Professional Documents
Culture Documents
Definition and Analysis of Receiving System Voltag
Definition and Analysis of Receiving System Voltag
fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/ACCESS.2019.2940409, IEEE Access
Date of publication xxxx 00, 0000, date of current version xxxx 00, 0000.
Digital Object Identifier 10.1109/ACCESS.2017.Doi Number
ABSTRACT Based on the analysis of the relationship between the voltage sensitivity of the receiving
system and the DC power stability, an evaluation index, Receiving System Voltage Support Strength Factor
(RVSF), is proposed in this paper for identifying the voltage support strength of the receiving system. The
threshold of RVSF is derived and used as the criteria for distinguishing the voltage support strength of the
receiving system. The critical Receiving System Voltage Support Strength Factor (CRVSF) can keep
constant in receiving systems which operate in different modes. Furthermore, the analytical expression of
RVSF is derived from the Jacobian matrix form of the incremental flow equation of the AC system. By
deriving the relationship between RVSF and power stability and considering the constraint of commutation
angle, it can be obtained that the receiving system is a very weak system when RVSF<0.60, a weak system
when 0.60<RVSF<2, and a strong system in case of RVSF>2. Finally, the performance of RVSF and other
widely used system strength indicators such as effective short circuit ratio (ESCR) and multi-infeed
effective short circuit ratio (MIESCR) are compared and analyzed. Compared with other indicators, it is
found that RVSF has a clear threshold when measuring the strength of different receiving systems.
INDEX TERMS Multi-infeed HVDC, power stability, receiving system voltage support strength factor
(RVSF), voltage sensitivity.
Ⅰ. INTRODUCTION (SCR), the effective short circuit ratio (ESCR) and the Q
With the development of HVDC transmission technology, effective short circuit ratio (QESCR)[15]. These indicators
lots of HVDC transmission projects have been put into have a clear physical concept, which is calculated by the
operation worldwide. After the implementation of the grid structure parameters and the active power of the DC
"West-to-East Electricity Transmission" strategy in China, system. Based on the constraint of DC power stability, the
a multi-infeed HVDC system has been formed in the load critical short circuit ratio (CSCR) can be derived and used
centers of economically developed regions such as Eastern to distinguish the voltage support strength of the receiving
and Southern China[1]. The increase in the capacity and system. It is generally considered that the critical short
number of HVDC systems fed into the same AC grid has circuit ratio is 2, which means that the LCC-HVDC system
raised the risk of safe and stable operation of the grid and does not work properly under the rated condition when the
brings a series of challenges to the normal operation of the short circuit ratio is less than 2[15]-[16]. In order to
grid[2]. Therefore, accurately measuring the strength of the evaluate the voltage support strength of the receiving
receiving power grid is crucial to ensure the normal system of the multi-infeed system, the CIGRE DC working
operation of the multi-infeed system[3]-[4]. group proposed an index of multi-infeed short circuit ratio
Researchers have done a lot of research on the system (MISCR)[17]. The indicator considers the interaction
structure, control strategy and stable operation of DC between different DC systems, but the selection of the
transmission and distribution[5]-[12].When evaluating the threshold lacks a rigorous theoretical derivation[4]. Based
voltage support strength of the receiving system, the on the multi-infeed system, the reference [18] considers the
indicators based on the grid structure parameters are widely effects of DC system reactive power compensation,
used, like, in a single-infeed system, the short circuit ratio
This work is licensed under a Creative Commons Attribution 4.0 License. For more information, see https://creativecommons.org/licenses/by/4.0/.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/ACCESS.2019.2940409, IEEE Access
different operation modes and parallel AC lines, and applicability of RVSF indicators.
proposes multi-infeed effective short circuit ratio The rest of this paper is organized into seven sections.
(MIESCR), multi-infeed operation short circuit ratio Following the introduction, analysis of DC system power
(MIOSCR) and improved short circuit ratio (ISCR). stability is assessed in Section Ⅱ. The definition of RVSF and
However, these indicators do not fundamentally solve the the threshold for identifying the strength of the receiving
problem that the multi-infeed system voltage support system with RVSF are provided in Section Ⅲ, while
strength index lacks theoretical support and clear threshold. analytical calculation method of RVSF is presented in
Based on an equivalent single-infeed model of a multi- Section Ⅳ. In Section Ⅴ, verification of the effectiveness of
infeed HVDC system, the reference [19] proposed an index RVSF indicator is obtained. Comparison between RVSF and
called equivalent effective short-circuit ratio (EESCR). other system strength indicators is performed in Section Ⅵ
However, since the different modes of operation of DC while the conclusion of this paper is shown in Section Ⅶ.
system are not considered, the proposed equivalent model is
optimistic. In the reference [20] and [21], the relationship Ⅱ. DC SYSTEM POWER STABILITY
between the maximum transmission power and the MISCR
of multi-infeed HVDC system is studied. It is proposed that A. POWER STABILITY ANALYSIS MODEL
the actual strength of the multi-feed HVDC system is The structure of a DC system and its receiving system is
between the MISCR and the SCR. In the reference [3], the shown in Fig. 1. Pd and −Qd indicate active power and
generalized short-circuit ratio index is defined from the reactive power flowing into the converter bus. U and δ are
perspective of the eigenvalue, and the threshold of the the converter bus voltage and its phase angle. The converter
index is determined by the voltage stability criterion, which transformer ratio is denoted as τ. DC voltage and DC
can effectively evaluate the voltage support strength of the current are represented by Ud and Id, and the extinction
multi-infeed system. The shortcoming of this method is that angle is plotted as while the commutation angle is
the steady-state operating characteristics of each DC system written as μ. Specially, the reactive power compensation
are assumed to be the same. Under different operation device on the converter bus is considered as part of the
modes of receiving system, the power transmission and receiving system.
control modes of DC systems are different, so that the For simplicity, the calculations in this paper are based on
steady-state operating characteristics cannot be generalized. the per unit value. the DC power is taken as the rated power
The reference [22] defines the operating impedance of capacity of the system. For the based voltages, the nominal
VSC-HVDC, and ESCR of the system is obtained. In the voltage at AC side and DC side are selected as base
reference [23], all DCs fed into the receiving system are voltages of AC side and DC side, respectively.
equivalent to an equivalent conventional DC, and the We can use the following equations to describe the AC
evaluation index named critical equivalent effective short- system shown in Fig. 1 [15].
circuit ratio(CEESCR) is derived. The indicators proposed
Id
in the above reference are based on the equivalent of DC
systems connected to the grid, and it is difficult to meet the Pd , −Qd :1
Receiving
situation of flexible and variable receiving system. It is a Ud
system
question worth exploring that whether there is a new
indicator that not only has clear threshold but also reflects
U ,
the voltage support strength of the receiving system well in DC system
the case that the receiving system operates flexibly. FIGURE 1. Receiving system model of AC-DC power system.
A voltage support strength index based on DC power
stability and the voltage sensitivity for receiving system is
Pd =CU 2 ( cos 2 − cos(2 + 2 ) ) (1)
proposed in this paper. The main contributions of this paper
are as follow: Qd =CU ( 2 + sin 2 − sin(2 + 2 ) )
2
(2)
1) By deriving the relationship between DC power
I d =KU ( cos − cos( + ) ) (3)
stability and voltage sensitivity, the receiving system
voltage support strength factor (RVSF) is defined to U d = Pd I d (4)
characterize the voltage support strength of the U =f ( Qd , Pd ) (5)
receiving system.
2) Deriving the threshold of RVSF as the identification P = Pd (6)
criteria for the strength of the receiving system. Q = −Qd (7)
3) The analytical expression of RVSF is derived by the
modified Jacobian matrix of the receiving system. Equation (1)-(4) are quasi-steady-state equations for DC
4) Comparing RVSF with other system strength systems. (5) represents the characteristic equation of the
indicators, verifying the superiority and wide receiving system. P and Q in (6) and (7) are the active
This work is licensed under a Creative Commons Attribution 4.0 License. For more information, see https://creativecommons.org/licenses/by/4.0/.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/ACCESS.2019.2940409, IEEE Access
operating point of the DC system. At the rated operating When (9) satisfies the condition, the voltage support
point, the nominal values of these variables are expressed capability of the receiving system is just enough to support
as Pdn =1, UN =1, IdN =1 and = N . Substituting the above the DC system to operate stably at the rated operating point.
nominal values and the parameter C into the (1)-(4), we can At this time, the voltage support capability of the receiving
derive the QdN, UdN, μN and K. It is worth mentioning that system is defined as the critical receiving system voltage
this is one way to easily obtain the value of K which is a support strength. If the voltage support capability of the
constant related to the parameters of the converter receiving system continues to decrease, and even becomes
transformer, and it keeps constant even if the operating less than the critical receiving voltage support strength, the
point changes. DC system will be difficult to operate normally under the
There are seven constraint equations in (1)-(7), so two rated conditions.
operating state variables are independent in the nine
variables. Once any two of these variables are determined, C. THE RELATIONSHIP BETWEEN THE VOLTAGE
the operating state of the DC system can be obtained. These SENSITIVITY OF THE RECEVING SYSTEM AND THE
two independent variables can be selected differently POWER STABILITY OF THE DC SYSTEM
according to different control modes and analysis purposes. There is = 0 when the inverter side of the DC system is
in the control mode of constant extinction angle . When the
B. POWER STABILITY DC current order ΔId is increased, the changes of other
Many studies have shown that power stability is a major operating state variables are ΔPd, ΔQd, ΔP, ΔQ, ΔU, ΔUd
factor limiting the normal operation of DC systems[8]. and Δμ. Because P = Pd and Q = Qd , the small signal
According to the analysis in Section II-A, we choose N total differential form of (5) can be written as
and Id as independent variables. In the constant extinction
U U
U = − Qd + Pd (10)
Q P
1.0
Where, U / Qd represents the sensitivity of the converter
Pd
0.8 bus voltage to the reactive power when the active power is
constant. U / Pd stands for the sensitivity of the converter
0.6 bus voltage to the active power when the reactive power is
constant. (10) establishes the relationship between the
0.5 1.0 1.5 2.0 sensitivity of the receiving system and the change of the
Id converter bus voltage. When the inverter side is under the
FIGURE 2. Maximum power curve of HVDC system.
This work is licensed under a Creative Commons Attribution 4.0 License. For more information, see https://creativecommons.org/licenses/by/4.0/.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/ACCESS.2019.2940409, IEEE Access
control mode of constant extinction angle, the total operating parameters of the DC system and the parameter C.
differential form of (1)-(4) is derived as (11)-(14). According to the calculation method in Section II-A, the
rated operating point of the system depends on parameters
Pd P
Pd = U + d (11) C and N . Without considering the voltage regulation of the
U converter transformer tap, parameter C is constant. If the
Qd Q parameter N is constant, the U Q corresponding to the
Qd = U + d (12)
U critical terminal support strength remains unchanged.
I d I
I d = U + d (13) Ⅲ. RECEVING SYSTEM VOLTAGE SUPPORT
U STRENGTH FACTOR
Pd
=0 (14) A. DEFINITION OF RECEVING VOLTAGE SUPPORT
I d STRENGTH FACTOR
The DC system consumes a lot of reactive power during
Where, operation, and the reactive power consumption changes
Pd when the DC power fluctuates. The measurement of the
U =2CU ( cos 2 − cos(2 + 2 ) ) voltage support capability of the receiving system is largely
a measure of the voltage stability of the converter bus when
Pd =2CU 2 sin(2 + 2 ) the reactive power of the receiving system changes. Define
the Receiving-system Voltage Support Strength Factor
Qd (RVSF) as
U =2CU ( 2 + sin 2 − sin(2 + 2 ) )
Q
(15) RVSF = (19)
Qd =2CU 2 (1 − cos(2 + 2 ) ) U P = PdN
Q =− QdN
I d =K ( cos − cos( + ) )
Where, P and Q are the active power and reactive power
U injected into the converter bus, respectively. Then at this
I time, Q U is the ratio of small reactive power change
d =KU sin ( + ) injected into the converter bus to the voltage change of the
converter bus when system operates at the rated operating
Through simplifying (10)-(14), we can get point and it does not consider the characteristics of the DC
system on the converter bus. The DC system on the
U converter bus can be replaced with constant power at its
+ba
dPd Q rated state, and then RVSF can be obtained by applying the
= (16)
dI d c + d U + e U reactive disturbance in the simulation. Obviously, RVSF
Q P can also be expressed as
-1
When the system is running at the rated power point, U
RVSF = (20)
there are PdN=1, UN=1, IdN=1, then Q
a = −4CQdN sin ( 2 N + 2 N ) + 4C (1 − cos ( 2 N + 2 N ) ) RVSF can reflect the voltage support strength of the
b = −2C sin ( 2 N + 2 N ) receiving system. When the reactive power is changed in
the injection receiving system, the larger the RVSF is, the
c = − K sin ( N + N ) (17)
more stable the converter bus voltage is, the greater the
d = −2 KQdN sin ( N + N ) + 2C (1 − cos ( 2 N + 2 N ) ) ability of the receiving system to support the voltage is.
e = 2 K sin ( N + N ) − 2C sin ( 2 N + 2 N ) B. RVSF THRESHOLD
The RVSF obtained when Pd / I d is defined as a Critical
Substituting (17) into (16), there is
Receiving-system Voltage Support Strength Factor
U sin ( 2 N + 2 N ) (CRVSF).
= (18)
Q 2QdN sin ( 2 N + 2 N ) − 2 (1 − cos ( 2 N + 2 N ) )
2 (1 − cos ( 2 N + 2 N ) ) − 2QdN sin ( 2 N + 2 N )
CRVSF= (21)
Because QdN is related to parameter C, the value of sin ( 2 N + 2 N )
U / Q corresponding to the critical receiving system
voltage support strength can be determined by the rated
This work is licensed under a Creative Commons Attribution 4.0 License. For more information, see https://creativecommons.org/licenses/by/4.0/.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/ACCESS.2019.2940409, IEEE Access
As can be seen from the analysis in Section II, the value The RVSF is changed along with the magnitude of the
of CRVSF is determined by parameters C and N .Based on impedance Zeq. A plurality of different impedance angles
the Cigre benchmark model, the typical values of the θeq are calculated, finally the point of MAP is coincident
converter transformer parameters are used. There are n=2, with the operating point of μ=30°, and RVSF of the
γN=15°, St =0.59179 and uk=18%. And then we can get that receiving system approaches 2. Therefore, the criterion for
C=1.3515. The CRVSF=0.603 can be obtained by taking distinguishing the weak receiving system from the strong
the typical value γN=15°of constant extinction angle control. receiving system is RVSF=2.
It is worth noting that we do not limit the parameters and
structure of the receiving system during the calculation of C. RVSF CRITERIA FOR DISTINGUISHING SYSTEM
CRVSF, so CRVSF is able to satisfy the diversity of When the DC system feeds power into the AC system, there
structure and components of the receiving system. It can is an interaction between AC and DC systems. The higher
also be regarded as a criterion used to distinguish weak the equivalent impedance of AC system, the smaller the
receiving system and very weak receiving system. short-circuit capacity of the system, and the more
significant the interaction between AC and DC systems.
E P, Q Pd , −Qd :1 When the system strength changes from weak to strong,
Ud RVSF=0.60 and RVSF=2 are two special points. When
Zeqeq RVSF<0.60, the IMAP corresponding to MAP is less than the
U , rated current Id=1. Since the system strength is unable to
support the DC system to operate at the rated operating
FIGURE 3. Simplified model of single-infeed HVDC system.
point, the power transfer limit of LCC is determined by the
MAP, which is smaller than rated power. When
In 12-pulse converter, the limit of the commutation angle
RVSF=0.60, the rated operating point coincides with the
μ is 30°. When the strength of the receiving system
point of MAP. At this time, the system strength can support
supporting voltage is weak, the point of MAP appears
the DC system to operate at the rated operating point of
before the operating point of μ=30° in the process of
Id=1, and the power limit is equal to the MAP. When
increasing the current Id. When the strength of the receiving
RVSF>0.6, the IMAP is greater than the rated current Id=1.
system supporting voltage is strong, the point of MAP
The system strength is adequate to support the DC system
appears after the operating point of μ=30°, so DC system
to operate at the rated point. Since a 12-pulse converter
will not suffer power instability. Since the operating point
usually requires its commutation angle to operate in a range
of μ=30°is not near the rated operating point, it is difficult
of less than 30 degrees, in some cases the commutation
to directly establish the relationship between the RVSF and
angle imposes constraints on the power transfer limit. When
the variables at the operating point. To determine this
0.6<RVSF<2, the IMAP is always less than the Iμ
relationship, we must rely on a structure of the receiving
corresponding to μ=30°, but greater than the rated current
system. For simplicity, the receiving system was simplified
Id=1. In the case, the commutation angle does not affect the
to a Thevenin equivalent circuit to form a single-infeed
system as shown in Fig. 3. Where, E, , Zeq and θeq are
power transfer limit, so the power transfer limit is
determined by the MAP. When RVSF>2, the IMAP appears
equivalent parameters of the AC system. P and Q represent later than the Iμ that the commutation angle imposes
the active power and reactive power flowing into the constraints on the power transfer limit. And the power
equivalent AC system from the converter bus. transfer limit is determined by the transfer power at μ =30°.
As shown in Fig. 3, the relationship between Q / U , The definitions of three systems are given below.
P / U and the system equivalent impedance parameters When the power transfer limit of the LCC is less than the
can be obtained by the power flow equation of the AC rated power, but equal to MAP, we call the receiving
system. system a very weak system, and its strength is described as
RVSF<0.6.
Z eq 2
Z eq sin eq + Qd When the power transfer limit is greater than the rated
U U2 power and equal to the MAP, we call the receiver system a
= (22)
Q Z eq 2
U−
U3
(Pd
2
+ Qd 2
) weak system, and its strength is described as 0.6<RVSF<2.
When the power transfer limit is greater than the rated
power, but limited by the commutation angle of 30° and
Z eq 2 cannot reach MAP, we call the receiver system a strong
Z eq cos eq − Pd
U U2 system, and its strength is described as RVSF>2.
= (23)
P Z eq 2 Therefore, the RVSF index based on the sensitivity of
U−
U3
(Pd
2
+ Qd 2
) reactive power to voltage can give a clearer boundary to the
system strength without considering the specific topology
This work is licensed under a Creative Commons Attribution 4.0 License. For more information, see https://creativecommons.org/licenses/by/4.0/.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/ACCESS.2019.2940409, IEEE Access
In addition to the DC equivalent of the converter busbar Where Bci is the admittance of the parallel reactive power
being constant power, it is also necessary to be considered compensation device on the commutating bus i.
that the power input from other DC systems to the AC The active power and reactive power of the VSC-HVDC
system when calculating the RVSF. In this case, the matrix is related to its control mode. When it is in the constant
J needs to be corrected. Since the delivery power of the DC active power and the constant reactive power control mode,
system is independent of the phase angle of the AC system, there is
only JPU and JQU need to be corrected. After correcting the
Jacobian matrix, the following power flow equation is
obtained:
This work is licensed under a Creative Commons Attribution 4.0 License. For more information, see https://creativecommons.org/licenses/by/4.0/.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/ACCESS.2019.2940409, IEEE Access
This work is licensed under a Creative Commons Attribution 4.0 License. For more information, see https://creativecommons.org/licenses/by/4.0/.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/ACCESS.2019.2940409, IEEE Access
that Em = 0.9870. In this system, there is dPd/dId =0 when dPd/dId is calculated by applying a small amount of
Id=1.00. change of 0.01pu to Id1. The calculation of the SCR is
The DC system is equivalent to a constant power load of shown in (36), and the analytical formula of the MIESCR is
the same capacity, and then the system is disturbed by shown in (37).
cutting a 0.01pu reactive load. We calculate the ratio of ESCR = Z11−1 (36)
reactive power variation to voltage change on the bus to get
the theoretical value. Compared with the theoretical value MIESCR = ( Z11 Pd 1 + Z12 Pd 2 )−1 (37)
CRVSF=0.603, the simulated value of RVSF is 0.611 that Where, Z11, Z12, and Z22 are elements in the node impedance
the error is 1.33%. matrix of the AC system shown in Fig. 4, respectively. The
1.001
Pd3 is changed from -0.55 to 0.55, and the step size is 0.01.
1.000 Zeq=0.4500
Zeq=0.4619 The correspondence between RVSF, ESCR, MIESCR and
0.999 Zeq=0.4700 dPd/dId are shown in Fig. 7 (a), (b) and (c), respectively. As
0.998 we know from Fig. 7, when Pd3 changes from -0.55 to 0.55,
P d/(p.u.)
0.997 case 4 is a weak system, but does not become a very weak
0.996 system. The critical values of each index corresponding to
0.995
case1~3 are shown in Tab. Ⅳ. As shown in Fig. 7 and Tab.
Ⅳ, neither ESCR nor MIESCR has obvious correlation
0.994
with dPd/dId in the hybrid multi-feed system which means
0.993
0.94 0.96 0.98 1 1.02 1.04 1.06 that these two indicators lack a clear critical threshold
Id/(p.u.) corresponding to dPd/dId=0. However, it can be found that
FIGURE 6. Power curve under different system support strength. RVSF has a good correlation with dPd/dId=0 in the hybrid
multi-feed system, and when dPd/dId=0, there is always
Ⅵ. COMPARATIVE ANALYSIS OF STRENGTH CRVSF=0.60, indicating that the CRVSF can accurately
EVALUATION INDICATORS measure the critical value of the voltage support strength of
This section compares RVSF, ESCR, MIESCR and the receiving system. These prominent advantages of RVSF
dPd/dId=0. Tab. Ⅲ shows the four sets of AC impedance make it possible to effectively evaluate the receiving
parameters and the corresponding control modes of VSC- system strength of the hybrid multi-infeed system.
HVDC. We mainly consider two kinds of control modes: 0.4 0.4
constant active power/constant reactive power (referred to 0.2 0.2
dPd1 /dId1
dPd1 /dId1
Case Z1 Z2 Z3 Z12 Z13 Z23 Control mode CESCR 1.76 0.84 2.04
Case 1 0.9 1.1 1.0 0.4 0.5 0.25 P/Q CMIESCR 1.01 0.52 1.18
Case 2 1.5 1.1 1.3 0.8 1.4 1.0 P/V RVSF 0.60 0.60 0.60
This work is licensed under a Creative Commons Attribution 4.0 License. For more information, see https://creativecommons.org/licenses/by/4.0/.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/ACCESS.2019.2940409, IEEE Access
In this paper, a sensitivity-based strength index of [7] D. L. H. Aik and G. Andersson, “Power stability analysis of multi-
infeed HVDC systems,” IEEE Transactions on Power Delivery, vol.
supporting voltage, the receiving system voltage support 13, no. 3, pp. 923-931, Jul 1998.
strength factor (RVSF), is proposed. Then the relationship [8] H. Xiao, Y. Li, J. Zhu and X. Duan, “Efficient approach to quantify
between RVSF and power stability criterion, dPd/dId, is commutation failure immunity levels in multi-infeed HVDC
systems,” IET Generation, Transmission & Distribution, vol. 10, no.
derived. The RVSF calculated based on dPd/dId =0 is
4, pp. 1032-1038, 3 10 2016.
defined as the critical voltage support strength factor of the [9] B. Franken and G. Andersson, “Analysis of HVDC converters
receiving system, that is called CRVSF. When LCC-HVDC connected to weak AC systems,” IEEE Transactions on Power
system connects to different receiving systems, the CRVSF Systems, vol. 5, no. 1, pp. 235-242, Feb. 1990.
[10] D. L. H. Aik and G. Andersson, “Voltage stability analysis of multi-
remains constant, which can satisfy the various operating infeed HVDC systems,” IEEE Transactions on Power Delivery, vol.
modes of the receiving system. The proposed criteria for 12, no. 3, pp. 1309-1318, Jul 1997.
identifying the strength of receiving system are as follow. [11] Chen Xingwang and Guan-Lin, “Research on limitation of the multi-
infeed short circuit ratio,” 2016 IEEE PES Asia-Pacific Power and
Very weak system: RVSF ≤ 0.60 Energy Engineering Conference (APPEEC), Xi'an, 2016, pp. 712-
Weak system: 0.60<RVSF≤2 715.
Strong system: RVSF>2 [12] Chen Xiuyu, Han Mingxiao, Liu Chongru, Impact of control modes
on voltage interaction between multi-infeed AC-DC system
In the hybrid multi-infeed HVDC system, considering [J] . Automation of Electric Power Systems,2012,36(2):58-63(in
the influence of VSC-HVDC transmission power and its Chinese).
different control modes, the Jacobian matrix of the [13] Y. Xia, W. Wei, M. Yu, X. Wang and Y. Peng, "Power Management
receiving system is modified to obtain the analytical for a Hybrid AC/DC Microgrid With Multiple Subgrids," in IEEE
Transactions on Power Electronics, vol. 33, no. 4, pp. 3520-3533,
expression of RVSF. April 2018.
The simulated value of RVSF is obtained from the model [14] Y. Xia, M. Yu, X. Wang and W. Wei, "Describing Function Method
built in PSCAD/EMTDC. Compared with the theoretical Based Power Oscillation Analysis of LCL-Filtered Single-Stage PV
Generators Connected to Weak Grid," in IEEE Transactions on
calculation value of RVSF, the error of the simulation value Power Electronics, vol. 34, no. 9, pp. 8724-8738, Sept. 2019.
is extremely small, and the validity of CRVSF=0.603 is [15] IEEE Guide for Planning DC Links Terminating at AC Locations
verified. A comparative analysis of RVSF with ESCR and Having Low Short-Circuit Capacities, in IEEE Std 1204-1997, vol.,
no., pp.1-216, Jan. 21 1997.
MIESCR shows that there is a strong correlation between [16] Xu Zheng. Characteristics of HVDC connected to weak AC systems part1:
RVSF=0.603 and dPd/dId=0. In different receiving systems, HVDC transmission capability[J]. Power System Technology, 1997,
CRVSF remains unchanged, while ESCR and MIESCR do 21(1): 12-16(in Chinese).
[17] D. Lee Hau Aik and G. Andersson, “Influence of load characteristics
not have clear thresholds. on the power/voltage stability of HVDC systems. II. Stability margin
Considering the sensitivity of voltage to reactive power, sensitivity,” IEEE Transactions on Power Delivery, vol. 13, no. 4, pp.
RVSF is a new way to evaluate the voltage support strength 1445-1452, Oct 1998.
[18] Y. Zhang, Y. Su and L. Guan, “Evaluation voltage supporting strength of
of the receiving system. Exploring other features of RVSF receiving-end power grid of HVDC transmission system in environment
and combining with the characteristics of the power system of AC/DC parallel power system and asynchronously interconnected
to apply these research results, will be carried out in further power grid,” Power System Technology, 2012, vol. 36, no. 1, pp. 90-95,
Jan 2012.
research work. [19] “Systems with multiple DC infeed,” Technical Brochure no.364 by
CIGRÉ Working Group B4.41, Dec. 2008.
REFERENCES [20] D. H. A. Lee and G. Andersson, “An Equivalent Single-Infeed
[1] D. Huang, Y. Shu, J. Ruan and Y. Hu, “Ultra High Voltage Model of Multi-Infeed HVDC Systems for Voltage and Power
Transmission in China: Developments, Current Status and Future Stability Analysis,” IEEE Transactions on Power Delivery, vol. 31,
Prospects,” Proceedings of the IEEE, vol. 97, no. 3, pp. 555-583, no. 1, pp. 303-312, Feb. 2016.
March 2009. [21] X. Chen, A. M. Gole and M. Han, “Analysis of Mixed
[2] Z. Wei, J. Liu, W. Fang, Junxian Hou and Z. Xiang, “Commutation Inverter/Rectifier Multi-Infeed HVDC Systems,” in IEEE
Failure analysis in single- and multi-infeed HVDC systems,” 2016 Transactions on Power Delivery, vol. 27, no. 3, pp. 1565-1573, July
IEEE PES Asia-Pacific Power and Energy Engineering Conference 2012.
(APPEEC), Xi'an, 2016, pp. 2244-2249. [22] X. Ni, A. M. Gole, C. Zhao and C. Guo, "An Improved Measure of
[3] F. Zhang et al., “Generalized short circuit ratio for multi-infeed LCC- AC System Strength for Performance Analysis of Multi-Infeed HVdc
HVDC systems,” 2017 IEEE Power & Energy Society General Systems Including VSC and LCC Converters," in IEEE Transactions
Meeting, Chicago, IL, 2017, pp. 1-5. on Power Delivery, vol. 33, no. 1, pp. 169-178, Feb. 2018.
[4] Lin Weifang, Tang Yong, Bu Guangquan and Shao Yao, “Voltage [23] D. L. Hau Aik and G. Andersson, "Impact of renewable energy
stability analysis of multi-infeed AC/DC power system based on sources on steady-state stability of weak AC/DC systems," in CSEE
multi-infeed short circuit ratio,” 2010 International Conference on Journal of Power and Energy Systems, vol. 3, no. 4, pp. 419-430,
Power System Technology, Hangzhou, 2010, pp. 1-6. Dec. 2017.
[5] Y. Liu and Z. Chen, "A Flexible Power Control Method of VSC-
HVDC Link for the Enhancement of Effective Short-Circuit Ratio in
a Hybrid Multi-Infeed HVDC System," in IEEE Transactions on
Power Systems, vol. 28, no. 2, pp. 1568-1581, May 2013.
[6] Shilpa G and P. Manohar, "Hybrid HVDC system for multi-infeed
applications," 2013 International Conference on Emerging Trends in
Communication, Control, Signal Processing and Computing
Applications (C2SPCA), Bangalore, 2013, pp. 1-5.
This work is licensed under a Creative Commons Attribution 4.0 License. For more information, see https://creativecommons.org/licenses/by/4.0/.