Reveal Panel RZ GB 013 04 20
Reveal Panel RZ GB 013 04 20
Reveal Panel RZ GB 013 04 20
Exclusion of Liability
RHEINZINK GmbH & Co. KG takes account of state-of-the-art technology, product development and research at all times in its technical opinions. Such comments or
recommendations are based on installation as is possible in standard cases in a European climate, specifically the indoor climate prevailing in Europe. We are of course
unable to cater for all conceivable circumstances, which may call for restrictions and/or further measures in individual cases. This means that on no account are such
comments provided by RHEINZINK GmbH & Co. KG any substitute for the advice or planning offered by an architect/consultant or contractor in charge of a specific
building project under consideration of the specific circumstances prevailing on site.
Usage of documentation made available by RHEINZINK GmbH & Co. KG constitutes a service for which no liability can be assumed for losses or further claims of
whatever nature. This does not affect liability arising in the case of intent, gross negligence or injury to life, limb or human health. Claims to compensation governed by
the German Product Liability Act shall be likewise by unaffected thereby.
13th edition
© 2020 RHEINZINK GmbH & Co. KG
All rights reserved. No part of this book may be reproduced in any form without written permission of RHEINZINK GmbH & Co. KG.
Foreword
This document describes the use of This document is based on our practi-
RHEINZINK-Reveal Panels. Although cal experience and represents the latest
it forms the basis for proper planning findings from research and development,
and classical application solutions, it is recognised standards and state-of-the-
no more than a guide for users. The de- art technology. We reserve the right to
tailed drawings included here describe make changes at any time in the course
solutions which are feasible at a practi- of further development.
cal level.
Please also note our information on the
We should like to explicitly point out that material and its processing on our web-
in actual practice it may not be possible sites.
to create the type of cladding illustrated
in this document – or not to their full ex- f you have any queries or suggestions,
tent. In this context every situation should please contact your customer advisor or
be examined in detail by the planner in get in touch with your local RHEINZINK
charge. It is necessary here to take ac- sales office. All contact data can be found
count of the system-specific effects on on our homepage www.rheinzink.com/
the property and local/climatic condi- contact
tions as well as the requirements in terms
of building physics. Compliance with the Datteln, May 2020
application techniques and specifications
described here does not release users
from any responsibility in this regard.
REVEAL PANELS, DESIGN AND APPLICATION
CONTENTS
2.8 Details
2.8.1 General Instructions
2.8.2 Pictograph
2.10 Design,
Overview horizontal Sections
Details horizontal Sections
2.11 Design,
Overview vertical Sections
Details vertical Sections
Reference Projects
Illustrations
REVEAL PANELS, DESIGN AND APPLICATION
PRODUCT LINES
blue-grey
RHEINZINK-CLASSIC RHEINZINK-prePATINA
ORIGINAL. PRE-WEATHERED.
EXPRESSIVE. SELF-HEALING.
PATINATES OVER TIME. NATURAL.
ONE BRAND –
5 PRODUCT LINES
CLASSIC
THE PERFECT
SOLUTION
FOR EVERY
REQUIREMENT
prePATINA
gold pearl-gold
brown moss-green
blue nut-brown
red blue
PRISMO
GRANUM
artCOLOR
SKYGREY AND BASALTE. PURE, GREY AESTHETIC, HARMONIOUS MATCH CREATIVE DESIGN POSSIBILITIES.
ELEGANCE. URBAN DESIGN. PHOS- WITH ITS SURROUNDINGS. SUBTLE INDIVIDUAL, EXPRESSIVE COLOUR
PHATED SURFACE WITH COUNTLESS COLOUR VARIETY FOR A UNIQUE COMPOSITIONS. COATED COLOUR
BUILDING PHYSICS
1.
Function of rear-ventilated 1.1 Windproof Building Envelope 1.2 Weather Protection
Facades This does not apply to the rear-ventilated Rear-ventilated facade cladding protects
facade, as this component itself cannot the supporting structure, the water-proo
■ Windproof Building Envelope be windproof. fed thermal facade insulation, and the
■ Weather Protection The building must be windproof before substructure, from the weather.
■ Moisture the rear-ventilated facade is installed. A Bracket-mounted rear-ventilated facades
■ Thermal Economy solid brick or concrete wall will ensure provide a high degree of protection from
■ Fire Protection that the building is windproof. Penetra- driving rain.
■ Rear-Ventilation tions (e.g. windows, ventilation pipes, Because of the physical structure, it is im-
■ Air Intake and Exhaust etc.) must be sealed from the building possible for the rain or capillary water
Openings component to the supporting structure. In transfer to reach the insulating layers.
■ Soundproofing the case of a skeleton construction, the Furthermore, moisture can always be
wall surface must also be sealed. drawn out through the ventilation space.
The rear-ventilated facade is a multi- If the building envelope is improperly This allows the insulating layers to dry
layered system, which, when designed sealed (wind suction, wind pressure), out quickly, without impeding thermal
properly, guarantees permanent func there is a high degree of ventilation/en- insulation.
tional capability. By functional capabil- ergy loss, which, along with drafts, cre-
ity, we mean that all requirements per- ates unpleasant room temperature. Dew 1.3 Moisture
taining to structural physics are met. This or condensation can be expected on the Rear-ventilated facade cladding pro
is described in detail below. leeward side of the building. vides protection from driving rain and
Air circulation in the room should be moisture. Moisture penetration as a result
By separating the rainscreen facade from provided through air conditioning or by of diffusion does not occur in the rear-
the thermal insulation and supporting opening the windows. ventilated facade.
structure, the building is protected from When the supporting structure is wind
the weather. proof, the diffusion current density is too
small to cause the dew point temperature
he supporting outer walls and the insula- to drop.
tion remain dry and thus fully functional.
Even when driving rain penetrates open
joints, it is quickly dried out as a result of
the air circulation in the ventilation space.
The bracket-mounted rear-ventilated fa
cade protects the components from se-
vere temperature influence. Heat loss in
the winter and too much heat gain in the
summer are prevented.
BUILDING PHYSICS
2. RHEINZINK Profile Group struction Products List B, Part 1 (edition Units for Loads and Forces
Reveal Panel SF 25 2015/2), section 1.0 relating to con- The load tables indicate permissible for
The reveal panel opens up a wealth of struction products subject to harmonised ces and loads in kN/m².
design possibilities for the designer, be- standards according to the Construction Deflection values in relation to span
cause it can be installed vertically and Products Directive, section 1.4.10.1 Self- width are given for single span, double
diagonally. Variable spacing of the supporting roof covering and wall clad- span or multi - span conditions.
reveal joints (0-30 mm) underscores ding elements for interior and exterior The following indicators are used for
segmentation when the reveal panel is application made of sheet metal. display purposes:
used. The reveal panel is available in Single span
widths of 200-333 mm. Static Load Tables Double span
Load tables are based on DIN 18807 Multi - span
Technical Approval for profile section properties.
The RHEINZINK-Reveal Panel System is Deflection:
subject to EN 14782 and is approved for 1/180 for facade components
use with substructure spacing ≤ 1.00 m Safety factor:
(other support spacing possible on re- g = 1.50
quest). In Germany the facade system (this is taken into account in the tables)
is additionally governed by the Con-
Span width in m 0.50 0.60 0.80 0.90 1.00 1.20 1.40 1.50 1.60 1.70
Permissible wind load 3.50 3.14 2.83 2.36 2.00 1.89 1.78 1.67
in kN/m2 .20 1.85 1.42 1.28 1.14 0.95 0.86 0.82 0.77 0.73
2.50 2.14 1.56 1.41 1.30 1.09 0.95 0.91 0.87 0.83
SF 25 - 200, s = 1.00 mm
Span width in m 0.50 0.60 0.80 0.90 1.00 1.20 1.40 1.50 1.60 1.70
Permissible wind load 2.83 2.50 2.27 1.89 1.62 1.49 1.40 1.32
in kN/m2
1.78 1.48 1.14 0.99 0.93 0.82 0.70 0.65 0.59 0.53
2.04 1.70 1.30 1.16 1.03 0.91 0.81 0.76 0.71 0.66
SF 25 - 250, s = 1.00 mm
Span width in m 0.50 0.60 0.80 0.90 1.00 1.20 1.40 1.50 1.60 1.70
Permissible wind load 2.82 2.12 1.89 1.71 1.41 1.18 1.07 0.97 0.89
in kN/m2 1.36 1.13 0.89 0.82 0.74 0.59
1.48 1.30 0.98 0.91 0.85 0.72 0.58 0.52
SF 25 - 333, s = 1.00 mm
PROFILE GEOMETRY
F S
Possible Applications
C 200 - 333
■ Facades
=F+J
■ Soffits
■ Parapets System section
Fastening
Using rivets or screws, the panels are
fastened directly onto the substructure,
through the protruding leg of the groove
~ 25
(see detail above).
Linear expansion is restricted by limit-
ing the length of the facade panel, and
accommodated via the deflection of the
substructure.
Dimensions
J = 0 - 30
■ Drawings: Dimensions in mm
■ Panel designation: SF 25 - 287 Joint configuration
(example)
■ Standard length: ≤ 4000 mm
■ : bay width
■ C: cover width
■ : joint width
■ : face width
REVEAL PANELS, DESIGN AND APPLICATION
PROFILE GEOMETRY
RHEINZINK panel, SF 25 with 15 mm Theater am Marientor (previously: Les Misérables), Duisburg, Germany
reveal joint
REVEAL PANELS, DESIGN AND APPLICATION
JOINT FORMATION
Fastening
Using rivets or adhesives, fastening is
one-sided directly onto the substructure
B or onto the lower panel.
C: Cornice Profile
The horizontal joint can be accentuated
by using profiles of varying widths. It is
important not to interrupt or close off the
C rear-ventilation space.
Note:
■ Theoretically, all of the joint forma-
tions illustrated here can be used on
D all vertically installed RHEINZINK
panels.
■ Facade sections should be sepa-
rated by means of expansion joints
- a max. of 4000 mm (Example A,
B, C).
■ When determining panel lengths
(Example C), air intake and ex-
haust openings must be taken into
account.
REVEAL PANELS, DESIGN AND APPLICATION
Facade field
Panel length ≤ 4000 mm
dinated with your local consultant
or the Department of Application
Facade field
Engineering.*
Example B
Facade field
exceeded.
* see www.rheinzink.com
REVEAL PANELS, DESIGN AND APPLICATION
SUBSTRUCTURE
Advantages
■ cost-effective
■ easy accommodation of building
tolerances
■ local thermal bridges only
Disadvantages:
■ two installation procedures
■ depending on the detailing require-
ments additional costs can occur
REVEAL PANELS, DESIGN AND APPLICATION
SUBSTRUCTURE
Multi-part substructure
REVEAL PANELS, DESIGN AND APPLICATION
FASTENING
2.5 Fasteners
Fasteners are parts that connect the clad- least 10 mm. Only corrosion-resistant
ding to the substructure mechanically. fasteners, which guarantee long-term
The edge distance of connections and function capability, may be used.
fasteners in the substructure must be at
Possible Fasteners
Area of Application
Drilling screws to join JT 3 - FR - 6 - 5,5 x 25 - E11
■ RHEINZINK panels
Marking Øx Length Drill capacity Clamping
onto
tI + tII thickness
■ steel substructures
mm mm mm mm
1,5 - 4,0 mm
■ aluminum substructures JT3 - FR - 6 5.5 x 25 min. 0,63 + 1,5 0 - 7.0
1,5 - 4,0 mm max. 2,0 + 4,0
INSTALLATION SEQUENCES
DI
DI
Note:
Tolerance adjustment using adaptor pan-
els ≤ 15 mm difference is hardly notice-
able.
DI: direction of installation
Example A: Example B:
The corner panel is installed first. Building The corner panel is part of the continu-
tolerances are accommodated either by ous installation sequence. Any tolerances
installing an adapter panel in the cen- that need to be adjusted at this point can
tre of the facade, or, next to the outside be accommodated by the corner panel.
corner panel.
REVEAL PANELS, DESIGN AND APPLICATION
DETAIL CONCEPT
Projection of Profiles
Depending on the detail design, the pro-
files either protrude from, or lie flush with
the facade surface.
Profile Group 2
A sharpe-edged profile will be installed
flush with the curtain wall, so that the
window frame design is not accentu-
ated.
Profile Group 3
The jamb profile selected for this window
surround can replicate the joint profile
Profile group 2 Profile group 3 (see profile group 1) and is used as a
flashing in conjunction with the window
sill and lintel.
REVEAL PANELS, DESIGN AND APPLICATION
DETAILS
h<8 ≥ 20 ≥ 40 ≥ 50
8 ≤ h ≤ 20 ≥ 20 ≥ 40 ≥ 80
h > 20 ≥ 20 ≥ 40 ≥ 100
Drip edge distances and overhang dimensions for copings and flashings.
* The overhang dimensions also apply on the roof side. If the roofing foil is routed to
the front edge of the facade without interruption, 50 mm overhang generally apply
independent from the building height.
REVEAL PANELS, DESIGN AND APPLICATION
PLANNING GRID
25
X
manufactured industrially with a high module determines the precise location
degree of precision. These components of penetrations and terminations. In the
determine appearance through precise case of reveal panels, the Y dimension
60
horizontal and vertical segmentation. is discretionary and is produced in cover
Penetrations and terminations that are widths of 200 mm to 333 mm, based on
25
not matched/coordinated with the axis the project.
grid can have a disturbing effect. The bay width (Y) is formed using the
The following instructions serve to assist visible surface of the panel and two half
proper planning of facade segmenta- joints.
C2 = 275
tion: The cover width is established from the
=F+J
visible surface and the width of the joint.
250
Principles The width of the reveal can vary from 0 to
As a rule, a differentiation should be 30 mm and is determined by appropriate
made between new construction and length of the “tongue“.
renovations when discussing grid prob-
lems. In the case of new construction, Dimension X
the facade grid can be coordinated or All of the sections marked with X are an
C1 = 250
In the case of renovations, the penetra-
250
=F
tions (e.g. windows) cannot be displaced
or removed, so the grid must be coordi-
nated with the penetrations.
When deviating from the grid, the follow-
ing principles apply:
■ At terminations, one should begin or
=½J+½J+F
B=y
■ Adjustments or displacements of
=½J+½J+F
60
C
PLANNING GRID
Position Z1 : Base
DESIGN
OVERVIEW
DESIGN
DETAIL H1: OUTSIDE CORNER
H1.1
20c
KA
10a 30a 23
25
MR
18b KA
10i
MR
H1.2
10a
20c
KA
10f 30a 23
25
MR
MR
18b
KA
16v
MR
MR
REVEAL PANELS, DESIGN AND APPLICATION
DESIGN
DETAIL H1: OUTSIDE CORNER
H1.3
10a 30a 23
20c
KA
MR
25
10i 18b
KA Detail H1: Outside Corner
10 RHEINZINK-Reveal Panel SF 25
MR a Standard panel
f Fitting panel
i Corner panel, groove-groove
16 RHEINZINK-Building Profile
v Corner profile
18 Support Profile
b Aluminium
20 Substructure
c Bracket system,
with thermal break*
23 Supporting Structure
25 Thermal Insulation
30 Ventilated Air Space
a Depth of air space ≥ 20 mm
DI Direction of installation
CE Controlled expansion of
substructure
*M anufacturers‘ guidelines must be
complied with
REVEAL PANELS, DESIGN AND APPLICATION
DESIGN
DETAIL H2: INSIDE CORNER
H2.1
23
25
20c
30a KA
MR 10a
10i
MR
MR
10h
KA
10a
MR
H2.2 23
25
20c
30a KA
18b
MR
10i
KA
MR
10a
REVEAL PANELS, DESIGN AND APPLICATION
DESIGN
DETAIL H2: INSIDE CORNER
23 H2.3
25
20c
30a KA
10 RHEINZINK-Reveal Panel SF 25
a Standard panel
f Fitting panel
h Corner panel, groove-tongue
i Corner panel, groove-groove
16 RHEINZINK-Building Profile
v Corner profile
18 Support Profile
b Aluminium
20 Substructure
c Bracket system,
with thermal break*
23 Supporting Structure
25 Thermal Insulation
30 Ventilated Air Space
a Depth of air space ≥ 20 mm
DI Direction of installation
CE Controlled expansion of
substructure
DESIGN
DETAIL H3: WINDOW JAMB
H3.1
23 24
25 16e
20c
30a KA
18d 16h
10a MR
H3.2
23 24
25 16e
20c
18d
30a KA 16h
10a 10f MR
REVEAL PANELS, DESIGN AND APPLICATION
DESIGN
DETAIL H3: WINDOW JAMB
H3.3
23 24
16e
25
20c
18d
30a KA 16h
10a 10f
MR
Detail H3: Window jamb
10 RHEINZINK-Reveal Panel SF 25
a Standard panel
f Fitting panel
16 RHEINZINK-Building Profile
e Receiver strip, with sealant tape
h Jamb profile
18 Support Profile
d Aluminium*
20 Substructure
c Bracket system,
with thermal break**
23 Supporting Structure
24 Window Foil
25 Thermal Insulation
30 Ventilated Air Space
a Depth of air space ≥ 20 mm
DI Direction of installation
CE Controlled expansion of
substructure
DESIGN
OVERVIEW
DESIGN
OVERVIEW
DESIGN
DETAIL V1: BASE
V1.1
10d 30a 25 23
20c
18b
16d
16e
V1.2
10d 30a 25 23
20c
19a 18b
16c
16d
REVEAL PANELS, DESIGN AND APPLICATION
DESIGN
DETAIL V1: BASE
V1.3
10c 30a 25 23
20c
16i
10 RHEINZINK-Reveal Panel SF 25
c Standard panel, with stopend
d Standard panel, with stopend
short
16 RHEINZINK-Building Profile
c Perforated strip
d Base profile
e Receiver strip, with sealant tape
i Termination profile,
partly perforated
18 Support Profile
b Aluminium
19 Separating Layer
a Structured underlay VAPOZINC
n Alternative: glued to support
profile over entire surface
20 Substructure
c Bracket system, with thermal
break*
23 Supporting Structure
25 Thermal Insulation
30 Ventilated Air Space
a Depth of air space ≥ 20 mm
DESIGN
DETAIL V2: WINDOW SILL
V2.1
19a
24
16k
18b 18a 23
16i 18e
20c
10c 30a 25
V2.2
19a
24
16k
18a 23
18b
30a 25
10e 20c
REVEAL PANELS, DESIGN AND APPLICATION
DESIGN
DETAIL V2: WINDOW SILL
V2.3
19a
24
16k
18b 18a 23
20c
10g 30a 25
Detail V2: Window sill
10 RHEINZINK-Reveal Panel SF 25
c Standard panel, with stopend
e Standard panel, with stopend
short, outward-facing
g Fitting panel, with bent up water
drip
16 RHEINZINK-Building Profile
i Connection/termination profile
k Window sill coping
18 Support Profile
a Galvanised steel, support angle
with thermal break
b Aluminium
e Aluminium, partly perforated
19 Separating Layer
a Structured underlay VAPOZINC
n Alternative: glued to support
profile over entire surface
20 Substructure
c Bracket system,
with thermal break*
23 Supporting Structure
24 Window Foil
25 Thermal Insulation
30 Ventilated Air Space
a Depth of air space ≥ 20 mm
DESIGN
DETAIL V3: WINDOW LINTEL
V3.1
20c
10d 30a 25 23
18a
24
16g 18d
V3.2
20c
10d 30a 25
23
24
18a
16g 18d
REVEAL PANELS, DESIGN AND APPLICATION
DESIGN
DETAIL V3: WINDOW LINTEL
V3.3
25
30a
10d 20c
23
24
16g 18d
16e
10 RHEINZINK-Reveal Panel SF 25
d Standard panel, with stopend
short
16 RHEINZINK-Building Profile
e Receiver strip, with sealant tape
g Lintel profile
18 Support Profile
a Galvanised steel, support profile
with thermal break
d Aluminium *
20 Substructure
c Bracket system,
with thermal break **
23 Supporting Structure
24 Window Foil
25 Thermal Insulation
30 Ventilated Air Space
a Depth of air space ≥ 20 mm
DESIGN
DETAIL V4: TWO-PART ROOF EDGE
V4.1
18b 2 19a
≥ 3°
20d 16a
18b
23
10e 30a 25
20c
V4.2
16m 19a
≥ 3°
20c
10e 30a 25
REVEAL PANELS, DESIGN AND APPLICATION
DESIGN
DETAIL V4: TWO-PART ROOF EDGE
V4.3
18b
16m 19a
≥ 3°
18b 20f
16j
20d 18b
23
10g 30a 25
20c
DESIGN
DETAIL V5: EXPANSION JOINT
V5.1
10b 30a 25 23
20c
10k
V5.2
10d 30a 25 23
20c
18b
16l
REVEAL PANELS, DESIGN AND APPLICATION
DESIGN
DETAIL V5: EXPANSION JOINT
V5.3
10c 30a 25 23
20c
16w
10 RHEINZINK-Reveal Panel SF 25
b Standard panel, without stopend
c Standard panel, with stopend
d Standard panel, with stopend
short
k Slave profile, with stopend
16 RHEINZINK-Building Profile
l Cornice coping
w Shadow gap profile,
partly perforated
18 Support Profile
b Aluminium
20 Substructure
c Bracket system,
with thermal break*
23 Supporting Structure
25 Thermal Insulation
30 Ventilated Air Space
a Depth of air space ≥ 20 mm
REFERENCE PROJECTS
1
REVEAL PANELS, DESIGN AND APPLICATION
REFERENCE PROJECTS
2 3
4