Professional Documents
Culture Documents
2015 - EE5102 - Distribution Systems
2015 - EE5102 - Distribution Systems
Faculty of Engineering
Department of Electrical Engineering
INSTRUCTIONS TO CANDIDATES
The examination accounts for 70% of the module assessment. The total mark attainable is
70. The marks assigned for each question and sections thereof are indicated in square
brackets.
Assume reasonable values for any essential data not given in or with the examination
paper. Clearly state such assumptions made on the scripts.
If you have any doubts to the interpretation of the wording of a question, make your own
decision, but clearly state it on the script.
Page 1 of 8
----This Page is intentionally left blank----
Page 2 of 8
Q1.
Two transformers, T1 and T2 are connected to a single feeder. As shown in Fig. Q1, T1 is serving
four customers and T2 is serving 2 customers.
Fig. Q1
The Table Q1 gives time intervals and kVA demands of the six customers during the peak
load period. Assume a power factor of 0.9 lagging for the customers connected to T1
transformer and a power factor of 0.95 lagging for the customers connected to T2
transformer.
(iv) Suggested transformer rating (25 kVA, 50 kVA, 75 kVA, 100 kVA, 150 kVA,
200 kVA). Explain the reasons for selecting the specified rating [3 marks]
Page 3 of 8
Q2.
a) State and draw a primary distribution feeder arrangement in which a "Network Protector" is
used. [3 marks]
b) What is the purpose of having the "Network Protector" in the feeder arrangement you
have stated in (a)? [2 marks]
c) An 11 kV feeder arrangement is shown in Fig. Q2. The line impedance is (0.5 + j0.9)
Ω/km and total length of the feeder is 18 km. The loads are star connected three-phase
loads totaling 1 MVA, 0.8 lagging power factor spaced as shown in Fig. Q2.
Fig. Q2
(i) Calculate the percentage voltage drop at the furthest end of the feeder.
[3 marks]
(ii) Calculate the percentage power loss in the feeder compared to the supplied load.
[3 marks]
(iii) Discuss whether the above percentage voltage drop is within the specified voltage
drop standards for Sri Lanka and using a phasor diagram explain how shunt
capacitors help to regulate the voltage.
[3 marks]
Q3.
a) Explain the following:
(i) Protective device coordination
(ii) Total clearing curve for a current limiting fuse
(iii) Autorecloser operation
(iv) Damage curve of an expulsion fuse [8 marks]
b) The characteristics of K and T type expulsion fuses given by the manufacturer are shown in
Fig. Q3. Maximum and minimum melting curves corresponding to one type are shown by
dotted lines and the maximum and minimum melting curves corresponding to other type are
given as solid lines.
(i) Identify the set of curves belonging to Type K and the set of curves belonging to
Type T. Indicate them on the graph (Attach page 4 into your answer script) and
explain the mathematical approach you took to determine the type of the fuse.
[4 marks]
Page 4 of 8
Fig. Q3
Page 5 of 8
Q4.
Fig. Q4
The line-to- line source voltage at Node 1 is 12.47 kV and the distribution line impedance is
(0.1 + j0.5) Ω/km. Using the forward-backward sweep method, compute the node voltages
after 2 iterations.
[14 marks]
Q5.
Let the simple radial distribution system shown in Fig. Q5 has the reliability
parameters shown in Table Q5.1 and the load point details shown in Table Q5.2.
Points t, u and v are places at which the installation of additional components is being
considered as shown in the two case studies given in Table Q5.3.
Fig. Q5
Table Q5.1
Component λ (failures/year) r (hours)
Feeder section 1 0.2 4
Feeder section 2 0.3 4
Distributor a 0.4 2
Distributor b 0.3 2
Page 6 of 8
Table Q5.2
Load point Number of customers Average energy (KWh)
A 500 3000
B 700 4000
Table Q5.3
Case study Additional components
1 An isolator at point t, solid links at points u and v
2 An isolator at point t, fuses at points u and v
Assume that all failures in feeder sections and distributors are short circuits which will
cause the main breaker at the supply point to operate, if no other primary protection
device operates. The isolation and switching time is 0.5 hours. The failure probability of
fuses is 0.1.
a) Evaluate the following reliability parameters of load points A and B for the two case
studies in Table Q5.3.
Then, discuss the values obtained for case studies 1 and 2. [1 mark]
b) Evaluate the following customer and load oriented reliability indices of load points A
and B for the case study 2 in Table Q5.3.
∑ 𝜆𝑟
𝑟 =
∑ 𝜆
𝑈 = 𝜆𝑟
Page 7 of 8
Contribution of component A to the failure rate:
Page 8 of 8