Professional Documents
Culture Documents
ENA - TS - 41-37 - Part - 1 General
ENA - TS - 41-37 - Part - 1 General
ENA - TS - 41-37 - Part - 1 General
www.energynetworks.org
PUBLISHING AND COPYRIGHT INFORMATION
All rights reserved. No part of this publication may be reproduced, stored in a retrieval
system or transmitted in any form or by any means, electronic, mechanical, photocopying,
recording or otherwise, without the prior written consent of Energy Networks Association.
Specific enquiries concerning this document should be addressed to:
Operations Directorate
Energy Networks Association
6th Floor, Dean Bradley House
52 Horseferry Rd
London
SW1P 2AF
This document has been prepared for use by members of the Energy Networks
Association to take account of the conditions which apply to them. Advice should be taken
from an appropriately qualified engineer on the suitability of this document for any other
purpose.
Revised, 2015
Contents
Foreword ................................................................................................................................8
1 General ............................................................................................................................9
1.1 Scope .....................................................................................................................9
1.2 Normative references..............................................................................................9
2 Normal and special service conditions ...........................................................................10
2.1 Normal service conditions .....................................................................................10
2.1.1 Indoor switchgear and controlgear ............................................................10
2.1.2 Outdoor switchgear and control gear ........................................................10
2.2 Special service conditions .....................................................................................11
2.2.1 Altitude ......................................................................................................11
2.2.2 Pollution ....................................................................................................11
2.2.3 Temperature and humidity ........................................................................11
2.2.4 Vibrations , shock or tilting ........................................................................11
2.2.5 Wind speed ...............................................................................................11
2.2.6 Other parameters ......................................................................................11
3 Terms and definitions .....................................................................................................11
4 Ratings ..........................................................................................................................13
4.1 Rated voltage (Ur) .................................................................................................13
4.1.1 Range 1 for rated voltages of 245 kV and below ....................................... 13
4.1.2 Range II, for rated voltages above 245 kV ................................................13
4.2 Rated insulation level (Up) .....................................................................................13
4.3 Rated frequency (fr) ..............................................................................................13
4.4 Rated normal current and temperature rise ...........................................................13
4.4.1 Rated normal current (Ir) ...........................................................................13
4.4.2 Temperature rise .......................................................................................14
4.5 Rated short-time withstand current (Ik) ..................................................................14
4.6 Rated peak withstand current (Ip) ..........................................................................14
4.7 Rated duration of short-circuit (tk)..........................................................................14
4.8 Rated supply voltage of closing and opening devices and of auxiliary and
control circuits (Ua) ................................................................................................14
4.8.1 General .....................................................................................................14
4.8.3 Tolerances ...................................................................................................15
The voltage at which switchgear and control equipment should function is to
cater for the boost voltage of the substation battery supplies,
particularly the voltage to boost the supply (110% of 125 V). .................... 15
4.8.4 Ripple voltage ..............................................................................................15
4.10 Rated pressure of compressed gas supply for controlled pressure systems........... 15
5 Design and construction.................................................................................................15
5.1 Requirement for liquids in switchgear and control gear ......................................... 15
5.1.1 Liquid level ................................................................................................15
5.1.2 Liquid quality .............................................................................................15
5.2 Requirements for gases in switchgear and control gear ........................................ 15
ENA Technical Specification 41-37 Part 1
Issue 2 2015
Page 2
Page 4
Page 6
Tables
Table 1 — Rated insulation levels ........................................................................................13
Table 2 — Rated normal current and rated short-time withstand current .............................. 13
Table 3 — Operating voltages ..............................................................................................14
Table 4 — Standard label requirements ...............................................................................25
Table 6 — Maximum allowable temperatures of touchable surfaces .................................... 31
ENA Technical Specification 41-37 Part 1
Issue 2 2015
Page 8
Foreword
This Technical Specification (TS) is published by the Energy Networks Association (ENA)
and comes into effect from date of publication. It has been prepared under the authority of
the ENA Engineering Policy and Standards Manager and has been approved for publication
by the ENA Electricity Networks and Futures Group (ENFG). The approved abbreviated title
of this engineering document is “ENA TS 41-37 Part 1”.
This document replaces and supersedes Technical Specification 41-37 Issue 1 2004.
This Technical Specification has been prepared by the Energy Networks Association.
ENA TS 41-37 is a suite of engineering documents that sets out ENA Member Company
requirements for specification of switchgear for use on 66 kV to 132 kV distribution systems.
ENA TS 41-37 is a multi-part document comprising of the following parts.
This specification should be read in conjunction with the relevant International and British
Standards, and to assist in cross-reference, the document follows the format of the major
International Standards. Where possible, the International Standards’ clause numbers have
been used preceded with the number of the relevant part of this specification.
The Electricity at Work Regulations 1989 made under the Health and Safety at Work Act
1974, apply to switchgear whenever manufactured, purchased or installed. Appendix 2 of the
Memorandum of guidance on the Regulations lists Standards, Codes of Practice and other
publications which contain guidance relevant to the Regulations and electrical safety.
Part 1 of the document covers all common clause requirements of switchgear, as defined.
Clauses specific to particular equipments are covered in the subsequent Parts of the
document.
Annex A of the document provides a summary of range, technical requirements and ratings
for each type of equipment for completion by the Purchaser.
1 General
IEC 62271-1 is the major normative Standard in this document and shall apply except where
modified. Part 1 of this specification amplifies and clarifies the requirements of IEC 62271-1
where alternative arrangements are specified by ENA and further information is necessary to
meet requirements of UK Distribution Network Operators.
1.1 Scope
This specification defines technical requirements for switchgear rated at voltages within the
range 72.5 kV to 145 kV and applies to alternating current switchgear, designed for indoor or
outdoor installation, cable or overhead conductor connected, and for operation at service
frequency of 50Hz on systems having voltages at 66 kV and up to and including 132 kV.
Equipment covered by this specification is for use on systems with the neutral point earthed
solidly, or effectively earthed through a resistor or reactor.
This specification presents the requirements which must be satisfied for all switchgear.
Standards publications
IEC 60445, Basic and safety principles for man-machine interface, marking and identification
– Identification of equipment terminals, conductor terminations and conductors
IEC 60815, Guide for the selection of insulators in respect of polluted conditions
IEC 61109, Insulators for overhead lines – Composite suspension and tension insulators for
a.c. systems with a nominal voltage greater than 1 000 V – Definitions, test methods and
acceptance criteria
IEC 61462, Composite hollow insulators - Pressurized and unpressurized insulators for use
in electrical equipment with rated voltage greater than 1 000 V - Definitions, test methods,
acceptance criteria and design recommendations
IEC 62271-102, High-voltage switchgear and controlgear – Part 102: Alternating current
disconnectors and earthing switches
IEC 62271-203, High-voltage switchgear and controlgear – Part 203: Gas-insulated metal-
enclosed switchgear for rated voltages above 52 kV
ENA Technical Specification 41-37 Part 1
Issue 2 2015
Page 10
IEC 62271-303 High- voltage switchgear and control gear part 303 use and handling of
sulphur hexafluoride (SF6)
BSEN ISO 13732-1 Methods for the assessment of human responses to contact with
surfaces. Hot surfaces
BS EN ISO 13732-1, Ergonomics of the thermal environment. Methods for the assessment of
human responses to contact with surfaces. Hot surfaces
BS 4781, Specification for pressure sensitive adhesive plastic labels for permanent use
BS 5499, Graphic symbols and signs - safety signs, including fire safety signs
Other publications
[N1] Statutory Instrument 1989 No. 635, The Electricity at Work Regulations 1989
[N2] Statutory Instrument 2007 No. 320, The Construction (Design and Management)
Regulations 2007
[N6] ENA TS 50-19, Specification for standard numbering for small wiring for switchgear and
transformers together with their associated relay and control panels
[N7] ENA TS 98-1, Environmental classification and corrosion protection of structures, plant
and equipment
a) The ambient air temperature does not exceed 40 ˚C and its average value, measured
over a period of 24 h, and does not exceed 35 ˚C. The minimum ambient air temperature
is –5 ˚C
2.1.2 Outdoor switchgear and control gear
Sub-clause 2.1.2 of IEC 62217-1 shall apply with the following additions.
ENA Technical Specification 41-37 Part 1
Issue 2 2015
Page 11
a) The ambient air temperature does not exceed 40 ˚C and its average value, measured
over a period of 24 h, and does not exceed 35°C. The minimum ambient air temperature
is –25 ˚C
b) Ice coating shall be 10 mm
2.2 Special service conditions
2.2.1 Altitude
Sub-clause 2.2.1 of IEC 62271-1 does not apply.
2.2.2 Pollution
Sub-clause 2.2.2 of IEC 62271-1 shall apply.
The supplier shall declare the maximum depth of water, measured from the base of the
equipment.(Including transformers, marshalling Kiosks, relay cabinets etc)
The supplier shall clearly define in the installation, commissioning and maintenance
documents for the equipment any special installation measures which are required to
achieve the above declared depths.
3.100
dependent manual operation
operation solely by means of directly applied manual energy, such that the speed and force
of the operation are dependent upon the action of the operator
Page 12
3.101
independent manual operation (of a mechanical switching device)
stored energy operation where the energy originates from manual power, stored and
released in one continuous operation, such that the speed and force of the operation are
independent of the action of the operator
3.102
independent power operation (of a mechanical switching device)
stored energy operation by means of power source other than manual, stored and released
in one continuous operation, such that the speed and force of the operation are independent
of the action of the power source
3.103
anti-pumping device
device which prevents reclosing after a close-open operation, as long as the device initiating
the closing is maintained in the position for closing
3.104
operations
3.104.1 normal operation
when equipment is operated as intended using the manual handle (as supplied by the
manufacturer), control switches, and interlock keys
NOTE: Normal operations includes switching, cable testing, LV isolation, but excludes
maintenance.
NOTE: An example of an emergency operation is using the manual handle (as supplied by
the manufacturer) for motorise equipment, whilst power operation is not available.
Note Unless otherwise stated, where padlocking facilities are required by this Specification,
it shall be possible to meet all such requirements by means of a padlock with 41mm square
body and with a 4mm to 7mm diameter shackle having a clear inside width of 21mm and an
inside length of 16mm to 45mm. The holes provided for the shackle shall not be less than 8
mm diameter.
3.105
Additional Earths
earthing equipment not forming an integral part of the switchgear but for which provision is
made in the design
ENA Technical Specification 41-37 Part 1
Issue 2 2015
Page 13
3.106
Point of Isolation
isolating device locked in the open position
4 Ratings
Clause 4 of IEC 62271-1 shall apply with the additions and exceptions detailed in the
following sub-clauses.
Page 14
4.8 Rated supply voltage of closing and opening devices and of auxiliary and control
circuits (Ua)
4.8.1 General
Sub-clause 4.8.1 of IEC 62271-1 shall apply with the following additions
4.8.2 Rated supply voltage of closing and opening devices and of auxiliary and control
circuits.
Switchgear shall be capable of all normal operations without any effect affecting its rated
performance , within the voltage ranges specified in Table
The number and capacity of cells in batteries, other than lead acid type, e.g. nickel cadmium,
shall ensure reasonable compliance with the voltage limits shown in the Table.3.
ENA Technical Specification 41-37 Part 1
Issue 2 2015
Page 15
4.8.3 Tolerances
Sub-clause 4.8.3 of IEC 62271-1 shall apply with the following modification
The voltage at which switchgear and control equipment should function is to cater for the
boost voltage of the substation battery supplies, particularly the voltage to boost the supply
(110% of 125 V).
a) The tolerances for d.c. voltages shall be as stated in Table 3.
4.8.4 Ripple voltage
Sub-clauses 4.8.4 and 4.8.5 of IEC 62271-1 shall apply.
4.9 Rated supply frequency of closing and opening devices and of auxiliary circuits
4.10 Rated pressure of compressed gas supply for controlled pressure systems
Sub-clauses 4.10 of IEC 62271-1 shall apply.
These Regulations apply to all switchgear supplied within, or supplied into, the EU and they
impose a mandatory duty on ‘designers’ (which includes manufacturers) to provide safe
means of working during the life of the asset by a consideration of safety at the design stage.
Clause 5 of IEC 62271-1 and IEC 62271-203 shall apply with the additions and exceptions of
the following sub-clauses.
a) Hydraulically operated mechanisms shall be provided with a low oil level alarm in the oil
reservoir.
5.1.2 Liquid quality
Sub-clause 5.1.2 of IEC 62271-1 shall apply.
Page 16
The gas service connection for each gas zone shall be readily accessible without the use of
special access equipment. A schematic diagram shall be provided showing the gas zones
within a bay and their relationship to the primary plant of that circuit or bus bar section.
Where main cables are to be connected, two terminals for connecting to the earthing
conductor shall be provided to earth the cable sheath.
5.4.1 Enclosures
5.4.1.1 General
Sub-clauses 5.4.1.1 and 5.4.1.2 of IEC 62271-1 and Sub-clause 6.2 of ENA TS 50-18 [N5]
shall apply.
All wiring shall be readily identified for the purpose of tracing through the equipment.
Page 18
5.4.4.4 Identification
Sub clause 5.4.4.4 of IEC 62271-1 shall apply with the following additional sub-clauses.
5.4.4.5.2.101 Terminal blocks for current transformer (CT) and voltage transformer
(VT) circuits
Sub-clause 7 .2.1 ENA TS 50-18 [N5] shall apply with the following additional sub-clauses.
The integrity of the shorting, and of open circuit of the CT circuits shall be easily established
by visual inspection.
The conductor termination shall satisfy the electrical requirements for the terminal block or
sub-component item to which it is attached.
Terminals and associated blocks shall be suitable for at least 50 disconnections and re-
connections without reduction in electrical or mechanical performance.
Page 20
5.4.4.5.101 SCADA
For each power-operated switching device there shall be the option for the unit to be
equipped with a local/remote control selector switch and SCADA indication of the open/close
position of this switch.
Any separate components associated with maintenance, slow operation shall be labelled
‘FOR MAINTENANCE PURPOSES ONLY’.
a) No movement of the main contacts is permissible before the release of stored energy.
However, in the case of earthing switches, such movement is permissible provided that
the contact movement shall not reduce any electrically stressed gap to below that which
will withstand the rated insulation levels specified.
b) For manual operation it shall only be possible to operate a mechanism by using a
dedicated operating handle applied in the correct manner.
5.6.1 Energy stored in gas receivers or hydraulic accumulators
Sub clause 5.6.1 of IEC 62271-1 shall apply.
This does not apply to springs directly connected to moving contacts as is the case of an
opening spring.
The maximum and minimum allowable handle heights from the operating platform for a hand
charging operation shall be 1 850 mm and 300 mm respectively.
For manual operation it shall only be possible to operate a mechanism by using a dedicated
operating handle applied in the correct manner.
Clear indication shall be given of the direction of motion of an operating handle to complete
the operation.
When not in use, any spring charging handle shall occupy a stowed position where it shall
not cause any obstruction. If the design is such that the handle is lifted into the engaged
position prior to operation, it shall be possible to release it again and return it to the stowed
position without moving the contacts of the switching device.
ENA Technical Specification 41-37 Part 1
Issue 2 2015
Page 22
a) Stored energy operation mechanisms shall be fitted with a local manual release for
opening and closing operations. Provision shall be made for electrical operation from
outside the switch room/ substation. In such cases precautions shall be taken to prevent
transfer of earth potential.
b) No movement of the spring charging handle shall occur as a result of the release of
spring energy to operate the mechanism.
5.8.1 Shunt closing release
Sub-clause 5.8.1 of IEC 62271-1 is not applicable. The voltage limits stated in Table 3 shall
apply.
ENA Technical Specification 41-37 Part 1
Issue 2 2015
Page 23
5.9.101 Gas density gauge or indicator for all equipment other than CTs and VTs
The gas density or temperature compensated gas pressure in each compartment shall be
continuously monitored and indicated locally.
The monitoring device shall provide at least two sets of alarms levels for pressure or density
(alarm and minimum functional pressure or density). A means of checking initiation of the
‘falling’ and ‘low’ density alarms without reducing the pressure in the main circuit
compartment shall be provided. This shall be achieved in such a way that operation of as
much of the alarm circuit as is reasonably practical is confirmed.
Page 24
5.10 Nameplates
Sub-clause 5.10 of IEC 62271-1 shall apply with the following additional sub-clauses.
5.10.100 Labelling
Labels shall be durable non-fading and, apart from circuit labels, permanently attached to the
equipment (pressure sensitive labels conforming to BS 4781 Parts 1 and 2 are considered
permanent).
Any inscriptions on the apparatus itself shall contrast with the background.
The circuit label shall be positioned adjacent to the controls and be clearly legible from the
operating position.
The standard phase markings are L1, L2 and L3 and the convention to be used is that the
right hand terminal, when viewed from the rear of the equipment, shall be the L1 phase. This
convention fulfils the requirements of IEC 60445.
When equipment has double terminals, terminal numbers are U1 U2, V1 V2, W1 W2 in
accordance with IEC 60445.
ENA Technical Specification 41-37 Part 1
Issue 2 2015
Page 25
Circuit breaker, I (as per symbol 5007-a of IEC 60417) or Signal red White
disconnector, ON.
or earthing switch I or ON shall not be used for earthing switch Lemon yellow Black
closed position indications, as per symbol
5017 of IEC 60417 or EARTH ON
Operation push Close: I (as per symbol 5007-a of IEC Black White
buttons 60417)
Page 26
5.11.100 Covers
During normal operation of the switchgear it shall not be possible to remove any covers
forming part of an interlocking or padlocking facility.
Operational interlocking is designed to limit operations for reasons other than safety.
a) the disconnector or (main) switch from being operated unless the associated earthing
switch is open;
b) the earthing switch from being operated unless the disconnector or (main) switch is open;
c) inadvertent operation from disconnector or (main) switch closed to earthing switch;
closed in a single operation;
d) Inadvertent operation from earthing switch closed to disconnector or (main) switch;
closed in a single operation;
Where the motorised disconnector is not fully interlocked, access in an emergency to the
manual operation shall be inhibited by a bolted cover (requiring the use of a tool to remove)
over the manual drive.
ENA Technical Specification 41-37 Part 1
Issue 2 2015
Page 27
Padlocking facilities, each requiring the use of a single padlock without additional loose
devices, shall be provided as follows.
NOTE: Failure mode and effects analysis (FMEA) was one of the first systematic failure
analysis methods adopted by engineering It involves reviewing as many components,
assemblies, and subsystems as possible to identify failure modes, and their causes and
effects. For each component, the failure modes and their resulting effects on the rest of the
system are recorded in a specific FMEA worksheet.
It shall not be possible to remove a cover/facia without first removing all padlocks on that
cover/facia.
Page 28
The indicator shall give an unambiguous indication of the position of the main circuit contacts
and should not be wholly visible until the operation is completed.
5.13.1 Protection of persons against access to hazardous parts and protection of the
equipment against ingress of solid foreign objects
The degree of protection, as per IEC 62271-1 provided by the enclosure against access by
persons to hazardous parts and protection of the equipment against ingress of solid foreign
objects shall be not less than IP3X for indoor equipment and IP3XD for outdoor equipment.
In addition, the design of equipment shall be such that their normal operation will not present
any possibility of contact with a moving mechanism or other possible cause of accidental
injury and shall be not less than IP2X.
Protection against rain and other weather conditions and shall be specified by means of
the supplementary letter W.
5.13.3 Protection of equipment against mechanical impact under normal service
conditions (IK coding)
The following sections of Sub clause 5.13.3 of IEC 62271-1 shall apply.
a) Sub-clause 5.13.3 of IEC 62271-1 shall apply and a minimum impact level IK07 for indoor
equipment shall apply.
b) A minimum impact level IK10 for outdoor equipment shall apply.
5.14 Creepage distances
Sub-clause 5.14 of IEC 62271-1 shall apply with the following additional sub-clause.
a) The leakage rate, Frel, of the gas of a closed pressure system shall be such that it shall
not require replenishment during its expected minimum operating life of 30 years and in
any case the leakage rate shall not exceed 0.5% per year at 20 °C.
5.16 Liquid tightness
Sub-clause 5.16 of IEC 62271-203 and IEC 62271-1 shall apply.
5.20 Corrosion
Safe working access shall be provided to all areas of the equipment where commissioning,
operation or maintenance activities are to be carried out.
To comply with the CDM Regulations [N2] the designers of switchgear have a responsibility
to ensure that the equipment can be safely operated.
It should be noted that conformance with the following sub-clauses will not automatically
ensure that equipment can be safely operated. A full assessment shall take account of the
interaction between height, force, direction of movement, location etc. for the normal
operation.
Page 30
All operations of switching devices shall be from the front of the equipment.
The door latch mechanism shall be padlockable using an approved padlock as described in
Clause 3.104.3 and shall be designed so that the specific IP rating is maintained.
Material finish other than paint systems shall have a performance equal or better than ENA
TS 98-1 [N7].
BS EN ISO 13732-1 and IEC Guide 117 for IEC 62271-1 shall be used to determine the
maximum allowable surface temperature appropriate to the surface contact duration (see
Table 6).
6 Type tests
6.1 General
Sub-clause 6.1 of IEC 62271-1 shall apply with the following additions.
a) All type testing shall be carried out in accordance with Short-circuit Testing Liaison (STL)
Guides where applicable.
b) Dielectric tests on cable connected equipment shall be performed on a test arrangement
agreed between the switchgear and cable termination manufacturers as being
representative of the cable termination systems referred to in Sub-clause 1.5.103.1.101,
made off in the cable box including connectors.
c) Equipment shall be subjected to dielectric tests in its most unfavourable arrangement.
d) Partial discharge tests shall be made. They shall be carried out after all dielectric tests.
For acceptable limits for discharge levels, reference shall be made to ENA TS 41-18 [N3].
ENA Technical Specification 41-37 Part 1
Issue 2 2015
Page 32
Note:-For specific type test requirements, for the various switchgear equipment covered by
this Specification, refer to the relevant type test tables in Parts 2, 3, 4, 5 and 6 of this
specification.
a) Partial discharge tests shall be made after all type and routine dielectric tests.
6.2.10 Dielectric tests on auxiliary and control circuits
Sub-clause 6.2.10 of IEC 62271-1 shall apply.
Sub-clause 6.8.1 of IEC 62271-1 controlled pressure systems for gas shall not apply
Temperature rise tests for outdoor equipment shall include the effects of solar radiation.
Manufacturers shall demonstrate that the influence of solar radiation up to a level of 1 000
W/m² (on a clear day at noon) has been taken into account in the testing of outdoor
equipment, e.g. temperature rise test at maximum solar gain where applicable.
NOTE: Calculations supporting the influence of these effects are acceptable.
6.201 Type test tables
For specific type test requirements, for the various switchgear equipment covered by this
Specification, refer to the relevant type test tables in Parts 2, 3, 4, 5, & 6 of this specification.
6.202 Reduced gas density withstands
Test evidence is required to confirm that devices containing gas other than air at atmospheric
pressure can withstand twice the rated phase to earth voltage applied across the open gap at
atmospheric pressure at 20 °C.
Alternatively, the manufacturer shall state the minimum gas pressure at which the device can
withstand twice the rated phase to earth voltage applied across the open gap at atmospheric
pressure at 20 °C.
A mechanical operations test of 10% of the specified operating cycles shall be performed on
a switching device that is intended for manual operation, but tested using an actuator. The
test shall use the standard production handle as delivered with the equipment or device
provided for the purpose in the manner described in the manufacturer’s handbook.
Page 34
For outdoor equipment, ageing tests shall be made on external composite bushings
and external insulation materials. The ageing test shall be conducted on the same
basis as that described in Annex C of IEC 61109 and should be for a period of not
less than 5 000 hours duration. Insulation manufacturers’ test data may be submitted
for consideration.
7 Routine tests
Clauses 7 to 7.5 inclusive of IEC 62271-1 shall apply.
10.2 Installation
Sub-clauses10.2 to 10.4.3 inclusive of IEC 62271-1 shall apply.
The information should include the above requirements, including the use, handling and
disposal of SF6 in accordance with IEC 62271-303, and method statements in conformance
with the CDM Regulations [N2], including ‘end of life’ statement per Article 4 of EC
Regulation on fluorinated greenhouse gases and controlled recovery of redundant SF6 (by
user/contractor or manufacturer).
ENA Technical Specification 41-37 Part 1
Issue 2 2015
Page 35
The installer shall provide risk assessment and method statements for installation and
commissioning.
Designs shall be such that extension equipment of corresponding type can be placed in the
correct working location without the need to make existing equipment dead and without
exposing live conductors. This requires that the bus bar compartment end cover must not
project beyond the side of the unit and it must be removable from inside the compartment.
11 Safety
Clause 11 to 11.6 inclusive of IEC 62271-1 shall apply.
13 Commissioning tests
13.100 Schedule for site commissioning
At the time of assessment, the manufacturer shall provide a schedule for site commissioning
tests. These tests are to be performed at site following installation and prior to energisation of
the switchgear. These tests shall as a minimum include checks to confirm the functional
operation and control of all installed equipment.
ENA Technical Specification 41-37 Part 1
Issue 2 2015
Page 36
Annex A
(normative)
*Delete as appropriate