NFC Aaac Al4 - 34.4&54.6 Ees Cable

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

www.eescable.

com

TECHNICAL SPECIFICATION
FOR
AAAC AL4 34.4
AAAC AL4 54.6
AAAC AL4 93.3

Hangzhou Easy Electric Wire and Cable Co.,LTD


Add: Room 305, Building 2, No. 380 Fengxin Road, Hangzhou, China
www.eescable.com
www.eescable.com

1. GENERAL

This listed specification covers the structure, test and packing information of power cables as

manufactured by HANGZHOU EASY ELECTRIC WIRE AND CABLE CO.,LTD. Matters not

mentioned in this technical specification shall be negotiated by purchaser & supplier. This

document confirms the two parties agreement as technical agreement of contract unless

otherwise in official written annexes.

2. STANDARDS

The cable which EES offered shall be designed, manufactured and tested according to

international standards as follows:

ISO 9001:2015 Quality Management Systems

ISO 14001:2015 Environmental Management Systems

OHSAS 18001:2007 Occupational health and safety management system

EN 50182:2001 Conductors for overhead lines- Round wire concentric lay stranded conductors
EN 50189 Conductors for overhead lines. Zinc coated steel wires

EN 50183 Conductors for overhead lines- Aluminum—magnesium-silicone Alloy wires

EN 60050-466 International Electrotechnical Vocabulary(IEV)-Chapter 466:overhead


lines
NF C 34-120 ACSR, Aluminium Conductors Steel Reinforced

NF C 34-125 Aluminum Alloy stranded conductor foroverhead liner

Hangzhou Easy Electric Wire and Cable Co.,LTD


Add: Room 305, Building 2, No. 380 Fengxin Road, Hangzhou, China
www.eescable.com
www.eescable.com

3.CONSTRUCTION AND SPECIFICATIONS


3.1:Cable Structure AAAC 34.4(34-AL4) AAAC 54.6(55-AL4)

Aluminum Alloy Wires

1 Code AAAC 34.4(34-AL4) AAAC 54.6(55-AL4)


2 Structure No./diameter 7×2.50mm 7×3.15mm
2 Stranded Diameter 7.5±0.1mm 9.45±0.1mm
3 Cross Sectional Area
34.4 54.6
of Conductor( mm2)
4 Aluminum Alloy Wire Property Tolerance of diameter ±0.03mm ±0.032mm
Standard :EN50183
Average 342 N/mm 2
342 N/mm2
Tensile strength ≮
Individual 325 N/mm2 325 N/mm2
Elongation in 250mm 3.0% 3.0%
Average 0.0326Ωmm /m
2
0.0326Ωmm2/m
Resistivity at 200C ≯
Individual 0.0329Ωmm2/m 0.0329Ωmm2/m
6 Twisting Direction S(left hand) S(left hand)
6 Final modulus of elasticity 60000N/mm 2
62000N/mm2
7 Coefficient of linear expansion 23.0×10-5 1/℃ 23.0×10-5 1/℃
8 Standard Weight 93.8±1.8 kg/km 148.9±3.1 kg/km
9 Calculated Breaking Load 11.17kN 17.73kN
10 Calculated Resistance DC at 20℃ 0.9593Ω/km 0.6042Ω/km
11 Calculated Resistance AC at 75℃ 1.1719Ω/km 0.7381Ω/km
12 Long term thermal carrying capacity (for 25 ℃ ambient
temperature,0.5m/sec wind velocity under effect of 1000w/mp solar 177Amps 236Amps
radiation for 75℃ conductor temperature)

Hangzhou Easy Electric Wire and Cable Co.,LTD


Add: Room 305, Building 2, No. 380 Fengxin Road, Hangzhou, China
www.eescable.com
www.eescable.com

2.1.1 Component Conductor Characteristics

Value
No. Parameter Unit
AAAC 34.3(34-AL4) AAAC 54.6(55-AL4)
1 Max. D.C. conductor resistance at 20’C Ω/km ≯0.9593 ≯0.6042
2 Diameter of cable (Tolerance ±10%) mm 7.5 9.45

3 Weight of the finished cable (Approx.) kg/km 93.8 148.9

4 Normal operating temperature °C 75 75


5 Emergency operating temperature °C 110 110
6 Allowable Current (25℃) A 177 236

Hangzhou Easy Electric Wire and Cable Co.,LTD


Add: Room 305, Building 2, No. 380 Fengxin Road, Hangzhou, China
www.eescable.com
www.eescable.com

4 ROUTINE TEST AND SAMPLE TEST FOR AAAC 34.4(34-AL4) AAAC 54.6(55-AL4)

AAAC shall be accordance with applicable standard of AAAC and requirements of customer. The
following test items shall be carried out according to corresponding reference.

No Item Reference
Tests for AAAC 34.4(34-AL4) AAAC 54.6(55-AL4)

1 Dimensions /

2 DC concudtor resistance 20℃ EN 50182

3 Visual examination(sample) EN 50182

4 Lay ratio EN 50182

5 The direction of outer layer EN 50182

6 Number and type of wires EN 50182

7 Diameter of aluminum alloy and steel wire EN 50182 EN50183 EN 50189


Wrapping test
8 EN 50182 EN50183 EN 50189
Tensile strength
9 EN 50182 EN50183 EN 50189

Hangzhou Easy Electric Wire and Cable Co.,LTD


Add: Room 305, Building 2, No. 380 Fengxin Road, Hangzhou, China
www.eescable.com

You might also like