Professional Documents
Culture Documents
CHAPTER 5 (Computations Exp 4-7)
CHAPTER 5 (Computations Exp 4-7)
In Partial Fulfillment
Prepared by:
Course Adviser
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
MAY 2023
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
INTRODUCTION
minimum of 4 pages
The project site is located at Magalang, Pampanga. Figure 1.6.1 shows the
topographic view of Magalang, Pampanga sourced from Google Earth. According to the
surface soils are composed of 54% sand, 21% silt, and 25% clay. Moreover, they
classified their soil as acidic based pH level except for the Arayat sandy clay loam that is
more alkaline. The project site has a latitude of 15° 14’5’’ N, and longitude of 120° 37’36’’
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
manner)
Atterberg Limit
Moisture
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
Sieve Analysis
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
CHAPTER 2: METHODOLOGY
with ASTM Procedures. These are the following laboratory tests carried out:
These test methods cover the laboratory determination of the water (moisture)
content by mass of soil, rock, and similar materials where the reduction in mass by
drying is due to loss of water. For simplicity, the word “material” shall refer to soil, rock
Apparatus
Electric Balance
Moisture Cans
Oven (For drying, the temperature of oven is generally kept between 105 ̊C to
110 ̊C. A higher temperature should be avoided to prevent the burning of organic
Experiment Procedure:
1. Determine the mass (g) of the empty moisture cans plus its cover (m1) using the
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
2. Place samples of the representative moist soil in moisture cans close the can with
3. Determine the combined mass (g) of the closed can and moist soil (m2).
4. Remove the cover from the top and place it on the bottom of the can.
5. Put it in the oven for at least 24 hours to dry the soil to a constant weight.
6. Determine the combined mass (g) of the dry soil sample plus the can and its cap
(m3).
ASTM D854: Standard Test Methods For Specific Gravity Of Soil Solids By Water
Pycnometer
These test methods cover the determination of the specific gravity of soil solids
passing a sieve by means of a water pycnometer. Soil solids for these test methods do
not include solids which can be altered by these methods, contaminated with a
substance that prohibits the use of these methods, or are highly organic soil solids, such
as fibrous matter which floats in water. Procedures for moist specimens such as organic
soils, highly plastic fine grained soils, tropical soils, and soils containing halloysite and
which shall be a stoppered flask, stoppered iodine flask, or volumetric flask; balance;
drying oven; thermometer; dessicator; a system for entrapped air removal which shall
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
Apparatus
Thermometer
Vacuum Pump
Drying Pan
Drying Oven
Funnel
Sieve
1. Clean, dry, and weigh the volumetric flask and record its mass, WF.
2. Carefully fill the flask with distilled water at room temperature up to the 500 mL
mark (bottom of the meniscus should be at the 500 mL mark). Dry the outside of
the flask and blot any water from the inside of the neck above the meniscus using
a long-handled swab.
3. Determine the mass of the flask and the water filled to the 500 mL mark (WFW).
4. Take the temperature of the water in the flask. This observed temperature (Ti) will
be used as the temperature reference. Table 2.2 indicates the relative density of
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
water to be used in determining the variation in the mass of the flask and over the
Experiment Procedure:
1. Pour off sufficient distilled water so that the flask bulb is approximately 1/3 full.
Place approximately 100 grams of soil from the sample jar into the flask.
2. Add distilled water to wash down any soil particles clinging to the inside of the
neck and to fill the flask slightly above the required to cover the soil.
3. Agitate the flask slightly to ensure that all soil is dispersed. Remove any entrapped
air by applying a vacuum to the flask. During the vacuum phase, samples should
4. Add distilled water to the volumetric flask until the bottom of the meniscus touches
the 500 mL mark. Dry the outside of the flask and blot any water from the inside of
5. Determine the combined mass of the flask plus soil plus water (WFWS).
8. Pour the soil and water into a pan. Wash the inside of the flask. Make sure that no
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
10. Determine the mass of the pan and oven-dried soil in pan (WPS).
ASTM D422: Standard Test Method For Particle-Size Analysis of Soils (Historical Method
Standard)
distribution of particle sizes in soils. The distribution of particle sizes larger than 75 um
(retained on the No. 200 sieve) is determined by sieving, while the distribution of
Apparatus
Oven
Experiment Procedure:
1. Collect a representative oven dry soil sample. Samples having largest particles of
the size of No. 4 sieve openings (4.75 mm) should be about 500 grams. For soils
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
having largest particles of size greater than 4.75 mm, larger weights are needed.
2. Break the soil sample into individual particles using a mortar and a rubber – tipped
pestle. Apply rolling process, and not pounding. (NOTE: the idea of break up the
4. Prepare a stack of sieves. A sieve with larger openings is placed above a sieve
with smaller openings. The sieve at the bottom should be the No. 200. A bottom
pan should be placed under sieve No. 200. The sieves that are generally used in a
stack are Nos. 4, 10, 20, 40, 60, 100, and 200; however, more sieves can be placed
in between.
5. Weigh the sieves and bottom pan and record its mass.
6. Pour the soil prepared in Steps 1 and 2 into the stack of sieves from the top.
8. Run the stack of sieves through a mechanical sieve shaker, or shake manually for
about 10 to 15 minutes.
9. Stop the sieve shaker and remove the stack of sieves carefully.
11. If a considerable amount of soil with silty and clayey fractions is retained on the
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
No. 200 sieve, it has to be washed. Washing is done by taking the No. 200 sieve
with the soil retained on it and pouring water through the sieve from a tap in the
laboratory.
12. Plot the percent finer versus particle size (use the logarithmic graph). Connect the
ASTM D4318: Standard Test Methods For Liquid Limit, Plastic Limit, Plasticity Index Of
Soils
classification systems to characterize the fine-grained fractions of soils and to specify the
fine-grained fraction of construction materials. The liquid limit, plastic limit, and
plasticity index of soils are also used extensively, either individually or together, with
Apparatus
Grooving Tool
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
Spatula
Paper Towels
Oven
Moisture Cans
Spatula
Moisture Cans
Experiment Procedure:
1. Determine the mass (g) of the empty moisture cans plus its cover (m1) using the
passing the 0.425 mm sieve which has been obtained in accordance with the
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
3. Mix the sample with 15 to 20 mL of distilled water (or tap water for this experiment).
Mix thoroughly by alternately stirring and kneading with the spatula. Further
4. Place a portion of the mixed sample in the brass cup of the liquid limit device.
5. Level off the sample through its surface with a spatula to a maximum depth of
10mm.
6. Divide the soil pat into two segments using the standard grooving tool,
7. Mount the brass cup to the carriage such that it can be raised and allowed to
drop sharply on the base through a height of 10mm by rotating the crank at an
approximate of two rotations per second until the closure of the groove is evident
NOTE: The closure should be by flow of the soil and not by sup page on the cup.
8. Take a slice of approximately width of spatula extending from the edge to edge
9. Place the removed sample in a moisture can and determine the total mass of the
10. Remove the cover from the top and place it on the bottom of the can.
11. Put it in the oven for at least 24 hours to dry the soil to a constant weight.
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
12. Repeat steps (4) to (12) with different moisture contents of the soil in the range of
10 – 40 blows.
14. Determine the combined mass (g) of the dry soil sample plus the can and its cover
(m3).
15. Plot the moisture content (Y-axis) against logarithmic number of blows (X-axis) and
draw a mean line (flow line). Determine the soil’s liquid limit by projecting the 25
1. Determine the mass (g) of the empty moisture cans plus its cover (m1) using the
2. An air-dried sample shall be taken from material passing the 0.425 mm sieve which
of disturbed soil sample for test. Mix thoroughly with distilled water (tap water) until
3. Take a portion of the mixture. Squeeze and form the sample into ball.
4. Roll the ball of soil between the fingers and the glass plate (or any non-absorbent
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
material) with just sufficient value of pressure into thread of uniform diameter
NOTE: Hands should be dry before handling the soil sample to prevent the addition
5. When the diameter of the thread becomes 1/8 of an inch, break the thread into
6 or 8 pieces.
6. Squeeze the pieces together between the thumbs and fingers into a uniform mass
and reroll.
7. Continue the alternate rolling to a thread of about 1/8 of an inch until the thread
9. Place the sample in a moisture can and determine the total mass of the moist
10. Put it in the oven for at least 24 hours to dry the soil to a constant weight.
12. Determine the combined mass (g) of the dry soil sample plus the can and its cover
(m3).
13. Determine the moisture content of the soil samples. Obtain the Plastic Limit of the
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
ASTM D-3282: Standard Practice for Classification of Soils and Soil-Aggregate Mixtures
This practice covers a procedure for classifying mineral and organomineral soils
limit, and plasticity index. It may be used when a precise engineering classification is
required, especially for highway construction purposes. Evaluation of soils within each
group is made by means of a group index, which is a value calculated from an empirical
formula.
AASHTO METHOD M145: Standard Specification for Classification of Soils and Soil–
This recommended practice describes a procedure for classifying soils into seven
groups based on laboratory determination of particle size distribution, liquid limit, and
plasticity index. Evaluation of soils within each group is made by means of a “group
index,” which is a value calculated from an empirical formula. The group classification,
including group index, should be useful in determining the relative quality of the soil
subbases, and bases. However, for the detailed design of important structures, additional
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
and plasticity index. According to ASTM D2487-17, there are three major soil divisions:
coarse-grained soils, fine-grained soils, and highly organic soils. These are subdivided
further into 15 basic groups, each with its own group symbol (e.g. GW).
material
Experiment Procedure:
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
where:
LL = Liquid limit
PI = plasticity index
Experiment Procedure:
- Compare R4 to 50% of CF
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
- Check F200
- Check F200
b. Check LL to 50%
2. Check criteria of the 4th column of Table 4.2 and identify Group Symbol at the 5th
column.
- Plot (LL, PI) in plasticity chart to check if above, on, or below A - line
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
3. If group symbol is already available, determine the group name using Figures 4.4, 4.5,
and 4.6.
ASTM D2166: Standard Test Method For Unconfined Compressive Strength Of Cohesive
Soil
This test method is applicable only to cohesive materials which will not expel or
bleed water (water expelled from the soil due to deformation or compaction) during the
loading portion of the test and which will retain intrinsic strength after removal of
confining pressures, such as clays or cemented soils. Dry and crumbly soils, fissured or
varved materials, silts, peats, and sands cannot be tested with this method to obtain
Apparatus:
Proving ring of 0.01 kg sensitivity for soft soils; 0.05 kg for stiff soils.
Soil trimmer.
coating).
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
maintain the emperature at the desired level. What is the range of the
Vernier calipers
Experiment Procedure:
1. Place the sampling soil specimen at the desired water content and density in the
large mould.
2. Push the sampling tube into the large mould and remove the sampling tube filled
with the soil. For undisturbed samples, push the sampling tube into the clay
sample.
4. Coat the split mould lightly with a thin layer of grease. Weigh the mould.
5. Extrude the sample out of the sampling tube into the split mould, using the
6. Trim the two ends of the specimen in the split mould. Weigh the mould with the
specimen.
7. Remove the specimen from the split mould by splitting the mould into two parts.
8. Measure the length and diameter of the specimen with vernier calipers.
9. Place the specimen on the bottom plate of the compression machine. Adjust the
10. Adjust the dial gauge and the proving ring gauge to zero.
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
11. Apply the compression load to cause an axial strain at the rate of ½ to 2% per
minute.
12. Record the dial gauge reading, and the proving ring reading every thirty seconds
up to a strain of 6%. The reading may be taken after every 60 seconds for a strain
13. Continue the test until failure surfaces have clearly developed or until an axial
14. Measure the angle between the failure surface and the horizontal, if possible.
15. Take the sample from the failure zone of the specimen for the water content
determination.
ASTM D3080: Standard Test Method For Direct Shear Test Of Soils Under Consolidated
Drained Conditions
This test method covers the determination of the consolidated drained shear
strength of a soil material in direct shear. The test is performed by deforming a specimen
configuration of the apparatus. Generally, three or more specimens are tested, each
under a different normal load, to determine the effects upon shear resistance and
Apparatus:
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
Balance.
Experiment Procedure:
2. Measure the diameter and height of the shear box. Compute 15% of the
diameter in millimeters.
3. Carefully assemble the shear box and place it in the direct shear device. Then
4. Place the sand into the shear box and level off the top. Place a filter paper, a
porous stone, and a top plate (with ball) on top of the sand
5. Remove the large alignment screws from the shear box. Open the gap between
the shear box halves to approximately 0.025 in. using the gap screws, and then
6. Weigh the pan of soil again and compute the mass of soil used.
7. Complete the assembly of the direct shear device and initialize the three gauges
(Horizontal displacement gage, vertical displacement gage and shear load gage)
to zero.
8. Set the vertical load (or pressure) to a predetermined value, and then close
bleeder valve and apply the load to the soil specimen by raising the toggle
switch.
9. Start the motor with selected speed so that the rate of shearing is at a selected
constant rate, and take the horizontal displacement gauge, vertical displacement
gage and shear load gage readings. Record the readings on the data sheet. (Note:
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
10. Continue taking readings until the horizontal shear load peaks and then falls, or
Mass of Moisture :
Mass 1 - Mass 2
Mass 2 - Mass 3
Moisture Content:
Mass of Moisture
MC =
Mass of Dry Soil
MC1 + MC 2 + MC 3
¿):
3
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
Mass of Soil:
Ms = W ps +W P
K (W S )
Gs =
W S +W FW @T x −W FWS
Mass of Soil Retained = (mass of sieve plus soil retained) - (mass of sieve)
Total Mass:
(Cumulative % Retained)n:
% Passing:
Uniformity Coefficient, C u:
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
D60
Cu =
D10
Coefficient of Gradation, C c :
( D30 )2
Cc =
D 10 x D6 0
Sorting Coefficient, So :
So =
√ D75
D25
mw
Moisture Content, % = x 100 %
ms
PLASTIC LIMIT
mw
Moisture Content, % = x 100 %
ms
w 1 + w 2+ w 3
Plastic Limit, % =
3
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
SHRINKAGE LIMIT
USDA
% Sand
M.% Sand = x (100 %)
100 % −%Gravel
% Silt
M.% Silt = x (100 %)
100 % −%Gravel
% Clay
M.% Clay = x (100 %)
100 % −%Gravel
AASHTO
USCS
GF = R4 = 100% - F 4
SF = F 4= F 4 − F 200
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
FF = F 200
AREA, Ao :
π
( D )2
4 o
2
πr h
SAMPLE DEFORMATION, γ :
UNIT STRAIN, ε :
γ
ε= x 100 %
LO
1
CF = ε
1−
100 %
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
SAMPLE STRESS:
P x 1000
q u=
CA
CA = CF x Ao
NORMAL LOAD, P:
P = m 1+ m 2
P
ϑ' =
Ao
SHEAR:
V = DR x LD
SHEAR STRESS:
V
τ=
Ao
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
Following are the results of the different tests conducted in the geotechnical laboratory
With the following data presented in the unconfined compression test, the average UCS
and USS of the soil is xx and xx, respectively. With this …. (add a brief discussion based
*For data that doesn’t require a graph, present your data in a paragraph. (In the
moisture content investigation, it was observed that the calculated average moisture of
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
..and so on. (The soil sample was found to be SP-SM under the USCS classification, A-5-6
With the gathered data of the soil, bearing capacity calculation can be determined based
Df =
Pu =
Groundwater table is located 2m below the footing depth, and Correlations were used in
obtaining SPT-N value equivalent, and Unit Weight of soil by Kulhawy and Mayne (1990)
and. …….
Present all equations used in the correlations and calculation of the bearing capacity.
Settlement was also found to be 12mm(example) which is lesser than the allowable
CHAPTER 5: COMPUTATIONS
Present all calculations and tables not included in the Data and results.
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
Mass of Moisture (m w ¿
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
USDA
Modified Percent:
Modified % Sand
% Sand 78.40 %
M.% Sand ¿ × 100 %= × 100 %=100 %
100 % −%Gravel 100 % − 21.60 %
Modified % Silt
% S ilt 0%
M.% Silt ¿ × 100 %= × 100 %=0 %
100 % −%Gravel 100 % − 21.60 %
Modified % Clay
% Clay 0%
M.% Clay ¿ × 100 %= × 100 %=0 %
100 % −%Gravel 100 % − 21.60 %
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
AASHTO
Soil Sample:
No.200 = 17.76% ≤ 35% ∴ Granular Material
Notes:
For the following classifications: A–1–a, A–1–b, A–3, A–2–4, and A–2 –5
∴ GI = 0
∴ A–1–b (0) = Excellent to Good
USCS
Soil Sample:
FF = F200 ¿ 17.76 %
CF = R200 ¿ 100 % −17.76 %=82.24 %
Table 4.2:
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
∴ Coarse-Grained Soil
GF = R4 ¿ 100 % − 91.308 %=8.692 %<50 %
∴ Sands
Since FF ¿ 17.76 %> 12%
∴ Sands with fines
Since PI ¿ 3.006 % <4∧¿=46.376 % (Plots Below A Line )
Group Symbol: SM
Figure 4.4:
GF = R4 ¿ 8.692 %<15 % Gravel
∴ Silty Sand
∴ Soil Sample: SM; Silty Sand
Area ( Ao )
π 2 π 2 2
Ao = (Do ) = (89.30 mm) =6263.1498 mm
4 4
Volume of the Soil (V)
89.30 mm 2
V=V =π r 2 h=π ( ) (130.473 mm)=204,292.986mm
3
2
Sample Deformation ( γ )
γ = deformation dial div ×deformation dial
25.4 mm
¿ 0.001 ¿ ×
*Deformation Dial ¿ mm
1∈¿=0.0254 ¿
¿
mm
γ 1=5÷×0.0254 =0.127 mm
¿
mm
γ 2=10÷×0.0254 =0.254 mm
¿
mm
γ 3=1 5÷× 0.0254 =0.381 mm
¿
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
mm
γ 4 =20÷× 0.0254 =0.508 mm
¿
mm
γ 5=2 5÷×0.0254 =0.635 mm
¿
mm
γ 6=30÷× 0.0254 =0.762mm
¿
mm
γ 7=3 5÷×0.0254 =0.889mm
¿
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
mm
γ 8=40÷× 0.0254 =1.016 mm
¿
mm
γ 9=4 5÷×0.0254 =1.143 mm
¿
mm
γ 10=50÷×0.0254 =1.270 mm
¿
mm
γ 11=55÷×0.0254 =1.397 mm
¿
mm
γ 12=60÷×0.0254 =1.524 mm
¿
mm
γ 13=6 5÷×0.0254 =1.651 mm
¿
mm
γ 14=70÷×0.0254 =1.778 mm
¿
mm
γ 15=7 5÷×0.0254 =1.905 mm
¿
mm
γ 16=80÷×0.0254 =2.032mm
¿
mm
γ 17=8 5÷×0.0254 =2.159 mm
¿
mm
γ 18=90÷×0.0254 =2.286 mm
¿
mm
γ 19=9 5÷×0.0254 =2.413 mm
¿
mm
γ 20=100÷×0.0254 =2.540 mm
¿
mm
γ 21=10 5÷× 0.0254 =2.667 mm
¿
mm
γ 22=110÷×0.0254 =2.794 mm
¿
mm
γ 23=115÷×0.0254 =2,921 mm
¿
mm
γ 24=120÷×0.0254 =3.048 mm
¿
Unit Strain (ɛ)
γ
ε= ×100 %
LO
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
γ 0.127 mm
ε 1= ×100 %= ×100 %=0.097 %
LO 130.473mm
γ 0.254 mm
ε 2= ×100 %= ×100 %=0.195 %
LO 130.473mm
γ 0.381 mm
ε 3= ×100 %= ×100 %=0.292 %
LO 130.473 mm
γ 0.508 mm
ε 4= × 100 %= × 100 %=0.389 %
LO 130.473 mm
γ 0.635 mm
ε 5= ×100 %= ×100 %=0.487 %
LO 130.473 mm
γ 0.762 mm
ε 6= ×100 %= ×100 %=0.584 %
LO 130.473 mm
γ 0.889 mm
ε 7= ×100 %= ×100 %=0.681 %
LO 130.473 mm
γ 1.016 mm
ε 8= ×100 %= ×100 %=0.779 %
LO 130.473 mm
γ 1.143 mm
ε 9= ×100 %= ×100 %=0.876 %
LO 130.473 mm
γ 1.270 mm
ε 10= ×100 %= ×100 %=0.973 %
LO 130.473 mm
γ 1.397 mm
ε 11= × 100 %= ×100 %=1.071 %
LO 130.473 mm
γ 1.524 mm
ε 12= × 100 %= ×100 %=1.168 %
LO 130.473 mm
γ 1.651mm
ε 13= ×100 %= ×100 %=1.265 %
LO 130.473 mm
γ 1.778 mm
ε 14= ×100 %= ×100 %=1.362 %
LO 130.473 mm
γ 1.905 mm
ε 15= ×100 %= ×100 %=1.460 %
LO 130.473 mm
γ 2.032mm
ε 16= ×100 %= ×100 %=1.557 %
LO 130.473mm
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
γ 2.159mm
ε 17= ×100 %= ×100 %=1.655 %
LO 130.473mm
γ 2.286 mm
ε 18= ×100 %= ×100 %=1.752 %
LO 130.473 mm
γ 2.413 mm
ε 19= × 100 %= ×100 %=1.849 %
LO 130.473 mm
γ 2.540 mm
ε 20= ×100 %= ×100 %=1.947 %
LO 130.473 mm
γ 2.667 mm
ε 21= × 100 %= ×100 %=2.044 %
LO 130.473 mm
γ 2.794 mm
ε 22= × 100 %= ×100 %=2.141 %
LO 130.473 mm
γ 2,921mm
ε 23= ×100 %= ×100 %=2.239 %
LO 130.473 mm
γ 3.048 mm
ε 24= ×100 %= ×100 %=2.336 %
LO 130.473 mm
Total Load Sample (P)
P = Load Dial Div ×Load Dial Reading; Load Dial = 1.90 N/Div
N
P1=1.90 ×8÷¿ 15.20 N
¿
N
P2=1.90 ×10.5÷¿ 19.95 N
¿
N
P3=1.90 ×15÷¿ 28.50 N
¿
N
P4 =1.90 × 19÷¿ 36.10 N
¿
N
P5=1.90 ×23÷¿ 43.70 N
¿
N
P6=1.90 ×26.5÷¿ 50.35 N
¿
N
P7=1.90 ×30÷¿ 57.00 N
¿
N
P8=1.90 ×34÷¿64.60 N
¿
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
N
P9=1.90 ×38÷¿ 72.20 N
¿
N
P10 =1.90 × 42÷¿ 79.80 N
¿
N
P11 =1.90 ×47÷¿ 89.30 N
¿
N
P12 =1.90 ×50.5÷¿ 95.95 N
¿
N
P13=1.90 ×55÷¿ 104.50 N
¿
N
P14 =1.90 ×58÷¿ 110.20 N
¿
N
P15 =1.90 ×62÷¿117.80 N
¿
N
P16 =1.90 ×67÷¿ 127.30 N
¿
N
P17=1.90 ×70.5÷¿ 133.95 N
¿
N
P18=1.90 ×75÷¿ 142.50 N
¿
N
P19=1.90 ×75.5÷¿143.45 N
¿
N
P20 =1.90 ×80÷¿ 152.00 N
¿
N
P21 =1.90 ×80÷¿ 152.00 N
¿
N
P22 =1.90 ×82÷¿155.80 N
¿
N
P23 =1.90 ×79.5÷¿ 157.05 N
¿
N
P24 =1.90 × 80÷¿ 152.00 N
¿
Correction Factor (CF)
1
CF = ε
1−
100 %
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
1 1
CF 1= = =1.001
ε 0.097 %
1− 1−
100 % 100 %
1 1
CF 2 = = =1.002
ε 0.195 %
1− 1−
100 % 100 %
1 1
CF 3 = = =1.003
ε 0.292 %
1− 1−
100 % 100 %
1 1
CF 4= = =1.004
ε 0.389 %
1− 1−
100 % 100 %
1 1
CF 5 = = =1.005
ε 0.487 %
1− 1−
100 % 100 %
1 1
CF 6 = = =1.006
ε 0.584 %
1− 1−
100 % 100 %
1 1
CF 7 = = =1.007
ε 0681 %
1− 1−
100 % 100 %
1 1
CF 8 = = =1.008
ε 0.779 %
1− 1−
100 % 100 %
1 1
CF 9= = =1.009
ε 0.876 %
1− 1−
100 % 100 %
1 1
CF 10= = =1.010
ε 0.973 %
1− 1−
100 % 100 %
1 1
CF 11= = =1.011
ε 1.071%
1− 1−
100 % 100 %
1 1
CF 12= = =1.012
ε 1.168 %
1− 1−
100 % 100 %
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
1 1
CF 13= = =1.013
ε 1.265 %
1− 1−
100 % 100 %
1 1
CF 14 = = =1.014
ε 1.363 %
1− 1−
100 % 100 %
1 1
CF 15= = =1.015
ε 1.460 %
1− 1−
100 % 100 %
1 1
CF 16= = =1.016
ε 1.557 %
1− 1−
100 % 100 %
1 1
CF 17= = =1.017
ε 1.655 %
1− 1−
100 % 100 %
1 1
CF 18= = =1.018
ε 1.752 %
1− 1−
100 % 100 %
1 1
CF 19= = =1.019
ε 1.849 %
1− 1−
100 % 100 %
1 1
CF 20= = =1.020
ε 1.947 %
1− 1−
100 % 100 %
1 1
CF 21= = =1.021
ε 2.044 %
1− 1−
100 % 100 %
1 1
CF 22= = =1.022
ε 2.141%
1− 1−
100 % 100 %
1 1
CF 23= = =1.023
ε 2.239 %
1− 1−
100 % 100 %
1 1
CF 24 = = =1.024
ε 2.336 %
1− 1−
100 % 100 %
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
Sample Stress (q u)
P × 1000
q u=
CA
P ×1000 15.20 ×1000
q u1= = =2.425 KPa
CA 6269.252 mm
2
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
Area of Specimen ( AO )
L1 + L2 + L3 2
Average Lengtℎ= ; AO =( Average Lengtℎ)
3
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
2
1m 2
Ao1 =[4.9+ 4.9+ 4.6 ¿ cm× ¿ ¿ 3] =0.002304 m
100 cm
2
1m 2
Ao2 =[5.1+4.7+ 4.8 ¿ cm× ¿ ¿ 3] =0.002401 m
100 cm
2
1m 2
Ao3 =[5.3+ 4.9+ 5.0 ¿ cm× ¿ ¿ 3] =0.002601 m
100 cm
Load Dial ( LD )
lbs. 4.448 N N
LD=0.31 × =1.379
¿ 1 lb . ¿
Weight Added, kg
0.4535924 kg
Specimen1=10 lbs .× =4.536 kg
1 lb.
0.4535924 kg
Specimen2=2 0 lbs. × =9.072 kg
1lb .
0.4535924 kg
Specimen3=3 0 lbs .× =13.608 kg
1 lb.
Normal Load (P)
P = m 1+ m 2
P1=7.5 kg +4.535934 kg=12.036 kg
Normal Load (ϑ )
P
ϑ' =
Ao
m 1 KN
12.036 kg × 9.81 ×
s 1000 N KPa
2
P
ϑ '1 = = 2
=51.247
Ao 0.002304 m
m 1 KN
16.572 kg × 9.81 ×
P s 1000 N
2 KPa
ϑ ' 2= = =67.709
Ao 0.002401 m 2
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
m 1 KN
21.108 kg ×9.81 ×
P s2 1000 N KPa
ϑ '3 = = 2
=79.611
Ao 0.002601m
Shear ( V)
V = DR ×LD
N
V 1=1.379 ×75÷¿ 103.425 N
¿
N
V 2=1.379 ×68÷¿ 93.772 N
¿
N
V 3=1.379 × 97÷¿ 133.763 N
¿
Shear Stress ( τ )
V
τ=
Ao
1 KN
103.425 N ×
1000 N
τ1= =44.88 9 KPa
0.002304 m2
1 KN
93.772 N ×
1000 N
τ 2= 2
=39.055 KPa
0.002401m
1 KN
133.763 N ×
1000 N
τ3= =51.428 KPa
0.002601m2
Cohesion, C’
C’ = 32 KPa
Angle of Friction, Ø’
Ø’= 11˚
Shear Stress , τ
41.961+45.161+ 47.475
τ= =44.866 K Pa
3
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
APPENDICES
C. Documentation
D. Tables Used
Add here all tables like the once used in Classification System, tables for Nc, Nq, and
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
REFERENCES
[2] M.P. Moseley and K. Kirsch (2004). Ground Improvement 2 nd Edition. Spoon Press.
[3] Peter G. Nicholson (2015). Soil Improvement and Ground Modification Methods.
Massachusetts, USA
[4] Klaus Kirsch and Allan Bell (2013). Ground Improvement 3 rd Edition. CRC Press.
[5] Jie Han (2015). Principles and Practice of Ground Improvement. John Wiley & Sons,
[6] Paolo Croce et.al. (2014). Jet Grouting: Technology, Design and Control. CRC Press.
[7] Keller UK. Jet Grouting: An efficient and versatile method for soil treatment.
[8] Joanna Bzowka (2012). Analysis of Bearing Capacity and Settlement of Jet Grouting
https://delibra.bg.polsl.pl/Content/28060/BCPS_31626_-_Analysis-of-bearing-
_0000.pdf
CIVIL ENGINEERING
SAINT LOUIS UNIVERSITY
Jet-grouted Columns In Sandy and Silty Soils. Journal on African Earth Sciences.
https://doi.org/10.1016/j.jafrearsci.2016.01.011
[10] American Society for Civil Engineers (2014). Case Histories of Ground Treatment
[11] Modoni Giuseppe et.al. (2019). Strength of Sandy and Clayey Soils Cemented with
Single and Double Fluid Jet Grouting. Journal on Soils and Foundation.
https://doi.org/10.1016/j.sandf.2019.03.007
[12] Onder Akcakal et.al. (2016). Deep Foundation under Wind Turbines: A Case Study.
[13] Department of Public Works and Highways (2015). Design Guidelines, Criteria and
https://www.dpwh.gov.ph/dpwh/sites/default/files/issuances/DO_179_s2015.pdf on
CIVIL ENGINEERING