High Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 29-Nov-2021


Order No:
Plant Section/Identification: AVR Input Panel 2HTP1

Electrical Measuring/protection Device:


Panel Type: 8BD4 (2015)
Circuit breaker: 3AH5113
Rated current range: 800 A
Type protection relays connected: 7SJ6005
CT Ratio: 300/5

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Mechanical operation working
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Checking of Load Break Switch:


Functional Testing N/A
Cleaning & Greasing N/A

Indication/monitoring instruments:
Types of indicators: VCB ON, VCB OFF, Ammeter, Voltmeter
Tested by secondary injection:

Remarks:
Terminal Contacts were missing hence installed.

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
RELAY TEST REPORT

Customer: Unilever RYK Test performed on: 25 Dec-2021


Order No:
Plant Section/Identification: AVR Input Panel 2HTP1

Type of Relay : 7SJ6005


CT Ratio : 300/5
Nominal Current : 5A :

OPERATIONAL SETTINGS:

Setting I> Characteristic Time Multiplier I>> Time


L1, L2, L3 1.1 NI 0.4 7.9 0.0
E/F 0.3 NI 0.4 4.5 0.0

TESTING:

S.No Injected Current Time Meas. Injected Current Time Meas.


I> I>>
(A) (sec) (A) (mSec)
L-1 11.20 3.870 41.47 93
L-2 11.21 3.892 41.35 92

L-3 11.18 3.830 41.40 91


Earth Injected Current Time Meas. Injected Current Time Meas.
Fault IE> IE>>
IE> (A) (sec) (A) (mSec)
3.18 3.67 22.10 111

Remarks:
Satisfactory Results

Siemens Representative Client’s Representative


Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
High Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 29-Nov-2021


Order No:
Plant Section/Identification: TR3 Supply Panel 2HTP2

Electrical Measuring/protection Device:


Panel Type: 8BD4 (2002)
Circuit breaker: 3AH5113
Rated current range: 630 A
Type protection relays connected: 7SJ6025
CT Ratio: 100/5

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Mechanical operation working
Components correctly labeled Relay and test plug tag missing

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Checking of Load Break Switch:


Functional Testing N/A
Cleaning & Greasing N/A

Indication/monitoring instruments:
Types of indicators: ON, OFF, Buchholz
Tested by secondary injection:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
RELAY TEST REPORT

Customer: Unilever RYK Test performed on: 25 Dec-2021


Order No:
Plant Section/Identification: TR3 Supply Panel 2HTP2

Type of Relay : 7SJ6025


CT Ratio : 100/5
Nominal Current : 5A :

OPERATIONAL SETTINGS:

Setting I> Characteristic Time Multiplier I>> Time


L1, L2, L3 1.3 NI 0.4 6.00 0.0
E/F 0.26 NI 0.4 2.00 0.0

TESTING:

S.No Injected Current Time Meas. Injected Current Time Meas.


I> I>>
(A) (sec) (A) (mSec)
L-1 12.52 4.10 30.40 108
L-2 12.71 4.08 30.53 129

L-3 13.10 4.03 30.20 150


Earth Injected Current Time Meas. Injected Current Time Meas.
Fault IE> IE>>
IE> (A) (sec) (A) (mSec)
2.46 4.34 10.14 109

Remarks:
Satisfactory Results

Siemens Representative Client’s Representative


Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
High Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 29-Nov-2021


Order No:
Plant Section/Identification: TR2 Supply Panel 2HTP3

Electrical Measuring/protection Device:


Panel Type: 8BD4 (2002)
Circuit breaker: 3AH5113
Rated current range: 630 A
Type protection relays connected: 7SJ6025
CT Ratio: 75/5

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Mechanical operation working
Components correctly labeled Relay and test plug tag missing

Electrical Checks:
Tripping mechanism OK
Indication connected working Indication Lights not working hence replaced
Electrical functional test OK

Checking of Load Break Switch:


Functional Testing N/A
Cleaning & Greasing N/A

Indication/monitoring instruments:
Types of indicators: ON, OFF, Buchholz
Tested by secondary injection:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
RELAY TEST REPORT

Customer: Unilever RYK Test performed on: 25 Dec-2021


Order No:
Plant Section/Identification: TR2 Supply Panel 2HTP3

Type of Relay : 7SJ6025


CT Ratio : 75/5
Nominal Current : 5A :

OPERATIONAL SETTINGS:

Setting I> Characteristic Time Multiplier I>> Time


L1, L2, L3 0.5 NI 0.5 3.1 0.05
E/F 0.1 NI 0.4 1.05 0.0

TESTING:

S.No Injected Current Time Meas. Injected Current Time Meas.


I> I>>
(A) (sec) (A) (mSec)
L-1 5.21 4.74 16.21 138
L-2 5.31 4.65 16.12 132

L-3 5.12 4.88 16.18 134


Earth Injected Current Time Meas. Injected Current Time Meas.
Fault IE> IE>>
IE> (A) (sec) (A) (mSec)
1.08 3.66 5.80 89

Remarks:
Satisfactory Results

Siemens Representative Client’s Representative


Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
High Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 29-Nov-2021


Order No:
Plant Section/Identification: TR1 Supply Panel 2HTP4

Electrical Measuring/protection Device:


Panel Type: 8BD4 (2002)
Circuit breaker: 3AH5113
Rated current range: 630 A
Type protection relays connected: 7SJ6025
CT Ratio: 75/5

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Mechanical operation working
Components correctly labeled Relay and test plug tag missing

Electrical Checks:
Tripping mechanism OK
Indication connected working Indication Lights not working hence replaced
Electrical functional test OK

Checking of Load Break Switch:


Functional Testing N/A
Cleaning & Greasing N/A

Indication/monitoring instruments:
Types of indicators: ON, OFF, Buchholz
Tested by secondary injection:

Remarks:
Plug housing damaged

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
RELAY TEST REPORT

Customer: Unilever RYK Test performed on: 25 Dec-2021


Order No:
Plant Section/Identification: TR1 Supply Panel 2HTP4

Type of Relay : 7SJ6025


CT Ratio : 75/5
Nominal Current : 5A :

OPERATIONAL SETTINGS:

Setting I> Characteristic Time Multiplier I>> Time


L1, L2, L3 1.1 NI 0.4 5.9 0.0
E/F 0.2 NI 0.4 5 0.0

TESTING:

S.No Injected Current Time Meas. Injected Current Time Meas.


I> I>>
(A) (sec) (A) (mSec)
L-1 11.10 3.98 32.81 109
L-2 9.69 4.90 31.15 90

L-3 10.07 4.64 30.95 89


Earth Injected Current Time Meas. Injected Current Time Meas.
Fault IE> IE>>
IE> (A) (sec) (A) (mSec)
2.45 3.12 26.35 91

Remarks:
Satisfactory Results

Siemens Representative Client’s Representative


Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
High Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 29-Nov-2021


Order No:
Plant Section/Identification: AVR Output Panel 2HTP5

Electrical Measuring/protection Device:


Panel Type: 8BD4 (2002)
Circuit breaker: 3AH5113
Rated current range: 630 A
Type protection relays connected: 7SJ6025
CT Ratio: 300/5

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Mechanical operation working
Components correctly labeled Relay and test plug tag missing

Electrical Checks:
Tripping mechanism OK
Indication connected working Indication Lights not working hence replaced
Electrical functional test OK

Checking of Load Break Switch:


Functional Testing N/A
Cleaning & Greasing N/A

Indication/monitoring instruments:
Types of indicators: ON, OFF
Tested by secondary injection:

Remarks:
Plug conduit damaged.
Terminal Contact missing hence installed.

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
RELAY TEST REPORT

Customer: Unilever RYK Test performed on: 25 Dec-2021


Order No:
Plant Section/Identification: AVR Output Panel 2HTP5

Type of Relay : 7SJ6025


CT Ratio : 300/5
Nominal Current : 5A :

OPERATIONAL SETTINGS:

Setting I> Characteristic Time Multiplier I>> Time


L1, L2, L3 1.0 NI 0.4 7.5 0.0
E/F 0.3 NI 0.4 4.5 0.0

TESTING:

S.No Injected Current Time Meas. Injected Current Time Meas.


I> I>>
(A) (sec) (A) (mSec)
L-1 10.61 3.77 40.58 90
L-2 10.63 3.69 40.51 110

L-3 10.50 3.76 40.7 89


Earth Injected Current Time Meas. Injected Current Time Meas.
Fault IE> IE>>
IE> (A) (sec) (A) (mSec)
3.49 3.17 27.48 80

Remarks:
Satisfactory Results

Siemens Representative Client’s Representative