Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 22

1.

Electromagetic Static Relays


1
00:00:00,830 --> 00:00:04,070
Hello and welcome, everyone, very happy that we're all together again.

2
00:00:04,280 --> 00:00:08,780
And this story, everyone took up how We ll about the different types of relays, so fast in your pills

3
00:00:09,170 --> 00:00:14,810
And let's get started them. The Sartorialist to look up how This tutorial is to talk about the different
types of protection relays

4
00:00:15,020 --> 00:00:20,630
according to their principle of working as we have an evolution and the relay's design and technology

5
00:00:20,660 --> 00:00:24,140
due to the great development of the relay is through the time.

6
00:00:24,740 --> 00:00:25,880
So let's go ahead.

7
00:00:26,270 --> 00:00:31,450
First of all, we say that the relays have some different types according to that the working principle. /N
8
00:00:31,790 --> 00:00:34,160
And for that, we have three main types.

9
00:00:34,430 --> 00:00:37,190
The first one is the electromagnetic relays.

10
00:00:37,430 --> 00:00:39,500
The second one is the static relays.

11
00:00:39,800 --> 00:00:42,680
And the third one as is the digital relays.

12
00:00:43,220 --> 00:00:46,190
So let's start now with the electromagnetic type.
13
00:00:46,730 --> 00:00:52,580
The first type of relays we have now is the electromagnetic relays and the there are the oldest type of
relays

14
00:00:52,700 --> 00:00:54,650
that are used and in the prediction protection system.

15
00:00:54,980 --> 00:00:59,180
And for that, it's the first generation of the protection related relay technology.

16
00:00:59,660 --> 00:01:02,270
And the type of relays has two main types.

17
00:01:02,510 --> 00:01:06,170
The first one is the henges are Metcher Hinged armature electromagnetic type.

18
00:01:06,620 --> 00:01:13,100
So the working principle of that type of four lazies Relays that when the full fault current passes
through
19
00:01:13,100 --> 00:01:18,130
the current transformer, it's transferred from the current transformer to the relay coil.

20
00:01:18,170 --> 00:01:19,110
Like that coil here.

21
00:01:19,350 --> 00:01:21,860
Hence, an electromagnetic field is generated.

22
00:01:21,890 --> 00:01:26,820
And (in) the coil and this electromagnetic field cosies (coils) the call (coils) to magnetize it.

23
00:01:27,380 --> 00:01:31,520
And when the kyla's (coil) magnetize it, it's converted to a temporary magnet.

24
00:01:31,970 --> 00:01:37,900
And this term prudery (temporary) magnet will attract the mover pull (movable) contact of the relay to
be connected to the
25
00:01:37,900 --> 00:01:38,900
fixed contact.

26
00:01:39,110 --> 00:01:44,870
So this attachment or this contact between the move up (movable) contact and the fixed contact will
make

27
00:01:44,870 --> 00:01:50,930
current to pass through the relay. hands (Hence), the relay will send a signal to the circuit breaker to
create (break)
28
00:01:50,960 --> 00:01:51,560
these circuit.

29
00:01:52,010 --> 00:01:54,470
So that's for the Hanjin or Metcher (Hinged armature) type.
30
00:01:55,310 --> 00:02:02,090
Now, the second type as the induction desk (disc) type and this type has of the same electrical principle

31
00:02:02,090 --> 00:02:03,080
of the previous one.

32
00:02:03,200 --> 00:02:09,260
But at the changes, it's mechanical working in principle, as what happens here is that the fault current

33
00:02:09,290 --> 00:02:15,920
is passing through the call (coil) of the relay. Hence, the relay Cauldwell p (coil will be) magnetize it
and it will be converted

34
00:02:15,920 --> 00:02:17,390
to a temporary magnet.

35
00:02:17,810 --> 00:02:24,380
And this magnetic force of the relay coil will be used to rotate this movable desk (disc) with a specific
angular

36
00:02:24,380 --> 00:02:29,570
distance that is proportional to the full (fault) current, which means when they fold (the fault) current
passes through

37
00:02:29,570 --> 00:02:33,740
the coil, this desk (disc) will move with a specific angular distance.
38
00:02:33,980 --> 00:02:39,530
And this is specific angular distance will make the fix (fixed) contact to touch the movable contact.
.

39
00:02:39,830 --> 00:02:44,780
And when the two contacts touches each other, the current will pass through the relay.

40
00:02:44,960 --> 00:02:49,090
Hence, the relay will send a signal to the circuit breaker to prigg (break) the circuit.

41
00:02:49,490 --> 00:02:55,700
And this is the shape of the induction disk (disc) type protective relay, which is used Embley (in the)
protection of the power system.

42
00:02:56,060 --> 00:03:02,870
But as of this type has some mechanical parts and this mechanical design plays an important role in its
design.

43
00:03:03,230 --> 00:03:08,320
There may be many errors of the Tappan's (that happens) during the dynamic operation of that type of
relays.

44
00:03:08,780 --> 00:03:14,270
And for the disadvantage of that type of relay, as we move to invent a second generation of the
protection relays

45
00:03:14,270 --> 00:03:21,080
which as (is) these static relays and the basic idea behind the aesthetic relays is that it uses

46
00:03:21,170 --> 00:03:24,170
an operational amplifier like that one here.

47
00:03:24,530 --> 00:03:28,690
And this operational amplifier has two inputs and one output here.

48
00:03:28,710 --> 00:03:34,640
The output will give a high signal when the positive signal has a larger value than the negative signal,

49
00:03:34,910 --> 00:03:42,470
while the outputs will give a zero signal or a low signal when the positive input has the same value of
the negative signal.

50
00:03:42,920 --> 00:03:48,170
And to apply the principle of the impressionable (operational) amplifier, in our case of the protection
relay

51
00:03:48,170 --> 00:03:57,080
we find the positive input to be connected to the signal coming from the current transformer and the
negative input is connected to the setting signal.

52
00:03:57,440 --> 00:04:03,050
And this value of the current as a B (the) rated value of the current that is coming from the current
transformer

53
00:04:03,200 --> 00:04:09,920
that the current transformer since (sends) at the normal case with no fault condition or with no fault.
Hence

54
00:04:09,950 --> 00:04:15,680
at the normal condition, with no fault, the current transformer will send the rate signal to the positive
input

55
00:04:15,740 --> 00:04:20,240
And at the same time the negative input is set on the sitting (setting) value.

56
00:04:20,420 --> 00:04:21,890
That is the rate at current.

57
00:04:22,340 --> 00:04:25,610
So there will be no difference between the two signals.

58
00:04:25,760 --> 00:04:31,610
Hence, the output of the operational amplifier will pay zero, which means the operational amplifier

59
00:04:31,610 --> 00:04:34,580
will send as zero signal to the circuit breaker.

60
00:04:34,730 --> 00:04:39,080
So the circuit breaker will since (sink) no current or that is no fault at that case.

61
00:04:39,230 --> 00:04:43,640
So the circuit breaker will take no action or it will not take any action.
62
00:04:44,060 --> 00:04:45,710
And this is at the normal case.

63
00:04:46,010 --> 00:04:55,880
But suppose now that is a fault and in the circuit here, the positive input will be connected to the
current transformer, which has the full (fault) current. Now wildly (while) negative input.

64
00:04:55,900 --> 00:04:58,400
Will still having the rated current signal.

65
00:04:58,730 --> 00:05:02,380
And we know that before (the fault) current is very large and Bamby (than the) rated current..

66
00:05:02,530 --> 00:05:08,230
So there will be a great difference between the two inputs of the original (operational) amplifier, as the
positive input

67
00:05:08,290 --> 00:05:14,500
has a larger signal, which is the full (fault) current, while the negative input is having the rated current.

68
00:05:14,980 --> 00:05:20,630
And due to the difference between these two inputs, the output of the operational amplifier will peahi
(be high)

69
00:05:20,650 --> 00:05:25,330
at that case, which means we will send a high signal to the circuit breaker.
70
00:05:25,660 --> 00:05:31,340
So once the circuit breaker senses (sends) a high signal, it will break the circuit as a tricky ignites
(recognizes).

71
00:05:31,390 --> 00:05:33,100
that there is a fault in the circuit.

72
00:05:33,420 --> 00:05:39,760
So this is of the basic idea behind the second generation of the protection relays, which is the static
relays.
73
00:05:40,240 --> 00:05:48,820
But that type of prediction (protection) relays has a disadvantage, which is that its output signal and its
results is affected by the temperature.

74
00:05:49,060 --> 00:05:52,780
And this may produce some errors due to the temperature change.

75
00:05:52,870 --> 00:05:59,390
So there may be some errors in the results and due to this advantage of that type of relays
76
00:05:59,590 --> 00:06:04,600
we invented a third generation of the relays, which as the digital relay is.

77
00:06:04,780 --> 00:06:07,780
But we will start illustrating it on the next tutorial.

78
00:06:08,380 --> 00:06:15,580
So this tutorial at which we illustrated the first two types or the first two generations of the prediction
relays.

79
00:06:15,950 --> 00:06:17,080
That's the clear right now.

80
00:06:17,110 --> 00:06:19,210
Thank you for watching and see you next tutorials.

2. Digital Relays
1
00:00:00,180 --> 00:00:01,470
Hello and welcome, everyone.

2
00:00:01,500 --> 00:00:06,750
For happy that we are all together again and this story will continue talking about the different types

3
00:00:06,750 --> 00:00:08,100
of B be protection relays.

4
00:00:08,490 --> 00:00:09,680
So fasten your poles.

5
00:00:09,780 --> 00:00:10,970
And let's get started.

6
00:00:11,450 --> 00:00:16,040
The aim of this material is to continue talking to possibly different types of the protection relays.

7
00:00:16,080 --> 00:00:21,870
According to that working principle, as we have an evolution and the release, design and technology

8
00:00:22,050 --> 00:00:25,200
due to the great development of the relay is through the time.

9
00:00:25,830 --> 00:00:26,910
So let's go ahead.

10
00:00:27,510 --> 00:00:33,130
Now, the next time we need to discuss is be digital relays and the digital relay.

11
00:00:33,130 --> 00:00:39,600
Simple idea is that the current transformer and the voltage transformer is sending its signal to the

12
00:00:39,600 --> 00:00:40,080
relay.

13
00:00:40,470 --> 00:00:47,130
But this since signal is an analog one, hands on the relay has an analog to digital converter that

14
00:00:47,130 --> 00:00:53,130
is used to convert the current M.B bullish signals from an analog one to a digital one that can be read

15
00:00:53,160 --> 00:00:53,760
and stored.

16
00:00:53,790 --> 00:00:59,780
And the ram ramp of the relay and then the relay compared that since signal to the sitting signal that is

17
00:00:59,800 --> 00:01:00,810
stored on it.

18
00:01:01,080 --> 00:01:03,900
And if since signal equals the setting signal.

19
00:01:03,930 --> 00:01:05,730
This means there is no fault.

20
00:01:05,760 --> 00:01:09,330
Hence the relay will not send a signal to the circuit breaker.

21
00:01:09,540 --> 00:01:16,050
So the circuit breaker will not Chalaby copy while at the send signal is larger than be sitting setting
signal.

22
00:01:16,350 --> 00:01:22,050
This means that the send signal from the current transformer or from the voltage transformer is a false

23
00:01:22,050 --> 00:01:25,500
signal and we must take an action to prag beaker these circuit.

24
00:01:25,890 --> 00:01:29,310
Hence the relay will send a signal to the circuit breaker to breaker.

25
00:01:29,310 --> 00:01:35,640
These circuit and B the modules that the digital relay consists of are the analog to digital module that

26
00:01:35,640 --> 00:01:42,240
we just illustrated and the microprocessor that is supposed to p be the Prain of the system which
analyze

27
00:01:42,300 --> 00:01:44,490
these signals and give the results.

28
00:01:44,970 --> 00:01:51,570
And also we have a B as Mattick the arithmetic logic unit, which is responsible for making some
charismatic arithmetic operation

29
00:01:51,990 --> 00:01:58,170
and then dirigiste data that is used to store the digital values inside the relay and the memory of

30
00:01:58,170 --> 00:02:04,350
the relay that the relay used to store the information like the ascent decent valley value of the current
and the bullish voltage

31
00:02:04,590 --> 00:02:09,540
that the relay will treb trip the circuit of the incoming signal exceeds those values.

32
00:02:10,020 --> 00:02:10,650
Very good.

33
00:02:11,040 --> 00:02:16,680
But after generating this third generation of relay is a B digital ones, once we found that we need

34
00:02:16,680 --> 00:02:20,340
to make some modifications on them to improve their results.

35
00:02:20,580 --> 00:02:27,240
Hence, we invented the adaptive digital relays, which as a b fourth generation of the release and

36
00:02:27,240 --> 00:02:32,190
those released have some additional options with respect to the digital relays.
37
00:02:32,610 --> 00:02:38,520
And the first added feature is that it can change at setting value or be current and voltage at any

38
00:02:38,520 --> 00:02:44,820
time automatically, according to some data that it's collected from the powered network, which means

39
00:02:44,850 --> 00:02:48,780
it can change the value of the current that it's well preg the circuit at which.

40
00:02:49,410 --> 00:02:55,920
And also the second feature of that kind of relays is that it can distinguish between the ordinary
increase

41
00:02:55,980 --> 00:02:59,720
and the loop current and the case at which there is a true fault.

42
00:02:59,880 --> 00:03:00,630
And these circuits.

43
00:03:00,870 --> 00:03:06,790
And this means this relay can recognize well, which is the ordinary case of the circuit with no fault.

44
00:03:07,020 --> 00:03:10,380
And which case as the faulty one, ODAC has a fault.

45
00:03:10,950 --> 00:03:11,530
All right.

46
00:03:12,150 --> 00:03:18,930
Now, the less type of relay is we have as the multi-function digital relay and this type of relay,

47
00:03:18,930 --> 00:03:24,180
it is a collective one, which means it collects more than one function and wonderly.

48
00:03:24,690 --> 00:03:30,660
And this is because for all of the previous types of as we discussed, we need a single relay for each
49
00:03:30,660 --> 00:03:31,160
parameter.

50
00:03:31,170 --> 00:03:32,570
We need to detect its fault.

51
00:03:32,850 --> 00:03:38,490
For example, we need a separated relate to detect the over current condition and we need another one

52
00:03:38,490 --> 00:03:40,550
to detect the over voltage condition.

53
00:03:40,890 --> 00:03:43,560
And we need a third one for the distance protection.

54
00:03:43,890 --> 00:03:50,130
But here in the multi-function relay, we can use only one relay that detect more than one type of faults.

55
00:03:50,430 --> 00:03:56,720
So with can detect the overcut on the over voltage and it can work as a distance relay and one type.

56
00:03:57,030 --> 00:04:02,730
But the disadvantage of that type of four lazes that if there is a failure and one protection system,

57
00:04:03,020 --> 00:04:09,090
all of the protection systems will stop as this relay detects all the faults and one module.

58
00:04:09,360 --> 00:04:13,470
So its failure means a total failure in all of these functions.

59
00:04:13,920 --> 00:04:19,860
But to solve this problem, there must be a backup protection system or a backup protection device that

60
00:04:19,860 --> 00:04:22,840
is used in case of the failure of that type of really.
61
00:04:23,340 --> 00:04:29,640
So the pickup protection will work in case of this protection system failure more than great.

62
00:04:29,760 --> 00:04:30,530
So that's ApoB.

63
00:04:30,540 --> 00:04:35,350
This tutorial at which we continue talking about the different types of relay is how.

64
00:04:35,430 --> 00:04:36,530
That's the clear right now.

65
00:04:36,570 --> 00:04:37,980
Thank you for watching and see you next.

66
00:04:37,980 --> 00:04:38,670
Tutorials.
3. Fators Affecting Fault Current
Hello and welcome everyone. We're happy that we are all together again in the upcoming tutorials. We
will talk about the overcurrent relay over current really in some details so fast in your felt fast senior
vote and let's get started. The aim of this tutorial is to talk about this story also took a part of the the
factors that affect the value of the fault current that passes through the circuit and the overcurrent relay
which must detect that overcurrent or that fault current. So let's go ahead.
First of all, if we need to revise the full current condition that occurs in the power system and how the
overcurrent relay overcut interrelate can detect at, we say that if this is the overcurrent relay and those
are the current transformers connected to at, and if we say that at the normal case, the current passes
through that motor is about 100 ampere current path through that motor is a pouch, one hundred and
pier. So we will set the overcurrent relay on 100 ampere, which means that it will trap the circuit. At
the passing current is larger than 100 ampere greatly one hundred ampere gritli. Now, at the passing
current through that relay, as 90 ampere, . The over cannot the overcurrent relay will not sense any
fault. Hence it will not send any signal to the circuit breaker.
Hence, the circuit breaker will continue closing the circuit. But if the passing current now is about 200
amperes, this value is larger than the setting sitting value on the relay, which is 100 ampere, as we
said. So the relay will send a signal to the circuit breaker to treb the circuit. So that's the idea behind the
overcurrent relay, which is to give a signal of trapping the circuit if the path in current is larger than its
sitting current. All right, now we need to know what are the factors which affect the value of the fold
furled current.
This is because the value of the fold full current can change greatly according to some factors. So it
with can increase or it can decrease. Here, the first factor is the fault position the full possession, as
when the fault position becomes far from the relay position, the impedance that starts from the fault
from the fall to the relay will increase. Hence the fault the full currents current will decrease as the
current is inversely proportional to the impedance. And the inverse is right, as when the position of the
fault default becomes nearer to the position of the relay, which means the impedance between them is
smaller and better condition
At that condition, the full current will be well, p larger, and we can apply that concept on that network.
Here. Suppose this is the first transmission line that has an impedance of Z one zie one, and this is the
second part of the transmission line that has an impedance of Z two. And this is the third part, and it
has an impedance of Z three. Now, we can represent the network in a simple circuit like that one.
Here. As you see, we have the generator as Legian ray rater as the power source and then the
impedance of the first transmission line to PZ one and then the impedance of the second transmission
line to PZ two Peezy two.. And then the impedance of the third transmission line to PZ three. And
finally, the load that the power network is going to feed so we can simplify it. And that impedance
here.
Very good. Now, suppose a fault occurs at the end of the first part of the transmission line. So this fault
will make the circuit to be a shortage one on the first impedance, which is z one. And this means the
total current now will pass only through z one zie. Hence hands, the current will equal the source
voltage over
And this is a very large current because the impedance is very small, which is z one only as z. one, Ali.
So at that case, as the fault is very near to the source, the current is larger at that case. So at that case, as
the fault is BEA faulvery near to the source, the current will be large. But suppose we have another
case at which the fault occurs at the end of the second part of the transmission lines. So the total
impedance that the source will see is z one plus z two.
So the Soby impedance increases now, and this will make the fault full current to decrease a little bit.
So the full current now equals V source over z one plus z two, which will give a smaller value of the
fault current. At that case, as the fault current becomes further from the source a little bit. All right,
now suppose the fault default becomes at the third transmission line. So the impedance now will
increase to PZ one plus z two plus z three.
And this means the current passing through the circuit will equal the source voltage over zie z one plus
z two plus z three. And as the impedance increases here, the full current will decrease, or we will have
a smaller full current when comparing it with the previous two cases. So at that case, when the fault
becomes more further from the source or from the protection relay, really, the fault the full current
current will become smaller. But you can note at all of those types we illustrated before, there is no
ground and default, so the lines were not connected to the ground. But suppose in that case here, the
lines are connected to the ground and the fault case here there will be an Earth resistance which will be
added to the total impedance of the circuit.
So the full current now will equal the source voltage over z one plus z two plus z three plus R sub f,
which is the ground resistance. But as the ground resistance has a very large value, so soby the fault
current at that case will be very small. And for that reason, this type of fault is called the high
impedance fault. And this type of fault is a hard one to detect because this fault Folt current is nearer to
the rated the eRate current of the circuit as the fault resistance is very high. So it's not easy for the relay
to distinguish between the fault current and the rated current through the circuit.
Very good. So let's support the first factor affecting the fault So that's a public first factor affecting the
full current, which is the fault position the full possession. Now, the second factor affecting the fault
current is the strength of the power source. And the strength of the power source is measured by the
value of the source impedance, as when the source impedance decreases, this means we have a more
strong power source. While when the strength of the power source increases, this means we have a less
strong power source.
For example, if we have those three power sources that are connected in parallel to feed a network, like
that one here. Now, the total impedance of the power source will p any one of them over three, as they
are connected in parallel. So it will p x surpass over three, which is a lower value than x sub S. And as
this x sub s over three is a lower value, those power sources will represent a low source impedance.
Hence, the current handsley passing through the circuit will be the source voltage over x sub s
knowledge over X. over three, plus the network impedance.
But as x sub s over three is a smaller value, this will give a larger fault Folt current. So we can conclude
that when the power source is more strong, we will have a higher or a great fault grateful current, as we
have a lower source impedance. And the inverse is right, as when we have a higher source impedance,
we will have a less least strong power source, as you see. In that case, we have only one power source.
So the total source impedance will be X sub s, which is a larger value than the previous case.
So it represents a high source impedance. Now, and then the fault current equals the source voltage
over the fault the foltz resistance plus the source impedance. And the fault current now will be a
smaller value, as the source has a high impedance, as you see.
So we say that a bit less a strong power source, the lower a villain will fold current more than great.
So that's a. This material at which we took the part of the factors affecting the over current or the full
current and the over current really hold that sickly right now. Thank you for watching and see you next.
Tutorials
4. Overcurrent Relays
1
00:00:00,970 --> 00:00:02,260
Hello and welcome, everyone.

2
00:00:02,290 --> 00:00:04,090
Very happy that we are all together again.

3
00:00:04,300 --> 00:00:10,240
And the story we will start talking about that letus this related to the over current Reles so fast

4
00:00:10,240 --> 00:00:10,870
in your pilled.
Trong hệ thống của bạn

5
00:00:10,930 --> 00:00:13,430
And let's get started them of this story.
6
00:00:13,430 --> 00:00:19,590
Also learn in general, what are the different tests that we apply on the over current relays as pie?Twice
7
00:00:19,640 --> 00:00:25,750
Those tests, we can't shake the quality of the over current relays and their ability to withstand the

8
00:00:25,750 --> 00:00:29,410
different conditions during the working operation and the power system.

9
00:00:30,010 --> 00:00:31,150
So let's go ahead.
10
00:00:31,600 --> 00:00:35,200
First of all, we need to say that the test is related to the over.

11
00:00:35,200 --> 00:00:39,630
Current relays are changing according to the type of the relay itself.

12
00:00:40,060 --> 00:00:46,360
And this means for the electromechanical relays, for example, we are performing some tests that may

13
00:00:46,360 --> 00:00:50,170
change from the tests which we perform on the digital relays.

14
00:00:50,500 --> 00:00:53,470
But we will illustrate the test for the digital relays.

15
00:00:53,650 --> 00:01:00,310
And the reason is that the distance related to the digital relays are some global and general tests

16
00:01:00,520 --> 00:01:06,400
that include all the required tests, and they include also the tests of the electromechanical relays.

17
00:01:06,670 --> 00:01:09,200
So let's see, what are those general tests?

18
00:01:09,220 --> 00:01:15,070
As for the digital relays, the first type of this is required for the digital over current relay is
19
00:01:15,100 --> 00:01:16,780
as a be protective function.

20
00:01:16,810 --> 00:01:23,500
This, this and at those tests we check the ability of the over currently to protect the circuit pi by

21
00:01:23,510 --> 00:01:28,240
tripping the circuit and the actual full cases after the design delay time.
22
00:01:28,570 --> 00:01:33,850
So we need to test the relay if we can depend on for protecting the circuit or not.
23
00:01:34,120 --> 00:01:39,590
And then the second type of this, this as the measuring accuracy test and of that type of distance,
24
00:01:39,640 --> 00:01:42,550
we measure the accuracy of the over current relay.

25
00:01:42,880 --> 00:01:46,990
If it works accurately according to the design parameters or not.
26
00:01:47,380 --> 00:01:53,620
For example, if the relay is adjusted to trip the circuit after one second, if we tested it and we

27
00:01:53,620 --> 00:01:59,500
find that it trips the circuit after one second sharply, the relay will be an accurate one.

28
00:01:59,920 --> 00:02:03,190
And if it's delay, time changes from one second.
29
00:02:03,370 --> 00:02:05,600
So it will p be and not accurate one.

30
00:02:06,340 --> 00:02:12,550
Also, the third test we have is the ability to withstand the maximum current and voltage levels.

31
00:02:12,610 --> 00:02:18,130
So we need to check at the relay can withstand some large values of the current and the voltage that
32
00:02:18,130 --> 00:02:25,120
may be applied to it or the relay can't withstand them as in some cases in the circuit due to some
reasons
33
00:02:25,330 --> 00:02:27,970
the voltage and the current may increase greatly.
34
00:02:28,300 --> 00:02:34,930
So we need to be sure that the relay will withstand those failures and we perform those tests to apply
35
00:02:34,940 --> 00:02:38,080
the relay to some large values of the current and the volition.
00:02:38,470 --> 00:02:44,290
And we see if it's Coile and it's different parts can be strong enough to withstand those values are
37
00:02:44,290 --> 00:02:45,700
not very good.
38
00:02:46,270 --> 00:02:52,390
Now, the fourth test we perform is the ability of the relay context to withstand the current passing

39
00:02:52,390 --> 00:02:53,020
through it.
40
00:02:53,290 --> 00:02:58,400
And this is because of the release since current signal to the circuit breaker to break the circuit.
41
00:02:58,750 --> 00:03:04,870
So this current signal is passing through the relay contacts and we need to ensure that the relay can
42
00:03:04,870 --> 00:03:06,610
withstand this current signal.
43
00:03:06,940 --> 00:03:12,540
For example, if a fault occurs in the circuit, the current transformer will sense the fault current.
44
00:03:12,820 --> 00:03:15,420
Hence it will send a signal to the relay to tell.
45
00:03:15,460 --> 00:03:18,490
At that there is a fault in the circuit and then they relay.

46
00:03:18,510 --> 00:03:25,150
Kyle will p magnetised coil will pee magnetize and it will attract the movable contact to touch the fixed
contact hands of the
47
00:03:25,150 --> 00:03:25,480
relay.related
48
00:03:25,510 --> 00:03:31,050
Kyle will p magnetize coil will pee magnetize it and it will attract the movable contact to touch Ali, fix
fixed contact.  to touch the effects of contact
49
00:03:31,330 --> 00:03:36,010
And then as the two contacts are touching each other, these circuits will be closed.
50
00:03:36,130 --> 00:03:37,710
Hence there will be a current Path passing
 

51
00:03:37,710 --> 00:03:40,420
from the first contact to the second contact.
Tiếp điểm thứ nhất sang tiếp điểm thứ hai
52
00:03:40,840 --> 00:03:43,720
And this current will go forward to the circuit breaker.
53
00:03:44,050 --> 00:03:49,780
So this current value may be a standard value of five amperes and it will less last and the circuit for a

54
00:03:49,780 --> 00:03:52,120
time of about two hundred seconds.
55
00:03:52,420 --> 00:03:58,060
So we need to ensure that the really contacts can withstand their current value for this specific time

56
00:03:58,240 --> 00:04:00,400
that the current will less and the circuit.
57
00:04:00,970 --> 00:04:01,510
All right.
58
00:04:02,050 --> 00:04:05,560
Also, the fifth test we have as the power supply test.

59
00:04:05,770 --> 00:04:11,290
And at that test, we need to ensure that, B, power supply that is feeding the relay coil is working
60
00:04:11,290 --> 00:04:14,440
well, and B, different cases, for example, of the system.

61
00:04:14,440 --> 00:04:18,520
Voltage changes from 110 volts till 220 volts.
62
00:04:18,730 --> 00:04:21,680
Here, we need to check that B power supply is acting.
63
00:04:21,730 --> 00:04:24,700
Well, PI feeding the circuit with the require power.
64
00:04:25,330 --> 00:04:25,890
All right.
65
00:04:26,080 --> 00:04:33,040
Now, the next test we have for the digital over current relays is the setting limit test and be sitting
66
00:04:33,040 --> 00:04:38,890
limit test as the test at which we check that the limits of the current value at which the relay will

67
00:04:38,890 --> 00:04:39,280
work.
68
00:04:39,520 --> 00:04:45,490
So we have some limits of the prompters of the relay like the current, and we need to check those limits
69
00:04:45,550 --> 00:04:46,480
and test them.

70
00:04:46,870 --> 00:04:51,820
And after that, the next test is the effect of the end of the current on the relay.
71
00:04:52,090 --> 00:04:56,800
So we need to check at the Indra's current can harm the relay or damage it or not.

72
00:04:57,160 --> 00:05:00,170
As of the over current relay must withstand the errors.
73
00:05:00,600 --> 00:05:02,200
Through its working operation.
74
00:05:02,460 --> 00:05:06,600
And for that, we check the relate behavior during the Endris current effect.
75
00:05:07,200 --> 00:05:12,820
And after that, the next test we have is the effect of the electromagnetic field on the over cannot
76
00:05:12,820 --> 00:05:13,300
really.

77
00:05:13,650 --> 00:05:17,910
As if there is any electromagnetic field which surrounds the over current relay.
78
00:05:18,090 --> 00:05:22,250
It may affect the relay readings or it may make the relay to work wrongly.
79
00:05:22,500 --> 00:05:26,350
And for that, we just the relay, Abby, surrounding electromagnetic field.

80
00:05:26,520 --> 00:05:28,290
To know if it works well or not.

81
00:05:28,650 --> 00:05:33,090
And after that, the ninth test we have is the man machine interface test.
82
00:05:33,420 --> 00:05:39,780
And the man machine interface test is a test that specifies of the degree of ease pie, which the man 

83
00:05:39,780 --> 00:05:42,390
can handle the interface of the digital relay.

84
00:05:42,600 --> 00:05:48,090
And this means we need to measure how it's easy for the user to handle the interface of the digital

85
00:05:48,090 --> 00:05:53,940
relay as they relate may have a complex interface with many parameters that is hard for the user to
86
00:05:53,940 --> 00:05:56,490
handle during the operation of the relay.

87
00:05:56,820 --> 00:05:59,130
So that's for the man machine interface test.

88
00:05:59,460 --> 00:06:04,860
And finally, the final test we have is of the ability of the relate to store the different events and

89
00:06:04,860 --> 00:06:10,890
the network and the events in the electrical network are some actions that happens during the working

90
00:06:10,890 --> 00:06:12,630
operation of the electrical power.

91
00:06:12,840 --> 00:06:18,480
For example, opening the circuit breaker or closing the circuit breaker or tripping the relays, or,
92
00:06:18,480 --> 00:06:23,340
for example, resetting the relays or any fault that may happen and the network.

93
00:06:23,520 --> 00:06:26,120
So all of those are considered to piece some events.

94
00:06:26,190 --> 00:06:31,830
And the network and for those events happening at the network, we need to be sure that the digital

95
00:06:31,830 --> 00:06:34,050
relay will save them or restore them.

96
00:06:34,080 --> 00:06:40,500
And the relay memory, as we will use those events while analyzing the performance of the network or

97
00:06:40,500 --> 00:06:42,930
for the relate to track the next actions.

98
00:06:43,410 --> 00:06:48,990
So we need to perform that test to check at the relay, can store the different events which happens

99
00:06:49,020 --> 00:06:51,840
in the network or not more than great.

100
00:06:51,930 --> 00:06:57,320
So that's a part of this tutorial at which we took an overview on the digital relay required tests.

101
00:06:57,600 --> 00:06:59,010
How that's likely right now.

102
00:06:59,070 --> 00:07:01,170
Thank you for watching and see your next materials.

You might also like