TECHNICAL MANUAL
AGS 429 FLUSHLINE DOUBLE GLAZED (100mm)
The AGS 429 double glazed Flushline (100mm) commercial framing system has
been developed to accommodate both internal and external glazing techniques.
Its front glazed arrangement has been designed to maximise internal areas whilst
achieving a clean and modern external appearance.
GREEN Water Penetration 900Pa CAP-059-008 6EcAEG/12/6Clr 3.0 0.27 0.38 0.09
The table below is a summary of this manual’s update history. Contact Capral for details of past updates.
The table below shows the details of the latest manual update.
Please read in conjunction with Important Conditions – Index (also available on Capral website)
IMPORTANT CONDITIONS ..
By using this manual you agree to the following:
DISCLAIMER ..
Whilst best efforts have been made to ensure the details contained herein are accurate and correct, Capral is not
responsible for any loss or damage whatsoever arising as a result of any errors contained in this manual. Interpretation of
standards or codes within this manual is Capral’s interpretation of such codes. Responsibility for code compliance remains
with the user of this manual. In some cases product specifications may vary without notice. Users should not act or rely
upon any information contained in this manual without obtaining appropriate professional advice relating to their particular
circumstances. To the maximum extent permitted by law Capral disclaims all liability for loss or damage suffered by anyone
who acts or fails to act in reliance of this manual.
COPYRIGHT ..
This manual remains the property of Capral and contains information which is the subject of copyright. The manual or any
part of it may not be reproduced, copied or loaned in any form without the prior written permission of Capral. The manual is
to be returned to Capral on request.
Please read in conjunction with Important Conditions – Index (also available on Capral website)
SPECIFICATIONS Section 1 .
Product Specifications 1
COMPONENTS Section 3 .
Glazing Details 1–3
Components 4
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Please read in conjunction with Important Conditions – Index (also available on Capral website)
SIZE LIMITATIONS
NOTE: Refer to the information below & Span Tables to check the maximum sizes that can be achieved for the
assigned performance requirements of the installation. Contact your Account Manager for any requirements
outside these limitations.
The Serviceability Pressures listed in the Span Tables have not been limited by a water performance.
Where water performance is necessary the product should be limited to the following maximum water ratings or
serviceability pressures:
Note: The use of a standard Subsill has been assumed for the Water Performance Ratings listed above.
Please read in conjunction with Important Conditions – Index (also available on Capral website)
38
P.P.
E34300
FLUSH FILLER
Paint Perimeter: 100mm
8
100
P.P.
55
EP16297
FRAME
Paint Perimeter: 472mm
Anodised Perimeter: 708mm
100
P.P.
55
EP19054
R2 FRAME
Paint Perimeter: 488mm
Anodised Perimeter: 732mm
EP16299
SMALL FLAT FILLER
Paint Perimeter: 100mm
P.P. 41 Anodised Perimeter: 132mm
Please read in conjunction with Important Conditions – Index (also available on Capral website)
27
18
EP17218
REVEAL FIN ADAPTOR
Paint Perimeter: NA
Anodised Perimeter: 321mm
82
82
P.P.
E19992
FLAT FILLER
Paint Perimeter: 100mm
8
EP7710
ALT. FRAME
Paint Perimeter: 191mm
Anodised Perimeter: 637mm
P.P. 100
55
EP19051
ALT. R2 FRAME
Paint Perimeter: 436mm
Anodised Perimeter: 653mm
P.P. 100
Please read in conjunction with Important Conditions – Index (also available on Capral website)
28.5
EP7713
INTERNAL BEAD
Paint Perimeter: 100mm
Anodised Perimeter: 262mm
55
26.5
EP7712
INTERNAL
SILL / TRANSOM
Paint Perimeter: 150mm
Anodised Perimeter: 451mm
P.P. 100
55
26.5
EP19076
R2 INTERNAL
SILL / TRANSOM
Paint Perimeter: 313mm
Anodised Perimeter: 469mm
P.P. 100
8.5 56
P.P. P.P.
EP7715
COVER BEAD
Paint Perimeter: 100mm
Anodised Perimeter: 147mm
55
55
EP7717
COVER
SILL / TRANSOM
Paint Perimeter: 167mm
Anodised Perimeter: 394mm
Please read in conjunction with Important Conditions – Index (also available on Capral website)
P.P.
EP13365
EXTERNAL BEAD
Paint Perimeter: 100mm
Anodised Perimeter: 133mm
35
P.P.
55
EP16298
EXTERNAL
SILL / TRANSOM
Paint Perimeter: 404mm
Anodised Perimeter: 605mm
P.P. 100
100
P.P.
100
E31961
CORNER POST
Paint Perimeter: 200mm
Anodised Perimeter: 455mm
Please read in conjunction with Important Conditions – Index (also available on Capral website)
100
E33696 E33693
MALE MULLION FEMALE MULLION
Paint Perimeter: 116mm Paint Perimeter: 118mm
Anodised Perimeter: 519mm Anodised Perimeter: 452mm
P.P. 27 P.P. 28
100
100
EP19052 EP19053
R2 MALE MULLION R2 FEMALE MULLION
Paint Perimeter: 323mm Paint Perimeter: 313mm
Anodised Perimeter: 484mm Anodised Perimeter: 469mm
P.P. 27 P.P. 28
Please read in conjunction with Important Conditions – Index (also available on Capral website)
P.P.
113
.5
29 EP18083
CORNER MULLION
P.P. COUPLER
Paint Perimeter: 394mm
Anodised Perimeter: 591mm
100
EP18085
CORNER MULLION
Paint Perimeter: 440mm
Anodised Perimeter: 660mm
64.5
Please read in conjunction with Important Conditions – Index (also available on Capral website)
55
EP16933
DG STRUCTURAL TRANSOM
Paint Perimeter: 284mm
Anodised Perimeter: 284mm
27.5 27.5
P.P. P.P.
57
57
EP16932 EP16931
DG STRUCTURAL FEMALE DG STRUCTURAL MALE
MULLION MULLION
Paint Perimeter: 226mm Paint Perimeter: 263mm
Anodised Perimeter: 339mm Anodised Perimeter: 394mm
Please read in conjunction with Important Conditions – Index (also available on Capral website)
17 11
P.P. P.P.
E31819 EP11223
SHALLOW TG ADAPTOR
18
18
SHALLOW SG ADAPTOR
Paint Perimeter: 100mm Paint Perimeter: 100mm
Anodised Perimeter: 115mm Anodised Perimeter: 131mm
17 11
P.P. P.P.
31
31
E31818 EP11224
DEEP SG ADAPTOR DEEP TG ADAPTOR
Paint Perimeter: 100mm Paint Perimeter: 100mm
Anodised Perimeter: 179mm Anodised Perimeter: 175mm
17
P.P.
101.6mm NARROWLINE - 80
29.5
EP11149 EP10536
ALT. SG ADAPTOR FLUSHLINE / NARROWLINE COUPLER
Paint Perimeter: 100mm Paint Perimeter: NA
Anodised Perimeter: 144mm Anodised Perimeter: 258mm
25
20
P.P. P.P.
25 25
EK9216 EK9111
25 x 25 x 1.6 TRIM ANGLE 25 x 20 x 1.6 TRIM ANGLE
Paint Perimeter: 100mm
Paint Perimeter: 100mm
Anodised Perimeter: 100mm
Anodised Perimeter: 100mm
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Please read in conjunction with Important Conditions – Index (also available on Capral website)
DRY GLAZING
GLASS SIZE WEDGE GAP WEDGE GAP
22mm 321919* 9.5mm 300011 7.5mm
300006 (315790*^) 6.5mm 300011 7.5mm
24mm
321919* 9.5mm 301232 4.5mm
26mm 301232 (315789*) 4.5mm 300011 7.5mm
27mm 301232 (315789*) 4.5mm 300006 6.5mm
* Captive Wedge Alternative
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Please read in conjunction with Important Conditions – Index (also available on Capral website)
STRUCTURAL GLAZING
GLASS SIZE GLAZING TAPE CAPTIVE WEDGE GAP GLAZING WEDGE GAP
22mm 6.4mm 322608 7.5mm 300011 7.5mm
24mm 3.2mm 301232 4.5mm 301232 9.5mm
26mm 3.2mm 301232 4.5mm 300011 7.5mm
27mm 3.2mm 301232 4.5mm 300006 6.5mm
Please read in conjunction with Important Conditions – Index (also available on Capral website)
316051 309156
CO-EXT EXPANSION JOINT SEAL 8g x 13mm CSK HEAD
500m ROLL - SC EACH
(10146) (FSC151)
300058 301304
10g x 12mm SS CSK SCREW U/C 8g x 40mm CSK SCREW
EACH EACH
(M028354) (M029591)
300064 300059
10g x 25mm CSK SCREW 10g x 25mm SS PAN SCREW
EACH EACH
(M029660) (M028598)
317494 317495
10g x 63mm CSK SCREW 10g x 76mm SS PAN SCREW
EACH EACH (MG086)
(MG089)
312431 315711
5-4 RIVET FEMALE MULLION
EACH, Ø4 x 6.4mm POCKET FILLER
(FRV021) EACH
(SPD03426)
315712 315713
FRAME POCKET FILLER MALE MULLION POCKET FILLER
EACH EACH
(SPD03427) (SPD03428)
311592 307411
REINFORCED FOIL TAPE PLASTIC NAILING FIN
50m ROLL CORNER COVER
(PT018) EACH
(SPD01182)
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Please read in conjunction with Important Conditions – Index (also available on Capral website)
© 15-08-2022
DD-MM-YYYY Sec4: Formula - Page 1
429 Flushline Framing System
Machining - Jambs & Mullions Scale 1:2
* CAVITY BEHIND THIS DRAINAGE PATH AT JAMBS TO BE SEALED WITH FULL HEIGHT FLAT OR FLUSH FILLER
** HOLES TO BE COUNTERSUNK FOR SPLIT AND STRUCTURAL MULLION
*** OPTIONAL ALTERNATIVE TO DRAINAGE ON TRANSOM
43 43
CTR CTR
25 16 25 16
CTR CTR CTR CTR
HEAD
19.5
CTR
EP7710 Ø10
** TRANSOM ONLY
50.5
CTR
SEE NOTE *
STRUCTURAL
Ø5
TRANSOM
TYP
50.5
CTR
34.5
CTR
INTERNAL & R2
INTERNAL SILL
CTR
4.5
EP7712 . EP19076 Ø10
INTERNAL TRANSOM
** TRANSOM ONLY
INTERNAL & R2
EP7712 . EP19076
**
4.5
CTR
CTR
28
STRUCTURAL
18.5
CTR
SILL
CTR
4.5
50.5
CTR
Ø10
COVER & EXTERNAL SILL
TRANSOM ONLY
TRANSOM
50.5
CTR
** CTR
28
18.5
CTR
EP7717
50.5
CTR
CTR
4.5
** 16 - 34 27
18.5
CTR
EP7717 CTR
CTR
ALTERNATING ON
SPLIT MULLION
CTR
4.5
16 16
CTR CTR
17.5
CTR
**
2
7 7 34
CTR
CTR CTR
Please read in conjunction with Important Conditions – Index (also available on Capral website)
* CAVITY BEHIND THIS DRAINAGE PATH AT JAMBS TO BE SEALED WITH FULL HEIGHT FLAT OR FLUSH FILLER
** HOLES TO BE COUNTERSUNK FOR SPLIT AND STRUCTURAL MULLION
43 43
16 CTR 25 16 CTR 25
CTR CTR CTR CTR
Ø10
19.5
CTR
TRANSOM ONLY
** SEE NOTE *
HEAD
TRANSOM
REVERSE EXTERNAL
50.5
CTR
Ø5
TYP
50.5
CTR
**
CTR
28
18.5
CTR
CTR
4.5
REVERSE
EXTERNAL SILL
INTERNAL TRANSOM
REVERSE INTERNAL & R2
50.5
** Ø10
TRANSOM ONLY
18.5
SEE NOTE *
CTR
EP7712
**
CTR
28
18.5
CTR
4.5
CTR
REVERSE INTERNAL
& R2 INTERNAL SILL
CTR
4.5
16
EP7712 CTR
** ALTERNATING ON
SPLIT MULLION
18.5
CTR
25
CTR
4.5
CTR
ALTERNATING ON
SPLIT MULLION
16 34
CTR CTR
17.5
CTR **
2
7 7 16
CTR CTR CTR
Please read in conjunction with Important Conditions – Index (also available on Capral website)
19.5
CTR
EP7710
TRANSOM
Ø4.6 - 4.7
50.5
CTR
HEAD TYP
DO NOT DRILL OVERIZE
A LARGER CLEARANCE HOLE WILL
ALLOW MATING OF
HEAD/SILL/TRANSOM
TO SLIP , CAUSING
MISALIGNMENT.
Ø10
TRANSOM ONLY
SEE NOTE * & ***
STRUCTURAL
50.5
CTR
TRANSOM
34.5
CTR
CTR
4.5
Ø10
TRANSOM ONLY
SEE NOTE * & ***
COVER &
50.5
CTR
EXTERNAL
TRANSOM
CTR
28
EP7717
18.5
CTR
CTR
4.5
50.5
CTR
COVER &
EXTERNAL SILL EP7717
18.5
CTR
16
CTR
CTR
4.5
16
CTR
EP18085
CORNER MULLION
Please read in conjunction with Important Conditions – Index (also available on Capral website)
60
60
5
TRANSOM HEIGHT = TH
TO CLEAR SCREW
HEAD @ 50.5
60
M
MU
X
NI
MA
MI
m
m
.5m
3m
15
H
TC
NO
SCREW HEAD
3m
EP18083
m
MI
Please read in conjunction with Important Conditions – Index (also available on Capral website)
22.5
25.5
135
°
CUTTING LENGTH = DOW + 25.5
EP7717
COVER SILL / TRANSOM
OPTIONAL TRIM
12.5
CUT LENGTH = DOW + 12.5
45°
Please read in conjunction with Important Conditions – Index (also available on Capral website)
50 50 EP7713
CTR
25
CTR INTERNAL BEAD
STD INSTALLATION WITH ALT. SIDE
TYP DRAINAGE TRANSOM ONLY
6
50 50 EP7713
CTR
25
CTR INTERNAL BEAD
TYP REVERSE INSTALLATION TRANSOM ONLY
FULL R
6
17.5
CTR
50 50
CTR CTR EP7712 . EP19076
25
TYP
INTERNAL TRANSOM
STD INSTALLATION TRANSOM ONLY
Please read in conjunction with Important Conditions – Index (also available on Capral website)
45°
CTR
50
25
25
CTR
50
45°
EP13365 EP13365
EXTERNAL BEAD EXTERNAL BEAD
OPTION 1 OPTION 2
STD INSTALLATION STD INSTALLATION
TRANSOM ONLY TRANSOM ONLY
6
50 50
CTR 25 25 CTR
EP16298 . EP15107 . EP13364 . EP14824
EXTERNAL TRANSOMS
STD INSTALLATION TRANSOM ONLY
Please read in conjunction with Important Conditions – Index (also available on Capral website)
41 56
CTR
50
25
25
CTR
50
Please read in conjunction with Important Conditions – Index (also available on Capral website)
24.5
43
38
43
24.5
EP17218
REVEAL FIN ADAPTOR
EP16298 . EP7717
EXTERNAL . COVER SILL / TRANSOM
Please read in conjunction with Important Conditions – Index (also available on Capral website)
HEAD
UNSEALED JAMB SHOWN
REF. FOLLOWING PAGES FOR ALT.
FLAT FILLER
E19992 FRAME
150mm @ 600 CTR EP7710
FLAT FILLER
E19992
150mm @ 600 CTRS
FRAME
EP7710
SEAL BOTH ENDS WITH
SMALL JOINT SEALANT
Please read in conjunction with Important Conditions – Index (also available on Capral website)
COVER SILL
DUE TO BEAD APPLICATION IT IS RECOMMENDED THAT
COVER SILLS ARE GLAZED BEFORE INSTALLATION
UNSEALED JAMB SHOWN
REF. FOLLOWING PAGES FOR ALT.
FLAT FILLER
E19992
150mm @ 600 CNTR
COVER SILL
10g x 76mm PAN SCREW EP7717
SEAL BOTH ENDS WITH
317459
SMALL JOINT SEALANT
INTERNAL SILL
SUB SILL
E95693
REF. TO SUB SILLS
& SUB FRAMES MANUAL
EXTERNAL SILL
INTERNAL BEAD
EP7713
APPLIED AFTER GLASS
INTERNAL SILL
EP7712
SEAL BOTH ENDS WITH
SMALL JOINT SEALANT
SUB SILL
E95693
REF. TO SUB SILLS
& SUB FRAMES MANUAL REVERSE
REVERSE EXTERNAL SILL
INTERNAL SILL
SEALED JAMB SHOWN
REF. FOLLOWING PAGES FOR ALT.
Please read in conjunction with Important Conditions – Index (also available on Capral website)
INTERNAL TRANSOM
FORWARD DRAINAGE SHOWN,
ALT. DRAIN THROUGH SEALED JAMB OR MULLION
FLAT FILLER
E19992
150mm @ 600mm CTRS
OR FULL HEIGHT FOR ALT.
SIDE DRAINAGE
INTERNAL BEAD
EP7713
APPLIED AFTER GLASS
FLAT FILLER
E19992
150 @ 600 CTRS
OR FULL HEIGHT FOR ALT.
SIDE DRAINAGE
Please read in conjunction with Important Conditions – Index (also available on Capral website)
© 01-10-2017
15-08-2022 Sec6 Assembly - Page 3
429 Flushline Framing System
Assembly -External Transoms Not To Scale
FRAME
EP7710
EXTERNAL BEAD
EP13365
APPLIED AFTER GLASS
FLAT FILLER
E19992
150mm @ 600 CTRS
OR FULL HEIGHT FOR ALT. EXTERNAL TRANSOM
SIDE DRAINAGE EP16298
SEAL BOTH ENDS
WITH SMALL JOINT SEALANT
10g x 25mm SS PAN SCREW
300059
EXPOSED SCREWS AND HOLES TO BE SMALL FLAT FILLER
SEALED INCLUDING ANY UNUSED HOLES EP16299
CREATED BY A PUNCH TOOL - SEAL INTO POSITION FULL LENGTH
- SEAL BOTH ENDS WITH SMALL JOINT SEALANT
EXTERNAL TRANSOM
FORWARD DRAINAGE SHOWN,
ALT. DRAIN THROUGH SEALED JAMB OR MULLION
Ø10 HOLE
REVERSE TRANSOM OR ALT.
STD TRANSOM SIDE DRAINAGE
POCKET FILLER
ENTIRE POCKET COMPLETELY
SEALED OVER POCKET FILLER
FRAME
EP7710
EXTERNAL BEAD
EP13365
APPLIED AFTER GLASS
SEAL CUT END AND
SNAP DETAIL FULL LENGTH
FLAT FILLER
E19992
FULL HEIGHT
SEALED INTO POSITION
Please read in conjunction with Important Conditions – Index (also available on Capral website)
COVER TRANSOM
FORWARD DRAINAGE SHOWN,
ALT. DRAIN THROUGH SEALED JAMB OR MULLION
FRAME
EP7710
POCKET FILLER
ENTIRE POCKET COMPLETELY
SEALED OVER POCKET FILLER
Ø10 HOLE
ALT. SIDE DRAINAGE DG COVER BEAD
EP7715
APPLY AFTER GLASS
Please read in conjunction with Important Conditions – Index (also available on Capral website)
REVEAL
REVEAL
STAPLE OR
OTHER FIXING
REINFORCED FOIL TAPE
311592
SEAL CORNERS & FRAME POCKET REINFORCED FOIL TAPE
ALT. USE 307411 NAILING FIN COVER 311592
SEAL OVER MULLION OPENING
CO-EXT EXPANSION
JOINT SEAL
CO-EXT EXPANSION 316051
JOINT SEAL
316051
FRAME
MALE MULLION
E33696
FRAME
E33696
FEMALE MULLION
429 DG FLUSHLINE
COVER BEAD
EP7715 INSTALLED SPLIT MULLION
10g x 25mm CSK SCREW VIEW FROM INSIDE
300064
429 DG FLUSHLINE
COVER SILL
EP7717
SILL BOTH ENDS WITH
SMALL JOINT OF SEALANT
SUB SILL
SPLIT MULLION EP5693
REF. TO SUB SILL &
SUB FRAME MANUAL
Please read in conjunction with Important Conditions – Index (also available on Capral website)
STRUCTURAL SPLIT
FRAME / MULLION (HEAD)
MULLION, HEAD
MALE SPLIT STRUCTURAL MULLION
CO-EXT EXPANSION JOINT SEAL
316051
FEMALE SPLIT STRUCTURAL MULLION
SEAL GAP
BEAD
SILL
SEAL GAP
MIN 2mm GAP FOR
EXPANSION / CONTRACTION
INSTALLED STRUCTURAL
SPLIT MULLION, SILL
SUB SILL MUST BE USED
Please read in conjunction with Important Conditions – Index (also available on Capral website)
SILICONE BEAD
TO FIX FULL LENGTH DG FRAME
ASSEMBLED AS SHOWN PREVIOUSLY
HEAD WITH
SG ADAPTORS
DEEP SG ADAPTOR
10g x 25mm SS PAN SCREW E31818
300059 5-4 RIVET
EXPOSED SCREWS AND HOLES TO 312431
BE SEALED INCLUDING ANY UNUSED
HOLES CREATED BY A PUNCH TOOL
SILICONE BEAD
TO FIX FULL LENGTH
SILICONE BEAD
TO FIX FULL LENGTH
DEEP SG ADAPTOR
E31818
FRAME
EP7710
5-4 RIVET
312431
SILICONE BEAD
TO FIX FULL LENGTH
TRANSOM WITH
SG ADAPTORS
SHALLOW SG ADAPTOR
E31819
(SHALLOW TG ADAPTOR
EP11223 FIXED WITH 309156)
Please read in conjunction with Important Conditions – Index (also available on Capral website)
EQUAL EQUAL
Please read in conjunction with Important Conditions – Index (also available on Capral website)
01
01
06 06
02
02
03
03
SUB FRAME
04 04 05 05
Please read in conjunction with Important Conditions – Index (also available on Capral website)
NOTE: REFER TO THE SUB SILL & SUB FRAME TECHNICAL MANUAL FOR SUB FRAME DETAILS
ALT. FRAME
EP7710
GLASS HEIGHT = DOH + 24
12
GLAZING WEDGE
DAYLIGHT= DOH
INTERNAL BEAD
12
EP7713
2&3
20mm SETTING BLOCK
INTERNAL 317195
55
SILL OR TRANSOM
POCKETED FILLER
GLASS HEIGHT = DOH + 24
12
EP7712
OUTSIDE
COVER SILL / TRANSOM
EP7717
12
DG COVER BEAD
2&3 EP7715
COVER
55
DG EXTERNAL BEAD
EP13365
SEAL INTO POSITION
EXTERNAL
SILL/TRANSOM
EP16798
END DAM
12
EXTERNAL SILL OR
TRANSOM SUB SILL
DG SMALL FLAT FILLER
EP16299
150mm @ 600 CTRS
SILICONE SEAL
CLOSED CELL
BACKING ROD
Please read in conjunction with Important Conditions – Index (also available on Capral website)
NOTE: REFER TO THE SUB SILL & SUB FRAME TECHNICAL MANUAL FOR SUB FRAME DETAILS
ALT. FRAME
EP7710
GLASS HEIGHT = DOH + 18
DEEP SG ADAPTOR
9
E31818
DAYLIGHT= DOH
5-4 RIVET
312431
INTERNAL BEAD
9
EP7713
2&3 20mm SETTING BLOCK
SG INTERNAL 317195
55
EP7712
OUTSIDE
EP7717
2&3 DEEP TG ADAPTOR
EP11224
TG COVER
55
POCKETED FILLER
SILL OR TRANSOM 8g x 13mm CSK SCREW
309156
SHALLOW TG ADAPTOR
GLASS HEIGHT = DOH + 18
EP11223
DAYLIGHT= DOH
DG EXTERNAL BEAD
EP13365
SEAL INTO POSITION
EXTERNAL
SILL/TRANSOM
EP16798
9
DEEP TG ADAPTOR
EP11224 (LEG SNAPPED)
2&3 SILICONE &
BACKING ROD
55
TG EXTERNAL SILL
OR TRANSOM SUB SILL
DG SMALL FLAT FILLER
EP16299
150mm @ 600 CTRS
SILICONE SEAL
CLOSED CELL
BACKING ROD
Please read in conjunction with Important Conditions – Index (also available on Capral website)
GLAZING WEDGE
DAYLIGHT= DOH
DOH + 24
INTERNAL BEAD
EP7713
EP7712
2&3
REVERSE GLAZED 20mm SETTING BLOCK
INTERNAL SILL OR 317195
55
POCKETED FILLER
TRANSOM
GLASS HEIGHT = DOH + 24
12
DAYLIGHT = DOH
DG EXTERNAL BEAD
12
EP13365
SEAL INTO POSITION
SILICONE & BACKING ROD
55
2&3
SUB SILL
REVERSE GLAZED
END DAM
EXTERNAL SILL
OR TRANSOM SILICONE SEAL
CLOSED CELL BACKING ROD
DG SMALL FLAT FILLER
IMPORTANT NOTE: REVERSE EXTERNAL EP16299
TRANSOM MUST BE DRAINED THROUGH
JAMB & BE USED SUB SILL.
6 6
2.5 2.5
126.5
6
126.5
EP5693 SHOWN EN5693 SHOWN
SIZE VARIES FOR OTHER SUB SILLS SIZE VARIES FOR OTHER SUB SILLS
REF. SUB SILLS & SUB FRAMES MANUAL REF. SUB SILLS & SUB FRAMES MANUAL
Please read in conjunction with Important Conditions – Index (also available on Capral website)
NOTE: THE SILICONE GLAZING TECHNIQUE & STRUCTURAL BITE ARE INDICATIVE ONLY.
FABRICATORS ARE REQUIRED TO CONFIRM THESE DETAILS WITH THEIR
CHOSEN STRUCTURAL SILICONE SUPPLIERS.
EP16299
1 150mm @ 600 CTRS
R2 FRAME
EP19054
12
OUTSIDE
STRUCTURAL TRANSOM
EP16933
18
2 STRUCTURAL SILICONE
STRUCTURAL 8mm SETTING BLOCK
317200
55
COVER
SILL/TRANSOM
EP7717
12
DG COVER BEAD
3 EP7715
SILICONE &
COVER SILL
55
BACKING ROD
OTHER SILLS SIMILAR
SUB SILL
END DAM
Please read in conjunction with Important Conditions – Index (also available on Capral website)
EXTERNAL CLADDING
LINTEL
INTERNAL
10 WALL LINING
ARCHITRAVE
10mm GAP TO SUIT
INSTALLATION
FLASHING BY OTHERS
100mm REVEAL
REVEAL FIN ADAPTOR
1 EP17218
FRAME
EP7710
GLAZING WEDGE
OUTSIDE
EP16297
GLAZING WEDGE
PLASTER
100mm REVEAL
EASY REVEAL
FRAME
4 EP7710
JAMB REVEAL FIN
INLINE EASY REVEAL
ADAPTOR
EP17218
10
FLASHING BY
OTHERS
OUTSIDE
Please read in conjunction with Important Conditions – Index (also available on Capral website)
4 5 4
UNSEALED STD JAMB MULLION R2 REVEALED JAMB
UNSEALED SHOWN SEALED SHOWN
* *
*
12 12 12 12
GLASS WIDTH = DOW + 24 2 GLASS WIDTH = DOW + 24
55 DAYLIGHT = DOW 57 DAYLIGHT = DOW 55
OUTSIDE
6
5
SUB / ALT. JAMB
UNSEALED SHOWN SPLICED MULLION
SMALL FLAT FILLER SUB FRAME SEAL 10g x 25mm PAN SCREW
EP16299 300059
SEE NOTE **
FRAME 50 x 6mm ALUMINIUM FLAT BAR
EP16297 POCKET FILLER ^
POCKET FILLER ^ 315713
SUB FRAME BEAD 315712 SILICONE SEAL
SUB FRAME BASE 100mm @ MULLION BASE
10g x 76mm PAN SCREW POCKET FILLER ^
317495 315711
* *
*
12 12 12
20 GLASS WIDTH = DOW + 24 2
MIN
55 DAYLIGHT = DOW 57
OUTSIDE
Please read in conjunction with Important Conditions – Index (also available on Capral website)
4 5 4
SG STD JAMB SG MULLION SG R2 JAMB
UNSEALED SHOWN UNSEALED SHOWN
DEEP SG SHALLOW SG
ADAPTOR ADAPTOR
E31818 E31819
* *
*
9 9 9 9
GLASS WIDTH = DOW + 18 2 GLASS WIDTH = DOW + 18
55 DAYLIGHT = DOW 57 DAYLIGHT = DOW 55
OUTSIDE
4 5 4
TG STD JAMB TG MULLION TG R2 REVEALED JAMB
SEALED SHOWN SEALED SHOWN
SILICONE SEAL CO-EXT EXPANSION
FLAT FILLER REVEAL FIN ADAPTOR
100mm @ MULLION BASE JOINT SEAL EP17218
E19992
DEEP TG ADAPTOR 316051
SEE NOTE ** 10g x 12mm CSK SCREW
EP11224
POCKET FILLER ^ FIX @ APPROPRIATE CTRS
FRAME GLAZING MALE MULLION 315711 R2 FRAME
EP7710 WEDGE E33696 FEMALE MULLION EP19051
POCKET FILLER ^ E33963 POCKET FILLER ^
315713 315712
SHALLOW TG
ADAPTOR
EP11223
* *
*
9 9 9 9
GLASS WIDTH = DOW + 18 2 GLASS WIDTH = DOW + 18
55 DAYLIGHT = DOW 57 DAYLIGHT = DOW 55.5
OUTSIDE
Please read in conjunction with Important Conditions – Index (also available on Capral website)
* IF A 6.5mm CAPTIVE WEDGE IS REQUIRED AT THIS LOCATION USE 320006 ALTERNATIVE WEDGE.
**150mm @ 600 CTRS WHEN FORWARD DRAINAGE IS USED. FULL HEIGHT WITH SIDE DRAINAGE. REF. SEC 6 FOR DETAILS
^ ENTIRE POCKET COMPLETELY SEALED OVER POCKET FILLER WITH SILICONE AT TRANSOMS
4 5 4
REVERSE JAMB REVERSE MULLION REVERSE ANGLE FIX JAMB
SEALED SHOWN
SEALED SHOWN SILICONE SEAL CO-EXT EXPANSION JOINT SEAL
100mm @ MULLION BASE 316051
FLAT FILLER
10g x 63mm CSK SCREW FEMALE MULLION E19992
FLAT FILLER 317494 EP19053
SEE NOTE **
E19992 POCKET FILLER ^ FRAME
SEE NOTE ** 315713 POCKET FILLER ^ EP7710
MALE MULLION 315711
GLAZING WEDGE EP19052 POCKET FILLER ^
315712
* *
12 12 12 12
GLASS WIDTH = DOW + 24 2 GLASS WIDTH = DOW + 24
55 DAYLIGHT = DOW 57 DAYLIGHT = DOW 55
OUTSIDE
6 5 5
REVERSE SUB / ALT. JAMB REVERSE MULLION REVERSE HD MULLION
SEALED SHOWN
FLUSH FILLER
E34300 10g x 25mm PAN SCREW 50 x 6mm
SEE NOTE ** 300059 ALUMINIUM FLAT
SUB FRAME BEAD FRAME POCKET FILLER ^ SILICONE SEAL BAR
EP16297 315713 100mm @ MULLION BASE
SUB FRAME
SUB FRAME SEAL
BASE
10g x 76mm PAN SCREW
317495
* *
* * * *
SMALL
FLAT FILLER
EP16299
12 12 12 12 12
20 GLASS WIDTH = DOW + 24 2 GLASS WIDTH = DOW + 24 2
MIN
55 DAYLIGHT = DOW 57 DAYLIGHT = DOW 57
OUTSIDE
Please read in conjunction with Important Conditions – Index (also available on Capral website)
NOTE: THE SILICONE GLAZING TECHNIQUE & STRUCTURAL BITE ARE INDICATIVE ONLY.
FABRICATORS ARE REQUIRED TO CONFIRM THESE DETAILS WITH THEIR
CHOSEN STRUCTURAL SILICONE SUPPLIERS.
4 5
STD JAMB STRUCTURAL SPLIT MULLION
SEALED SHOWN STRUCTURAL MALE STRUCTURAL FEMALE
MULLION MULLION
EP16931 EP16932
POCKET FILLER ^
315712 CAPTIVE GLAZING 10g X 25mm CSK SCREW
WEDGE 300064
12 18 18
2
55 DAYLIGHT = DOW 57
GLASS WIDTH = DOW + 30
HEAD & SILL WIDTH = DOW + 27.5
OUTSIDE
5 5
STRUCTURAL SPLIT MULLION STIFFENED STRUCTURAL SPLIT
MULLION
SILICONE SEAL CO-EXT EXPANSION JOINT SEAL 50 x 6mm FLAT BAR
100mm @ MULLION BASE 316051
18 18 18 18
2 2
57 DAYLIGHT = DOW 57
GLASS WIDTH = DOW + 36
HEAD & SILL WIDTH = DOW + 55
OUTSIDE
^ ENTIRE POCKET COMPLETELY SEALED OVER POCKET FILLER WITH SILICONE AT TRANSOMS
Please read in conjunction with Important Conditions – Index (also available on Capral website)
CORNER POST
FLUSHLINE / NARROWLINE OUTSIDE CORNER SHOWN.
COUPLER INSIDE CORNER SIMILAR.
3
LEGS MACHINED
TO SUIT
105 100
128
CORNER
OUTSIDE
CORNER MULLION COUPLER
MULLION EP18083
INSIDE LEGS TRIMMED AT SCREW LOCATIONS.
REF. SECTION 10 FOR DETAILS
SILICONE SEAL
100mm @ MULLION BASE
DAYR2 = DOW
CORNER MULLION
EP18085
12
68
2
12
DAYLIGHT = DOW 68 OUTSIDE
STRUCTURAL TRANSOM WIDTH = DOW + 12.5^
COVER SILL / TRANSOM WIDTH = DOW + 22.6*
HEAD & EXTERNAL SILL / TRANSOM WIDTH = DOW + 25.5*
* HEAD & COVER OR EXTERNAL SILL/TRANSOM ARE MITRE CUT THEN TRIMMED
^ STRUCTURAL TRANSOM IS MITE CUT, TRIMMING OPTIONAL
REFER TO MACHINING PAGES FOR FURTHER INFORMATION
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Configuration: F / F / F . F /F / F
Glass: 6mm Clear Float / 12mm Air / 6mm Clear Float & 6mm Clear Float
Glazing: Roll in Wedges Outside & Continuous Silicone Seal Inside
1500Pa 1500Pa
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Configuration: F . F
Glass: 5mm Clear Toughened / 14mm Air Gap / 5mm Clear Toughened
Bead / Glazing : Internal Bead / Co Extruded Captive Glazing Wedge & Glazing Wedge
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Configuration: F . F
Glass: 5mm Clear Toughened / 14mm Air Gap / 5mm Clear Toughened
Bead / Glazing : Cover Bead / Co Extruded Captive Glazing Wedge & Glazing Wedge
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Configuration: F . F
Glass: 6mm Clear Toughened / 12mm Air Gap / 6mm Clear Toughened
Bead / Glazing : Cover Bead / Co Extruded Captive Glazing Wedge & Glazing Wedge
Configuration: F . F
Glass: 6mm Clear Toughened / 12mm Air Gap / 6mm Clear Toughened
Bead / Glazing : Cover Bead / Co Extruded Captive Glazing Wedge & Glazing Wedge
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Configuration: F / F
Glass: 5mm Clear Toughened / 18mm Air Gap / 5mm Clear Toughened
Bead / Glazing : Cover Bead / Co Extruded Captive Glazing Wedge & Glazing Wedge
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Configuration: F . F
Glass: 5mm Clear Toughened / 18mm Air Gap / 5mm Clear Toughened
Bead / Glazing : Internal Bead / Co Extruded Captive Glazing Wedge & Glazing Wedge
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Configuration: F / F
Glass: 6mm Clear Toughened / 12mm Air Gap / 6mm Clear Toughened
Bead / Glazing : Cover Bead / Co Extruded Captive Glazing Wedge & Glazing Wedge
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Configuration: F / F
Glass: 6mm Clear Toughened / 12mm Air Gap / 6mm Clear Toughened
Bead / Glazing : Internal Bead / Co Extruded Captive Glazing Wedge & Glazing Wedge
Please read in conjunction with Important Conditions – Index (also available on Capral website)
TEST RESULTS:
Performance Criteria Time to Failure (min) Position of Failure
Formation of through-gaps greater than 3mm. No Failure -
Sustained failure for 10sec. on the non-fire side. No Failure -
Flaming on the fire –exposed side at the end of the 60min.
No Failure -
test period.
Radiant heat flux 365mm from the non-fire exposed side
No Failure -
exceeding 15kW/m2.
Mean and maximum temperature rises greater than 140K No applicable for glazed
-
& 180K. elements.
Radiant heat flux 250mm from the specimen, greater than
No Failure -
3kW/m2 between 20mins. and 60mins.
Mean and maximum temperature of internal faces
Not applicable for glazed
exceeding 250ºC and 300ºC respectively between 20mins. -
elements.
and 60mins. after commencement of test.
Crib Class A Peak Heat Flux 40 kW/m2
Test Result BAL-A40
Please read in conjunction with Important Conditions – Index (also available on Capral website)
ACOUSTIC
Performed by: Day Design Pty Ltd, New South Wales – February, 2010
Test Drawing Number: 31-391
Configuration: F.F
Please read in conjunction with Important Conditions – Index (also available on Capral website)
ACOUSTIC OPINION
Acoustic opinions are theoretical estimates of performance, these opinions are based on physical test
data with variations assessed such as glass, size or configuration.
Opinion Estimated to be within 1 degree of +- 1dB
Configuration: F.F
SAMPLE DETAILS:
Glass: 6.5mm VLam Hush / 9mm Air / 10.5mm VLam Hush
Glazing Wedge: 301232 4.5mm Gap Glazing Wedge; 300011 7.5mm Gap Glazing Wedge
Mullion Seal: 316051 Expansion Joint Seal
SAMPLE DETAILS:
Glass: 6.38mm Laminate / 12mm Air / 6.38mm Laminate
Glazing Wedge: 300006 6.5mm Gap Glazing Wedge; 300011 7.5mm Gap Glazing Wedge
Mullion Seal: 316051 Expansion Joint Seal
SAMPLE DETAILS:
Glass: 6.38mm Laminate / 12mm Air / 6mm
Glazing Wedge: 300006 6.5mm Gap Glazing Wedge; 300011 7.5mm Gap Glazing Wedge
Mullion Seal: 316051 Expansion Joint Seal
SAMPLE DETAILS:
Glass: 6mm / 12mm Air / 6mm
Glazing Wedge: 300006 6.5mm Gap Glazing Wedge; 300011 7.5mm Gap Glazing Wedge
Mullion Seal: 316051 Expansion Joint Seal
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Serviceability pressures have not been limited by water performance. Where water
performance is necessary, refer to Product Specifications page.
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Note:
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Serviceability pressures have not been limited by a water performance. Where water
performance is necessary, refer to Product Specifications page.
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Serviceability pressures have not been limited by water performance. Where water
performance is necessary, refer to Product Specifications page.
EP2382, EP2222 or EP2220 / EP2219 Sills & Transom are required for pressures above
2500Pa.
NOTE: This table is based on theoretical section properties not on approved AS2047 testing data.
A maximum stress level of 110MPa has been applied when generating this table.
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Serviceability pressures have not been limited by a water performance. Where water
performance is necessary, refer to Product Specifications page.
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Serviceability pressures have not been limited by a water performance. Where water
performance is necessary, refer to Product Specifications page.
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Serviceability pressures have not been limited by water performance. Where water
performance is necessary, refer to Product Specifications page.
Transom Spacing
Maximum Design Pressure (kPa)
(mm)
S (L/250) 3.000 3.000 2.245 1.496 1.051 0.769 0.580
1500
U 4.500 4.500 3.472 2.617 2.052 1.656 1.368
S (L/250) 3.000 3.000 2.284 1.528 1.076 0.789 0.596
1450
U 4.500 4.500 3.538 2.676 2.104 1.701 1.407
S (L/250) 3.000 3.000 2.328 1.563 1.104 0.810 0.614
1400
U 4.500 4.500 3.613 2.742 2.160 1.750 1.448
S (L/250) 3.000 3.000 2.378 1.602 1.134 0.834 0.632
1350
U 4.500 4.500 3.696 2.814 2.222 1.803 1.494
S (L/250) 3.000 3.000 2.434 1.645 1.167 0.860 0.653
1300
U 4.500 4.500 3.789 2.894 2.290 1.860 1.543
S (L/250) 3.000 3.000 2.496 1.692 1.204 0.888 0.675
1250
U 4.500 4.500 3.892 2.981 2.363 1.923 1.597
S (L/250) 3.000 3.000 2.566 1.745 1.243 0.919 0.699
1200
U 4.500 4.500 4.007 3.078 2.445 1.992 1.656
S (L/250) 3.000 3.000 2.644 1.803 1.287 0.953 0.725
1150
U 4.500 4.500 4.135 3.185 2.534 2.067 1.720
S (L/250) 3.000 3.000 2.731 1.867 1.336 0.990 0.754
1100
U 4.500 4.500 4.278 3.303 2.632 2.149 1.790
S (L/250) 3.000 3.000 2.829 1.939 1.389 1.031 0.786
1050
U 4.500 4.500 4.438 3.433 2.740 2.240 1.867
S (L/250) 3.000 3.000 2.938 2.019 1.449 1.076 0.822
1000
U 4.500 4.500 4.500 3.579 2.861 2.341 1.953
S (L/250) 3.000 3.000 3.000 2.108 1.515 1.127 0.861
950
U 4.500 4.500 4.500 3.742 2.995 2.454 2.048
S (L/250) 3.000 3.000 3.000 2.209 1.590 1.184 0.905
900
U 4.500 4.500 4.500 3.924 3.145 2.579 2.154
S (L/250) 3.000 3.000 3.000 2.322 1.674 1.247 0.955
850
U 4.500 4.500 4.500 4.130 3.314 2.720 2.273
S (L/250) 3.000 3.000 3.000 2.450 1.769 1.319 1.011
800
U 4.500 4.500 4.500 4.363 3.505 2.879 2.408
S (L/250) 3.000 3.000 3.000 2.597 1.877 1.402 1.074
750
U 4.500 4.500 4.500 4.500 3.723 3.060 2.561
S (L/250) 3.000 3.000 3.000 2.767 2.002 1.496 1.147
700
U 4.500 4.500 4.500 4.500 3.973 3.268 2.736
S (L/250) 3.000 3.000 3.000 2.963 2.147 1.605 1.232
650
U 4.500 4.500 4.500 4.500 4.262 3.509 2.939
S (L/250) 3.000 3.000 3.000 3.000 2.316 1.733 1.331
600
U 4.500 4.500 4.500 4.500 4.500 3.790 3.177
Transom Width (mm) 1500 1750 2000 2250 2500 2750 3000
LEGEND: S = Serviceability Pressure, U = Ultimate Pressure
NOTE: This table is based on a combination of approved AS2047 testing data and theoretical section properties.
A maximum stress level of 110MPa has been applied when generating this table.
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Serviceability pressures have not been limited by water performance. Where water
performance is necessary, refer to Product Specifications page.
Transom Spacing
Maximum Design Pressure (kPa)
(mm)
S (L/250) 3.000 3.000 1.898 1.265 0.889 0.650 0.491
1500
U 4.500 3.967 2.822 2.127 1.668 1.346 1.112
S (L/250) 3.000 3.000 1.931 1.292 0.910 0.667 0.504
1450
U 4.500 4.018 2.876 2.176 1.710 1.383 1.143
S (L/250) 3.000 3.000 1.969 1.322 0.934 0.685 0.519
1400
U 4.500 4.079 2.937 2.229 1.756 1.422 1.177
S (L/250) 3.000 3.000 2.011 1.355 0.959 0.705 0.535
1350
U 4.500 4.151 3.004 2.288 1.806 1.465 1.214
S (L/250) 3.000 3.000 2.058 1.391 0.987 0.727 0.552
1300
U 4.500 4.235 3.080 2.352 1.861 1.512 1.255
S (L/250) 3.000 3.000 2.111 1.431 1.018 0.751 0.571
1250
U 4.500 4.331 3.164 2.424 1.921 1.563 1.298
S (L/250) 3.000 3.000 2.170 1.476 1.052 0.777 0.591
1200
U 4.500 4.440 3.257 2.502 1.987 1.619 1.346
S (L/250) 3.000 3.000 2.236 1.525 1.089 0.806 0.613
1150
U 4.500 4.500 3.362 2.589 2.060 1.680 1.398
S (L/250) 3.000 3.000 2.310 1.579 1.130 0.837 0.638
1100
U 4.500 4.500 3.478 2.685 2.139 1.747 1.455
S (L/250) 3.000 3.000 2.392 1.640 1.175 0.872 0.665
1050
U 4.500 4.500 3.607 2.791 2.228 1.821 1.518
S (L/250) 3.000 3.000 2.485 1.707 1.225 0.910 0.695
1000
U 4.500 4.500 3.752 2.909 2.325 1.903 1.588
S (L/250) 3.000 3.000 2.589 1.783 1.282 0.953 0.728
950
U 4.500 4.500 3.915 3.042 2.434 1.994 1.665
S (L/250) 3.000 3.000 2.707 1.868 1.345 1.001 0.766
900
U 4.500 4.500 4.099 3.190 2.556 2.096 1.751
S (L/250) 3.000 3.000 2.840 1.964 1.416 1.055 0.807
850
U 4.500 4.500 4.306 3.357 2.694 2.211 1.848
S (L/250) 3.000 3.000 2.992 2.072 1.496 1.116 0.855
800
U 4.500 4.500 4.500 3.547 2.849 2.340 1.957
S (L/250) 3.000 3.000 3.000 2.197 1.588 1.185 0.909
750
U 4.500 4.500 4.500 3.763 3.026 2.488 2.082
S (L/250) 3.000 3.000 3.000 2.340 1.693 1.265 0.970
700
U 4.500 4.500 4.500 4.012 3.229 2.656 2.224
S (L/250) 3.000 3.000 3.000 2.506 1.815 1.357 1.042
650
U 4.500 4.500 4.500 4.301 3.465 2.852 2.389
S (L/250) 3.000 3.000 3.000 2.701 1.959 1.466 1.125
600
U 4.500 4.500 4.500 4.500 3.741 3.081 2.582
Transom Width (mm) 1500 1750 2000 2250 2500 2750 3000
LEGEND: S = Serviceability Pressure, U = Ultimate Pressure
NOTE: This table is based on theoretical section properties not on approved AS2047 testing data.
A maximum stress level of 110MPa has been applied when generating this table.
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Serviceability pressures have not been limited by water performance. Where water
performance is necessary, refer to Product Specifications page.
Transom Spacing
Maximum Design Pressure (kPa)
(mm)
S (L/250) 3.619 2.005 1.241 0.827 0.581 0.425 -
1500
U 3.872 2.512 1.787 1.347 1.056 0.853 -
S (L/250) 3.624 2.028 1.262 0.844 0.595 0.436 -
1450
U 3.878 2.544 1.821 1.378 1.083 0.876 -
S (L/250) 3.640 2.055 1.287 0.864 0.610 0.448 -
1400
U 3.897 2.583 1.859 1.411 1.112 0.901 -
S (L/250) 3.665 2.088 1.314 0.886 0.627 0.461 -
1350
U 3.929 2.629 1.902 1.449 1.144 0.928 -
S (L/250) 3.701 2.127 1.345 0.909 0.645 0.475 -
1300
U 3.973 2.681 1.950 1.489 1.178 0.957 -
S (L/250) 3.749 2.171 1.380 0.936 0.665 0.491 -
1250
U 4.031 2.742 2.003 1.535 1.216 0.990 -
S (L/250) 3.808 2.222 1.418 0.965 0.687 0.508 -
1200
U 4.102 2.811 2.062 1.584 1.258 1.025 -
S (L/250) 3.880 2.279 1.462 0.997 0.712 0.527 0.401
1150
U 4.187 2.890 2.128 1.639 1.304 1.064 0.885
S (L/250) 3.966 2.345 1.510 1.032 0.738 0.547 0.417
1100
U 4.289 2.978 2.202 1.700 1.355 1.106 0.921
S (L/250) 4.067 2.420 1.564 1.072 0.768 0.570 0.435
1050
U 4.407 3.079 2.284 1.767 1.410 1.153 0.961
S (L/250) 4.186 2.504 1.624 1.116 0.801 0.595 0.454
1000
U 4.545 3.192 2.376 1.842 1.472 1.205 1.005
S (L/250) 4.323 2.601 1.692 1.165 0.838 0.623 0.476
950
U 4.705 3.321 2.479 1.926 1.541 1.263 1.054
S (L/250) 4.483 2.710 1.769 1.221 0.879 0.654 0.500
900
U 4.889 3.466 2.595 2.020 1.619 1.327 1.109
S (L/250) 4.668 2.835 1.856 1.283 0.925 0.689 0.528
850
U 5.101 3.632 2.726 2.126 1.706 1.400 1.170
S (L/250) 4.883 2.979 1.955 1.354 0.978 0.729 0.559
800
U 5.347 3.822 2.876 2.246 1.804 1.482 1.239
S (L/250) 5.000 3.144 2.069 1.436 1.038 0.775 0.594
750
U 5.632 4.040 3.047 2.383 1.916 1.575 1.318
S (L/250) 5.000 3.336 2.201 1.529 1.107 0.827 0.634
700
U 5.964 4.293 3.244 2.540 2.045 1.682 1.408
S (L/250) 5.000 3.560 2.353 1.638 1.186 0.887 0.681
650
U 6.355 4.587 3.473 2.723 2.194 1.806 1.513
S (L/250) 5.000 3.824 2.533 1.766 1.280 0.958 0.736
600
U 6.817 4.935 3.742 2.938 2.369 1.951 1.635
Transom Width (mm) 1500 1750 2000 2250 2500 2750 3000
LEGEND: S = Serviceability Pressure, U = Ultimate Pressure
NOTE: This table is based on a combination of approved AS2047 testing data and theoretical section properties.
A maximum stress level of 110MPa has been applied when generating this table.
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Serviceability pressures have not been limited by water performance. Where water
performance is necessary, refer to Product Specifications page.
Transom Spacing
Maximum Design Pressure (kPa)
(mm)
S (L/250) 3.733 2.068 1.280 0.853 0.599 0.438 -
1500
U 4.104 2.662 1.894 1.427 1.119 0.904 -
S (L/250) 3.738 2.091 1.302 0.871 0.614 0.450 -
1450
U 4.110 2.696 1.930 1.460 1.147 0.928 -
S (L/250) 3.754 2.120 1.327 0.891 0.629 0.462 -
1400
U 4.130 2.737 1.971 1.496 1.178 0.955 -
S (L/250) 3.780 2.154 1.356 0.913 0.647 0.476 -
1350
U 4.164 2.786 2.016 1.535 1.212 0.983 -
S (L/250) 3.818 2.193 1.388 0.938 0.665 0.490 -
1300
U 4.211 2.842 2.067 1.579 1.249 1.015 -
S (L/250) 3.866 2.239 1.423 0.965 0.686 0.506 -
1250
U 4.272 2.906 2.123 1.626 1.289 1.049 -
S (L/250) 3.928 2.291 1.463 0.995 0.709 0.524 -
1200
U 4.347 2.979 2.186 1.679 1.333 1.086 -
S (L/250) 4.002 2.351 1.507 1.028 0.734 0.543 0.413
1150
U 4.438 3.062 2.256 1.737 1.382 1.127 0.938
S (L/250) 4.091 2.419 1.557 1.065 0.762 0.564 0.430
1100
U 4.545 3.157 2.334 1.802 1.436 1.172 0.976
S (L/250) 4.195 2.496 1.613 1.105 0.792 0.588 0.448
1050
U 4.671 3.263 2.421 1.873 1.495 1.222 1.019
S (L/250) 4.317 2.583 1.675 1.151 0.826 0.614 0.469
1000
U 4.817 3.383 2.518 1.952 1.561 1.277 1.065
S (L/250) 4.459 2.683 1.745 1.202 0.864 0.643 0.491
950
U 4.986 3.519 2.627 2.041 1.634 1.338 1.117
S (L/250) 4.500 2.796 1.825 1.259 0.906 0.675 0.516
900
U 5.181 3.674 2.750 2.141 1.716 1.407 1.175
S (L/250) 4.500 2.925 1.915 1.324 0.954 0.711 0.544
850
U 5.406 3.850 2.890 2.253 1.808 1.484 1.240
S (L/250) 4.500 3.073 2.017 1.397 1.009 0.752 0.576
800
U 5.667 4.051 3.048 2.380 1.912 1.570 1.314
S (L/250) 4.500 3.243 2.134 1.481 1.070 0.799 0.613
750
U 5.969 4.282 3.229 2.525 2.031 1.669 1.397
S (L/250) 4.500 3.441 2.270 1.577 1.141 0.853 0.654
700
U 6.321 4.550 3.438 2.692 2.167 1.783 1.493
S (L/250) 4.500 3.672 2.427 1.690 1.224 0.915 0.702
650
U 6.735 4.862 3.681 2.886 2.325 1.914 1.603
S (L/250) 4.500 3.945 2.613 1.821 1.320 0.988 0.759
600
U 7.000 5.230 3.966 3.113 2.510 2.068 1.733
Transom Width (mm) 1500 1750 2000 2250 2500 2750 3000
LEGEND: S = Serviceability Pressure, U = Ultimate Pressure
NOTE: This table is based on theoretical sections properties, not on approved AS2047 testing data.
A maximum stress level of 110MPa has been applied when generating this table.
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Combined glass thickness has been limited to 16mm according to the capacity of the suite.
These tables have been developed to assist Fabricators in making an assessment of the
maximum glass thickness that the transom member can support before it is considered
unstable (deflection & stress).
Wind load and human impact requirements are not included in the tables below. A glass
thickness assessment for windload and human impact must still be completed in
accordance with AS1288.
Height Above
Maximum Glass Thickness with Support Blocks at 1/4 Points (mm)
Transom (mm)
1200 10 6 6 4 - - - - -
1100 10 8 6 5 - - - - -
1000 12 8 6 5 4 - - - -
900 12 10 8 6 4 - - - -
800 12 10 8 6 5 4 - - -
700 16 12 10 6 6 4 - - -
600 16 12 12 8 6 5 4 - -
Transom Width (mm) 1400 1600 1800 2000 2200 2400 2600 2800 3000
Downward
2.3 2.7 3.0 3.3 3.7 4.0 4.3 4.7 5.0
Deflection (mm)
Height Above
Maximum Glass Thickness with Support Blocks at 1/8 Points (mm)
Transom (mm)
1200 16 12 10 8 6 5 - - -
1100 16 16 12 8 6 5 4 - -
1000 16 16 12 10 6 6 4 - -
900 16 16 12 10 8 6 5 4 -
800 16 16 16 12 8 6 5 4 -
700 16 16 16 12 10 8 6 5 4
600 16 16 16 16 12 10 6 6 5
Transom Width (mm) 1400 1600 1800 2000 2200 2400 2600 2800 3000
Downward
2.3 2.7 3.0 3.3 3.7 4.0 4.3 4.7 5.0
Deflection (mm)
Please read in conjunction with Important Conditions – Index (also available on Capral website)
© 01-12-2016
15-08-2022 Sec9 Span Tables - Page 11
429 Flushline Framing System
Maximum Glass Thickness Table - Deadload Assessment
INTERNAL TRANSOM - EP7713 / EP7712
Note:
Combined glass thickness has been limited to 16mm according to the capacity of the suite.
These tables have been developed to assist Fabricators in making an assessment of the
maximum glass thickness that the transom member can support before it is considered
unstable (deflection & stress).
Wind load and human impact requirements are not included in the tables below. A glass
thickness assessment for windload and human impact must still be completed in
accordance with AS1288.
Height Above
Maximum Glass Thickness with Support Blocks at 1/4 Points (mm)
Transom (mm)
1200 10 8 6 5 4 - - - -
1100 12 8 6 5 4 - - - -
1000 12 10 8 6 4 - - - -
900 12 10 8 6 5 4 - - -
800 16 12 10 8 6 4 - - -
700 16 12 10 8 6 5 4 - -
600 16 16 12 10 8 6 4 - -
Transom Width (mm) 1400 1600 1800 2000 2200 2400 2600 2800 3000
Downward
2.3 2.7 3.0 3.3 3.7 4.0 4.3 4.7 5.0
Deflection (mm)
Height Above
Maximum Glass Thickness with Support Blocks at 1/8 Points (mm)
Transom (mm)
1200 16 12 10 8 6 5 - - -
1100 16 16 12 8 6 5 4 - -
1000 16 16 12 10 6 6 4 - -
900 16 16 12 10 8 6 5 4 -
800 16 16 16 12 8 6 5 4 -
700 16 16 16 12 10 8 6 5 4
600 16 16 16 16 12 10 6 6 5
Transom Width (mm) 1400 1600 1800 2000 2200 2400 2600 2800 3000
Downward
2.3 2.7 3.0 3.3 3.7 4.0 4.3 4.7 5.0
Deflection (mm)
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Combined glass thickness has been limited to 16mm according to the capacity of the suite.
These tables have been developed to assist Fabricators in making an assessment of the
maximum glass thickness that the transom member can support before it is considered
unstable (deflection & stress).
Wind load and human impact requirements are not included in the tables below. A glass
thickness assessment for windload and human impact must still be completed in
accordance with AS1288.
Height Above
Maximum Glass Thickness with Support Blocks at 1/4 Points (mm)
Transom (mm)
1200 16 16 10 8 6 4 - - -
1100 16 16 12 8 6 5 4 - -
1000 16 16 12 8 6 5 4 - -
900 16 16 12 10 8 6 4 - -
800 16 16 16 12 8 6 5 4 -
700 16 16 16 12 10 8 6 5 4
600 16 16 16 16 12 8 6 5 4
Transom Width (mm) 1400 1600 1800 2000 2200 2400 2600 2800 3000
Downward
2.3 2.7 3.0 3.3 3.7 4.0 4.3 4.7 5.0
Deflection (mm)
Height Above
Maximum Glass Thickness with Support Blocks at 1/8 Points (mm)
Transom (mm)
1200 16 16 16 12 10 8 6 5 4
1100 16 16 16 16 12 8 6 6 4
1000 16 16 16 16 12 10 8 6 5
900 16 16 16 16 12 10 8 6 6
800 16 16 16 16 16 12 10 8 6
700 16 16 16 16 16 12 12 8 6
600 16 16 16 16 16 16 12 10 8
Transom Width (mm) 1400 1600 1800 2000 2200 2400 2600 2800 3000
Downward
2.3 2.7 3.0 3.3 3.7 4.0 4.3 4.7 5.0
Deflection (mm)
Please read in conjunction with Important Conditions – Index (also available on Capral website)
© 01-12-2016
15-08-2022 Sec9 Span Tables - Page 13
429 Flushline Framing System
Maximum Glass Thickness Table - Deadload Assessment
COVER TRANSOM - EP7717
Note:
Combined glass thickness has been limited to 16mm according to the capacity of the suite.
These tables have been developed to assist Fabricators in making an assessment of the
maximum glass thickness that the transom member can support before it is considered
unstable (deflection & stress).
Wind load and human impact requirements are not included in the tables below. A glass
thickness assessment for windload and human impact must still be completed in
accordance with AS1288.
Height Above
Maximum Glass Thickness with Support Blocks at 1/4 Points (mm)
Transom (mm)
1200 16 16 12 8 6 5 4 - -
1100 16 16 12 10 6 5 4 - -
1000 16 16 12 10 8 6 5 4 -
900 16 16 16 12 8 6 5 4 -
800 16 16 16 12 10 8 6 5 4
700 16 16 16 16 12 8 6 5 4
600 16 16 16 16 12 10 8 6 5
Transom Width (mm) 1400 1600 1800 2000 2200 2400 2600 2800 3000
Downward
2.3 2.7 3.0 3.3 3.7 4.0 4.3 4.7 5.0
Deflection (mm)
Height Above
Maximum Glass Thickness with Support Blocks at 1/8 Points (mm)
Transom (mm)
1200 16 16 16 16 12 10 6 6 5
1100 16 16 16 16 12 10 8 6 5
1000 16 16 16 16 12 12 8 6 6
900 16 16 16 16 16 12 10 8 6
800 16 16 16 16 16 12 10 8 6
700 16 16 16 16 16 16 12 10 8
600 16 16 16 16 16 16 12 12 10
Transom Width (mm) 1400 1600 1800 2000 2200 2400 2600 2800 3000
Downward
2.3 2.7 3.0 3.3 3.7 4.0 4.3 4.7 5.0
Deflection (mm)
Please read in conjunction with Important Conditions – Index (also available on Capral website)
Combined glass thickness has been limited to 16mm according to the capacity of the suite.
These tables have been developed to assist Fabricators in making an assessment of the
maximum glass thickness that the transom member can support before it is considered
unstable (deflection & stress).
Wind load and human impact requirements are not included in the tables below. A glass
thickness assessment for windload and human impact must still be completed in
accordance with AS1288.
Height Above
Maximum Glass Thickness with Support Blocks at 1/4 Points (mm)
Transom (mm)
1200 16 16 16 12 8 6 5 4 -
1100 16 16 16 12 8 6 5 4 -
1000 16 16 16 12 10 8 6 5 4
900 16 16 16 16 12 8 6 5 4
800 16 16 16 16 12 10 8 6 5
700 16 16 16 16 12 10 8 6 6
600 16 16 16 16 16 12 10 8 6
Transom Width (mm) 1400 1600 1800 2000 2200 2400 2600 2800 3000
Downward
2.3 2.7 3.0 3.3 3.7 4.0 4.3 4.7 5.0
Deflection (mm)
Height Above
Maximum Glass Thickness with Support Blocks at 1/8 Points (mm)
Transom (mm)
1200 16 16 16 16 16 12 10 8 6
1100 16 16 16 16 16 12 10 8 6
1000 16 16 16 16 16 12 12 8 8
900 16 16 16 16 16 16 12 10 8
800 16 16 16 16 16 16 12 12 10
700 16 16 16 16 16 16 16 12 10
600 16 16 16 16 16 16 16 16 12
Transom Width (mm) 1400 1600 1800 2000 2200 2400 2600 2800 3000
Downward
2.3 2.7 3.0 3.3 3.7 4.0 4.3 4.7 5.0
Deflection (mm)
Please read in conjunction with Important Conditions – Index (also available on Capral website)
© 01-12-2016
15-08-2022 Sec9 Span Tables - Page 15