AUTUMN 11 ISSUE 40
FIRE
PROTECTION
Requirements to avoid unnecessary risk
www.theiet.org/wm
Appendix 4 - Cables | 3
Appendix 4 of
Amendment 1 of
BS 7671:2008
By Geoff Cronshaw
Appendix 4 is an informative Installation methods and current ratings have been an inner skin of wood or
appendix within BS 7671. The reference methods calculated which cover all of wood-like material having a
appendix includes tabulated The number of installation the installations stated in the thermal conductance of at
current carrying capacities for methods described in Table Wiring Regulations, and are least 10 W/m2K. The
some of the most commonly 4A2 of appendix 4 has been called reference methods. conduit is fixed so as to be
used cables in the electrical increased to almost 80 in close to, but not necessarily
installation industry. Amendment 1 of the 17th All the individually numbered touching, the inner skin.
edition compared to just 20 in installation methods have a Heat from the cables is
These include single and the16th edition. Although this lettered reference method assumed to escape through
multicore 70 degree may appear to make things stated against them in Table the inner skin only. The
thermoplastic and 90 degree more complicated, the 4A2, except for flat twin and conduit can be metal or
thermosetting insulated cables appendix now embraces earth cables which have plastic.)
with copper conductors, 70 installation methods that are reference method numbers
degree thermoplastic insulated used but which were not 100 to 103. There are seven Reference method B –
and sheathed flat cable with previously accounted for, alphabetically lettered reference Enclosed in conduit on a
protective conductor (copper), including installation methods methods, that is A to G. wall or in trunking etc.
a range of armoured cables, in building voids, direct in
and mineral insulated cables. ground, in ducts in the ground, The lettered reference Reference method C –
Also a range of cables with and flat twin and earth cables methods broadly cover the Clipped direct.
aluminium conductors. in thermal insulation. following areas:
Reference method D –
Tables 4D1A to Tables 4J4A It is impractical to calculate Reference method A – Direct in the ground or in
contain the current carrying and publish current ratings for Enclosed in conduit in ducting in the ground.
capacities in amperes for the every installation method, thermally insulated walls
various types of cable. Each since many would result in the etc. (Note: The wall consists Reference method E –
table contains reference same current rating. Therefore of an outer weatherproof Multicore cables in free air
methods. a suitable (limited) number of skin, thermal insulation and or on perforated trays etc. E
Reference method F –
Single-core cable touching
Warning tape
in free air or on perforated
trays etc.
Reference method G –
Single-core cable spaced in
free air or on perforated
trays etc.
Sifted material
Effective current-carrying
capacity
The current-carrying capacity
of a cable corresponds to the
maximum current that can be
carried in specified conditions
without the conductors
exceeding the permissible
limit of steady-state Cable buried directly in
temperature for the type of
the ground Cable
insulation concerned.
Important: a rating factor Cf for semi-enclosed fuse to amendment 1 includes some
The values of current has to be applied where BS 3036 significant changes.
tabulated represent the the installation conditions
effective current-carrying differ from those for which Cg for grouping The current-carrying
capacity only where no rating values of current-carrying capacities tabulated for cables
factor is applicable. capacity are tabulated in Ci for thermal insulation in the ground are based upon
Tables 4D1A to Tables 4J4A a soil thermal resistivity of 2.5
Otherwise, the current of appendix 4. Cs for thermal resistivity of soil. K.m/W and are intended to be
carrying capacity corresponds applied to cables laid in and
to the tabulated value The various rating factors Cables direct in ground or in around buildings, i.e.
multiplied by the appropriate (some of which have been ducts in the ground disturbed soil.
factor or factors for ambient modified by amendment 1) It is worthwhile highlighting
temperature, grouping and are identified below. that the amendment 1 of BS In locations where the effective
thermal insulation as well as 7671:2008 (17th edition) soil thermal resistivity is higher
depth of burial and soil Ca for ambient temperature includes references for cables than 2.5 K.m/W, an
thermal resistivity, for buried buried in the ground appropriate reduction in
cables, as applicable. Where Cc for circuits buried in the (installation methods 70 to current-carrying capacity
harmonic currents are present ground 73). These were introduced in should be made. Rating
further factors may need to be the 17th edition when it was factors for soil thermal
applied. Cd for depth of burial published in 2008 but resistivities other than 2.5
Wiring Matters is a quarterly publication produced by IET Services Limited, a subsidiary of The Institution of Engineering and
Technology (IET), for the IET. Michael Faraday House, Six Hills Way, Stevenage, Herts, SG1 2AY, United Kingdom Tel: +44 (0)1438
313311 Fax: +44 (0)1438 313465. The Institution of Engineering and Technology is registered as a Charity in England & Wales (no
211014) and Scotland (no SC038698). The IET is not as a body responsible for the opinions expressed.
Advertising Sales D Smith +44 (0)1438 767224 daniellesmith@theiet.org | Editor G D Cronshaw +44 (0)1438 767384 gcronshaw@theiet.org |
Contributing Editors M Coles, R Townsend, P Bicheno | Sub editors Jim Hannah, Leanne Farnell | Design John Rooney, Jon Bonny, Dan Shadrake |
Production controller Nikki McEllin
©2011: The Institution of Engineering and Technology. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system,
or transmitted in any form or by any means without the permission in writing of the publisher. Copying of articles is not permitted except for personal
and internal use. Multiple copying of the content of this publication without permission is always illegal. Printed by Wyndeham Group.
Cooperating Organisations The Institution of Engineering & Technology acknowledges the contribution made by the following organisations in the prepara
tion of this publication: British Electrotechnical & Allied Manufacturers Association Ltd – P D Galbraith, M H Mullins | Department for Communities and
Local Government – I Drummond | Electrical Contractors Association – D Locke, S Burchell | City & Guilds of London Institute – H R Lovegrove | Electri
cal Contractors Association of Scotland SELECT – N McGuiness | Health & Safety Executive – K Morton | Electrical Safety Council | ERA Technology
Limited – M Coates, A Finney | Consultant - M. Al-Rufaie | Dept of Health - C Holme | British Cables Association – C Reed | Scottish Building Standards
Agency | Department for Business, Enterprise and Regulatory Reform | GAMBICA – M Hadley, A. Sedhev | Lighting Association – L Barling
ISSN 1749-978-X
of testing’s future.
Now offering
n 2-wire non-tripping loop testing
Infrastructure
TC
12th-13th October
11:15am Can cabling help support energy efficiency?
Rob Cardigan, Nexans
12:00pm Growth of IP solutions
London 2:15pm
Mark Marriage, COE Limited
Designing and implementing standards
compliant parallel optics networks within
budget – a roadmap
Alastair Waite,TE Connectivity
The UK’s leading event for the networking and platinum
show sponsors 3:00pm Contamination, inspection and cleaning of
data communications industry is returning for optical fibre connections
a fifth year in 2011. Martin Warne, Exfo
The Netcoms Show 2011 promises to be the
biggest and best yet, attracting exhibitors and Thursday 13th October
visitors from every industry sector.
10:30am Parallel optical systems – purchasing,
installing and caring for your system
The event will again be held at the
Rosemary McGlashon, 3M
prestigious Emirates Stadium, home to show sponsors
Conclusion
Please note this article is only
intended as a brief overview
of some of the changes
introduced into Appendix 4
by amendment 1 of the 17th
edition of the wiring
regulations.
Protection
against fire
By Geoff Cronshaw
It is perhaps worth noting that Prevention of Fire Risks Arising effect on 1 January 2012 livestock and property against
almost 130 years ago the first from Electric Lighting. includes requirements for fire caused by electrical
edition of the Wiring protection against thermal equipment, against burns and
Regulations, introduced in Amendment number 1 of the effects. The requirements are overheating and includes
1882, was called the Rules 17th edition published in July contained in Chapter 42 for precautions where particular
and Regulations for the this year and coming into the protection of persons, risks of fire exist.
Fig 1: Insulation
support box
PROTECTION AGAINST FIRE proximity to such equipment. lightning strikes, see the surface temperature sufficient
CAUSED BY ELECTRICAL The regulation gives examples IEC 62305 series to cause a risk of fire or
EQUIPMENT of causes of damage, injury or harmful effects to adjacent
Regulation 421 requires ignition including: Regulation 421.2 requires that materials.
persons, livestock and property the heat generated by fixed
to be protected against thermostats, temperature electrical equipment in normal be mounted on or within
damage or injury caused by limiters, seals of cable use should not be capable of materials that will withstand
heat or fire. penetrations and wiring causing a fire or harmful such temperatures
systems thermal effects to adjacent be screened by materials
Regulation 421 requires overcurrent fixed material. The regulation that will withstand such
measures to prevent electrical insulation faults and/or arcs offers three installation temperatures
equipment from presenting a causing interference methods for equipment which be mounted in a manner
fire hazard to materials in close harmonic currents in normal operation has a that permits safe heat
dissipation and gives
adequate clearance from
surrounding equipment or
materials. Example of an
insulation support box is
shown in Fig 1
be totally enclosed in
arc-resistant material, or
be screened by arc
resistant material, or
Fig 2: Semi-enclosed fuses be mounted so as to allow
safe extinction of the
w
f
Axis
equipment, a retention pit venting and/or automatic the walls have been
filled with pebbles or granite fire suppression or foam Fig 5 below, extracted from IEE constructed to contain any blast
chips (the net capacity of inlets and integration Guidance Note 4, shows an in the event of explosion.
the bund or retention pit with the automatic fire oil-filled transformer located in a
when filled with pebbles or detection and alarm system plant room, which incorporates PRECAUTIONS WHERE
chips should exceed the oil of the building, where many of the measures PARTICULAR RISKS OF
capacity of the equipment appropriate described above: the location is FIRE EXIST
by at least 10 per cent) ramped floors fitted with a fire door, the floor This section contains
providing a drainpit and use of an outdoor location falls to a central drainage point requirements for:
flame arrestor blast walls between large leading to a drainpit (grille just
provision of automatic fire items. visible to left of picture) and
Fig 5 An oil-filled
transformer
Conclusion
Please note this article is only
intended as a brief overview of
some of the requirements of
Chapter 42 of amendment 1 of
the 17th edition of the wiring
regulations. For more
information, refer to
Amendment 1 of BS
7671:2008.
Thanks
Thanks to TLC-Direct for Figs 2
& 3 www.tlc-direct.co.uk
No
application process is just ridiculously
easy and once registered we keep
the paperwork down to an absolute
minimum. Or the fact that we’ve
introduced a flexible direct debit
payment process that allows you to
Worrie
spread the cost of your assessment fee.
Perhaps its our assessors, all of which
are time-served electricians who offer a
fair and objective service. Whatever the
reasons are, be a bright spark and ease
the process of Part P with ELECSA.
www.elecsa.co.uk
This three day course has been updated to incorporate the 1st Amendment and
City & Guilds will launch the new qualification, 2382-12 (formerly 2382-10) in September 2011.
Be one of the first to get qualified to the 1st Amendment by booking on our updated course/exam in October.
T: 01438 767289
www.theiet.org/wiring-courses E: coursesreg@theiet.org
W: www.theiet.org/courses-wm
The Institution of Engineering and Technology is registered as a Charity in England & Wales (no 211014) and Scotland (no SC038698).
The IET, Michael Faraday House, Six Hills Way, Stevenage, SG1 2AY, UK
Earthing
By Geoff Cronshaw
Book your
basically the same way as for a damage or chemical
circuit protective conductor, deterioration or be damaged
except that Table 54.1 of BS by electro- dynamic effects
7671 must be applied to any
buried earthing conductor. For
a TN-C-S (PME) supply, it
produced by passing earth
fault current through it. If
mechanical protection is not
place today!
should be no smaller than the provided the minimum size is
London – 4 Oct – West Ham United FC, Upton Park
main bonding conductors. 4mm2 copper or equivalent. South – 25 Oct – Portsmouth FC, Fratton Park
East Anglia – 1 Nov – Newmarket Racecourse
Sizing of circuit protective BS 7671 provides two North West – 23 Nov – Wigan FC, DW Stadium
conductors methods for sizing protective Yorkshire – 24 Nov – York Racecourse
There are several factors which conductors including earthing Wales – 6 Dec – Cardiff City Football Stadium
may influence or determine conductors (see also Table Midlands – 24 Jan – Birmingham City FC, St. Andrew’s
Northern Ireland – 1 Feb – Everglades Hotel, Derry
the size required for a circuit 54.1). The easier method is to
South West – 14 Feb – National Marine Aquarium, Plymouth
protective conductor. A determine the protective
North East – 6 Mar – Sunderland FC, Stadium of Light
minimum cross-sectional area of conductor size from Table Scotland – 17 Apr – Livingston FC
2.5mm2 copper is required for 54.7 but this may produce a
Book online NOW at www.niceicdirect.com
any separate circuit protective larger size than is strictly
conductor, i.e. one which is necessary, since it employs a To find out more click or call
not part of a cable or formed by
a wiring enclosure or contained
simple relationship to the
cross-sectional area of the 0843 290 3468
techtalk@niceic.com
in such an enclosure. phase conductor(s).
VI-PD KIT
TYPE OF EARTHING
SYSTEMS, ADVANTAGES AND
DISADVANTAGES
Protective multiple earthing
(PME).
Such a supply system is
described in BS 7671 as
TN-C-S. The advantage of this
Fig 5 TT system system is that it provides an
effective and reliable method
of providing customers with an
earth connection. For example
the maximum Ze specified by
a distributor is 0.35 Ω for
TN-C-S supplies compared to
0.8 Ω for TN-S supplies.
Fig 6 No earth provided (TT system). Based on 25 mm2 tails and selection from Table 54.7. Note: An
isolator is not always installed by the electricity distributor. Manufacturers recommendations should
be sought with regards to connections to earth electrodes.
The second method involves a Regulation 543.1.3 states: which can flow through the
formula calculation. The The cross-sectional area, associated protective device,
formula is commonly referred where calculated, shall be not due account being taken of the
to as the ‘adiabatic equation’ less than the value determined current limiting effect of the
and is the same as that used by the following formula or circuit impedances and the
for short-circuit current shall be obtained by reference limiting capability (I2t) of that
calculations (see Regulation to BS 7454. protective device.
434.5.2). It assumes that no ___
heat is dissipated from the S = √ ___
I 2t Account shall be taken of the
protective conductor during k effect, on the resistance of
an earth fault and therefore where: circuit conductors, of their
errs on the safe side. Even so, temperature rise as a result of
application of the formula S is the nominal cross overcurrent - see Regulation
will in many instances result sectional area of the conductor 413-02-05.
in a protective conductor in mm2.
having a smaller csa than that of t is the operating time of the
the live conductors of the I is the value in amperes (rms. disconnecting device in
associated circuit. This is quite for a.c.) of fault current for a seconds corresponding to the
acceptable. fault of negligible impedance, fault current I amperes.
fixed building
distribution
pitch
socket-outlets
c.p.c. of
distribution cable
distribution board segregated from
pitch supply 30 mA
earthing RCDs
Fig 7 Typical site distribution for a PME supply, separation from PME earth at pitch supply point
fixed building
distribution
100 mA or pitch
greater RCD to socket-outlets
discriminate with
pitch socket-outlet
RCDs
main pitch
distribution board distribution board 30 mA
RCDs
Fig 8 Typical site distribution for a PME supply, separation from PME earth at main distribution board
ELEX2011
Professional Electrician
Sponsored by
DON’T
MISS
The Electricians’ Exhibition
Wiha TorqueVario VDE Megger raises the bar for multifunction testers
17th Edition Wiring Regulation
New from Megger, the MFT1700 series brings the convenience of
134.1.1 requires that manufac
2-wire non-trip loop testing to multifunction installation testers. Safety
turer’s instructions, including
rated at Category IV, the top of the range MFT1730 includes 3-pole
the proper torqueing of terminal
earth electrode testing, phase rotation indication and is rechargeable.
screws, should always be fol
lowed. Germany’s Wiha Tools
now offer a 1000V insulated
torque-setting screwdriver for For more information call
absolute assurance. The Wiha TorqueVario VDE offers safety to Megger on 01304 502 101 or
both the client and fitter for around £119 ex VAT. e-mail uksales@megger.com
www.wiha.com/england www.megger.com
Wiring Regulations Digital – Domestic Package for £99! Handheld Electronic Label Printer
The IET are offering Wiring Matters readers Brother’s P-touch range of durable handheld electronic label printers are perfect
the opportunity to purchase the Domestic for electrical installers who need to mark wiring and tools clearly and effectively.
Package of Wiring Regulations Digital Brother’s patented TZ tapes create durable labels that are scuff, fade, water,
for just £99 (inc VAT). The package temperature and chemical resistant. The label printers are designed to withstand
contains e-book versions of BS 7671, the tough on-site conditions and their compact
On-Site Guide, Guidance Notes 1 & 3 and design make them easy to store and transport.
the Electrician’s Guide to the Building Brother T: 0844 499 9444
Regulations. The price includes all 17th
Edition versions and Amendment No 1
versions of each book as they become
available.
Visit www.theiet.org/digital-regs and enter
the code WRDDP1 at checkout.
www.theiet.org/digital-regs www.brother.co.uk/electrician
For details on how to feature your product contact Danielle Smith on 01438 767224
Autumn 11 | IET Wiring Matters
26 | Your questions answered
Neutral Current (DNC). Values in guarantee the earth conductor for connection to distributor’s service cable into
excess of 100 mA to be subject to connection back to the source, the consumer’s earth terminal, the premises or to a separate
greater investigation with possible e.g. a low voltage overhead unless inappropriate for protective conductor of, for
recommendation for removal and supply, where there is the reasons of safety (Reg 24 of instance, an overhead supply.
replacement with a TT or isolated
likelihood of the earth wire ESQCR). Construction site,
TN-S system.
either becoming somehow farm or swimming pool Large consumers may have
Also, mines and quarries are disconnected or even stolen. installations might be one or more HV/LV
another area. A supply taken inappropriate unless additional transformers dedicated to their
to an underground shaft, or for A distributor also might not precautions are taken, such as installation and installed
use in the production side of a provide means of earthing for an additional earth electrode. adjacent to or within their
quarry, must have an earthing certain outdoor installations, premises. In such situations
system which is segregated e.g. a construction site TN-S system the usual form of system
from any system bonded to the temporary installation, leaving A TN-S system has the neutral earthing is TN-S. L
PME terminal. it to the consumer to make of the source of energy
suitable and safe connected with earth at one More information on earthing
Finally, because of the arrangements for which they point only, at or as near as is and bonding is available in IEE
practical difficulties in bonding are fully responsible. reasonably practicable to the Guidance Note 5 and 8. Also
all accessible extraneous source and the consumer’s more information on special
conductive-parts electricity The electricity distributor is earthing terminal is typically locations is available in IEE
distribution companies might required to make available his connected to the metallic Guidance Note 7.
not provide a PME earth to supply neutral or protective sheath or armour of the
construction sites and
agricultural and horticultural
installations.
In addition, Regulation
704.411.3.1 does not allow a
PME earthing facility to be
used as a means of earthing
unless all extraneous
conductive-parts are reliably
connected to the main
earthing terminal in
accordance with Regulation
411.3.1.2.
Furthermore, Regulation
705.415.2.1 includes a note
which states: Unless a metal
grid is laid in the floor, the use
of a PME earthing facility as a
means of earthing for the
electrical installation is not
recommended.
TT system
With TT, the consumer must
provide his or her own
connection to earth, i.e. by
installing a suitable earth
electrode local to the
installation.
Discover a whole
new world of
lighting at LuxLive
n The latest innovations including
new-generation LEDs
n Market-leading exhibitors including
Philips, Osram and GE
n Free to attend seminars including speakers from
John Lewis Partnership, Nando’s and the Carbon Trust
n Dedicated EcoLight conference helping to transform lighting
estates and reduce energy bills
LuxLive | Earls Court | London | 9-10 November Contact: T 01905 724734 www.luxlive.co.uk @Lux_magazine for #LuxLive updates
Order Form
Ordering information
Quantity Book No. Title/Author Price (£)
Subtotal
- Member discount **
+ Postage/Handling*
total
inFormation security:
Payment methods
Please do not submit your form by email. The IET
takes the security of your personal details and by cheque made payable to the Institution of Engineering and Technology
credit/debit card information very seriously and will
not process email transactions. by credit/debit card
* Postage/Handling: postage within the UK is £3.50 Visa Mastercard American Express Maestro Issue No:_____________
for any number of titles. Outside UK (Europe) add
£5.00 for first title and £2.00 for each additional Valid from: Expiry date: Card security code:
book. Rest of World add £7.50 for the first book and
£2.00 for each additional book. Books will be sent Card No: (3 or 4 digits on reverse of card)
via airmail. Courier rates are available on request,
please call +44 (0)1438 767328 or email sales@
theiet.org for rates Signature_______________________________________________Date_____________________
(Orders not valid unless signed)
data protection
The information that you provide to the IET will be
used to ensure we provide you with products and Country:
The Institution of Engineering and Technology is registered as a charity in England & Wales (no 211014) and Scotland (no SCO38698)
Order for £20.40 *
Order now at www.theiet.org/onsite-wm * Offer available for the 1st copy only pre-ordered directly
from the IET before 18th September 2011. Not to be
used in conjunction with any other offers or discounts.
The Institution of Engineering and Technology (the IET) is registered as a Charity in England and Wales (No. 211014) and Scotland (No. SC038698). Michael Faraday House, Six Hills Way, Stevenage, SG1 2AY, UK.
Wiring Regulations Digital e-books from the IET offer a wealth of functionality to make
using the IET Wiring Regulations a quick and simple process. Instantly search for any
term or keyword across the range of e-books, follow links within and between books and
keep track of your work by highlighting sections of text and making your own notes.
The Domestic Package of Wiring Regulations Digital includes the following titles,
with both the 17th Edition AND 1st Amendment versions included*:
■ BS 7671
■ The On-Site Guide
■ The Electrician’s Guide to the Building Regulations
■ Guidance Note 1
■ Guidance Note 3
*You will initially receive all of the 17th Edition versions and any 1st Amendment titles published to date. Your package will be updated for free with the additional 1st Amendment versions of these books upon publication.
The Institution of Engineering and Technology is registered as a Charity in England & Wales (no 211014) and Scotland (no SCO38698). Michael Faraday House, Six Hills Way, Stevenage, SG1 2AY.
Electrical Installation Condition Report | 31
Periodic
Inspection and
the Electrical Why change the ‘Periodic
Installation
in a clear and consistent
Inspection Report’? manner. A project team was
It is worth stating that an set-up to propose
electrical installation should developments to the existing
Condition Report
still be subjected to periodic periodic inspection report. The
inspection and testing as result of the project team was
recommended in Regulation issued as part of the
135.1. This states that every Amendment 1 draft for public
electrical installation is comment (DPC) stage. Over
subjected to periodic 500 comments were received
inspection and testing in on this topic alone from a
BS 7671:2008 Amendment 1 was published on 1 accordance with Chapter 62. number of areas of the
July. One of the amendments is to the reporting of The reporting of the inspection industry. After reviewing these
a periodic inspection for an electrical installation and testing is the key change. comments the Committee
As part of the Amendment 1 eventually decided on the
where the previous ‘Periodic Inspection Report’ development programme the solution now published as part
has been changed to ‘Electrical Installation technical committee of Amendment 1.
Condition Report’. This article will answer some responsible for BS 7671
JPEL/64 decided that periodic When should the new condition
typical questions and describe some of the key inspection and testing was not report be used?
aspects of what has been amended. being carried out and reported Although Amendment 1 was
published on 1 July this does
By Paul Bicheno not mean that engineers who
provide reports associated with
periodic inspection and testing
need to start using the new
electrical installation condition
report straight away. The
introduction to Amendment 1
states that it comes into effect
on 1 January 2012 so this is
when the new report will be
need to be used. Until that
time the existing periodic
inspection report can be used.
schedule of test results. All of premises where the supply is dedicated schedule is It is worth clarifying that the
these are included as model rated no more than 100 A provided. This will need to be report is intended to report on
forms in Appendix 6 of BS single-phase or three-phase. agreed between the client and the condition of an existing
7671:2008(2011). However, a Originally the intention was to person doing the work as to installation and not to certify
key change is to the schedule have a series of schedules how the inspection aspect is an installation. The person
of inspections that is to be aimed at larger installations to documented. The previous carrying out the inspection and
used when carrying out a complement this schedule; ‘Schedule of Inspections’ testing is looking to determine
periodic inspection. Previously however, the comments from model form remains but is to if there is any damage,
the schedule of inspections industry during the DPC period be used only when new deterioration, defects,
was generic and used for both voiced concerns over the installation work is being dangerous conditions and any
the periodic inspection report amount of paperwork that certified and not as part of a non-compliance with the
and electrical installation could be generated if this periodic inspection. Finally, the requirements of the
certificate. Now a condition approach was adopted. schedule of test results Regulations which may give
report will need to have a Therefore, the decision was remains applicable to both rise to danger. Only these
schedule of inspections taken to only have the installation work and periodic aspects should be recorded on
relevant to the periodic domestic and similar schedule. inspection and testing and the report and not a full list of
inspection work carried out. For larger installation thus would be included as part non-compliance with the
Included in Appendix 6 is an arrangements a list of example of the report. The structure of Regulations. Installations built
inspection schedule for items requiring inspection has an electrical installation to an earlier edition are not
domestic and similar premises been included in Appendix 6. condition report applicable to likely to fully comply with the
with a supply rated up to 100 The intention is for this list to domestic or similar premises is current edition. However, this
A. This particular schedule is be used as the basis of the shown in Fig 1. does not mean that the
aimed at smaller electrical inspection for a larger installation is unsafe for
installations such as domestic installation arrangement. The What is the intention of the continued use. Also the report
and small commercial type key difference being no condition report? should not state how any
1 2
Form 6 Form No: …………../6 Form 6 Form No: …………../6
ELECTRICAL INSTALLATION CONDITION REPORT
SECTION I. SUPPLY CHARACTERISTICS AND EARTHING ARRANGEMENTS
SECTION A. DETAILS OF THE CLIENT / PERSON ORDERING THE REPORT Earthing Number and Type of Live Nature of Supply Parameters Supply Protective Device
Name .......................................................................................................................................................................................................................... arrangements Conductors
Address ....................................................................................................................................................................................................................... TN-C a.c. d.c. Nominal voltage, U / U0(1) .......................... V BS (EN) ..............................
........................................................................................................................................................................................ Post Code: ........................ TN-S 1-phase, 2-wire 2-wire Nominal frequency, f(1) ............................. Hz Type ...................................
TN-C-S 1-phase, 3-wire 3-wire Prospective fault current, Ipf(2) .................. kA
TT 2 phase, 3-wire Other External loop impedance, Ze(2) ................ Rated current .....................A
SECTION B. REASON FOR PRODUCING THIS REPORT ..................................................................................................................................... IT 3 phase, 3-wire Note: (1) by enquiry
...................................................................................................................................................................................................................................... 3 phase, 4-wire
similar premises
SECTION D. EXTENT AND LIMITATIONS OF INSPECTION AND TESTING Main protective bonding
Material ……......................... csa ........................mm2 Connection / continuity verified
Extent of the electrical installation covered by this report conductors
...................................................................................................................................................................................................................................... To incoming water service To incoming gas service To incoming oil service To structural steel
...................................................................................................................................................................................................................................... To lightning protection To other incoming service(s) Specify ..........................................................................................................
Agreed limitations including the reasons (see Regulation 634.2) .............................................................................................................................. Main Switch / Switch-Fuse / Circuit-Breaker / RCD
...................................................................................................................................................................................................................................... Location ...................................................... Current rating ..................................... A If RCD main switch
...................................................................... Fuse / device rating or setting .......... A Rated residual operating current (In) .....................mA
Agreed with: ................................................................................................................................................................................................................
BS(EN) ........................................................ Voltage rating ..................................... V Rated time delay .....................................................ms
Operational limitations including the reasons (see page no..............) .......................................................................................................................
No of poles .................................................. Measured operating time(at In) ..............................ms
......................................................................................................................................................................................................................................
The inspection and testing detailed in this report and accompanying schedules have been carried out in accordance with BS 7671: 2008 (IET SECTION K. OBSERVATIONS
Wiring Regulations) as amended to ………………………………….. Referring to the attached schedules of inspection and test results, and subject to the limitations specified at the Extent and limitations of inspection
It should be noted that cables concealed within trunking and conduits, under floors, in roof spaces, and generally within the fabric of the building or and testing section
underground, have not been inspected unless specifically agreed between the client and inspector prior to the inspection. No remedial action is required The following observations are made (see below):
SECTION E. SUMMARY OF THE CONDITION OF THE INSTALLATION OBSERVATION(S) CLASSIFICATION FURTHER
CODE INVESTIGATION
General condition of the installation (in terms of electrical safety) ............................................................................................................................. REQUIRED
...................................................................................................................................................................................................................................... (YES / NO)
...................................................................................................................................................................................................................................... ............................................................................................................................................................... .............................. ...............................
Overall assessment of the installation in terms of its suitability for continued use
............................................................................................................................................................... .............................. ...............................
SATISFACTORY / UNSATISFACTORY* (Delete as appropriate)
*An unsatisfactory assessment indicates that dangerous (code C1) and/or potentially dangerous (code C2) conditions have been identified. ............................................................................................................................................................... .............................. ...............................
SECTION F. RECOMMENDATIONS ............................................................................................................................................................... .............................. ...............................
Where the overall assessment of the suitability of the installation for continued use above is stated as UNSATISFACTORY, I / we recommend that ............................................................................................................................................................... .............................. ...............................
any observations classified as ‘Danger present’ (code C1) or ‘Potentially dangerous’ (code C2) are acted upon as a matter of urgency. ............................................................................................................................................................... .............................. ...............................
Investigation without delay is recommended for observations identified as ‘further investigation required’. ............................................................................................................................................................... .............................. ...............................
Observations classified as ‘Improvement recommended’ (code C3) should be given due consideration. ............................................................................................................................................................... .............................. ...............................
............................................................................................................................................................... .............................. ...............................
Subject to the necessary remedial action being taken, I / we recommend that the installation is further inspected and tested by …………..…(date)
............................................................................................................................................................... .............................. ...............................
SECTION G. DECLARATION
I/We, being the person(s) responsible for the inspection and testing of the electrical installation (as indicated by my/our signatures ............................................................................................................................................................... .............................. ...............................
below), particulars of which are described above, having exercised reasonable skill and care when carrying out the inspection and ............................................................................................................................................................... .............................. ...............................
testing, hereby declare that the information in this report, including the observations and the attached schedules, provides an accurate ............................................................................................................................................................... .............................. ...............................
assessment of the condition of the electrical installation taking into account the stated extent and limitations in section D of this report. ............................................................................................................................................................... .............................. ...............................
Inspected and tested by: Report authorised for issue by: ............................................................................................................................................................... .............................. ...............................
Name (Capitals) ............................................................................... Name (Capitals) .............................................................................. ............................................................................................................................................................... .............................. ...............................
Signature ......................................................................................... Signature ......................................................................................... ............................................................................................................................................................... .............................. ...............................
For/on behalf of ............................................................................... For/on behalf of ............................................................................... ............................................................................................................................................................... .............................. ...............................
Position ............................................................................................ Position ............................................................................................ ............................................................................................................................................................... .............................. ...............................
Address ............................................................................................ Address ........................................................................................... ............................................................................................................................................................... .............................. ...............................
Post code ………………… Date ............................. Post code ………………… Date ............................ One of the following codes, as appropriate, has been allocated to each of the observations made above to indicate to the person(s) responsible for
SECTION H. SCHEDULE(S) the installation the degree of urgency for remedial action.
…………schedule(s) of inspection and ……...schedule(s) of test results are attached. C1 – Danger present. Risk of injury. Immediate remedial action required
The attached schedule(s) are part of this document and this report is valid only when they are attached to it. C2 – Potentially dangerous - urgent remedial action required
C3 – Improvement recommended
Page 2 of …
Page 1 of …
3 4
Form 7 Form No: …………../7 Form 7 Form No: …………../7
CONDITION REPORT INSPECTION SCHEDULE FOR Acceptable Unacceptable State C1 Improvement
DOMESTIC AND SIMILAR PREMISES WITH UP TO 100 A SUPPLY
OUTCOMES
condition condition or C2 recommended
State C3 Not verified N/V Limitation LIM Not applicable N/A
Note: This form is suitable for many types of smaller installation not exclusively domestic. OUTCOME Further
ITEM (Use codes above. Provide additional investigation
DESCRIPTION comment where appropriate. required?
NO C1, C2 and C3 coded items to be recorded (Y or N)
Acceptable Unacceptable State C1 Improvement in Section K of the Condition Report)
OUTCOMES
condition condition or C2 recommended
State C3 Not verified N/V Limitation LIM Not applicable N/A
5.0 FINAL CIRCUITS
OUTCOME
(Use codes above. Provide additional
Further 5.1 Identification of conductors (514.3.1)
ITEM investigation
5.2 Cables correctly supported throughout their run (522.8.5)
DESCRIPTION comment where appropriate. required?
NO C1, C2 and C3 coded items to be recorded (Y or N) 5.3 Condition of insulation of live parts (416.1)
in Section K of the Condition Report)
5.4 Non-sheathed cables protected by enclosure in conduit, ducting or trunking (521.10.1)
To include the integrity of conduit and trunking systems (metallic and plastic)
1.0 DISTRIBUTOR’S / SUPPLY INTAKE EQUIPMENT
5.5 Adequacy of cables for current-carrying capacity with regard for the type and nature of
1.1 Service cable condition
installation (Section 523)
1.2 Condition of service head 5.6 Coordination between conductors and overload protective devices (433.1; 533.2.1)
1.3 Condition of tails - Distributor 5.7 Adequacy of protective devices: type and rated current for fault protection (411.3)
1.4 Condition of tails - Consumer 5.8 Presence and adequacy of circuit protective conductors (411.3.1.1; 543.1)
1.5 Condition of metering equipment 5.9 Wiring system(s) appropriate for the type and nature of the installation and external influences
+
1.6 Condition of isolator (where present) (Section 522)
5.10 Concealed cables installed in prescribed zones (see Section D. Extent and limitations)
2.0 PRESENCE OF ADEQUATE ARRANGEMENTS FOR OTHER SOURCES SUCH AS (522.6.101)
MICROGENERATORS (551.6; 551.7) 5.11 Concealed cables incorporating earthed armour or sheath, or run within earthed wiring system,
or otherwise protected against mechanical damage from nails, screws and the like (see Section
3.0 EARTHING / BONDING ARRANGEMENTS (411.3; Chap 54) D. Extent and limitations) (522.6.101; 522.6.103)
3.1 Presence and condition of distributor’s earthing arrangement (542.1.2.1; 542.1.2.2) 5.12 Provision of additional protection by RCD not exceeding 30 mA:
3.2 Presence and condition of earth electrode connection where applicable (542.1.2.3) for all socket-outlets of rating 20 A or less provided for use by ordinary persons unless an
exception is permitted (411.3.3)
3.3 Provision of earthing / bonding labels at all appropriate locations (514.13)
for supply to mobile equipment not exceeding 32 A rating for use outdoors (411.3.3)
3.4 Confirmation of earthing conductor size (542.3; 543.1.1)
for cables concealed in walls or partitions (522.6.102; 522.6.103)
3.5 Accessibility and condition of earthing conductor at MET (543.3.2)
5.13 Provision of fire barriers, sealing arrangements and protection against thermal effects (Section 527)
3.6 Confirmation of main protective bonding conductor sizes (544.1)
5.14 Band II cables segregated / separated from Band I cables (528.1)
3.7 Condition and accessibility of main protective bonding conductor connections (543.3.2; 544.1.2)
5.15 Cables segregated / separated from communications cabling (528.2)
3.8 Accessibility and condition of all protective bonding connections (543.3.2)
5.16 Cables segregated / separated from non-electrical services (528.3)
5.17 Termination of cables at enclosures – indicate extent of sampling in Section D of the report
4.0 CONSUMER UNIT(S) / DISTRIBUTION BOARD(S)
(Section 526)
4.1 Adequacy of working space / accessibility to consumer unit / distribution board (132.12; 513.1) Connections soundly made and under no undue strain (526.6)
4.2 Security of fixing (134.1.1) No basic insulation of a conductor visible outside enclosure (526.8)
4.3 Condition of enclosure(s) in terms of IP rating etc (416.2)
Connections of live conductors adequately enclosed (526.5)
4.4 Condition of enclosure(s) in terms of fire rating etc (526.5)
Adequately connected at point of entry to enclosure (glands, bushes etc.) (522.8.5)
4.5 Enclosure not damaged/deteriorated so as to impair safety (621.2(iii))
5.18 Condition of accessories including socket-outlets, switches and joint boxes (621.2(iii))
4.6 Presence of main linked switch (as required by 537.1.4)
5.19 Suitability of accessories for external influences (512.2)
4.7 Operation of main switch (functional check) (612.13.2)
4.8 Manual operation of circuit-breakers and RCDs to prove disconnection (612.13.2)
6.0 LOCATION(S) CONTAINING A BATH OR SHOWER
4.9 Correct identification of circuit details and protective devices (514.8.1; 514.9.1)
6.1 Additional protection for all low voltage (LV) circuits by RCD not exceeding 30 mA (701.411.3.3)
4.10 Presence of RCD quarterly test notice at or near consumer unit / distribution board (514.12.2)
6.2 Where used as a protective measure, requirements for SELV or PELV met (701.414.4.5)
4.11 Presence of non-standard (mixed) cable colour warning notice at or near consumer unit /
6.3 Shaver sockets comply with BS EN 61558-2-5 formerly BS 3535 (701.512.3)
distribution board (514.14)
4.12 Presence of alternative supply warning notice at or near consumer unit / distribution board (514.15) 6.4 Presence of supplementary bonding conductors, unless not required by BS 7671:2008
(701.415.2)
4.13 Presence of other required labelling (please specify) (Section 514)
6.5 Low voltage (e.g. 230 volt) socket-outlets sited at least 3 m from zone 1 (701.512.3)
4.14 Examination of protective device(s) and base(s); correct type and rating (no signs of
unacceptable thermal damage, arcing or overheating) (421.1.3) 6.6 Suitability of equipment for external influences for installed location in terms of IP rating
4.15 Single-pole protective devices in line conductor only (132.14.1; 530.3.2) (701.512.2)
6.7 Suitability of equipment for installation in a particular zone (701.512.3)
4.16 Protection against mechanical damage where cables enter consumer unit / distribution board
(522.8.1; 522.8.11) 6.8 Suitability of current-using equipment for particular position within the location (701.55)
4.17 Protection against electromagnetic effects where cables enter consumer unit / distribution board /
enclosures (521.5.1) 7.0 OTHER PART 7 SPECIAL INSTALLATIONS OR LOCATIONS
4.18 RCD(s) provided for fault protection – includes RCBOs (411.4.9; 411.5.2; 531.2) 7.1 List all other special installations or locations present, if any. (Record separately the results of
4.19 RCD(s) provided for additional protection - includes RCBOs (411.3.3; 415.1) particular inspections applied.)
Inspected by:
Name (Capitals) ...................................................... Signature ......................................................... Date ........................
Page … of …
Page … of …
5
Form 4 Form No: …………../4
+
Circuit number
capacity (kA)
Test button /
functionality
Live (mm2)
(R1 + R2) *
Reference
rn (neutral)
cpc (mm2)
Circuit Description
rating (A)
Live-Live
breaking
BS (EN)
Method
r1 (line)
r2 (cpc)
@ 5In
Live-E
@ In
type
R2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
* Where there are no spurs connected to a ring final circuit this value is also the (R1 + R2) of the circuit.
defects should be rectified e.g. published domestic and included as part of the assessment to the client to
consumer unit should be similar condition report schedule for easy reference. clarify any dangers,
replaced. This information inspection schedule (see Fig The person carrying out the improvements or limitations
should be provided separately 2) has been designed so that a work should also record an and will aid any future
if requested by the client. number of specific items associated comment to inspection of the installation.
requiring inspection are listed reinforce the reason for a For each item there will also be
Domestic and similar condition that are likely to be relevant to particular outcome. This a requirement to record if any
report inspection schedule an installation of this type and approach is intended to further investigation is
A main part of the work was to size. Any relevant regulation provide more detail on the recommended as it is
produce an inspection references are provided for an condition of a number of recognised that various factors
schedule that would be a item to assist the inspector. aspects of an installation and could inhibit a complete
benefit to the person carrying The requirement is for an is one of the key differences inspection at the time it is
out the inspection to enable outcome based on the compared to the previous carried out or the inspector
them to inspect an installation inspector’s assessment to be report where only a summary has not verified an item but
in a structured and consistent recorded against each item. list of observations and feels that further assessment is
way and for the client to better These are listed in Table 1 recommendations were needed to confirm the safety
understand the result of the along with a description of recorded. This has the benefit aspect. The second key
inspection. The format of the their meaning but are also of providing a detailed difference is to do with the
classification codes to highlight for the inspector included in Form 7 Form No: …………../7
CONDITION REPORT INSPECTION SCHEDULE FOR
an unacceptable condition or Appendix 6 should have a DOMESTIC AND SIMILAR PREMISES WITH UP TO 100 A SUPPLY
Note: This form is suitable for many types of smaller installation not exclusively domestic.
improvement. This is now statement highlighting that any New classification outcomes
limited to C1 (danger present older installations designed
Acceptable Unacceptable State C1 Improvement
OUTCOMES
condition condition or C2 recommended
State C3 Not verified N/V Limitation LIM Not applicable N/A
OUTCOME
– immediate remedial action prior to BS 7671:2008 may not
Further
ITEM (Use codes above. Provide additional investigation
DESCRIPTION comment where appropriate. required?
NO C1, C2 and C3 coded items to be recorded (Y or N)
required), C2 (potentially have been provided with RCDs Grouped inspection items in Section K of the Condition Report)
The previous C3 code (further classification code as a 2.0 PRESENCE OF ADEQUATE ARRANGEMENTS FOR OTHER SOURCES SUCH AS
MICROGENERATORS (551.6; 551.7)
investigation) is now covered minimum in relation to item 3.0 EARTHING / BONDING ARRANGEMENTS (411.3; Chap 54)
Regulation references provided
by an individual entry for each 5.12 of the schedule. This is to 3.1
3.2
Presence and condition of distributor’s earthing arrangement (542.1.2.1; 542.1.2.2)
Presence and condition of earth electrode connection where applicable (542.1.2.3)
3.3 Provision of earthing / bonding labels at all appropriate locations (514.13)
item and summarized on the highlight that the installation 3.4 Confirmation of earthing conductor size (542.3; 543.1.1)
3.5 Accessibility and condition of earthing conductor at MET (543.3.2)
observations section K on the could be improved in this 3.6
3.7
Confirmation of main protective bonding conductor sizes (544.1)
Condition and accessibility of main protective bonding conductor connections (543.3.2; 544.1.2)
report. The previous C4 code respect. 3.8 Accessibility and condition of all protective bonding connections (543.3.2)
classification code should be cfm. They are also provided by Outcome entered against Record if further
recorded in the summary of other organisations. However each item plus any additional investigation is
observations section K on the they are model forms and may comments required
Page … of …
Re-Subscribe Today
Re-subscribe to keep receiving free
copies of Wiring Matters Magazine and
stay ahead of developments in BS 7671.
Re-subscribing is easy and there are two ways to do it:
Re-subscribe now:
www.subscription.co.uk/cc/wm/I311
*If you have destroyed the magazine wrapper and need a copy of your unique reference number, please send an
email to controlled1@subscription.co.uk with your full name and address details.
ERCIAL
COMM
ST RIA L
IND U
t NA P IT
harge a
extra c
...no
To join NAPIT or for more information call: 0800 954 0438
info@napit.org.uk www.napit.org.uk