Transformer Oil Test Report


Pakistan

Customer : Unilever Pakistan Ltd Date : 10.02.2022

No. of Samples 04

Transformer 1 Transformer 2 Transformer 3 Transformer


Units / 2000 kVA 2000 kVA 2500 kVA 1000 kVA
S. No. Tests LPK No. 21400808 LPK No. 21001169 LPK No. 21700316 22306
(Sp. Values)

Av. Results Remarks Av. Results Remarks Av. Results Remarks Av. Results Remarks

Kinematic Viscosity (at (mm2 / sec


1 9.79 - 10.79 - 9.46 - 9.48 -
40 0C) ( < 12 )

0
2 Flash Point C 156 Good 148 Good 150 Good 152 Good
( > 135 )

Clear, free from


3 Appearance Clear Good Clear Good Clear Good Clear Good
sediments

kg/dm3
4 Density (at 20 0C) 0.8739 - 0.8568 - 0.8386 - 0.8631 -
( < 0.895 )

0
5 Pour Point C -42 - >=-45 - -45 - -9 -
( Max -30 )

PPM (good = <15;


6 Water by crackle fair = 15-20; 6.55 Good 15.07 Fair 4.23 Good 17.71 Fair
poor = >20)

kV ( good = >60;
7 Breakdown voltage : fair = 50-60; 90 91 91 Good 83 Good 81 Good
poor = < 50 )

mg KOH / g
( good = < 0.10;
8 Acidity 0.046 Good 0.172 Poor 0.032 Good 0.216 Poor
fair= 0.10-0.15;
poor = > 0.15 )