DSEGenset®

DSE8920 SPECIFICATIONS

DC SUPPLY

7” Colour Load Share & Synchronising CONTINUOUS VOLTAGE RATING


5 V to 35 V Continuous

Control Module CRANKING DROPOUTS


Able to survive 0 V for 100 ms, providing
supply was at least 10 V before dropout
and supply recovers to 5 V. This is
achieved without the need for internal
batteries.LEDs and backlight will not be
maintained during cranking.

MAXIMUM OPERATING CURRENT


1.2 A at 12 V, 0.6 A at 24 V

Module can be MAXIMUM STANDBY CURRENT


0.7 A at 12 V, 0.35 A at 24 V
configured to
function as a DSE8910 CHARGE FAIL/EXCITATION RANGE
Auto Start 0 V to 35 V

Synchronising and GENERATOR & MAINS (UTILITY)


Load Sharing Control VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
Module. 26 V to 719 V AC (Ph to Ph)

FREQUENCY RANGE
3.5 Hz to 75 Hz

MAGNETIC PICKUP
VOLTAGE RANGE
KEY FEATURES • Independent earth fault protection KEY BENEFITS +/- 0.5 V to 70 V
• 7” optically bonded, sunlight • Breaker control via fascia buttons • Can be configured for use as a
readable colour TFT display • Fuel and start outputs configurable DSE8910 Auto Start Module FREQUENCY RANGE
(800 x 480) when using CAN • Real-time clock provides accurate 10,000 Hz (max)
• Comprehensive synchronising & • 8 configurable DC outputs event logging INPUTS
load sharing capabilities • 2 configurable volt-free relay • Ethernet communication, provides DIGITAL INPUTS A TO L
• Built in governor, AVR & CAN outputs built in advanced remote Negative switching
control • 4 configurable analogue/digital monitoring. ANALOGUE INPUTS A TO D
• Base load (kW export) control inputs • Increased input and output Configurable as:
• Positive & negative kVAr export • Built in sensors to support 0 V to 10 expansion capability via DSENet® Negative switching digital input
control 0 V to 10 V sensor
V & 4 mA to 20 mA • Licence-free PC software
4 mA to 20 mA sensor
• Mains (Utility) decoupling protection • 12 configurable digital inputs • IP65 rating (with supplied gasket) 0 Ω to 480 Ω sensor
• Mains (Utility) failure detection • Configurable 5 stage dummy load offers increased resistance to water
• Mains (Utility) power (kW, kV Ar, and load shedding outputs ingress OUTPUTS
OUTPUT A & B (FUEL & START)
kV A & pf) monitoring • CAN, MPU and alternator frequency • Advanced internal PLC editor 15 A DC at supply voltage
• RoCoF and vector shift protection speed sensing in one variant allows user configurable functions
• Mains (utility) kW export protection • Real time clock to meet complex application OUTPUTS C & D
8 A AC at ­­­250 V AC (Volt-free)
• Peak lopping & shaving functionality • Manual and automatic fuel pump requirements.
• Multiple display languages control AUXILIARY OUTPUTS E to L
• Five key menu navigation • Engine run-time scheduler EXPANSION DEVICES 2 A DC at supply voltage
• LCD alarm indication • Fuel usage monitor and low fuel • DSE124 CAN/MSC Extender
BUILT IN AVR GOVERNOR CONTROL
• DSENet® expansion compatibility level alarms • DSE2130 Input Expansion Module MINIMUM LOAD IMPEDANCE
• Data logging & trending facility • Simultaneous use of all • DSE2131 Ratio-metric Input 500 Ω
• Drag & drop advanced PLC editor communication ports Expansion Module Fully isolated
• Protections disable feature • Remote SCADA monitoring via • DSE2133 RTD & Thermo-couple GAIN VOLTAGE
• Fully configurable via PC using various DSE software applications Expansion Module 0 V to 10 V DC
USB, RS485 & Ethernet • MODBUS RTU & TCP IP support • DSE2152 Ratio-metric Output Fully isolated
communication with configurable MODBUS Expansion Module
OFFSET VOLTAGE
• Front panel configuration with pages • DSE2157 Output Expansion Module 0 V to 10 V DC
PIN protection • 3 configurable maintenance alarms • DSE2548 LED Expansion Fully isolated
• Power save mode • Compatible with a wide range of
DIMENSIONS
• 3 phase mains (utility) & generator CAN engines, including tier 4F, OVERALL
sensing and protection stage 5 engine support 310 mm x 162 mm x 51 mm
• Generator current and power • Uses DSE Configuration Suite PC 12.2” x 6.4” x 2.0”
monitoring (kW, kvar, kVA, pf) Software for simplified configuration
PANEL CUT-OUT
• kW and kvar overload alarms 282 mm x 136 mm
• Reverse power alarms 11.1” x 5.4”
• Over current protection
MAXIMUM PANEL THICKNESS
• Unbalanced load protection 8 mm
0.3”

STORAGE TEMPERATURE RANGE


RELATED MATERIALS
-40 °C to +85 °C
TITLE PART NO. -40 °F to +185 °F
DSE8920 Installation Instructions 053-248
DSE8920 Operator Manual 057-311 OPERATING TEMPERATURE RANGE
-30 °C to +70 °C
DSE8920 PC Configuration Suite Manual 057-303 -40 °F to +185 °F
DSE8910 Data Sheet 055-264

DEEP SEA ELECTRONICS LTD DEEP SEA ELECTRONICS INC


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL sales@deepseaelectronics.com WEBSITE www.deepseaelectronics.com EMAIL usasales@deepseaelectronics.com WEBSITE www.deepseaelectronics.com
Deep Sea Electronics Ltd maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457 055-264/11/19 (1)
DSEGenset®

DSE8920 ENVIRONMENTAL TESTING STANDARDS

7” Colour Load Share & Synchronising ELECTRO MAGNETIC COMPATIBILITY


BS EN 61000-6-2
Control Module EMC Generic Immunity Standard for the
Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the
Industrial Environment

ELECTRICAL SAFETY
The DSE8920 is a 7” full colour, Comprehensive communications are KEY LOAD SHARE FEATURES: BS EN 60950
Safety of Information Technology Equipment,
optically bonded synchronising also available via RS485 and Ethernet • Peak lopping/sharing (with including Electrical Business Equipment
Auto Mains (Utility) Failure Control for remote PC control and monitoring appropriate DSE mains (utility)
Module suitable for paralleling single and integration into building controller TEMPERATURE
BS EN 60068-2-1
gensets (diesel or gas) with a mains management systems • Manual voltage/frequency
Ab/Ae Cold Test -30 ºC
(utility) supply. The controller can be adjustment BS EN 60068-2-2
configured for use as a DSE8910 The event log will record 250 events • RoCoF and vector shift Bb/Be Dry Heat +70 ºC
Auto Start Control Module. When to facilitate easy maintenance, and an protection
VIBRATION
converted for use as a DSE8910 the extensive number of fixed and flexible • Mains (Utility) decoupling BS EN 60068-2-6
unit provides generator to generator monitoring, metering and protection • Mains (Utility) decoupling Ten sweeps in each of three major axes
load share functionality. features are included. test mode 5 Hz to 8 Hz at +/-7.5 mm, 8 Hz to 500 Hz
at 2 gn
• Direct governor and AVR control
Designed to synchronise a single Designed to offer increased built • Volts and frequency matching HUMIDITY
genset with a single mains (utility) in support for active sensors for • kW and kvar load sharing BS EN 60068-2-30
supply the DSE8920 will automatically 0 V to 10 V & 4 mA to 20 mA. Db Damp Heat Cyclic 20/55 ºC at 95% RH
48 Hours
control the change over from mains Comprehensive communication BS EN 60068-2-78
(utility) to generator supply or run the and system expansion options are Cab Damp Heat Static 40 ºC at 93% RH
generator in synchronisation with the available. 48 Hours
mains (utility), to provide no break, SHOCK
peak lopping and peak shaving power Using the DSE PC Configuration BS EN 60068-2-27
solutions. Suite software allows easy alteration Three shocks in each of three major axes
15 gn in 11 mS
of the operational sequences, timers
System alarms are annunciated on and alarms. With all communication DEGREES OF PROTECTION
the LCD screen (multiple language ports capable of being active at the PROVIDED BY ENCLOSURES
options available), illuminated LED same time, the DSE8920 is ideal for a BS EN 60529
IP65 - Front of module when installed into the
and audible sounder.­­ wide variety of demanding load share control panel with the supplied sealing gasket.
applications.

COMPREHENSIVE FEATURE LIST TO SUIT A WIDE


VARIETY OF LOAD SHARE APPLICATIONS

You might also like