OUTGOING 1 (29/05/2023) Page 1

Properties
Customer : VNG2
Project :
Switchboard :
Cubicle :
Print date : 29/05/23
OUTGOING 1 (29/05/2023) Page 2

Sepam hardware configuration


Type of application : Transformer (T20)
Sepam Type : OUTGOING 1
Sepam model : UD model (with fixed advanced UMI)
MES (Input / output module) : MES114 (10I + 4O module)
MET148 (8 temperature sensors module) : Absent
MSA141 (1 analog output module) : Absent
DSM303 (Remote advanced UMI module) : Absent
Interface de communication : Absent
Synchronization mode : Network
OUTGOING 1 (29/05/2023) Page 3

Program logic
Circuit breaker control : Yes
Logic discrimination : No
Protections excluded from CB control :
50/51 - 1A : No
50/51 - 1B : No
50/51 - 2A : No
50/51 - 2B : No
50N/51N - 1A : No
50N/51N - 1B : No
50N/51N - 2A : No
50N/51N - 2B : No
46 : No

Use of logic inputs


I11 : Open position
I12 : Closed position
I13 : Customized use
I14 : Customized use
I21 : POS External tripping 1
I22 : POS External tripping 2
I23 : Customized use
I24 : Customized use
I25 : Customized use
I26 : Customized use

Set up outputs
Used Shunt coil Undervoltage coil Impulsed mode
O1 Yes X
O2 Yes X
O3 Yes X
O4 Yes X
O11 Yes X
O12 Yes X
O13 Yes X
O14 Yes X
OUTGOING 1 (29/05/2023) Page 4

General characteristics
Network frequency : 50 Hz
Setting group : A
Remote setting enabled : No
Sepam working language : English
CT rating : TC 5A
Number of CTs : I1, I2, I3
Rated current (In) : 50 A
Base current (Ib) : 50 A
Integration period : 5 mn
Residual current : 3I sum
Rated residual current (In0) : 50 A
Number of periods which are memorised before the fault recording trigger : 36 Periods
OUTGOING 1 (29/05/2023) Page 5

Protection: Phase overcurrent (50/51)


Element number : 1
Element activity : On

Setting group A
Tripping curve : Very inverse time
Threshold current : 45 A
Delay : 200 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : Yes
Icc current : 6300 A

Setting group B
Tripping curve : Definite time
Threshold current : 300 A
Delay : 300 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : No
Icc current : 6300 A

Tripping behavior
Output O1 - Type : Shunt coil
Output O1 - Mode: Continuous
Latching : Yes
Activate output O1 : Yes
Trigger fault recording : With
Activate indicators : L1, L9
OUTGOING 1 (29/05/2023) Page 6

Protection: Phase overcurrent (50/51)


Element number : 2
Element activity : On

Setting group A
Tripping curve : Definite time
Threshold current : 300 A
Delay : 50 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : Yes
Icc current : 6300 A

Setting group B
Tripping curve : Definite time
Threshold current : 300 A
Delay : 300 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : No
Icc current : 6300 A

Tripping behavior
Output O1 - Type : Shunt coil
Output O1 - Mode: Continuous
Latching : Yes
Activate output O1 : Yes
Trigger fault recording : With
Activate indicators : L2, L9
OUTGOING 1 (29/05/2023) Page 7

Protection: Earth fault (50N/51N)


Element number : 1
Element activity : On

Setting group A
Tripping curve : Long time inverse
Threshold current : 20 A
Delay : 200 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : Yes

Setting group B
Tripping curve : Definite time
Threshold current : 630 A
Delay : 300 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : No

Tripping behavior
Output O1 - Type : Shunt coil
Output O1 - Mode: Continuous
Latching : Yes
Activate output O1 : Yes
Trigger fault recording : With
Activate indicators : L3, L9
OUTGOING 1 (29/05/2023) Page 8

Protection: Earth fault (50N/51N)


Element number : 2
Element activity : On

Setting group A
Tripping curve : Definite time
Threshold current : 250 A
Delay : 50 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : Yes

Setting group B
Tripping curve : Definite time
Threshold current : 630 A
Delay : 300 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : No

Tripping behavior
Output O1 - Type : Shunt coil
Output O1 - Mode: Continuous
Latching : Yes
Activate output O1 : Yes
Trigger fault recording : With
Activate indicators : L4, L9
OUTGOING 1 (29/05/2023) Page 9

Protection: Thermal overload (49RMS)


Element activity : Off

Basic settings (group A)


Heat rise alarm set point : 85 %
Heat rise tripping set point : 120 %
Heating time constant : 20 mn
Cooling time constant : 20 mn

Advanced settings
Negative sequence factor : None (0)
Initial heat rise value : 0 %
Thermal overload inhibited by I26 : No
Accounting for ambient temperature : No

Additional settings (group B)


Activity : Off
Switching mode between A and B : Is
Switching current Is : 50 % of Ib
Heat rise alarm set point : 85 %
Heat rise tripping set point : 120 %
Heating time constant : 20 mn
Cooling time constant : 20 mn
Initial heat rise value : 0 %

Alarm behavior
Activate an output : No
Activate indicators : Without

Tripping behavior
Output O1 - Type : Shunt coil
Output O1 - Mode: Continuous
Activate output O1 : Yes
Activate indicators : L9
OUTGOING 1 (29/05/2023) Page 10

Protection: Negative sequence current / unbalance (46)


Element activity : Off

Setting group
Tripping curve : Definite time
Threshold current : 10 % of Ib
Delay : 100 ms

Tripping behavior
Output O1 - Type : Shunt coil
Output O1 - Mode: Continuous
Latching : No
Activate output O1 : Yes
Trigger fault recording : With
Activate indicators : Without