
2072 2 Over Add Alrm # Inj Read/Write unsigned int 0 65535 3
2074 2 Check Add Tol Time Read/Write unsigned int 0 65535 10
2076 2 Unauth Flow Alrm Vol Read/Write unsigned int 0 65535 100
2078 2 Valve Fault Alrm Vol Read/Write unsigned int 0 65535 300
2080 2 Over Inject Vol Read/Write unsigned int 0 65535 0
2082 2 Creep Reset Time Read/Write unsigned int 0 65535 0
2084 2 Unauth Reset Time Read/Write unsigned int 0 65535 0
unsigned
2086 2 Max Pistn Throw Time Read/Write 0.1 10 1.8
div1000
2088 2 Pump Start Alrm Time Read/Write unsigned int 0 65535 2
2090 2 Meter Creep Alrm Vol Read/Write unsigned int 0 65535 150
2092 2 Remote Calibration Read/Write disable/enable Enabled

45
MULTILOAD II – MODBUS MAPPING

Min Max Default


Register Length Description Read/Write Data Type Value Value Value
2094 2 B.V. Open Alrm Time Read/Write unsigned int 0 65535 10
2096 2 B.V. Close Alrm Time Read/Write unsigned int 0 65535 10
2098 2 Pump Stop Delay Read/Write unsigned int 0 65535 3
2100 2 Flush Pump Run Time Read/Write unsigned int 0 65535 30
2102 2 Meter Flushed Read/Write disable/enable Disabled
2104 2 Solenoid Flushed Read/Write disable/enable Disabled
2106 2 Unused Read/Write
W&M Alarm Promo
2108 2 Read/Write unsigned int 0 65535 0
Count
W&M Alarm Reset
2110 2 Read/Write alarm count 0 10 0
Mode
2170 2 Unused Read/Write
2172 2 Unused Read/Write
2174 2 Unused Read/Write
Flush Pump Run
2176 2 Read/Write fcm address Disabled
FCM#
2178 2 Close Blk Val FCM# Read/Write fcm address Disabled
2180 2 Blk Val Status FCM# Read/Write fcm address Disabled
2182 2 Open Blk Val FCM# Read/Write fcm address Disabled
2184 2 Test Button FCM# Read/Write fcm address Disabled
2186 2 Pump Run FCM# Read/Write fcm address Disabled
2188 2 Pump Kill FCM# Read/Write fcm address Disabled
2190 2 Pump Status FCM# Read/Write fcm address Disabled
2192 2 Alarm Out FCM# Read/Write fcm address Disabled
2194 2 Authorized FCM# Read/Write fcm address Disabled
2196 2 Permiss FCM# Read/Write fcm address Disabled
2198 2 Permiss Out FCM# Read/Write fcm address Disabled

46
MULTILOAD II – MODBUS MAPPING

5
Chapter

Chapter 5 Real -Time Registers


This chapter outlines two types of Real-Time registers. The Real-Time Totalizers are continuously updated, while
the Real-Time value registers are update live and specific to the current batch.

Real-Time Totalizer Registers


5.1.1 Real-Time Preset Gross Totalizer

Register Length Preset Data Type Read/Write Min Value Max Value
3000 2 1 uint Read 0 1,000,000,000
3002 2 2 uint Read 0 1,000,000,000
3004 2 3 uint Read 0 1,000,000,000
3006 2 4 uint Read 0 1,000,000,000
3008 2 5 uint Read 0 1,000,000,000
3010 2 6 uint Read 0 1,000,000,000
3012 2 7 uint Read 0 1,000,000,000
3014 2 8 uint Read 0 1,000,000,000
3016 2 9 uint Read 0 1,000,000,000
3018 2 10 uint Read 0 1,000,000,000
3020 2 11 uint Read 0 1,000,000,000
3022 2 12 uint Read 0 1,000,000,000

5.1.2 Real-Time Meter Gross Totalizer

Register Length Preset Meter Data Type Read/Write Min Value Max Value
3024 2 1 1 uint Read 0 1,000,000,000
3026 2 1 2 uint Read 0 1,000,000,000
3028 2 1 3 uint Read 0 1,000,000,000
3030 2 1 4 uint Read 0 1,000,000,000
3032 2 1 5 uint Read 0 1,000,000,000
3034 2 2 1 uint Read 0 1,000,000,000
3036 2 2 2 uint Read 0 1,000,000,000
3038 2 2 3 uint Read 0 1,000,000,000
3040 2 2 4 uint Read 0 1,000,000,000

47
MULTILOAD II – MODBUS MAPPING

Register Length Preset Meter Data Type Read/Write Min Value Max Value
3042 2 2 5 uint Read 0 1,000,000,000
3044 2 3 1 uint Read 0 1,000,000,000
3046 2 3 2 uint Read 0 1,000,000,000
3048 2 3 3 uint Read 0 1,000,000,000
3050 2 3 4 uint Read 0 1,000,000,000
3052 2 3 5 uint Read 0 1,000,000,000
3054 2 4 1 uint Read 0 1,000,000,000
3056 2 4 2 uint Read 0 1,000,000,000
3058 2 4 3 uint Read 0 1,000,000,000
3060 2 4 4 uint Read 0 1,000,000,000
3062 2 4 5 uint Read 0 1,000,000,000
3064 2 5 1 uint Read 0 1,000,000,000
3066 2 5 2 uint Read 0 1,000,000,000
3068 2 5 3 uint Read 0 1,000,000,000
3070 2 5 4 uint Read 0 1,000,000,000
3072 2 5 5 uint Read 0 1,000,000,000
3074 2 6 1 uint Read 0 1,000,000,000
3076 2 6 2 uint Read 0 1,000,000,000
3078 2 6 3 uint Read 0 1,000,000,000
3080 2 6 4 uint Read 0 1,000,000,000
3082 2 6 5 uint Read 0 1,000,000,000
3084 2 7 1 uint Read 0 1,000,000,000
3086 2 7 2 uint Read 0 1,000,000,000
3088 2 7 3 uint Read 0 1,000,000,000
3090 2 7 4 uint Read 0 1,000,000,000
3092 2 7 5 uint Read 0 1,000,000,000
3094 2 8 1 uint Read 0 1,000,000,000
3096 2 8 2 uint Read 0 1,000,000,000
3098 2 8 3 uint Read 0 1,000,000,000
3100 2 8 4 uint Read 0 1,000,000,000
3102 2 8 5 uint Read 0 1,000,000,000
3104 2 9 1 uint Read 0 1,000,000,000
3106 2 9 2 uint Read 0 1,000,000,000
3108 2 9 3 uint Read 0 1,000,000,000
3110 2 9 4 uint Read 0 1,000,000,000
3112 2 9 5 uint Read 0 1,000,000,000
3114 2 10 1 uint Read 0 1,000,000,000
3116 2 10 2 uint Read 0 1,000,000,000
3118 2 10 3 uint Read 0 1,000,000,000
3120 2 10 4 uint Read 0 1,000,000,000
3122 2 10 5 uint Read 0 1,000,000,000

48
MULTILOAD II – MODBUS MAPPING

Register Length Preset Meter Data Type Read/Write Min Value Max Value
3124 2 11 1 uint Read 0 1,000,000,000
3126 2 11 2 uint Read 0 1,000,000,000
3128 2 11 3 uint Read 0 1,000,000,000
3130 2 11 4 uint Read 0 1,000,000,000
3132 2 11 5 uint Read 0 1,000,000,000
3134 2 12 1 uint Read 0 1,000,000,000
3136 2 12 2 uint Read 0 1,000,000,000
3138 2 12 3 uint Read 0 1,000,000,000
3140 2 12 4 uint Read 0 1,000,000,000
3142 2 12 5 uint Read 0 1,000,000,000

5.1.3 Real-Time Component Gross Totalizer

Register Length Preset Component Data Type Read/Write Min Value Max Value
3144 2 1 1 uint Read 0 1,000,000,000
3146 2 1 2 uint Read 0 1,000,000,000
3148 2 1 3 uint Read 0 1,000,000,000
3150 2 1 4 uint Read 0 1,000,000,000
3152 2 1 5 uint Read 0 1,000,000,000
3154 2 1 6 uint Read 0 1,000,000,000
3156 2 1 7 uint Read 0 1,000,000,000
3158 2 1 8 uint Read 0 1,000,000,000
3160 2 2 1 uint Read 0 1,000,000,000
3162 2 2 2 uint Read 0 1,000,000,000
3164 2 2 3 uint Read 0 1,000,000,000
3166 2 2 4 uint Read 0 1,000,000,000
3168 2 2 5 uint Read 0 1,000,000,000
3170 2 2 6 uint Read 0 1,000,000,000
3172 2 2 7 uint Read 0 1,000,000,000
3174 2 2 8 uint Read 0 1,000,000,000
3176 2 3 1 uint Read 0 1,000,000,000
3178 2 3 2 uint Read 0 1,000,000,000
3180 2 3 3 uint Read 0 1,000,000,000
3182 2 3 4 uint Read 0 1,000,000,000
3184 2 3 5 uint Read 0 1,000,000,000
3186 2 3 6 uint Read 0 1,000,000,000
3188 2 3 7 uint Read 0 1,000,000,000
3190 2 3 8 uint Read 0 1,000,000,000
3192 2 4 1 uint Read 0 1,000,000,000

49
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
3194 2 4 2 uint Read 0 1,000,000,000
3196 2 4 3 uint Read 0 1,000,000,000
3198 2 4 4 uint Read 0 1,000,000,000
3200 2 4 5 uint Read 0 1,000,000,000
3202 2 4 6 uint Read 0 1,000,000,000
3204 2 4 7 uint Read 0 1,000,000,000
3206 2 4 8 uint Read 0 1,000,000,000
3208 2 5 1 uint Read 0 1,000,000,000
3210 2 5 2 uint Read 0 1,000,000,000
3212 2 5 3 uint Read 0 1,000,000,000
3214 2 5 4 uint Read 0 1,000,000,000
3216 2 5 5 uint Read 0 1,000,000,000
3218 2 5 6 uint Read 0 1,000,000,000
3220 2 5 7 uint Read 0 1,000,000,000
3222 2 5 8 uint Read 0 1,000,000,000
3224 2 6 1 uint Read 0 1,000,000,000
3226 2 6 2 uint Read 0 1,000,000,000
3228 2 6 3 uint Read 0 1,000,000,000
3230 2 6 4 uint Read 0 1,000,000,000
3232 2 6 5 uint Read 0 1,000,000,000
3234 2 6 6 uint Read 0 1,000,000,000
3236 2 6 7 uint Read 0 1,000,000,000
3238 2 6 8 uint Read 0 1,000,000,000
3240 2 7 1 uint Read 0 1,000,000,000
3242 2 7 2 uint Read 0 1,000,000,000
3244 2 7 3 uint Read 0 1,000,000,000
3246 2 7 4 uint Read 0 1,000,000,000
3248 2 7 5 uint Read 0 1,000,000,000
3250 2 7 6 uint Read 0 1,000,000,000
3252 2 7 7 uint Read 0 1,000,000,000
3254 2 7 8 uint Read 0 1,000,000,000
3256 2 8 1 uint Read 0 1,000,000,000
3258 2 8 2 uint Read 0 1,000,000,000
3260 2 8 3 uint Read 0 1,000,000,000
3262 2 8 4 uint Read 0 1,000,000,000
3264 2 8 5 uint Read 0 1,000,000,000
3266 2 8 6 uint Read 0 1,000,000,000
3268 2 8 7 uint Read 0 1,000,000,000
3270 2 8 8 uint Read 0 1,000,000,000
3272 2 9 1 uint Read 0 1,000,000,000
3274 2 9 2 uint Read 0 1,000,000,000

50
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
3276 2 9 3 uint Read 0 1,000,000,000
3278 2 9 4 uint Read 0 1,000,000,000
3280 2 9 5 uint Read 0 1,000,000,000
3282 2 9 6 uint Read 0 1,000,000,000
3284 2 9 7 uint Read 0 1,000,000,000
3286 2 9 8 uint Read 0 1,000,000,000
3288 2 10 1 uint Read 0 1,000,000,000
3290 2 10 2 uint Read 0 1,000,000,000
3292 2 10 3 uint Read 0 1,000,000,000
3294 2 10 4 uint Read 0 1,000,000,000
3296 2 10 5 uint Read 0 1,000,000,000
3298 2 10 6 uint Read 0 1,000,000,000
3300 2 10 7 uint Read 0 1,000,000,000
3302 2 10 8 uint Read 0 1,000,000,000
3304 2 11 1 uint Read 0 1,000,000,000
3306 2 11 2 uint Read 0 1,000,000,000
3308 2 11 3 uint Read 0 1,000,000,000
3310 2 11 4 uint Read 0 1,000,000,000
3312 2 11 5 uint Read 0 1,000,000,000
3314 2 11 6 uint Read 0 1,000,000,000
3316 2 11 7 uint Read 0 1,000,000,000
3318 2 11 8 uint Read 0 1,000,000,000
3320 2 12 1 uint Read 0 1,000,000,000
3322 2 12 2 uint Read 0 1,000,000,000
3324 2 12 3 uint Read 0 1,000,000,000
3326 2 12 4 uint Read 0 1,000,000,000
3328 2 12 5 uint Read 0 1,000,000,000
3330 2 12 6 uint Read 0 1,000,000,000
3332 2 12 7 uint Read 0 1,000,000,000
3334 2 12 8 uint Read 0 1,000,000,000

5.1.4 Real-Time Additive Gross Totalizer

Register Length Preset Additive Data Type Read/Write Min Value Max Value
3336 2 1 1 uint Read 0 1,000,000,000
3338 2 1 2 uint Read 0 1,000,000,000
3340 2 1 3 uint Read 0 1,000,000,000
3342 2 1 4 uint Read 0 1,000,000,000
3344 2 1 5 uint Read 0 1,000,000,000
3346 2 1 6 uint Read 0 1,000,000,000

51
MULTILOAD II – MODBUS MAPPING

Register Length Preset Additive Data Type Read/Write Min Value Max Value
3348 2 1 7 uint Read 0 1,000,000,000
3350 2 1 8 uint Read 0 1,000,000,000
3352 2 1 9 uint Read 0 1,000,000,000
3354 2 1 10 uint Read 0 1,000,000,000
3356 2 1 11 uint Read 0 1,000,000,000
3358 2 1 12 uint Read 0 1,000,000,000
3360 2 1 13 uint Read 0 1,000,000,000
3362 2 1 14 uint Read 0 1,000,000,000
3364 2 1 15 uint Read 0 1,000,000,000
3366 2 1 16 uint Read 0 1,000,000,000
3368 2 2 1 uint Read 0 1,000,000,000
3370 2 2 2 uint Read 0 1,000,000,000
3372 2 2 3 uint Read 0 1,000,000,000
3374 2 2 4 uint Read 0 1,000,000,000
3376 2 2 5 uint Read 0 1,000,000,000
3378 2 2 6 uint Read 0 1,000,000,000
3380 2 2 7 uint Read 0 1,000,000,000
3382 2 2 8 uint Read 0 1,000,000,000
3384 2 2 9 uint Read 0 1,000,000,000
3386 2 2 10 uint Read 0 1,000,000,000
3388 2 2 11 uint Read 0 1,000,000,000
3390 2 2 12 uint Read 0 1,000,000,000
3392 2 2 13 uint Read 0 1,000,000,000
3394 2 2 14 uint Read 0 1,000,000,000
3396 2 2 15 uint Read 0 1,000,000,000
3398 2 2 16 uint Read 0 1,000,000,000
3400 2 3 1 uint Read 0 1,000,000,000
3402 2 3 2 uint Read 0 1,000,000,000
3404 2 3 3 uint Read 0 1,000,000,000
3406 2 3 4 uint Read 0 1,000,000,000
3408 2 3 5 uint Read 0 1,000,000,000
3410 2 3 6 uint Read 0 1,000,000,000
3412 2 3 7 uint Read 0 1,000,000,000
3414 2 3 8 uint Read 0 1,000,000,000
3416 2 3 9 uint Read 0 1,000,000,000
3418 2 3 10 uint Read 0 1,000,000,000
3420 2 3 11 uint Read 0 1,000,000,000
3422 2 3 12 uint Read 0 1,000,000,000
3424 2 3 13 uint Read 0 1,000,000,000
3426 2 3 14 uint Read 0 1,000,000,000
3428 2 3 15 uint Read 0 1,000,000,000

52
MULTILOAD II – MODBUS MAPPING

Register Length Preset Additive Data Type Read/Write Min Value Max Value
3430 2 3 16 uint Read 0 1,000,000,000
3432 2 4 1 uint Read 0 1,000,000,000
3434 2 4 2 uint Read 0 1,000,000,000
3436 2 4 3 uint Read 0 1,000,000,000
3438 2 4 4 uint Read 0 1,000,000,000
3440 2 4 5 uint Read 0 1,000,000,000
3442 2 4 6 uint Read 0 1,000,000,000
3444 2 4 7 uint Read 0 1,000,000,000
3446 2 4 8 uint Read 0 1,000,000,000
3448 2 4 9 uint Read 0 1,000,000,000
3450 2 4 10 uint Read 0 1,000,000,000
3452 2 4 11 uint Read 0 1,000,000,000
3454 2 4 12 uint Read 0 1,000,000,000
3456 2 4 13 uint Read 0 1,000,000,000
3458 2 4 14 uint Read 0 1,000,000,000
3460 2 4 15 uint Read 0 1,000,000,000
3462 2 4 16 uint Read 0 1,000,000,000
3464 2 5 1 uint Read 0 1,000,000,000
3466 2 5 2 uint Read 0 1,000,000,000
3468 2 5 3 uint Read 0 1,000,000,000
3470 2 5 4 uint Read 0 1,000,000,000
3472 2 5 5 uint Read 0 1,000,000,000
3474 2 5 6 uint Read 0 1,000,000,000
3476 2 5 7 uint Read 0 1,000,000,000
3478 2 5 8 uint Read 0 1,000,000,000
3480 2 5 9 uint Read 0 1,000,000,000
3482 2 5 10 uint Read 0 1,000,000,000
3484 2 5 11 uint Read 0 1,000,000,000
3486 2 5 12 uint Read 0 1,000,000,000
3488 2 5 13 uint Read 0 1,000,000,000
3490 2 5 14 uint Read 0 1,000,000,000
3492 2 5 15 uint Read 0 1,000,000,000
3494 2 5 16 uint Read 0 1,000,000,000
3496 2 6 1 uint Read 0 1,000,000,000
3498 2 6 2 uint Read 0 1,000,000,000
3500 2 6 3 uint Read 0 1,000,000,000
3502 2 6 4 uint Read 0 1,000,000,000
3504 2 6 5 uint Read 0 1,000,000,000
3506 2 6 6 uint Read 0 1,000,000,000
3508 2 6 7 uint Read 0 1,000,000,000
3510 2 6 8 uint Read 0 1,000,000,000

53
MULTILOAD II – MODBUS MAPPING

Register Length Preset Additive Data Type Read/Write Min Value Max Value
3512 2 6 9 uint Read 0 1,000,000,000
3514 2 6 10 uint Read 0 1,000,000,000
3516 2 6 11 uint Read 0 1,000,000,000
3518 2 6 12 uint Read 0 1,000,000,000
3520 2 6 13 uint Read 0 1,000,000,000
3522 2 6 14 uint Read 0 1,000,000,000
3524 2 6 15 uint Read 0 1,000,000,000
3526 2 6 16 uint Read 0 1,000,000,000
3528 2 7 1 uint Read 0 1,000,000,000
3530 2 7 2 uint Read 0 1,000,000,000
3532 2 7 3 uint Read 0 1,000,000,000
3534 2 7 4 uint Read 0 1,000,000,000
3536 2 7 5 uint Read 0 1,000,000,000
3538 2 7 6 uint Read 0 1,000,000,000
3540 2 7 7 uint Read 0 1,000,000,000
3542 2 7 8 uint Read 0 1,000,000,000
3544 2 7 9 uint Read 0 1,000,000,000
3546 2 7 10 uint Read 0 1,000,000,000
3548 2 7 11 uint Read 0 1,000,000,000
3550 2 7 12 uint Read 0 1,000,000,000
3552 2 7 13 uint Read 0 1,000,000,000
3554 2 7 14 uint Read 0 1,000,000,000
3556 2 7 15 uint Read 0 1,000,000,000
3558 2 7 16 uint Read 0 1,000,000,000
3560 2 8 1 uint Read 0 1,000,000,000
3562 2 8 2 uint Read 0 1,000,000,000
3564 2 8 3 uint Read 0 1,000,000,000
3566 2 8 4 uint Read 0 1,000,000,000
3568 2 8 5 uint Read 0 1,000,000,000
3570 2 8 6 uint Read 0 1,000,000,000
3572 2 8 7 uint Read 0 1,000,000,000
3574 2 8 8 uint Read 0 1,000,000,000
3576 2 8 9 uint Read 0 1,000,000,000
3578 2 8 10 uint Read 0 1,000,000,000
3580 2 8 11 uint Read 0 1,000,000,000
3582 2 8 12 uint Read 0 1,000,000,000
3584 2 8 13 uint Read 0 1,000,000,000
3586 2 8 14 uint Read 0 1,000,000,000
3588 2 8 15 uint Read 0 1,000,000,000
3590 2 8 16 uint Read 0 1,000,000,000
3592 2 9 1 uint Read 0 1,000,000,000

54
MULTILOAD II – MODBUS MAPPING

Register Length Preset Additive Data Type Read/Write Min Value Max Value
3594 2 9 2 uint Read 0 1,000,000,000
3596 2 9 3 uint Read 0 1,000,000,000
3598 2 9 4 uint Read 0 1,000,000,000
3600 2 9 5 uint Read 0 1,000,000,000
3602 2 9 6 uint Read 0 1,000,000,000
3604 2 9 7 uint Read 0 1,000,000,000
3606 2 9 8 uint Read 0 1,000,000,000
3608 2 9 9 uint Read 0 1,000,000,000
3610 2 9 10 uint Read 0 1,000,000,000
3612 2 9 11 uint Read 0 1,000,000,000
3614 2 9 12 uint Read 0 1,000,000,000
3616 2 9 13 uint Read 0 1,000,000,000
3618 2 9 14 uint Read 0 1,000,000,000
3620 2 9 15 uint Read 0 1,000,000,000
3622 2 9 16 uint Read 0 1,000,000,000
3624 2 10 1 uint Read 0 1,000,000,000
3626 2 10 2 uint Read 0 1,000,000,000
3628 2 10 3 uint Read 0 1,000,000,000
3630 2 10 4 uint Read 0 1,000,000,000
3632 2 10 5 uint Read 0 1,000,000,000
3634 2 10 6 uint Read 0 1,000,000,000
3636 2 10 7 uint Read 0 1,000,000,000
3638 2 10 8 uint Read 0 1,000,000,000
3640 2 10 9 uint Read 0 1,000,000,000
3642 2 10 10 uint Read 0 1,000,000,000
3644 2 10 11 uint Read 0 1,000,000,000
3646 2 10 12 uint Read 0 1,000,000,000
3648 2 10 13 uint Read 0 1,000,000,000
3650 2 10 14 uint Read 0 1,000,000,000
3652 2 10 15 uint Read 0 1,000,000,000
3654 2 10 16 uint Read 0 1,000,000,000
3656 2 11 1 uint Read 0 1,000,000,000
3658 2 11 2 uint Read 0 1,000,000,000
3660 2 11 3 uint Read 0 1,000,000,000
3662 2 11 4 uint Read 0 1,000,000,000
3664 2 11 5 uint Read 0 1,000,000,000
3666 2 11 6 uint Read 0 1,000,000,000
3668 2 11 7 uint Read 0 1,000,000,000
3670 2 11 8 uint Read 0 1,000,000,000
3672 2 11 9 uint Read 0 1,000,000,000
3674 2 11 10 uint Read 0 1,000,000,000

55
MULTILOAD II – MODBUS MAPPING

Register Length Preset Additive Data Type Read/Write Min Value Max Value
3676 2 11 11 uint Read 0 1,000,000,000
3678 2 11 12 uint Read 0 1,000,000,000
3680 2 11 13 uint Read 0 1,000,000,000
3682 2 11 14 uint Read 0 1,000,000,000
3684 2 11 15 uint Read 0 1,000,000,000
3686 2 11 16 uint Read 0 1,000,000,000
3688 2 12 1 uint Read 0 1,000,000,000
3690 2 12 2 uint Read 0 1,000,000,000
3692 2 12 3 uint Read 0 1,000,000,000
3694 2 12 4 uint Read 0 1,000,000,000
3696 2 12 5 uint Read 0 1,000,000,000
3698 2 12 6 uint Read 0 1,000,000,000
3700 2 12 7 uint Read 0 1,000,000,000
3702 2 12 8 uint Read 0 1,000,000,000
3704 2 12 9 uint Read 0 1,000,000,000
3706 2 12 10 uint Read 0 1,000,000,000
3708 2 12 11 uint Read 0 1,000,000,000
3710 2 12 12 uint Read 0 1,000,000,000
3712 2 12 13 uint Read 0 1,000,000,000
3714 2 12 14 uint Read 0 1,000,000,000
3716 2 12 15 uint Read 0 1,000,000,000
3718 2 12 16 uint Read 0 1,000,000,000

5.1.5 Real-Time Preset Net Totalizer

Register Length Preset Data Type Read/Write Min Value Max Value
3720 2 1 uint Read 0 1,000,000,000
3722 2 2 uint Read 0 1,000,000,000
3724 2 3 uint Read 0 1,000,000,000
3726 2 4 uint Read 0 1,000,000,000
3728 2 5 uint Read 0 1,000,000,000
3730 2 6 uint Read 0 1,000,000,000
3732 2 7 uint Read 0 1,000,000,000
3734 2 8 uint Read 0 1,000,000,000
3736 2 9 uint Read 0 1,000,000,000
3738 2 10 uint Read 0 1,000,000,000
3740 2 11 uint Read 0 1,000,000,000
3742 2 12 uint Read 0 1,000,000,000

56
MULTILOAD II – MODBUS MAPPING

5.1.6 Real-Time Component Net Totalizer

Register Length Preset Component Data Type Read/Write Min Value Max Value
3744 2 1 1 uint Read 0 1,000,000,000
3746 2 1 2 uint Read 0 1,000,000,000
3748 2 1 3 uint Read 0 1,000,000,000
3750 2 1 4 uint Read 0 1,000,000,000
3752 2 1 5 uint Read 0 1,000,000,000
3754 2 1 6 uint Read 0 1,000,000,000
3756 2 1 7 uint Read 0 1,000,000,000
3758 2 1 8 uint Read 0 1,000,000,000
3760 2 2 1 uint Read 0 1,000,000,000
3762 2 2 2 uint Read 0 1,000,000,000
3764 2 2 3 uint Read 0 1,000,000,000
3766 2 2 4 uint Read 0 1,000,000,000
3768 2 2 5 uint Read 0 1,000,000,000
3770 2 2 6 uint Read 0 1,000,000,000
3772 2 2 7 uint Read 0 1,000,000,000
3774 2 2 8 uint Read 0 1,000,000,000
3776 2 3 1 uint Read 0 1,000,000,000
3778 2 3 2 uint Read 0 1,000,000,000
3780 2 3 3 uint Read 0 1,000,000,000
3782 2 3 4 uint Read 0 1,000,000,000
3784 2 3 5 uint Read 0 1,000,000,000
3786 2 3 6 uint Read 0 1,000,000,000
3788 2 3 7 uint Read 0 1,000,000,000
3790 2 3 8 uint Read 0 1,000,000,000
3792 2 4 1 uint Read 0 1,000,000,000
3794 2 4 2 uint Read 0 1,000,000,000
3796 2 4 3 uint Read 0 1,000,000,000
3798 2 4 4 uint Read 0 1,000,000,000
3800 2 4 5 uint Read 0 1,000,000,000
3802 2 4 6 uint Read 0 1,000,000,000
3804 2 4 7 uint Read 0 1,000,000,000
3806 2 4 8 uint Read 0 1,000,000,000
3808 2 5 1 uint Read 0 1,000,000,000
3810 2 5 2 uint Read 0 1,000,000,000
3812 2 5 3 uint Read 0 1,000,000,000
3814 2 5 4 uint Read 0 1,000,000,000
3816 2 5 5 uint Read 0 1,000,000,000
3818 2 5 6 uint Read 0 1,000,000,000

57
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
3820 2 5 7 uint Read 0 1,000,000,000
3822 2 5 8 uint Read 0 1,000,000,000
3824 2 6 1 uint Read 0 1,000,000,000
3826 2 6 2 uint Read 0 1,000,000,000
3828 2 6 3 uint Read 0 1,000,000,000
3830 2 6 4 uint Read 0 1,000,000,000
3832 2 6 5 uint Read 0 1,000,000,000
3834 2 6 6 uint Read 0 1,000,000,000
3836 2 6 7 uint Read 0 1,000,000,000
3838 2 6 8 uint Read 0 1,000,000,000
3840 2 7 1 uint Read 0 1,000,000,000
3842 2 7 2 uint Read 0 1,000,000,000
3844 2 7 3 uint Read 0 1,000,000,000
3846 2 7 4 uint Read 0 1,000,000,000
3848 2 7 5 uint Read 0 1,000,000,000
3850 2 7 6 uint Read 0 1,000,000,000
3852 2 7 7 uint Read 0 1,000,000,000
3854 2 7 8 uint Read 0 1,000,000,000
3856 2 8 1 uint Read 0 1,000,000,000
3858 2 8 2 uint Read 0 1,000,000,000
3860 2 8 3 uint Read 0 1,000,000,000
3862 2 8 4 uint Read 0 1,000,000,000
3864 2 8 5 uint Read 0 1,000,000,000
3866 2 8 6 uint Read 0 1,000,000,000
3868 2 8 7 uint Read 0 1,000,000,000
3870 2 8 8 uint Read 0 1,000,000,000
3872 2 9 1 uint Read 0 1,000,000,000
3874 2 9 2 uint Read 0 1,000,000,000
3876 2 9 3 uint Read 0 1,000,000,000
3878 2 9 4 uint Read 0 1,000,000,000
3880 2 9 5 uint Read 0 1,000,000,000
3882 2 9 6 uint Read 0 1,000,000,000
3884 2 9 7 uint Read 0 1,000,000,000
3886 2 9 8 uint Read 0 1,000,000,000
3888 2 10 1 uint Read 0 1,000,000,000
3890 2 10 2 uint Read 0 1,000,000,000
3892 2 10 3 uint Read 0 1,000,000,000
3894 2 10 4 uint Read 0 1,000,000,000
3896 2 10 5 uint Read 0 1,000,000,000
3898 2 10 6 uint Read 0 1,000,000,000
3900 2 10 7 uint Read 0 1,000,000,000

58
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
3902 2 10 8 uint Read 0 1,000,000,000
3904 2 11 1 uint Read 0 1,000,000,000
3906 2 11 2 uint Read 0 1,000,000,000
3908 2 11 3 uint Read 0 1,000,000,000
3910 2 11 4 uint Read 0 1,000,000,000
3912 2 11 5 uint Read 0 1,000,000,000
3914 2 11 6 uint Read 0 1,000,000,000
3916 2 11 7 uint Read 0 1,000,000,000
3918 2 11 8 uint Read 0 1,000,000,000
3920 2 12 1 uint Read 0 1,000,000,000
3922 2 12 2 uint Read 0 1,000,000,000
3924 2 12 3 uint Read 0 1,000,000,000
3926 2 12 4 uint Read 0 1,000,000,000
3928 2 12 5 uint Read 0 1,000,000,000
3930 2 12 6 uint Read 0 1,000,000,000
3932 2 12 7 uint Read 0 1,000,000,000
3934 2 12 8 uint Read 0 1,000,000,000

5.1.7 Real-Time Preset Mass Totalizer

Register Length Preset Data Type Read/Write Min Value Max Value
11720 2 1 Read uint 0 1,000,000,000
11722 2 2 Read uint 0 1,000,000,000
11724 2 3 Read uint 0 1,000,000,000
11726 2 4 Read uint 0 1,000,000,000
11728 2 5 Read uint 0 1,000,000,000
11730 2 6 Read uint 0 1,000,000,000
11732 2 7 Read uint 0 1,000,000,000
11734 2 8 Read uint 0 1,000,000,000
11736 2 9 Read uint 0 1,000,000,000
11738 2 10 Read uint 0 1,000,000,000
11740 2 11 Read uint 0 1,000,000,000
11742 2 12 Read uint 0 1,000,000,000

5.1.8 Real-Time Component Mass Totalizer

Register Length Preset Meter Data Type Read/Write Min Value Max Value
11744 2 1 1 Read uint 0 1,000,000,000
11746 2 1 2 Read uint 0 1,000,000,000
11748 2 1 3 Read uint 0 1,000,000,000

59
MULTILOAD II – MODBUS MAPPING

Register Length Preset Meter Data Type Read/Write Min Value Max Value
11750 2 1 4 Read uint 0 1,000,000,000
11752 2 1 5 Read uint 0 1,000,000,000
11754 2 1 6 Read uint 0 1,000,000,000
11756 2 1 7 Read uint 0 1,000,000,000
11758 2 1 8 Read uint 0 1,000,000,000
11760 2 2 1 Read uint 0 1,000,000,000
11762 2 2 2 Read uint 0 1,000,000,000
11764 2 2 3 Read uint 0 1,000,000,000
11766 2 2 4 Read uint 0 1,000,000,000
11768 2 2 5 Read uint 0 1,000,000,000
11770 2 2 6 Read uint 0 1,000,000,000
11772 2 2 7 Read uint 0 1,000,000,000
11774 2 2 8 Read uint 0 1,000,000,000
11776 2 3 1 Read uint 0 1,000,000,000
11778 2 3 2 Read uint 0 1,000,000,000
11780 2 3 3 Read uint 0 1,000,000,000
11782 2 3 4 Read uint 0 1,000,000,000
11784 2 3 5 Read uint 0 1,000,000,000
11786 2 3 6 Read uint 0 1,000,000,000
11788 2 3 7 Read uint 0 1,000,000,000
11790 2 3 8 Read uint 0 1,000,000,000
11792 2 4 1 Read uint 0 1,000,000,000
11794 2 4 2 Read uint 0 1,000,000,000
11796 2 4 3 Read uint 0 1,000,000,000
11798 2 4 4 Read uint 0 1,000,000,000
11800 2 4 5 Read uint 0 1,000,000,000
11802 2 4 6 Read uint 0 1,000,000,000
11804 2 4 7 Read uint 0 1,000,000,000
11806 2 4 8 Read uint 0 1,000,000,000
11808 2 5 1 Read uint 0 1,000,000,000
11810 2 5 2 Read uint 0 1,000,000,000
11812 2 5 3 Read uint 0 1,000,000,000
11814 2 5 4 Read uint 0 1,000,000,000
11816 2 5 5 Read uint 0 1,000,000,000
11818 2 5 6 Read uint 0 1,000,000,000
11820 2 5 7 Read uint 0 1,000,000,000
11822 2 5 8 Read uint 0 1,000,000,000
11824 2 6 1 Read uint 0 1,000,000,000
11826 2 6 2 Read uint 0 1,000,000,000
11828 2 6 3 Read uint 0 1,000,000,000
11830 2 6 4 Read uint 0 1,000,000,000

60
MULTILOAD II – MODBUS MAPPING

Register Length Preset Meter Data Type Read/Write Min Value Max Value
11832 2 6 5 Read uint 0 1,000,000,000
11834 2 6 6 Read uint 0 1,000,000,000
11836 2 6 7 Read uint 0 1,000,000,000
11838 2 6 8 Read uint 0 1,000,000,000
11840 2 7 1 Read uint 0 1,000,000,000
11842 2 7 2 Read uint 0 1,000,000,000
11844 2 7 3 Read uint 0 1,000,000,000
11846 2 7 4 Read uint 0 1,000,000,000
11848 2 7 5 Read uint 0 1,000,000,000
11850 2 7 6 Read uint 0 1,000,000,000
11852 2 7 7 Read uint 0 1,000,000,000
11854 2 7 8 Read uint 0 1,000,000,000
11856 2 8 1 Read uint 0 1,000,000,000
11858 2 8 2 Read uint 0 1,000,000,000
11860 2 8 3 Read uint 0 1,000,000,000
11862 2 8 4 Read uint 0 1,000,000,000
11864 2 8 5 Read uint 0 1,000,000,000
11866 2 8 6 Read uint 0 1,000,000,000
11868 2 8 7 Read uint 0 1,000,000,000
11870 2 8 8 Read uint 0 1,000,000,000
11872 2 9 1 Read uint 0 1,000,000,000
11874 2 9 2 Read uint 0 1,000,000,000
11876 2 9 3 Read uint 0 1,000,000,000
11878 2 9 4 Read uint 0 1,000,000,000
11880 2 9 5 Read uint 0 1,000,000,000
11882 2 9 6 Read uint 0 1,000,000,000
11884 2 9 7 Read uint 0 1,000,000,000
11886 2 9 8 Read uint 0 1,000,000,000
11888 2 10 1 Read uint 0 1,000,000,000
11890 2 10 2 Read uint 0 1,000,000,000
11892 2 10 3 Read uint 0 1,000,000,000
11894 2 10 4 Read uint 0 1,000,000,000
11896 2 10 5 Read uint 0 1,000,000,000
11898 2 10 6 Read uint 0 1,000,000,000
11900 2 10 7 Read uint 0 1,000,000,000
11902 2 10 8 Read uint 0 1,000,000,000
11904 2 11 1 Read uint 0 1,000,000,000
11906 2 11 2 Read uint 0 1,000,000,000
11908 2 11 3 Read uint 0 1,000,000,000
11910 2 11 4 Read uint 0 1,000,000,000
11912 2 11 5 Read uint 0 1,000,000,000

61
MULTILOAD II – MODBUS MAPPING

Register Length Preset Meter Data Type Read/Write Min Value Max Value
11914 2 11 6 Read uint 0 1,000,000,000
11916 2 11 7 Read uint 0 1,000,000,000
11918 2 11 8 Read uint 0 1,000,000,000
11920 2 12 1 Read uint 0 1,000,000,000
11922 2 12 2 Read uint 0 1,000,000,000
11924 2 12 3 Read uint 0 1,000,000,000
11926 2 12 4 Read uint 0 1,000,000,000
11928 2 12 5 Read uint 0 1,000,000,000
11930 2 12 6 Read uint 0 1,000,000,000
11932 2 12 7 Read uint 0 1,000,000,000
11934 2 12 8 Read uint 0 1,000,000,000

Real-Time Value Registers


5.2.1 Preset quantity in whole units

Register Length Preset Data Type Read/Write Min Value Max Value
4036 2 1 uint Read 0 9,999,999
4038 2 2 uint Read 0 9,999,999
4040 2 3 uint Read 0 9,999,999
4042 2 4 uint Read 0 9,999,999
4044 2 5 uint Read 0 9,999,999
4046 2 6 uint Read 0 9,999,999
4048 2 7 uint Read 0 9,999,999
4050 2 8 uint Read 0 9,999,999
4052 2 9 uint Read 0 9,999,999
4054 2 10 uint Read 0 9,999,999
4056 2 11 uint Read 0 9,999,999
4058 2 12 uint Read 0 9,999,999

5.2.2 Preset Delivered Gross Quantity in Whole Units

Register Length Preset Data Type Read/Write Min Value Max Value
4060 2 1 uint Read 0 9,999,999
4062 2 2 uint Read 0 9,999,999
4064 2 3 uint Read 0 9,999,999
4066 2 4 uint Read 0 9,999,999
4068 2 5 uint Read 0 9,999,999
4070 2 6 uint Read 0 9,999,999
4072 2 7 uint Read 0 9,999,999
4074 2 8 uint Read 0 9,999,999

62
MULTILOAD II – MODBUS MAPPING

Register Length Preset Data Type Read/Write Min Value Max Value
4076 2 9 uint Read 0 9,999,999
4078 2 10 uint Read 0 9,999,999
4080 2 11 uint Read 0 9,999,999
4082 2 12 uint Read 0 9,999,999
5.2.3 Preset Delivered Net Quantity in Whole Units

Register Length Preset Data Type Read/Write Min Value Max Value
4084 2 1 uint Read 0 9,999,999
4086 2 2 uint Read 0 9,999,999
4088 2 3 uint Read 0 9,999,999
4090 2 4 uint Read 0 9,999,999
4092 2 5 uint Read 0 9,999,999
4094 2 6 uint Read 0 9,999,999
4096 2 7 uint Read 0 9,999,999
4098 2 8 uint Read 0 9,999,999
4100 2 9 uint Read 0 9,999,999
4102 2 10 uint Read 0 9,999,999
4104 2 11 uint Read 0 9,999,999
4106 2 12 uint Read 0 9,999,999

5.2.4 Preset Batch Average Temp in Tenths or Hundredths

Register Length Preset Data Type Read/Write Min Value Max Value
4108 2 1 int Read -50.00 350.00
4110 2 2 int Read -50.00 350.00
4112 2 3 int Read -50.00 350.00
4114 2 4 int Read -50.00 350.00
4116 2 5 int Read -50.00 350.00
4118 2 6 int Read -50.00 350.00
4120 2 7 int Read -50.00 350.00
4122 2 8 int Read -50.00 350.00
4124 2 9 int Read -50.00 350.00
4126 2 10 int Read -50.00 350.00
4128 2 11 int Read -50.00 350.00
4130 2 12 int Read -50.00 350.00

5.2.5 Batch Average Pressure in Tenths or Hundredths

Register Length Preset Data Type Read/Write Min Value Max Value
4132 2 1 int Read -20.00 650.00

63
MULTILOAD II – MODBUS MAPPING

Register Length Preset Data Type Read/Write Min Value Max Value
4134 2 2 int Read -20.00 650.00
4136 2 3 int Read -20.00 650.00
4138 2 4 int Read -20.00 650.00
4140 2 5 int Read -20.00 650.00
4142 2 6 int Read -20.00 650.00
4144 2 7 int Read -20.00 650.00
4146 2 8 int Read -20.00 650.00
4148 2 9 int Read -20.00 650.00
4150 2 10 int Read -20.00 650.00
4152 2 11 int Read -20.00 650.00
4154 2 12 int Read -20.00 650.00

5.2.6 Preset Batch Average Density/Relative Density/Gravity

Register Length Preset Data Type Read/Write Min Value Max Value
4156 2 1 int Read -100.00 1200.00
4158 2 2 int Read -100.00 1200.00
4160 2 3 int Read -100.00 1200.00
4162 2 4 int Read -100.00 1200.00
4164 2 5 int Read -100.00 1200.00
4166 2 6 int Read -100.00 1200.00
4168 2 7 int Read -100.00 1200.00
4170 2 8 int Read -100.00 1200.00
4172 2 9 int Read -100.00 1200.00
4174 2 10 int Read -100.00 1200.00
4176 2 11 int Read -100.00 1200.00
4178 2 12 int Read -100.00 1200.00

5.2.7 Preset Gross Flow Rate in Whole Units

Register Length Preset Data Type Read/Write Min Value Max Value
4180 1 1 uint Read 0 65535
4181 1 2 uint Read 0 65535
4182 1 3 uint Read 0 65535
4183 1 4 uint Read 0 65535
4184 1 5 uint Read 0 65535
4185 1 6 uint Read 0 65535
4186 1 7 uint Read 0 65535
4187 1 8 uint Read 0 65535
4188 1 9 uint Read 0 65535

64
MULTILOAD II – MODBUS MAPPING

Register Length Preset Data Type Read/Write Min Value Max Value
4189 1 10 uint Read 0 65535
4190 1 11 uint Read 0 65535
4191 1 12 uint Read 0 65535

5.2.8 Meter Delivered Gross Quantity in Whole Units

Register Length Preset Meter Data Type Read/Write Min Value Max Value
4192 2 1 1 uint Read 0 65535
4194 2 1 2 uint Read 0 65535
4196 2 1 3 uint Read 0 65535
4198 2 1 4 uint Read 0 65535
4200 2 1 5 uint Read 0 65535
4202 2 2 1 uint Read 0 65535
4204 2 2 2 uint Read 0 65535
4206 2 2 3 uint Read 0 65535
4208 2 2 4 uint Read 0 65535
4210 2 2 5 uint Read 0 65535
4212 2 3 1 uint Read 0 65535
4214 2 3 2 uint Read 0 65535
4216 2 3 3 uint Read 0 65535
4218 2 3 4 uint Read 0 65535
4220 2 3 5 uint Read 0 65535
4222 2 4 1 uint Read 0 65535
4224 2 4 2 uint Read 0 65535
4226 2 4 3 uint Read 0 65535
4228 2 4 4 uint Read 0 65535
4230 2 4 5 uint Read 0 65535
4232 2 5 1 uint Read 0 65535
4234 2 5 2 uint Read 0 65535
4236 2 5 3 uint Read 0 65535
4238 2 5 4 uint Read 0 65535
4240 2 5 5 uint Read 0 65535
4242 2 6 1 uint Read 0 65535
4244 2 6 2 uint Read 0 65535
4246 2 6 3 uint Read 0 65535
4248 2 6 4 uint Read 0 65535
4250 2 6 5 uint Read 0 65535
4252 2 7 1 uint Read 0 65535
4254 2 7 2 uint Read 0 65535
4256 2 7 3 uint Read 0 65535
4258 2 7 4 uint Read 0 65535

65
MULTILOAD II – MODBUS MAPPING

Register Length Preset Meter Data Type Read/Write Min Value Max Value
4260 2 7 5 uint Read 0 65535
4262 2 8 1 uint Read 0 65535
4264 2 8 2 uint Read 0 65535
4266 2 8 3 uint Read 0 65535
4268 2 8 4 uint Read 0 65535
4270 2 8 5 uint Read 0 65535
4272 2 9 1 uint Read 0 65535
4274 2 9 2 uint Read 0 65535
4276 2 9 3 uint Read 0 65535
4278 2 9 4 uint Read 0 65535
4280 2 9 5 uint Read 0 65535
4282 2 10 1 uint Read 0 65535
4284 2 10 2 uint Read 0 65535
4286 2 10 3 uint Read 0 65535
4288 2 10 4 uint Read 0 65535
4290 2 10 5 uint Read 0 65535
4292 2 11 1 uint Read 0 65535
4294 2 11 2 uint Read 0 65535
4296 2 11 3 uint Read 0 65535
4298 2 11 4 uint Read 0 65535
4300 2 11 5 uint Read 0 65535
4302 2 12 1 uint Read 0 65535
4304 2 12 2 uint Read 0 65535
4306 2 12 3 uint Read 0 65535
4308 2 12 4 uint Read 0 65535
4310 2 12 5 uint Read 0 65535

5.2.9 Meter Gross Flow Rate in Whole Units

Register Length Preset Meter Data Type Read/Write Min Value Max Value
4312 1 1 1 uint Read 0 65535
4313 1 1 2 uint Read 0 65535
4314 1 1 3 uint Read 0 65535
4315 1 1 4 uint Read 0 65535
4316 1 1 5 uint Read 0 65535
4317 1 2 1 uint Read 0 65535
4318 1 2 2 uint Read 0 65535
4319 1 2 3 uint Read 0 65535
4320 1 2 4 uint Read 0 65535
4321 1 2 5 uint Read 0 65535

66
MULTILOAD II – MODBUS MAPPING

Register Length Preset Meter Data Type Read/Write Min Value Max Value
4322 1 3 1 uint Read 0 65535
4323 1 3 2 uint Read 0 65535
4324 1 3 3 uint Read 0 65535
4325 1 3 4 uint Read 0 65535
4326 1 3 5 uint Read 0 65535
4327 1 4 1 uint Read 0 65535
4328 1 4 2 uint Read 0 65535
4329 1 4 3 uint Read 0 65535
4330 1 4 4 uint Read 0 65535
4331 1 4 5 uint Read 0 65535
4332 1 5 1 uint Read 0 65535
4333 1 5 2 uint Read 0 65535
4334 1 5 3 uint Read 0 65535
4335 1 5 4 uint Read 0 65535
4336 1 5 5 uint Read 0 65535
4337 1 6 1 uint Read 0 65535
4338 1 6 2 uint Read 0 65535
4339 1 6 3 uint Read 0 65535
4340 1 6 4 uint Read 0 65535
4341 1 6 5 uint Read 0 65535
4342 1 7 1 uint Read 0 65535
4343 1 7 2 uint Read 0 65535
4344 1 7 3 uint Read 0 65535
4345 1 7 4 uint Read 0 65535
4346 1 7 5 uint Read 0 65535
4347 1 8 1 uint Read 0 65535
4348 1 8 2 uint Read 0 65535
4349 1 8 3 uint Read 0 65535
4350 1 8 4 uint Read 0 65535
4351 1 8 5 uint Read 0 65535
4352 1 9 1 uint Read 0 65535
4353 1 9 2 uint Read 0 65535
4354 1 9 3 uint Read 0 65535
4355 1 9 4 uint Read 0 65535
4356 1 9 5 uint Read 0 65535
4357 1 10 1 uint Read 0 65535
4358 1 10 2 uint Read 0 65535
4359 1 10 3 uint Read 0 65535
4360 1 10 4 uint Read 0 65535
4361 1 10 5 uint Read 0 65535
4362 1 11 1 uint Read 0 65535

67
MULTILOAD II – MODBUS MAPPING

Register Length Preset Meter Data Type Read/Write Min Value Max Value
4363 1 11 2 uint Read 0 65535
4364 1 11 3 uint Read 0 65535
4365 1 11 4 uint Read 0 65535
4366 1 11 5 uint Read 0 65535
4367 1 12 1 uint Read 0 65535
4368 1 12 2 uint Read 0 65535
4369 1 12 3 uint Read 0 65535
4370 1 12 4 uint Read 0 65535
4371 1 12 5 uint Read 0 65535

5.2.10 Component Delivered Gross Quantity in Whole Units

Register Length Preset Component Data Type Read/Write Min Value Max Value
4372 2 1 1 uint Read 0 65535
4374 2 1 2 uint Read 0 65535
4376 2 1 3 uint Read 0 65535
4378 2 1 4 uint Read 0 65535
4380 2 1 5 uint Read 0 65535
4382 2 1 6 uint Read 0 65535
4384 2 1 7 uint Read 0 65535
4386 2 1 8 uint Read 0 65535
4388 2 2 1 uint Read 0 65535
4390 2 2 2 uint Read 0 65535
4392 2 2 3 uint Read 0 65535
4394 2 2 4 uint Read 0 65535
4396 2 2 5 uint Read 0 65535
4398 2 2 6 uint Read 0 65535
4400 2 2 7 uint Read 0 65535
4402 2 2 8 uint Read 0 65535
4404 2 3 1 uint Read 0 65535
4406 2 3 2 uint Read 0 65535
4408 2 3 3 uint Read 0 65535
4410 2 3 4 uint Read 0 65535
4412 2 3 5 uint Read 0 65535
4414 2 3 6 uint Read 0 65535
4416 2 3 7 uint Read 0 65535
4418 2 3 8 uint Read 0 65535
4420 2 4 1 uint Read 0 65535
4422 2 4 2 uint Read 0 65535
4424 2 4 3 uint Read 0 65535

68
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
4426 2 4 4 uint Read 0 65535
4428 2 4 5 uint Read 0 65535
4430 2 4 6 uint Read 0 65535
4432 2 4 7 uint Read 0 65535
4434 2 4 8 uint Read 0 65535
4436 2 5 1 uint Read 0 65535
4438 2 5 2 uint Read 0 65535
4440 2 5 3 uint Read 0 65535
4442 2 5 4 uint Read 0 65535
4444 2 5 5 uint Read 0 65535
4446 2 5 6 uint Read 0 65535
4448 2 5 7 uint Read 0 65535
4450 2 5 8 uint Read 0 65535
4452 2 6 1 uint Read 0 65535
4454 2 6 2 uint Read 0 65535
4456 2 6 3 uint Read 0 65535
4458 2 6 4 uint Read 0 65535
4460 2 6 5 uint Read 0 65535
4462 2 6 6 uint Read 0 65535
4464 2 6 7 uint Read 0 65535
4466 2 6 8 uint Read 0 65535
4468 2 7 1 uint Read 0 65535
4470 2 7 2 uint Read 0 65535
4472 2 7 3 uint Read 0 65535
4474 2 7 4 uint Read 0 65535
4476 2 7 5 uint Read 0 65535
4478 2 7 6 uint Read 0 65535
4480 2 7 7 uint Read 0 65535
4482 2 7 8 uint Read 0 65535
4484 2 8 1 uint Read 0 65535
4486 2 8 2 uint Read 0 65535
4488 2 8 3 uint Read 0 65535
4490 2 8 4 uint Read 0 65535
4492 2 8 5 uint Read 0 65535
4494 2 8 6 uint Read 0 65535
4496 2 8 7 uint Read 0 65535
4498 2 8 8 uint Read 0 65535
4500 2 9 1 uint Read 0 65535
4502 2 9 2 uint Read 0 65535
4504 2 9 3 uint Read 0 65535
4506 2 9 4 uint Read 0 65535

69
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
4508 2 9 5 uint Read 0 65535
4510 2 9 6 uint Read 0 65535
4512 2 9 7 uint Read 0 65535
4514 2 9 8 uint Read 0 65535
4516 2 10 1 uint Read 0 65535
4518 2 10 2 uint Read 0 65535
4520 2 10 3 uint Read 0 65535
4522 2 10 4 uint Read 0 65535
4524 2 10 5 uint Read 0 65535
4526 2 10 6 uint Read 0 65535
4528 2 10 7 uint Read 0 65535
4530 2 10 8 uint Read 0 65535
4532 2 11 1 uint Read 0 65535
4534 2 11 2 uint Read 0 65535
4536 2 11 3 uint Read 0 65535
4538 2 11 4 uint Read 0 65535
4540 2 11 5 uint Read 0 65535
4542 2 11 6 uint Read 0 65535
4544 2 11 7 uint Read 0 65535
4546 2 11 8 uint Read 0 65535
4548 2 12 1 uint Read 0 65535
4550 2 12 2 uint Read 0 65535
4552 2 12 3 uint Read 0 65535
4554 2 12 4 uint Read 0 65535
4556 2 12 5 uint Read 0 65535
4558 2 12 6 uint Read 0 65535
4560 2 12 7 uint Read 0 65535
4562 2 12 8 uint Read 0 65535

5.2.11 Component Delivered Net Quantity in Whole Units

Register Length Preset Component Data Type Read/Write Min Value Max Value
4564 2 1 1 uint Read 0 65535
4566 2 1 2 uint Read 0 65535
4568 2 1 3 uint Read 0 65535
4570 2 1 4 uint Read 0 65535
4572 2 1 5 uint Read 0 65535
4574 2 1 6 uint Read 0 65535
4576 2 1 7 uint Read 0 65535
4578 2 1 8 uint Read 0 65535
4580 2 2 1 uint Read 0 65535

70
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
4582 2 2 2 uint Read 0 65535
4584 2 2 3 uint Read 0 65535
4586 2 2 4 uint Read 0 65535
4588 2 2 5 uint Read 0 65535
4590 2 2 6 uint Read 0 65535
4592 2 2 7 uint Read 0 65535
4594 2 2 8 uint Read 0 65535
4596 2 3 1 uint Read 0 65535
4598 2 3 2 uint Read 0 65535
4600 2 3 3 uint Read 0 65535
4602 2 3 4 uint Read 0 65535
4604 2 3 5 uint Read 0 65535
4606 2 3 6 uint Read 0 65535
4608 2 3 7 uint Read 0 65535
4610 2 3 8 uint Read 0 65535
4612 2 4 1 uint Read 0 65535
4614 2 4 2 uint Read 0 65535
4616 2 4 3 uint Read 0 65535
4618 2 4 4 uint Read 0 65535
4620 2 4 5 uint Read 0 65535
4622 2 4 6 uint Read 0 65535
4624 2 4 7 uint Read 0 65535
4626 2 4 8 uint Read 0 65535
4628 2 5 1 uint Read 0 65535
4630 2 5 2 uint Read 0 65535
4632 2 5 3 uint Read 0 65535
4634 2 5 4 uint Read 0 65535
4636 2 5 5 uint Read 0 65535
4638 2 5 6 uint Read 0 65535
4640 2 5 7 uint Read 0 65535
4642 2 5 8 uint Read 0 65535
4644 2 6 1 uint Read 0 65535
4646 2 6 2 uint Read 0 65535
4648 2 6 3 uint Read 0 65535
4650 2 6 4 uint Read 0 65535
4652 2 6 5 uint Read 0 65535
4654 2 6 6 uint Read 0 65535
4656 2 6 7 uint Read 0 65535
4658 2 6 8 uint Read 0 65535
4660 2 7 1 uint Read 0 65535
4662 2 7 2 uint Read 0 65535

71
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
4664 2 7 3 uint Read 0 65535
4666 2 7 4 uint Read 0 65535
4668 2 7 5 uint Read 0 65535
4670 2 7 6 uint Read 0 65535
4672 2 7 7 uint Read 0 65535
4674 2 7 8 uint Read 0 65535
4676 2 8 1 uint Read 0 65535
4678 2 8 2 uint Read 0 65535
4680 2 8 3 uint Read 0 65535
4682 2 8 4 uint Read 0 65535
4684 2 8 5 uint Read 0 65535
4686 2 8 6 uint Read 0 65535
4688 2 8 7 uint Read 0 65535
4690 2 8 8 uint Read 0 65535
4692 2 9 1 uint Read 0 65535
4694 2 9 2 uint Read 0 65535
4696 2 9 3 uint Read 0 65535
4698 2 9 4 uint Read 0 65535
4700 2 9 5 uint Read 0 65535
4702 2 9 6 uint Read 0 65535
4704 2 9 7 uint Read 0 65535
4706 2 9 8 uint Read 0 65535
4708 2 10 1 uint Read 0 65535
4710 2 10 2 uint Read 0 65535
4712 2 10 3 uint Read 0 65535
4714 2 10 4 uint Read 0 65535
4716 2 10 5 uint Read 0 65535
4718 2 10 6 uint Read 0 65535
4720 2 10 7 uint Read 0 65535
4722 2 10 8 uint Read 0 65535
4724 2 11 1 uint Read 0 65535
4726 2 11 2 uint Read 0 65535
4728 2 11 3 uint Read 0 65535
4730 2 11 4 uint Read 0 65535
4732 2 11 5 uint Read 0 65535
4734 2 11 6 uint Read 0 65535
4736 2 11 7 uint Read 0 65535
4738 2 11 8 uint Read 0 65535
4740 2 12 1 uint Read 0 65535
4742 2 12 2 uint Read 0 65535
4744 2 12 3 uint Read 0 65535

72
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
4746 2 12 4 uint Read 0 65535
4748 2 12 5 uint Read 0 65535
4750 2 12 6 uint Read 0 65535
4752 2 12 7 uint Read 0 65535
4754 2 12 8 uint Read 0 65535

5.2.12 Component Batch Average Temp in Tenths or Hundredths

Register Length Preset Component Data Type Read/Write Min Value Max Value
4756 2 1 1 int Read -50.00 350.00
4758 2 1 2 int Read -50.00 350.00
4760 2 1 3 int Read -50.00 350.00
4762 2 1 4 int Read -50.00 350.00
4764 2 1 5 int Read -50.00 350.00
4766 2 1 6 int Read -50.00 350.00
4768 2 1 7 int Read -50.00 350.00
4770 2 1 8 int Read -50.00 350.00
4772 2 2 1 int Read -50.00 350.00
4774 2 2 2 int Read -50.00 350.00
4776 2 2 3 int Read -50.00 350.00
4778 2 2 4 int Read -50.00 350.00
4780 2 2 5 int Read -50.00 350.00
4782 2 2 6 int Read -50.00 350.00
4784 2 2 7 int Read -50.00 350.00
4786 2 2 8 int Read -50.00 350.00
4788 2 3 1 int Read -50.00 350.00
4790 2 3 2 int Read -50.00 350.00
4792 2 3 3 int Read -50.00 350.00
4794 2 3 4 int Read -50.00 350.00
4796 2 3 5 int Read -50.00 350.00
4798 2 3 6 int Read -50.00 350.00
4800 2 3 7 int Read -50.00 350.00
4802 2 3 8 int Read -50.00 350.00
4804 2 4 1 int Read -50.00 350.00
4806 2 4 2 int Read -50.00 350.00
4808 2 4 3 int Read -50.00 350.00
4810 2 4 4 int Read -50.00 350.00
4812 2 4 5 int Read -50.00 350.00
4814 2 4 6 int Read -50.00 350.00
4816 2 4 7 int Read -50.00 350.00
4818 2 4 8 int Read -50.00 350.00

73
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
4820 2 5 1 int Read -50.00 350.00
4822 2 5 2 int Read -50.00 350.00
4824 2 5 3 int Read -50.00 350.00
4826 2 5 4 int Read -50.00 350.00
4828 2 5 5 int Read -50.00 350.00
4830 2 5 6 int Read -50.00 350.00
4832 2 5 7 int Read -50.00 350.00
4834 2 5 8 int Read -50.00 350.00
4836 2 6 1 int Read -50.00 350.00
4838 2 6 2 int Read -50.00 350.00
4840 2 6 3 int Read -50.00 350.00
4842 2 6 4 int Read -50.00 350.00
4844 2 6 5 int Read -50.00 350.00
4846 2 6 6 int Read -50.00 350.00
4848 2 6 7 int Read -50.00 350.00
4850 2 6 8 int Read -50.00 350.00
4852 2 7 1 int Read -50.00 350.00
4854 2 7 2 int Read -50.00 350.00
4856 2 7 3 int Read -50.00 350.00
4858 2 7 4 int Read -50.00 350.00
4860 2 7 5 int Read -50.00 350.00
4862 2 7 6 int Read -50.00 350.00
4864 2 7 7 int Read -50.00 350.00
4866 2 7 8 int Read -50.00 350.00
4868 2 8 1 int Read -50.00 350.00
4870 2 8 2 int Read -50.00 350.00
4872 2 8 3 int Read -50.00 350.00
4874 2 8 4 int Read -50.00 350.00
4876 2 8 5 int Read -50.00 350.00
4878 2 8 6 int Read -50.00 350.00
4880 2 8 7 int Read -50.00 350.00
4882 2 8 8 int Read -50.00 350.00
4884 2 9 1 int Read -50.00 350.00
4886 2 9 2 int Read -50.00 350.00
4888 2 9 3 int Read -50.00 350.00
4890 2 9 4 int Read -50.00 350.00
4892 2 9 5 int Read -50.00 350.00
4894 2 9 6 int Read -50.00 350.00
4896 2 9 7 int Read -50.00 350.00
4898 2 9 8 int Read -50.00 350.00
4900 2 10 1 int Read -50.00 350.00

74
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
4902 2 10 2 int Read -50.00 350.00
4904 2 10 3 int Read -50.00 350.00
4906 2 10 4 int Read -50.00 350.00
4908 2 10 5 int Read -50.00 350.00
4910 2 10 6 int Read -50.00 350.00
4912 2 10 7 int Read -50.00 350.00
4914 2 10 8 int Read -50.00 350.00
4916 2 11 1 int Read -50.00 350.00
4918 2 11 2 int Read -50.00 350.00
4920 2 11 3 int Read -50.00 350.00
4922 2 11 4 int Read -50.00 350.00
4924 2 11 5 int Read -50.00 350.00
4926 2 11 6 int Read -50.00 350.00
4928 2 11 7 int Read -50.00 350.00
4930 2 11 8 int Read -50.00 350.00
4932 2 12 1 int Read -50.00 350.00
4934 2 12 2 int Read -50.00 350.00
4936 2 12 3 int Read -50.00 350.00
4938 2 12 4 int Read -50.00 350.00
4940 2 12 5 int Read -50.00 350.00
4942 2 12 6 int Read -50.00 350.00
4944 2 12 7 int Read -50.00 350.00
4946 2 12 8 int Read -50.00 350.00

5.2.13 Component Batch Average Pressure in Tenths or Hundredths

Register Length Preset Component Data Type Read/Write Min Value Max Value
4948 2 1 1 int Read -20.00 650.00
4950 2 1 2 int Read -20.00 650.00
4952 2 1 3 int Read -20.00 650.00
4954 2 1 4 int Read -20.00 650.00
4956 2 1 5 int Read -20.00 650.00
4958 2 1 6 int Read -20.00 650.00
4960 2 1 7 int Read -20.00 650.00
4962 2 1 8 int Read -20.00 650.00
4964 2 2 1 int Read -20.00 650.00
4966 2 2 2 int Read -20.00 650.00
4968 2 2 3 int Read -20.00 650.00
4970 2 2 4 int Read -20.00 650.00
4972 2 2 5 int Read -20.00 650.00

75
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
4974 2 2 6 int Read -20.00 650.00
4976 2 2 7 int Read -20.00 650.00
4978 2 2 8 int Read -20.00 650.00
4980 2 3 1 int Read -20.00 650.00
4982 2 3 2 int Read -20.00 650.00
4984 2 3 3 int Read -20.00 650.00
4986 2 3 4 int Read -20.00 650.00
4988 2 3 5 int Read -20.00 650.00
4990 2 3 6 int Read -20.00 650.00
4992 2 3 7 int Read -20.00 650.00
4994 2 3 8 int Read -20.00 650.00
4996 2 4 1 int Read -20.00 650.00
4998 2 4 2 int Read -20.00 650.00
5000 2 4 3 int Read -20.00 650.00
5002 2 4 4 int Read -20.00 650.00
5004 2 4 5 int Read -20.00 650.00
5006 2 4 6 int Read -20.00 650.00
5008 2 4 7 int Read -20.00 650.00
5010 2 4 8 int Read -20.00 650.00
5012 2 5 1 int Read -20.00 650.00
5014 2 5 2 int Read -20.00 650.00
5016 2 5 3 int Read -20.00 650.00
5018 2 5 4 int Read -20.00 650.00
5020 2 5 5 int Read -20.00 650.00
5022 2 5 6 int Read -20.00 650.00
5024 2 5 7 int Read -20.00 650.00
5026 2 5 8 int Read -20.00 650.00
5028 2 6 1 int Read -20.00 650.00
5030 2 6 2 int Read -20.00 650.00
5032 2 6 3 int Read -20.00 650.00
5034 2 6 4 int Read -20.00 650.00
5036 2 6 5 int Read -20.00 650.00
5038 2 6 6 int Read -20.00 650.00
5040 2 6 7 int Read -20.00 650.00
5042 2 6 8 int Read -20.00 650.00
5044 2 7 1 int Read -20.00 650.00
5046 2 7 2 int Read -20.00 650.00
5048 2 7 3 int Read -20.00 650.00
5050 2 7 4 int Read -20.00 650.00
5052 2 7 5 int Read -20.00 650.00
5054 2 7 6 int Read -20.00 650.00

76
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
5056 2 7 7 int Read -20.00 650.00
5058 2 7 8 int Read -20.00 650.00
5060 2 8 1 int Read -20.00 650.00
5062 2 8 2 int Read -20.00 650.00
5064 2 8 3 int Read -20.00 650.00
5066 2 8 4 int Read -20.00 650.00
5068 2 8 5 int Read -20.00 650.00
5070 2 8 6 int Read -20.00 650.00
5072 2 8 7 int Read -20.00 650.00
5074 2 8 8 int Read -20.00 650.00
5076 2 9 1 int Read -20.00 650.00
5078 2 9 2 int Read -20.00 650.00
5080 2 9 3 int Read -20.00 650.00
5082 2 9 4 int Read -20.00 650.00
5084 2 9 5 int Read -20.00 650.00
5086 2 9 6 int Read -20.00 650.00
5088 2 9 7 int Read -20.00 650.00
5090 2 9 8 int Read -20.00 650.00
5092 2 10 1 int Read -20.00 650.00
5094 2 10 2 int Read -20.00 650.00
5096 2 10 3 int Read -20.00 650.00
5098 2 10 4 int Read -20.00 650.00
5100 2 10 5 int Read -20.00 650.00
5102 2 10 6 int Read -20.00 650.00
5104 2 10 7 int Read -20.00 650.00
5106 2 10 8 int Read -20.00 650.00
5108 2 11 1 int Read -20.00 650.00
5110 2 11 2 int Read -20.00 650.00
5112 2 11 3 int Read -20.00 650.00
5114 2 11 4 int Read -20.00 650.00
5116 2 11 5 int Read -20.00 650.00
5118 2 11 6 int Read -20.00 650.00
5120 2 11 7 int Read -20.00 650.00
5122 2 11 8 int Read -20.00 650.00
5124 2 12 1 int Read -20.00 650.00
5126 2 12 2 int Read -20.00 650.00
5128 2 12 3 int Read -20.00 650.00
5130 2 12 4 int Read -20.00 650.00
5132 2 12 5 int Read -20.00 650.00
5134 2 12 6 int Read -20.00 650.00
5136 2 12 7 int Read -20.00 650.00

77
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
5138 2 12 8 int Read -20.00 650.00
5.2.14 Component Batch Average Density/Relative Density/Gravity

Register Length Preset Component Data Type Read/Write Min Value Max Value
5140 2 1 1 int Read -100.00 1200.00
5142 2 1 2 int Read -100.00 1200.00
5144 2 1 3 int Read -100.00 1200.00
5146 2 1 4 int Read -100.00 1200.00
5148 2 1 5 int Read -100.00 1200.00
5150 2 1 6 int Read -100.00 1200.00
5152 2 1 7 int Read -100.00 1200.00
5154 2 1 8 int Read -100.00 1200.00
5156 2 2 1 int Read -100.00 1200.00
5158 2 2 2 int Read -100.00 1200.00
5160 2 2 3 int Read -100.00 1200.00
5162 2 2 4 int Read -100.00 1200.00
5164 2 2 5 int Read -100.00 1200.00
5166 2 2 6 int Read -100.00 1200.00
5168 2 2 7 int Read -100.00 1200.00
5170 2 2 8 int Read -100.00 1200.00
5172 2 3 1 int Read -100.00 1200.00
5174 2 3 2 int Read -100.00 1200.00
5176 2 3 3 int Read -100.00 1200.00
5178 2 3 4 int Read -100.00 1200.00
5180 2 3 5 int Read -100.00 1200.00
5182 2 3 6 int Read -100.00 1200.00
5184 2 3 7 int Read -100.00 1200.00
5186 2 3 8 int Read -100.00 1200.00
5188 2 4 1 int Read -100.00 1200.00
5190 2 4 2 int Read -100.00 1200.00
5192 2 4 3 int Read -100.00 1200.00
5194 2 4 4 int Read -100.00 1200.00
5196 2 4 5 int Read -100.00 1200.00
5198 2 4 6 int Read -100.00 1200.00
5200 2 4 7 int Read -100.00 1200.00
5202 2 4 8 int Read -100.00 1200.00
5204 2 5 1 int Read -100.00 1200.00
5206 2 5 2 int Read -100.00 1200.00
5208 2 5 3 int Read -100.00 1200.00
5210 2 5 4 int Read -100.00 1200.00
5212 2 5 5 int Read -100.00 1200.00

78
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
5214 2 5 6 int Read -100.00 1200.00
5216 2 5 7 int Read -100.00 1200.00
5218 2 5 8 int Read -100.00 1200.00
5220 2 6 1 int Read -100.00 1200.00
5222 2 6 2 int Read -100.00 1200.00
5224 2 6 3 int Read -100.00 1200.00
5226 2 6 4 int Read -100.00 1200.00
5228 2 6 5 int Read -100.00 1200.00
5230 2 6 6 int Read -100.00 1200.00
5232 2 6 7 int Read -100.00 1200.00
5234 2 6 8 int Read -100.00 1200.00
5236 2 7 1 int Read -100.00 1200.00
5238 2 7 2 int Read -100.00 1200.00
5240 2 7 3 int Read -100.00 1200.00
5242 2 7 4 int Read -100.00 1200.00
5244 2 7 5 int Read -100.00 1200.00
5246 2 7 6 int Read -100.00 1200.00
5248 2 7 7 int Read -100.00 1200.00
5250 2 7 8 int Read -100.00 1200.00
5252 2 8 1 int Read -100.00 1200.00
5254 2 8 2 int Read -100.00 1200.00
5256 2 8 3 int Read -100.00 1200.00
5258 2 8 4 int Read -100.00 1200.00
5260 2 8 5 int Read -100.00 1200.00
5262 2 8 6 int Read -100.00 1200.00
5264 2 8 7 int Read -100.00 1200.00
5266 2 8 8 int Read -100.00 1200.00
5268 2 9 1 int Read -100.00 1200.00
5270 2 9 2 int Read -100.00 1200.00
5272 2 9 3 int Read -100.00 1200.00
5274 2 9 4 int Read -100.00 1200.00
5276 2 9 5 int Read -100.00 1200.00
5278 2 9 6 int Read -100.00 1200.00
5280 2 9 7 int Read -100.00 1200.00
5282 2 9 8 int Read -100.00 1200.00
5284 2 10 1 int Read -100.00 1200.00
5286 2 10 2 int Read -100.00 1200.00
5288 2 10 3 int Read -100.00 1200.00
5290 2 10 4 int Read -100.00 1200.00
5292 2 10 5 int Read -100.00 1200.00
5294 2 10 6 int Read -100.00 1200.00

79
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
5296 2 10 7 int Read -100.00 1200.00
5298 2 10 8 int Read -100.00 1200.00
5300 2 11 1 int Read -100.00 1200.00
5302 2 11 2 int Read -100.00 1200.00
5304 2 11 3 int Read -100.00 1200.00
5306 2 11 4 int Read -100.00 1200.00
5308 2 11 5 int Read -100.00 1200.00
5310 2 11 6 int Read -100.00 1200.00
5312 2 11 7 int Read -100.00 1200.00
5314 2 11 8 int Read -100.00 1200.00
5316 2 12 1 int Read -100.00 1200.00
5318 2 12 2 int Read -100.00 1200.00
5320 2 12 3 int Read -100.00 1200.00
5322 2 12 4 int Read -100.00 1200.00
5324 2 12 5 int Read -100.00 1200.00
5326 2 12 6 int Read -100.00 1200.00
5328 2 12 7 int Read -100.00 1200.00
5330 2 12 8 int Read -100.00 1200.00

5.2.15 Component Current Temp in Hundredths

Register Length Preset Component Data Type Read/Write Min Value Max Value
5332 2 1 1 int Read -50.00 350.00
5334 2 1 2 int Read -50.00 350.00
5336 2 1 3 int Read -50.00 350.00
5338 2 1 4 int Read -50.00 350.00
5340 2 1 5 int Read -50.00 350.00
5342 2 1 6 int Read -50.00 350.00
5344 2 1 7 int Read -50.00 350.00
5346 2 1 8 int Read -50.00 350.00
5348 2 2 1 int Read -50.00 350.00
5350 2 2 2 int Read -50.00 350.00
5352 2 2 3 int Read -50.00 350.00
5354 2 2 4 int Read -50.00 350.00
5356 2 2 5 int Read -50.00 350.00
5358 2 2 6 int Read -50.00 350.00
5360 2 2 7 int Read -50.00 350.00
5362 2 2 8 int Read -50.00 350.00
5364 2 3 1 int Read -50.00 350.00
5366 2 3 2 int Read -50.00 350.00

80
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
5368 2 3 3 int Read -50.00 350.00
5370 2 3 4 int Read -50.00 350.00
5372 2 3 5 int Read -50.00 350.00
5374 2 3 6 int Read -50.00 350.00
5376 2 3 7 int Read -50.00 350.00
5378 2 3 8 int Read -50.00 350.00
5380 2 4 1 int Read -50.00 350.00
5382 2 4 2 int Read -50.00 350.00
5384 2 4 3 int Read -50.00 350.00
5386 2 4 4 int Read -50.00 350.00
5388 2 4 5 int Read -50.00 350.00
5390 2 4 6 int Read -50.00 350.00
5392 2 4 7 int Read -50.00 350.00
5394 2 4 8 int Read -50.00 350.00
5396 2 5 1 int Read -50.00 350.00
5398 2 5 2 int Read -50.00 350.00
5400 2 5 3 int Read -50.00 350.00
5402 2 5 4 int Read -50.00 350.00
5404 2 5 5 int Read -50.00 350.00
5406 2 5 6 int Read -50.00 350.00
5408 2 5 7 int Read -50.00 350.00
5410 2 5 8 int Read -50.00 350.00
5412 2 6 1 int Read -50.00 350.00
5414 2 6 2 int Read -50.00 350.00
5416 2 6 3 int Read -50.00 350.00
5418 2 6 4 int Read -50.00 350.00
5420 2 6 5 int Read -50.00 350.00
5422 2 6 6 int Read -50.00 350.00
5424 2 6 7 int Read -50.00 350.00
5426 2 6 8 int Read -50.00 350.00
5428 2 7 1 int Read -50.00 350.00
5430 2 7 2 int Read -50.00 350.00
5432 2 7 3 int Read -50.00 350.00
5434 2 7 4 int Read -50.00 350.00
5436 2 7 5 int Read -50.00 350.00
5438 2 7 6 int Read -50.00 350.00
5440 2 7 7 int Read -50.00 350.00
5442 2 7 8 int Read -50.00 350.00
5444 2 8 1 int Read -50.00 350.00
5446 2 8 2 int Read -50.00 350.00
5448 2 8 3 int Read -50.00 350.00

81
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
5450 2 8 4 int Read -50.00 350.00
5452 2 8 5 int Read -50.00 350.00
5454 2 8 6 int Read -50.00 350.00
5456 2 8 7 int Read -50.00 350.00
5458 2 8 8 int Read -50.00 350.00
5460 2 9 1 int Read -50.00 350.00
5462 2 9 2 int Read -50.00 350.00
5464 2 9 3 int Read -50.00 350.00
5466 2 9 4 int Read -50.00 350.00
5468 2 9 5 int Read -50.00 350.00
5470 2 9 6 int Read -50.00 350.00
5472 2 9 7 int Read -50.00 350.00
5474 2 9 8 int Read -50.00 350.00
5476 2 10 1 int Read -50.00 350.00
5478 2 10 2 int Read -50.00 350.00
5480 2 10 3 int Read -50.00 350.00
5482 2 10 4 int Read -50.00 350.00
5484 2 10 5 int Read -50.00 350.00
5486 2 10 6 int Read -50.00 350.00
5488 2 10 7 int Read -50.00 350.00
5490 2 10 8 int Read -50.00 350.00
5492 2 11 1 int Read -50.00 350.00
5494 2 11 2 int Read -50.00 350.00
5496 2 11 3 int Read -50.00 350.00
5498 2 11 4 int Read -50.00 350.00
5500 2 11 5 int Read -50.00 350.00
5502 2 11 6 int Read -50.00 350.00
5504 2 11 7 int Read -50.00 350.00
5506 2 11 8 int Read -50.00 350.00
5508 2 12 1 int Read -50.00 350.00
5510 2 12 2 int Read -50.00 350.00
5512 2 12 3 int Read -50.00 350.00
5514 2 12 4 int Read -50.00 350.00
5516 2 12 5 int Read -50.00 350.00
5518 2 12 6 int Read -50.00 350.00
5520 2 12 7 int Read -50.00 350.00
5522 2 12 8 int Read -50.00 350.00

82
MULTILOAD II – MODBUS MAPPING

5.2.16 Component Current Pressure in Hundredths

Register Length Preset Component Data Type Read/Write Min Value Max Value
5524 2 1 1 int Read -20.00 650.00
5526 2 1 2 int Read -20.00 650.00
5528 2 1 3 int Read -20.00 650.00
5530 2 1 4 int Read -20.00 650.00
5532 2 1 5 int Read -20.00 650.00
5534 2 1 6 int Read -20.00 650.00
5536 2 1 7 int Read -20.00 650.00
5538 2 1 8 int Read -20.00 650.00
5540 2 2 1 int Read -20.00 650.00
5542 2 2 2 int Read -20.00 650.00
5544 2 2 3 int Read -20.00 650.00
5546 2 2 4 int Read -20.00 650.00
5548 2 2 5 int Read -20.00 650.00
5550 2 2 6 int Read -20.00 650.00
5552 2 2 7 int Read -20.00 650.00
5554 2 2 8 int Read -20.00 650.00
5556 2 3 1 int Read -20.00 650.00
5558 2 3 2 int Read -20.00 650.00
5560 2 3 3 int Read -20.00 650.00
5562 2 3 4 int Read -20.00 650.00
5564 2 3 5 int Read -20.00 650.00
5566 2 3 6 int Read -20.00 650.00
5568 2 3 7 int Read -20.00 650.00
5570 2 3 8 int Read -20.00 650.00
5572 2 4 1 int Read -20.00 650.00
5574 2 4 2 int Read -20.00 650.00
5576 2 4 3 int Read -20.00 650.00
5578 2 4 4 int Read -20.00 650.00
5580 2 4 5 int Read -20.00 650.00
5582 2 4 6 int Read -20.00 650.00
5584 2 4 7 int Read -20.00 650.00
5586 2 4 8 int Read -20.00 650.00
5588 2 5 1 int Read -20.00 650.00
5590 2 5 2 int Read -20.00 650.00
5592 2 5 3 int Read -20.00 650.00
5594 2 5 4 int Read -20.00 650.00
5596 2 5 5 int Read -20.00 650.00
5598 2 5 6 int Read -20.00 650.00
5600 2 5 7 int Read -20.00 650.00

83
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
5602 2 5 8 int Read -20.00 650.00
5604 2 6 1 int Read -20.00 650.00
5606 2 6 2 int Read -20.00 650.00
5608 2 6 3 int Read -20.00 650.00
5610 2 6 4 int Read -20.00 650.00
5612 2 6 5 int Read -20.00 650.00
5614 2 6 6 int Read -20.00 650.00
5616 2 6 7 int Read -20.00 650.00
5618 2 6 8 int Read -20.00 650.00
5620 2 7 1 int Read -20.00 650.00
5622 2 7 2 int Read -20.00 650.00
5624 2 7 3 int Read -20.00 650.00
5626 2 7 4 int Read -20.00 650.00
5628 2 7 5 int Read -20.00 650.00
5630 2 7 6 int Read -20.00 650.00
5632 2 7 7 int Read -20.00 650.00
5634 2 7 8 int Read -20.00 650.00
5636 2 8 1 int Read -20.00 650.00
5638 2 8 2 int Read -20.00 650.00
5640 2 8 3 int Read -20.00 650.00
5642 2 8 4 int Read -20.00 650.00
5644 2 8 5 int Read -20.00 650.00
5646 2 8 6 int Read -20.00 650.00
5648 2 8 7 int Read -20.00 650.00
5650 2 8 8 int Read -20.00 650.00
5652 2 9 1 int Read -20.00 650.00
5654 2 9 2 int Read -20.00 650.00
5656 2 9 3 int Read -20.00 650.00
5658 2 9 4 int Read -20.00 650.00
5660 2 9 5 int Read -20.00 650.00
5662 2 9 6 int Read -20.00 650.00
5664 2 9 7 int Read -20.00 650.00
5666 2 9 8 int Read -20.00 650.00
5668 2 10 1 int Read -20.00 650.00
5670 2 10 2 int Read -20.00 650.00
5672 2 10 3 int Read -20.00 650.00
5674 2 10 4 int Read -20.00 650.00
5676 2 10 5 int Read -20.00 650.00
5678 2 10 6 int Read -20.00 650.00
5680 2 10 7 int Read -20.00 650.00
5682 2 10 8 int Read -20.00 650.00

84
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
5684 2 11 1 int Read -20.00 650.00
5686 2 11 2 int Read -20.00 650.00
5688 2 11 3 int Read -20.00 650.00
5690 2 11 4 int Read -20.00 650.00
5692 2 11 5 int Read -20.00 650.00
5694 2 11 6 int Read -20.00 650.00
5696 2 11 7 int Read -20.00 650.00
5698 2 11 8 int Read -20.00 650.00
5700 2 12 1 int Read -20.00 650.00
5702 2 12 2 int Read -20.00 650.00
5704 2 12 3 int Read -20.00 650.00
5706 2 12 4 int Read -20.00 650.00
5708 2 12 5 int Read -20.00 650.00
5710 2 12 6 int Read -20.00 650.00
5712 2 12 7 int Read -20.00 650.00
5714 2 12 8 int Read -20.00 650.00

5.2.17 Component Current Density in Tenths

Register Length Preset Component Data Type Read/Write Min Value Max Value
5716 2 1 1 uint Read 0 1200.00
5718 2 1 2 uint Read 0 1200.00
5720 2 1 3 uint Read 0 1200.00
5722 2 1 4 uint Read 0 1200.00
5724 2 1 5 uint Read 0 1200.00
5726 2 1 6 uint Read 0 1200.00
5728 2 1 7 uint Read 0 1200.00
5730 2 1 8 uint Read 0 1200.00
5732 2 2 1 uint Read 0 1200.00
5734 2 2 2 uint Read 0 1200.00
5736 2 2 3 uint Read 0 1200.00
5738 2 2 4 uint Read 0 1200.00
5740 2 2 5 uint Read 0 1200.00
5742 2 2 6 uint Read 0 1200.00
5744 2 2 7 uint Read 0 1200.00
5746 2 2 8 uint Read 0 1200.00
5748 2 3 1 uint Read 0 1200.00
5750 2 3 2 uint Read 0 1200.00
5752 2 3 3 uint Read 0 1200.00
5754 2 3 4 uint Read 0 1200.00

85
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
5756 2 3 5 uint Read 0 1200.00
5758 2 3 6 uint Read 0 1200.00
5760 2 3 7 uint Read 0 1200.00
5762 2 3 8 uint Read 0 1200.00
5764 2 4 1 uint Read 0 1200.00
5766 2 4 2 uint Read 0 1200.00
5768 2 4 3 uint Read 0 1200.00
5770 2 4 4 uint Read 0 1200.00
5772 2 4 5 uint Read 0 1200.00
5774 2 4 6 uint Read 0 1200.00
5776 2 4 7 uint Read 0 1200.00
5778 2 4 8 uint Read 0 1200.00
5780 2 5 1 uint Read 0 1200.00
5782 2 5 2 uint Read 0 1200.00
5784 2 5 3 uint Read 0 1200.00
5786 2 5 4 uint Read 0 1200.00
5788 2 5 5 uint Read 0 1200.00
5790 2 5 6 uint Read 0 1200.00
5792 2 5 7 uint Read 0 1200.00
5794 2 5 8 uint Read 0 1200.00
5796 2 6 1 uint Read 0 1200.00
5798 2 6 2 uint Read 0 1200.00
5800 2 6 3 uint Read 0 1200.00
5802 2 6 4 uint Read 0 1200.00
5804 2 6 5 uint Read 0 1200.00
5806 2 6 6 uint Read 0 1200.00
5808 2 6 7 uint Read 0 1200.00
5810 2 6 8 uint Read 0 1200.00
5812 2 7 1 uint Read 0 1200.00
5814 2 7 2 uint Read 0 1200.00
5816 2 7 3 uint Read 0 1200.00
5818 2 7 4 uint Read 0 1200.00
5820 2 7 5 uint Read 0 1200.00
5822 2 7 6 uint Read 0 1200.00
5824 2 7 7 uint Read 0 1200.00
5826 2 7 8 uint Read 0 1200.00
5828 2 8 1 uint Read 0 1200.00
5830 2 8 2 uint Read 0 1200.00
5832 2 8 3 uint Read 0 1200.00
5834 2 8 4 uint Read 0 1200.00
5836 2 8 5 uint Read 0 1200.00

86
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
5838 2 8 6 uint Read 0 1200.00
5840 2 8 7 uint Read 0 1200.00
5842 2 8 8 uint Read 0 1200.00
5844 2 9 1 uint Read 0 1200.00
5846 2 9 2 uint Read 0 1200.00
5848 2 9 3 uint Read 0 1200.00
5850 2 9 4 uint Read 0 1200.00
5852 2 9 5 uint Read 0 1200.00
5854 2 9 6 uint Read 0 1200.00
5856 2 9 7 uint Read 0 1200.00
5858 2 9 8 uint Read 0 1200.00
5860 2 10 1 uint Read 0 1200.00
5862 2 10 2 uint Read 0 1200.00
5864 2 10 3 uint Read 0 1200.00
5866 2 10 4 uint Read 0 1200.00
5868 2 10 5 uint Read 0 1200.00
5870 2 10 6 uint Read 0 1200.00
5872 2 10 7 uint Read 0 1200.00
5874 2 10 8 uint Read 0 1200.00
5876 2 11 1 uint Read 0 1200.00
5878 2 11 2 uint Read 0 1200.00
5880 2 11 3 uint Read 0 1200.00
5882 2 11 4 uint Read 0 1200.00
5884 2 11 5 uint Read 0 1200.00
5886 2 11 6 uint Read 0 1200.00
5888 2 11 7 uint Read 0 1200.00
5890 2 11 8 uint Read 0 1200.00
5892 2 12 1 uint Read 0 1200.00
5894 2 12 2 uint Read 0 1200.00
5896 2 12 3 uint Read 0 1200.00
5898 2 12 4 uint Read 0 1200.00
5900 2 12 5 uint Read 0 1200.00
5902 2 12 6 uint Read 0 1200.00
5904 2 12 7 uint Read 0 1200.00
5906 2 12 8 uint Read 0 1200.00

5.2.18 Additive Delivered Quantity in Thousands

Register Length Preset Additive Data Type Read/Write Min Value Max Value
5908 2 1 1 uint Read 0 65535

87
MULTILOAD II – MODBUS MAPPING

Register Length Preset Additive Data Type Read/Write Min Value Max Value
5910 2 1 2 uint Read 0 65535
5912 2 1 3 uint Read 0 65535
5914 2 1 4 uint Read 0 65535
5916 2 1 5 uint Read 0 65535
5918 2 1 6 uint Read 0 65535
5920 2 1 7 uint Read 0 65535
5922 2 1 8 uint Read 0 65535
5924 2 1 9 uint Read 0 65535
5926 2 1 10 uint Read 0 65535
5928 2 1 11 uint Read 0 65535
5930 2 1 12 uint Read 0 65535
5932 2 1 13 uint Read 0 65535
5934 2 1 14 uint Read 0 65535
5936 2 1 15 uint Read 0 65535
5938 2 1 16 uint Read 0 65535
5940 2 2 1 uint Read 0 65535
5942 2 2 2 uint Read 0 65535
5944 2 2 3 uint Read 0 65535
5946 2 2 4 uint Read 0 65535
5948 2 2 5 uint Read 0 65535
5950 2 2 6 uint Read 0 65535
5952 2 2 7 uint Read 0 65535
5954 2 2 8 uint Read 0 65535
5956 2 2 9 uint Read 0 65535
5958 2 2 10 uint Read 0 65535
5960 2 2 11 uint Read 0 65535
5962 2 2 12 uint Read 0 65535
5964 2 2 13 uint Read 0 65535
5966 2 2 14 uint Read 0 65535
5968 2 2 15 uint Read 0 65535
5970 2 2 16 uint Read 0 65535
5972 2 3 1 uint Read 0 65535
5974 2 3 2 uint Read 0 65535
5976 2 3 3 uint Read 0 65535
5978 2 3 4 uint Read 0 65535
5980 2 3 5 uint Read 0 65535
5982 2 3 6 uint Read 0 65535
5984 2 3 7 uint Read 0 65535
5986 2 3 8 uint Read 0 65535
5988 2 3 9 uint Read 0 65535
5990 2 3 10 uint Read 0 65535

88
MULTILOAD II – MODBUS MAPPING

Register Length Preset Additive Data Type Read/Write Min Value Max Value
5992 2 3 11 uint Read 0 65535
5994 2 3 12 uint Read 0 65535
5996 2 3 13 uint Read 0 65535
5998 2 3 14 uint Read 0 65535
6000 2 3 15 uint Read 0 65535
6002 2 3 16 uint Read 0 65535
6004 2 4 1 uint Read 0 65535
6006 2 4 2 uint Read 0 65535
6008 2 4 3 uint Read 0 65535
6010 2 4 4 uint Read 0 65535
6012 2 4 5 uint Read 0 65535
6014 2 4 6 uint Read 0 65535
6016 2 4 7 uint Read 0 65535
6018 2 4 8 uint Read 0 65535
6020 2 4 9 uint Read 0 65535
6022 2 4 10 uint Read 0 65535
6024 2 4 11 uint Read 0 65535
6026 2 4 12 uint Read 0 65535
6028 2 4 13 uint Read 0 65535
6030 2 4 14 uint Read 0 65535
6032 2 4 15 uint Read 0 65535
6034 2 4 16 uint Read 0 65535
6036 2 5 1 uint Read 0 65535
6038 2 5 2 uint Read 0 65535
6040 2 5 3 uint Read 0 65535
6042 2 5 4 uint Read 0 65535
6044 2 5 5 uint Read 0 65535
6046 2 5 6 uint Read 0 65535
6048 2 5 7 uint Read 0 65535
6050 2 5 8 uint Read 0 65535
6052 2 5 9 uint Read 0 65535
6054 2 5 10 uint Read 0 65535
6056 2 5 11 uint Read 0 65535
6058 2 5 12 uint Read 0 65535
6060 2 5 13 uint Read 0 65535
6062 2 5 14 uint Read 0 65535
6064 2 5 15 uint Read 0 65535
6066 2 5 16 uint Read 0 65535
6068 2 6 1 uint Read 0 65535
6070 2 6 2 uint Read 0 65535
6072 2 6 3 uint Read 0 65535

89
MULTILOAD II – MODBUS MAPPING

Register Length Preset Additive Data Type Read/Write Min Value Max Value
6074 2 6 4 uint Read 0 65535
6076 2 6 5 uint Read 0 65535
6078 2 6 6 uint Read 0 65535
6080 2 6 7 uint Read 0 65535
6082 2 6 8 uint Read 0 65535
6084 2 6 9 uint Read 0 65535
6086 2 6 10 uint Read 0 65535
6088 2 6 11 uint Read 0 65535
6090 2 6 12 uint Read 0 65535
6092 2 6 13 uint Read 0 65535
6094 2 6 14 uint Read 0 65535
6096 2 6 15 uint Read 0 65535
6098 2 6 16 uint Read 0 65535
6100 2 7 1 uint Read 0 65535
6102 2 7 2 uint Read 0 65535
6104 2 7 3 uint Read 0 65535
6106 2 7 4 uint Read 0 65535
6108 2 7 5 uint Read 0 65535
6110 2 7 6 uint Read 0 65535
6112 2 7 7 uint Read 0 65535
6114 2 7 8 uint Read 0 65535
6116 2 7 9 uint Read 0 65535
6118 2 7 10 uint Read 0 65535
6120 2 7 11 uint Read 0 65535
6122 2 7 12 uint Read 0 65535
6124 2 7 13 uint Read 0 65535
6126 2 7 14 uint Read 0 65535
6128 2 7 15 uint Read 0 65535
6130 2 7 16 uint Read 0 65535
6132 2 8 1 uint Read 0 65535
6134 2 8 2 uint Read 0 65535
6136 2 8 3 uint Read 0 65535
6138 2 8 4 uint Read 0 65535
6140 2 8 5 uint Read 0 65535
6142 2 8 6 uint Read 0 65535
6144 2 8 7 uint Read 0 65535
6146 2 8 8 uint Read 0 65535
6148 2 8 9 uint Read 0 65535
6150 2 8 10 uint Read 0 65535
6152 2 8 11 uint Read 0 65535
6154 2 8 12 uint Read 0 65535

90
MULTILOAD II – MODBUS MAPPING

Register Length Preset Additive Data Type Read/Write Min Value Max Value
6156 2 8 13 uint Read 0 65535
6158 2 8 14 uint Read 0 65535
6160 2 8 15 uint Read 0 65535
6162 2 8 16 uint Read 0 65535
6164 2 9 1 uint Read 0 65535
6166 2 9 2 uint Read 0 65535
6168 2 9 3 uint Read 0 65535
6170 2 9 4 uint Read 0 65535
6172 2 9 5 uint Read 0 65535
6174 2 9 6 uint Read 0 65535
6176 2 9 7 uint Read 0 65535
6178 2 9 8 uint Read 0 65535
6180 2 9 9 uint Read 0 65535
6182 2 9 10 uint Read 0 65535
6184 2 9 11 uint Read 0 65535
6186 2 9 12 uint Read 0 65535
6188 2 9 13 uint Read 0 65535
6190 2 9 14 uint Read 0 65535
6192 2 9 15 uint Read 0 65535
6194 2 9 16 uint Read 0 65535
6196 2 10 1 uint Read 0 65535
6198 2 10 2 uint Read 0 65535
6200 2 10 3 uint Read 0 65535
6202 2 10 4 uint Read 0 65535
6204 2 10 5 uint Read 0 65535
6206 2 10 6 uint Read 0 65535
6208 2 10 7 uint Read 0 65535
6210 2 10 8 uint Read 0 65535
6212 2 10 9 uint Read 0 65535
6214 2 10 10 uint Read 0 65535
6216 2 10 11 uint Read 0 65535
6218 2 10 12 uint Read 0 65535
6220 2 10 13 uint Read 0 65535
6222 2 10 14 uint Read 0 65535
6224 2 10 15 uint Read 0 65535
6226 2 10 16 uint Read 0 65535
6228 2 11 1 uint Read 0 65535
6230 2 11 2 uint Read 0 65535
6232 2 11 3 uint Read 0 65535
6234 2 11 4 uint Read 0 65535
6236 2 11 5 uint Read 0 65535

91
MULTILOAD II – MODBUS MAPPING

Register Length Preset Additive Data Type Read/Write Min Value Max Value
6238 2 11 6 uint Read 0 65535
6240 2 11 7 uint Read 0 65535
6242 2 11 8 uint Read 0 65535
6244 2 11 9 uint Read 0 65535
6246 2 11 10 uint Read 0 65535
6248 2 11 11 uint Read 0 65535
6250 2 11 12 uint Read 0 65535
6252 2 11 13 uint Read 0 65535
6254 2 11 14 uint Read 0 65535
6256 2 11 15 uint Read 0 65535
6258 2 11 16 uint Read 0 65535
6260 2 12 1 uint Read 0 65535
6262 2 12 2 uint Read 0 65535
6264 2 12 3 uint Read 0 65535
6266 2 12 4 uint Read 0 65535
6268 2 12 5 uint Read 0 65535
6270 2 12 6 uint Read 0 65535
6272 2 12 7 uint Read 0 65535
6274 2 12 8 uint Read 0 65535
6276 2 12 9 uint Read 0 65535
6278 2 12 10 uint Read 0 65535
6280 2 12 11 uint Read 0 65535
6282 2 12 12 uint Read 0 65535
6284 2 12 13 uint Read 0 65535
6286 2 12 14 uint Read 0 65535
6288 2 12 15 uint Read 0 65535
6290 2 12 16 uint Read 0 65535

5.2.19 Component Current Relative Density in Ten Thousands

Register Length Preset Component Data Type Read/Write Min Value Max Value
6292 2 1 1 uint Read 0 4.0000
6294 2 1 2 uint Read 0 4.0000
6296 2 1 3 uint Read 0 4.0000
6298 2 1 4 uint Read 0 4.0000
6300 2 1 5 uint Read 0 4.0000
6302 2 1 6 uint Read 0 4.0000
6304 2 1 7 uint Read 0 4.0000
6306 2 1 8 uint Read 0 4.0000
6308 2 2 1 uint Read 0 4.0000

92
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
6310 2 2 2 uint Read 0 4.0000
6312 2 2 3 uint Read 0 4.0000
6314 2 2 4 uint Read 0 4.0000
6316 2 2 5 uint Read 0 4.0000
6318 2 2 6 uint Read 0 4.0000
6320 2 2 7 uint Read 0 4.0000
6322 2 2 8 uint Read 0 4.0000
6324 2 3 1 uint Read 0 4.0000
6326 2 3 2 uint Read 0 4.0000
6328 2 3 3 uint Read 0 4.0000
6330 2 3 4 uint Read 0 4.0000
6332 2 3 5 uint Read 0 4.0000
6334 2 3 6 uint Read 0 4.0000
6336 2 3 7 uint Read 0 4.0000
6338 2 3 8 uint Read 0 4.0000
6340 2 4 1 uint Read 0 4.0000
6342 2 4 2 uint Read 0 4.0000
6344 2 4 3 uint Read 0 4.0000
6346 2 4 4 uint Read 0 4.0000
6348 2 4 5 uint Read 0 4.0000
6350 2 4 6 uint Read 0 4.0000
6352 2 4 7 uint Read 0 4.0000
6354 2 4 8 uint Read 0 4.0000
6356 2 5 1 uint Read 0 4.0000
6358 2 5 2 uint Read 0 4.0000
6360 2 5 3 uint Read 0 4.0000
6362 2 5 4 uint Read 0 4.0000
6364 2 5 5 uint Read 0 4.0000
6366 2 5 6 uint Read 0 4.0000
6368 2 5 7 uint Read 0 4.0000
6370 2 5 8 uint Read 0 4.0000
6372 2 6 1 uint Read 0 4.0000
6374 2 6 2 uint Read 0 4.0000
6376 2 6 3 uint Read 0 4.0000
6378 2 6 4 uint Read 0 4.0000
6380 2 6 5 uint Read 0 4.0000
6382 2 6 6 uint Read 0 4.0000
6384 2 6 7 uint Read 0 4.0000
6386 2 6 8 uint Read 0 4.0000
6388 2 7 1 uint Read 0 4.0000
6390 2 7 2 uint Read 0 4.0000

93
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
6392 2 7 3 uint Read 0 4.0000
6394 2 7 4 uint Read 0 4.0000
6396 2 7 5 uint Read 0 4.0000
6398 2 7 6 uint Read 0 4.0000
6400 2 7 7 uint Read 0 4.0000
6402 2 7 8 uint Read 0 4.0000
6404 2 8 1 uint Read 0 4.0000
6406 2 8 2 uint Read 0 4.0000
6408 2 8 3 uint Read 0 4.0000
6410 2 8 4 uint Read 0 4.0000
6412 2 8 5 uint Read 0 4.0000
6414 2 8 6 uint Read 0 4.0000
6416 2 8 7 uint Read 0 4.0000
6418 2 8 8 uint Read 0 4.0000
6420 2 9 1 uint Read 0 4.0000
6422 2 9 2 uint Read 0 4.0000
6424 2 9 3 uint Read 0 4.0000
6426 2 9 4 uint Read 0 4.0000
6428 2 9 5 uint Read 0 4.0000
6430 2 9 6 uint Read 0 4.0000
6432 2 9 7 uint Read 0 4.0000
6434 2 9 8 uint Read 0 4.0000
6436 2 10 1 uint Read 0 4.0000
6438 2 10 2 uint Read 0 4.0000
6440 2 10 3 uint Read 0 4.0000
6442 2 10 4 uint Read 0 4.0000
6444 2 10 5 uint Read 0 4.0000
6446 2 10 6 uint Read 0 4.0000
6448 2 10 7 uint Read 0 4.0000
6450 2 10 8 uint Read 0 4.0000
6452 2 11 1 uint Read 0 4.0000
6454 2 11 2 uint Read 0 4.0000
6456 2 11 3 uint Read 0 4.0000
6458 2 11 4 uint Read 0 4.0000
6460 2 11 5 uint Read 0 4.0000
6462 2 11 6 uint Read 0 4.0000
6464 2 11 7 uint Read 0 4.0000
6466 2 11 8 uint Read 0 4.0000
6468 2 12 1 uint Read 0 4.0000
6470 2 12 2 uint Read 0 4.0000
6472 2 12 3 uint Read 0 4.0000

94
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
6474 2 12 4 uint Read 0 4.0000
6476 2 12 5 uint Read 0 4.0000
6478 2 12 6 uint Read 0 4.0000
6480 2 12 7 uint Read 0 4.0000
6482 2 12 8 uint Read 0 4.0000

5.2.20 Component Current BSW Hund

Register Length Preset Component Data Type Read/Write Min Value Max Value
6484 2 1 1 uint Read 0 65535
6486 2 1 2 uint Read 0 65535
6488 2 1 3 uint Read 0 65535
6490 2 1 4 uint Read 0 65535
6492 2 1 5 uint Read 0 65535
6494 2 1 6 uint Read 0 65535
6496 2 1 7 uint Read 0 65535
6498 2 1 8 uint Read 0 65535
6500 2 2 1 uint Read 0 65535
6502 2 2 2 uint Read 0 65535
6504 2 2 3 uint Read 0 65535
6506 2 2 4 uint Read 0 65535
6508 2 2 5 uint Read 0 65535
6510 2 2 6 uint Read 0 65535
6512 2 2 7 uint Read 0 65535
6514 2 2 8 uint Read 0 65535
6516 2 3 1 uint Read 0 65535
6518 2 3 2 uint Read 0 65535
6520 2 3 3 uint Read 0 65535
6522 2 3 4 uint Read 0 65535
6524 2 3 5 uint Read 0 65535
6526 2 3 6 uint Read 0 65535
6528 2 3 7 uint Read 0 65535
6530 2 3 8 uint Read 0 65535
6532 2 4 1 uint Read 0 65535
6534 2 4 2 uint Read 0 65535
6536 2 4 3 uint Read 0 65535
6538 2 4 4 uint Read 0 65535
6540 2 4 5 uint Read 0 65535
6542 2 4 6 uint Read 0 65535
6544 2 4 7 uint Read 0 65535

95
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
6546 2 4 8 uint Read 0 65535
6548 2 5 1 uint Read 0 65535
6550 2 5 2 uint Read 0 65535
6552 2 5 3 uint Read 0 65535
6554 2 5 4 uint Read 0 65535
6556 2 5 5 uint Read 0 65535
6558 2 5 6 uint Read 0 65535
6560 2 5 7 uint Read 0 65535
6562 2 5 8 uint Read 0 65535
6564 2 6 1 uint Read 0 65535
6566 2 6 2 uint Read 0 65535
6568 2 6 3 uint Read 0 65535
6570 2 6 4 uint Read 0 65535
6572 2 6 5 uint Read 0 65535
6574 2 6 6 uint Read 0 65535
6576 2 6 7 uint Read 0 65535
6578 2 6 8 uint Read 0 65535
6580 2 7 1 uint Read 0 65535
6582 2 7 2 uint Read 0 65535
6584 2 7 3 uint Read 0 65535
6586 2 7 4 uint Read 0 65535
6588 2 7 5 uint Read 0 65535
6590 2 7 6 uint Read 0 65535
6592 2 7 7 uint Read 0 65535
6594 2 7 8 uint Read 0 65535
6596 2 8 1 uint Read 0 65535
6598 2 8 2 uint Read 0 65535
6600 2 8 3 uint Read 0 65535
6602 2 8 4 uint Read 0 65535
6604 2 8 5 uint Read 0 65535
6606 2 8 6 uint Read 0 65535
6608 2 8 7 uint Read 0 65535
6610 2 8 8 uint Read 0 65535
6612 2 9 1 uint Read 0 65535
6614 2 9 2 uint Read 0 65535
6616 2 9 3 uint Read 0 65535
6618 2 9 4 uint Read 0 65535
6620 2 9 5 uint Read 0 65535
6622 2 9 6 uint Read 0 65535
6624 2 9 7 uint Read 0 65535
6626 2 9 8 uint Read 0 65535

96
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
6628 2 10 1 uint Read 0 65535
6630 2 10 2 uint Read 0 65535
6632 2 10 3 uint Read 0 65535
6634 2 10 4 uint Read 0 65535
6636 2 10 5 uint Read 0 65535
6638 2 10 6 uint Read 0 65535
6640 2 10 7 uint Read 0 65535
6642 2 10 8 uint Read 0 65535
6644 2 11 1 uint Read 0 65535
6646 2 11 2 uint Read 0 65535
6648 2 11 3 uint Read 0 65535
6650 2 11 4 uint Read 0 65535
6652 2 11 5 uint Read 0 65535
6654 2 11 6 uint Read 0 65535
6656 2 11 7 uint Read 0 65535
6658 2 11 8 uint Read 0 65535
6660 2 12 1 uint Read 0 65535
6662 2 12 2 uint Read 0 65535
6664 2 12 3 uint Read 0 65535
6666 2 12 4 uint Read 0 65535
6668 2 12 5 uint Read 0 65535
6670 2 12 6 uint Read 0 65535
6672 2 12 7 uint Read 0 65535
6674 2 12 8 uint Read 0 65535

5.2.21 Component Current API Gravity Tenths

Register Length Preset Component Data Type Read/Write Min Value Max Value
6676 2 1 1 int Read -100.00 1100.00
6678 2 1 2 int Read -100.00 1100.00
6680 2 1 3 int Read -100.00 1100.00
6682 2 1 4 int Read -100.00 1100.00
6684 2 1 5 int Read -100.00 1100.00
6686 2 1 6 int Read -100.00 1100.00
6688 2 1 7 int Read -100.00 1100.00
6690 2 1 8 int Read -100.00 1100.00
6692 2 2 1 int Read -100.00 1100.00
6694 2 2 2 int Read -100.00 1100.00
6696 2 2 3 int Read -100.00 1100.00
6698 2 2 4 int Read -100.00 1100.00

97
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
6700 2 2 5 int Read -100.00 1100.00
6702 2 2 6 int Read -100.00 1100.00
6704 2 2 7 int Read -100.00 1100.00
6706 2 2 8 int Read -100.00 1100.00
6708 2 3 1 int Read -100.00 1100.00
6710 2 3 2 int Read -100.00 1100.00
6712 2 3 3 int Read -100.00 1100.00
6714 2 3 4 int Read -100.00 1100.00
6716 2 3 5 int Read -100.00 1100.00
6718 2 3 6 int Read -100.00 1100.00
6720 2 3 7 int Read -100.00 1100.00
6722 2 3 8 int Read -100.00 1100.00
6724 2 4 1 int Read -100.00 1100.00
6726 2 4 2 int Read -100.00 1100.00
6728 2 4 3 int Read -100.00 1100.00
6730 2 4 4 int Read -100.00 1100.00
6732 2 4 5 int Read -100.00 1100.00
6734 2 4 6 int Read -100.00 1100.00
6736 2 4 7 int Read -100.00 1100.00
6738 2 4 8 int Read -100.00 1100.00
6740 2 5 1 int Read -100.00 1100.00
6742 2 5 2 int Read -100.00 1100.00
6744 2 5 3 int Read -100.00 1100.00
6746 2 5 4 int Read -100.00 1100.00
6748 2 5 5 int Read -100.00 1100.00
6750 2 5 6 int Read -100.00 1100.00
6752 2 5 7 int Read -100.00 1100.00
6754 2 5 8 int Read -100.00 1100.00
6756 2 6 1 int Read -100.00 1100.00
6758 2 6 2 int Read -100.00 1100.00
6760 2 6 3 int Read -100.00 1100.00
6762 2 6 4 int Read -100.00 1100.00
6764 2 6 5 int Read -100.00 1100.00
6766 2 6 6 int Read -100.00 1100.00
6768 2 6 7 int Read -100.00 1100.00
6770 2 6 8 int Read -100.00 1100.00
6772 2 7 1 int Read -100.00 1100.00
6774 2 7 2 int Read -100.00 1100.00
6776 2 7 3 int Read -100.00 1100.00
6778 2 7 4 int Read -100.00 1100.00
6780 2 7 5 int Read -100.00 1100.00

98
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
6782 2 7 6 int Read -100.00 1100.00
6784 2 7 7 int Read -100.00 1100.00
6786 2 7 8 int Read -100.00 1100.00
6788 2 8 1 int Read -100.00 1100.00
6790 2 8 2 int Read -100.00 1100.00
6792 2 8 3 int Read -100.00 1100.00
6794 2 8 4 int Read -100.00 1100.00
6796 2 8 5 int Read -100.00 1100.00
6798 2 8 6 int Read -100.00 1100.00
6800 2 8 7 int Read -100.00 1100.00
6802 2 8 8 int Read -100.00 1100.00
6804 2 9 1 int Read -100.00 1100.00
6806 2 9 2 int Read -100.00 1100.00
6808 2 9 3 int Read -100.00 1100.00
6810 2 9 4 int Read -100.00 1100.00
6812 2 9 5 int Read -100.00 1100.00
6814 2 9 6 int Read -100.00 1100.00
6816 2 9 7 int Read -100.00 1100.00
6818 2 9 8 int Read -100.00 1100.00
6820 2 10 1 int Read -100.00 1100.00
6822 2 10 2 int Read -100.00 1100.00
6824 2 10 3 int Read -100.00 1100.00
6826 2 10 4 int Read -100.00 1100.00
6828 2 10 5 int Read -100.00 1100.00
6830 2 10 6 int Read -100.00 1100.00
6832 2 10 7 int Read -100.00 1100.00
6834 2 10 8 int Read -100.00 1100.00
6836 2 11 1 int Read -100.00 1100.00
6838 2 11 2 int Read -100.00 1100.00
6840 2 11 3 int Read -100.00 1100.00
6842 2 11 4 int Read -100.00 1100.00
6844 2 11 5 int Read -100.00 1100.00
6846 2 11 6 int Read -100.00 1100.00
6848 2 11 7 int Read -100.00 1100.00
6850 2 11 8 int Read -100.00 1100.00
6852 2 12 1 int Read -100.00 1100.00
6854 2 12 2 int Read -100.00 1100.00
6856 2 12 3 int Read -100.00 1100.00
6858 2 12 4 int Read -100.00 1100.00
6860 2 12 5 int Read -100.00 1100.00
6862 2 12 6 int Read -100.00 1100.00

99
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
6864 2 12 7 int Read -100.00 1100.00
6866 2 12 8 int Read -100.00 1100.00
5.2.22 Component Current Mass Delivered

Register Length Preset Component Data Type Read/Write Min Value Max Value
6868 2 1 1 uint Read 0 65535
6870 2 1 2 uint Read 0 65535
6872 2 1 3 uint Read 0 65535
6874 2 1 4 uint Read 0 65535
6876 2 1 5 uint Read 0 65535
6878 2 1 6 uint Read 0 65535
6880 2 1 7 uint Read 0 65535
6882 2 1 8 uint Read 0 65535
6884 2 2 1 uint Read 0 65535
6886 2 2 2 uint Read 0 65535
6888 2 2 3 uint Read 0 65535
6890 2 2 4 uint Read 0 65535

100
MULTILOAD II – MODBUS MAPPING

6
Chapter

Chapter 6 Alarm Registers


This chapter outlines the register addresses for preset, meter, component and additive alarms.

See MultiLoad Communications manual for register definitions and hexadecimal bit mapping.

Alarm Messages
6.1.1 Bay Alarm Messages

Register Length Description Read/Write Data Type Min Value Max Value
2500 1 Modbus Bay Alarm Index Read/Write uint 0 65535
2501 1 Bay Alarm Base Level Read/Write uint 0 65535
2502 15 Bay Alarm Message Read/Write char 32 122
2517 1 Bay Alarm Promotion Count Read/Write uint 0 65535
2518 1 Bay Alarm Promoted Level Read/Write uint 0 65535
2519 1 Bay Alarm Count Reset Mode Read/Write uint 0 65535

6.1.2 Preset Alarm Messages

Data Min Max


Register Length Description Read/Write Type Value Value
Modbus Preset Alarm
2520 1 Index Read/Write uint 0 65535
2521 1 Preset Alarm Base Level Read/Write uint 0 65535
2522 15 Preset Alarm Message Read/Write char 32 122
Preset Alarm Promotion
2537 1 Count Read/Write uint 0 65535
Preset Alarm Promoted
2538 1 Level Read/Write uint 0 65535
Preset Alarm Count Reset
2539 1 Mode Read/Write uint 0 65535

101
MULTILOAD II – MODBUS MAPPING

6.1.3 Meter Alarm Messages

Register Length Description Read/Write Data Type Min Value Max Value
2540 1 Modbus Meter Alarm Index Read/Write uint 0 65535
2541 1 Meter Alarm Base Level Read/Write uint 0 65535
2542 15 Meter Alarm Message Read/Write char 32 122
2557 1 Meter Alarm Promotion Count Read/Write uint 0 65535
2558 1 Meter Alarm Promoted Level Read/Write uint 0 65535
2559 1 Meter Alarm Count Reset Mode Read/Write uint 0 65535

6.1.4 Component Alarm Messages

Data Min Max


Register Length Description Read/Write Type Value Value
2560 1 Modbus Component Alarm Index Read/Write uint 0 65535
2561 1 Component Alarm Base Level Read/Write uint 0 65535
2562 15 Component Alarm Message Read/Write char 32 122
2577 1 Component Alarm Promotion Count Read/Write uint 0 65535
2578 1 Component Alarm Promoted Level Read/Write uint 0 65535
Component Alarm Count Reset
2579 1 Mode Read/Write uint 0 65535

6.1.5 Additive Alarm Messages

Register Length Description Read/Write Data Type Min Value Max Value
2580 1 Modbus Additive Alarm Index Read/Write uint 0 65535
2581 1 Additive Alarm Base Level Read/Write uint 0 65535
2582 15 Additive Alarm Message Read/Write char 32 122
2597 1 Additive Alarm Promotion Count Read/Write uint 0 65535
2598 1 Additive Alarm Promoted Level Read/Write uint 0 65535
2599 1 Additive Alarm Count Reset Mode Read/Write uint 0 65535

Trip Preset Alarms


Register Length Preset Data Type Read/Write Min Value Max Value
7082 1 1 uint Read 0 65535
7083 1 2 uint Read 0 65535
7084 1 3 uint Read 0 65535
7085 1 4 uint Read 0 65535
7086 1 5 uint Read 0 65535
7087 1 6 uint Read 0 65535
7088 1 7 uint Read 0 65535

102
MULTILOAD II – MODBUS MAPPING

Register Length Preset Data Type Read/Write Min Value Max Value
7089 1 8 uint Read 0 65535
7090 1 9 uint Read 0 65535
7091 1 10 uint Read 0 65535
7092 1 11 uint Read 0 65535
7093 1 12 uint Read 0 65535

Request Alarms
6.3.1 Request Preset Alarms

Register Length Preset Data Type Read/Write Min Value Max Value
4024 1 1 uint Read 0 65535
4025 1 2 uint Read 0 65535
4026 1 3 uint Read 0 65535
4027 1 4 uint Read 0 65535
4028 1 5 uint Read 0 65535
4029 1 6 uint Read 0 65535
4030 1 7 uint Read 0 65535
4031 1 8 uint Read 0 65535
4032 1 9 uint Read 0 65535
4033 1 10 uint Read 0 65535
4034 1 11 uint Read 0 65535
4035 1 12 uint Read 0 65535

6.3.2 Request Bay Alarms

Register Length Description Data Type Read/Write Min Value Max Value
7094 1 Bay Alarm uint Read 0 65535

6.3.3 Request Component Alarms

Register Length Preset Component Data Type Read/Write Min Value Max Value
7095 1 1 1 uint Read 0 65535
7096 1 1 2 uint Read 0 65535
7097 1 1 3 uint Read 0 65535
7098 1 1 4 uint Read 0 65535
7099 1 1 5 uint Read 0 65535
7100 1 1 6 uint Read 0 65535
7101 1 1 7 uint Read 0 65535
7102 1 1 8 uint Read 0 65535
7103 1 2 1 uint Read 0 65535
7104 1 2 2 uint Read 0 65535

103
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
7105 1 2 3 uint Read 0 65535
7106 1 2 4 uint Read 0 65535
7107 1 2 5 uint Read 0 65535
7108 1 2 6 uint Read 0 65535
7109 1 2 7 uint Read 0 65535
7110 1 2 8 uint Read 0 65535
7111 1 3 1 uint Read 0 65535
7112 1 3 2 uint Read 0 65535
7113 1 3 3 uint Read 0 65535
7114 1 3 4 uint Read 0 65535
7115 1 3 5 uint Read 0 65535
7116 1 3 6 uint Read 0 65535
7117 1 3 7 uint Read 0 65535
7118 1 3 8 uint Read 0 65535
7119 1 4 1 uint Read 0 65535
7120 1 4 2 uint Read 0 65535
7121 1 4 3 uint Read 0 65535
7122 1 4 4 uint Read 0 65535
7123 1 4 5 uint Read 0 65535
7124 1 4 6 uint Read 0 65535
7125 1 4 7 uint Read 0 65535
7126 1 4 8 uint Read 0 65535
7127 1 5 1 uint Read 0 65535
7128 1 5 2 uint Read 0 65535
7129 1 5 3 uint Read 0 65535
7130 1 5 4 uint Read 0 65535
7131 1 5 5 uint Read 0 65535
7132 1 5 6 uint Read 0 65535
7133 1 5 7 uint Read 0 65535
7134 1 5 8 uint Read 0 65535
7135 1 6 1 uint Read 0 65535
7136 1 6 2 uint Read 0 65535
7137 1 6 3 uint Read 0 65535
7138 1 6 4 uint Read 0 65535
7139 1 6 5 uint Read 0 65535
7140 1 6 6 uint Read 0 65535
7141 1 6 7 uint Read 0 65535
7142 1 6 8 uint Read 0 65535
7143 1 7 1 uint Read 0 65535
7144 1 7 2 uint Read 0 65535
7145 1 7 3 uint Read 0 65535

104
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
7146 1 7 4 uint Read 0 65535
7147 1 7 5 uint Read 0 65535
7148 1 7 6 uint Read 0 65535
7149 1 7 7 uint Read 0 65535
7150 1 7 8 uint Read 0 65535
7151 1 8 1 uint Read 0 65535
7152 1 8 2 uint Read 0 65535
7153 1 8 3 uint Read 0 65535
7154 1 8 4 uint Read 0 65535
7155 1 8 5 uint Read 0 65535
7156 1 8 6 uint Read 0 65535
7157 1 8 7 uint Read 0 65535
7158 1 8 8 uint Read 0 65535
7159 1 9 1 uint Read 0 65535
7160 1 9 2 uint Read 0 65535
7161 1 9 3 uint Read 0 65535
7162 1 9 4 uint Read 0 65535
7163 1 9 5 uint Read 0 65535
7164 1 9 6 uint Read 0 65535
7165 1 9 7 uint Read 0 65535
7166 1 9 8 uint Read 0 65535
7167 1 10 1 uint Read 0 65535
7168 1 10 2 uint Read 0 65535
7169 1 10 3 uint Read 0 65535
7170 1 10 4 uint Read 0 65535
7171 1 10 5 uint Read 0 65535
7172 1 10 6 uint Read 0 65535
7173 1 10 7 uint Read 0 65535
7174 1 10 8 uint Read 0 65535
7175 1 11 1 uint Read 0 65535
7176 1 11 2 uint Read 0 65535
7177 1 11 3 uint Read 0 65535
7178 1 11 4 uint Read 0 65535
7179 1 11 5 uint Read 0 65535
7180 1 11 6 uint Read 0 65535
7181 1 11 7 uint Read 0 65535
7182 1 11 8 uint Read 0 65535
7183 1 12 1 uint Read 0 65535
7184 1 12 2 uint Read 0 65535
7185 1 12 3 uint Read 0 65535
7186 1 12 4 uint Read 0 65535

105
MULTILOAD II – MODBUS MAPPING

Register Length Preset Component Data Type Read/Write Min Value Max Value
7187 1 12 5 uint Read 0 65535
7188 1 12 6 uint Read 0 65535
7189 1 12 7 uint Read 0 65535
7190 1 12 8 uint Read 0 65535

6.3.4 Request Meter Alarms

Register Length Preset Meter Data Type Read/Write Min Value Max Value
7191 1 1 1 uint Read 0 65535
7192 1 1 2 uint Read 0 65535
7193 1 1 3 uint Read 0 65535
7194 1 1 4 uint Read 0 65535
7195 1 1 5 uint Read 0 65535
7196 1 2 1 uint Read 0 65535
7197 1 2 2 uint Read 0 65535
7198 1 2 3 uint Read 0 65535
7199 1 2 4 uint Read 0 65535
7200 1 2 5 uint Read 0 65535
7201 1 3 1 uint Read 0 65535
7202 1 3 2 uint Read 0 65535
7203 1 3 3 uint Read 0 65535
7204 1 3 4 uint Read 0 65535
7205 1 3 5 uint Read 0 65535
7206 1 4 1 uint Read 0 65535
7207 1 4 2 uint Read 0 65535
7208 1 4 3 uint Read 0 65535
7209 1 4 4 uint Read 0 65535
7210 1 4 5 uint Read 0 65535
7211 1 5 1 uint Read 0 65535
7212 1 5 2 uint Read 0 65535
7213 1 5 3 uint Read 0 65535
7214 1 5 4 uint Read 0 65535
7215 1 5 5 uint Read 0 65535
7216 1 6 1 uint Read 0 65535
7217 1 6 2 uint Read 0 65535
7218 1 6 3 uint Read 0 65535
7219 1 6 4 uint Read 0 65535
7220 1 6 5 uint Read 0 65535
7221 1 7 1 uint Read 0 65535
7222 1 7 2 uint Read 0 65535

106
MULTILOAD II – MODBUS MAPPING

Register Length Preset Meter Data Type Read/Write Min Value Max Value
7223 1 7 3 uint Read 0 65535
7224 1 7 4 uint Read 0 65535
7225 1 7 5 uint Read 0 65535
7226 1 8 1 uint Read 0 65535
7227 1 8 2 uint Read 0 65535
7228 1 8 3 uint Read 0 65535
7229 1 8 4 uint Read 0 65535
7230 1 8 5 uint Read 0 65535
7231 1 9 1 uint Read 0 65535
7232 1 9 2 uint Read 0 65535
7233 1 9 3 uint Read 0 65535
7234 1 9 4 uint Read 0 65535
7235 1 9 5 uint Read 0 65535
7236 1 10 1 uint Read 0 65535
7237 1 10 2 uint Read 0 65535
7238 1 10 3 uint Read 0 65535
7239 1 10 4 uint Read 0 65535
7240 1 10 5 uint Read 0 65535
7241 1 11 1 uint Read 0 65535
7242 1 11 2 uint Read 0 65535
7243 1 11 3 uint Read 0 65535
7244 1 11 4 uint Read 0 65535
7245 1 11 5 uint Read 0 65535
7246 1 12 1 uint Read 0 65535
7247 1 12 2 uint Read 0 65535
7248 1 12 3 uint Read 0 65535
7249 1 12 4 uint Read 0 65535
7250 1 12 5 uint Read 0 65535

6.3.5 Request Additive Alarms

Register Length Preset Additive Data Type Read/Write Min Value Max Value
7251 1 1 1 uint Read 0 65535
7252 1 1 2 uint Read 0 65535
7253 1 1 3 uint Read 0 65535
7254 1 1 4 uint Read 0 65535
7255 1 1 5 uint Read 0 65535
7256 1 1 6 uint Read 0 65535
7257 1 1 7 uint Read 0 65535
7258 1 1 8 uint Read 0 65535

107
MULTILOAD II – MODBUS MAPPING

Register Length Preset Additive Data Type Read/Write Min Value Max Value
7259 1 1 9 uint Read 0 65535
7260 1 1 10 uint Read 0 65535
7261 1 1 11 uint Read 0 65535
7262 1 1 12 uint Read 0 65535
7263 1 1 13 uint Read 0 65535
7264 1 1 14 uint Read 0 65535
7265 1 1 15 uint Read 0 65535
7266 1 1 16 uint Read 0 65535
7267 1 2 1 uint Read 0 65535
7268 1 2 2 uint Read 0 65535
7269 1 2 3 uint Read 0 65535
7270 1 2 4 uint Read 0 65535
7271 1 2 5 uint Read 0 65535
7272 1 2 6 uint Read 0 65535
7273 1 2 7 uint Read 0 65535
7274 1 2 8 uint Read 0 65535
7275 1 2 9 uint Read 0 65535
7276 1 2 10 uint Read 0 65535
7277 1 2 11 uint Read 0 65535
7278 1 2 12 uint Read 0 65535
7279 1 2 13 uint Read 0 65535
7280 1 2 14 uint Read 0 65535
7281 1 2 15 uint Read 0 65535
7282 1 2 16 uint Read 0 65535
7283 1 3 1 uint Read 0 65535
7284 1 3 2 uint Read 0 65535
7285 1 3 3 uint Read 0 65535
7286 1 3 4 uint Read 0 65535
7287 1 3 5 uint Read 0 65535
7288 1 3 6 uint Read 0 65535
7289 1 3 7 uint Read 0 65535
7290 1 3 8 uint Read 0 65535
7291 1 3 9 uint Read 0 65535
7292 1 3 10 uint Read 0 65535
7293 1 3 11 uint Read 0 65535
7294 1 3 12 uint Read 0 65535
7295 1 3 13 uint Read 0 65535
7296 1 3 14 uint Read 0 65535
7297 1 3 15 uint Read 0 65535
7298 1 3 16 uint Read 0 65535
7299 1 4 1 uint Read 0 65535

108
MULTILOAD II – MODBUS MAPPING

Register Length Preset Additive Data Type Read/Write Min Value Max Value
7300 1 4 2 uint Read 0 65535
7301 1 4 3 uint Read 0 65535
7302 1 4 4 uint Read 0 65535
7303 1 4 5 uint Read 0 65535
7304 1 4 6 uint Read 0 65535
7305 1 4 7 uint Read 0 65535
7306 1 4 8 uint Read 0 65535
7307 1 4 9 uint Read 0 65535
7308 1 4 10 uint Read 0 65535
7309 1 4 11 uint Read 0 65535
7310 1 4 12 uint Read 0 65535
7311 1 4 13 uint Read 0 65535
7312 1 4 14 uint Read 0 65535
7313 1 4 15 uint Read 0 65535
7314 1 4 16 uint Read 0 65535
7315 1 5 1 uint Read 0 65535
7316 1 5 2 uint Read 0 65535
7317 1 5 3 uint Read 0 65535
7318 1 5 4 uint Read 0 65535
7319 1 5 5 uint Read 0 65535
7320 1 5 6 uint Read 0 65535
7321 1 5 7 uint Read 0 65535
7322 1 5 8 uint Read 0 65535
7323 1 5 9 uint Read 0 65535
7324 1 5 10 uint Read 0 65535
7325 1 5 11 uint Read 0 65535
7326 1 5 12 uint Read 0 65535
7327 1 5 13 uint Read 0 65535
7328 1 5 14 uint Read 0 65535
7329 1 5 15 uint Read 0 65535
7330 1 5 16 uint Read 0 65535
7331 1 6 1 uint Read 0 65535
7332 1 6 2 uint Read 0 65535
7333 1 6 3 uint Read 0 65535
7334 1 6 4 uint Read 0 65535
7335 1 6 5 uint Read 0 65535
7336 1 6 6 uint Read 0 65535
7337 1 6 7 uint Read 0 65535
7338 1 6 8 uint Read 0 65535
7339 1 6 9 uint Read 0 65535
7340 1 6 10 uint Read 0 65535

109
MULTILOAD II – MODBUS MAPPING

Register Length Preset Additive Data Type Read/Write Min Value Max Value
7341 1 6 11 uint Read 0 65535
7342 1 6 12 uint Read 0 65535
7343 1 6 13 uint Read 0 65535
7344 1 6 14 uint Read 0 65535
7345 1 6 15 uint Read 0 65535
7346 1 6 16 uint Read 0 65535
7347 1 7 1 uint Read 0 65535
7348 1 7 2 uint Read 0 65535
7349 1 7 3 uint Read 0 65535
7350 1 7 4 uint Read 0 65535
7351 1 7 5 uint Read 0 65535
7352 1 7 6 uint Read 0 65535
7353 1 7 7 uint Read 0 65535
7354 1 7 8 uint Read 0 65535
7355 1 7 9 uint Read 0 65535
7356 1 7 10 uint Read 0 65535
7357 1 7 11 uint Read 0 65535
7358 1 7 12 uint Read 0 65535
7359 1 7 13 uint Read 0 65535
7360 1 7 14 uint Read 0 65535
7361 1 7 15 uint Read 0 65535
7362 1 7 16 uint Read 0 65535
7363 1 8 1 uint Read 0 65535
7364 1 8 2 uint Read 0 65535
7365 1 8 3 uint Read 0 65535
7366 1 8 4 uint Read 0 65535
7367 1 8 5 uint Read 0 65535
7368 1 8 6 uint Read 0 65535
7369 1 8 7 uint Read 0 65535
7370 1 8 8 uint Read 0 65535
7371 1 8 9 uint Read 0 65535
7372 1 8 10 uint Read 0 65535
7373 1 8 11 uint Read 0 65535
7374 1 8 12 uint Read 0 65535
7375 1 8 13 uint Read 0 65535
7376 1 8 14 uint Read 0 65535
7377 1 8 15 uint Read 0 65535
7378 1 8 16 uint Read 0 65535
7379 1 9 1 uint Read 0 65535
7380 1 9 2 uint Read 0 65535
7381 1 9 3 uint Read 0 65535

110
MULTILOAD II – MODBUS MAPPING

Register Length Preset Additive Data Type Read/Write Min Value Max Value
7382 1 9 4 uint Read 0 65535
7383 1 9 5 uint Read 0 65535
7384 1 9 6 uint Read 0 65535
7385 1 9 7 uint Read 0 65535
7386 1 9 8 uint Read 0 65535
7387 1 9 9 uint Read 0 65535
7388 1 9 10 uint Read 0 65535
7389 1 9 11 uint Read 0 65535
7390 1 9 12 uint Read 0 65535
7391 1 9 13 uint Read 0 65535
7392 1 9 14 uint Read 0 65535
7393 1 9 15 uint Read 0 65535
7394 1 9 16 uint Read 0 65535
7395 1 10 1 uint Read 0 65535
7396 1 10 2 uint Read 0 65535
7397 1 10 3 uint Read 0 65535
7398 1 10 4 uint Read 0 65535
7399 1 10 5 uint Read 0 65535
7400 1 10 6 uint Read 0 65535
7401 1 10 7 uint Read 0 65535
7402 1 10 8 uint Read 0 65535
7403 1 10 9 uint Read 0 65535
7404 1 10 10 uint Read 0 65535
7405 1 10 11 uint Read 0 65535
7406 1 10 12 uint Read 0 65535
7407 1 10 13 uint Read 0 65535
7408 1 10 14 uint Read 0 65535
7409 1 10 15 uint Read 0 65535
7410 1 10 16 uint Read 0 65535
7411 1 11 1 uint Read 0 65535
7412 1 11 2 uint Read 0 65535
7413 1 11 3 uint Read 0 65535
7414 1 11 4 uint Read 0 65535
7415 1 11 5 uint Read 0 65535
7416 1 11 6 uint Read 0 65535
7417 1 11 7 uint Read 0 65535
7418 1 11 8 uint Read 0 65535
7419 1 11 9 uint Read 0 65535
7420 1 11 10 uint Read 0 65535
7421 1 11 11 uint Read 0 65535
7422 1 11 12 uint Read 0 65535

111
MULTILOAD II – MODBUS MAPPING

Register Length Preset Additive Data Type Read/Write Min Value Max Value
7423 1 11 13 uint Read 0 65535
7424 1 11 14 uint Read 0 65535
7425 1 11 15 uint Read 0 65535
7426 1 11 16 uint Read 0 65535
7427 1 12 1 uint Read 0 65535
7428 1 12 2 uint Read 0 65535
7429 1 12 3 uint Read 0 65535
7430 1 12 4 uint Read 0 65535
7431 1 12 5 uint Read 0 65535
7432 1 12 6 uint Read 0 65535
7433 1 12 7 uint Read 0 65535
7434 1 12 8 uint Read 0 65535
7435 1 12 9 uint Read 0 65535
7436 1 12 10 uint Read 0 65535
7437 1 12 11 uint Read 0 65535
7438 1 12 12 uint Read 0 65535
7439 1 12 13 uint Read 0 65535
7440 1 12 14 uint Read 0 65535
7441 1 12 15 uint Read 0 65535
7442 1 12 16 uint Read 0 65535

112
MULTILOAD II – MODBUS MAPPING

Chapter

7
Chapter 7 Preset Status Registers
This chapter outlines the register address for Preset State and Status.

See MultiLoad Communications manual for register definitions and hexadecimal bit mapping.

Preset State
Register Length Preset Data Type Read/Write Min Value Max Value
4000 1 1 uint Read 0 99
4001 1 2 uint Read 0 99
4002 1 3 uint Read 0 99
4003 1 4 uint Read 0 99
4004 1 5 uint Read 0 99
4005 1 6 uint Read 0 99
4006 1 7 uint Read 0 99
4007 1 8 uint Read 0 99
4008 1 9 uint Read 0 99
4009 1 10 uint Read 0 99
4010 1 11 uint Read 0 99
4011 1 12 uint Read 0 99

Preset Status
Register Length Preset Data Type Read/Write Min Value Max Value
4012 1 1 uint Read 0 65535
4013 1 2 uint Read 0 65535
4014 1 3 uint Read 0 65535
4015 1 4 uint Read 0 65535
4016 1 5 uint Read 0 65535
4017 1 6 uint Read 0 65535
4018 1 7 uint Read 0 65535
4019 1 8 uint Read 0 65535
4020 1 9 uint Read 0 65535
4021 1 10 uint Read 0 65535

113
MULTILOAD II – MODBUS MAPPING

Register Length Preset Data Type Read/Write Min Value Max Value
4022 1 11 uint Read 0 65535
4023 1 12 uint Read 0 65535

State/Status Registers
Register Length Description Read/Write Data Type Min Value Max Value
7000 1 RCU State Read uint 0 65535
7001 1 Card Status Read uint 0 65535
7002 1 RCU Status Read uint 0 65535

Start Preset Flow


Register Length Preset Data Type Read/Write Min Value Max Value
7443 1 1 uint Read 0 65535
7444 1 2 uint Read 0 65535
7445 1 3 uint Read 0 65535
7446 1 4 uint Read 0 65535
7447 1 5 uint Read 0 65535
7448 1 6 uint Read 0 65535
7449 1 7 uint Read 0 65535
7450 1 8 uint Read 0 65535
7451 1 9 uint Read 0 65535
7452 1 10 uint Read 0 65535
7453 1 11 uint Read 0 65535
7454 1 12 uint Read 0 65535

Stop Preset Flow


Register Length Preset Data Type Read/Write Min Value Max Value
7455 1 1 uint Read 0 65535
7456 1 2 uint Read 0 65535
7457 1 3 uint Read 0 65535
7458 1 4 uint Read 0 65535
7459 1 5 uint Read 0 65535
7460 1 6 uint Read 0 65535
7461 1 7 uint Read 0 65535
7462 1 8 uint Read 0 65535
7463 1 9 uint Read 0 65535
7464 1 10 uint Read 0 65535
7465 1 11 uint Read 0 65535

114
MULTILOAD II – MODBUS MAPPING

Register Length Preset Data Type Read/Write Min Value Max Value
7466 1 12 uint Read 0 65535

115
Toptech Systems North America office:

Toptech Systems Inc


1124 Florida Central Parkway
Longwood, FL 32750, USA
Phone: +1 (407) 332-1774

Europe office:
Toptech Systems NV
Nieuwe Weg 1
2070 Zwijndrecht (Antwerp), Belgium
Phone: +32 (0)3 250 60 60

You might also like