Republic of the Philippines

DEPARTMENT OF THE INTERIOR AND LOCAL GOVERNMENT


BUREAU OF FIRE PROTECTION REGIONAL OFFICE 5
OFFICE OF THE CITY FIRE MARSHAL
TABACO CITY FIRE STATION
Ziga Avenue, Tabaco City Tel. No.487-4432 Cp No. +639488506663

12 August 2014 September 12 2015


Date
NUMBER: 2015-003-A

INSPECTION ORDER

TO
SFO1 ROMULO C DIZON/FO2PETER JOHN M MARINDA/FO1 JR B ZEPEDA/
FO1 OWEN SERRANO/FO1 JOEL NERBES/FO1 HYREN A TRIPULCA BFP

PROCEED
Christian Hauz of Uniform Cynthia Casi Rizal St., Cormidal TC

PURPOSE To conduct Fire Safety Inspection to determine compliance of provisions of the Fire Code of
INITIAL the Philippines of 2008, (RA 9514)
RE-
INSPECTION
DURATION Until inspection Is finished.
REMARKS OR 1. Coordinate with the owner, Submit After Inspection Report within Seventy Two Hours (72). Be in
ADDITIONAL proper uniform.
INSTRUCTION

RECOMMEND APPROVAL:

SFO1 Ronaldo A Celestial BFP____


Chief, Fire Safety Enforcement Section
APPROVED:

CINSP BERNADETTE D MADRID BFP


CITY FIRE MARSHAL
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
ACKNOWLEDGEMENT
This is to acknowledge that permission was granted to the above-named Fire Safety Inspector/s accompanied by authorized
representative to conduct Fire Safety Inspection within the premises in accordance to law.

_____________________________________________ ___________________
Signature over Printed Name/Authorized Representative Date/Time

“PAALALA:” MAHIGPIT NA IPINAGBABAWAL NG BUREAU OF FIRE PROTECTION SA MGA KAWANI NITO ANG MAGBENTA O
MAGREKOMENDA NG ANUMANG BRAND NG FIRE EXTINGUISHER”
Violator shall be apprehended pursuant to applicable provisions of RA 9514 or Fire
Code of the Philippines of 2008.

_____ ALREADY INSPECTED _____ CANNOT BE LOCATED _____ CHANGED NAME ____CLOSED/NO
OPERATION DURING INSPECTION _____ NOT INSPECTED _____ NOT EXISTING _____PERMANENTLY CLOSED
_____ RELOCATED _____ RESCHEDULED _____ UNDER RENOVATION _____ OTHERS/PLS SPECIFY______________________
Republic of the Philippines
DEPARTMENT OF THE INTERIOR AND LOCAL GOVERNMENT
BUREAU OF FIRE PROTECTION REGIONAL OFFICE 5
OFFICE OF THE CITY FIRE MARSHAL
TABACO CITY FIRE STATION
Ziga Avenue, Tabaco City Tel. No.487-4432 Cp No. +639488506663

12 August 2014 September 12 2015


Date
NUMBER: 2015-004-A

INSPECTION ORDER

TO
SFO1 ROMULO C DIZON/FO2PETER JOHN M MARINDA/FO1 JR B ZEPEDA/
FO1 OWEN SERRANO/FO1 JOEL NERBES/FO1 HYREN A TRIPULCA BFP

PROCEED
Alsons Trading Salvacion Ballesteros T. Cabiles St. San Juan TC

PURPOSE To conduct Fire Safety Inspection to determine compliance of provisions of the Fire Code of
INITIAL the Philippines of 2008, (RA 9514)
RE-
INSPECTION
DURATION Until inspection Is finished.
REMARKS OR 1. Coordinate with the owner, Submit After Inspection Report within Seventy Two Hours (72). Be in
ADDITIONAL proper uniform.
INSTRUCTION

RECOMMEND APPROVAL:

SFO1 Ronaldo A Celestial BFP____


Chief, Fire Safety Enforcement Section
APPROVED:

CINSP BERNADETTE D MADRID BFP


CITY FIRE MARSHAL
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
ACKNOWLEDGEMENT
This is to acknowledge that permission was granted to the above-named Fire Safety Inspector/s accompanied by authorized
representative to conduct Fire Safety Inspection within the premises in accordance to law.

_____________________________________________ ___________________
Signature over Printed Name/Authorized Representative Date/Time

“PAALALA:” MAHIGPIT NA IPINAGBABAWAL NG BUREAU OF FIRE PROTECTION SA MGA KAWANI NITO ANG MAGBENTA O
MAGREKOMENDA NG ANUMANG BRAND NG FIRE EXTINGUISHER”
Violator shall be apprehended pursuant to applicable provisions of RA 9514 or Fire
Code of the Philippines of 2008.

_____ ALREADY INSPECTED _____ CANNOT BE LOCATED _____ CHANGED NAME ____CLOSED/NO
OPERATION DURING INSPECTION _____ NOT INSPECTED _____ NOT EXISTING _____PERMANENTLY CLOSED
_____ RELOCATED _____ RESCHEDULED _____ UNDER RENOVATION _____ OTHERS/PLS SPECIFY______________________
Republic of the Philippines
DEPARTMENT OF THE INTERIOR AND LOCAL GOVERNMENT
BUREAU OF FIRE PROTECTION REGIONAL OFFICE 5
OFFICE OF THE CITY FIRE MARSHAL
TABACO CITY FIRE STATION
Ziga Avenue, Tabaco City Tel. No.487-4432 Cp No. +639488506663

12 August 2014
Date
NUMBER: 2015-005-A

INSPECTION ORDER

TO
SFO1 ROMULO C DIZON/FO2PETER JOHN M MARINDA/FO1 JR B ZEPEDA/
FO1 OWEN SERRANO/FO1 JOEL NERBES/FO1 HYREN A TRIPULCA BFP

PROCEED
Adrian Mae Marketing Christine Cea Pier Site, Quinale TC

PURPOSE To conduct Fire Safety Inspection to determine compliance of provisions of the Fire Code of
INITIAL the Philippines of 2008, (RA 9514)
RE-
INSPECTION
DURATION Until inspection Is finished.
REMARKS OR 1. Coordinate with the owner, Submit After Inspection Report within Seventy Two Hours (72). Be in
ADDITIONAL proper uniform.
INSTRUCTION

RECOMMEND APPROVAL:

SFO1 Ronaldo A Celestial BFP____


Chief, Fire Safety Enforcement Section
APPROVED:

CINSP BERNADETTE D MADRID BFP


CITY FIRE MARSHAL
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
ACKNOWLEDGEMENT
This is to acknowledge that permission was granted to the above-named Fire Safety Inspector/s accompanied by authorized
representative to conduct Fire Safety Inspection within the premises in accordance to law.

_____________________________________________ ___________________
Signature over Printed Name/Authorized Representative Date/Time

“PAALALA:” MAHIGPIT NA IPINAGBABAWAL NG BUREAU OF FIRE PROTECTION SA MGA KAWANI NITO ANG MAGBENTA O
MAGREKOMENDA NG ANUMANG BRAND NG FIRE EXTINGUISHER”
Violator shall be apprehended pursuant to applicable provisions of RA 9514 or Fire
Code of the Philippines of 2008.

_____ ALREADY INSPECTED _____ CANNOT BE LOCATED _____ CHANGED NAME ____CLOSED/NO
OPERATION DURING INSPECTION _____ NOT INSPECTED _____ NOT EXISTING _____PERMANENTLY CLOSED
_____ RELOCATED _____ RESCHEDULED _____ UNDER RENOVATION _____ OTHERS/PLS SPECIFY______________________
Republic of the Philippines
DEPARTMENT OF THE INTERIOR AND LOCAL GOVERNMENT
BUREAU OF FIRE PROTECTION REGIONAL OFFICE 5
OFFICE OF THE CITY FIRE MARSHAL
TABACO CITY FIRE STATION
Ziga Avenue, Tabaco City Tel. No.487-4432 Cp No. +639488506663

12 August 2014 September 12 2015


Date
NUMBER: 2015-006-A

INSPECTION ORDER

TO
SFO1 ROMULO C DIZON/FO2PETER JOHN M MARINDA/FO1 JR B ZEPEDA/
FO1 OWEN SERRANO/FO1 JOEL NERBES/FO1 HYREN A TRIPULCA BFP

PROCEED
Heliewa International
CD-R King Corporation G/F Tabaco City Mall, P-1, Divino Rostro TC

PURPOSE To conduct Fire Safety Inspection to determine compliance of provisions of the Fire Code of
INITIAL the Philippines of 2008, (RA 9514)
RE-
INSPECTION
DURATION Until inspection Is finished.
REMARKS OR 1. Coordinate with the owner, Submit After Inspection Report within Seventy Two Hours (72). Be in
ADDITIONAL proper uniform.
INSTRUCTION

RECOMMEND APPROVAL:

SFO1 Ronaldo A Celestial BFP____


Chief, Fire Safety Enforcement Section
APPROVED:

CINSP BERNADETTE D MADRID BFP


CITY FIRE MARSHAL
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
ACKNOWLEDGEMENT
This is to acknowledge that permission was granted to the above-named Fire Safety Inspector/s accompanied by authorized
representative to conduct Fire Safety Inspection within the premises in accordance to law.

_____________________________________________ ___________________
Signature over Printed Name/Authorized Representative Date/Time

“PAALALA:” MAHIGPIT NA IPINAGBABAWAL NG BUREAU OF FIRE PROTECTION SA MGA KAWANI NITO ANG MAGBENTA O
MAGREKOMENDA NG ANUMANG BRAND NG FIRE EXTINGUISHER”
Violator shall be apprehended pursuant to applicable provisions of RA 9514 or Fire
Code of the Philippines of 2008.

_____ ALREADY INSPECTED _____ CANNOT BE LOCATED _____ CHANGED NAME ____CLOSED/NO
OPERATION DURING INSPECTION _____ NOT INSPECTED _____ NOT EXISTING _____PERMANENTLY CLOSED
_____ RELOCATED _____ RESCHEDULED _____ UNDER RENOVATION _____ OTHERS/PLS SPECIFY______________________
Republic of the Philippines
DEPARTMENT OF THE INTERIOR AND LOCAL GOVERNMENT
BUREAU OF FIRE PROTECTION REGIONAL OFFICE 5
OFFICE OF THE CITY FIRE MARSHAL
TABACO CITY FIRE STATION
Ziga Avenue, Tabaco City Tel. No.487-4432 Cp No. +639488506663

12 August 2014
Date
NUMBER: 2015-222-A

INSPECTION ORDER

TO
SFO1 ROMULO C DIZON/FO2PETER JOHN M MARINDA/FO1 JR B ZEPEDA/
FO1 OWEN SERRANO/FO1 JOEL NERBES/FO1 HYREN A TRIPULCA BFP

PROCEED
apaloosa tailoring & gen. mdse Nelson Mayor Burgos St., San Juan TC

PURPOSE To conduct Fire Safety Inspection to determine compliance of provisions of the Fire Code of
INITIAL the Philippines of 2008, (RA 9514)
RE-
INSPECTION
DURATION Until inspection Is finished.
REMARKS OR 1. Coordinate with the owner, Submit After Inspection Report within Seventy Two Hours (72). Be in
ADDITIONAL proper uniform.
INSTRUCTION

RECOMMEND APPROVAL:

SFO1 Ronaldo A Celestial BFP____


Chief, Fire Safety Enforcement Section
APPROVED:

CINSP BERNADETTE D MADRID BFP


CITY FIRE MARSHAL
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
ACKNOWLEDGEMENT
This is to acknowledge that permission was granted to the above-named Fire Safety Inspector/s accompanied by authorized
representative to conduct Fire Safety Inspection within the premises in accordance to law.

_____________________________________________ ___________________
Signature over Printed Name/Authorized Representative Date/Time

“PAALALA:” MAHIGPIT NA IPINAGBABAWAL NG BUREAU OF FIRE PROTECTION SA MGA KAWANI NITO ANG MAGBENTA O
MAGREKOMENDA NG ANUMANG BRAND NG FIRE EXTINGUISHER”
Violator shall be apprehended pursuant to applicable provisions of RA 9514 or Fire
Code of the Philippines of 2008.

_____ ALREADY INSPECTED _____ CANNOT BE LOCATED _____ CHANGED NAME ____CLOSED/NO
OPERATION DURING INSPECTION _____ NOT INSPECTED _____ NOT EXISTING _____PERMANENTLY CLOSED
_____ RELOCATED _____ RESCHEDULED _____ UNDER RENOVATION _____ OTHERS/PLS SPECIFY______________________
Republic of the Philippines
DEPARTMENT OF THE INTERIOR AND LOCAL GOVERNMENT
BUREAU OF FIRE PROTECTION REGIONAL OFFICE 5
OFFICE OF THE CITY FIRE MARSHAL
TABACO CITY FIRE STATION
Ziga Avenue, Tabaco City Tel. No.487-4432 Cp No. +639488506663

12 August 2014 September 12 2015


Date
NUMBER: 2015-008-A

INSPECTION ORDER

TO
SFO1 ROMULO C DIZON/FO2PETER JOHN M MARINDA/FO1 JR B ZEPEDA/
FO1 OWEN SERRANO/FO1 JOEL NERBES/FO1 HYREN A TRIPULCA BFP

PROCEED
Ecleo's tailoring Paliencia Ecleo Llorente St. Quinale TC

PURPOSE To conduct Fire Safety Inspection to determine compliance of provisions of the Fire Code of
INITIAL the Philippines of 2008, (RA 9514)
RE-
INSPECTION
DURATION Until inspection Is finished.
REMARKS OR 1. Coordinate with the owner, Submit After Inspection Report within Seventy Two Hours (72). Be in
ADDITIONAL proper uniform.
INSTRUCTION

RECOMMEND APPROVAL:

SFO1 Ronaldo A Celestial BFP____


Chief, Fire Safety Enforcement Section
APPROVED:

CINSP BERNADETTE D MADRID BFP


CITY FIRE MARSHAL
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
ACKNOWLEDGEMENT
This is to acknowledge that permission was granted to the above-named Fire Safety Inspector/s accompanied by authorized
representative to conduct Fire Safety Inspection within the premises in accordance to law.

_____________________________________________ ___________________
Signature over Printed Name/Authorized Representative Date/Time

“PAALALA:” MAHIGPIT NA IPINAGBABAWAL NG BUREAU OF FIRE PROTECTION SA MGA KAWANI NITO ANG MAGBENTA O
MAGREKOMENDA NG ANUMANG BRAND NG FIRE EXTINGUISHER”
Violator shall be apprehended pursuant to applicable provisions of RA 9514 or Fire
Code of the Philippines of 2008.

_____ ALREADY INSPECTED _____ CANNOT BE LOCATED _____ CHANGED NAME ____CLOSED/NO
OPERATION DURING INSPECTION _____ NOT INSPECTED _____ NOT EXISTING _____PERMANENTLY CLOSED
_____ RELOCATED _____ RESCHEDULED _____ UNDER RENOVATION _____ OTHERS/PLS SPECIFY______________________
Republic of the Philippines
DEPARTMENT OF THE INTERIOR AND LOCAL GOVERNMENT
BUREAU OF FIRE PROTECTION REGIONAL OFFICE 5
OFFICE OF THE CITY FIRE MARSHAL
TABACO CITY FIRE STATION
Ziga Avenue, Tabaco City Tel. No.487-4432 Cp No. +639488506663

12 August 2014 September 12 2015


Date
NUMBER: 2015-009-A

INSPECTION ORDER

TO
SFO1 ROMULO C DIZON/FO2PETER JOHN M MARINDA/FO1 JR B ZEPEDA/
FO1 OWEN SERRANO/FO1 JOEL NERBES/FO1 HYREN A TRIPULCA BFP

PROCEED
City Fashion Haus & Gen. Mdse. Lucila Nimfa JJ Bldg., Herrera St., Quinale, TC

PURPOSE To conduct Fire Safety Inspection to determine compliance of provisions of the Fire Code of
INITIAL the Philippines of 2008, (RA 9514)
RE-
INSPECTION
DURATION Until inspection Is finished.
REMARKS OR 1. Coordinate with the owner, Submit After Inspection Report within Seventy Two Hours (72). Be in
ADDITIONAL proper uniform.
INSTRUCTION

RECOMMEND APPROVAL:

SFO1 Ronaldo A Celestial BFP____


Chief, Fire Safety Enforcement Section
APPROVED:

CINSP BERNADETTE D MADRID BFP


CITY FIRE MARSHAL
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
ACKNOWLEDGEMENT
This is to acknowledge that permission was granted to the above-named Fire Safety Inspector/s accompanied by authorized
representative to conduct Fire Safety Inspection within the premises in accordance to law.

_____________________________________________ ___________________
Signature over Printed Name/Authorized Representative Date/Time

“PAALALA:” MAHIGPIT NA IPINAGBABAWAL NG BUREAU OF FIRE PROTECTION SA MGA KAWANI NITO ANG MAGBENTA O
MAGREKOMENDA NG ANUMANG BRAND NG FIRE EXTINGUISHER”
Violator shall be apprehended pursuant to applicable provisions of RA 9514 or Fire
Code of the Philippines of 2008.

_____ ALREADY INSPECTED _____ CANNOT BE LOCATED _____ CHANGED NAME ____CLOSED/NO
OPERATION DURING INSPECTION _____ NOT INSPECTED _____ NOT EXISTING _____PERMANENTLY CLOSED
_____ RELOCATED _____ RESCHEDULED _____ UNDER RENOVATION _____ OTHERS/PLS SPECIFY______________________
Republic of the Philippines
DEPARTMENT OF THE INTERIOR AND LOCAL GOVERNMENT
BUREAU OF FIRE PROTECTION REGIONAL OFFICE 5
OFFICE OF THE CITY FIRE MARSHAL
TABACO CITY FIRE STATION
Ziga Avenue, Tabaco City Tel. No.487-4432 Cp No. +639488506663

12 August 2014 September 12 2015


Date
NUMBER: 2015-010-A

INSPECTION ORDER

TO
SFO1 ROMULO C DIZON/FO2PETER JOHN M MARINDA/FO1 JR B ZEPEDA/
FO1 OWEN SERRANO/FO1 JOEL NERBES/FO1 HYREN A TRIPULCA BFP

PROCEED
Clarahil trading Raul Peña MMG Bldg. RM.207-208 Tayhi TC

PURPOSE To conduct Fire Safety Inspection to determine compliance of provisions of the Fire Code of
INITIAL the Philippines of 2008, (RA 9514)
RE-
INSPECTION
DURATION Until inspection Is finished.
REMARKS OR 1. Coordinate with the owner, Submit After Inspection Report within Seventy Two Hours (72). Be in
ADDITIONAL proper uniform.
INSTRUCTION

RECOMMEND APPROVAL:

SFO1 Ronaldo A Celestial BFP____


Chief, Fire Safety Enforcement Section
APPROVED:

CINSP BERNADETTE D MADRID BFP


CITY FIRE MARSHAL
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
ACKNOWLEDGEMENT
This is to acknowledge that permission was granted to the above-named Fire Safety Inspector/s accompanied by authorized
representative to conduct Fire Safety Inspection within the premises in accordance to law.

_____________________________________________ ___________________
Signature over Printed Name/Authorized Representative Date/Time

“PAALALA:” MAHIGPIT NA IPINAGBABAWAL NG BUREAU OF FIRE PROTECTION SA MGA KAWANI NITO ANG MAGBENTA O
MAGREKOMENDA NG ANUMANG BRAND NG FIRE EXTINGUISHER”
Violator shall be apprehended pursuant to applicable provisions of RA 9514 or Fire
Code of the Philippines of 2008.

_____ ALREADY INSPECTED _____ CANNOT BE LOCATED _____ CHANGED NAME ____CLOSED/NO
OPERATION DURING INSPECTION _____ NOT INSPECTED _____ NOT EXISTING _____PERMANENTLY CLOSED
_____ RELOCATED _____ RESCHEDULED _____ UNDER RENOVATION _____ OTHERS/PLS SPECIFY______________________
Republic of the Philippines
DEPARTMENT OF THE INTERIOR AND LOCAL GOVERNMENT
BUREAU OF FIRE PROTECTION REGIONAL OFFICE 5
OFFICE OF THE CITY FIRE MARSHAL
TABACO CITY FIRE STATION
Ziga Avenue, Tabaco City Tel. No.487-4432 Cp No. +639488506663

12 August 2014
Date
NUMBER: 2015-012-A

INSPECTION ORDER

TO
SFO1 ROMULO C DIZON/FO2PETER JOHN M MARINDA/FO1 JR B ZEPEDA/
FO1 OWEN SERRANO/FO1 JOEL NERBES/FO1 HYREN A TRIPULCA BFP

PROCEED
Cuakimta Commercial corporation Aurora Cua T. Cabiles St., San Juan TC

PURPOSE To conduct Fire Safety Inspection to determine compliance of provisions of the Fire Code of
INITIAL the Philippines of 2008, (RA 9514)
RE-
INSPECTION
DURATION Until inspection Is finished.
REMARKS OR 1. Coordinate with the owner, Submit After Inspection Report within Seventy Two Hours (72). Be in
ADDITIONAL proper uniform.
INSTRUCTION

RECOMMEND APPROVAL:

SFO1 Ronaldo A Celestial BFP____


Chief, Fire Safety Enforcement Section
APPROVED:

CINSP BERNADETTE D MADRID BFP


CITY FIRE MARSHAL
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
ACKNOWLEDGEMENT
This is to acknowledge that permission was granted to the above-named Fire Safety Inspector/s accompanied by authorized
representative to conduct Fire Safety Inspection within the premises in accordance to law.

_____________________________________________ ___________________
Signature over Printed Name/Authorized Representative Date/Time

“PAALALA:” MAHIGPIT NA IPINAGBABAWAL NG BUREAU OF FIRE PROTECTION SA MGA KAWANI NITO ANG MAGBENTA O
MAGREKOMENDA NG ANUMANG BRAND NG FIRE EXTINGUISHER”
Violator shall be apprehended pursuant to applicable provisions of RA 9514 or Fire
Code of the Philippines of 2008.

_____ ALREADY INSPECTED _____ CANNOT BE LOCATED _____ CHANGED NAME ____CLOSED/NO
OPERATION DURING INSPECTION _____ NOT INSPECTED _____ NOT EXISTING _____PERMANENTLY CLOSED
_____ RELOCATED _____ RESCHEDULED _____ UNDER RENOVATION _____ OTHERS/PLS SPECIFY______________________
Republic of the Philippines
DEPARTMENT OF THE INTERIOR AND LOCAL GOVERNMENT
BUREAU OF FIRE PROTECTION REGIONAL OFFICE 5
OFFICE OF THE CITY FIRE MARSHAL
TABACO CITY FIRE STATION
Ziga Avenue, Tabaco City Tel. No.487-4432 Cp No. +639488506663

12 August 2014
Date
NUMBER: 2015-020-A

INSPECTION ORDER

TO
SFO1 ROMULO C DIZON/FO2PETER JOHN M MARINDA/FO1 JR B ZEPEDA/
FO1 OWEN SERRANO/FO1 JOEL NERBES/FO1 HYREN A TRIPULCA BFP

PROCEED
Ellana Anatyn Ellana, Elma Divino Rostro, TC

PURPOSE To conduct Fire Safety Inspection to determine compliance of provisions of the Fire Code of
INITIAL the Philippines of 2008, (RA 9514)
RE-
INSPECTION
DURATION Until inspection Is finished.
REMARKS OR 1. Coordinate with the owner, Submit After Inspection Report within Seventy Two Hours (72). Be in
ADDITIONAL proper uniform.
INSTRUCTION

RECOMMEND APPROVAL:

SFO1 Ronaldo A Celestial BFP____


Chief, Fire Safety Enforcement Section
APPROVED:

CINSP BERNADETTE D MADRID BFP


CITY FIRE MARSHAL
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
ACKNOWLEDGEMENT
This is to acknowledge that permission was granted to the above-named Fire Safety Inspector/s accompanied by authorized
representative to conduct Fire Safety Inspection within the premises in accordance to law.

_____________________________________________ ___________________
Signature over Printed Name/Authorized Representative Date/Time

“PAALALA:” MAHIGPIT NA IPINAGBABAWAL NG BUREAU OF FIRE PROTECTION SA MGA KAWANI NITO ANG MAGBENTA O
MAGREKOMENDA NG ANUMANG BRAND NG FIRE EXTINGUISHER”
Violator shall be apprehended pursuant to applicable provisions of RA 9514 or Fire
Code of the Philippines of 2008.

_____ ALREADY INSPECTED _____ CANNOT BE LOCATED _____ CHANGED NAME ____CLOSED/NO
OPERATION DURING INSPECTION _____ NOT INSPECTED _____ NOT EXISTING _____PERMANENTLY CLOSED
_____ RELOCATED _____ RESCHEDULED _____ UNDER RENOVATION _____ OTHERS/PLS SPECIFY______________________
Republic of the Philippines
DEPARTMENT OF THE INTERIOR AND LOCAL GOVERNMENT
BUREAU OF FIRE PROTECTION REGIONAL OFFICE 5
OFFICE OF THE CITY FIRE MARSHAL
TABACO CITY FIRE STATION
Ziga Avenue, Tabaco City Tel. No.487-4432 Cp No. +639488506663

12 August 2014
Date
NUMBER: 2015-024-A

INSPECTION ORDER

TO
SFO1 ROMULO C DIZON/FO2PETER JOHN M MARINDA/FO1 JR B ZEPEDA/
FO1 OWEN SERRANO/FO1 JOEL NERBES/FO1 HYREN A TRIPULCA BFP

PROCEED
NIETO SARI-SARI / #5 G/F MARKET, DIVINO ROSTRO, TABACO CITY/

PURPOSE To conduct Fire Safety Inspection to determine compliance of provisions of the Fire Code of
INITIAL the Philippines of 2008, (RA 9514)
RE-
INSPECTION
DURATION Until inspection Is finished.
REMARKS OR 1. Coordinate with the owner, Submit After Inspection Report within Seventy Two Hours (72). Be in
ADDITIONAL proper uniform.
INSTRUCTION

RECOMMEND APPROVAL:

SFO1 Ronaldo A Celestial BFP____


Chief, Fire Safety Enforcement Section
APPROVED:

CINSP BERNADETTE D MADRID BFP


CITY FIRE MARSHAL
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
ACKNOWLEDGEMENT
This is to acknowledge that permission was granted to the above-named Fire Safety Inspector/s accompanied by authorized
representative to conduct Fire Safety Inspection within the premises in accordance to law.

_____________________________________________ ___________________
Signature over Printed Name/Authorized Representative Date/Time

“PAALALA:” MAHIGPIT NA IPINAGBABAWAL NG BUREAU OF FIRE PROTECTION SA MGA KAWANI NITO ANG MAGBENTA O
MAGREKOMENDA NG ANUMANG BRAND NG FIRE EXTINGUISHER”
Violator shall be apprehended pursuant to applicable provisions of RA 9514 or Fire
Code of the Philippines of 2008.

_____ ALREADY INSPECTED _____ CANNOT BE LOCATED _____ CHANGED NAME ____CLOSED/NO
OPERATION DURING INSPECTION _____ NOT INSPECTED _____ NOT EXISTING _____PERMANENTLY CLOSED
_____ RELOCATED _____ RESCHEDULED _____ UNDER RENOVATION _____ OTHERS/PLS SPECIFY______________________
Republic of the Philippines
DEPARTMENT OF THE INTERIOR AND LOCAL GOVERNMENT
BUREAU OF FIRE PROTECTION REGIONAL OFFICE 5
OFFICE OF THE CITY FIRE MARSHAL
TABACO CITY FIRE STATION
Ziga Avenue, Tabaco City Tel. No.487-4432 Cp No. +639488506663

12 August 2014
Date
NUMBER: 2015-027-A

INSPECTION ORDER

TO
SFO1 ROMULO C DIZON/FO2PETER JOHN M MARINDA/FO1 JR B ZEPEDA/
FO1 OWEN SERRANO/FO1 JOEL NERBES/FO1 HYREN A TRIPULCA BFP

PROCEED
Tabaco Liberty Commercial Tabaco Liberty Commercial
Center Inc. Center Inc. Ziga Ave. San juan TC

PURPOSE To conduct Fire Safety Inspection to determine compliance of provisions of the Fire Code of
INITIAL the Philippines of 2008, (RA 9514)
RE-
INSPECTION
DURATION Until inspection Is finished.
REMARKS OR 1. Coordinate with the owner, Submit After Inspection Report within Seventy Two Hours (72). Be in
ADDITIONAL proper uniform.
INSTRUCTION

RECOMMEND APPROVAL:

SFO1 Ronaldo A Celestial BFP____


Chief, Fire Safety Enforcement Section
APPROVED:

CINSP BERNADETTE D MADRID BFP


CITY FIRE MARSHAL
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
ACKNOWLEDGEMENT
This is to acknowledge that permission was granted to the above-named Fire Safety Inspector/s accompanied by authorized
representative to conduct Fire Safety Inspection within the premises in accordance to law.

_____________________________________________ ___________________
Signature over Printed Name/Authorized Representative Date/Time

“PAALALA:” MAHIGPIT NA IPINAGBABAWAL NG BUREAU OF FIRE PROTECTION SA MGA KAWANI NITO ANG MAGBENTA O
MAGREKOMENDA NG ANUMANG BRAND NG FIRE EXTINGUISHER”
Violator shall be apprehended pursuant to applicable provisions of RA 9514 or Fire
Code of the Philippines of 2008.

_____ ALREADY INSPECTED _____ CANNOT BE LOCATED _____ CHANGED NAME ____CLOSED/NO
OPERATION DURING INSPECTION _____ NOT INSPECTED _____ NOT EXISTING _____PERMANENTLY CLOSED
_____ RELOCATED _____ RESCHEDULED _____ UNDER RENOVATION _____ OTHERS/PLS SPECIFY______________________
Republic of the Philippines
DEPARTMENT OF THE INTERIOR AND LOCAL GOVERNMENT
BUREAU OF FIRE PROTECTION REGIONAL OFFICE 5
OFFICE OF THE CITY FIRE MARSHAL
TABACO CITY FIRE STATION
Ziga Avenue, Tabaco City Tel. No.487-4432 Cp No. +639488506663

12 August 2014
Date
NUMBER: 2015-033-A

INSPECTION ORDER

TO
SFO1 ROMULO C DIZON/FO2PETER JOHN M MARINDA/FO1 JR B ZEPEDA/
FO1 OWEN SERRANO/FO1 JOEL NERBES/FO1 HYREN A TRIPULCA BFP

PROCEED
Romeo Casaul Technological Romeo Casaul Technological
Institute Institute T. Cabiles St. San Juan TC

PURPOSE To conduct Fire Safety Inspection to determine compliance of provisions of the Fire Code of
INITIAL the Philippines of 2008, (RA 9514)
RE-
INSPECTION
DURATION Until inspection Is finished.
REMARKS OR 1. Coordinate with the owner, Submit After Inspection Report within Seventy Two Hours (72). Be in
ADDITIONAL proper uniform.
INSTRUCTION

RECOMMEND APPROVAL:

SFO1 Ronaldo A Celestial BFP____


Chief, Fire Safety Enforcement Section
APPROVED:

CINSP BERNADETTE D MADRID BFP


CITY FIRE MARSHAL
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
ACKNOWLEDGEMENT
This is to acknowledge that permission was granted to the above-named Fire Safety Inspector/s accompanied by authorized
representative to conduct Fire Safety Inspection within the premises in accordance to law.

_____________________________________________ ___________________
Signature over Printed Name/Authorized Representative Date/Time

“PAALALA:” MAHIGPIT NA IPINAGBABAWAL NG BUREAU OF FIRE PROTECTION SA MGA KAWANI NITO ANG MAGBENTA O
MAGREKOMENDA NG ANUMANG BRAND NG FIRE EXTINGUISHER”
Violator shall be apprehended pursuant to applicable provisions of RA 9514 or Fire
Code of the Philippines of 2008.

_____ ALREADY INSPECTED _____ CANNOT BE LOCATED _____ CHANGED NAME ____CLOSED/NO
OPERATION DURING INSPECTION _____ NOT INSPECTED _____ NOT EXISTING _____PERMANENTLY CLOSED
_____ RELOCATED _____ RESCHEDULED _____ UNDER RENOVATION _____ OTHERS/PLS SPECIFY______________________