Professional Documents
Culture Documents
Data - Philip
Data - Philip
DATA
The evaluation of the LEV system design in the Lualhati Building, spanning from the
ground to the third floor in UE Manila, encompasses the assessment of ventilation and exhaust
rates in designated rooms or areas, along with an evaluation of the construction methods and
materials used in those areas. This evaluation aims to ensure that the LEV system is designed
to provide adequate ventilation and exhaust rates, effectively capturing and removing
contaminants from the air. Additionally, the construction methods and materials used in the
identified areas will be evaluated to ensure that they are appropriate for maintaining the integrity
and effectiveness of the LEV system.
The areas to be evaluated are the ventilation and exhaust system of the following areas
in the building.
A. Ground Floor
Welding Room
Male Comfort Room
Female Comfort Room
Chaplain’s Restroom
B. Second Floor
Canteen
CE Tool Room
EE Tool Room
Male Comfort Room
Female Comfort Room
Faculty (Male and Female) Restroom
Dean’s Restroom
Staff Restroom
C. Third Floor
Male Comfort Room
Female Comfort Room
Qrequired =
(
2000 CFM Welder
Welder 10000 f t 3 )
( 662 f t 2 ) ( 17.5 ft )
Qrequired =2317 CFM
Therefore, comparing the value of the required CFM to the capacity of the installed unit
in the welding room, it is observed that the installed capacity is larger than the required flow
rate. The percent difference is computed below.
Qinstalled > Qrequired
Q −Q required 6270 CFM −2317 CFM
%difference= installed = =63 %
Q installed 6270CFM
The air velocity based on the capacity of the installed unit can be computed using the
computation below. According to Air Quality Engineering (2017), the recommended air velocity
should be 100 fpm for welding applications or rooms.
Qinstalled 6270CFM
V supply = =
A supplylouvre ( No . ofLouvres)
0.45 m ×0.45 m (
3.28 ft 2
1m
(2))
V supply =1439.01 fpm
Qinstalled 6270 CFM
V exhaust = =
( )
2
A exhaustlouvre (No . ofLouvres) 3.28 ft
0.32m ×0.32 m (4)
1m
V exhaust =1423 fpm
Therefore;
V supply >V recommended
V supply −Qrecommended 1439.01 fpm−100 fpm
%difference= = =93 %
V supply 1439.01 fpm
Also;
V exhaust >V recommended
V exhaust −Q recommended 1423 fpm−100 fpm
%difference= = =93 %
V exhaust 1423 fpm
The table below shows the required CFM and the capacity of the installed unit in the
welding room according to Air Quality Engineering.
Table 1. Required and Installed Ventilation Rates for Welding Room
Roo Minimum Installe Percent Duct Recommend Percent
m Recommend d unit Differenc Velocit ed Velocity Differenc
Area ed Capacit e in y e in
Ventilation y terms of (Suppl terms of
Rate CFM y) fpm
Supply 662 2317 CFM 6270 63% 1439.0 100 fpm 93%
ft2 CFM 1 fpm
Exhau 662 2317 CFM 6270 63% 1423 100 fpm 93%
st ft2 CFM fpm
Based on the table above, the installed unit capacity is larger than the recommended
ventilation rate. The installed unit in the welding room is larger by 63% which is considered as
overly designed by the designers. The same procedure was done to the exhaust rate of the LEV
system in the welding room.
According to the principle of continuity, the general goal is to balance the volumetric flow
rate of the exhaust and the supply of an LEV system. Based on the capacity of the installed unit
in the building, the supply – exhaust relationship is considered balanced.
Qsupply =Qexhaust
6270 CFM=6270CFM
The figure above shows the floor plan of the welding room with the actual dimensions of
each component of the existing duct design.
NORTH
WEST EAST
SOUTH
The table above shows the locations as well as the area of the restrooms that are
provided with exhaust systems. The recommended exhaust system for the restrooms are to be
compared with the unit capacity installed in the building.
The table below shows the minimum required exhaust rate for different types of rooms.
Table 5. Minimum Exhaust Rates
For the Dean’s Restrooms located on Second Floor West Side (Private)
The recommended value is 25 – 50 CFM per unit. Considering that the restrooms are
frequently used, the considered value should be 50 CFM instead of 25 CFM.
50 CFM
Qreq = ( 1unit )=50 CFM
unit
Upon research, it is identified that the capacity of the exhaust unit (Niagara Nia120) for
the private restrooms installed in the building has a capacity of 70 CFM (niagarafans.com, n.d.).
Qinstalled =70 CFM
The same procedure can be done to the other restrooms to get the required CFM. The
table below shows the comparison of the required CFM and the installed CFM of the restrooms.
Table 6. Summary of Comparison of Exhaust/ Ventilation Rate
Floor Location Area Descriptio No. of Total Installed Percentage Remarks
East West m2 ft2 n Units Require Unit Difference
(Toilets d Capacity (%)
, Exhaust (CFM)
Urinals Rate
) (CFM)
1 Male - 25. 27 Public 11 770 424 44.94 Underdesign
Restroo 5 4
m
Female - 50 53 Public 8 560 424 24.29 Underdesign
Restroo 8
m
Chaplai - 3.3 36 Private 1 50 70 28.57 Overdesign
n’s 1
Restroo
m
2 Male - 34 36 Public 12 840 424 49.52 Underdesign
Restroo 6
m
Female - 45 48 Public 10 700 424 39.43 Underdesign
Restroo 4
m
- Male 26 28 Public 11 770 424 44.94 Underdesign
Restroo 0
m
- Female 33 35 Public 10 700 424 39.43 Underdesign
Restroo 5
m
- Dean’s 3.5 38 Private 1 50 70 28.57 Overdesign
Restroo
m
- Male 8 86 Public 3 210 424 50.47 Overdesign
Faculty
Restroo
m
Female 8.3 89 Public 3 210 424 50.47 Overdesign
Faculty
Restroo
m
- Staff 2.2 24 Private 1 50 70 28.57 Overdesign
Restroo
m
3 Male - 34 36 Public 12 840 424 49.52 Underdesign
Restroo 6
m
Female - 45 48 Public 10 700 424 39.43 Underdesign
Restroo 4
m
- Male 26 28 Public 11 770 424 44.94 Underdesign
Restroo 0
m
- Female 33 35 Public 10 700 424 39.43 Underdesign
Restroo 5
m
Manner of Construction for Comfort Rooms (from Ground Floor to Third Floor)
The duct work in comfort rooms from the ground floor to third floor will be examined and
observed below.
The table shown below is the summary of the collected data measured in each comfort
room required.
Table 7. Summary of Measured Data of Comfort Rooms from Ground Floor to Third Floor
AIR AIR
TEMPERATURE,
TEMPERATURE, VELOCITY, VELOCITY,
ROOM degC (close
degC (2ft distance) m/s (close m/s (2ft
distance)
distance) distance)
GROUND MALE CR 21.5 31.5 - -
FLOOR FEMALE CR 21.5 31.5 - -
MALE CR 30.1 30.3 1.17 0.15
FEMALE CR 30.4 30.5 1.17 0.15
MALE CR
near 31.6 31.6 1.17 0.15
ELEVATOR
2ND FLOOR FEMALE CR
near 31.6 31.6 1.17 0.15
ELEVATOR
CR near
DEAN’S 31 31 1.17 0.15
OFFICE
3RD FLOOR MALE CR 32.5 32.5 - -
FEMALE CR 32.4 32.4 - -
MALE CR
near 31.8 31.8 - -
ELEVATOR
FEMALE CR 31.8 31.8 - -
near
ELEVATOR
West East
South
Figure 4. Male and Female Comfort Rooms in Ground Floor
with direction
The table presented below presents the summary of hood distances from the walls.
Vent (Direction)
By observing the construction of the exhaust systems in all of the comfort rooms in
Lualhati Bldg., it is obvious that all ducts leads to the outside. The direction of air flow in the
exhaust systems leads to the outside of the building for its release.
According to ASHRAE (2007), the minimum ventilation and exhaust rate for electrical
equipment rooms (EE Room) is 0.06 CFM/ ft 2 and since the Tool Rooms in the building also
serves as storage rooms for the tools and other equipment the ventilation rate required for
storage rooms is considered with 0.12 CFM.ft2 of required flow rate. Therefore,
CFM
Qreq =0.06 ( Room Area )
f t2
For the EE Room (1st Floor):
CFM
Qreq =0.06 2
( 112 f t 2 )=6.72 CFM
ft
Upon research, it is identified that the exhaust/ ventilation unit installed in the tool rooms
and the EE rooms are the Niagara Nia2000 with 424 CFM capacity and the Niagara Nia120 with
the capacity of 70 CFM. The table below shows the summary of the required exhaust rate and
the installed unit capacity of the aforementioned rooms.
Table 11. Summary of Exhaust Rates for the EE and Tool Rooms
Area Minimum
Total Required Percent
Required Installed Unit
Floor Room Exhaust Rate Difference Remarks
m 2
ft 2
Exhaust Rate Capacity (CFM)
(CFM) (%)
(CFM/ft2)
1st EE Room 10.4 112 0.06 6.72 70 90.4 Overdesign
Tool Room
65.8 708 0.12 84.96 424 80.0 Overdesign
(Electronics)
2nd Tool Room
65.8 708 0.12 84.96 424 80.0 Overdesign
(Electrical)
EE Room 15.7 169 0.06 10.14 70 85.5 Overdesign
3rd EE Room 15.7 169 0.06 10.14 70 85.5 Overdesign
Recommended
Floor Room Height as Per Actual Height Remarks
OSHA
Table 14. Comparison between the recommended and actual distance from the wall of the
exhaust hood of the Tool/ EE Room
Recommended Actual Distance
Floor Room Direction Distance from the from the Wall , m
Wall , in (in)
North 6 0.6 (23.6)
East 6 1.4 (55.1)
1 EE Room
West 6 2.3 (90.55)
South 6 0.4 (15.7)
North 6 1.5 (59.1)
East 6 2.2 (86.6)
ECE Tool Room
West 6 3.3 (129.9)
South 6 1.5 (59.1)
North 6 1.5 (59.1)
East 6 2.2 (86.6)
2 EE Tool Room
West 6 3.3 (129.9)
South 6 1.6 (62.9)
North 6 1.2 (47.2)
East 6 0.5 (19.6)
EE Room
West 6 0.5 (19.6)
South 6 2.2 (86.6)
North 6 1.2 (47.2)
East 6 0.5 (19.6)
3 EE Room
West 6 0.5 (19.6)
South 6 2.2 (86.6)
Source: lg.com
Since there are three units of air conditioners in the canteen. The summation of the flow
rate must be taken to solve for the total installed supply air flow rate in the room.
Qinstalled =600+600+600=1800 CFM
To evaluate the designed capacity of the supply air in the canteen, the required
ventilation rate must be identified first.
Table 16. Required Ventilation Rate for canteen
Based on the table above, the required ventilation rate must be 0.18 CFM per ft2. Solving
for the total required:
CFM
CF M req =0.18 2
( 1775 f t 2 )=319.5 CFM
ft
Exhaust Air for Canteen
The exhaust system is used for the kitchen inside the canteen. The figure below shows
the plan for the exhaust system in the canteen. The kitchen has an area of 16m2 or 172ft2.
The table below shows the summary of the computed CFM in comparison with the
installed capacity of the units installed.
Table 18. Comparison between the Required and the installed CFM of the supply air in
canteen
Roo Minimum Installed Percent Remarks
m Recommended unit Difference
Area Ventilation Capacity
Rate
Supply 1775 319.5 CFM 1800 82% Overdesign
(Canteen) ft2 CFM
Exhaust 172 ft2 120.4 CFM - - Suggested
(Kitchen) capacity
The table below shows the summary of all the exhaust and ventilation rate of the rooms
in the first to third floor of Lualhati Building.
Table 19. Summary of Ventilation and Exhaust Rates
Location Ventilation Exhaust
Total Total
Require Installed Percenta Require Installe Percentag
Floor d Unit ge d d Unit e
East West Remarks Remarks
Exhaust Capacity Differenc Exhaust Capacit Difference
Rate (CFM) e (%) Rate y (CFM) (%)
(CFM) (CFM)
Male
- - - - - 770 424 44.94 Underdesign
Restroom
Female
- - - - - 560 424 24.29 Underdesign
Restroom
1 Chaplain’s
- - - - - 50 70 28.57 Overdesign
Restroom
Welding Overdesig 2317 6270
- 2317 6270 63% 63% Overdesign
Room n CFM CFM
EE Room - - - - - 6.72 70 90.4 Overdesign
Male
- - - - - 840 424 49.52 Underdesign
Restroom
Female
- - - - - 700 424 39.43 Underdesign
Restroom
Male
- Restroo - - - - 770 424 44.94 Underdesign
m
2 Female
- Restroo - - - - 700 424 39.43 Underdesign
m
Dean’s
- Restroo - - - - 50 70 28.57 Overdesign
m
Male
- - - - - 210 424 50.47 Overdesign
Faculty
Restroo
m
Female
Faculty
- - - - - 210 424 50.47 Overdesign
Restroo
m
Staff
- Restroo - - - - 50 70 28.57 Overdesign
m
Tool Room
- - - - - 84.96 424 80 Overdesign
(Electrical)
Tool Room
(Electronic - - - - - 84.96 424 80 Overdesign
s)
EE Room - - - - - 10.14 70 85.5 Overdesign
Overdesig Suggested
- Canteen 319.5 1800 82% 120.4 - -
n capacity
Male
- - - - - 840 424 49.52 Underdesign
Restroom
Female
- - - - - 700 424 39.43 Underdesign
Restroom
Male
3 - Restroo - - - - 770 424 44.94 Underdesign
m
Female
- Restroo - - - - 700 424 39.43 Underdesign
m
EE Room - - - - - 10.14 70 85.5 Overdesign
11.5 ft
11.5 ft
Figure 8. Separation Distances and Location of the Supply Diffuser
Height of Supply Diffuser
The supply air diffusers or grilles are typically installed at a height of 7 to 9 feet (2.1 to
2.7 meters) above the finished floor level. This height helps to distribute the air evenly across
the occupied zone and ensures that it reaches the breathing zone of the occupants (ASHRAE,
2017).
The figure below shows the actual height of the diffuser in the canteen.
The table below shows the comparison of the actual supply diffuser to the recommended
height given by ASHRAE.
Table 20. Comparison between the recommended height of the supply diffuser
Room Canteens
Recommended Height 7 - 9 ft (2.1 – 2.7 m)
Actual Height 8.73 ft (2.66 m)
Remarks The actual height is inside the suggested range
Height of the Hood (Exhaust)
The height of the hood according to OSHA (1926.353), must be atleast 1.8 meters or 6
feet high. During the actual measurement in the Canteen room, the hood is still not installed but
the duct is already in place. The measured height for the duct is 2.6 m or 8.7 feet. Logically
speaking, the hood of the exhaust system will have a room of 0.8 m or 2.7 feet for installation
and will still be within the range of the recommended height.