TECHNICAL CHARACTERISTICS FOR OFFERED TRANSFORMER

Standard: IEC 60076


Rated Power: 500 kVA
Continuos Rated Power: 100 % Duty Cycle
Phases: Three (3)
Windings: Two
Rated Voltages (Currents) at no-load :
Primary: 11000 V (26.26 A)
Secondary 415 V (695.61 A)
Voltage regulation (Off-load Tapswitch) ± 2 steps @ 2.5%
Rated Frequency 50 Hz
Connections of Phases:
Primary (HV) winding Delta
Secondary (LV) winding Star
Connection(vector group) symbol Dyn11
Type of Core: Three limb core type
Core material: Cold-rolled grain oriented Silicone Steel, Grade M3 - 0.23mm
Type of Tank: Heametically Sealed with upper bolted cover
Coolant Mineral Oil according to IEC 60296
Cooling Method ONAN
Installation Type Suitable for both InDoor & OutDoor (Max Ambient 40oC)
Max Temperature-Rise Limits:
Windings 55°C
Top oil 50°C
Insulation Level
Power frequency withstand voltage:
Primary winding 28 kV
Secondary winding 3 kV
Lightning impulse withstand voltage:
Primary winding 95 kV
Secondary winding - kV

Losses:
No-load loss 740 W (Tolerance as per IEC 60076)
Load loss 6580 W (Tolerance as per IEC 60076)
Impedance voltage 6.00 % (Tolerance as per IEC 60076)
Approximate Weights:
Mineral Oil: 335 kg
Total Weight 1550 kg

Approximate Overall Dimensions including Bushings & other Fittings :


Height 1510 mm
Length 1515 mm
Width 925 mm

** Note: All dimensions and weigths are specified as approximately. Actual product may differ from above calculated values.
Accessories/Fittings : Pressure Relief Valve, Oil Level Indicator, Off-load TapChanger.
Oil Temperature Indicator, Hv & Lv Porcelain Bushings, Lifting Lugs, 2 x Earthing Terminals

Prepared By : K. Kadzimba