Eaton AFDD+ ​Eaton.

com

AFDD+ Arc Fault Detection


Device Application Guide

Thanks to the highly sensitive electronics of the AFDD+,


arc fault detection is now possible.
AFDD+ Application Guide

Arc Fault Detection Device - Application Guide


The technology behind the AFDD+ (Eaton‘s Arc Fault Detection Device) will help you further reduce In case the AFDD+ LED blinks (3 times, 6x ) when switched on, the device didn´t pass the self
the risk of fire. Conventional devices are unable to detect any arc faults occurring inside your check and needs to be replaced. In addition if the AFDD+ LED blinks ( ,…) or when the
electrical installation. The device permanently checks your electrical installation to identify patterns device LED is not emitting any light the device either needs replacement or further checks need to
that are characteristic of arc faults. With this application guide, Eaton intends to make it easier for
you to localize the sources of such faults. be performed.

Trip cause What is important to note when connecting the AFDD+?


The AFDD+ will only emit the signature trip-flash pattern at the first power-up following a trip event. The AFDD+ has designated connections for the line side and the load side.
If the AFDD+ is switched off and on again, the light sequence will be red, orange and permanently The line side is to be connected to the lower terminals, and the load side to the upper
green. If you want the device to display the trip cause again, hold down the test button when terminals.
switching on
the device.
Can I use the AFDD+ as a root switching device?
Troubleshooting For technical reasons, the AFDD+ cannot be used as a root switching device. Each final circuit
requires a separate AFDD+, as also stated in IEC 60364-4-42 and in IEC 60364-5-53 the 32/40 A
Arc fault due to installation / load fault: Remedy: types are intended for final circuits with high loads only
• Dirty switches Clean or replace (e.g. electrical radiators).
• Sluggish switches Replace
• Switches that emit visible and audible sparks Replace Particular type of load?
• all kinds of damaged cables Replace The AFDD+ arc fault trip cause indication can differentiate between 3 types of arcs:
• Loose pins Tighten or replace the pins Serial arc: an arc occurring on loads in general
• Bulb replacement under voltage Replace only when no voltage is present (including dimmed loads with nearly 0 % dimming)
• Old devices that are no longer in use Clean through repeated actuation Dimmer arc: an arc occurring on dimmed lamps, adjustable hand tools, ...
(the switch is already corroded) or replace Parallel arc: an arc between L and N,
Other faults: Remedy: Arc on loads with high starting currents, ...
• Overvoltage Contact your network operator
• Overtemperature Check the temperature of the
Support
distribution board and the load situation
For technical inquiries please get in contact with your local Eaton team.
FAQ
The support engineer will need the following information:
How can I check if the AFDD+ is functioning properly?
Pressing the test button will initiate a functional test of the entire AFDD unit, including the elect- General information AFDD+ information Information about the faulty
ronics and finally trips the AFDD+. The light sequence red-orange-permanently green ( ) at load
the power-up following the test indicates that the device is functioning properly. • Description of the installation • Part no. • Manufacturer
• How many AFDD units do you • MCB characteristics • Part no.
have installed?
• How many of them are • RCCB characteristics • Photos
functioning properly? (device, nameplate)
• Supplier
2 EATON CORPORATION BR003016EN EATON CORPORATION BR003016EN 3
AFDD+ Application Guide

Assembly instructions Danger Installation


Trip cause Montageanweisung Lebensgefahr Montage n
AFDD has tripped, toggle is in Instructions de montage Danger de mort Montage u
Montážní návod Nebezpečí Montáž po
the lower position Montážní návod Nebezpečenstvo Montáž iba
Montagevejledning
Instrucciones de montaje
Any interventions in the electrical
Fare
Peligro
Må kun ins
Debe ser i
Szerelési utasitás
Istruzioni di montaggio installation must be carried out
Életveszély
Pericolo di morte
Csak szak
Montaggio
The middle color indicator is: Montasjeveiledning
by qualified personnel!
Fare
Levensgevaar
Må monte
Montage a
Montage instructie
Instruções de montagem Perigo Deve ser i
Instrukcja montazu Niebezpieczenstwo Montaz tyl
Montageanvisning Varning Får endas
Asennusohjeet Vaara Asennus v
Montaj talimati Hayati Tehlike Sadece uz
White Blue Instructiuni de montaj Pericol Instalare n

Tripping due to Switch the AFDD


MCB functionality back on

What is the LED color pattern?

First red, orange, green, Orange flashing, then No pattern, the AFDD
then permanently green permanently green trips again right away
x1

x2
Tripping due to What is the flash sequence? See “AFDD+ trips immediately”
RCD functionality x3 (see pages 6 to 7)
x1
x4
x2

3 times repeated, 3 times repeated, 3x5times repeated, 3 times repeated, 3 times repeated,
x3 3 times repeated,
1 x flashing 2 x flashing 3 x flashing 4 x flashing 5 x flashing 6 x flashing
x6  x4

Tripping due to Tripping due to x1 Tripping due to Tripping due to mains x5Tripping due to AFDD device fault
serial arc dimmed serial arc parallel arc overvoltage overtemperature

x2
x1
x3 U > 270 V x6 Ti > 115oC
x2

x1 x3 x4
x2 Arc fault tripping x4 x5 Other trip causes
x3

x5
x6
4 x4
x6  EATON CORPORATION BR003016EN EATON CORPORATION BR003016EN 5
x5

x6 
AFDD+ Application Guide

Assembly instructions Danger Installation


AFDD+ trips immediately Montageanweisung Lebensgefahr Montage n
Instructions de montage Danger de mort Montage u
Montážní návod Nebezpečí Montáž po
Montážní návod Nebezpečenstvo Montáž iba
Disconnect both poles at the load side of the
Montagevejledning Any interventions in the electrical
Fare Må kun ins
Instrucciones de montaje Peligro Debe ser i
AFDD+ Szerelési utasitás
installation must be carried out
Életveszély Csak szak
Istruzioni di montaggio Pericolo di morte Montaggio
Montasjeveiledning
Montage instructie by qualified personnel!
Fare
Levensgevaar
Må monte
Montage a
Instruções de montagem Perigo Deve ser i
Is it possible to switch on the AFDD+? Instrukcja montazu Niebezpieczenstwo Montaz tyl
Montageanvisning Varning Får endas
Asennusohjeet Vaara Asennus v
Montaj talimati Hayati Tehlike Sadece uz
Instructiuni de montaj Pericol Instalare n

No Yes

Does the mains voltage What is the trip cause? Check LED
exceed 264 V AC? color pattern (see “Trip cause”)

Yes No Tripping due to arc Other trip cause

Tripping due to Reconnect the AFDD+ on the load side but Either overcurrent, a short circuit (both shown
mains overvoltage disconnect each and every load or switch it off. by white middle indicator) or an earth fault
U > 270 V AC (shown by blue middle indicator) caused the
tripping of the device.
Check installation for such faults.
Does the housing temperature Is it possible to switch on the AFDD+?
of the AFDD+ exceed ~80°C?

Yes No No Yes

Tripping due to AFDD device fault Installation fault (or failure to See “Finding the faulty load”
overtemperature Please claim the defective AFDD device at your disconnect/switch off all loads) (see pages 10 to 11)
o
Ti > 115 C local wholesales office.

6 EATON CORPORATION BR003016EN EATON CORPORATION BR003016EN 7


AFDD+ Application Guide

Assembly instructions Danger Installation


The AFDD+ trips infrequently Montageanweisung Lebensgefahr Montage n
Instructions de montage Danger de mort Montage u
Montážní návod Nebezpečí Montáž po
Montážní návod Nebezpečenstvo Montáž iba
Montagevejledning
Instrucciones de montaje
Any interventions in the electrical
Fare
Peligro
Må kun ins
Debe ser i
Szerelési utasitás
Istruzioni di montaggio
installation must be carried out
Életveszély
Pericolo di morte
Csak szak
Montaggio
Montasjeveiledning
Montage instructie
by qualified personnel!
Fare
Levensgevaar
Må monte
Montage a
Instruções de montagem Perigo Deve ser i
Instrukcja montazu Niebezpieczenstwo Montaz tyl
Connect a load greater than
Montageanvisning Varning Får endas
Asennusohjeet Vaara Asennus v
1 kW (e.g. a radiator)
Montaj talimati Hayati Tehlike Sadece uz
Instructiuni de montaj Pericol Instalare n

Loop back to the initial question and repeat


steps as shown in the diagram
Does the AFDD trip every time?

No Yes

Are the loads connected Disconnect each and every


and active? load or switch it off.

No Yes

Reconnect and switch the loads back Please contact your local Eaton team for See “Finding the faulty load”
on one by one technical support. (see pages 10 to 11)

Does the AFDD+ trip after switching on a new


load?

No Yes

That new load is the faulty load

8 EATON CORPORATION BR003016EN EATON CORPORATION BR003016EN 9


AFDD+ Application Guide

Assembly instructions Danger Installation


Finding the faulty load All loads have been disconnected
Montageanweisung
Instructions de montage
Lebensgefahr
Danger de mort
Montage n
Montage u
Montážní návod Nebezpečí Montáž po
or switched off Montážní návod Nebezpečenstvo Montáž iba
Montagevejledning
Instrucciones de montaje
Any interventions in the electrical
Fare
Peligro
Må kun ins
Debe ser i
Szerelési utasitás
Istruzioni di montaggio installation must be carried out
Életveszély
Pericolo di morte
Csak szak
Montaggio

Connect a load greater than


Montasjeveiledning
Montage instructie by qualified personnel!
Fare
Levensgevaar
Må monte
Montage a
1 kW (e.g. a radiator) Instruções de montagem
Instrukcja montazu
Perigo
Niebezpieczenstwo
Deve ser i
Montaz tyl
Montageanvisning Varning Får endas
Asennusohjeet Vaara Asennus v
Montaj talimati Hayati Tehlike Sadece uz
Instructiuni de montaj Pericol Instalare n
Is it possible to switch on the AFDD+?

Yes No

Reconnect all loads Installation fault


one by one and (or failure to disconnect/
power them up again switch off all loads)

Does the new load cause tripping?


Repeat until all loads
were added and
powered
up in the final circuit.
No Yes

No Are all loads connected? Can a load fault be detected?

Yes

Yes No
There is a sporadic arc fault pattern on the
mains network

Load fault Please contact your local Eaton team for


Contact your local Eaton team for technical
technical support.
support
10 EATON CORPORATION BR003016EN EATON CORPORATION BR003016EN 11
Eaton’s electrical business is a global leader with deep regional
application expertise in power distribution and circuit protection;
power quality, backup power and energy storage; control and
automation; life safety and security; structural solutions; and
harsh and hazardous environment solutions. Through end-to-end
services, channel and an integrated digital platform & insights
Eaton is powering what matters across industries and around the
world, helping customers solve their most critical electrical power
management challenges.

For more information, visit Eaton.com.

To contact us please visit https://www.eaton.com/us/en-us/support/


international-support-contacts.html
For technical support inquiries please get in contact
with your local Eaton team.

Eaton Industries (Austria) GmbH


Scheydgasse 42
1210 Vienna
Austria
Changes to the products, to the information contained in
this document, and to prices are reserved; so are errors
9 010238 08273 1

and omissions. Only order confirmations and technical


documentation by Eaton is binding. Photos and pictures also
Eaton do not warrant a specific layout or functionality. Their use
EMEA Headquarters in whatever form is subject to prior approval by Eaton. The
Route de la Longeraie 7 same applies to Trademarks (especially Eaton, Moeller, and
1110 Morges, Switzerland Cutler-Hammer). The Terms and Conditions of Eaton apply,
Eaton.eu as referenced on Eaton Internet pages and Eaton order
confirmations.
© 2020 Eaton
All Rights Reserved
Printed in Austria Follow us on social media to get the
Publication No. : BR003016EN Eaton is a registered trademark.
latest product and support information.
Article number 195206-MK
September 2020 All other trademarks are property
Grafics: SRA, Schrems of their respective owners.

You might also like