E-LINE KO-II
Plug-in Busbar Distribution System
160...800A
E-LINE DABLINE
Underfloor Busbar Systems
63-80 A
Introduction 2 E L E K T R İ K
Distribution & Horizontal Applications 4
Riser & Vertical Applications 5
Technical Characteristics 6
Order Code System 10
Standard Straight Length 11
Elbow Lengths 12
Standard Components 16
Expansion Modules 17
End Closer 18
Panel Connections 19
Panel Modules / Flexibles 22
Panel Modules Technical Table 23
Transformer Modules 25
Transformer Modules Technical Table 29
Vertical & Horizontal Support Applications 30
Suspension Components 31
Measuring a Special Length 35
Horizontal Mounting Application 36
Vertical Mounting Application 37
Cast Resin Application 38
EC Certficate of Conformity 40
Certificates 41
Product Overview 42
ELINECR
Introduction
Example of a Traditional
Cable System
1m
2
ELINECR
Technical Features
High IP Rating
The body of the E-Line CR busbar is formed using Short Circuit Withstand
DURACOMP a composite material of epoxy resin and pure The structure of the E-Line
silicon, which gives protection against external elements as CR has a high mechanical
listed above (page 2). strength, a very high short
circuit withstand
characteristic, and
extreme external thermal
PE L3 L2 L1 N resistance.
Diagram 1 Diagram 2
3
ELINECR
Distribution & Horizontal Applications
When using the E-Line CR to create an electrical Utilisation Factor (Diversity)
distribution system, the following criteria should be
taken into consideration. The utilisation factor (a) depends on the type and number of
loads. Most are 0.7 or less. Intense Lighting and Motor Fed
The Power of the load to be connected to the system Lines "0,6" is quite difficult to rise above. Even at automobile
and their locations. welding plants it could fall down to "0,30". With only one
Utilisation factor (diversity) assay, single and large load can it go up to "1".
Power and short circuit currents of transformers,
System coordination with other distribution systems Voltage Drop
(heat, steam, water, etc.), All the required values for voltage Drop Calculations,
Determining a route of the E-Line CR on layout of the formulas, basic calculations for simple cases the tables are
designed system, given on pages 6-9. Further support can be obtained from
Determination of the types of supports according our Design Department.
to plan,
If necessary, the system can be integrated with E-Line
KX busbar system.
Short Circuit Values
Sample Project Design (For Horizontal Application) Short circuit test values are given on the tables on pages 7
and 8. The short circuit values high-light the high short circuit
withstand characteristic of the E-Line CR.
Rated Current
The rating of the busbar current required is
calculated using the formula shown below.
54 m. (18 Pcs x 3 m.)
CRA 20504
P.a
IB =
Ö3.U.cos j
IB = Operation current (A)
P = Total power load
a = Utilisation factor (diversity)
U = Supply voltage (V)
The busbar current rating is chosen as being equal to,
or greater than the calculated current (IB).
After calculating the volt drop, if the current rating is
not adequate, then a higher rating should be chosen.
Component List
4
ELINECR
Riser & Vertical Applications
The details on this page briefly explain the information necessary a= ......
for designing the vertical installation project.
PE L3 L2 L1 N PE L3 L2 L1 N
h= ......
I14
er
a rri a= ...... 9th Floor
eB
Fir
h= ......
I13
h= ......
150 150
I12
h= ......
h=Floor Height, from Floor to Floor (cm)
35 I11
a= ...... 6th Floor
350
h= ......
I10
h= ......
I9
I8
a= ...... 4th Floor
h= ......
I7
I6
a= ...... 3rd Floor
h= ......
I5
or
Th
ick I4
ne
ss
(cm a= ...... 1st Floor
)
h= ......
I3
Pre-Project Design and cost Analysis
a= ...... Ground Floor
Before design and cost analysis can be made, please submit the n
h= ......
5
ELINECRA
Technical Characteristics
Aluminium Conductor (Al)
Rated Current In A 630 800 1000 1250 1600 2000 2500 2250 2500 3000 3200 3600 4000 5000 L3 L2 L1 N PE L3 L2 L1 N
Busbar Code 06 08 10 12 16 20 25 23 27 30 33 36 40 50
Standards IEC 61439-6:2012 Ed.1 ; IEC 61439-1 Ed.2:2011, TS EN 61439-1: 2011
Rated Isolation Voltage Ui V 1000 L3 L2 L1 N PE L3 L2 L1 N
6 7
ELINECRC
Technical Characteristics
Copper Conductor (Cu)
Rated Current In A 800 1000 1250 1600 2000 2500 3000 3200 3600 4000 5000 6300 L3 L2 L1 N PE L3 L2 L1 N
Busbar Code 08 10 12 16 20 25 30 32 36 40 50 63
Standards IEC 61439-6:2012 Ed.1 ; IEC 61439-1 Ed.2:2011, TS EN 61439-1: 2011
Rated Isolation Voltage Ui V 1000 L3 L2 L1 N PE L3 L2 L1 N
8 9
ELINECR
BUSBAR
Order Code System CONDUCTOR MATERIAL
BUSBAR CODE
PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILISATION TYPE / FEEDER
COMPONENT
CR C 16 8 04 B TR40
Busbar Type
Upwards Elbow U
Downwards Elbow D
CRA - Al CRC - Cu Conductor Left Elbow L
Cross
Conductor Conductor Section Right Elbow R
Rated Busbar Rated Busbar
Current Code Current Code Left Horizontal Offset LH
630 06 800 08 6x40 Right Horizontal Offset RH
800 08 1000 10 6x55 Upwards Horizontal Offset UV
1000 10 1250 12 6x80 Downwards Horizontal Offset DV
1250 12 1600 16 6x110 BUSBAR CODE Upwards Left Combined Offset KUL
1600 16 2000 20 6x160 Upwards Left Combined Offset KUR
2000 20 2500 25 6x200 Downwards Left Combined Offset KDL
2500 25 - - 6x250 Downwards Right Combined Offset KDR
23 30 2(6x110)
Left Upwards Combined Offset KLU
2250 3000
Right Upwards Combined Offset KRU
2500 27 3200 32 2(6x125)
Left Downwards Combined Offset KLD
- - 3600 36 2(6x140)
Right Downwards Combined Offset KRD
3000 30 4000 40 2(6x160)
3200 33 - - 2(6x170)
End Closure S
3600 36 5000 50 2(6x200)
Reduction RD
4000 40 - - 2(6x250)
5000 50 6300 63 3(6x200) Tee Module T
Component
Horizontal Expansion YDT
Vertical Expansion DDT
Phase Transposition Module FDM
PROTECTION DEGREE
IP 68 8 Panel Connection P10
Upwards Panel Connection PU20
Downwards Panel Connection PD20
Number of Conductor Configuration Right Panel Connection PR30
Code Left Panel Connection PL30
Conductors L1 L2 L3 N N
Clean ½
Panel Connection P40
Earth Clean Earth
10
ELINECR BUSBAR
CONDUCTOR MATERIAL
BUSBAR CODE
Standard Straight Length PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILISATION TYPE / FEEDER
COMPONENT
CR
Feeder
PE
L3
L2
L1
N
3000
Note:
Minimum Special Length = 45cm
A
A
A
Rated Current 630 800 1000 1250 1600 2000 2500 2250 2500 - 3000 3200 3600 4000 5000
CRA - Al (A)
Attention ! Conductor Busbar Code 06 -
08 10 12 16 20 25 23 27 30 33 36 40 50
The standard mounting of the Cast Resin
Rated Current 800 1000 1250 1600 2000 2500 - 3000 3200 3600 4000 - 5000 - 6300
busbar is with the conductors on edge This CRC - Cu (A)
allows for the easy application of the resin at Conductor Busbar Code 08 10 12 16 20 25 - 30 32 36 40 - 50 - 63
the joint.
A (mm) 90 105 130 160 210 250 300 310 340 370 410 430 490 590 730
11
ELINECR BUSBAR
CONDUCTOR MATERIAL
BUSBAR CODE
Elbows PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILISATION TYPE / FEEDER
COMPONENT
CR
443
CRC 32608 - U
384
443
CRC 32608 - D
443
384
B
A PE Left Elbow L Sample Order:
L3
L2
L1 2000 A, Copper, Feeder, IP 68,
N 5 Conductors
CRC 20608 - L
CRA 20608 - R
Rated Current 630 800 1000 1250 1600 2000 2500 2250 2500 - 3000 3200 3600 4000 5000
CRA - Al (A)
Conductor Busbar Code 06 08 10 12 16 20 25 23 27 - 30 33 36 40 50
Attention ! Rated Current 800 1000 1250 1600 2000 2500 - - -
CRC - Cu (A)
3000 3200 3600 4000 5000 6300
The standard mounting of the Cast Resin
busbar is with the conductors on edge. This Conductor Busbar Code 08 10 12 16 20 25 - 30 32 36 40 - 50 - 63
allows for the easy application of the resin at A (mm) 415 430 455 485 535 575 625 635 665 695 735 755 815 915 1055
the joint.
B (mm) 370 377 390 405 430 450 475 480 495 510 530 540 570 620 690
The dimensions given above are minimum values. Please call us for non-standard components
12
ELINECR BUSBAR
CONDUCTOR MATERIAL
BUSBAR CODE
Elbows PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILISATION TYPE / FEEDER
COMPONENT
443
CR
384
384
443
443
384
PE Downwards Vertical Offset DV Sample Order:
L3
L2
L1 Note: Y=25 cm, 2000 A, Aluminium
N X=min: 30 cm, Feeder, IP 68, 5 Conductor
*Please see the table for max dimensions.
CRA 20608 - DV25
Y=220
384
443
Rated Current 630 800 1000 1250 1600 2000 2500 2250 2500 - 3000 3200 3600 4000 5000
CRA - Al (A)
Conductor Busbar Code 06 08 10 12 16 20 25 23 27 - 30 33 36 40 50
Rated Current 800 1000 1250 1600 2000 2500 - 3000 3200 3600 4000 - 5000 - 6300
Attention ! CRC - Cu (A)
The standard mounting of the Cast Resin Conductor Busbar Code 08 10 12 16 20 25 - 30 32 36 40 - 50 - 63
busbar is with the conductors on edge. This
A (mm) 415 430 455 485 535 575 625 635 665 695 735 755 815 915 1055
allows for the easy application of the resin at
the joint. B (mm) 370 377 390 405 430 450 475 480 495 510 530 540 570 620 690
X (mm) 290 305 330 360 410 450 500 510 540 570 610 630 690 710 930
The dimensions given above are minimum values. Please call us for non-standard components
13
ELINECR BUSBAR
CONDUCTOR MATERIAL
BUSBAR CODE
Elbows PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILISATION TYPE / FEEDER
COMPONENT
CR
A
B
4
38
3
44
A
B
PE Upwards Right Combined Offset KUR Sample Order:
L3
L2
L1 3200 A, Copper
Y
N Feeder, IP 68, 5 Conductor
Note:
Y= min. 30cm CRC 32608 - B - KUR
4
38
3
44
443
384
PE Downwards Left Combined Offset K D L Sample Order:
L3
L2
L1 3300 A, Copper
N Feeder, IP 68, 5 Conductor
Note:
Y= min. 30cm CRC 32608 - B - KDL
443
384
PE Downwards Left Combined Offset K D L Sample Order:
L3
L2
L1 3200 A, Copper
N Feeder, IP 68, 5 Conductor
Y Note:
Y= min. 30cm CRC 32608 - B - KDL
B Rated Current 630 800 1000 1250 1600 2000 2500 2250 2500 -
CRA - Al (A)
3000 3200 3600 4000 5000
A
Conductor Busbar Code 06 08 10 12 16 20 25 23 27 - 30 33 36 40 50
Attention !
The standard mounting of the Cast Resin Rated Current 800 1000 1250 1600 2000 2500 - 3000 3200 3600 4000 - 5000 - 6300
CRC - Cu (A)
busbar is with the conductors on edge. This Conductor Busbar Code 08 10 12 16 20 25 - 30 32 36 40 - 50 - 63
allows for the easy application of the resin at
the joint. A (mm) 415 430 455 485 535 575 625 635 665 695 735 755 815 915 1055
B (mm) 370 377 390 405 430 450 475 480 495 510 530 540 570 620 690
The dimensions given above are minimum values. Please call us for non-standard components
14
ELINECR BUSBAR
CONDUCTOR MATERIAL
BUSBAR CODE
Elbows PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILISATION TYPE / FEEDER
COMPONENT
CR
L1
N Feeder, IP 68, 5 Conductor
Note:
Y= min. 30cm CRC 32608 - B - KLU
B
A
B A Note:
384
Rated Current 630 800 1000 1250 1600 2000 2500 2250 2500 - 3000 3200 3600 4000 5000
CRA - Al (A)
Conductor Busbar Code 06 08 10 12 16 20 25 23 27 - 30 33 36 40 50
Attention !
The standard mounting of the Cast Resin Rated Current 800 1000 1250 1600 2000 2500 - 3000 3200 3600 4000 - 5000 - 6300
CRC - Cu (A)
busbar is with the conductors on edge. This Conductor Busbar Code 08 10 12 16 20 25 - 30 32 36 40 - 50 - 63
allows for the easy application of the resin at
the joint. A (mm) 415 430 455 485 535 575 625 635 665 695 735 755 815 915 1055
B (mm) 370 377 390 405 430 450 475 480 495 510 530 540 570 620 690
The dimensions given above are minimum values. Please call us for non-standard components
15
ELINECR BUSBAR
CONDUCTOR MATERIAL
BUSBAR CODE
Standard Components PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILISATION TYPE / FEEDER
COMPONENT
CR
Reduction
Is used to change busbar cross section.
Note:
Decision and selection of reduction module and protection on lower side is under the customer's responsibility.
Reducers Table
C
Tee Connection T Sample Order:
2500 A, Copper,
Feeder, IP 68, 5 Conductor
CRC 25608 - T
A
B
PE
L3
L2
L1
N
CR
PE
L3
118 L2
L1
N
700
PE
L3
118 L2
L1
N
A
Note: 1) Horizontal Expansion unit should
1500
be used when the busbar run crosses to an
adjacent building or crosses a building Attention! the total length of the module should be adjusted to 1500mm after installation.
expansion joint.
2) This module is used on the long busbar
line (75m) where line is ended by end closure
and is not fixed on the support rigidly.
3) Horizontal Expansion Joint has sufficient
movement span of 25mm max.
FDM Dimension Table
Rated Current 630 800 1000 1250 1600 2000 2500 2250 2500 - 3000 3200 3600 4000 5000
Attention ! CRA - Al (A)
The standard mounting of the Cast Resin Conductor Busbar Code 06 08 10 12 16 20 25 23 27 - 30 33 36 40 50
busbar is with the conductors on edge. This Rated Current 800 1000 1250 1600 2000 2500 - - -
CRC - Cu 3000 3200 3600 4000 5000 6300
allows for the easy application of the resin at (A)
CR
PE
L3
118 L2
L1
N
1500
PE
CRC 25608 - S
Rated Current 630 800 1000 1250 1600 2000 2500 2250 2500 - 3000 3200 3600 4000 5000
Attention ! CRA - Al (A)
The standard mounting of the Cast Resin Conductor Busbar Code 06 08 10 12 16 20 25 23 27 - 30 33 36 40 50
busbar is with the conductors on edge. This Rated Current 800 1000 1250 1600 2000 2500 - - -
CRC - Cu 3000 3200 3600 4000 5000 6300
allows for the easy application of the resin at (A)
CR
125
195
150
446
19
ELINECR BUSBAR
CONDUCTOR MATERIAL
BUSBAR CODE
Panel Connections PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILISATION TYPE / FEEDER
COMPONENT
CR
443
384
200 393
The "A" and "B" dimensions for PR30 and
543 PL30 are the same dimensions as left and right elbows.
150
443
384
200 393
The "A" and "B" dimensions for PR30 and PL30
543 are the same dimensions as left and right elbows.
150
CR
A
B
150
A
B
150
21
ELINECR BUSBAR
CONDUCTOR MATERIAL
BUSBAR CODE
Panel Connections PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILISATION TYPE / FEEDER
COMPONENT
CR
1135
min.
110
165 165 165 165
connections. X=.....mm
Y=.....mm
Z=.....mm
ø=.....mm
22
ELINECR
Panel Connections
150
150
150
150
150
150
150
Ø14 Ø14 Ø14 Ø14 Ø14 Ø14 Ø14
23 40
23 40
23 40
23 40
23 40
23 40
23 40
PE L3 L2 L1 N
20 20 20 15 20 20 25
40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 100 100 100 100
40 55 80 110 160 200 250
150
150
150
23 40
23 40
23 40
PE L3 L2 L1 N
10 25 20 15
40 40 40 4040 40 40 40 40 4040 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 100 100 100 100
260 290 320 360
150
150
23 40
23 40
PE L3 L2 L1 N
25 20 30
40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 100 100 100 100
380 440 540
CRA 50
CRC 63
20
23
40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 X X X X
680
Please call us for non-standard components Distance between conductors can vary +-5mm. The dimensions given above are minimum values.
23
ELINECR BUSBAR
CONDUCTOR MATERIAL
BUSBAR CODE
Panel Connection Dimensions PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILISATION TYPE / FEEDER
COMPONENT
CR
N
L1
L2 Flanş PE
L3 Earth
PE
PE L3 L2 L1 N
B
A
100
Ø7
12,5
A B Number of
Rated Busbar Rated Busbar Conductor Holes along
Current Code Current Code Size (mm) (mm)
length B
24
ELINECR BUSBAR
CONDUCTOR MATERIAL
BUSBAR CODE
Transformer Connections PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILISATION TYPE / FEEDER
COMPONENT
CR
125
195
150
446
25
ELINECR BUSBAR
CONDUCTOR MATERIAL
BUSBAR CODE
Transformer Connection PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILISATION TYPE / FEEDER
COMPONENT
CR
443
384
123 393
The "A" and "B" dimensions for PR30 and PL30
543 are the same dimensions as left and right elbows.
150
443
384
123 393
The "A" and "B" dimensions for PR30 and PL30
543 are the same dimensions as left and right elbows.
150
CR
A
B
150
A
B
150
27
ELINECR BUSBAR
CONDUCTOR MATERIAL
BUSBAR CODE
Transformer Connection PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILISATION TYPE / FEEDER
COMPONENT
CR
For between Transformer and Panel connection applications EAE Designing department can prepare your projects on request.
.
min
110
250
N
670
min. L1
250
670
L2
670 L3
.
min
250
PE
225
0
248
118
.
min
110
200
250
min.
100
N
670
L1
670
L2
670 L3
.
min
110
PE
The dimensions given above are minimum values. Please call us for non-standard components
28
ELINECR
Transformer Connections
150
150
150
150
150
150
150
Ø14 Ø14 Ø14 Ø14 Ø14 Ø14 Ø14
23 40
23 40
23 40
23 40
23 40
23 40
23 40
PE L3 L2 L1 N
20 20 20 15 20 20 25 100 100 100 100
40 40 40 40 40 40 40 40 40 40 40 40 40 40 40
40 55 80 110 160 200 250
150
150
150
23 40
23 40
PE L3 L2 L1 N
10 25 20 15 100 100 100 100
40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40
260 290 320 360
150
150
23 40
23 40
PE L3 L2 L1 N
25 20 30 100 100 100 100
40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40
380 440 540
CRA 50
CRC 63
150
Sample Connection
150
Ø14
23 40
20
40 40 40 40 40 40 40 40 40 40 40 40
680
Please call us for non-standard components Distance between conductors can vary in +-5mm. The dimensions given above are minimum values.
29
ELINECR
Horizontal & Vertical Cast Resin Busbar Applications
FIGURE 1 - EDGEWISE APPLICATION FIGURE 5 - CROSSING UNDER A BEAM ON
CEILING
FLATWISE APPLICATION
CEILING
500
BEAM
100
200
WALL
PE
FIGURE 2 - EDGEWISE APPLICATION FIGURE 6 - SAMPLE WALL CROSSING WITH FIRE BARRIER
CEILING
WALL
500
HOLE
PE L3 L2 L1 N
200 BUSBAR-2 BUSBAR
WALL
200
500
350 (min.)
HOLE
200
BUSBAR
WALL
BUSBAR-1 BUSBAR-2
200
PE PE
CENTRE OF
L3 L3 JOINT POINT
L2 L2
L1 L1
N N
CEILING
Attention !
For correct installation, the dimension from the busbar to
BEAM
BUSBAR RUNNING ON EDGEWISE PE L3 L2 L1 N The dimensions given above are minimum values.
APPLICATION AS STANDARD
All dimensions are given in mm.
30
ELINECR
Suspension Components
Supports
CR-UT HANGER SET FOR EDGEWISE APPLICATION (STANDARD APPLICATION)
Conductor
CRA - Al CRC - Cu Order
Cross L A Code
Conductor Conductor Section
Rated Busbar Rated Busbar (mm) (mm)
Current Code Current Code
630 06 800 08 6x40 300 90 3025348
800 08 1000 10 6x55 300 105 3025348
1000 10 1250 12 6x80 300 130 3025348
1250 12 1600 16 6x110 350 160 3025348
1600 16 2000 20 6x160 400 210 3025348
2000 20 2500 25 6x200 400 250 3025348
2500 25 - - 6x250 450 300 3025348
A
43 65
4
L
65
4
L
*Flatwise Application is supplied for only on special conditions. Please call us for non-standard dimensions.
31
ELINECR
Suspension Components
Supports
CR HANGER SET WITH BRACKETS FOR CR HANGER SET WITH BRACKETS FOR
EDGEWISE APPLICATION EDGEWISE APPLICATION
(Standard Application) (Non-Standard Application)
5 5
50 50 50 50
L L
UAS-K5 Supports
Description L Order Code
(mm)
L
UAS-K5 Support (1) 200 3005324
L
UAS-K5 Support (2) 250 3005323
50 UAS-K5 Support (3) 300 3005322
5 50 UAS-K5 Support (4) 350 3005321
Threaded Rod UAS-K5 Support (5) 400 3005320
UAS-K5 Support (6) 500 3005319
UAS-K5 Support (7) 600 3005318
UAS-K5 Support (8) 700 3005317
Extension Unit UAS-K5 Support (9) 1100 3005316
Connection Units
Description L Order Code
(mm)
Suspension Components
Supports
IDT
IDY
IDT
IDT
33
ELINECR ORDER CODE
LENGTH L (mm)
Suspension Components
Supports
UPY
Steel
Dowel T
L
Threaded
Rod
65
UPY 43
UPY
34
ELINECR
Measuring a Special Length
After installation of standard 3m busbar lengths, special lengths ( make up pieces ) shorter than 3m may be required.
The minimum length for these special pieces is 35cm
125 125
Attention !
The standard mounting of the Cast Resin The quantity must be determined according to number
busbar is with the conductors on edge. This of joint in the project and then ordered separately.
allows for the easy application of the resin at
the joint.
35
ELINECR
Cast Resin Busbar Horizontal Application
1 2 3
mm
250
Conductors must be cleaned using a The second busbar is introduced and After checking the three parts for
cloth to remove dust and damp. Then installed to the joint block correct alignment, and the distance
install and fix the joint block between the two busbar lengths is
25cm tighten the joint to 83 Nm using
a torque wrench.
4 400 m
m 5
Assemble the casting moulds and place rubber sealing Before the casting mould is fitted, apply de-moulding agent
strips into the shaped returns. wax to all surfaces of the inside of the casting moulds and
wait until wax is totally dry. This is imperative to enable removal
of the casting moulds after setting.
6 7
m
7c
The casting mould plates must be fitted approximately 7 cm Please check the installation manual to get extra information.
from busbar end.
36
ELINECR
Cast Resin Busbar Vertical Applications
1 2 3
mm
250
Conductors must be cleaned using a The second busbar is introduced and After checking the three parts for correct
cloth to remove dust and damp. Then installed to the joint block. alignment, and the distance between the
install and fix the joint block. two busbar lengths is 25cm tighten the
joint to 83 Nm using a torque wrench.
4 5
400 mm
Assemble the casting moulds and place rubber sealing strips Before the casting mould is fitted, Apply de-moulding agent
into the shaped returns. wax to all surfaces of the inside of the casting moulds and
wait until wax is totally dry. This is imperative to enable
removal of the casting moulds after setting.
6 7
7 cm
The casting mould plates must be fitted approximately 7 cm Gaskets must be located only bottom part of the mould plates.
from busbar end. By this way resin can be poured from top side.
37
ELINECR
Preparation of Joint Casting Material
Megger test must be done at joint and the result must be
higher than 1mOhm
< 5°C STOP
Resin (A), Hardener (B) and fillers; must be stored at least < 35°C STOP
one day over (> 20 °C ).
Ambient temperature of job side must be 5°C < T amb
MW
T(°C)
<40°C < 1MW OK
< 1MW NOT OK
FILLER
RESIN(A)
HARDENER (B)
350 mm
150 mm + 100 mm
1 2 3
a
b
a
b
Filler removed from the plastic bucket Resin and hardener are mixed in plastic bucket.
and fillers have to be absolutely dry
4 5
Mix resin and hardener thoroughly with stirrer at least 1 Add fillers and mix until homogeneous; at least 5 minutes.
minute. Then application must be done within 30 minutes.
38
ELINECR
Casting Vertical and Horizontal Installation
Horizontal Application
The prepared cast resin mix can be poured in once the casting
mould has been fitted.
The cast resin mix requires a setting time of 7-8 h under normal
ambient conditions..
If one bucket of resin is not enough for the joint; the second one
must be prepared and applied immediately.
Vertical Application
The prepared cast resin mix can be poured in once the casting
mould has been fitted.
The cast resin mix requires a setting time of 7-8 h under normal
ambient conditions..
If one bucket of resin is not enough for the joint; the second one
must be prepared and applied immediately.
39
ELINECR
Declaration
EC DECLARATION OF CONFORMITY
Product Group E-Line CR Busbar Energy Distribution System
This is to attest, under our sole responsibility, that the aforementioned products conforms with
the determined regulations,guidelines and the below standards.
Standard :
EN 61439-6
Low-voltage switchgear and controlgear assemblies - Part 6: Busbar trunking
systems
IEC 61439-6
Low-voltage switchgear and controlgear assemblies - Part 6: Busbar trunking
systems (busways)
CE - Directive
2006/95/EC “Electrical equipment designed for use within certain voltage limits”
21.01.2014
40
ELINECR
Certificates
41
ELINECR
Product Overview
2- Electrical Characteristics
- Busbar systems nominal insulation voltage shall be 1000 V.
- As per ampere rates, minimum short circuit values shall be as given below;
For Aluminium Conductors; 630A :1 sec/rms 20kA, Peak 40kA
800A :1 sec/rms 28kA, Peak 58,8kA
1000A :1 sec/rms 40kA, Peak 84kA
1250A :1 sec/rms 55kA, Peak 121kA
1600-2000-2500A :1 sec/rms 70kA, Peak 154kA
2250A-2500A :1 sec/rms 100kA,Peak 220kA
3000A and above :1 sec/rms 120kA,Peak 264kA
2.2- Conductors
Aluminium or Copper conductors shall be tin plated at the joints upon the wire configuration and required numbers, which are described below.
- Busbar system shall have aluminium conductors between 630A – 5000A.
- Busbar system shall have copper conductors between 800A – 6300A.
- Busbar system shall have the following number of conductors and wire configuration;
a) 3 Conductors
b) 4 Conductors
c) 4 ½ Conductors
d) 5 Conductors
e) 6 Conductors
- Aluminium conductors shall be of EC grade aluminium. Minimum conductivity shall be 34m/mm².W.
- Copper conductors shall be minimum 99,95% electrolytic copper. Minimum conductivity shall be 56m/mm².W.
2.3- Insulation
- Busbars have to be insulated special selected silisium and calcile mixed with electrical grade epoxy resin to make superior composite.This material continuosly works under temperature change and
movements.
- Insulation system shall be suitable for 1.000V continuous operation. Conductor size shall be designed so that temperature rise on the conductors shall not exceed 100 C degree at nominal current, which
helps with the problem of global heating. With this reason, insulation class shall be “B class”.
2.4- Protection
- Protection degree of the housing and joints shall be IP68
2.5- Acessories
- Busbar system shall have all necessary accessories (elbows, offsets, panel-transformer connections, reductions, etc.) Manufacturer shall supply special dimensioned units in short time, if the project
conditions requires.
- For horizontal runs, a horizontal expansion unit shall be used at every 40m and expansion points of the building.
42