Fpa101249 BR (B) 001-003

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

LINEAR SCALE 1:50 & 1:100

1:100 0 1 2 3 4 5 6 7 8 9 10m
1:50 0 1 2 3 4 5m
10m
5m
9
8
4

Single ply membrane roofing providing aa fire


rating for surface spread of flame with a current
Continuous ridge vent BBA or WIMLAS Certificate and laid to
7

specialist specification Tiles hung vertically


on 25mm x 38mm
preservative treated
6
3

battens

BUILDING REGULATIONS NOTES


5

PLANNING NOTE
Velux window It is recommended that the Agent contact the local planning authority for advice on all
4
2

780x1400 GGL matters concerning permitted development.


M08 (308)
9mm Supalux Promat cement A loft conversion for your house is considered to be permitted development and not
3

particular boards ( for half hour fire Code 5 lead soakers requiring an application for planning permission, subject to the following limits and
dressed to existing
Velux window Velux window Velux window resistance ) - for walls which are conditions:
roof tiles&behind
780x1400 GGL 780x1400 GGL 780x1400 GGL within 1000mm of boundary, set to new dormer tiles • Materials must be similar in appearance to the existing house.
2
1

M08 (308) M08 (308) M08 (308) framing. • Volume of enlargement (including any previous enlargement) must not exceed
the original roof space by more than:
40 cubic metres for terraced houses; or
1

50 cubic metres otherwise.


Dormer to be set in by more than 200mm • Must not exceed the height of the existing roof.
Roof lights will not project more than • On the principal elevation of the house (where it fronts a highway), must not
1:100 0
0

150mm. Dormer face and cheek will be extend beyond the existing roof slope.
LINEAR SCALE 1:50 & 1:100

• Must not include:


tile to match existing.
1:50

verandas, balconies* or raised platforms; or


ROOF LIGHTS installation, alteration or replacement of any chimney, flue, or ‘soil and vent
Vent Min U-value of 1.6 W/m²K. pipe’.
EXISTING FRONT ELEVATION Roof-lights to be double glazed • Side-facing windows must be obscure-glazed; and, if opening, to be 1.7 metres
above the floor of the room in which they are installed.
with16mm argon gap and soft low-E
• Construction must ensure that:
(scale 1:100) glass. Window Energy Rating to be Band
C or better. Roof lights to be fitted in
1. The eaves of the original roof are maintained (or reinstated)
2. Any enlargement is set back, so far as practicable, at least 20cm from the original
accordance with manufacturer's eaves
instructions with rafters doubled up to 3. The roof enlargement does not overhang the outer face of the wall of the original
sides and suitable flashings etc. house

With the exceptions that:


Points 1 and 2 do not apply to the relevant parts of any hip-to-gable enlargement
None of these three points apply to the relevant parts of any enlargement that
joins the original roof to the roof of a side or rear extension.

(Ref - https://www.planningportal.co.uk)

PARTY WALL ACT


The owner should they need to do so under the requirements of the Party Wall Act 1996
has a duty to serve a Party Structure Notice on any adjoining owner if the building work
involves works on or to an existing Party Wall including:
• Support of beam
• Insertion of DPC through wall
• Raising of wall or cutting of projections
• Demolition and rebuilding
• Underpinning
• Insertion of lead flashings
• Excavations within 3 metres of an existing structure where the new foundations
will go deeper than adjoining foundations, or within 6 metres of an existing structure
where the new foundations are within a 45 degree line of the adjoining foundations.
A Party wall agreement is to be in place prior to start of works on site.

THERMAL BRIDGING
Care shall be taken to limit the occurrence of thermal bridging in the insulation layers
caused by gaps within the thermal element, (i.e. around windows and door openings).
PROPOSED FRONT ELEVATION PROPOSED SIDE ELEVATION MATERIALS AND WORKMANSHIP
All works are to be carried out in a workmanlike manner. All materials and
(scale 1:50) (scale 1:50) workmanship must comply with Regulation 7 of the Building Regulations, all relevant
British Standards, European Standards, Agreement Certificates, Product Certification of
Schemes (Kite Marks) etc. Products conforming to a European technical standard or
harmonised European product should have a CE marking.
EXISTING REAR ELEVATION EXISTING STRUCTURE
Existing structure including foundations, floor, beams, walls, roof and lintels are to be
(scale 1:100) exposed and checked for adequacy prior to commencement of work and as required by
the Building Control Officer.

BEAMS AND STRUCTURE


Engineer's Structural calculations and details are to be provided for all beams, roof,
lintels, joists, bearings, padstones and any other load bearing elements before works
commence on site. New steel beams to be encased in 12.5mm Gyproc FireLine board
Single ply membrane roofing providing aa fire Single ply membrane roofing providing aa fire with staggered joints, Gyproc FireCase or painted in Nullifire S or similar intumescent
rating for surface spread of flame with a current rating for surface spread of flame with a current paint to provide 1/2 hour fire resistance as agreed with Building Control. All fire
BBA or WIMLAS Certificate and laid to BBA or WIMLAS Certificate and laid to protection to be installed as detailed by specialist manufacturer.
specialist specification specialist specification
Tiles hung vertically DORMER CONSTRUCTION
on 25mm x 38mm To achieve minimum U Value of 0.18 W/m²K
preservative treated Structure to engineer's details and calculations. Tiles hung vertically on 25 x 38mm
battens preservative treated battens (vertical counter battens to be provided to ensure vented and
drained cavity if required) fixed to breathable membrane (having a vapour resistance of
not more than 0.6 MNs/g) and 12mm thick W.B.P external quality plywood sheathing
(or other approved). Ply fixed to treated timber frame studs constructed using: 100mm x
Code 5 lead soakers Code 5 lead soakers 50mm head and sole plates and vertical studs (with noggins) at 400mm centres or to
dressed to existing dressed to existing Velux window structural engineer's details and calculations. Insulation to be 90mm Celotex GA4000
roof tiles&behind roof tiles&behind 780x1400 GGL between studs with 50mm Celotex GA4000 over. Provide vcl and 12.5mm plasterboard
new dormer tiles new dormer tiles M08 (308) over internal face of insulation. Finish with 3mm skim coat of finishing plaster.
All junctions to have water tight construction, seal all perimeter joints with tape
Code 5 lead soakers internally and with silicon sealant externally. Dormer walls built off existing masonry
New rwp dressed to existing walls to have galvanised mild steel straps placed at 900 centres. Dormer cheeks within
roof tiles&behind 9mm Supalux Promat cement 1m of the boundary to be lined externally with 12.5mm Supalux and 12.5mm Gyproc
new dormer tiles particular boards ( for half hour fire FireLine board internally to achieve 1/2 hour fire resistance from both sides.
Tiles hung vertically Dormer side to have resistance ) - for walls which are
on 25mm x 38mm 1/2h fire protection within 1000mm of boundary, set to WARM FLAT DORMER ROOF
preservative treated framing. (imposed load max 1.0 kN/m² - dead load max 0.75 kN/m²)
battens To achieve U value 0.15 W/m²K
To Structural Engineer's details. Flat roof to be single ply membrane roofing providing
aa fire rating for surface spread of flame with a current BBA or WIMLAS Certificate
Dormer to be set in by more than 200mm and laid to specialist specification. Single ply membrane to be fixed to 18mm exterior
Roof lights will not project more than quality plywood (if required by manufacturer) over 150mm Celotex XR4000 insulation.
ROOF LIGHTS Insulation bonded to 18mm external quality plywood decking or similar approved on sw
150mm. Dormer face and cheek will be
firings to minimum 1 in 80 fall on sw treated 47 x 170mm flat roof C24 timber joists at
Min U-value of 1.6 W/m²K. tile to match existing.
400mm c/cs or as Structural Engineer's details and calculations. Underside of joists to
EXISTING SIDE ELEVATION Roof-lights to be double glazed
with16mm argon gap and soft low-E
have 12.5mm foil backed plasterboard and skim.
Provide restraint to flat roof by fixing of 30 x 5 x 1000mm ms galvanised lateral
glass. Window Energy Rating to be Band
(scale 1:100) C or better. Roof lights to be fitted in
restraint straps at maximum 2000mm centres fixed to 100 x 50mm wall plates and
anchored to wall.
accordance with manufacturer's THIS IS A GENERAL GUIDE BASED ON NORMAL LOADING CONDITIONS
instructions with rafters doubled up to FOUND IN DOMESTIC CONSTRUCTION. IT IS YOUR RESPONSIBILITY TO
sides and suitable flashings etc. ASSESS YOUR DESIGN TO ASCERTAIN WHETHER ENGINEER'S
DETAILS/CALCULATIONS ARE REQUIRED. PLEASE REFER TO THE TRADA
DOCUMENT – 'SPAN TABLES FOR SOLID TIMBER MEMBERS IN FLOORS,
CEILINGS AND ROOFS FOR DWELLINGS' OR ASK YOUR BUILDING
CONTROL OFFICER FOR ADVICE.

13 Hendre Road,
Llangennech,
Llanelli,

ADDRESS
SA14 8TE

LOFT CONVERSION

PROJECT
PROPOSED REAR ELEVATION PROPOSED ADJ. SIDE ELEVATION

DWG NO
As shown FPA101249 01 B

SCALE

PAGE

REV
(scale 1:50) (scale 1:50)
K. Miller March-2023

DRAWN
EXISTING ADJ. SIDE ELEVATION

DATE
(scale 1:100)
These drawings are produced to obtain planning and
building regulations approval only and copywrite of
the designer, all dimension to be checked on site.
LINEAR SCALE 1:50 & 1:100
1:100 0 1 2 3 4 5 6 7 8 9 10m
1:50 0 1 2 3 4 5m
10m
5m
9
8
4
7

UTILITY
Up Up
6
3

LEAD WORK AND FLASHINGS


5

Down All lead flashings, any valleys or soakers to be Code 5 lead and laid according to Lead
Existing rafters Development Association. Flashings to be provided to all jambs and below window
WR New dormer roof openings with welded upstands. Joints to be lapped min 150mm and lead to be dressed
4
2

CPB 200mm under tiles, etc. All work to be undertaken in accordance with the Lead
Ex. purlin Development Association recommendations.
DINING ROOM KITCHEN CPB
3

BEDROOM STUD ASHLAR/DWARF WALL

King post rafter

King post rafter


BATHROOM To achieve minimum U Value of 0.28 W/m²K
Ex. purlin Construct stud wall using 100mm x 50mm head and sole plates and vertical studs (with
2
1

noggins) at 400mm centres or to structural engineer's details and calculations. Insulation


between and over studs; 60mm Celotex GA4000 between plus 37.5mm Celotex PL4000
Ridge Ridge insulated plasterboard with VCL.
1

Up WR Finish with 3mm skim coat of finishing plaster. All junctions to have water tight
LANDING Ridge construction, seal all perimeter joints with tape internally and with silicon sealant
externally.
1:100 0
0

Ex. purlin
LINEAR SCALE 1:50 & 1:100

UPGRADING SOLID GABLE WALL (cold adjoining space)


WR
1:50

The existing walls must be checked for stability and be free from defects as required by
HALL the Building Control Officer. Provide a scratch coat render to existing wall. Insulate
LOUNGE SITTING ROOM wall on the warm side using Multifoil insulation installed as per manufacturer's details.
BEDROOM BEDROOM Ex. purlin All work in accordance with BS 8212 (Code of practice for dry lining).

UPGRADE OF PITCHED ROOF


Existing ceiling joists (imposed load max 0.75 kN/m² - dead load max 0.75 kN/m²)
WR
Vented roof – pitch 22-45°
To achieve U-value 0.16 W/m²K
Existing roof structure to be assessed by a structural engineer and any alterations to be
carried out in strict accordance with structural engineer’s details and calculations which
Up must be approved by building control before works commence on site. The existing roof
condition must be checked and be free from defects as required by the Building Control
Officer any defective coverings or felt to be replaced in accordance with manufacturer’s
details.
EXISTING GROUND FLOOR PLAN EXISTING FIRST FLOOR PLAN EXISTING ATTIC FLOOR PLAN EXISTING ROOF PLAN PROPOSED ROOF PLAN Multifoil insulation installed as per manufacturer's details.
(Cavity of 25mm provided by fixing battens between plasterboard and under rafter
(scale 1:100) (scale 1:100) (scale 1:100) (scale 1:100) (scale 1:100) insulation recommended where insulation under rafters exceeds 50mm).
Maintain a 50mm air gap above insulation to ventilate roof. Provide opening at eaves
level at least equal to continuous strip 25mm wide and opening at ridge equal to
continuous strip 5mm wide to promote ventilation or provide equivalent high and low
level tile vents in accordance with manufacturer's details.

UPGRADE OF EXISTING FLOORS


Ensure first floor achieves modified half-hour fire resistance.
New second floor –22mm T&G flooring grade chipboard ( V313 grade water resistant
to new bathroom) to 170x47mm C24 at 400 c/c. Doubled trimmers to floor and for stair
opening to be 170x47mm C24 as per floor plan. Floor joists doubled below all new stud
partitions as per plan. Provide for mid span herringbone strutting as per floor plan.
Provide for Chickenwire mesh laid over the existing ceiling joist with 100mm
Rockwool flexislab (for half hour fire protection to the existing ceiling ) set between at
400 c/c carried to eaves voids where it is to be overlaid with 175mm Rockwool quilt
insulation. To give a total thicknes to unheated voids of 275 mm.

INTERNAL STUD PARTITIONS


100mm x 50mm softwood treated timbers studs at 400mm cts with 50 x 100mm head
Supply and install new structural and sole plates and solid intermediate horizontal noggins at 1/3 height or 450mm c/cs.
elements such as new beams, roof Existing structure including Provide min 10kg/m³ density acoustic soundproof quilt tightly packed (eg. 100mm
structure, floor structure, bearings, beams, walls and lintels carrying Rockwool or Isowool mineral fibre sound insulation) in all voids the full depth of the
and padstones in accordance with the new and altered loads are to be ROOF LIGHTS stud. Partitions built off doubled up joists where partitions run parallel or provide
Structural Engineer's calculations and exposed and checked for Min U-value of 1.6 W/m²K. noggins where at right angles. Walls faced throughout with 12.5mm plaster board with
details. New steel beams to be adequacy prior to Roof-lights to be double glazed skim plaster finish. Taped and jointed complete with beads and stops.
encased in 12.5mm Gyproc fireline commencement of work and as with16mm argon gap and soft low-E
board with staggered joints nailed to required by the Building Control ALL PARTITIONS glass. Window Energy Rating to be Band NEW STAIRCASE
timber cradles or painted in Nullifire S Officer. ENCLOSING THE STAIRS IS C or better. Roof lights to be fitted in Dimensions to be checked and measured on site prior to fabrication of stairs. Timber
UTILITY
or similar intumescent paint to provide TO HAVE 30 MINUTES FIRE accordance with manufacturer's stairs to comply with BS585 and with Part K of the Building Regulations. Max rise
1/2 hour fire resistance. RESISTANCE INCLUDING instructions with rafters doubled up to 220mm, min going 220mm. Two risers plus one going should be between 550 and
Up 700mm. Tapered treads to have going in centre of tread at least the same as the going on
Up GLAZING sides and suitable flashings etc.
the straight. Min 50mm going of tapered treads measured at narrow end. Pitch not to
Check ex. lintel Check ex. lintel exceed 42 degrees. The width and length of every landing should be at least as great as
the smallest width of the flight. Doors which swing across a landing at the bottom of a
flight should leave a clear space of at least 400mm across the full width of the flight.
Min 2.0m headroom measured vertically above pitch line of stairs and landings.
Check ex. lintel Check ex. lintel Check ex. lintel Check ex. lintel However, if there is not enough space to achieve this height the headroom will be
satisfactory if the height measured at the centre of the stair width is l.9 m reducing to
Insulation to be 90mm Loadbearing stud 1.8m at one side of the stair. Handrail on staircase to be 900mm above the pitchline,
FD 20 FD 20
Down of Celotex GA4000 handrail to be at least one side if stairs are less than 1m wide and on both sides if they
between studs and are wider. Ensure a clear width between handrails of minimum 600mm. Balustrading
50mm Celotex designed to be unclimbable and should contain no space through which a 100mm sphere
WR Dormer side to have GA4000 over studs SD could pass. Allow for all structure as designed by a Structural Engineer.
FD 20
1/2h fire protection with VLC.
ELECTRICAL WORKS
CPB All electrical work required to meet the requirements of Part P (electrical safety) must
Multifoil insulation installed be designed, installed, inspected and tested by a competent person registered under a
SD KITCHEN BEDROOM as per manufacturer's details competent person self certification scheme such as BRE certification Ltd, BSI, NICEIC
DINING ROOM CPB
Down Certification Services or Zurich Ltd. An appropriate BS7671 Electrical Installation
BEDROOM Certificate is to be issued for the work by a person competent to do so. A copy of a
EXTRACT SHOWER ROOM Multifoil insulation installed
certificate will be given to the Council.
Shower room to have as per manufacturer's details
mechanical vent ducted to INTERNAL LIGHTING
SD BATHROOM external air to provide min 15 Install low energy light fittings that only take lamps having a luminous efficiency better
litres / sec extraction. Vent to be FD 20
Ridge beam to BEDROOM than 80 lumens per circuit watt. All fixed to have lighting capacity (lm) 185 x total
connected to light switch and to structural engineer detail floor area, to comply with Part L of the current Building Regulations and the Domestic
have 15 minute over run if no Building Services Compliance Guide.
FD 20 window in room. Internal doors LANDING
should be provided with a HEATING
10mm gap below the door to Extend all heating and hot water services from existing and provide new TRVs to
LANDING radiators. Heating system to be designed, installed, tested and fully certified by a GAS
aid air circulation. Ventilation
Ridge beam to SAFE registered specialist. All work to be in accordance with the Local Water
provision in accordance with structural engineer detail
Up the Domestic Ventilation Authorities by laws, Gas safety requirements and IEEE regulations.
WR Compliance Guide. Intermittent FD 20
FD 20 Up NEW GAS BOILER
ALL PARTITIONS FD 20 extract fans to BS EN 13141-4.
All fixed mechanical ventilation Wastes from Shower to Heating and hot water will be supplied via a wall mounted condensing vertical balanced
ENCLOSING THE STAIRS IS flue pressurised boiler with a minimum efficiency of 91% (as defined in ErP(1))
TO HAVE 30 MINUTES FIRE systems, where they can be be connected to ex. svp
The energy performance of the new components to be assessed. The results should be
RESISTANCE INCLUDING tested and adjusted, shall be
FD 20 recorded and given to the building owner.
GLAZING FD 20 commissioned and a SITTING ROOM All accessible pipes to be insulated to the standards in Table 4.4 Approved Document L.
commissioning notice given to
All parts of the system including pipework and emitters to be sized to allow the space
the Building Control Body. heating system to operate effectively and in a manner that meets the heating needs of the
ALL PARTITIONS SHOWER ROOM
WR Velux window dwelling, at a maximum flow temperature of 55°C or lower.
ENCLOSING THE STAIRS IS Velux window
HALL 780x1400 GGL
TO HAVE 30 MINUTES FIRE 780x1400 GGL
M08 (308)
RESISTANCE INCLUDING Velux window M08 (308)
GLAZING 780x1400 GGL
M08 (308)
LOUNGE
SD SITTING ROOM
BEDROOM
BEDROOM

Access hatch
Insulation between and over studs: 60mm
Celotex GA4000 between plus 37.5mm insulated Loadbearing stud 13 Hendre Road,
WR
Celotex PL4000 insulated plaster board
over VOID Llangennech,
Llanelli,

ADDRESS
SA14 8TE

Up

LOFT CONVERSION

PROJECT
PROPOSED GROUND FLOOR PLAN PROPOSED FIRST FLOOR PLAN PROPOSED ATTIC FLOOR PLAN

DWG NO
As shown FPA101249 02 B

SCALE

PAGE
(scale 1:50) (scale 1:50) (scale 1:50)

REV
K. Miller March-2023

DRAWN

DATE
These drawings are produced to obtain planning and
building regulations approval only and copywrite of
the designer, all dimension to be checked on site.
LINEAR SCALE 1:50 & 1:100
1:100 0 1 2 3 4 5 6 7 8 9 10m
1:50 0 1 2 3 4 5m
10m
5m
9
8
4

Supply and install new structural


elements such as new beams, roof
7

Single ply membrane roofing providing aa fire


structure, floor structure, bearings, rating for surface spread of flame with a current
and padstones in accordance with BBA or WIMLAS Certificate and laid to
the Structural Engineer's
6
3

specialist specification
calculations and details. New steel 150mm Celotex XR4000 insulation
beams to be encased in 12.5mm Multifoil insulation installed
Gyproc fireline board with staggered No combustible materials within 50mm of the flue. Rooms to be fitted with thermostatic
5

as per manufacturer's details


Main bearer steel beam Flat roof joists radiator valves and all necessary zone controls and boiler control interlocks. The system
joints nailed to timber cradles or
painted in Nullifire S or similar spliced at 1/3rds splice 170x47 C24 at 400c/c will be installed, commissioned and tested by a GAS SAFE Registered Specialist and a
detail as per engineers Velux window certificate issued that the installation complies with the requirements of PART L. All
intumescent paint to provide 1/2
4
2

drawing / calculations 780x1400 GGL work to be in accordance with the Local Water Authorities bye laws, the Gas Safety
hour fire resistance.
M08 (308) (Installation and Use) Regulations 1998 and IEE Regulations.
Gas-fired combination boilers installed in existing dwellings, to have at least one of the
3

following
18mm plywood Ridge beam to structural Ex. purlin energy efficiency measures, appropriate to the system:
Insulation to be 90mm of Celotex engineer detail
2
1

GA4000 between studs and a. Flue gas heat recovery.


100x47 C16 b. Weather compensation.
50mm Celotex GA4000 over Insulation between and
Ex. purlin for restraint to rafter feet c. Load compensation.
studs with VLC. over studs: 60mm
bolted with either M8 bolts
1

Celotex GA4000 d. Smart thermostat with automation and optimisation.


Rockwool or toothed plate connectors
flexislab 100 mm between plus 37.5mm
MEANS OF ESCAPE - Fire doors
Strutting on chickenwire Celotex PL4000
1:100 0
0

Form a protected escape stairway by providing half hour fire resistance to all partitions
insulated plaster board
LINEAR SCALE 1:50 & 1:100

as well as floors and ceilings above and below rooms. Stairway to be protected at all
over
1:50

levels - from the loft room/rooms then leading directly to an external door at ground level
(no inner rooms allowed). All doors on to the stairway must be FD20 rated fire doors to
BS 476-22:1987 or the European equivalent BS EN 1634 (fitted with intumescent strips
rebated around sides & top of door or frame if required by BCO). Where applicable, any
Floor joists
glazing in fire doors to be half hour fire resisting and glazing in the walls forming the
170x47 C24 escape route enclosure to have 30 minutes fire resistance and be at least 1.1m above the
at 400 c/c floor level or stair pitch line.
Floor joists ROOF LIGHTS Insulation
170x47 C24 Min U-value of 1.6 W/m²K. 175 mm
Strutting Strutting Roof-lights to be double glazed 220mm - min. go SMOKE DETECTION
at 400 c/c
Stair trimmers

Insulation 220mm - max. rise Mains operated linked smoke alarm detection system to BS EN 14604 and BS
with16mm argon gap and soft low-E Sound insulation 100 mm 5839-6:2019 to at least a Grade D category LD3 standard to be mains powered with
glass. Window Energy Rating to be Band 100 mm
Ex. ceiling joists battery back up to be placed on each storey with an additional interlinked heat detector at
C or better. Roof lights to be fitted in
50mm minimum tread ceiling level in kitchens if required by BCO. Smoke alarms should be sited so that there
accordance with manufacturer's
on stair winders is a smoke alarm in the circulation space on all levels/ storeys and within 7.5m of the
instructions with rafters doubled up to door to every habitable room. If ceiling mounted they should be 300mm from the walls
Ridge beam to structural sides and suitable flashings etc.
1/2 HR Fire and light fittings. Where the kitchen area is not separated from the stairway or circulation
engineer detail
protection space by a door, there should be an interlinked heat detector in the kitchen.
to u/s stairs
BACKGROUND VENTILATION
STAIR DETAIL Controllable background ventilation at least 1700mm above floor level to be provided to
habitable rooms and kitchens at a rate of min 10,000mm², and to wet rooms at a rate of
scale 1:20 min 5000mm²,
Background ventilators to be tested to BS EN 13141-1
Background ventilator equivalent area and operation to be measured and recorded.

Floor joists PURGE VENTILATION


170x47 C24 Supply and install new structural elements such Minimum total area of opening in accordance with Table 1.4 Approved Document F1.
at 400 c/c Hinged pivot windows with an opening angle of 15 to 30 degrees to have an openable
as new beams, roof structure, floor structure,
bearings, and padstones in accordance with the area in excess 1/10 of the floor area of the room.
Structural Engineer's calculations and details. Sash windows, external doors or hinged pivot windows with an opening angle of equal
to or greater than 30 degrees to have an openable area in excess of 1/20 of the floor area
New steel beams to be encased in 12.5mm
1/2 HR Fire of the room.
Gyproc fireline board with staggered joints
protection Purge ventilation should be capable of extracting at least 4 air changes per hour per room
nailed to timber cradles or painted in Nullifire S directly to the outside.
to u/s stairs or similar intumescent paint to provide 1/2 hour Internal doors should be provided with a 10mm gap below the door to aid air circulation
fire resistance.
EXTRACT FOR SHOWER ROOM
Provide mechanical extract ventilation to Shower room ducted to external air capable of
extracting at a rate of not less than 15 litres per second. Vent to be connected to light
switch and to have 15 minute over run if no window in the room. Internal doors should
be provided with a 10mm gap below the door to aid air circulation. Ventilation provision
Existing tie beam to be re-inforced Existing tie beam to be re-inforced in accordance with the Domestic Ventilation Compliance Guide. Intermittent extract fans
with steel channels both sides with steel channels both sides to BS EN 13141-4. All fixed mechanical ventilation systems, where they can be tested
TYPICAL SECTION and adjusted, shall be commissioned and a commissioning notice given to the Building
Control Body.
(scale 1:50) RAINWATER DRAINAGE
New rainwater goods to be new 110mm upvc half round gutters taken to and connected
into 68mm dia upvc downpipes

ABOVE GROUND DRAINAGE


All new above ground drainage and plumbing to comply with BS EN 12056-2:2000 for
sanitary pipework. All drainage to be in accordance with part H of the Building
Regulations. Wastes to have 75mm deep anti vac bottle traps and rodding eyes to be
provided at changes of direction.

Size of wastes pipes and max length of branch connections (if max length is exceeded
STEELWORK AND JOISTS LAYOUT then anti vacuum traps to be used)
Wash basin - 1.7m for 32mm pipe 3m for 40mm pipe
(scale 1:50) Bath/shower - 3m for 40mm pipe 4m for 50mm pipe
W/c - 6m for 100mm pipe for single WC
All branch pipes to connect to 110mm soil and vent pipe terminating min 900mm above
any openings within 3m.
Or to 110mm upvc soil pipe with accessible internal air admittance valve complying with
BS EN 12380, placed at a height so that the outlet is above the trap of the highest fitting.
Waste pipes not to connect within 200mm of the WC connection. Supply hot and cold
water to all fittings as appropriate.

ROOF LIGHTS
Min U-value of 1.6 W/m²K.
Roof-lights to be double glazed with 16mm argon gap and soft low-E glass. Window
Energy Rating to be Band C or better. Roof lights to be fitted in accordance with
U-value 0.15 W/m²K manufacturer's instructions with rafters doubled up to sides and suitable flashings etc.
Flat roof to be single ply membrane roofing with aa SAFETY GLAZING
fire rating laid as specialist specification with a All glazing in critical locations to be toughened or laminated safety glass to BS 6206, BS
current BBA or WIMLAS Certificate (on 18mm EN 14179 or BS EN ISO 12543-1:2011 and Part K (Part N in Wales) of the current
U-value 0.18 W/m²K building regulations. i.e. within 1500mm above floor level in doors and side panels
plywood if required)
within 300mm of door opening and within 800mm above floor level in windows.

Treated timber frame constructed using 150mm Celotex XR4000 insulation NEW AND REPLACEMENT WINDOWS
New and replacement windows to be double glazed with 16-20mm argon gap and soft
100mm x 50mm head & sole plates and Tiles hung vertically on 25mm x 38mm Treated timber frame constructed using Provide min10kg/m³ density
coat low-E glass. Window Energy Rating to be Band B or better and to achieve U-value
vertical studs preservative treated battens acoustic soundproof quilt tightly Vapour control layer
100mm x 50mm head & sole plates and of 1.4 W/m²K. The door and window openings should be limited to 25% of the extension
packed (e.g. 100mm Rockwool or floor area plus the area of any existing openings covered by the extension.
vertical studs Isowool mineral fibre sound
18mm external quality plywood decking or similar Insulated plasterboard to be used in reveals to abut jambs and to be considered within
insulation) reveal soffits. Fully insulated and continuous cavity closers to be used around reveals.
approved on sw firings to minimum 1 in 80 fall Windows and door frames to be taped to surrounding openings using air sealing tape.
Lined with 12.5mm Gyproc
FireLine board with skim NEW AND REPLACEMENT DOORS
Insulation between and over studs: 60mm External quality plywood sheathing - 12mm thick plaster finisheach side 50mm x 100mm timber stud New and replacement doors to achieve a U-Value of 1.4W/m²K. Glazed areas to be
Insulation to be 90mm of Celotex GA4000
Celotex GA4000 between plus 37.5mm marine plywood (or other approved) (at 400mm centres) double glazed with 16-20mm argon gap and soft low-E glass. Glass to be toughened or
between studs and 50mm Celotex GA4000 laminated safety glass to BS 6206, BS EN 14179 or BS EN ISO 12543-1 and Part K
Celotex PL4000 insulated plaster board
over studs with VLC. (Part N in Wales) of the current Building Regulations.
over Insulated plasterboard to be used in reveals to abut jambs and to be considered within
reveal soffits. Fully insulated and continuous cavity closers to be used around reveals.
Windows and door frames to be taped to surrounding openings using air sealing tape.

12.5mm plasterboard over studs finished with


Breathable membrane - having a vapour
3mm skim coat of finishing plaster
Finish with 3mm plaster skim resistance of not more than 0.6 MNs/g

13 Hendre Road,
DETAIL -
Ceilings of 12.5mm plasterboard over vapour
barrier with skim plaster finish.
Llangennech,
INTERNAL STUD WALL 47 x 170mm grade C24 joists at 400mm ctrs
Llanelli,

ADDRESS
scale 1:10 SA14 8TE
DETAIL - DETAIL - DETAIL -
ASHLAR/DWARF WALLS DORMER WALL DORMER FLAT ROOF
scale 1:10
scale 1:10 LOFT CONVERSION

PROJECT
scale 1:10

DWG NO
As shown FPA101249 03 B

SCALE

PAGE

REV
K. Miller March-2023

DRAWN

DATE
These drawings are produced to obtain planning and
building regulations approval only and copywrite of
the designer, all dimension to be checked on site.

You might also like