This document is property of Design NTDC. No Part of this can be modified or used for any purpose other than its designated purpose.
 
 
NATIONAL
N L TRANSMISSION & D
DESPATCH
H COMPAN
NY LIMITED

 
 
AMENDMENT NO.01 
 
Spe ecification No. P‐205:2005 
 
i. Sub‐Claause 1.2 is deleted 
ii. Add the e followingg at Sr. No.21 under ssub clause 4.1: 
 

LY
“21) Rating factorr 1.2 1.2 1.2 1.2” 
iii. Add the e followingg at the end of the exxisting textt of sub‐claause 5.1.6:: 

N
 

O
“Alternately, the  multiple rations mayy be achieeved by suitable arraangement 
of the ssecondary windings” 17
20
iv. The  con ntents  of  sub‐clause e  5.2.1  (Prrimary  term minals)  bee  replaced  with  the 
followin ng:‐ 
5-

 
-7

“The  primary  terrminals  shall  be  singgle‐stem,  horizontall,  made  off  copper, 
R

adequaately  shield ded  and  co orona  freee.  The  term minals  for  66  KV,  132  KV  and 
O

220  KV V  current  transformers  shall  be  circular  rod  type  having  following 
N

dimensions: 
R

 
FO

C.T Rating    Length (m mm)    Diameteer (mm) 


 
66 KV           80                  30 
132 KV          125            40 
220 KV          175                     60  
 
v. Add the e followingg new sub‐clause 5.3.2: 
 
“Provision shall b be made in n the botto om plate o of each terminal box  for entry 
of 1 No. 75 mm dia Gl pipe ffor runningg the 4x6 m mm2 Contrrol Cables”” 
 
vi. Add the e followingg new sub‐clause 5.8.6 under C Clause 5.8 ((Marshallin ng Box): 
 
This document is property of Design NTDC. No Part of this can be modified or used for any purpose other than its designated purpose.
“Provision shall be made in the bottom plate marshalling box for entry of 4 
No. 75 mm dia. Gl pipe for running the 4x6 mm2 Control Cables” 
 
vii. The CTs are required to have only one core, meant for metering.  
 
viii. One marshalling box for each set of 3 C.Ts is included in the scope of supply 
as per sub‐clause 5.8 of specification P‐205:2005. 
 
 
 
 
 

LY
 
 

N
 

O
 
  17
20
 
 
5-

 
-7

 
R

 
O

 
N

 
R

 
FO

 
 
 
 
 
 
 
 
 
 
 
 
 
This document is property of Design NTDC. No Part of this can be modified or used for any purpose other than its designated purpose.
 
C  O  N  T  E  N  T  S 
 
 
0. Foreword 
 
1. Scope  
 
2. Reference Specification  
 
3. Service Conditions 
 
4. Ratings 
 

LY
5. Construction 

N
 

O
6. Terminal Markings 
 
7. Rating Plate  17
20
 
8. Tests 
5-

 
-7

9. Drawings and Descriptive Data 
R

 
O

 
N

 
R

 
FO

 
 
 
 
 
 
 
 
 
 
 
 
This document is property of Design NTDC. No Part of this can be modified or used for any purpose other than its designated purpose.
 
SPECIFICAITON P‐205: 2005 
 
CURRENT  TRANSFORMERS FOR SPECIAL APPLICATIONS 
(ENERGY METERING) 
 
0 FOREWORD 
 
0.1       This specification has been prepared by the Design Department (NTDC) 
 
0.2        This  Specification  is  intended  for  the  procurement  of  material  and  does  not   
include all the necessary provisions of a contract. 
 
 0.3      This specification is subject to revision as and when required. 

LY
 
1 SCOPE 

N
 

O
1.1 This specification covers the requirements for current transformers of 0.2S class 
intended  for  special  energy  metering  applications  in  66KV  through  500  KV 
systems.  17
20
 
1.2 WAPDA reserves the right to reject the current  transformers with top head tank  
5-

design (inverted type)   
-7

 
R

2 REFERENCE SPECIFICAITON  
O

 
N

2.1 The  current  transformers  shall  be  designed,  manufactured  and  tested  in 
accordance with the latest issue of relevant IEC Publication  and  particulars IEC‐
R

60044‐I and particulars listed herein. 
FO

 
2.2  In  case  the  requirements  laid  down  herein  differ  from  those  given  in  the  IEC 
Publication  in  any  particular,  the  current  transformers  shall  comply  with  the 
requirements listed herein in regard to that item. 
 
3 SERVICE CONDITIONS 
 
3.1 The  current  transformers  and  all  accessories  shall  be  suitable  for  satisfactory 
operation under the following service conditions: 
 
3.1.1 Ambient Temperature 
 
Maximum       50°C 
Maximum mean over   45°C 
This document is property of Design NTDC. No Part of this can be modified or used for any purpose other than its designated purpose.
any 24 hours 
Mean in any year    30°C 
Minimum       ‐10°C 
 
3.1.2 Relative Humidity 
 
The relative humidity may range from 0 to 100 percent. The maximum value 
of  the  ambient  temperature  and  humidity,  however,  do  not  occur 
simultaneously.  During  the  monsoon,  high  humidity  may  persist  for  many 
days at a time along with temperature ranging from 30°C to 40°C. 
 
3.1.3 Altitude 
 
Installation up to 1000m above sea level. 
 

LY
3.1.4 Atmospheric Conditions  
 

N
It  may  be  assumed  that  the  air  is  not  normally  heavily  polluted  by  dust, 

O
smoke,  aggressive  gases,  vapors  or  salt  spray.  However,  at  certain  times  of 
the year, severe dust storms may be experienced. 
 
17
20
4 RATINGS 
5-

 
4.1 The current transformers shall have the following ratings: 
-7

 
R

    500 KV 200 KV  132 KV 66KV


O

1.  Nominal System Voltage, kV rms 500 200  132 66


N

2.  Rated Voltage for the equipment  550 245  145 72.5


R

kV rms 
FO

3.  Rated frequency,Hz 50 50  50 50


4.  Rated lightning impulse  1550 1050  650 325
withstand voltage, kV peak 
5.  Rated switching  impulse  1175 ‐  ‐ ‐
withstand voltage, kV  peak 
6.  Rated primary power frequency  680 460  275 140
short‐time withstand voltage, kV 
rms. 
7.  Short –time (one‐second) 50 40  40 20
thermal current rating (Ith), kA       
rms 
8.  Dynamic current  rating (Idyn),  125 100  100 50
kA rms 
9.   Transformation ratios 3000‐ 2400‐  1200‐ 300‐
This document is property of Design NTDC. No Part of this can be modified or used for any purpose other than its designated purpose.
1500/1A 1200/1A  600/1A  150/1A
10.   Number of secondary core  1 1  1 1
11.   Accuracy class (at all ratios) 0.2S 0.2S  0.2S 0.2S
14.  Instrument security factor  10 10  10 10
15.  Rated burden, VA  15 15  15 15
16.  Secondary winding insulation     
         
One minute power frequency   3  3  3  3 
withstand  voltage, kV rms         
17.   Inter‐turn insulation:    
         
One minute overvoltage  4.5  4.5  4.5  4.5 
withstand over complete 

LY
secondary winding, kV peak 
18.  Maximum temperature‐rise of  45 45  45 45

N
the insulating oil above an 

O
ambient of 50 deg. C, deg.C 
19.   Minimum external creepage 
distance, mm 
17 13750 7000  3800 1800
20
20.  Radio interference voltage  at  500 500  500 500
5-

1.1 Ur/ √3 kV and 1000 kHz, 
microvolts 
-7

 
R

4.2 The accuracy class as stipulated in sub‐clause 4.1 shall be guaranteed at all 
O

specified ratios. 
N

 
R

5     CONSTRUCTION  
FO

 
5.1      General  
 
5.1.1 The  material  and  workmanship  shall  be  of  best  quality  and  in  accordance 
with  the  modern  practices.  The  design  shall  be  such  that  installation, 
replacement and general maintenance may be undertaken with a minimum 
of time and expense. Liberal factors of safety shall be used in the design.  
 
5.1.2 The  current  transformers  shall  be  single  pole,  single‐core,  free  standing, 
hermetically  sealed,  oil  filled,  self  contained  outdoor  type.  These  shall  be 
supplied  complete  with  oil  level  indicators,  steel  support  structures, 
solderless  clamp  type  HV  terminal  connectors  for  connection  to  conductor 
and/or aluminum tube, terminal boxes with terminals for outgoing secondary 
wires, grounding terminals and marshalling boxes as specified. 
  document is property of Design NTDC. No Part of this can be modified or used for any purpose other than its designated purpose.
This
5.1.3 The  oil  shall  be  class  I  oil  conforming  to  the  latest  issue  of  relevant  IEC 
Publication  
 
5.1.4 The current transformers shall be constructed to provide adequate insulation 
for  the  insulation  class  specified  and  to  withstand  mechanical  and  thermal 
stresses produced during short circuit conditions. All insulation and magnetic 
materials  shall  have  proven  and  well  established  physical  and  electrical 
properties  such  as  to  give  continuous  and  prolonged  service  without 
deterioration. 
  
5.1.5 The  current  transformers  shall  be  hermetically  sealed  with  appropriate  and 
most reliable arrangement to accommodate oil level variation. The design of 
220 KV & 500 KV CTs shall essentially employ suitable grade of stainless steel 
bellows  with  the  provision  of  suitable  device  for  indicating  the  position  of 

LY
bellows  which  shall  be  visible  from  ground  level.  In  case  of  other  designs, 
provision shall be made for indicating the oil level. 

N
 

O
5.1.6 To  obtain  multiple  ratios,  series  parallel  arrangement  for  connections  of 
17
primary  winding  shall  be  provided  and  it  shall  be  possible  to  connect  the 
primary  windings  externally  to  change  the  ratios  and  the  interior  of  the 
20
transformer should remain scaled. 
5-

 
5.2 Primary Terminal 
-7

 
R

5.2.1  The primary terminals shall be single‐stem, horizontal, made of copper with 
O

minimum 125 mm length and 60 mm dia. The terminals shall be corona free 
N

and adequately shielded. 
R

 
FO

5.3 Secondary Terminals and Terminal Boxes 
 
5.3.1 The  secondary  leads  shall  be  brought  out  through  the  current  transformer 
tank  wall  be  means  of  multiple  bushings,  equipped  with  connectors  for  6 
sq.mm to 10 sq.mm stranded copper conductor and shall terminate in a low 
voltage weather proof box mounted on the side of the tank. The nameplate 
shall  be  fixed  at  the  outside  of  the  terminal  box  to  be  visible  with  the  box 
closed.  Connection  diagram  shall  be  affixed  inside  the  secondary  terminal 
box so that it can be easily read while working in the box. Provision shall be 
made  for  scaling  the  terminal  box  by  means  of  lashed  wire  as  well  as  pad 
lock. 
 
 
 
  document is property of Design NTDC. No Part of this can be modified or used for any purpose other than its designated purpose.
This
5.4 Earthing Terminals 
 
5.4.1 Two  numbers  earthing  terminals  at  diagonally  opposite  position  shall  be 
provided. Each terminal shall be capable of carrying full short circuit current 
and be suitable for accommodating 95 to 185 sq.  mm copper earthing lead 
depending upon the voltage class of the CT. 
 
5.5 Core and Windings  
 
5.5.1 The  core  shall  be  made  of  high  quality  non‐aging  grain  oriented  annealed 
silicon steel, or some other  superior material, carefully selected and tested 
to provide the best magnetic characteristics. 
 
5.5.2 The  core  and  windings  structure  shall  be  rigidly  braced  and  clamped  to 

LY
sustain given mechanical short‐time rating. The design of core and windings 
shall  be  such  as  to  ensure  high  accuracy,  uniform  impulse  distribution 

N
throughout the winding and low leakage reactance.   

O
 
 
 
17
20
5.6 H.V. Bushings 
 
5-

5.6.1 The  current  transformers  shall  be  equipped  with  H.V.  bushing  of  an 
-7

insulation class not less than that of the winding terminal to which they are 
R

connected and of creepage distance as specified in section 4. 
O

 
N

5.6.2 The bushings shall be manufactured from wet process porcelain and suitable 
for  continuous  outdoor  service.  The  bushings  shall  be  so  constructed  as  to 
R

produce a uniform electrical stress distribution throughout, contain no voids, 
FO

and  be  leak  proof  at  all  temperatures.  Provision  shall  be  available  for 
measurement of capacitance and dielectric loss factor of each bushing. 
 
5.7 Tank  
 
5.7.1 The tank housing the active  part shall  be constructed of galvanized  steel or 
corrosion  proof,  high  quality,  cavity‐free,  cast  aluminum  alloy  and  shall  be 
suitably  reinforced  to  withstand  rigors  of  handling  and  excessive    pressure 
under  fault  conditions  without  distortion.  All  welded  joints,  pipe  work  and 
valves  etc.  shall  be  oil‐leak  tested.  A  clamp  on  cover  shall  preferably  be 
provided to allow access to component parts within the tank without undue 
difficulty. 

This document is property of Design NTDC. No Part of this can be modified or used for any purpose other than its designated purpose.
5.7.2 Grounding  lugs  complete  with  connectors  suitable  for  95  to  185  mm2 
stranded copper conductor depending upon the voltage class of the CT shall 
be provided  
 
5.8 Marshalling Box 
 
5.8.1 A marshalling box shall be mounted on centre phase structure with terminals 
to  terminate  all  secondary  connections  of  three  CTs  in  a  3  phase  set.  Self‐
shorting  and  isolating  type  terminals  shall  be  provided  for  CT  secondary 
circuits.  The  box  shall  be  fabricated  from  steel  sheet,  not  less  than  3  mm 
thick,  seam‐welded  at  corners.  However,  in  case  of  rigid  frame  design,  the 
thickness  of  steel  sheets  may  be  reduced  according  to  manufacturer’s 
standard design. At least 20% spare terminals shall be provided in the box. 
 

LY
5.8.2 The  box  shall  be  designed  for  protection  class  IP54  in  accordance  with  IEC‐
529. Gland plates shall be provided for proper termination of cables. 

N
 

O
5.8.3 Provision  shall  be  made  for  locking  the  marshalling  bob  by  pad  locks  and 
sealing by means of lashed wire and lead seals. 
 
17
20
5.8.4 Heaters  with  thermostat  and  humidistats  shall  be  provided  inside  each 
marshalling  box.  Lamps  with  door  operated  switch  shall  be  provided  for 
5-

internal illumination. There shall be a single phase power socket inside each 
-7

marshalling  box.  An  MCB  with  auxiliary  contact  shall  be  provided  for 
R

switching  ON/OFF  the  AC  power  supply  to  the  heating,  illumination  and 
O

power  socket.  The  MCB  shall  also  be  equipped  with  sensitive  earth  fault 
N

protection for personnel safety.  
 
R

5.8.5 Each  star‐point  of  the  CT  circuit  shall  be  separately  grounded  through 
FO

isolating  type  terminals  to  enable  convenient  verification  of  single‐point 


grounding of the interconnected CT circuit.   
 
5.9 Accessories  
 
5.9.1 The current transformers shall be provided with the following accessories: 
 
1).   Lifting lugs  
2).   Drain and filling valves with stainless steel plugs  
3).   Bellows (if applicable) and level indicators  
 
 
 
 
This document is property of Design NTDC. No Part of this can be modified or used for any purpose other than its designated purpose.
6 TERMINAL MARKINGS 
 
6.1 The terminal markings for the current transformers shall be in accordance 
with the latest issue of relevant IEC Publication, and shall clearly identify the 
secondary terminals corresponding to each specified current ratio. 
 
7 RATING PLATE 
 
7.1        The  rating  plate  makings  shall  be  of  permanent  nature  and  shall  be  in 
accordance with the latest issue of relevant IEC Publication. In addition to the 
data mentioned in IEC Standard, knee point voltage, magnetizing current and 
secondary  winding  resistance  at  specified  temperature  of  core  at  each  tap 
shall  be  engraved  on  the  nameplate.  Engraving  shall  be  white  on  a  black 
background. 

LY
 
8 TESTS 

N
 

O
8.1 General 
 
17
The  current  transformers  shall  be  subjected  to  type  and  routine  tests 
20
specified herein. 
 
5-

8.2  Type Tests 
-7

 
R

The  following  type  tests  shall  be  made  on  a  CT  of  each  type  and  rating  in 
O

accordance with the latest issue of relevant  IEC Publication 60044‐1 (2003‐
N

02). 
 
R

(1)    Short –time current tests, sub‐clause 7.1. 
FO

(2)    Temperature‐rise test, sub‐clause 7.2 
(3) Lightning and switching impulse voltage tests on primary windings as  
applicable, sub‐clauses 7.3.2 and 7.3.3 
(4)     Determination of errors, sub‐clauses 11.4 and 11.6. 
(5)     Wet test for outdoor type transformers, sub‐clause 7.4. 
(6)     Radio interference voltage measurement (RIV), sub‐clause 7.5 
(7) Measurement of capacitance and dielectric dissipation factor .The 
variation of Tan Delta measured at 1.1 Un must be less than 0.2 % 
between 20˚C and 75˚C sub‐clause 9.2. 
 
Satisfactory  and  valid  type  test  reports  from  an  accredited  independent 
laboratory  on  similar  units  may  be  submitted  in  lieu  of  performing  the  test 
for approval. In case the reports are not found relevant or are otherwise not 
to the satisfaction of the purchaser, the type tests shall be performed at one 
This document is property of Design NTDC. No Part of this can be modified or used for any purpose other than its designated purpose.
of the designated independent laboratories in presence of representative of 
the purchaser at the arrangement , cost and expenses of the supplier. 
 
8.3  Routine Test  
 
The following routine tests shall be made on all CTs in accordance with the 
IEC Publication 60044‐1 (2003‐02) for all ratios and at all taps when provided: 
 
(1)  Verification of terminal markings, sub‐clause 8.1. 
(2)   Power‐frequency withstand test on primary winding, sub‐clause 8.2.1. 
(3) Power‐frequency withstand test on secondary winding and between 
sections, sub‐clause 8.3. 
(4)    Inter‐turn over‐voltage tests, sub‐clause 8.4 
(5)    Partial discharge measurement, sub‐clause 8.2.2 

LY
(6)  Determination of errors and accuracy, sub‐clauses 11.5, 12.4, 11.6, 12.6 

N
and 14.4.  

O
 
9 DRAWINGS AND DESCRIPTIVE DATA 
  17
20
9.1 Tender Drawings & Data: 
 
5-

A) Descriptive in formation (General) : 
-7

 
The following information shall be provided with the bid: 
R

 
O

1) Detailed  dimensional  drawing  of  the  current  transformer,  also  showing 


N

the  location  of  accessories,  alongwith  a  list  of  components  duly  cross‐
R

referred with the drawings. 
FO

2) Sectional drawings of the current transformer indicating the inner details. 
3) Primary connections arrangement drawing. 
4) Secondary terminal box drawing and marshalling termination details.  
5) Drawing showing fixing arrangement of the bellows, if applicable. 
6) Drawing  showing  the  method  of  sealing  and  attachment  in  case  of 
bellows also indicating the material and endurance life. 
7) Typical  current  error  and  phase  displacement  curve  for  the  standard 
burdens from 0 to 1.5 times rated secondary current. 
8) Typical  excitation  curves  for  current  transformer  upto  20  times  the 
secondary rated current. 
9) Transient response curves. 
10) The maximum allowable mechanical loads for: 
a) Any one primary terminal in any direction  
b) Total  resulting  load  applicable  to  top  assembly  in  any  direction  on 
This document is property of Design NTDC. No Part of this can be modified or used for any purpose other than its designated purpose.
primary terminals. 
c) Torque/resulting torque in horizontal direction on primary terminals. 
11)  Technical catalogue in respect of the bushings. 
12)  Installation, erection, maintenance and operation instruction manuals.  
13)  Reference data for moisture content and dissolved gases of oil.  
14)  For  evaluation  purpose,  foundation  drawings/data  such  static  dynamic 
forces, using RCC structure (if steel supports are not provided) and steel 
support  shall  be  provided  using  the  soil  bearing  capacity  10  tons/meter2 
for  seismic  and  non  seismic  zones  separately  taking  horizontal 
acceleration  0.2  G  for  seismic  zones.  Design  calculations  and  guidelines 
for these shall also be supplied. 
 
 
 
 

LY
 
 

N
 

O
 
 
 
17
20
 
 
5-

 
-7

 
R

 
O

 
N

 
 
R

 
FO

 
 
 
 
 
 
 
 
 
 
 
 
 
 
This document is property of Design NTDC. No Part of this can be modified or used for any purpose other than its designated purpose.
B)                    Schedule of Technical Data (Particular): 
 
The following information, as applicable shall be furnished with the Bid for each 
type of voltage transformer: 
 
1.  Manufacturer  ______________________
2.  Type  ______________________
3.  Rated nominal voltage,kV rms ______________________
4.  Rated steady state maximum voltage,  
kV rms   
______________________ 
5.  Rated continuous overvoltage , kV rms ______________________
6.  Rated frequency Hz ______________________
7.  Rated primary current, A rms ______________________

LY
8.  Rated secondary current, A rms ____________________
   

N
9.  Rated transformation ratios ______________________

O
10.  Rated output, VA  ______________________
11.  Accuracy Class 
12.  Accuracy limit factor
17 ______________________
______________________
20
13.  Instrument security factor ______________________
5-

14.  Short time current ratings: ______________________


i) Thermal, kA  ______________________ 
-7

ii) Dynamic, kA  ______________________ 


R

15.  Rated  lightning  impulse  withstand  ______________________


O

voltage, kV Peak  
N

16.  Rated  switching  impulse  withstand  ______________________


R

voltage kV Peak 
FO

17.  Power  frequency  withstand  voltage,  kV  ______________________


rms 
18.  Rated  secondary  winding  power  ______________________
frequency withstand voltage 
19.  Maximum  temperature‐rise  under  ______________________
specified  service  conditions  above 
ambient of 50 ˚C  
20.  Partial discharge level  ______________________
21.  Design test certificate:
(a) Issuing institute    
(b) Number and data  ______________________ 
22.  Creepage distance, mm ______________________
23.  Max.  RIV  at  1.2  nominal  voltage  and 1  ______________________
MHz, micro‐volts 
24.  Mechanical load on primary terminals:
This document is property   purpose other than its designated purpose.
of Design NTDC. No Part of this can be modified or used for any
(a) Dynamic load, N ______________________
(b) Static Load, N 
25.  Material of bellows, if applicable  ______________________
26.  Minimum height, mm ______________________
27.  Minimum phase spacing, mm ______________________
28.  Minimum clearance, mm ______________________
29.  Minimum creepage distance, mm ______________________
30.  Overall dimensions, mm ______________________
31.  Size  and  section  of  terminal  bolt  (attach  ______________________
drawing), mm 
32.  Weight per pole, kg ______________________
33.  Weight of oil per pole, kg ______________________
34.  Weight  of  supporting  structure,  if  ______________________
applicable, kg 

LY
35.  Type of oil and reference specifications 
(a) Oil density at 25˚C, gm/ml   

N
(b) Oil viscosity at 25 ˚C, cs   

O
36.  Maximum allowable static and dynamic
Forces  applied  at  outermost  point  of   
bushings: 
17
20
(a) Horizontal, N                            ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐
5-

(b) Vertical ,N  ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ 


-7

 
R

9.2 Contract Drawings 
O

 
N

The following drawings & data shall be supplied by the manufacture/bidder for 
approval  by  the  purchaser  after  the  order  is  placed  and  before  the 
R

manufacturing is started:  
FO

 
1. All data and drawings asked for in clause 9.1. 
2. Drawing and dimensional details of the foundation bolts. 
3. Name plate drawing. 
4. Connection diagram plate drawing. 
5. Drawing showing arrangement of fixing of base and grounding screws. 
6. Large  scale  dimensional  sketches  along  with  reproducible  of  the  current 
transformer showing the details of base and its fixing arrangement on steel 
and/or reinforced cement concrete supporting structure. 
7. Ten  copies  along  with  one  set  of  reproducible  of  the  installation,  erection, 
maintenance and operation instruction books.   
 
 
 
This document is property of Design NTDC. No Part of this can be modified or used for any purpose other than its designated purpose.
 
 
PRIMARY TERMINAL OF 500kV 
          CURRENT TRANSFORMER 

17.5 mm                  45 mm                                                     45 mm                             17.5mm 

17.5mm
17 mm Ǿ 

45 mm
LY
N
O
17
20
5-

THICKNESS 
-7

45 mm 
30 mm 
R

MATERIAL 
O

COPPER 
N
175 mm

R
FO

6.75 mm 

 125 mm

  Figure ‐1 
This document is property of Design NTDC. No Part of this can be modified or used for any purpose other than its designated purpose.