Sop Battery Rectifier Replacement

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

STANDART OPERATIONAL

PROCEDURE

TOPIC REPLACEMENT BATTERY RECTIFIER


AREA RECTIFIER CABINET
SCOPE
a. Administration proces WO/RFC
b. Preparation and check visual
c. Preparation Tools
d. Replacement proces
e. Check setting rectifier
f. Measurement result after replacement
g. Documentation

PROCEDURE

1. Have work order / RFC


2. Have Permit enter site
3. Coordination with Lider regional ROH and NOC Power

TYPE SITE PLN WITH GENSET


1. Prepare Tools
2. Check Rectifier condition no alarm major will be impact during battery replacement.
3. Check visual battery existing save condition for working
4. Running Genset for suply power rectifier
5. Turn Off Fuse Battery First bank
6. Replace battery First bank
7. Check result connection battery and replacement already correct.
8. Measure Voltage 12 VDC and 48 VDC fisrt bank
9. Turn ON Battery fuse FIRST bank battery.
10. Do step 5 – 9 for Next bank
11. Check Setting BCL 10% for VRLA and 20% for fast charging
12. Check setting LLVD 46 VDC
13. Check BLVD 44 VDC
14. Make sure battery already charging >80%
15. Switch off genset and tranfer load to PLN
16. Complete Documentation after Replacement
17. Call Cluster lider and NOC Power all replacement completion
18. Make sure all rectifier, environment site all OK before leave site
TYPE SITE PLN ONLY WITH BATTERY BANK MORE THEN 1 BANK

1. Prepare Tools
2. Check Rectifier condition no alarm major will be impact during battery replacement.
3. Check visual battery existing save condition for working
4. Turn Off Fuse Battery First bank
5. Replace battery First bank
6. Check result connection battery and replacement already correct.
7. Measure Voltage each block 12 VDC and 48 VDC fisrt bank
8. Turn ON Battery fuse FIRST bank battery.
9. Do step 5 – 9 for Next bank
10. Check Setting BCL 10% for VRLA and 20% for fast charging
11. Check setting LLVD 46 VDC
12. Check BLVD 44 VDC
13. Make sure battery already charging > 80%
14. Complete Documentation after Replacement
15. Call Cluster lider and NOC Power all replacement completion
16. Make sure all rectifier, environment site all OK before leave site

TYPE SITE PLN ONLY WITH BATTERY 1 BANK

1. Prepare Tools
2. Check Rectifier condition no alarm major will be impact during battery replacement.
3. Check visual battery existing save condition for working
4. Turn Off Fuse Battery First bank
5. Replace battery First bank
6. Check result connection battery and replacement already correct.
7. Measure Voltage each block 12 VDC and 48 VDC fisrt bank
8. Turn ON Battery fuse FIRST bank battery.
9. Check Setting BCL 10% for VRLA and 20% for fast charging
10. Check setting LLVD 46 VDC
11. Check BLVD 44 VDC
12. Make sure battery already charging > 80%
13. Complete Documentation after Replacement
14. Call Cluster lider and NOC Power all replacement completion
15. Make sure all rectifier, environment site all OK before leave site