BSD Reviewer

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 17

LESSON 1: CODES AND REGULATIONS building considered to be a potential source of

fire or explosion.
NATIONAL BULDING CODE OF THE PHILIPPINES
• REPUBLIC ACT NO. 6541 RULE II. Administration and Enforcement
An act to ordain and institute a National Building Code of
• Responsibility for Administration and Enforcement
the Philippines
(Building Code)
• PRESIDENTIAL DECREE (P.D.) NO. 1096 - Enacted on
➢ The administration and enforcement of the
august 1972
provisions of the Code and this IRR, including the
Adopting a National Building Code of the Philippines imposition of penalties for administrative
(NBCP) thereby revising Republic Act numbered sixty- violations thereof, is hereby vested in the
five hundred forty-one (R.A. No. 6541) Secretary.

Enacted ON 1977 • TECHNICAL STAFF (SECTION 202) DPWH - Department of Public


Works and highways
The National Building Code Development Office
Issued on February 19, 1977 has achieved the purpose of (NBCDO) created through DPWH Department Order,
enforcing uniform standards and requirements on shall serve as the technical staff of the Secretary. The
building design, construction, use, occupancy and functions thereof are as follows:
maintenance in line with the policy of the state to
safeguard life, health, property and public welfare. 1. Assist the Secretary in the administration and
Rule no. 1 - General Provisions
REGULATIONS Rule no. 2 - Administration and Enforcement enforcement of the provisions of
the Code and its
Rule no. 3 - Permits and Inspection
Rule no. 4 - Types of Construction
IRR.
RULE I. General Provisions Rule no. 7 - Classification and General Requirements of all
Buildings by Use or Occupancy 2. Review, evaluate and take final
action on various
• General Building Requirements technical and legal problems forwarded to the Office
1. All buildings or structures as well as accessory facilities of the Secretary.
thereto shall conform in all respects to the principles of 3. Conduct seminar/workshops on the Code, its IRR,
safe construction and must be suited to the purpose for and Batas Pambansa Blg. 344 (Accessibility Law).
which they are designed.
4. Undertake such other duties and tasks as may be
2. Buildings or structures intended to be used for the assigned by the Secretary from time to time.
manufacture and/or production of any kind of article or
product shall observe adequate environmental General Powers and Functions of the SECRETARY
safeguards. 1. Formulate policies, plans, standards and guidelines on
3. Buildings or structures and all parts thereof as well as building design, construction, use, occupancy, and
all facilities found therein shall be maintained in safe, maintenance, in accordance with the Code.
sanitary, and good working condition. 2. Issue and promulgate additional rules and regulations
• Site Requirements in the form of Memorandum Circulars to implement the
provisions of the Code and ensure compliance with
➢ The land or site upon which will be constructed policies, plans, standards and guidelines and issue office
any building or structure, or any ancillary or guidelines or Memorandum Circulars to guide the actions
auxiliary facility thereto, shall be sanitary, of the Building Official in the performance of his duties
hygienic, or safe. and responsibilities.
➢ In case of sites or buildings intended for use as
human habitation or abode, the same shall be at 3. Exercise appellate jurisdiction over the decisions and
a safe distance, as determined by competent orders of the Building Official. The order or decision of
authorities, from streams or bodies of water the Secretary shall be final and executory subject only to
and/or sources of air considered to be polluted; review by the Office of the President of the Republic.
from a volcano or volcanic site and/or any other 4. Evaluate, review, approve and/or take final action on
changes and/or amendments to existing Referral Codes
as well as on the incorporation of other referral codes, 3. A member of good standing of a duly accredited
which are not yet expressly made supplementary to the organization of his profession for not less than five (5)
Code and its IRR. years endorsed or recommended by the accredited
professional organization.
5. Prescribe and impose the amount of fees and other
4. Has at least five (5) years of diversified and
charges as may be deemed necessary that the Building
professional experience in building design and
Official shall collect in connection with the performance
construction.
of regulatory functions.
5. Has attended and successfully completed a
6. Appoint a Building Official, separate and distinct from seminar workshop on PD 1096 and its IRR conducted
the Office of the City/Municipal Engineers in all Cities and by the DPWH.
Municipalities.
• DUTIES OF THE BUILDING OFFICIALS (S. 207)
• PROFESSIONAL AND TECHNICAL ASSISTANCE (S. 204) The Building Official shall have the following duties:
➢ The Secretary may secure professional, technical, 1. Be primarily responsible for the enforcement of
scientific, and other services including testing the provisions of the Code and its IRR, as well as
laboratories and facilities from other agencies of circulars, memoranda, opinions, and
the National Government when deemed decisions/orders issued pursuant thereto. His actions
necessary. shall always be guided by appropriate
➢ He may also engage and compensate within orders/directives from the Secretary.
available appropriations, such number of
consultants, experts, and advisers on full or part- 2. Have overall administrative control and/or
time basis, as may be necessary, coming from the supervision over all works pertinent to
government or private business, entities or buildings/structures in his area of responsibility and
associations to carry out the provisions of the shall be charged with the processing of all permit
Code and this IRR. applications and certificates as well as the issuance
of the same.
• BUILDING OFFICIALS (S. 205)
3. Ensure that all changes, modifications, and
➢ Except as otherwise provided herein, the alterations in the design plans during the
Building Official shall be responsible for carrying construction phase shall not start until the modified
out the provisions of the Code in the field as well design plan has been evaluated and the necessary
as the enforcement of orders and decisions made amendatory permit issued.
pursuant thereto.
➢ All Building Officials appointed or designated 4. Undertake annual inspections of all
other than by the Secretary, shall continue to act buildings/structures and keep an up-to-date record
as the Building Official until such time that the of their status.
Secretary appoints the Building Official. Offices of
5. Upon complaint and after due notice/s and
the Building Officials already established,
hearing, initiate action towards:
separate and distinct from the office of the
a. non-issuance, suspension, revocation and/or
City/Municipal Engineers in cities and
invalidation of a building permit or certificate of
municipalities may continue to exist until such
occupancy.
time that a regular office is created. (Fig. II.1.)
b. Issuance of work stoppage order, or an order
• QUALIFICATIONS OF BUILDING OFFICIALS (S. 206) for discontinuance of the use or occupancy of the
building/structure or portion thereof.
No person shall be appointed as Building Official c. Declaration of a building/structure as ruinous
unless he possesses the following qualifications: or dangerous; and/or
1. A Filipino citizen and of good moral character. d. The imposition of appropriate fines/penalties.
2. A duly registered architect or civil engineer.
6. Submit a quarterly situational report to the done. The prescribed application for building permit
Secretary through the NBCDO, on the status of all form (NBC Form B-01) shall be used by all applicants.
existing, on-going, and proposed public as well as
2. Permits supplementary to a Building Permit shall
private building/structure activities. (See
be applied for and issued by the Building Official.
Communication Flow Chart, Fig. II.2.)
These include Ancillary and the Accessory Permits.
7. Undertake such other duties and tasks as may
be assigned by the Secretary from time to time. a. Ancillary Permits - The Ancillary Permits duly
signed and sealed by the corresponding
• FEES (SECTION 208) professionals and the plans and specifications shall
be submitted together with the duly notarized
1. The Secretary, thru Memorandum Circulars, shall
application for Building Permit. The Building Permit is
prescribe the rates of fees and formulate guidelines
null and void if not accompanied by the Ancillary
in the imposition and collection of fees.
Permits. The prescribed Ancillary and other
2. Subject to existing budgetary, accounting and Accessory Permits/forms shall likewise be used
auditing rules and regulations, the Building Official whenever applicable. The Ancillary Permits are the
shall retain not more than 20% of the following.
income/collection derived from permit fees and
i. Architectural Permit
other charges for the operating expenses of his
ii. Civil/Structural Permit
office. The remainder of 100% shall accrue to the
iii. Electrical Permit
general fund of the respective city/municipality.
iv. Mechanical Permit
3. Every Building Official shall keep a permanent v. Sanitary Permit
record and accurate account of all fees and other vi. Plumbing Permit
charges fixed and authorized to be collected and vii. Electronics Permit
received.
b. Accessory Permits
• EXEMPTION (SECTION 209)
i. Accessory Permits are issued by the Building Official for
➢ Public buildings and traditional indigenous family accessory parts of the project with very special functions
dwellings shall be exempt from payment of or use which are indicated in the plans and specifications
building permit fees. that accompany the building permit application. These
➢ As used in the Code, the term “traditional may include, among others: bank and records vaults;
indigenous family dwelling” means a dwelling swimming pools; firewalls separate from the
intended for the use and occupancy by the family building/structure; towers; silos; smokestacks; chimneys;
of the owner only and constructed of native commercial/industrial fixed ovens; industrial
materials such as bamboo, nipa, logs, or lumber, kilns/furnaces; water/waste treatment tanks, septic
the total cost of which does not exceed fifteen vaults; concrete and steel tanks; booths, kiosks and
thousand pesos (P 15,000.00). stages; and tombs, mausoleums and niches.

RULE III. Permits and Inspection ii. Accessory Permits are issued by the Building Official for
• BUILDING PERMITS (SECTION 301) activities being undertaken prior to or during the
processing of the building permit. The coverage is spelled
1. No person, firm or corporation, including any out in the accessory permit form including the expiry
agency or instrumentality of the government shall period. These shall be signed by the concerned
construct, alter, repair, convert, use, occupy, move, owner/applicant and by the concerned professionals.
demolish and add any building/structure or any These permits include, among others, ground
portion thereof or cause the same to be done, preparation and excavation, encroachment of foundation
without first obtaining a building permit therefor to public area, fencing, for fence not exceeding 1.80
from the Building Official assigned in the place where meters high, sidewalk construction, temporary sidewalk
the subject building/structure is located or to be enclosure and occupancy, erection of scaffolding,
no one is allowed to construct, occupy, repair ng erecting, repair, removal of sign; and demolition.
building/structure without obtaining building
permits from building officials na naka assigned
sa place
3. Exemption from Building Permits Type V - steel, iron, concrete, or masonry construction
A building permit shall not be required for the following and walls with 4-hour fire-resistive throughout
minor constructions and repairs, provided these shall not
violate any provision of the Code and this IRR. • CHANGES IN TYPES (SECTION 402)
➢ No change shall be made in the type of
a. Minor Constructions construction of any building which would place
i. Sheds, outhouses, greenhouses, children’s playhouses, the building in a different sub- type or type of
aviaries, poultry houses and the like, not exceeding 6.00 construction unless such building is made to
sq. meters in total area, provided they are completely comply with the requirements for such sub-type
detached from any other building and are intended only of construction.
for the private use of the owner. ➢ Except, when the changes are approved by the
ii. Addition of open terraces or patios resting directly on Building Official upon showing that the new or
the ground, not exceeding 20.00 sq. meters in total floor proposed construction is less hazardous, based
area, exclusively for the private use of the owner. on life and fire risk, than the existing
iii. Installation of window grilles. construction.
iv. Garden pools for the habitation of water plants and/or Requirements on Type of Construction
aquarium fish not exceeding 500 millimeters in depth and 1. Fire Resistive Requirements
exclusively for private use. a. Exterior bearing and non-bearing walls of Types II and
v. Garden masonry walls other than party walls not III Constructions shall have one hour fire-resistive rating,
exceeding 1.20 meters in height, footpaths, residential while those of Types IV and V shall have four-hour fire-
garden walks and/or driveways. resistive rating.
b. Interior bearing walls, permanent partitions, floors,
b. Repair Works and roofs of Types II, III and IV Construction shall have
i. Repair works not affecting or involving any structural one-hour fire-resistive rating while those of Type V shall
member, such as replacement of deteriorated roofing have three- hour fire-resistive rating for bearing walls and
sheets or tiles, gutters, downspouts, fascias, ceilings one-hour fire-resistive rating for vertical openings, floors
and/or sidings. and roofs.
ii. Repair and/or replacement of non-load-bearing c. Structural frames of Types II and III Construction shall
partition walls. iii. Repair and/or replacement of any have one-hour fire-resistive rating, while those of Type IV
interior portion or a house not involving addition or shall have two-hour fire-resistive rating and those of Type
alteration. V shall have three-hour fire-resistive rating.
iv. Repair and/or replacement work of doors and d. Exterior doors and windows shall have one hour fire-
windows. resistive rating for all Types.
v. Repair and/or replacement work of flooring.
vi. Repair of perimeter fence and walls. 2. Interior Wall and Ceiling Finishes
vii. Repair and/or replacement of plumbing fixtures, a. Finishes for interior walls and ceilings of any building
fittings or pipings, such as toilet bowls, sinks, lavatories, shall be classified according to their flame-spread
urinals, bidets, pipes, faucets, valves for single detached characteristic using generally accepted engineering
dwellings and duplexes. standards. The smoke density shall not be greater than
that obtained from burning of untreated wood under
RULE IV. Types of Construction similar conditions when tested in accordance with the
• TYPES OF CONSTRUCTION (SECTION 401) “Tunnel Test” in the way intended for use.
Type I – wood construction b. Requirements for flame-spread characteristics of
Type II – wood construction with protective fire-resistant finishes shall not apply to frames and trim of doors and
materials and 1 hour fire-resistive throughout windows and to materials which are less than 1.00
Type III – masonry and wood construction millimeter in thickness cemented to the surface of walls
Type IV – steel, iron, concrete, or masonry construction or ceilings.
and walls
c. Materials required to be flame-spread proofed shall be required to the location on property whichever is
treated with a flame-retardant having a flame-spread of the least restrictive.
fifty (50) or less as determined by the “Tunnel Test”. ➢ Distance shall be measured at right angles from
the property line.
3. Standards for materials use in structural framework, ➢ When openings in exterior walls are required to
exterior walls and openings, floors, exits, stairs & roofs be protected due to distance from property line,
shall be governed by the pertinent provision of the Fire the sum of the areas of such openings in any
Code of the Philippines. storey shall not exceed 50% of the total area of
the wall in that storey.
RULE VII. Classification and General Requirements of all
Buildings by Use or Occupancy o Buildings on Same Property and Buildings
Containing Courts
• Occupancy Classified (Section 701) ➢ For determining the required wall and opening
Buildings proposed for construction shall be identified protection, buildings on the same property and
according to their use or the character of its occupancy court walls shall be assumed to have a property
and shall be classified as follows: line between them.
Group A – Residential Dwellings ➢ When a new building is to be erected on the
Group B – Residentials, Hotels and Apartments same property with an existing building, the
Group C – Education and Recreation assumed property line from the existing
Group D – Institutional building shall be the distance to the property
Group E – Business and Mercantile line for each occupancy.
Group F – Industrial ➢ Provided, that two or more buildings on the
Group G – Storage and Hazardous same property may be considered as one
Group H – Assembly Other than Group I building if the aggregate area of such building is
Group I – Assembly Occupant Load 1000 or more within the limits of allowable floor areas for a
Group J – Accessory single building, and when the buildings so
considered, house different occupancies or are
LESSON 2: Classification and General Requirements of of different types of construction, the area shall
all Buildings by Use or Occupancy be that allowed for the most restrictive
occupancy or construction.
• Location on Property o Allowable Floor Areas
General ➢ The allowable floor areas for one-storey building
➢ No building shall be constructed unless it adjoins and buildings over one-storey shall not exceed
or has direct access to a public space, yard or the limits prescribed for each occupancy groups
street on at least one of its sides. and/or types of construction.
➢ The centerline or an adjoining street or alley shall ➢ Each portion of a building separated by one or
be considered an adjacent property line. more area separation walls may be considered a
➢ Eaves over required windows shall not be less separate building provided the area separation
than 750 millimeters from the side and rear walls meet the requirements prescribed.
property lines. ➢ The floor areas hereinabove provided may be
o Fire Resistance of Walls increased in certain specific instances and under
➢ Exterior walls shall have fire resistance and appropriate conditions, based on the:
opening protection in accordance with the ✓ existence of public space
requirements set forth by the Secretary. ✓ streets or yards extending along and
➢ Projections beyond the exterior wall shall not adjoining two or more sides of the
exceed beyond a point one-third the distance building
from an assumed vertical plane located where ✓ structure subject to the approval of the
the fire-resistive protection of openings is first Building Official
o Maximum Height of Buildings H. Stairs - Stairs shall be at least 750 mm in clear
➢ shall be dependent upon the character of width, with a rise of 200 mm and a minimum run of
occupancy and the type of construction as 250 mm.
determined by the Secretary considering I. Entrance and Exit - There shall be at least one
population density, building bulk, widths of entrance and another one for exit.
streets and car parking requirements. J. Electrical Requirements - All electrical installation
➢ The height shall be measured from the highest shall conform to the requirements of the Philippine
adjoining sidewalk or ground surface: Provided, Electrical Code.
that the height measured from the lowest K. Mechanical Requirements - Mechanical systems
adjoining surface shall not exceed such and/or equipment installation shall be subject to the
maximum height by more than 3.00 meters; requirement of the Philippine Mechanical
➢ Except, that towers, spires, and steeples, erected Engineering Code.
as part of a building and not used for habitation
or storage are limited as to height only by
• Requirements for Other Group Occupancies
structural design if completely of incombustible
materials, or may extend not to exceed 6.00 Subject to the provisions of this Code, rules and
meters above the height limits for each regulations for each of the other Group Occupancies shall
occupancy group if of combustible materials. be covering:

✓ allowable construction, height, and area.


• Minimum requirements for GROUP A – DWELLINGS
A. Dwelling Location and Lot Occupancy ✓ location on property, exit facilities, light,
ventilation, and sanitation.
The dwelling shall occupy not more than 90% of a
✓ enclosures of vertical openings; fire
corner lot and 80% of an inside lot, and subject to
the provisions on Easements of Light and View of the extinguishing systems.
Civil Code of Philippines, shall be at least 2 meters ✓ special hazards.
from the property line.
BUILDING PROJECTION OVER PUBLIC STREETS
B. Light and Ventilation
Every dwelling shall be so constructed and arranged • Projection into Alleys or Streets
as to provide adequate light and ventilation as ➢ No part of any structure or its appendage shall
project into any alley or street, national road, or
provided under the section in this code.
public highway except as provided in this Code.
C. Sanitation
➢ Footings located at least 2.40 meters below
Every dwelling shall be provided with at least one
sanitary toilet and adequate washing and drainage grade along national roads or public highway
may project not more than 300 millimeters
facilities.
beyond the property line.
D. Foundation
Footings shall be of sufficient size and strength to ➢ Foundations may be permitted to encroach into
support the load of the dwelling and shall be at least public sidewalk areas to a width not exceeding
500 mm; provided, that the top of the said
250 millimeters thick and 600 millimeters below the
foundations is not less than 600 mm below the
surface of the ground.
E. Post established grade; and provided further, that
Each post shall be anchored to such footing by straps said projection does not obstruct any existing
utility such as power, communication, gas,
and bolts of adequate size.
water, or sewer lines, unless the owner
F. Floor - The live load of the first floor shall be at
concerned shall pay the corresponding entities
least 200 kilograms per square meter and for the
second floor, at least 150 kilograms per square for the rerouting of the parts of the affected
meter. utilities.
G. Roof - The wind load for roofs shall be at least 120
kilograms per square meter for vertical projection.
• Projection of Balconies over Streets 3. Fences - Fences shall be built of an approved material,
The clearance between the established grade of the not less than 2.40 m in height above grade, and be
street and/or sidewalk and the lowest under surface of placed on the side of the walkway nearest to the building
any part of the balcony shall not be less than 3.00 site. Fences shall enclose entirely the building site.
meters. Openings in such fences shall be provided with doors
which shall be kept closed at all times.
PROTECTION OF PEDESTRIANS DURING CONSTRUCTION 4. Canopies - The protective canopy shall have a clear
OR DEMOLITION height of 2.40 m above the railway and shall be
structurally safe. Every canopy shall have a solid fence
• Storage in Public Property built along its entire length on the construction side. If
Materials and equipment necessary for work to be done materials are stored or work is done on top of the canopy,
under a permit when placed or stored on public property the edge along the street shall be protected by a tight
shall not obstruct free and convenient approach to and curb board not less than 300 mm high and a railing not
use of any fire hydrant, fire or police alarm box, utility less than 1.00 m high shall be provided. The entire
box, catch basin, or manhole and shall not interfere with structure shall be designed to carry the loads imposed
any drainage of any street or alley gutter. upon it: Provided, that the live load shall be not less than
600 kilograms per square meter.
• Mixing Mortar on Public Property
The mixing of mortar, concrete, or similar materials on • General Design and Construction Requirements
public streets shall not be allowed. Excavation, Foundation, and Retaining Walls

• Protection of Utilities ▪ Excavation and Fills


➢ All public or private utilities above or below the 1. Excavation or fills for buildings or structures shall be so
ground shall be protected from any damage by constructed or protected that they do not endanger life
any work being done under the permit. or property.
➢ The protection shall be maintained while such 2. Whenever the depth of excavation for any construction
work is being done and shall not obstruct the is such that the lateral and subjacent support of the
normal functioning of any such utility. adjoining property or existing structure thereon would be
affected in a manner that the stability or safety of the
• Walkway same is endangered, the person undertaking or causing
➢ When the Building Official authorizes a sidewalk the excavation to be undertaken shall be responsible for
to be fenced or closed, or in case there is no the expense of underpinning or extending the foundation
sidewalk in front of the building site during or footings of the aforementioned property or structure.
construction or demolition, a temporary 3. Excavation and other similar disturbances made on
walkway of not less than 1.20 meters wide shall public property shall, unless otherwise excluded by the
be provided. Building Official, be restored immediately to its former
➢ The walkway shall be capable of supporting a condition within 48 hours from the start of such
uniform live load of 650 kilograms per square excavation and disturbances by whosoever caused such
meter. A durable wearing surface shall be excavation or disturbance.
provided throughout the construction period.
▪ Footings, Foundations, and Retaining Wall
• Pedestrian Protection 1. Footings and foundations shall be of the
1. Protection Required - Pedestrian traffic shall be appropriate type, of adequate size, and capacity to
protected by a railing on the street side when the safely sustain the superimposed loads under
walkway extends into the roadway, by a railing when seismic or any condition of external forces that may
adjacent to excavations. affect the safety or stability of the structure.
2. Railings - Adequate railings when required shall be 2. Whenever or wherever there exist in the site of the
built substantially strong and should be at least 1.00 m in construction an abrupt change in the ground levels
height. or level of the foundation such that instability of the
soil could result, retaining walls shall be provided and to the requirements specified under the type of
such shall be of adequate design and type of construction of the building in which they are
construction as prescribed. located.
Air Ducts
▪ Veneer ➢ Air ducts passing through a floor shall be
➢ Veneer is a nonstructural facing of brick, enclosed in a shaft. The shaft shall be as required
concrete, tile, metal, plastic, glass, or other in this Code for vertical openings. Dampers shall
similar approved materials attached to a be installed where ducts pierce the shaft
backing or structural components of the enclosure walls. Air ducts in Group A
building for the purpose of ornamentation, Occupancies need not be enclosed in a shaft if
protection, or enclosure that may be adhered, conforming to the mechanical provisions of this
integrated, or anchored either on the interior or Code.
exterior of the building or structure. • Floor Construction
Design Requirements ➢ Floors shall be of such materials and construction
1. Veneer shall support no load other than its own as specified under Fire Zones and Fire-Resistive
weight and the vertical dead load of veneer Standards and under Types of Construction.
immediately above. ➢ All floors shall be so framed and secured into the
2. Surfaces to which veneer is attached shall be framework and supporting walls as to form an
designed to support the additional vertical and integral part of the whole building.
lateral loads imposed by the veneer. ➢ The types of floor construction used shall provide
3. Consideration shall be given to differential means to keep the beam and girders from lateral
movements of the supports including those caused buckling.
by temperature changes, shrinkage, creep, and ➢ The types of floor construction used shall provide
deflection. means to keep the beam and girders from lateral
4. Adhered veneer and its backing shall be designed buckling.
to have a bond to the supporting elements sufficient
to withstand shearing stresses due to their weights • Roof Construction and Covering
including seismic effects on the total assemblage. ▪ Roof Covering
5. Anchored veneer and its attachment shall be Roof covering for all buildings shall be either fire-
designed to resist horizontal forces equal to twice the retardant or ordinary depending upon the fire-resistive
weight of the veneer. requirements of the particular type of construction. The
6. Anchors supports and ties shall be non- use of combustible roof insulation shall be permitted in
combustible and corrosion resistant. all types of construction provided it is covered with
approved roof covering applied directly thereto.
• Enclosure of Vertical Openings
Vertical openings shall be enclosed depending upon the Roof Trusses
fire-resistive requirements of a particular type of All roofs shall be so framed and tied into the framework
construction. and supporting walls so as to form an integral part of the
whole building. Roof trusses shall have all joints well
Elevator Enclosures fitted and shall have all tension members well tightened
➢ Walls and partitions enclosing elevators and before any load is placed in the truss. Diagonal and sway
escalators shall be of not less than the fire- bracing shall be used to brace all roof trusses. The
resistive construction required under the Types allowable working stresses of materials in trusses shall
of Construction. Enclosing walls of elevator conform to this Code. Camber shall be provided to
shafts may consist of wire glass set in metal prevent sagging.
frames on the entrance side only. ✓ Camber - During production, trusses improve on
Other Vertical Openings traditional rafter design by forcing an upward
➢ All shafts, ducts, chutes, and other vertical bend into the chords of trusses. This is referred
openings shall have enclosing walls conforming to as a 'camber'. A camber helps to resist loads.
For example, the amount of bend is calculated to number of persons. No obstruction shall be placed in the
help resist the load of tiles and ceiling lining. The required width of an exit except permitted projections.
calculations are designed to ensure the truss 3. Posting of Room Capacity – Any room having an
eventually flattens out to provide straight chords occupant load of more than 50 where fixed seats are not
once it is fully loaded. installed, and which is used for classroom, assembly, or
Attics similar purpose shall have the capacity of the room
➢ An attic access opening shall be provided in the posted in a conspicuous place near the main exit from the
ceiling of the top floor of buildings with a room.
combustible ceiling or roof construction. 4. Changes in Elevation – Except in Group A Occupancies,
➢ The opening shall be located in a corridor or changes in floor elevations of less than 300 millimeters
hallway of buildings of three or more storeys in along any exit serving a tributary occupant load of 10 or
height, and readily accessible in buildings of any more shall be by means of ramps.
height.
➢ An opening shall not be less than 600 mm • Exits
square or 600 mm in diameter. 1. Number of Exits – Every building or usable portion
➢ The minimum clear headroom of 800 mm shall thereof shall have at least one exit. In all occupancies,
be provided above the access opening. For floors above the first storey having an occupant load of
ladder requirements, refer to the Philippine more than 10 shall not have less than two exits. Each
Mechanical Engineering code. mezzanine floor used for other than storage purposes, if
greater in area than 185 square meters or more than
Roof Drains 18.00 meters in any dimension, shall have at least two
Roof drains shall be installed at low points of the roof and stairways to an adjacent floor.
shall be adequate in size to discharge all tributary waters. 2. Width – The total width of exits in meters shall not be
less than the total occupant load served divided by 165.
Overflow Drains and Scuppers Such width of exits shall be divided approximately equally
Where roof drains are required, adequate overflow among the separate exits.
drains shall be provided. 3. Arrangement of Exits –If only two exits are required,
they shall be placed a distance apart to not less than 1/5
Concealed Piping of the perimeter of the area served measured in a
Roof drains and overflow drains, when concealed within straight line between exits.
the construction of the building, shall be installed in 4. Distance to Exists - No point in a building without a
accordance with the provisions of the National Plumbing sprinkler system shall be more than 45 m from an
Code. exterior exit door, a horizontal exit, exit passageway, or
an enclosed stairway, measured along the line of travel.
Over Public Property of Roof Drainage System In a building equipped with a complete automatic fire
Roof drainage water from a building shall not be extinguishing system the distance from exits may be
permitted to flow over public property, except for Group increased to 60 m
A and J Occupancies.

Stairs, Exits, and Occupant Loads


1. Determination of Occupant Loads – The occupant load
permitted in any building or portion thereof shall be • Doors
determined by dividing the floor area assigned to that 1. Width and Height – Every required exit doorway shall
use by the unit area allowed per occupant as determined be of a size as to permit the installation of a door not less
by the Secretary. than 900 millimeters in width and not less than 2.00
2. Exit Requirements – Exits requirements of a building meters in height.
or portion thereof used for different purposes shall be 2. Door Leaf Width – No leaf of an exit door shall exceed
determined by the occupant load which gives the largest 1.20 meters in width.
3. Additional Doors – When additional doors are
provided for egress purposes, they shall conform to all ➢ The performance of the building envelope is
provisions in the following cases: Approved revolving impacted by a number of sub-systems, such as
doors having leaves which will collapse under opposing heating, cooling and ventilating equipment,
pressures may be used in exit situations; provided; that plumbing and electrical systems.
such doors have a minimum width of 2.00 meters or they ➢ The interaction of the sub-systems with the
are not used in occupancies where exits are required to components of the building envelope, as well as
be equipped with panic hardware or at least one certain activities of the occupants, can affect the
conforming exit door is located adjacent to each performance of the building envelope.
revolving doors installed in a building and the revolving The building envelope is the enclosure, barrier, and
door shall not be considered to provide any exit width. separator of the outdoor environment and the desired
indoor environment. It is also the protector from the
• Stairways undesired outdoor threats of danger.
1. Width – minimum of 750 millimeters
2. Rise and Run – The rise of every step in a stairway shall
not exceed 200 millimeters and the run shall not be less
than 250 millimeters.
3. Landings – Every landing shall have a dimension
measured in the direction of travel equal to the width of
the stairway. Such dimension need not exceed 1.20
meters when the stairs have a straight run.
4. Handrails – shall be placed not less than 800 What is it supposed to do?
millimeters nor more than 900 millimeters above the
nosing of treads and ends of handrails shall be returned The building envelope should keep out:
or shall terminate in newel posts or safety terminals.
✓ temperature extremes
✓ moisture, as vapor or liquid
Fire-Extinguishing Systems
✓ Dust
➢ In every storey, basement or cellar with an area
✓ Wind
of 200 square meters or more which is used for
habitation, recreation, dining, study, or work, Additionally, to maintain durability, the building
and which has an occupant load of more than envelope should not permit weather elements to be
20. trapped inside the walls. This may cause wall
➢ In all dressing rooms, rehearsal rooms, components to deteriorate and continue to decay. In
workshops or factories, and other rooms with an the early stages, it can usually be remedied relatively
occupant load of more than 10 or assembly halls inexpensively. As time progresses, costs increase
under Group H and I occupancies with occupant exponentially.
load of more than 500, and if the next doors of
MAINTENANCE & INSPECTIONS
said rooms are more than 30.00 meters from the
nearest safe fire dispersal area of the building or ➢ The building envelope, like a car, requires
opening to an exit court or street. regular inspection and maintenance. Some
➢ In all rooms used for storage or handling of maintenance guides suggest the exterior of the
photographic x-ray nitrocellulose films and building does not need much attention in the
other inflammable articles. early years.
➢ The numerous failures of building envelopes in
LESSON 4. BUILDING ENVELOPE the costal climate zone suggests that it is wise to
The building envelope includes all the building have an inspection program in place that starts
components that separate the indoors from the in the first year of occupancy in a building and
outdoors. Building envelopes include the exterior continues annually thereafter. This inspection
walls, foundations, roof, windows and doors. should be done by an experienced professional.
➢ If problems can be detected early, before RAIN PENETRATION
obvious damage is caused, they can be Generally, there are three factors which are needed for
remedied at much less expense and while any water to penetrate a building:
existing warranty programs are still in effect.
1. presence of water on the exterior of the building.
PREVENTING PROBLEMS
2. an opening for the water to move through, and
If your strata corporation does not have a schedule for 3. a driving force (such as wind or gravity).
maintenance and inspection of the building envelope:
Wind will create a pressure difference between indoors
➢ Communicate the need for this precaution in and outdoors. In both face seal and rainscreen systems,
writing to the strata council. this pressure change occurs primarily at the most air-
➢ Attend the Annual General Meeting and explain tight element in the wall construction. This air-tight
why a maintenance program is important. If material is referred to as the air-barrier.
possible, give examples of problems
encountered by other condominium complexes ➢ Face seal refers to a strategy for rain penetration
that were aggravated by the lack of a control that relies solely on the elimination of
maintenance program. holes in the exposed exterior face of the
➢ Put forth in a motion to the AGM the need for a assembly.
maintenance program and that it is recorded in ➢ Face sealed walls rely on creating a completely
the minutes of the meeting. impervious barrier to water at the outer face of
How do you know if there is a problem? A problem likely the wall. This is also the air barrier, thus it is at
exists if there is: the surface at which the pressure drop occurs.
➢ This surface is frequently wetted, and any
▪ no regular inspection and preventive maintenance imperfections in the face seal will certainly lead
program in place to air movement through the holes, which in
▪ mold or fungi formation turn will create the driving force required to
▪ wood rot bring the water into the wall assembly, and trap
▪ water flowing down the sides of the building instead it there. The water remains in the wall, or dries
of running off from the eaves and drainpipes. slowly, causing deterioration of wood
▪ wind blowing through the walls. components.
▪ peeling paint ➢ Rainscreen assemblies refers to a construction
▪ cracked or missing sealants (caulking) strategy for rain penetration control that relies
▪ water stains on inside walls, ceilings or inside the on the deflection of the majority of water at the
foundation cladding but also incorporates a cavity which
▪ gaps that allow the weather to get through the walls. provides a drainage path for water that
▪ pools of water on the decks penetrates past the cladding.
▪ windows that are wet on the inside. ➢ Rainscreen technology recognizes that some
incidental water may penetrate the exterior
cladding but allows this water to drain through
These problems may not all be related to a failure of the the rainscreen cavity.
building envelope: ➢ Rainscreen technology can come in many
different designs and has been evolving since its
➢ Some may be localized maintenance items that
earliest use in the late 1940s.
can be fixed relatively inexpensively.
➢ In the example shown below, the air- barrier is
➢ Some may be caused by interior systems in the
illustrated to occur across the sheathing paper
unit. For example, an un-vented clothes dryer
that is on the exterior surface of the sheathing.
will create moisture inside.
➢ The cladding is not airtight, and in fact,
➢ Some are caused by certain activities of the
deliberate openings are left to facilitate drainage
occupants. For example, hanging wet clothes
and drying.
inside will create excessive moisture.
➢ The pressure drop therefore occurs primarily at Systematically describes the principles by which good
the sheathing paper. By moving the pressure architectural details are designed. Principles are
drop away from the cladding, the driving force is explained in brief, and backed by extensive illustrations
removed from the cladding, which greatly that show you how to design details that will not leak
reduces the potential for water to move past it. water or air, will control the flow of heat and water vapor,
➢ The small amount of water that does pass will adjust to all kinds of movement, and will be easy to
through the cladding drains through the cavity, construct.
leaving the interior of the wall assembly dry.
Structural
DESIGN CONSIDERATIONS 1. Loads
2. Resistance/Material
Architectural 3. Serviceability
4. Strength
1. Building layout and shape 5. Relative Moments
The shape of a building layout is the spatial attribute that 6. Control/Joints
defines the outline of the building. It affects the areas and Environmental
sizes of vertical components such as external walls and 1. Thermal
associated finishes, windows, partitions and associated 2. Moisture/Air
finishes, etc., as well as the perimeter detailing such as 3. Sound
ground beams, fascias, and the eaves of roofs. 4. Fire
Mechanical
2. Efficiency 1. Heat
Design that make efficient use of energy and resources. 2. Ventilation
The problem of energy efficient, reliable multi-layer 3. Air-conditioning
network design is known to result in different trade-offs Human Requirements for Buildings
between key performance measures. o Sensitivity to thermal changes and air
movements
3. Fenestration o Sensitivity to vibrations and noise
The arrangement of windows and doors on the o Problems of vision, within a building and
elevations of a building. Fenestration refers to the looking out from a building
openings in the building envelope, including the o Social aspects and location
installation of windows, doors, and skylights. o Safety
Requirements for a Barrier
The inclusion of windows and other openings in the 1. Durability
home are necessary as they improve the overall 2. Strength
environment inside the home, however they do work to 3. Rigidity
break the seal of the home, providing possible places for 4. Control of heat flow (Insulation)
air, water, and cold air to enter the home 5. Control of air flow (Air Barrier)
The number of openings included in a home must be 6. Control of vapor flow (Vapor)
taken into account, as well as the quality of the materials 7. Control of rain penetration
used to create these openings along with the placement. 8. Control of solar and other radiation
9. Control of sound transmission
➢ Benefits of fenestration in the building envelope 10.Control of fire protection
✓ increase in comfort. 11.Aesthetically pleasing
✓ improve indoor air quality. 12.Economical requirements
✓ saving money
✓ control condensation.
LESSON 5
4. Detailing I. BUILDING DESIGN PROCESS
II. BUILDING REFERRAL CODES ✓ Schedule of Finishes: floors, walls, ceilings

➢ National Building Code of the Philippines (PD


1096) and its Implementing Rules and III. ARCHITECTURAL DESIGN
Regulations
PD 1096 Referral Codes: (Technical Professional • Site Development Plan
➢ In SDP, the position, shape, and dimensions of
Codes)
the proposed project are shown.
➢ Architectural Code of the Philippines – UAP
➢ The improvements proposed to be introduced on
➢ National Structural Code of the Philippines –
the property are also indicated.
ASEP
➢ Philippine Electrical Code – IIEE • ARCHITECTURAL DESIGN DOCUMENTS
➢ Philippine Mechanical Code – PSME
➢ Philippine Electronics Code – IECEP • Vicinity Map/Location Plan
➢ National Plumbing Code of the Philippines – ➢ The Lot Plan is prepared by the Geodetic
NAMPAP Engineer on a prescribed drawing sheet.
➢ Uniform Plumbing Code – PSSE ➢ The exact position of the project site in a
➢ Accessibility Law (BP 344) – DPWH, DOTC subdivision or community is pinpointed.
➢ Fire Code of the Philippines – BFP, DILG ➢ Details shown on the location map are
➢ Code on Sanitation of the Philippines – NWRB the lots, blocks and the network of roads
➢ Climate Change Act (RA 9729) in the area, etc.
➢ Philippine Disaster Risk Reduction Management • Perspective
Act (RA 10121) ➢ Perspective is a technique for depicting
➢ National Cultural Heritage Act (RA 10066) three-dimensional volumes and spatial
➢ Philippine Green Building Code – DPWH relationships in two dimensions, as if
➢ DGCS Vol. 6 (Public Buildings and other related from the view-point of an observer.
structures) – DPWH ➢ The main characteristic of perspective is
➢ Other applicable codes/clearances, LGU that objects appear smaller the further
ordinances/Zoning regulations they are from the observer.

• ARCHITECTURAL DESIGN • ARCHITECTURAL DESIGN PROCESS

➢ Functionality, aesthetics, sustainability, climate


change adaptability, disaster resiliency
➢ Compliance with Project’s TOR/Proponent’s
Space/Area Requirements and Amenities (SAS, if
Office Building)
➢ Compliance with PD 1096, its IRR and its various
Referral Codes, other Agency Codes/Standards,
LGU Ordinances/Zoning Regulations

• ARCHITECTURAL DESIGN DOCUMENTS • ARCHITECTURAL DESIGN


✓ Site Development Plan General Acceptability Criteria for Site Planning
✓ Vicinity Map/Location Plan
✓ Perspective ➢ Site Development Plan (SDP) is a pre-building
✓ Floor Plans (min scale 1:100) design activity to position a proposed building
✓ Elevations (4) (min scale 1:100) within the confines of its host site.
✓ Sections (2) (min scale 1:100) ➢ An SDP properly founded on site investigations
✓ Roof Plan (min scale 1:100) can result in vast savings.
✓ Details (in forms of plans, elev./sect. min scale
1:50)
✓ Schedule of Doors and Windows Minimum Building Setbacks and Footprint
FOUNDATION PLAN (SAME SCALE WITH
ARCHITECTURAL PLAN)
➢ Property line, footing and column designations.
➢ Location of walls with wall footings, slab on fill
thickness and rebar spacing

FLOOR FRAMING PLAN (SAME SCALE WITH


ARCHITECTURAL PLAN)
➢ Beam, column, RC wall, and slab designation
➢ Columns terminated at a particular floor should
be hatched.

ROOF FRAMING PLAN (SAME SCALE WITH


ARCHITECTURAL PLAN)
➢ Roof beams, truss, rafters, bracings designations
➢ Purlin size and spacing call out

SCHEDULE AND TYPICAL DETAILS

➢ Slabs, beams, footings showing all necessary


dimensions and rebar size and number
➢ Detailed column section and typical column
elevation showing splice
IV. STRUCTURAL DESIGN ➢ Truss and rafter schematic diagrams with sizes
and connection details with gusset plate at all
➢ Stability, resiliency, serviceability, economically
truss joints
viable (Value Engineering)
➢ Purlin to roofing (J-bolt), sagrod, bracing
➢ Structural systems and members shall be
connection details
designed to have adequate stiffness to limit
➢ Stair details
deflections, lateral drifts, vibration and shall
➢ Shear wall and footing details, ramp details
result in a system that provides a complete load
➢ Elevated water tank detail including concrete
path capable of transferring all loads and forces
saddles.
from their origin to the load resisting element.
➢ Cistern, septic tank details
(Section 104, Chapter 1, NSCP 2010)
• STRUCTURAL CODES AND REFERENCES
• STRUCTURAL DESIGN DOCUMENTS
National Structural Code of the Philippines (NSCP 2015)
General Notes
✓ Referral Code of RA 6541 National Building Code
➢ Excavation notes including soil bearing capacity. of the Philippines (NBCP)
➢ Construction notes and design criteria ✓ Code Basis: UBC 1997, IBC 2009, ASCE 7-10, ACI
➢ Notes on rebars and structural steel Code 318-14M, AISC-05
➢ Notes requiring shop drawings.

MASONRY • STRUCTURAL LOADINGS


➢ Wall footings, CHB wall reinforcements
1. Dead Load
➢ CHB wall opening details, lintel beam location
➢ weight of the structure and permanent
and details, stiffener details.
attachments
➢ Rebar splice, development length, hook schedule
➢ self-weight
➢ Slab opening
➢ Roofing materials
➢ Pipe sleeve on beam, change in elevation of
➢ Ceiling
beams.
➢ Plumbing and electrical fixtures
➢ Finishes ➢ analysis due to earthquake
➢ Fixed equipment ➢ NSCP 2015 Section 208

2. Live Load ➢ Lateral force Procedures


➢ maximum loads expected due to intended use or ✓ Simplified Static
occupancy. ✓ Static
➢ NSCP 2015 Section 205 ✓ Dynamic
➢ determined by the function and occupancy of
• Seismic Load – Parameters in Building Design
the building.
➢ Weights of temporarily placed items. ➢ Seismic Zone, Z
✓ Furnishings ➢ Site characteristics
✓ Human occupants ✓ Soil profile type & zone (seismic coefficient)
✓ Construction activities ✓ Seismic Source Type & Distance from Fault
line
➢ Occupancy
➢ Building Configuration (regular or irregular)
➢ Earthquake Force Resisting Structural Systems

(NSCP Table 1.3-1 Occupancy Category)

3. Wind Load 5. Other Load (impact load, crane loads, heliport landing
➢ NSCP 2015 Section 207 areas, soil load)
➢ every building and every portion thereof shall be
designed and constructed to resist the effects of
wind. V. GEOTECHNICAL WORKS
➢ Design wind load for the Main Wind Force
• Site Investigation
Resisting System (MWFRS)
➢ For structures two storeys or higher, an
4. Seismic Load exhaustive geotechnical shall be
➢ Structures and portions thereof shall, as a performed to evaluate in-situ soil
minimum, be designed and constructed to resist parameters for foundation design and
the effects of seismic ground motions. analysis.
➢ Foundation Investigation (NSCP 2015
Section 303.1)
• GEOTECHNICAL WORKS
➢ Minimum number of boreholes per
structure (NSCP 2015 Table 303-1) Site Investigation
➢ An exhaustive geotechnical investigation should
also be conducted in cases of:
✓ questionable, expansive or problematic
soils.
✓ to determine the location of existing
ground water table.
✓ Floor is located below finished ground
level.
✓ If Pile Foundation and/or ground
improvement are anticipated.
✓ Rock strata is suspected to be
questionable.
✓ Other cases deemed by the
Geotechnical Engineer

• NON-STRUCTURAL FAILURES
A borehole is a hole that is bored beneath the ground
Collapsed CHB Walls
during a geotechnical evaluation of a design pathway
➢ Inadequate dowels/rebars and poor quality
for the installation of underground services.
CHB
Conceptually similar to potholing, a borehole NOTE: The non-structural elements like CHB walls
provides information about the design pathway
may alter the assumed structural response
itself.
Collapsed Ceiling
➢ Lack of ceiling hangers (support)
Collapsed RC Gutter
➢ R.C./CHB gutter collapsed due to lack of
anchorage and nonexistence of column
stiffeners.
Collapsed Column
➢ Improper tie hook end and improper splicing

VI. BUILDING SERVICES (ELECTRICAL, MECHANICAL,


ELECTRONICS, SANITARY & PLUMBING)

• ELECTRICAL DESIGN
Governing Laws and Applicable Codes and Standards • Governing Laws and Applicable Codes and
Standards
➢ RA 7920 – New Electrical Engineering Law
o RA 1096 – National Building Code of the
➢ P.D. 1096 – National Building Code of the
Philippines (NBCP)
Philippines (NBCP)
o RA 9514 – Fire Code of the Philippines
➢ RA 9514 – Fire Code of the Philippines
o RA 9592 – Electronics Engineering Law
➢ Philippine Electrical Code (PEC)
o Philippine Electrical Code
➢ DoE Guidelines, etc.
• SANITARY & PLUMBING DESIGN
• ELECTRICAL DESIGN DOCUMENTS

✓ Location Plan
✓ Single Line Diagram
✓ General Notes
✓ Legends/Symbols
✓ Lighting Plan
✓ Power Plan
✓ Load Schedules
✓ Schematic and Control Diagrams
✓ Installation Details
✓ Exterior Distribution System Plan
✓ Technical Specifications
Governing Laws and Applicable Codes and Standards
✓ Bill of Materials
✓ Project Estimate ➢ P.D. 1096 – National Building Code of the
• MECHANICAL DESIGN Phillippines (NBCP)
➢ RA 1364 - Sanitary Enginering Law
➢ RA 1378 - Master Plumbing Law
➢ Fire Code of the Philippines
➢ National Plumbing Code of the Philippines
➢ Philippine Clean Water Act of 2004
➢ PD 1067 - Water Code of the Philippines
➢ Solid Waste Management Act of 2002

Governing Laws and Applicable Codes and Standards

➢ P.D. 1096 – National Building Code of the


Philippines (NBCP)
➢ RA 9514 – Fire Code of the Philippines
➢ Philippine Society of Mechanical Engineering
(PSME), Mechanical Engineering Code

• ELECTRONICS DESIGN

You might also like