User Manual of SY5000 series AC Drive Overview

Chapter 1 Overview

Thank you for choosing SYRUNS SY5000 series AC Drive!


SY5000 series AC Drive is a high-quality, multi-function, low-noise inverter
which is designed, developed and produced according to international standards.
It can meet different needs of industrial conditions. It is applied advanced control
technology of space voltage PWM, with functions of constant voltage control,
power-off restart, dead zone compensation, automatic slip compensation, on-line
modification parameter. It is also with compact structure, easy to install.
For safety, please read the manual thoroughly before using SY5000 series
AC Drive. Meanwhile, please retain the manual and you can use it when regulate,
maintain and inspect the equipment in future.
The manual provides using instruction of SY5000 series AC Drive:
1. SY5000-G series general purpose AC Drive
2. SY5000-P series fan and pump purpose AC Drive
3. SYB-U50, SYB-U100 braking unit
4. Remote control keypad and extention cable

1.1 Purchase verification


Please verify the following items when open the box.
Table 1-1 Verification item
Verification item Verification method
Is it what you order, or not Please watch nameplate on the side of SY5000 AC Drive.
Parts damages or not Please check overall appearance.
Screws loose or not If necessary, use a screwdriver to check it.
If abnormal, please get in touch with the agent.

~~
User Manual of SY5000 series AC Drive Overview

1.2 Instruction of model no.

1.3 Nameplate instruction

~~
User Manual of SY5000 series AC Drive Overview

1.4 Specification of SY5000 series AC Drive


Table 1-2 Specification of SY5000 series AC Drive
Voltage Motor power Rated output
Item Model no.
class (KW) current (A)
SY5000-G0D422 0.4 3
Single
General SY5000-G0D722 0.75 4.5
phase
purpose SY5000-G1D522 1.5 7
220V
SY5000-G2D222 2.2 11
SY5000-G0D744 0.75 2
SY5000-G1D544 1.5 4
SY5000-G2D244 2.2 5.5
SY5000-G3D744 3.7 8
SY5000-G5D544 5.5 13
SY5000-G7D544 7.5 17
SY5000-G01144 11 24
SY5000-G01544 15 33
SY5000-G01844 18.5 39
SY5000-G02244 22 44
SY5000-G03044 30 60
Three General SY5000-G03744 37 75
phase purpose SY5000-G04544 45 90
380V SY5000-G05544 55 110
SY5000-G07544 75 150
SY5000-G09044 90 175
SY5000-G11044 110 210
SY5000-G13244 132 255
SY5000-G16044 160 305
SY5000-G18544 185 340
SY5000-G20044 200 380
SY5000-G22044 220 425
SY5000-G24544 245 480
SY5000-G28044 280 545
SY5000-G31544 315 615

~~
User Manual of SY5000 series AC Drive Overview

SY5000-P3D744 3.7 8
SY5000-P5D544 5.5 13
SY5000-P7D544 7.5 17
SY5000-P01144 11 24
SY5000-P01544 15 33
SY5000-P01844 18.5 39
SY5000-P02244 22 44
SY5000-P03044 30 60
SY5000-P03744 37 75
SY5000-P04544 45 90
Three Fan and
SY5000-P05544 55 110
phase pump
SY5000-P07544 75 150
380V purpose
SY5000-P09044 90 175
SY5000-P11044 110 210
SY5000-P13244 132 255
SY5000-P16044 160 305
SY5000-P18544 185 340
SY5000-P20044 200 380
SY5000-P22044 220 425
SY5000-P24544 245 480
SY5000-P28044 280 545
SY5000-P31544 315 615

Table 1-3 Technical specification of SY5000 series AC Drive


Item Specification
Single phase /triple phase corresponding input voltage,
Output voltage
constant voltage control is optional
Output
Output frequency 0.10~650.00Hz; highest frequency can set freely between
range 25.00~650.00Hz
Voltage, 1PH 220V±15%; 3PH 380V±15% 50Hz; 3PH 440V±
Power
frequency 10% 60Hz
Digital SVPWM space voltage vector control; carrier
Control Control mode
frequency 1.0~16.0KHz adjustable continuously
function
Start frequency 0.00~25.00HZ setting freely

~~
User Manual of SY5000 series AC Drive Overview

Resolution of
0.01Hz
output frequency
Digital setting: under 100Hz:0.01HZ; others: 0.1Hz;
Resolution of
analog input (external terminal) setting: 1% of highest
frequency setting
frequency
Linear V/F: base frequency can be set freely between
V/F feature
Control 25.00~650.00Hz
function constant torque, 1.2-th power and 1.5-th power decreasing
Torque
torque compensation mode selectable, compensation
compensation
voltage range: 0~30%
Start frequency(0.00~10.00Hz), voltage(0~15%),
DC braking
duration(0.0~10.0s)can be set freely
Overload General purpose: 150% rated current 1minute;
capacity fan and pump purpose: 120% rated current 1 minute
FWD-REV, RUN/FWD-REV, FWD-REV/self-
Operation mode
sustaining,3 modes available
Stop mode Deceleration stop/free stop

Operation panel▲▼key in, external potentiometer, panel


Frequency
potentiometer external analog current signal DC4~20mA,
setting
external anolog voltage signal DC0~5V or DC0~10V

0.1~6000.0 seconds (accel /decel can be set seperately)


Time mode of
No.1/No.2 accel /decel time, linear /S-curve type accel
accel /decel rate
/decel modes selectable
8-section speed of the external terminal control or
Operation Multi-section 4-section speed of parameters setting (one-cycle or repeat
function speed operation cycle), each section can be set freely, accel /decel time of
speed, two methods selectable
Frequency(0~highest frequency), accel /decel
Jog operation time(0.1~6000.0 seconds), accel /decel mode (linear/S
type) can be set freely
Frequency of Upper limit frequency (lower limit frequency~highest
upper limit and frequency), lower limit frequency (0~upper limit
lower limit frequency) setting freely
Fault recovery, jog frequency, external analog, input
bias/gain setting, speed display system, slip conpensation,
Other functions
fault history record (4 times), dynamic parameter (part)
modify, anti-reverse, etc.

~~
User Manual of SY5000 series AC Drive Overview

Operation panel Display: 5 data LED;parameter setting: 6 switches


External terminal4 programmable inputs(PI1~PI4), FWD, REV, EMS,
input RES
Fault output IC relay output (AC250V, 1A,resistance load)
Input
OUT-COM: Signal in operation/signal of speed arrival
output Output with open
of detection rate/ signal of overload alarm are selectable
signal collector
(Rated 24V, available output 50mA)
DC0~10V (max output current:10mA, resolution
Frequency table
ratio:0.4%), rated output frequency/rated current/rated
output
voltage are optional
Overcurrent stalling protection (50~200% of rated
current), overvoltage stalling protection, overvoltage
Protection
Protection protection,overcurrent protection, overload protection,
function
overheat protection, undervoltage protection, emergency
stop,etc.
Indoor,altitude of less than 1km,dust free, non-corrosive
Installation site
gases,no direct sunlight
Application
0℃~+40℃,20%~90%RH (no dew)
Working environment
condition Vibration Less than 0.5g
Storage
-25℃~+65℃
temperature
Mounting type Wall-mounted type, floor cabinet type
General purpose:IP20 (≤7.5kw); IP10 (≥11kw)
Protection degree
Fanand pump purpose:IP20 (≤11kw); IP10 (≥15kw)
Cooling mode Forced air cooling

1.5 Safety symbol instruction


It is very dangerous when use wrongly, possiblely make
people die.

Danger

It is dangerous if use wrongly, possiblely make people


injury or machine damage.

Caution

~~
User Manual of SY5000 series AC Drive Overview

1.6 Precautions
1. The inverter just applies to general triple-phase AC induction motors or variable
frequency motors. The installation environment should be well ventilated.
2. It is a normal phenomenon that temperature and noise of the motor raise a little
higher than power frequency when use the inverter.
3. General motors can’t work long under low-speed.
4. Output terminal of the inverter cannot be connected with RC absorbing device,
such as capacitor, varistor, etc.
5. If install the contactor between the inverter and the motor, must ensure that the
inverter does not output when the contactor is on-off. Otherwise, it will damage
the inverter.
6. The inverter should be used derating if the altitude is higher than 1000 meters.
Derate 10% when the altitude rises 1500 meters.
7. The inverter is as industrial waste when scrap it. Please be careful:
(1)Inner polymer capacitors probably explode if set it on fire.
(2)Plastic pieces may produce toxic gases when burn it.

~~
User Manual of SY5000 series AC Drive Installation

Chapter 2 Installation

2.1 Overall and installation dimensions

(a) 0.75~2.2KW (b) 3.7~7.5KW


Figure 2-1 Overall of SY5000 series AC Drive
Table 2-1 Overall and installation dimensions of SY5000 series AC Drive
Voltage class Model no. W W1 H H1 D d
SY5000-0D422
85 73 141.5 129.5 113 4.5
Single-phase SY5000-0D722
220V SY5000-1D522
SY5000-2D222
SY5000-0D744 115 105 180 170 160 5
SY5000-1D544
Three phase SY5000-2D244
380V-440V SY5000-3D744 150 138 235 223 160 5
SY5000-5D544
190 178 300 288 179 6.5
SY5000-7D544

~~
User Manual of SY5000 series AC Drive Installation

Figure 2-2 (a) 11KW~160KW

Figure 2-2 (b) ≥185KW

~~
User Manual of SY5000 series AC Drive Installation

Table 2-2 Overall dimensions(≥11KW)


Voltage
Type Model no. W W1 H H1 H2 D d
class
SY5000-G01144
243 196 392 372 350 185 9.5
SY5000-G01544
SY5000-G01844
SY5000-G02244 293 200 504 484 460 236 9.5
SY5000-G03044
SY5000-G03744 307 200 554 534 510 236 9.5
SY5000-G04544
390 300 620 590 560 248 10
SY5000-G05544
Three SY5000-G07544
General 430 300 860 800 830 340 12
phase SY5000-G09044
purpose
380V SY5000-G11044
SY5000-G13244 570 500 900 870 840 375 13
SY5000-G16044
SY5000-G18544
SY5000-G20044
610 — 1906 — — 605 —
SY5000-G22044
SY5000-G24544
SY5000-G28044
730 — 2000 — — 605 —
SY5000-G31544
SY5000-P01144
SY5000-P01544 243 196 392 372 350 185 9.5
SY5000-P01844
SY5000-P02244
SY5000-P03044 293 200 504 484 460 236 9.5
SY5000-P03744
SY5000-P04544 307 200 554 534 510 236 9.5
SY5000-P05544
390 300 620 590 560 248 10
Three Fan and SY5000-P07544
phase pump SY5000-P09044 430 300 860 800 830 340 12
380V purpose SY5000-P11044
SY5000-G13244 570 500 900 870 840 375 13
SY5000-G16044
SY5000-G18544
SY5000-G20044
610 — 1906 — — 605 —
SY5000-G22044
SY5000-G24544
SY5000-G28044
730 — 2000 — — 605 —
SY5000-G31544

~10~
User Manual of SY5000 series AC Drive Installation

2.2 Installation instruction


2.2.1 Disassembly and assembly of panel and keypad

2
2

1
1

(a) (b)
Figure 2-3 Disassembly and assembly of small panel

2
1 Claw locker A
1
Claw locker B

(a) (b)
Figure 2-4 Disassembly and assembly of keypad

1
1
2
2

(a) (b)
Figure 2-5 Disassembly and assembly of big panel

~11~
User Manual of SY5000 series AC Drive Installation

1. Disassembly and assembly of small panel (terminal cover)


(1) Disassembly of small panel
As shown in Figure 2-3 (a), press two faces according to direction 1, meanwhile,
lift lower part of small panel according to direction 2.
(2) Assembly of small panel
As shown in Figure 2-3 (b),when assembly,firstly align small panel and big panel,
lean panels forward, embed bayonet shapes of panel in big panel, and then press
down the panels according to direction 2.

2. Disassembly and assembly of keypad


(1) Disassembly of keypad
As shown in Figure 2-4 (a), press the buckle on the side of keypad according to
direction 1, unhook it from big panel, lift it according to direction 2, and then get the
keypad.
(2) Assembly of keypad
As shown in Figure 2-4 (b), stick Digital Console from the 1 directions the claw
locker A(place 2), pressing to keep toward 2 directions immediately after hearing the
“click”voice, stick the claw locker B (place 2).

3. Disassembly and assembly of big panel


(1) Disassembly of big panel
As shown in Figure 2-5 (a), make an effort toward 1 direction to press the two side
of console support, in the meantime, please press 2 directions to lift console support
lower part.
(2) Assembly of big panel
As shown in Figure 2-5 (b) , console support head two cards hang up to block from
the 1 directions the hull body(place 2), press to keep toward 2 directions immediately
after hearing the“click”voice.
2.2.2 Disassembly and assembly of terminal housing and keypad (≥11 kW)
1. Disassembly and assembly of terminal housing
(1) Disassembly of terminal housing
Use standard No. 1 crosshead screwdriver to take off two M4 screw bolts (as shown
in Figure 2-6 (a)), and then you can remove the terminal housings.
(2) Assembly of terminal housing
Use two M4 × 8 bolts to fix terminal housings (The direction is as shown in Figure

~12~
User Manual of SY5000 series AC Drive Installation

2-7(b)), and tighten by using standard No.1 crosshead screwdriver, and tightening
torque is about 5 ~ 8 N • m.

screw hole

(a) (b)
Figure 2-6 Disassembly and assembly of terminal housing and keypad (≥11 kW)

2. Disassembly and assembly of keypad


(1) Disassembly of keypad
◆ Use standard No.1 crosshead screwdriver to take off four M4 bolts(as shown in
Figure 2-7 (a) );
◆ Disconnect the connection cable of keypad, and remove control panel;
◆ As shown in Figure 2-7 (b), rollover control panel, push out the jaw of keypad,
and remove keypad.
(2) Assembly of keypad
◆ As shown in Figure 2-7 (c), firstly inbed keypad in keypad adapter, and confirm
the correction of inbedding in the slotted hole;
◆ Connect the connection wire of keypad with control circuitboard;
◆ Fix control panel on the box by using four M4×8 bolts, and tighten by using
standard No.1 crosshead screwdriver, and tightening torque is about 5 ~ 8 N • m.

screw
hole clasp

(a) (b) (c)


Figure 2-7 Disassembly and assembly of keypad (≥11kW)

~13~
User Manual of SY5000 series AC Drive Installation

Caution

1. In order to avoid being exposed and damaged, don’t use other methods to
disassembly and assembly keypad and panels.
2. Don’t directly install big panel with keypad in the AC Drive, otherwise, it will
bring poor contact.Please separately install big panel in the AC Drive, then
install keypad in the big panel.

2.3 Requirements and management of installation site

Caution

3. Please hold the bottom of AC Drive when carry it.


Risk of feet injury if only holding the panel.
4. Please install in metal board and other nonflammable materials.
Risk of fire if installing in flammable materials.
5. If install two or more AC Drives in the same cabinet, please set the cooling fan,
and keep the air temperature below 40℃.
Risk of fire and other accidents if overheating.

2.3.1 Installation site:


The installation site should meet the following conditions:
 Good indoor ventilation
 Ambient temperature -10°C~40°C
 Humidity less than 90%RH, without dew
 Don’t install in the combustibles such as woods
 Avoid direct sunlight
 No combustible, explosive, corrosive gases and liquids
 No ash dust, oil dust, floatable fibers and metal particles
 strong installed base, no vibration
 No electromagnetic interference

~14~
User Manual of SY5000 series AC Drive Installation

2.3.2 Ambient temperature


To improve operation reality of AC Drive, please install in well-ventilated place.
When used in an enclosed cabinet, install the cooling fan or cooling air-conditioning,
and keep the environment temperature below 40°C.
2.3.3 Precaution
Please put a dust cover on the AC Drive when install. Do not fall metal framents
into AC Drive internal when drill holes. Please remove dust cover after installation
finishes.
2.3.4 Installation direction and space

Figure 2-8 Installation direction and space of SY5000 series AC Drive


In order to get good effect of cooling cycle, must install the AC Drive in vertical
direction. Please refer to Figure 2-8.

*********************************************************************
Note: When install two AC Drives upper and lower, we should utilize isolating plate.
*********************************************************************

~15~
User Manual of SY5000 series AC Drive Wiring

Chapter 3 Wiring

Danger

1 Before wiring, please confirm the cut-off of input power supply.


Risk of electric shock and fire.
2 Wiring operations must be carried out by electric engineerting specialists.
Risk of electric shock and fire.
3 Ground terminal must be reliably grounded.(380V class:especially the third
ground)Risk of electric shock and fire.
4 After connecting with the terminal of emergency stop, be sure to check the
validity of actions.Risk of injury.(The responsibility of wrong wiring is
undertaked by users.)
5 Do not directly touch the output terminals. Do not connect the output terminals of
inverter with the housings. Do not be short circuit between output terminals.
Risk of electric shock and short-circuit.

Caution

1 Make sure rated voltages of AC main circuit power supply and inverter are the
same. Risk of injury and electric shock.
2 Do not test withstand voltage of inverter.
It will damage semiconductor components.
3 Please connect braking unit or braking resistor according to wiring diagram.
Risk of fire.
4 Please use the specified torque screwdriver fastening terminals. Risk of fire.
5 Do not connect the cable of input power supply to output U、V、W terminals.
It will damage the internal of the inverter if adding voltage onoutput terminals.
6 Do not switch phase-shift capacitor into output circuit. It will damage the internal
of the inverter.
7 Do not switch electric-magnetic switch and electric-magnetic contactor into ouput
circuit. When the inverter is in operation with a load, surge current generated by
electromagnetic switches, electromagnetic contactors will cause the over-current
protection circuit action of inverter.

~16~
User Manual of SY5000 series AC Drive Wiring

3.1 Connection with peripheral equipments


SY5000 series inverter standard connection diagram with peripheral equipments
(As shown in Figure 3-1)

Figure 3-1 Connection diagram with peripheral equipments

~17~
User Manual of SY5000 series AC Drive Wiring

3.2 Connection diagram


Figure 3-2a,3-2b,3-3a,3-3b are connection diagrams of SY5000 series
inverter. When manipulate the inverter by using keyboard of control panel, the electric
motor can work only when connect main circuit.

Figure 3-2a Connection diagram of SY5000-G series (≤15KW)

~18~
User Manual of SY5000 series AC Drive Wiring

Figure 3-2b Connection diagram of SY5000-G series (≥18.5KW)

~19~
User Manual of SY5000 series AC Drive Wiring

Figure 3-3a Connection diagram of SY5000-P series (≤18.5KW)

~20~
User Manual of SY5000 series AC Drive Wiring

Figure 3-3b Connection diagram of SY5000-P series (≥22KW)

Remark:
*1:MC is mainly used to prevent fault re-start or transcient power-cut re-start;
Resistor overheat protection of external braking unit also should be connected to the
control loop of MC.

*2:For 220V series,input power supply switches in L1,L2;for 380V, inputpower

~21~
User Manual of SY5000 series AC Drive Wiring

supply switch in R, S, T;
*3:Be decided by JP3 jumpers of CPU board: Located in position 1, input voltage
range of external analog voltage V2 is 0~5V;located in position 3, input voltage
range of V2 is 0~10V. If no special requirements before delivery, JP3 jumper is locaed
in position 1, namely input voltage range of V2 is 0~5V. See above figure。
3.3 The composition of terminal blocks
Terminal blocks of SY5000 series inverter include terminal blocks of control
circuit and terminal blocks of main circuit:
 Terminal block of general control circuit
1 Analog input:0~5V(0~10V)voltage source V2, 4~20mA current source
I2, GND
2 Digital input:SF, COM, SR, RST, EMS, PI1, PI2, PI3, PI4.
3 Digital output:OUT, TA, TB, TC
4 Analog output:FM
5 Signal of power supply:+5V voltage source Vcc, +24V power supply
 Terminal block of main circuit
1 Input power supply:R(L1), S(L2), T
2 Ground terminal:
3 Connection terminal of external braking unit: ,
4 Connection terminal of braking resistor: , PB和 2, PB
5 Connection terminal of DC reactor: 1, 1 2
6 Electrical wiring:U, V, W
PI1 PI2 PI3 PI4 SF SR RST EMS FM GND

Ta Tb Tc +24V COM OUT VCC V2 I2 GND

Terminal blocks of SY5000-G series control circuit

Terminal blocks of SY5000-P series control circuit

~22~
User Manual of SY5000 series AC Drive Wiring

R S T 1 2 PB U V W

terminal blocks of main circuit (3PH 380V)


5.5, 7.5KW (SY5000-G series)
7.5, 11KW (SY5000-P series)

R S T

U V W PB
terminal blocks of main circuit (3PH 380V)
0.75~2.2KW (SY5000-G series)
3.7KW (SY5000-P series)

PB R S T U V W
terminal blocks of main circuit (3PH 380V)
3.7KW (SY5000-G series)
5.5KW (SY5000-P series)

Terminal blocks of main circuit (3PH 380V)


11KW, 15KW (SY5000-G series)
15KW, 18.5KW (SY5000-P series)

~23~
User Manual of SY5000 series AC Drive Wiring

Terminal blocks of main circuit (3PH 380V)


18.5KW~37KW (SY5000-G series)
22KW~45KW (SY5000-P series)

Terminal blocks of main circuit (3PH 380V)


45KW~90KW (SY5000-G series)
55KW~110KW (SY5000-P series)

Terminal blocks of main circuit (1PH 220V)


Figure 3-4 Arrangement of terminal blocks of control circuit and main circuit

3.4 Wiring of terminal blocks of main circuit


3.4.1 Cable size of main circuit and pressure wire terminals
Cable size and terminal screw size of main circuit, as shown in Figure 3-1

~24~
User Manual of SY5000 series AC Drive Wiring

Figure 3-1 terminal screw size and sectional area of wire


Sectional
Terminal area of Wire
Model no. Terminal symbol
screw wire species
(mm2)
SY5000-G0D422 M2.5 2.5
1PH SY5000-G0D722 L1,L2 M2.5 2.5
220V SY5000-G1D522 U,V,W,PB, , , M4 4
SY5000-G2D222 M4 6
SY5000-G0D744 R,S,T, M4 2.5
SY5000-G1D544 M4 2.5
SY5000-G2D244 U,V,W,PB, , , M4 4
SY5000-G3D744 PB, , ,R,S,T,U,V,W, M4 4
SY5000-G5D544 M5 6
SY5000-G7D544 R,S,T, 1, 2,PB, ,U,V,W, M5 6
750V
SY5000-G01144 M5 8
R,S,T, , ,PB , ,U,V,W plastic
SY5000-G01544 M5 8
3PH cable
SY5000-G01844 M6 16
380V-
SY5000-G02244 M6 16
440V R,S,T, , +1 , , ,U,V,W
SY5000-G03044 M6 25
SY5000-G03744 M8 25
SY5000-G04544 M8 35
SY5000-G05544 M8 35
R,S,T, +1 , +2 , , ,U,V,W
SY5000-G07544 M10 60
SY5000-G09044 M10 60
SY5000-G11044 M10 60
SY5000-G13244 R,S,T, , +1 , , ,U,V,W M12 100
SY5000-G16044 M12 100

3.4.2 Function of main circuit terminal


Terminal function of main circuit, as shown in figure 3-2
Table 3-2 Function of main circuit terminal
Terminal
Function description
sign
AC power supply input terminal:connect 3PH AC power supply
R(L1),
(R, S, T)(3PH 380V series) or 1PH AC power supply(L 1,
S(L2), T
L2)(1PH 220V series)
U, V, W Inverter output terminal, which is connected to 3PH AC motor.
, , respectively are anode and cathode of DC bus.

~25~
User Manual of SY5000 series AC Drive Wiring

, 1,
1, 1 2 are DC reactor terminals of main circuit
1, 2
PB Between PB and is the terminal of built-in braking resistor
Ground terminal,grounding

3.4.3 Precautions of main circuit wiring

1. Installation of ELCB
As the inverter’s output is high-frequency PWM signal, the inverter will generate
high-frequency leakage current, please select Y2 type delay leakage circuit breaker
with above 30mA current sensitivity; if use ordinary ELCB, please select ELCB with
above 200mA current sensitivity.
2. Connection with terminal blocks
The phase sequence of input power supply is irrevelant to R(L1), S(L2), T phase
sequences of terminal block, so it can be any connection.
3. Setting of AC reactor or DC reactor
When the input power is connected with capacitive load, it will generate high peak
current in power grid.
If don’t take appropriate measures, the peak current may damage inverter rectifier
and other power modules.
When there is high peak current in power grid, please connect 3PH AC reactor
(optional) on the power input side of inverter, or install DC reactor on the terminal of
DC reactor.
Therefore, it not only suppresses peak current, but also improves power factor.
4. Setting of Surge Protection Device (SPD)
When there is inductive load near the inverter (electromagnetic contactor,
electromagnetic valve, electromagnetic coil, electromagnetic circuit breaker), please
install SPD at two ends of its coil.
5. Wiring of inverter and electric motor
Please check whether rotate forwards when confirm the command of forward.
When the motor is reverse rotation, exchanging any two of U, V, W output
terminals can change rotation direction of the motor.
Use jog function to confirm forward and reverse rotations.

~26~
User Manual of SY5000 series AC Drive Wiring

6. Absolutely prohibit the connection of power supply wire and output terminal
Don’t connect the input power line to the output terminal.
If you input the power at the output terminal, the internal components of inverter
will be damaged.
7. Absolute prohibit short-circuit or grounding of output terminal
Do not directly touch the output terminal. Do not short the output line with inverter
housing. Otherwise, there will be danger of electric shock and short circuit.
In addition, don’t short the output line.
8. Absolutely prohibit the use of phase-shift capacitor
Don’t connect the capacitor in the output circuit. It will cause the damage of the
inverter.
9. Absolutely prohibit the use of electromagnetic switch
Don’t connect electromagnetic switches and electromagnetic contactors.
Otherwise, inverter surge current will cause protection action, and that will damage
interial components when it’s serious.
10. Wiring distance between inverter and motor
The longer wiring distance between the inverter and the motor, the higher high-
harmonic leakage current of the cable.
Leakage current will negatively impack the inverter and near equipments. Then it
should minimize the leakage current.
Wiring distance and carrier frequency are as shown in Table 3-3:

Table 3-3 Wiring distance and carrier frequency between inverter and motor
Wiring distance between inverter
Below 50m Below 100m Above 100m
and motor
Carrier frequency Blow 12KHz Below 10KHz Below 5KHz

Function code of parameter b-026 ≤12.0 ≤10.0 ≤5.0

11. Ground connection


① Ground terminal, please connect the ground.
220V series:type 3 ground(grounding resistance is less than 100Ω)
380V series:special type 3 ground(grounding resistance is less than 10Ω)
② Don’t share the grounding line with welding machines or power equipments.
③ Please use the grounding wire according to electrical equipments technical
standards. And the distance from the ground is as short as possible.

~27~
User Manual of SY5000 series AC Drive Wiring

④ Don’t form the grounding line to a loop in the place when use two or more
inverters. Correct and wrong grounding methods are as shown in Figure 3-5.

Figure 3-5 Grounding comection

3.5 Wiring of control circuit terminal


In order to reduce interference and attenuation of control signal, wire length of
control signal should be less than 20m. The interval distance between wire length
and power line should be more than 30cm. Control signal line should be twisted-pair
shield cable.

3.5.1 Wire size and line terminal of general control circuit


Table 3-4 Size of terminal and wire and tightening torque of screw
Terminal Sectional area of wire Tightening torque
Wire type
screw (mm2) of screw(N·m)
Multi-unit
M3.5 0.5~2 0.8
shield wire

~28~
User Manual of SY5000 series AC Drive Wiring

3.5.2 Function of general control circuit terminal


PI1 PI2 PI3 PI4 SF SR RST EMS FM GND

Ta Tb Tc +24V COM OUT VCC V2 I2 GND

Figure 3-6 Arrangement of general control circuit terminal

Table 3-5 Function of control circuit terminal


Name and function of
Catagory Terminal sign Signal requirements
terminals
SF Forward/stop
SR Reverse/stop
Optical isolation,
RST Reset
Digital short-circuit effective
EMS Emergency stop
input with CM terminal
Programmable input
PI1 ~ PI4
terminal
COM common port
0~5V(when terminal 1
of JP3 on CPU board is
Input terminal of analog
V2 short) or 0~10V(when
voltage
Analog terminal 3 of JP3 on CPU
input dboard is short)
Input terminal of analog
I2 4~20mA
current
GND Analog grounding Control panel grounding
Rated 24V,
OUT Open collector output
permissible output 50mA
TA, TB, TC
Digital (TA, TC Contact capacity:
output normal open, Fault alarm output relay 250V AC:<1A
TB, TC normal 30V DC:<1A
close)
COM Common port

~29~
User Manual of SY5000 series AC Drive Wiring

Can be connected to the Maximum output:


Analog FM*
output of voltmeter* DC 0~10V,10mA
output
GND Analog grounding Control panel grounding
Power supply of CPU
+5V +5V-GND
Power board
supply COM external voltage The current is less than
+24V
output 20mA
*Remark:Long cable is easy to generate interference. It is recommended to use
shield cable.

3.5.3 Notes of control circuit wiring


● Sperately arrange connecting wire of control circuit, connectin wire of main
circuit, other power wires or power line
●To avoid malfunction caused by interference, you’d better use twisted shield
cable as connecting wire of control circuit. Wiring distance should be less than 20m.
● One end of shield wire should be connected to the ground.

3.6 EMC guide


The inverter can generate a certain noise. To reduce or eliminate the noise, we
should correctly connect cables and wires, but also adopt the following meansures
according to actual situation on sites:

3.6.1. Treating of conducted interference


(1) Set noise filter on the side of power supply can inhibit the noise generated by
the inverter power supply, and also inhibit the power supply noise effect on the
inverter. The inverter needs the special input noise filter.
(2) Isolate other equipments by using isolation transformers or power filters.
(3) Check whether external equipment and inverter wiring constitute closed loop.

3.6.2. Treating of radio-frequency interference (RFI)


(1) For easy-effecctive equipments and signal lines, please install far away from the
inverter.Use shield lines as singal lines.
Shield layer is connected to the ground, and cable of signal line is set into metal
tube.

~30~
User Manual of SY5000 series AC Drive Wiring

Try to far away from inverter and its input and output wires.
If the signal cable must cross power cable, keep orthogonality between them.
(2) Connect output line into ground metal tube. The interval distance between
output line and signal line is more than 30cm.
(3) On the output side of the inverter, install special radio noise filter and linear
noise filter(ferrite common-mode retardation coil) to restrain radiation noise
of power line.
(4) Avoid parallel wiring or bundle wiring between signal line and power line,
make easy-effected equipments aways from the inverter, make easy-effected
signal away from input and output lines of the inverter.
It is better that shield signal line and power line, and respectively put into metal
tubes. The interval distance between metal tubes is more than 20mm.
(5) Shield with steel vessel. Connection line between inverter and the motor should
be as short as possible.

3.7 Wiring inspection


After wiring is completed, please inspect the wiring.
 Connection is right, or not;
 Screws and wire terminals are left in the equipment, or not;
 Screws are loose, or not;
 The bare wire of terminal parts is short-circuiting to other terminals, or not.

~31~
User Manual of SY5000 series AC Drive Keypad operation

Chapter 4 Keypad operation

4.1 Keypad function


Control panel keypad of SY5000 series inverter consists of LED digital monitor,
LED indicator, operation keys and panel potentiometer, as shown in Figure 4-1.

Figure 4-1 Name and instruction of keypad


4.1.1 Display format
There is a 5-digit 8-section LED monitor on the keypad, which is used for
displaying running status, function code, parameter value and fault code.
4.1.2 Indicator
RUN:When the inverter is running, the green indicator “RUN” lights;
ERR:When fault or error occur, the red indicator “ERR” lights and blinks.

~32~
User Manual of SY5000 series AC Drive Keypad operation

4.1.3 Keypad operation
Function of keys is as shown in Table 4-1
Table 4-1 Function of keys
Key Name Function
In the direct mode, click here to enter functional group option, and
Function
click the key again to ruturn back direct display status.In the status
key
of parameter setting, click here to return previous status.

In the status of functional group, do selection operation to functional


group options (basic function b group, extended function E group,
PID adjustment P group, 485 communication R group).
In the status of function code, do upwards selection operation to
function code.
Up key
In the status of parameter value, do adding setting value operation
to parameter value.
When the inverter runs according to control panel direct setting
frequency, enter the setting status of b-000 parameter, click the key
to increase output frequency.
In the status of functional group, do selection operation to functional
group options (basic function b group, extended function E group,
PID adjustment P group, 485 communication R group).
In the status of function code, do downwards selection operation to
Down function code.
key In the status of parameter value, do subtracting setting value
operation to parameter value.
When the inverter runs according to control panel direct setting
frequency, enter the setting status of b-000 parameter, click the key
to decrease output frequency.

In the direct mode, click here to enter functional group option.


Set key In other statuses, click here to confirm options or data, and store
setting data in E2PROM which can be stored for long.
It is the start command key when controlled by control panel.

Run key Clicking and releasing the key to issue running commands, the
inverter will accelerates running according to setting acceleration
time.
It is the stop command key when controlled by control panel.
Stop/ Clicking and releasing the key to issue stop commands, the inverter
reset
key will decelerates stop according to setting deceleration time.
Use the key to reset the inverter when it trips because of a fault.

~33~
User Manual of SY5000 series AC Drive Keypad operation

4.2 Basic operation of the keypad


4.2.1 Direct status disply
Direct display status of SY5000 series inverter refers to initial display mode
after power-on, which is used for displaying output frequency of inverter.
4.2.2 Switching of display parameter
In the status of direct display, we can view or modify function parameters by
keypad operations.
All display parameter codes are devided into four groups: basic function
b group, extended function E group, PID regulation function P group and 485
communication R group.
Firstly determine display code of parameters, locat its function group, and
then do operations in the following order.

Figure 4-2 Operation procedure of parameter setting

~34~
User Manual of SY5000 series AC Drive Keypad operation

Example of function setting and parameter regulation (under the status of direct
display)
E.g. 1:Set base frequency as 60Hz:
No. Operation Explanation

1 Access to basic function status,display - - b - -

Access in parameter setting of basic function group,


2
display b-000

3 Keep pressing the key until display b-008

4 Display the current setting as 50.00

5 Keep pressing the key until display 60.00

Temporarily store current setting value 60.00 into


memory unit, the inverter will run according to new
setting value, and new data will be lost when power off.
6
Store current setting value 60.00 into memory unit, the
inverter will run according to new setting value, and new
data will be saved even if power off.
When need set other parameters of b group, please repeat
2~6
above 2~6 steps.
7
Press the key of FNC,and return to direct display mode

E.g. 2:Set the function of constant voltage control as 370V:


No. Operation Explanation

1 Access in status of function group, display - - b - -

2 Press 1 time, display - - E - -

~35~
User Manual of SY5000 series AC Drive Keypad operation

Acess in parameter setting of extended function group,


3
display E-000

4 Keep pressing the key until display E-045

5 Display current setting value 380

6 Keep pressing the key until display 370

Temporarily store current setting value 370(V)into


memory unit, the inverter will run according to new
setting value, and new data will be lost when power off.
7
Store current setting value 370(V)into memory unit,
the inverter will run according to new setting value, and
new data will be saved even if power off.
When need set other parameters of E group, please
4~7
repeat above 4~7 steps.
8
Press the key of FNC,and return to direct display
mode

4.2.3 Frequency setting


There are various ways and methods for frequency setting of SY5000 series
inverter, their priority is as shown in Table 4-2.
Table 4-2 frequency setting method and priority
Corresponding function
Priority Signal name
parameters
1 Jog operation b-002
2 Multi-stage speed run b-003
high 3 0~5V/0~10V input of analog b-004
↓ 4 4~20mA input of analog b-005
low 5 Operation panel potentiometer b-006
6 Purse input b-007
Setting frequency of panel
7 b-001
number

~36~
User Manual of SY5000 series AC Drive Parameter instrction

Chapter 5 Parameter instruction

5.1 Parameter table


Basic parameters (group b)
Modification mark in operation:
○: The parameter can be set during operation;
Х: The parameter can’t be set during operation
Function Factory
Description Setting range Increment Unit
code setting
Frequency
○ b-000
setting
0.00 ~ [b-010] 0.01 Hz 0.00

0: RUN/STOP keys disabled, RUN,


STOP and motional direction are
determined by status of SF, SR and
[b-036];
1: RUN/STOP of the motor
is controlled by status of PI1-
COM, motor motional direction is
determined by [b-035];
2: RUN/STOP of the motor
is controlled by status of PI2-
COM, motor motional direction is
determined by [b-035];
Keypad 3: RUN/STOP of the motor
○ b-001
command is controlled by status of PI3-
1 5
COM, motor motional direction is
determined by [b-035];
4 : R U N / S TO P o f t h e m o t o r i s
controlled by status of PI4-COM,
the motor motional direction is
determined by [b-035];
5: RUN/STOP keys control RUN/
STOP of the motor, if [b-003]=
0, motor motional direction is
determined by [b-035]; if [b-003]
≠0, the direction is determined by
[E-018].

~37~
User Manual of SY5000 series AC Drive Parameter instrction

0: disabled;
1: jog command is controlled by
status of PI1-COM;
2: jog command is controlled by
Jog status of PI2-COM;
○ b-002
command 3: jog command is controlled by
1 0
status of PI3-COM;
4: jog command is controlled by
status of PI4-COM;
5: enabled.

0: disabled;
1: 8-step speed running according
to according to statuses of [E-019],
[E-020], [E-021];
Multi-step
2: single-cycle operation according
○ b-003 speed
to frequency [E-022] ~ [E-025], then
1 0
command
maintain running at frequency of
[E-025];
3: recycle operation according to
frequency of [E-022] ~ [E-025]

0: disabled;
1: analog voltage input setting
frequency is controlled by PI1-COM
status;
2: analog voltage input setting
frequency is controlled by PI2-COM
Analog
status;
voltage
○ b-004
input
3: analog voltage input setting 1 0
frequency is controlled by PI3-COM
command
status;
4: analog voltage input setting
frequency is controlled by PI4-COM
status;
5: set frequency according to analog
voltage input

~38~
User Manual of SY5000 series AC Drive Parameter instrction

0: disabled;
1: analog current input setting
frequency is controlled by PI1-
COM status;
2: analog current input setting
frequency is controlled by PI2-
Analog COM status;
○ b-005 current input 3: analog current input setting 1 0
command frequency is controlled by PI3-
COM status;
4: analog current input setting
frequency is controlled by PI4-
COM status;
5: set frequency according analog
current input

0: disabled;
1: panel potentiometer setting
frequency is controlled by PI1-COM
status;
2: panel potentiometer setting
frequency is controlled by PI2-COM
Keypad status;
○ b-006 potentiometer 3: panel potentiometer setting 1 5
command frequency is controlled by PI3-COM
status;
4: panel potentiometer setting
frequency is controlled by PI4-COM
status;
5: Set frequency by panel
potentiometer.

0: pulse input setting frequency


disabled which is controlled by
PI3-COM (increasing frequency)
status and PI4-COM (decreasing
Pulse
frequency) status;
○ b-007 frequency
1: pulse input setting frequency
1 0
input
enabled which is controlled by
PI3-COM (increasing frequency)
status and PI4-COM (decreasing
frequency) status;
Base
Х b-008 25.00 ~ 650.00 0.01 Hz 50.00
frequency

~39~
User Manual of SY5000 series AC Drive Parameter instrction

Highest
Х b-009 25.00 ~ 650.00 0.01 Hz 50.00
frequency
Upper limit
○ b-010
frequency
[b-011] ~ [b-009] 0.01 Hz 50.00

Lower limit
○ b-011
frequency
0.00 ~ [b-010] 0.01 Hz 0.00

Lower limit
0: lower limit frequency stop mode;
Х b-012 frequency 1 0
1: lower limit frequency run mode。
mode
Lower limit
○ b-013 hysteresis 0.00 ~ [b-010] 0.01 Hz 0.00
frequency
Start
○ b-014
frequency
0.00 ~ 25.00 0.01 Hz 0.00

0: select accel / decel time 1;


1: select accel /decel time 1 or 2
according to PI1-COM status;
2: select accel /decel time 1 or 2
according to PI2-COM status;
3: select accel /decel time 1 or 2
Accel
according to PI3-COM status;
○ b-015 /decel time
4: select accel /decel time 1 or 2
1 0
command
according to PI4-COM status;
5: select accel /decel time 2
(Note: Pix is not shorted with COM,
then accel / decel time 1 enabled;
Pix is shorted with COM, then accel /
decel time 2 enabled, x = 1,2,3,4)
Accel /decel
○ b-016
mode 1
0: linear mode;1: S-curve mode 1 0
○ b-017 Accel time 1 0.1 ~ 6000.0 0.1 s 15.0
○ b-018 Decel time 1 0.1 ~ 6000.0 0.1 s 15.0
Accel /decel
○ b-019
mode 2
0: linear mode;1: S-curve mode 1 0
○ b-020 Accel time 2 0.1 ~ 6000.0 0.1 s 15.0
○ b-021 Decel time 2 0.1 ~ 6000.0 0.1 s 15.0
Torque 0: constant torque mode;
Х b-022 compensation 1: 1.2th power reduced torque mode; 1 0
voltage mode 2: 1.5th power reduced torque mode;

~40~
User Manual of SY5000 series AC Drive Parameter instrction

Torque
Х b-023 compensation 0 ~ 30 1 % 3
voltage
0: overload protection function
Electronic disabled;
○ b-024
thermal relay 1: overload protection function
1 1
enabled;
Electronic
○ b-025 thermal relay 50 ~ 150 1 % 100
level
PWM
○ b-026 Carrier 1~ 16 1 KHz 6
frequency
○ b-027 Jog frequency 0.00 ~ b-010 0.01 Hz 0.00
Jog accel/
○ b-028
decel mode
0: linear mode;1: S-curve mode 1 0

○ b-029 Jog accel time 0.1~ 6000.0 0.1 s 15.0


○ b-030 Jog decel time 0.1~ 6000.0 0.1 s 15.0
DC braking
○ b-031
duration
0.0 ~ 10.0 0.1 s 0.0

0: disabled;
1: controlled by PI1-COM status;
DC braking
2: controlled by PI2-COM status;
○ b-032 command
3: controlled by PI3-COM status;
1 0
when stop
4: controlled by PI4-COM status;
5: enabled
DC braking
Х b-033 start 0.00 ~ 10.00 0.01 Hz 3.00
frequency
DC braking
Х b-034 0 ~ 15 1 % 3
torque
Motor
0: forward;
Х b-035 direction 1 0
1: reverse.
command

~41~
User Manual of SY5000 series AC Drive Parameter instrction

0: FWD/REV mode——
if SF-COM short, then order the motor
to rotate forward; if SR-COM short,
then order the motor to rotate reverse;
1: RUN, FWD/REV mode——
If SF-COM short, then order the
motor to run forward, if both of SF-
SF, SR
○ b-036
command
COM,SR-COM are short, then order 1 0
the motor to run reversely, if SF-COM
is off, then the motor stops;
2: self-sustaining mode——
SF-COM pulse signal orders the motor
to run forward, SR-COMpulse signal
orders the motor to run reversely, PI1-
COM pulse signal stop the motor.

0: conventional switch mode——Fan


starts running when inverterruns, fan
delays to stop when inverter stops;
1: auto switch mode——Fan starts
working when radiator temperature
○ b-037 Fan mode
reaches to higher than 40℃;
1 0
Fan stops when radiator temperature
reduces to smaller than 30℃;
2: always run mode;
3: always stop mode.

Reverse 0: reverse allowed;


Х b-038 1 0
command 1: reverse not allowed
SF,SR input
○ b-039
filter factor
0~5000 1 3

DC braking
○ b-040
before start
0.0~10.0 0.1 s 0.0

0: display “0”
1: display setting frequency;
2: display output frequency;
Display 3: display DC bus voltage;
content 4: display output voltage;
○ b-041
command in 5: display output current;
1 0
standby state 6: display PID regulation reference
value;
7: display PID regulation feedback
value.

~42~
User Manual of SY5000 series AC Drive Parameter instrction

Code table of extended function (group E)


Function
Explanation Unit Description
code
The display frequency is decided by the priority of
E-000 Setting frequency Hz
running mode.
When PID regulation function enabled, it is used to
E-001 Reference value
display current reference value
When PID regulation function enabled, it is used to
E-002 Feedback value
display current feedback value
E-003 Output frequency Hz Display current output frequency of the inverter
E-004 Output voltage V Display current output voltage value of the inverter
E-005 Output current A Display enabled value of current output current
E-006 DC bus voltage V Display DC voltage of main circuit
E-007 Temperature display ℃ Display the current temperature of the radiator
E-008 Total running time hour Display total running time of the inverter
Display the current state of the terminal
short circuit
与 C0M 端子短接
Display of terminal with COM
E-009 --
input signal 与disconnect
C0M 端子断开
EMS RST SF SR PI4 PI3 PI2 PI1 with COM
E-010 1st fault record -- Fault code of last time
E-011 2 fault record
nd
-- Fault code of second-to-last time
E-012 3rd fault record -- Fault code of third-to-last time
E-013 4 fault record
th
-- Fault code of fourth-to-last time

Function
Description Setting range Increment Unit Default
code
Cycle operation
○ E-014
duration 1
0.1 ~ 6000.0 0.1 s 2.0

Cycle operation
○ E-015
duration 2
0.1 ~ 6000.0 0.1 s 2.0

Cycle operation
○ E-016
duration 3
0.1 ~ 6000.0 0.1 s 2.0

Cycle operation
○ E-017
duration 4
0.1 ~ 6000.0 0.1 s 2.0

Mult-step speed
○ E-018 running direction 0 ~ 255 1 0
setting

~43~
User Manual of SY5000 series AC Drive Parameter instrction

0: PI1~ PI4 disabled;


1: When [b-003] = 1,
choose PI1 as the least bit of
programmable 8-step speed;
2: When [b-003] = 1,
Multi-step choose PI2 as the least bit of
○ E-019 speed switching programmable 8-step speed; 1 0
1 3: When [b-003] = 1,
choose PI3 as the least bit of
programmable 8-step speed;
4: When [b-003] = 1,
choose PI4 as the least bit of
programmable 8-step speed;
0: PI1~ PI4 disabled;
1: When [b-003] = 1,
choose PI1 as the least bit of
programmable 8-step speed;
2: When [b-003] = 1,
Multi-step choose PI2 as the least bit of
○ E-020 speed switching programmable 8-step speed; 1 0
2 3: When [b-003] = 1,
choose PI3 as the least bit of
programmable 8-step speed;
4: When [b-003] = 1,
choose PI4 as the least bit of
programmable 8-step speed;
0: PI1~ PI4 disabled;
1: When [b-003] = 1,
choose PI1 as the least bit of
programmable 8-step speed;
2: When [b-003] = 1,
Multi-step choose PI2 as the least bit of
○ E-021 speed switching programmable 8-step speed; 1 0
3 3: When [b-003] = 1,
choose PI3 as the least bit of
programmable 8-step speed;
4: When [b-003] = 1,
choose PI4 as the least bit of
programmable 8-step speed;
Multi-step
○ E-022
speed setting 1
0.00 ~ [b-010] 0.01 Hz 0.00
Multi-step
○ E-023
speed setting 2
0.00 ~ [b-010] 0.01 Hz 0.00
Multi-step speed
○ E-024
setting 3
0.00 ~ [b-010] 0.01 Hz 0.00

~44~
User Manual of SY5000 series AC Drive Parameter instrction

Multi-step speed
○ E-025
setting 4
0.00 ~ [b-010] 0.01 Hz 0.00
Multi-step speed
○ E-026
setting 5
0.00 ~ [b-010] 0.01 Hz 0.00
Multi-step speed
○ E-027
setting 6
0.00 ~ [b-010] 0.01 Hz 0.00
Multi-step speed
○ E-028
setting 7
0.00 ~ [b-010] 0.01 Hz 0.00
Each speed accel
○ E-029 / decel time 0 ~ 255 1 0
command
Positive/negative
0: positive characteristic;
○ E-030 characteristic
1: negative characteristic
1 0
command
Analog input
○ E-031
bias
-50.0 ~ 50.0 0.1 Hz 0.0
Analog input
○ E-032
gain
0.01 ~ 5.00 0.01 1.00
Pulse frequency
○ E-033
input eguivalent
0.10 ~ 5.00 0.01 Hz 0.10

0: the voltage between FM


and GND is about 10 V when
output highest frequency;
1: the voltage between FM
Meter output
○ E-034
command
and GND is about 5 V when 1 0
output rated current;
2: the voltage between FM
and GND is about 5 V when
output rated voltage.
Meter output
○ E-035
gain
0.50 ~ 1.20 0.01 1.00

○ E-036 Skip frequency 1 0.00 ~ [E-036] 0.01 Hz 0.00


○ E-037 Skip frequency 2 [E-036] ~ [E-038] 0.01 Hz 0.00
○ E-038 Skip frequency 3 [E-037] ~ [b-010] 0.01 Hz 0.00
○ E-039 Skip width 0.00 ~ 10.00 0.01 Hz 0.00
Motor stall 0: disabled;
○ E-040
level command 1: enabled
1 1

Motor stall
○ E-041
level
50 ~ 200 1 % 150
Power input 0: disabled;
○ E-042
start 1: enabled
1 0

~45~
User Manual of SY5000 series AC Drive Parameter instrction

Resychronization
○ E-043
waiting time
0.0 ~ 100.0 0.1 s 20.0
Slip
Х E-044 0.00 ~ 10.00 0.01 % 0.00
compensation
Constant
Х E-045 0 ~ 400 1 V 380
voltage control
0: decel stop;
1: free stop is controlled by
PI1-COM status;
2: free stop is controlled by
Free stop PI2-COM status;
○ E-046
command 3: free stop is controlled by
1 0
PI3-COM status;
4: free stop is controlled by
PI4-COM status;
5: free stop.
Emergency stop 0: disabled;
○ E-047
command 1: enabled;
1 0
0: Alarm output prohibited
when emergency stop, and
Alarm
fault relay don’t act.
○ E-048 allow when
1: Alarm output allowed
1 0
emergency stop
when emergency stop and
fault relay acts.
0: free stop;
1: stop according to decel
Emergency stop
○ E-049
mode
time 1 ([b-018]); 1 0
2: stop according to decel
time 2 ([b-021]).
Tripping mode
○ E-050 when under 0: tripping;1: disabled 1 0
voltage
0: disabled:
1: try recovery on
overcurrent (o.C) fault;
2: try recovery on
Fault trial
overvoltage (o.E) fault;
○ E-051 recovery project
3: try recovery on IPM (F.Lt)
1 0
command
fault;
4: reserved;
5: try recovery on all above
faults.
Fault trial
○ E-052
recovery time
0.1 ~ 20.0 0.1 s 10.0

~46~
User Manual of SY5000 series AC Drive Parameter instrction

Fault trial 0~8 (times)/9: always try


○ E-053
recovery times recovery faults
1 1

0: operation signal—— if
output frequency is higher than
[E-055], then open collector
between OUT-COM output low
level;
Open collector 1: frequency arrival signal——
output if output frequency is in the
Х E-054 command range of (setting frequency ± 1 0
(for SY5000-G [E-056]) , then open collector
series only) between OUT and COM output
low level;
2: overload alarm signal——
if overload fault happens,then
open collector between OUT
and COM output low level.
0: operation signal—— when
output frequency is higher than
[E-055] settings, relay closes,
otherwise disconnects;
1: frequency arrival signal
—— when output frequency
is in the range of ± [E-056]
settings, relay closes, otherwise
disconnects;
2: overload alarm signal——
when overload failure happens,
Output relay closes, otherwise
selection of disconnects;
3: operation signal in zero
relay Y1
Х E-054 speed—— when output 1 0
(for SY5000-P
frequency is 0 and still in
series only) operation status, relay closes,
otherwise disconnects;
4: under-voltage locking
signal—— When under-
voltage failure happens
(display “P.Off”), relay closes,
otherwise disconnects.
(Note: relay closing means
Y10-Y11 connecting and
Y10-Y12 disconnecting; relay
disconnection means Y10-Y11
disconnecting, and Y10-Y12
closing).

~47~
User Manual of SY5000 series AC Drive Parameter instrction

Operation
○ E-055 signal 0.01 ~ [b-010] 0.01 Hz 0.10
frequency

Speed reach
○ E-056 detection 0.0 ~ 50.0 0.1 Hz 0.0
amplitude
Keypad display
○ E-057
magnification
0.1 ~ 100.0 0.1 1.0

0: all parameters can be


modified;
1: other parameters are
Writing-
prohibited to modify, except
○ E-058 prohibited
[b-000];
1 0
command
2: all parameters are prohibited
to modify;
3~100: no operation.

Parameter 0: no operation;
initialization 1: restore all default
Х E-059 1 0
(restore parameters;
default) 2: clear all fault records.

Code table of PID regulation (group P)


Function
Description Setting range Increment Unit Default
code
PID regulation 0: disabled;
○ P-000
command 1: enabled
1 0

0: digital voltage setting ([P-002]) ;


1: digital current setting ([P-003]) ;
The reference
2: select analog voltage input V2-
○ P-001 channel
GND;
1 0
command
3: select analog current inputI
2-GND.

Digital voltage
○ P-002
setting value
0.00 ~ 10.00 0.01 V 0.00

Digital current
○ P-003
setting value
0.0 ~ 20.0 0.1 mA 0.0

~48~
User Manual of SY5000 series AC Drive Parameter instrction

0: select analog voltage input V2-


Feedback
GND;
○ P-004 value channel
1: select analog current input I2-
1 1 0
command
GND。
Feedback value
○ P-005
bias
-100.0 ~ 100.0 0.1 % 0.0

Feedback value
○ P-006
gain
0.0 ~ 10.0 0.1 1.0

Positive/
negative
0: positive characteristic;
○ P-007 characteristic
1: negative characteristic
1 0
of feedback
value
PID regulator
○ P-008
rate Kp
0.0 ~ 10.0 0.1 1.5

PID regulator
○ P-009
integration Ti
0.0 ~ 100.0 0.1 s 0.1

PID regulator
○ P-010
differential Td
0.0 ~ 100.0 0.1 s 0.0

Sample cycle
○ P-011
Ts
0.1 ~ 50.0 0.1 s 0.1

Bias limit
○ P-012 of PID 1 ~ 20 1 % 1
regulation

Display
magnification
of reference 0.1 ~ 600.0(SY5000-G series)
○ P-013
value and 0.1~100.0(SY5000-P series)
0.1 10.0
feedback
value

~49~
User Manual of SY5000 series AC Drive Parameter instrction

Code table of PID regulation (group P) (for SY5000-P series only)


0: Sleep function disabled;
1: PI1 control sleep;
2: PI2 control sleep;
3: PI3 control sleep;
4: PI4 control sleep;
PID sleep
○ P-014
control options
5: Sleep function enabled. 1 0
(Note: Sleep function disabled
if Pix does not short circuit with
COM; Sleep function enabled if
Pix short circuit with COM, x =
1,2,3,4)
PID sleep
○ P-015
delay
0.0~6000.0 0.1 s 60.0
PID sleep
○ P-016
frequency
0.00~[b-010] 0.01 Hz 0.00
PID sleep
○ P-017
wake-up value
0.00~100.00 0.01 % 0.00
PID sleep
○ P-018
wake-up delay
0.0~60.0 0.1 s 0.5

Code table of group G (for SY5000-P series)


Function Factory
Description Setting range Increment Unit
code setting
0: ‘1 to 2 function’ disabled;
1: Y1, Y2 are selected as output
terminals of ‘1 to 2 control’
function;
2: Y1, Y3 are selected as output
terminals of ‘1 to 2 control’
function;
Option of ‘1 to 3: Y2, Y3 are selected as output
Х G-000 1 0
2 control’ terminals of ‘1 to 2 control’
function.
(When [G-000]=1, settings
of [E-054], [G-010], [G-011]
disabled; when [G-000]=2, settings
of [E-054], [G-010], [G-012]
disabled; when [G-000]=3, settings
of [G-011], [G-012] disabled)
Automatic
○ G-001 switching 0 ~ 2000 1 min 0
internal time

~50~
User Manual of SY5000 series AC Drive Parameter instrction

Adding-pump
○ G-002
delay time
0.0 ~ 6000.0 0.1 s 0.0

Subtracting-
○ G-003 pump delay 0.0 ~ 6000.0 0.1 s 0.0
time
Y1 closing
○ G-004
delay
0.0 ~ 6000.0 0.1 s 0.0

Y1
○ G-005 disconnecting 0.0 ~ 6000.0 0.1 s 0.0
delay
Y2 closing
○ G-006
delay
0.0 ~ 6000.0 0.1 s 0.0

Y2
○ G-007 disconnecting 0.0 ~ 6000.0 0.1 s 0.0
delay

Y3 closing
○ G-008
delay
0.0 ~ 6000.0 0.1 s 0.0

Y3
○ G-009 disconnecting 0.0 ~ 6000.0 0.1 s 0.0
delay
Water-supply
monitoring
○ G-010
function of
0: no output 1 0
(When [G-010]=0, output of Y1 is
relay Y1
determined by [E-054] );
Water-supply 1: frequency upper limit monitoring;
monitoring 2: frequency lower limit monitoring
○ G-011
function of 3: feedback value upper limit
1 0
relay Y2 monitoring;
4: feedback value lower limit
Water-supply monitoring
monitoring
○ G-012
function of
1 0
relay Y3
Upper limit
frequency of
○ G-013
monitoring
[G-014]~b010 0.01 Hz 50.00
signal
Lower limit
frequency of
○ G-014
monitoring
0.00~[G-013] 0.01 Hz 0.00
signal

~51~
User Manual of SY5000 series AC Drive Parameter instrction

Upper limit
feedback value
○ G-015
of monitoring
[G-016]~100.00 0.01 % 100.00
signal
Lower limit
feedback value
○ G-016
of monitoring
0.00~[G-015] 0.01 % 0.00
signal

Code table of RS485 communication parameter (group R)


Function
Description Setting range Increment Unit Default
code
Communication
Х R-000 function 0: disabled;1: enabled 1 0
command
0: 19200;1: 9600;
2: 6400; 3: 4800;
Х R-001 Baud rate 1 1
4: 3840; 5: 3200;
6: 2740; 7: 2400。
Х R-002 Reserved -- -- --
Х R-003 Local address 0~31 1 0
0: output frequency;
Command 1: setting frequency;
of status 2: DC bus voltage;
Х R-004 1 0
monitoring 3: output voltage;
value 4: output current;
5: radiator temperature
Х R-005 Reserved -- -- --
Communication
Х R-006 1~500 1 1
delay time

*********************************************************
Note: * Here parameters are only enabled in fan and pump purpose inverters, and
disabled in other purpose inverters.
********************************************************

~52~
User Manual of SY5000 series AC Drive Parameter instrction

5.2 Parameter instruction

Function code of basic function (group b)


b-000 setting frequency by panel number
When all parameters of b-002 jog operation, b-003 multi-step speed running,
b-004 voltage input selection, b-005 current input selection, b-006 panel
potentiometer selection and b-007 pulse frequency given simultaneously choose
0(disabled), the inverter runs according this setting frequency. At this moment,

enter setting state of parameter b-000 panel number setting frequency, click

keys and immediately modify oprating frequency of the inverter.( ):

increasing frequency;( ): decreasing frequency

b-001 panel selection


Used to select RUN / STOP keys are enabled.
b-001 Corresponding function
Run, stop, and motional direction of the motor all are
0
determined by b-036, b-035 is disabled.
When setting terminals (1~4 correspond to PI1 ~ PI4) are
short-circuiting with COM, run and stop are controlled by
1~4
RUN/STOP keys, motional direction of the motor at this
moment is determined by b-035.
Run and stop of the motor is controlled by RUN/STOP keys,
5 motional direction of the motor at this moment is determined
by b-035.

b-002 jog command


b-027 jog frequency
b-028 jog accel/decel mode
b-029 jog accel time
b-030 jog decel time

~53~
User Manual of SY5000 series AC Drive Parameter instrction

b-002 Corresponding function


0 Jog command is disabled.
Selection terminal PI1~PI4. When selected terminal disconnects with COM,
jog operation is inenabled; when they are connected, jog operation is enabled.
1~4 When carry out jog operation, setting frequency is the value of b-027. accel and
decel at this moment is determined by b-028 ~b-030. For jog accel /decel mode,
linear type(b-028 = 0) and S-curve type(b-028 = 1) are optional.
5 Jog operation by control panel.

b-003 multi-step speed operation mode


b-003 Corresponding function
0 Multi-step speed operation is disabled.
Set a integer of 0~7 (E-019 is low post,E-021 is high post) by three virance
of E-019,E-020,E-021.
0 corresponds to multi-step speed setting default speed, 1 corresponds to multi-
1
step speed setting 1, and so on.
Thereby setting output frequency is one of 8 multi-step speed setting
frequencies.

Firstly run for some time (the time is determined by E-014) at the frequency
which is set by E-022.
Secondly run for some time (the time is determined by E-015) at the frequency
which is set by E-023.
2 Thirdly run for some time (the time is determined by E-016) at the frequency
which is set by E-024.
After that, run for some time (the time is determined by E-017) at the frequency
which is set by E-025.
Finally stop at the frequency which is set by E-025.

~54~
User Manual of SY5000 series AC Drive Parameter instrction

Similar with the way when parameter value is 2.But after run for some time (the
time is determined by E-017) at the frequency which is set by E-025. Run again
3
for some time (the time is determined by E-014) at the frequency which is set by
E-022. Carry out next cycle.

b-004 analog voltage input comand


b-004 Corresponding function
0 External analog voltage input V2 is disabled

When setting terminas(1~4 respectively corresponds to terminals PI1~PI4)


are short-circuiting with COM terminal, set frequency by external voltage
1~4
terminal V2 input signal(0~5V or 0~10V are optional (please see instruction
on control circuit terminal in Chapter 3)).

5 External analog voltage input V2 is enabled.

b-005 analog current input command


b-005 Corresponding function
0 External analog current input I2 is disabled
When setting terminas(1~4 respectively corresponds to terminals PI1~PI4)
1~4 are short-circuiting with COM terminal, set frequency by external current
terminal I2 input signal(4~20mA).
5 External analog current input I2 is enabled.

b-006 panel potentiometer command


b-006 Corresponding function
0 Panel potentiometer is disabled
When setting terminals(1~4 respectively corresponds to terminals PI1~PI4)
1~4 are short-circuited with COM, set frequency (0~highest frequency) by panel
potentiometer.
5 Panel potentiometer is enabled.

b-007 pulse frequency


When set parameter b-007 as 1, namely pulse frequency is enabled, set
output frequency as pulse frequency. For given equivalent value, please see setting
instruction of E-033 in Chapter 5.2.
Default value is 0,namely pulse frequency is disabled

~55~
User Manual of SY5000 series AC Drive Parameter instrction

b-008 base frequency


Base frequency means maximum frequency in constant torque range.
Due to factory default is 50.00 Hz, please set base frequency as 60.00Hz, if
driving frequency of the motor is 60Hz.

b-009 highest frequency


Highest frequency is allowable maximum output frequency of the inverter.
Moreover, all values of accel /decel time is the time between 0 and highest frequency.
All analog inputs (0- 10V,4- 20mA) meet the output frequency range in
proportion; if maximum frequency is 60HZ and analog input is 0-10V, 0-10V linear
corresponding frequency is 0-60HZ.

Parameter range: 25.00~650.0Hz.


Factory setting: 50.00 Hz.

b-010 upper limit frequency


If you don’t want the motor runs at above frequency, use parameter [b-010]. Use
a actual frequency value as output upper limit frequency value of the inverter, e.g.
[b-009] (maximum output frequency) is 50.00HZ.

b-011 lower limit frequency


b-012 lower limit frequency mode
0:stop mode ;1:running mode
b-013 lower limit hysteresis frequency
For adjusting external analog signal input (0~5V/10V、4~20mA)or setting

~56~
User Manual of SY5000 series AC Drive Parameter instrction

frequency by panel potentiometer, you can set upper limit frequency(b-010)and


lower limit frequency(b-011).
For input signal which is below lower limit frequency, you can select stop(b-012
= 0)or run at lower limit frequency(b-012 = 1).
b-013 can be used to set hysteresis frequency width when b-012=0.

b-012=0 b-012=1

b-014 start frequency


This parameter can best adjust start torque characteristic with torque
compensation.
If the value is set too big, sometimes over-current fault occurs.
If the operation frequency is lower than start frequency, it will decrease to
operation frequency as soon as output reaches start frequency.

*********************************************************
*Note: if b-014 is too big, the motor may overheat or the inverter may alarm “OC”
.
*********************************************************

~57~
User Manual of SY5000 series AC Drive Parameter instrction

b-015 accel/decel time command


b-016 accel/decel mode1
0:linear mode ;1:S-curve mode
b-017 accel time1
b-018 decel time1
b-019 accel/decel mode 2
0:linear mode ;1:S-curve mode
b-020 accel time 2
b-021 decel time 2
b-015 Corresponding function
Select accel / decel time 1, accel /decel time and mode are determined by
0
b-016,b-017,b-018.
Select terminals of PI1~PI4. If selected terminal disconnects with COM,
select accel / decel time 1,accel / decel time and mode are determined by
1~4 b-016,b-017,b-018;
If selected terminal connects with COM, select accel /decel time 2, accel
/decel time and mode are determined by b-019,b-020,b-021.
Select accel /decel time 2, accel/decel time and mode are determined by
5
parameters of b-019,b-020,b-021.

~58~
User Manual of SY5000 series AC Drive Parameter instrction

For accel/decel mode, linear mode and S-curve mode are optional. Accel time
is defined as the required time when output frequency increases from 0 to highest
frequency; decel time is defined as the required time when output frequency increases
from highest frequency to 0.

b-022 torque compensation voltage mode


b-023 torque compensation voltage value

Torque compensation can compensate insufficient torque at low speed, as shown


in above figures.
*********************************************************
Note: If b-023 is too big, the motor may overheat or the inverter may alarm “ OC”.
*********************************************************

b-024 function command of electronic thermal relay


0: disabled; 1: enabled
b-025 electronic thermal relay level
When b-024 = 1, set action level of electronic overheat protection according to
rated current of the motor, as shown in the below figure.
When b-025 = 100(%), if output current equals 150% rated current for 1
minutes,overload protection acts. When b-024 = 0, protection function of electronic
thermal relay is disabled

~59~
User Manual of SY5000 series AC Drive Parameter instrction

*********************************************************
*Note: When drive multiple motors or rated current of the motor is low than b-025, it
will not protect the motor. At this time, please configure thermal protection relay for
each motor.
*********************************************************
b-026 PWM carrier frequency
Properly adjusting the value of this parameter can avoid resonance between
inverter and current or the machine with load, and change electromagnetic nosie of
the motor.
Carrier frequency 1-16 KHz is adjustable in SY-5000-G series inverters.
b-031 DC braking duration
This parameter decides DC braking time when the motor stops.
b-032 DC braking when stop
b-032 Corresponding function
0 DC braking is inenabled when stop.
When setting terminals (1~4 respectively corresponds to terminals
of PI1~PI4) is short-circuiting with COM terminal, short-circuiting
1~4
or disconnection status control DC braking enabled or inenabled
when stop.
5 DC braking is enabled when stop.

b-033 DC braking start frequency


When output frequency reaches setting frequency during the decel, DC braking
will start.

~60~
User Manual of SY5000 series AC Drive Parameter instrction

b-034 DC braking voltage


DC braking function can make the motor stop during the motor decel. It displays
“dC.on”when DC braking. When both of b-031 and b-032 are not 0, DC braking
function is enabled during decel. Parameter of b-033 is the frequency when DC
braking starts during decel.
If b-031=0.0 or b-032 = 0, DC braking function is inenabled when stop. All
keypad signals are inenabled during DC braking. Braking progress is shown in below
figure. DC braking voltage is determined by the setting value of b-034.
Must add DC braking and make leaf blades completely static, because leaf
blades may not completely stop rotating before running in fan loads. At this time, set
the value of b-040 according to different loads. If it is used for pump loads, no need
DC braking before start running. At this time, make sure b-040= 0.0, namely no DC
braking before start.

~61~
User Manual of SY5000 series AC Drive Parameter instrction

b-035 motor direction


The function is enabled only when b-001 is 5 (namely panel control enabled),
and the parameter is used to decide motor motional direction. The function is
inenabled when b-001 is 0 (namely panel control inenabled), and the parameter setting
is inenabled (please see setting instruction of b-001).
b-035 = 0:commanding motor rotating forward;b-035 = 1:commanding
motor rotating reversely
Default is 0, namely commanding motor rotating forward.
b-036 SF,SR terminal function
If b-001 is 0, namely when panel control inenabled, run/stop and motional
direction is controlled by SF, SR terminals.
(1)FWD-REV mode(b-036 = 0)
SF,SR terminal status Motor status
SF-COM connect,SR- COM disconnect Forward running
SF- COM disconnect,SR- COM connect Reverse running
Both of SF- COM, SR- COM disconnect Stop running(inverter standby)
Both of SF- COM, SR- COM are connect Stop running(inverter standby)

Forward

Reverse

(2)RUN/ FWD-REV mode(b-036 = 1)


SF、SR terminal status Motor status
SF- COM connect,SR- COM disconnect Forward running
SF- COM,SR- COM connect Reverse running
SF- COM,SR- COM disconnect Stop running(inverter standby)
SF- COM disconnect,SR- COM connect Stop running(inverter standby)

(3)FWD-REV/ self-sustaining mode(b-036 = 2)

~62~
User Manual of SY5000 series AC Drive Parameter instrction

In this mode, if you want to stop running, there must be to maintain the signal
input of PI1 terminal.

SF、SR and X1 terminal status Motor status


only SF-COM has pulse signal and PI1-COM
Forward running
disconnect
only SR-COM has pulse signal and PI1-COM
Reverse running
disconnect
Both of SF-COM and SR-COM have pulse signals
Stop running(inverter standby)
and PI1-COM disconnect
PI1-COM pulse close signal Stop running(inverter standby)

Forward

Reverse

Stop

b-037 fan mode


Four kinds of fan control mode can be selected according to different cooling
conditions:
①normal switch mode(b-037 is set as 0):Inverter with output, the fan starts
running; inverter without output, the fan stop running after delay;
②automatic switch mode(b-037 is set as 1):When radiator temperature raises
to higher than 40℃, the fan starts running; when radiator temperature declines lower
than 30℃, the fan stops running;
③always open mode(b-037 is set as 2):No matter what state the inverter is, the
fan still runs;
④always close mode(b-037 is set as 3):No matter what state the inverter is, the
fan still does not run.
Default is 0,namely normal switch mode.

~63~
User Manual of SY5000 series AC Drive Parameter instrction

b-038 reverse command


0:Motor can be reversed
1:Motor can not rotates reversely and all commands can make the motor
rotates forward;
b-039 SF, SR input filter factor
It is designed for the suppression of system interference.When using the SF, SR
terminals control frequent forward and reverse of inverter, if the value is bigger, the
filter is stronger, but the inverter will response slowly. It is suggested to set under the
guidance of the manufacturer.
b-040 DC braking duration before start
Determine DC braking duration time before start according to different load
conditions, which is the value of parameter b-040. It is being noted that:
(1)If use for pump loads, don’t need DC braking before start, at this time set
this parameter as 0.0, namely no DC braking before start.
(2)Functions of parameter b-040 and b-031(DC braking duration)are
independent, the two will no affect each other.

Extended function (group E)


E-000 frequency setting
Display top-class setting frequency according to priority, unit: Hz.
Because this operation can be done during stop period, it can be used to check
setting input signal.
E-001 given value
PID regulation function is enabled, that is to say, when [P-000] = 1, [P-013]
= 10, the value of [E-001] is the percentage of setting value in maximum value, as
shown at below:
[E-001] =(when [P-013] = 10, [E-001])×[P-013]
E-002 feedback value
PID regulation function is enabled, that is to say, when [P-000] = 1,[P-013] =
10, the value of [E-002] is the percentage of feedback value in maximum value, as
show at below:
[E-002] =(when [P-013] = 10, [E-002])×[P-013]
E-003 output frequency
display output frequency of the inverter,unit:Hz

~64~
User Manual of SY5000 series AC Drive Parameter instrction

E-004 output voltage


display inverter output voltage value,unit:V
E-005 output current
display inverter output current value is enabled,unit:A
E-006 DC bus voltage
display DC voltage of main circuit,unit:V
E-007 radiator temperature
display current radiator temperature,unit:℃
E-008 total running time of the inverter
display total running time of the inverter,unit:hour
E-009 display of terminal input signal
display current terminal status:
Short
与 CM circuit
端子短接 with CM terminal

与 CM 端子断开
Disconnect with CM terminal
EMS RST SF SR PI4 PI3 PI2 PI1

E-010 fault code of last time


display fault code of this time
E-011 fault code of second-to-last time
display fault code of second-to-last time
E-012 fault code of third-to-last time
display fault code of third-to-last time
E-013 fault code of fourth-to-last time
display fault code of fourth-to-last time
*********************************************************************
*Note: E-000 ~ E-013 are relevant display when the inverter is in operation, read only,
can’t be modified.
*********************************************************************
E-014 cycle operation duration 1
E-015 cycle operation duration 2
E-016 cycle operation duration 3
E-017 cycle operation duration 4
E-018 cycle operation direction
E-019 multi-step speed switching 1
E-020 multi-step speed switching 2

~65~
User Manual of SY5000 series AC Drive Parameter instrction

E-021 multi-step speed switching 3


E-022 multi-step speed setting 1
E-023 multi-step speed setting 2
E-024 multi-step speed setting 3
E-025 multi-step speed setting 4
E-026 multi-step speed setting 5
E-027 multi-step speed setting 6
E-028 multi-step speed setting 7
E-029 each step speed accel/decel time selection
When b-003 = 1, set frequency by terminal state combination which is selected
by E-019, E-020、E-021. There are 8 state combination, respectively corresponds
to 1~8 steps speed. (As shown in the following table, 1 represents short-circuiting
between corresponding terminal and COM, 0 represents disconnection between
corresponding terminal and COM.

E-021 E-020 E-019 Corresponding running section

Default frequencies
0 0 0 (b-004=0:panel potentiometer setting frequency;
b-004=5: external potentiometer setting frequency)

0 0 1 Step 1(E-022)
0 1 0 Step 2(E-023)
0 1 1 Step 3(E-024)
1 0 0 Step 4(E-025)
1 0 1 Step 5(E-026)
1 1 0 Step 6(E-027)
1 1 1 Step 7(E-028)
When set b-003 as 2 or 3, No.1~ 4 step speed automatic cycle operation (2 is
single cycle, 3 is repeat cycle). Accel /decel time of each step speed is determined
by E-029. When b-003 is not 0 and b-001=5, direction of multi-step speed operation
is determined by the value of E-018. Firstly confirm the corresponding binary value
according to direction(0:forward;1:reverse) of each step speed, as shown in
the follow figure. Then change to decimal system, namely E-018. When b-003 is not
0 and b-001 = 0, operation direction of each step speed is determined by states of SF,
SR terminals, and it is unrelated with E-018.

~66~
User Manual of SY5000 series AC Drive Parameter instrction

E.g. as known in below figure, E-018 should set as (10101100)2, namely


172.

When b-003 = 1, setting frequency of default step speed is determined by


panel potentiometer(b-004 = 0) or external potentiometer (b-004 = 5), and
corresponding frequency values of other each step speed are determined by E-022 ~
E-028.
Accel /decel times of first step speed are determined by b-015 ~ b-021, and accel
/decel time of other each step speed is determined by the value of E-029.

~67~
User Manual of SY5000 series AC Drive Parameter instrction

The following is multi-step speed operation diagram when b-003 = 1, b-004 = 0,


E-019 = 1, E-020 = 2, E-021 = 3, E-018 = 0.

When [b-003] ≠ 0, accel/decel time of multi-step speed operation is selected by


the value of [E-029]:
Firstly ensure corresponding binary value according to accel /decel time (0:
select accel /decel time 1([b-017], [b-018]);1:select accel /decel time 2([b-020],
[b-021])of each step speed,
Then change into decimal system, namely [E-029].

~68~
User Manual of SY5000 series AC Drive Parameter instrction

E.g. as known in below figure, [E-029] should set as (10101100)2, namely


172.

*********************************************************
*Note: When b-003 = 3, properly setting relevant parameters can reach the function
of wobbing frequency.
*********************************************************

~69~
User Manual of SY5000 series AC Drive Parameter instrction

E-030 positive characteristics / negative characteristic


E-031 analog input bias
E-032 analog input gain
E-030 is used to select positive/ negative characteristics when set frequency
method by external analog input (analog voltage input0~5V/10V, external analog
current input 4~20mA, panel potentiometer).

0——positive characteristic;1—— negative characteristic

When set frequency by external analog signal input (0~5V/10V,4~20mA) or


panel potentiometer, you can set output frequency by adjusting values of E-031 and
E-032.
Initial settings of inverter: input: 0~5V, corresponding output frequency: 0 ~
highest frequency(50.00 Hz),
Input-output characteristic curve (see below left figure) can be expressed at

below: ,
X means input voltage,Y means output frequency,at this time, bias
E-031 = 0.0,gain E-032 = 1.00.

~70~
User Manual of SY5000 series AC Drive Parameter instrction

For example: set frequency by external analog voltage input, now require output
frequency 0 ~ 50.00 Hz which is corresponded to input 1 ~ 4V, so input output
characteristic curve (see above right figure) at this time can be expressed at below:

X means input voltage, Y means output voltage


E-031、E-032 are set according to below formula:

.
E-033 pulse frequency
When b-007 = 1, namely select setting frequency as pulse signal given, when
detect a rising edge in PI3 terminal, output frequency increases a equivalent which
is determined by E-033; when detect a rising edge in PI4 terminal, output frequency
decreases a equivalent which is determined by E-033.
*********************************************************
* Note: When set b-007 as 1, PI3, PI4 terminals can not be used for other purposes.
*********************************************************
E-034 meter output command
E-035 meter output gain

+
FM

_
GND

~71~
User Manual of SY5000 series AC Drive Parameter instrction

By connecting frequency meter or voltage meter, it can remotely monitor output


frequency or output current of the inverter.
Please connect a meter (resistance is more than 2KΩ) which full scales is 10V,
manximum allowable output current is 10mA.
E-034 = 0:When output highest frequency, output voltage between FM-COM is
10V;
E-034 = 1:When output rated current, output voltage between FM-COM is 5V.
Due to effect of load change, output current will contain ±15% bias;
E-034 = 2:When output rated voltage, output voltage between FM-COM is 10V.
By setting E-035, it can adjust output voltage, so don’t need connect the variable
resistor for the use of full-scale calibration. Maximum output voltage is about 10.6V.
E-036 skip frequency 1
E-037 skip frequency 2
E-038 skip frequency 3
E-039 skip frequency width

Skip frequency function is mainly used to prevent mechanical vibration of the


load (noise) and avoid occurrence of resonance.
(1)Jump point can be set up to 3, namely E-036, E-037, E-038。
(2)When jump width(E-039)is set as 0.00 Hz, jump is disabled
(3)Three skip frequency ranges can overlap, but make sure E-036<E-037<
E-038,the skip frequency overlap region will be consolidated.
(4)This function applies to various situation of frequency settings.
E-040 motor stall level selection
E-041 motor stall level
E-040 = 1, the function of prevention current stall is enabled.

~72~
User Manual of SY5000 series AC Drive Parameter instrction

As show in below figure, stop frequency rising once output current is beyond
stall prevention level (E-041) in accel, and immediately adjust accel time and again
accelerate once the current declines, thus prevent over-current stall.
Therefore, actual accel time is often longer than setting accel time when enable
this function.
Otherwise, when the motor runs at the setting frequency, it automatically decline
output frequency once the current beyond stall level, so control output current lower
than stall level.
When E-040 = 0, the function of preventing current stall is disabled

E-042 power input start


When b-001 = 5, namely RUN/STOP keys contro run/stop of the motor, the
inverter immediately runs at setting frequency after connecting power supply, only
need set parameter E-042 as 1. When E-042 = 0, this function is disabled

E-043 resychronization waiting time


Users set free stop, its waiting time thus determined.

E-044 slip compensation

~73~
User Manual of SY5000 series AC Drive Parameter instrction

Slip compensation function makes output frequency changes according to load


changes, therefore control motor speed at fixed value, as shown in above figure. If
E-044= 0.00,slip compensation function is disabled.
*********************************************************
*Note: This function is enabled only when motor power is the same as inverter power.
*********************************************************
E-045 constant voltage control

Constant voltage control function can automatically control output voltage at the
constant value when power voltage changes. Don’t need to adjust V/F characteristic
or change rated voltage of the motor, even if different input voltage areas.
Default is set as 380V(3-phase 380V series)/220V(1-phase 220V series)
*********************************************************
*Note: this function can’t increase output voltage higher than input power’s voltage.
*********************************************************
E-046 free stop selection
Two stop methods: decel stop and free stop. Free stop is also enabled for external
terminal.
E-046 = 0:decel stop;
E-046 = 1~4:use external terminals of PI1~PI4 to free stop——if selected
terminal connects with COM, free stop and display “FrEE”;if selected
terminal disconnects with COM, decel stop when there are stop signals;
E-046 = 5:free stop and display “FrEE”.
Free stop waiting time is determined by parameter of E-043.
E-047 input permission when emergency stop.

~74~
User Manual of SY5000 series AC Drive Parameter instrction

E-048 alarm permission when emergency stop


E-049 stop mode when emergency stop
When E-047 = 1, namely emergency stop input is allowable, free stop at the
parameter of E049 or at methods of decel time 1(E-049 = 1)或decel time 2(E-049
= 2)when EMS terminal is connected.
When E-047 = 0,EMS terminal input signal is disabled When E-048 = 1,
namely emergency stop alarm is allowable, the inverter issues fault alarm, and fault
relay acts; when E-048 = 0, fault relay output doesn’t act.
E-050 tripping mode when under voltage
When input voltage declines, select motor stop mode by this parameter.
E-050 = 0—— free stop method: free stop when DC bus voltage is lower than
400V(3-phase 380V series)or 210 V(1-phase 220V series), meanwhile display
“P.oFF”.
E-050 = 1——decel stop mode: motor will decelerate to stop when DC bus
voltage is lower than 400V(3phase 380V series) or 210V(1-phase 220V series).
In some cases, the inverter can continue to run by using renewable energy of the
motor when instantaneous power outage happens.
E-051 fault trial recovery project selection
E-052 fault trial recovery time
E-053 fault trial recovery times
You can use trial recovery function when protection function activates inverter
tripping. Parameter of E-051 can be set trial recovery on what kind of faults.
E-051 = 0:Fault trial recovery function is inenabled;
E-051 = 1:try recovery on overcurrent fault(o.C.);
E-051 = 2:try recovery on overvoltage fault(o.E.);
E-051 = 3:try recovery on IPM(F.Lt);
E-051 = 4:reserved;
E-051 = 5:try recovery on all faults.
For the selected fault, after a period of time (parameter E-052), trial recovery
function automatically restore, check speed, synchronize and run again. The number
of trial recovery actions can be set to 0~8 or 9. If it cannot recover to run in setting
times, it will be forced tripping and displays final tripping reason. If it take stop
opration during trial receovery operation, this operation will interrupt. E-053 = 9
means always carrying out fault trial recovery.

~75~
User Manual of SY5000 series AC Drive Parameter instrction

*********************************************************
*Note:
(1) When rare fault occurs and it is difficult to do reset operation, please try fault
recovery.
(2) If faults always happen, we must firstly check out reasons;
(3) If the load inertia is very large, sometimes unable to use trial recovery functions.
(4) Although there is always the function of trial recovery fault, you must carefully
the characteristic of mechanical equipment before using the function. When can
not start with a load or immediate alarm once no output of inverter, do not use
this function.
*********************************************************
E-054 open collector output selection
E-055 operations signal frequency
E-056 speed reaches detection amplitude
Example of terminal connection

Output signal (terminal OUT) of open colletor can be any one of operation
signal, speed arrival signal and overload alarm signal.
Factory setting is operation signal. Value of E-054 : 0 —— operation signal; 1
—— frequency arrival signal; 2 —— overload alarm signal.

~76~
User Manual of SY5000 series AC Drive Parameter instrction

Operation signal——if set E-054 as 0, output of terminal OUT is operation


signal. Here you can set the operation frequency (E-055).
If output frequency is higher than operations signal frequency, open collector
output is low level, as shown in above figure.
Frequency arrival signal——if set E-054 as 1, output of OUT terminal is
frequency arrival signal. Here you can set the frequency arrival checkout amplitude (
E-056).
When output frequency is in the range of (setting frequency±speed arrival
checkout amplitude), open collector output (OUT terminal) is low level, as
shown at below.

Overload alarm signal——if set E-054 as 2,output of OUT terminal is overload


alarm signal. At this time, if overload fault occurs, open collector output (OUT
terminal)is low level.

E-057 free magnification of panel display


Change output frequency display on operation panel into angular velocity or
linear velocity through setting this parameter.
Display value = output frequency×[E-057].

~77~
User Manual of SY5000 series AC Drive Parameter instrction

E-058 written prohibition selection


This parameter is used to prevent data from being mistakenly modified:
E-058 = 0:All parameters are allowed to be rewritten;
E-058 = 1:Other parameters are prohibited to be modified, except b-000;
E-058 = 2:All parameters are prohibited to be rewritten.
If you try to modify parameters under read only state, it will display“-.Err”.
*********************************************************
*Note:In the state of E-058 = 0, although all parameters are allowed to be modified,
some parameters are not allowed to be modified in operation. At this moment, it
will immediately display “¬-.Err” when you try to change parameters. Pleasemodify
parameters after stop the motor.
*********************************************************
E-059 parameter initialization
E-059 = 0——Reserved;
E-059 = 1——All parameter values will be restored to factory settings;
E-059 = 2——Clear all fault information which is recorded by the system.
After initialization, the system will automatically reset this parameter as 0.
E-054 output selection of relay Y1 (for SY5000-P series only)
E-055 operation signal frequency (for SY5000-P series only)
E-056 speed arrival detection amplitude (for SY5000-P series only)
Output of relay Y1 can be any one of operation signal, speed arrival signal or
overload alarm signal. Factory setting is operation signal. Value of [E-054]: 0——
operation signal; 1——frequency arrival signal; 2——overload alarm signal.
Operation signal——if [E-054] setting is 0, output of relay Y1 is operation signal
and operation frequency can be set here ([E-055]). Relay Y1 closes when output
frequency is higher than operation signal frequency, otherwise disconnects.
Frequency arrival signal——if [E-054] setting is 1, output of relay Y1 is
frequency arrival signal and frequency arrival detection amplitude can be set here
([E-056]) . Relay Y1 closes when output frequency is in the range (setting frequency
± speed arrival detection amplitude), otherwise disconnects.
Overload alarm signal——if [E-054] setting is 2, output of relay Y1 is overload
alarm signal. Relay Y1 closes when overload failure happens otherwise disconnects.
Zero speed operation signal——if [E-054] setting is 3, output of relay Y1 is AC
Drive zero speed operation signal. Relay closes when output frequency equals to 0

~78~
User Manual of SY5000 series AC Drive Parameter instrction

and still is under operation status, otherwise disconnects.


Under-voltage locking signal——if [E-054] setting is 4, output of relay Y1 is
under-voltage locking signal. Relay Y1 closes when under-voltage failure (display
‘P.oFF’) happens otherwise disconnects.
(Note: relay closing means Y10, Y11 connecting, Y10, Y12 disconnecting; relay
disconnecting means Y10, Y11 disconnecting, Y10, Y12 closing.)

Parameter code of PID regulation (group P)


P-000 PID regulation selection
When this parameter is 0 , PID regulation is inenabled;when this parameter is 1 ,
PID regulation is enabled。PID regulation diagram is as shown at below.
P-001 given quantity channel selection
This parameter is used to select setting method of given value:
[P-001] = 0:given value is setting voltage value of [P-002];
[P-001] = 1:given value is setting current value of [P-003];
[P-001] = 2:given value is analog voltage input V2-GND;
[P-001] = 3:given value is analog current inputI2-GND。
P-002 digital voltage setting value
When [P-001] = 0, given value controlled by PID is determined by this
parameter value.
P-003 digital current setting value
When [P-001] = 1, given value controlled by PID is determined by this
parameter value.
P-004 feedback value channel selection
This parameter is used to select setting method of feedback value:
[P-004] = 0:Feedback value is analog voltage input signal V2-GND;
[P-004] = 1:Feedback value is analog current input signal I2-GND.
*********************************************************
* Note:[P-004] and [P-001] selected channels can not be repeated.
*********************************************************
P-005 feedback value bias
P-006 feedback value gain
P-007 positive/negative characteristics of feedback value
[P-005] ~ [P-007] are used to feedback calculation value when PID regulates.
When actual feedback value can’t meet PID regulation requirement, you can adjust

~79~
User Manual of SY5000 series AC Drive Parameter instrction

by setting these three parameter values.


P-008 PID regulator proportion Kp
P-009 PID regulator integral Ti
P-010 PID regulator differential Td
P-011 Sampling period Ts
Bigger [P-008] will help speed up the system response, but it will generate
agitation if it is too big and the response is slow if it is too small.
The response is slow and control ability to external interference goes off if
[P-009] value is too big. The response is quick but it will generate agitation if it is too
small. If [P-009] is set as 0.0, the integral doesn’t work.
Bigger [P-010] will help speed up the system response and reduce agitation, but
control ability to external interference will go off. At present [P-010] is reseved, its
value has no impact on the inverter operation.
[P-011] sampling time which is used to set feedback value
P-012 bias limit of PID regulation

If relative bias value of closed loop system is bigger than setting value of bias
limit, namely bigger than +[P-012] % or less than -[P-012] %,then use PID
regulator to adjust.
If relative bias value of closed loop system is in the setting range [-[P-012] %,
+[P-012] % ] of bias limit, PID regulator stops to adjust, and output of PID regulator
is unchanged, as shown in below figure.

~80~
User Manual of SY5000 series AC Drive Parameter instrction

~81~
User Manual of SY5000 series AC Drive Parameter instrction

P-013 display magnification of given value and feedback value


PID regulation function is enabled, namely When [P-000] = 1 and [P-013] = 10,
[E-001] value is the percentage of setting value in maximum value, then [E-001] value
is displayed according to blow equality:
[E-001] =(When [P-013] = 10, [E-001] value)×[P-013]

PID regulation function is enabled, namely When [P-000] = 1 and [P-013] = 10,
[E-001] value is the percentage of setting value in maximum value, then [E-001] value
is displayed according to blow equality:
[E-002] =([E-002] value when [P-013] = 10)×[P-013]

PID regulation (group P) (for SY5000-P series only)


P-014 PID Sleep control selection
P-015 PID Sleep delay
P-016 PID Sleep frequency
P-017 PID Sleep wake-up value
P-018 PID Sleep wake-up delay
In the case of valid PID regulation, [P-014] is used to select sleep function
valid or not. In the case of valid sleep function, sleep function start up when output
frequency is lower than [P-016] setting; PID regulation stops after [P-015] setting
duration time, and AC Drive output frequency reduce to 0.00 which means stop into
sleep status.
Sleep wake-up function starts up when feedback value is higher than [P-017]
setting; PID regulation starts up after [P-018] setting duration time, and AC Drive
output frequency induces from 0.00 and finish sleep status into normal running status.
Note: Under these conditions, if Y1,Y2 are used as subtracting-pump signal,
sleep function starts up only when on adding-pump signal, otherwise not into sleep
status.

Group G code (for SY5000-P series only)


********************************************************************
* Note: Ensure PID regulation function enabled before using ‘1 to 2 control’ function,
namely P-000 = 1.
********************************************************************

~82~
User Manual of SY5000 series AC Drive Parameter instrction

G-000 ‘1 to 2 control’ function


G-001 automatic switching internal time
G-002 adding-pump delay time
G-003 subtracting-pump delay time
Use [G-000] to select ‘1 to 2 control’ function. ‘1 to 2 control’ function means
that an AC Drive automatically control two motors according to feedback value. So
that PLC was spared to greatly simplify external circuits and relevant devices.
Firstly start up an AC Drive, then run another motor under power frequency
when meet any one of following situations: (1) output frequency equals to or higher
than upper limit frequency and duration time reaches [G-002] settings; (2) feedback
value is lower than or equals to lower limit value and duration time reaches [G-002]
settings. Then AC drive decelerates to lower limit frequency and carries out PID
regulation.
Automatically stop running motor under power frequency when meet any one
of following situations: (1) output frequency equals to or is lower than lower limit
frequency and duration time reaches [G-003] settings; (2) feedback value is higher
than or equals to upper limit value and duration time reaches [G-003] settings. Then
AC Drive accelerates to upper limit frequency and carries out PID regulation.
In the moment of adding a pump, decelerating the motor will effectively smooth
sudden water pressure rise away. In the moment of subtracting a pump, accelerating
the motor will effectively smooth sudden water pressure drop. As shown in following
figure.

~83~
User Manual of SY5000 series AC Drive Parameter instrction

If only an AC Drive is running and constant running time reaches [G-001]


settings, stop the motor and switch over to another motor.

G-004 Y1 closing delay


Y10, Y11 connection delay time (Y10, Y12 disconnect)
G-005 Y1 disconnecting delay
Y10, Y1disconnection delay time (Y10, Y12 connect)
G-006 Y2 closing delay
Y20, Y21 connection delay time (Y20, Y22 disconnect)
G-007 Y2 disconnection delay
Y20, Y21 disconnection delay time (Y20, Y22 connect)
G-008 Y3 closing delay
Y30, Y31 connection delay time (Y30, Y32 disconnect)
G-009 Y3 disconnection delay
Y30, Y31 disconnection delay time (Y30, Y32 disconnect)
G-010 water-supply monitoring function
G-011 water-supply monitoring function of relay Y2
G-012 water-supply monitoring function of relay Y3
G-013 upper limit settings of monitoring signal
G-014 lower limit settings of monitoring signal
G-015 upper limit feedback value settings of monitoring signal
G-016 lower limit feedback value settings of monitoring signal

~84~
User Manual of SY5000 series AC Drive Parameter instrction

G-010~G012 Corresponding signal


0 Water-supply monitoring disabled
1 Frequency upper limit monitoring
2 Frequency lower limit monitoring
3 Upper limit monitoring of feedback value
4 Lower limit monitoring of feedback value

If [G-010]/[G-011]/[G-012] = 0, water-supply function is disabled and relay


disconnects all along. (Note: when G-010 = 0, Y1 output is determined by [E-054]
settings)
If [G-010]/[G-011]/[G-012] = 1, Y1/Y2/Y3 output is upper limit value of
output frequency. Monitoring signal is determined by [G-013] settings. When output
frequency is higher than [G-013] settings, Y1/Y2/Y3 closes, otherwise disconnects.
If [G-010]/[G-011]/[G-012] = 2, Y1/Y2/Y3 output frequency is lower limit
value of frequency monitoring. Monitoring signal is determined by [G-014] settings.
When output frequency is higher than [G-014] settings, Y1/Y2/Y3 closes, otherwise
disconnects.
If [G-010]/[G-011]/[G-012] = 3, Y1/Y2/Y3 output is upper limit value of
feedback value monitoring.. Monitoring signal is determined by [G-015] settings.
When feedback value is lower than [G-015] settings, Y1/Y2/Y3 closes, otherwise
disconnects.
If [G-010]/[G-011]/[G-012] = 4, Y1/Y2/Y3 output is lower limit value of
feedback value monitoring. Monitoring signal is determined by [G-016] settings.
When feedback value is lower than [G-016] settings, Y1/Y2/Y3 closes, otherwise
disconnects.
Note: Relay Yx closing means Yx0, Yx1 closes, Yx0, Yx2 disconnects; relay Yx
disconnecting means Yx0, Yx1 disconnects, Yx0, Yx2 closes. (x = 1, 2, 3)

MODBUS communication parameter code (group R)


These parameters are used for MODBUS communication. For communication
protocol, please see Appendix1 -- MODBUS communication protocol.
[R-000]: communication function selection
0: disabled;
1: enabled.

~85~
User Manual of SY5000 series AC Drive Parameter instrction

[R-001]: baud rate


0: 19200
1: 9600
2: 6400
3: 4800
4: 3840
5: 3200
6:2740
7:2400
[R-002]: reserved
[R-003]: local address

This parameter is used to set the site address when RS485 communicates, and the
inverter only receives host computer data which is consistent with the site.
[R-004]: selection of status monitoring value
0: output frequency
1: setting frequency
2: DC bus voltage
3: output voltage
4: output current
5: radiator temperature
This parameter is used to read PZD data.
[R-005]: reserved
[R-006]: communication delay time
This parameter is used to set communication delay time,interval time which
is between inverter complete receiving data and starting to send data to the host
computer.

~86~
User Manual of SY5000 series AC Drive Commissioning

Chapter 6 Commissioning

Danger

1. After install terminal housing, switch on input power.


Do not disassemble the housing when power on. Risk of electic shock.
2. Do not close to equipments if set power input-start function on the inverter,
because the inverter will suddenly re-start when power on. Risk of injury.
3. Please connect emergency stop switch (Stop key is only valid when set
keyboard running). Risk of injury.

Caution

1. Please confirm once again allowable use range of electrical and mechanical
equipments. Risk of injury.
2. Do not check signal when running.

6.1 Commissioning procedure


Commissioning procedure is shown in Figure 6-1.

Figure 6-1 Commissioning procedure


6.2 Commissioning operation
6.2.1 Switch on power supply
Precautions before switch on power supply
 Voltage of power supply is correct or not
220V series:1PH AC 220V,50/60Hz
380V series:3PH AC 380V-440V,50/60Hz
 Input power cord is whether connected with input terminal of inverter or not.
 Connect output terminals of inverter U, V, W with input terminal of the
motor
 Correctly connect control loop terminal with control equipments.
 The status of load motor is no load.

~87~
User Manual of SY5000 series AC Drive Commissioning

 Switch on power when above settings are correct.


 , output terminal of DC bus voltage of inverter,
the third ground terminal
If the inverter damages due to above wiring error, it is not in the range of quality
guarantee.
6.2.2 Energization status confirmation
After the power is on, LED displays as 0 if works normally, as shown in Figure
6-2.RUN indicator and ERR indicator both extinguish.

Figure 6-2 LED normal display


When the input voltage is very low, after power on, LED displays P.oFF and
blinks, as shown in Figure 6-3. Meanwhile ERR indicator lights and blinks.

Figure 6-3 LED under-voltage display


After power-on, please refer to fault instructions in chapter 7 if there is other
abnormal display.
6.2.3 No-load operation
When the motor is in no-load state, use keypad to set the parameters, and
commission the motor.
 Set basic frequency
Default basic frequency of inverter is 50.00Hz. Before commissioning, please
make sure that parameter value of function code b-008 (basic frequency) equals
rate frequency of motor which is 50.00HZ.
 Start inverter
① Modifty the parameter value of b-000 form 0.00 to 50.00
② Press RUN key of control panel and release, the motor start rotating until it
reaches the setting frequency.
③ Observe the rotation direction of motor is whether correct or not, if wrong,
exchange any two connect cables of output terminal U,V,W of inverter.
④ Change b-035 from 0 to 1. And the motor reverse totates until reaches the

~88~
User Manual of SY5000 series AC Drive Commissioning

setting frequency.
⑤ In operation, enter the status of b-000, click ▲▼ keys, and can immediately
change motor rotation speed.
⑥ Click STOP key of control panel, the motor speed declines and then stop
rotating.
⑦ Set b-002 as 5, b-027 as 10.00Hz. Press RUN key and release, the inverter
runs to output frequency as 10.00Hz, and the motor rotates according to current
setting direction.
 Observation of running status
① Change frequency command or rotation direction, and observe whether there
is vibration and noise of the motor.
② Please confirm the inverter whether works normally or not.
6.2.4 Load operation
After the motor works normally with no load, connect the load, and commission
with load.
 Connect machanical load
① After the motor stops, connect mechanical load.
② Fastening screw, so that mechanical load fixed on the motor shaft.
 Start inverter
① Use control panel to start the inverter. It is the same as no load.
② Change parameter value of b-035 from 0 to 1. And the motor reverse totates
until reaches the setting frequency.
③ In operation, enter the parameter setting status of b-000, click ▲▼ keys,
and can immediately change motor rotation speed.
④ Click STOP key of control panel, the motor speed declines and then stop
rotating.
⑤ Set parameter value of b-002 as 5, b-027 as 10.00Hz. Press RUN key and
release, the inverter runs to output frequency as 10.00Hz, and the motor rotates
according to current setting direction.
 Observation of running status
① Make sure that the running direction of mechanical load is whether correct
or not.
② Change frequency command or rotation direction, and observe whether there
is vibration and noise of the motor.
③ When running, please switch to E-005 function code to see if the motor
current is excessive.

~89~
User Manual of SY5000 series AC Drive Toubleshooting

Chapter 7 Troubleshooting

After detecting anomaly of inverter, protection circuit and fault output relay
work and display fault and stop running. Please be sure to find fault reasons and
corresponding countermeasures, and run again after troubleshooting.

7.1 Protection function


Table 7-1 Protection function
Item Function
Over-current When output current exceeds 200% of inverter rated current, cut off
protection (o.C.) inverter output and stop running.

When renewable energy of motor decel make main circuit DC voltage


Over-voltage
raise above 400V (1ph 220V series) or 800V (3-ph 380V series), cut
protection (o.E.)
off the output and stop running.
Intelligent power
module protection When IPM fault happens, cut off output and stop running.
(F.Lt)
Under-voltage When inverter power voltage is under 170V (1ph 220V series) or 300V
protection (3-ph 380V series) because of power-cut or voltage drop, cut off the
(P.oFF) output and stop running.

Once overload, the inverter will automatically adjust the output


frequency, so that the output current fall below over-current limit value
Over-current limit
which is setted by current stalling electrical level.
(current stalling)
(overload capacity: general purpose is 150% rated current, 1 minute;
fan and pump purpose is 120% rated current, 1 minute)

If the output frequency declines sharply, renewable energy from the


Over-voltage
electric motor raises DC bus voltage of main circuit. Meanwhile,
limit (voltage
automatically adjust the output frequency in order to make DC voltage
stalling)
does not exceed the setting value.

Starts the function of electronic over-heat protection (set b-024 as 1).


Cut of the output and stop running when the load exceeds setting output
Over-load
value (b-025).(factory default: general purpose is general purpose is
protection (o.L.)
150% rated current, 1 minute; fan and pump purpose is 120% rated
current, 1minute)

~90~
User Manual of SY5000 series AC Drive Toubleshooting

Over-heat Detect the temperature of radiator, cut off output and shut down when it
protection (o.t.) is approximately 85℃

Self-diagnosis Detecting interior CPU, peripheral circuit and data storage is normal, or
(-.Err) not.

7.2 Fault code and reason analysis


The inverter records latest four fault reasons. After fault reset, you can view
(E-010~E-013) in group E of function parameters any time. Insturction of fault code
is as shown in Table 7-2.
Table 7-2 Fault name and reason analysis
Fault code Name Reason Troubleshooting
Please identify reasons,
and reset after taking
Over-current Output short circuit or
approximate measures. If
in operation mutation load
this persists, please seek
technical support.
1. The setting value of 1. increase accel time
accel time is too small; value;
Over-current
2. Torque compensation 2. increase or decrease
in accel
voltage value is set in torque compensation
an error. voltage value
1. The setting value of 1. increase decel time
Over-current decel time is too small; value;
in decel 2. Output short or load 2. eliminate short-circuit
mutation. or load mutation
Over-voltage 1.Make sure that the
1.Power voltage is too
in operation power voltage is in the
high;
normal range;
Over-voltage 2.Load speed has
2.Decrease fluctuation of
in accel fluctuated
load speed.
1. To change the decel
Over-voltage Load inertia (GD2) is time so that it is suitable
in decel too big for the load inertia;
2. connect braking unit

~91~
User Manual of SY5000 series AC Drive Toubleshooting

1. Short-circuit happens
Intelligent Please identify reasons,
in the upper and lower
power and reset after taking
bridge arms of IPM;
module approximate measures. If
2. Other reason causes
(IPM) this persists, please seek
oversized transcient
protection technical support.
current.
Transcient The power voltage
power-cut declines or transcient Please check power status
or under- power failure occurs in and wiring of input side.
voltage fault operation.
1. Check fan operation;
1. Cooling fan is
2.Make inverter operating
abnormal;
Over-heat of environment meet the
2. Ambient temperature
inverter requirements;
is too high;
3. Eliminate dust of the
3. Air vent is blocked
air vent.
1. Decrease load or
1. Motor over-load; replace larger capacity
2. V/F feature or torque inverter;
Over load 2. Increase or decrease
compensation capacity
is uncertain. torque compensation
voltage
Please store this
parameter again by using
E2PROM
Errors happen when SET key, or initialize by
write data
E2PROM stores data. using E-059 parameter,
error
cut off the power and then
power on.
Emergency Terminal input, EMS Confirm the signal
stop acts connection.

(Remark) E2PROM errors of wiring data, just display anomaly and don’t trip.

7.3 Anomaly and countermeasure


Reason and countermeasure of anomaly are as shown in Figure 7-3.

~92~
User Manual of SY5000 series AC Drive Toubleshooting

Table 7-3 Anomaly and countermeasure


Anomaly Reason Countermeasure
1.Please check input and output
1. Wrongly connect lines of
wirings;
input, output or phase-failure
2.Please reduce the load;
occurs;
3.Please chek if there is EMS signal
2. Over-burdened load or the
input;
motor locked rotation;
The motor 4.Please check the correctness of
3. EMS terminal has signal
doesn’t work. biasing (parameter E-031) and
input;
gaining (parameter E-032);
4. Set frequency as 0;
5.Measure output voltage, confirm if
5. No output voltage of inverter
3-ph output is balanced;
output terminal ;
6.If the fault happens, please run
6. Stop due to faults.
gain after troubleshooting.
The motor
The sequence of output terminal Please adjust the wiring sequence of
rotates in reverse
reverses. U, V, W
direction.
1. The load is over-burdened; 1.Please reduce the load;
The motor
2. The upper limit frequency 2.Check maximum frequency value
rotates, but the
(b-010) is too low; (b-010);
speed doesn’t
3. Frequency setting signal is too 3.Check signal value and the loop
change.
low. connection
The motor can
not accelerate Setting value of accel/decel time
Increase accel/decel time value
or decelerate is too short.
smoothly.
1. Large fluctuation of load or
1. Please lower the load fluctuations
The motor over-burdened load;
or reduce the load;
operating speed 2. The rated values of the
2. Please select the inverter and the
changes. inverter and the motor do not
motor with approximate load
match the load
1. The setting display proportion
1. Please check the pair number of
The motor is wrong;
electric poles;
operating speed 2. Setting value of highest
2. Please check the setting value of
does not match frequency (b-009) or base
highest frequency (b-009) or base
the setting frequency (b-008) is wrong;
frequency (b-008);
value. 3. The motor terminal voltage is
3. Please use thick lines output
low.

~93~
User Manual of SY5000 series AC Drive Maintenance

Chapter 8 Maintenance

Danger

1. Do not touch the inverter terminals, which there is high voltage on terminal.
Risk of electric shock.
2. Before power on, please install terminal housing. When disassemble housing,
please switch off power supply. Risk of electric shock.
3. Cut off power supply of main circuit, then carry out inspection and maintenance
after confirm LED extinguishing for 5~10 minutes. Risk of residual voltage of
electrolytic capacitor.
4. Non-specialists do not do maintenance and inspection. Risk of electric shock.

Caution

1. CMOS integrated circuits are installed in keypad, control circuit board and
drive circuit board. Please take care!
Don’t directly touch circuit board. Electrostatic induction may damage
integrated chips of circuit board.
2. Do not change wiring or remove terminal wires when it is power-up. Risk of
electric shock.
3. Do not check signals in operation. Risk of damaging equipments.
8.1 Inspection and maintenance
Ambient temperature, humidity, dust and vibration effects, as well as aging of
components all are likely lead to potential failure of the inverter.Therefore, must do
regular inspection maintenance.
8.1.1 Regualr inspection and maintenance
 Hearing and touching the housing,check if there are abnormal heating, noise
and vibration from the inverter and the motor.
 Check if ambient temperature and humidity exceeds the manual provision by
using thermometer and hygrometer.
 Load current is in the range of rated value, or not.
 Cooling fan runs normally, or not.
8.1.2 Daily inspection
Be sure to cut off the power when do regular inspections.

~94~
User Manual of SY5000 series AC Drive Maintenance

Start to check after no displaying of the monitor and turning off of the main
circuit power indicator.
Inspection contents are as shown in Table 8-1
Table 8-1 Regualr inspection contents
Inspection items Inspection contents Abnormal countermeasures
Main circuit terminal, screw Loosening of screws,
Tighten with a screwdriver
of control circuit terminal or not
Use 4~6kg/cm2 pressure dry
Heat sink Dust or not
compressed air to blow off
Use 4~6kg/cm2 pressure dry
PCB Dust or not
compressed air to blow off
Abnormal noise,
abnormal vibration, or
Cooling fan Replace cooling fan
total running time up
to 20,000 hours.
Use 4~6kg/cm2 pressure dry
Power components Dust or not
compressed air to blow off
Discoloring, off-flavor,
Aluminium capacitor Replace aluminium capacitor
bubbling, or not
8.1.3 Daily maintenance
Operational lifespan of inverter electronic components are closely related to
using environment, using condition and maintenance situation. Lifespan of vulnerable
parts under normal using conditions are as shown in Table 8-2:
Table 8-2 Replacement time of inverter components
Component name Lifespan
Cooling fan 2~3 years
Capacitor 4~5 years
PCB 5~8 years
Regular service conditions of above inverter components are:
1. Ambient temperature:annual average 30℃。
2. Load factor:under 80%
3. Run time:below 12 hour/day
Users determine replacement period according to actual situation.
8.1.4 Storage
1. Store inverters in well-ventilated places, and avoid high temperature,
humidity and dustiness.
2. Long time storage will lead to deterioration of electrolytic capacitors. So
ensure connection the inverter to power supply at least once in two years. And
input voltage slowly raises rated value by the voltage regulator.

~95~
User Manual of SY5000 series AC Drive Braking unit and braking resistor

Chapter 9 Braking unit and braking resistor

When the inverter-driven control equipment requires rapid braking, use braking
unit or braking resistor to release the energy which be feedbacked to DC bus when the
motor brakes.

9.1 Model instruction of braking unit

9.2 Model instruction of braking resistor

9.3 Technical specification of braking unit


Table 9-1 SYB Technical specification of braking unit
380V ~ 460V
Items of braking unit
SYB-U50 (A type) SYB-U100 (B type)
Input output
Peak discharge current (A) 50 100
characteristic
Input output
Rated discharge current (A) 15 35
characteristic
Braking start voltage 630/660/690/730/760V ±6V
Maximum hysteresis error About 16V
Linked input, linked output, up to 10 parallel
Synchronous signal
operaitons
Power supply DC bus voltage Peak value 460 (1.35×380×0.9) ~ 800V
24V,500mA or 24V,
Power supply Power supply fan None
250mA

~96~
User Manual of SY5000 series AC Drive Braking unit and braking resistor

Above 45℃ the fan


Temperature-controlled fan None runs, below 45℃ the fan
stops
Thermal protection device
Protection Heatsinke overheating
(85℃ relay acts,output normal open,、nornal
function (IGBT abnormal)
close each 1 pairs contacts)
Charging indicator remains “on” until DC bus
Power supply indication
voltage <50 V
Running indication Green LED lights when braking unit works.
Ambient
Installation site indoor(to avoid corrosive gases and dust)
condition
Ambient temperature -10°C ~ +40°C(no forzen)
Storage temperature -20°C ~ +60°C
Humidity 90%RH(no dew)
Vibration 10~20Hz for 1G,20~50Hz for 0.2G
Thermal losses (W) 54 59

9.4 Selection of braking resistor


Table 9-2 Selection of braking resistor
SY5000 Braking
Braking unit Braking resistor
AC Drive torque
Motor
Using Using (use ratio
power HP Model no. Model no. Resistor details
quantity quantity 10%ED)%
(KW)
1 (0.75) SYB-U50 1 SYB-R750-80 80W/750Ω 1 125
2 (1.5) SYB-U50 1 SYB-R400-300 300W/400Ω 1 125
3 (2.2) SYB-U50 1 SYB-R250-300 300W/250Ω 1 125
5 (3.7) SYB-U50 1 SYB-R150-400 400W/150Ω 1 125
7.5 (5.5) SYB-U50 1 SYB-R100-500 500W/100Ω 1 125
10 (7.5) SYB-U50 1 SYB-R75-1000 1000W/75Ω 1 125
15 (11) SYB-U50 1 SYB-R50-1000 1000W/50Ω 1 125
20 (15) SYB-U50 1 SYB-R40-1500 1500W/40Ω 1 125
25 (18.5) SYB-U50 1 SYB-R32-4800 4800W/32Ω 1 125
30 (22) SYB-U50 1 SYB-R27-4800 4800W/27.2Ω 1 125
40 (30) SYB-U50 1 SYB-R20-6000 6000W/20Ω 1 125
50 (37) SYB-U100 1 SYB-R16-9600 9600W/16Ω 1 125
60 (45) SYB-U100 1 SYB-R13-9600 9600W /13.6Ω 1 125
75 (55) SYB-U50 2 SYB-R20-6000 6000W/20Ω 2 135

~97~
User Manual of SY5000 series AC Drive Braking unit and braking resistor

100 (75) SYB-U100 2 SYB-R13-9600 9600W/13.6Ω 2 145


150 (110) SYB-U50 3 SYB-R20-6000 6000W/20Ω 3 100

9.5 Wiring of braking unit


 Wiring of braking unit
Wiring of braking unit, as shown in Figure 9-1

Figure 9-1 Installation of braking unit


 Parallel connection of braking unit
Paralle connection of braking unit, as shown in Figure 9-2

Figure 9-2 Parallel installation of braking unit

 Linked connection of braking unit


Linked connection of braking unit, as shown in Figure 9-3

Figure 9-3 Linked connection of braking unit

~98~
User Manual of SY5000 series AC Drive MODBUS communication protocol

Appendix 1 MODBUS communication protocol


1 Communication parameter
[r-000]:Communication function selection
0:Communication function is invalid
1:Communication function is valid
[r-001]:Baud rate
0:19200 bps
1:9600 bps
2:6400 bps
3:4800 bps
4:3840 bps
5:3200 bps
6:2740 bps
7:2400 bps
[r-002]:Communication data format
0:7,N,2 for ASCII
1:7,E,1 for ASCII
2:7,O,1 for ASCII
3:8,N,2 for RTU
4:8,E,1 for RTU
5:8,O,1 for RTU
[r-003]:Local address
Setting range:1~254
[r-004]:Reserved
[r-005]:Reserved
[r-006]:Communication delay time
The parameter is used to set communication delay time, namely interval time
between inverter completely receiving data and starting to send data to host computer.

2 Encoding meaning

~99~
User Manual of SY5000 series AC Drive MODBUS communication protocol

Communication protocol is 16-hex, the meaning of ASCII message character:


Character ‘0’ ‘1’ ‘2’ ‘3’ ‘4’ ‘5’ ‘6’ ‘7’
ASCII code 30H 31H 32H 33H 34H 35H 36H 37H
Character ‘8’ ‘9’ ‘A’ ‘B’ ‘C’ ‘D’ ‘E’ ‘F’
ASCII code 38H 39H 41H 42H 43H 44H 45H 46H

3 Communication data frame:


3.1 ASCII mode:
STX Start character‘:’(3AH)
Address Hi Communication address:
Address Lo 8-bit address consists of 2 ASCII codes
Function Hi Function code:
Function Lo 8-bit function code consists of 2 ASCII codes
Data(n-1) Contents of data:
…… n*8-bit data consists of 2n ASCII codes
Data 0 n≤25, up to 50 ASCII codes(Note:now only support n≤12)
LRC CHK Hi LRC check code:
LRC CHK Lo 8 bit check code consists of 2 ASCII codes
END Hi End characters:
END Lo END Hi = CR(0DH), END Lo = LF(0AH)

3.2 RTU mode


START Maintain the non-input signal ≥10ms
Address Communication address:8-bit binary address
Function Function code:8-bit binary function code
DATA(n-1)
Contents of data:
……
n*8bit data,n≤16(Note:now only support n≤6)
DATA 0
CRC CHK Low CRC check code:
CRC CHK High 16-bit CRC check code consists of two 8-bit binary characters
END Maintain the non-input signal ≥10ms
3.3 Communication address(Address):
00H:Broadcasting on all drives(Broadcast)
01H~FEH:Sending to No. 01~254 inverters

~100~
User Manual of SY5000 series AC Drive MODBUS communication protocol

3.4 Function code(Function)


03H:Reading register contents
06H:Writing a WORD to register
08H:Loop detection
3.5 Example of reading data command:
a) ASCII mode:

Command message:
STX ‘:’
‘0’
Address
‘1’
‘0’
Function
‘3’
‘2’
‘1’
Starting address
‘0’
‘2’
DATA
‘0’
Number of data(count ‘0’
by word) ‘0’
‘2’
‘D’
LRC Check
‘7’
CR
END
LF

Response message:
STX ‘:’
‘0’
Address
‘1’
‘0’
Function
‘3’

~101~
User Manual of SY5000 series AC Drive MODBUS communication protocol

Number of data (count ‘0’


by byte) ‘4’
‘1’
Content of starting ‘7’
address 2102H ‘7’
DATA
‘0’
‘0’
Content of address ‘0’
2103H ‘0’
‘0’
‘7’
LRC Check
‘1’
CR
END
LF

b) RTU mode:
Command message:
Address 01H
Function 03H
21H
Starting data address
02H
Number of data 00H
(count by word) 02H
CRC CHK Low 6FH
CRC CHK High F7H
Response message:
Address 01H
Function 03H
Number of data 04H
(count by byte)
Content of data 17H
address 2102H 70H
Content of data 00H
address 2103H 00H
CRC CHK Low FEH
CRC CHK High 5CH

~102~
User Manual of SY5000 series AC Drive MODBUS communication protocol

3.6 Example of writing data command


a) ASCII mode:
Command message:
STX ‘:’
‘0’
Address
‘1’
‘0’
Function
‘6’
‘0’
‘1’
data address
‘0’
‘0’
DATA
‘1’
‘7’
Data content
‘7’
‘0’
‘7’
LRC Check
‘1’
CR
END
LF

Response message:
STX ‘:’
‘0’
Address
‘1’
‘0’
Function
‘6’
‘0’
‘1’
data address
‘0’
‘0’
DATA
‘1’
‘7’
Data content
‘7’
‘0’
‘7’
LRC Check
‘1’
CR
END
LF

b) RTU mode:

~103~
User Manual of SY5000 series AC Drive MODBUS communication protocol

Command message:
Address 01H
Function 06H
01H
Data address
00H
17H
Data content
70H
CRC CHK Low 86H
CRC CHK High 22H

Response message:
Address 01H
Function 06H
01H
Data address
00H
17H
Data content
70H
CRC CHK Low 86H
CRC CHK High 22H

3.7 Example of loop detection command


a) ASCII mode:
Command message:

STX ‘:’
‘0’
Address
‘1’
‘0’
Function
‘8’
‘0’
‘0’
Data address
‘0’
‘0’
DATA
‘1’
‘2’
Data content
‘A’
‘B’
‘3’
LRC Check
‘A’
CR
END
LF

~104~
User Manual of SY5000 series AC Drive MODBUS communication protocol

Response message:
STX ‘:’
‘0’
Address
‘1’
‘0’
Function
‘8’
‘0’
‘0’
Data address
‘0’
‘0’
DATA
‘1’
‘2’
Data content
‘A’
‘B’
‘3’
LRC Check
‘A’
CR
END
LF

b) RTU mode:
Command message:
Address 01H
Function 08H
00H
Sub Function
00H
12H
Data content
ABH
CRC CHK Low ADH
CRC CHK High 14H
Response message:
Address 01H
Function 08H
00H
Sub Function
00H
12H
Data content
ABH
CRC CHK Low ADH
CRC CHK High 14H

~105~
User Manual of SY5000 series AC Drive MODBUS communication protocol

4. Definition of parameter address of communication protocol

Parameter
Definition Description
address
GG represents parameter group number; nn represents
parameter number.
Set parameter
(instruction of parameter group number: 0 corresponds to
in internal GGnnH
group b, 1 corresponds to group E, 2 corresponds to group P, 3
inverter
corresponds to group G, 4 corresponds to group r)
e.g.:P-005 expressed by 0205H
bit 0 Run command 0:No 1:Yes
bit 1 Reserved -- --
bit 2 Stop command 0:No 1:Yes
Command of 2000H bit 3 Reserved -- --
inverter bit 4 Run at uplink frequency 0:No 1:Yes
bit 5 Fault reset 0:No 1:Yes
bit 6~15 Reserved -- --
2001H frequency
fault code:
bit 0 Under voltage 0:No 1:Yes
bit 1 Over current 0:No 1:Yes
bit 2 Over voltage 0:No 1:Yes
2100H bit 3 Over load 0:No 1:Yes
bit 4 IPM protection 0:No 1:Yes
bit 5 Over heat 0:No 1:Yes
bit 6 Other faults 0:No 1:Yes
bit 7~15 Reserved -- --
Inverter is ready to run, at a
bit 0 0:No 1:Yes
standstill
Monitor Inverter has been running to
inverter bit 1 0:No 1:Yes
the preset frequency
status
bit 2 In acceleration 0:No 1:Yes
2101H bit 3 In deceleration 0:No 1:Yes
bit 4 Inverter with output 0:No 1:Yes
Inverter controlled by host
bit 5 0:No 1:Yes
computer
bit 6 Parameter lock 0:No 1:Yes
bit 7~15 Reserved -- --
2102H Setting frequency
2103H PID given value
2104H PID feedback value
2105H Output frequency

~106~
User Manual of SY5000 series AC Drive MODBUS communication protocol

2106H Output voltage


Monitor 2107H Output current
inverter 2108H DC bus voltage
status 2109H Inverter current temperature
210AH Total running time of inverter
Parameter
Definition Description
address
Short circuit between PI1 and
210BH bit 0 0:No 1:Yes
COM terminal
Short circuit between PI2 and
bit 1 0:No 1:Yes
COM terminal
Short circuit between PI3 and
bit 2 0:No 1:Yes
COM terminal
Short circuit between PI4 and
bit 3 0:No 1:Yes
COM terminal
Short circuit between SR and
bit 4 0:No 1:Yes
COM terminal
Short circuit between SF and
bit 5 0:No 1:Yes
COM terminal
Short circuit between RST and
bit 6 0:No 1:Yes
COM terminal
Short circuit between EMS
bit 7 0:No 1:Yes
and COM terminal
bit 8~15 Reserved -- --

5. The slave’s response when communication fault


The host computer generates an error when communicating with the
inverter, the inverter will response the corresponding fault code,reply the
host commands of “Function code”. OR. 80H.

a) Example of response data when an error occurs:


ASCII mode:
STX ‘:’
‘0’
Address
‘1’
‘8’
Function code
‘6’
‘0’
Exception code
‘2’

~107~
User Manual of SY5000 series AC Drive MODBUS communication protocol

‘7’
LRC CHK
‘7’
CR
END
LR

RTU mode:
Address 01H
Function 86H
Exception code 02H
CRC CHK Low C3H
CRC CHK High A1H

b) Meaning of fault code:


Fault code Description
Function code fault:
01
inverter only identify functions of 03H, 06H, 08H
Command address error
02
Address inverter does not exist in the command.

Command content is wrong:


03 Command content is out of range, e.g.: when write parameters,
command parameter value are beyond limits.
Command can not be implemented.
04 Inverter can not perform the command, e.g.: command modifies read-
only data or parameter.
Check code error
09
Check byte of command data frame is not correct.
Command data is too short.
12 (less than 17 bytes at ASCII mode, RTU less than 8 bytes at RTU
mode.)
Command data is too long,
total bytes is not beyond 27 bytes in ASCII mode(that is to say, the
13 data bit is not beyond 10 bytes),
total bytes is not beyond 12 bytes in RTU mode(that is to say, the data
bit is not beyond 4 bytes.)

15 Error occurs when execute writing command.

~108~
User Manual of SY5000 series AC Drive MODBUS communication protocol

Attachment:
Calculation of check code
1 Check code of ASCII mode(LRC Check)
Check code(LRC Check)is the total value adding from address to data. E.g.:
STX ‘:’
‘0’
Address
‘1’
‘0’
Function
‘3’
‘2’
‘1’
Start=ing address
‘0’
‘2’
DATA
‘0’
Number of data ‘0’
(count by word) ‘0’
‘2’
‘D’
LRC Check
‘7’
CR
END
LF
Calculation of check codes of above command:
01H+03H+21H+02H+00H+02H=29H, then take the complement of 29H and get
check code of D7H.

2 Check code of RTU mode(CRC Check)


Check code is the value from Address to Data.
Its calculation rules are as following:

Step 1:load a 16-bit register(called CRC register)=FFFFH.


Step 2:first 8-bit byte message command and 16-bit low byte of CRC register
will be treated as Exclusive OR,and store the result into CRC register.
Step 3:Right move one bit CRC register, fill 0 in high byte.
Step 4:Check the value of right move, if 0, store the new value of Step 3 into
CRC register, otherwise exclusive OR A001H and CRC register, store the result
into CRC register.
Step 5:Repeat Step 3~Step 4,complete all calculation of 8-bit.

~109~
User Manual of SY5000 series AC Drive MODBUS communication protocol

Step 6:Repeat Step 2~Step 5,take next 8-bit message command until
all message command calculation completes. After all, get the value of CRC
register, namely CRC check code. It is worth noting that CRC check code must
be swapped to place in the confirmation code.

The following is calculation example of CRC check code which is written by C


language: unsigned char *data //message command pointer
unsigned char length //message command length
unsigned int crc_chk(unsigned char *data,unsigned char length)
{
int j;
unsigned int reg_crc=0xFFFF;
while(length--)
{
reg_crc ^ = *data++;
for(j=0;j<8;j++)
{
if(reg_crc & 0x01) reg_crc=(reg_crc>>1)^0xA001;
else reg_crc=reg_crc>>1;
}
}
}
return reg_crc; // return CRC register

~110~
User Manual of SY5000 series AC Drive Operation panel and extension cable

Appendix 2 Operation panel and extension cable

1 Installation of operation panel


1.1 Overall dimension and buckle installation dimension

Figure 1-1 Sketch map of operation panel

Specific shape of
top panel depends
on models.

Figure 1-2 Sketch map of top panel

~111~
User Manual of SY5000 series AC Drive Operation panel and extension cable

1.2 Installation instruction


1.2.1 Instruction of operation panel

Figure 1-3 Instruction of operation panel

NOTE:
1. Put operation panel into the groove of external control panel, as shown in the figure,
and then slightly push down.
2. Confirm the entering of operation panel.

2 Optional accessories
2.1 extension cable
Operation panel can connect with inverter host by extension cable (as shown
in Figure 2-2). Length of cable: 1m, 2m, 3m, 5m. If users need extension cable
longer than 5m, please contact the factory when place the order. The shape of
extension cable is as shown in Figure 2-1.

~112~
User Manual of SY5000 series AC Drive Operation panel and extension cable

Figure 2-1 Extension cable

Interface plug of
inverter control board

Figure 2-2 Connection diagram of extension cable

~113~