Professional Documents
Culture Documents
Control Sixteen
Control Sixteen
TELEMETRY
VOLTAGE TELEMETERING
CURRENT TELEMETERING
THE EARLY DEVICES FOR MEASURING CURRENT WERE COMPARABLE TO THOSE IN FIG. 1.
A PRESSURE-SENSITIVE BOURDON TUBE PLACES A SLIDING CONTACT ON A SLIDEWIRE
POTENTIOMETER, WHICH IS CONNECTED IN LINE TO A BATTERY. A CURRENT MEASURING
EQUIPMENT IS LINKED TO A PAIR OF CABLES THAT MAKE UP THE TELEMETERING CHANNEL. THE
BOURDON TUBE MOVES AND POSITIONS THE SLIDING CONTACT IN RESPONSE TO CHANGES IN
THE MEASURED PRESSURE, WHICH ALTERS THE CURRENT IN THE TELEMETERING CHANNEL. A
POINTER IS PLACED ON A SCALE THAT IS GRADUATED ACCORDING TO THE PRESSURE BEING
MEASURED BY THE MILLIAMMETER, WHICH ALSO MEASURES CURRENT.
FIG. 1: TRADITIONAL VOLTAGE AND CURRENT TELEMETRY SYSTEMS. (A) VOLTAGE (B)
CURRENT AND (C) FORCE BALANCE CURRENT.
POSITION TELEMETERING
FREQUENCY TELEMETERING
THESE SYSTEMS MAKE USE OF VARIOUS TYPES OF ELECTRIC PULSES AND TRANSMIT THEM
AS A FUNCTION OF TIME, INDEPENDENTLY OF ELECTRICAL VARIATIONS IN THE TRANSMISSION
CHANNEL. TELEGRAPH AND TELETYPE SYSTEMS EMPLOY THIS PRINCIPLE. PULSE TELEMETERING
SYSTEMS CAN BE CLASSIFIED AS PULSE DURATION, PULSE COUNT, AND PULSE CODE OR DIGITAL
TELEMETERING SYSTEMS.
PULSE DURATION SYSTEM
2. RECEIVING INSTRUMENTS ARE NOT EXPOSED TO FIELD CONDITIONS. ONLY THE TRANSMITTER
IS EXPOSED TO PROCESS FLUIDS AND FIELD ATMOSPHERES. CONTROLLERS, INDICATORS, AND
RECORDERS OPERATE MORE RELIABLY IN A CLEAN CONTROL ROOM ENVIRONMENT.
3. RECEIVING INSTRUMENTS CAN BE STANDARDIZED. THE SAME KIND OF CONTROLLER,
INDICATOR, OR RECORDER CAN BE USED FOR ALL PROCESS VARIABLES SUCH AS FLOW,
TEMPERATURE, AND LEVEL.
AIR QUALITY
TO ENSURE ACCURATE AND RELIABLE OPERATION OF PNEUMATIC INSTRUMENTS, A
CLEAN, DRY, REGULATED AIR SUPPLY MUST BE PROVIDED. SOLID OR LIQUID CONTAMINANTS IN
COMPRESSED AIR CAN CLOG THE SMALL PASSAGES THAT ARE A PART OF ALL PNEUMATIC
INSTRUMENTS, CAUSING LOSS OF ACCURACY OR EVEN COMPLETE FAILURE. MOISTURE IN THE
AIR, CONDENSING AND FREEZING, CAN CAUSE THE SAME PROBLEMS. CORROSIVE
CONTAMINANTS AND OIL IN COMPRESSED AIR CAN DAMAGE METAL AND PLASTIC INSTRUMENT
COMPONENTS, RESULTING IN UNRELIABLE OPERATION AND EXCESSIVE MAINTENANCE COSTS.
ISA STANDARD S7.3 RECOMMENDS THE FOLLOWING MINIMUM STANDARDS FOR
INSTRUMENT AIR:
MOISTURE. THE DEW POINT AT THE LINE PRESSURE SHOULD BE 10°C (18°F) BELOW THE
MINIMUM AMBIENT TEMPERATURE, BUT IN NO CASE SHOULD IT BE ABOVE 2°C (35°F).
PARTICLE SIZE. THE MAXIMUM PARTICLE SIZE IN THE AIR STREAM AT THE INSTRUMENT SHOULD
BE 3 (0.0001 IN).
OIL CONTENT. THE MAXIMUM OIL CONTENT SHOULD BE AS CLOSE TO ZERO AS POSSIBLE,
BUT UNDER NO CIRCUMSTANCES SHOULD IT EXCEED 1 PPM.
AIR SUPPLY PRESSURE
THE INSTRUMENT AIR SUPPLY PRESSURE MUST BE REGULATED TO MAINTAIN ACCURATE
OPERATION. WITH A TYPICAL PNEUMATIC TRANSMITTER, A CHANGE OF 5 PSI (33 KPA) IN SUPPLY
PRESSURE WILL CHANGE THE TRANSMITTER OUTPUT BY ABOUT 1%, CAUSING A MEASUREMENT
UNCERTAINTY. AS SHOWN IN FIG. 12, A SEPARATE FILTER REGULATOR IS USED FOR EACH FIELD
INSTRUMENT. THIS PROVIDES ONE FINAL STAGE OF FILTERING AND MOISTURE REMOVAL, AS
WELL AS A STABLE INSTRUMENT SUPPLY PRESSURE. IN A CONTROL PANEL, A SINGLE HIGH-
CAPACITY REGULATOR AND FILTER SET IS USED TO SUPPLY ALL INSTRUMENTS THROUGH AN AIR
SUPPLY HEADER. A SECOND REGULATOR AND FILTER SET IS USUALLY PROVIDED FOR STANDBY
SERVICE.
STEP RESPONSE OF PNEUMATIC TUBING
STEP RESPONSE TESTS FOR 500 FT (152.4 M) OF 1/4 -IN (6.35-MM) AND 3/8-IN (9.5 MM)
TUBING ARE SHOWN IN FIG. 14. THESE OUTPUT RESPONSES TO A STEP INPUT SHOW A DEAD
TIME, RELATED TO THE SONIC VELOCITY, AND A HIGH-ORDER COMPLETION CURVE
CHARACTERISTIC OF A DISTRIBUTED PARAMETER SYSTEM. THE PNEUMATIC RESISTANCE TO
FLOW AND THE PNEUMATIC CAPACITANCE (VOLUME) ARE DISTRIBUTED ALONG THE LENGTH OF
THE TRANSMISSION LINE.
FIG. 15: RESPONSE TIME FOR A 63.2% RESPONSE FOR A 8.4 TO 9.6 PSI STEP INPUT FOR OF
1/4 -IN (6.35-MM) AND 3/8-IN (9.5 MM) OD TUBING.
RECEIVER VOLUME
A LARGE RECEIVER VOLUME SERIOUSLY INCREASES THE RESPONSE TIME IN PNEUMATIC
TRANSMISSION. THE PROBLEM WITH A LARGE RECEIVER VOLUME IS THAT OF FILLING A LARGE
VOLUME THROUGH A LENGTH OF RESTRICTIVE TUBING, RATHER THAN THE TRANSMISSION
REQUIREMENT OF SIMPLY FILLING THE TUBING. TYPICAL INDICATORS, RECORDERS,
CONTROLLERS, AND VALVE POSITIONERS HAVE INLET VOLUMES ON THE ORDER OF THE 1.2-IN3
(0.02-L) STANDARD TEST VOLUME INDICATED IN FIG. 14. THE INLET VOLUME OF A CONTROL
VALVE (WITHOUT A VALVE POSITIONER) IS MUCH GREATER THAN THIS. WHERE FAST RESPONSE
IS IMPORTANT, A VALVE POSITIONER OR A BOOSTER RELAY SHOULD BE USED TO TERMINATE
THE TRANSMISSION LINE IN A SMALL VOLUME.
USE OF VOLUME BOOSTERS
MOST PROCESS CONTROL INSTRUMENTS HAVE A SUFFICIENT FLOW CAPACITY AND A
SUITABLY SMALL INLET VOLUME SO THAT NO SPECIAL PRECAUTIONS NEED BE TAKEN TO
MAINTAIN THE BEST POSSIBLE TRANSMISSION SYSTEM RESPONSE. FURTHERMORE, IN MANY
INSTALLATIONS OPTIMUM RESPONSE SPEED IS NOT NECESSARY TO MEET PROCESS OBJECTIVES,
AND THE EFFECTS OF A LOW FLOW CAPACITY OR A LARGE TERMINATION VOLUME ARE NOT
OBJECTIONABLE. IN APPLICATIONS WHERE FAST RESPONSE IS REQUIRED AND EQUIPMENT
LIMITATIONS CAUSE SLOW TRANSMISSION, VOLUME BOOSTER RELAYS CAN BE USED TO
IMPROVE RESPONSE.
FIG. 19: THE DERIVATIVE CAN BE ON THE INPUT OR OUTPUT OF THE CONTROLLER