MV Panel Report
MV Panel Report
MV Panel Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Mechanical operation working
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators: VCB ON, VCB OFF, Ammeter, Voltmeter
Tested by secondary injection:
Remarks:
Terminal Contacts were missing hence installed.
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
RELAY TEST REPORT
OPERATIONAL SETTINGS:
TESTING:
Remarks:
Satisfactory Results
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Mechanical operation working
Components correctly labeled Relay and test plug tag missing
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators: ON, OFF, Buchholz
Tested by secondary injection:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
RELAY TEST REPORT
OPERATIONAL SETTINGS:
TESTING:
Remarks:
Satisfactory Results
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Mechanical operation working
Components correctly labeled Relay and test plug tag missing
Electrical Checks:
Tripping mechanism OK
Indication connected working Indication Lights not working hence replaced
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators: ON, OFF, Buchholz
Tested by secondary injection:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
RELAY TEST REPORT
OPERATIONAL SETTINGS:
TESTING:
Remarks:
Satisfactory Results
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Mechanical operation working
Components correctly labeled Relay and test plug tag missing
Electrical Checks:
Tripping mechanism OK
Indication connected working Indication Lights not working hence replaced
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators: ON, OFF, Buchholz
Tested by secondary injection:
Remarks:
Plug housing damaged
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
RELAY TEST REPORT
OPERATIONAL SETTINGS:
TESTING:
Remarks:
Satisfactory Results
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Mechanical operation working
Components correctly labeled Relay and test plug tag missing
Electrical Checks:
Tripping mechanism OK
Indication connected working Indication Lights not working hence replaced
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators: ON, OFF
Tested by secondary injection:
Remarks:
Plug conduit damaged.
Terminal Contact missing hence installed.
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
RELAY TEST REPORT
OPERATIONAL SETTINGS:
TESTING:
Remarks:
Satisfactory Results