Professional Documents
Culture Documents
Pheonwj W Spe 0007 - 0
Pheonwj W Spe 0007 - 0
Revision : 0
PHE ONWJ
Reviewer
Table of Content
1. Scope ............................................................................................................................................. 4
2. References..................................................................................................................................... 4
4. Abbreviations ................................................................................................................................. 5
5. General Requirements................................................................................................................... 6
6. Materials ........................................................................................................................................ 6
7. Qualification ................................................................................................................................... 7
9.2 Test....................................................................................................................................1 1
1 0. Marking ........................................................................................................................................ 1 3
1 2. Documentation ............................................................................................................................ 1 3
1.
Scope
This specification covers the minimum requirements for the materials, application, inspection
2.
References
Design, manufacture, performance and testing should be in compliance with the following
codes and standard, except where otherwise specified. The following documents should form
2.1
Local Regulation and Standards
300.K/38/M.PE/1 997
Decree 84.K/38/DJ M/1 998 Inspection Guidelines for Safety on Facilities, Equipment
Activity
Regulation
Safety Audit to Inspection, Equipment and Technique
06P/0746/M.PE/1 991
used In Oil and Gas Mining and Geothermal Activities.
1 979
The above are listed only as a guide to the applicable Indonesian Acts. CONRACTOR
shall be responsible for determining all statutory requirements applicable to the scope of
2.2
Company Specification
2.3
International Standards and Codes
Except where otherwise noted, the latest edition of the following codes and standards
shall apply:
Reinforcement
ASTM C31 Making and Curing Concrete Test Specimens in the Field
ASTM C42 Obtaining and Testing Drilled Cores and Sawed Beams of
Concrete
Concrete
Concrete
in Cylindrical Molds
Concrete
Cable
The CONTRACTOR shall have readily available for use, at the request of the COMPANY
latest editions of all the Codes, Specifications and Standards necessary for the
3.
Definition of Terms
CONTRACTOR The party that carries out all or part of the design, engineering,
the CONTRACTOR.
4.
Abbreviations
5.
General Requirements
• Compressive strength of concrete shall not be less than 3500 psi (24.1 MPa) for 7 days
• Cutback length shall be of 300 ± 1 0 mm measured from the root face of the pipe, be
square to the surface, and tapered back to a slope of approximately two-to-one (2:1 ).
• Minimum thickness of the concrete will be specified but shall not be less than 25 mm.
3
3
If applicable, the particular specification will specify additional information (e.g. requirements
6.
Materials
6.1
Cement
Cement shall be Portland cement suitable for marine use, conform to ASTM C1 50 type
II or equivalent. Cement held in storage for longer than 3 months shall be tested in
accordance to standards, prior to use. The alkali content shall be less than 0.6 percent.
The tricalcium-aluminate (C3A) content shall be less than 8%. Cement that has hardened
Tests certificates from the cement seller shall be supplied for every cement delivery to
the coating yard site. If no alkali percentage is stated on the certificate, an additional
6.2
Aggregates
Materials shall be clean, free of clay, and injurious amounts of acid, alkalis, oil, sulfates,
Size of fine aggregate shall be between 0.1 5 mm and 4.75 mm. Size of coarse
aggregate shall be between 0.1 5 mm and 9.5 mm. Fine aggregate shall be tested for
shall have COMPANY approval and comply with relevant standards i.e. ASTM C330 for
COMPANY reserves the right to reject any aggregate not deemed acceptable by virtue
6.3
Water
Water shall be clean potable or water which free from contamination and conform to
6.4
Concrete Admixtures
6.5
Reclaimed Concrete
The use of reclaimed materials shall only be allowed provided it can be demonstrated to
COMPANY’s satisfaction that there is no detrimental effect to the final concrete product
and that it is applied within the 30 minute allowable period since mixing.
Secondary mixing of the freshly batched concrete with the reclaimed material shall
follow immediately and should produce a homogeneous cohesive mixture. When breaks
in the operation for whatever cause or reason exceed 30 minutes then the reclaimed
6.6
Steel Reinforcement
sectional area of the concrete coating. The minimum longitudinal reinforcement shall be
The reinforcement shall be either the steel welded wire or cage type. Reinforcement
steel shall conform to ASTM A82 or ASTM A61 5 (or equivalent), and shall be galvanized
The steel welded wire fabric shall be minimum wire gauge 2.0 mm and conform to
The reinforcement for cage type shall be in the form of spirally wound cages having a
continuous hoop wire with a number of straight longitudinal bars evenly spaced around
the spiral and welded at each wire intersection. Alternatively, the continuous hoop wire
may be replaced by single circumferential hoop. The spacing of the longitudinal bars
shall be between 50 and 250 mm but not less than four longitudinal bars (at
approximately equal spacing) shall be provided. The circumferential hoop spacing shall
longitudinal and 6 mm for circumferential. The welding of the materials shall result in a
steel fabric in accordance with ASTM A1 85. Welding shall be in accordance with the
6.7
Spacer and Rubber End Ring
Spacer shall be installed to precise dimensions that allows for the reinforcement to be
set evenly and at the correct distance from the corrosion protection coating. Plastic
spacer shall conform to ASTM D1 248 or equivalent. Rubber end ring shall be fitted at a
set distance each end of the pipe to allow for the correct concrete cutback distance.
7.
Qualification
Before commencement of the work, all necessary tests and trials shall be performed to
Concrete mixing, not less than 4 days old, shall be tested in accordance with ASTM C642 or
equivalent to determine the density of the concrete and the saturated weight after
the expected correlation between the fresh concrete density and dry density.
Compressive strength test for 7 days strength and 28 days strength shall be performed in
accordance with ASTM C873 or equivalent. Samples of proctor cylinder shall be prepared in
Subsequent to selection of the mix, trials shall be performed by concrete coating application
on lengths to test the placing procedures of the concrete and the following determined:
Qualification shall include the method of curing, repair, and stripping. Stripping shall be
demonstrated that does not damage the adjacent corrosion protection coating. Repair
materials used for concrete repairs shall be tested for compressive strength as determined by
28 day strength results. The minimum strength to be achieved shall be that of the strength
• electrical continuity test between pipe and anode which the electric resistance is less than
Ω
0.1 0 .
The above procedure qualification details shall be furnished to COMPANY for approval prior to
8.
Coating Application
8.1
Pipe Preparation
Pipe identification shall be preserved by maintaining identity of each line pipe. Internal
identification words and numerals shall be re-stenciled with paint inside pipe if
necessary.
Prior to placement of reinforcement, the corrosion protection coating of each pipe shall
be carefully inspected visually and by holiday detectors. Foreign matters, if any, shall be
removed from the surface of the corrosion protection coating. Testing for coating flaws
shall be in accordance with NACE RP0274. If damages are found, they shall be repaired
in accordance with the relevant specification issued for this purpose before start of the
work.
8.2
Reinforcement Application
Reinforcement shall be placed around the pipe in such a manner to cover the whole pipe
length or sections to be concrete coated. The reinforcement shall not protrude beyond
the concrete coating at ends. The reinforcement shall not contact the corrosion
protection coating.
Splicing shall be done either by binding with soft steel wire having a minimum diameter
of 1 .5 mm and an overlap of three meshes or pre-bend the end of the wires on the new
roll into hooks and then engage it in the end of the preceding roll and pressed short.
Wire fabric in rolls (ribbon mesh) shall be provided with a spiral lap of one mesh.
A minimum of one layer reinforcement shall be used and it shall be placed as close as
possible to the center of the concrete coating. If more than one layer of the
reinforcement is used, the layer shall be evenly distributed throughout the concrete
thickness. The reinforcement shall not contact to the pipe corrosion coating surface.
circumference shall be smooth and free of undulations and knobs at the ends.
8.3
Concrete Application
8.3.1
Equipment
method. The casting method shall not be used. The method shall ensure the
The mechanical equipment used for performing the concrete coating shall be
of all materials.
mixing, where all feeds are accurately controlled and percentages of mixer
All coating machinery and pipe moving wheels or rollers shall be equipped with
rubber or hard fiber wheels. Knurled steel or other type wheels, capable of
8.3.2
Concrete Mixing
The calibration of the weighing devices and the water meter shall be checked at
the beginning of each shift work. The moisture content of the aggregates used
8.3.3
Concrete Placing
Concrete shall be placed within 30 minutes from the time of mixing and shall be
loss. Concrete containers shall always be kept clean and free from hardened or
in the right location. No pass shall be stopped for more than 30 minutes. In case
of any interruption beyond 30 minutes, coating shall be removed and entire joint
shall be re-coated.
practices.
8.3.4
Curing
from the effects of sunshine, drying, winds, rain or running water, and its
efficiency particularly under adverse climatic conditions. Coated pipe shall not be
The use of water sprays in the curing process is not permitted if freezing
is wrapped continuously over the last concrete layer, and tied securely in place
with band. The wrap shall be applied under tension with a minimum 50 mm
overlap between sheets. Interface between the concrete and steel at the pipe
If the curing process involves steam, then it shall demonstrate that the process
shall the pipe wall be allowed to reach a temperature that would cause any
For curing by sealing compound, the sealing compounds shall conform to ASTM
instructions. The ingredients of any such compound shall be non-toxic and non-
inflammable and shall not react with any ingredient of the concrete, the
8.3.5
Repair and Stripping
If the damage area is less than 0.8 m² in any 3 m length of pipe may be repaired
by hand patching providing that such repairs are carried out within 4 hours of
concrete application. If the damage area is more than 0.8 m² but less than 25%
of total coating, repairs shall be made using gunite. The concrete remaining shall
cracked or broken concrete at the point of coating damage, wetting the fresh
surface of the broken coating (unless the coating is still too ’green’ to require it),
and trowelling a stiff mixture of cement, water and aggregate, of the same
materials and proportions as the coating, into and through the reinforcing. This
mixture shall be built up until the surface is level with the coating around the
repair. The pipe shall then be carefully laid in a position where it shall be allowed
to moist cure for a minimum of 36 hours. The resulting coating shall be equal in
coating.
Concrete cracks that are in excess of 1 .5 mm in width and extend over 1 80°
circumferentially around the pipe or cracks that are over 300 mm in length
longitudinally along the pipe irrespective of width shall be repaired. Repairs shall
be made by chiseling the crack out to width of not less than 25 mm throughout
the length of the crack. The crack shall be repaired with materials similar to that
from which the coating is made and in a manner similar to that outline above.
The repairs shall be kept moist and allowed to remain undisturbed for a period at
least 36 hours.
Surface damage shall not be considered a defect if the total surface area of
damage per pipe is less than 0.1 m² with damage depth does not exceed 20%
8.4
Anode Installation
9.
Inspection and Test
9.1 Inspection
All materials shall be certified by means of the manufacturer’s certificate of analysis for
All stages of the work shall be subject to full time inspection by COMPANY’s Inspector.
Coating Applicator shall give reasonable access and facilities required for inspection to
the COMPANY’s Inspector. COMPANY reserves the right to require additional testing at
9.2
Test
9.2.1
Aggregate
9.2.2
Diameter Measurement
The outer diameter of each pipe joint shall be measured, either continuously by
reasonably spaced, along the length of the concrete coating. Diameter tolerance
shall be ± 1 0 mm. The concrete coating shall be concentric on the pipe. This
girth measurement shall be recorded and the average shall be used in the
the tolerances of pipe diameter and weight and location of reinforcement shall
be taken into account. Concrete shall be placed within 30 minutes from the time
of mixing. If the tolerances and conditions for corrective actions cannot be met,
9.2.3
Weighing of Pipe
between -5% and +7% of calculated total pipe weight (steel pipe, corrosion
9.2.4
Concrete Density and Water Absorption
Concrete mixing, not less than 4 days old, shall be tested in accordance with
ASTM C642 or equivalent to determine the density of the concrete and the
concrete coating shall not absorb water more than 5% of its weight in water
immersion. The test shall be taken for every 1 00 joints of production or once per
9.2.5
Negative Buoyancy
The negative buoyancy tolerance for each individual concrete coated pipe shall
9.2.6
Reinforcement
For one pipe chosen at random out of each 1 00 (can be chosen by COMPANY),
the freshly placed concrete shall be cleared away down to the corrosion coating
for an area 1 00 mm wide and 250 mm long in the longitudinal direction. This
If the reinforcement is not positioned correctly, the pipe shall be rejected and
recoated. Each pipe in succession shall be inspected and rejected in this manner
reinforcement steel and the pipe or the anode (where fitted) are electrically
discontinuous. Every pipe joint with an anode attached shall be checked and the
9.2.7
Compressive Strength
ASTM C31 and ASTM C39 or equivalent. Samples of the fresh concrete mix
shall be taken from the feed. One set of four test cylinders shall be taken for
One to be tested at 7 days and two at 28 days. The fourth cylinder is spare.
In the event that concrete cylinders do not meet the specified strength,
COMPANY shall have the right to order additional testing of the suspect pipe
coatings or to reject the pipe joints coated with concrete from the same batch.
9.3
Supplementary Test
The particular specification will indicate which supplementary testing shall be applied:
9.3.1
Drilled Core
If specified, with reference to ASTM C42, 6 core samples shall be taken from
one joint for every 1 00 joints produced. The joints can be chosen by COMPANY.
The cores shall be drilled out of the concrete coating at the latest 3 days after
with ASTM C39 or equivalent. Cores shall be cured alongside the parent pipe at
all times. No single core result shall be below 80% of the specified proctor
The cores shall be drilled at 3 locations on the pipe body; between 1 and 2 m
from each end, and within the middle. The set of 3 cores for each testing age
If any of the test cores fail, the coating cannot be accepted and pipes on either
side of the reject (in the coating sequence) shall then be tested to the same
parameters as above. This operation will continue until acceptable pipes are
found.
If the average strengths are below the minimum requirements, a further two
pipes from the same production shall be tested. If the average using the original
three results plus the additional six cores satisfy the strength requirements, the
If any of the new cores fail to meet the minimum requirements, or the new
pipe basis.
9.3.2
Impact Testing
impact testing shall be scrapped and not repaired or incorporated in the pipeline.
The test shall be carried out 90° to pipe axis at one location. Impact blows (5
times) shall be directed on the same location. Hammer should have a vertical
weight shall be 2.68 ton and/or 1 .84 ton with 1 0 mm radius of striker edge.
The concrete coated test pipe shall be rigidly supported from the rear over its
full length by moist sand and shall be held rigidly at its ends by wooden cradles
The point of impact on the concrete shall be at the 3 o ’clock position. The pipe
shall be supported so that impact of the concrete is made when the hammer is
are satisfied:
• spalling has not occurred further than 300mm from the impact location.
9.3.3
Shear Testing
concrete coating. Shear testing is performed to ensure the shear strength of the
bond between the concrete weight coating and corrosion protection coating
would withstand the large tensions that the pipe would endure during
9.3.4
Bend Testing
If specified, bend testing is required to ensure that the coatings can withstand
the loads expected during installation. The bending radius or degree of bend
shall represent that the pipeline will undergo during installation. If there is no
1 0. Marking
All marking on inside of pipe in the as received condition shall not be removed. Coating
If specified in the particular specification, concrete coated pipe shall be color-coded in order to
readily identify the different categories of pipe thickness, coating thickness and attachments.
The paint shall be marine paint and suitable for long-term storage at the designated final
delivery location. These bands shall be 50mm wide starting at 1 50mm from each end of the
concrete coating. The bands shall be applied immediately after concrete curing.
Refer to PHEONWJ -W-PRC-0009 for the pipe handling, storage and transportation.
1 2. Documentation
At completion of work, Coating Applicator shall submit a MDR that contain, as a minimum:
• certificates of compliance stating that the coating has been manufactured, applied,
inspected, and tested in accordance with the requirements specified, and the results of the
coating tests and other required tests have been found to conform to such requirements.