First red, orange, green, Orange flashing, then No pattern, the AFDD
then permanently green permanently green trips again right away
x1
x2
Tripping due to What is the flash sequence? See “AFDD+ trips immediately”
RCD functionality x3 (see pages 6 to 7)
x1
x4
x2
3 times repeated, 3 times repeated, 3x5times repeated, 3 times repeated, 3 times repeated,
x3 3 times repeated,
1 x flashing 2 x flashing 3 x flashing 4 x flashing 5 x flashing 6 x flashing
x6 x4
Tripping due to Tripping due to x1 Tripping due to Tripping due to mains x5Tripping due to AFDD device fault
serial arc dimmed serial arc parallel arc overvoltage overtemperature
x2
x1
x3 U > 270 V x6 Ti > 115oC
x2
x1 x3 x4
x2 Arc fault tripping x4 x5 Other trip causes
x3
x5
x6
4 x4
x6 EATON CORPORATION BR003016EN EATON CORPORATION BR003016EN 5
x5
x6
AFDD+ Application Guide
No Yes
Does the mains voltage What is the trip cause? Check LED
exceed 264 V AC? color pattern (see “Trip cause”)
Tripping due to Reconnect the AFDD+ on the load side but Either overcurrent, a short circuit (both shown
mains overvoltage disconnect each and every load or switch it off. by white middle indicator) or an earth fault
U > 270 V AC (shown by blue middle indicator) caused the
tripping of the device.
Check installation for such faults.
Does the housing temperature Is it possible to switch on the AFDD+?
of the AFDD+ exceed ~80°C?
Yes No No Yes
Tripping due to AFDD device fault Installation fault (or failure to See “Finding the faulty load”
overtemperature Please claim the defective AFDD device at your disconnect/switch off all loads) (see pages 10 to 11)
o
Ti > 115 C local wholesales office.
No Yes
No Yes
Reconnect and switch the loads back Please contact your local Eaton team for See “Finding the faulty load”
on one by one technical support. (see pages 10 to 11)
No Yes
Yes No
Yes
Yes No
There is a sporadic arc fault pattern on the
mains network