PM/PB Series

Microprocessor Panel Meter


Operation Manual

No.16, Tzuchiang St., Tucheng Industrial Park, New Taipei City 236, Taiwan
Tel: 886-2-22696789 Fax: 886-2-22686682
e-mail: info@fine-tek.com http: //www.fine-tek.com 08-PBXXX-B1-EM,01/21/2013
MENU 1. Product Introduction
PB-1470, PB-1471, PB-1570, PB-2471 are bargraph panel meters, with both
numeric display and analog bargraph display, perform signal indication and
1. Product Introduction 3. Program Settings process control. MG series can accept various different signal inputs, digital
1.1 System Block Diagram
numeric display could be set to any unit range as required by the user,
3.1 Program Settings Flowchart
3.2 Input Buttons
examples, kg/cm2, bar, cm and kg. This feature is very useful and suitable for
2. Operation Panel, 3.3 Input Signal Module
various electrical and medium measurement controls in various industries.
Technical Specification & Settings Method
PM-1430, PM-1530, PM-2430 series does not include bargraph,
& Installation Dimension 3.4 Program Commands List PM-1430 is 4 digit display panel meter, PM-1530 is 5 digit display panel meter.
3.5 Input Signal Settings PM-2430, PB-2471 features 2 channel independent input signals capability and
2.1 PB-1471 2 channel signal outputs. Modbus communication can be downloaded from
2.1.1 Operation panel 3.5.1 Diagram
http: //www.fine-tek.com
2.1.2 Technical Specifications 3.5.2 Input Signal & Settings Table
2.1.3 Relay Outputs 3.5.3 Current Input Example Feature :
2.1.4 Exterior Dimensions 3.5.4 Non-linear feature settings Accept all kinds of process signals: 0~20mA, 4~20mA, 20~0mA, 20~4mA,
2.1.5 Panel Cutout Dimensions
0~10V, 0~5V, 1~5V, 0~20V, 0~200V, also possible to use in non-standard
3.6 Output Signal Settings
input signal ranges. Continuous capacitance level transmitter.
2.1.6 Terminal Arrangements 3.6.1 Optional Relay Output Settings
2 / 4 / 6 / 8 (PB-2471) sets of replay outputs and LED indication on front
2.2 PB-1470 / PB-1570 3.6.2 Analog Output Settings
panel face.
2.2.1 Operation panel
2.2.2 Technical Specifications
4. Program Settings Example PM / PB series provide optional volume conversion feature, ideal for use in
4.1 Diagram of Setting Values non-conventional tank level measurement.
2.2.3 Relay Outputs
2.2.4 Exterior Dimensions 4.2 Program Settings Example Optional analog signal output for every signal input.
2.2.5 Panel Cutout Dimensions 4.2.1 Example 1 (PB-2430, PB-2471 have dual inputs and dual outputs)
2.2.6 Terminal Arrangements 4.2.2 Example 2 Varity of signal input signals. (refer to ordering guide).
2.3 PB-2471 4.2.3 Example 3 Readable range is -1999~9999 (4 digits) or -19999~32767 (5 digits).
2.3.1 Operation panel Input power supply is AC85V~AC265V or dc18~36V.
5. Frequently Asked Questions 3 input button control, easy operations.
2.3.2 Technical Specifications
2.3.3 Relay Outputs & Troubleshooting
2.3.4 Exterior Dimensions 1.1 System Block Diagram
2.3.5 Panel Cutout Dimensions
2.3.6 Terminal Arrangements ~ Excitation
AC Power =
2.4 PM-1430 / PM-1530
2.4.1 Operation panel

Micro processor
2.4.2 Technical Specifications Current Input A
Voltage Input D
2.4.3 Relay Outputs Control Panel
2.4.4 Exterior Dimensions
2.4.5 Panel Cutout Dimensions Data Storage E2 PROM
2.4.6 Terminal Arrangements
RS485
2.5 PM-2430 D
A Voltage Output
2.5.1 Operation panel
2.5.2 Technical Specifications . Attention: PM / PB series functions are the Current Output
same but may have different outlook, SP1
2.5.3 Relay Outputs all diagrams in this manual is based SP2
2.5.4 Exterior Dimensions on the outlook of PB-1471
SP3
2.5.5 Panel Cutout Dimensions 4 or 6 relay contacts
SP4 to output signal.
2.5.6 Terminal Arrangements
SP5

SP6
-01- -02-
2. Operation Panel / Technical Specification /
& Installation Dimension
2.1 PB-1471

2.1.1 Operation Panel 2.1.2 Technical Specifications 2.1.4 Exterior Dimensions 2.1.5 Cutout Dimensions
Display
4 digits, 0.36" 7 segment red LED display.
101 segment LED red bargraph display. 48
6 (max.)
F0.6
Relay Display range: -1999~+9999 45G0 10 (min.)
SP
6 Indicator Input Signal
5
4 Range: 0~20mA, 4~20mA, 20~0mA, 20~4mA,
3
101 LED 0~10V.
2
1
Bargraph Display (Refer to Ordering Information for more types)
Accuracy: 0.1%FS or A1 digit
UP Temperature coefficient: 200ppm/BC 144 144 135.5 138F1
G0

SHIFT
ADC resolution: 4-1/2 digit
Sampling Rate: 4 samples/second
ENTER Relay Contact:
4 or 6 relays 3A 250VAC or 5A 30VDC
(N.C. / N.O. jumper selectable)
Digital Working Condition:
Display
-20~70BC (20% to 90% RH non-condensed) 9 111 14 10
Storage Condition: (min.)
FlneTek -25~75BC (20% to 90% RH non-condensed)
Power Supply: ( u n i t:m m )
AC85V~AC265V or DC18V~DC36V 2.1.6 Terminal Arrangements
Switching Power Supply
Power comsumption: 9VA
Insulation Voltage: >AC1500V/min EXC 24V 1 19 Isolated +24V
2 Isolated GND
Insulation Resistance: >100MW/500Vdc/min GND
3
20
Volt Input Signal 21 Isolated analog O/P+
Optional Output (Isolated): Current Input Signal 4 22 Isolated analog GND
2.1.3 Relay Outputs *Analog Output: Signal GND 5 23 (Option)
6 24
0~20mA, 4~20mA, 20~0mA, 20~4mA 7
0~10V, 2~10V, 0~5V, 1~5V. 8

9 12 bit DAC resolution


MAIN 10 SP4 CONTACT
11 9 25 F
PCB 12 SP3 CONTACT All of relay original setting is N.O.. SP4
10 26 G
RS485 (Option)
13 To select N.C. / N.O. setting need from PC Board
SP2 CONTACT 11 27
14 directly. SP3
12 28
15 The 4 sets N.C./N.O. jumper selector are near
SP1 CONTACT 13 29
16 relay, which design is for user to select N.C./N.O. SP2
14 30
Type, the diagram is shown below :
15 31
33 SP1
OCB 34
SP6 CONTACT 16 32
35 17 33
PCB 36 SP5 CONTACT Power Supply
18 34
SP6
RY4 RY3 RY2 RY1 (Option)
35
SP5
36

JP4 JP3 JP2 JP1


NC.

NO. NC. NO. NC. NO.NC.NO.NC. NO.

-03- -04-
2.2 PB-1471 / PB-1570
2.2.1 Operation Panel 2.2.2 Technical Specifications 2.2.4 Exterior Dimensions
Display
4 digits, 0.56" 7 segment red LED display. 144
101 LED Bargraph Display
PB-1470 101 segment LED red bargraph display. 111 21
Display range: -1999~+9999
UP
(PB-1470 Series Products) 43.5
48
SHIFT Display range: -19999~+32767

ENTER (PB-1570 Series Products)


Input Signal 7
Range: 0~20mA, 4~20mA, 20~0mA, 20~4mA,
Relay Indicator Digital
Display
0~10V. 2.2.5 Cutout Dimensions
(Refer to Ordering Information for more types)
Accuracy: 0.1%FS or 1 digit
PB-1570 Temperature coefficient: 200ppm/BC
10 (min.)
ADC resolution: 4-1/2 digit
Sampling Rate: 4 samples/second
Relay Contact: 4 or 6 relays, 3A 250VAC
or 5A 30VDC
(N.C./N.O. jumper selectable) 45F0.6
G0
Working Condition: ( u n i t:m m )
-20~70BC (20% to 90% RH non-condensed) F1 10
Storage Condition: 138
G0 (min.)
-25~75BC (20% to 90% RH non-condensed)
Power Supply:
AC85V~AC265V or DC18V~DC36V 2.2.6 Terminal Arrangements
Switching Power Supply (Option)
Power comsumption: 9VA

Isolated analog O/P+


Isolated analog GND
Insulation Voltage: >AC1500V/min
Insulation Resistance: >100MW/500Vdc/min

Isolated +24V
Isolated GND
Optional Output (Isolated):
2.2.3 Relay Outputs *Analog Output: (Option) (Option)
RS 485
0~20mA, 4~20mA, 20~0mA, 20~4mA F G SP6 SP5

0~10V, 2~10V, 0~5V, 1~5V.


9 12 bit DAC resolution. 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
MAIN 10
SP4 CONTACT

PCB 11 All of relay original setting is N.O..


SP3 CONTACT
12
13 To select N.C. / N.O. setting need from PC Board
SP2 CONTACT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
14 directly.
15 The 4 sets N.C./N.O. jumper selector are near
SP1 CONTACT
16 relay, which design is for user to select N.C./N.O.
EXC 24V

Volt Input Signal


Current Input Signal
Signal GND
GND SP4 SP3 SP2 SP1 Power
Type, the diagram is shown below : Supply
33
OCB 34
SP6 CONTACT

PCB 35 SP5 CONTACT


36 RY4 RY3 RY2 RY1

JP4 JP3 JP2 JP1


NC.
NO. NC. NO. NC. NO.NC. NO.NC. NO.

-05- -06-
2.3 PB-2471

2.3.1 Operation Panel 2.3.2 Technical Specifications 2.3.4 Exterior Dimensions 2.3.5 Cutout Dimensions

Display
CH1 Dual 4 digits, 0.36" 7 segment red LED display. 6(max.)
Digital Display 48
Dual 101 segment LED red bargraph display. F0.6
45 G0 10 (min.)
Relay Display range: -1999~+9999
Indicator Ch1 in RED color, CH2 in GREEN color.
CH1-101 LED Input Signal
Bargraph Display
Range: 0~20mA, 4~20mA, 20~0mA, 20~4mA,
CH2-101 LED 0~10V. F1
Bargraph Display 144 144 135.5 138G0
(Refer to Ordering Information for more types)
UP Accuracy: 0.1%FS or A1 digit
Temperature coefficient: 200ppm/BC
SHIFT
ADC resolution: 4-1/2 digit
ENTER Sampling Rate: 2 samples/second/chnnel
Relay Contact:
CH2
Digital Display
4 or 8 relays 3A, 250VAC or 5A30VDC
(N.C. / N.O. jumper selectable) 9 111 14 10
(min.)
Working Condition :
-20~70BC (20% to 90% RH non-condensed)
( u n i t:m m )
Storage Condition:
-25~75BC (20% to 90% RH non-condensed)
Power Supply:
AC85V~AC265V or DC18V~DC36V 2.3.6 Terminal Arrangements
Switching Power Supply
Power comsumption: 12VA EXC 24V 1 19 Isolated +24V
GND 2 20 Isolated GND
Insulation Voltage: >AC1500V/min Volt Input Signal 3 21 Isolated analog O/P+
Insulation Resistance: >100MW/500Vdc/min CH1 Current Input Signal 4 22 Isolated analog GND
CH1

Signal GND 5 23 Isolated analog O/P+


Optional Output (Isolated): Volt Input Signal 6 24 Isolated analog GND
CH2
2.3.3 Relay Outputs *Analog Output: CH2 Current Input Signal 7
0~20mA, 4~20mA, 20~0mA, 20~4mA Signal GND 8

0~10V, 2~10V, 0~5V, 1~5V.


9
MAIN 10
CH2 SP2 12 bit DAC resolution. CH2 SP2
9 25 F
RS485 (Option)
11 10 26 G
PCB 12 CH2 SP1 11 27
All of relay original setting is N.O.. CH2 SP1
13 12 28
CH1 SP2 To select N.C. / N.O. setting need from PC Board
14 13 29
15 directly. CH1 SP2 CH2 SP4
CH1 SP1 14 30
16 The 4 sets N.C./N.O. jumper selector are near 15 31
relay, which design is for user to select N.C./N.O. CH1 SP1 CH2 SP3
16 32
29 Type, the diagram is showed as below : 17 33
OCB 30 CH4 SP4 Power Supply
18 34
CH1 SP4

PCB 31 35
CH3 SP3
32 36 CH1 SP3
33 RY4 RY3 RY2 RY1
CH4 SP4
34
35
CH3 SP3
36 JP4 JP3 JP2 JP1
NC.

NO. NC. NO. NC. NO.NC. NO.NC. NO.

-07- -08-
2.4 PM-1430 / PM-1530
2.4.1 Operation Panel
Relay
Digital Display
Indicator 2.4.4 Exterior Dimensions

96 10 118.5

48 44.8

UP SHIFT ENTER

2.4.2 Technical Specifications 2.4.5 Cutout Dimensions


Display
4 digits (PM-1430), 5digit (PM-1530) Working Condition: -20~70BC
0.56" 7 segment red LED display. (20% to 90% RH non-condensed) 22
101 segment LED red bargraph display. Storage Condition: -25~75BC (min)
Display range: -1999~+9999 (PM-1430) (20% to 90% RH non-condensed)
-19999~+32767 (PM-1530) Power Supply:
Input Signal AC85V~AC265V or DC18V~DC36V
Range: 0~20mA, 4~20mA, 20~0mA, Switching Power Supply 45F0.6
G0

20~4mA,0~10V. Power comsumption: 7VA


(Refer to Ordering Information for more types) Insulation Voltage: >AC1500V/min
F0.8
Insulation Resistance: 92G0 10 (min) ( u n i t:m m )
Accuracy: 0.1%FS or A1digit >100MW/500Vdc/min
Temperature coefficient: 200ppm/BC Optional Output (Isolated):
ADC resolution: 4-1/2 digit * Analog Output:
Sampling Rate: 4 samples/second 0~20mA, 4~20mA, 20~0mA, 20~4mA
Relay Contact: 0~10V, 2~10V, 0~5V, 1~5V. 2.4.6 Terminal Arrangements
4~6 relays, 3A 250VAC or 5A 30VDC 12 bit DAC resolution.
(Option)
(N.C./N.O. Jumper selectable) RS-485 SP 4 SP 3
Analog Iso
2.4.3 Relay Outputs Out GND (NC/NO) (COM) (NC/NO) (COM)
All of relay original setting is N.O..
To select N.C. / N.O. Setting need from PC Board
directly. 11 12 13 14 15 16 17 18 19 20
The 4 sets N.C./N.O. jumper selector are near
relay, which design is for user to select N.C./N.O.
5 Type, the diagram is shown below :
MAIN 6
SP2 contact

PCB 7
8
SP1 contact

RY2 RY1 1 2 3 4 5 6 7 8 9 10
17
OCB 18
SP4 contact
JP2 JP1 EXC GND SIG (NC/NO) (COM) (NC/NO) (COM)
PCB 19
SP3 contact NC . Power
20 +24V (IN-) (IN+)
NO . NO . NC . NO . NC . SP2 SP1 Supply

-09- -10-
2.5 PM-2430
2.5.1 Operation Panel Digital
2.5.4 Exterior Dimensions
Display Relay
Indicator

96 10 118.5

48 44.8

UP SHIFT ENTER
2.5.2 Technical Specifications 2.5.5 Cutout Dimensions
Display Working Condition: -20~70BC
4 digits, 0.36" 7 segment red LED (20% to 90% RH non-condensed)
display. Storage Condition: -25~75BC 22
Display range: -1999~+9999 (20% to 90% RH non-condensed) (min)
Power Supply:
Input Signal AC85V~AC265V or DC18V~DC36V
Range: 0~20mA, 4~20mA, 20~0mA, Switching Power Supply
20~4mA, 0~10V. Power comsumption: 7VA 45F0.6
G0
(Refer to Ordering Information for more types) Insulation Voltage: >AC1500V/min
Accuracy: 0.1%FS orA1digit Insulation Resistance: F0.8
Temperature coefficient: 200ppm/BC >100MW/500Vdc/min 92G0 10 (min) ( u n i t:m m )
ADC resolution: 4-1/2 digit Optional Output (Isolated):
Sampling Rate: 2 samples/second * Analog Output:
Relay Contact: 0~20mA, 4~20mA, 20~0mA, 20~4mA
4 or 6 relays, 3A 250VAC or 5A 30VDC 0~10V, 2~10V, 0~5V, 1~5V.
(N.C./N.O. Jumper selectable) 12 bit DAC resolution. 2.5.6 Terminal Arrangements
CH 2
2.5.3 Relay Outputs Analog (Option)
RS-485 SP 2 SP 1
Analog Iso CH2
All of relay original setting is N.O.. Out GND Out (NC/NO) (COM) (NC/NO) (COM)
To select N.C. / N.O. setting need from PC Board
directly.
The 4 sets N.C./N.O. jumper selector are near 11 12 13 14 15 16 17 18 19 20
relay, which design is for user to select N.C./N.O.
Type, the diagram is shown below :
5
MAIN 6 SP2 contact
CH1
PCB 7
8 SP1 contact

RY2 RY1

17 1 2 3 4 5 6 7 8 9 10
OCB 18
SP2 contact JP2 JP1
CH2 NC .
PCB 19
SP1 contact EXC GND CH1 CH2 (NC/NO) (COM) (NC/NO) (COM)
20 NO .
NO . NC . NO . NC .
+24V (IN-) (IN+) (IN+) Power
SP2 SP1 Supply

CH 1

-11- -12-
3. Program Settings 3.2 Input Buttons

3.1 Program Settings Flowchart Buttons Explanation

To choose CH1 or CH2 from here


The settings on the panel meter is controlled by the 3 buttons on the
PASS
(0only for PM-2430, PB-2471 ) panel (UP, SHIFT and ENTER). First choose the function, then input
required value of 3 buttons while in "Selection" and "Setting" are:
CHSL CHSL CH1~2

Selection Settings
SCAL DCPT
UP Escape Addition
SCH
SHIFT Enter Position Shift
SCL
ENT ENTER Switch Confirmation
SETP SP1~6
*Please enter password to modify the parameter. (Default password: 4607)
HON1~6
ENT ENTER Button
HOF1~6
1) Main menu switch or sub-menu switch.
Example: STEP 1 ~ STEP 2 and STEP 3 ~ STEP 5.
DON1~6
2) Confirmation to save settings
DOF1~6 Example: Confirmation of change of SCHi value

ENB1~6

ALR1~6
SCAL 1 2 34
SCHi
FULL 1234
STEP 1 ENT
Blinking
INP iSEL

SCHi
: modify
SETP
ENT
: save
SCLi
STEP 2 ENT

OUT SIG
INP iSEL
NOLI SEL
NOLI (Non-Linear Tank Volume
Conversion Function):Optional STEP 3 ENT
LP1~20

CONN IDNO SCHi


BPS
COD STEP 4 ENT

STYL
ENT
SYS LOAD FORN SCLi
STEP 5
FINE TOUR

-13- -14-
3.3 Input Signal Module and Setup Method

SIM Input Module Specifications and Jumper Elaboration.


SHIFT Button
Module Input Signal Range Jumper Setting
Entry into main menu or entry into sub-menu or position change.
01 4~20mA with Exc+24V DC 4~20mA
Example: STEP 1, STEP 2 and STEP 3 ~ STEP 7
Position shift 02 A0~20mA with Exc+24V DC 0~20mA
After entering into value input, use this button to shift between digit position. 5V
03 A0~200mA with Exc+24V DC 0~200mA 10V
20V
SCAL DCPT SETTING 04 A5V with Exc+24V DC A5V 200V
STEP 1 STEP 5 20mA
05 A10 with Exc+24V DC A10V 200mA
ENT ENT

CH1 CH2
06 A20 with Exc+24V DC A20V
SETP SP1 SETTING SCH SETTING
STEP 2 STEP 3 STEP 6 07 A200V with Exc+24V DC A200V
ENT ENT Left & right Jumpers must
A1 2mA AC Scaled RMS AC 0~2mA change symmetrically.
J3 J4
SP2 SETTING SCL SETTING A2 20mA AC Scaled RMS AC 0~20mA 200m 200mA
STEP 4 STEP 7 20mA 20mA
A3 200mA AC Scaled RMS AC 0~200mA 2mA 2mA

Moving Numeric : Moving the A4 1A AC Scaled RMS AC 0~1A


parameter numeric to modify. 1234
For example : Into SCHi function SCHi A5 5A AC Scaled RMS AC 0~5A
12 3 4
setting, one of the numeric will B1 100mV AC Scaled RMS DC 0~100mV
blinking to modify, and use SHIFT The blinking digit
bottom to select blinking digit for modify. is for modify B2 200mV AC Scaled RMS AC 0~200mV 200mV
2V
B3 2V AC Scaled RMS AC 0~2V

UP Button B4 20V AC Scaled RMS AC 0~20V 20V 200V 600V

To escape from main menu and to escape To change input value by addition. B5 200V AC Scaled RMS AC 0~200V J3
from sub-menu to main menu. Example: To change the value of SCHi
Example: STEP 1 and STEP 2 from "1230" to "1234", press B6 600V AC Scaled RMS AC 0~600V
button four times.
DC A2mA Left & right Jumpers must
C1 A2mA Exc+24V change symmetrically.
J4 J5
C2 A20mA Exc+24V DC A20mA 200mA 200mA
20mA 20mA
INP iSEL C3 A200mA Exc+24V DC A200mA 2mA 2mA
STEP 1 1230
SCHi
ENT 1234 C4 A1Amp DC A1A

Blinking C5 A5 Amp DC A5A


SCHi
D1 A20mV Exc+24V DC A20mV
J3
ENT
D2 A50mV Exc+24V DC A50mV 200mV
100mV
SCLi D3 A100mV Exc+24V DC A100mV 50mV
STEP 2 20mV
D4 A200mV Exc+24V DC A200mV
ENT

-15- -16-
3.4 Program Commands List
4 Digital 4 Digit Factory 5 Digital 5 Digit Factory 4 Digital 4 Digit Factory 5 Digital 5 Digit Factory
Command Description Setting Range Default Setting Range Default Command Description Setting Range Default Setting Range Default
PASS Password 0~9999 4607 0~9999 4607 DOF1 SP1 Delay Off Setting 00~99 00 0~999 000

CHSL Channel Selection CH1/CH2 CH1 CH1/CH2 CH1 DOF2 SP2 Delay Off Setting 00~99 00 0~999 000

SCAL Set DCPT, SCH, SCL DOF3 SP3 Delay Off Setting 00~99 00 0~999 000

DCPT Decimal point Selection 0~3 Dot1 0~4 Dot2 DOF4 SP4 Delay Off Setting 00~99 00 0~999 000
Display value for SPAN -1999 100.0 -19999 100.00 SP5 Delay Off Setting
SCH ~9999 ~32767 DOF5 00~99 00 0~999 000
Display value for SPAN -1999 000.0 -19999 000.00 SP6 Delay Off Setting
SCL ~9999 ~32767 DOF6 00~99 00 0~999 000

SETP Set SP1~6, HON1~6, DON1~6, DOF1~6, ENB1~6, ALR1~6, FULL ENB1 SP1 Relay On / Off Selecting ON / OFF ON ON / OFF ON
SP1 Set point value -1999 020.0 -19999 020.00
SP1 ~9999 ~32767 ENB2 SP2 Relay On / Off Selecting ON / OFF ON ON / OFF ON
SP2 Set point value -1999 040.0 -19999 040.00
SP2 ~9999 ~32767 ENB3 SP3 Relay On / Off Selecting ON / OFF ON ON / OFF ON

SP3 Set point value -1999 060.0 -19999 060.00 ENB4


SP3 ~9999 ~32767 SP4 Relay On / Off Selecting ON / OFF ON ON / OFF ON

SP4 Set point value -1999 -19999 080.00 ENB5


SP4 ~9999 080.0 ~32767 SP5 Relay On / Off Selecting ON / OFF OFF ON / OFF OFF
-1999 -19999 NULL
SP5 SP5 Set point value ~9999 NULL ~32767 ENB6 SP6 Relay On / Off Selecting ON / OFF OFF ON / OFF OFF
-1999 -19999 NULL ALR1
SP6 SP6 Set point value ~9999 NULL ~32767 SP1 Hi / Lo Alarm Selection HI / LO LO HI / LO LO

HON1 SP1 Hysterises High Band 0~9999 000.0 0~32767 000.00 ALR2 SP2 Hi / Lo Alarm Selection HI / LO LO HI / LO LO

HON2 SP2 Hysterises High Band 0~9999 000.0 0~32767 000.00 ALR3 SP3 Hi / Lo Alarm Selection HI / LO HI HI / LO HI

HON3 SP3 Hysterises High Band 0~9999 000.0 0~32767 000.00 ALR4 SP4 Hi / Lo Alarm Selection HI / LO HI HI / LO HI

HON4 SP4 Hysterises High Band 0~9999 000.0 0~32767 000.00 ALR5 SP5 Hi / Lo Alarm Selection HI / LO HI HI / LO HI

HON5 SP5 Hysterises High Band 0~9999 000.0 0~32767 000.00 ALR6 SP6 Hi / Lo Alarm Selection HI / LO HI HI / LO HI

HON6 SP6 Hysterises High Band 0~9999 000.0 0~32767 000.00 FULL Enter this item for all setting items YES / NO NO YES / NO NO

HOF1 SP1 Hysterises Low Band 0~9999 000.0 0~32767 000.00 inp Input Signal Setting
HOF2 SP2 Hysterises Low Band 0~9999 000.0 0~32767 000.00 iSEL Iutput Type Selection 4~20 4~20

SCHi -1999 100.0 -19999 100.00


HOF3 SP3 Hysterises Low Band 0~9999 000.0 0~32767 000.00 SPAN Percentage for SPE mode ~9999 ~32767
SCLi -1999 000.0 -19999 000.00
HOF4 SP4 Hysterises Low Band 0~9999 000.0 0~32767 000.00 ZERO Percentage for SPE mode ~9999 ~32767
HOF5 SP5 Hysterises Low Band 0~9999 000.0 0~32767 000.00 out Output Signal Setting
HOF6 SP6 Hysterises Low Band 0~9999 000.0 0~32767 000.00 SIG Analog Output Type Selection 4~20 4~20

DON 1 SP1 Delay On Setting 00~99 00 0~99 00


NOLI Non-Linear Tank Function
DON 2 SP2 Delay On Setting 00~99 00 0~99 00
SEL Enable / Disable ON / OFF OFF ON / OFF OFF
DON 3 SP3 Delay On Setting 00~99 00 0~99 00
LP1 Control Point #1 0~1999 5 0~19999 5
DON 4 SP4 Delay On Setting 00~99 00 0~99 00
LP2 Control Point #2 0~1999 10 0~19999 10
DON 5 SP5 Delay On Setting 00~99 00 0~99 00
LP3 Control Point #3 0~1999 15 0~19999 15
DON 6 SP6 Delay On Setting 00~99 00 0~99 00
-17- -18-
4 Digital 4 Digit Factory 5 Digital 5 Digit
Description Setting Factory
Command Description Setting Range Default Setting Range Factory Default
Command
Range Default
LP4 C o n tro l P o i n t # 4 0~1999 20 0~19999 20 CONN RS485 Settings

LP5 C o n tro l P o i n t # 5 0~1999 25 0~19999 25 IDNO Settings ModBus Address 0~255 255
LP6 C o n tro l P o i n t # 6 0~1999 30 0~19999 30 BPS Setting ModBus BaudRate more
LP7 C o n tro l P o i n t # 7 0~1999 35 0~19999 35 600 600BPS 600
LP8 C o n tro l P o i n t # 8 0~1999 40 0~19999 40 1200 1200BPS 1200
LP9 C o n tro l P o i n t # 9 0~1999 45 0~19999 45 2400 2400BPS 2400

LP10 C o n tro l P o i n t # 1 0 0~1999 50 0~19999 50 4800 4800BPS 4800


600
LP11 C o n tro l P o i n t # 11 0~1999 55 0~19999 55 9600 9600BPS 9600

LP12 C o n tro l P o i n t # 1 2 0~1999 60 0~19999 60 144G 14400BPS 14400

LP13 C o n tro l P o i n t # 1 3 0~1999 65 0~19999 65 192G 19200BPS 19200

LP14 C o n tro l P o i n t # 1 4 0~1999 70 0~19999 70 288G 28800BPS 28800

LP15 C o n tro l P o i n t # 1 5 0~1999 75 0~19999 75 576G 57600BPS 57600

LP16 C o n tro l P o i n t # 1 6 0~1999 80 0~19999 80 STYL Settings Data Type more

LP17 C o n tro l P o i n t # 1 7 0~1999 85 0~19999 85 8N1 8 Byte, No Parity, 1 Stop Bits 8N1

LP18 C o n tro l P o i n t # 1 8 0~1999 90 0~19999 90 7N2 7 Byte, No Parity, 2 Stop Bits 7N2

LP19 C o n tro l P o i n t # 1 9 0~1999 95 0~19999 95 7O1 7 Byte, Odd Parity, 1 Stop Bits 701

LP20 C o n tro l P o i n t # 2 0 0~1999 100 0~19999 100 7E1 7 Byte, Even Parity, 1 Stop Bits 7E1
8N1
cod C h a n g e P a s s w o rd 0~9999 4607 4607 0~9999 8N2 8 Byte, No Parity, 2 Stop Bits 8N2

SYS System Settings 8O1 8 Byte, Odd Parity, 1 Stop Bits 801

LOAD Reset to factory default YES/NO NO YES/NO NO 8E1 8 Byte, Even Parity, 1 Stop Bits 8E1

FINE R e a d S o f t w a r e Ve r s i o n C o d e 7O2 7 Byte, Odd Parity, 2 Stop Bits 702

7E2 7 Byte, Even Parity, 2 Stop Bits 7E2

FORN Settings Data Format more

HEX RTU Mode HEX HEX

ASCI ASCII Mode ASCII

TOUT Time Out 100~9999mS 300mS

-19- -20-
3.5.Input Signal Settings

This section will elaborate how to adapt to different input signals in the 3.5.2 Input Signal & Setting Table
panel meter, by using the correct jumper and using iSEL command.
Panel meter series can accommodate 6 types of conventional input SIM No. Signal Type Jumper position User Setup (iSEL)
signals, 20mA, 200mA, 5V, 10V, 20V, 200V, please refer below for setup. 0~20mA iSEL 0 - 20

STEP 1: Please confirm the type of input signal 4~20mA iSEL 4 - 20


01
STEP 2: Open up MG casing and locate the SIM input signal module, select the 20~0mA iSEL 20 - 0
& 20mA
jumper connection that corresponds to the required input signal. 02 20~4mA iSEL 20 - 0

STEP 3: Enter the main menu of the MG after password input, select iSEL and Special range iSEL SPE SCHi
select the correct input signal from the list below.
0~20mA SCLi

A200mA iSEL 0 - 20
3.5.1 Diagram Output Control Signal Input
Board module 03 Special range 200mA iSEL SPE SCHi Refer to
48x96 Analog Signal
SCLi
4.2.2
Output lnput 0~200mA
A5V iSEL 0-5

1~5V iSEL 1-5


Relay 04 5V
Contact Refer to
Relay Special range iSEL SPE SCHi
Contact AC 110V
4.2.2
0~5V SCLi
Display iSEL 0 - 10
A10V
Board
2~10V iSEL 2 - 10
05 10V
Special range iSEL SPE SCHi Refer to
POWER+CPU Board
4.2.2
0~10V SCLi

48x144 Output Control Signal Input A20V iSEL 0 - 20


Board module
Analog Signal 06 Special range 20V iSEL SPE SCHi Refer to
Output lnput
4.2.2
0~20V SCLi

A200V iSEL 0 - 20

07 Special range 200V iSEL SPE SCHi Refer to


Relay 4.2.2
Contact 0~200V SCLi

Relay AC 110V AC Current iSEL 0 - 10


Contact
Display RMS
A1 SCAL DCPT 3
Board 0~2mA 2mA
SCH 2.000

AC Current iSEL 0 - 10
RMS
POWER+CPU Board A2 SCAL DCPT 2
0~20mA 20mA
SCH 20.00

-21- -22-
SIM No. Signal Type Jumper position User Setup (iSEL) SIM No. Signal Type Jumper position User Setup (iSEL)
AC Current iSEL 0 - 10 DC Current iSEL 0 - 10
RMS
A3 SCAL DCPT 1 C1 SCAL DCPT 3
0~200mA 200mA 2mA
A2mA
SCH 200.0 SCH 2.000
AC Current iSEL 0 - 10 DC Current iSEL 0 - 10
RMS
A4 SCAL DCPT 3 C2 SCAL DCPT 2
0~1A 1A
A20mA 20mA
SCH 100.0 SCH 20.00
AC Current iSEL 0 - 10 DC Current iSEL 0 - 10
RMS
A5 SCAL DCPT 3 C3 SCAL DCPT 1
0~5A 5A
A200mA 200mA
SCH 5.000 SCH 200.0
A C Vo l t a g e iSEL 0 - 10 DC Current iSEL 0 - 10
RMS
B1 SCAL DCPT 1 C4 SCAL DCPT 3
0~100mV 100mV
A1A 1A
SCH 100.0 SCH 1.000
A C Vo l t a g e iSEL 0 - 10 DC Current iSEL 0 - 10
RMS
B2 SCAL DCPT 1 C5 SCAL DCPT 3
0~200mV 200mV 5A
A5A
SCH 200.0 SCH 5.000
A C Vo l t a g e iSEL 0 - 10 D C Vo l t a g e iSEL 0 - 10
RMS
B3 SCAL DCPT 3 D1 SCAL DCPT 2
0~2V 2V
A20mV 20mV
SCH 2.000 SCH 20.00
A C Vo l t a g e iSEL 0 - 10 D C Vo l t a g e iSEL 0 - 10
RMS
B4 SCAL DCPT 2 Refer to D2 SCAL DCPT 1
0~20V 20V
4.2.2 A50mV 50mV
SCH 20.00 SCH 050.0
A C Vo l t a g e iSEL 0 - 10 D C Vo l t a g e iSEL 0 - 10
RMS
B5 SCAL DCPT 1 Refer to D3 SCAL DCPT 1
0~200V 200V A100mV
4.2.2 100mV
SCH 200.0 SCH 100.0
A C Vo l t a g e iSEL 0 - 10 D C Vo l t a g e iSEL 0 - 10
RMS
B6 SCAL DCPT 1 D4 SCAL DCPT 1
0~600V 600V A200mV 200mV
SCH 600.0
SCH 200.0

-23- -24-
3.5.3 Current Signal Input Example

3.5.4 Non-linear feature settings


Special feature:
A. 2 wire 4~20mA current signal input example Non-linear settings could be used in applications concerning non-conventional
shaped tanks, thereby solving the problem for level v.s. volume measurement
LevelTransducer for non-linear tank shapes.

To divide the maximum 100.0


100.0

measurement into 20 set points, 95.0


PASS 94.0
IN COM then configure each of these 20 90.0
88.0
EXC

2 wire 4~20mA set points according to the shape 85.0


ZERO SPAN Transmitter CHSL of the tank, the panel meter will 80.0 82.0
75.0 76.0
v w
then calculate a proportional
70.0
SETP
readout from the input signal to 70.0
65.0
64.0
+24V O/P reflect the true value according 60.0
1 EXC 24V to the Meter settings. 55.0
58.0

2 INP 52.8
50.0
3 45.0 46.0

4 A Input OUT 40.0 40.0


5 35.0 35.4
6 30.0
28.0
7 NOLI SEL ON 25.0
22.0
20.0
8 LP1 002.0
15.0 16.0
LP2 004.0 10.0
10.0 6.0
PM LP3 006.0 5.0 2.0
4.0
8.0

Panel Meter LP4 008.0 0.0


0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

LP5 010.0
B. 3 wire 4~20mA current signal input example
LP6 016.0
+24V
LP7 022.0
GND (Shielding) Set point
LP8 028.0
LP20
LP9 034.0 LP19
LP18
1 EXC 24V LP10 040.0 LP17
2 GND LP16
LP11 046.0 LP15
3
052.0 LP14
4 A Input LP12
LP13
5 LP13 058.0 LP12
Signal 6 LP11
7 LP14 064.0 LP10
LP9
8 LP15 070.0 LP8
LP7
LP16 076.0 LP6
LP5
LP17 082.0 LP4
PM LP18 088.0 LP3
LP2
Panel Meter LP19 094.0 LP1

LP20 100.0

-25- -26-
3.6 Output Signal Setting
3.6.1 Optional relay output setting 3.6.2 Analog output signal selection
The optional relay output is switchable to NO (Normal Open) or Analog output signal (optional) provides 4~20mA or
NC (Normal Close), it is selectable by the jumper on the OCB 0~10V signal, it can be selected by the jumper on the
(Output Control Board). The default setting is "NO". OCB (Output Control Board) for current output 4~20mA
or voltage output (0~10V).
Model: PB-1470, PB-1471, PB-1570
SP5 and SP6 relay setting is as below drawing:
Model: PB-1470, PB-1471, PB-1570, PB-2471

RY1 RY2
NO

NC

SP5 SP6

CH2 CH1

JP2 JP1

Channel 1 is selected by JP1 Jumper is for current output


Model: PB-2471 Series Model: PM-1430, PM-1530, Channel 2 is selected by JP2 Jumper is for voltage output
SP5, SP6, SP7 and SP8 relay PM-2430 Series
setting is as below drawing: Model: PM-1430, PM-1530, PM-2430

RY1 RY2 NO
NO

NC NC
RY1
SP7
SP5 SP6 RY3

NO NC RY4
SP8 SP1 SP2
RY2 Jumper is for current output
Jumper is for voltage output
CH2 CH1

-27- -28-
4. Program Setting Example
4.1 Diagram of Setting Values 4.2.1 Example 1
Application example:
PASS
4mA represents 000.0 when the tank is empty
SCAL DCPT
20mA represents 100.0 when tank is full
SETP SP(1~6) SCH Set point 1 is set at 20% of full tank as low level alarm
INP iSEL 4-20 HON(1~6) SCL Set point 2 is set at 40% of full tank as low level alarm
OUT SIG 4-20 SCHi 0-20 HOF(1~6) Set point 3 is set at 60% of full tank as high level alarm
SCLi
Set point 4 is set at 80% of full tank as high level alarm
COD 0-20 20-4 DON(1~6)
Linear proportional out signal
SYS LOAD 20-4 20-0 DOF(1~6)
Proportional output: Empty tank: 0mA, Full tank: 20mA
FINE 20-0 0-5 ENB(1~6) Settings are as follows:
0-5 1-5 ALR(1~6)
INP iSEL 4-20
1-5 0-10 FULL

0-10 2-10
SCAL DCPT 1
2-10 SPE SCH 100.0
SCL 000.0
4.2 Program Settings Example
Magnetic Float Level Indicator delivers a current output that change proportionately with SETP SP1 020.0 SETP ENB1 ON
level. The 4 ~ 20mA output could be used in conjunction with the PB-1471 panel meter. SP2 040.0 ENB2 ON
SP3 060.0 ENB3 ON
Magnetic Float PB-1471 SP4 080.0 ENB4 ON
Level Indicator
OUT SIG 0-20 SETP ALR1 LO
4~20mA
ALR2 LO
ALR3 HI
ALR4 HI

SCH 4.2.2 Example 2 (Special input signal range's proportional settings)


To address the problem of special input signal range that falls within 4~20mA,
SP4 use of the command "SPE" is needed to program a proportionate setting for
the input.
Example is Fine Automation capacitance level indicator,
SP3 Current Input range is 7mA ~ 11mA, to display 000.0% ~ 100.0%
Formula:
SP2 SCHi / SCLE set value =
Expected signal value
SIM signal selection x 100% INP ISEL SPE
SP1
SCHi 035.0
Settings are as follow:
Input current 7mA ~ 11mA SCLi 055.0
SCL
7 100%= 35% 11
SCLi= X SCHi= X 100%= 55% OUT SIG 20-4
20 20
-29- -30-
5. Frequently Asked Questions
& Troubleshooting
4.2.3 Example 3
Problem Rectification method

Value Settings are as follows: Panel Face doesn't 1) Check power supply wire is it connected wrongly or not
lights up connected.
SCH=100.0 SCL=000.0 SP1=020.0 HON1=005.0 HOF1=010.0
DON=03 DOF=02 ENB1=ON ALR1=HI 2) Check whether the power supply is AC85V ~ 265V.

Relay Contact fails 1) Check whether LED indication on the panel face is doing
Analog Input to action action.
50 2. Check whether wiring on the terminals are connected
correctly.
45

40

35 1) Enter operation menu, check " " is ON (Default is ON)


Panel face LED
indicators and Relay 2) Enter operation menu, check " " " " has
30
contacts no action or any set value.
25
not working properly. 3) Enter operation menu, check " " " " has
20 any set value.
15 4) Enter operation menu, check " " has the
same value as factory default.
10

5
Proportional signal Enter operation menu, check " ", " ", " ", " "
0
input does not &" " is configured correctly.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 correspond to panel
display

Set point 1's action diagram:


Analog Input
OFF 1
No change in display Check input signal connection is connected correctly or
and bargraph after is it loose.
proportionate input
signal

ON 0

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

-31- -32-