Professional Documents
Culture Documents
WRT - Maintenance Instruction
WRT - Maintenance Instruction
L6764-Z-MA-005 0
Document number L6764-Z-MA-005
Revision 0
Page 2 of 63
REVISION HISTORY
CHANGE DESCRIPTION
TABLE OF CONTENTS
1 MAINTENANCE INSTRUCTIONS
1.1 Introduction
This document gives maintenance instructions for the National Oilwell Varco TM Wireline
Riser Tension System (WRT system) for rig/vessel stated on the front page of this
document.
A Maintenance Log must be established for this equipment, and all maintenance,
special observations and repairs must be logged. Upon request, the log should be made
available to supplier’s service personnel.
Supplier is keeping and maintaining a failure database for its offshore equipment. It is of
great importance and much appreciated that user is reporting failures and problems to
supplier. This information is essential for supplier to identify critical items prone to failure
or replacement, and it will highlight components that require a design review to improve
safety and reliability. Areas of major concern shall without hesitancy be brought to the
attention of supplier. If urgent deficiencies appear after the equipment is taken into use,
supplier will issue product bulletins to user as necessary.
1.2 Abbreviations
The following abbreviations may be used in this document.
AISI American Iron and Steel Institute (material standards)
APV Air pressure vessel
ARV Anti recoil valve
ATC Accumulated ton cycles (= maintenance parameter for support wires)
AW Auxiliary well
BOP Blow-out preventer (installed on wellhead at the seabed)
CAPV Composite air pressure vessel (versus conventional steel APV)
CMC Crown mounted compensator (= drillstring compensator)
CPU Central processing unit (part of PLC)
DCR Drilling control room (= driller’s cabin)
DSV Digital smart valve (DSV card = controller card of anti-recoil valve)
EDS Emergency disconnect sequence
FAT Factory acceptance test
FFU Fluid fill unit
H Hydraulic component (used in position numbers)
HP High pressure
HPU Hydraulic power unit
LER Local equipment room (= LIR)
LIR Local instrument room (= LER)
LMRP Lower marine riser package (installed at lower end of riser string)
LP Low pressure
LPT Linear position transducer
MCC Motor control centre
MW Main well
N2 Nitrogen
NOV National Oilwell Varco Norway AS (= the system supplier)
NS Norwegian Standard
OD Outer diameter
PLC Programmable logic controller
PPM Parts per million
RAR Riser anti recoil
RARS Riser anti recoil system
RIT Riser tensioner
ROV Remotely operated vehicle (subsea)
RT Riser tension
SD Shutdown
SP Setpoint
UPS Uninterruptible power supply
WC Wellcentre
WRT Wireline riser tension
WT Wireline tensioner
Document number L6764-Z-MA-005
Revision 0
Page 7 of 63
2 SAFETY SUMMARY
The following types of safety messages may appear in this
document:
It is the responsibility and duty of all personnel involved in the operation and
maintenance of this equipment to fully understand the SAFETY measures, by which
hazards are reduced or eliminated. Personnel must familiarize themselves with all
aspects of safety and operation of the equipment before starting any operation or
maintenance.
x Only qualified personnel are allowed to carry out maintenance and fault finding.
x Only the prescribed maintenance may be carried out by user. Anything else must be
approved by supplier’s service department before carried out.
x Dropped objects are potential killers. Make sure that no loose objects (tools or
equipment) are dropped from or forgotten at high places. In cold waters make sure
that ice and snow cannot fall on people below.
Document number L6764-Z-MA-005
Revision 0
Page 8 of 63
x Crushing hazard: Beware of the equipment’s moving parts. Stay away from cylinder
rods, support wires and wire sheaves during operation.
x Grease splashing from the support wires may make walkways slippery. Prevent
skidding/slipping accidents by regularly removing any grease spots from the
walkways.
x The equipment makes use of high-pressure hydraulic oil, tensioner fluid and air.
Beware of the risk of pipe/hose burst. Pipe/hose connections must not be loosened
or tightened before the system is fully depressurized.
x If anyone gets hydraulic oil or tensioner fluid into the eyes or open wounds, wash at
once with lots of fresh water. Consult a doctor if necessary.
x If APVs (air pressure vessels) need to be isolated, make sure that the correct APVs
are isolated. Isolating the wrong APVs can cause serious damage to equipment and
people.
x When opening valves manually, always open slowly to avoid pressure shocks.
x Always use eye protection while working with fluids and air under pressure.
x Hydraulic oil, tensioner fluid and lubricants may contain toxic additives that by
repeated skin contact or inhalation can be dangerous to your health. Study the
safety data sheets for the different compounds, and protect yourself as required.
x Be especially aware of the danger involved with hydraulic oil under pressure. It can
be injected under the skin without the victim being aware.
x Adjustable valves that have been set and sealed by supplier are not to be adjusted
by user without approval and guidelines from supplier.
x Heat or excessive force must not be used to move a part, unless it is beyond repair.
Document number L6764-Z-MA-005
Revision 0
Page 9 of 63
3 ROUTINE INSPECTIONS
x Read and log the total riser tension. Compare the reading with the reading the last
days to verify that the system is stable.
x Read the tension on each tensioner, and verify that the total load is distributed
evenly. If one tensioner has low tension, keep an eye on this tensioner the next days
to spot leaks or malfunction.
x Inspect the overall equipment to verify smooth operation. Check for abnormal noise
and vibrations in all moving parts.
x Look and listen for air leaks. Generally no leaks are acceptable.
x Look and listen for leaks in the fluid system. Generally no leaks are acceptable.
After two months operation, when the equipment has proved stable and reliable through
field experience, the daily inspections can be transferred to the list of weekly
inspections.
x During system operation, verify that the cylinder rods are being lubricated by a thin
film of tensioner fluid.
x Check visually for fluid leaks outside the anti-recoil valves and the HP accumulators.
Verify that tensioner fluid is not running down the cylinder casings, which would be
an indication of worn cylinder seals.
See the Checking for fluid leaks section for more info.
x Inspect the wire sheaves at both ends of the tension cylinders, and all idler sheaves,
to verify smooth operation. Verify that the wire enters the sheave groove in a proper
way, and that all sheaves are rotating.
x Inspect the ropes of the cylinder position sensors. Splintery ropes must be changed
as described in separate procedure.
x Inspect all wire anchor clamps at the fixed sheave houses. Verify visually that the
clamp bolts are tight, and that there is no sign of wire slipping.
Document number L6764-Z-MA-005
Revision 0
Page 10 of 63
x Check visually for corrosion, wear, damage, and loose bolts and parts.
x At the air control skid, inspect the filter regulator for the instrument air supply. Verify
that the pressure out is 8 bar, and that the filter bowl is empty. If necessary the bowl
must be emptied manually of precipitated water.
x At the Accumulated Ton Cycles (ATC) display, verify that the ATC counters and the
belonging alarm limits are correctly set for each support wire. The ATC parameters
are important maintenance parameters, and tell the operators when to most
efficiently change the support wires. See more info at the description of the display
(in the Operating Instructions) and at the Accumulated Ton Cycles wire monitoring
section. After this point is known to be taken care of, it no longer needs be checked
this often.
x Inspect the open spelter socket type wire terminations at the riser tension ring. Look
for deformations, cracks, corrosion and loose bolts.
x Inspect the walkways below and around the support wires to see if grease splashes
have made them slippery. Skidding/slipping accidents can be prevented by keeping
the walkways clean.
x Check that the breather filters are in place at the top of all fluid drain tanks (two
tanks at each fixed sheave house).
Document number L6764-Z-MA-005
Revision 0
Page 11 of 63
x Take a sample of the tensioner fluid in one third of the HP accumulators and the
belonging cylinders, and have it analysed by a laboratory. See more details in the
Checking purity and chemical properties of tensioner fluid section, including the
Houghton Recommendation.
x Check the fluid levels in all HP accumulators as described in the Checking fluid level
in HP accumulators section. After reliable operation is proven through field
experience (after minimum four weeks of normal operation), this point can be
transferred to the 6-monthly maintenance routine.
Document number L6764-Z-MA-005
Revision 0
Page 12 of 63
x Clean and lubricate the cylinder rods as described in the Lubrication section.
x Keep all other unpainted metal surfaces covered by suitable anti-corrosion oil.
x Take a sample of the tensioner fluid in half of the HP accumulators and the
belonging cylinders, and check (by the on-board particle counter) that the fluid
purity satisfies ISO 4406:99, Class 19/17/14. See more details in the Checking
purity and chemical properties of tensioner fluid section. If no abnormalities are
observed the first six months of operation, this point may be transferred to the 3-
monthly maintenance routine and combined with the laboratory sampling.
x Check the fluid drain tanks (two tanks at each fixed sheave house). Verify that the
breather filter is in place, and write down the fluid level in the tank. Compare the fluid
level with earlier recordings and with the recordings from the other drain tanks to
spot any abnormalities. Drain the tank manually if it is more than half full. If a tank
remains empty for a longer period; inspection of the anti-recoil valve and pipe lines is
needed. The drain tank fluid volume equals the leakage from the HP accumulator
and can be used to decide if fluid needs to be added on the HP accumulator (at the
underside of the accumulator piston).
x Drain to safe location all working APVs by opening each APV’s drain valve for a
short while. Use ear and eye protection during the draining. Careful, the APVs
are pressurized!
x Test the operation of each anti-recoil valve by running a test sequence four or five
times. The test sequence is explained in the Description of controls section in the
Operating Instructions.
x Take a sample of the tensioner fluid in one third of the HP accumulators and the
belonging cylinders, and have it analysed by a laboratory. See more details in the
Checking purity and chemical properties of tensioner fluid section.
Document number L6764-Z-MA-005
Revision 0
Page 13 of 63
x Change the elements of the three small filters on each anti-recoil valve as described
in separate section. After the first half year of operation, this point only needs to be
carried out 6-monthly.
x At the APVs, check that the quality of the air supplied from the compressors satisfies
ISO 8573-1, Class 3.3.3. See Checking the quality of the air section for procedure.
x Perform all the routine inspections listed in the Routine inspections section and
complete an inspection report. A signed copy of the inspection report must be filed in
the maintenance log, and the remarks must be followed up.
x Test the opening setpoint of the pressure relief valve on top of each HP accumulator
as described in the Pressure relief valve maintenance section. Verify that the valves
are clean and in good working condition. Write down the results in the maintenance
log.
x Maintain the pressure relief valve on each working APV as described in the Pressure
relief valve maintenance section.
x Check/retighten all terminal blocks and other electrical connection points, including
earthing.
x Check for moisture inside all outdoor junction boxes and panels. Add new drying
agent as required.
x Check the condition of the oily Denso tape fitted to protect the fluid tubing fittings
against corrosion. If the tape is drying out, soak it with hydraulic oil to maintain the
corrosion preventing effect.
5.1 Lubrication
Wireline tensioners: The tensioners are to be lubricated according to the lubrication
charts referred to at the end of this document. The charts show intervals, where to
lubricate and what kind of lubricant to use. A grease gun is used for the nipple greasing,
and the greasing should each time continue until fresh grease is seen oozing out
between the shaft and the bushing/bearing. The greasing can normally take place while
the system is operating. Always take necessary safety precautions while the system is
operating.
Cylinder rods: The rods of the tension cylinders are lubricated by tensioner fluid while
the cylinders are fully retracted. During system operation the cylinders normally operate
around mid-stroke only, and the outer end of the rods may be left without lubrication for
a longer period. If the on-going operations allow it, it is recommended to retract the
cylinders fully at least 2-weekly. If this is not practical, it is recommended to clean
(remove salt and mud) and preserve the rods with the same tensioner fluid as is used in
the cylinders. This routine will reduce the risk of corrosion on the cylinder rods, protect
the scraper rings and seals, and increase the service life of the cylinders.
Idler sheaves: Lubricate all idler sheaves according to their lubrication chart. The chart
shows intervals, where to lubricate and what kind of lubricant to use. A grease gun is
used for the nipple greasing, and the greasing should each time continue until fresh
grease is seen oozing out between the shaft and the bushing/bearing. The greasing can
take place while the system is operating, provided that the sea is calm.
Support wires: Grease each support wire by using a suitable brush on a rod (for safe
distance to the moving wires). It is of particular importance to keep well-greased the
areas where the wire bends over the sheaves. The greasing can take place while the
system is operating. Be aware of the safety issues of greasing a moving wire. Brilube 70
or equivalent wire grease is recommended for this lubrication.
Document number L6764-Z-MA-005
Revision 0
Page 16 of 63
Bleed
Minimess
On the block and bleed valve make sure the block valve is open, close the bleed valve,
connect the measuring instrument to the minimess and open bleed.
When the measuring is completed, close the bleed valve and remove the measuring
instrument from the minimess.
Document number L6764-Z-MA-005
Revision 0
Page 17 of 63
Both fluid types are water-glycol based and well suited as tensioner fluid, but are
not to be mixed. The maintenance supervisor must keep track of what type is used and
order new fluid of the same type. If the rig is changing from one fluid type to the other,
all old fluid must be drained first. Only these types of fluid may be used. The equipment
supplier (NOV) refuses all responsibility for damage caused by the use of non-approved
fluids and damage caused by mixing fluids of different types.
The tensioner fluid is filled on the HP accumulators. During system operation the fluid is
circulating between the HP accumulator and the (lower) piston side of the tension
cylinder. On the way the fluid passes back and forth through the open anti-recoil valve.
The specified fluids are highly resistant to fires and explosions, which is important when
fluids are in contact with high-pressure air (ref. the diesel effect). They also lubricate and
protect against corrosion, and in a closed system the fluid vapour prevents corrosion
even above the fluid surface. The fluids are very resistant to biological attacks from
bacteria and fungi; have no significant negative effect on the rubber seals, and are not
aggressive on the commonly used offshore paints. From a toxicological point of view the
fluids are more acceptable than most similar fluids. Fluid spill can be flushed away with
water, and there is no need for special cleaning chemicals. During fluid change the old
fluid shall still not be disposed into the sea, but returned to a licensed waste contractor
and treated according to the applicable environment protection regulations.
Document number L6764-Z-MA-005
Revision 0
Page 18 of 63
The following illustrations of the HP accumulators are useful while carrying out the
different procedures in the next sections:
High Pressure
Accumulator (HPA)
Top view of cylinder & accumulator assembly
Document number L6764-Z-MA-005
Revision 0
Page 19 of 63
Filter
Anti-recoil valve
Anti-recoil valve
Drain port
Anti-recoil valve
Drain valve
HPA (BV04)
High Pressure
Accumulator (HPA)
Dip Tube
The tension cylinders are exposed to extreme working conditions, and it is important
that the tensioner fluid remains clean and according to specification. Compliance with
specification is verified by regularly taking samples of the fluid in the HP accumulators.
The sampling intervals and type of sample are stated in the Periodic Maintenance
Schedule. If a sample is not satisfactory, the fluid must be cleaned or changed soonest.
Separate samples are taken for purity checking and for analysis of the fluid’s
chemical properties. The purity checks can normally be done by the on-board particle
counter, and the fluid purity must satisfy ISO 4406:99, Class 19/17/14 (NAS 8). The
chemical properties analysis must take place at a laboratory. The laboratory will
compare the result with the recommendation from the fluid manufacturer, and decide if
the fluid is suited for continued use.
During system running-in the first six months of operation, purity samples are required
more frequently than later. During all sampling it is each time sufficient to take samples
from half (not all) of the tensioners. Which tensioners the samples are taken from must
be logged and marked on the sample bottles, and the next sampling must be from the
other half of the tensioners. After two rounds all tensioners have been sampled. If
unexpected impurities are found in a tensioner, this tensioner must be checked each
time thereafter. If necessary, the supplier must be contacted.
The samples must be taken according to the recommendation which is shown on the
next 2 pages.
Document number L6764-Z-MA-005
Revision 0
Page 22 of 63
If the tensioner fluid no longer satisfies the purity requirement, but the chemical
properties otherwise are OK, the fluid must be cleaned in the fluid fill unit (FFU).
An extract of the flow diagram for the FFU is shown below. The extract gives an
overview of the FFU’s (atmospheric) main tank and the belonging LP filling pump (H01).
The skid mounted fluid fill unit (FFU) consists of an atmospheric fluid tank, a vane
pump, piping, valves, instrumentation and a local control panel. The unit is used for
filling tensioner fluid on the tensioners’ HP accumulators, and for draining the same fluid
from the accumulators when the fluid quality no longer is acceptable. If only the purity is
unacceptable, the fluid will be cleaned in the unit and refilled on the accumulators. If the
chemical properties are unacceptable, the fluid will be drained further to external waste
fluid containers, and replaced with new clean fluid. The fluid fill unit is shown in the
illustration below and on the next pages. The WRTS hookup to the FFU via the FFU’s
connections F and D. Both connections are hard-piped to the bottom fill/drain valve of
all the HP accumulators of the WRT. The fluid will be drained into the main tank via
connection D, and later pumped back via connection F using the LP filling pump.
Inspection hatch
Breather filter
Control panel
Pump motor
LP filling pump
Local control panel of the Fluid Fill Unit.See Operating Instructions for a detailed description.
Document number L6764-Z-MA-005
Revision 0
Page 26 of 63
The fluid is cleaned because the purity no longer satisfies ISO 4406:99 19/17/14. The
cleaning will continue until Class 19/17/14 is obtained.
It is recommended that the WRTS is unloaded and shut down first. It is also
recommended to clean the fluid from one pair of diametrically opposite tensioners at a
time. This is the base case described in the procedure.
The procedure for cleaning the fluid in the HP accumulators includes the following
steps:
x Draining the HP accumulator
x Cleaning the fluid
x Refilling cleaned fluid on the HP accumulator
x Close valve BV03 at the top of the pair’s first HP accumulator to be drained.
x Open valve BV04 and the drain valve below the HP accumulator to be drained.
x Allow the fluid to be drained completely from the HP accumulator and into the tank.
The fluid enters the tank via return filter H07.
x Unplug and open valve NV03 at the top of the cylinder, This will make sure that all
the fluid is drained from the cylinder and into the pipe system.
x Close and plug valve NV03 and open valve NV01 again to drain the fluid in the pipe
system further to the tank.
x Continuation below
Document number L6764-Z-MA-005
Revision 0
Page 28 of 63
x At the bottom of the first HP accumulator open the fill valve. The drain valve should
still be open from the draining. If not, open the drain valve too.
x At the fluid fill unit open valve H15. Keep valve H17 closed.
x Start the cleaning by starting the fill pump on the FFU. This can be done using the
local control panel of the FFU, or the local control panel of the WRT system in the
moonpool area. The fluid in the tank will then repeatedly be circulated from the FFU,
through the pump’s pressure filter, all the way through the fill and drain valves at the
bottom of the HP accumulator, through the tank return filter, and back to the tank.
(Some of it will be passing through pressure control valve H09.)
By keeping valve H17 closed while keeping the fill valve and the
drain valve at the bottom of the accumulator open, all the fluid in
the pipe system will be included in the cleaning process. Valve
BV04 must be closed.
x Throughout the cleaning, observe the local clogging (pressure drop) indicator at
return filter H07. When the indicator is in the red area, stop the pump and change
the elements of both the return filter and the pressure filter. Then restart the pump
and continue the cleaning. Repeat this as long as the cleaning goes on. Several
element changes may be needed before the fluid is clean enough.
x The fluid circulates through the pipes leading to the first HP accumulator. Go on for
approx. 20 minutes. Then, while the pump is running, carefully and slowly open the
fill valve and the drain valve below the second HP accumulator. Then carefully and
slowly close the fill valve and the drain valve below the first HP accumulator. The
fluid will now circulate through the pipes leading to the second HP accumulator.
x Run the pump for about 45 minutes, and then take a sample of the circulated fluid.
The sample can be taken while the pump is running by connecting a Minimess hose
to Minimess connector H12, or via the tank top breather hole H08. Check the purity
of the sample fluid by an on-board particle counter. If the sample satisfies ISO
4406:99 19/17/14, the fluid has been cleaned enough. If the sample doesn’t satisfy
this purity class, go on for 45 more minutes, and take a new sample. Continue
circulating and cleaning the fluid until ISO 4406:99 19/17/14 is obtained.
x When the fluid has reached the desired cleanliness class, stop the pump and
change the elements of both the return filter and the pressure filter one last time.
x Close the fill valve and the drain valve below the HP accumulator.
x Continuation below.
Document number L6764-Z-MA-005
Revision 0
Page 29 of 63
x If the fluid quantity in the main tank is believed to be insufficient for proper refilling,
add some more (new) fluid to the tank via the “Oil filling” connection F and valve
H16. See Filling the main tank in the Changing fluid in the accumulators section.
x Prepare the FFU for refilling as follows: Verify that valve H15 is open. Verify that
valve H17 is closed.
x At the bottom of the first HP accumulator to be filled open valve BV04 and the fill
valve beneath it.
x At the top of the cylinder, connect a hose to valve NV03, and point the other end of
the hose into a bucket. Open valve NV03.
x Start filling fluid on the cylinder by starting the filling pump from the local control
panel of the FFU or the WRT system. Go on filling until there is fluid coming out of
valve NV03. Then stop the pump. Close and plug valve NV03.
x At the top of the accumulator connect a hose to the dip tube outlet and point the
other end of the hose into a bucket. Carefully open valve NV02.
x Study the above Sectional view of HP accumulator illustration. As the fluid is filled on
the HP accumulator it will eventually meet the dip tube which is positioned in the
accumulator. When the fluid has reached the outlet of the dip tube, the fluid level is
correct.
x Start filling fluid on the cylinder by starting the filling pump from the local control
panel of the FFU or the WRT system. Go on filling until there is fluid coming out of
the dip tube outlet. Then stop the pump.
After all refilling is completed; return the fluid fill unit to normal as follows:
Verify that valves H17 and H16 are closed.
Document number L6764-Z-MA-005
Revision 0
Page 30 of 63
The HP tensioner fluid is changed in much the same way as described above for the
fluid cleaning, and the same illustrations apply. The major difference is that after the
old fluid is drained into the main tank of the fluid fill unit, the fluid will be drained from the
tank and new fluid filled, instead of cleaning the fluid in the tank. Here as well it is
recommended that the WRTS is unloaded and shut down first. This is the base case
described in the procedure.
The procedure for changing the fluid includes the following steps:
x Close valve BV03 at the top of the pair’s first HP accumulator to be drained.
x Open valve BV04 and the drain valve below the HP accumulator to be drained.
x Allow the fluid to be drained completely from the HP accumulator and into the tank.
The fluid enters the tank via return filter H07.
x Unplug and open valve NV03 at the top of the cylinder, This will make sure that all
the fluid is drained from the cylinder and into the pipe system.
x Close and plug valve NV03 and open valve NV01 again to drain the fluid in the pipe
system further to the tank.
x Continuation below
x Place one or more empty fluid containers at a lower elevation than the fluid fill unit,
and connect a drain hose between the tank drain valve (H14) and one of the
containers.
x Open the drain valve and drain all fluid from the tank.
x If there is any reason to believe that the inside of the tank is not clean, unscrew the
tank top inspection hatch and inspect and clean the tank as necessary. Then
reinstall the hatch.
x Close the drain valve, remove the drain hose, and plug the valve outlet.
x Have the old fluid returned to a licensed waste contractor for environmentally correct
disposal.
x Continuation below
x Bring the containers with the new fluid. The new fluid must be of the original type, as
specified in the Type and quantity of tensioner fluid section.
x Unplug the fluid fill unit’s “Oil filling” connection F, and connect a clean filling hose
between the first container and the F-connection. A portable and clean fluid pump
(supplied by others) must be fitted at the container end of the hose. A 3-micron
particle filter is recommended at the HPU end of the hose.
x At the fluid fill unit, verify that valves H14, H15 and H17 are closed. Open fill valve
H16.
x Using the portable pump, fill up the tank with the required fluid quantity (probably a
little more than what was drained from the tank). The fluid enters the tank via return
filter H07.
x Disconnect the filling hose, close filling valve H16, and plug connection F.
x Continuation below.
Document number L6764-Z-MA-005
Revision 0
Page 32 of 63
x Prepare the fluid fill unit for refilling as follows: Verify that valve H15 is open. Verify
that valve H17 is closed.
x At the bottom of the first HP accumulator to be filled open valve BV04 and the fill
valve beneath it.
x At the top of the cylinder, connect a hose to valve NV03, and point the other end of
the hose into a bucket. Open valve NV03.
x Start filling fluid on the cylinder by starting the filling pump from the local control
panel of the FFU or the WRT system. Go on filling until there is fluid coming out of
valve NV03. Then stop the pump. Close and plug valve NV03.
x At the top of the accumulator connect a hose to the dip tube outlet and point the
other end of the hose into a bucket. Carefully open valve NV02.
x Study the above Sectional view of HP accumulator illustration. As the fluid is filled on
the HP accumulator it will eventually meet the dip tube which is positioned in the
accumulator. When the fluid has reached the outlet of the dip tube, the fluid level is
correct.
x Start filling fluid on the cylinder by starting the filling pump from the local control
panel of the FFU or the WRT system. Go on filling until there is fluid coming out of
the dip tube outlet. Then stop the pump.
x After all refilling is completed; return the fluid fill unit to normal as follows:
Verify that valves H17 and H16 are closed.
Document number L6764-Z-MA-005
Revision 0
Page 33 of 63
1. Starting point: The WRT system operates normally with all tensioner pairs activated.
2. Select and deactivate the pair of diametrically opposite tensioners to be checked by
closing the common main air valve for these tensioners.
3. Retract the cylinders of these two tensioners by venting to safe location the
common air pressure in the pair. Verify that both cylinders are fully retracted.
4. Close the manual air inlet valves on top of the two HP accumulators.
5. Consider the need for raising the working air pressure in the other tensioner pairs, in
order to keep the tension on the riser at the original level.
6. Carefully unplug and open valve NV02 at the top of the first HP accumulator in the
pair. (Some pressure may still be left.)
7. If the fluid just reaches to the outlet of the dip tube, the fluid level is OK and no
topping up is needed.
8. If there is no fluid at the outlet of the dip tube, the fluid filling is low and topping up
more fluid is needed. This is done with the help of the fluid fill unit and as follows:
i. Connect the fluid fill unit to the WRT system, and check that there is sufficient
fluid in the tank.
ii. Prepare the fluid fill unit for the topping up according to the fluid fill unit’s
operating instructions.
iii. Open the fill/drain valve BV04 at the underside of the HP accumulator to be
topped up.
iv. Open the fill valve of the belonging HP accumulator on the fixed pipes.
v. Prepare correct filling of the first HP accumulator by studying the Sectional view
of HP accumulator illustration. As fluid is filled on the accumulator through the
fill/drain valve the fluid level will rise and will eventually meet the dip tube in the
HP accumulator. The filling is correct when the fluid has reached the outlet of
needle valve NV02 at the top of the dip tube.
vi. Start filling fluid on the cylinder by starting the filling pump from the local control
panel of the FFU or the WRT system.
vii. Go on filling until the fluid level is at the specified height. Then stop the pump.
viii. Close the fill/drain valve at the bottom of the HP accumulator.
ix. Close the fill valve on the fixed pipes.
x. Close and plug valve NV02 at the top of the HP accumulator.
9. Check the fluid level in the second HP accumulator in the same way.
10. When the fluid levels in both HP accumulators are OK, return the tensioners to
normal operation as follows:
11. Pressurize both tensioners from the working APVs by opening their main air valve.
Document number L6764-Z-MA-005
Revision 0
Page 34 of 63
12. Slowly extend the cylinder of the first tensioner by opening the (smaller) bypass
valve of the air inlet valve (at the accumulator top). When the cylinder is
approximately at mid-stroke, the support wire will be tensioned. Then open the air
inlet valve to the HP accumulator and close the inlet valve’s bypass valve.
13. Extend the second cylinder in the same way as the first.
14. Adjust the working air pressure for this tensioner pair to the same level as the other
pairs. Select all pairs at the (Cyberbase) Wireline Tensioners display, and fine tune
the working air pressures as necessary to return to the target total tension.
Tensioners with deviating fluid levels must be checked more frequently the next months.
Check for leaks, and also check the drain tanks to see if the fluid is escaping this way.
Document number L6764-Z-MA-005
Revision 0
Page 35 of 63
Each anti-recoil valve (which actually is a valve block) has three small filters identified
as F1, F2 and F3 in the flow diagram. The elements of these filters must be changed at
the intervals specified in the Periodic maintenance schedule.
Ear and eye protectors must be used while the filters are
changed.
Some pressure may be left at the filters, and may be bled off
when the filters are loosened.
1. Starting point: The system is shut down and all pressure vented.
3. Clean the areas around the filters, so that impurities will not easily enter the system
when the filters are unscrewed.
4. Carefully loosen and unscrew the (large) hex nut filter caps.
5. Remove the dirty elements, and check them for abnormal contamination. Also make
sure that no old seal rings remains inside the valve.
6. Install new elements of the original type, along with any new seal rings supplied with
them. Wet the seals with clean tensioner fluid before reinstallation.
7. Attach a note to each filter, stating date of change. Also write it down in the
maintenance log. Remember to open the V1 valve when done!
Filters
V1 valve
Typical anti-recoil valve, with arrows pointing at the three filter caps and the V1 valve
Document number L6764-Z-MA-005
Revision 0
Page 36 of 63
The maximum number of visible broken wires is given by the below table. The table is
reproduced from “Table 2” of ISO 4309, second edition 1990-08-15: Cranes, Wire
Ropes, Code of Practice for Examination and Discard.
Classification Group: M5
6d 30 d
4 8
“Table 2”
Example: To check if the wire is acceptable, choose a wire length of 6 times the wire
diameter (see wire diameter in the Product Data Sheet document or at the wire sheave
assembly drawings), chosen at the most worn place. If the number of visible broken
wires within the length is 4 or more, the wire must be replaced.
An Accumulated Ton Cycles (ATC) counter is included for each wire, and the result is
displayed at the Cyberbase Accumulated Ton Cycles screen display. An ATC
maintenance alarm can be set to announce when the ATC value/load has reached the
wire change limit, which alternatively can be a thorough wire inspection limit. The
controls for (re)setting the counters and (re)setting the alarm limits are described in the
Operating Instructions.
When this is manual is prepared, no accumulated wire change limit based on field
experience exists. The initial recommendation is therefore to zero all counters to when
the system is commissioned, and to inspect the wires regularly as described in the
preceding section. When the inspectors conclude that the wires need to be changed, or
a wire breaks, the accumulated value at that time must be logged. After the wires are
changed, this figure minus a suitable safety discount can be set as the new alarm limit.
From then on the monitoring system will be a good help in estimating the remaining
operating life of the installed wires.
Document number L6764-Z-MA-005
Revision 0
Page 38 of 63
The support wire has an open spelter socket in one end and a needle eye in the other.
The spelter socket is for connection to the riser tension ring, and the needle eye for the
pulling rope used during installation. When a new wire is supplied on board, the needle
eye will be at the outer end on the transport drum.
x Carefully release the riser tension ring from its parking suspension and extend all
tension cylinders exactly to mid-stroke. The tension ring will then be exactly at the
“design position” set at the initial working length calibration of the support wires
(during commissioning). Leave the tension ring here (kept in position by the wires
from the other tensioners) throughout the wire change, as this position also is used
for working length calibration at the final stages of the installation of the new wire.
x Retract the tension cylinder w the wire to be changed, just a little to slacken this one
wire, and disconnect the spelter socket from the tension ring. Connect this wire end
to the transport drum, if necessary by a pulling rope, so that this end is ready to be
reeled on the transport drum.
x Extend the tension cylinder back out to the exact mid-stroke position.
x Prepare the coiled-up excess wire length (length coiled up by the tensioner) to be
pulled through and out of the tensioner. Attach a pulling rope to the needle eye wire
end to control this end during the pulling-out, and secure the pulling rope as
necessary to remain in control.
Document number L6764-Z-MA-005
Revision 0
Page 39 of 63
x At the fixed sheave house, unscrew the six bolts of the wire anchor clamp
(“deadman”), and remove the bolts and the clamp top.
x Start removing the old wire from the tensioner by reeling in wire on the transport
drum. Follow up at the needle eye end and feed wire and rope into the tensioner.
x Install the transport drum with the new wire in the empty transport drum reel.
x Attach a pulling rope to the needle eye of the new wire, and route the rope through
the idler sheave, through the tensioner sheaves, three turns around the snubber
drum, past the open wire anchor clamp, over to a suitable utility winch, and secure
the rope end to the drum of the winch. The winch must be able to pull in the wire on
the tensioner.
x Start pulling in the wire on the tensioner by the winch, and follow up by the transport
drum reel (paying out).
x Go on pulling in until the wire is off the transport drum. Then attach a pulling rope to
the spelter socket and guide this wire end over to the riser tension ring and connect
it at the designated location for this wire.
x Assuming that the riser tension ring still is exactly at the “design position” and that
the tension cylinder is exactly at mid-stroke, reel in any slack by the winch but don’t
pull the tension ring out of position. The working wire length is now correctly
calibrated.
x While the winch keeps the wire tight at the present position, torque up the wire
anchor clamp on the wire. (See torque table at assembly drawing for fixed sheave
house.)
x Mark the wire on both sides of the clamp to make it easier to spot any slipping at
future inspections.
x Unload the pulling winch, unreel the excess wire from the winch drum, and coil it up
and secure it next to the tensioner. If there is sufficient excess length, this length can
later be utilised in a cut & slip operation.
x In the driller’s cabin, at the Cyberbase Accumulated Ton Cycles display, read and
write down the accumulated tons value for the old wire. Then zero the counter to
prepare it for counting the accumulated value of the new wire. Based on experience
from the old wire, adjust the maintenance alarm limit for the new wire as necessary,
so that the next change (or cut & slip) is announced safely and economically.
x Repeat the overall procedure for any other tensioners needing a wire change.
Document number L6764-Z-MA-005
Revision 0
Page 41 of 63
Preparations:
x Starting point: The WRT system is unloaded, the riser tension ring is suspended at
its parking place below deck, and the support wires are slack. No other work takes
place in the moonpool. A sufficiently empty transport drum on a motor-driven reel is
ready to receive the worn wire length to be removed, and suitable pulling ropes are
available. The pulling ropes must be strong enough to hold the full weight of the
wire, if the wire gets out of control.
x Check that there is sufficient excess wire coiled up by the tensioner to replace the
worn length to be removed.
x Carefully release the riser tension ring from its parking suspension, and extend all
tension cylinders exactly to mid-stroke. The tension ring will then be exactly at the
“design position” set at the initial working length calibration of the support wires.
Leave the tension ring here (kept in position by the wires from the other tensioners)
until after working length calibration of subject wire (after it has been cut).
x Retract the tension cylinder of the wire to be cut, just a little to slacken this one wire,
and disconnect the spelter socket from the tension ring. Connect this wire end to the
transport drum, if necessary by a pulling rope, so that this end is ready to be reeled
on the transport drum. Remember that the spelter socket must remain accessible, as
it later will be cut from the wire.
x Prepare the coiled-up excess wire length to be uncoiled and pulled through the
tensioner. Arrangements must be made to keep suitably tight the excess (needle
eye) wire end entering the tensioner, and to hold the entire wire if the other end gets
out of control. This may involve the use of a pulling rope at the needle eye end.
x At the tensioner’s fixed sheave house, unscrew the six bolts of the wire anchor
clamp (“deadman”), and remove the bolts and the clamp top.
Document number L6764-Z-MA-005
Revision 0
Page 42 of 63
x Continue transferring wire to the transport drum until the last worn part is suitably
past the idler sheave. Then stop the transport drum.
x Mark the place the wire is to be cut, secure both sides of the mark (by suitable
ropes), and cut the wire.
x Measure the cut length and write it down in the maintenance log.
x Cut the spelter socket from the cut length and prepare it for reinstallation at the end
of the remaining wire.
x Inspect the cut ends and look for internal corrosion and any other damage that
indicates weakening of the wire. Make a new cut at the most worn part of the cut
wire and inspect here as well. If deemed necessary, cut a small length from the wire
and have it examined by the wire manufacturer or other specialist. Write down all
input from the inspections in the maintenance log and use the info for planning the
next wire changes in a safe and cost effective way.
x Connect the spelter socket to the riser tension ring, which still is at the “design
position”.
x Using the winch, tighten up the wire from the spelter socket. Don’t tighten so much
that the tension ring is pulled out of the design position. When the wire is just tight,
the calibration of the working wire length is exactly right. Then stop the winch and
hold the wire there.
x At the tensioner’s fixed sheave house, clean the wire clamp, lubricate the six bolts,
and torque up the clamp on the wire.
x Mark the wire on both sides of the clamp to make it easier to spot any slipping at
future inspections.
x Unload the winch, unreel the remaining wire and pulling rope from the winch drum,
disconnect the rope, and coil up and secure the remaining wire next to the tensioner.
x Repeat the overall procedure for any other tensioners needing the described
maintenance.
x File the job report from the licensed wire service contractor in the maintenance log.
Document number L6764-Z-MA-005
Revision 0
Page 43 of 63
The wire sheaves (including the idler sheaves) require maintenance at the intervals
specified in the Periodic maintenance schedule. The sheave maintenance is the
following:
Definition: X = outer diameter of the support wires. This diameter is stated in the
Product Data Sheet document and/or at the wire sheave assembly drawings.
The pressure relief valves on the HP accumulator and the APVs are of different types
and must not be mixed. The different maintenance procedures are described below.
HP accumulators
Each HP accumulator is equipped with a pressure relief valve as shown in the
illustration below. The opening setpoints can be found on the belonging flow diagram.
The opening setpoint of each valve is to be checked yearly, preferably in a test bench,
and the setpoint adjusted (or valve changed) if necessary.
x Disassembly:
1. Break the thread seal
2. Unscrew the top screw cap
3. Loosen the lock nut
Document number L6764-Z-MA-005
Revision 0
Page 45 of 63
x Adjusting:
1. Apply pressure and adjust the adjusting screw until the opening pressure
is just correct
2. Depressurize
x Assembly:
1. Lock the lock nut
2. Reinstall the screw cap
3. Reinstall the lock wire and seal the wire
APVs
Each working APV is equipped with a pressure relief valve as shown in the illustration
below. The opening setpoints can be found on the belonging flow diagram.
x Pressure venting:
1. Make sure that the main isolation valve is closed before relieving the APV
from all pressure, according to the Operating Instructions
2. Vent all pressure from the APV
3. Remove the valve from the APV
x Dissasambly:
1. Break the wire lock seal
2. Remove the setscrew cover
3. Unlock locking nut
4. Turn setscrew fully counter clockwise
5. Loosen the spring housing
6. Remove spring housing, set spring, spring guide (2x)
7. Remove valve housing
8. Remove seat
Document number L6764-Z-MA-005
Revision 0
Page 47 of 63
x Assembly precautions:
1. Components must be handled carefully
2. Components must be reassembled on a test bench with all the usual facilities
available
3. New O-rings of the correct specification must be fitted on re-assembly
4. Use the correct lubricants
5. Carry out pressure leak test after re-assembly and before re-setting the relief
valve
6. All components must be clean and dry before assembly
x Assembly:
1. Reassemble the valve by reversing disassembly instructions
TIGHTENING OF BOLTS
ALL BOLTS LUBRICATED WITH
MOLYKOTE® G-RAPID PLUS
Size Torque [Nm]
Black / tZn (HDG) Stainless Steel
Thread Pitch
Property Class Property Class A
d [M] P[mm] 8.8 10.9 70 80
M8 1,25 20,6 28,4 15,4 19,8
M 10 1,5 40 56 30,8 40,7
M 12 1,75 70 98 52,8 70,4
M 14 2,0 110 156 84 112
M 16 2,0 169 238 130 173
M 18 2,5 237 332 180 240
M 20 2,5 331 465 252 337
M 22 2,5 445 626 339 453
M 24 3,0 572 804 436 581
M 27 3,0 826 1161 630 840
M 30 3,5 1127 1582 859 1146
M 33 3,5 1522 2133 1155 1543
M 36 4,0 1961 2761 1497 1995
M 39 4,0 2520 3543 1922 2560
M 42 4,5 3130 4395
Note:
Stainless steel Material Property Class 50 shall not be used; Material Property Class 80
may be used. Preferred property class in A4 is 70 which is the international available
trade property.
Black steel / tZn Material Property Class 4.6, 5.8 and 12.9 shall not be used by NOVN!
Only the given Property Classes shall be used!
Document number L6764-Z-MA-005
Revision 0
Page 49 of 63
To find the leak it is recommended to use soap water. Apply the soap water to all pipe
connections and fittings belonging to this pair of cylinders, including piping at the air
control skid. When the leak is found, deactivate this pair as described in the Shutting
down pair of tensioners section in the Operating Instructions. The system operation can
continue without interruption.
Repair the leak while the involved piping is fully depressurized. After the repair, return
the tensioner pair to service as described in the Returning pair of tensioners to
operation section (in the Operating Instructions). Procedure points that are known to be
OK or not applicable can be omitted.
Check visually for leaks at the tension cylinders. The cylinder rods are lubricated by
tensioner fluid, and as the rods are retracted and out, a thin fluid film should normally be
visible on the rod surface. If the rod is wetter than this, and fluid is seen running down
the cylinder casing, the sealing inside the cylinder is worn. In that case the entire
cylinder must be repaired or changed, and supplier must be contacted. Tension
cylinders shall not be repaired on board.
If leaks are suspected, check the fluid levels as described in the Checking fluid level in
HP accumulators section.
Also check the fluid level in the drain tanks. High level here is most likely just caused by
the late resetting of the anti-recoil valves.
Document number L6764-Z-MA-005
Revision 0
Page 50 of 63
Each tension cylinder is equipped with a position sensor of the FSG Rope Length
Transmitter type. The sensor measures the cylinder stroke and transmits an electric
position signal to the WRT system’s control system.
During installation the rope is pulled out of the box and the ring is hooked to a bracket at
the cylinder’s front end sheave house. See illustration above with arrow at the bracket.
When the cylinder later is extended, the rope will be paid out accordingly.
Bracket
Rope ring
Junction box
Inside sensor box, from Left: Encoder, drum unit, spring housing and junction box (black box).
4x nuts M8 for mounting plate.
Document number L6764-Z-MA-005
Revision 0
Page 52 of 63
The wire rope is subject to wear, and when getting splintery, damaged or broken it must be
replaced by a new drum unit of the original type.
Pos Description
1 Screws for mounting the adapter
2 Screws for mounting the encoder
3 Coupling
4 Round ring in the adapter
5 Adapter
6 Encoder
7 Drum unit
8 Spring housing
9 Bellow
10 Screws for mounting the bellow
11 Lock ring/ Plug socket
12 Pulley
13 Wire
14 Brush
15 Ring eye
Document number L6764-Z-MA-005
Revision 0
Page 53 of 63
Never release the rope after pulling it out. Free back-running wire
will damage the device and there is also a danger of injury.
Document number L6764-Z-MA-005
Revision 0
Page 55 of 63
1. Never release the rope after pulling it out. Free back-running wire will damage
the device and there is also a danger of injury.
2. Don´t pull the wire directly. The wire may be bent and this will cause trouble in
the pull-back mechanism.
3. Don´t pull the wire along of edges. The wire will be damaged.
- At the Cyberbase, or at the local control panel, the reference position of the position
indicator (encoder) must now be reset as described in the Operating instructions.
- Verify correct position indication at the local control panel and at the Cyberbase.
- At the Cyberbase operator station, re-enable the position sensor by un-checking the
Disabled for Maintenance, Position checkbox at the Tensioner display for this tensioner.
- Return the tensioner to normal operation as described in the Operating Instructions.
Document number L6764-Z-MA-005
Revision 0
Page 56 of 63
9 FAULT FINDING
In the case of malfunction, try the following solutions before contacting supplier’s service
department:
Fault Solution
x General fault. x Check detailed alarm info at the alarm
displays.
x Check all fuses.
x Check/retighten all terminal blocks and
other electrical connection points,
including earthing.
x The total riser tension is low. x Increase the working air pressures.
x One tensioner carries lower x Check and tighten air leaks.
load than the others. x Check and tighten fluid leaks.
x Reset the reference position of the
position sensor for this cylinder. (See
procedure at the description of the
Reset Position R-button in the
Operating Instructions.)
x A tension cylinder cannot be x Check the fluid level in the HP
fully extended (during accumulator, and add fluid as
testing, while the system is necessary.
unused). x Reset the reference position of the
position sensor for this cylinder. (See
procedure at the description of the
Reset Position R-button in the
Operating Instructions.)
x The compensation stroking x Adjust the working length of the support
of the tension cylinders does wires (distance between riser and wire
not take place around mid- anchor). See more info in the Changing
stroke. the support wires section.
Document number L6764-Z-MA-005
Revision 0
Page 58 of 63
x Before the storage, test the operation of each anti-recoil valve by running a test
sequence four or five times. The test sequence is explained in the Description of
controls section in the Operating Instructions.
x Verify that the entire system is shut down as described in the Operating Instructions.
(All tension cylinders must be fully retracted.)
x Go through the lubrication charts, and verify that the equipment is well lubricated.
x Apply a coating of anticorrosion oil on all unpainted surfaces, except the cylinder
rods. Coat the support wires with grease.
x Fill the HPA 100% with hydraulic fluid. If the HPA has a piston, fluid can be added on
top of the piston to evacuate all air from the HPA.
x Verify that the equipment is protected against mechanical damage, and arrange
suitable protection as necessary.
Before starting up the WRTS after storage, make sure that the fluid level in the HPAs
are calibrated according to section 5.10 Checking fluid level in HP accumulators.
Document number L6764-Z-MA-005
Revision 0
Page 59 of 63
11 SPECIAL TOOLS
No special tools are supplied or required for user maintenance.
12 SPARE PARTS
Please refer to Spare parts lists in the user manual.
Only original spare parts ordered through National Oilwell Varco (NOV) must be used,
as modifications may have been performed by NOV on standard parts. Non-modified
parts may interfere with the original performance. Use of non-modified parts will also
influence the terms of warranty.
13 LUBRICATION CHARTS
The following lubrication charts are attached in the manual’s Procedures section, and
form an integrated part of the maintenance instructions:
Check the fluid drain tanks (two tanks at each fixed sheave house).
Verify that the breather filter is in place, and write down the fluid level
in the tank. Compare the fluid level with earlier recordings and with
the recordings from the other drain tanks to spot any abnormalities.
Drain the tank manually if it is more than half full. If a tank remains
9 1 empty for a longer period; inspection of the anti-recoil valve and pipe
lines is needed. The drain tank fluid volume equals the leakage from
the HP accumulator and can be used to decide if fluid needs to be
added on the HP accumulator (at the underside of the accumulator
piston).