exida hereby confirms that the:

DVC6200 SIS Digital Valve Controller


The manufacturer
may use the mark:
Emerson Process Management
Fisher Controls International, LLC
Marshalltown, IA - USA
Has been assessed per the relevant requirements of:

IEC 61508 : 2010 Parts 1-7


and meets requirements providing a level of integrity to:

Systematic Capability: SC 3 (SIL 3 Capable)


Random Capability: Type A, Route 1H Device
PFDAVG and Architecture Constraints
Valid until October 1, 2016 must be verified for each application
Revision 2.0 October 1, 2013
Safety Function:
The DVC6200 SIS Digital Valve Controller will vent / supply
pressure to a pneumatic actuator when the input is
De-Energized / Energized To Trip.
Application Restrictions:
The unit must be properly designed into a Safety Instrumented
Function per the Safety Manual requirements.

Place embossed Evaluating Assessor


seal here for
originals, lining it
up at the bottom

Certifying Assessor
ANSI Accredited Program
PRODUCT CERTIFICATION
#1004 Page 1 of 2
Certificate / Certificat / Zertifikat /
EFC 1202027 C001
Systematic Capability: SC 3 (SIL 3 Capable)
Random Capability: Type A, Route 1H Device
PFDAVG and Architecture Constraints
must be verified for each application

Systematic Capability :
DVC6200 SIS Digital
The product has met manufacturer design process requirements of Safety
Valve Controller Integrity Level (SIL) 3. These are intended to achieve sufficient integrity
against systematic errors of design by the manufacturer.
A Safety Instrumented Function (SIF) designed with this product must not be
used at a SIL level higher than stated.
Random Capability:
The SIL limit imposed by the Architectural Constraints for each element.

IEC 61508 Failure Rates in FIT1 for DETT Applications

Device λSD λSU λDD λDU


2
DETT Applications - w/PVST 582 279 79 41
DETT Applications - Normal 0 461 0 120
Adder for LCP100 0 29 0 1
Adder for LC340 0 19 0 0

IEC 61508 Failure rates in FIT1 for ETT Applications

Device λSD λSU λDD λDU


2
ETT Applications - w/PVST 487 124 273 94
ETT Applications - Normal 0 183 0 367
Adder for LCP100 0 28 0 2

SIL Verification:
The Safety Integrity Level (SIL) of an entire Safety Instrumented Function (SIF)
must be verified via a calculation of PFDAVG considering redundant
architectures, proof test interval, proof test effectiveness, any automatic
diagnostics, average repair time and the specific failure rates of all products
included in the SIF. Each subsystem must be checked to assure compliance
with minimum hardware fault tolerance (HFT) requirements.
The following documents are a mandatory part of certification:
Assessment Report: EFC Q12/02-027 R004 V2 R1
64 N Main St
Sellersville, PA 18960
Safety Manual: Safety manual FIELDVUE DVC6200 SIS (D103601X012)
1 FIT = 1 failure / 109 hours
T-061, V1R1-3 2 PVST = Partial Valve Stroke Test
Page 2 of 2